SVC ref3
SVC ref3
ABSTRACT because the location is far from the generator point. Further,
the flow of real power in transmission lines reduces the supply
In present day restructured power systems, increased of reactive power demand of the system and creates voltage
transactions often lead to the situations where the system no problems. Hence, the reactive power compensators are used to
longer remains in secure operating condition. To overcome maintain the voltage profile and thereby to improve the
such undesirable situation the Flexible AC transmission performances of the power system [4].
system (FACTS) controllers can be placed in a power system,
which are able to provide fast and flexible control of voltage The Flexible Alternating Current Transmission Systems
magnitude, active and reactive powers and to improve voltage (FACTS) devices are popularly used for improving the
security and stability. As investment cost of FACTS overall performance of a power system. FACTS devices are
controllers is very high, these devices must be placed the solid state converters having capability of improving
optimally in a power system. Static Var Compensators (SVC) power transmission capacity, voltage profile, enhancing
is a shunt FACTS device that can be used for improvement of power system stability and security [5]. There are many
voltage profile in a power system. For optimal placement of reactive compensation devices used for reactive power
SVC, this paper proposes a method that considers single line compensation, each of which is having their own advantages
outage contingencies. On the basis of Voltage Performance and disadvantages. So it is necessary to select the most
Index two most critical contingencies are considered for favorable device for compensation and placing it optimally
searching the optimal location of SVC. The impact of SVC at [1].
selected optimal locations is evaluated and compared for
varying load condition of the power system. The criteria for A few research works has been done on FACTS controllers on
selection of optimal location consider improvement of the improving the performance of power system by locating it
voltage profile and reduction in the system losses in a power optimally. F.D. Gailana in [6] proposes the comparison of
system. The effectiveness of the proposed method is various FACTS devices on behavior of power system. In [7]
demonstrated on a standard IEEE 30-bus system. Gyugyi proposes the investment cost of FACTS controllers
General Terms and their impact on power generation cost. The ref. [8]
Contingency analysis, SVC, Line Losses proposes a genetic algorithm based approach to determine the
suitable types of FCATS devices and their optimal locations.
In [9, 10], new SVC (a shunt compensation device) models
Keywords and their implementation in Newton-Raphson load flow and
Load flow analysis, FACTS devices, SVC, Voltage optimal power flow algorithms has been is developed. The
Performance Index, and Voltage Profile. ref. [10] focuses on the placement of SVC to maintain the
voltage profile of a power system under different
contingencies. SVC is placed for improving the voltage
profile while reducing the real power losses in the system.
1. INTRODUCTION Optimal location of SVC for voltage security enhancement
Modern electric power system is facing many challenges due using MOPSO is discussed in [11].
to the increase complexity in their operation and structure. In
recent years, the stable operation of power systems has been a
great concern for power system operators because of the
2. FACTS DEVICES
The FACTS devices have become very popular for improving
limited transmission capacity of restructured power system
the overall performance of a power system. FACTS devices
[1]. The main reason for occurring voltage collapse is when
may series, shunt or combination of series-series or series-
the power system is heavily loaded, faulted and/or having
shunt deices. These devices provide direct and flexible control
shortage of reactive power [2]. The voltage collapse problem
while transferring the power in steady state condition and
is closely related to the planning of reactive power
reduces the power flows while the high speed commands
particularly when the contingencies are considered [3]. Thus,
gives the qualities to improve the dynamic stability. The
the reactive power planning is one of the most crucial
optimal location of FCATS devices thus allow to increase the
problems of a power system. When contingencies like line
system loadability and the security margin [13].
outage or generator outages occur, sometimes the power
system becomes insecure from the viewpoint of bus voltage/
In power system FACTS devices are used to achieve several
loading of transmission lines. During the outage conditions of
goals. In a meshed network when steady state condition
some critical lines, generators are capable of supplying
arises, the FACTS device supplies or absorbs reactive power.
