Bulletin 140U/Ue: Molded Case Circuit Breakers
Bulletin 140U/Ue: Molded Case Circuit Breakers
Bulletin 140U/Ue: Molded Case Circuit Breakers
BULLETIN 140U/UE
Molded Case Circuit Breakers
CATALOG NUMBERS 140U/UE
Bulletin 140U/UE
Mechanical Specifications
Weight Dimensions Mounting Hardware Terminals, Lugs, and End Caps 7 7 7 7
Termination Specifications
G- & H-Frames J- & K-Frames L- & M-Frames N-Frame 8 10 12 14
Dimension Drawings
G-Frame H-Frame J-Frame K-Frame L-Frame M-Frame N-Frame 18 20 23 24 25 27 28
Bulletin 140U/UE
Bulletin 140U/UE
Bulletin 140U/UE
Bulletin 140U/UE
No. of Poles Main Poles Auxiliary Circuit Main Conductors Auxiliary Circuits IEC (50 Hz) [V] [V]
Rated Operational Voltage (Ue) - AC [V] 440 480 690 600/347 690 600/347 690 600 690 600 690 600 690 600 690 600 690 600 UL/NEMA (60 [V] Hz) UL 489 CSA 22.2 No. 5 IEC 60947-2
Standards Compliance Ambient Operating Temperature Range +16140F (8.960C) Permissible Ambient Temperature, Low Setting/High Setting Derating Factor (%) Molded Case Circuit Breaker At 40 C At 50 C At 55 C At 60 C At 70 C At 40 C At 50 C At 55 C At 60 C At 70 C 100 96 93 91 86 100 /100 96/92 93/87 91/83 86/73 100 100 96 81 86 100 /100 96/92 93/87 91/83 86/73 100 100 96 81 86 100/100 96/94 94/90 92/87 88/80 Isolation Switch 100 100 96 88 82 100 100 96 90 85 100 100 95 90 84 100 100 95 90 84 100 100 95 90 84 100 91 85 81 100/100 96/92 93/87 90/84 85/75 100/100 96/91 93/86 90/82 84/70 100/100 96/91 93/86 90/82 84/70 100/100 96/91 93/86 90/82 84/70 100 91 85 81
DC - Rated Short Circuit Breaking Capacity (kA) Time Constant < 8ms, non-inductive loads 1 Pole 2 Poles in Series 3 Poles in Series 250V 440V 660V 10 (2p) 10 20 20 10 20 20 10 20 20 10 20 20 10 20 20 10 20 30 10
Thermal set at max. on Fixed Thermal. Bulletin 140UE versions of the H-, J-, L-, M-, and N-Frame only comply with IEC 60947-2.
Bulletin 140U/UE
[W]
40
40
75
107
160
87
87/210
with Supplied Leads in. (cm) AWG mm2 Lb-in Nm 48 (122) #18 0.82 7..12.4 0.8..1.4 48 (122) #18 0.82 7..12.4 0.8..1.4 48 (122) #18 0.82 7..12.4 0.8..1.4 48 (122) #18 0.82 7..12.4 0.8..1.4 48 (122) #18 0.82 7..12.4 0.8..1.4 48 (122) #18 0.82 7..12.4 0.8..1.4 48 (122) #18 0.82 7..12.4 0.8..1.4 48 (122) #18 0.82 7..12.4 0.8..1.4 48 (122) #18 0.82 7..12.4 0.8..1.4
Auxiliary & Alarm Contacts Rated Thermal Current - Ith Rated Making Capacities Rated Operational Current (AC15) 230V 400V 480V 690V Rated Operational Current (DC13) 24V 125V 240V [A] [A] [A] 5 6 0.5 0.15 6 0.5 0.15 6 0.5 0.15 6 0.5 0.15 6 0.5 0.15 6 0.5 0.15 6 0.5 0.15 6 0.5 0.15 [A] [A] [A] [A] 6 (240V) 0.25 (600V) 0.25 (600V) 0.25 0.25 0.25 0.25 0.25 0.25 6 3 6 3 6 3 6 3 6 3 6 3 6 3 6 3 [A] 6 6 6 6 6 6 6 6 6
[A]
10
20
20
20
20
20
20
20
20
Back-up Protection (max rating) Fuses Miniature Circuit Breakers [A] [A] 6 6 6/4/4 6/4 6/4/4 6/4/4 6/4/4 6/4 6/4/4 6/4 6/4/4 6/4 6/4/4 6/4 6/4/4 6/4 6/4/4 6/4
Bulletin 140U/UE
Power Consumption
Power Consumption
Bulletin 140U/UE
140U-G-MHS 140U-H-MHS
M4 x 0.7 x 75 M4 0.7 x 75 M4 x 0.7 x 75 M4 x 0.7 x 90 M6 x 1.0 x 45 M5 x 0.8 x M5 x 0.8 x M8 x 1.0 x 35 M8 x 1.0 x 35 mm mm mm mm mm 100 mm 100 mm mm mm 140U-G140U-H140U-H140U-K140U-M140U-N140U-J-MHM 140U-L-MHM 140U-L-MHM MHM MHM MHM MHM MHM MHM 4 Pan Head 15 1.69 4 Pan Head 15 1.69 4 Pan Head 15 1.69 4 Pan Head 10 1.13 4 Pan Head 2025 23 4 Pan Head 25 3 4 Pan Head 25 3 4 Pan Head 28 3 4 Pan Head 28 3
Bulletin 140U/UE
Frame Size
Terminal Type
B
Material A B C D Fastener Lb-in Torque Nm 1/2 (12.7) 7/16 (10.99) 1/4 (6.35) 1/5 (5.0)
Standard Steel
Dim.
Flathead
Cable Type Cable Temperature Rating Cable Quantity Wire Strip Length in.
(A) (B) (C) 1(A) (B) (C) 13/81/ 3/47/ 1/41- 3/81/ 3/47/ 1/412 in. 8 in. 3/8 in. 2 in. 8 in. 3/8 in. (A) 913 mm #3 3/0 3595 (B) 1922 mm #14#2 2.535 Allen - 5/32 in. (4 mm) 50 5.6 70 lb-in 7.9 Nm (C) 3235 mm (A) 913 mm (B) 1922 mm #14#6 2.510 Allen - 3/32 in. (3 mm) 25 lb-in 2.8 Nm (C) 3235 mm
mm
D C
Wire Range
B
AWG
mm2 2.56
Wire Torque
10
Bulletin 140U/UE
Lugs Specification Std/Optional 3/4(19.05) 5/8(15.88) Cat. No. Material Box Lugs Optional 140U-JTLS1 Steel Phillips Head 10 0.2 Cu Only 60/75C (1) 0.75 19.05 4350 MCM Allen 180 20 Optional 140U-KTLC1 Copper Optional 140U-JTLA1 Alumium Phillips head 10 0.2 Cu/Al 60/75C (1) 0.75 19.05 4350 MCM 25185 Allen 250 28 Optional 140U-KTLA1 Optional 140U-KTLA1A Optional 140U-KTLC2 Copper Mechanical Lugs Optional 140U-KTLA2 Alumium Optional 140U-KTLC1A Copper Optional 140U-KTLA2A Optional 140U-KTLA1B Optional 140U-KTLC1B Copper
5/16(7.94) Terminal Fastener Hardware 5/16(8.0) Hex 180/250 20/28 Terminal Fastener Torque Lb-in Nm
Cable Type Cable Temperature Rating Cable Quantity Wire Strip Length in. mm AWG
D C
Wire Range
B
Material A Dim. B C D Fastener Torque Lb-in Nm 1(25.4) 3/4(19.05) 3/8(9.53) Hex 275/375 3/42
Alumium Alumium
Alumium Alumium
Terminal Fastener Hex 7/32 Hex 7/32 Hex 7/32 Hex 7/32 Hex 7/32 Hex 7/32 Hex 7/32 Hex 7/32 Hex 7/32 Hardware 11/32(8.9) Terminal Fastener Torque Lb-in Nm 96 10.8 Cu Only 60/75C (1) 1 25.4 96 10.8 Cu/Al 60/75C (1) 1 25.4 96 10.8 Cu/Al 60/75C (1) 1 25.4 96 10.8 Cu Only 60/75C (2) 1 25.4 96 10.8 Cu/Al 60/75C (2) 1 25.4 96 10.8 Cu Only 60/75C (1) 1 25.4 96 10.8 Cu/Al 60/75C (2) 1 25.4 96 10.8 Cu/Al 60/75C (1) 1 25.4 96 10.8 Cu Only 60/75C (1) 1 25.4
Cable Type Cable Temperature Rating Cable Quantity Wire Strip Length in. mm
K
A
AWG
D C
250 500
250 500
3350
Wire Range
B
2/0250 MCM (2) 50075 or 0 2/0500 (1) 70120 (2) or 70240 (1) 27537 5 31 or 42 30040 0 (1)
50075 0
mm2
120 240
120 240
30185
95120
95120
30185
Allen 3/8 Allen 3/8 Allen 3/8 Allen 3/8 Allen 3/8 Allen 3/8 Allen 3/8 Allen 3/8 Allen 3/8 375 42 375 42 275 31 275 31 275 31 275 31 550 62 550 62
11
Bulletin 140U/UE
Lugs Frame Size Specification Std/Optional Cat. No. Material Terminal Fastener Hardware Terminal Fastener Torque Lb-in Nm Optional 140U-J-MTL3A Aluminum 1/420 screw 50 lb-in 5.6 Nm Cu/Al 60/75C (3) (A) 3/81/2 in. (A) 913 mm (B) 3/47/8 in. (B) 1922 mm #14#2 2.525 Allen - 5/32 in. (4 mm) 70 lb-in 7.9 Nm Optional 140U-K-MTL3A Aluminum .375 x 25 screw 72 -96 lb-in 8.610.8 Nm Cu/Al 60/75C (3) (A) 9/16.3/4 (B) 1-3/16.1in. 1/2 in. (A) 1419 mm (B) 3038 mm #122/0 470 Allen - 3/16 in. (5 mm) 120 lb-in 13.5 Nm (C) 1-7/821/4 in. (C) 4857 mm (C) 1-1/413/8 in. (C) 3235 mm (6) (A) 3/81/2 in. (A) 913 mm (B) 3/47/8 in. (B) 1922 mm #14#6 2.510 Allen - 3/32 in. 25 lb-in 2.8 Nm Optional 140U-K-MTL6A Aluminum .375 x 25 screw 72 -96 lb-in 8.610.8 Nm Cu/Al 60/75C (6) (A) 9/16.3/4 (B) 1-3/16.1in. 1/2 in. (A) 1419 mm (B) 3038 mm #142 AWG 2.570 Allen - 1/8 in. (3 mm) 25 lb-in 2.8 Nm (C) 1-7/821/4 in. (C) 4857 mm (C) 1-1/413/8 in. (C) 3235 mm Multitap Optional 140U-J-MTL6A Aluminum 1/420 screw 50 lb-in 5.6 Nm Cu/Al 60/75C End Cap Optional 140U-J-ECM Molded Housing Allen - 4 mm 120144 Lbin 1416 Nm Optional 140U-K-ECM Molded Housing Allen - 8 mm 275 Lb-in 31 -m
Cable Type Cable Temperature Rating J Cable Quantity Wire Strip Length in. mm Wire Range AWG mm2
Terminal Type Wire Torque Lb-in Nm Std/Optional Cat. No. Material Terminal Fastener Hardware Terminal Fastener Torque Lb-in Nm
Cable Type Cable Temperature Rating K Cable Quantity Wire Strip Length in. mm AWG mm2 Lb-in Nm
Wire Range
12
Bulletin 140U/UE
Dim.
