GEN Series
Fire-fighting booster sets EN 12845
Horizontal Centrifugal electric pumps FHF and SHF series
equipped with high efficiency PLM motors
50 Hz
Lowara
WEB 11-2009
Lowara
CONTENTS
12
18
27
29
Range ...............................................................................................................................................
33
45
47
51
57
61
71
Lowara
CONTENTS
83
85
Range ...............................................................................................................................................
88
98
99
103
107
111
117
127
Accessories ..................................................................................................................................
142
Lowara
GEN SERIES OF BOOSTER SETS
GENERAL INTRODUCTION PRODUCT DESCRIPTION
The GEN booster sets are built in conformity with EN12845 for automatic sprinkler systems and with UNI10779 for
hydrant systems.
In accordance with the above standards, all the main components of the booster set are factory connected and
assembled.
The configuration of the booster set depends on the number of pumps installed and on the type of electric motor or
diesel engine, consistently with the type of supply chosen for the fire-fighting system from among those described in
the standard. The water supply can be single, superior, duplicated or combined. Two main service pumps, one backing
up the other, are normally installed for fire-fighting systems. The choice of electric motors or diesel engines depends on
the level of reliability required from the system. In practice, fire-fighting booster sets have one electric service pump and
one diesel service pump.
Point 10.2 of EN 12845 states that for superior or duplicate water supplies, and if more than one pump is installed, no
more than one service pump can be driven by the electric motor.
This concept means that mixed assemblies, comprising electric or diesel pumps, have to be installed.
This does not mean that it is not possible to have two electric pumps, one backing up the other, if the ascertained fire
risk is low (single supplies) or if a diesel generator is already incorporated in the system.
The Lowara GEN series of booster sets are therefore configured according to system requirements and initial
considerations. They are also factory tested and comprise the following:
One or two horizontal or vertical service pumps with the same hydraulic performance level, driven by
an electric motor.
Two horizontal service pumps with the same hydraulic performance level, driven by an electric motor
and a diesel engine.
A horizontal service pump driven by a diesel engine.
The booster set is built and completed with the following main components:
A Lowara SV series jockey electric pump (if required), controlled by an electric panel in the automatic
mode. The jockey pump is automatically started and stopped by its pressure switch in order to restore
supply pressure. This prevents the service pumps from starting and activating the main alarms.
A control panel for each service pump.
Two pressure switches for each service pump (if the first fails, the second repeats permission for the
pump to start).
On the discharge side of each service pump there is a on-off valve, a check valve and a tap for connection
to the priming circuit for suction lift installations. Moreover, if the service pump works with a closed
discharge line, a water recirculation tap has been applied to the pump body in order to prevent the
pump from overheating.
Discharge manifold connected to each service pump, fitted with a weld-on flange for connection to
the system.
Single base containing all the booster set components within a compact structure and ready for
installation.
To complete the pump station as requested by the standard, the GEN series of booster sets are fitted with the
following accessories :
Suction side kit.
Flow meter.
Alarm panel.
If diesel engine pump is installed, set of spare parts for diesel engines.
Priming tank with accessories (for suction lift installations).
24L diaphragm tanks.
Lowara
IDENTIFICA
TION CODES
IDENTIFICATION
GEN
CP
Options:
CP = Clean contacts in the panel.
IP55 = IP55 grade panels.
KV = Voltmeter kit.
Electric jockey pump description.
FHF : Electric service pump description.
SHF : Electric service pump description.
0 = Without jockey pump.
1 = With jockey pump.
1 = 1 Service pump.
2 = 2 Service pumps.
X = Automatic shut-off.
B = Basic version.
A = Version with periodic self-test function.
Electric service pump start-up
D = Direct start-up (Up to 22 kW included).
Y = Star/Delta start-up.
I = Impedance start-up.
GEN Fire-Fighting series.
GRU
REFERENCE ST
ANDARDS
STANDARDS
The Lowara fire-fighting booster sets are EC certified in conformity with the following directives:
- Machine Directive 98/37/EC.
- Low Voltage Directive 2006/95/CE.
- Electromagnetic Compatibility Directive 89/336/EEC and subsequent modifications.
The electric pump performance is declared to be in accordance with the following standard:
ISO 9906-A Rotodynamic pumps hydraulic performance tests and acceptation criteria.
The fire-fighting booster sets conform to the European fire-fighting Standard EN 12845-2009.
The automatic shut-off versions also conform to the UNI 10779 Italian Standard for hydrant systems.
Lowara
GEN SERIES OF BOOSTER SETS
FUNCTIONAL DIAGRAM FOR POSITIVE SUCTION HEAD INST
ALLA
TIONS
INSTALLA
ALLATIONS
Lowara
GEN SERIES OF BOOSTER SETS
MECHANICAL CONFIGURA
TION
CONFIGURATION
DENOMINAZIONE COMPONENTI
GRUPPI DIESEL EN12845
REF.
1
2
3
4
5
6
7
8
DESCRIPTION
REF.
9
10
11
12
13
14
15
16
DESCRIPTION
Lowara
CHARACTERISTIC
S OF THE PUMPS USED IN THE GEN SERIES
CHARACTERISTICS
OF BOOSTER SETS
SV2, 4, 8 ELECTRIC PUMPS (JOCKEY PUMP)
Multistage centrifugal vertical electric pumps. All
metal parts in contact with pumped liquid are made
of stainless steel.
Version F: round flanges, in-line discharge and
suction ports, AISI 304 (Standard version).
Version N: round flanges, in-line discharge and
suction ports, AISI 316 (Available on request).
Reduced axial thrusts enable the use of off-the-shelf
standard motors
motors. The performance levels
of Lowara PLM surface motors lie within
what is usually referred to as efficiency
class 1.
Lowara
MAIN COMPONENTS
FIRE-FIGHTING SETS WITH HORIZONT
AL ELECTRIC PUMPS
HORIZONTAL
On/off valves on the delivery side of each pump, ball valves with lever handle for diameters up to and including
1" 1/2 butterfly valve with lever handle from DN50 to DN100 diameter, butterfly valve with handwheel and
reduction manual gear for DN125 diameter and above. Device for monitoring ON/OFF status included. Electrical
connections by customer.
(Lockable kit available on request).
Recirculation device for each service pump.
The re-circulation device allows a minimum capacity in order to prevent the pump overheating when working
with closed delivery. It includes the activation pressure switch for the alarms of the pumps running, the test valve
for checking the seal of the check valves, the couplings for any connecting pipes to the priming tank in the case
of suction lift installation. The connection of each re-circulation to the suction tank or the priming tank is to be
seen to by the person installing the equipment.
Pressure gauge on the delivery side of each service pump between check valve and on/off valve.
Inspectable check valve on the discharge side of each pump. Threaded coupling for diameters up to 1"1/2
included, flanged coupling for larger sizes.
Painted iron delivery manifold (PN 16) and threaded stubs with relative caps for connecting any 24 litre
membrane tanks. Blind and welding zinc-plated flanges.
Two start-up pressure switches for every service pump.
For the electric service pumps, start-up takes place through the pressure switch, but it must be manually stopped
using the key-operated selector switch on the panel (excluding the version with automatic shut-off). For the
electric jockey pump, if present, both start-up and stopping are determined by the pressure switch.
Start-up pressure switch circuit for the service pump, including connecting pipes for the delivery manifold,
recirculation circuit.
This circuit includes on/off valve, a non-return valve, a discharge valve and various pipe fittings. The
configuration of the circuit allows the pressure switch to intervene also when the relative on/off valve is closed.
Various pipe fittings (copper, zinc-plated steel).
Base made of bent sheet or structural iron with epoxy powder painting RAL 5010.
Control panel frame made of structural iron with epoxy powder painting RAL 5010.
Electric panel for each electric service pump.
Starting: Direct (DOL) up to and including 22 kW, star/triangle from 30 kW up.
A panel mounting bracket kit for floor mounting and a jockey pump kit can be supplied on request.
The control panels for the electric pumps up to 55 kW power supply are fixed on bracket. For higher powers, the
control panels for electric pump service are floor mounted, instead the jockey electric pump panel is wall mounted
fixed.
10
Lowara
SUCTION KIT
The set is supplied with its suction side free from components.
On request, for the SUCTION side of the individual service pump, TWO versions are available according to the
systems installation type:
T KIT
POSITIVE SUCTION HEAD and SUCTION LIF
LIFT
Kit suitable for positive suction head or suction lift installation.
The suction side of the individual pump includes:
- Anti-vibration joint to attach to the pump inlet.
- Eccentric cone or flanged stub pipe.
- Vacuum pressure gauge.
- On/off butterfly valve with lever handle for diameters up to DN100, butterfly valve with handwheel and
reduction manual gear for DN125 and higher. Device for monitoring ON/OFF status included.
Electrical connections by customer.
(Valve lock kit available on request).
- Weld-on flange.
Conforming to the requirements of the EN 12845 Standard (chapter 10.5 and chapter 10.6).
These requirements are connected with the type of installation and the measurement of the piping sections.
(see tables on pages 124-127).
OTHER VERSIONS
As well as the basic GENDB versions (direct start-up), GENYB (star triangle start-up), GENIB (impedance start-up),
the following versions are also available:
GEN..A
With periodic self-test function.
There is a self-test circuit including a weekly clock on the electric panel of each electric service pump. For the time
and date pre-set, the pump is started up and kept functioning for 1 minute. During this interval the check circuit
checks that the pressure in the re-circulation circuit closes the pressure switch contact of the pump which is
running. In the case of irregularities, the relative auxiliary self-test alarm relay available for remote signalling is
activated and memorised.
The EN12845 Standard does not provide for the presence of a self-test circuit but asks for periodic checks to be
carried out by the user, hence the periodic self-test function cannot substitute the above checks.
GEN..X (For fire hydrant systems, UNI 10779)
With automatic shut-off.
There is an automatic shut-off circuit on the electric panel of each electric service pump.
In certain situations, it allows automatic shut-off once the system pressure has been kept at higher values than the
start-up values for at least twenty minutes.
The self-test and automatic shut-off versions are available for each type of GEND.., GENY.., GENI.. start-up and in
combination between them (See identification codes page).
11
Lowara
ACCES
SORIES A
VAILABLE ON REQUEST
ACCESSORIES
AV
Protection against dry running for the electric jockey pump in
one of the following versions:
- Float switch, in case of suction lift.
- Probes kit in case of suction lift (needs optional probe module
in the electric jockey pump).
- Minimum pressure switch, in case of positive suction head.
Electric panel for remote status and alarm monitoring of one or
two Lowara pumps installed in GEN fire-fighting booster sets,
according to EN12845.
In the electric service pump mode, the following conditions are
visualised: Motor powered, pump start-up request, pump
running, failure to start.
In the diesel engine service pump mode, the following
conditions are visualised: switch in non-automatic position,
QAL12845 Panel
diesel engine fails to start after 6 attempts, pump running,
controller failure.
Additionally: minimum suction tank or fuel level, minimum
priming tank level, on-off valve on suction and discharge side
not fully open.
All the above conditions, required by EN12845, are visualised
with signal LEDs and buzzers.
A buzzer alarm reset button and LED tester button are
included.
The control unit is also fitted out to signal the following
general alarms, if present:
- General alarm for incorrect electrical connection in the
exchange contacts of: flow meter circuit valve, discharge
pump, jockey pump status.
- Fault in electrical connection in the exchange contact relative
to panel 1 (electric pump/diesel engine pump).
Flow meter
- Fault in electrical connection in the exchange contact relative
to panel 2 (electric pump/diesel engine pump).
- Jockey pump overload; - Jockey pump running; - Discharge pump overload;
- Battery low; - No communication with ModBus system.
All the above conditions are visualised with signal LEDs and on the display. The customer may decide to enable
the buzzer. Further information available on page 144.
Circuit for test flow of the service pumps. Includes the direct reading flow meter (sized according to the capacity
of the service pump) according to the type of flow meter, connecting piping and straight piping upline from the
instrument, on/off ball valve for diameters up to and including 2 butterfly valve with lever handle from DN65 to
DN100 diameter, butterfly valve with handwheel and reduction manual gear for DN125 diameter and above.
ON/OFF status monitoring included.
New model of flow meter (P6) for diameters up to and including DN80.
Diaphragm tank with relative ball valve, in the same number as that of the pumps present, for dampening any
pressure oscillations in the system. 24 litre model with maximum pressure 8.10 or 16 bar according to the
maximum head of the pumps.
Priming tank for each service pump, in the case of suction lift installation.
Accessories for the priming tank suck as float switch tap, level indicator, valves, automatic air discharger on each
service pump, in the case of suction lift installation.
All the main characteristics of the priming tanks, the flow meters and the available membrane tanks are shown in
the accessories section.
12
Lowara
SPECIAL EQUIPMENT ON REQUEST
(Contact the Sales and technical Assistance Service)
Sets for pumping sea water with electric pumps, valves, manifold and AISI 316 piping or compatible alloys.
Non-standard supply power sets.
Sets with separate electric jockey pump supplied as a kit.
Sets with different electric jockey pump from the standard one.
Sets installed inside prefabricated boxes for outdoor use.
Notes
The set is supplied without a suction manifold in accordance with the EN12845 Standard (points 10.6.2.2 and
10.6.2.3) which provides for independent suction for each pump.
Please see the EN12845 Standard on fixed systems and fire extinguishing Automatic sprinkler systems Design,
installation and maintenance?- for sizing the suction piping, define whether the installation is to be considered
suction lift or positive suction head for the use limits.
The Standard ask that, whenever possible, the pumps are installed with positive suction head, otherwise priming
tanks must be provided with suitable automatic devices for signalling and reintegration.
The EN12845 Standard states that the water pressure should not exceed 12 bar (point 8.2.1). In some applications
it is possible to have pressures of over 12 bar (point 8.2.2).
In this case, pump sets with higher pressures than those within the regulatory limit are used.
The catalogue also shows booster sets with pump closing head up to 150 metres suitable for such installations.
13
Lowara
SPECIAL EQUIPMENT ON REQUEST
14
Lowara
COMMAND P
ANEL FOR THE ELECTRIC SERVICE PUMP
PANEL
Painted metal casing (IP 54) complete with:
General door-locking switch.
Analogical ammeter.
MAN AUT 0 selector with extractable key only in
automatic position.
Keyboard for indicating electric voltage presence,
correct phase sequence (three phase power supply),
start-up request, pump functioning and no start-up,
through LED lamps, lamp test button and starting and
stopping buttons, according to the provisions of
EN12845 paragraph 10.8.6.
Inside:
12/24V transformer for auxiliary circuits and electronic
board.
Fuse holder and fuses for power and auxiliary circuits.
Line contact maker (direct start-up up to 22 kW
included), line and star/triangle contact makers (startriangle start-up), line contact makers and reactance
switching (impedance start-up).
Star/triangle exchanger timer or reactance switching.
Relay for signalling no phase.
Auxiliary relays.
Current transformer.
Terminal boards.
Clean contacts (max. 24V, 1A) for activating acoustic/
visual alarms for no phase, pump on demand, pump
running and start failure.
Cable glands (excluding the versions to be fixed to the
floor).
Wiring diagram.
On request digital trasmission card via RS485 serial by
ModBus comunication protocol.
15
Lowara
COMMAND P
ANEL FOR THE ELECTRIC JOCKEY PUMP
PANEL
Painted metal casing (IP 55) complete with:
General door-locking switch.
Visual indicators for line, running, thermal shutdown.
Manual automatic selector excluded.
Inside:
Transformer for 24V auxiliary circuits.
Fuse holder and fuses for power and auxiliary circuits.
Line contact maker.
Overload cut-out switch.
Pump shut-off timer (0 90 s).
Terminal boards.
Cable glands.
Wiring diagram.
Suitable for connecting to a float switch or a minimum
pressure switch for preventing dry running. An optional
level control module (supplied on request) allows the
connection of probes with the possibility of regulating the
sensitivity according to the hardness of the water.
OPTIONS A
VAILABLE ON REQUEST
AV
CP alternative
Series of clean contacts for checking the status of the electric service pump panel, as well as the contacts already
provided for signalling alarms:
No phase
Motor running
Selector position MAN-AUT-0
No start-up
Start-up request
Series of clean contacts for checking the status of the electric jockey pump:
Pump running
Thermal shutdown (overload)
No water
KV alternative
Control panel for the electric service pump with analogical voltmeter and with phase switch.
IP55 alternative
Electric service pump panel with extra IP55 protection.
The set is supplied already assembled, calibrated and factory tested. The set is supplied
complete with an instruction manual, pump manuals and wiring diagrams for the panels.
For the sets including floor panels, the electric panels are sent together with the set in a separate pack and
supplied with 5-metre long connecting cables (longer lengths available on request). The fitter is responsible for
preparing the routes and installing the cables.
16
Lowara
COMMAND P
ANEL DIMENSIONS
PANEL
SERVICE PUMP P
ANEL
PANEL
POWER (kW)
PROTECTION
CLASS
from 0,7 to 7,5
IP54
350
160
500
from 9,2 to 22
IP54
400
200
600
from 30 to 37
IP54
500
200
700
from 45 to 55
IP54
600
250
800
from 75 to 90
IP54
600
300
1500
IP54
800
400
1700
qe-serv-en_d_td
JOCKEY PUMP P
ANEL
PANEL
PROTECTION
CLASS
IP54
250
160
17
H
300
qe-pil-en_b_td
Lowara
GEN SERIES OF BOOSTER SETS
CHOICE AND SELECTION
Criteria for choosing fire-fighting sets
The correct choice of a fire-fighting set must consider various factors, including the correct sizing of the performance
levels required for the system, local regulations and legislation, and especially the installation conditions relative to
the installation site and whether a suction lift or a positive suction head is involved.
Choosing the type of water supply
The type of water supply and, therefore, the type of booster set to select depends on the type of system involved and
is chosen according to the risk analysis performed by the designer.
There is no written rule for identifying the correct number of pumps to install.
GEN booster sets are normally designed so that every service pump can satisfy the following requirements:
100% of rated capacity with one or two pumps installed (one in service and the other in reserve).
If three pumps are installed, the capacity of the pump will be 50% of the total rated capacity and the third service
pump will be considered as a reserve. In these cases, when superior or duplicated water supplies are involved, only
one pump must be driven by an electric motor. This type of configuration is available on request.
Suction conditions of the booster set
The type of installation, suction lift or positive suction head, tends to affect (negatively or positively) the hydraulic
performance of the pump. Remembering that EN12845 recommends against using suction lift installations, the
following condition given by EN12845 must be satisfied in order to use the pump curve correctly:
NPSHd NPSHr +1 [m]
Where: NPSHd is defined available.
NPSHr is defined requested from the pump.
As the suction check condition must be made at the max. requested flow, there can be different performance levels
always respecting the NPSHd condition.
To select the booster set, consult the dedicated sections. Choice and selection. Hydraulic performance levels. Suction
lift or positive suction head installation.
Performance levels of booster sets: using the tables
The tables showing the hydraulic performance levels of booster sets indicate the flow values according to the risk
class for precalculated systems followed by the respective pressure value. This value does not refer to pump performance
but is net of the pressure drop on the pump discharge line, to the discharge manifold flange.
This field is shown in grey and the selection must be made here, where performance levels comply with the reference
standard which considers the following conditions:
Maximum water speed in the service pump discharge piping 6 m/sec.
NPSHd NPSHr + 1 at the maximum flow required.
Max. difference in level of water considered 3,2 m (for positive suction head).
Suction pressure drops due to valves, piping, suction kit 1,5 m (limit value).
The reference suction conditions are the severest and most extreme that can occur.
The values taken in the fields that are not in grey indicate booster set performance levels in areas outside the limits of
the standard and must not be used to choose the set.
18
Lowara
GEN SERIES OF BOOSTER SETS
CHOICE AND SELECTION
Method of selecting a fire-fighting booster set
Referring to EN 12845, after identifying the risk classes of the activity to protect and performing the precalculation
method, the flow and head values required for the fire-fighting system can be obtained.
This data is used as follows:
1. Configuration of the booster set, choice of the number of service pumps and relative type of motor/engine
(two pumps, one electric and the other driven by a diesel engine).
2. Installation conditions (e.g.. positive suction head), see performance levels for positive suction head installation.
3. Determination of service flow e.g.: 1100 l/min risk class OH3.
TABELLA DI PRESTAZIONI IDRAULICHE NETTE GRUPPI EN12845 SERIE FHF50 2 poli 50 Hz 1 POMPA DI SERVIZIO, INST SOPRAB
RATED
FHF..
POWER
ELECTRIC
PUMP
PUMP
OH3n
TYPE
OH2n
RISK CLASS
Q = DELIVERY
l/min 0
600
700
m3/h 0
36
42
725
850
1000
1100
1200
1300
1350
1400
1500
1600
44
51
60
66
72
78
81
84
90
96
kW
11,8
3,7
15,8
8,0
4. Determining
the
head e.g.:
35GRUPPI
m. EN12845 SERIE20,2
TABELLA
DI PRESTAZIONI
IDRAULICHE
NETTE
FHF50 2 poli 50 Hz 1 13,1
POMPA DI SERVIZIO, INST SOPRAB
27,3
18,2
34,8
FHF..
POWER
ELECTRIC
PUMP
PUMP
42,8
31,2
49,9
38,6
OH3n
RATED
OH2n
TYPE
RISK 26,5
CLASS
60,4
69,5
48,8
Q = DELIVERY
58,8
l/min 0
600
700
725
850
1000
1100
1200
1300
1350
1400
1500
1600
m3/h 0
36
42
44
51
60
66
72
78
81
84
90
96
79,0
68,1
kW
50-125/22
50-125/D119
1 x 2,2
16,8
13,7
12,3
11,8
9,5
6,2
3,7
0,9
50-125/30
50-125/D130
1x3
19,9
17,5
16,1
15,8
13,6
10,5
8,0
5,3
2,3
50-125/40
50-125/D139
1x4
24,3
21,8
20,6
20,2
18,3
15,3
13,1
10,5
7,7
6,2
4,6
50-160/55
50-160/D158
1 x 5,5
31,8
29,3
27,7
27,3
24,8
21,1
18,2
15,0
11,4
9,5
7,6
50-160/75
50-160/D174
1 x 7,5
39,8
36,6
35,2
34,8
32,5
29,1
26,5
23,5
20,2
18,5
16,7
50-200/110A 50-200/D197
1 x 11
50,6
45,6
43,4
42,8
39,5
34,8
31,2
27,3
23,1
20,9
18,6
50-200/110
1 x 11
58,0
52,6
50,5
49,9
46,7
42,1
38,6
34,7
30,4
28,1
25,7
50-200/D209
60,4
48,8
69,5
58,8
12,7
20,7
19
Lowara
GEN SERIES OF BOOSTER SETS
CHOICE AND SELECTION - POSITIVE SUCTION HEAD INST
ALLA
TION
INSTALLA
ALLATION
EN12845 recommends always installing pumps in suction lift conditions, where possible If this is not possible, the
pumps can be installed in positive suction head conditions according to the following rules:
The height of the minimum water level at the pump axis must not be greater than 3,2 m.
A foot valve must be installed in the lowest point of the suction piping.
If more than one pump is installed, the suction piping must not be interconnected.
Liv. normale
Normal
level
Max 3,2 m
Liv.level
Min XX
Min.
20
Lowara
GEN SERIES OF BOOSTER SETS
CHOICE AND SELECTION - POSITIVE SUCTION HEAD INST
ALLA
TION
INSTALLA
ALLATION
At this point, the installation conditions (positive suction head) must be checked at the maximum required
flow.
flow
The following values are replaced in the known relation, NPSHd NPSHr + 1:
NPSHr can be deduced from the table on page 45 which in this case is 4,6 m at the maximum requested flow.
After replacing the value, the following will be true (water temperature around 15C):
NPSHd = 10,33 + (-3,2) - Hct
Where
10,33 atmospheric pressure
3,2 geodetic difference in level
Hct suction pressure drop ((valves, pipes, elbows..)
The value of Hct considers the pressure drops of the suction kit, inclusive of vibration-proof joint, reduction cone
and on-off valve (Hc), as well as the pressure drops relative to all the suction piping, foot valve, elbows, elbows,
etc...
The value of Hc at the maximum required flow of the selected pump can be found in the diagram on page 81.
This value is 0,16 m.
After entering it in the formula, we will have:
Hct = 0,16 + X
Where X is the pressure drop relative to all the suction piping
Hence
NPSHd NPSHr + 1. After replacing this, we will have:
10,33 + (-3,2) - Hct = 4,6 +1
10,33 + (-3,2) 0,16 - X = 4,6 +1 which gives
X = 1,37 m
Maximum value of total drops to consider on the inlet piping in order to respect the conditions of the standard.
Of course, this case was deliberately put in the worst suction conditions. The designer must check and set the
values in an attempt to optimise suction conditions.
21
Lowara
GEN SERIES OF BOOSTER SETS
CHOICE AND SELECTION - POSITIVE SUCTION HEAD INST
ALLA
TION
INSTALLA
ALLATION
Checking performance of the set at rated flow
flow..
The performance of the booster set must now be checked in the installation conditions of the example used up
until now.
Work point: Qn: 1100 l/min H = 35 m
The selected pump is FHF50-200/110
Starting from the usual relation given by the standard, we will have:
NPSHd NPSHr + 1
NPSHd = 10,33 + (-3,2) - Hct
NPSHr can be deduced from the table on page 45 which in this case is 2,9 m at the rated flow.
The value of Hct considers the pressure drops of the suction kit, inclusive of vibration-proof joint, reduction cone
and on-off valve (Hc), as well as the pressure drops relative to all the suction piping, foot valve, elbows, elbows,
etc...
The value of Hc at the rated required flow of the selected pump can be found in the diagram on page 81. This
value is 0,12 m.
After entering it in the formula, we will have:
Hct = 0,12 + X
Where X is the pressure drop relative to all the suction piping
Hence
NPSHd NPSHr + 1. After replacing this, we will have:
10,33 + (-3,2) - Hct = 2,9 +1
10,33 + (-3,2) 0,12 - X = 2,9 +1 which gives
X = 3,11 m
Value of the total drops to consider on the suction piping
Taking the pressure value of the selected set, the value corresponds to 38,6 m at the rated flow.
Therefore, the verification of the pressure values in the above suction conditions becomes:
H = 38,6 -0,12 -3,11 = 35,4 m > 35 m which is the pressure required for the system
The result satisfies the performance required for the system in the installation conditions of the example.
22
Lowara
GEN SERIES OF BOOSTER SETS
CHOICE AND SELECTION - SUCTION LIF
T INST
ALLA
TION
LIFT
INSTALLA
ALLATION
Suction lift installation
EN12845 recommends always installing pumps in suction lift conditions, where possible, according to the following
rules:
At least two thirds of the effective capacity of the suction tank must be above the level of the pump axis.
The pump axis must not be more than 2 m above the minimum water level in the suction tank.
Normal
level
Liv.
normale
2/3
2/3 della
of
capacit
effective
effettiva
capacity
Max 2 m
Min. Min
levelXX
Liv.
23
Lowara
GEN SERIES OF BOOSTER SETS
CHOICE AND SELECTION - SUCTION LIF
T INST
ALLA
TION
LIFT
INSTALLA
ALLATION
Being aware of the rated flow 1100 l/min and the pressure required for the system (e.g.: 35 m), the pump is selected
according to the tables on page 44-45, making sure the performance rating lies inside the area shown in grey.
The pump that satisfies the required work point is FHF50-200/110.
At this point, the installation conditions (suction lift) must be checked at the maximum required flow.
The following values are replaced in the known relation, NPSHd NPSHr + 1:
NPSHr can be deduced from the table on page 45 which in this case is 4,6 m at the maximum requested flow.
After replacing the value, the following will be true (water temperature around 15C):
NPSHd = 10,33 + (0) - Hct
Where
10,33 atmospheric pressure
0 geodetic difference in level
Hct suction pressure drop (valves, pipes, elbows...)
The value of Hct considers the pressure drops of the suction kit, inclusive of vibration-proof joint, reduction cone
and on-off valve (Hc), as well as the pressure drops relative to all the suction piping, foot valve, elbows, elbows, etc
The value of Hc at the maximum required flow of the selected pump can be found in the diagram on page 87.
This value is 0,32 m.
After entering it in the formula, we will have:
Hct = 0,32 + X
Where X is the pressure drop relative to all the suction piping
Hence
NPSHd NPSHr + 1. After replacing this, we will have:
10,33 + (0) - Hct = 4,6 +1
10,33 + (0) 0,32 - X = 4,6 +1 which gives
X = 4,41 m
Maximum value of total drops to consider on the inlet piping in order to respect the conditions of the standard.
Of course, the case in point was deliberately tested in neutral suction conditions that neither benefit nor optimise
suction.
The designer must check and set the values in an attempt to make suction conditions as efficient as possible.
24
Lowara
GEN SERIES OF BOOSTER SETS
CHOICE AND SELECTION - SUCTION LIF
T INST
ALLA
TION
LIFT
INSTALLA
ALLATION
Checking performance of the selected set at rated flow
flow..
The performance of the booster set must now be checked in the installation conditions of the example used up until
now.
Work point: Qn 1100 l/min H = 35 m
The selected pump is FHF50-200/110
Starting from the usual relation given by the standard, we will have:
NPSHd NPSHr + 1
NPSHd = 10,33 + (0) - Hct
NPSHr can be deduced from the table on page 45 which in this case is 2,9 m at the rated flow
flow.
The value of Hct considers the pressure drops of the suction kit, inclusive of vibration-proof joint, reduction cone
and on-off valve (Hc), as well as the pressure drops relative to all the suction piping, foot valve, elbows, elbows, etc...
The value of Hc at the rated required flow of the selected pump can be found in the diagram on page 87. This value
is 0,22 m.
After entering it in the formula, we will have:
Hct = 0,22 + X
Where X is the pressure drop relative to all the suction piping
Hence
NPSHd NPSHr + 1. After replacing this, we will have:
10,33 + (0) - Hct = 2,9 +1
10,33 + (0) 0,22 - X = 2,9 +1 which gives
X = 6,21 m
Value of the total drops to consider on the suction piping
Taking the pressure value of the selected set, the value corresponds to 38,6 m at the rated flow.
Therefore, the verification of the pressure values in the above suction conditions becomes:
H = 38,6 -0,22 -6,21 = 32,17 m < 35 m which is the pressure required for the system.
The value obtained, doesnt satisfy the performance necessary for the system, but as is evident, we have used deliberately
a neutral installation condition that it doesnt give benefits to the suction. It results that installed the pump with
positive suction of 3 m, we will have a pressure value of 35,17 m that it satisfied the relation.
25
Lowara
26
Lowara
GEN../FHF Series
Fire-fighting booster sets EN 12845
Horizontal Centrifugal electric pumps FHF series
equipped with high efficiency PLM motors
50 Hz
27
Lowara
28
Lowara
RANGE
GEN../FHF RANGE
The range of EN 12845 series fire-fighting booster sets includes
models with 1 or 2 electric service pumps and some with jockey
pumps for adapting to the specific requirements of each application.
GEN10 SERIES
Head up to 100 m.
Flow up to 650 m3/h.
GEN11 SERIES
Head up to 100 m.
Flow up to 650 m3/h.
GEN20 SERIES
Head up to 100 m.
Flow up to 1300 m3/h.
GEN21 SERIES
29
Head up to 100 m.
Flow up to 1300 m3/h.
Lowara
GEN../FHF BOOSTER SETS SERIES
TABELLA DI PRESTAZIONI IDRAULICHE POMPE PILOTA SV2-4 PER GRUPPI EN12845
HYDRA
ULIC PERFORMANCE T
ABLE A
T 50 Hz (JOCKEY PUMP)
HYDRAULIC
TABLE
AT
PUMP
NOMINAL
TYPE
POWER
Q = DELIVERY
l/min 0
20
30
40
50
60
70
100
120
133
m3/h 0
1,2
1,8
2,4
3,6
4,2
7,2
37,0
26,0
18,0
kW
HP
SV2 04
0,55
0,75
42,5
37,5
34,0
30,5
26,0
20,5
SV2 06
0,75
64,0
56,0
51,0
45,5
38,5
31,0
22,0
SV2 09
1,1
1,5
96,0
84,0
76,5
68,5
58,0
46,5
32,5
SV2 12
1,5
128,0
112,0
102,0
91,0
77,0
62,0
44,0
SV2 14
2,2
150,0
131,0
119,0
106,0
90,0
73,0
52,0
SV2 15
2,2
160,2
140,3
128,2
114,0
97,4
78,2
55,9
SV4 07
1,1
1,5
70,0
59,5
56,0
53,0
51,0
SV4 09
1,5
90,0
76,5
73,0
68,5
65,5
47,0
33,5
23,0
SV4 13
2,2
131,0
111,0
105,0
99,0
95,0
68,0
48,0
34,0
15,0
EN12845_pp_sv2-4-2p50-en_b_th
NOMINAL
TYPE
POWER
Q = DELIVERY
l/min 0
3
m /h 0
kW
100
120
133
150
167
200
233
7,2
10
12
14
33
HP
SV8 05
2,2
68
62
60
57,5
55
51
43
SV8 06
82
74,5
71
69
66
61,5
52
40
SV8 07
5,5
95,9
87
88
80
76
71
60
46,2
SV8 09
5,5
123
112
107
104
97,5
92
78
60
EN12845_pp_sv8-2p50-en_a_th
30
Lowara
GEN../FHF 32-80 BOOSTER SETS SERIES
TABELLA ABBINAMENTI POMPA SERVIZIO FH32-80 - POMPA PILOTA GRUPPI GEN 1
SERVICE PUMP JOCKEY PUMP COMBINA
TIONS
COMBINATIONS
SERVICE PUMP
JOCKEY PUMP
PUMP
32-125/07
32-125/11
32-160/15
32-160/22
32-200/30
32-200/40
40-125/11
40-125/15
40-125/22
40-160/30
40-160/40
40-200/55
40-200/75
40-250/110A
40-250/110
40-250/150
50-125/22
50-125/30
50-125/40
50-160/55
50-160/75
50-200/110A
50-200/110
50-250/150
50-250/185
50-250/220
65-125/40
65-125/55
65-125/75
65-160/110A
65-160/110
65-160/150
65-200/150
65-200/185
65-200/220
65-250/220
65-250/300
65-250/370
80-160/150
80-160/185
80-200/220
80-200/300
80-250/370
80-250/450
80-250/550
SV8 09
SV8 07
SV8 06
SV8 05
SV4 13
SV4 09
SV4 07
SV2 15
SV2 14
SV2 12
SV2 09
FHF..
ELECTRIC
SV2 06
SV2 04
TYPE
PUMP
32-125/D119
32-125/D136
32-160/D150
32-160/D164
32-200/D188
32-200/D204
40-125/D112
40-125/D122
40-125/D143
40-160/D159
40-160/D171
40-200/D190
40-200/D209
40-250/D218
40-250/D233
40-250/D251
50-125/D119
50-125/D130
50-125/D139
50-160/D158
50-160/D174
50-200/D197
50-200/D209
50-250/D224
50-250/D237
50-250/D250
65-125/D121
65-125/D129
65-125/D140
65-160/D161
65-160/D168
65-160/D178
65-200/D187
65-200/D198
65-200/D210
65-250/D220
65-250/D241
65-250/D258
80-160/D163
80-160/D173
80-200/D189
80-200/D207
80-250/D225
80-250/D238
80-250/D256
12845-FHF32-80_ap-en_a_tc
31
Lowara
GEN../FHF 100-125 BOOSTER SETS SERIES
TABELLA ABBINAMENTI POMPA SERVIZIO FH100-125 - POMPA PILOTA GRUPPI GE
SERVICE PUMP JOCKEY PUMP COMBINA
TIONS
COMBINATIONS
SERVICE PUMP
JOCKEY PUMP
PUMP
100-160/185
100-160/220
100-160/300
100-200/185
100-200/300
100-200/370
100-200/450
100-250/300
100-250/450
100-250/550
100-250/750
100-250/900
125-200/300
125-200/450
125-200/550
125-270/750
125-270/900
125-270/1100
125-270/1320
SV8 09
SV8 07
SV8 06
SV8 05
SV4 13
SV4 09
SV4 07
SV2 15
SV2 14
SV2 12
SV2 09
FHF..
ELECTRIC
SV2 06
SV2 04
TYPE
PUMP
100-160/D150
100-160/D165
100-160/D185
100-200/D168
100-200/D192
100-200/D203
100-200/D213
100-250/D200
100-250/D221
100-250/D235
100-250/D254
100-250/D267
125-200/D180
125-200/D206
125-200/D216
125-270/D224
125-270/D237
125-270/D253
125-270/D266
12845-FHF100-125_ap-en_a_tc
32
Lowara
HYDRA
ULIC PERFORMANCE T
ABLE A
T 50 HZ (POSITIVE SUCTION HEAD)
HYDRAULIC
TABLE
AT
TABELLA DI PRESTAZIONI IDRAULICHE NETTE GRUPPO EN12845 SERIE FHF32 2 poli 50 Hz, 1 POMPA DI SERVIZIO, ASP ESCLUSA INS SOPRA
GEN../FHF 32 BOOSTER SETS SERIES
TYPE
RATED
FHF..
POWER
ELECTRIC
PUMP
PUMP
LHn
RISK CLASS
Q = DELIVERY
l/min 0
100
150
200
225
250
275
300
375
400
425
450
500
m3/h 0
12
14
15
17
18
23
24
26
27
30
kW
32-125/07
32-125/D119
1 x 0,75
16,9
15,6
14,1
12,1
10,9
9,6
8,1
6,6
32-125/11
32-125/D136
1 x 1,1
21,9
20,5
19,1
17,2
16,1
14,9
13,5
12,1
7,1
5,2
32-160/15
32-160/D150
1 x 1,5
27,3
25,6
24,0
21,8
20,5
19,0
17,4
15,6
9,5
7,2
32-160/22
32-160/D164
1 x 2,2
34,7
33,1
31,5
29,3
27,9
26,5
24,9
23,2
17,3
15,0
12,7
10,2
32-200/30
32-200/D188
1x3
44,2
41,3
39,3
36,8
35,3
33,7
32,0
30,1
23,4
20,8
18,0
15,0
32-200/40
32-200/D204
1x4
54,4
51,7
49,5
46,8
45,2
43,5
41,7
39,7
33,2
30,8
28,2
25,6
20,0
Performance levels relative to set with 1 service pump running and compliant with ISO 9906 - Annex A.
