FULLY FEATURED

• Compact, f ul l y featured s i n g l e p o i nt Heat-trace C o n t r o l l e r

• Compatible with ALL types of h e a t i n g e q u i p m e n t and cables

• Computer m o n i t o r i n g e l i m i n a t e s n e e d for preventative m a i n t e n a n c e

• F u l l G F I protection - i n d e p e n d e n t A l ar m a n d Trip settings

COST EFFECTIVE

• Per point costs s i m i l a r to l a r g e r m u l t i - p o i n t p a n e l s

• No n e e d for a d d i t i o n a l G F I protection devices

VERSATIUTY

• D o u b l e pole Solid-state or E l e c t r o - m e c h a n i c a l relay switching

• Supports both s i n g l e a n d 2 p o l e c o n f i g u r a t i o n s to a f u l ! 30 Amps


DigiTrace™

REUABIUTY
Proven performance
• Excellent corrosion protection (conformally coated circuitry)

and technology for O


State of the art surface m o u n t technology

all of your heat

trace control

applications.
EVERYTHING YOU NEED IN A S I N G L E P O I N T CONTROLLER:

Each 91 O Controller supports one individual heat trace circuit. Terminals are

included for low-level signals such as RTDs, alarming and communications, as

well as for power wiring.

C H O I C E OF OUTPUT DEVICES:

The 91 O Series HTC is available in two output types:

electro-mechanical relay (EMR) output for use in ordinary (non-hazardous)

areas, and

solid-state relay ( S S R ) output for use in either ordinary or Class 1, Div. 2 /

Zone

2 hazardous locations.

Ratings of 30A, 1 2 0 to 277Vac are standard for both types.

UNIVERSAL DESIGN:

The Controller incorporales a universal power supply (100-277Vac), 50/60Hz

support, voltage, currsnt, and ground fault sensing. No other components are

required.

INTEGRAL C O N S O L E :

Large, easy to read alpha-numeric characters and menu-driven interface eases

configuration and eliminates the need for an externa! programmer. AII monitored

parameters, programmed values and alarming information are available to the

u ser.

OPTIONAL C O M M U N I C A T I O N S :

Communications modules are available for remote monitoring and configuration.

A modem version maintaining compatibility with all existing Pyrotenax heat trace

controls and upstream devices (GCCs, H H P s , and PyroMaster™ software) may

be chosen, or other industry-standard interfaces such as RS-485 and RS-232

may be specified.

VERSATILE MONITORING ANO A L A R M I N G :

The Controller monitors and alarms on high or low temperature, voltage, resist­

ance, or load curren! at user defined levels. Two separate temperature inputs are

standard, and both are monitored for open or shorted sensors. The 9 1 O Series

Controller also monitors ground fault currents and is suitable for meeting the lat­

es! NEC, CEC, and I E E E equipment protection requirements. The user may pro­

gram separate ground fault alarm and trip levels.

RESISTANCE MONITORING:

This feature provides enhanced functionality over the standard low curren! alarm­

ing when using tracing with constan! resistance. The Controller calculates trace

resistance in real-time, m i n i m i z i n g nuisance low curren! alarms when the line

voltage fluctuates. This makes for more reliable detection of heating zone loss for

constan! wattage heating cables.

AUTO-CYCLE™:

The controller will momentarily energize the circuí! at a user defined interval.

Circuit alarms will be generated at the time of auto-cycle, rather than only when

heat is required. This feature essentially eliminates the requirement for preventa­

tive maintenance checks.

DigiTrace™ REMOTE ENABLE/DISABLE:

I n applications where the designer wishes to disable individual or grouped

Controllers directly, a remote contact can force the unit(s) into an idle state,

where temperature control is disabled, but trace monitoring and alarming func­
Proven performance
tions remain active.

and technology for


HARSH E N V I R O N M E N T OPERATION:
a l l of your heat Wide temperature range operation plus conformally coated circuitry permits

installation in almos! any environment. Suitable for use in Class 1 , D i v i s i ó n 2 and


trace control
Zone 2 hazardous areas (Solid-state output versions only) as well as ordinary

(non-hazardous) locations.
applications.
GENERAL:

Operating Ambient: -40 to +60ºC (-40 to + 1 4 0 º F )

Universal 100-277Vac 50/60Hz operation

APPROVALS:

� lndicates certification of products meeting both U.S. and Canadian

standards

Ordinary locations ( S S R and EMR versions)

Class 1, Div. 2, Groups A , B , C , D and Ex nA I I A , I I B , I I C (SSR version only) , T-code: T4

TEMPERATURE CONTROL:

(2) 3-wire 1 0 0 ohm Platinum (o:=0.00385.Q/Q/"C) RTD inputs

Also supports 2- or 3-wire 1 0 0 ohm Nickel-lron RTD

Open/shorted sensor alarm, lead resistance compensated to 20 ohms per lead

-60 to +570ºC (-76 to + 1 0 5 8 º F ) measurement range

Proportional / Deadband, adjustable from 1 to S O º C ( 2 to 122ºF)

8 Temperature Control Modes

Remate lnhibit/Override Operation

OUTPUT CONTROL:

S S R : 2-pole, 30A @ 1 2 0 to 277Vac nominal., SOA 1 sec. in-rush, 625A 1 cycle in-rush

EMR: 2-pole, 30A @ 1 2 0 to 277Vac n o m i n a l .

