Siemens Draft Range Pressure Installation Recommendations ADSITRPDS3-1r1
Siemens Draft Range Pressure Installation Recommendations ADSITRPDS3-1r1
Siemens Draft Range Pressure Installation Recommendations ADSITRPDS3-1r1
APPLICATION DATA
ADSITRPDS3-1
Rev 1 May 2005
Venturi Tube
Pitot Tube
Orifice Plate
Boilers Air flow into a boiler is measured with an averaging pitot tube or venturi to control fuel-air ratio. Waste gases that are a result of boiler operation can also be measured with a pitot tube or averaging pitot tube. Furnaces Fuel or cover gas flow into a furnace can be measured with any of the devices mentioned, selection depending upon the accuracy required.
Pressure Drop Measurement of the DP across devices such as air heaters, precipitators, scrubbers, and other filter-type elements is performed to determine when they require service. An example of an application follows: Boilers To maximize efficiency, we measure the pressure drop across parts of a boiler that can build up soot or ash (e.g., air heaters, scrubbers, economizers, and precipitators) to determine when maintenance is needed.
DPT DPT DPT
Pressure It is often necessary to measure the gauge pressure in devices such as boilers, heat treat furnaces, glass furnaces, reheat furnaces, and soaking pits. Several applications follow: Boilers To assure efficient operation and complete combustion, we measure the gauge pressure in the interior of a boiler furnace in order to keep it slightly negative (typically -0.25" H2O) by controlling the boiler inlet or outlet dampers. Furnaces A slight positive pressure (typically +0.1" H2O) is required in most thermal market furnaces. This assures good fuel economy and efficient use of cover gas through control of the damper in the furnace stack.
PT Boiler Furnace
PT
Furnace Stack
+ +
+ +
MG00362a
Diaphragm Plane
Diaphragm Plane
MG00362a
Zero-shift is easily eliminated either during bench test or after installation using the magnetic pushbuttons on the SITRANS P 1. During a bench test, the transmitter can be oriented in its final mounting position and then calibrated. If the transmitter is already installed, simply correct for Zero position error using the
PDM software and a HART-based hand-held are options available for transmitter calibration and configuration
pushbuttons to select transmitter Operating Mode 7 (Set Zero Position Correction). Zero correction must be performed with a stable zero differential across the transmitter pressure inputs. A draft transmitter must be rigidly mounted. A change in transmitter orientation due to temperature variations, bumps, vibration, etc. can cause a zero-shift; see the figure below. Note that even a minimal 0.001" H2O shift represents a 0.25% error at a span of 0.4" H2O. For this reason, use the supplied bracket to mount the transmitter to a wall, I-beam, or pipe that is not likely to vibrate or to be bumped and will remain stable in spite of ambient temperature changes. A zero-shift error introduced by transmitter orientation can easily be zeroed out, but the varying effects of an unstable mounting can not be corrected by recalibrating the transmitter.
+
MG010000
Stable Mounting
Unstable Mounting
Impulse Piping Measurement errors can occur when good practice is not followed during impulse pipe installation. For example, impulse pipe must be installed such that no unwanted liquid or gas can accumulate in the transmitter process flange cavity. In draft pressure applications, the process fluid is usually air or gas so care must be taken to prevent any accumulation of liquid (e.g., condensate) in the impulse piping to the transmitter. Always mount the transmitter above the process connections and slope all horizontal runs to the process downward at one inch per foot. This will prevent liquid from accumulating at the transmitter.
Flow
When the process fluid is a liquid, mount the transmitter below the process connections with all horizontal runs to the process sloped upward at one inch per foot. This will prevent air or gas from accumulating at the transmitter.
Flow
Gauge Pressure Measurement Often draft pressure measurements will be straight gauge pressure applications as opposed to true DP applications. In these situations the Low Pressure (LP) port of the differential transmitter must be vented to atmosphere. This should not be done by simply leaving the port unconnected because air flowing past the open LP port (from heating and cooling fans, natural wind currents, traffic, etc.) will cause a slight vacuum resulting in measurement errors. The solution is to pipe the LP port as shown below. Vent the open end of this pipe into a still air chamber which is vented to atmosphere. The still air chamber can be as simple as a one gallon milk jug. Another solution is to put a porous sponge, like that used for an air filter, around the end of the LP pipe. Other techniques will also work. The goal is to have a stable reference to atmosphere that is unaffected by air currents.
MG010000
MG010000
Capsule Heating Uneven radiant heating can cause draft pressure transmitter errors. The SITRANS P 7MF4433 is a twodiaphragm, balanced, fluid filled system. The fill has a known thermal expansion coefficient that is included in transmitter compensation. However, if one side of the capsule is heated differently than the other, measurement errors will occur; see the following two figures.
+
+ +
MG010000
Identify and protect the transmitter from possible sources of radiant heating when selecting a mounting location for a draft transmitter. These sources include boilers, furnaces, heaters, ovens and even the sun. If the source of heat can not be eliminated, mount the transmitter so that the capsule is evenly heated by the source, as shown in the above left figure. Accuracy A transmitter can be ranged using your plant-standard pressure source and transmitter Operating Modes 2 and 3 (Set Zero and Set Full Scale respectively) to set up zero and full scale. Alternatively, range the transmitter using the blind method and Operating Modes 5 and 6 (Set Zero Blind and Set Full Scale Blind respectively). Both procedures are described in the Users Manual 2. If the accuracy of the plantstandard pressure source is insufficient, the blind method may offer optimal accuracy. Static Pressure Effects In some applications, very low pressures are measured at high static pressures. Maximum performance can be obtained by calibrating the transmitter to remove any zero-shift due to mounting position and static pressure at the same time. This should be done with the transmitter in its final position, with the static pressure applied, and with zero DP across the transmitter.
Refer to UMSITRPDS3-1, Users Manual SITRANS P, Series DSIII Transmitter for Pressure, Differential Pressure, Flanged Level, and Absolute Pressure Model 7MF4*33-
CONTACT INFORMATION Telephone Fax E-mail Hours of Operation Public Internet Site Repair Service +1 800 569 2132, option 2 +1 215 283 6358 mailto:PItechsupp@sea.siemens.com 8 a.m. to 4:45 p.m. eastern time Monday Friday (except holidays) www.sea.siemens.com/ia +1 215 646 7400 extension 3187
NORTH AMERICA
Outside of North America see the Siemens web site at www.sea.siemens.com/ia; locate Customer Support Process Instrumentation and click the Contact Tech Support link to access the Global Support link.
Siemens Energy & Automation, Inc. assumes no liability for errors or omissions in this document or for the application and use of information in this document. The information herein is subject to change without notice. Customers are urged to consult a Siemens Energy & Automation, Process Industries Division sales representative to confirm availability and specifications. Copyright 2005, Siemens Energy & Automation, Inc.