Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                

Genfhfshf 50 TD en

Download as pdf or txt
Download as pdf or txt
You are on page 1of 152

Lowara

GEN Series
Fire-fighting booster sets EN 12845
Horizontal Centrifugal electric pumps FHF and SHF series
equipped with high efficiency PLM motors
50 Hz

Lowara

WEB 11-2009

Lowara
CONTENTS

General introduction .............................................................................................................................

Characteristics of electric pumps ...........................................................................................................

12

Accessories and main components ..................................................................................................

18

Choice and selection ........................................................................................................................

27

GEN../FHF series .............................................................................................................................

29

Range ...............................................................................................................................................

33

Hydraulic performance tables ...........................................................................................................

45

Electrical data tables ........................................................................................................................

47

GEN..10/FHF series ...........................................................................................................................

51

GEN..11/FHF series ............................................................................................................................

57

GEN..20/FHF series ............................................................................................................................

61

GEN..21/FHF series ............................................................................................................................

71

Hc pressure drop curve in suction kit ................................................................................................

Lowara
CONTENTS

83

GEN../SHF series ............................................................................................................................

85

Range ...............................................................................................................................................

88

Hydraulic performance tables ...........................................................................................................

98

Electrical data tables .........................................................................................................................

99

GEN..10/SHF series ...........................................................................................................................

103

GEN..11/SHF series ......................................................................................................................

107

GEN..20/SHF series ......................................................................................................................

111

GEN..21/SHF series ......................................................................................................................

117

Hc pressure drop curve in suction kit ...........................................................................................

127

Accessories ..................................................................................................................................

142

Product description by technical specifications ............................................................................

Lowara
GEN SERIES OF BOOSTER SETS
GENERAL INTRODUCTION PRODUCT DESCRIPTION
The GEN booster sets are built in conformity with EN12845 for automatic sprinkler systems and with UNI10779 for
hydrant systems.
In accordance with the above standards, all the main components of the booster set are factory connected and
assembled.
The configuration of the booster set depends on the number of pumps installed and on the type of electric motor or
diesel engine, consistently with the type of supply chosen for the fire-fighting system from among those described in
the standard. The water supply can be single, superior, duplicated or combined. Two main service pumps, one backing
up the other, are normally installed for fire-fighting systems. The choice of electric motors or diesel engines depends on
the level of reliability required from the system. In practice, fire-fighting booster sets have one electric service pump and
one diesel service pump.
Point 10.2 of EN 12845 states that for superior or duplicate water supplies, and if more than one pump is installed, no
more than one service pump can be driven by the electric motor.
This concept means that mixed assemblies, comprising electric or diesel pumps, have to be installed.
This does not mean that it is not possible to have two electric pumps, one backing up the other, if the ascertained fire
risk is low (single supplies) or if a diesel generator is already incorporated in the system.
The Lowara GEN series of booster sets are therefore configured according to system requirements and initial
considerations. They are also factory tested and comprise the following:
One or two horizontal or vertical service pumps with the same hydraulic performance level, driven by
an electric motor.
Two horizontal service pumps with the same hydraulic performance level, driven by an electric motor
and a diesel engine.
A horizontal service pump driven by a diesel engine.
The booster set is built and completed with the following main components:
A Lowara SV series jockey electric pump (if required), controlled by an electric panel in the automatic
mode. The jockey pump is automatically started and stopped by its pressure switch in order to restore
supply pressure. This prevents the service pumps from starting and activating the main alarms.
A control panel for each service pump.
Two pressure switches for each service pump (if the first fails, the second repeats permission for the
pump to start).
On the discharge side of each service pump there is a on-off valve, a check valve and a tap for connection
to the priming circuit for suction lift installations. Moreover, if the service pump works with a closed
discharge line, a water recirculation tap has been applied to the pump body in order to prevent the
pump from overheating.
Discharge manifold connected to each service pump, fitted with a weld-on flange for connection to
the system.
Single base containing all the booster set components within a compact structure and ready for
installation.
To complete the pump station as requested by the standard, the GEN series of booster sets are fitted with the
following accessories :
Suction side kit.
Flow meter.
Alarm panel.
If diesel engine pump is installed, set of spare parts for diesel engines.
Priming tank with accessories (for suction lift installations).
24L diaphragm tanks.

