Chapter-2 Lecture note
Chapter-2 Lecture note
2.1.Introduction
A slab is a flat surface planar structural element having thickness small compared to its other two
dimensions. It provides a working flat surface or a covering shelter in buildings. Depending on
the load transfer mechanism, slabs can be classified as One-way and Two-way slab systems, as
discussed in Reinforced Concrete Structures-I course.
The analysis and design of one-way slabs, especially for beam supported and one-way ribbed
slab systems was done by taking 1m strip width in the shorter span and designed as a singly
reinforced rectangular beam. Analysis and design of two-way slab system is a lot more complex
as load transfer is in two orthogonal directions and computing the design actions is not
straightforward as in one-way slabs. For rectangular slabs with standard edge conditions (beam
supported slabs) and subject to uniformly distributed loads, normally the bending moments are
obtained using tabulated coefficients.
Concrete two-way slabs may in some cases be supported by relatively shallow, flexible beams
(submerged beam or hidden beam), or directly by columns without the use of beams or girders.
Such slabs are generally referred as column supported two-way slabs (Flat slabs) (refer ES EN
1992-1-1:2015 section 5.11). Beams may also be used where the slab is interrupted as around
stair, walls or at discontinuous edges. The main concern of this chapter is we can analysis and
design such types of slabs.
a) Flat Plate: they are flat slabs with flat soffit. Such slabs have uniform thickness
supported on columns. They are used for relatively light loads, as experienced in
apartments or similar buildings. Flat plats are most economical for spans from 4.5𝑚 to
6𝑚 (see Figure 2.1a).
b) Flat slab: they are slab systems with the load transfer to the column is accomplished by
thickening the slab near the column, using drop panels and/or by flaring the top of the
column to form a column capital. They may be used for heavy industrial loads and for
spans of 6𝑚 to 9𝑚 (see Figure 2.1b)
c) Waffle slabs: they are two-way joist systems with reduced self-weights. They are used
for spans from 7.5𝑚 to 12𝑚. (Note: for large spans, the thickness required to transmit the
vertical loads to the columns exceeds that required for bending. As a result the concrete at
the middle of the panel is not efficiently used. To lighten the slab, reduce the slab
moments, and save material, the slab at mid-span can be replaced by intersecting ribs.
Near the columns the full depth is retained to transmit loads from the slab to the columns
(see Figure 2.1c).
Effective in reducing the shearing stresses developed around column where the
column is liable to punch through the slab.
Influence the distribution of moments in the slab by reducing the clear or effective
span.
It also provide an increased moment of resistance of slab where the negative moments
are greatest.
Stiffen the slab and hence reduce deflection
Drop panels are square or rectangular. The side of the drop panel shall be at least one-third of the
smaller span length. The maximum thickness of drop panel below slab used in computing the
negative steel area shall not be more than one-fourth of the distance from edge of the drop to the
edge of the column capital (𝑡𝑑 ≤ 𝑠⁄4) or 25 to 50 percent thicker than the rest of the slab.
The columns in practically all cases flare out toward the top, forming a capital of a shape
somewhat similar to an inverted truncated cone.
The effective diameter of the capital should be taken as the diameter of the circle at the point at
which a 45º line form the base of the capital intersects the bottom of the slab or dropped panel.
The diameter of column head ℎ𝑐 should not exceed 1⁄4𝑡ℎ of the shortest span framing in to the
column. The effective diameter of a column or column head ℎ𝑐 is the diameter of a circle whose
area equals the cross-sectional area of the column or if column heads are used, the area of the
column head based on the effective dimensions.
The effective dimensions of a column head for use in calculation of ℎ𝑐 are limited according to
the depth of the head. In any direction, the effective dimension of a head 𝐿ℎ shall be taken as the
lesser of the actual dimension 𝐿ℎ0 or 𝐿ℎ,𝑚𝑎𝑥 where 𝐿ℎ,𝑚𝑎𝑥 is given by:
For a flared head, the actual dimension 𝐿ℎ0 is that measured 40𝑚𝑚 below the soffit of the slab
or drop as shown in figure 2.3.
If the head is not circular, ℎ𝑐 should be the diameter of circle having an equivalent area.
𝑨𝒄
𝒉𝒄 = 𝟐√
𝝅
Simplified form work and reduced story heights make flat slab more economical.
Windows can extend up to the underside of the slab and there is no beam to obstruct the
light and the circulation of air.
Suitable for irregular column layouts, curved floor shapes, ramps, etc.
Flat slab carries a high concentration of shear force around the column, when the total
shear force exceeds the shear resistance of the slab, the slab will be pushed down around
the column.
Flat slab construction is that the arrangement of reinforcement can be very complex,
particularly adjacent to columns where punching shear reinforcement is often required if
the slab depth is kept to a minimum.
A flat slab spans between column supports without the need for beams. For a regular layout of
columns, failure can occur by the formation of hinge lines along the lines of maximum
hogging/support and sagging/span moments. A complementary set of yield lines can form in the
orthogonal direction. One misconception of some engineers is to consider a reduced loading
when analyzing in a particular direction. The moments applied in each orthogonal direction must
each sustain the total loading to maintain equilibrium. There is no sharing of the load by partial
resistance in each orthogonal direction.
The deflected shape of an interior panel of a flat slab on a regular grid of columns under typical
in-service conditions is a function of the sum of the deflections in each orthogonal direction as
shown in Figure 2.5. Similar deflected shapes will obtain from an irregular grid of columns, but
the interaction between adjacent bays may be more complex.
