protn1
protn1
protn1
Dr Keith Mitchell
ELEC 5203 - Topics in Power
Engineering
Fairly low current, but if not detected can cause catastrophic effects
Effects of Short-Circuits
• Switch
• Disconnector / Isolator
– On-load / Off-load
• Circuit Breaker
• Fuse
Source
To load
Current Transformers
• Either single bar primary or double wound
• Standard of either 5 Amp or 1 Amp secondaries
• Primary is in series with load – acts like a current fed
device
• Output impedance (“burden”) must be low – short out
secondary when not in use
• Can only supply a certain secondary voltage before
iron saturates – design and impedance of relay, meters
etc is very important
• Symbol:
High Voltage
CTs
33kV single bar
primary type
CTs
Bar primary
Secondary coil
500kV “hairpin”
single bar
primary type
CTs, with SF6 CB’s
behind
CT Excitation Characteristics
CTs can only produce a certain output voltage before the iron
saturates (“kneepoint” voltage). The circuit impedance (“burden”)
in the CT secondary should be kept as low as possible.
OC, Fuse &
Thermal Time
Characteristics
Overload vs Short-Circuits
Source
Source OC curve
Intermediate
Local Sub OC curve Time margins > 0.35 Sec
Note instantaneous setting
Local
PLANT TO BE
PROTECTED
I1 = I2 ⇒ Healthy; no trip
| I1 - I2 | > Limit ⇒ Fault; trip
Δ Δ-Y
Transformer
∆ ∆
Y Y Y
Busbars
Circuit LV Side
breakers
Back-up Protection
• Protection devices are themselves also not 100%
reliable, so protection has to be duplicated.
• Two forms of backup – remote (an upstream
device) or local (i.e. a duplicate protection
scheme).
• HV Transmission lines and substations have both
duplicate local and remote backup.
Intertripping
• All “unit” (differential) schemes require
intertripping – i.e. if the CB is tripped at one
end , the CB at the other end has to be tripped
as well.
• Done by an auxiliary relay initiated by the first
protection relay, plus pilot wires down to the
relay at the remote end
CB Fail
• Circuit breakers are also never 100% reliable,
so back up for CBs has to be provided as well.
• Can be remote (eg with O/C schemes) or local,
using intertripping and “CB Fail” relays.
• Exercise: look at the zones of protection in slide
#57. Which CBs would you inter-trip to cover
failure of CB P2 in zone 5?
Which Relays are Used in What
Applications?
Protection Type Application Areas
Fuse Local LV distributor
It depends on HRC Fuse Major LV feeder, local HV spur line, HV
side of distribution substation
the Overcurrent and Earth Fault relay Major HV distribution feeder, backup to
transformer differential protection and
feeder impedance protection on sub-
importance Impedance relay
transmission lines
Primary protection on transmission and
of the power Differential relay
sub-transmission lines
Primary protection on large distribution
and all sub-transmission and transmission
system level transformers; large generators
Thermal Overload relay Transmission and sub-transmission level
element transformers, large motors, large
generators
being Oil Surge relay Transmission and sub-transmission level
transformers
Under and Over Volts relay Large motors, large generators
protected. Under and Over Frequency relay Large generators
Negative Sequence relay Large generators
Loss of Excitation relay Large generators
Microprocessor (Digital) Relays
• All modern relays are of this type
• Wave shape is sampled typically at up to 20 kHz
• Many relays have multiple functions – eg impedance
plus overcurrent, differential plus overcurrent
• Setting data is prepared off-line and down-loaded
• Additional control, event data logging, metering
functions
• Many have data comms back to central location – but
protection operation is done autonomously and locally
Comparison of Electromechanical and
Digital Relays
Feature Electromechanical Digital