Hex (8 mm) Hex (8 mm) Hex (8 mm) Hex (8 mm) Hex (8 mm) Hex (8 mm) 200 22 Cu/Al 60/75C (1) 1-1/8 29 500750 240380 550 62 Optional 140U-MTLC3 Copper Bolt (19 mm) 3035 200 22 Cu only 60/75C (1) 1-1/8 29 500750 240380 500 57 Optional 140U-MTLA2 Aluminum Bolt (19 mm) 3035 200 22 Cu/Al 60/75C (2) 1-1/8 29 2500 35240 375 42 Optional 140U-MTLC2 Copper Bolt (19 mm) 3035 200 22 Cu only 60/75C (2) 1-1/8 29 2500 35240 375 42 Optional 140U-MTLA3 Aluminum Bolt (19 mm) 3035 200 22 Cu/Al 60/75C (1) 1-1/8 29 2500 35240 375 42 Optional 140U-MTLA2A Aluminum Bolt (19 mm) 3035 200 22 Cu only 60/75C (1) 1-1/8 29 2500 35240 375 42 Optional
D C
Wire Range
Terminal Type
B
Hex (8 mm) Hex (8 mm) Hex (8 mm) Hex (8 mm) Hex (8 mm) Hex (8 mm)
Wire Torque 1-1/16 (26.99) 17/8 (45) 1/2 (12.7) 1/2 (12.7) Socket 275/400 31.1/45.2
Std/Optional Cat. No. Material Terminal Fastener Hardware Terminal Fastener Torque Cable Type Cable Temperature Rating Cable Quantity Wire Strip Length
D
ft-lb Nm
Lb-in Nm
40.547.5 40.547.5 40.547.5 40.547.5 40.547.5 Cu only 60/75C (3) 1-1/16 27 3/0300 95185 275 31 Cu/Al 60/75C (2) 1-1/16 27 1500 50240 375 42 Cu only 60/75C (2) 1-1/16 27 2/0500 70240 300 34 Cu/Al 60/75C (3) 1-1/16 27 3/0400 95185 375 42 Cu/Al 60/75C (2) 1-1/16 27 500750 95185 500 56
in. mm
Wire Range
B
Hex (8 mm) Hex (8 mm) Hex (8 mm) Hex (8 mm) Hex (8 mm)
13
Bulletin 140U/UE
Lugs Frame Size Specification Std/Optional Cat. No. Material Terminal Fastener Hardware Terminal Fastener Torque Lb-in Nm Optional (B) 3038 mm #122/0 470 Lb-in Nm (C) 1-7/821/4 in. (C) 4857 mm Multitap Optional (6) (A) 9/16.3/4 (B) 1-3/16.1in. 1/2 in. (A) 1419 mm (B) 3038 mm (C) 1-7/821/4 in. (C) 4857 mm End Cap Optional 140U-L-ECM Molded Housing Allen - 8 mm 200 Lb-in 22 Nm
Cable Type Cable Temperature Rating L Cable Quantity Wire Strip Length in. mm AWG mm2 Lb-in Nm
Wire Range
Std/Optional Cat. No. Material Terminal Fastener Hardware Terminal Fastener Torque
Cable Type Cable Temperature Rating M Cable Quantity Wire Strip Length in. mm Wire Range AWG mm2 Lb-in Nm
14
Bulletin 140U/UE
Terminal Fastener Hardware Terminal Fastener Torque Cable Type Cable Temperature Rating ft-lb
Bolt (19 mm) 3545 40.547.5 Cu/Al 60/75C (2) 1 25.4 #1500 MCM 50240 Hex (8 mm) 375 42
Bolt (19 mm) 3545 40.547.5 Cu Only 60/75C (2) 1 25.4 2/0500 MCM 70240 Hex (8 mm) 300 34
Bolt (19 mm) 3545 40.547.5 Cu/Al 60/75C (4) 1 25.4 4/0500 MCM 120240 Hex (8 mm) 375 34
Bolt (19 mm) 3545 40.547.5 Cu Only 60/75C (3) 1 25.4 3/0500 MCM 95240 Hex (8 mm) 300 34
Bolt (19 mm) 3545 40.547.5 Cu Only 60/75C (4) 1 25.4 3/0400 MCM 95185 Hex (8 mm) 275 31
Nm 40.547.5 Cu/Al 60/75C (3) in. mm AWG mm2 1 25.4 3/0400 MCM 95185 Hex (8 mm) 375 42
D C D
Wire Range
Terminal Type
B
Wire Torque
Lb-in Nm
15
Bulletin 140U/UE
Dimensions
G Frame
.49 [ 12,5 ]
.14 [ 3,6 ]
2.42 [ 61,5 ]
3.22 [ 81,8 ]
1.00 [ 25,4 ]
.16 [ 4]
1.22 [ 30,9 ]
1.22 [ 30,9 ]
16
Bulletin 140U/UE
Dimensions, Continued
.84 [ 21,3 ] .36 [ 9,1 ] .45 [ 11,4 ]
.16 [ 4,1 ]
3.21 [ 81,4 ]
4.88 [ 123,8 ]
140U G FRAME
3.22 [ 81,7 ]
1.00 [ 25,4 ]
1.00 [ 25,4 ]
2.41 [ 61,2 ]
.45 [ 11,4 ]
1.22 [ 31 ]
140U G-FRAME
17
Bulletin 140U/UE
0.8524 (21.6509)
0.4179 (10.6146)
0.1680 (4.2672)
3.8120 (96.8248)
1.0070 (25.5778)
2.9725 (75.5015)
18
Bulletin 140U/UE
.47 [ 11,9 ]
.88 [ 22,2 ]
.54 [ 13,6 ]
5.50 [ 139,7 ]
3.81 [ 96,9 ]
3.44 [ 87,4 ]
1.00 [ 25,4 ]
1.00 [ 25,4 ]
19
Bulletin 140U/UE
.97
.97
5.50
3.81
3.81
5.50
4-POLE
20
Bulletin 140U/UE
7.00 [ 177,8]
5.50 [ 139,7]
1.38 [ 34,9]
1.38 [ 34,9]
2.84 [ 72,2]
.78
4-POLE
21
Bulletin 140U/UE
1.48 [ 37,7 ]
.28 [ 7,1 ]
.84 [ 21,4 ]
1.19 [ 30,2 ]
10.13 [ 257,2 ]
1.72 [ 43,7 ]
4.06 [ 103,2 ]
1.43 [ 36,2 ]
1.06 [ 27]
1.01 [ 25,7 ]
140U K FRAME
22
Bulletin 140U/UE
10.13 [ 257,2]
8.44 [ 214,4]
1.72 [ 43,7 ]
1.72 [ 43,7 ]
5.43 [ 137,9 ]
23
Bulletin 140U/UE
5.48
1.72
.84
.84
10.13
8.44
8.44
10.13
24
Bulletin 140U/UE
.38 [ 9,5 ]
.63 [ 15,9]
.74 [ 18,7]
16.00 [ 406,4]
14.75 [ 374,7]
.84 [ 21,4]
1.87 [ 47,6]
1.03 [ 26,2]
25
Bulletin 140U/UE
2.75 [ 69,9]
.34 [ 8,7]
.63 [ 15,9]
5.19 [ 131,8]
16.00 [ 406,4]
14.75 [ 374,7]
5.50 [ 139,7]
140U/UE N FRAME
2.00 [ 50,8]
26
Bulletin 140U/UE
10 kA 10 kA 10 kA 10 kA
10 kA 10 kA 10 kA 10 kA 10 kA 10 kA 10 kA 10 kA 10 kA 10 kA 10 kA 10 kA 10 kA 10 kA 10 kA 10 kA 10 kA 10 kA 3 kA 3 kA 3 kA
40 kA 40 kA 40 kA 40 kA 40 kA 40 kA 40 kA 40 kA 40 kA 40 kA 40 kA 40 kA 40 kA 40 kA 40 kA 10 kA 10 kA 10 kA 10 kA 10 kA 10 kA 10 kA 10 kA 10 kA 10 kA 10 kA 10 kA 10 kA 10 kA 10 kA 1 kA 1.25 kA 1.25 kA 1.25 kA 10 kA 10 kA 10 kA 1.6 kA 1.6 kA 1.6 kA 1.6 kA 1.6 kA 3 kA 2 kA 2 kA 2 kA 2 kA 2 kA 3 kA 3 kA 2.5 kA 2.5 kA 2.5 kA 2.5 kA 2.5 kA 2.5 kA
Downstream
27
Bulletin 140U/UE
28
Downstream
Bulletin 140U/UE
Time-Current Curves
Bul.140U
Time-Current Curves for Bulletin 140U-G Thermal-Magnetic Molded Case Circuit Breakers
CURRENT IN PERCENT OF BREAKER TRIP UNIT RATING
40 00 6000 70 00 8000 9000 10,000 6 00 700 8 00 900 1 000 2000 3000 5000 70 80 90 100 2 00 300 400 5 00 60,000 70,000 80,000 90,000 100,000 20,000 30,000 40,000 50,000 50 60
10,000
10,000
2 HOURS
2 HOURS
5,000
5,000
1 HOUR
1 HOUR
For application and coordination purposes only. Based on 40 C ambient, cold start. Connected with four (4) feet of rated wire (60/75C) per terminal. Tested in open air with current in all poles except for instantaneous trip, see below. Maximum Volts Breaker Type 140U-G Ac Volts 60 Hz 480
3,000
2,000
2,000
1,000
1,000
Breaker Rating Continuous Amperes 15-60 70-100 Interrupting Rating (UL Listed) Breaker Type 140U-G Instantaneous Trip, Amperes Single Pole 2 Poles in Series 500-1300 400-1100 1300-1800 700-1300 Symmetrical RMS Amperes 240 Volts 480 Volts 22,000 65,000
500
500
300
300
200
200
100
100
1 MINUTE
1 MINUTE
50
50
30
30
20
20
10
10
Maximum
5
Minimum
TIME IN SECONDS
TIME IN SECONDS
.5
.5
.3
.3
.2
.2
.1
.1
.05
.05
.03
.03
.005
.005
.003
.003
.002
.002
.001
60 70 80 90 100 50 60,000 70,000 80,000 90,000 100,000 6000 7000 8 000 9000 10,000 20,000 30,000 40,000 50,000 600 700 800 900 1000 3000 4000 5 000 2000 400 300 500 200
.001
29
Bulletin 140U/UE
Bul.140U/UE
Bulletin 140U/UE - H-, J-, L-Frames Current Limiting Characteristics (Ip) 210415V AC, 50/60 Hz
200 kA 100 80
0.2
cos = 0.25
60
CUT-OFF CURRENT ID
40
0.3
20
J
10 8 6
2 5 7 10 20 30 50 kA 100
30
Bulletin 140U/UE
Bul.140U/UE
Time-Current Curves for Bulletin 140U-H Thermal-Magnetic Molded Case Circuit Breakers
Number of Poles: 3, 4 o Ambient 40 C Interrupting Ratings - 50/60 Hz RMS Symmetrical Amperes (kA), Icu Two Series Poles Inst. MagneticTrip Shown. Individual Pole Inst. Magnetic Trip +30%. DC Inst. Magnetic Trip +30% Higher Than AC. Notes: (a) (b) Fixed Inverse-Time Overcurrent Release. Fixed Electromagnetic Release. Total Operation Time. Interrupting Rating determines end of Curve.