Deflection is one of the governing factor in dimension flat slab systems, especially when the
flat slab system doesn‘t incorporate deeper beams.
The use of finite element methods shows that the distribution of bending moments per unit width
is characterized by hogging moments that are sharply peaked in the immediate vicinity of the
columns. The magnitude of the hogging moments locally to the column face can be several times
that of the sagging moments in the mid-span zones. These moments do occur in practice and the
design should take them into account. Redistribution allows a more uniform spread of
reinforcement but increases the likelihood of cracking.
A typical distribution of bending stresses for a uniformly distributed load on a flat slab with a
regular layout of columns is illustrated in Figure 2.6.
As the vertical load on the slab increases, the following changes occur:
Stage 1: Moments at the supports and mid-span increase elastically until the first cracks occur.
These are likely to appear first at the top of the slab close to the column and may occur during
construction if the removal of formwork takes place early. Otherwise, this limited cracking may
occur under the quasi-permanent combination of actions.
Stage 2: As the loading is increased beyond the characteristic combination of actions, cracking
may increase to some way into the span from the column, and cracks may also have started to
appear at mid-span. This is unlikely under the frequent or quasi-permanent combination of
actions. The cracking increases the non-linear behavior of the slab, although it still behaves
elastically as the load increases between the formations of new cracking, and can be modeled
elastically-taking account of the tension stiffening of the concrete.
Stage 3: As the loading is further increased, the reinforcement first starts to yield in the top bars
close to the columns and the junction of the slab at edge column starts to behave as a plastic
hinge. Apart from this, the slab still behaves elastically as the load increases between the
formation of new cracks but with reducing tension stiffening.
A typical load versus deflection curve of a flat slab is shown in Figure 2.7.
Consider the following column supported two way slabs. If a surface load 𝑤 is applied (see
Figure 2.8a), it is shared between imaginary slab strips 𝑙𝑎 in the short direction and 𝑙𝑏 in the
longer direction. Note that the portion of the load that is carried by the long strips 𝑙𝑏 is delivered
to the beams B1 which in turn carried in the short direction plus that directly carried in the short
direction by the slab strips 𝑙𝑎 sums up to 100 percent of the load applied to the panel. The same
is true in the other direction.
A similar situation is obtained in the flat plate floor (see Figure 2.8b) where broad strips of the
slab centered on the column lines in each direction serve the same function as the beams.
Therefore; for column supported construction, 100 percent of the applied load must be carried in
each direction, jointly by the slab and its supporting beams.
The static moment 𝑴𝟎 is simply the total moment required by statics to be carried by a member.
Consider the typical interior panel of a flat slab subjected to a uniform load ‘𝑤’ per unit area
supported by columns at A, B, C and D as shown in Figure 2.9a.
(𝑎)
Figure 2.9 Moment variations in column-supported two-way slabs
Nichols had developed total static moment based on the assumption that the boundaries of the
slab panel and all line of symmetry are free from shear and torsion except the curved sections
which follows column capital.
𝑙𝑦 𝑤𝜋ℎ𝑐2 𝑙𝑥 𝑙𝑦 𝜋ℎ𝑐2
Loads on half panel, 𝑤1 = 𝑤 ∗ 𝑙𝑥 ∗ − = 𝑤( − )
2 8 2 8
If the upward shear 𝑤1 around curved section is considered uniformly distributed, the resultant
ℎ𝑐⁄
acts at 𝜋 distance from AC. Then, equilibrium of moment about AC gives:
2
𝑤𝑙𝑥 𝑙𝑦2 4ℎ𝑐 4ℎ𝑐3 𝑤𝑙𝑥 𝑙𝑦2 2ℎ𝑐
𝑀𝑛 + 𝑀𝑝 = (1 − + 2
) ≅ (1 − ) … … … … … … … … … … … … … .2.3
8 𝜋𝑙𝑦 3𝑙𝑥 𝑙𝑦 8 3𝑙𝑦
2
𝑤𝑙𝑥 𝑙𝑦2 2ℎ𝑐 𝑤𝑙𝑥 2ℎ𝑐 2
𝑀0𝑦 ≅ (1 − ) = (𝑙𝑦 − ) … … … … … … … … … … … … … … … … … … … 2.4
8 3𝑙𝑦 8 3
From the equations 2.4 and 2.5 static moment in each direction, the moment in the long direction
is larger than those in the short direction unlike to the situation for the slab with stiff edge beams.
Both equations (2.4 and 2.5) of total static moments does not give any information regarding
how total static moment is distributed between positive and negative moment, and how these
moments vary along the width of the slab.
The total static moment in the longer direction may vary along the width of the slab as shown
Figure 2.10. The variation shows larger share of moment developed in flat slab near to columns,
smaller near to middle of slab panel.
The moments across the width of critical sections such as AB or EF are not constant as shown
qualitatively (see figure 2.10).
For design purpose, moments may be considered constant within the bounds of a middle strip or
column strip, unless beams are present in column lines.
Hence, for analysis and design purpose the panel in flat slab is divided in to column strips and
middle strips as shown Figure 2.12 (adopted from ES EN 1992-1-1:2015Annex I).
Figure 2.12: Division of panels in flat slabs (Source: Adopted from ES EN 1992-1-1:2015Annex I)
A column strip is a design strip with a width on each side of a column centerline equal to 0.25𝐿𝑥
𝐿𝑥⁄
or if drops with dimension not less than 3 are used, a width equal to the drop dimension. A
middle strip is a design strip bounded by two column strips.
Flat slabs should be analyzed using a proven method of analysis, such as grillage (in which the
plate is idealized as a set of interconnected discrete members), finite element, yield line or
equivalent frame.