12845_1pg-sp-fhf32-2p50-en_a_th
LHn = class of risk value referred to the required rated capacity (Tab.6 para 7.3.1 EN12845)
Inlet pressure drops must be deducted. Make sure that these drops, added to the difference in level (max. 3.2m), are less than 4.5m
The values shown identify performance levels according to the reference standard EN12845.
HYDRA
ULIC PERFORMANCE T
ABLE A
T 50 HZ (SUCTION LIF
T)
HYDRAULIC
TABLE
AT
LIFT)
TABELLA DI PRESTAZIONI IDRAULICHE NETTE GRUPPO EN12845 SERIE FHF32 2 poli 50 Hz, 1 POMPA DI SERVIZIO, ASP ESCLUSA INS SOTTO
GEN../FHF 32 BOOSTER SETS SERIES
TYPE
RATED
FHF..
POWER
ELECTRIC
PUMP
PUMP
LHn
RISK CLASS
Q = DELIVERY
l/min 0
100
150
200
225
250
275
300
375
400
425
450
500
m3/h 0
12
14
15
17
18
23
24
26
27
30
kW
32-125/07
32-125/D119
1 x 0,75
16,9
15,6
14,1
12,1
10,9
9,6
8,1
6,6
32-125/11
32-125/D136
1 x 1,1
21,9
20,5
19,1
17,2
16,1
14,9
13,5
12,1
7,1
5,2
32-160/15
32-160/D150
1 x 1,5
27,3
25,6
24,0
21,8
20,5
19,0
17,4
15,6
9,5
7,2
32-160/22
32-160/D164
1 x 2,2
34,7
33,1
31,5
29,3
27,9
26,5
24,9
23,2
17,3
15,0
12,7
10,2
32-200/30
32-200/D188
1x3
44,2
41,3
39,3
36,8
35,3
33,7
32,0
30,1
23,4
20,8
18,0
15,0
32-200/40
32-200/D204
1x4
54,4
51,7
49,5
46,8
45,2
43,5
41,7
39,7
33,2
30,8
28,2
25,6
Performance levels relative to set with 1 service pump running and compliant with ISO 9906 - Annex A.
LHn = class of risk value referred to the required rated capacity (Tab.6 para 7.3.1 EN12845)
Inlet pressure drops must be deducted. Make sure these drops are less than 4.5m
The values shown identify performance levels according to the reference standard EN12845.
20,0
12845_1pg-st-fhf32-2p50-en_a_th
RATED
FHF..
POWER
ELECTRIC
PUMP
PUMP
LHn
LH
RISK CLASS
Q = DELIVERY
l/min 0
100
150
200
225
250
275
300
350
375
400
450
500
3
m /h 0
12
14
15
17
18
21
23
24
27
30
kW
32-125/07
32-125/D119
1 x 0,75
1,6
1,6
1,7
1,8
2,0
2,2
32-125/11
32-125/D136
1 x 1,1
1,6
1,6
1,7
1,8
2,0
2,2
2,9
3,4
4,0
32-160/15
32-160/D150
1 x 1,5
2,2
2,4
2,5
2,7
2,8
3,0
3,6
3,9
4,4
32-160/22
32-160/D164
1 x 2,2
2,2
2,4
2,5
2,7
2,8
3,0
3,6
3,9
4,4
5,9
32-200/30
32-200/D188
1x3
2,7
2,9
3,1
3,3
3,5
3,8
4,3
4,6
4,9
5,5
32-200/40
32-200/D204
1x4
2,7
2,9
3,1
3,3
3,5
3,8
4,3
4,6
4,9
5,5
The declared NPSH values were obtained in the laboratory and refer to a single service pump
LHn = class of risk value referred to the required rated capacity (Tab.6 para 7.3.1 EN12845)
Check that NPSHd NPSHr+1m is satisfied
33
6,2
12845_1p-fhf32-2p50_NPSHr-en_a_th
Lowara
HYDRA
ULIC PERFORMANCE
T
ABLE
T 50
SUCTION
HEAD)
HYDRAULIC
TABLE
AT
TABELLA DI PRESTAZIONI
IDRAULICHE NETTE GRUPPI EN12845
SERIEA
FHF40
2 poliHZ
50 Hz(POSITIVE
1 POMPA DI SERVIZIO,
ASP ESCLUSA INST
SOPRAB
GEN../FHF 40 BOOSTER SETS SERIES
TYPE
RATED
FHF..
POWER
ELECTRIC
PUMP
PUMP
OH1n
RISK CLASS
Q = DELIVERY
l/min 0
300
350
375
540
600
700
725
750
800
900
1000
1100
m3/h 0
18
21
23
32
36
42
44
45
48
54
60
66
kW
40-125/11
40-125/D112
1 x 1,1
13,9
11,3
10,0
9,3
3,4
40-125/15
40-125/D122
1 x 1,5
18,0
15,3
14,0
13,3
7,4
0,7
4,7
40-125/22
40-125/D143
1 x 2,2
25,3
21,8
20,5
19,8
14,0
11,4
6,4
5,0
3,6
40-160/30
40-160/D159
1x3
31,6
28,1
26,8
26,0
19,5
16,5
10,8
9,2
7,6
40-160/40
40-160/D171
1x4
38,3
35,1
33,7
32,9
26,5
23,6
18,1
16,5
15,0
0,6
11,7
40-200/55
40-200/D190
1 x 5,5
46,4
42,7
41,2
40,4
33,1
29,7
23,3
21,5
19,6
40-200/75
40-200/D209
1 x 7,5
57,5
53,1
51,6
50,7
43,8
40,7
34,8
33,2
31,5
28,0
40-250/110A 40-250/D218
1 x 11
63,6
57,8
56,2
55,2
47,8
44,5
38,2
36,5
34,8
31,1
40-250/110
40-250/D233
1 x 11
71,7
66,0
64,3
63,4
55,7
52,3
45,8
44,0
42,1
38,3
40-250/150
40-250/D251
1 x 15
85,0
78,6
76,9
76,0
68,4
65,0
58,6
56,8
55,0
51,1
42,6
Performance levels relative to set with 1 service pump running and compliant with ISO 9906 - Annex A.
12845_1pg-sp-fhf40-2p50-en_a_th
OHn = class of risk value referred to the required rated capacity (Tab.6 para 7.3.1 EN12845)
Inlet pressure drops must be deducted. Make sure that these drops, added to the difference in level (max. 3.2m), are less than 4.5m
The values shown identify performance levels according to the reference standard EN12845.
HYDRA
ULIC PERFORMANCE T
ABLE
A2 T
50 HZ (SUCTION LIF
T)
HYDRAULIC
TABLE
LIFT)
TABELLA DI PRESTAZIONI IDRAULICHE NETTE GRUPPI EN12845
SERIE FHF40AT
poli 50 Hz 1 POMPA DI SERVIZIO, ASP ESCLUSA
INST SOTTO
GEN../FHF 40 BOOSTER SETS SERIES
TYPE
RATED
FHF..
POWER
ELECTRIC
PUMP
PUMP
OH1n
RISK CLASS
Q = DELIVERY
l/min 0
300
350
375
540
600
700
725
750
800
900
1000
1100
m3/h 0
18
21
23
32
36
42
44
45
48
54
60
66
kW
40-125/11
40-125/D112
1 x 1,1
13,9
11,3
10,0
9,3
3,4
40-125/15
40-125/D122
1 x 1,5
18,0
15,3
14,0
13,3
7,4
0,7
4,7
40-125/22
40-125/D143
1 x 2,2
25,3
21,8
20,5
19,8
14,0
11,4
6,4
5,0
3,6
40-160/30
40-160/D159
1x3
31,6
28,1
26,8
26,0
19,5
16,5
10,8
9,2
7,6
0,6
40-160/40
40-160/D171
1x4
38,3
35,1
33,7
32,9
26,5
23,6
18,1
16,5
15,0
40-200/55
40-200/D190
1 x 5,5
46,4
42,7
41,2
40,4
33,1
29,7
23,3
21,5
19,6
40-200/75
40-200/D209
1 x 7,5
57,5
53,1
51,6
50,7
43,8
40,7
34,8
33,2
31,5
28,0
40-250/110A 40-250/D218
1 x 11
63,6
57,8
56,2
55,2
47,8
44,5
38,2
36,5
34,8
31,1
11,7
40-250/110
40-250/D233
1 x 11
71,7
66,0
64,3
63,4
55,7
52,3
45,8
44,0
42,1
38,3
40-250/150
40-250/D251
1 x 15
85,0
78,6
76,9
76,0
68,4
65,0
58,6
56,8
55,0
51,1
Performance levels relative to set with 1 service pump running and compliant with ISO 9906 - Annex A.
OHn = class of risk value referred to the required rated capacity (Tab.6 para 7.3.1 EN12845)
Inlet pressure drops must be deducted. Make sure these drops are less than 4.5m
The values shown identify performance levels according to the reference standard EN12845.
34
42,6
12845_1pg-st-fhf40-2p50-en_a_th
Lowara
NPSH
REQUIRED
PUMP
FHF
TABELLA DI PRESTAZIONI
IDRAULICHEFOR
NPSHr GRUPPI
EN12845 SERIES
SERIE FHF40 2 poli
50 Hz 140
POMPA DI SERVIZIO
RATED
FHF..
POWER
ELECTRIC
PUMP
PUMP
OH1m
TYPE
OH1n
RISK CLASS
l/min 0
300
350
375
540
600
700
725
750
800
900
1000
1100
m3/h 0
18
21
23
32
36
42
44
45
48
54
60
66
Q = DELIVERY
kW
40-125/11
40-125/D112
1 x 1,1
1,8
1,9
1,9
2,4
2,7
40-125/15
40-125/D122
1 x 1,5
1,8
1,9
1,9
2,4
2,7
3,7
40-125/22
40-125/D143
1 x 2,2
1,8
1,9
1,9
2,4
2,7
3,7
4,1
4,6
40-160/30
40-160/D159
1x3
1,9
1,9
1,9
2,4
2,9
4,1
4,5
5,0
6,3
40-160/40
40-160/D171
1x4
1,9
1,9
1,9
2,4
2,9
4,1
4,5
5,0
40-200/55
40-200/D190
1 x 5,5
2,0
2,1
2,2
2,9
3,4
4,5
4,9
5,3
6,2
40-200/75
40-200/D209
1 x 7,5
2,0
2,1
2,2
2,9
3,4
4,5
4,9
5,3
6,3
40-250/110A 40-250/D218
1 x 11
1,0
1,1
1,2
1,6
1,7
2,1
2,2
2,3
2,6
40-250/110
40-250/D233
1 x 11
1,0
1,1
1,2
1,6
1,7
2,1
2,2
2,3
2,6
40-250/150
40-250/D251
1 x 15
1,0
1,1
1,2
1,6
1,7
2,1
2,2
2,3
2,6
The declared NPSH values were obtained in the laboratory and refer to a single service pump
OHn, OHm = class of risk value referred to the required rated and maximum capacity (Tab.6 para 7.3.1 EN12845)
Check that NPSHd NPSHr+1m is satisfied at the maximum requested capacity
35
3,5
12845_1p-fhf40-2p50_NPSHr-en_a_th
Lowara
HYDRA
ULIC PERFORMANCE
T
ABLE
T 50
SUCTION
HYDRAULIC
TABLE
AT
TABELLA DI PRESTAZIONI
IDRAULICHE NETTE GRUPPI EN12845
SERIEA
FHF50
2 poliHZ
50 Hz(POSITIVE
1 POMPA DI SERVIZIO,
INST SOPRAB HEAD)
GEN../FHF 50 BOOSTER SETS SERIES
RATED
FHF..
POWER
ELECTRIC
PUMP
PUMP
OH3n
TYPE
OH2n
RISK CLASS
Q = DELIVERY
l/min 0
600
700
725
850
1000
1100
1200
1300
1350
1400
1500
1600
m3/h 0
36
42
44
51
60
66
72
78
81
84
90
96
kW
50-125/22
50-125/D119
1 x 2,2
16,8
13,7
12,3
11,8
9,5
6,2
3,7
0,9
50-125/30
50-125/D130
1x3
19,9
17,5
16,1
15,8
13,6
10,5
8,0
5,3
2,3
50-125/40
50-125/D139
1x4
24,3
21,8
20,6
20,2
18,3
15,3
13,1
10,5
7,7
6,2
4,6
50-160/55
50-160/D158
1 x 5,5
31,8
29,3
27,7
27,3
24,8
21,1
18,2
15,0
11,4
9,5
7,6
50-160/75
50-160/D174
1 x 7,5
39,8
36,6
35,2
34,8
32,5
29,1
26,5
23,5
20,2
18,5
16,7
50-200/110A 50-200/D197
1 x 11
50,6
45,6
43,4
42,8
39,5
34,8
31,2
27,3
23,1
20,9
18,6
12,7
50-200/110
50-200/D209
1 x 11
58,0
52,6
50,5
49,9
46,7
42,1
38,6
34,7
30,4
28,1
25,7
50-250/150
50-250/D224
1 x 15
68,1
62,8
60,9
60,4
57,3
52,6
48,8
44,4
39,4
36,7
33,8
50-250/185
50-250/D237
1 x 18,5
76,5
71,7
70,0
69,5
66,6
62,3
58,8
54,7
50,0
47,4
44,7
38,6
50-250/220
50-250/D250
1 x 22
86,0
81,2
79,5
79,0
76,1
71,7
68,1
64,0
59,4
56,8
54,1
48,1
20,7
41,4
Performance levels relative to set with 1 service pump running and compliant with ISO 9906 - Annex A.
12845_1pg-sp-fhf50-2p50-en_a_th
OHn = class of risk value referred to the required rated capacity (Tab.6 para 7.3.1 EN12845)
Inlet pressure drops must be deducted. Make sure that these drops, added to the difference in level (max. 3.2m), are less than 4.5m
The values shown identify performance levels according to the reference standard EN12845.
HYDRA
ULIC PERFORMANCE T
ABLE
A2 T
50 HZ (SUCTION LIF
T)
HYDRAULIC
TABLE
LIFT)
TABELLA DI PRESTAZIONI IDRAULICHE NETTE GRUPPI EN12845
SERIE FHF50AT
poli 50 Hz 1 POMPA DI SERVIZIO, INST SOTT
GEN../FHF 50 BOOSTER SETS SERIES
RATED
FHF..
POWER
ELECTRIC
PUMP
PUMP
OH3n
TYPE
OH2n
RISK CLASS
Q = DELIVERY
l/min 0
600
700
725
850
1000
1100
1200
1300
1350
1400
1500
1600
m3/h 0
36
42
44
51
60
66
72
78
81
84
90
96
kW
50-125/22
50-125/D119
1 x 2,2
16,8
13,7
12,3
11,8
9,5
6,2
3,7
0,9
50-125/30
50-125/D130
1x3
19,9
17,5
16,1
15,8
13,6
10,5
8,0
5,3
2,3
50-125/40
50-125/D139
1x4
24,3
21,8
20,6
20,2
18,3
15,3
13,1
10,5
7,7
6,2
4,6
50-160/55
50-160/D158
1 x 5,5
31,8
29,3
27,7
27,3
24,8
21,1
18,2
15,0
11,4
9,5
7,6
50-160/75
50-160/D174
1 x 7,5
39,8
36,6
35,2
34,8
32,5
29,1
26,5
23,5
20,2
18,5
16,7
50-200/110A 50-200/D197
1 x 11
50,6
45,6
43,4
42,8
39,5
34,8
31,2
27,3
23,1
20,9
18,6
12,7
50-200/110
50-200/D209
1 x 11
58,0
52,6
50,5
49,9
46,7
42,1
38,6
34,7
30,4
28,1
25,7
50-250/150
50-250/D224
1 x 15
68,1
62,8
60,9
60,4
57,3
52,6
48,8
44,4
39,4
36,7
33,8
50-250/185
50-250/D237
1 x 18,5
76,5
71,7
70,0
69,5
66,6
62,3
58,8
54,7
50,0
47,4
44,7
38,6
50-250/220
50-250/D250
1 x 22
86,0
81,3
79,5
79,0
76,1
71,7
68,2
64,1
59,5
56,9
54,2
48,2
Performance levels relative to set with 1 service pump running and compliant with ISO 9906 - Annex A.
OHn = class of risk value referred to the required rated capacity (Tab.6 para 7.3.1 EN12845)
Inlet pressure drops must be deducted. Make sure these drops are less than 4.5m
The values shown identify performance levels according to the reference standard EN12845.
36
20,7
41,6
12845_1pg-st-fhf50-2p50-en_a_th
Lowara
NPSH
REQUIRED
FOR
PUMP
SERIES
TABELLA DI PRESTAZIONI
IDRAULICHE
NPSHr GRUPPI
EN12845
SERIE FHF50 FHF
2 poli 50 50
Hz 1 POMPA DI SERVIZIO
POWER
Q = DELIVERY
l/min 0
ELECTRIC
PUMP
PUMP
OH3m
FHF..
OH3n
RATED
OH2n
TYPE
OH2m
RISK CLASS
m /h 0
600
700
725
850
1000
1100
1200
1300
1350
1400
1500
1600
36
42
44
51
60
66
72
78
81
84
90
96
kW
50-125/22
50-125/D119
1 x 2,2
2,1
2,3
2,3
2,6
3,1
3,5
3,9
50-125/30
50-125/D130
1x3
2,1
2,3
2,3
2,6
3,1
3,5
3,9
4,4
50-125/40
50-125/D139
1x4
2,1
2,3
2,3
2,6
3,1
3,5
3,9
4,4
4,7
5,0
50-160/55
50-160/D158
1 x 5,5
1,9
2,1
2,2
2,5
2,9
3,2
3,6
4,2
4,6
5,1
50-160/75
50-160/D174
1 x 7,5
1,9
2,1
2,2
2,5
2,9
3,2
3,6
4,2
4,6
5,1
50-200/110A 50-200/D197
1 x 11
1,8
1,9
2,0
2,2
2,6
2,9
3,4
4,1
4,6
5,1
50-200/110
50-200/D209
1 x 11
1,8
1,9
2,0
2,2
2,6
2,9
3,4
4,1
4,6
5,1
50-250/150
50-250/D224
1 x 15
1,5
1,7
1,7
2,0
2,4
2,7
3,1
3,6
3,9
4,2
50-250/185
50-250/D237
1 x 18,5
1,5
1,7
1,7
2,0
2,4
2,7
3,1
3,6
3,9
4,2
5,1
50-250/220
50-250/D250
1 x 22
1,5
1,7
1,7
2,0
2,4
2,7
3,1
3,6
3,9
4,2
5,1
The declared NPSH values were obtained in the laboratory and refer to a single service pump
OHn, OHm = class of risk value referred to the required rated and maximum capacity (Tab.6 para 7.3.1 EN12845)
Check that NPSHd NPSHr+1m is satisfied at the maximum requested capacity
37
6,5
6,7
6,4
12845_1p-fhf50-2p50_NPSHr-en_a_th
Lowara
HYDRA
ULIC PERFORMANCE T
ABLE A
T 50 HZ (POSITIVE SUCTION HEAD)
HYDRAULIC
TABLE
AT
TABELLA DI PRESTAZIONI IDRAULICHE NETTE GRUPPI EN12845 SERIE FHF65 2 poli 50 Hz 1 POMPA DI SERVIZIO, ASP ESCLUSA INST SOPRAB
GEN../FHF 65 BOOSTER SETS SERIES
RATED
FHF..
POWER
ELECTRIC
PUMP
PUMP
OH4n
TYPE
OH3n
RISK CLASS
Q = DELIVERY
l/min 0
800
900
1000
1100
1200
1350
1400
1500
1800
2000
2100
2300
m3/h 0
48
54
60
66
72
81
84
90
108
120
126
138
kW
65-125/40
65-125/D121
1x4
19,1
15,6
14,6
13,5
12,3
10,9
8,7
7,9
6,2
65-125/55
65-125/D129
1 x 5,5
22,7
19,6
18,8
17,8
16,7
15,5
13,5
12,7
11,2
5,7
65-125/75
65-125/D140
1 x 7,5
27,1
24,3
23,5
22,7
21,7
20,7
18,9
18,2
16,8
12,0
8,1
65-160/110A 65-160/D161
1 x 11
32,7
29,2
28,3
27,2
26,0
23,9
23,2
21,6
15,9
11,5
9,0
65-160/110
65-160/D168
1 x 11
35,9
32,5
31,5
30,5
29,4
27,4
26,7
25,2
19,8
15,6
13,3
65-160/150
65-160/D178
1 x 15
41,9
38,9
38,1
37,1
36,1
34,2
33,6
32,2
27,2
23,2
21,1
65-200/150
65-200/D187
1 x 15
45,2
43,4
42,3
41,1
39,7
37,3
36,4
34,6
28,4
23,8
21,3
65-200/185
65-200/D198
1 x 18,5
51,6
50,2
49,2
48,2
47,0
44,9
44,1
42,4
36,5
31,8
29,2
65-200/220
65-200/D210
1 x 22
59,1
57,2
56,3
55,3
54,2
52,1
51,4
49,8
44,1
39,6
37,1
65-250/220
65-250/D220
1 x 22
62,8
60,6
59,4
58,0
56,4
53,5
52,5
50,2
42,1
35,7
32,1
16,3
31,6
65-250/300
65-250/D241
1 x 30
76,4
75,0
73,9
72,6
71,1
68,5
67,5
65,4
57,8
51,6
48,2
40,6
65-250/370
65-250/D258
1 x 37
90,8
89,9
89,0
88,0
86,7
84,5
83,7
81,8
74,8
68,8
65,4
57,7
Performance levels relative to set with 1 service pump running and compliant with ISO 9906 - Annex A.
12845_1pg-sp-fhf65-2p50-en_a_th
OHn = class of risk value referred to the required rated capacity (Tab.6 para 7.3.1 EN12845)
Inlet pressure drops must be deducted. Make sure that these drops, added to the difference in level (max. 3.2m), are less than 4.5m
The values shown identify performance levels according to the reference standard EN12845.
HYDRA
ULIC PERFORMANCE T
ABLE A
T 50 HZ (SUCTION LIF
T)
HYDRAULIC
TABLE
AT
LIFT)
TABELLA DI PRESTAZIONI IDRAULICHE NETTE GRUPPI EN12845 SERIE FHF65 2 poli 50 Hz 1 POMPA DI SERVIZIO, ASP ESCLUSA INST SOTTOB
GEN../FHF 65 BOOSTER SETS SERIES
RATED
FHF..
POWER
ELECTRIC
PUMP
PUMP
OH4n
TYPE
OH3n
RISK CLASS
Q = DELIVERY
l/min 0
800
900
1000
1100
1200
1350
1400
1500
1800
2000
2100
2300
m3/h 0
48
54
60
66
72
81
84
90
108
120
126
138
kW
65-125/40
65-125/D121
1x4
19,1
15,6
14,6
13,5
12,3
10,9
8,7
7,9
6,2
65-125/55
65-125/D129
1 x 5,5
22,7
19,6
18,8
17,8
16,7
15,5
13,5
12,7
11,2
5,7
65-125/75
65-125/D140
1 x 7,5
27,1
24,3
23,5
22,7
21,7
20,7
18,9
18,2
16,8
12,0
8,1
65-160/110A 65-160/D161
1 x 11
32,7
29,2
28,3
27,2
26,0
23,9
23,2
21,6
15,9
11,5
9,0
65-160/110
1 x 11
35,9
32,5
31,5
30,5
29,4
27,4
26,7
25,2
19,8
15,6
13,3
65-160/D168
65-160/150
65-160/D178
1 x 15
41,9
38,9
38,1
37,1
36,1
34,2
33,6
32,2
27,2
23,2
21,1
65-200/150
65-200/D187
1 x 15
45,2
43,4
42,3
41,1
39,7
37,3
36,4
34,6
28,4
23,8
21,3
65-200/185
65-200/D198
1 x 18,5
51,6
50,2
49,2
48,2
47,0
44,9
44,1
42,4
36,5
31,8
29,2
65-200/220
65-200/D210
1 x 22
59,1
57,2
56,3
55,3
54,2
52,1
51,4
49,8
44,1
39,6
37,1
65-250/220
65-250/D220
1 x 22
62,8
60,6
59,4
58,0
56,4
53,5
52,5
50,2
42,1
35,7
32,1
16,3
31,6
65-250/300
65-250/D241
1 x 30
76,4
75,0
73,9
72,6
71,1
68,5
67,5
65,4
57,8
51,6
48,2
40,6
65-250/370
65-250/D258
1 x 37
90,8
89,9
89,0
88,0
86,7
84,5
83,7
81,8
74,8
68,8
65,4
57,7
Performance levels relative to set with 1 service pump running and compliant with ISO 9906 - Annex A.
OHn = class of risk value referred to the required rated capacity (Tab.6 para 7.3.1 EN12845)
Inlet pressure drops must be deducted. Make sure these drops are less than 4.5m
The values shown identify performance levels according to the reference standard EN12845.
38
12845_1pg-st-fhf65-2p50-en_a_th
Lowara
NPSH
REQUIRED FOR PUMP SERIES FHF 65
TABELLA DI PRESTAZIONI IDRAULICHE NPSHr GRUPPI EN12845 SERIE FHF65 2 poli 50 Hz 1 POMPA DI SERVIZIO
POWER
Q = DELIVERY
l/min 0
ELECTRIC
PUMP
PUMP
OH4m
FHF..
OH4n
RATED
OH3n
TYPE
OH3m
RISK CLASS
m /h 0
800
900
1000
1100
1200
1350
1400
1500
1800
2000
2100
2300
48
54
60
66
72
81
84
90
108
120
126
138
kW
65-125/40
65-125/D121
1x4
1,0
1,2
1,3
1,6
1,9
2,4
2,6
3,1
65-125/55
65-125/D129
1 x 5,5
1,0
1,2
1,3
1,6
1,9
2,4
2,6
3,1
5,1
65-125/75
65-125/D140
1 x 7,5
1,0
1,2
1,3
1,6
1,9
2,4
2,6
3,1
5,1
7,0
65-160/110A 65-160/D161
1 x 11
2,4
2,4
2,5
2,6
2,9
2,9
3,2
4,2
5,3
6,0
65-160/110
65-160/D168
1 x 11
2,3
2,4
2,5
2,7
2,8
2,9
3,1
3,7
4,4
4,9
65-160/150
65-160/D178
1 x 15
2,3
2,4
2,5
2,7
2,8
2,9
3,1
3,7
4,4
4,9
65-200/150
65-200/D187
1 x 15
1,8
1,9
2,0
2,1
2,3
2,4
2,6
3,4
4,5
5,3
65-200/185
65-200/D198
1 x 18,5
1,8
1,9
2,0
2,1
2,3
2,4
2,6
3,4
4,3
4,9
65-200/220
65-200/D210
1 x 22
1,8
1,9
2,0
2,1
2,3
2,4
2,6
3,4
4,3
4,9
65-250/220
65-250/D220
1 x 22
1,7
2,0
2,2
2,5
2,9
3,1
3,4
4,3
5,0
5,4
65-250/300
65-250/D241
1 x 30
1,7
2,0
2,2
2,5
2,9
3,1
3,4
4,3
5,0
5,4
6,2
65-250/370
65-250/D258
1 x 37
1,7
2,0
2,2
2,5
2,9
3,1
3,4
4,3
5,0
5,4
6,2
The declared NPSH values were obtained in the laboratory and refer to a single service pump
OHn, OHm = class of risk value referred to the required rated and maximum capacity (Tab.6 para 7.3.1 EN12845)
Check that NPSHd NPSHr+1m is satisfied at the maximum requested capacity
39
6,6
6,6
12845_1p-fhf65-2p50_NPSHr-en_a_th
Lowara
HYDRA
ULIC PERFORMANCE
T
ABLE
T 50
SUCTION
HEAD)
HYDRAULIC
TABLE
AT
TABELLA DI PRESTAZIONI
IDRAULICHE NETTE GRUPPI EN12845
SERIEA
FHF80
2 poliHZ
50 Hz(POSITIVE
1 POMPA DI SERVIZIO,
ASP ESCLUSA INST
SOPRA
GEN../FHF 80 BOOSTER SETS SERIES
RATED
FHF..
POWER
ELECTRIC
PUMP
PUMP
HH1n
TYPE
OH4n
RISK CLASS
Q = DELIVERY
l/min 0
1500
1650
1800
2050
2100
2200
2300
2600
3216
3500
3600
3650
m3/h 0
90
99
108
123
126
132
138
156
193
210
216
219
kW
80-160/150
80-160/D163
1 x 15
32,9
30,2
29,1
27,8
25,4
24,9
23,8
22,7
18,8
9,4
4,4
80-160/185
80-160/D173
1 x 18,5
39,0
35,6
34,5
33,4
31,2
30,7
29,7
28,6
25,1
16,2
11,3
80-200/220
80-200/D189
1 x 22
48,0
44,7
43,4
41,8
39,0
38,3
37,0
35,6
30,9
19,2
12,8
80-200/300
80-200/D207
1 x 30
59,9
56,9
55,8
54,4
51,9
51,3
50,1
48,9
44,7
34,2
28,5
80-250/370
80-250/D225
1 x 37
70,8
67,3
65,8
63,9
60,4
59,6
57,9
56,1
50,1
34,7
26,1
9,5
8,5
26,4
25,3
80-250/450
80-250/D238
1 x 45
80,0
78,0
76,5
74,8
71,5
70,8
69,2
67,6
62,0
47,5
39,6
36,5
80-250/550
80-250/D256
1 x 55
88,9
89,9
88,8
87,5
84,8
84,2
82,9
81,5
76,7
64,0
56,7
54,0
52,6
Performance levels relative to set with 1 service pump running and compliant with ISO 9906 - Annex A.
12845_1pg-sp-fhf80-2p50-en_a_th
OHn, HHn = class of risk value referred to the required rated capacity (Tab.6 para 7.3.1, Tab.7 para 7.3.2 EN12845)
Inlet pressure drops must be deducted. Make sure that these drops, added to the difference in level (max. 3.2m), are less than 4.5m
The values shown identify performance levels according to the reference standard EN12845.
HYDRA
ULIC PERFORMANCE
T
ABLE
(SUCTION
LIF
T)
HYDRAULIC
TABLE
AT
LIFT)
TABELLA DI PRESTAZIONI
IDRAULICHE NETTE GRUPPI EN12845
SERIE FHF80A
2T
poli50
50 Hz HZ
1 POMPA
DI SERVIZIO, ASP ESCLUSA
INST SOTTO
GEN../FHF 80 BOOSTER SETS SERIES
RATED
FHF..
POWER
ELECTRIC
PUMP
PUMP
HH1n
TYPE
OH4n
RISK CLASS
Q = DELIVERY
l/min 0
1500
1650
1800
2050
2100
2200
2300
2600
3216
3500
3600
3650
m3/h 0
90
99
108
123
126
132
138
156
193
210
216
219
kW
80-160/150
80-160/D163
1 x 15
32,9
30,2
29,1
27,8
25,4
24,9
23,8
22,7
18,8
9,4
4,4
80-160/185
80-160/D173
1 x 18,5
39,0
35,6
34,5
33,4
31,2
30,7
29,7
28,6
25,1
16,2
11,3
80-200/220
80-200/D189
1 x 22
48,0
44,7
43,4
41,8
39,0
38,3
37,0
35,6
30,9
19,2
12,8
80-200/300
80-200/D207
1 x 30
59,9
56,9
55,8
54,4
51,9
51,3
50,1
48,9
44,7
34,2
28,5
80-250/370
80-250/D225
1 x 37
70,8
67,3
65,8
63,9
60,4
59,6
57,9
56,1
50,1
34,7
26,1
9,5
8,5
26,4
25,3
80-250/450
80-250/D238
1 x 45
80,0
78,0
76,5
74,8
71,5
70,8
69,2
67,6
62,0
47,5
39,6
36,5
80-250/550
80-250/D256
1 x 55
88,9
89,9
88,8
87,5
84,8
84,2
82,9
81,5
76,7
64,0
56,7
54,0
Performance levels relative to set with 1 service pump running and compliant with ISO 9906 - Annex A.
OHn, HHn = class of risk value referred to the required rated capacity (Tab.6 para 7.3.1, Tab.7 para 7.3.2 EN12845)
Inlet pressure drops must be deducted. Make sure these drops are less than 4.5m
The values shown identify performance levels according to the reference standard EN12845.
40
52,6
12845_1pg-st-fhf80-2p50-en_a_th
Lowara
NPSH
REQUIRED FOR PUMP SERIES FHF 80
TABELLA DI PRESTAZIONI IDRAULICHE NPSHr GRUPPI EN12845 SERIE FHF80 2 poli 50 Hz 1 POMPA DI SERVIZIO
POWER
ELECTRIC
PUMP
PUMP
HH1m
FHF..
HH1n
RATED
OH4n
TYPE
OH4m
RISK CLASS
Q = DELIVERY
l/min 0
1500
1650
1800
2050
2100
2200
2300
2600
3216
3500
3600
3650
3
m /h 0
90
99
108
123
126
132
138
156
193
210
216
219
6,5
6,8
6,9
7,3
kW
80-160/150
80-160/D163
1 x 15
3,7
3,8
3,9
4,0
4,1
4,2
4,2
4,5
5,4
6,2
80-160/185
80-160/D173
1 x 18,5
3,7
3,8
3,9
4,0
4,1
4,2
4,2
4,5
5,4
6,2
80-200/220
80-200/D189
1 x 22
2,8
3,0
3,1
3,3
3,4
3,5
3,6
3,9
5,1
6,3
80-200/300
80-200/D207
1 x 30
2,8
3,0
3,1
3,3
3,4
3,5
3,6
3,9
5,1
6,3
80-250/370
80-250/D225
1 x 37
3,0
3,1
3,3
3,6
3,6
3,8
3,9
4,4
6,0
7,4
80-250/450
80-250/D238
1 x 45
2,4
2,6
2,7
3,0
3,1
3,2
3,3
3,8
4,9
5,5
5,7
80-250/550
80-250/D256
1 x 55
2,4
2,6
2,7
3,0
3,1
3,2
3,3
3,8
4,9
5,5
5,7
The declared NPSH values were obtained in the laboratory and refer to a single service pump
OHn, OHm, HHn, HHm = class of risk value referred to the required rated and maximum capacity (Tab.6 para 7.3.1, Tab.7 para 7.3.2 EN12845)
Check that NPSHd NPSHr+1m is satisfied at the maximum requested capacity
41
5,8
12845_1p-fhf80-2p50_NPSHr-en_a_th
Lowara
HYDRA
ULIC PERFORMANCE T
ABLE A
T 50 HZ (POSITIVE SUCTION HEAD)
HYDRAULIC
TABLE
AT
GEN../FHF 100 BOOSTER SETS SERIES
POWER
ELECTRIC
PUMP
PUMP
HH4n
FHF..
HH3n
RATED
HH2n
TYPE
HH1n
RISK CLASS
l/min 0
1333
1500
1667
2300
2900
3050
3216
3800
4066
4266
4333
5000
5166
5316
5500
6000
m3/h 0
80
90
100
138
174
183
193
228
244
256
260
300
310
319
330
360
Q = DELIVERY
kW
100-160/185
100-160/D150
1 x 18,5
26,7
26,0
19,9
19,0 18,0
9,6
3,5
1,8
100-160/220
100-160/D165
1 x 22
33,0
32,2
25,3
24,4 23,3
7,6
5,9
100-160/300
100-160/D185
1 x 30
42,3
41,2
34,6
33,6 32,5
100-200/185
100-200/D168
1 x 18,5
36,3
23,5
22,0 20,3
13,5 10,1
100-200/300
100-200/D192
1 x 30
49,0
39,5
38,3 36,8
100-200/370
100-200/D203
1 x 37
56,0
46,9
45,8 44,4
100-200/450
100-200/D213
1 x 45
61,0
53,6
52,6 51,4
100-250/300
100-250/D200
1 x 30
54,6
52,1 47,7
41,8
40,0 37,9
100-250/450
100-250/D221
1 x 45
68,8
66,9 63,5
58,7
57,2 55,4
100-250/550
100-250/D235
1 x 55
78,5
76,9 74,0
69,8
68,5 66,9
7,4
4,2
2,2
5,3
6,4
5,9
FHF..
POWER
ELECTRIC
PUMP
PUMP
Q = DELIVERY
l/min 0
1667
2500
3800
4150
4550
4700
4800
5000
5316
5500
6000
6366
6416
6500
6716
6750
m3/h 0
100
150
228
249
273
282
288
300
319
330
360
382
385
390
403
405
kW
100-250/750
100-250/D254
1 x 75
100-250/900
100-250/D267
1 x 90
HH6n
RATED
HH5n
TYPE
HH4n
RISK CLASS
90,5
66,1
63,7 62,1
102,9 101,6
91,7
77,9
75,6 74,0
Performance levels relative to set with 1 service pump running and compliant with ISO 9906 - Annex A.
HHn = class of risk value referred to the required rated capacity (Tab.7 para 7.3.2 EN12845)
Inlet pressure drops must be deducted. Make sure that these drops, added to the difference in level (max. 3.2m), are less than 4.5m
The values shown identify performance levels according to the reference standard EN12845.
31,1
12845_1pg-sp-fhf100-2p50-en_a_th
HYDRA
ULIC PERFORMANCE T
ABLE A
T 50 HZ (SUCTION LIF
T)
HYDRAULIC
TABLE
AT
LIFT)
GEN../FHF 100 BOOSTER SETS SERIES
POWER
ELECTRIC
PUMP
PUMP
HH4n
FHF..
HH3n
RATED
HH2n
TYPE
HH1n
RISK CLASS
l/min 0
1333
1500
1667
2300
2900
3050
3216
3800
4066
4266
4333
5000
5166
5316
5500
6000
m3/h 0
80
90
100
138
174
183
193
228
244
256
260
300
310
319
330
360
Q = DELIVERY
kW
100-160/185
100-160/D150
1 x 18,5
26,7
26,8
26,6
26,4 25,0
23,1
22,6 21,9
19,3
100-160/220
100-160/D165
1 x 22
33,0
33,0
32,7
32,4 30,8
28,6
28,0 27,2
24,3
100-160/300
100-160/D185
1 x 30
42,3
42,0
41,8
41,5 39,9
37,8
37,2 36,5
33,6
100-200/185
100-200/D168
1 x 18,5
36,3
34,5
33,9 30,7
26,7
25,6 24,2
18,9
100-200/300
100-200/D192
1 x 30
49,0
48,5
48,1 45,8
42,8
41,9 40,8
36,4
100-200/370
100-200/D203
1 x 37
56,0
55,5
55,2 53,1
50,2
49,3 48,3
44,1
100-200/450
100-200/D213
1 x 45
61,0
61,0
60,7 59,2
56,9
56,2 55,3
51,7
100-250/300
100-250/D200
1 x 30
54,6
53,3 49,8
45,0
43,5 41,8
34,7
100-250/450
100-250/D221
1 x 45
68,8
68,1 65,6
61,9
60,8 59,4
53,5
100-250/550
100-250/D235
1 x 55
78,5
78,1 76,2
73,0
72,0 70,8
65,6
18,2
FHF..
