Flat Slab
Flat Slab
When a rectangular slab is supported on all the sides and the length-to-breadth ratio is less than two, it is
considered to be a two-way slab. The slab spans in both the orthogonal directions. A circular slab is a
two-way slab. In general, a slab which is not falling in the category of one-way slab, is considered to be a
two-way slab.
Rectangular two-way slabs can be divided into the following types.
1) Flat plates: These slabs do not have beams between the columns, drop panels or column capitals.
Usually, there are spandrel beams at the edges.
2) Flat slabs: These slabs do not have beams but have drop panels or column capitals.
3) Two-way slabs with beams: There are beams between the columns. If the beams are wide and
shallow, they are termed as band beams.
For long span construction, there are ribs in both the spanning directions of the slab. This type of slabs is
called waffle slabs.
The slabs can be cast-in-situ (cast-in-place). Else, the slabs can be precast at ground level and lifted to
the final height. The later type of slabs is called lift slabs. A slab in a framed building can be a two-way
slab depending upon its length-to-breadth (L / B) ratio. Two-way slabs are also present as mat (raft)
foundation.
The following sketches show the plan of various cases of two-way slabs. The spanning directions in each
case are shown by the double headed arrows. `
The values can be increased to 48 and 52, respectively, if the deflection, camber and vibration are not
objectionable. The following photographs show post-tensioned flat plate and flat slab.
Analysis
The analysis of two-way slabs is given in Section 31, IS:456 - 2000, under Flat Slabs.The analysis is
applicable to flat plates, flat slabs and two-way slabs with deflecting beams. For two-way slabs with
beams, if the beams are sufficiently stiff, then the method (based on moment coefficients) given in Annex
D, IS:456 2000, is applicable.
The direct design method of analysing a two-way slab is not recommended for prestressed slabs. The
equivalent frame method is recommended by ACI 318-02. It is given in Subsection 31.5, IS:456 - 2000.
This method is briefly covered in this section for flat plates and flat slabs.
Prestressed Concrete Structures Dr. Amlan K Sengupta and Prof. Devdas
Flat Slabs
A reinforced concrete flat slab, also called as beamless slab, is a slab supported directly by columns
without beams. A part of the slab bounded on each of the four sides by centre line of column is called
panel. The flat slab is often thickened closed to supporting columns to provide adequate strength in shear
and to reduce the amount of negative reinforcement in the support regions. The thickened portion i.e. the
projection below the slab is called drop or drop panel. In some cases, the section of column at top, as it
meets the floor slab or a drop panel, is enlarged so as to increase primarily the perimeter of the critical
section, for shear and hence, increasing the capacity of the slab for resisting two-way shear and to
reduce negative bending moment at the support. Such enlarged or flared portion of and a capital. Slabs of
constant thickness which do not have drop panels or column capitals are referred to as flat plates. The
strength of the flat plate structure is often limited due to punching shear action around columns, and
consequently they are used for light loads and relatively small spans
In general, in column-supported slabs, with or without beams along the column lines, 100 percent of the
slab load has to be transmitted by the floor system in both directions (transverse and longitudinal)
towards the columns. In such cases, the entire floor system and the columns act integrally in a two-way
frame action.
Proportioning of Slab Thickness, Drop Panel and Column Head Slab Thickness
The thickness of the slab is generally governed by deflection control criteria. [Shear is also an important
design criterion especially in flat plates (slabs without beams and drop panels) and at exterior column
supports]. The calculation of deflections of two-way slab systems is quite complex, and recourse is often
made to empirical rules which limit maximum span/depth ratios as indirect measures of deflection control.
For this purpose, the Code (Cl. 31.2.1) recommends the same l/d ratios prescribed (in Cl. 23.2, also refer
Section 5.3.2) for flexural members in general, with the following important differences:
the longer span should be considered (unlike the case of slabs supported on walls or stiff beams,
where the shorter span is considered);
for the purpose of calculating the modification factor kt [Table 5.2] for tension reinforcement, an
average percentage of steel across the whole width of panel should be considered [Ref. 11.11];
When drop panels conforming to Cl. 31.2.2 are not provided around the column supports, in flat
slabs the calculated l/d ratios should be further reduced by a factor of 0.9;
the minimum thickness of the flat slab should be 125 mm
However, discontinuous edges shall be provided with an edge beam with stiffnes ratio, b, of not less than
0.8, failing which the thickness given by Eq. 1 shall be increased by 10 percent
For slabs with drop panels, the minimum thickness of slab is:
D [l (0.6 + f / 1000)] / [30{1+(2x /l )(D -D)/D}]
where xd / (ln/2) is smaller of the values determined in the two directions, and xd is not greater than ln/4,
and (Dd-D) is not larger than D.
For slabs with beams between all supports, the minimum thickness of slab is:
D [ln (0.6 + fy / 1000)] / {30 + 4bm }
2a
where bm is not greater than 2.0. This limit is to ensure that with heavy beams all around the panel, the
slab thickness does not become too thin. In the above equations,
Dd overall thickness of drop panel, mm;
xd dimension from face of column to edge of drop panel, mm;
fy characteristic yield strength of steel (in MPa);
(clear long span)/(clear short span);
average value of for all beams on edges of slab panel
bm
beam stiffness parameter, defined as the ratio of the flexural stiffness of the beam section to that of
b
a width of slab bounded laterally by the centreline of the adjacent panel (if any) on each side of the beam
where I is the second moment of area with respect to the centriodal axis of the gross flanged section of
b
the beam [shaded area in Fig. 11.27( (a),(b), (c) and (d)) and Is = I2D /12. The value of Ib may be taken
as
3
3a
where b is the width and Db is overall depth of the beam. The minimum thickness for flat slabs obtained
from Eq. 11.25 are given in Table 11.2
Table 11.2 Minimum thicknesses for two-way slabs without beams between interior column supports (Eq. 11.25)
Column Capital
The column capital (or column head), provided at the top of a column, is intended primarily to increase
the capacity of the slab to resist punching shear [see Section 11.8.2]. The flaring of the column at top is
generally done such that the plan geometry at the column head is similar to that of the column.
The Code (Cl. 31 2.3) restrict the structurally useful portion of the column capital to that portion which lies
within the largest (inverted) pyramid or right circular cone which has a vertex angle of 90 degrees, and
can be included entirely within the outlines of the column and the column head [Fig. 11.28(b)]. This is
based on the assumption of a 45 degree failure plane, outside of which enlargements of the support are
considered ineffective in transferring shear to the column
unbalanced moment must be resisted by the columns above and below in proportion to their relative
stiffnesses [Fig. 11.29(a)].
In slabs without beams along the column line, the transfer of the unbalanced moment from the slab to the
column takes place partly through direct flexural stresses, and partly through development of non-uniform
shear stresses around the MMcolumn head. A part (Mub) of the unbalanced moment can be considered
to the transferred by flexure and the balance (Muv) through eccentricity of shear forces, as shown in Fig
11.29 (b) and (c). The Code recommendation (Cl. 31.3.3) for the apportioning of M ub and Muv is based on
a study described in Ref. 11.23
Mub = Mu
Muv = (1-)Mu
where =
Here c1 and c2 are the dimensions of the equivalent rectangular column, capital or bracket, measured in
the direction moments are being determined and in the transverse direction, respectively, and d is the
effective depth of the slab at the critical section for shear [refer Section 11.8.2]. For square and round
columns, c1 = c2, and = = 0.6.