(c)
1 minute
(d)
1 minute
31
Bulletin 140U/UE
Bul.140U/UE
Bulletin 140U/UE - H-, J-, L-Frames Current Limiting Characteristics (Ip) 210415V AC, 50/60 Hz
200 kA 100 80
0.2
cos = 0.25
60
CUT-OFF CURRENT ID
40
0.3
20
J
10 8 6
2 5 7 10 20 30 50 kA 100
32
Bulletin 140U/UE
Bul.140U/UE
Earth Leakage Curves for Bulletin 140U/UE-H IEC-Rated Thermal-Magnetic Molded Case Circuit Breakers
.01 .02 .03 .04 .05 .07 .1 .2 .3 .4 .5 .7 1.0 2.0 3.0 4.0 5.0
7.0
10.0
20.0
50.0
80.0
Circuit Breaker Time/Current Curves 1. 140U/UE-H Circuit Break.Earth Leakage Mod., 3 and 4 Poles, 110 - 480V 60Hz. 2. For application and coordination purposes only. -20 C to 55 C ambient. 3. Total clearing times include the response time of the Earth Leakage module, opening time of the circuit breaker, and interruption of current. 4. For additional curve tolerances, contact Rockwell Automation.
200.0
200.0
20.0
20.0
.03
10.0 9.0 8.0 7.0 6.0 5.0 4.0 3.0
.1
.3
10
Available I n Settings
10.0 9.0 8.0 7.0 6.0 5.0 4.0 3.0
2.0
2.0
1S
TIME IN SECONDS
1.0 .9 .8 .7 .6 .5 .4 .3 1.0 .9 .8 .7 .6 .5 .4 .3
TIME IN SECONDS
500ms
300ms
.2
150ms
.2
60ms
Inst.
.02 .02
.002
.002
.001
.01 .02 .03 .04 .05 .07 .1 .2 .3 .4 .5 .7 1.0 2.0 3.0 4.0 5.0 7.0 10.0 20.0 50.0 80.0
.001
Ig (Amperes)
33
Bulletin 140U/UE
Bul.140U/UE
Earth Leakage Curves for Bulletin 140U/UE-H UL-Rated Thermal-Magnetic Molded Case Circuit Breakers
1000.0 900.0 800.0 700.0 600.0 500.0 400.0 300.0
.01 .02 .03 .04 .05 .07 .1 .2 .3 .4 .5 .7 1.0 2.0 3.0 4.0 5.0 7.0 10.0 20.0 50.0 80.0
Circuit Breaker Time/Current Curves 1. 140U/UE-H Cir. Break. Earth Leakage Mod., 3 and 4 Poles, 110 - 480V 60Hz. 2. For application and coordination purposes only. -20 C to 55 C ambient. 3. Total clearing times include the response time of the Earth Leakage module, opening time of the circuit breaker, and interruption of current. 4. For additional curve tolerances, contact Rockwell Automation
200.0
200.0
20.0
20.0
.03
.1
.3
10
2.0
2.0
1S
TIME IN SECONDS
TIME IN SECONDS
1.0 .9 .8 .7 .6 .5 .4 .3 1.0 .9 .8 .7 .6 .5 .4 .3
500ms
300ms
150ms
.2 .2
60ms
Inst.
.03
.02
.02
.002
.002
.001
.01
.02
.03
.04 .05
.07
.1
.2
.3
.4
.5
.7
1.0
2.0
3.0
4.0 5.0
7.0
10.0
20.0
50.0
80.0
.001
Ig (A)
40752-603 (1) Curve No. TC01212004E Effective September 2005
34
Bulletin 140U/UE
Bul.140U/UE
Time-Current Curves for Bulletin 140U-J Thermal-Magnetic Molded Case Circuit Breakers
Allen-Bradley 63250 A
35
Bulletin 140U/UE
Bul.140U/UE
Time-Current Curves for Bulletin 140U-J Electronic LS Molded Case Circuit Breakers
Current in Multiples of (Ir)
.5 .7 1 2 3 4 5 7 10 20 30
2 HOURS
1 HOUR
1.15
4000 3000
2000
In
A B C D E F G H
Notes: 1. Curve accuracy applies from -20C to +55C ambient. Temperatures above +88 C cause an over temperature protection trip. For possible continuous ampere derating for ambient above 40C, consult Rockwell Automation. 2. Application frequency is 50/60 Hertz.
200
1 MINUTE
100 90 80 70 60 50 40 30
Available Long Delay Time: 2,4,7,10,12,15,20,24 sec. Shown @ 6x Ir 2,4,7,15,24 seconds +0/-30%
3. There is a memory effect that can act to shorten the Long Delay. The memory effect comes into play if a current above the circuit breaker itself. A subsequent overload will cause the circuit breaker to trip in shorter time than normal. The amount of time delay reduction is inverse to the amount of time that has elapsed since the previous overload. Approximately five minutes is required between overloads to completely reset memory. 4. The right portion of the curve is determined by the interrupting rating of the circuit breaker. 5. The left portion of the curve is shown as a multiple of the Long Delay Setting (Long Delay Pick Up = 115% of Ir). Range is 110% - 120%.
20
24
TIME IN SECONDS
. . .
7
6. Total clearing times shown include the response times of the trip unit, the breaker opening, and the interruption of the current. 7. The Short Delay Pick Up has 9 settings/positions: 2 - 8 & 10, 14. 8. Short Delay I T band has a tolerance of 15%. 9. Breakpoint back to FLAT response occurs @ 8x Ir for upper line of the I T curve. 10. For high fault current levels an additional fixed instantaneous hardware override is provided at 14x (In). 11. For LD Response & SD with Flat Response curve, see:
2 2 2
10 9 8 7 6 5 4 3
15
.
4 3
40752-622
12. For LD Response & SD with I T Response (this curve): 40752-621 13. For Ground Fault Delay Response curve, see: 40752-623
.
2 4
2
1 .9 .8 .7 .6 .5 .4 .3
1 .9 .8 .7 .6 .5
7
.4 .3
8 14
.2
.2
10
.
67ms
See Note 9
.02
14x
.02
.01
.5
.7
10
20
30
40
50
70
100
10
20
30
40
50
70
.01 100
Current in Multiples of ( I n )
Trip Style
36
TIME IN SECONDS
Bulletin 140U/UE
Bul.140U/UE
Time-Current Curves for Bulletin 140U-J Electronic LSI Molded Case Circuit Breakers
Current in Multiples of (Ir)
.5 .7 1 2 3 4 5 7 10 20 30
Long Delay Response & Short Delay with Flat Response Curve
2 HOURS
1 HOUR
1.15
4000 3000
2000
In
A B C D E F G H
Notes:
200
1. Curve accuracy applies from -20C to +55C ambient. Temperatures above +88 C cause an overtemperature protection trip. For possible continuous ampere derating for ambient above 40C, consult Rockwell Automation.
100 90 80 70 60 50 40 30
1 MINUTE
Available Long Delay Time: 2,4,7,10,12,15,20,24 sec. Shown @ 6x Ir 2,4,7,15,24 seconds +0/-30%
2. Application frequency is 50/60 Hertz. 3. There is a memory effect that can act to shorten the Long Delay. The memory effect comes into play if a current above the circuit breaker itself. A subsequent overload will cause the circuit breaker to trip in shorter time than normal. The amount of time delay reduction is inverse to the amount of time that has elapsed since the previous overload. Approximately five minutes is required between overloads to completely reset memory. 4. The right portion of the curve is determined by the interrupting rating of the circuit breaker.
20
24
TIME IN SECONDS
. . .
7
5. The left portion of the curve is shown as a multiple of the Long Delay Setting. (Long Delay Pick Up = 115% of Ir). Range is 110% - 120%. 6. Total clearing times shown include the response times of the trip unit, the breaker opening, and the interruption of the current. 7. The Short Delay Pick Up has 9 settings/positions, 2 - 8 & 10, 14. 8. For high fault current levels an additional fixed instantaneous hardware override is provided at 14x (In). 9. For LD Response & SD with Flat Response (this curve): 10. For LD Response & SD with I T Response curve, see: 11. For Ground Fault Delay Response curve, see:
2
10 9 8 7 6 5 4 3
15
.
4
.