limited reactive power even sometimes the supplied reactive
Thus, it increases or reduces voltage and controls the phase
power cannot be used to fulfill the requirement of the network
angle as well as the series impedance to permit the
44
International Journal of Computer Applications (0975 – 8887)
Volume 32– No.6, October 2011
transmission line to operate near to their thermal limits and 3.2 Modeling of SVC
reduces the line flows. FACTS devices can be used for short Earlier the SVC model used for power flow analysis
circuits conditions as they limits the short circuit currents. considered the SVC as a generator behind an inductive
reactance while operating within limits. This reactance
As shown in Fig. 1, the active power transmitted by a represents the SVC voltage regulation characteristic, i.e.,
transmission line between bus i and bus j can be calculated as SVC's slope Xst [2]. A simpler representation assumes that the
SVC slope is zero for voltage regulation. This assumption
𝑉𝑖 𝑉𝑗
𝑃𝑖𝑗 = sin 𝛿𝑖𝑗 may be acceptable as long as the Static Var Compensator is
𝑋𝑖𝑗 operating within limits, but if the SVC operates close to its
reactive limits it may lead to gross errors [5]. The voltage-
Where 𝑉𝑖 and 𝑉𝑗 are the voltages at bus i and j ; 𝑋𝑖𝑗 is the current characteristic of SVC is shown in Fig.2. The upper
reactance of the line ; 𝛿𝑖𝑗 is the angle between 𝑉𝑖 and 𝑉𝑗 . characteristic of the system are observed when low loading
conditions are considered. If the slope is taken to be zero, then
the generator will violate its minimum reactive limit,
point 𝐵𝑋 𝑆𝐿=0 . However, the generator will operate well within
bus i bus j limits if the SVC slope is taken into consideration which is
shown by point B [9, 12].
Vi Xij Vj
45
International Journal of Computer Applications (0975 – 8887)
Volume 32– No.6, October 2011
While implementing this model for load flow analysis, it may production or absorption reactive power capabilities will be a
require the Jacobian reordering and re-dimensioning during function of the nodal voltage at the SVC point of connection
the iterative solution. Also it becomes necessary to verify to get the voltage 1.0 p.u.
whether or not the SVC can return to operate inside the limits.
While operating outside the limits, it is important to model the 4.2 Transmission Losses Minimization
Static Var Compensator as a susceptance and not as a The proposed algorithm also considers the transmission loss
generator set at its violated limit Qvoilated. If it is not set within minimization for selecting optimal location of SVC.
the violated limits it will lead to inaccurate results. The reason Transmission loss minimization is responsible for the
is that the amount of reactive power drawn by the SVC is redistribution of the reactive power throughout the network,
given by the product of the fixed susceptance, Bfixed and the which in turn induces changes in the active power generated
nodal voltage magnitude Vk. A Vk is a function of network by the slack bus. It has been observed that if the network
operating conditions as the amount of reactive power drawn losses were reduced in only 0.15%, a more uniform voltage
by the fixed susceptance model may differ from the reactive profile was observed at all the buses of a power system. The
power drawn by the generator model, i.e. real and reactive power losses can be calculated using (6) and
(7).
𝑄𝑣𝑜𝑖𝑙𝑎𝑡𝑒𝑑 ≠ −𝐵𝑓𝑖𝑥𝑒𝑑 𝑉𝑘2 (1)
𝑛𝑙
𝑃𝐿 = 𝑘=1 𝑔𝑘 [ 𝑉𝑖2 + 𝑉𝑗2 - 2 𝑉𝑖 𝑉𝑗 cos( 𝛿𝑖 - 𝛿𝑗 )] (6)
𝑛𝑙
3.3 SVC Load Flow Models
The circuit shown in Fig. 3 is used to derive the SVC's 𝑄𝐿 = 𝑔𝑘 [𝑉𝑖2 + 𝑉𝑗2 − 2𝑉𝑖 𝑉𝑗 sin(𝛿𝑗 − 𝛿𝑗 )] (7)
nonlinear power equations and the linearised equations 𝑘=1
46
International Journal of Computer Applications (0975 – 8887)
Volume 32– No.6, October 2011
9. Find out the optimal location for the placement by SVC at bus 5 because it is a PV bus so the remaining two
comparing the voltage profile as obtained in steps 6 -8. buses 7 and 30 are considered for the optimal location of
SVC. The voltage profiles for the line outage 5 with SVC
6. CASE STUDIES placed at bus 30 and bus 7 are shown in Table 3. The real and
The proposed algorithm for optimal placement and sizing of reactive power losses and SVC rating are shown in Table 4. In
SVC has been implemented on IEEE 30 bus system [15]. This this line outage condition also the optimal location for the
system comprises of one slack bus, 5 PV buses, 24 PQ buses placement of SVC is found to be bus 30.