Equivalent frame:-this method is suitable for regular layouts of columns, but requires
engineering judgment for irregular layouts.
Finite element analysis:-this method allows the design of irregular column layouts and can
provide the design of reinforcement details. Where the appropriate software is available, it is
possible to obtain reasonable assessment of deflections.
Grillage analysis:-this method has similar facilities to finite element models and can also be used
for irregular layouts of columns.
Yield-line methods:-these can provide suitable designs for ULS but do not give adequate
information for serviceability design (the concern of chapter 4 of this course).
But, in this course we have limited to deals with the direct design method (DDM) (Simplified
moment coefficient method) and Equivalent Frame Analysis method (EFM).
The provision in these methods (DDM and EFM) are for the design of flat slabs supported by a
generally rectangular arrangement of columns and where the ratio of the longer to the shorter
spans does not exceed 2. For both methods, the negative moments greater than those at a distance
ℎ𝑐 ⁄2 from the center-line of the column may be ignored provide that the sum of the maximum
positive moment and the average of the maximum negative moments in any span of the slab
must be greater than or equal to the total static moment of slab.
𝑤𝑑 𝐿𝑥 2ℎ𝑐 2
𝑀0 = 𝑀𝑝 + 𝑀𝑛.𝑎𝑣𝑔 ≥ (𝐿𝑦 − ) … … … … … … … … … … … … … … … … … … … … … … .2.6
8 3
Where 𝐿𝑦 is length of the longer span and 𝐿𝑥 is length of the shorter span
When the above condition is not satisfied, the negative design moments shall be increased by
providing the drop panels or column capitals.
The direct-design method could have been called the simplified moment coefficient method
because this method essentially prescribes values for moments in various parts of the slab panel
without the need for structural analysis. It has to be noted that this method was introduced in the
era when most engineering calculations were made with hand & no computer software was
available. Thus, for continuous-floor slab panels with relatively uniform lengths and subjected to
distributed loading, a series of moment coefficients were developed that would lead to safe
flexural designs of two-way floor systems.
For design purpose, the slab is considered to be a series of frames in the two directions as shown
in Figure 2.13.
Static Moment, 𝐌𝟎
These frames extend to the middle of the panels on each side of the column lines. In each span of
each of the frames, it is necessary to compute the total static moment 𝑀0 . We thus have
𝑤𝑑 𝑙2 𝑙𝑛2
𝑀0 =
8
Where:
The longitudinal distribution of design span and support moments depends on the relative
stiffness of the different sections which in turn depends on the restraint provided for the slab by
the supports. Accordingly, the prescribed distribution factors of the longitudinal design moments
without structural analysis are given in the Table 2.1.
Table 2.1: Bending Moment and Shear Force coefficients for flat slabs of three or more spans
(Direct design method)
𝐹 is the total design ultimate load on the strip of slab between adjacent columns
considered. 𝐹 = 𝑤𝑑 ∗ 𝐿𝑥 ∗ 𝐿𝑦
2ℎ𝑐
𝐿 is the effective span 𝐿 = 𝐿𝑦 − 3
Lateral distribution of moments between Column strips and Middle strips for negative and
positive moments
The design moment obtained from the above (or equivalent frame analysis) shall be divided
between the column and middle strips according to the following Table 2.2.
Table 2.2: Simplified apportionment of bending moment for a flat slab (Source: Adopted from ES
EN 1992-1-1:2015Annex I)
Limitations on the use of the Direct Design Method as per ACI Code (Section 13.6.1)
If a beam is present in the column strip, it affects the distribution of negative moments in the
column and middle strips. At an exterior edge, the division of the exterior-end factored negative
moment distributed to the column and middle strips spanning perpendicular to the edge also
depends on the torsional stiffness of the edge beam, calculated as the shear modulus, 𝐺 times the
torsional constant of the edge beam, 𝐶 divided by the flexural stiffness of the slab spanning
perpendicular to the edge beam (i.e. 𝐸𝐼 for a slab having a width equal to the length of the edge
beam from the center of one span to the center of the other span as shown Figure 2.14.
Assuming that Poisson‘s ratio is zero 𝐺 = 𝐸/2 gives then this torsional stiffness ratio is defined
𝐸 𝐶
as 𝛽𝑡 = 2𝐸𝑐𝑏 𝐼
𝑐𝑠 𝑠
The term 𝐶 refers to the torsional constant of the edge beam. This is roughly equivalent to a polar
moment of inertia.
It is calculated by subdividing the cross section into rectangles and carrying out the summation
where 𝑥 the shorter side of a rectangle is and 𝑦 is the longer side. Different combinations of
rectangles should be tried to get the maximum value of 𝐶. The maximum value normally is
obtained when the wider rectangle is made as long as possible.
𝑥 𝑥3𝑦
𝐶 = ∑ [(1 − 0.63 ) ]
𝑦 3
Slabs frequently are built with beams spanning from column to column around the perimeter of
the building. These beams act to stiffen the edge of the slab and help to reduce the deflections of
the exterior panels of the slab.