2 2 4 14 3 5 6 8
.6
.5 .4 .3
.5 .4 .3
.2
.2
7
120ms (M,N,O)
10
Inst. (J,K,L)
.02
.02
14x
.01
.5
.7
10
20
30
40
50
70
100
10
20
30
40
50
70
.01 100
TIME IN SECONDS
1 .9 .8 .7 .6
1 .9 .8 .7
37
Bulletin 140U/UE
Bul.140U/UE
Time-Current Curves for Bulletin 140U-J Electronic LSG & LSIG Molded Case Circuit Breakers
.1
10000 9000 8000 7000 6000 5000 4000
.2
.3
.4
.5
.7
1.0
2.0
3000
2000
Switch Setting J K L M N O P Q R
tSD Inst. Inst. Inst. 120 120 120 300 300 300
tGF Inst. 120 300 Inst. 120 300 Inst. 120 300
200
1 MINUTE
100 90 80 70 60 50 40 30
TIME IN SECONDS
20
10 9 8 7 6 5 4 3
1 .9 .8 .7 .6 .5 .4 .3
0.8X
300ms (L,O,R)
.2
Notes:
.1 .09 .08 .07 .06 .05 .04 .03
120ms (K,N,Q)
1. Curve accuracy applies from -20C to +55C ambient. Temperatures above +88 C cause an over-temperature protection trip. For possible continuous ampere derating for ambient above 40C, consult Rockwell Automation. 2.Application frequency is 50/60 Hertz.
Inst. (J,M,P)
3. Trip units are suitable for functional field testing with test kit style # 70C1056G52. 4. For LD Response & SD with Flat Response curve, see: 5. For LD Response & SD with I T Response curve, see: 6. For Ground Fault Delay Response (this curve):
2
.02
.01
.1
.2
.3
.4
.5
.7
1.0
2.0
38
Bulletin 140U/UE
Bul.140U/UE
Earth Leakage Curves for Bulletin 140U/UE-J IEC-Rated Thermal-Magnetic Molded Case Circuit Breakers
1000 900.0 800.0 700.0 600.0 500.0 400.0
.01 .02 .03 .04 .05 .07 .1 .2 .3 .4 .5 .7 1.0 2 3 4 5 7 10
1. 140U/UE-J Circuit Breaker Earth Leakage Module, 3 and 4 Poles, 110 - 480V 50/60Hz. 2. For application and coordination purposes only. -20C to 55C ambient. 3. Total clearing times include the response time of the Earth Leakage module, opening time of the circuit breaker, and interruption of current. 4. For additional curve tolerances, contact Rockwell Automation.
500.0 400.0
300.0
300.0
200.0
200.0
30.0
30.0
20.0
20.0
.03
10.0 9.0 8.0 7.0 6.0 5.0 4.0
.1
.3
10
Available I n settings
10.0 9.0 8.0 7.0 6.0 5.0 4.0
3.0
3.0
2.0
2.0
TIME IN SECONDS
TIME IN SECONDS
1S
1.0 .9 .8 .7 .6 .5 .4
1.0 .9
500ms
.8 .7 .6 .5
300ms
.4
.3
.3
150ms
.2 .2
60ms
.03
.03
Inst
.02 .02
.003
.003
.002
.002
.001
.01 .02 .03 .04 .05 .07 .1 .2 .3 .4 .5 .7 1.0 2 3 4 5 7 10
.001
I n
(Amperes)
39
Bulletin 140U/UE
Bul.140U/UE
Earth Leakage Curves for Bulletin 140U/UE-J UL-Rated Thermal-Magnetic Molded Case Circuit Breakers
1000 900.0 800.0 700.0 600.0 500.0 400.0
.01 .02 .03 .04 .05 .07 .1 .2 .3 .4 .5 .7 1.0 2 3 4 5 7 10
1. 140U/UE-J Circuit Breaker Earth Leakage Module, 3and 4 Poles, 110 - 480V 50/60Hz. 2. For application and coordination purposes only. -20C to 55C ambient. 3. Total clearing times include the response time of the Earth Leakage module, opening time of the circuit breaker, and interruption of current. 4. For additional curve tolerances, contact Rockwell Automation. F
500.0 400.0
300.0
300.0
200.0
200.0
30.0
30.0
20.0
20.0
.03
10.0 9.0 8.0 7.0 6.0 5.0 4.0
.1
.3
10
3.0
3.0
2.0
2.0
TIME IN SECONDS
TIME IN SECONDS
1S
1.0 .9 .8 .7 .6 .5 .4
1.0 .9
500ms
.8 .7 .6 .5
300ms
.4
.3
.3
150ms
.2 .2
60ms
.03
.03
Inst
.02 .02
.003
.003
.002
.002
.001
.01 .02 .03 .04 .05 .07 .1 .2 .3 .4 .5 .7 1.0 2 3 4 5 7 10
.001
Ig(A)
40752-625 (1) Curve No. TC01204004E Effective September 2005
40
Bulletin 140U/UE
Bul.140U
Time-Current Curves for Bulletin 140U-K3/K6 Thermal-Magnetic Molded Case Circuit Breakers
600 700 800 900 1000 60 70 80 90 100 6000 7000 8000 9000 10,000 4000 2000 3000 300 200 400 500 5000 60,000 70,000 80,000 90,000 100,000
10,000
10,000
2 HOURS
2 HOURS
5,000
5,000
1 HOUR
1 HOUR
2,000
For application and coordination purposes only. Based on 40 C ambient, cold start. Connected with four (4) feet of rated wire (60C up to 125 A. 75 C above 125 A) per terminal. Tested in open air with current in all poles. Instantaneous calibration based on single-pole tests. Maximum Voltage 600V., AC (60 Hz) 250 V., DC
3,000
2,000
1,000
1,000
500
(250-400A)
300
(125-225A)
200
Breaker Rating Rated Amperes (In) Instantaneous Trip Amperes 100, 125, 150, 500 to 1000% of trip unit rating 175, 200, 225, (See Figure Below) 250, 300, 350, (Dc values are approximately 40% higher) 400 Interrupting Rating (UL/CSA) RMS Sym Amperes Amperes Breaker Type @ 240 V., AC @ 480 V., AC @ 600 V., AC @ 250 V., DC
140U-K3 140U-K6
500
300
65,000 100,000
35,000 65,000
25,000 35,000
10,000 22,000
200
(100A)
100
Single pole data at 25C based on NEMA Procedures (AB 4-1991) for verifying performance of molded case circuit breakers.
100
1 MINUTE
1 MINUTE
Minimum
50
Maximum
50
30
30
20
7.5
20
7.5
10
Push to Trip
7.5
10
5 Amps (In)
10
10
Magnetic Multiples Of In
40C
Cat. No.
TIME IN SECONDS
TIME IN SECONDS
.3
10X
.5
5X
20%
10%
.5
.3
.2
.2
.1
.1
.05
.05
.03
.03
.02
.02
.01
.01
.005
.005
.003
.003
.002
.002
.001
30,000 20,000 40,000 50,000 60,000 70,000 80,000 90,000 100,000 60 70 80 90 100 50 6000 7000 8000 9000 10,000 500 600 700 800 900 1000 200 300 400 2000 4000 3000 5000
.001
41
Bulletin 140U/UE
Bul.140U
Time-Current Curves for Bulletin 140U-K0 Thermal-Magnetic Molded Case Circuit Breakers
60 00 7000 8000 9000 10,000 2000 4000 600 700 800 900 1 000 300 200 4 00 500 70 80 90 100 5000 3000 50 60 60,000 70,000 80,000 90,000 100,000
10,000
10,000
2 HOURS
2 HOURS
5,000
1 HOUR
5,000
1 HOUR
3,000
3,000
2,000
2,000
1,000
Breaker Rating Rated Amperes (In) 100, 125, 150, 175, 200, 225, 250, 300, 350, 400
1,000
Instantaneous Trip Amperes 500 to 1000% of trip unit rating (See Figure Below) (DC values are approximately 40% higher)
500
500
(250-400A)
300
200
Interrupting Rating (UL/CSA) RMS Sym Amperes Breaker Type @ 240 V., AC @ 480 V., AC 140U-K0 200,000
100,000
Amperes
@ 600 V., AC 50,000 @ 250 V., DC 22,000
200 300
Single pole test data at 25C based on NEMA Procedures (AB 4-1991) for verifying performance of molded case circuit breakers.
(100A)
100 100
1 MINUTE
1 MINUTE
Minimum
50
Maximum
50
30
30
20
7.5 7.5
20
10
Push to Trip
7.5
10
10
Magnetic Multiples Of In
40C
Cat. No.
TIME IN SECONDS
TIME IN SECONDS
.3
10X
.5
5X
20%
10%
.5
.3
.2
.2
.1
.1
.05
.05
.03
.03
.02
.02
480 V., Ac
.005 .005
240 V., Ac
.003 .003
.002
.002
.001
30,000 40,000 50,000 60,000 70,000 80,000 90,000 100,000 6000 7000 8000 9000 10,000 20,000 50 60 70 80 90 100 500 600 700 800 900 1000 200 300 400 2000 3000 4000 5000
.001
42
Bulletin 140U/UE
Bul.140U
Time-Current Curves for Bulletin 140U-K Electronic LS, LSG Trip Units and Bulletin 140U-K3, -K6 Molded Case Circuit Breakers
10,000 .5 .7
6 7 8 9 10
20
2 HOURS
5,000
1 HOUR
Technical Data Covers, Bul. No. 140U-KTH3, -KTG3 Electronic Trip Units for use with Circuit Breaker Types 140U-K3X3 and -K6X3, 400 A Max.
3,000
TEST
Remove
Type
300
200
Long Delay Maximum Total Clearing Time Long Delay Minimum Total Clearing Time
Short Delay Pickup Range Amperes 800-3200 700-2800 600-2400 500-2000 450-1800 400-1600
100
1 MINUTE
50
Interrupting Ratings 50/60 RMS Sym. Amperes (kA) Breaker Type 140U-K3 140U-K6 Breaker Type
240V 65 100
380V 40 65
415V 40 65
30
140U-K3 140U-K6
20
2X
Notes Electronic trip units are suitable for functional field testing with test kit. For field testing using primary injection methods, follow NEMA publication AB-4-1991. There is a memory effect that can act to shorten the long delay. The memory effect comes into play if a current above the long delay pick up value exists for a time and then is cleared by the tripping of a down stream device or the circuit breaker itself. A subsequent overload will cause the circuit breaker to trip in shorter time than normal. The amount of time delay reduction is inverse to the amount of time that has elapsed since the previous overload. Approximately five minutes is required between overloads to completely reset the memory. Curve accuracy applies from 20 C to +55 C ambient. For possible continuous ampere derating for ambient above 40 C, consult Rockwell Automation. For high fault current levels a fixed instantaneous override is provided at 4000 A. (Tolerance 15%). The end of the curve is determined by the interrupting rating of the circuit breaker. See above tabulation. For ground fault time/current curve see 40752-636.