POWER
ELECTRIC
PUMP
PUMP
Q = DELIVERY
l/min 0
1667
2500
3800
4150
4550
4700
4800
5000
5316
5500
6000
6366
6416
6500
6716
6750
m3/h 0
100
150
228
249
273
282
288
300
319
330
360
382
385
390
403
405
kW
100-250/750
100-250/D254
1 x 75
100-250/900
100-250/D267
1 x 90
HH6n
RATED
HH5n
TYPE
HH4n
RISK CLASS
89,4
81,3
78,1
73,7
71,8 70,6
91,7
91,7
92,9
89,8
85,5
83,7 82,5
Performance levels relative to set with 1 service pump running and compliant with ISO 9906 - Annex A.
HHn = class of risk value referred to the required rated capacity (Tab.7 para 7.3.2 EN12845)
Inlet pressure drops must be deducted. Make sure these drops are less than 4.5m
The values shown identify performance levels according to the reference standard EN12845.
42
47,3
12845_1pg-st-fhf100-2p50-en_a_th
Lowara
NPSH REQUIRED FOR PUMP SERIES FHF 100
HH4m
HH3m
HH2m
HH4n
POWER
HH1m
FHF..
HH3n
RATED
HH2n
TYPE
HH1n
RISK CLASS
Q = DELIVERY
l/min 0 1333 1500 1667 2300 2900 3050 3216 3800 4066 4266 4333 5000 5166 5316 5500 6000
ELECTRIC
100-160/185
100-160/220
100-160/300
100-200/185
100-200/300
100-200/370
100-200/450
100-250/300
100-250/450
100-250/550
m3/h 0
PUMP
PUMP
80
90
100
138
100-160/D150
100-160/D165
100-160/D185
100-200/D168
100-200/D192
100-200/D203
100-200/D213
100-250/D200
100-250/D221
100-250/D235
1 x 18,5
1 x 22
1 x 30
1 x 18,5
1 x 30
1 x 37
1 x 45
1 x 30
1 x 45
1 x 55
174
183
193
228
244
256
260
300
310
319
330
360
kW
6,3
5,0
5,0
6,4
5,2
5,2
4,2
3,1
3,1
3,1
6,6
5,4
5,4
4,2
3,1
3,1
3,1
4,7
4,6
4,6
7,3
6,2
6,2
4,6
3,3
3,3
3,3
5,0
4,7
4,7
8,0
6,9
6,9
5,6
3,5
3,5
3,5
5,3
4,7
4,7
8,2
7,0
7,0
6,0
3,6
3,6
3,6
5,4
4,8
4,8
8,4
7,2
7,2
6,5
3,7
3,7
3,7
5,4
4,8
4,8
9,2
7,9
7,9
9,2
4,2
4,2
4,2
5,7
4,8
4,8
HH5m
POWER
HH4m
FHF..
HH6n
RATED
HH5n
TYPE
HH4n
RISK CLASS
Q = DELIVERY
l/min 0 1667 2500 3800 4150 4550 4700 4800 5000 5316 5500 6000 6366 6416 6500 6716 6750
ELECTRIC
100-250/750
100-250/900
m3/h 0 100
PUMP
PUMP
150
228
249
100-250/D254
100-250/D267
1 x 75
1 x 90
273
282
288
300
319
330
360
382
385
390
403
405
6,6
6,6
6,7
6,7
6,9
7,8
7,9
kW
4,6
4,6
4,7
4,7
4,8
4,8
4,9
4,9
5,0
5,0
5,0
5,0
5,0
5,0
5,1
5,1
5,2
5,2
The declared NPSH values were obtained in the laboratory and refer to a single service pump
HHn, HHm = class of risk value referred to the required rated and maximum capacity (Tab.7 para 7.3.2 EN12845)
Check that NPSHd NPSHr+1m is satisfied at the maximum requested capacity
43
5,3
5,3
5,8
5,8
12845_1p-fhf100-2p50_NPSHr-en_a_th
Lowara
HYDRA
ULIC PERFORMANCE T
ABLE A
T 50 HZ (POSITIVE SUCTION HEAD)
HYDRAULIC
TABLE
AT
TABELLA DI PRESTAZIONI IDRAULICHE NETTE GRUPPI EN12845 SERIE FHF125 2 poli 50 Hz 1 POMPA DI SERVIZIO, ASP ESCLUSA INST SOPRA
GEN../FHF 125 BOOSTER SETS SERIES
0
384
403
360
342
291
m3/h 0 120
kW
PUMP
PUMP
ELECTRIC
6716 6783 7500 7983 8400 8667 8966 9333 9583 10000 10333 10833
6400
6000
5700
Q = DELIVERY
POWER
HH10n
4850
FHF..
HH9n
RATED
HH6n
TYPE
HH8n
RISK CLASS
HH7n
150
288
407
450
479
504
520
538
560
575
600
620
650
125-200/300
125-200/D180
1 x 30
19,8
19,6
15,8
14,4
125-200/450
125-200/D206
1 x 45
34,8
34,6
30,3
28,6
7,6
125-200/550
125-200/D216
1 x 55
45,6
45,4
41,0
39,3
125-270/750
125-270/D224
1 x 75
65,1
63,7
56,0
55,8
51,5
49,8
47,3 45,3 44,8 39,8 36,1 32,7 30,5 27,9 24,6 22,3
125-270/900
125-270/D237
1 x 90
75,3
73,6
67,0
66,8
62,8
61,1
58,8 56,8 56,3 51,2 47,4 43,8 41,4 38,5 34,8 32,2
27,5
125-270/1100 125-270/D253
1 x 110
88,2
85,4
79,2
79,0
75,1
73,5
71,2 69,2 68,8 63,5 59,5 55,7 53,0 49,9 45,8 42,8
37,6
33,1
125-270/1320 125-270/D266
1 x 132
97,5
94,8
88,6
88,4
84,7
83,2
81,1 79,2 78,8 74,0 70,3 66,8 64,5 61,7 58,0 55,4
50,7
46,8
Performance levels relative to set with 1 service pump running and compliant with ISO 9906 - Annex A.
HHn = class of risk value referred to the required rated capacity (Tab.7 para 7.3.2 EN12845)
Inlet pressure drops must be deducted. Make sure that these drops, added to the difference in level (max. 3.2m), are less than 4.5m
The values shown identify performance levels according to the reference standard EN12845.
40,5
12845_1pg-sp-fhf125-2p50-en_a_th
HYDRA
ULIC PERFORMANCE T
ABLE A
T 50 HZ (SUCTION LIF
T)
HYDRAULIC
TABLE
AT
LIFT)
TABELLA DI PRESTAZIONI IDRAULICHE NETTE GRUPPI EN12845 SERIE FHF125 2 poli 50 Hz 1 POMPA DI SERVIZIO, ASP ESCLUSA INST SOTTOB
GEN../FHF 125 BOOSTER SETS SERIES
0
342
291
PUMP
403
m3/h 0 120
kW
ELECTRIC
384
360
PUMP
Q = DELIVERY
POWER
6716 6783 7500 7983 8400 8667 8966 9333 9583 10000 10333 10833
4850
FHF..
6400
RATED
HH10n
6000
TYPE
HH9n
5700
HH7n
HH8n
RISK CLASS
HH6n
150
288
407
450
479
504
520
538
560
575
600
620
650
125-200/300
125-200/D180
1 x 30
22,2
22,0
19,1
18,0
125-200/450
125-200/D206
1 x 45
37,1
37,0
33,5
32,2
125-200/550
125-200/D216
1 x 55
48,0
47,8
44,2
42,8
125-270/750
125-270/D224
1 x 75
65,1
64,4
58,4
58,2
54,7
53,3
51,3 49,7 49,3 45,2 42,2 39,5 37,6 35,5 32,8 30,9
125-270/900
125-270/D237
1 x 90
75,3
74,4
69,3
69,2
66,0
64,7
62,8 61,2 60,8 56,6 53,5 50,5 48,5 46,1 43,0 40,8
36,9
125-270/1100 125-270/D253
1 x 110
88,2
86,2
81,5
81,4
78,4
77,1
75,2 73,6 73,2 68,9 65,6 62,4 60,1 57,5 54,0 51,5
47,0 43,1
125-270/1320 125-270/D266
1 x 132
97,5
95,5
90,9
90,8
88,0
86,8
85,1 83,6 83,3 79,4 76,4 73,5 71,6 69,3 66,2 64,0
60,1 56,8
Performance levels relative to set with 1 service pump running and compliant with ISO 9906 - Annex A.
HHn = class of risk value referred to the required rated capacity (Tab.7 para 7.3.2 EN12845)
Inlet pressure drops must be deducted. Make sure these drops are less than 4.5m
The values shown identify performance levels according to the reference standard EN12845.
51,4
12845_1pg-st-fhf125-2p50-en_a_th
TABELLA DI PRESTAZIONI IDRAULICHE NPSHr EN12845 SERIE FHF125 2 poli 50 Hz 1 POMPA DI SERVIZIO
PUMP
HH8m
HH9m
l/min 0
2000
2500
4800
4850
5700
6000
6400
6716
6783
7500
7983
8400
8667
8966
9333
9583
m3/h 0
120
150
288
291
342
360
384
403
407
450
479
504
520
538
560
575
HH7m
HH6m
PUMP
HH10n
ELECTRIC
HH9n
POWER
HH8n
FHF..
HH7n
RATED
HH6n
TYPE
HH10m
RISK CLASS
Q = DELIVERY
10000 10333 10833
600
620
650
kW
125-200/300
125-200/D180
1 x 30
6,5
6,8
8,5
8,5
9,1
9,3
9,6
9,9
9,9
10,4
125-200/450
125-200/D206
1 x 45
6,1
6,2
7,1
7,1
7,6
7,7
8,0
8,3
8,3
8,9
9,5
10,0
10,4
125-200/550
125-200/D216
1 x 55
6,1
6,2
7,1
7,1
7,6
7,7
8,0
8,3
8,3
8,9
9,5
10,0
10,4
10,8
11,5
125-270/750
125-270/D224
1 x 75
7,8
8,3
8,3
8,5
8,6
8,7
8,8
8,9
9,3
9,7
10,1
10,5
11,1
11,9
12,7
125-270/900
125-270/D237
1 x 90
6,0
6,9
6,9
7,2
7,3
7,5
7,7
7,7
8,1
8,4
8,8
9,0
9,4
9,9
10,4
11,4
125-270/1100 125-270/D253
1 x 110
6,0
6,9
6,9
7,2
7,3
7,5
7,7
7,7
8,1
8,4
8,8
9,0
9,4
9,9
10,4
11,4
12,5
125-270/1320 125-270/D266
1 x 132
6,0
6,9
6,9
7,2
7,3
7,5
7,7
7,7
8,1
8,4
8,8
9,0
9,4
9,9
10,4
11,4
12,5
The declared NPSH values were obtained in the laboratory and refer to a single service pump
HHn, HHm = class of risk value referred to the required rated and maximum capacity (Tab.7 para 7.3.2 EN12845)
Check that NPSHd NPSHr+1m is satisfied at the maximum requested capacity
44
14,8
12845_1p-fhf125-2p50_NPSHr-en_a_th
Lowara
GEN../FHF 32-80 BOOSTER SETS
TABELLA DATI ELETTRICI GRUPPI GEN../FHF 2 poli 50 Hz
ELECTRICAL DA
TA T
ABLE A
T 50 Hz
DAT
TABLE
AT
ELECTRIC
SERVICE PUMP
3 X 400 V
TYPE
FHF..
ELECTRIC
PUMP
32-125/07
32-125/11
32-160/15
32-160/22
32-200/30
32-200/40
40-125/11
40-125/15
40-125/22
40-160/30
40-160/40
40-200/55
40-200/75
40-250/110A
40-250/110
40-250/150
50-125/22
50-125/30
50-125/40
50-160/55
50-160/75
50-200/110A
50-200/110
50-250/150
50-250/185
50-250/220
65-125/40
65-125/55
65-125/75
65-160/110A
65-160/110
65-160/150
65-200/150
65-200/185
65-200/220
65-250/220
65-250/300
65-250/370
80-160/150
80-160/185
80-200/220
80-200/300
80-250/370
80-250/450
80-250/550
PUMP
32-125/D119
32-125/D136
32-160/D150
32-160/D164
32-200/D188
32-200/D204
40-125/D112
40-125/D122
40-125/D143
40-160/D159
40-160/D171
40-200/D190
40-200/D209
40-250/D218
40-250/D233
40-250/D251
50-125/D119
50-125/D130
50-125/D139
50-160/D158
50-160/D174
50-200/D197
50-200/D209
50-250/D224
50-250/D237
50-250/D250
65-125/D121
65-125/D129
65-125/D140
65-160/D161
65-160/D168
65-160/D178
65-200/D187
65-200/D198
65-200/D210
65-250/D220
65-250/D241
65-250/D258
80-160/D163
80-160/D173
80-200/D189
80-200/D207
80-250/D225
80-250/D238
80-250/D256
ELECTRIC
CURRENT
JOCKEY PUMP
3 X 400 V
ABSORBED SET
3 X 400V
NOMINAL
POWER
Pn
kW
In
A
TYPE
Pn
kW
In
A
GEN..10
A
GEN..11
A
GEN..20
A
GEN..21
A
0,75
1,1
1,5
2,2
3
4
1,1
1,5
2,2
3
4
5,5
7,5
11
11
15
2,2
3
4
5,5
7,5
11
11
15
18,5
22
4
5,5
7,5
11
11
15
15
18,5
22
22
30
37
15
18,5
22
30
37
45
55
2,15
2,61
3,02
4,68
5,77
7,59
2,61
3,02
4,68
5,77
7,59
10,70
13,90
19,80
19,80
26,20
4,68
5,77
7,59
10,70
13,90
19,80
19,80
26,20
33,40
41,70
7,59
10,70
13,90
19,80
19,80
26,20
26,20
33,40
41,70
41,70
54,00
65,00
26,20
33,40
41,70
54,00
65,00
80,00
99,00
SV206
SV206
SV206
SV206
SV206
SV209
SV206
SV206
SV206
SV206
SV206
SV206
SV209
SV209
SV209
SV209
SV206
SV206
SV206
SV206
SV206
SV209
SV209
SV209
SV209
SV209
SV206
SV206
SV206
SV206
SV206
SV206
SV206
SV209
SV209
SV209
SV209
SV212
SV407
SV407
SV407
SV409
SV409
SV409
SV413
0,75
0,75
0,75
0,75
0,75
1,1
0,75
0,75
0,75
0,75
0,75
0,75
1,1
1,1
1,1
1,1
0,75
0,75
0,75
0,75
0,75
1,1
1,1
1,1
1,1
1,1
0,75
0,75
0,75
0,75
0,75
0,75
0,75
1,1
1,1
1,1
1,1
1,5
1,1
1,1
1,1
1,5
1,5
1,5
2,2
2,02
2,02
2,02
2,02
2,02
2,61
2,02
2,02
2,02
2,02
2,02
2,02
2,61
2,61
2,61
2,61
2,02
2,02
2,02
2,02
2,02
2,61
2,61
2,61
2,61
2,61
2,02
2,02
2,02
2,02
2,02
2,02
2,02
2,61
2,61
2,61
2,61
3,45
2,61
2,61
2,61
3,45
3,45
3,45
5,03
2,15
2,61
3,02
4,68
5,77
7,59
2,61
3,02
4,68
5,77
7,59
10,70
13,90
19,80
19,80
26,20
4,68
5,77
7,59
10,70
13,90
19,80
19,80
26,20
33,40
41,70
7,59
10,70
13,90
19,80
19,80
26,20
26,20
33,40
41,70
41,70
54,00
65,00
26,20
33,40
41,70
54,00
65,00
80,00
99,00
4,17
4,63
5,04
6,70
7,79
10,20
4,63
5,04
6,70
7,79
9,61
12,72
16,51
22,41
22,41
28,81
6,70
7,79
9,61
12,72
15,92
22,41
22,41
28,81
36,01
44,31
9,61
12,72
15,92
21,82
21,82
28,22
28,22
36,01
44,31
44,31
56,61
68,45
28,81
36,01
44,31
57,45
68,45
83,45
104,03
4,30
5,22
6,04
9,36
11,54
15,18
5,22
6,04
9,36
11,54
15,18
21,40
27,80
39,60
39,60
52,40
9,36
11,54
15,18
21,40
27,80
39,60
39,60
52,40
66,80
83,40
15,18
21,40
27,80
39,60
39,60
52,40
52,40
66,80
83,40
83,40
108,00
130,00
52,40
66,80
83,40
108,00
130,00
160,00
198,00
6,32
7,24
8,06
11,38
13,56
17,79
7,24
8,06
11,38
13,56
17,20
23,42
30,41
42,21
42,21
55,01
11,38
13,56
17,20
23,42
29,82
42,21
42,21
55,01
69,41
86,01
17,20
23,42
29,82
41,62
41,62
54,42
54,42
69,41
86,01
86,01
110,61
133,45
55,01
69,41
86,01
111,45
133,45
163,45
203,03
The current indicated is the maximum current absorbed by the electric pumps.
ENELP-FHF32-80_2p50-en_b_te
45
Lowara
GEN../FHF 100-125 BOOSTER SETS
TABELLA DATI ELETTRICI GRUPPI GEN../FHF 2 poli 50 Hz
ELECTRICAL DA
TA T
ABLE A
T 50 Hz
DAT
TABLE
AT
ELECTRIC
SERVICE PUMP
3 X 400 V
TYPE
FHF..
ELECTRIC
Pn
CURRENT
ABSORBED SET
3 X 400V
TYPE
Pn
In
GEN..10
GEN..11
GEN..20
GEN..21
kW
SV407
SV407
SV407
SV407
SV407
SV407
SV409
SV407
SV409
SV409
SV413
SV413
SV805
SV805
SV806
SV806
SV807
SV807
SV809
1,1
1,1
1,1
1,1
1,1
1,1
1,5
1,1
1,5
1,5
2,2
2,2
2,2
2,2
3
3
4
4
4
2,61
2,61
2,61
2,61
2,61
2,61
3,45
2,61
3,45
3,45
5,03
5,03
5,03
5,03
6,01
6,01
8,02
8,02
8,02
33,40
41,70
54,00
33,40
54,00
65,00
80,00
54,00
80,00
99,00
133,00
157,00
54,00
80,00
99,00
133,00
157,00
196,00
235,00
36,01
44,31
56,61
36,01
56,61
67,61
83,45
56,61
83,45
102,45
138,03
162,03
59,03
85,03
105,01
139,01
165,02
204,02
243,02
66,80
83,40
108,00
66,80
108,00
130,00
160,00
108,00
160,00
198,00
266,00
314,00
108,00
160,00
198,00
266,00
314,00
392,00
470,00
69,41
86,01
110,61
69,41
110,61
132,61
163,45
110,61
163,45
201,45
271,03
319,03
113,03
165,03
204,01
272,01
322,02
400,02
478,02
PUMP
PUMP
100-160/185
100-160/220
100-160/300
100-200/185
100-200/300
100-200/370
100-200/450
100-250/300
100-250/450
100-250/550
100-250/750
100-250/900
125-200/300
125-200/450
125-200/550
125-270/750
125-270/900
125-270/1100
125-270/1320
In
ELECTRIC
JOCKEY PUMP
3 X 400 V
100-160/D150
100-160/D165
100-160/D185
100-200/D168
100-200/D192
100-200/D203
100-200/D213
100-250/D200
100-250/D221
100-250/D235
100-250/D254
100-250/D267
125-200/D180
125-200/D206
125-200/D216
125-270/D224
125-270/D237
125-270/D253
125-270/D266
kW
18,5
22
30
18,5
30
37
45
30
45
55
75
90
30
45
55
75
90
110
132
33,40
41,70
54,00
33,40
54,00
65,00
80,00
54,00
80,00
99,00
133,00
157,00
54,00
80,00
99,00
133,00
157,00
196,00
235,00
The current indicated is the maximum current absorbed by the electric pumps.
ENELP-FHF100-125_2p50-en_b_te
46
Lowara
Fire-fighting
booster sets
EN 12845
MARKET SECTORS
CIVIL, INDUSTRIAL
APPLICA
TIONS
APPLICATIONS
Fixed fire-fighting systems.
GEN..10/FHF
Series
SPECIFICA
TIONS
SPECIFICATIONS
Flow up to 650 m3/h.
Head up to 100 m.
Panel supply power voltage:
3 x 400V 10%.
Motor start-up :
Frequency: 50 Hz.
Voltage for controls outside panel:
24 Vac.
Protection grade:
47
Lowara
GEN..10/FHF 32-80 SERIES
FIRE-FIGHTING BOOSTER SETS EN 12845
48
Lowara
GEN..10/FHF 32-80 SERIES
FIRE-FIGHTING BOOSTER SETS EN 12845
GEN..10
DRW
DNA
DNM
N
FHF32-125/07
R 2"
Rp 1" 1/2
740
80
212
360
820
773
1347
FHF32-125/11
R 2"
Rp 1" 1/2
740
80
212
360
820
773
1347
FHF32-160/15
R 2"
Rp 1" 1/2
840
80
232
390
920
813
1387
FHF32-160/22
R 2"
Rp 1" 1/2
840
80
232
390
920
813
1387
FHF32-200/30
R 2"
Rp 1" 1/2
840
80
260
390
920
861
1435
FHF32-200/40
R 2"
Rp 1" 1/2
840
80
260
390
920
861
1435
FHF40-125/11
65
65
740
80
212
360
820
994
1582
FHF40-125/15
65
65
840
80
212
390
920
994
1582
FHF40-125/22
65
65
840
80
212
390
920
994
1582
FHF40-160/30
65
65
840
80
232
390
920
1034
1622
FHF40-160/40
65
65
840
80
232
390
920
1034
1622
FHF40-200/55
65
65
940
100
260
450
1040
1082
1670
FHF40-200/75
65
65
940
100
260
450
1040
1082
1670
FHF40-250/110A
65
65
1175
100
280
540
1275
1147
1735
FHF40-250/110
65
65
1175
100
280
540
1275
1147
1735
FHF40-250/150
65
65
1175
100
280
540
1275
1147
1735
FHF50-125/22
65
65
840
100
232
390
940
1116
1704
FHF50-125/30
65
65
840
100
232
390
940
1116
1704
FHF50-125/40
65
65
840
100
232
390
940
1116
1704
FHF50-160/55
65
65
940
100
260
450
1040
1164
1752
FHF50-160/75
65
65
940
100
260
450
1040
1164
1752
FHF50-200/110A
65
65
1060
100
260
490
1160
1184
1772
FHF50-200/110
65
65
1060
100
260
490
1160
1184
1772
FHF50-250/150
65
65
1175
100
280
540
1275
1229
1817
FHF50-250/185
65
65
1175
100
280
540
1275
1229
1817
FHF50-250/220
65
65
1175
100
280
540
1275
1229
1817
FHF65-125/40
80
80
825
100
260
390
925
1221
1815
FHF65-125/55
80
80
925
100
260
450
1025
1221
1815
FHF65-125/75
80
80
925
100
260
450
1025
1221
1815
FHF65-160/110A
80
80
1175
100
260
540
1275
1241
1835
FHF65-160/110
80
80
1175
100
260
540
1275
1241
1835
FHF65-160/150
80
80
1175
100
260
540
1275
1241
1835
FHF65-200/150
80
80
1175
100
280
540
1275
1286
1880
FHF65-200/185
80
80
1175
100
280
540
1275
1286
1880
FHF65-200/220
80
80
1175
100
280
540
1275
1286
1880
FHF65-250/220
80
80
1160
100
310
540
1260
1341
1935
FHF65-250/300
80
80
1310
100
310
610
1410
1341
1935
FHF65-250/370
80
80
1310
100
310
610
1410
1341
1935
FHF80-160/150
100
100
1175
125
280
540
1300
1354
1961
FHF80-160/185
100
100
1175
125
280
540
1300
1354
1961
FHF80-200/220
100
100
1175
125
280
540
1300
1379
1986
FHF80-200/300
100
100
1325
125
310
610
1450
1409
2016
FHF80-250/370
100
100
1310
125
310
610
1435
1439
2046
FHF80-250/450
100
100
1310
125
365
610
1435
1494
2101
FHF80-250/550
2
100
Dimensions in mm. Tolerance 10 mm.
100
1510
125
390
660
1635
1519
2126
gen10_fhf-en_d_td
49
Lowara
GEN..10/FHF 100-125 SERIES
FIRE-FIGHTING BOOSTER SETS EN 12845
GEN..10
DRW
DNM
FHF100-160/185
125
125
1266
125
298
550
1391
1518
2138
FHF100-160/220
125
125
1315
125
298
550
1440
1518
2138
FHF100-160/300
125
125
1435
125
298
550
1560
1518
2138
FHF100-200/185
125
125
1266
125
273
550
1391
1493
2113
FHF100-200/300
125
125
1435
125
273
550
1560
1493
2113
FHF100-200/370
125
125
1435
125
273
550
1560
1493
2113
FHF100-200/450
125
125
1470
125
318
670
1595
1538
2158
FHF100-250/300
125
125
1435
140
298
550
1575
1518
2138
FHF100-250/450
125
125
1470
140
298
550
1610
1518
2138
FHF100-250/550
125
125
1575
140
343
670
1715
1563
2183
FHF100-250/750
125
125
1650
140
373
740
1790
1593
2213
FHF100-250/900
125
125
1650
140
373
740
1790
1593
2213
FHF125-200/300
150
150
1495
140
323
550
1635
1675
2309
FHF125-200/450
150
150
1530
140
343
670
1670
1695
2329
FHF125-200/550
150
150
1635
140
343
670
1775
1695
2329
FHF125-270/750
150
150
1710
140
423
750
1850
1815
2449
FHF125-270/900
150
150
1710
140
423
750
1850
1815
2449
FHF125-270/1100
150
150
1850
140
478
870
1990
1870
2504
150
1850
140
478
870
1990
1870
2504
FHF125-270/1320
150
Dimensions in mm. Tolerance 10 mm.
gen10_fhf100-en_c_td
50
Lowara
Fire-fighting
booster sets
EN 12845
MARKET SECTORS
CIVIL, INDUSTRIAL
APPLICA
TIONS
APPLICATIONS
Fixed fire-fighting systems.
Automatic Sprinkler systems.
GEN..11/FHF
Series
SPECIFICA
TIONS
SPECIFICATIONS
Flow up to 650 m3/h.
Head up to 100 m.
Panel supply power voltage:
3 x 400V 10%.
Motor start-up :
Frequency: 50 Hz.
Voltage for controls outside panel:
24 Vac.
ey pump
Electric jock
jockey
Protection grade:
51
Lowara
GEN..11/FHF 32-80 SERIES
FIRE-FIGHTING BOOSTER SETS EN 12845
52
Lowara
GEN..11/FHF 32-80 SERIES
FIRE-FIGHTING BOOSTER SETS EN 12845
GEN..11
DRW DNA
DNP
DNM
A1
N
FHF32-125/07
R 2"
Rp 1"
260
240
590
45
225
950
955
873 1447
FHF32-125/11
R 2"
Rp 1"
260
240
590
45
225
950
955
873 1447
FHF32-160/15
R 2"
Rp 1"
253
240
650
65
225
FHF32-160/22
R 2"
Rp 1"
253
240
650
65
225
FHF32-200/30
R 2"
Rp 1"
253
240
650
65
225
FHF32-200/40
R 2"
Rp 1"
253
240
650
65
225
FHF40-125/11
65
Rp 1"
65
320
260
240
590
45
225
950
FHF40-125/15
65
Rp 1"
65
327
253
240
650
65
225
FHF40-125/22
65
Rp 1"
65
327
253
240
650
65
225
FHF40-160/30
65
Rp 1"
65
327
253
240
650
65
225
FHF40-160/40
65
Rp 1"
65
327
253
240
650
65
225
FHF40-200/55
65
Rp 1"
65
338
222
240
710
85
245
FHF40-200/75
65
Rp 1"
65
338
222
240
710
85
245
FHF40-250/110A
65
Rp 1"
65
435
295
280
890
105
245
FHF40-250/110
65
Rp 1"
65
435
295
280
890
105
245
FHF40-250/150
65
Rp 1"
65
435
295
280
890
105
245
FHF50-125/22
65
Rp 1"
65
327
253
240
650
65
225
FHF50-125/30
65
Rp 1"
65
327
253
240
650
65
225
FHF50-125/40
65
Rp 1"
65
327
253
240
650
65
225
FHF50-160/55
65
Rp 1"
65
338
222
240
710
85
245
FHF50-160/75
65
Rp 1"
65
338
222
240
710
85
245
FHF50-200/110A
65
Rp 1"
65
435
295
280
790
105
245
FHF50-200/110
65
Rp 1"
65
435
295
280
790
105
245
FHF50-250/150
65
Rp 1"
65
435
295
280
890
105
245
FHF50-250/185
65
Rp 1"
65
435
295
280
890
105
245
FHF50-250/220
65
Rp 1"
65
435
295
280
890
105
245
FHF65-125/40
80
Rp 1"
80
323
187
240
650
50
225
FHF65-125/55
80
Rp 1"
80
338
222
240
710
70
245
FHF65-125/75
80
Rp 1"
80
338
222
240
710
70
245
FHF65-160/110A
80
Rp 1"
80
435
295
280
890
105
245
FHF65-160/110
80
Rp 1"
80
435
295
280
890
105
245
FHF65-160/150
80
Rp 1"
80
435
295
280
890
105
245
FHF65-200/150
80
Rp 1"
80
435
295
280
890
105
245
FHF65-200/185
80
Rp 1"
80
435
295
280
890
105
245
FHF65-200/220
80
Rp 1"
80
435
295
280
890
105
245
FHF65-250/220
80
Rp 1"
80
435
295
280
890
90
245
FHF65-250/300
80
Rp 1"
80
430
250
280
990
115
245
FHF65-250/370
80
Rp 1"
80
430
250
280
990
115
245
FHF80-160/150
100
435
295
280
890
105
245
FHF80-160/185
100
435
295
280
890
105
245
FHF80-200/220
100
435
295
280
890
105
245
FHF80-200/300
100
430
250
280
990
130
245
FHF80-250/370
100
430
250
280
990
115
245
FHF80-250/450
100
430
250
330
990
115
245
FHF80-250/550
2
100 Rp 1" 1/4
Dimensions in mm. Tolerance 10 mm.
100
525
275
265
53
Lowara
GEN..11/FHF 100-125 SERIES
FIRE-FIGHTING BOOSTER SETS EN 12845
54
Lowara
GEN..11/FHF 100-125 SERIES
FIRE-FIGHTING BOOSTER SETS EN 12845
GEN..11
DRW DNA
DNP
DNM
A1
N
FHF100-160/185
125
Rp 1"1/4
125
411
269
291
890
85
245
418
FHF100-160/220
125
Rp 1"1/4
125
411
269
190
1020
105
245
418
FHF100-160/300
125
Rp 1"1/4
125
411
269
310
1020
105
245
418
FHF100-200/185
125
Rp 1"1/4
125
411
269
291
890
85
245
393
FHF100-200/300
125
Rp 1"1/4
125
411
269
310
1020
105
245
393
FHF100-200/370
125
Rp 1"1/4
125
411
269
310
1020
105
245
393
FHF100-200/450
125
Rp 1"1/4
125
451
249
215
1130
125
245
438
FHF100-250/300
125
Rp 1"1/4
125
411
269
310
1020
105
245
418
FHF100-250/450
125
Rp 1"1/4
125
411
269
345
1020
105
245
418
FHF100-250/550
125
Rp 1"1/4
125
451
249
320
1130
125
245
463
FHF100-250/750
125
Rp 1"1/4
125
620
220
400
1110
140
265
513
FHF100-250/900
125
Rp 1"1/4
125
620
220
400
1110
140
265
513
FHF125-200/300
150
Rp 1"1/2
150
411
269
370
1020
105
250
443
FHF125-200/450
150
Rp 1"1/2
150
451
249
275
1130
125
250
463
FHF125-200/550
150
Rp 1"1/2
150
451
249
380
1130
125
250
463
FHF125-270/750
150
Rp 1"1/2
150
620
220
370
1400
80
270
563
FHF125-270/900
150
Rp 1"1/2
150
620
220
370
1400
80
270
563
FHF125-270/1100
150
Rp 1"1/2
150
650
220
510
1400
80
270
618
FHF125-270/1320
3
150 Rp 1"1/2
Dimensions in mm. Tolerance 10 mm.
150
650
220
510
1400
80
270
618
gen11_fhf100-en_d_td
55
Lowara
56
Lowara
Fire-fighting
booster sets
EN 12845
MARKET SECTORS
CIVIL, INDUSTRIAL
APPLICA
TIONS
APPLICATIONS
Fixed fire-fighting systems.
Automatic Sprinkler systems.
GEN..20/FHF
Series
SPECIFICA
TIONS
SPECIFICATIONS
Flow up to 1300 m3/h.
Head up to 100 m.
Panel supply power voltage:
3 x 400V 10%.
Motor start-up :
Frequency: 50 Hz.
Voltage for controls outside panel:
24 Vac.
Protection grade:
12 bar.
57
Lowara
GEN..20/FHF 32-80 SERIES
FIRE-FIGHTING BOOSTER SETS EN 12845
58
Lowara
GEN..20/FHF 32-80 SERIES
FIRE-FIGHTING BOOSTER SETS EN 12845
GEN..20
DRW
DNA
DNM
Q
1459
N
FHF32-125/07
R 2"
R 2"
345
240
590
45
312
1400
480
1170
955
879
FHF32-125/11
R 2"
R 2"
345
240
590
45
312
1400
480
1170
955
879
1459
FHF32-160/15
R 2"
R 2"
345
240
650
65
332
1400
480
1170
1035
919
1499
FHF32-160/22
R 2"
R 2"
345
240
650
65
332
1400
480
1170
1035
919
1499
FHF32-200/30
R 2"
R 2"
345
240
650
65
360
1400
480
1170
1035
967
1547
FHF32-200/40
R 2"
R 2"
345
240
650
65
360
1400
480
1170
1035
967
1547
FHF40-125/11
65
65
335
240
590
45
312
1400
540
1210
955
1094
1682
FHF40-125/15
65
65
335
240
650
65
312
1400
540
1210
1035
1094
1682
FHF40-125/22
65
65
335
240
650
65
312
1400
540
1210
1035
1094
1682
FHF40-160/30
65
65
335
240
650
65
332
1400
540
1210
1035
1134
1722
FHF40-160/40
65
65
335
240
650
65
332
1400
540
1210
1035
1134
1722
FHF40-200/55
65
65
335
240
710
85
380
1420
540
1210
1135
1202
1790
FHF40-200/75
65
65
335
240
710
85
380
1420
540
1210
1135
1202
1790
FHF40-250/110A
65
65
385
280
890
105
400
1420
630
1400
1375
1267
1855
FHF40-250/110
65
65
385
280
890
105
400
1420
630
1400
1375
1267
1855
FHF40-250/150
65
65
385
280
890
105
400
1570
630
1400
1375
1267
1855
FHF50-125/22
65
80
335
240
650
65
332
1400
540
1210
1055
1223
1817
FHF50-125/30
65
80
335
240
650
65
332
1400
540
1210
1055
1223
1817
FHF50-125/40
65
80
335
240
650
65
332
1400
540
1210
1055
1223
1817
FHF50-160/55
65
80
335
240
710
85
380
1420
540
1210
1135
1291
1885
FHF50-160/75
65
80
335
240
710
85
380
1420
540
1210
1135
1291
1885
FHF50-200/110A
65
80
385
280
790
105
380
1420
630
1400
1275
1311
1905
FHF50-200/110
65
80
385
280
790
105
380
1420
630
1400
1275
1311
1905
FHF50-250/150
65
80
385
280
890
105
400
1570
630
1400
1375
1356
1950
FHF50-250/185
65
80
385
280
890
105
400
1750
630
1400
1375
1356
1950
FHF50-250/220
65
80
385
280
890
105
400
1750
630
1400
1375
1356
1950
FHF65-125/40
80
100
335
240
650
50
360
1400
540
1210
1040
1333
1940
FHF65-125/55
80
100
335
240
710
70
380
1420
540
1210
1120
1353
1960
FHF65-125/75
80
100
335
240
710
70
380
1420
540
1210
1120
1353
1960
FHF65-160/110A
80
100
350
280
890
105
380
1420
700
1400
1375
1373
1980
FHF65-160/110
80
100
350
280
890
105
380
1420
700
1400
1375
1373
1980
FHF65-160/150
80
100
350
280
890
105
380
1570
700
1400
1375
1373
1980
FHF65-200/150
80
100
350
280
890
105
400
1570
700
1400
1375
1418
2025
FHF65-200/185
80
100
350
280
890
105
400
1570
700
1400
1375
1418
2025
FHF65-200/220
80
100
350
280
890
105
400
1570
700
1400
1375
1418
2025
FHF65-250/220
80
100
350
280
890
90
430
1750
700
1400
1360
1473
2080
FHF65-250/300
80
100
425
280
990
115
430
1750
700
1550
1485
1473
2080
FHF65-250/370
80
100
425
280
990
115
430
1940
700
1550
1485
1473
2080
FHF80-160/150
100
125
350
280
890
105
400
1570
700
1400
1400
1487
2107
FHF80-160/185
100
125
350
280
890
105
400
1750
700
1400
1400
1487
2107
FHF80-200/220
100
125
350
280
890
105
400
1750
700
1400
1400
1512
2132
FHF80-200/300
100
125
425
280
990
130
430
1750
700
1550
1525
1542
2162
FHF80-250/370
100
125
425
280
990
115
430
1940
700
1550
1510
1572
2192
FHF80-250/450
100
125
425
330
990
115
485
1940
700
1550
1560
1627
2247
FHF80-250/550
2
100
Dimensions in mm. Tolerance 10 mm.