In the ACI Code, the effects of beam stiffness on deflections and the distribution of moments are
expressed as a function of 𝜶𝒇𝟏 defined as the flexural stiffness 4𝐸𝐼/𝐿 of the beam divided by the
flexural stiffness of a width of slab bounded laterally by the centerlines of the adjacent panels on
each side of the beam:
4𝐸𝑐𝑏 𝐼𝑏 /𝐿
𝛼𝑓 =
4𝐸𝑐𝑠 𝐼𝑠 /𝐿
Because the lengths, of the beam and slab are equal, this quantity is simplified and expressed in
the code as
4𝐸𝑐𝑏 𝐼𝑏 𝐸𝑐𝑏 𝐼𝑏
𝛼𝑓 = =
4𝐸𝑐𝑠 𝐼𝑠 𝐸𝑐𝑠 𝐼𝑠
Where 𝐸𝑐𝑏 and 𝐸𝑐𝑠 are the moduli of elasticity of the beam concrete and slab concrete,
respectively 𝐼𝑏 and 𝐼𝑠 are the moments of inertia of the un-cracked beams and slabs.
Table 2.3: Percentage distribution of negative factored moment to the column strip at exterior
supports
The direct design method is applicable when the proposed structures satisfy the restrictions on
geometry and loading. If the structure does not satisfy the criteria, the more general method of
elastic analysis is the equivalent frame method.
EFM is based on the idealization of three dimensional slab and column system by a series of two
dimensional frames in longitudinal and transverse directions. Each frame consists of a slab-beam
element bounded laterally by the center line of panels on each side of the center of supports as
shown in Figure 2.15.
This provides an acceptable representation of the behavior of the floor by a system of columns
and slab strips analyzed separately in each direction. Rather than a full height frame, a series of
sub-frames comprising a single floor with columns above and below is more commonly used,
subject to the most unfavorable arrangement of load. The final moments can be redistributed.
The width of the frame strips is taken between mid-points of the columns or the edge of the slab
as appropriate. When considering only vertical loads, the stiffness of the slab strip may be based
on the full width. In any combination of loading that includes lateral loads the stiffness should be
based on the half the width.
The moment obtained from the analysis of the equivalent frame are the total moments on the slab
strip. However, the distribution of moment across the width of the strip is quite obviously not
uniform, since the slab is only supported in the center of the strip.
Unless there are perimeter beams, which are adequately designed for torsion, moments
transferred to edge or corner columns𝑀𝑠𝑢,𝑒𝑑𝑔𝑒 should be limited to the moment of resistance of a
rectangular section equal to 0.17𝑏𝑒 𝑑 2 𝑓𝑐𝑘 . 𝑏𝑒 Effective width of a flat slab see Figure 2.26. The
positive moment in the end span should be adjusted accordingly.
Limitations on the use of the Equivalent Frame Method as per ES EN 1992-1-1:2015 (Annex I)
1) The width of slab used to define the effective stiffness of the slab will depend upon the
aspect ratio of the panels and the type of loading, but the following provisions may be
applied in the absence of more accurate methods:
In the case of vertical loading, the full width of the panel, and
For lateral loading, 40% the width of the panel may be used to calculate the
stiffness of the slab.
2) The moment of inertia of any section of slab or column used in calculating the relative
stiffness of members may be assumed to be that of the cross section of the concrete alone.
3) Moments and forces within a system of flat slab panels may be obtained from analysis of
the structure under the single load case of maximum design load on all spans or panels
simultaneously, provided:
The ratio of the characteristic imposed load to the characteristic dead load does not
exceed 1.25. The characteristic imposed load does not exceed 5.0𝑘𝑁/𝑚2 excluding
partitions.
4) Where it is not appropriate to analyse for the single load case of maximum design load on
all spans, it will be sufficient to consider following arrangement of vertical loads:
All spans loaded with the maximum design ultimate load, and
Alternate spans with the maximum design ultimate load and all other spans loaded with
the minimum design ultimate load (1.0𝐺𝑘 ).
5) Each frame may be analysed in its entirety by any elastic method. Alternatively, for
vertical loads only, each strip of floor and roof may be analysed as a separate frame with
the columns above and below fixed in position and direction at their extremities. In either
case, the analysis shall be carried out for the appropriate design ultimate loads on each
span calculated for a strip of slab of width equal to the distance between centre lines of
the panels on each side of the columns.
Method of analysis of Flat slabs with Irregular column layout ES EN 1992-1-1:2015 (Annex I)
Where, due to the irregular layout of columns, a flat slab cannot be sensibly analyzed using the
equivalent frame method, a grillage or other elastic method may be used. In such a case the
following simplified approach will normally be sufficient:
Distribution moments moments, and these are further divided between middle strips and
divided between middle strips and column strips in exactly the same
column strips. way as in the direct-design
method.
It should be noted that the difference between the two methods is in the analysis of the static
moment only.
Slabs to be designed by any procedure that satisfies both equilibrium and geometric
compatibility, provided that every section has a strength at least equal to the required strength
and that serviceability conditions are satisfied. The thickness of the flat slabs provided based on
deflections requirement should be checked for the shear and bending moments.
A shear failure in a beam results from an inclined crack caused by flexural and shearing stresses.
This crack starts at the tensile face of the beam and extends diagonally to the compression zone,
as explained in previous sections. In the case of a two-way slab or footing, the two shear failure
mechanisms shown in Figure 2.16 are possible. One-way shear or beam-action shear (Figure
2.16a) involves an inclined crack extending across the entire width of the structure. Two-way
shear or punching shear involves a truncated cone or pyramid-shaped surface around the
column, as shown schematically in Figure 2.16b.
2.3.1.1.Punching shear
Consider a portion of slab subjected to an increasing concentrated load. Eventually the slab will
fail. One possible method of failure is that the load punches through the slab. The failure
mechanism is by shear, hence the name Punching Shear. Some examples of the occurrence of
concentrated loads on a slab or on a pad foundation are a common.
A flat slab supported by a column, where there is a high concentration of shear force around the
column head. When the total shear force exceeds the shear resistance of the slab, the slab will be
pushed down around the column, or this can be viewed as the column being pushed through the
slab.
