Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                

BTL6 E500 Manual

Download as pdf or txt
Download as pdf or txt
You are on page 1of 8

BTL6-E500-M_ _ _ _-E2/E28-KA_ _/KE_ _/LA_ _

english

User's Guide

Balluff GmbH Schurwaldstrasse 9 73765 Neuhausen a.d.F. Germany Phone +49 7158 173-0 Fax +49 7158 5010 Servicehotline +49 7158 173-370 balluff@balluff.de www.balluff.com

BTL6-E500-M_ _ _ _-E2/E28-KA_ _/KE_ _/LA_ _ Micropulse Transducer - Rod Style

Contents 1 1.1 1.2 1.3 1.4 2 Safety Advisory .................... 2 Proper application ................. 2 Qualified personnel ............... 2 Use and inspection ............... 2 Scope ..................................... 2

Safety Advisory 1.4 Scope

Read this manual before installing and operating the Micropulse Transducer. 1.1 Proper application

This guide applies to the model BTL6-E...E2/E28-KA/KE/LA... Micropulse transducer. An overview of the various models can be found in section 6 Versions (indicated on part label) on page 7. Note: For special versions, which are indicated by an -SA_ _ _ designation in the part number, other technical data may apply (affecting calibration, wiring, dimensions etc.).

Function and Characteristics ..................... 3 2.1 Function ................................. 3 3 3.1 3.2 3.3 4 5 5.1 5.2 5.3 5.4 5.5 5.6 6 Installation ............................ 4 Installation variants ............... 5 Transducer, Installation ......... 5 Magnets, Installation ............. 6 Wiring .................................... 6 Startup .................................. 7 Check connections ................ 7 Turning on the system ........... 7 Check output values ............. 7 Check functionality ................ 7 Fault conditions ..................... 7 Noise elimination ................... 7

The BTL6 Micropulse transducer is intended to be installed in a machine or system. Together with a controller (PLC) it comprises a position measuring system and may only be used for this purpose. Unauthorized modifications and non-permitted usage will result in the loss of warranty and liability claims. 1.2 Qualified personnel

This guide is intended for specialized personnel who will perform the installation and setup of the system. 1.3 Use and inspection

Versions (indicated on part label) .............................. 7 6.1 Included in shipment ............. 7 6.2 Available stroke lengths and magnets .......................... 7 7 Accessories (order separately) ............................ 7 7.1 Magnets ................................. 7 8 Technical Data ...................... 8 8.1 Dimensions, weights, ambient conditions ................ 8 8.2 Supply voltage (external) ....... 8 8.3 Output signals ....................... 8 8.4 Overvoltage protection .......... 8

The relevant safety regulations must be followed when using the transducer system. In particular, steps must be taken to ensure that should the transducer system become defective no hazards to persons or property can result.

english

BTL6-E500-M_ _ _ _-E2/E28-KA_ _/KE_ _/LA_ _ Micropulse Transducer - Rod Style

2 2.1

Function and Characteristics Function The torsional wave arriving at the end of the waveguide is absorbed in the damping zone. The wave arriving at the beginning of the waveguide creates an electrical signal in the coil surrounding the waveguide. The propagation time of the wave is used to derive the position. This is output as a current value and has rising characteristics, Fig. 2-1. This process takes place with measuring high precision and repeatability within the stroke range defined as nominal stroke length. When there is no magnet located in the nominal stroke range, a signal is output as an error indication. At the rod end is a damping zone, within which no reliable signal is available, but which may be entered by the magnet. The electrical connection between the transducer, the controller and the power supply is via a cable or leads. Dimensions for installing the Micropulse transducer: Fig. 3-1.

The transducer contains a tubular waveguide enclosed by an outer stainless steel rod. A magnet attached to the moving member of the machine or to the cylinder piston is moved over the rod and its position constantly updated. The magnet defines the measured position on the waveguide. An internally generated INIT pulse interacts with the magnetic field of the magnet to generate a magnetostrictive torsional wave in the waveguide which propagates at ultrasonic speed.

Output signal

Position of the magnet: 1) in the nominal stroke range 2) no magnet located

Null point

End point

Fig. 2-1: Output signal with rising characteristics

english

BTL6-E500-M_ _ _ _-E2/E28-KA_ _/KE_ _/LA_ _ Micropulse Transducer - Rod Style

Installation mounting surface damping zone


nom. length = measuring range

-KA axial, centric


electrical connection

-1

magnet

13

O-ring support ring E2

10.2 mm thread M4 x 4/6 deep without thread

unusable area not included

E28 8 mm

-KE axial, eccentric max. bending radius (KA/KE) static flexed drag chain 3 x cable 7.5 x cable 10 x cable

13

O-ring support ring -LA axial with leads

12

The assured EMC properties can only be achieved when the BTL6-E500-M...-LA00,3 is completely enclosed in a grounded metal housing.