and 41lines. For optimal placement of SVC, single line outage
contingencies are simulated in the sample power system. The 6.1.3 Impact of SVC at bus7 and 30 during load
severity of a contingency is evaluated by using the VPI [16] variation and line outage 36
as given by (9). It has been observed that when the load at various buses of the
IEEE 30 bus system is varied randomly in wide range (.± 30%
𝑁𝐵
VPI = 𝑖=1(∆|𝑉𝑖| /∆ | 𝑉𝑖𝑚𝑎𝑥 |)2m (9) ), the voltage profile of all the buses was good with SVC
connected at bus 30. The lowest voltage which appears on bus
Where ∆ 𝑉𝑖 is the difference between the voltage magnitude 26 is 0.9948p.u. The voltage deviation with SVC at bus 30 is
for line outage condition and base case voltage magnitude; 0.0046 p.u. but the rating of SVC is -0.1106 which is higher
∆|𝑉𝑖𝑚𝑎𝑥 | is the value set by the utility engineers indicating as compared to that of contingency case. When the losses
how much they wish to limit a bus voltage from changing on were considered then it was observed that the losses at bus 30
outage case. was lower than at bus 7. Table 5 and Table 6 show the voltage
profile and performance for load variation on IEEE 30 bus
It has been observed that NR load flow converges for 37 line system.
outages out of 41 line outages. The VPI gives the idea about
severity of a contingency. On the basis of VPI, the ranking 6.1.4 Impact of SVC at bus 7 during load
order of severe contingencies in descending order is 36, 5, 9, variation and line outage 5
37, 26, 11 and so on. In this paper two most critical This case shows the effect of connecting SVC at bus 7 and 30
contingencies i.e. outage of line no. 36 and 5 have been one by one when the load is varied (± 30%) and outage of line
considered for the placement of SVC. 5 occurs. The voltage profile observed on all the buses was
good but not as good as the first case when the SVC was
6.1 Line Outages Contingency connected at bus 30. The voltage deviation is zero but the
The first case considered for placement of SVC is the line power losses are much more comparing when the load is
outage 36, which provides highest value of VPI and hence is varied at bus 30. The Table 7 and Table 8 show the voltage
the most severe contingency. To place an SVC optimally, this profile and performance observed for the system.
line outage condition has been analyzed in detail.
6.2 Comparison of both the cases for Line
6.1.1 Impact of SVC at bus 30 with line outage 36
It is clear from Table 1 that the voltages at bus 30, 29, 27 and
outage 36 and Line outage 5
When the line outages cases for the lines 36 and 5 were
26 are very low. These 4 buses are considered one by one for considered it was observed that the voltage profile was
selecting optimal location of SVC. But due to limited space, maintained when SVC was connected at bus 30. For line
the voltage profiles for line outage 36 with SVC placed at bus outage 36 the voltage profile was better than that for line
nos. 30 and 29 are shown in Table1. The developed load flow outage 5, when SVC was connected at bus 7. The real and
program also calculates the rating of SVC to maintain the reactive losses, rating and voltage deviations for both the
voltage magnitude 1.0 p.u. at the connected bus. Table 2 cases were analyzed for system. The voltage deviation for line
outage 36 when SVC placed at bus 30 was 0.0493 p.u. and the
depicts the performance of the power system with and without
real losses were 0.1272 and reactive losses were 0.2570 which
SVC. It includes rating of SVC to maintain the voltage is smaller than when the SVC is placed at bus 7. So in both
magnitude 1 p.u., voltage deviations, and real and reactive the cases the bus 30 is the optimal location to place SVC to
power losses at the connected bus. It was found that the size maintain the voltage profile of the power system.