Punching shear is the most common, and is a major design consideration, in flat slab
construction. In pad foundations, where weight and depth are not so critical, its effects are
satisfied by providing sufficient depth. The major emphasis of this topic is, therefore,
concentrated on flat slabs.
Methods have been proposed for checking the stress on the failure planes, but the general method
adopted is similar to that for transverse shear in beams, but checks shear stresses rather than
shear forces.
a) Plan
b) Section
Figure 2.17: Verification model for punching shear at the ultimate limit state (Source: Adopted
from ES EN 1992-1-1:2015 section 6.4)
Thus, the shear force acting on a perimeter u around the loaded area is resisted by a nominal
shear stress (capacity) 𝑽𝑹𝒅,𝒄 acting over the average effective depth d of the section.
Once punching has occurred, the top bars make only a very limited contribution to the shear
resistance since the cover is easily turn away (but prior to punching they are vital to the truss
analogy in determining the strength. However, the bottom bars, being more deeply embedded,
are not pushed out in the same way and thus provide more resistance. This is attributable initially
to dowel action, and then later at larger deformation to its being kinked, as shown.
When punching occurs at a slab-column connection without shear reinforcement the resistance
and thus the load carrying capacity is greatly reduced. The load is therefore transferred to the
adjacent connections, which may also suffer punching failures. This may lead to a general failure
of the floor which in turn could lead to a progressive collapse of the structure as one floor fails
onto the floor below. This has occurred several times with flat slab structures in recent years,
frequently during construction when the concrete strength is not fully developed.
Providing shear reinforcement to restrain the top bars by tying them to the bottom bars greatly
increases the resistance and ductility of the slab-column connection. Running the bottom bars
through the column or anchoring them in the column will also increases the ductility.
The empirical formula for the shear capacity (stress), 𝑽𝑹𝒅,𝒄 of a section shear reinforcement
(similar to beam shear) is given below.
Punching shear resistance of slabs and column bases without shear reinforcement 𝑽𝑹𝒅,𝒄 ES EN
1992-1-1:2015 section 6.4.4
The punching shear resistance of a slab should be assessed for the basic control section
according to 6.4.2. The design punching shear resistance [𝑀𝑃𝑎] may be calculated as follows:
1
𝐶 𝑘(100𝜌𝑓𝑐𝑘 ) ⁄3 + 𝑘1 𝜎𝑐𝑝
𝑉𝑅𝑑,𝑐 = 𝑀𝑎𝑥. { 𝑅𝑑,𝑐
𝑣𝑚𝑖𝑛 + 𝑘1 𝜎𝑐𝑝
Where:
200
𝑘 =1+√ ≤ 2.0 𝑑 𝑖𝑛 𝑚𝑚
𝑑
𝜌 = √𝜌𝑥 ∗ 𝜌𝑦 ≤ 0.02
𝐴𝑠𝑥 𝐴𝑠𝑦
𝜌𝑥 = 𝑎𝑛𝑑 𝜌𝑦 =
𝑏𝑑 𝑏𝑑
The values 𝝆𝒙 and 𝝆𝒚 should be calculated as mean values taking into account a slab width 𝒃
equal to the column width plus 3d each side (𝑚𝑚2 ⁄𝑚𝑚).
𝜎𝑐𝑦 +𝜎𝑐𝑥
𝜎𝑐𝑝 = ≤ 0.2𝑓𝑐𝑑 [𝑀𝑃𝑎]
2
𝝈𝒄𝒚 , 𝝈𝒄𝒙 are the normal concrete stresses in the critical section in 𝑦 − and 𝑥 −directions (𝑀𝑃𝑎
positive if compression):
𝑁𝐸𝑑,𝑦 𝑁𝐸𝑑,𝑥
𝜎𝑐𝑦 = 𝑎𝑛𝑑 𝜎𝑐𝑥 =
𝐴𝑐𝑦 𝐴𝑐𝑥
𝑵𝑬𝒅,𝒚, 𝑵𝑬𝒅,𝒙 are the design axial compression load in 𝑦 − and 𝑥 −directions
𝑘1 = 0.1
3⁄ 1⁄
𝑣𝑚𝑖𝑛 = 0.035𝑘 2 𝑓𝑐𝑘 2
𝑉𝑅𝑑,𝑐 is the design value of the punching shear resistance of a slab without punching shear
reinforcement along the control section considered.
𝑉𝑅𝑑,𝑐𝑠 is the design value of the punching shear resistance of a slab with punching shear
reinforcement along the control section considered.
𝑉𝑅𝑑,𝑚𝑎𝑥 is the design value of the maximum punching shear resistance along the control section
considered.
(a) At the column perimeter, or the perimeter of the loaded area, the maximum punching
shear stress should not be exceeded:
𝑉𝐸𝑑 ≤ 𝑉𝑅𝑑,𝑚𝑎𝑥
𝑉𝐸𝑑 ≤ 𝑉𝑅𝑑,𝑐
(c) Where 𝑉𝐸𝑑 exceeds the value 𝑉𝑅𝑑,𝑐 for the control section considered, punching shear
reinforcement should be provided according to ES EN 1992-1-1:2015 section 6.4.5.