O-ring support ring Fig. 3-1: Micropulse Transducer BTL6-E500....E2/E28..., dimensions


4 english

BTL6-E500-M_ _ _ _-E2/E28-KA_ _/KE_ _/LA_ _ Micropulse Transducer - Rod Style

Installation (cont.)

Threaded stud DIN 914 M5x8

Fig. 3-2: Micropulse Transducer BTL6-E500....E2/E28..., installation

Threaded stud M5

3.1

Installation variants

Be sure that no strong electrical or magnetic fields are generated in the direct vicinity of the transducer. For horizontal mounting of transducer with stroke lengths greater than 500 mm, the pressure tube should be supported or attached at its end. Be sure that no strong electrical or magnetic fields are generated in the direct vicinity of the transducer. Fig. 3-3. 3.2 Transducer, Installation E2 a = non-magnetizable material b = magnet Fig. 3-3: Installation: at non-magnetizable material

B 13 mm

The smallest permissible distance between magnet ring and rod mounting surface is shown in Fig. 3-1. Essentially the BTL transducer can be attached in two ways in a toleranced hole 48 H8 , whereby sealing is accomplished using the O-ring and support ring supplied: The body of the transducer is fixed in place using 3 M5 threaded studs at 120 spacing.

E28 11 mm

a = magnetizable material b = magnet c = spacer of nonmagnetizable material

Fig. 3-4: Installation: at magnetizable material


english 5

BTL6-E500-M_ _ _ _-E2/E28-KA_ _/KE_ _/LA_ _ Micropulse Transducer - Rod Style

3 3.3

Installation (cont.) Magnets, Installation BTL-P-0814-GR-PAF

Wiring Note the following when making electrical connections:

A magnet is required for each transducer. This must be ordered separately. Fig. 3-5. For mounting the magnet we recommend to use non-magnetizable material. Fig. 3-1.

System and control cabinet must be at the same ground potential. To ensure the electromagnetic compatibility (EMC) which Balluff warrants with the CE Mark, the following instructions must be strictly followed. BTL transducer and the processor/control must be connected using shielded cable. Shielding: Copper filament braided, 85% coverage. The shield must be tied to the connector housing in the BKS connector Pin assignments can be found in Table 4-1.

BTL-P-1013-4R

BTL-P-1014-2R

BTL-P-1012-4R

Fig. 3-5: Spacer (optional) To avoid coupled noise, avoid proximity to high-current lines when routing cable between transducer, controller and power supply. Inductive coupled noise from AC harmonics (e.g., from phase controls) are especially critical, against which the cable shield offers very little protection. Max. cable length 20 m. Longer cables may be used if their construction, shielding and routing prevent noise interference. The cable must be routed strainrelieved.

BTL6-E... Output signal: 4...20 mA 0 V(output) GND DC 10...30 V

cable

GN green GY gray BU blue BN brown

Supply voltage (external):

If there is no magnet within the


BTL6-E500...E2/E28-KA...

4...20 mA 0V GND 10...30 V

GN GY
Controller with analog input

active stroke area, a current of 3.6 mA will be output as an error signal. Table 4-1: Wiring

BU BN

Fig. 4-1: BTL6-E500...E2/E28... with controller

english

BTL6-E500-M_ _ _ _-E2/E28-KA_ _/KE_ _/LA_ _ Micropulse Transducer - Rod Style

5 5.1

Startup Check connections 5.3 Check output values 5.5 Fault conditions

Although the connections are polarity reversal protected, components can be damaged by improper connections and overvoltage. Before you apply power, check the connections carefully. 5.2 Turning on the system

After replacing or repairing a transducer, it is advisable to verify the values for the start and end position of the magnet in manual mode. If values other* than those present before the replacement or repair are found, a correction should be made.
* Transducers are subject to modification or manufacturing tolerances.

When there is evidence that the transducer system is not operating properly, it should be taken out of service and guarded against unauthorized use. 5.6 Noise elimination

Note that the system may execute uncontrolled movements when first turned on or when the transducer is part of a closed-loop system whose parameters have not yet been set. Therefore make sure that no hazards could result from these situations.

5.4

Check functionality

The functionality of the transducer system and all its associated components should be regularly checked and recorded.

To avoid a equipotential bonding - a current flow - through the cable shield, we recommend that putting the control cabinet and the system in which the BTL6 is located at the same ground potential.

Versions (indicated on part label) Supply voltage 5 = DC 10...30 V Electr. connection: KA02: KE02: LA00,3: axial centric with 2 m cable axial eccentric with 2 m cable axial with 0.3 m long leads

BTL6-E500-M0450-E28-KA02
Micropulse Linear Transducer

thinner rod (if applicable) 8 = 8 mm Rod construction, pressure tube 10.2 mm Mounting: Plug flange Nom. length (4 digits): M = metric in mm Interface: E = 4...20 mA

6.1

Included in shipment

6.2

Transducer with short guide incl. O-ring and support ring.