of SVC at bus 29 was slightly smaller than at bus 30 but the 6.3 Comparison for the cases when load is
voltage deviation, the real and reactive power losses at bus 29
varied randomly
was much greater than those with SVC at bus 30. The voltage When the load variation is done randomly, the voltage profile
deviation at bus 30 is 0.0653p.u. which is minimum of all the of the buses with SVC connected at bus 30 and at bus 7 was
four cases. Hence, the optimal location for the placement of computed. It was found that the voltages at bus 29 and 30
SVC may be bus 30 as far as the most critical line outage 36 is when SVC is placed at bus 7 were not good i.e.0.9952, 0.9796
concerned. p.u. But when these results are compared with the other case
when SVC is connected at bus 30 the voltage are much
6.1.2 Impact of SVC at bus 7 with line outage 5 improved as 1.011 and 1.00 p.u. the losses real and reactive
The voltage profile for line outage 5 is shown in Table 3. It
were improved as for SVC at bus 30 it was 17.2360MW and
has been observed from table 3 that voltages at bus 7, 5 and
41.7615MVAR which are much less than that when SVC is
30 was very low. So, to place the SVC optimally, this line
placed at bus 7. The Table 9 and Figure 4 show and compare
outage contingency is also analyzed. As we cannot connect
47
International Journal of Computer Applications (0975 – 8887)
Volume 32– No.6, October 2011
the voltage profile of the system with SVC at bus 7 and bus 0.8884
27 0.9928 0.9891
30. From these, bus 30 is found to be the optimal location for
SVC to improve voltage profile and to reduce losses, 28 1.0137 1.0158 1.0158
29 0.8651 0.991 1
7. CONCLUSION 0.8517
30 1 0.9748
In this paper, a method for optimal placement and sizing of
SVC has been proposed for improving the voltage profile and
reducing the system losses in a power system. On the basis of
VPI two most critical contingencies and two optimal
locations of SVC were selected. With SVC connected on the Table 2 Performance of IEEE 30-Bus System With and
selected buses, their impact on power system under single line Without SVC for line outage 36
outages and random load variation in wide range has been Without
analyzed and compared for the selection of optimal location Bus Number SVC With SVC
of SVC for a power system. Though the proposed approach
at 30 at 29
has been implemented on IEEE 30 bus system, the same can SVC Rating
be implemented on practical power systems as well. (p.u.) - -0.1206 -0.1158
Real Power
Table 1 Voltage profile of IEEE 30 bus system with and Losses(p.u.) 0.179 0.1381 0.1383
without SVC for line outage 36
Line outage 36 Reactive Power 0.4877 0.2789 0.2795
Bus Without With SVC With SVC
number SVC at bus 30 at bus 29
1 1.06 1.06 1.06
2 1.043 1.043 1.043
3 1.0186 1.021 1.021
4 1.0093 1.0123 1.0122
Table 3 Voltage profile on IEEE 30 bus system with SVC
5 1.01 1.01 1.01 for line outage 5
Line outage 5
6 1.0095 1.0122 1.0122
1.0019 Bus Without SVC With SVC at With SVC at
7 1.0036 1.0035 Number bus 30 bus 7
8 1.01 1.01 1.01 1.06
1 1.06 1.06
9 1.0374 1.0513 1.0511 1.043
2 1.043 1.043
10 1.0184 1.0457 1.0452 1.0109
3 1.0154 1.0157
11 1.082 1.082 1.082 1.0009
4 1.0064 1.0067
12 1.0481 1.058 1.0578 0.9318
5 1.01 1.01
13 1.071 1.071 1.071 0.9988
1.0292 6 1.0071 1.0076
14 1.0427 1.0424
0.9596
1.0196 7 0.9964 1
15 1.0364 1.036
1.01
16 1.0282 1.0455 1.0452 8 1.01 1.01
1.0434
17 1.0159 1.0403 1.0399 9 1.0481 1.0481
1.0358
18 1.0068 1.0275 1.0271 10 1.0408 1.0407
1.082
19 1.0024 1.0254 1.025 11 1.082 1.082
1.0056 1.0523
20 1.0297 1.0293 12 1.0554 1.0553
1.0022 1.071
21 1.0319 1.0314 13 1.071 1.071
22 1.0017 1.032 1.0314 1.0369
14 1.0404 1.0403
23 0.9957 1.0221 1.0214 1.0315
15 1.0353 1.0351
24 0.9729 1.0121 1.0109 1.0379
16 1.0418 1.0418
25 0.9135 0.9925 0.9898 1.031
17 1.0357 1.0356
26 0.8938 0.9744 0.9716 1.0207
18 1.0251 1.0249
48
International Journal of Computer Applications (0975 – 8887)
Volume 32– No.6, October 2011
49
International Journal of Computer Applications (0975 – 8887)
Volume 32– No.6, October 2011
1.55
1.45
1.35
1.25 SVC at bus 7
SVC at bus 30
1.15
1.05
0.95
1 3 5 7 9 11 13 15 17 19 21 23 25 27 29
50
International Journal of Computer Applications (0975 – 8887)
Volume 32– No.6, October 2011
51