125
430
330
1120
155
530
1960
820
1680
1730
1672
2292
gen20_fhf-en_e_td
59
Lowara
60
Lowara
Fire-fighting
booster sets
EN 12845
MARKET SECTORS
CIVIL, INDUSTRIAL
APPLICA
TIONS
APPLICATIONS
Fixed fire-fighting systems.
Automatic Sprinkler systems.
GEN..21/FHF
Series
SPECIFICA
TIONS
SPECIFICATIONS
Flow up to 1300 m3/h.
Head up to 100 m.
Panel supply power voltage:
3 x 400V 10%.
Motor start-up :
Frequency: 50 Hz.
Voltage for controls outside panel:
24 Vac.
ey pump
Electric jock
jockey
Protection grade:
61
Lowara
GEN..21/FHF 32-80 SERIES
FIRE-FIGHTING BOOSTER SETS EN 12845
62
Lowara
GEN..21/FHF 32-80 SERIES
FIRE-FIGHTING BOOSTER SETS EN 12845
GEN..21
DRW
DNA
DNP
DNM
N
FHF32-125/07
R 2"
Rp 1"
R 2"
350
240
590
45
225
312
1400
370
1440
955
879
1459
FHF32-125/11
R 2"
Rp 1"
R 2"
350
240
590
45
225
312
1400
370
1440
955
879
1459
FHF32-160/15
R 2"
Rp 1"
R 2"
350
240
650
65
225
332
1400
370
1440 1035
919
1499
FHF32-160/22
R 2"
Rp 1"
R 2"
350
240
650
65
225
332
1400
370
1440 1035
919
1499
FHF32-200/30
R 2"
Rp 1"
R 2"
350
240
650
65
225
360
1400
370
1440 1035
967
1547
FHF32-200/40
R 2"
Rp 1"
R 2"
350
240
650
65
225
360
1400
370
1440 1035
967
1547
FHF40-125/11
65
Rp 1"
65
350
240
590
45
225
312
1400
370
1440
1094 1682
FHF40-125/15
65
Rp 1"
65
350
240
650
65
225
312
1400
370
FHF40-125/22
65
Rp 1"
65
350
240
650
65
225
312
1400
370
FHF40-160/30
65
Rp 1"
65
350
240
650
65
225
332
1400
370
FHF40-160/40
65
Rp 1"
65
350
240
650
65
225
332
1400
370
FHF40-200/55
65
Rp 1"
65
335
240
710
85
245
380
1420
440
FHF40-200/75
65
Rp 1"
65
335
240
710
85
245
380
1420
440
FHF40-250/110A
65
Rp 1"
65
400
280
890
105
245
400
1420
440
FHF40-250/110
65
Rp 1"
65
400
280
890
105
245
400
1420
440
FHF40-250/150
65
Rp 1"
65
400
280
890
105
245
400
1570
440
FHF50-125/22
65
Rp 1"
80
350
240
650
65
225
332
1400
370
FHF50-125/30
65
Rp 1"
80
350
240
650
65
225
332
1400
370
FHF50-125/40
65
Rp 1"
80
350
240
650
65
225
332
1400
370
FHF50-160/55
65
Rp 1"
80
335
240
710
85
245
380
1420
440
FHF50-160/75
65
Rp 1"
80
335
240
710
85
245
380
1420
440
FHF50-200/110A
65
Rp 1"
80
400
280
790
105
245
380
1420
440
FHF50-200/110
65
Rp 1"
80
400
280
790
105
245
380
1420
440
FHF50-250/150
65
Rp 1"
80
400
280
890
105
245
400
1570
440
FHF50-250/185
65
Rp 1"
80
400
280
890
105
245
400
1750
440
FHF50-250/220
65
Rp 1"
80
400
280
890
105
245
400
1750
440
FHF65-125/40
80
Rp 1"
100
335
240
650
50
225
360
1400
440
FHF65-125/55
80
Rp 1"
100
335
240
710
70
245
380
1420
440
FHF65-125/75
80
Rp 1"
100
335
240
710
70
245
380
1420
440
FHF65-160/110A
80
Rp 1"
100
400
280
890
105
245
380
1420
440
FHF65-160/110
80
Rp 1"
100
400
280
890
105
245
380
1420
440
FHF65-160/150
80
Rp 1"
100
400
280
890
105
245
380
1570
440
FHF65-200/150
80
Rp 1"
100
400
280
890
105
245
400
1570
440
FHF65-200/185
80
Rp 1"
100
400
280
890
105
245
400
1570
440
FHF65-200/220
80
Rp 1"
100
400
280
890
105
245
400
1570
440
FHF65-250/220
80
Rp 1"
100
400
280
890
90
245
430
1750
440
FHF65-250/300
80
Rp 1"
100
430
280
990
115
245
430
1750
490
FHF65-250/370
80
Rp 1"
100
430
280
990
115
245
430
1940
490
FHF80-160/150
100
Rp 1" 1/4
125
400
280
890
105
245
400
1570
440
FHF80-160/185
100
Rp 1" 1/4
125
400
280
890
105
245
400
1750
440
FHF80-200/220
100
Rp 1" 1/4
125
400
280
890
105
245
400
1750
440
FHF80-200/300
100
Rp 1" 1/4
125
430
280
990
130
245
430
1750
490
FHF80-250/370
100
Rp 1" 1/4
125
430
280
990
115
245
430
1940
490
FHF80-250/450
100
Rp 1" 1/4
125
430
330
990
115
245
485
1940
490
FHF80-250/550
2
100
Rp 1" 1/4
Dimensions in mm. Tolerance 10 mm.
125
450
330
1120
155
265
530
1960
600
955
gen21_fhf-en_e_td
63
Lowara
GEN..21/FHF 100-125 SERIES
FIRE-FIGHTING BOOSTER SETS EN 12845
64
Lowara
GEN..21/FHF 100-125 SERIES
FIRE-FIGHTING BOOSTER SETS EN 12845
GEN..21
DRW
DNA
DNP
DNM
N
FHF100-160/185
125
Rp 1"1/4
150
430
291
890
85
245
418
1750
490
FHF100-160/220
125
Rp 1"1/4
150
430
190
1020
105
245
418
1750
490
FHF100-160/300
125
Rp 1"1/4
200
430
310
1020
105
245
418
1750
490
FHF100-200/185
125
Rp 1"1/4
150
430
291
890
85
245
393
1750
490
FHF100-200/300
125
Rp 1"1/4
150
430
310
1020
105
245
393
1750
490
FHF100-200/370
125
Rp 1"1/4
150
430
310
1020
105
245
393
1750
490
FHF100-200/450
125
Rp 1"1/4
200
470
215
1130
125
245
438
1750
600
FHF100-250/300
125
Rp 1"1/4
150
430
310
1020
105
245
418
1750
490
FHF100-250/450
125
Rp 1"1/4
200
430
345
1020
105
245
418
1750
490
FHF100-250/550
125
Rp 1"1/4
200
470
320
1130
125
245
463
1750
600
FHF100-250/750
125
Rp 1"1/4
200
590
400
1110
140
265
513
600
FHF100-250/900
125
Rp 1"1/4
200
590
400
1110
140
265
513
600
FHF125-200/300
150
Rp 1"1/2
200
430
370
1020
105
250
443
1750
490
FHF125-200/450
150
Rp 1"1/2
200
470
275
1130
125
250
463
1750
600
FHF125-200/550
150
Rp 1"1/2
200
470
380
1130
125
250
463
1750
600
FHF125-270/750
150
Rp 1"1/2
250
590
370
1400
80
225
563
600
FHF125-270/900
150
Rp 1"1/2
250
590
370
1400
80
225
563
600
FHF125-270/1100
150
Rp 1"1/2
250
650
510
1400
80
225
618
650
FHF125-270/1320
3
150
Rp 1"1/2
Dimensions in mm. Tolerance 10 mm.
250
650
510
1400
80
225
618
650
65
Lowara
GEN../FHF 32-80 SERIES
DIMENSIONS FOR FL
OOR FIXING
FLOOR
66
Lowara
GEN../FHF 32-80 SERIES
DIMENSIONS FOR FL
OOR FIXING
FLOOR
GEN..10
PUMP
GEN..11
GEN..20
GEN..21
FHF 32-125/07
320
540
20
130
770
540
90
25
990
540
90
25
1260
540
90
25
FHF 32-125/11
320
540
20
130
770
540
90
25
990
540
90
25
1260
540
90
25
FHF 32-160/15
350
600
20
150
770
600
90
25
990
600
90
25
1260
600
90
25
FHF 32-160/22
350
600
20
150
770
600
90
25
990
600
90
25
1260
600
90
25
FHF 32-200/30
350
600
20
150
770
600
90
25
990
600
90
25
1260
600
90
25
FHF 32-200/40
350
600
20
150
770
600
90
25
990
600
90
25
1260
600
90
25
FHF 40-125/11
350
600
20
150
770
540
90
25
1030
600
90
25
1260
540
90
25
FHF 40-125/15
350
600
20
150
770
600
90
25
1030
600
90
25
1260
600
90
25
FHF 40-125/22
350
600
20
150
770
600
90
25
1030
600
90
25
1260
600
90
25
FHF 40-160/30
350
600
20
150
770
600
90
25
1030
600
90
25
1260
600
90
25
FHF 40-160/40
350
600
20
150
770
600
90
25
1030
600
90
25
1260
600
90
25
FHF 40-200/55
400
660
25
170
960
585
20
55
1170
585
20
55
1510
585
20
55
FHF 40-200/75
400
660
25
170
960
585
20
55
1170
585
20
55
1510
585
20
55
FHF 40-250/110A
490
840
25
205
1130
765
20
55
1360
765
20
55
1640
765
20
55
FHF 40-250/110
490
840
25
205
1130
765
20
55
1360
765
20
55
1640
765
20
55
FHF 40-250/150
490
840
25
205
1130
765
20
55
1360
765
20
55
1640
765
20
55
FHF 50-125/22
350
600
20
150
770
600
90
25
1030
600
90
25
1260
600
90
25
FHF 50-125/30
350
600
20
150
770
600
90
25
1030
600
90
25
1260
600
90
25
FHF 50-125/40
350
600
20
150
770
600
90
25
1030
600
90
25
1260
600
90
25
FHF 50-160/55
400
660
25
170
960
585
20
55
1170
585
20
55
1510
585
20
55
FHF 50-160/75
400
660
25
170
960
585
20
55
1170
585
20
55
1510
585
20
55
FHF 50-200/110A
440
740
25
190
1130
665
20
55
1360
665
20
55
1640
665
20
55
FHF 50-200/110
440
740
25
190
1130
665
20
55
1360
665
20
55
1640
665
20
55
FHF 50-250/150
490
840
25
205
1130
765
20
55
1360
765
20
55
1640
765
20
55
FHF 50-250/185
490
840
25
205
1130
765
20
55
1360
765
20
55
1640
765
20
55
FHF 50-250/220
490
840
25
205
1130
765
20
55
1360
765
20
55
1640
765
20
55
FHF 65-125/40
350
600
20
150
820
600
90
25
1030
600
90
25
1370
600
90
25
FHF 65-125/55
400
660
25
170
960
585
20
55
1170
585
20
55
1510
585
20
55
FHF 65-125/75
400
660
25
170
960
585
20
55
1170
585
20
55
1510
585
20
55
FHF 65-160/110A
490
840
25
205
1130
765
20
55
1360
765
20
55
1640
765
20
55
FHF 65-160/110
490
840
25
205
1130
765
20
55
1360
765
20
55
1640
765
20
55
FHF 65-160/150
490
840
25
205
1130
765
20
55
1360
765
20
55
1640
765
20
55
FHF 65-200/150
490
840
25
205
1130
765
20
55
1360
765
20
55
1640
765
20
55
FHF 65-200/185
490
840
25
205
1130
765
20
55
1360
765
20
55
1640
765
20
55
FHF 65-200/220
490
840
25
205
1130
765
20
55
1360
765
20
55
1640
765
20
55
FHF 65-250/220
490
840
25
205
1130
765
20
55
1360
765
20
55
1640
765
20
55
FHF 65-250/300
550
940
30
230
1130
865
20
55
1510
685
20
55
1800
865
20
55
FHF 65-250/370
550
940
30
230
1130
865
20
55
1510
685
20
55
1800
865
20
55
FHF 80-160/150
490
840
25
205
1130
765
20
55
1360
765
20
55
1640
765
20
55
FHF 80-160/185
490
840
25
205
1130
765
20
55
1360
765
20
55
1640
765
20
55
FHF 80-200/220
490
840
25
205
1130
765
20
55
1360
765
20
55
1640
765
20
55
FHF 80-200/300
550
940
30
230
1130
865
20
55
1510
685
20
55
1800
865
20
55
FHF 80-250/370
550
940
30
230
1130
865
20
55
1510
685
20
55
1800
865
20
55
FHF 80-250/450
550
940
30
230
1130
865
20
55
1510
685
20
55
1800
865
20
55
FHF 80-250/550
600
1060
30
270
1360
950
20
90
1640
985
20
55
2100
950
20
90
inter_fhf-en_b_td
67
Lowara
GEN../FHF 100-125 SERIES
DIMENSIONS FOR FL
OOR FIXING
FLOOR
68
Lowara
GEN../FHF 100-125 SERIES
DIMENSIONS FOR FL
OOR FIXING
FLOOR
GEN..10
PUMP
GEN..11
GEN..20
GEN..21
FHF 100-160/185
500
700
25
200
1130
795
20
25
1510
795
20
25
1800
795
20
25
FHF 100-160/220
500
830
25
220
1130
925
20
25
1510
925
20
25
1800
925
20
25
FHF 100-160/300
500
830
25
220
1130
925
20
25
1510
925
20
25
1800
925
20
25
FHF 100-200/185
500
700
25
200
1130
795
20
25
1510
795
20
25
1800
795
20
25
FHF 100-200/300
500
830
25
220
1130
925
20
25
1510
925
20
25
1800
925
20
25
FHF 100-200/370
500
830
25
220
1130
925
20
25
1510
925
20
25
1800
925
20
25
FHF 100-200/450
610
940
30
240
1260
845
20
25
1800
1035
20
25
2100
1035
20
25
FHF 100-250/300
500
830
25
220
1130
925
20
25
1510
925
20
25
1800
925
20
25
FHF 100-250/450
500
830
25
220
1130
925
20
25
1510
925
20
25
1800
925
20
25
FHF 100-250/550
610
940
30
240
1260
845
20
25
1800
1035
20
25
2100
1035
20
25
FHF 100-250/750
680
1050
30
260
1380
930
30
90
1940
930
30
90
1900
930
30
90
FHF 100-250/900
680
1050
30
260
1380
930
30
90
1940
930
30
90
1900
930
30
90
FHF 125-200/300
500
830
25
220
1130
925
20
25
1510
925
20
25
1800
925
20
25
FHF 125-200/450
610
940
30
240
1260
845
20
25
1800
1035
20
25
2100
1035
20
25
FHF 125-200/550
610
940
30
240
1260
845
20
25
1800
1035
20
25
2100
1035
20
25
FHF 125-270/750
700
1200
25
200
1380
1080
30
90
1940
1080
30
90
2320
1080
30
90
FHF 125-270/900
700
1200
25
200
1380
1080
30
90
1940
1080
30
90
2320
1080
30
90
FHF 125-270/1100
820
1200
25
200
1490
1080
30
90
2190
1080
30
90
2540
1080
30
90
FHF 125-270/1320
820
1200
25
200
1490
1080
30
90
2190
1080
30
90
2540
1080
30
90
inter_fhf100-en_a_td
69
Lowara
70
Lowara
GEN../FHF SERIES OF BOOSTER SETS (POSITIVE SUCTION HEAD)
Hc PRES
SURE DROP CURVE IN SUCTION KIT
PRESSURE
2900 [rpm]
0
0
20
40
20
60
40
80
60
80
Q [US gpm]
120
100
0,25
20
40
20
60
40
Q
[Imp gpm]
100
80
60
80
Q [US gpm]
120
100
0,25
0,8
H [ft]
Hc [m]
0,8
Hc [m]
2900 [rpm]
FH 32 - 160
Q [Imp gpm]
100
0,20
H [ft]
FH 32 - 125
0,20
0,6
0,6
0,15
0,15
0,4
0,4
0,10
0,10
0,2
0,2
0,05
0,05
0,00
6
0,0
0,00
10
0,0
30
8
15
25
4
NPSHr [m]
NPSHr [ft]
NPSHr [m]
15
4
NPSHr [ft]
20
6
10
10
5
2
0
0
10
100
15
200
20
20
25
300
40
40
60
60
0
0
0
80
Q [m3/h]
30
Q [l/min]
500
400
2900 [rpm]
FH 32 - 200
0
20
100
10
100
15
200
100
Q120
[Imp gpm]
Q [US gpm]
140
400
100
Q [l/min]
500
100
Q [m3/h]
30
150
200
Q [Imp gpm]
Q [US
250 gpm]
200
0,4
1,5
H [ft]
H [ft]
1,5
Hc [m]
0,5
Hc [m]
0,5
50
50
25
300
2900 [rpm]
FH 40 - 125
120
20
76475_A_CH
76474_A_CH
0,4
1,0
0,3
1,0
0,3
0,2
0,2
0,5
0,5
0,1
0,1
0,0
10
0,0
0,0
15
0,0
30
40
8
25
10
20
NPSHr [ft]
NPSHr [m]
15
4
NPSHr [ft]
NPSHr [m]
30
20
10
10
0
0
0
10
100
15
200
20
300
25
400
30
Q [m3/h]
35
500
Q [l/min]
0
0
0
10
200
20
30
400
40
600
The declared performance value are valid for liquids with density = 1.0 Kg/dm3 and kinematic viscosity = 1 mm2/sec.
The NPSHr values required for the service pump were obtained in the laboratory. When using them for EN 12845 for fire-fighting systems, increase the value by 1 m.
Hc: Pressure drop curve in suction kit.
71
50
800
Q [m3/h]
60
Q 1000
[l/min]
76477_A_CH
76476_A_CH
Lowara
GEN../FHF SERIES OF BOOSTER SETS (POSITIVE SUCTION HEAD)
Hc PRES
SURE DROP CURVE IN SUCTION KIT
PRESSURE
2900 [rpm]
FH 40 - 160
0
0
50
100
50
100
150
200
Q [US
250 gpm]
200
2900 [rpm]
FH 40 - 200
Q [Imp gpm]
50
0,5
100
50
150
100
150
200
Q [Imp gpm]
Q [US
250 gpm]
200
0,4
H [ft]
Hc [m]
1,5
H [ft]
Hc [m]
0,6
0,5
1,5
0,4
1,0
0,3
1,0
0,3
0,2
0,2
0,5
0,5
0,1
0,1
0,0
15
0,0
0,0
15
0,0
40
40
10
10
20
5
0
0
0
10
20
200
30
400
50
100
50
50
600
Q 1000
[l/min]
0
0
150
200
20
200
30
Q [Imp gpm]
50
600
100
Q 1000
[l/min]
200
100
Q [m3/h]
60
800
2900 [rpm]
0
0
40
400
FH 50 - 125
Q [US
250 gpm]
200
10
100
Q [m3/h]
60
800
2900 [rpm]
FH 40 - 250
0
40
76456_A_CH
10
76478_A_CH
10
Q [Imp gpm]
300
200
300
400
Q [US gpm]
Hc [m]
H [ft]
0,5
1,5
H [ft]
0,5
0,6
Hc [m]
NPSHr [ft]
NPSHr [m]
20
30
NPSHr [ft]
NPSHr [m]
30
0,4
1,5
0,4
1,0
0,3
1,0
0,3
0,2
0,2
0,5
0,5
0,1
0,1
0,0
15
0,0
0,0
15
0,0
40
40
10
10
20
NPSHr [ft]
NPSHr [m]
20
30
NPSHr [ft]
NPSHr [m]
30
0
0
0
10
200
20
30
400
40
600
50
800
Q [m3/h]
60
Q 1000
[l/min]
0
0
0
20
200
40
400
600
60
800
1000
80
1200
The declared performance value are valid for liquids with density = 1.0 Kg/dm3 and kinematic viscosity = 1 mm2/sec.
The NPSHr values required for the service pump were obtained in the laboratory. When using them for EN 12845 for fire-fighting systems, increase the value by 1 m.
Hc: Pressure drop curve in suction kit.
72
1400
Q [m3100
/h]
1600
Q [l/min]
76481_A_CH
10
76457_A_CH
10
Lowara
GEN../FHF SERIES OF BOOSTER SETS (POSITIVE SUCTION HEAD)
Hc PRES
SURE DROP CURVE IN SUCTION KIT
PRESSURE
2900 [rpm]
FH 50 - 160
0
100
200
100
300
200
300
400
2900 [rpm]
FH 50 - 200
Q [Imp gpm]
Q [US gpm]
100
100
300
200
400
300
Q [Imp gpm]
Q
[US gpm]
500
400
0,4
1,5
0,4
1,0
0,3
1,0
0,3
0,2
0,2
0,5
0,5
0,1
0,1
0,0
15
0,0
0,0
15
0,0
40
40
10
10
20
NPSHr [ft]
NPSHr [m]
20
30
NPSHr [ft]
NPSHr [m]
30
0
0
0
20
200
40
400
600
800
80
1000
1200
2900 [rpm]
FH 50 - 250
0
60
100
200
100
1400
Q
1600
[l/min]
0
0
300
400
40
60
500
Q [Imp gpm]
0
0
100
1500
2900 [rpm]
100
200
100
300
Q [l/min]
2000
300
200
3
Q [m120
/h]
Q
[Imp gpm]
500
400
400
Q [US
600 gpm]
500
H [ft]
0,5
H [ft]
0,6
Hc [m]
0,6
80
1000
FH 65 - 125
Q
[US gpm]
500
400
20
200
3
Q [m100
/h]
76483_A_CH
10
76482_A_CH
10
0,5
1,5
1,5
0,4
0,4
1,0
0,3
1,0
0,3
0,2
0,2
0,5
0,5
0,1
0,1
0,0
15
0,0
0,0
15
0,0
40
40
10
10
20
NPSHr [ft]
NPSHr [m]
20
30
NPSHr [ft]
NPSHr [m]
30
0
0
0
20
40
500
60
1000
80
100
1500
3
Q [m120
/h]
10
76484_A_CH
10
0
0
Q [l/min]
2000
20
40
500
60
1000
80
100
1500
The declared performance value are valid for liquids with density = 1.0 Kg/dm3 and kinematic viscosity = 1 mm2/sec.
The NPSHr values required for the service pump were obtained in the laboratory. When using them for EN 12845 for fire-fighting systems, increase the value by 1 m.
Hc: Pressure drop curve in suction kit.
73
120
0
3
Q [m140
/h]
2000
Q [l/min]
76485_A_CH
Hc [m]
H [ft]
H [ft]
1,5
Hc [m]
0,5
Hc [m]
0,5
200
Lowara
GEN../FHF SERIES OF BOOSTER SETS (POSITIVE SUCTION HEAD)
Hc PRES
SURE DROP CURVE IN SUCTION KIT
PRESSURE
2900 [rpm]
FH 65 - 160
0
0
100
100
200
200
300
300
400
400
500
500
Q [US
gpm]
700
600
100
200
100
300
200
300
400
400
Q [Imp gpm]
500
500
Q [US
gpm]
700
600
H [ft]
0,5
H [ft]
0,6
Hc [m]
0,6
0,5
1,5
1,5
0,4
0,4
1,0
0,3
1,0
0,3
0,2
0,2
0,5
0,5
0,1
0,1
0,0
15
0,0
0,0
15
0,0
40
40
10
10
20
187
65-160/150
178
20
5
65-200/220
65-200/185
178
0
0
20
40
500
60
1000
100
100
100
120
1500
200
200
400
400
3
Q [m160
/h]
0
0
2500
Q [l/min]
500
500
600
198
10
300
300
140
2000
2900 [rpm]
FH 65 - 250
0
80
210
10
20
40
500
60
1000
Q [Imp gpm]
0
0
1500
120
200
200
400
400
140
2000
2500
Q [l/min]
600
0
3
Q [m160
/h]
Q [Imp gpm]
800
800
1000
Q [US gpm]
0,5
H [ft]
Hc [m]
0,6
100
2900 [rpm]
FH 80 - 160
Q [US
gpm]
700
80
76487_A_CH
168
76486_A_CH
65-160/150
65-160/110
Hc [m]
65-200/150
NPSHr [ft]
65-160/150
178
30
NPSHr [ft]
NPSHr [m]
161
NPSHr [m]
30
65-160/110A
0,5
1,5
H [ft]
Hc [m]
2900 [rpm]
FH 65 - 200
Q [Imp gpm]
0,4
1,5
0,4
1,0
0,3
1,0
0,3
0,2
0,2
0,5
0,5
0,1
0,1
0,0
15
0,0
0,0
15
0,0
40
40
10
10
65-160/150
178
20
NPSHr [ft]
20
NPSHr [m]
65-160/150
178
30
NPSHr [ft]
NPSHr [m]
30
0
0
0
20
40
500
60
1000
80
100
1500
120
2000
140
3
Q [m160
/h]
2500
Q [l/min]
0
0
0
50
1000
100
150
2000
200
3000
The declared performance value are valid for liquids with density = 1.0 Kg/dm3 and kinematic viscosity = 1 mm2/sec.
The NPSHr values required for the service pump were obtained in the laboratory. When using them for EN 12845 for fire-fighting systems, increase the value by 1 m.
Hc: Pressure drop curve in suction kit.
74
3
Q [m250
/h]
Q 4000
[l/min]
76489_A_CH
10
76488_A_CH
10
Lowara
GEN../FHF SERIES OF BOOSTER SETS (POSITIVE SUCTION HEAD)
Hc PRES
SURE DROP CURVE IN SUCTION KIT
PRESSURE
2900 [rpm]
FH 80 - 200
0
200
400
200
600
400
600
800
800
1000
2900 [rpm]
FH 80 - 250
Q [Imp gpm]
Q [US gpm]
200
400
200
600
400
600
Q [Imp gpm]
800
800
0,4
1,5
H [ft]
H [ft]
1,5
Hc [m]
0,5
Hc [m]
0,5
0,4
1,0
0,3
1,0
0,3
0,2
0,2
0,5
0,5
0,1
0,1
0,0
15
0,0
0,0
15
0,0
40
40
10
10
80-250/370
225
65-160/150
178
20
NPSHr [ft]
20
NPSHr [m]
65-160/150
178
30
NPSHr [ft]
NPSHr [m]
30
5
80-250/550
80-250/450
256
238
0
50
100
1000
3000
2900 [rpm]
200
200
400
400
600
600
Q 4000
[l/min]
0
0
1000
1000
1400
0,25
150
1000
2000
3000
2900 [rpm]
200
200
400
400
600
600
0
3
Q [m250
/h]
200
800
800
Q 4000
[l/min]
1000
1000
Q
[Imp gpm]
1400
1200
1200
1400
0,25
0,8
H [ft]
Hc [m]
0,8
Hc [m]
100
FH 100 - 200
Q
[Imp gpm]
1400
1200
1200
50
800
800
3
Q [m250
/h]
200
2000
FH 100 - 160
0
150
0,20
H [ft]
76491_A_CH
10
76490_A_CH
10
0,20
0,6
0,6
0,15
0,15
0,4
0,4
0,10
0,10
0,2
0,2
0,05
0,05
0,00
15
0,0
100-160/185
0,00
15
0,0
40
135/165
100-200/185
10
40
141/195
10
65-160/150
178
20
65-160/150
178
100-200/450
100-200/370
100-200/300
213
203
189/195
0
0
50
1000
100
150
2000
200
3000
250
4000
300
5000
350
6000
0
3
Q [m400
/h]
Q [l/min]
10
76492_A_CH
10
20
NPSHr [ft]
159/171
30
0
0
0
50
1000
100
150
2000
200
3000
250
4000
300
5000
The declared performance value are valid for liquids with density = 1.0 Kg/dm3 and kinematic viscosity = 1 mm2/sec.
The NPSHr values required for the service pump were obtained in the laboratory. When using them for EN 12845 for fire-fighting systems, increase the value by 1 m.
Hc: Pressure drop curve in suction kit.
75
350
6000
0
3
Q [m400
/h]
Q [l/min]
76493_A_CH
185
NPSHr [m]
100-160/300
100-160/220
NPSHr [ft]
NPSHr [m]
30
Lowara
GEN../FHF SERIES OF BOOSTER SETS (POSITIVE SUCTION HEAD)
Hc PRES
SURE DROP CURVE IN SUCTION KIT
PRESSURE
2900 [rpm]
500
1000
500
1000
Q [US gpm]
1500
0,25
2900 [rpm]
FH 125 - 200
500
500
1000
1000
1500
1500
Q2500
[Imp gpm]
2000
2000
Q3000
[US gpm]
2500
0,25
0,8
Hc [m]
H [ft]
Hc [m]
0,8
0,20
H [ft]
FH 100 - 250
0,20
0,6
0,6
0,15
0,15
0,4
0,4
0,10
0,10
0,2
0,2
0,05
0,05
0,00
15
0,0
0,00
15
0,0
125-200/300
162/194
40
40
10
200
30
20
125-200/550
125-200/450
NPSHr [m]
65-160/150
178
NPSHr [ft]
NPSHr [m]
100-250/300
205
65-160/150
178
20
5
267
254
10
221
0
0
100
200
2000
6000
2900 [rpm]
500
500
1000
1000
Q [l/min]
0
0
0
100
2000
200
300
4000
400
6000
500
8000
1500
1500
0
3
Q [m500
/h]
400
4000
FH 125 - 270
300
10
2000
2000
2500
2500
Q [Imp gpm]
3000
Q [US
3500gpm]
0,25
H [ft]
Hc [m]
0,8
0,20
0,6
0,15
0,4
0,10
0,2
0,05
0,00
20
0,0
60
50
15
125-270/750
216/230
125-270/1320 266
65-160/150
125-270/1100 253
178
125-270/900 237
30
NPSHr [ft]
40
10
20
5
0
0
0
100
2000
200
300
4000
400
6000
500
8000
600
10000
700
0
3
Q [m800
/h]
12000
Q [l/min]
76496_A_CH
10
The declared performance value are valid for liquids with density = 1.0 Kg/dm3 and kinematic viscosity = 1 mm2/sec.
The NPSHr values required for the service pump were obtained in the laboratory. When using them for EN 12845 for fire-fighting systems, increase the value by 1 m.
Hc: Pressure drop curve in suction kit.
76
600
10000
0
3
Q [m700
/h]
Q [l/min]
76495_A_CH
235
76494_A_CH
100-250/900
100-250/750
100-250/550
100-250/450
NPSHr [m]
30
216
NPSHr [ft]
10
Lowara
GEN../FHF SERIES OF BOOSTER SETS (SUCTION LIF
T)
LIFT)
Hc PRES
SURE DROP CURVE IN SUCTION KIT
PRESSURE
2900 [rpm]
FH 32 - 125
0
0
20
40
20
60
40
80
60
80
Q [US gpm]
120
100
2900 [rpm]
FH 32 - 160
Q [Imp gpm]
100
0,5
20
40
20
60
40
Q
[Imp gpm]
100
80
60
80
Q [US gpm]
120
100
0,4
H [ft]
Hc [m]
1,5
H [ft]
Hc [m]
0,6
0,5
1,5
0,4
1,0
0,3
1,0
0,3
0,2
0,2
0,5
0,5
0,1
0,1
0,0
6
0,0
0,0
10
0,0
30
8
15
25
4
NPSHr [m]
NPSHr [ft]
NPSHr [m]
15
4
NPSHr [ft]
20
6
10
10
5
2
0
0
10
100
15
200
20
20
25
300
40
40
60
60
100
10
100
15
200
100
Q120
[Imp gpm]
120
Q [US gpm]
140
20
50
100
50
25
300
400
2900 [rpm]
FH 40 - 125
Q [l/min]
500
100
Q [m3/h]
30
150
200
Q [Imp gpm]
Q [US
250 gpm]
200
H [ft]
0,5
H [ft]
0,6
Hc [m]
0,6
Hc [m]
0
0
80
Q [m3/h]
30
Q [l/min]
500
400
2900 [rpm]
FH 32 - 200
0
20
76452_A_CH
76451_A_CH
0,5
1,5
1,5
0,4
0,4
1,0
0,3
1,0
0,3
0,2
0,2
0,5
0,5
0,1
0,1
0,0
10
0,0
0,0
15
0,0
30
40
8
25
10
20
NPSHr [ft]
NPSHr [m]
15
4
NPSHr [ft]
NPSHr [m]
30
20
10
10
0
0
0
10
100
15
200
20
300
25
400
30
Q [m3/h]
35
500
Q [l/min]
0
0
0
10
200
20
30
400
40
600
The declared performance value are valid for liquids with density = 1.0 Kg/dm3 and kinematic viscosity = 1 mm2/sec.
The NPSHr values required for the service pump were obtained in the laboratory. When using them for EN 12845 for fire-fighting systems, increase the value by 1 m.
Hc: Pressure drop curve in suction kit.
77
50
800
Q [m3/h]
60
Q 1000
[l/min]
76454_A_CH
76453_A_CH
Lowara
GEN../FHF SERIES OF BOOSTER SETS (SUCTION LIF
T)
LIFT)
Hc PRES
SURE DROP CURVE IN SUCTION KIT
PRESSURE
2900 [rpm]
FH 40 - 160
0
0
50
100
50
100
150
200
Q [US
250 gpm]
200
50
100
50
150
100
150
200
Q [Imp gpm]
Q [US
250 gpm]
200
H [ft]
0,5
H [ft]
0,6
Hc [m]
0,6
0,5
1,5
1,5
0,4
0,4
1,0
0,3
1,0
0,3
0,2
0,2
0,5
0,5
0,1
0,1
0,0
15
0,0
0,0
15
0,0
40
40
10
10
20
5
0
0
0
10
20
200
30
400
50
100
50
50
600
Q 1000
[l/min]
0
0
150
200
20
200
30
Q [Imp gpm]
600
100
800
Q 1000
[l/min]
200
100
Q [m3/h]
60
Q [Imp gpm]
300
200
300
400
Q [US gpm]
H [ft]
0,5
H [ft]
0,6
Hc [m]
0,6
50
2900 [rpm]
0
0
40
400
FH 50 - 125
Q [US
250 gpm]
200
10
100
Q [m3/h]
60
800
2900 [rpm]
FH 40 - 250
0
40
76456_A_CH
10
76455_A_CH
10
0,5
1,5
1,5
0,4
0,4
1,0
0,3
1,0
0,3
0,2
0,2
0,5
0,5
0,1
0,1
0,0
15
0,0
0,0
15
0,0
40
40
10
10
NPSHr [m]
20
30
NPSHr [ft]
NPSHr [m]
30
20
NPSHr [ft]
Hc [m]
NPSHr [ft]
NPSHr [m]
20
30
NPSHr [ft]
NPSHr [m]
30
0
0
0
10
200
20
30
400
40
600
50
800
Q [m3/h]
60
Q 1000
[l/min]
10
76457_A_CH
10
0
0
0
20
200
40
400
600
60
800
1000
80
1200
The declared performance value are valid for liquids with density = 1.0 Kg/dm3 and kinematic viscosity = 1 mm2/sec.
The NPSHr values required for the service pump were obtained in the laboratory. When using them for EN 12845 for fire-fighting systems, increase the value by 1 m.
Hc: Pressure drop curve in suction kit.
78
1400
0
3
Q [m100
/h]
1600
Q [l/min]
76458_A_CH
Hc [m]
2900 [rpm]
FH 40 - 200
Q [Imp gpm]
Lowara
GEN../FHF SERIES OF BOOSTER SETS (SUCTION LIF
T)
LIFT)
Hc PRES
SURE DROP CURVE IN SUCTION KIT
PRESSURE
2900 [rpm]
FH 50 - 160
0
100
200
100
300
200
300
400
Q [US gpm]
100
200
100
200
400
300
Q [Imp gpm]
Q
[US gpm]
500
400
H [ft]
0,5
H [ft]
0,6
Hc [m]
0,6
0,5
1,5
1,5
0,4
0,4
1,0
0,3
1,0
0,3
0,2
0,2
0,5
0,5
0,1
0,1
0,0
15
0,0
0,0
15
0,0
40
40
10
10
20
5
0
0
20
200
40
400
600
800
100
1000
200
100
1200
1400
Q
1600
[l/min]
0
0
300
400
40
60
500
Q [Imp gpm]
0
0
100
1500
2900 [rpm]
100
200
100
300
Q [l/min]
2000
300
200
3
Q [m120
/h]
Q
[Imp gpm]
500
400
400
Q [US
600 gpm]
500
H [ft]
0,5
H [ft]
0,6
Hc [m]
0,6
80
1000
FH 65 - 125
Q
[US gpm]
500
400
20
200
0
3
Q [m100
/h]
80
2900 [rpm]
FH 50 - 250
0
60
76473_A_CH
10
76459_A_CH
10
0,5
1,5
1,5
0,4
0,4
1,0
0,3
1,0
0,3
0,2
0,2
0,5
0,5
0,1
0,1
0,0
15
0,0
0,0
15
0,0
40
40
10
10
NPSHr [m]
20
30
NPSHr [ft]
NPSHr [m]
30
20
NPSHr [ft]
Hc [m]
NPSHr [ft]
NPSHr [m]
20
30
NPSHr [ft]
NPSHr [m]
30
0
0
0
20
40
500
60
1000
80
100
1500
3
Q [m120
/h]
Q [l/min]
2000
10
76460_A_CH
10
0
0
0
20
40
500
60
1000
80
100
1500
The declared performance value are valid for liquids with density = 1.0 Kg/dm3 and kinematic viscosity = 1 mm2/sec.
The NPSHr values required for the service pump were obtained in the laboratory. When using them for EN 12845 for fire-fighting systems, increase the value by 1 m.
Hc: Pressure drop curve in suction kit.