Available stroke lengths and magnets


Stroke length Increment

Part No. BTL6...-E2-

50 ... 1500 mm 5 mm

BTL6...-E28- 50 ... 1016 mm 5 mm

Special lengths on request.

7 7.1

Accessories (order separately) Magnets Magnet BTL-P-1014-2R Dimensions Fig. 3-5 Weight approx. 10 g Housing anodized aluminum Operating temp. 40 C to +85 C Magnet BTL-P-GR-PAF Dimensions Fig. 3-5 Weight approx. 2 g Housing PA Operating temp. 40 C to +85 C

Magnet BTL-P-1013-4R, BTL-P-1012-4R Dimensions Fig. 3-5 Weight approx. 10 g Housing anodized aluminum Operating temp. 40 C to +85 C included in shipment Spacer 8 mm Material POM (Polyoxymethylene)

english

BTL6-E500-M_ _ _ _-E2/E28-KA_ _/KE_ _/LA_ _ Micropulse Transducer - Rod Style

Technical Data

Typical values at DC 24 V, room temperature and BTL6-E500-... with nominal length 500 mm and KA02. Ready to use, full accuracy reached after warm-up phase. With magnet BTL-P-1013-4R, BTL-P-1014-2R, BTL-P-1012-4R or BTL-P-0814-GR-PAF: Resolution typical 7 A, with input filter 27 KHz Sampling rate nom. length < 1300 mm nom. length > 1300 mm 1 kHz 0.5 kHz Humidity < 90 %, non-dewing Protection rating IEC 60529 IP 67 when closed up Shock loading 100 g/6 ms per IEC 60068-2-27 1 Continuous shock 50 g/2 ms per IEC 60068-2-29 1 Vibration 12 g, 10 to 2000 Hz per IEC 60068-2-6 1 (take care to avoid natural resonance of protective ) Pressure BTL6...E2 up to 350 bar BTL6...E28 up to 250 bar when installed in a hydraulic cylinder
1

8.3

Output signals 4 - 20 mA < 4 mA, typ. 3.6 mA

Position signal BTL6-E Error signal BTL6-E 8.4

Non-linearity: nom. length < 500 mm < 200 m nom. length > 500 mm < 0.04 % FS typ.0.02 %FS Temperature coefficient 8.1 typ. 25 m/K

Overvoltage protection

Dielectric strength with respect to housing BTL6-...E2-

500 V DC

Dimensions, weights, ambient conditions page 4 approx. 2.0 kg/m Stainless steel 4404 Stainless steel 4571
BTL6...E28 < 1016 mm 8 mm 0.9 mm

Dimensions Weight Housing Pressure tube nom. length Diameter

Individual specifications as per Balluff factory standard

8.2

Supply voltage (external)

Compatibility tests (EMC Directive): ISO 14982 Agricultural and Forestry Machinery ISO 13766 Earthmoving Machinery ISO 7637-1/2/3 Highway Vehicles EN 12895 Lift Trucks

approx. 200 kN/mm PTFE NBR Operating temp. -40 C to 85 C Storage temp. max. 90 C

E-Moduls Support ring O-Ring

The CE Mark verifies that our products meet the requirements of EC Directive 89/336/EEC (EMC Directive) and the EMC Law. Testing in our EMC Laboratory, which is accredited by DATech for Testing Electromagnetic Compatibility, has confirmed that Balluff products meet the EMC requirements of the following Generic Standards: EN 61000-6-4 (emission) EN 61000-6-2 (noise immunity)

Emission tests: RF Emission EN 55011 Group 1, Class A+B Noise immunity tests: Static electricity (ESD) EN 61000-4-2 Severity level 3 Electromagnetic fields (RFI) EN 61000-4-3 Severity level 3 Fast transients (Burst) EN 61000-4-4 Severity level 3 Surge EN 61000-4-5 Severity level 2 Line-induced noise induced by high-frequency fields EN 61000-4-6 Severity level 3 Magnetic fields EN 61000-4-8 Severity level 4

EN 50121-3-2 Rail applications ISO 11452-5 Electromagnetic field HF, 200 V/m Restrictions: External protection measures must be taken: EN 150121-3-2: (Burst 2kV per EN 61000-4-4): ISO 7637-2 Pulse 5a External buffering measures must be taken: Fluctuations and interruptions in the supply (EN 50155)

english

No. 853 589 -726 E 00.000000 Edition 0707; specifications subject to changes.

BTL6...E2 < 1500 mm 10.2 mm Wall thickness 2 mm

Regulated supply voltage DC 10 ... 30 V < 0.2 Vss Ripple Current draw typical 2 W Inrush typical (Sampling rate 1 KHz) < 80 mA at 24 V DC Overvoltage 36 V Polarity reversal protection max. 40 V

You might also like