The design shear resistance of the section without shear reinforcement is:-
𝑉𝑅𝑑,𝑐 ∗ 𝑈 ∗ 𝑑
𝑑𝑥 +𝑑𝑦
𝑑 is the average effective depth of the section 𝑑 = 2
Comparisons with a large number of test results show that the closer the basic control perimeter
is to the loaded area, the greater is the influence on the size of the loaded area relative to the
slab depth on the shear resistance of the slab. To be largely independent to this ratio, the distance
of the basic control perimeter from the face of the loaded area is taken as 2𝑑 from the loaded
area and should be constructed so as to minimize its length (see Figure 2.18).
Figure 2.18: Basic control perimeter (Source: Adopted from ES EN 1992-1-1:2015 section 6.4.2)
There are other parameters which affect the positions and length of control perimeters.
Free edges
For loaded areas situated near an unsupported edge or corner, the basic control perimeter is as
shown Figure 2.19, provided this gives a perimeter, excluding the unsupported edges, which is
less than that calculated for an internal loaded area. For loaded areas situated near an edge or
corner, i.e. at a distance smaller than 𝑑, special edge reinforcement should always be provided,
see 9.3.1.4.
Figure 2.19: Basic control perimeters for loaded areas close to or at edge or corner (Source:
Adopted from ES EN 1992-1-1:2015 section 6.4.2)
Openings
For loaded areas situated near openings, if the shortest distance between the perimeter of the
loaded area and the edge of the opening does not exceed 6𝑑, that part of the control perimeter
contained between the two tangents drawn to the outline of the opening from the center of the
loaded area is considered ineffective (see Figure 2.20).
Figure 2.20: Control perimeter near an opening (Source: Adopted from ES EN 1992-1-1:2015
section 6.4.2)
For slabs with circular column heads for which 𝑙𝐻 < 2ℎ𝐻 (see Figure 2.21) a check of the
punching shear stresses according to 6.4.3 is only required on the control section outside the
column head. The distance of this section from the centroid of the column 𝑟𝑐𝑜𝑛𝑡 may be taken as:
𝑟𝑐𝑜𝑛𝑡 = 2𝑑 + 𝑙𝐻 + 0.5𝐶
Where:
𝑙𝐻 is the distance from the column face to the edge of the column head
Figure 2.21: Slab with enlarged column head where 𝑙𝐻 < 2.0ℎ𝐻 (Source: Adopted from ES EN
1992-1-1:2015 section 6.4.2)
For a rectangular column with a rectangular head with 𝑙𝐻 < 2.0ℎ𝐻 (see Figure 2.21) and
overall dimensions 𝑙1 and 𝑙2 (𝑙1 = 𝐶1 + 2𝑙𝐻1 , 𝑙2 = 𝐶2 + 2𝑙𝐻2 , 𝑙1 < 𝑙2), the value 𝑟𝑐𝑜𝑛𝑡 may be
taken as the lesser of:
2𝑑 + 0.56√𝑙1 𝑙2
𝑟𝑐𝑜𝑛𝑡 = 𝑀𝑖𝑛. {
2𝑑 + 0.69𝑙1
For slabs with enlarged circular column heads where 𝑙𝐻 < 2ℎ𝐻 (see Figure 2.22) control
sections both within the head and in the slab should be checked and may be taken as:
𝑟𝑐𝑜𝑛𝑡,𝑒𝑥𝑡 = 2𝑑 + 𝑙𝐻 + 0.5𝐶
Figure 2.22: Slab with enlarged column head where 𝑙𝐻 > 2(𝑑 + ℎ𝐻 ) (Source: Adopted from ES
EN 1992-1-1:2015 section 6.4.2)
Effective Shear Force (Equivalent Punching shear adjacent to columns) [ES EN 1992-1-
1:2015 section 6.4.2]
For a slab-column connection the design is based on the total shear force, 𝑉𝐸𝑑 at the column face
(where an equivalent frame analysis has been used the direction giving the greater value of 𝑉𝐸𝑑 is
used). Generally, moment is transferred to the columns so the shear distribution is not uniform
and a factor, 𝛽 is used to take account of local concentrations.
𝑉
𝑣𝐸𝑑 = 𝛽 𝑢𝐸𝑑𝑑
0
Figure 2.23: Shear distribution due to an unbalanced moment at a slab internal column
connection (Source: Adopted ES EN 1992-1-1:2015 section 6.4.3)
For structures where the lateral stability does not depend on frame action between the slabs and
columns, and where the adjacent spans do not differ in length by more than 25%, simplified
values of 𝛽 may be used. Otherwise 𝛽 must be calculated
Figure 2.24: Recommended values for 𝛽 (Source: Adopted ES EN 1992-1-1:2015 section 6.4.3)
Design procedure
Step 1: Calculate the effective shear force, 𝛃𝑽𝑬𝒅 at the face of the loaded area.
Step 2: Calculate the shear stress, 𝑣𝐸𝑑 at the face of the loaded area, where 𝑢0 is the perimeter of
(𝑑𝑥 + 𝑑𝑦 )⁄
the loaded area and 𝑑 = 2.
𝑉𝐸𝑑
𝑣𝐸𝑑 = 𝛽
𝑢0 𝑑
𝑓𝑐𝑘
𝑉𝑅𝑑,𝑚𝑎𝑥 = 0.5𝑣𝑓𝑐𝑑 𝑣 = 0.6 (1 − 250 )
Step 5: Calculate the punching shear stress resistance, 𝑽𝑹𝒅,𝒄 of the slab at the basic control
perimeter.
1
𝐶 𝑘(100𝜌𝑓𝑐𝑘 ) ⁄3 + 𝑘1 𝜎𝑐𝑝
𝑉𝑅𝑑,𝑐 = 𝑀𝑎𝑥. { 𝑅𝑑,𝑐
𝑣𝑚𝑖𝑛 + 𝑘1 𝜎𝑐𝑝
Step 6: Calculate the shear stress at the basic control perimeter, 𝑣𝐸𝑑 (for edge and order columns
the reduced perimeter, 𝑢1 may be used).
