DATWYLER UPS - 10~50 kVA (3:3 Phase)

Tower / Rack Mounted

OVERVIEW

Datwyler´s DUPS series is the small to medium power trans-


formerless UPS. The series is designed to a high standard
and can be improved based on client's technical and budget
customiza�on requirements.

APPLICATION

This Uninterrup�ble Power Supply (UPS) offers guaranteed


power protec�on for connected electronics. When power is
interrupted or fluctuates outside the safe levels, UPS will
instantly provides a clean ba�ery backup power and surge
protec�on for connected and sensi�ve devices.

TECHNICAL FEATURES

■ Fully digital control ■ Flexible battery configuration ■ Strong load capacity


Digital control process (DSP) makes the system more Batteries number of each group can be Output power factor is 1.0, UPS can support
stable and reliable selected form 30 pcs to 50 pcs 100% unbalance load

■ Parallel redundancy function ■ LBS function ■ Flexible Installation


Parallel redundancy design, up to 6 units available, Load Bus synchronization can realize 2 Supports 19-inch rack mounting and tower
makes the configuration more flexible independent UPS system work in mounting
Support sharing batteries for the UPS in parallel synchronization, and it enhances the
reliability of the system ■ Intelligent Monitoring Function
■ Power saving RS232 / RS485 communication interface
High input power factor, it can be up to 0.99 ■ Intelligent Charging Method USB interface
Three level inverter topology, the efficiency The series UPS adopts advanced Parallel interface
can be up to 95.5% three-stage charging method— SNMP card(optional)
1st stage: high current constant current Relay card (optional)
■ Safty and reliable protection charging to guarantee to charge back to Battery temperature compensation adapter
Power up self-diagnosis function 90%; (optional)
Output overload, output short circuit, inverter 2nd-stage: Constant Voltage, in order to
over temperature, battery under voltage vitalize battery and make sure batteries ■ EPO Function
warning and battery overcharge protection are fully charged The series UPS may be completely shut off
Static electronic bypass switches 3rd stage: floating mode. when the EPO is pressed. REPO function
Cold (DC) start function With this 3-stage charging method, it (Remote EPO) is also available in this series
Fan intelligent speed regulation design, prolong extends the life of the batteries and UPS.
fan life, high efficiency and energy saving guarantees fast charging.

Page 1 / 2 Subject to technical modifica�on


DATWYLER UPS - 10~50 kVA (3:3 Phase)
Tower / Rack Mounted
SPECIFICATIONS
MODEL DUPS10 DUPS15 DUPS20 DUPS25 DUPS30 DUPS40 DUPS50 -

10kkVA 15kkVA 20kkVA 25kkVA 30kkVA 40kkVA 50kkVA


Capacity (VA/Watts)
10kW 15kW 20kW 25kW 30kW 40kW 50kW
INPUT
Nominal voltage 380/400/415Vac, (3Ph+N+PE)

Operating voltage range 138~485Vac

Operating frequency range 40Hz-70Hz

Power factor ≥0.99

Harmonic distortion (THDi) ≤3% (100%non-linear load )

220Vac Max.voltage: +25% (optional +10%,+15%,+20% )


230Vac Max.voltage: +20% (optional +10%,+15% )
Bypass voltage range 240Vac Max.voltage: +15% (optional +10% )
Min. voltage: -45% (optional -20%,-30%)
Frequency synchronize tracing range: ±10%

Generator input Support

OUTPUT
Output voltage 380/400/415Vac (3Ph+N+PE)

Voltage regulation ±1%

Power factor 1.0

1.Line Mode: synchronize with input; when input frequency >±10% (±1%/±2%/±4%/±5% optional)
Output frequency
2.Battery Mode:50/60*(1±0.02%)Hz

Crest factor 3:1

≤2% with linear load


Harmonic distortion (THD)
≤4% with non linear load

Efficiency 95.5%

BATTERY

Optional Voltage:
Battery voltage ±180V/±192V/±204V/±216V/±228V/±240/±252/±264/±276/±288/±300Vdc(30/32/34/36/38/40/42/44/46/48/50pcs optional)
360Vdc~600Vdc ( 36~50 pcs no power derating - 32~34 pcs output power factor 0.9 - 30 pcs output power factor 0.8 )

Charge Current(A)
(charge current can be set according Max. current 18A Max. current 20A
to battery capacity installed)

SYSTEM FEATURES
Transfer time Utility to Battery : 0ms; Utility to bypass: 0ms

Overload Load≤110%: last 60min,≤125%: last 10min,≤150%: last 1min

Alarm overload, utility abnormal, UPS fault, battery low, etc.

Backfeed Support

Protection short circuit, overload, over temperature, battery low, fan fault alarm.

10-30kVA USB, RS232, RS485, Parallel port, Dry contact port, REPO port, Backfeed port, Intelligent slot, SNMP card (optional)
Communication USB, RS232, RS485, Parallel port, REPO port, LBS port, Backfeed port,
40-50kVA
Intelligent slot, SNMP card (optional), Relay card (optional)

ENVIRONMENTAL
Operating temperature 0℃~40℃

Storage temperature -25℃~55℃(no battery)

Humidity range 0~95% (non condensing)

Altitude < 1500m.When>1500m,lower the rated power for use

Noise level <55dB <56dB <58dB

PHYSICAL
Dimension D×W×H (mm) 670×440×130(3U) 800×440×175 (4U)

Net weight (kg) 25 27~28 45 48

STANDARDS
Safety IEC/EN62040-1,IEC/EN60950-1

EMC IEC/EN62040-3,IEC61000-4-2,IEC61000-4-3,IEC61000-4-4,IEC61000-4-5,IEC61000-4-6,IEC61000-4-8

Packaging dimension differ based on actuals or customised packing requests.

Page 2 / 2 Subject to technical modifica�on