10
3X
4X 5X 6X
TIME IN SECONDS
.5
.2
7X
.3
8X
.1
.1
.05
.05 .04
.03
.03
.02
.02
SECONDS
.01
.01
.005
.003
.002
.001
.001
1000 2000 3000 4000 5000 10,000 20,000 30,000 40,000 50,000
CURRENT IN AMPS
100,000
.5
.6 .7 .8 .9 1
3 4 5
6 7 8 9 10
20
43
Bulletin 140U/UE
Bul.140U
Time-Current Curves for Bulletin 140U-K Electronic LSI, LSIG Trip Units and Bulletin 140U-K3, -K6 Molded Case Circuit Breakers
.5 .7
10,000
6 7 8 9 10
20
2 HOURS
5,000
1 HOUR
Technical Data Covers, Cat. Nos. 140U-KTL3, -KTI3 Electronic Trip Units for use with Circuit Breaker Types 140U-K3, -K6, 400A. max.
3,000
2,000
TEST
Remove
500
Available Rating Plugs Ampere Rating (In) 400 350 300 250 225 200
Type
300
200
Long Delay Maximum Total Clearing Time Long Delay Minimum Total Clearing Time
Short Delay Pickup Range Amperes 800-3200 700-2800 600-2400 500-2000 450-1800 400-1600
100
1 MINUTE
Interrupting Ratings 50/60 RMS Sym. Amperes (kA) Breaker Type 140U-K3 140U-K6 Breaker Type
50
240V 65 100
380V 40 65
415V 40 65
30
140U-K3 140U-K6
20
Notes Electronic trip units are suitable for functional field testing with test kit. For field testing using primary injection methods, follow NEMA publication AB-4-1991.
2X
10
There is a memory effect that can act to shorten the long delay. The memory effect comes into play if a current above the long delay pick up value exists for a time and then is cleared by the tripping of a down stream device or the circuit breaker itself. A subsequent overload will cause the circuit breaker to trip in shorter time than normal. The amount of time delay reduction is inverse to the amount of time that has elapsed since the previous overload. Approximately five minutes is required between overloads to completely reset the memory. Curve accuracy applies from 20C to +55C ambient. For possible continuous ampere derating for ambient above 40C, consult Rockwell Automation. For high fault current levels a fixed instantaneous override is provided at 4000A. (Tolerance 15%). The end of the curve is determined by the interrupting rating of the circuit breaker. See above tabulation. For ground fault time/current curve see 40752-636.
4X
2
6X 7X 8X
TIME IN SECONDS
.5
.5
3X
5X
300 ms
.3
.4 .3
200 ms
.2 .2
100 ms
.1 .1
.05
I
.05 .04
.03
.03
.02
.02
SECONDS
.01
.01
.005
.003
.002
1000
3000
4000
2000
5000
.001
CURRENT IN AMPS
44
100,000
.5
.6 .7 .8 .9 1
3 4 5
6 7 8 9 10
20
Bulletin 140U/UE
Bul.140U
Time-Current Curves for Bulletin 140U-K Electronic LS, LSG Trip Units and 140U-K0 Molded Case Circuit Breakers
CURRENT IN MULTIPLES OF RATING PLUG AMPERES (In)
.. 8 .9 16 2 3 4 5
10,000
.5
.7
6 7 8 9 10
20
2 HOURS
5,000
1 HOUR
3,000
Technical Data Covers, Cat. No. 140U-KTH3, -KTG3 Electronic Trip Units for use with Circuit Breaker Type 140U-K0, 400A. max. Fixed Short Delay Time Typical Trip Unit Nameplate
Short Delay Push to Trip Pickup xIr 4 Engaged 2 Trip Unit o 40 C 5 6 3 7 8
2,000
TEST
Remove
500
Type
200
Long Delay Maximum Total Clearing Time Long Delay Minimum Total Clearing Time
100
Short Delay Pickup Range Amperes 800-3200 700-2800 600-2400 500-2000 450-1800 400-1600
1 MINUTE
50
30
Interrupting Ratings 50/60 RMS Sym. Amperes (kA) Breaker Type 140U-K0
20
3X
10
2X
4X
Notes Electronic trip units are suitable for functional field testing with test kit. For field testing using primary injection methods, follow NEMA publication AB-4-1991. There is a memory effect that can act to shorten the long delay. The memory effect comes into play if a current above the long delay pick up value exists for a time and then is cleared by the tripping of a down stream device or the circuit breaker itself. A subsequent overload will cause the circuit breaker to trip in shorter time than normal. The amount of time delay reduction is inverse to the amount of time that has elapsed since the previous overload. Approximately five minutes is required between overloads to completely reset the memory. Curve accuracy applies from 20 C to +55 C ambient. For possible continuous amp derating for ambient above 40 C, consult Rockwell Automation For high fault current levels a fixed instantaneous override is provided at 4000A. (Tolerance 15%). The end of the curve is determined by the interrupting rating of the circuit breaker. See above tabulation. For ground fault time/current curve see 40752-636.
5X 6X
TIME IN SECONDS
.5
.2
7X
.3
8X
.1
.1
.05
.05 .04
.03
.03
.02
.02
SECONDS
600 VAC
.01
.01
.005
.003
.002
.001
.001
2000 3000 4000 5000
.5
.6 .7 .8 .9 1
3 4 5
6 7 8 9 10
20
CURRENT IN AMPS
45
Bulletin 140U/UE
Bul.140U
Time-Current Curves for Bulletin 140U-K Electronic LSI, LSIG Trip Units and 140U-K0 Molded Case Circuit Breakers
10,000 .5 .7
6 7 8 9 10
20
2 HOURS
5,000
1 HOUR
Technical Data Covers, Cat. Nos. 140U-KTL3, -KTI3 Electronic Trip Units for use with Circuit Breaker Cat. No 140U-K0, 400A. max.
3,000
Cat. In
TEST
Remove
Type
Short Delay Pickup Range Amperes 800-3200 700-2800 600-2400 500-2000 450-1800 400-1600
300
200
Long Delay Maximum Total Clearing Time Long Delay Minimum Total Clearing Time
100
1 MINUTE
Interrupting Ratings 50/60 RMS Sym. Amperes (kA) Breaker Type 140U-K0
50
Breaker Type
30
240V 200
380V 100
415V 100
140U-K0
20
Notes electronic trip units are suitable for functional field testing with test kit. For field testing using primary injection methods, follow NEMA publication AB-4-1991.
2X
10
There is a memory effect that can act to shorten the long delay. The memory effect comes into play if a current above the long delay pick up value exists for a time and then is cleared by the tripping of a down stream device or the circuit breaker itself. A subsequent overload will cause the circuit breaker to trip in shorter time than normal. The amount of time delay reduction is inverse to the amount of time that has elapsed since the previous overload. Approximately five minutes is required between overloads to completely reset the memory. Curve accuracy applies from 20C to +55 C ambient. For possible continuous ampere derating for ambient above 40C, consult Rockwell Automation. For high fault current levels a fixed instantaneous override is provided at 4000A. (Tolerance 15%). The end of the curve is determined by the interrupting rating of the circuit breaker. See above tabulation. For ground fault time/current curve see 40752-636.
4X
2
6X 7X 8X
TIME IN SECONDS
.5
3X
5X
300 ms
.3
200 ms
.2
100 ms
.1 .1
I
.05 .05 .04 .03 .03
.02
.02
SECONDS
.01
.01
.005
.003
.002
.001
2000
3000
4000
5000
10,000
30,000
40,000
20,000
50,000
CURRENT IN AMPS
46
100,000
200,000
.5
.6 .7 .8 .9 1
6 7 8 9 10
.001 20
Bulletin 140U/UE
Bul.140U
Time-Current Curves for Bulletin 140U-K Electronic Trip Units with Ground Fault Protection
480
10,000
2 HOURS
5,000
160
240
320
80
400
8000
GROUND CURRENT-AMPERES
1 HOUR
3,000
2,000
1,000
Engaged
Remove
500
Time ms
300 150 INST 500
300
TEST
200
Remove
Notes Curve accuracy applies from 20 C to +55 C ambient. For possible continuous ampere derating for ambient above 40 C, consult Rockwell Automation.
100
1 MINUTE
Electronic trip units are suitable for functional field testing with test kit. For field testing using primary injection methods, follow NEMA publication AB-4-1991.
50
30
20
10
1xIG
3xIG
4xIG
TIME IN SECONDS
Ground Fault Pickup Settings (Tolerance 10% Except 20% on 1xIG Setting)
2xIG
5xIG
500 ms
.5
300 ms
.3
.2
150 ms
.1
.05
.03
.02
.01
.005
.003
.002
.001
7 8 9 10
100
47
Bulletin 140U/UE
Bul.140U
Time-Current Curves for Bulletin 140U-K0 Thermal-Magnetic Molded Case Circuit Breakers
600 700 800 900 1 000 4 00 60 00 7000 8000 9000 10,000 2000 4000 30 0 200 70 80 90 100 500 5000 3000 50 60 60,000 70,000 80,000 90,000 100,000
10,000
10,000
2 HOURS
2 HOURS
5,000
1 HOUR
5,000
1 HOUR
3,000
3,000
2,000
2,000
1,000
Breaker Rating Rated Amperes (In) 100, 125, 150, 175, 200, 225, 250, 300, 350, 400
1,000
Instantaneous Trip Amperes 500 to 1000% of trip unit rating (See Figure Below) (Dc values are approximately 40% higher)
500
500
(250-400A)
300
200
Interrupting Rating (UL/CSA) RMS Sym Amperes Breaker Type @ 240 V., AC @ 480 V., AC 140U-K0 200,000
100,000
Amperes
@ 600 V., AC 50,000 @ 250 V., DC 22,000 0
200 300
Single pole test data at 25 C based on NEMA Procedures (AB 4-1991) for verifying performance of molded case circuit breakers.
(100A)
100 100
1 MINUTE
1 MINUTE
Minimum
50
Maximum
50
30
30
20
7.5 7.5
20
10
Push to Trip
7.5
10
10
Magnetic Multiples Of In
40C
Cat. No.