79
120
0
3
Q [m140
/h]
2000
Q [l/min]
76461_A_CH
Hc [m]
2900 [rpm]
FH 50 - 200
Q [Imp gpm]
Lowara
GEN../FHF SERIES OF BOOSTER SETS (SUCTION LIF
T)
LIFT)
Hc PRES
SURE DROP CURVE IN SUCTION KIT
PRESSURE
2900 [rpm]
FH 65 - 160
0
0
100
100
200
200
300
300
400
400
500
500
Q [US
gpm]
700
600
100
200
100
300
200
300
400
400
Q [Imp gpm]
500
500
Q [US
gpm]
700
600
H [ft]
0,5
H [ft]
0,6
Hc [m]
0,6
0,5
1,5
1,5
0,4
0,4
1,0
0,3
1,0
0,3
0,2
0,2
0,5
0,5
0,1
0,1
0,0
15
0,0
0,0
15
0,0
40
40
10
10
20
187
65-160/150
178
20
5
65-200/220
65-200/185
178
0
20
40
500
60
1000
100
100
100
120
1500
200
200
3
Q [m160
/h]
2500
Q [l/min]
0
0
0
300
300
140
2000
2900 [rpm]
FH 65 - 250
0
80
400
400
500
500
600
198
10
0
0
210
10
20
40
500
60
1000
Q [Imp gpm]
0
0
1500
120
200
200
400
400
140
2000
2500
Q [l/min]
600
0
3
Q [m160
/h]
Q [Imp gpm]
800
800
1000
Q [US gpm]
H [ft]
0,5
H [ft]
0,6
Hc [m]
0,6
100
2900 [rpm]
FH 80 - 160
Q [US
gpm]
700
80
76463_A_CH
168
76462_A_CH
65-160/150
65-160/110
0,5
1,5
1,5
0,4
0,4
1,0
0,3
1,0
0,3
0,2
0,2
0,5
0,5
0,1
0,1
0,0
15
0,0
0,0
15
0,0
40
40
10
10
20
NPSHr [m]
65-160/150
178
30
NPSHr [ft]
NPSHr [m]
30
65-160/150
178
20
NPSHr [ft]
Hc [m]
65-200/150
NPSHr [ft]
65-160/150
178
30
NPSHr [ft]
NPSHr [m]
161
NPSHr [m]
30
65-160/110A
0
0
0
20
40
500
60
1000
80
100
1500
120
2000
140
3
Q [m160
/h]
2500
Q [l/min]
10
76464_A_CH
10
0
0
0
50
1000
100
150
2000
200
3000
The declared performance value are valid for liquids with density = 1.0 Kg/dm3 and kinematic viscosity = 1 mm2/sec.
The NPSHr values required for the service pump were obtained in the laboratory. When using them for EN 12845 for fire-fighting systems, increase the value by 1 m.
Hc: Pressure drop curve in suction kit.
80
3
Q [m250
/h]
Q 4000
[l/min]
76465_A_CH
Hc [m]
2900 [rpm]
FH 65 - 200
Q [Imp gpm]
Lowara
GEN../FHF SERIES OF BOOSTER SETS (SUCTION LIF
T)
LIFT)
Hc PRES
SURE DROP CURVE IN SUCTION KIT
PRESSURE
2900 [rpm]
FH 80 - 200
0
200
400
200
600
400
600
800
800
1000
Q [US gpm]
200
400
200
600
400
600
Q [Imp gpm]
800
800
H [ft]
0,5
H [ft]
0,6
Hc [m]
0,6
0,5
1,5
1,5
0,4
0,4
1,0
0,3
1,0
0,3
0,2
0,2
0,5
0,5
0,1
0,1
0,0
15
0,0
0,0
15
0,0
40
40
10
10
80-250/370
225
65-160/150
178
20
NPSHr [ft]
20
NPSHr [m]
65-160/150
178
30
NPSHr [ft]
NPSHr [m]
30
5
80-250/550
80-250/450
256
238
0
50
100
1000
3000
2900 [rpm]
200
200
400
400
600
600
Q 4000
[l/min]
0
0
1000
1000
1400
0,25
150
1000
2000
3000
2900 [rpm]
200
200
400
400
600
600
0
3
Q [m250
/h]
200
800
800
Q 4000
[l/min]
1000
1000
Q
[Imp gpm]
1400
1200
1200
1400
0,25
0,8
H [ft]
Hc [m]
0,8
Hc [m]
100
FH 100 - 200
Q
[Imp gpm]
1400
1200
1200
50
800
800
3
Q [m250
/h]
200
2000
FH 100 - 160
0
150
0,20
H [ft]
76467_A_CH
10
76466_A_CH
10
0,20
0,6
0,6
0,15
0,15
0,4
0,4
0,10
0,10
0,2
0,2
0,05
0,05
0,00
15
0,0
100-160/185
0,00
15
0,0
40
135/165
100-200/185
10
40
141/195
10
159/171
65-160/150
178
20
30
65-160/150
178
100-200/450
100-200/370
100-200/300
213
203
189/195
0
0
50
1000
100
150
2000
200
3000
250
4000
300
5000
350
6000
0
3
Q [m400
/h]
Q [l/min]
10
76468_A_CH
10
20
NPSHr [ft]
185
NPSHr [m]
100-160/300
100-160/220
NPSHr [ft]
NPSHr [m]
30
0
0
0
50
1000
100
150
2000
200
3000
250
4000
300
5000
The declared performance value are valid for liquids with density = 1.0 Kg/dm3 and kinematic viscosity = 1 mm2/sec.
The NPSHr values required for the service pump were obtained in the laboratory. When using them for EN 12845 for fire-fighting systems, increase the value by 1 m.
Hc: Pressure drop curve in suction kit.
81
350
6000
0
3
Q [m400
/h]
Q [l/min]
76469_A_CH
Hc [m]
2900 [rpm]
FH 80 - 250
Q [Imp gpm]
Lowara
GEN../FHF SERIES OF BOOSTER SETS (SUCTION LIF
T)
LIFT)
Hc PRES
SURE DROP CURVE IN SUCTION KIT
PRESSURE
2900 [rpm]
500
1000
500
1000
Q [US gpm]
1500
0,25
2900 [rpm]
FH 125 - 200
500
500
1000
1000
1500
1500
Q2500
[Imp gpm]
2000
2000
Q3000
[US gpm]
2500
0,25
0,8
Hc [m]
H [ft]
Hc [m]
0,8
0,20
H [ft]
FH 100 - 250
0,20
0,6
0,6
0,15
0,15
0,4
0,4
0,10
0,10
0,2
0,2
0,05
0,05
0,00
15
0,0
0,00
15
0,0
125-200/300
162/194
40
40
10
200
30
20
125-200/550
125-200/450
NPSHr [m]
65-160/150
178
NPSHr [ft]
NPSHr [m]
100-250/300
205
65-160/150
178
20
5
267
254
10
221
0
0
100
200
2000
6000
2900 [rpm]
500
500
1000
1000
Q [l/min]
0
0
0
100
2000
200
300
4000
400
6000
500
8000
1500
1500
0
3
Q [m500
/h]
400
4000
FH 125 - 270
300
10
2000
2000
2500
2500
Q [Imp gpm]
3000
Q [US
3500gpm]
0,25
H [ft]
Hc [m]
0,8
0,20
0,6
0,15
0,4
0,10
0,2
0,05
0,00
20
0,0
60
50
15
125-270/750
216/230
125-270/1320 266
65-160/150
125-270/1100 253
178
125-270/900 237
30
NPSHr [ft]
40
10
20
5
0
0
0
100
2000
200
300
4000
400
6000
500
8000
600
10000
700
0
3
Q [m800
/h]
12000
Q [l/min]
76472_A_CH
10
The declared performance value are valid for liquids with density = 1.0 Kg/dm3 and kinematic viscosity = 1 mm2/sec.
The NPSHr values required for the service pump were obtained in the laboratory. When using them for EN 12845 for fire-fighting systems, increase the value by 1 m.
Hc: Pressure drop curve in suction kit.
82
600
10000
0
3
Q [m700
/h]
Q [l/min]
76471_A_CH
235
76470_A_CH
100-250/900
100-250/750
100-250/550
100-250/450
NPSHr [m]
30
216
NPSHr [ft]
10
Lowara
GEN../SHF Series
Fire-fighting booster sets EN 12845
Horizontal Centrifugal electric pumps SHF series
equipped with high efficiency PLM motors
50 Hz
83
Lowara
84
Lowara
RANGE
GEN../SHF RANGE
The range of EN 12845 series fire-fighting booster sets includes
models with 1 or 2 electric service pumps and some with jockey
pumps for adapting to the specific requirements of each application.
GEN10 SERIES
Head up to 100 m.
Flow up to 220 m3/h.
GEN11 SERIES
Head up to 100 m.
Flow up to 220 m3/h.
GEN20 SERIES
Head up to 100 m.
Flow up to 440 m3/h.
GEN21 SERIES
85
Head up to 100 m.
Flow up to 440 m3/h.
Lowara
GEN../SHF BOOSTER SETS SERIES
TABELLA DI PRESTAZIONI IDRAULICHE POMPE PILOTA SV2-4 PER GRUPPI EN12845
HYDRA
ULIC PERFORMANCE T
ABLE A
T 50 HZ (JOCKEY PUMP)
HYDRAULIC
TABLE
AT
PUMP
NOMINAL
TYPE
POWER
Q = DELIVERY
l/min 0
20
30
40
50
60
70
100
120
133
m3/h 0
1,2
1,8
2,4
3,6
4,2
7,2
37,0
26,0
18,0
kW
HP
SV2 04
0,55
0,75
42,5
37,5
34,0
30,5
26,0
20,5
SV2 06
0,75
64,0
56,0
51,0
45,5
38,5
31,0
22,0
SV2 09
1,1
1,5
96,0
84,0
76,5
68,5
58,0
46,5
32,5
SV2 12
1,5
128,0
112,0
102,0
91,0
77,0
62,0
44,0
SV2 14
2,2
150,0
131,0
119,0
106,0
90,0
73,0
52,0
SV2 15
2,2
160,2
140,3
128,2
114,0
97,4
78,2
55,9
SV4 07
1,1
1,5
70,0
59,5
56,0
53,0
51,0
SV4 09
1,5
90,0
76,5
73,0
68,5
65,5
47,0
33,5
23,0
SV4 13
2,2
131,0
111,0
105,0
99,0
95,0
68,0
48,0
34,0
15,0
EN12845_pp_sv2-4-2p50-en_b_th
86
Lowara
GEN../SHF BOOSTER SETS SERIES
TABELLA ABBINAMENTI POMPA SERVIZIO SH32-80 - POMPA PILOTA GRUPPI GEN 1
SERVICE PUMP - JOCKEY PUMP COMBINA
TIONS
COMBINATIONS
32-125/07
32-125/11
32-160/15
32-160/22
32-200/30
32-200/40
32-250/55
32-250/75
32-250/110
40-125/11
40-125/15
40-125/22
40-160/30
40-160/40
40-200/55
40-200/75
40-250/110A
40-250/110
40-250/150
50-125/22
50-125/30
50-125/40
50-160/55
50-160/75
50-200/110A
50-200/110
50-250/150
50-250/185
50-250/220
65-160/40
65-160/55
65-160/75
65-160/110A
65-160/110
65-200/150
65-200/185
65-200/220
65-250/300
65-250/370
80-160/110
80-160/150
80-160/185
80-200/220
80-200/300
80-200/370
80-250/450
80-250/550
80-250/750
SV8 09
SV8 07
SV8 06
SV8 05
SV4 13
SV4 09
SV4 07
SV2 15
SV2 14
SV2 12
ELECTRIC
PUMP
SV2 04
TYPE
SHF
SV2 09
JOCKEY PUMP
SV2 06
SERVICE PUMP
PUMP
32-125/D121
32-125/D136
32-160/D150
32-160/D168
32-200/D188
32-200/D204
32-250/D222
32-250/D242
32-250/D256
40-125/D112
40-125/D126
40-125/D143
40-160/D159
40-160/D171
40-200/D190
40-200/D209
40-250/D218
40-250/D233
40-250/D251
50-125/D119
50-125/D130
50-125/D139
50-160/D158
50-160/D174
50-200/D197
50-200/D209
50-250/D224
50-250/D237
50-250/D250
65-160/D119
65-160/D129
65-160/D137
65-160/D168
65-160/D177
65-200/D192
65-200/D203
65-200/D215
65-250/D240
65-250/D255
80-160/D169
80-160/D177
80-160/D186
80-200/D198
80-200/D215
80-200/D226
80-250/D237
80-250/D252
80-250/D270
12845-SHF_ap-en_a_tc
87
Lowara
HYDRA
ULIC PERFORMANCE T
ABLE A
T 50 HZ (POSITIVE SUCTION HEAD)
HYDRAULIC
TABLE
AT
TABELLA DI PRESTAZIONI IDRAULICHE NETTE GRUPPI EN12845 SERIE SHF32 2 poli 50 Hz 1 POMPA DI SERVIZIO, ASP ESCLUSA SOPRABATT
GEN../SHF 32 BOOSTER SETS SERIES
TYPE
RATED
SHF..
POWER
LHn
RISK CLASS
Q = DELIVERY
l/min 0
ELECTRIC
PUMP
PUMP
m /h 0
150
180
200
225
300
350
375
400
416
425
450
540
11
12
14
18
21
23
24
25
26
27
32
15,2
13,1
24,1
kW
32-125/07
32-125/D121
1 x 0,75
16,7
14,0
12,9
12,1
11,0
7,6
5,1
3,7
1,9
32-125/11
32-125/D136
1 x 1,1
21,6
19,0
17,9
17,0
15,9
12,3
9,6
8,1
6,2
32-160/15
32-160/D150
1 x 1,5
27,6
24,2
22,9
21,8
20,5
16,3
13,0
11,3
9,1
32-160/22
32-160/D168
1 x 2,2
35,0
32,0
30,9
29,9
28,7
24,7
21,5
19,7
17,5
16,1
32-200/30
32-200/D188
1x3
43,8
38,1
36,4
35,1
33,4
28,0
23,9
21,6
18,8
17,1
32-200/40
32-200/D204
1x4
53,6
48,6
47,1
45,9
44,4
39,3
35,1
32,8
29,9
28,1
27,0
32-250/55
32-250/D222
1 x 5,5
61,7
56,3
54,6
53,2
51,6
46,0
41,7
39,3
36,4
32-250/75
32-250/D242
1 x 7,5
74,1
68,4
66,7
65,3
63,6
58,1
53,8
51,4
48,6
46,9
45,8
32-250/110
32-250/D256
1 x 11
86,3
79,8
77,9
76,5
74,7
69,0
64,7
62,3
59,5
57,8
56,7
54,0
Performance levels relative to set with 1 service pump running and compliant with ISO 9906 - Annex A.
12845_1pg-sp-shf32-2p50-en_a_th
LHn = risk class value referred to the required rated capacity (Tab.6 para 7.3.1 EN12845)
Inlet pressure drops must be deducted. Make sure that these drops, added to the difference in level (max. 3.2m), are less than 4.5m
The values shown identify performance levels according to the reference standard EN12845.
HYDRA
ULIC PERFORMANCE T
ABLE A
T 50 HZ (SUCTION LIF
T)
HYDRAULIC
TABLE
AT
LIFT)
TABELLA DI PRESTAZIONI IDRAULICHE NETTE GRUPPI EN12845 SERIE SHF32 2 poli 50 Hz 1 POMPA DI SERVIZIO, ASP ESCLUSA SOTTOBATT
GEN../SHF 32 BOOSTER SETS SERIES
TYPE
RATED
SHF..
POWER
ELECTRIC
PUMP
PUMP
LHn
RISK CLASS
Q = DELIVERY
l/min 0
150
180
200
225
300
350
375
400
416
425
450
540
3
m /h 0
11
12
14
18
21
23
24
25
26
27
32
15,2
13,1
24,1
kW
32-125/07
32-125/D121
1 x 0,75
16,7
14,0
12,9
12,1
11,0
7,6
5,1
3,7
1,9
32-125/11
32-125/D136
1 x 1,1
21,6
19,0
17,9
17,0
15,9
12,3
9,6
8,1
6,2
32-160/15
32-160/D150
1 x 1,5
27,6
24,2
22,9
21,8
20,5
16,3
13,0
11,3
9,1
32-160/22
32-160/D168
1 x 2,2
35,0
32,0
30,9
29,9
28,7
24,7
21,5
19,7
17,5
16,1
32-200/30
32-200/D188
1x3
43,8
38,1
36,4
35,1
33,4
28,0
23,9
21,6
18,8
17,1
32-200/40
32-200/D204
1x4
53,6
48,6
47,1
45,9
44,4
39,3
35,1
32,8
29,9
28,1
27,0
32-250/55
32-250/D222
1 x 5,5
61,7
56,3
54,6
53,2
51,6
46,0
41,7
39,3
36,4
32-250/75
32-250/D242
1 x 7,5
74,1
68,4
66,7
65,3
63,6
58,1
53,8
51,4
48,6
46,9
45,8
32-250/110
32-250/D256
1 x 11
86,3
79,8
77,9
76,5
74,7
69,0
64,7
62,3
59,5
57,8
56,7
Performance levels relative to set with 1 service pump running and compliant with ISO 9906 - Annex A.
LHn = risk class value referred to the required rated capacity (Tab.6 para 7.3.1 EN12845).
Inlet pressure drops must be deducted. Make sure these drops are less than 4.5m
The values shown identify performance levels according to the reference standard EN12845.
88
54,0
12845_1pg-st-shf32-2p50-en_a_th
Lowara
NPSH REQUIRED FOR PUMP SERIES SHF 32
TABELLA DI PRESTAZIONI IDRAULICHE NPSHr GRUPPI EN12845 SERIE SHF32 2 poli 50 Hz
TYPE
RATED
SHF..
POWER
LHn
RISK CLASS
Q = DELIVERY
l/min 0
ELECTRIC
PUMP
PUMP
m /h 0
150
180
200
225
300
350
375
400
416
425
450
540
11
12
14
18
21
23
24
25
26
27
32
4,4
5,2
6,9
kW
32-125/07
32-125/D121
1 x 0,75
1,0
1,0
1,1
1,2
1,6
2,1
2,3
2,7
32-125/11
32-125/D136
1 x 1,1
1,0
1,0
1,1
1,2
1,6
2,1
2,3
2,7
32-160/15
32-160/D150
1 x 1,5
1,5
1,6
1,7
1,9
2,5
3,0
3,2
3,5
32-160/22
32-160/D168
1 x 2,2
1,2
1,4
1,5
1,6
2,2
2,8
3,3
3,8
4,2
32-200/30
32-200/D188
1x3
1,7
1,8
1,9
2,1
2,8
3,7
4,3
5,2
5,8
32-200/40
32-200/D204
1x4
1,6
1,8
2,0
2,2
2,8
3,4
3,9
4,6
5,1
5,5
32-250/55
32-250/D222
1 x 5,5
2,8
3,2
3,5
3,8
5,1
6,2
6,9
7,7
32-250/75
32-250/D242
1 x 7,5
2,7
3,0
3,2
3,5
4,5
5,3
5,8
6,3
6,6
6,9
32-250/110
32-250/D256
1 x 11
2,7
3,0
3,2
3,5
4,5
5,3
5,8
6,3
6,6
6,9
The declared NPSH values were obtained in the laboratory and refer to a single service pump
LHn = risk class value referred to the required rated capacity (Tab.6 para 7.3.1 EN12845)
Check that NPSHd NPSHr+1m is satisfied
89
7,5
12845_1p-shf32-2p50_NPSHr-en_a_th
Lowara
HYDRA
ULIC PERFORMANCE T
ABLE A
T 50 HZ (POSITIVE SUCTION HEAD)
HYDRAULIC
TABLE
AT
TABELLA DI PRESTAZIONI IDRAULICHE NETTE GRUPPI EN12845 SERIE SHF40 2 poli 50 Hz 1 POMPA DI SERVIZIO, ASP ESCLUSA, INST SOPRA
GEN../SHF 40 BOOSTER SETS SERIES
TYPE
RATED
SHF..
POWER
ELECTRIC
PUMP
PUMP
OH1n
RISK CLASS
Q = DELIVERY
l/min 0
300
375
540
640
677
700
725
750
800
833
850
1000
m3/h 0
18
23
32
38
41
42
44
45
48
50
51
60
kW
40-125/11
40-125/D112
1 x 1,1
13,9
11,3
10,0
9,3
3,4
0,7
40-125/15
40-125/D126
1 x 1,5
18,0
15,3
14,0
13,3
7,4
4,7
40-125/22
40-125/D143
1 x 2,2
25,3
21,8
20,5
19,8
14,0
11,4
6,4
5,0
3,6
40-160/30
40-160/D159
1x3
31,6
28,1
26,8
26,0
19,5
16,5
10,8
9,2
7,6
40-160/40
40-160/D171
1x4
38,3
35,1
33,7
32,9
26,5
23,6
18,1
16,5
15,0
40-200/55
40-200/D190
1 x 5,5
46,4
42,7
41,2
40,4
33,1
29,7
23,3
21,5
19,6
40-200/75
0,6
11,7
40-200/D209
1 x 7,5
57,5
53,1
51,6
50,7
43,8
40,7
34,8
33,2
31,5
28,0
40-250/110A 40-250/D218
1 x 11
63,6
57,8
56,2
55,2
47,8
44,5
38,2
36,5
34,8
31,1
40-250/110
40-250/D233
1 x 11
71,7
66,0
64,3
63,4
55,7
52,3
45,8
44,0
42,1
38,3
40-250/150
40-250/D251
1 x 15
85,0
78,6
76,9
76,0
68,4
65,0
58,6
56,8
55,0
51,1
42,6
Performance levels relative to set with 1 service pump running and compliant with ISO 9906 - Annex A.
12845_1pg-sp-shf40-2p50-en_a_th
OHn = risk class value referred to the required rated capacity (Tab.6 para 7.3.1 EN12845)
Inlet pressure drops must be deducted. Make sure that these drops, added to the difference in level (max. 3.2m), are less than 4.5m
The values shown identify performance levels according to the reference standard EN12845.
HYDRA
ULIC PERFORMANCE T
ABLE A
T 50 HZ (SUCTION LIF
T)
HYDRAULIC
TABLE
AT
LIFT)
TABELLA DI PRESTAZIONI IDRAULICHE NETTE GRUPPI EN12845 SERIE SHF40 2 poli 50 Hz 1 POMPA DI SERVIZIO, ASP ESCLUSA, INST SOTT
GEN../SHF 40 BOOSTER SETS SERIES
TYPE
RATED
SHF..
POWER
ELECTRIC
PUMP
PUMP
OH1n
RISK CLASS
Q = DELIVERY
l/min 0
300
375
540
640
677
700
725
750
800
833
850
1000
m3/h 0
18
23
32
38
41
42
44
45
48
50
51
60
kW
40-125/11
40-125/D112
1 x 1,1
13,9
11,3
10,0
9,3
3,4
40-125/15
40-125/D126
1 x 1,5
18,0
15,3
14,0
13,3
7,4
0,7
4,7
40-125/22
40-125/D143
1 x 2,2
25,3
21,8
20,5
19,8
14,0
11,4
6,4
5,0
3,6
40-160/30
40-160/D159
1x3
31,6
28,1
26,8
26,0
19,5
16,5
10,8
9,2
7,6
40-160/40
40-160/D171
1x4
38,3
35,1
33,7
32,9
26,5
23,6
18,1
16,5
15,0
40-200/55
40-200/D190
1 x 5,5
46,4
42,7
41,2
40,4
33,1
29,7
23,3
21,5
19,6
40-200/75
0,6
11,7
40-200/D209
1 x 7,5
57,5
53,1
51,6
50,7
43,8
40,7
34,8
33,2
31,5
28,0
40-250/110A 40-250/D218
1 x 11
63,6
57,8
56,2
55,2
47,8
44,5
38,2
36,5
34,8
31,1
40-250/110
40-250/D233
1 x 11
71,7
66,0
64,3
63,4
55,7
52,3
45,8
44,0
42,1
38,3
40-250/150
40-250/D251
1 x 15
85,0
78,6
76,9
76,0
68,4
65,0
58,6
56,8
55,0
51,1
Performance levels relative to set with 1 service pump running and compliant with ISO 9906 - Annex A.
OHn = risk class value referred to the required rated capacity (Tab.6 para 7.3.1 EN12845)
Inlet pressure drops must be deducted. Make sure these drops are less than 4.5m
The values shown identify performance levels according to the reference standard EN12845.
90
42,6
12845_1pg-st-shf40-2p50-en_a_th
Lowara
NPSH
REQUIRED FOR PUMP SERIES SHF 40
TABELLA DI PRESTAZIONI IDRAULICHE GRUPPI EN12845 SERIE SHF40 2 poli 50 Hz 1 POMPA DI SERVIZIO
RATED
SHF..
POWER
ELECTRIC
PUMP
PUMP
OH1m
TYPE
OH1n
RISK CLASS
l/min 0
300
375
540
640
677
700
725
750
800
833
850
1000
m3/h 0
18
23
32
38
41
42
44
45
48
50
51
60
Q = DELIVERY
kW
40-125/11
40-125/D112
1 x 1,1
0,7
1,0
1,5
2,0
40-125/15
40-125/D126
1 x 1,5
0,7
1,0
1,5
2,0
2,3
2,5
40-125/22
40-125/D143
1 x 2,2
0,7
1,0
1,5
2,0
2,3
2,5
2,8
3,1
40-160/30
40-160/D159
1x3
1,1
1,4
2,1
2,6
2,9
3,2
3,5
3,8
40-160/40
40-160/D171
1x4
1,1
1,4
2,1
2,6
2,9
3,2
3,5
3,8
4,9
40-200/55
40-200/D190
1 x 5,5
1,4
1,8
2,7
3,4
3,7
3,9
4,2
4,5
5,4
40-200/75
40-200/D209
1 x 7,5
1,4
1,8
2,7
3,4
3,7
3,9
4,2
4,5
5,4
6,4
40-250/110A 40-250/D218
1 x 11
1,4
1,4
1,7
3,0
4,1
5,0
40-250/110
40-250/D233
1 x 11
1,3
1,4
1,6
1,8
1,9
40-250/150
40-250/D251
1 x 15
1,3
1,4
1,6
1,8
1,9
2,2
2,5
3,3
4,3
2,1
The declared NPSH values were obtained in the laboratory and refer to a single service pump
OHn, OHm = risk class value referred to the required rated and maximum capacity (Tab.6 para 7.3.1 EN12845)
Check that NPSHd NPSHr+1m is satisfied at the maximum requested capacity
91
5,0
12845_1p-shf40-2p50_NPSHr-en_a_th
Lowara
HYDRA
ULIC PERFORMANCE T
ABLE A
T 50 HZ (POSITIVE SUCTION HEAD)
HYDRAULIC
TABLE
AT
TABELLA DI PRESTAZIONI IDRAULICHE NETTE GRUPPI EN12845 SERIE SHF50 2 poli 50 Hz 1 POMPA DI SERVIZIO, ASPESCLUSA INST SOPRA
GEN../SHF 50 BOOSTER SETS SERIES
RATED
SHF..
POWER
ELECTRIC
PUMP
PUMP
OH3n
TYPE
OH2n
RISK CLASS
Q = DELIVERY
l/min 0
600
680
725
1000
1100
1200
1300
1350
1380
1400
1450
1500
m3/h 0
36
41
44
60
66
72
78
81
83
84
87
90
12,5
10,4
kW
50-125/22
50-125/D119
1 x 2,2
17,2 13,2
12,0
11,3
5,9
3,6
1,2
50-125/30
50-125/D130
1x3
21,7 17,4
16,1
15,3
9,8
7,6
5,2
50-125/40
50-125/D139
1x4
25,6 21,8
20,6
19,8
14,4
12,1
9,8
7,3
6,0
5,3
4,7
50-160/55
50-160/D158
1 x 5,5
34,0 29,3
27,8
26,9
20,4
17,5
14,4
11,1
9,4
8,3
7,6
50-160/75
2,8
50-160/D174
1 x 7,5
40,7 36,1
34,7
33,9
27,6
24,7
21,6
18,1
16,3
15,2
14,4
50-200/110A 50-200/D197
1 x 11
34,0 29,3
27,8
26,9
20,4
17,5
14,4
11,1
9,4
8,3
7,6
50-200/110
50-200/D209
1 x 11
40,7 36,1
34,7
33,9
27,6
24,7
21,6
18,1
16,3
15,2
14,4
12,5
50-250/150
50-250/D224
1 x 15
70,3 65,5
64,0
63,0
54,6
50,4
45,4
39,6
50-250/185
50-250/D237
1 x 18,5
80,1 73,8
72,1
71,1
62,8
58,7
54,1
48,9
46,0
44,2
50-250/220
50-250/D250
1 x 22
88,9 83,2
81,6
80,6
72,3
68,4
64,0
59,1
56,4
54,7
53,6
50,6
Performance levels relative to set with 1 service pump running and compliant with ISO 9906 - Annex A.
12845_1pg-sp-shf50-2p50-en_a_th
OHn = risk class value referred to the required rated capacity (Tab.6 para 7.3.1 EN12845)
Inlet pressure drops must be deducted. Make sure that these drops, added to the difference in level (max. 3.2m), are less than 4.5m
The values shown identify performance levels according to the reference standard EN12845.
HYDRA
ULIC PERFORMANCE T
ABLE A
T 50 HZ (SUCTION LIF
T)
HYDRAULIC
TABLE
AT
LIFT)
TABELLA DI PRESTAZIONI IDRAULICHE NETTE GRUPPI EN12845 SERIE SHF50 2 poli 50 Hz 1 POMPA DI SERVIZIO, ASPESCLUSA INST SOTTO
GEN../SHF 50 BOOSTER SETS SERIES
RATED
SHF..
POWER
ELECTRIC
PUMP
PUMP
OH3n
TYPE
OH2n
RISK CLASS
Q = DELIVERY
l/min 0
600
680
725
1000
1100
1200
1300
1350
1380
1400
1450
1500
m3/h 0
36
41
44
60
66
72
78
81
83
84
87
90
12,5
10,4
kW
50-125/22
50-125/D119
1 x 2,2
17,2 13,2
12,0
11,3
5,9
3,6
1,2
50-125/30
50-125/D130
1x3
21,7 17,4
16,1
15,3
9,8
7,6
5,2
2,8
50-125/40
50-125/D139
1x4
25,6 21,8
20,6
19,8
14,4
12,1
9,8
7,3
50-160/55
50-160/D158
1 x 5,5
34,0 29,3
27,8
26,9
20,4
17,5
14,4
11,1
9,4
8,3
7,6
50-160/75
50-160/D174
1 x 7,5
40,7 36,1
34,7
33,9
27,6
24,7
21,6
18,1
16,3
15,2
14,4
50-200/110A 50-200/D197
1 x 11
34,0 29,3
27,8
26,9
20,4
17,5
14,4
11,1
9,4
8,3
7,6
50-200/110
50-200/D209
1 x 11
40,7 36,1
34,7
33,9
27,6
24,7
21,6
18,1
16,3
15,2
14,4
12,5
50-250/150
50-250/D224
1 x 15
70,3 65,5
64,0
63,0
54,6
50,4
45,4
39,6
50-250/185
50-250/220
50-250/D237
50-250/D250
1 x 18,5
1 x 22
80,1 73,8
88,9 83,2
72,1
81,6
71,1
80,6
62,8
72,3
58,7
68,4
54,1
64,0
48,9
59,1
46,0
56,4
44,2
54,7
53,6
50,6
Performance levels relative to set with 1 service pump running and compliant with ISO 9906 - Annex A.
OHn = risk class value referred to the required rated capacity (Tab.6 para 7.3.1 EN12845)
Inlet pressure drops must be deducted. Make sure these drops are less than 4.5m
The values shown identify performance levels according to the reference standard EN12845.
92
6,0
5,3
4,7
12845_1pg-st-shf50-2p50-en_a_th
Lowara
NPSH REQUIRED FOR PUMP SERIES SHF 50
TABELLA DI PRESTAZIONI IDRAULICHE NPSHr GRUPPI EN12845 SERIE SHF50 2 poli 50 Hz 1 POMPA DI SERVIZIO
POWER
3
PUMP
PUMP
600
680
725
1000
1100
1200
1300
1350
1380
1400
1450
1500
36
41
44
60
66
72
78
81
83
84
87
90
6,5
7,6
Q = DELIVERY
l/min 0
ELECTRIC
OH3m
SHF..
OH3n
RATED
OH2m
TYPE
OH2n
RISK CLASS
m /h 0
kW
50-125/22
50-125/D119
1 x 2,2
1,6
1,8
1,9
2,8
3,4
4,3
50-125/30
50-125/D130
1x3
1,6
1,8
1,9
2,7
3,1
3,7
4,6
50-125/40
50-125/D139
1x4
1,6
1,8
1,9
2,7
3,1
3,7
4,6
5,2
5,7
6,0
50-160/55
50-160/D158
1 x 5,5
2,0
2,1
2,1
2,8
3,2
3,7
4,7
5,4
5,9
6,3
50-160/75
50-160/D174
1 x 7,5
1,9
2,1
2,2
2,8
3,1
3,6
4,3
4,9
5,3
5,6
50-200/110A 50-200/D197
1 x 11
2,0
2,1
2,1
2,8
3,2
4,0
5,2
6,1
6,7
7,2
50-200/110
50-200/D209
1 x 11
1,9
2,1
2,2
2,8
3,2
3,7
4,7
5,4
5,9
6,3
7,5
50-250/150
50-250/D224
1 x 15
1,6
1,7
1,8
2,3
2,7
3,3
4,8
50-250/185
50-250/D237
1 x 18,5
1,5
1,7
1,8
2,4
2,7
3,1
3,7
4,1
4,4
50-250/220
50-250/D250
1 x 22
1,5
1,7
1,8
2,4
2,7
3,1
3,7
4,1
4,7
5,4
The declared NPSH values were obtained in the laboratory and refer to a single service pump
OHn, OHm = risk class value referred to the required rated and maximum capacity (Tab.6 para 7.3.1 EN12845)
Check that NPSHd NPSHr+1m is satisfied at the maximum requested capacity
93
4,4
12845_1p-shf50-2p50_NPSHr-en_a_th
Lowara
HYDRA
ULIC PERFORMANCE T
ABLE A
T 50 HZ (POSITIVE SUCTION HEAD)
HYDRAULIC
TABLE
AT
TABELLA DI PRESTAZIONI IDRAULICHE NETTE GRUPPI EN12845 SERIE SHF65 2 poli 50 Hz 1 POMPA DI SERVIZIO, ASP ESCLUSA INST SOPRA
GEN../SHF 65 BOOSTER SETS SERIES
RATED
SHF..
POWER
ELECTRIC
PUMP
PUMP
OH4n
TYPE
OH3n
RISK CLASS
Q = DELIVERY
l/min 0
800
900
1000
1100
1350
1500
1800
1900
2000
2050
2100
2200
m3/h 0
48
54
60
66
81
90
108
114
120
123
126
132
kW
65-160/40
65-160/D119
1x4
19,6
15,9
14,9
13,8
12,6
9,4
7,3
2,9
65-160/55
65-160/D129
1 x 5,5
24,2
20,5
19,5
18,4
17,2
13,9
11,7
7,0
5,4
65-160/75
65-160/D137
1 x 7,5
28,2
25,1
24,2
23,1
22,0
18,8
16,7
12,0
10,4
65-160/110A 65-160/D168
1 x 11
38,2
34,3
33,0
31,5
29,8
25,2
22,0
15,2
12,9
39,7
38,4
36,9
35,3
30,6
27,4
20,5
18,1
47,5
45,9
44,1
38,9
35,3
27,1
24,1
65-160/110
65-160/D177
1 x 11
42,9
65-200/150
65-200/D192
1 x 15
53,0
8,7
15,6
65-200/185
65-200/D203
1 x 18,5
60,2
55,2
53,6
51,9
46,9
43,4
35,5
32,6
29,5
65-200/220
65-200/D215
1 x 22
68,0
63,0
61,6
60,0
55,2
51,9
44,3
41,5
38,5
37,0
35,5
65-250/300
65-250/D240
1 x 30
83,7
80,2
78,9
74,9
71,9
64,4
61,4
58,3
56,6
54,9
65-250/370
65-250/D255
1 x 37
96,7
93,6
92,2
88,0
84,9
77,4
74,6
71,7
70,1
68,5
65,2
Performance levels relative to set with 1 service pump running and compliant with ISO 9906 - Annex A.
12845_1pg-sp-shf65-2p50-en_a_th
OHn = risk class value referred to the required rated capacity (Tab.6 para 7.3.1 EN12845)
Inlet pressure drops must be deducted. Make sure that these drops, added to the difference in level (max. 3.2m), are less than 4.5m
The values shown identify performance levels according to the reference standard EN12845.
HYDRA
ULIC PERFORMANCE T
ABLE A
T 50 HZ (SUCTION LIF
T)
HYDRAULIC
TABLE
AT
LIFT)
TABELLA DI PRESTAZIONI IDRAULICHE NETTE GRUPPI EN12845 SERIE SHF65 2 poli 50 Hz 1 POMPA DI SERVIZIO, ASP ESCLUSA INST SOTTO
GEN../SHF 65 BOOSTER SETS SERIES
RATED
SHF..
POWER
ELECTRIC
PUMP
PUMP
OH4n
TYPE
OH3n
RISK CLASS
Q = DELIVERY
l/min 0
800
900
1000
1100
1350
1500
1800
1900
2000
2050
2100
2200
m3/h 0
48
54
60
66
81
90
108
114
120
123
126
132
kW
65-160/40
65-160/D119
1x4
19,6
15,9
14,9
13,8
12,6
9,4
7,3
2,9
65-160/55
65-160/D129
1 x 5,5
24,2
20,5
19,5
18,4
17,2
13,9
11,7
7,0
5,4
65-160/75
65-160/D137
1 x 7,5
28,2
25,1
24,2
23,1
22,0
18,8
16,7
12,0
10,4
65-160/110A 65-160/D168
1 x 11
38,2
34,3
33,0
31,5
29,8
25,2
22,0
15,2
12,9
39,7
38,4
36,9
35,3
30,6
27,4
20,5
18,1
47,5
45,9
44,1
38,9
35,3
27,1
24,1
65-160/110
65-160/D177
1 x 11
42,9
65-200/150
65-200/D192
1 x 15
53,0
8,7
15,6
65-200/185
65-200/D203
1 x 18,5
60,2
55,2
53,6
51,9
46,9
43,4
35,5
32,6
29,5
65-200/220
65-200/D215
1 x 22
68,0
63,0
61,6
60,0
55,2
51,9
44,3
41,5
38,5
37,0
35,5
65-250/300
65-250/D240
1 x 30
83,7
80,2
78,9
74,9
71,9
64,4
61,4
58,3
56,6
54,9
65-250/370
65-250/D255
1 x 37
96,7
93,6
92,2
88,0
84,9
77,4
74,6
71,7
70,1
68,5
Performance levels relative to set with 1 service pump running and compliant with ISO 9906 - Annex A.