𝑉𝐸𝑑
𝑣𝐸𝑑 = 𝛽
𝑢1 𝑑
Step 7: If 𝑽𝑬𝒅 > 𝑽𝑹𝒅,𝒄 several design options are available to increase the shear resistance of the
slab, such as:
i. Punching shear resistance of slabs and column bases with shear reinforcement [ES
EN 1992-1-1:2015 section 6.4.5]
The shear resistance of the section with shear reinforcement, 𝑉𝑅𝑑,𝑐𝑠 is:-
Where
𝐴𝑠𝑤 is the area of one perimeter of shear reinforcement around the column [𝑚𝑚2 ]
𝑆𝑟 is the radial spacing of perimeters of shear reinforcement (not exceed 0.75𝑑) [𝑚𝑚]
𝑓𝑦𝑤𝑑,𝑒𝑓 is the effective design strength of the punching shear reinforcement, according to
𝛼 is the angle between the shear reinforcement and the plane of the slab
The control perimeter where shear reinforcement is not required, 𝑈𝑜𝑢𝑡 can be calculated:-
𝛽𝑉𝐸𝑑
𝑈𝑜𝑢𝑡 =
𝑉𝑅𝑑,𝑐 𝑑
The outermost perimeter of shear reinforcement should be placed at a distance not greater than
𝑘𝑑 within 𝑈𝑜𝑢𝑡 (see Figure 2.25).
It should be fixed on at least two perimeters, the inner of which, 𝑆𝑂 is located between
0.3𝑑 and 0.5𝑑 from the face of the loaded area;
The spacing of link perimeters, 𝑆𝑟 must not exceed 0.75𝑑;
The spacing of links around a perimeter, 𝑆𝑡 must not exceed 1.5𝑑 for perimeters with in
the basic control perimeter and 2𝑑 for perimeters outside the basic control perimeter.
These criteria will often dedicate the amount of shear reinforcement provided.
a) Links
Traditional shear links provide a strong reinforcement cage around the column head. However,
they do take a long time to fix and often require additional longitudinal link hanger’s bars
running between the main bars.
b) Ladders
The area and spacing of reinforcement in the vertical legs of the shear ladders is determined
from the area and spacing of the links they are designed to replace.
d) Shear Hoops
A shear hoop is a prefabricated, single perimeter of links tied together by two hoop bars.
The fixing time is far less than for traditional links. Different size hoops are placed around the
column, here four shear hoops have been fixed as shown.
e) Shear heads
A shear head is prefabricated from structural steel channel sections which carry all the shear
force at the column. Service holes are easily provided adjacent to the column.
The detail is much simpler than traditional links, making is far easier to fix. The shear resistance
of a shear head is either determined by test, or provided by the manufacturer.
An enlarged column head or column capital increases the perimeter of the loaded area, 𝑢𝑜 so
reducing the shear stress 𝑣𝐸𝑑 . It also increases the length of the basic control perimeter, 𝑢1
thereby reducing the shear stress, 𝑣𝐸𝑑 at that section.
The main disadvantage of providing a column head is the additional formwork and the
consequential increase in the construction time. Column heads are used, generally, as
architectural features where the soffit is exposed.
An increased depth of slab by providing drop panel around the column reduces 𝑣𝐸𝑑 by increasing
the length of the basic control perimeter 𝑢1 . It also reduces 𝑣𝐸𝑑 at the face of the loaded area by
increasing the effective depth 𝑑.
Generally, drop panels are provided with a shallow slab to carry large shear forces. Because of
this they tend to be quiet large such that punching is checked on another control perimeter within
the drop.
The main disadvantages of drops are the extra formwork, resulting in an increase in construction
time, and the possible interference with routing of services below the slab.
If 𝑣𝐸𝑑 exceeds 𝑉𝑅𝑑,𝑐 , the basic control perimeter by small amount, and this was true of many
slab-column connection in the design, then either the loaded area or the slab depth could be
increased, although the latter would also increase the permanent load. The most economical
solution might be to increase the concrete strength. If, at the face of the loaded area 𝑣𝐸𝑑 greatly
exceeds 𝑉𝑅𝑑,𝑐 then thought must be given to changing the structural layout or even the form of
construction.
Detailing rules of reinforcements for the Flat Slabs as per ES EN 1992-1-1: 2015 section 9.4
(1) The arrangement of reinforcement in flat slab construction should reflect the behaviour under
working conditions. In general this will result in a concentration of reinforcement over the
columns.
(2) At internal columns, unless rigorous serviceability calculations are carried out, top
reinforcement of area 0.5𝐴𝑡 should be placed in a width equal to the sum of 𝟎. 𝟏𝟐𝟓𝒕𝒊𝒎𝒆𝒔 the
panel width on either side of the column. 𝐴𝑡 represents the area of reinforcement required to
resist the full negative moment from the sum of the two half panels each side of the column.
(3) Bottom reinforcement (≥ 2𝑏𝑎𝑟𝑠) in each orthogonal direction should be provided at internal
columns and this reinforcement should pass through the column.
Reinforcement perpendicular to a free edge required to transmit bending moments from the slab
to an edge or corner column should be placed within the effective width be shown in Figure 2.26.
(1) Where punching shear reinforcement is required it should be placed between the loaded
area/column and 𝑘𝑑 inside the control perimeter at which shear reinforcement is no
longer required. It should be provided in at least two perimeters of link legs (see Figure
2.27). The spacing of the link leg perimeters should not exceed 0.75𝑑.