TIME IN SECONDS
TIME IN SECONDS
.3
10X
.5
5X
20%
10%
.5
.3
.2
.2
.1
.1
.05
.05
.03
.03
.02
.02
480 V., Ac
.005 .005
240 V., Ac
.003 .003
.002
.002
.001
30,000 40,000 50,000 60,000 70,000 80,000 90,000 100,000 6000 7000 8000 9000 10,000 20,000 50 60 70 80 90 100 500 600 700 800 900 1000 200 300 400 2000 3000 4000 5000
.001
48
Bulletin 140U/UE
Bul.140U/UE
Time-Current Curves for Bulletin 140U-L Thermal-Magnetic Molded Case Circuit Breakers
Circuit Breaker Time/Current Curves
For application and coordination purposes only. Thermal calibration based on 40 C ambient, cold start. Connected with four (4) feet of rated wire (75C) per terminal. Tested in open air with current in all poles. Instantaneous calibration based on single-pole tests. Maximum Voltage 600V., AC (50/60 Hz) 250 V., DC Breaker Rating Rated Amperes (In) 250, 300, 320, 350 Poles 3 and 4
1 Hour
1 Hour
Instantaneous Trip Amperes (see below) 500 to 1000% of trip unit rating (DC values are approximately 40% higher)
Interrupting Rating (UL/CSA) Breaker RMS Sym Amperes Type @ 240 V., AC @ 480 V., AC 140U-L3 140U-L6 65 100 35 65
Interrupting Rating (IEC 60947-2) Breaker RMS Sym kA, 50/60 Hz, AC Type @ 240 V. (Ue) @ 480 V (Ue) Icu 140U-L3 140U-L6 65 Ics 65 Icu 35 70 Ics 35 70
100 100
1 MINUTE
1 MINUTE
49
Bulletin 140U/UE
Bul.140U/UE
Earth Leakage Curves for Bulletin 140U/UE-L Thermal-Magnetic Molded Case Circuit Breakers
1000.0 900.0 800.0 700.0 600.0 500.0 400.0 300.0
.01 .02 .03 .04 .05 .07 .1 .2 .3 .4 .5 .7 1.0 2.0 3.0 4.0 5.0 7.0 10.0 20.0 50.0 80.0
Circuit Breaker Time/Current Curves 1. 140U/UE-L Cir. Break. Earth Leakage Mod., 3 and 4 Poles, 110 480V 60Hz. 2. For application and coordination purposes only. -20 C 55 C ambient. 3. Total clearing times include the response time of the Earth Leakage module, opening time of the circuit breaker, and interruption of current. 4. For additional curve tolerances, contact Rockwell Automation.
200.0
200.0
20.0
20.0
.03
.1
.5
30
10.0 9.0 8.0 7.0 6.0 5.0 4.0 3.0
2.0
2.0
1S
TIME IN SECONDS
TIME IN SECONDS
1.0 .9 .8 .7 .6 .5 .4 .3 1.0 .9 .8 .7 .6 .5 .4 .3
500ms
300ms
.2
150ms
.2
60ms
.02
Inst.
.02
.002
.002
.001
.01
.02
.03
.04 .05
.07
.1
.2
.3
.4
.5
.7
1.0
2.0
3.0
4.0 5.0
7.0
10.0
20.0
50.0
80.0
.001
Ig (A)
50
Bulletin 140U/UE
Bul.140U/UE
Earth Leakage Curves for Bulletin 140U/UE-L Thermal-Magnetic Molded Case Circuit Breakers
.01 .02 .03 .04 .05 .07 .1 .2 .3 .4 .5 .7 1.0 2.0 3.0 4.0 5.0 7.0 10.0 20.0 50.0 80.0
Circuit Breaker Time/Current Curves 1. 140U/UE-L Cir. Break. Earth Leak. Mod., 3 and 4 Poles, 110 480V 60Hz. 2. For application and coordination purposes only. -20 C 55 C ambient. 3. Total clearing times include the response time of the Earth Leakage module, opening time of the circuit breaker, and interruption of current. 4. For additional curve tolerances, contact Rockwell Automation.
200.0
200.0
20.0
20.0
.03
10.0 9.0 8.0 7.0 6.0 5.0 4.0 3.0
.1
.3
10
Available I n Settings
10.0 9.0 8.0 7.0 6.0 5.0 4.0 3.0
2.0
2.0
1S
TIME IN SECONDS
1.0 .9 .8 .7 .6 .5 .4 .3 1.0 .9 .8 .7 .6 .5 .4 .3
TIME IN SECONDS
500ms
300ms
.2
150ms
.2
60ms
Inst.
.02 .02
.002
.002
.001
.01 .02 .03 .04 .05 .07 .1 .2 .3 .4 .5 .7 1.0 2.0 3.0 4.0 5.0 7.0 10.0 20.0 50.0 80.0
.001
I n (Amperes)
51
Bulletin 140U/UE
Bul.140U/UE
Long Delay Response & Short Delay with Flat Response Curve, Bulletin 140U/UE-L
Current in Multiples of (Ir)
.5 .7 1 2 3 4 5 7 10 20 30
2 HOURS
1 HOUR
4000 3000
2000
1. Curve accuracy applies from -20C to +55C ambient. Temperatures above +85 C cause an overtemperature protection trip. For possible continuous ampere derating for ambient above 40C, refer to Rockwell Automation. 2. Application frequency is 50/60 Hertz. 3. There is a memory effect that can act to shorten the Long Delay. The memory effect comes into play if a current above the circuit breaker itself. A subsequent overload will cause the circuit breaker to trip in shorter time than normal. The amount of time delay reduction is inverse to the amount of time that has elapsed since the previous overload. Approximately five minutes is required between overloads to completely reset memory. 4. The right portion of the curve is determined by the interrupting rating of the circuit breaker. 5. The left portion of the curve is shown as a multiple of the Long Delay Setting. (Long Delay Pick Up = 115% of Ir). Range is 110% - 120%. 6. Total clearing times shown include the response times of the trip unit, the breaker opening, and the interruption of the current. 7. The Short Delay Pick Up has 8 settings/positions, 2 - 8 & 10. 8. For high fault current levels an additional fixed instantaneous hardware override is provided (corresponding to SDPU position 9) at 14x (In) and designated as 14I i. Instantaneous tolerance is 20%. 9. For LD Response & SD with Flat Response (this curve): 10. For LD Response & SD with I T Response curve, see: 11. For Ground Fault Delay Response curve, see:
2
200
1 MINUTE
100 90 80 70 60 50 40 30
Available Long Delay Time: 2,4,7,10,12,15,20,24 sec. Shown @ 6x Ir 2,4,7,15,24 seconds +0/-30%
20
24
TIME IN SECONDS
. . .
7
10 9 8 7 6 5 4 3
15
.
4
.
2
8 5
.6 .5 .4
.5 .4 .3
.3
.2
.2
120ms (M,N,O)
10
Inst. (J,K,L)
.02
.02
14 Ii
.01
.5
.7
10
20
30
40
50
70
100
10
20
30
40
50
70
.01 100
52
TIME IN SECONDS
1 .9 .8 .7 .6
1 .9 .8 .7
Bulletin 140U/UE
Bul.140U/UE
Long-Delay Response & Short-Delay with I2T Response Curve, Bulletin 140U/UE-L
Current in Multiples of (Ir)
.5 .7 1 2 3 4 5 7 10 20 30
2 HOURS
1 HOUR
4000 3000
Ir A B C D E F G H
In
Notes: 1. Curve accuracy applies from -20C to +55C ambient. Temperatures above +85 C cause an over temperature protection trip. For possible continuous ampere derating for ambient above 40C, refer to Rockwell Automation. 2. Application frequency is 50/60 Hertz.
200
1 MINUTE
100 90 80 70 60 50 40 30
Available Long Delay Time: 2,4,7,10,12,15,20,24 sec. Shown @ 6x Ir 2,4,7,15,24 seconds +0/-30%
3. There is a memory effect that can act to shorten the Long Delay. The memory effect comes into play if a current above the circuit breaker itself. A subsequent overload will cause the circuit breaker to trip in shorter time than normal. The amount of time delay reduction is inverse to the amount of time that has elapsed since the previous overload. Approximately five minutes is required between overloads to completely reset memory. 4. The right portion of the curve is determined by the interrupting rating of the circuit breaker. 5. The left portion of the curve is shown as a multiple of the Long Delay Setting (Long Delay Pick Up = 115% of Ir). Range is 110% - 120%.
20
24
TIME IN SECONDS
. . .
7
6. Total clearing times shown include the response times of the trip unit, the breaker opening, and the interruption of the current. 7. The Short Delay Pick Up has eight settings/positions: 2 - 8 & 10. 8. Short Delay I T band has a tolerance of 15%. 9. Breakpoint back to FLAT response occurs @ 8x Ir for upper line of the I T curve. 10. For high fault current levels an additional fixed instantaneous hardware override is provided (corresponding to SDPU position 9) at 14x (In) and designated as 14I i . Instantaneous tolerance is 20% 11. For LD Response & SD with Flat Response curve, see:
2 2 2
10 9 8 7 6 5 4 3
15
.
4 3
40752-653
.
2 4
40752-655
2
1 .9 .8 .7 .6 .5 .4 .3
1 .9 .8 .7 .6 .5
7
.4 .3
8
.2
.2
10
.
67ms
See Note 9
.02
14 Ii
.02
.01
.5
.7
10
20
30
40
50
70
100
10
20
30
40
50
70
.01 100
Trip Style
TIME IN SECONDS
Available Short Delay Pick Up Settings 2 - 8 & 10 x Ir 5% (See Notes 7 and 10)
53
Bulletin 140U/UE
Bul.140U/UE
Ground Fault Delay Response Curve, Bulletin 140U/UE-L
.1
10000 9000 8000 7000 6000 5000 4000 3000
.2
.3
.4
.5
.7
1.0
2.0
Ground Fault Delay Response Notes: 1. Curve accuracy applies from -20C to +55C ambient. Temperatures above +85 C cause an over-temperature protection trip. For possible continuous ampere derating for ambient above 40C, refer to Rockwell Automation. 2.Application frequency is 50/60 Hertz.
2000
3. Trip units are suitable for functional field testing with test kit style # 70C1056G52. 4. For LD Response & SD with Flat Response curve, see: 5. For LD Response & SD with I T Response curve, see: 6. For Ground Fault Delay Response (this curve):
2
200
1 MINUTE
100 90 80 70 60 50 40 30
TIME IN SECONDS
20
10 9 8 7 6 5 4 3
Ground Fault Pickup Settings (Tolerance 10%) NOTE: Refer to table below for variations.