OHn = risk class value referred to the required rated capacity (Tab.6 para 7.3.1 EN12845)
Inlet pressure drops must be deducted. Make sure these drops are less than 4.5m
The values shown identify performance levels according to the reference standard EN12845.
94
65,2
12845_1pg-st-shf65-2p50-en_a_th
Lowara
NPSH
REQUIRED FOR PUMP SERIES SHF 65
TABELLA DI PRESTAZIONI IDRAULICHE NPSHr GRUPPI EN12845 SERIE SHF65 2 poli 50 Hz 1 POMPA DI SERVIZIO
POWER
ELECTRIC
PUMP
PUMP
OH4m
SHF..
l/min 0
800
900
1000
1100
1350
1400
1500
1800
1900
2000
2100
2200
m3/h 0
48
54
60
66
81
84
90
108
114
120
126
132
OH4n
RATED
OH3m
TYPE
OH3n
RISK CLASS
Q = DELIVERY
kW
65-160/40
65-160/D119
1x4
1,9
1,8
1,9
1,9
2,5
2,7
3,3
7,4
65-160/55
65-160/D129
1 x 5,5
1,9
1,9
1,9
1,9
2,4
2,6
3,1
5,4
6,6
65-160/75
65-160/D137
1 x 7,5
1,9
1,9
1,9
1,9
2,4
2,6
3,1
5,4
6,6
65-160/110A 65-160/D168
1 x 11
1,3
1,4
1,6
1,7
2,1
2,1
2,4
3,5
4,2
1,3
1,4
1,6
1,7
2,1
2,1
2,4
3,5
4,2
1,7
1,7
1,6
1,7
1,7
1,9
4,1
6,4
65-160/110
65-160/D177
1 x 11
65-200/150
65-200/D192
1 x 15
8,0
5,2
65-200/185
65-200/D203
1 x 18,5
1,7
1,7
1,6
1,7
1,7
1,9
3,0
3,9
5,3
65-200/220
65-200/D215
1 x 22
1,7
1,7
1,6
1,7
1,7
1,9
3,0
3,9
5,3
7,5
65-250/300
65-250/D240
1 x 30
1,3
1,3
1,4
1,5
1,7
3,2
4,1
5,4
7,0
65-250/370
65-250/D255
1 x 37
1,3
1,3
1,3
1,4
1,6
2,9
3,7
4,8
6,2
The declared NPSH values were obtained in the laboratory and refer to a single service pump
OHn, OHm = risk class value referred to the required rated and maximum capacity (Tab.6 para 7.3.1 EN12845)
Check that NPSHd NPSHr+1m is satisfied at the maximum requested capacity
95
8,1
12845_1p-shf65-2p50_NPSHr-en_a_th
Lowara
HYDRA
ULIC PERFORMANCE T
ABLE A
T 50 HZ (POSITIVE SUCTION HEAD)
HYDRAULIC
TABLE
AT
TABELLA DI PRESTAZIONI IDRAULICHE NETTE GRUPPI EN12845 SERIE SHF80 2 poli 50 Hz 1 POMPA DI SERVIZIO, ASP ESCLUSA INST SOPRA
GEN../SHF 80 BOOSTER SETS SERIES
RATED
SHF..
POWER
ELECTRIC
PUMP
PUMP
80-160/110
80-160/150
80-160/185
80-200/220
80-200/300
80-200/370
80-250/450
80-250/550
80-250/750
Q = DELIVERY
l/min 0
1200
1500
1800
2100
2300
3216
3300
3500
3600
3700
3800
4000
m3/h 0
72
90
108
126
138
193
198
210
216
222
228
240
14,1
20,2
31,1
40,4
44,6
59,6
77,0
12,4
29,3
38,5
27,4
36,6
32,7
57,3
74,8
72,5
kW
80-160/D169
80-160/D177
80-160/D186
80-200/D198
80-200/D215
80-200/D226
80-250/D237
80-250/D252
80-250/D270
1 x 11
1 x 15
1 x 18,5
1 x 22
1 x 30
1 x 37
1 x 45
1 x 55
1 x 75
HH1n
TYPE
OH4n
RISK CLASS
33,0
39,5
46,4
51,9
62,2
69,8
82,2
93,9
109,7
30,9
37,8
44,7
69,9
28,6
35,6
42,6
48,5
59,7
68,1
79,1
91,9
108,6
25,7
32,7
39,8
45,8
57,1
65,7
76,2
89,2
106,0
22,2
29,4
36,6
42,5
53,9
62,8
72,6
85,9
102,7
19,7
26,9
34,2
40,1
51,5
60,5
69,8
83,2
100,2
6,2
13,2
20,7
26,7
37,8
47,2
53,3
67,7
85,0
4,8
11,8
19,3
25,3
36,4
45,7
51,5
66,0
83,3
8,4
15,9
21,9
32,9
42,2
47,0
61,8
79,2
Performance levels relative to set with 1 service pump running and compliant with ISO 9906 - Annex A.
12845_1pg-sp-shf80-2p50-en_a_th
OHn = risk class value referred to the required rated capacity (Tab.6 para 7.3.1 EN12845)
Inlet pressure drops must be deducted. Make sure that these drops, added to the difference in level (max. 3.2m), are less than 4.5m
The values shown identify performance levels according to the reference standard EN12845.
HYDRA
ULIC PERFORMANCE T
ABLE A
T 50 HZ (SUCTION LIF
T)
HYDRAULIC
TABLE
AT
LIFT)
TABELLA DI PRESTAZIONI IDRAULICHE NETTE GRUPPI EN12845 SERIE SHF80 2 poli 50 Hz 1 POMPA DI SERVIZIO, ASP ESCLUSA INST SOTTO
GEN../SHF 80 BOOSTER SETS SERIES
RATED
SHF..
POWER
ELECTRIC
PUMP
PUMP
80-160/110
80-160/150
80-160/185
80-200/220
80-200/300
80-200/370
80-250/450
80-250/550
80-250/750
Q = DELIVERY
l/min 0
1200
1500
1800
2100
2300
3216
3300
3500
3600
3700
3800
4000
m3/h 0
72
90
108
126
138
193
198
210
216
222
228
240
14,1
20,2
31,1
40,4
44,6
59,6
77,0
12,4
29,3
38,5
27,4
36,6
32,7
57,3
74,8
72,5
kW
80-160/D169
80-160/D177
80-160/D186
80-200/D198
80-200/D215
80-200/D226
80-250/D237
80-250/D252
80-250/D270
1 x 11
1 x 15
1 x 18,5
1 x 22
1 x 30
1 x 37
1 x 45
1 x 55
1 x 75
HH1n
TYPE
OH4n
RISK CLASS
33,0
39,5
46,4
51,9
62,2
69,8
82,2
93,9
109,7
30,9
37,8
44,7
69,9
28,6
35,6
42,6
48,5
59,7
68,1
79,1
91,9
108,6
25,7
32,7
39,8
45,8
57,1
65,7
76,2
89,2
106,0
22,2
29,4
36,6
42,5
53,9
62,8
72,6
85,9
102,7
19,7
26,9
34,2
40,1
51,5
60,5
69,8
83,2
100,2
6,2
13,2
20,7
26,7
37,8
47,2
53,3
67,7
85,0
Performance levels relative to set with 1 service pump running and compliant with ISO 9906 - Annex A.
OHn = risk class value referred to the required rated capacity (Tab.6 para 7.3.1 EN12845)
Inlet pressure drops must be deducted. Make sure these drops are less than 4.5m
The values shown identify performance levels according to the reference standard EN12845.
96
4,8
11,8
19,3
25,3
36,4
45,7
51,5
66,0
83,3
8,4
15,9
21,9
32,9
42,2
47,0
61,8
79,2
12845_1pg-st-shf80-2p50-en_a_th
Lowara
NPSH REQUIRED FOR PUMP SERIES SHF 80
TABELLA DI PRESTAZIONI IDRAULICHE GRUPPI EN12845 SERIE SHF80 2 poli 50 Hz 1 POMPA DI SERVIZIO
POWER
ELECTRIC
PUMP
PUMP
80-160/110
80-160/150
80-160/185
80-200/220
80-200/300
80-200/370
80-250/450
80-250/550
80-250/750
l/min 0
1200
1500
1800
2100
2300
3216
3300
3500
3600
3700
3800
4000
m3/h 0
72
90
108
126
138
193
198
210
216
222
228
240
6,1
4,9
4,4
4,4
4,6
4,6
4,6
6,8
4,7
4,7
5,0
5,0
6,0
5,1
5,1
6,0
Q = DELIVERY
kW
80-160/D169
80-160/D177
80-160/D186
80-200/D198
80-200/D215
80-200/D226
80-250/D237
80-250/D252
80-250/D270
1 x 11
1 x 15
1 x 18,5
1 x 22
1 x 30
1 x 37
1 x 45
1 x 55
1 x 75
HH1m
SHF..
HH1n
RATED
OH4m
TYPE
OH4n
RISK CLASS
2,3
2,3
2,3
2,0
2,5
2,5
2,5
2,2
2,2
2,2
1,9
1,9
1,9
2,7
2,7
2,7
2,4
2,4
2,4
2,2
2,2
2,2
3,0
2,9
2,9
2,7
2,6
2,6
2,4
2,4
2,4
3,2
3,0
3,0
2,8
2,8
2,8
2,6
2,6
2,6
5,9
4,3
4,3
3,9
3,7
3,7
3,6
3,6
3,6
6,5
4,6
4,6
4,1
3,8
3,8
3,7
3,7
3,7
5,5
5,5
4,6
4,2
4,2
4,2
4,2
4,2
The declared NPSH values were obtained in the laboratory and refer to a single service pump
12845_1p-shf80-2p50_NPSHr-en_a_th
OHn, OHm, HHn, HHm = risk class value referred to the required rated and maximum capacity (Tab.6 para 7.3.1, Tab.7 para 7.3.2 EN12845)
Check that NPSHd NPSHr+1m is satisfied at the maximum requested capacity
97
Lowara
GEN../SHF 32-80 BOOSTER SETS
TABELLA DATI ELETTRICI GRUPPI GEN../SHF 2 poli 50 Hz
ELECTRICAL DA
TA T
ABLE A
T 50 Hz
DAT
TABLE
AT
ELECTRIC
ELECTRIC
CURRENT
SERVICE PUMP
JOCKEY PUMP
ABSORBED SET
3 X 400 V
3 X 400V
3 X 400 V
TYPE
NOMINAL
SHF..
ELECTRIC
POWER
PUMP
PUMP
32-125/07
32-125/11
32-160/15
32-160/22
32-200/30
32-200/40
32-250/55
32-250/75
32-250/110
40-125/11
40-125/15
40-125/22
40-160/30
40-160/40
40-200/55
40-200/75
40-250/110A
40-250/110
40-250/150
50-125/22
50-125/30
50-125/40
50-160/55
50-160/75
50-200/110A
50-200/110
50-250/150
50-250/185
50-250/220
65-160/40
65-160/55
65-160/75
65-160/110A
65-160/110
65-200/150
65-200/185
65-200/220
65-250/300
65-250/370
80-160/110
80-160/150
80-160/185
80-200/220
80-200/300
80-200/370
80-250/450
80-250/550
80-250/750
32-125/D121
32-125/D136
32-160/D150
32-160/D168
32-200/D188
32-200/D204
32-250/D222
32-250/D242
32-250/D256
40-125/D112
40-125/D126
40-125/D143
40-160/D159
40-160/D171
40-200/D190
40-200/D209
40-250/D218
40-250/D233
40-250/D251
50-125/D119
50-125/D130
50-125/D139
50-160/D158
50-160/D174
50-200/D197
50-200/D209
50-250/D224
50-250/D237
50-250/D250
65-160/D119
65-160/D129
65-160/D137
65-160/D168
65-160/D177
65-200/D192
65-200/D203
65-200/D215
65-250/D240
65-250/D255
80-160/D169
80-160/D177
80-160/D186
80-200/D198
80-200/D215
80-200/D226
80-250/D237
80-250/D252
80-250/D270
Pn
In
kW
0,75
1,1
1,5
2,2
3
4
5,5
7,5
11
1,1
1,5
2,2
3
4
5,5
7,5
11
11
15
2,2
3
4
5,5
7,5
11
11
15
18,5
22
4
5,5
7,5
11
11
15
18,5
22
30
37
11
15
18,5
22
30
37
45
55
75
2,15
2,61
3,02
4,68
5,77
7,59
10,70
13,90
19,80
2,61
3,02
4,68
5,77
7,59
10,70
13,90
19,80
19,80
26,20
4,68
5,77
7,59
10,70
13,90
19,80
19,80
26,20
33,40
41,70
7,59
10,70
13,90
19,80
19,80
26,20
33,40
41,70
54,00
65,00
19,80
26,70
33,40
41,70
54,00
65,00
80,00
99,00
133,00
TYPE
SV206
SV206
SV206
SV206
SV206
SV209
SV209
SV209
SV209
SV206
SV206
SV206
SV206
SV206
SV206
SV209
SV209
SV209
SV209
SV206
SV206
SV206
SV206
SV206
SV209
SV209
SV209
SV209
SV209
SV206
SV206
SV206
SV206
SV206
SV209
SV209
SV209
SV209
SV212
SV407
SV407
SV407
SV407
SV409
SV409
SV409
SV413
SV413
Pn
In
GEN..10
GEN..11
GEN..20
kW
0,75
0,75
0,75
0,75
0,75
1,1
1,1
1,1
1,1
0,75
0,75
0,75
0,75
0,75
0,75
1,1
1,1
1,1
1,1
0,75
0,75
0,75
0,75
0,75
1,1
1,1
1,1
1,1
1,1
0,75
0,75
0,75
0,75
0,75
1,1
1,1
1,1
1,1
1,5
1,1
1,1
1,1
1,1
1,5
1,5
1,5
2,2
2,2
2,02
2,02
2,02
2,02
2,02
2,61
2,61
2,61
2,61
2,02
2,02
2,02
2,02
2,02
2,02
2,61
2,61
2,61
2,61
2,02
2,02
2,02
2,02
2,02
2,61
2,61
2,61
2,61
2,61
2,02
2,02
2,02
2,02
2,02
2,61
2,61
2,61
2,61
3,45
2,61
2,61
2,61
2,61
3,45
3,45
3,45
5,03
5,03
2,15
2,61
3,02
4,68
5,77
7,59
10,70
13,90
19,80
2,61
3,02
4,68
5,77
7,59
10,70
13,90
19,80
19,80
26,20
4,68
5,77
7,59
10,70
13,90
19,80
19,80
26,20
33,40
41,70
7,59
10,70
13,90
19,80
19,80
26,20
33,40
41,70
54,00
65,00
19,80
26,70
33,40
41,70
54,00
65,00
80,00
99,00
133,00
4,17
4,63
5,04
6,70
7,79
10,20
13,31
16,51
22,41
4,63
5,04
6,70
7,79
9,61
12,72
16,51
22,41
22,41
28,81
6,70
7,79
9,61
12,72
15,92
22,41
22,41
28,81
36,01
44,31
9,61
12,72
15,92
21,82
21,82
28,81
36,01
44,31
56,61
68,45
22,41
29,31
36,01
44,31
57,45
68,45
83,45
104,03
138,03
4,30
5,22
6,04
9,36
11,54
15,18
21,40
27,80
39,60
5,22
6,04
9,36
11,54
15,18
21,40
27,80
39,60
39,60
52,40
9,36
11,54
15,18
21,40
27,80
39,60
39,60
52,40
66,80
83,40
15,18
21,40
27,80
39,60
39,60
52,40
66,80
83,40
108,00
130,00
39,60
53,40
66,80
83,40
108,00
130,00
160,00
198,00
266,00
6,32
7,24
8,06
11,38
13,56
17,79
24,01
30,41
42,21
7,24
8,06
11,38
13,56
17,20
23,42
30,41
42,21
42,21
55,01
11,38
13,56
17,20
23,42
29,82
42,21
42,21
55,01
69,41
86,01
17,20
23,42
29,82
41,62
41,62
55,01
69,41
86,01
110,61
133,45
42,21
56,01
69,41
86,01
111,45
133,45
163,45
203,03
271,03
The current indicated is the maximum current absorbed by the electric pumps.
GEN..21
ENELP-SHF_2p50-en_b_te
98
Lowara
Fire-fighting
booster sets
EN 12845
MARKET SECTORS
CIVIL, INDUSTRIAL
APPLICA
TIONS
APPLICATIONS
Fixed fire-fighting systems.
GEN..10/SHF
Series
SPECIFICA
TIONS
SPECIFICATIONS
Flow up to 220 m3/h.
Head up to 100 m.
Panel supply power voltage:
3 x 400V 10%.
Motor start-up :
Frequency: 50 Hz.
Voltage for controls outside panel:
24 Vac.
Protection grade:
99
Lowara
GEN..10/SHF 32-80 SERIES
FIRE-FIGHTING BOOSTER SETS EN 12845
100
Lowara
GEN..10/SHF 32-80 SERIES
FIRE-FIGHTING BOOSTER SETS EN 12845
GEN..10
DRW
DNA
DNM
N
SHF32-125/07
R 2"
Rp 1" 1/2
740
80
212
360
820
773
1347
SHF32-125/11
R 2"
Rp 1" 1/2
740
80
212
360
820
773
1347
SHF32-160/15
R 2"
Rp 1" 1/2
840
80
232
390
920
813
1387
SHF32-160/22
R 2"
Rp 1" 1/2
840
80
232
390
920
813
1387
SHF32-200/30
R 2"
Rp 1" 1/2
840
80
260
390
920
861
1435
SHF32-200/40
R 2"
Rp 1" 1/2
840
80
260
390
920
861
1435
SHF32-250/55
R 2"
Rp 1" 1/2
1045
100
280
490
1145
926
1500
SHF32-250/75
R 2"
Rp 1" 1/2
1045
100
280
490
1145
926
1500
SHF32-250/110
R 2"
Rp 1" 1/2
1175
100
280
540
1275
926
1500
SHF40-125/11
65
65
740
80
212
360
820
994
1582
SHF40-125/15
65
65
840
80
212
390
920
994
1582
SHF40-125/22
65
65
840
80
212
390
920
994
1582
SHF40-160/30
65
65
840
80
232
390
920
1034
1622
SHF40-160/40
65
65
840
80
232
390
920
1034
1622
SHF40-200/55
65
65
940
100
260
450
1040
1082
1670
SHF40-200/75
65
65
940
100
260
450
1040
1082
1670
SHF40-250/110A
65
65
1175
100
280
540
1275
1147
1735
SHF40-250/110
65
65
1175
100
280
540
1275
1147
1735
SHF40-250/150
65
65
1175
100
280
540
1275
1147
1735
SHF50-125/22
65
65
840
100
232
390
940
1116
1704
SHF50-125/30
65
65
840
100
232
390
940
1116
1704
SHF50-125/40
65
65
840
100
232
390
940
1116
1704
SHF50-160/55
65
65
940
100
260
450
1040
1164
1752
SHF50-160/75
65
65
940
100
260
450
1040
1164
1752
SHF50-200/110A
65
65
1060
100
260
490
1160
1184
1772
SHF50-200/110
65
65
1060
100
260
490
1160
1184
1772
SHF50-250/150
65
65
1175
100
280
540
1275
1229
1817
SHF50-250/185
65
65
1175
100
280
540
1275
1229
1817
SHF50-250/220
65
65
1175
100
280
540
1275
1229
1817
SHF65-160/40
80
80
825
100
260
390
925
1221
1815
SHF65-160/55
80
80
925
100
260
450
1025
1221
1815
SHF65-160/75
80
80
925
100
260
450
1025
1221
1815
SHF65-160/110A
80
80
1175
100
260
540
1275
1241
1835
SHF65-160/110
80
80
1175
100
260
540
1275
1241
1835
SHF65-200/150
80
80
1175
100
280
540
1275
1286
1880
SHF65-200/185
80
80
1175
100
280
540
1275
1286
1880
SHF65-200/220
80
80
1175
100
280
540
1275
1286
1880
SHF65-250/300
80
80
1310
100
310
610
1410
1341
1935
SHF65-250/370
80
80
1310
100
310
610
1410
1341
1935
SHF80-160/110
100
100
1175
125
280
540
1300
1354
1961
SHF80-160/150
100
100
1175
125
280
540
1300
1354
1961
SHF80-160/185
100
100
1175
125
280
540
1300
1354
1961
SHF80-200/220
100
100
1175
125
280
540
1300
1379
1986
SHF80-200/300
100
100
1325
125
310
610
1450
1409
2016
SHF80-200/370
100
100
1310
125
310
610
1435
1439
2046
SHF80-250/450
100
100
1310
125
365
610
1435
1494
2101
SHF80-250/550
100
100
1510
125
390
660
1635
1519
2126
100
1710
125
420
730
1835
1549
SHF80-250/750
2
100
Dimensions in mm. Tolerance 10 mm.
2156
gen10_shf-en_d_td
101
Lowara
102
Lowara
Fire-fighting
booster sets
EN 12845
MARKET SECTORS
CIVIL, INDUSTRIAL
APPLICA
TIONS
APPLICATIONS
Fixed fire-fighting systems.
Automatic Sprinkler systems.
GEN..11/SHF
Series
SPECIFICA
TIONS
SPECIFICATIONS
Flow up to 220 m3/h.
Head up to 100 m.
Panel supply power voltage:
3 x 400V 10%.
Motor start-up :
Frequency: 50 Hz.
Voltage for controls outside panel:
24 Vac.
ey pump
Electric jock
jockey
Protection grade:
103
Lowara
GEN..11/SHF 32-80 SERIES
FIRE-FIGHTING BOOSTER SETS EN 12845
104
Lowara
GEN..11/SHF 32-80 SERIES
FIRE-FIGHTING BOOSTER SETS EN 12845
GEN..11
DRW DNA
DNP
DNM
A1
N
SHF32-125/07
R 2"
Rp 1"
Rp 1" 1/2
320
260
240
590
45
225
950
955
873 1447
SHF32-125/11
R 2"
Rp 1"
Rp 1" 1/2
320
260
240
590
45
225
950
955
873 1447
SHF32-160/15
R 2"
Rp 1"
Rp 1" 1/2
327
253
240
650
65
225
SHF32-160/22
R 2"
Rp 1"
Rp 1" 1/2
327
253
240
650
65
225
SHF32-200/30
R 2"
Rp 1"
Rp 1" 1/2
327
253
240
650
65
225
SHF32-200/40
R 2"
Rp 1"
Rp 1" 1/2
327
253
240
650
65
225
SHF32-250/55
R 2"
Rp 1"
Rp 1" 1/2
448
282
240
790
90
245
SHF32-250/75
R 2"
Rp 1"
Rp 1" 1/2
448
282
240
790
90
245
SHF32-250/110
R 2"
Rp 1"
Rp 1" 1/2
459
271
280
890
105
245
SHF40-125/11
65
Rp 1"
65
327
253
240
590
45
225
950
SHF40-125/15
65
Rp 1"
65
327
253
240
650
65
225
SHF40-125/22
65
Rp 1"
65
327
253
240
650
65
225
SHF40-160/30
65
Rp 1"
65
327
253
240
650
65
225
SHF40-160/40
65
Rp 1"
65
327
253
240
650
65
225
SHF40-200/55
65
Rp 1"
65
338
222
240
710
85
245
SHF40-200/75
65
Rp 1"
65
338
222
240
710
85
245
SHF40-250/110A
65
Rp 1"
65
459
271
280
890
105
245
SHF40-250/110
65
Rp 1"
65
459
271
280
890
105
245
SHF40-250/150
65
Rp 1"
65
459
271
280
890
105
245
SHF50-125/22
65
Rp 1"
65
327
253
240
650
65
225
SHF50-125/30
65
Rp 1"
65
327
253
240
650
65
225
SHF50-125/40
65
Rp 1"
65
327
253
240
650
65
225
SHF50-160/55
65
Rp 1"
65
338
222
240
710
85
245
SHF50-160/75
65
Rp 1"
65
338
222
240
710
85
245
SHF50-200/110A
65
Rp 1"
65
448
282
280
790
105
245
SHF50-200/110
65
Rp 1"
65
448
282
280
790
105
245
SHF50-250/150
65
Rp 1"
65
459
271
280
890
105
245
SHF50-250/185
65
Rp 1"
65
459
271
280
890
105
245
SHF50-250/220
65
Rp 1"
65
459
271
280
890
105
245
SHF65-160/40
80
Rp 1"
80
323
237
240
650
50
225
SHF65-160/55
80
Rp 1"
80
338
392
240
710
70
245
SHF65-160/75
80
Rp 1"
80
338
392
240
710
70
245
SHF65-160/110A
80
Rp 1"
80
459
271
280
890
105
245
SHF65-160/110
80
Rp 1"
80
459
271
280
890
105
245
SHF65-200/150
80
Rp 1"
80
459
271
280
890
105
245
SHF65-200/185
80
Rp 1"
80
459
271
280
890
105
245
SHF65-200/220
80
Rp 1"
80
459
271
280
890
105
245
SHF65-250/300
80
Rp 1"
80
453
227
280
990
115
245
SHF65-250/370
80
Rp 1"
80
453
227
280
990
115
245
SHF80-160/110
100
459
271
280
890
105
245
SHF80-160/150
100
459
271
280
890
105
245
SHF80-160/185
100
459
271
280
890
105
245
SHF80-200/220
100
459
271
280
890
105
245
SHF80-200/300
100
453
227
280
990
130
245
SHF80-200/370
100
453
227
280
990
115
245
SHF80-250/450
100
453
227
330
990
115
245
SHF80-250/550
100
525
275
265
SHF80-250/750
2
100 Rp 1" 1/4
Dimensions in mm. Tolerance 10 mm.
(1) Dimensions on request.
100
(1)
(1)
265
560
600
(1)
105
Lowara
106
Lowara
Fire-fighting
booster sets
EN 12845
MARKET SECTORS
CIVIL, INDUSTRIAL
APPLICA
TIONS
APPLICATIONS
Fixed fire-fighting systems.
Automatic Sprinkler systems.
GEN..20/SHF
Series
SPECIFICA
TIONS
SPECIFICATIONS
Flow up to 440 m3/h.
Head up to 100 m.
Panel supply power voltage:
3 x 400V 10%.
Motor start-up :
Frequency: 50 Hz.
Voltage for controls outside panel:
24 Vac.
Protection grade:
12 bar.
107
Lowara
GEN..20/SHF 32-80 SERIES
FIRE-FIGHTING BOOSTER SETS EN 12845
108
Lowara
GEN..20/SHF 32-80 SERIES
FIRE-FIGHTING BOOSTER SETS EN 12845
GEN..20
DRW
DNA
DNM
N
SHF32-125/07
R 2"
R 2"
345
240
590
45
312
1400
480
1170
955
879
1459
SHF32-125/11
R 2"
R 2"
345
240
590
45
312
1400
480
1170
955
879
1459
SHF32-160/15
R 2"
R 2"
345
240
650
65
332
1400
480
1170
1035
919
1499
SHF32-160/22
R 2"
R 2"
345
240
650
65
332
1400
480
1170
1035
919
1499
SHF32-200/30
R 2"
R 2"
345
240
650
65
360
1400
480
1170
1035
967
1547
SHF32-200/40
R 2"
R 2"
345
240
650
65
360
1400
480
1170
1035
967
1547
SHF32-250/55
R 2"
R 2"
385
240
790
90
400
1420
630
1400
1220
1052
1632
SHF32-250/75
R 2"
R 2"
385
240
790
90
400
1420
630
1400
1220
1052
1632
SHF32-250/110
R 2"
R 2"
385
280
890
105
400
1570
630
1400
1375
1052
1632
SHF40-125/11
65
65
335
240
590
45
312
1400
540
1210
955
1094
1682
SHF40-125/15
65
65
335
240
650
65
312
1400
540
1210
1035
1094
1682
SHF40-125/22
65
65
335
240
650
65
312
1400
540
1210
1035
1094
1682
SHF40-160/30
65
65
335
240
650
65
332
1400
540
1210
1035
1134
1722
SHF40-160/40
65
65
335
240
650
65
332
1400
540
1210
1035
1134
1722
SHF40-200/55
65
65
335
240
710
85
380
1420
540
1210
1135
1202
1790
SHF40-200/75
65
65
335
240
710
85
380
1420
540
1210
1135
1202
1790
SHF40-250/110A
65
65
385
280
890
105
400
1570
630
1400
1375
1267
1855
SHF40-250/110
65
65
385
280
890
105
400
1570
630
1400
1375
1267
1855
SHF40-250/150
65
65
385
280
890
105
400
1570
630
1400
1375
1267
1855
SHF50-125/22
65
80
335
240
650
65
332
1400
540
1210
1055
1223
1817
SHF50-125/30
65
80
335
240
650
65
332
1400
540
1210
1055
1223
1817
SHF50-125/40
65
80
335
240
650
65
332
1400
540
1210
1055
1223
1817
SHF50-160/55
65
80
335
240
710
85
380
1420
540
1210
1135
1291
1885
SHF50-160/75
65
80
335
240
710
85
380
1420
540
1210
1135
1291
1885
SHF50-200/110A
65
80
385
280
790
105
380
1570
630
1400
1275
1311
1905
SHF50-200/110
65
80
385
280
790
105
380
1570
630
1400
1275
1311
1905
SHF50-250/150
65
80
385
280
890
105
400
1570
630
1400
1375
1356
1950
SHF50-250/185
65
80
385
280
890
105
400
1750
630
1400
1375
1356
1950
SHF50-250/220
65
80
385
280
890
105
400
1750
630
1400
1375
1356
1950
SHF65-160/40
80
100
335
240
650
50
360
1400
540
1210
1040
1333
1940
SHF65-160/55
80
100
335
240
710
70
380
1420
540
1210
1120
1353
1960
SHF65-160/75
80
100
335
240
710
70
380
1420
540
1210
1120
1353
1960
SHF65-160/110A
80
100
350
280
890
105
380
1570
700
1400
1375
1373
1980
SHF65-160/110
80
100
350
280
890
105
380
1570
700
1400
1375
1373
1980
SHF65-200/150
80
100
350
280
890
105
400
1570
700
1400
1375
1418
2025
SHF65-200/185
80
100
350
280
890
105
400
1750
700
1400
1375
1418
2025
SHF65-200/220
80
100
350
280
890
105
400
1750
700
1400
1375
1418
2025
SHF65-250/300
80
100
425
280
990
115
430
1750
700
1550
1485
1473
2080
SHF65-250/370
80
100
425
280
990
115
430
1750
700
1550
1485
1473
2080
SHF80-160/110
100
125
350
280
890
105
400
1570
700
1400
1400
1487
2107
SHF80-160/150
100
125
350
280
890
105
400
1570
700
1400
1400
1487
2107
SHF80-160/185
100
125
350
280
890
105
400
1750
700
1400
1400
1487
2107
SHF80-200/220
100
125
350
280
890
105
400
1750
700
1400
1400
1512
2132
SHF80-200/300
100
125
425
280
990
130
430
1750
700
1550
1525
1542
2162
SHF80-200/370
100
125
425
280
990
115
430
1750
700
1550
1510
1572
2192
SHF80-250/450
100
125
425
330
990
115
485
1940
700
1550
1560
1627
2247
SHF80-250/550
100
125
430
330
1120
155
530
1960
820
1680
1730
1672
2292
SHF80-250/750
2
100
Dimensions in mm. Tolerance 10 mm.
(1) Dimensions on request.
125
(1)
270
1260
185
560
(1)
(1)
1840
1702
2322
gen20_shf-en_e_td
109
Lowara
110
Lowara
Fire-fighting
booster sets
EN 12845
MARKET SECTORS
CIVIL, INDUSTRIAL
APPLICA
TIONS
APPLICATIONS
Fixed fire-fighting systems.
Automatic Sprinkler systems.
GEN..21/SHF
Series
SPECIFICA
TIONS
SPECIFICATIONS
Flow up to 440 m3/h.
Head up to 100 m.
Panel supply power voltage:
3 x 400V 10%.
Motor start-up :
Frequency: 50 Hz.
Voltage for controls outside panel:
24 Vac.
ey pump
Electric jock
jockey
Protection grade:
111
Lowara
GEN..21/SHF 32-80 SERIES
FIRE-FIGHTING BOOSTER SETS EN 12845
112
Lowara
GEN..21/SHF 32-80 SERIES
FIRE-FIGHTING BOOSTER SETS EN 12845
GEN..21
DRW
DNA
DNP
DNM
Q
1459
N
SHF32-125/07
R 2"
Rp 1"
R 2"
350
240
590
45
225
312
1400
370
1440
955
879
SHF32-125/11
R 2"
Rp 1"
R 2"
350
240
590
45
225
312
1400
370
1440
955
879
1459
SHF32-160/15
R 2"
Rp 1"
R 2"
350
240
650
65
225
332
1400
370
1440 1035
919
1499
SHF32-160/22
R 2"
Rp 1"
R 2"
350
240
650
65
225
332
1400
370
1440 1035
919
1499
SHF32-200/30
R 2"
Rp 1"
R 2"
350
240
650
65
225
360
1400
370
1440 1035
967
1547
SHF32-200/40
R 2"
Rp 1"
R 2"
350
240
650
65
225
360
1400
370
1440 1035
967
1547
SHF32-250/55
R 2"
Rp 1"
R 2"
400
240
790
90
245
400
1420
440
SHF32-250/75
R 2"
Rp 1"
R 2"
400
240
790
90
245
400
1420
440
SHF32-250/110
R 2"
Rp 1"
R 2"
400
280
890
105
245
400
1570
440
SHF40-125/11
65
Rp 1"
65
350
240
590
45
225
312
1400
370
1440
SHF40-125/15
65
Rp 1"
65
350
240
650
65
225
312
1400
370
SHF40-125/22
65
Rp 1"
65
350
240
650
65
225
312
1400
370
SHF40-160/30
65
Rp 1"
65
350
240
650
65
225
332
1400
370
SHF40-160/40
65
Rp 1"
65
350
240
650
65
225
332
1400
370
SHF40-200/55
65
Rp 1"
65
335
240
710
85
245
380
1420
440
SHF40-200/75
65
Rp 1"
65
335
240
710
85
245
380
1420
440
SHF40-250/110A
65
Rp 1"
65
400
280
890
105
245
400
1570
440
SHF40-250/110
65
Rp 1"
65
400
280
890
105
245
400
1570
440
SHF40-250/150
65
Rp 1"
65
400
280
890
105
245
400
1570
440
SHF50-125/22
65
Rp 1"
80
350
240
650
65
225
332
1400
370
SHF50-125/30
65
Rp 1"
80
350
240
650
65
225
332
1400
370
SHF50-125/40
65
Rp 1"
80
350
240
650
65
225
332
1400
370
SHF50-160/55
65
Rp 1"
80
335
240
710
85
245
380
1420
440
SHF50-160/75
65
Rp 1"
80
335
240
710
85
245
380
1420
440
SHF50-200/110A
65
Rp 1"
80
400
280
790
105
245
380
1570
440
SHF50-200/110
65
Rp 1"
80
400
280
790
105
245
380
1570
440
SHF50-250/150
65
Rp 1"
80
400
280
890
105
245
400
1570
440
SHF50-250/185
65
Rp 1"
80
400
280
890
105
245
400
1750
440
SHF50-250/220
65
Rp 1"
80
400
280
890
105
245
400
1750
440
SHF65-160/40
80
Rp 1"
100
335
240
650
50
225
360
1400
440
SHF65-160/55
80
Rp 1"
100
335
240
710
70
245
380
1420
440
SHF65-160/75
80
Rp 1"
100
335
240
710
70
245
380
1420
440
SHF65-160/110A
80
Rp 1"
100
400
280
890
105
245
380
1570
440
SHF65-160/110
80
Rp 1"
100
400
280
890
105
245
380
1570
440
SHF65-200/150
80
Rp 1"
100
400
280
890
105
245
400
1570
440
SHF65-200/185
80
Rp 1"
100
400
280
890
105
245
400
1750
440
SHF65-200/220
80
Rp 1"
100
400
280
890
105
245
400
1750
440
SHF65-250/300
80
Rp 1"
100
430
280
990
115
245
430
1750
490
SHF65-250/370
80
Rp 1"
100
430
280
990
115
245
430
1750
490
SHF80-160/110
100
Rp 1" 1/4
125
400
280
890
105
245
400
1570
440
SHF80-160/150
100
Rp 1" 1/4
125
400
280
890
105
245
400
1570
440
SHF80-160/185
100
Rp 1" 1/4
125
400
280
890
105
245
400
1750
440
SHF80-200/220
100
Rp 1" 1/4
125
400
280
890
105
245
400
1750
440
SHF80-200/300
100
Rp 1" 1/4
125
430
280
990
130
245
430
1750
490
SHF80-200/370
100
Rp 1" 1/4
125
430
280
990
115
245
430
1750
490
SHF80-250/450
100
Rp 1" 1/4
125
430
330
990
115
245
485
1940
490
SHF80-250/550
100
Rp 1" 1/4
125
470
330
1120
155
265
530
1960
600
SHF80-250/750
2
100
Rp 1" 1/4
Dimensions in mm. Tolerance 10 mm.