Adaptive Soft-StartingTM (ln-rush current-Limit), Breaker Trip, Output Switch Protection

Programmable Power Limiting, Overcurrent Trip Feature

Adjustable Ground Fault Trip

4 Switch Control Modes i n c l u d i n g Proportional Ambient Control

AC ME A S U R E M EN T S :

Voltage measurement range: 80 to 295Vac

Curren! measurement range: 0.3 to 1 ODA (limited by output device)

Ground Fault Curren! range: 20 to 250ma

ALARMING:

Adjustable HI/LO Temperature, Curren!, Voltage, and Resistance Alarms

Adjustable HI Ground Fault Alarm

Temperature Sensor, Output Switch, and Communications Failure Alarms

Overcurrent Alarm

Alarm Filtering

Low voltage and Line voltage alarm outputs

OTHER FEATURES:

Power Accumulator (kW-h)

Programmable Alarm Output Contact

Programmable Auto-Cycle ™

Random Startup Delay

OPTIONAL COMMUNICATIONS:

HTCBusTM / Modbus (RTU or A S C I I )

Optional RS-232 / lsolated Modem / lsolated RS-485 (2-wire)

STANDARD CONSOLE:

Output, Alarm, Communications Status lndicators

Degrees C or F lndication

6 digit Alpha-numeric Display

Wide Temperature Operation

Programming Keypad
9 1 O S e r i e s Controller A s s e m b l i e s are ordered as c o m p l e t e u n i t s .

Contact your local representatíve far other av aílable configurations that are not listed beiow.

DESCRIPTION MODEL CODE

Controller in an 8"x1 O" FRP Enclosure with window. 910*E1FWL*EMR2

2 pole 30A 277V EMR. Controls a s i n g l e circuit

with a 2-pole electro-mechanical relay.

Controller in an 8"x1 O" FRP Enclosure with window. 91 O * E 1 F W L *SSR2

2 pole 30A 277V SSR. Controls a s i n g l e circuit

with a 2-pole solid-state relay.

DESCRIPTION MODEL CODE

1 0 0 ohm Platinum RTD with 1 0 foot S/S corrugated sheath. *RTD10CS

Modem communications option *MDM

lsolated 2-wire RS-485 communications option *485

RS-232 communications option *232

Red ar Green Pilot Light *ALR or *ALG

Stainless Steel 8 " x 1 0 " Enclosure with Window replace *E1 FWL

with * E 1 S W

DigiTrace™

Proven performance

and t e c h n o l o g y for

a l i of your heat

trace control

applications.

TIHE FIRST CHOICE FOR INSTALLERS AND SPECIFIERS


WORLDWIDE HEADOUARTERS GANADA
FOR OVER SO YEARS
Tyco Thermal Controls Tyco Thermal Controls

300 Constitution Orive

Menlo Park, CA 94025-í í 64


'tt¡CD / Flow ! Tyco Thermal
250 West St.

Trenton, Ontario
/ Control Controls
USA K8V 5S2

Tel: (800) 545-6258 For professional installation only. Must be installed according to manufacturer's Te!: (800) 545-6258

Fax: (650) 4 7 4 - 7 5 1 7 instructions and in compliance with all applicable codes and standards. Fax: (650) 4 7 4 - 7 5 1 7

H56864 ( 1 0 2 1 6 )
OigiTrace" RTD .. 200 �

RTD temperature s e n s o r for a m b i e n t s e n s i n g

The RTD-200 is a three-wire platinum RTD sensing. The RTD-200 comes with a 1/2" RTD in a typical ambient location. This also

(resistance temperature detector) typically NPT fitting that installs to the appropriate allows for splicing of RTD extension wire

used with electronic control systems that conduit box. This allows m o u n t i n g of the back to the controller.

require accurate ambient temperature

speeíñcanons

Sensor

Housing 3 1 6 stainless steel

Dimensions 3-in (7.6 mm) length, 1/4-in (6 mm) diameter

Accuracy ± 0.3ºF (± 0.2ºC)

Range -1 OOºF to 300ºF (-73ºC to 1 4 9 º C )

Resistance 1 0 0 ohms ± 0.25 ohm at OºC a=0.00385 ohms/ohm/°C

Extension wire

Wire size (each of three) 22AWG

Wire dielectric strength 600 V

Length 6 ft ( 1 . S m )

Outer jacket Fluoropolymer

M ax i m u m exposure temperature 300ºF ( 1 4 9 º C )

Sensor fitting 1/2-in ( 1 2 . 7 m m ) NPT with sealing washer and nut

Appmvals Approvals associated with control device. Not to be used in Division 1 areas.