Ir A B C D E F G H
In
1 .9 .8 .7 .6 .5 .4 .3
.8X
300ms (L,O,R)
.2
120ms (K,N,Q)
Inst. (J,M,P)
.02
.01
.1
.2
.3
.4
.5
.7
1.0
2.0
54
Bulletin 140U/UE
Bul.140U
Time-Current Curves for Bulletin 140U-Q3/Q6 Thermal-Magnetic Molded Case Circuit Breakers
50
60
10,000
10,000
2 HOURS
2 HOURS
5,000
5,000
1 HOUR
1 HOUR
2,000
For application and coordination purposes only. Thermal calibration based on 40 C ambient, cold start. Connected with four (4) feet of rated wire (75C) per terminal. Tested in open air with current in all poles. Instantaneous calibration based on single-pole tests. Maximum Voltage 600 V., AC (50/60 Hz.) 250 V., DC
3,000
2,000
1,000
Breaker Rating Rated Amperes (In) 300, 350, 400, 500, 600
1,000
Instantaneous Trip Amperes (See Figure Below) 500 to 1000% of trip unit rating (DC values are approximately 40% higher)
500
500
300
Interrupting Rating Breaker UL/CSA Type RMS Sym. kA, 50/60 Hz. 240 V. 140U-Q3 140U-Q6 480 V. 600 V. 25 35
kA, Dc 250 V. 10 20 kA, Dc 415 V., (U ) e Icu Ics 40 65 10 17 250 V., (U) e Icu Ics 10 20 3 5
300
200
Minimum
100
Maximum
65 35 100 65 IEC 947-2 RMS Sym. kA, 50/60 Hz. 240 V., (U ) e Icu Ics 380 V., (U) e Icu Ics 40 65 10 17
200
100
1 MINUTE
1 MINUTE
50
17 25
Utilization Category A U IMP = 8 kV Note: For additional information on the trip unit, see IL 29C606. Single pole data at 25 C based on NEMA Procedures (AB 4-1991) for verifying performance of molded case circuit breakers.
50
30
30
20
20
7.5
7.5
10
Push to Trip
7.5
10
10 5
Magnetic Multiples Of In
40C
Cat. No.
TIME IN SECONDS
TIME IN SECONDS
10X
5X
20%
10%
1
.5
.5
.2
.2
.1
.1
.05
.05
.03
.03
.02
.02
.01
.01
.005
.005
.003
.003
.002
.002
.001
60,000 70,000 80,000 90,000 100,000 30,000 6000 7000 8000 9000 10,000 20,000 50,000 40,000 60 70 80 90 100 50 500 600 700 800 9 00 1000 30 0 40 0 200 2000 3000 4000 5000
.001
55
Bulletin 140U/UE
Bul.140U/UE
Time-Current Curves for Bulletin 140U-M5, -M6 Thermal-Magnetic (300600 A) Molded Case Circuit Breakers
CURRENT IN PERCENT OF BREAKER TRIP UNIT RATING (In)
6000 7000 8000 9000 10,000 600 700 800 900 1000 3000 4000 2000 60 70 80 90 100 200 5000 500 300 400 60,000 70,000 80,000 90,000 100,000 20,000 30,000 40,000 50,000
50
10,000
10,000
2 HOURS
5,000
1 HOUR
5,000
3,000
3,000
2,000
2,000
1,000
1,000
Instantaneous Trip Amperes (See Figure Below) 500 to 1000% of trip unit rating (DC values are approximately 40% higher)
500
500
300
Interrupting Rating Breaker UL/CSA Type RMS Sym. kA, 50/60 Hz. 140U-M5 140U-M6 Breaker Type 240V 65 100 IEC 947-2 RMS Sym. kA, 50/60 Hz. ) 240V (Ue Icu Ics 140U-M5 140U-M6 65 100 65 100 380/415V (Ue ) 690V (Ue) Icu Ics Ics Icu 50 70 50 50 20 25 10 13 480V 50 65 600V 25 35
300
200
200
Minimum
100
Maximum
100
1 MINUTE
50
Utilization Category A U IMP = 8 kV Note: For additional information on the trip unit, see IL 29C607.
50
30
Single pole data at 25 C based on NEMA Procedures (AB 4-1991) for verifying performance of molded case circuit breakers.
30
20
7.5 7.5 Push to Trip 7.5
20
10
10
10
5 Amps (In)
10
10
Magnetic Multiples Of In
40 C
Cat. No.
TIME IN SECONDS
10X
5X
? 20%
? 10%
1
.5
.5
.2
.2
.1
.1
.05
.05
.03
.03
.02
.02
.01
.01
.005
.005
.003
.003
.002
.002
.001 30,000 40,000 60,000 70,000 80,000 90,000 100,000 20,000 6000 7000 8000 9000 10,000 50,000 60 70 80 90 100 50 500 600 700 800 900 1000 200 300 400 2000 3000 4000 5000
.001
56
Bulletin 140U/UE
Bul.140U/UE
Time-Current Curves for Bulletin 140U-M5, -M6 Thermal-Magnetic (700 & 800 A) Molded Case Circuit Breakers
CURRENT IN PERCENT OF BREAKER TRIP UNIT RATING (In)
2000 3000 6000 7000 8 0 00 9000 10,000 600 700 800 900 1000 4000 5000 200 300 400 70 80 90 100 500 60,000 70,000 80,000 90,000 100,000 30,000 40,000 20,000 50,000 50 60
10,000
10,000
2 HOURS
2 HOURS
5,000
5,000
1 HOUR
1 HOUR
2,000
For application and coordination purposes only. Thermal calibration based on 40 C ambient, cold start. Connected with four (4) feet of rated wire (75 C) per terminal. Tested in open air with current in all poles. Instantaneous calibration based on single-pole tests. Maximum Voltage 600 V AC (50/60 Hz.) 250 V DC
3,000
2,000
1,000
1,000
n)
Instantaneous Trip Amperes (See Figure Below) 400 to 800% of Trip Unit rating (DC values are approximately 40% higher)
500
500
300
Interrupting Rating Breaker UL/CSA Type RMS Sym. kA, 50/60 Hz. 140U-M5 140U-M6 Breaker Type 240V 65 100 IEC 947-2 RMS Sym. kA, 50/60 Hz. 240V (U ) e Ics Icu 140U-M5 140U-M6 65 100 65 100 380/415V (U e) Ics Icu 50 70 50 50 690V (U) e Ics Icu 20 25 10 13 480V 50 65 600V 25 35
300
200
200
Minimum
100
Maximum
100
1 MINUTE
1 MINUTE
50
50
30
Single pole data at 25C based on NEMA Procedures (AB 4-1991) for verifying performance of molded case circuit breakers.
6 6 Thermal Magnetic Trip Unit 8 4 8 4 Amps (In) C Cat. No. Push to Trip 8 4 6
30
20
20
10
10
Magnetic Multiples Of In
TIME IN SECONDS
TIME IN SECONDS
4X
8X
? 20%
? 10%
1
.5
.5
.2
.2
.1
.1
.05
.05
.03
.03
.02
.02
.01
.01
.005
.005
.003
.003
.002
.002
.001 20,000 30,000 60,000 70,000 80,000 90,000 100,000 40,000 6000 7000 8000 9000 10,000 50,000 50 60 70 80 90 100 500 600 70 0 800 900 1000 200 300 400 4000 2000 3000 5000
.001
57
Bulletin 140U/UE
Bul.140U/UE
Time-Current Curves for Bulletin 140U-M Electronic LS, LSG Trip Units and 140U-M5, -M6 Molded Case Circuit Breakers
10,000 .5
CURRENT IN MULTIPLES OF RATING PLUG AMPERES (In) .7 .9 16 .8 . 2 3 4 5 6 7 8 9 10
20
2 HO U R S
1 HO U R
3,000
2,000
Remove
500
Available Rating Plugs Ampere Rating (I n ) 800 700 600 500 450 400 Interrupting Rating
Type
300
200
Long Delay Maximum Total Clearing Time Long Delay Minimum Total Clearing Time
Rating Plug Catalog Number 140U-MRP3-D80 140U-MRP3-D70 140U-MRP3-D60 140U-MRP3-D50 140U-MRP3-D45 140U-MRP3-D40
Short Delay Pickup Range Amperes 1600-6400 1400-5600 1200-4800 1000-4000 900-3600 800-3200
100
1 MIN U T E
50
30
140U-M5 140U-M6
IEC 947-2 RMS Sym. kA, 50/60 Hz 380/415V (U 240V (U e) Ics Icu Ics Icu 65 100 Utilization Category A U imp = 8kV 65 100 50 70 50 50
e)
Icu 20 25
690V (U e) Ics 10 13
20
10
2X
3X
Notes Electronic trip units are suitable for functional field testing with test kit. For field testing using primary injection methods, follow NEMA AB4-1991 publications.
3 2
Calibration response in short delay pick-up range is same for 1, 2 or 3 poles in series. There is a memory effect that can act to shorten the long delay. The memory effect comes into play if a current above the long delay pick-up value exists for a time and then is cleared by the tripping of a downstream device or the circuit breaker itself. A subsequent overload will cause the circuit breaker to trip in shorter time than normal. The amount of time delay reduction is inverse to the amount of time that has elapsed since the previous overload. Approximately five minutes is required between overloads to completely reset the memory.
4X 5X
TIME IN SECONDS
Curve accuracy applies from 20 C to +55C ambient. For possible continuous ampere derating for ambient above 40 C, consult Rockwell Automation.
8X
For high fault current levels a fixed instantaneous override is provided at 5500A.
1
(Tolerance 15%).
6X
The end of the curve is determined by the interrupting rating of the circuit breaker.
See above tabulation.
.5
.2
7X
.3
.1
.1
.05
.05 .04
.03
.03
.02
.02
.01
SECONDS
.01
.005
.003
.002
30,000
40,000
10,000
20,000
50,000
CURRENT IN AMPS
58
100,000
1000
2000
4000
3000
5000
20
.001
Bulletin 140U/UE
Bul.140U/UE
Time-Current Curves for Bulletin 140U-M Electronic LSI, LSIG Trip Units and 140U-M5, -M6 Molded Case Circuit Breakers
10,000 2 HO U R S .5
.7
20
1 HO U R
Technical Data Covers, Cat. nos. 140U-MTH3, -MTI3 Electronic Trip Units for use with Circuit Breaker Types 140U-M5, -M6, 800 A max.