125
505
270
1260
185
265
560
600
955
1094 1682
gen21_shf-en_e_td
113
Lowara
GEN../SHF 32-80 SERIES
DIMENSIONS FOR FL
OOR FIXING
FLOOR
114
Lowara
GEN../SHF 32-80 SERIES
DIMENSIONS FOR FL
OOR FIXING
FLOOR
GEN..10
PUMP
GEN..11
GEN..20
GEN..21
SHF 32-125/07
320
540
20
130
770
540
90
25
990
540
90
25
1400
495
90
25
SHF 32-125/11
320
540
20
130
770
540
90
25
990
540
90
25
1400
495
90
25
SHF 32-160/15
350
600
20
150
770
600
90
25
990
600
90
25
1400
555
90
25
SHF 32-160/22
350
600
20
150
770
600
90
25
990
600
90
25
1400
555
90
25
SHF 32-200/30
350
600
20
150
770
600
90
25
990
600
90
25
1400
555
90
25
SHF 32-200/40
350
600
20
150
770
600
90
25
990
600
90
25
1400
555
90
25
SHF 32-250/55
440
740
25
190
1130
665
20
55
1360
665
20
55
1640
665
20
55
SHF 32-250/75
440
740
25
190
1130
665
20
55
1360
665
20
55
1640
665
20
55
SHF 32-250/110
490
840
25
205
1130
765
20
55
1360
765
20
55
1640
765
20
55
SHF 40-125/11
350
600
20
150
770
540
90
25
1030
600
90
25
1400
495
90
25
SHF 40-125/15
350
600
20
150
770
600
90
25
1030
600
90
25
1400
555
90
25
SHF 40-125/22
350
600
20
150
770
600
90
25
1030
600
90
25
1400
555
90
25
SHF 40-160/30
350
600
20
150
770
600
90
25
1030
600
90
25
1400
555
90
25
SHF 40-160/40
350
600
20
150
770
600
90
25
1030
600
90
25
1400
555
90
25
SHF 40-200/55
400
660
25
170
960
585
20
55
1170
585
20
55
1510
585
20
55
SHF 40-200/75
400
660
25
170
960
585
20
55
1170
585
20
55
1510
585
20
55
SHF 40-250/110A
490
840
25
205
1130
765
20
55
1360
765
20
55
1640
765
20
55
SHF 40-250/110
490
840
25
205
1130
765
20
55
1360
765
20
55
1640
765
20
55
SHF 40-250/150
490
840
25
205
1130
765
20
55
1360
765
20
55
1640
765
20
55
SHF 50-125/22
350
600
20
150
770
600
90
25
1360
765
20
55
1400
555
90
25
SHF 50-125/30
350
600
20
150
770
600
90
25
1360
765
20
55
1400
555
90
25
SHF 50-125/40
350
600
20
150
770
600
90
25
1360
765
20
55
1400
555
90
25
SHF 50-160/55
400
660
25
170
960
585
20
55
1360
765
20
55
1510
585
20
55
SHF 50-160/75
400
660
25
170
960
585
20
55
1360
765
20
55
1510
585
20
55
SHF 50-200/110A
440
740
25
190
1130
665
20
55
1360
765
20
55
1640
665
20
55
SHF 50-200/110
440
740
25
190
1130
665
20
55
1360
765
20
55
1640
665
20
55
SHF 50-250/150
490
840
25
205
1130
765
20
55
1360
765
20
55
1640
765
20
55
SHF 50-250/185
490
840
25
205
1130
765
20
55
1360
765
20
55
1640
765
20
55
SHF 50-250/220
490
840
25
205
1130
765
20
55
1360
765
20
55
1640
765
20
55
SHF 65-160/40
400
660
25
170
960
585
20
55
1170
585
20
55
1510
585
20
55
SHF 65-160/55
440
740
25
190
1130
665
20
55
1170
585
20
55
1640
665
20
55
SHF 65-160/75
440
740
25
190
1130
665
20
55
1170
585
20
55
1640
665
20
55
SHF 65-160/110A
490
840
25
205
1130
765
20
55
1360
765
20
55
1640
765
20
55
SHF 65-160/110
490
840
25
205
1130
765
20
55
1360
765
20
55
1640
765
20
55
SHF 65-200/150
490
840
25
205
1130
765
20
55
1360
765
20
55
1640
765
20
55
SHF 65-200/185
490
840
25
205
1130
765
20
55
1360
765
20
55
1640
765
20
55
SHF 65-200/220
490
840
25
205
1130
765
20
55
1360
765
20
55
1640
765
20
55
SHF 65-250/300
550
940
30
230
1130
865
20
55
1510
865
20
55
1800
865
20
55
SHF 65-250/370
550
940
30
230
1130
865
20
55
1510
865
20
55
1800
865
20
55
SHF 80-160/110
490
840
25
205
1130
765
20
55
1360
765
20
55
1640
765
20
55
SHF 80-160/150
490
840
25
205
1130
765
20
55
1360
765
20
55
1640
765
20
55
SHF 80-160/185
490
840
25
205
1130
765
20
55
1360
765
20
55
1640
765
20
55
SHF 80-200/220
490
840
25
205
1130
765
20
55
1360
765
20
55
1640
765
20
55
SHF 80-200/300
550
940
30
230
1130
865
20
55
1510
865
20
55
1800
865
20
55
SHF 80-200/370
550
940
30
230
1130
865
20
55
1510
865
20
55
1800
865
20
55
SHF 80-250/450
550
940
30
230
1130
865
20
55
1510
865
20
55
1800
865
20
55
SHF 80-250/550
600
1060
30
270
1360
950
20
90
1640
985
20
55
2100
950
20
90
SHF 80-250/750
670
1200
30
300
(1)
(1)
(1)
(1)
(1)
(1)
(1)
(1)
2170
1090
20
90
inter_shf-en_a_td
115
Lowara
116
Lowara
GEN../SHF SERIES OF BOOSTER SETS (POSITIVE SUCTION HEAD)
Hc PRES
SURE DROP CURVE IN SUCTION KIT
PRESSURE
2900 [rpm]
0
0
20
20
40
60
40
80
60
80
Q [US gpm]
120
100
0,25
20
20
40
60
40
80
60
80
Q [US gpm]
120
100
0,25
0,8
H [ft]
Hc [m]
0,8
Hc [m]
2900 [rpm]
SH 32 - 160
Q [Imp gpm]
100
0,20
H [ft]
SH 32 - 125
0,20
0,6
0,6
0,15
0,15
0,4
0,4
0,10
0,10
0,2
0,2
0,05
0,05
0,00
6
0,0
0,00
8
0,0
25
15
20
15
32-160/15
150
65-160/150
32-160/15 178
164
10
NPSHr [ft]
NPSHr [m]
10
NPSHr [ft]
NPSHr [m]
2
5
0
5
10
15
100
200
20
20
25
300
400
2900 [rpm]
SH 32 - 200
0
20
40
60
Q [l/min]
500
0
0
80
80
100
0
0
15
100
200
300
40
400
60
Q [l/min]
500
60
40
Q [m330
/h]
25
2900 [rpm]
20
20
20
80
80
Q [US gpm]
120
100
0,25
0,8
H [ft]
Hc [m]
0,8
Hc [m]
10
SH 32 - 250
Q [US gpm]
120
0,25
60
40
Q [m3/h]
30
0,20
H [ft]
0,20
0,6
0,6
0,15
0,15
0,4
0,4
0,10
0,10
0,2
0,2
0,05
0,05
0,00
8
0,0
0,00
8
0,0
25
25
32-250/55
20
222
20
15
4
32-200/40 204
65-160/150
178
10
NPSHr [m]
188
15
4
65-160/150
178
10
NPSHr [ft]
32-250/110 256
32-250/75 242
NPSHr [ft]
32-200/30
0
0
0
10
100
15
200
20
300
25
400
Q [m330
/h]
Q [l/min]
500
76519_A_CH
0
0
0
10
100
15
200
20
300
The declared performance value are valid for liquids with density = 1.0 Kg/dm3 and kinematic viscosity = 1 mm2/sec.
The NPSHr values required for the service pump were obtained in the laboratory. When using them for EN 12845 for fire-fighting systems, increase the value by 1 m.
Hc: Pressure drop curve in suction kit.
117
25
400
Q [m330
/h]
Q [l/min]
500
76520_A_CH
NPSHr [m]
76518_A_CH
76517_A_CH
Lowara
GEN../SHF SERIES OF BOOSTER SETS (POSITIVE SUCTION HEAD)
Hc PRES
SURE DROP CURVE IN SUCTION KIT
PRESSURE
2900 [rpm]
50
100
50
150
100
150
0,25
50
100
50
Q [Imp gpm]
150
100
150
0,25
0,8
H [ft]
Hc [m]
0,8
Hc [m]
2900 [rpm]
SH 40 - 160
Q [Imp gpm]
0,20
H [ft]
SH 40 - 125
0,20
0,6
0,6
0,15
0,15
0,4
0,4
0,10
0,10
0,2
0,2
0,05
0,05
0,0
0,00
8
0,0
25
20
10
NPSHr [m]
15
4
20
NPSHr [ft]
15
4
10
2
10
100
20
200
300
30
400
50
500
600
2900 [rpm]
SH 40 - 200
700
150
100
Q800
[l/min]
0
0
0
100
50
Q [m3/h]
50
40
Q [Imp gpm]
0,25
200
0
0
30
300
40
400
500
600
2900 [rpm]
50
100
50
Q [m3/h]
60
50
700
Q800
[l/min]
150
100
150
Q [US
250gpm]
200
0,25
0,8
H [ft]
Hc [m]
0,8
Hc [m]
100
20
SH 40 - 250
Q [US gpm]
200
150
10
0,20
H [ft]
0,20
0,6
0,6
0,15
0,15
0,4
0,4
0,10
0,10
0,2
0,2
0,05
0,05
0,0
0,00
8
0,0
25
25
20
10
NPSHr [m]
15
4
20
NPSHr [ft]
40-250/110A
15
216
4
65-160/150
178
40-250/150
40-250/110
251
233
0
0
0
10
100
20
200
300
30
400
40
500
50
600
700
Q [m3/h]
60
Q800
[l/min]
76523_A_CH
10
NPSHr [ft]
0,00
8
NPSHr [m]
76522_A_CH
76521_A_CH
0
0
0
10
200
20
30
400
40
600
The declared performance value are valid for liquids with density = 1.0 Kg/dm3 and kinematic viscosity = 1 mm2/sec.
The NPSHr values required for the service pump were obtained in the laboratory. When using them for EN 12845 for fire-fighting systems, increase the value by 1 m.
Hc: Pressure drop curve in suction kit.
118
50
800
Q [m360
/h]
Q [l/min]
1000
76524_A_CH
NPSHr [m]
25
NPSHr [ft]
0,00
8
Lowara
GEN../SHF SERIES OF BOOSTER SETS (POSITIVE SUCTION HEAD)
Hc PRES
SURE DROP CURVE IN SUCTION KIT
PRESSURE
2900 [rpm]
100
200
100
300
200
Q [US gpm]
400
300
100
0,25
200
100
Q [Imp gpm]
300
200
Q [US gpm]
400
300
0,25
0,8
H [ft]
Hc [m]
0,8
Hc [m]
2900 [rpm]
SH 50 - 160
Q [Imp gpm]
0,20
H [ft]
SH 50 - 125
0,20
0,6
0,6
0,15
0,15
0,4
0,4
0,10
0,10
0,2
0,2
0,05
0,05
0,00
8
0,0
0,00
10
0,0
25
30
8
20
15
50-125/40 139
50-125/30
130
65-160/150
178
10
50-160/55
20
119
15
65-160/150
178
50-160/75
174
NPSHr [ft]
119
NPSHr [m]
NPSHr [m]
50-125/22
25
NPSHr [ft]
10
2
2
0
0
0
20
200
40
400
600
60
800
1200
2900 [rpm]
SH 50 - 200
0
100
1000
1400
Q
1600
[l/min]
300
200
Q [Imp gpm]
200
40
400
600
60
800
100
1000
1200
1400
Q
1600
[l/min]
200
100
3
Q [m100
/h]
80
2900 [rpm]
Q [US gpm]
400
300
20
SH 50 - 250
Q [Imp gpm]
300
200
Q [US gpm]
400
300
H [ft]
0,25
0,8
0,20
H [ft]
0,30
Hc [m]
0,30
0,25
0,8
0,20
0,6
0,6
0,15
0,15
0,4
0,4
0,10
0,10
0,2
0,05
0,00
10
0,2
0,05
0,0
0,00
10
0,0
30
30
8
25
50-200/110 209
65-160/150
178
15
20
6
50-250/150
224
15
65-160/150
178
10
50-250/220
50-250/185
250
NPSHr [ft]
20
NPSHr [m]
NPSHr [m]
197
NPSHr [ft]
50-200/110A
25
10
237
0
0
0
20
200
40
400
600
60
800
1000
80
1200
1400
3
Q [m100
/h]
Q
1600
[l/min]
5
76527_A_CH
0
0
0
20
200
40
400
600
60
800
1000
80
1200
The declared performance value are valid for liquids with density = 1.0 Kg/dm3 and kinematic viscosity = 1 mm2/sec.
The NPSHr values required for the service pump were obtained in the laboratory. When using them for EN 12845 for fire-fighting systems, increase the value by 1 m.
Hc: Pressure drop curve in suction kit.
119
1400
3
Q [m100
/h]
Q
1600
[l/min]
76528_A_CH
Hc [m]
0
0
200
100
3
Q [m100
/h]
80
76526_A_CH
76525_A_CH
Lowara
GEN../SHF SERIES OF BOOSTER SETS (POSITIVE SUCTION HEAD)
Hc PRES
SURE DROP CURVE IN SUCTION KIT
PRESSURE
2900 [rpm]
SH 65 - 160
0
100
200
100
300
200
300
400
400
Q [US600
gpm]
500
100
200
100
300
200
300
Q
[Imp gpm]
500
400
400
Q [US600
gpm]
500
Hc [m]
H [ft]
0,25
1,2
H [ft]
0,4
0,30
Hc [m]
2900 [rpm]
SH 65 - 160
Q
[Imp gpm]
500
0,8
1,0
0,3
0,20
0,6
0,8
0,2
0,15
0,6
0,4
0,10
0,4
0,1
0,2
0,05
0,2
0,00
10
0,0
0,0
10
0,0
30
30
8
25
15
NPSHr [m]
NPSHr [m]
65-160/40 139
65-160/30 130
65-160/150
178
20
15
65-160/150
178
10
10
65-160/110 177
65-160/110A 168
0
0
0
20
200
40
400
600
60
800
1000
100
1200
100
1400
1600
2900 [rpm]
SH 65 - 200
0
80
200
100
300
1800
2000
3
Q [m140
/h]
Q
2200
[l/min]
0
0
0
300
200
120
5
76529_A_CH
200
40
400
Q [US600
gpm]
500
20
600
60
800
1000
0,4
100
100
80
1200
100
1400
1600
200
200
2000
3
Q [m140
/h]
Q
2200
[l/min]
300
300
120
1800
2900 [rpm]
SH 65 - 250
Q
[Imp gpm]
500
400
400
NPSHr [ft]
20
76530_A_CH
119
NPSHr [ft]
65-160/22
25
400
400
Q [Imp gpm]
500
500
Hc [m]
H [ft]
Hc [m]
0,6
1,2
0,5
1,5
1,0
0,3
0,4
0,8
0,2
1,0
0,3
0,6
0,2
0,4
0,5
0,1
0,0
10
0,2
0,1
0,0
0,0
10
0,0
30
30
8
25
15
65-160/150
178
65-250/300
240
65-250/370
255
10
65-200/220
65-200/185
10
215
203
20
200
400
40
600
60
800
1000
80
1200
1400
100
1600
120
1800
2000
3
Q [m140
/h]
Q
2200
[l/min]
5
76531_A_CH
15
65-160/150
178
0
0
0
20
40
500
60
1000
80
100
1500
120
2000
The declared performance value are valid for liquids with density = 1.0 Kg/dm3 and kinematic viscosity = 1 mm2/sec.
The NPSHr values required for the service pump were obtained in the laboratory. When using them for EN 12845 for fire-fighting systems, increase the value by 1 m.
Hc: Pressure drop curve in suction kit.
120
140
3
Q [m160
/h]
2500
Q [l/min]
76532_A_CH
20
6
NPSHr [m]
192
NPSHr [ft]
65-200/150
NPSHr [ft]
20
6
NPSHr [m]
25
Lowara
GEN../SHF SERIES OF BOOSTER SETS (POSITIVE SUCTION HEAD)
Hc PRES
SURE DROP CURVE IN SUCTION KIT
PRESSURE
2900 [rpm]
SH 80 - 160
0
0
200
200
400
400
800
600
Q [US gpm]
1000
800
2900 [rpm]
SH 80 - 200
Q [Imp gpm]
200
400
400
600
600
800
800
Q [US gpm]
1200
1000
1,0
0,3
H [ft]
H [ft]
1,2
Hc [m]
0,4
Hc [m]
0,4
200
0,3
1,5
0,2
1,0
0,1
0,5
0,0
10
0,0
0,8
0,2
0,6
0,4
0,1
0,2
0,0
10
0,0
30
30
8
25
80-160/185
80-160/150
186
177
20
198
80-200/370 225
65-160/150
80-200/300
215
178
10
10
0
0
50
100
1000
3000
2900 [rpm]
200
200
400
400
3
Q [m250
/h]
200
2000
SH 80 - 250
0
150
Q4000
[l/min]
0
0
0
50
1000
100
150
2000
200
3000
600
800
Q [Imp gpm]
Q [US gpm]
1000
800
1,2
H [ft]
Hc [m]
0,4
1,0
0,3
0,8
0,2
0,6
0,4
0,1
0,2
0,0
10
0,0
30
8
25
15
65-160/150
178
NPSHr [ft]
20
10
2
0
0
0
50
1000
100
150
2000
200
3000
3
Q [m250
/h]
4000
Q [l/min]
76535_A_CH
The declared performance value are valid for liquids with density = 1.0 Kg/dm3 and kinematic viscosity = 1 mm2/sec.
The NPSHr values required for the service pump were obtained in the laboratory. When using them for EN 12845 for fire-fighting systems, increase the value by 1 m.
Hc: Pressure drop curve in suction kit.
121
250
4000
3
Q [m300
/h]
Q [l/min]
5000
76534_A_CH
5
76533_A_CH
NPSHr [m]
15
NPSHr [ft]
15
65-160/150
178
80-200/220
6
NPSHr [m]
NPSHr [m]
20
169x15
NPSHr [ft]
80-160/150
25
Lowara
GEN../SHF SERIES OF BOOSTER SETS (SUCTION LIF
T)
LIFT)
Hc PRES
SURE DROP CURVE IN SUCTION KIT
PRESSURE
2900 [rpm]
SH 32 - 125
0
0
20
20
40
60
40
80
60
80
Q [US gpm]
120
100
2900 [rpm]
SH 32 - 160
Q [Imp gpm]
100
0,4
20
20
40
60
40
80
60
80
Q [US gpm]
120
100
H [ft]
Hc [m]
H [ft]
Hc [m]
0,6
0,5
1,0
0,3
1,5
0,4
0,2
1,0
0,3
0,5
0,2
0,5
0,1
0,1
0,0
6
0,0
0,0
8
0,0
25
15
20
15
32-160/15
150
65-160/150
32-160/15 178
164
10
NPSHr [ft]
NPSHr [m]
10
NPSHr [ft]
NPSHr [m]
2
5
0
0
10
15
100
200
20
20
25
300
400
2900 [rpm]
SH 32 - 200
0
20
40
60
Q [l/min]
500
80
80
100
10
15
100
Q [US gpm]
120
300
40
400
60
Q [l/min]
500
60
40
Q [m330
/h]
25
2900 [rpm]
20
20
20
200
SH 32 - 250
80
80
Q [US gpm]
120
100
H [ft]
0,5
H [ft]
0,6
Hc [m]
0,6
0,5
1,5
1,5
0,4
0,4
1,0
0,3
1,0
0,3
0,2
0,2
0,5
0,5
0,1
0,1
0,0
8
0,0
0,0
8
0,0
25
25
32-250/55
20
20
15
4
32-200/40 204
65-160/150
178
10
NPSHr [m]
188
15
4
65-160/150
178
10
NPSHr [ft]
32-250/110 256
32-250/75 242
NPSHr [ft]
NPSHr [m]
32-200/30
222
0
0
0
10
100
15
200
20
300
25
400
Q [m330
/h]
Q [l/min]
500
76499_A_CH
0
0
0
10
100
15
200
20
300
The declared performance value are valid for liquids with density = 1.0 Kg/dm3 and kinematic viscosity = 1 mm2/sec.
The NPSHr values required for the service pump were obtained in the laboratory. When using them for EN 12845 for fire-fighting systems, increase the value by 1 m.
Hc: Pressure drop curve in suction kit.
122
25
400
Q [m330
/h]
Q [l/min]
500
76500_A_CH
Hc [m]
0
0
60
40
Q [m3/h]
30
76498_A_CH
76497_A_CH
Lowara
GEN../SHF SERIES OF BOOSTER SETS (SUCTION LIF
T)
LIFT)
Hc PRES
SURE DROP CURVE IN SUCTION KIT
PRESSURE
2900 [rpm]
SH 40 - 125
0
50
100
50
150
100
150
50
100
50
Q [Imp gpm]
150
100
150
H [ft]
0,5
H [ft]
0,6
Hc [m]
0,6
0,5
1,5
1,5
0,4
0,4
1,0
0,3
1,0
0,3
0,2
0,2
0,5
0,5
0,1
0,1
0,0
0,0
8
0,0
25
20
10
NPSHr [m]
15
4
20
NPSHr [ft]
15
4
10
2
0
0
0
10
100
20
200
300
30
400
50
500
600
2900 [rpm]
SH 40 - 200
700
150
100
Q800
[l/min]
Q [Imp gpm]
100
20
200
Q [US gpm]
200
150
10
30
300
40
400
500
50
100
50
Q [m3/h]
60
50
600
2900 [rpm]
SH 40 - 250
0,6
700
Q800
[l/min]
150
100
150
Q [US
250gpm]
200
0,5
H [ft]
Hc [m]
0,6
H [ft]
Hc [m]
0
0
100
50
Q [m3/h]
50
40
0,5
1,5
1,5
0,4
0,4
1,0
0,3
1,0
0,3
0,2
0,2
0,5
0,5
0,1
0,1
0,0
8
0,0
0,0
8
0,0
25
25
20
10
NPSHr [m]
15
4
20
NPSHr [ft]
NPSHr [m]
76502_A_CH
76501_A_CH
40-250/110A
15
216
4
65-160/150
178
40-250/150
40-250/110
251
233
0
0
0
10
100
20
200
300
30
400
40
500
50
600
700
Q [m3/h]
60
Q800
[l/min]
76503_A_CH
10
NPSHr [ft]
NPSHr [m]
25
NPSHr [ft]
0,0
8
0
0
0
10
200
20
30
400
40
600
The declared performance value are valid for liquids with density = 1.0 Kg/dm3 and kinematic viscosity = 1 mm2/sec.
The NPSHr values required for the service pump were obtained in the laboratory. When using them for EN 12845 for fire-fighting systems, increase the value by 1 m.
Hc: Pressure drop curve in suction kit.
123
50
800
Q [m360
/h]
Q [l/min]
1000
76504_A_CH
Hc [m]
2900 [rpm]
SH 40 - 160
Q [Imp gpm]
Lowara
GEN../SHF SERIES OF BOOSTER SETS (SUCTION LIF
T)
LIFT)
Hc PRES
SURE DROP CURVE IN SUCTION KIT
PRESSURE
2900 [rpm]
SH 50 - 125
0
100
200
100
300
200
Q [US gpm]
400
300
100
200
100
Q [Imp gpm]
300
200
Q [US gpm]
400
300
H [ft]
0,5
H [ft]
0,6
Hc [m]
0,6
Hc [m]
2900 [rpm]
SH 50 - 160
Q [Imp gpm]
0,5
1,5
1,5
0,4
0,4
1,0
0,3
1,0
0,3
0,2
0,2
0,5
0,5
0,1
0,1
0,0
8
0,0
0,0
10
0,0
25
30
8
20
15
50-125/40 139
50-125/30
130
65-160/150
178
10
50-160/55
20
119
15
65-160/150
178
50-160/75
174
NPSHr [ft]
119
NPSHr [m]
NPSHr [m]
50-125/22
25
NPSHr [ft]
10
2
2
0
0
0
20
200
40
400
600
60
800
1200
2900 [rpm]
SH 50 - 200
0
100
1000
1400
Q
1600
[l/min]
300
200
Q [Imp gpm]
200
40
400
600
60
800
100
1000
1200
1400
Q
1600
[l/min]
200
100
3
Q [m100
/h]
80
2900 [rpm]
Q [US gpm]
400
300
20
SH 50 - 250
Q [Imp gpm]
300
200
Q [US gpm]
400
300
H [ft]
0,5
H [ft]
0,6
Hc [m]
0,6
0,5
1,5
1,5
0,4
0,4
1,0
0,3
1,0
0,3
0,2
0,2
0,5
0,5
0,1
0,1
0,0
10
0,0
0,0
10
0,0
30
30
8
25
50-200/110 209
65-160/150
178
15
20
6
50-250/150
224
15
65-160/150
178
10
50-250/220
50-250/185
250
NPSHr [ft]
20
NPSHr [m]
NPSHr [m]
197
NPSHr [ft]
50-200/110A
25
10
237
0
0
0
20
200
40
400
600
60
800
1000
80
1200
1400
3
Q [m100
/h]
Q
1600
[l/min]
5
76507_A_CH
0
0
0
20
200
40
400
600
60
800
1000
80
1200
The declared performance value are valid for liquids with density = 1.0 Kg/dm3 and kinematic viscosity = 1 mm2/sec.
The NPSHr values required for the service pump were obtained in the laboratory. When using them for EN 12845 for fire-fighting systems, increase the value by 1 m.
Hc: Pressure drop curve in suction kit.
124
1400
3
Q [m100
/h]
Q
1600
[l/min]
76508_A_CH
Hc [m]
0
0
200
100
3
Q [m100
/h]
80
76506_A_CH
76505_A_CH
Lowara
GEN../SHF SERIES OF BOOSTER SETS (SUCTION LIF
T)
LIFT)
Hc PRES
SURE DROP CURVE IN SUCTION KIT
PRESSURE
2900 [rpm]
SH 65 - 160
0
100
200
100
300
200
300
400
400
Q [US600
gpm]
500
100
200
100
300
200
300
Q
[Imp gpm]
500
400
400
Q [US600
gpm]
500
H [ft]
0,5
H [ft]
0,6
Hc [m]
0,6
0,5
1,5
1,5
0,4
0,4
1,0
0,3
1,0
0,3
0,2
0,2
0,5
0,5
0,1
0,1
0,0
10
0,0
0,0
10
0,0
30
30
8
25
15
NPSHr [m]
15
65-160/150
178
10
10
65-160/110 177
65-160/110A 168
0
0
0
20
200
40
400
600
60
800
1000
100
1200
100
1400
1600
2900 [rpm]
SH 65 - 200
0
80
200
100
300
1800
2000
3
Q [m140
/h]
Q
2200
[l/min]
Q
[Imp gpm]
500
400
400
200
40
400
Q [US600
gpm]
500
20
600
60
800
1000
100
100
80
1200
100
1400
1600
200
200
2000
3
Q [m140
/h]
Q
2200
[l/min]
300
300
120
1800
2900 [rpm]
SH 65 - 250
400
400
Q [Imp gpm]
500
500
H [ft]
0,5
H [ft]
0,6
Hc [m]
0,6
Hc [m]
0
0
300
200
120
5
76510_A_CH
0,5
1,5
1,5
0,4
0,4
1,0
0,3
1,0
0,3
0,2
0,2
0,5
0,5
0,1
0,1
0,0
10
0,0
0,0
10
0,0
30
30
8
25
20
192
15
65-160/150
178
20
6
NPSHr [m]
65-200/150
NPSHr [ft]
6
NPSHr [m]
25
65-250/300
240
65-250/370
255
10
65-200/220
65-200/185
10
215
203
20
200
400
40
600
60
800
1000
80
1200
1400
100
1600
120
1800
2000
3
Q [m140
/h]
Q
2200
[l/min]
5
76512_A_CH
15
65-160/150
178
NPSHr [ft]
NPSHr [m]
65-160/40 139
65-160/30 130
65-160/150
178
20
NPSHr [ft]
20
76511_A_CH
119
NPSHr [ft]
65-160/22
25
0
0
0
20
40
500
60
1000
80
100
1500
120
2000
The declared performance value are valid for liquids with density = 1.0 Kg/dm3 and kinematic viscosity = 1 mm2/sec.
The NPSHr values required for the service pump were obtained in the laboratory. When using them for EN 12845 for fire-fighting systems, increase the value by 1 m.
Hc: Pressure drop curve in suction kit.
125
140
3
Q [m160
/h]
2500
Q [l/min]
76513_A_CH
Hc [m]
2900 [rpm]
SH 65 - 160
Q
[Imp gpm]
500
Lowara
GEN../SHF SERIES OF BOOSTER SETS (SUCTION LIF
T)
LIFT)
Hc PRES
SURE DROP CURVE IN SUCTION KIT
PRESSURE
2900 [rpm]
SH 80 - 160
0
0
200
200
400
400
800
600
Q [US gpm]
1000
800
200
200
400
400
600
600
800
800
Q [US gpm]
1200
1000
H [ft]
0,5
H [ft]
0,6
Hc [m]
0,6
0,5
1,5
1,5
0,4
0,4
1,0
0,3
1,0
0,3
0,2
0,2
0,5
0,5
0,1
0,1
0,0
10
0,0
0,0
10
0,0
30
30
8
25
80-160/185
80-160/150
186
177
20
198
80-200/370 225
65-160/150
80-200/300
215
178
10
10
0
0
50
100
1000
3000
2900 [rpm]
200
200
400
400
3
Q [m250
/h]
200
2000
SH 80 - 250
0
150
Q4000
[l/min]
0
0
0
50
1000
100
150
2000
200
3000
600
5
76514_A_CH
800
Q [Imp gpm]
Q [US gpm]
1000
800
H [ft]
Hc [m]
0,6
0,5
1,5
0,4
1,0
0,3
0,2
0,5
0,1
0,0
10
0,0
30
8
25
15
65-160/150
178
NPSHr [ft]
20
6
NPSHr [m]
15
NPSHr [ft]
15
65-160/150
178
80-200/220
6
NPSHr [m]
NPSHr [m]
20
169x15
NPSHr [ft]
80-160/150
25
10
2
0
0
0
50
1000
100
150
2000
200
3000
3
Q [m250
/h]
4000
Q [l/min]
76516_A_CH
The declared performance value are valid for liquids with density = 1.0 Kg/dm3 and kinematic viscosity = 1 mm2/sec.
The NPSHr values required for the service pump were obtained in the laboratory. When using them for EN 12845 for fire-fighting systems, increase the value by 1 m.
Hc: Pressure drop curve in suction kit.
126
250
4000
3
Q [m300
/h]
Q [l/min]
5000
76515_A_CH
Hc [m]
2900 [rpm]
SH 80 - 200
Q [Imp gpm]
Lowara
ACCESSORIES
127
Lowara
DIAPHRAGM T
ANKS
TANKS
The booster sets are ready for installation, directly on the manifold, of 24-litre diaphragm tanks, one for each
pump. The sets are also equipped with caps to close off the unused couplings. Larger tanks can also be connected
to the unused end of the discharge manifold. For proper sizing of the tank please refer to the technical appendix.
Kit featuring the following accessories are available on request
request:
diaphragm tank;
on-off ball valve;
operating instructions;
packaging.
DIAPHRAGM
T
ANK KITVESSEL KIT
TANK
STANDARD DIAPHRAGM
DIMENSIONS (mm)
Materials
Volume
PN
Litres
bar
Valve
Diaphragm
Vessel
Valve
205
390
1" FF
EPDM
Painted steel
Nickel-plated brass
24
270
555
1" FF
EPDM
Painted steel
Nickel-plated brass
24
10
270
555
1" FF
EPDM
Painted steel
Nickel-plated brass
24
16
270
555
1" FF
EPDM
Painted steel
Nickel-plated brass
24
10
270
575
1" FF
Butyl
Stainless steel
COUNTERFLANGE KIT
Counterflange coupling kits made of zinc-plated or stainless steel are available on request.
The counterflange kits are equipped with:
- N. 2 flanges.
- gasket and bolts/screws.
THREADED COUNTERFLANGES
DIMENSIONI KIT CONTROFLANGE TONDE FI
DIMENSIONS (mm)
KIT
HOLES
TYPE
DN
PN
2"
50
Rp 2
125
16
165
24
18
25
2"
65
Rp 2
145
16
185
23
18
16
3"
80
Rp 3
160
17
200
27
18
16
Gcom-ctf-tonde-f-en_a_td
KIT
HOLES
TYPE
DN
PN
2"
50
61
125
19
165
18
16
2"1/2
65
77
145
20
185
18
16
3"
80
90
160
20
200
18
16
4"
100
116
180
22
220
18
16
5"
125
141,5
210
22
250
18
16
6"
150
170,5
240
24
285
22
16
8"
200
221,5
295
26
340
22
12
16
10"
250
276,5
355
29
405
26
12
16
12"
300
327,5
410
32
460
26
12
16
Gcom-ctf-tonde-s-en_c_td
128
Lowara
ACCES
SORIES FOR BOOSTER SETS
ACCESSORIES
SUCTION SIDE KIT
The EN 12845 fire-fighting booster sets are supplied without valves and stubs on the suction side of the service pump
and can be completed with suitable kits that depend on legal standards.
These requirements are expressed by EN 12845 (chapter 10.5 and chapter 10.6) and are connected with the maximum
speed value of the water in the pipes, their minimum section and type of installation - suction lift or positive suction
head.
To provide for one suction kit for each duty pump.
The suction side kit are equipped with:
- Anti-vibration joint to attach to the pump inlet.
- Eccentric cone or flanged stub pipe.
- Vacuum pressure gauge.
- On/off butterfly valve with lever handle for diameters up to DN100, butterfly valve with handwheel and
reduction manual gear for DN125 and higher. Device for monitoring ON/OFF status included. Electrical
connections by customer.
(Valve lock kit available on request).
- Weld-on flange.
The following table summarises the pump type installed on the fire-fighting sets and the kit that corresponds to the
installation type.
129
Lowara
GEN../ SERIES OF FIRE-FIGHTING BOOSTER SETS
SUCTION SIDE KIT DIMENSIONS T
ABLE
TABLE
SUCTION
DIMENSIONS
KIT
TYPE
DNS
PN
DNA
PN
L (mm)
H (mm)
50 X 32
50
16
32
16
340
50 X 40
50
16
40
16
340
65 X 32
65
16
32
16
395
17
65 X 40
65
16
40
16
375
14
65 X 50
65
16
50
16
355
80 X 32
80
16
32
16
445
23
80 X 40
80
16
40
16
425
20
80 X 50
80
16
50
16
395
14
80 X 65
80
16
65
16
365
100 X 40
100
16
40
16
520
33
100 X 50
100
16
50
16
500
27
100 X 65
100
16
65
16
470
19
100 X 80
100
16
80
16
435
13
125 X 50
125
16
50
16
605
40
125 X 65
125
16
65
16
565
32
125 X 80
125
16
80
16
540
25
125 X 100
125
16
100
16
455
13
150 X 65
150
16
65
16
675
46
150 X 80
150
16
80
16
640
40
150 X 100
150
16
100
16
565
27
150 X 125
150
16
125
16
520
14
200 X 80
200
10
80
16
830
65
200 X 100
200
10
100
16
755
52
200 X 125
200
10
125
16
710
40
200 X 150
200
10
150
16
620
25
250 X 100
250
10
100
16
965
79
250 X 125
250
10
125
16
930
67
250 X 150
250
10
150
16
840
52
300 X 125
300
10
125
16
1120
92
300 X 150
300
10
150
16
1040
78
350 X 150
350
10
150
16
1160
94
400 X 150
400
10
150
16
1375
119
kit-asp-en_b_td
130
Lowara
GEN../FHF 32-80 SERIES FIRE-FIGHTING BOOSTER SETS
SUCTION SIDE KIT DIMENSIONS T
ABLE
TABLE
SUCTION LIFT
PUMP
RISK
SUCTION
RISK
SUCTION
RISK
SUCTION
RISK
CLASS *
KIT
CLASS *
KIT
CLASS *
KIT
CLASS *
TYPE
TYPE
TYPE
SUCTION
KIT
TYPE
FHF 32-125/07
LH
65 X 50
LH
80 X 50
FHF 32-125/11
LH
65 X 50
LH
80 X 50
FHF 32-160/15
LH
65 X 50
LH
80 X 50
FHF 32-160/22
LH
65 X 50
LH
80 X 50
FHF 32-200/30
LH
65 X 50
LH
80 X 50
FHF 32-200/40
LH
65 X 50
LH
80 X 50
FHF 40-125/11
OH1
80 X 65
OH1
100 X 65
FHF 40-125/15
OH1
80 X 65
OH1
100 X 65
FHF 40-125/22
OH1
80 X 65
OH1
100 X 65
FHF 40-160/30
OH1
80 X 65
OH1
100 X 65
FHF 40-160/40
OH1
80 X 65
OH1
100 X 65
FHF 40-200/55
OH1
80 X 65
OH1
100 X 65
FHF 40-200/75
OH1
80 X 65
OH1
100 X 65
FHF 40-250/110A
OH1
80 X 65
OH1
100 X 65
FHF 40-250/110
OH1
80 X 65
OH1
100 X 65
FHF 40-250/150
OH1
80 X 65
OH1
100 X 65
FHF 50-125/22
OH2
100 X 65
OH2
125 X 65
FHF 50-125/30
OH2
100 X 65
OH2
125 X 65
FHF 50-125/40
OH3
125 X 65
OH2
100 X 65
OH3
150 X 65
OH2
125 X 65
FHF 50-160/55
OH3
125 X 65
OH2
100 X 65
OH3
150 X 65
OH2
125 X 65
FHF 50-160/75
OH3
125 X 65
OH2
100 X 65
OH3
150 X 65
OH2
125 X 65
FHF 50-200/110A
OH3
125 X 65
OH2
100 X 65
OH3
150 X 65
OH2
125 X 65
FHF 50-200/110
OH3
125 X 65
OH2
100 X 65
OH3
150 X 65
OH2
125 X 65
FHF 50-250/150
OH3
125 X 65
OH2
100 X 65
OH3
150 X 65
OH2
125 X 65
FHF 50-250/185
OH3
125 X 65
OH2
100 X 65
OH3
150 X 65
OH2
125 X 65
FHF 50-250/220
OH3
125 X 65
OH2
100 X 65
OH3
150 X 65
OH2
125 X 65
FHF 65-125/40
OH3
125 X 80
OH3
150 X 80
FHF 65-125/55
OH3
125 X 80
OH3
150 X 80
FHF 65-125/75
OH3
125 X 80
OH3
150 X 80
FHF 65-160/110A
OH4
150 X 80
OH3
125 X 80
OH4
200 X 80
OH3
150 X 80
FHF 65-160/110
OH4
150 X 80
OH3
125 X 80
OH4
200 X 80
OH3
150 X 80
FHF 65-160/150
OH4
150 X 80
OH3
125 X 80
OH4
200 X 80
OH3
150 X 80
FHF 65-200/150
OH4
150 X 80
OH3
125 X 80
OH4
200 X 80
OH3
150 X 80
FHF 65-200/185
OH4
150 X 80
OH3
125 X 80
OH4
200 X 80
OH3
150 X 80
FHF 65-200/220
OH4
150 X 80
OH3
125 X 80
OH4
200 X 80
OH3
150 X 80
FHF 65-250/220
OH4
150 X 80
OH3
125 X 80
OH4
200 X 80
OH3
150 X 80
FHF 65-250/300
OH4
150 X 80
OH3
125 X 80
OH4
200 X 80
OH3
150 X 80
FHF 65-250/370
OH4
150 X 80
OH3
125 X 80
OH4
200 X 80
OH3
150 X 80
FHF 80-160/150
HH1
200 X 100
OH4
150 X 100
HH1
200 X 100
OH4
200 X 100
FHF 80-160/185
HH1
200 X 100
OH4
150 X 100
HH1
200 X 100
OH4
200 X 100
FHF 80-200/220
HH1
200 X 100
OH4
150 X 100
HH1
200 X 100
OH4
200 X 100
FHF 80-200/300
HH1
200 X 100
OH4
150 X 100
HH1
200 X 100
OH4
200 X 100
FHF 80-250/370
HH1
200 X 100
OH4
150 X 100
HH1
200 X 100
OH4
200 X 100
FHF 80-250/450
HH1
200 X 100
OH4
150 X 100
HH1
200 X 100
OH4
200 X 100
FHF 80-250/550
HH1
200 X 100
OH4
150 X 100
HH1
200 X 100
OH4
200 X 100
kit-asp-fhf-en_b_td
- the pumps must be chosen according to the performance levels indicated in Tab. 6 para 7.3.1, Tab.7 para 7.3.2 and the classes of risk.