The vertical component of only those pre-stressing tendons passing within a distance of
𝟎. 𝟓𝒅 of the column may be included in the shear calculation.
(2) Bent-up bars passing through the loaded area or at a distance not exceeding 0.25𝑑 from
this area may be used as punching shear reinforcement (see Figure 2.27 b).
(3) The spacing of link legs around a perimeter should not exceed 1.5𝑑 within the first
control perimeter (2𝑑 from loaded area), and should not exceed 2𝑑 for perimeters outside
the first control perimeter where that part of the perimeter is assumed to contribute to the
shear capacity (see Figure 2.28).
Table 2.4: Minimum bend point locations and Extensions for reinforcement in Flat Slabs
Step 2: Choose the slab thickness (deflection limitation and shear at both exterior and interior
columns)
Step 3: Choose the design method (direct design or equivalent frame methods)
Step 5: Check thickness of the slab for both shear and flexure
Step 6: Determine the distribution of the moments across the width of the slab
Step 7: If there are beams, a portion of the moments must be assigned to the beams
Generally, it is not necessary to calculate the deflections explicitly as simple rules, provided the
limits to span/depth ratio formulated are satisfied, which will be adequate for avoiding deflection
problems in normal circumstances. More rigorous checks are necessary for members which lie
outside such limits, or where deflection limits other than those implicit in simplified methods are
appropriate.
Provided that reinforced concrete beams or slabs in buildings are dimensioned so that
they comply with the limits of span to depth ratio.
The appearance and general utility of the structure could be impaired when the calculated
sag of a beam, slab or cantilever subjected to quasi-permanent loads exceeds 𝑠𝑝𝑎𝑛/250.
Pre-camber may be used to compensate for some or all of the deflection but any upward
deflection incorporated in the formwork should not generally exceed 𝑠𝑝𝑎𝑛/250.
For the deflection after construction, 𝑠𝑝𝑎𝑛/500 is normally an appropriate limit for
quasi-permanent loads.
The limiting span to depth ratio may be estimated from expressions and multiplying this
by correction factors to allow for the type of reinforcement used and other variables.
No allowance has been made for any pre-camber in the derivation of these expressions.
3⁄
𝐿 𝜌0 𝜌 2
𝑑
= 𝐾 [11 + 1.5√𝑓𝑐𝑘 𝜌
+ 3.2√𝑓𝑐𝑘 ( 𝜌0 − 1) ] 𝑖𝑓 𝜌 ≤ 𝜌0 … … … … … … … … … … … … … … … … … 7.16𝑎
𝐿 0 𝜌 𝜌′
= 𝐾 [11 + 1.5√𝑓𝑐𝑘 𝜌−𝜌′ + 3.2√𝑓𝑐𝑘 √𝜌 ] 𝑖𝑓 𝜌 > 𝜌0 … … … … … … … … … … … … … … … … … 7.16𝑏
𝑑 0
Where:
𝐿
𝑑
is the limit span/depth
𝐾 is the factor to take into account the different structural systems from Table 7.4N
𝜌 is the required tension reinforcement ratio at mid-span to resist the moment due to the design
loads (at support for cantilevers)
𝜌′ is the required compression reinforcement ratio at mid-span to resist the moment due to design
loads (at support for cantilevers)
Expressions (7.16𝑎) and (7.16𝑏) have been derived on the assumption that the steel stress under
the appropriate design load at SLS at a cracked section at the mid-span of a beam or slab or at the
support of a cantilever is 310𝑀𝑃𝑎 (corresponding roughly to 𝑓𝑦𝑘 = 500𝑀𝑃𝑎). Where other
stress levels are used, the values obtained using Expression (7.16) should be multiplied
by 310⁄𝜎𝑠 . It will normally be conservative to assume that:
310 500
=
𝜎𝑠 𝐴𝑠,𝑟𝑒𝑞
(𝑓𝑦𝑘 ⁄𝐴 )
𝑠,𝑝𝑟𝑜
310 500
=
𝜎𝑠 𝑓𝑦𝑘
Where:
𝜎𝑠 is the tensile steel stress at mid-span (at support for cantilevers) under the design load at SLS
𝐴𝑠,𝑟𝑒𝑞 is the area of steel required at this section for ultimate limit state
For flat slabs where the greater span exceeds 8.5𝑚, and which support partitions liable to be
damaged by excessive deflections, the values of 𝐿/𝑑 given by Expression (7.16) should be
multiplied by 8.5⁄𝐿 (𝐿𝑒𝑓𝑓 𝑖𝑛 𝑚𝑒𝑡𝑒𝑟𝑠).
𝑒𝑓𝑓
Table 7.4N: Basic ratios of 𝑠𝑝𝑎𝑛/𝑒𝑓𝑓𝑒𝑐𝑡𝑖𝑣𝑒 𝑑𝑒𝑝𝑡ℎ for reinforced concrete members without
axial compression
0.26𝑓𝑐𝑡𝑚 𝑏𝑡 𝑑
𝐴𝑠,𝑚𝑖𝑛 = but not less than 0.0013𝑏𝑡 𝑑
𝑓𝑦𝑘
𝐴𝑠,𝑚𝑎𝑥 = 0.04𝐴𝑐
In areas with concentrated loads or areas of maximum moment those provisions become
respectively:
The minimum clear distance (horizontal and vertical) between individual parallel bars or
horizontal layers of parallel bars should be not less than (ES EN 1992-1-1: 2015 section 8.2)