3,000
Remove
Type
300
Rating Plug Catalog Number 140U-MRP3-D80 140U-MRP3-D70 140U-MRP3-D60 140U-MRP3-D50 140U-MRP3-D45 140U-MRP3-D40
Short Delay Pickup Range Amperes 1600-6400 1400-5600 1200-4800 1000-4000 900-3600 800-3200
200
Long Delay Maximum Total Clearing Time Long Delay Minimum Total Clearing Time
Interrupting Rating Breaker Type 140U-M5 140U-M6 Breaker Type UL/CSA RMS Sym. kA, 50/60 Hz 240V 65 100 IEC 947-2 RMS Sym. kA, 50/60 Hz 240V (Ue) Icu Ics 140U-M5 140U-M6 65 100 Utilization Category A U imp = 8kV 65 100 380/415V (U e ) Icu Ics 50 70 50 50 690V (U e) Icu Ics 20 25 10 13 480V 50 65 600V 25 35
100
1 MIN U T E
50
30
20
2X
10
Notes Electronic trip units are suitable for functional field testing with test kit. For field testing using primary injection methods, follow NEMA AB4-1991 publications. Calibration response in short delay pickup range is same for 1, 2 or 3 poles in series.
4X
6X
There is a memory effect that can act to shorten the long delay. The memory effect comes into play if a current above the long delay pickup value exists for a time and then is cleared by the tripping of a downstream device or the circuit breaker itself. A subsequent overload will cause the circuit breaker to trip in shorter time than normal. The amount of time delay reduction is inverse to the amount of time that has elapsed since the previous overload. Approximately five minutes is required between overloads to completely reset the memory. Curve accuracy applies from 20 C to +55 C ambient. For possible continuous ampere derating for ambient above 40 C, consult Rockwell Automation. For high fault current levels a fixed instantaneous override is provided at 5500A. (Tolerance 15%). The end of the curve is determined by the interrupting rating of the circuit breaker. See above tabulation. For ground fault time/current curves see 40752-678.
TIME IN SECONDS
.5
3X
5X
7X
8X
300 ms
.3
200 ms
.2
100 ms
.1 .1
I
.05 .05 .04 .03 .03
.02
.02
.01
SECONDS
.01
.005
.003
.002
1000
4000
2000
3000
5000
.001
.001 10,000 40,000 30,000 50,000 20,000 100,000 .5 2 3 4 5 6 7 8 9 10 .6 .7 .8 .9 1 CURRENT IN MULTIPLES OF RATING PLUG AMPERES (In) 20
CURRENT IN AMPS
59
Bulletin 140U/UE
Bul.140U/UE
Time-Current Curves for Bulletin 140U-M Electronic Trip Units with Ground Fault Protection
Ground Fault Protection
320 160 10,000 1120 1280 1440 1600 800 480 640 960 16000
GROUND CURRENT-AMPERES
2 HOURS
5,000
1 HOUR
3,000
2,000
4 2
6 3 7 8
Remove
1,000
500
Remove
300
Notes Curve accuracy applies from 20 C to +55 C ambient. For possible continuous ampere derating for ambient above 40 C, consult Rockwell Automation. Electronic trip units are suitable for functional field testing with test kit. For field testing using primary injection methods, follow NEMA publication (AB4-1991). For phase time/current curves see: 40752-674 40752-675 40752-676 40752-677
200
100
1 MINUTE
50
30
20
10
1xIG
3xIG
5 3
4xIG
TIME IN SECONDS
Ground Fault Pickup Settings (Tolerance 10% Except 20% on 1xIG Setting)
2xIG
5xIG
500 ms
.5
300 ms
.3
.2
150 ms
.1
.05
.03
.02
.01
.005
.003
.002
.001
7 8 910
100
60
Bulletin 140U/UE
Bul.140U/UE
Time-Current Curves for Bulletin 140U-N Electronic LS Trip Units
10,000
CURRENT IN MULTIPLES OF RATING PLUG AMPERES (In) .5 .6 .7 .8 .9 1 2 3 4 5 6 7 8 9 10
20
2 HO U R S
Circuit Breaker
5,000
1 HO U R
Electronic Trip Units are AC only devices that employ microprocessor based technology that provides true RMS current sensing means for proper correlation with thermal characteristics of conductors and equipment. They are used with Circuit Breaker Types 140U-N5, -N6, and -N0. I2t Ramp Short Time Delay
Rating Plug
3,000
2,000
Push to Trip
Cat. /n Y
TEST
Engaged
Remov e
500
A vailable Rating Plugs Ampere Rating (I n) 1200 1000 800 700 600 600, 800, 1000, 1200
Type
Short Delay Pickup Range Amperes 2400-9600 2000-8000 1600-6400 1400-5600 1200-4800 1200-9600
300
200
Long Delay Maximum Total Clearing Time Long Delay Minimum Total Clearing Time
100
50
Interrupting Ratings 50/60 Hz RMS Sym. Amperes (kA) UL/CSA Breaker Type 240V 480V 65 50 ND, CND 100 65 HND, CHND 200 100 NDC, CNDC
1 MIN U T E
600V 25 35 50
380-415V 50 65 100
30
20
3X
2X
Notes
Curve accuracy applies from -20 C to +55 ambient above 40 C, consult Rockwell Automation Electronic trip units are suitable for functional field testing with test kit. For field testing using primary injection methods, follow NEMA publication AB-4-1991. For ground fault time-current curves see 40752-692.
10
3 2
There is a memory effect that can act to shorten the long delay. The memory effect comes into play if a current above the long delay pickup value exists for a time and then is cleared by the tripping of a downstream device or the circuit breaker itself. A subsequent overloads will cause the circuit breaker to trip in shorter time than normal. The amount of time delay reduction is inverse to the amount of time that has elapsed since the previous overload. Approximately five minutes is required between overloads to completely reset the memory For high fault current levels a fixed instantaneous override is provided at14000A (Tolerance 15%).
4X 5X
8X
TIME IN SECONDS
The end of the curve is determined by the interrupting rating of the circuit breaker. See above tabulation. Not UL/CSA Listed.
.5
.2
7X
.3
6X
.1
.1
.05
.05
.03
.03 .02
.02
SECONDS
.01
.01
.005
.005
.003
.003 .002
.002
CURRENT IN AMPS
200,000
40,000
10,000
20,000
30,000
50,000
20
.001
61
Bulletin 140U/UE
Bul.140U/UE
Time-Current Curves for Bulletin 140U-N LSI Electronic Trip Unit
CURRENT IN MULTIPLES OF RATING PLUG AMPERES (In) .5 .6 .7 .8 .9 1 2 3 4 5 6 7 8 9 10
10,000
20
2 HO U R S
Circuit Breaker
1 HO U R
5,000
Electronic Trip Units are AC only devices that employ microprocessor-based technology that provides true RMS current sensing means for proper correlation with thermal characteristics of conductors and equipment. For use with Circuit Breaker Types 140U-N5, -N6, and -N0. Adjustable Short Time Delay
Rating Plug
Push to Trip Cat. /n Y Short Delay Pickup x In 5 4 6 3 2 7 8
3,000
2,000
TEST
Engaged
Remov e
1,000
Frame Rating Amperes (Max.) 1200 A vailable Rating Plugs Ampere Type Rating (I n) 1200 1000 800 700 600 600, 800, 1000, 1200 Fixed Fixed Fixed Fixed Fixed Adj. Catalog Number 140U-NRP3-E12 140U-NRP3-E10 140U-NRP3-D80 140U-NRP3-D70 140U-NRP3-D60 140U-NRPA-E12 Short Delay Pickup Range Amperes 2400-9600 2000-8000 1600-6400 1400-5600 1200-4800 1200-9600
500
300
200
Long Delay Maximum Total Clearing Time Long Delay Minimum Total Clearing Time
100
1 MIN U T E
Interrupting Ratings 50/60 Hz RMS Sym. Amperes (kA) UL/CSA Breaker Type 240V 480V 65 50 140U-N5 100 65 140U-N6 200 100 140U-N0
600V 25 35 50
380-415V 50 65 100
50
Notes
30
20
2X
For ground fault time-current curves see 40752-692. There is a memory effect that can act to shorten the long delay. The memory effect comes into play if a current above the long delay pickup value exists for a time and then is cleared by the tripping of a downstream device or the circuit breaker itself. A subsequent overloads will cause the circuit breaker to trip in shorter time than normal. The amount of time delay reduction is inverse to the amount of time that has elapsed since the previous overload. Approximately five minutes is required between overloads to completely reset the memory
10
4X
3 2
For high fault current levels a fixed instantaneous override is provided at14000A (Tolerance 15%). The end of the curve is determined by the interrupting rating of the circuit breaker. See above tabulation. Not UL/CSA Listed.
6X 3X 5X 7X 8X
TIME IN SECONDS
.5
300 MS
.3
200 MS
.2
100MS
.1 .1
I
.05 .05
.03
.03 .02
.02
.01
SECONDS
.01
.005
.005
.003
.003 .002
.002
CURRENT IN AMPS
62
200,000
40,000
50,000
20,000
10,000
30,000
20
.001
Bulletin 140U/UE
Bul.140U/UE
Time-Current Curves for Bulletin 140U-N Electronic LSG, LSIG Trip Units with Ground Fault Protection
CURRENT IN AMPERES
2000 3000 600 700 800 900 1000 4000 .50 .60 .70 .80 .90 100 5000
200
300
400
10,000
2 HO U R S
500
Circuit Breaker
1 HO U R
5,000
Electronic Trip Units are AC only devices that employ microprocessor-based technology that provides true RMS current sensing means for proper correlation with thermal characteristics of conductors and equipment. They are used with Circuit Breaker Types 140U-N5, -N6, and N0.
2,000
Rating Plug
Push to Trip Cat. /n Y
1,000
Engaged Remov e
IG=200A
100
1 MIN U T E
50
30
20
200 A .
600 A .
10
1000 A .
3 2
Ground Fault Pick Up Settings (Tolerance 10% Except 20% on 200 A. Setting)
400 A . 1200 A .
1
TIME IN SECONDS
800 A .
.5
.5 SEC
.3
.3 SEC
.2
.15 SEC
.1
.05
.03
.02
.01
.005
.003
.002
.001
500
2000
4000
CURRENT IN AMPERES
3000
5000
200
300
400
63
Publication 140U-TD001B-EN-P November 2006 Copyright 2006 Rockwell Automation, Inc. All Rights Reserved. Printed in USA.