- some pump models can satisfy the conditions of one or more classes of risk.
- always check the correct selection of the pump depending on the performance level of the set.
** Insert the 50 mm minimal thickness under the GEN10 fire-fighting booster sets only.
131
Lowara
GEN../FHF 100-125 SERIES FIRE-FIGHTING BOOSTER SETS
SUCTION SIDE KIT DIMENSIONS T
ABLE
TABLE
SUCTION LIFT
PUMP
RISK
SUCTION
RISK
SUCTION
RISK
SUCTION
RISK
CLASS *
KIT
CLASS *
KIT
CLASS *
KIT
CLASS *
TYPE
TYPE
TYPE
SUCTION
KIT
TYPE
FHF 100-160/185
HH3
250 X 125
HH2
250 X 125
HH3
250 X 125
HH2
250 X 125
FHF 100-160/220
HH4
250 X 125
HH3
250 X 125
HH4
300 X 125**
HH3
250 X 125
FHF 100-160/300
HH4
250 X 125
HH3
250 X 125
HH4
300 X 125**
HH3
250 X 125
FHF 100-200/185
HH3
250 X 125**
HH2
250 X 125**
HH3
250 X 125**
HH2
250 X 125**
FHF 100-200/300
HH3
250 X 125**
HH2
250 X 125**
HH3
250 X 125**
HH2
250 X 125**
FHF 100-200/370
HH4
250 X 125**
HH3
250 X 125**
HH4
300 X 125**
HH3
250 X 125**
FHF 100-200/450
HH4
250 X 125
HH3
250 X 125
HH4
300 X 125**
HH3
250 X 125
FHF 100-250/300
HH3
250 X 125
HH2
250 X 125
HH3
250 X 125
HH2
250 X 125
FHF 100-250/450
HH4
250 X 125
HH3
250 X 125
HH4
300 X 125**
HH3
250 X 125
FHF 100-250/550
HH4
250 X 125
HH3
250 X 125
HH4
300 X 125
HH3
250 X 125
FHF 100-250/750
HH5
300 X 125
HH4
250 X 125
HH5
300 X 125
HH4
300 X 125
FHF 100-250/900
HH6
300 X 125
HH5
300 X 125
HH6
300 X 125
HH5
300 X 125
FHF 125-200/300
HH7
300 X 150
HH6
300 X 150
HH7
300 X 150
HH6
300 X 150
FHF 125-200/450
HH9
300 X 150
HH8
300 X 150
HH9
400 X 150**
HH8
350 X 150**
FHF 125-200/550
HH10
350 X 150**
HH9
300 X 150
HH10
400 X 150**
HH9
400 X 150**
FHF 125-270/750
HH10
350 X 150
HH9
300 X 150
HH10
400 X 150
HH9
400 X 150
FHF 125-270/900
HH10
350 X 150
HH9
300 X 150
HH10
400 X 150
HH9
400 X 150
FHF 125-270/1100
HH10
350 X 150
HH9
300 X 150
HH10
400 X 150
HH9
400 X 150
FHF 125-270/1320
HH10
350 X 150
HH9
300 X 150
HH10
400 X 150
HH9
400 X 150
kit-asp-fhf100-en_a_td
- the pumps must be chosen according to the performance levels indicated in Tab. 6 para 7.3.1, Tab. 7 para 7.3.2 and the classes of risk.
- some pump models can satisfy the conditions of one or more classes of risk.
- always check the correct selection of the pump depending on the performance level of the set.
** Insert the 50mm minimal thickness under the GEN10 fire-fighting booster sets only.
132
Lowara
GEN../SHF 32-80 SERIES FIRE-FIGHTING BOOSTER SETS
SUCTION SIDE KIT DIMENSIONS T
ABLE
TABLE
SUCTION LIFT
PUMP
RISK
SUCTION
RISK
SUCTION
RISK
SUCTION
RISK
CLASS *
KIT
CLASS *
KIT
CLASS *
KIT
CLASS *
TYPE
TYPE
TYPE
SUCTION
KIT
TYPE
SHF 32-125/07
LH
65 X 50
LH
80 X 50
SHF 32-125/11
LH
65 X 50
LH
80 X 50
SHF 32-160/15
LH
65 X 50
LH
80 X 50
SHF 32-160/22
LH
65 X 50
LH
80 X 50
SHF 32-200/30
LH
65 X 50
LH
80 X 50
SHF 32-200/40
LH
65 X 50
LH
80 X 50
SHF 32-250/55
LH
65 X 50
LH
80 X 50
SHF 32-250/75
LH
65 X 50
LH
80 X 50
SHF 32-250/110
LH
65 X 50
LH
80 X 50
SHF 40-125/11
OH1
80 X 65
OH1
100 X 65
SHF 40-125/15
OH1
80 X 65
OH1
100 X 65
SHF 40-125/22
OH1
80 X 65
OH1
100 X 65
SHF 40-160/30
OH1
80 X 65
OH1
100 X 65
SHF 40-160/40
OH1
80 X 65
OH1
100 X 65
SHF 40-200/55
OH1
80 X 65
OH1
100 X 65
SHF 40-200/75
OH1
80 X 65
OH1
100 X 65
SHF 40-250/110A
OH1
80 X 65
OH1
100 X 65
SHF 40-250/110
OH1
80 X 65
OH1
100 X 65
SHF 40-250/150
OH1
80 X 65
OH1
100 X 65
SHF 50-125/22
OH2
100 X 65
OH2
125 X 65
SHF 50-125/30
OH2
100 X 65
OH2
125 X 65
SHF 50-125/40
OH3
125 X 65
OH2
100 X 65
OH3
150 X 65
OH2
125 X 65
SHF 50-160/55
OH3
125 X 65
OH2
100 X 65
OH3
150 X 65
OH2
125 X 65
SHF 50-160/75
OH3
125 X 65
OH2
100 X 65
OH3
150 X 65
OH2
125 X 65
SHF 50-200/110A
OH3
125 X 65
OH2
100 X 65
OH3
150 X 65
OH2
125 X 65
SHF 50-200/110
OH3
125 X 65
OH2
100 X 65
OH3
150 X 65
OH2
125 X 65
SHF 50-250/150
OH2
100 X 65
OH2
125 X 65
SHF 50-250/185
OH3
125 X 65
OH2
100 X 65
OH3
150 X 65
OH2
125 X 65
SHF 50-250/220
OH3
125 X 65
OH2
100 X 65
OH3
150 X 65
OH2
125 X 65
SHF 65-160/40
OH3
125 X 80
OH3
150 X 80
SHF 65-160/55
OH3
125 X 80
OH3
150 X 80
SHF 65-160/75
OH3
125 X 80
OH3
150 X 80
SHF 65-160/110A
OH3
125 X 80
OH3
150 X 80
SHF 65-160/110
OH3
125 X 80
OH3
150 X 80
SHF 65-200/150
OH3
125 X 80
OH3
150 X 80
SHF 65-200/185
OH3
125 X 80
OH3
150 X 80
SHF 65-200/220
OH4
150 X 80
OH3
125 X 80
OH4
200 X 80
OH3
150 X 80
SHF 65-250/300
OH4
150 X 80
OH3
125 X 80
OH4
200 X 80
OH3
150 X 80
SHF 65-250/370
OH4
150 X 80
OH3
125 X 80
OH4
200 X 80
OH3
150 X 80
SHF 80-160/110
HH1
200 X 100
OH4
150 X 100
HH1
200 X 100
OH4
200 X 100
SHF 80-160/150
HH1
200 X 100
OH4
150 X 100
HH1
200 X 100
OH4
200 X 100
SHF 80-160/185
HH1
200 X 100
OH4
150 X 100
HH1
200 X 100
OH4
200 X 100
SHF 80-200/220
HH1
200 X 100
OH4
150 X 100
HH1
200 X 100
OH4
200 X 100
SHF 80-200/300
HH1
200 X 100
OH4
150 X 100
HH1
200 X 100
OH4
200 X 100
SHF 80-200/370
HH1
200 X 100
OH4
150 X 100
HH1
200 X 100
OH4
200 X 100
SHF 80-250/450
HH1
200 X 100
OH4
150 X 100
HH1
200 X 100
OH4
200 X 100
SHF 80-250/550
HH1
200 X 100
OH4
150 X 100
HH1
200 X 100
OH4
200 X 100
SHF 80-250/750
HH1
200 X 100
OH4
150 X 100
HH1
200 X 100
OH4
200 X 100
kit-asp-shf-en_a_td
- the pumps must be chosen according to the performance levels indicated in Tab. 6 para 7.3.1, Tab. 7 para 7.3.2 and the classes of risk.
- some pump models can satisfy the conditions of one or more classes of risk.
- always check the correct selection of the pump depending on the performance level of the set.
** Insert the 50mm minimal thickness under the GEN10 fire-fighting booster sets only.
133
Lowara
ALARMS CONTROL ELECTRICAL P
ANEL
PANEL
Electric panel for remote status and alarm monitoring of one or two Lowara pumps installed in GEN fire-fighting
booster sets, according to EN12845.
In the electric service pump mode, the following conditions are visualised:
- Motor powered.
- Pump start-up request.
- Pump running
- Failure to start.
Additionally: minimum suction tank level, minimum priming tank level, on-off valve on suction and discharge side
not fully open. The valves are complete with status monitor.
In the diesel engine service pump mode, the following conditions are visualised, as required by EN12845:
- Switch on diesel engine pump control panel in non-automatic position.
- Diesel engine ails to start after 6 attempts.
- Pump running
- Controller fault.
Additionally: minimum fuel or suction tank level, minimum priming tank level, on-off valve on suction and
discharge side not fully open. The valves are complete with status monitor.
All the above conditions, required by EN12845, are visualised with signal LEDs and buzzers. A buzzer alarm reset
button and LED tester button are included.
The control unit is also fitted out to signal the following general alarms, if present:
- General alarm for incorrect electrical connection in the exchange contacts of: flow meter circuit valve, discharge
pump, jockey pump status.
- Fault in electrical connection in the exchange contact relative to panel 1 (electric pump/diesel engine pump)
- Fault in electrical connection in the exchange contact relative to panel 2 (electric pump/diesel engine pump)
- Jockey pump overload (*).
- Jockey pump running(*)
- Discharge pump overload (*).
- Battery voltage low.
- Communications failure with ModBus system.
All the above conditions are visualised with signal LEDs and on the display. The customer may decide to enable
the buzzer.
The panel comprises a plastic casing (IP55), battery, battery charger, alarms and pump status display, if connected
with 485 serial communication.
Fitted to transmit alarms for GSM or PC module.
The electric connection between the contacts on the electric alarms control panel and other electric panels is to be
seen to by the person installing the equipment.
(*) Check that the electric control panel combined with the electric pump is complete with clean contacts for
pump running and overload signals.
275
DESCRIPTION
VALUE
V
L1/
V
+
L2/
L2/
V
L3
A
L3
N.P.
INCREASE
Absorbed
0,1A
A
L1/
Protection grade
Battery
ENTER
DECREASE / MENU'
IP55
370
Dimensions
SHIFT
Hermetic lead
12 Vcc
LAMPS TEST
PROVA
LAMPADE
BUZZER
SWITCH OFF
TACITAZIONE
SIRENA
L2
L1
JOCKEY PUMP
L3
Type
DSRC
Plant Type:
Tipo impianto:
GA11E+1D
POWER ON
PRESENZA TENSIONE
-
2,3 Ah ( uncharged in 20 h)
Dimensions of battery
178 x 34 x 66 mm
75dB
1,5kg
+ UNDER THRESHOLD
SOTTO SOGLIA
PUMP ON
POMPA IN MARCIA
INTERRUPTED LINES
LINEE INTERROTTE
Code N. 32.000.10.0
Buzzer 12Vcc 90mA 75dB(A)
L2
OVERLOAD
SOVRACCARICO
SPRINKLER PUMPS ROOM
SPRINKLER SALA POMPE
PUMP SET ON DEMAND
RICHIESTA DI AVVIAMENTO
SELECTOR NOT IN
AUT. FUNCTION
SELETTORE NON IN AUT.
!
OFF
!
OFF
1
POMPA COMPENSAZIONE
L3
L1
Circ. N. 17.029.001.0
0,2 A
IP 55
START FAILURE
MANCATO AVVIAMENTO
SWITCHBOARD FAILURE
GUASTO QUADRO
!
OFF
1
!
OFF
2
12845_002_D_DD
12845-qal-en_b_td
134
SPRINKLER DRAINAGE
PUMPS ROOM FAULT PUMP
ACCORDING TO EN12845
Lowara
FL
OW METER KIT
FLOW
The flow meter is supplied as part of the assembly kit. The EN 12845 standard requires the presence of the flow meter
for checking the hydraulic performance during the test stage and duration periodic inspections. The suction side kit
are equipped with:
- Direct reading flow meter.
- On/off ball valve for diameters up to 2" inclusive, butterfly valve with lever handle from DN65 to DN100
diameter, butterfly valve with handwheel and reduction manual gear for DN125 diameter and above. Device
for monitoring ON/OFF status included. Electrical connections by customer. (Valve lock kit available on request).
- Connection piping.
The meter is available in various sizes according to the flow of a service pump and suitable for being connected to the
offtake of the head manifold. For a correct match, identify the type as shown in the set size tables. The flow meter
must be installed, where possible, in a stretch of piping with a steady flow and sufficient back pressure at the
discharge outlet. The assembly and the discharge piping towards the tank and discharge outlet are to be seen to by
the person installing the equipment.
A
SHAPE B
C
TABELLASHAPE
DIMENSIONALE
KIT_FLUSSIMETRO
GRUPPISHAPE
EN12845
SHAPE D
DIMENSIONS (mm)
DIMENSIONS (mm)
TYPE
TYPE
DN
DNAS
SHAPE
DN
DNAS
SHAPE
32X25P
32
25
90
605
100X40P
100
40
300
760
32X32P
32
32
90
625
100X50P
100
50
300
750
32X40P
32
40
90
645
100X65P
100
65
340
410
40X25P
40
25
100
605
100X80P
100
80
340
410
40X32P
40
32
100
630
100X125
100
125
340
945
40X40P
40
40
100
645
125X50P
125
50
300
760
40X50P
40
50
100
640
125X65P
125
65
340
425
50X25P
50
25
105
610
125X80P
125
80
340
425
50X32P
50
32
105
635
125X125
125
125
340
755
50X40P
50
40
105
655
125X150
125
150
340
1085
50X50P
50
50
105
645
150X65P
150
65
380
435
65X25P
65
25
300
700
150X80P
150
80
380
440
65X32P
65
32
300
725
150X125
150
125
380
770
65X40P
65
40
300
740
150X150
150
150
380
900
65X50P
65
50
300
730
150X200
150
200
380
1380
65X65P
65
65
340
390
200X80P
200
80
380
465
65X80P
65
80
340
595
200X125
200
125
380
795
80X40P
80
40
300
745
200X150
200
150
380
925
80X50P
80
50
300
735
200X200
200
200
380
1170
80X65P
80
65
340
400
250X125
250
125
440
825
80X80P
80
80
340
400
250X150
250
150
440
950
80X125
80
125
340
910
250X200
250
200
440
1195
12845_kit_flux-acc-en_a_td
135
Lowara
TABLE OF COMBINA
TIONS FOR FL
OW METER KIT
COMBINATIONS
FLOW
AND FHF SERVICE PUMP SERIES
ELECTRIC
TYPE
COMBINATION
TYPE
COMBINATION
FHF..
FHF..
GEN..
PUMP
PUMP
10
11
ELECTRIC
20
21
GEN..
PUMP
PUMP
10
11
20
21
32-125/07
32-125/D119
65-200/D187
32-125/11
32-125/D136
65-200/D198
32-160/15
32-160/D150
65-200/D210
32-160/22
32-160/D164
65-250/D220
32-200/30
32-200/D188
65-250/D241
32-200/40
32-200/D204
65-250/D258
40-125/11
40-125/D112
80-160/D163
40-125/15
40-125/D122
80-160/D173
40-125/22
40-125/D143
80-200/D189
40-160/30
40-160/D159
80-200/D207
40-160/40
40-160/D171
80-250/D225
40-200/55
40-200/D190
80-250/D238
40-200/75
40-200/D209
80-250/D256
40-250/110A 40-250/D218
40-250/110
40-250/D233
40-250/150
40-250/D251
50-125/22
50-125/D119
50-125/30
50-125/D130
50-125/40
50-125/D139
50-160/55
50-160/D158
50-160/75
50-160/D174
50-200/110A 50-200/D197
50-200/110
50-200/D209
50-250/150
50-250/D224
50-250/185
50-250/D237
50-250/220
50-250/D250
65-125/40
65-125/D121
65-125/55
65-125/D129
65-125/75
65-125/D140
65-160/110A 65-160/D161
65-160/110
65-160/D168
80X80P 80X80P 100X80P 100X80P 125-270/1100 125-270/D253 150X200 150X200 250X200 250X200
65-160/150
65-160/D178
80X80P 80X80P 100X80P 100X80P 125-270/1320 125-270/D266 150X200 150X200 250X200 250X200
12845_kit_flux-fhf_10-21-en_b_th
136
Lowara
TABLE OF COMBINA
TIONS FOR FL
OW METER KIT
COMBINATIONS
FLOW
AND SHF SERVICE PUMP SERIES
ELECTRIC
TYPE
COMBINATION
TYPE
COMBINATION
SHF..
SHF..
GEN..
PUMP
PUMP
10
11
ELECTRIC
20
21
GEN..
PUMP
PUMP
10
11
20
21
32-125/07
32-125/D121
32-125/11
32-125/D136
50-200/D209
32-160/15
32-160/D150
50-250/D224
32-160/22
32-160/D168
50-250/D237
32-200/30
32-200/D188
50-250/D250
32-200/40
32-200/D204
65-160/D119
32-250/55
32-250/D222
65-160/D129
32-250/75
32-250/D242
65-160/D137
32-250/110
32-250/D256
40-125/11
40-125/D112
65-160/D177
40-125/15
40-125/D126
65-200/D192
40-125/22
40-125/D143
65-200/D203
40-160/30
40-160/D159
65-200/D215
40-160/40
40-160/D171
65-250/D240
40-200/55
40-200/D190
65-250/D255
40-200/75
40-200/D209
80-160/D169
40-250/110A 40-250/D218
80-160/D177
40-250/110
80-160/D186
40-250/D233
40-250/150
40-250/D251
80-200/D198
50-125/22
50-125/D119
80-200/D215
50-125/30
50-125/D130
80-200/D226
50-125/40
50-125/D139
80-250/D237
50-160/55
50-160/D158
80-250/D252
50-160/75
50-160/D174
80-250/D270
137
Lowara
PRIMING T
ANK
TANK
The priming tank is used in suction lift installations and carries out the function of maintaining the pump body
and suction pipe full of water even if there are leaks through the bottom valve.
Each pump must have its own independent priming tank, placed at a higher level than the pump. The tank must
be connected to a water source for adding water and keeping it full. The diameter of the connecting pipe to the
pump depends on the use class. The return piping for re-circulation can be connected to the tank, which must
also provide for discharge if it is too full.
A level indicator automatically actions the service pump if the level of the tank drops and is not reintegrated.
The hydraulic connections must be seen to by the person installing the equipment.
The horizontal 500 l tank is made of zinc-plated steel.
ACCES
SORIES PRIMING T
ANK KIT
ACCESSORIES
TANK
The available accessories kit includes:
- Filling and discharge valves, reductions, non-return valve, closing plugs and automatic air discharger.
- Float switch tap complete with ring nut for fixing to the hole through the tank.
- Level indicator to connect to the electric panel and assembly instruction sheet.
Available on request tank support, height 75, 100, 150, 200 cm.
Example of connection to the tank and accessories:
1
2
3
4
5
6
7
DESCRIPTION
8
9
10
11
12
13
14
DESCRIPTION
138
Lowara
ELECTRIC JOCKEY PUMP KIT
The jockey pump or compensation pump has the job of keeping the system under pressure and compensating for
any small loses without the intervention of the service pumps. In fact, the jockey pump is commanded by an
automatic shut-off panel. Should an electric jockey pump of a different size from the standard be required or
should it be installed later on sets which are not predisposed, or should non-standard different size requirements
be required, it is possible to configure the booster set with just the service pumps and add the electric jockey
pump, also later on.
The kit includes:
- the hydraulic components for installing the electric pump (base, valves, pressure switch).
- the pre-chosen electric pump and the relative electric panel.
The hydraulic connection to the set can be easily carried out using one of the couplings on the delivery manifold
for the membrane tanks using an adaptor.
Kits are available for the vertical electric jockey pumps SV2, SV4, SV8 series and submersed series 2GS, 4GS, 6GS.
The diagram illustrates some connection examples:
1
2
3
4
5
DESCRIPTION
Electric pump
Control Box
Connection to trunk main
Pipe connection to delivery side of the jockey pump
To trunk main
acc-kit-fil-en_a_tc
139
Lowara
PANEL BRACKET KIT
The electric command panels supplied separately, for example in
the sets with submersed pumps, are suitable for being mounted
on the wall. Universal bracket kit are available, upon request, for
supporting the panels; it must be fixed to the floor using blocks.
GU_ACC_M0001_A_SC
HYDRA
ULIC CONNECTION FOR FIRE-FIGHTING EN 12845 SETS
HYDRAULIC
1
2
3
4
DESCRIPTION
5
6
7
8
DESCRIPTION
140
Lowara
ACCES
SORIES
ACCESSORIES
FLOATS
MONITORED VALVES
VALVES
HYDRO TUBE
FLOW METER
ELASTIC JOINTS
141
PRESSURE SWITCHS
Lowara
PRODUCT DESCRIPTION B
Y TECHNICAL SPECIFICA
TIONS
BY
SPECIFICATIONS
Description EN 12845 fire-fighting booster set
Series : GEN
Model: electric service pump
jock
ey or compensation pump
jockey
The pump station will comprise the following components:
- N1 electric jockey pump;
- N1 electric service pump;
- One electrical power and control panel for the electric service pump;
- One electrical power and control panel for the electric jockey pump;
- Components and materials required for perfect operation and assembly;
IT
T Lowara booster sets are CE-certified and comply with the following directives:
ITT
142
Lowara
PRODUCT DESCRIPTION B
Y TECHNICAL SPECIFICA
TIONS
BY
SPECIFICATIONS
Basic version with periodic auto-test, Series GEN..A.
Electronic auto-test circuit with weekly programmer in the electrical panel of the service pump. The pump is turned
on an kept working for a minute at the previously established time and date.
During this interval the check circuit checks that the pressure in the re-circulation circuit closes the pressure switch
contact of the pump which is running. In the case of irregularities, the relative auxiliary self-test alarm relay available
for remote signalling is activated and memorised.
The EN 12845 Standard does not provide for the presence of a self-test circuit but asks for periodic checks to be
carried out by the user, hence the periodic self-test function cannot substitute the above checks.
For the precalculated HHP and HHS risk class systems and in the integrally calculated systems, the pump must be able
to provide, at 140% of rated capacity, a pressure of not less than 70% of the rated pressure of the pump.
Each pump generally backs up the other even if much depends on the chosen type of water supply. If the service
pump fails, or a blackout occurs, system pressure will decrease and the backup diesel pump will start. The pumps are
started automatically by the pressure switches while they are manually stopped from the electrical panel (key switch).
143
Lowara
PRODUCT DESCRIPTION B
Y TECHNICAL SPECIFICA
TIONS
BY
SPECIFICATIONS
Main characteristics of the electric service pump:
TABELLA MATERIALI POMPA SERVIZIO FHF PER CAPITOLATI TECNICI
Brand
Model:
Flow rate
Head:
Pump body:
Seal housing:
Impeller:
Shaft:
Elastomers:
Mechanical seal:
Motor power:
Input voltage:
Frequency:
Rated current input:
Speed of rotation:
Max. ambient temp:
Protection class:
Insulation class:
ITT LOWARA
FHF
m3/h
m.c.a.
Cast iron, EN 1561-GJL-200 (JL1030)
Cast iron, EN 1561-GJL-200 (JL1030)
Cast iron, EN 1561-GJL-200 (JL1030)
Stainless steel EN10088-1-X2 CrNiMo17-12-2
NBR
Ceramic/Carbon/NBR
Kw
V
Hz
A
r.p.m.
C
400 / 3
50
2900
40
IP 55
F
tec_FHF-en_a_tm
Electric jock
ey pump comprising:
jockey
Multi-cell vertical centrifugal Jockey pump, SV
SV... with metal parts in contact with liquid in stainless steel,
pump body and shaft in AISI 304 stainless steel, impeller in AISI 304 stainless steel, mechanical seal in Carburundum/
carbon/EPDM.
Three-phase electric motor, shape B14, performance values within what is referred to as efficiency class 2, short
circuit squirrel cage motor, closed aluminium casing and external ventilation, performance according to EN 60034-1,
directly coupled to the vertical pump. Protected to IP55, insulation class F.
144
Lowara
PRODUCT DESCRIPTION B
Y TECHNICAL SPECIFICA
TIONS
BY
SPECIFICATIONS
Main technical characteristics of the jock
ey pump:
jockey
TABELLA MATERIALI POMPA SERVIZIO SV PER CAPITOLATI TECNICI
Brand:
Model:
Flow rate:
Head:
Pump body:
Impeller:
Diffuser:
Shaft:
Outer sleeve:
Mechanical seal:
Motor power:
Input voltage:
Frequency:
Rated current:
Speed:
Max. ambient temp.:
Protection class:
Insulation class:
ITT LOWARA
SV..
m3/h
m.c.a.
Stainless steel (1.4301)
Stainless steel (1.4301)
Stainless steel (1.4301)
Stainless steel (1.4301)
Stainless steel (1.4301)
Silicon carbide/Carbon/EPDM
Kw
V
Hz
A
r.p.m.
C
400 / 3
50
2900
40
IP - 55
F
tec_SV-en_a_tm
Electric panels
Inside:
-
145
Lowara
PRODUCT DESCRIPTION B
Y TECHNICAL SPECIFICA
TIONS
BY
SPECIFICATIONS
-
Line contact maker (direct start-up), line and star/delta contact makers (star/delta start-up), line contact makers
and reactance switching (impedance start-up).
Star/delta exchanger timer or reactance switching.
Relay for signalling no phase.
Auxiliary relays.
Current transformer.
Terminal boards.
Clean contacts (max 24V, 1A) for activating acoustic/ visual alarms for no phase, pump on demand, pump
running and start failure.
Cable glands (excluding the versions to be fixed to the floor).
Wiring diagram.
Jock
ey pump electrical panel
Jockey
Painted metal casing (IP55) complete with:
Inside:
Suitable for connecting to a float switch or a minimum pressure switch for preventing dry running. An optional level
control module (supplied upon request) allows the connection of probes with the possibility of regulating the sensitivity
according to the hardness of the water.
Series of clean contacts for checking the status of the electric service pump panel, as well as
the contacts already provided for signalling alarms (on request):
No phase.
Motor running..
Selector position Man-Aut-0.
Failure to start.
Start-up request.
Series of clean contacts for checking the status of the electric jock
ey pump (on request)
jockey
- Pump running.
- Thermal shutdown (overload).
- No water.
146
Lowara
PRODUCT DESCRIPTION B
Y TECHNICAL SPECIFICA
TIONS
BY
SPECIFICATIONS
Electrical alarms panel
Plastic casing protected to IP55 with an electronic board at the front for the visual and acoustic signalling of the
status of one or two service pumps. The following alarms are signalled :
Electric pump
Power off.
Start-up request.
Pump running.
No start-up.
The electric panel is fitted with a buzzer with reset button, signal LED test button, battery charger and battery and is
fitted out to signal the following general alarms, if present:
- General alarm for incorrect electrical connection in the exchange contacts of:
status of flow measurement circuit valve, drain pump, jockey pump.
- Fault in electrical connection in the exchange contact relative to panel 1 (electric pump/diesel engine pump).
- Fault in electrical connection in the exchange contact relative to panel 2 (electric pump/diesel engine pump).
- Jockey pump overload.
- Jockey pump running.
- Discharge pump overload.
- Battery voltage low.
- Communications failure with ModBus system.
GSM modem system status transmission module and RS232/485 converter module available on request.
275
DESCRIPTION
VALUE
V
L1/
V
+
L2/
L2/
V
L3
A
L3
N.P.
INCREASE
Absorbed
A
L1/
Protection grade
Battery
ENTER
DECREASE / MENU'
IP55
370
Dimensions
SHIFT
0,1A
Hermetic lead
12 Vcc
SPRINKLER DRAINAGE
PUMPS ROOM FAULT PUMP
ACCORDING TO EN12845
LAMPS TEST
PROVA
LAMPADE
BUZZER
SWITCH OFF
TACITAZIONE
SIRENA
L2
L1
JOCKEY PUMP
L3
DSRC
GA11E+1D
POWER ON
PRESENZA TENSIONE
-
2,3 Ah ( uncharged in 20 h)
Dimensions of battery
178 x 34 x 66 mm
75dB
1,5kg
+ UNDER THRESHOLD
SOTTO SOGLIA
PUMP ON
POMPA IN MARCIA
INTERRUPTED LINES
LINEE INTERROTTE
Code N. 32.000.10.0
Buzzer 12Vcc 90mA 75dB(A)
L2
OVERLOAD
SOVRACCARICO
SPRINKLER PUMPS ROOM
SPRINKLER SALA POMPE
PUMP SET ON DEMAND
RICHIESTA DI AVVIAMENTO
SELECTOR NOT IN
AUT. FUNCTION
SELETTORE NON IN AUT.
!
OFF
!
OFF
1
POMPA COMPENSAZIONE
Type
Plant Type:
Tipo impianto:
L3
L1
Circ. N. 17.029.001.0
0,2 A
IP 55
START FAILURE
MANCATO AVVIAMENTO
SWITCHBOARD FAILURE
GUASTO QUADRO
!
OFF
1
!
OFF
2
12845_002_D_DD
12845-qal-en_b_td
On/off valves on the delivery side of each pump, ball valves with lever handle for diameters up to 11/4" inclusive,
butterfly valve with lever handle from DN65 to DN100 diameter, butterfly valve with handwheel and reduction
manual gear for DN125 diameter and above.
- Re-circulation device for each service pump.
The re-circulation device allows a minimum capacity in order to prevent the pump overheating when working with
closed delivery. It includes the activation pressure switch for the alarms of the pumps running, the test valve for
checking the seal of the check valves, the couplings for any connecting pipes to the priming tank in the case of
suction lift installation. The connection of each re-circulation to the suction tank or the priming tank is to be seen
to by the person installing the equipment.
147
Lowara
PRODUCT DESCRIPTION B
Y TECHNICAL SPECIFICA
TIONS
BY
SPECIFICATIONS
-
Pressure gauge on the delivery side of each service pump between check valve and on/off valve.
Check valve be inspected type, on the delivery side of each pump. Threaded connector up to and including a
diameter of 11/4". Flanged connector for larger diameters.
Painted iron delivery manifold (PN 16) and threaded stubs with relative caps for connecting any 24 litre
membrane tanks. Blind and welding zinc-plated flanges.
Start-up pressure switch circuit for the service pump, including connecting pipes for the delivery manifold,
recirculation circuit. This circuit includes on/off valve, a non-return valve, a discharge or test valve and various
pipe fittings. The configuration of the circuit allows the pressure switch to intervene also when the relative on/off
valve is closed.
Base made of bent sheet or structural iron with epoxy powder painting RAL 5010.
Control panel frame made of structural iron with epoxy powder painting RAL 5010.
The control panels for the electric pumps up to 55 kW power supply are fixed on bracket. For higher powers, the
control panels for electric pump service are floor mounted, instead the jockey electric pump panel is wall mounted
fixed.
148
Lowara
PRODUCT DESCRIPTION B
Y TECHNICAL SPECIFICA
TIONS
BY
SPECIFICATIONS
Flow meter
The flow meter is supplied as part of the assembly kit. The EN 12845 standard requires the presence of the flow
meter for checking the hydraulic performance during the test stage and duration periodic inspections. The kit
comprises:
- Direct reading flow meter.
- On/off ball valve for diameters up to 2 inclusive, butterfly valve with lever handle from DN65 to DN100 diameter,
butterfly valve with handwheel and reduction manual gear for DN125 diameter and above.
- Straight plastic connection piping.
IThe flow meter is available in various sizes according to the flow of a service pump and suitable for being connected
to the offtake of the head manifold. For a correct match, identify the type as shown in the set size tables.
The assembly and the discharge piping towards the tank and discharge outlet are to be seen to by the person
installing the equipment.
The following illustration shows the type and size of flow meter:
Dimensions (mm):
DN =
DNAS =
L=
H=
Qmax (m3/h) =
149
Lowara
PRODUCT DESCRIPTION B
Y TECHNICAL SPECIFICA
TIONS
BY
SPECIFICATIONS
Diaphragm tanks
The booster sets are ready for installation, directly on the manifold, of 24-litre diaphragm tanks, one for each pump.
The sets are also equipped with caps to close off the unused couplings. Larger tanks can also be connected to the
unused end of the discharge manifold.
The kit is made up of the following accessories:
Diaphragm tank;
On-off ball valve;
Instructions manual;
Packaging.
Suction kit
The EN 12845 fire-fighting booster sets are supplied without valves and stubs on the suction side of the service pump
and can be completed with suitable kits that depend on legal standards.
These requirements are expressed by EN 12845 (chapter 10.5 and chapter 10.6) and are connected with the
maximum speed value of the water in the pipes, their minimum section and type of installation - suction lift or
positive suction head. To provide for one suction kit for each duty pump.
The kit comprises:
Dimensions (mm):
DNA =
DNS =
L=
H=
150
Lowara
PRODUCT DESCRIPTION B
Y TECHNICAL SPECIFICA
TIONS
BY
SPECIFICATIONS
The set is supplied already assembled, calibrated and factory tested. The set is supplied
complete with an instruction manual, pump manuals and wiring diagrams for the panels.
F
or the sets including floor panels, the electric panels are sent together with the set in a
For
separate pack and supplied with 5-metre long connecting cables (longer lengths
available on request). The fitter is responsible for preparing the routes and installing the
cables.
151
Lowara
ITT Lowara part of ITT Corporation and headquarters of Residential and
Commercial Water - EMEA.
World leading in offering high reliable fluid handling solutions for Building
Services, Irrigation and Industrial applications. We provide a complete range of
high quality pumps, packaged systems and controls and are specialized in
engineering and manufacturing stainless steel products.
ITT Lowara is headquartered in Vicenza, Italy and operates in more than 80
countries across the world with own plants in Italy, Austria, Poland and Hungary.
The company has 1.300 employees and generated 2008 sales exceeding $440
million. ITT Lowara is wholly owned by the ITT Corporation of White Plains, New
York, and is the EMEA headquarter of ITTs Residential and Commercial Water
division. ITT Corporation is a high-technology engineering and manufacturing
company operating on all seven continents in three vital markets: water and fluids
management, global defense and security, motion and flow control. ITT
Corporation generated 2008 sales of $11.7 billion
cod. 191000001
191000451 PW07/09
11/09
IRELAND
ITT IRELAND
50 Broomhill Close
Airton Road
Tallaght
DUBLIN 24
Tel. (+353) 01 4524444
Fax (+353) 01 4524795
e-mail: lowara.ireland@itt.com http://www.lowara.ie
NEDERLAND
LOWARA NEDERLAND B.V.
Zandweistraat 22
4181 CG Waardenburg
Tel. (+31) 0418 65 50 60
Fax (+31) 0418 65 50 61
e-mail: sales.nl@itt.com
http://www.lowara.nl
POLAND
LOWARA VOGEL POLSKA Sp. z o.o.
PL 57-100 Strzelin
ul. Kazimierza Wielkiego 5
Tel. (+48) 071 769 3900 - Fax (+48) 071 769 3909
e-mail: info.lowarapl@itt.com http://www.lowara-vogel.pl
PORTUGAL
ITT PORTUGAL, Lda
Praeta da Castanheira, 38
4475-019 Barca
Tel. (+351) 22 9478550
Fax (+351) 22 9478570
e-mail: info.pt@itt.com
http://www.itt.pt
RUSSIA
LOWARA RUSSIA
Kalanchevskaya st. 11 b.2, off. 334
107078 Moscow
Tel. (+7) 495 631 55 15
Fax (+7) 495 631 59 72
info.lowararu@itt.com - www.lowara.ru
UK
LOWARA UK LTD.
Millwey Rise, Industrial Estate
Axminster - Devon EX13 5HU UK
Tel. (+44) 01297 630200
Fax (+44) 01297 630270
e-mail: lowaraukenquiries@itt.com
http://www.lowara.co.uk