Lowara
IDENTIFICA
TION CODES
IDENTIFICATION
GEN

1 / FHF 50-250/185 + SV209

CP
Options:
CP = Clean contacts in the panel.
IP55 = IP55 grade panels.
KV = Voltmeter kit.
Electric jockey pump description.
FHF : Electric service pump description.
SHF : Electric service pump description.
0 = Without jockey pump.
1 = With jockey pump.
1 = 1 Service pump.
2 = 2 Service pumps.
X = Automatic shut-off.

B = Basic version.
A = Version with periodic self-test function.
Electric service pump start-up
D = Direct start-up (Up to 22 kW included).
Y = Star/Delta start-up.
I = Impedance start-up.
GEN Fire-Fighting series.

GRU

REFERENCE ST
ANDARDS
STANDARDS
The Lowara fire-fighting booster sets are EC certified in conformity with the following directives:
- Machine Directive 98/37/EC.
- Low Voltage Directive 2006/95/CE.
- Electromagnetic Compatibility Directive 89/336/EEC and subsequent modifications.
The electric pump performance is declared to be in accordance with the following standard:
ISO 9906-A Rotodynamic pumps hydraulic performance tests and acceptation criteria.
The fire-fighting booster sets conform to the European fire-fighting Standard EN 12845-2009.
The automatic shut-off versions also conform to the UNI 10779 Italian Standard for hydrant systems.

Lowara
GEN SERIES OF BOOSTER SETS
FUNCTIONAL DIAGRAM FOR POSITIVE SUCTION HEAD INST
ALLA
TIONS
INSTALLA
ALLATIONS

GEN SERIES OF BOOSTER SETS


FUNCTIONAL DIAGRAM FOR SUCTION LIF
T INST
ALLA
TIONS
LIFT
INSTALLA
ALLATIONS

Lowara
GEN SERIES OF BOOSTER SETS
MECHANICAL CONFIGURA
TION
CONFIGURATION

DENOMINAZIONE COMPONENTI
GRUPPI DIESEL EN12845
REF.

1
2
3
4
5
6
7
8

DESCRIPTION

REF.

jockey pump discharge line


pump suction line
eccentric divergent
divergent on discharge line
recirculation circuit tap
electric service pump
on-off valve on discharge line
control panels

9
10
11
12
13
14
15
16

DESCRIPTION

service pump starter (2x)


diaphragm tanks
discharge manifold
pressure gauge
inspectable check valve
priming circuit tap
vacuum pressure gauge
on-off valve on suction line
gen21-comp-en_a_tp

Lowara
CHARACTERISTIC
S OF THE PUMPS USED IN THE GEN SERIES
CHARACTERISTICS
OF BOOSTER SETS
SV2, 4, 8 ELECTRIC PUMPS (JOCKEY PUMP)
Multistage centrifugal vertical electric pumps. All
metal parts in contact with pumped liquid are made
of stainless steel.
Version F: round flanges, in-line discharge and
suction ports, AISI 304 (Standard version).
Version N: round flanges, in-line discharge and
suction ports, AISI 316 (Available on request).
Reduced axial thrusts enable the use of off-the-shelf
standard motors
motors. The performance levels
of Lowara PLM surface motors lie within
what is usually referred to as efficiency
class 1.

Mechanical seal according to EN 12756 (ex DIN


24960) and ISO 3069.
Easy maintenance. No special tools required for
assembly or disassembly.
For other characteristics, consult the relative
dedicated technical catalogue.

FHF32, 40, 50, 65, 80, 100, 125 PUMP SERIES


Single impeller cast iron horizontal centrifugal pump and shaft made of AISI 316L stainless steel. End suction
and radial discharge ports.
Impeller: made of AISI 316L stainless steel laser technology welded, for sizes 32, 40, 50, 65-125, or cast iron for
sizes 65-160, 65-200, 65-250, 80, 100, 125.
Hydraulic sizes and nominal diameter DN of suction and discharge ports according to EN 733 (ex DIN 24255).
Flanges according to EN 1092-2 (ex UNI 2236) and DIN 2532.
Motor: motor/pump coupling with bracket, support, flexible coupling with spacer coupling and aligning and
anchoring base. The performance levels of Lowara PLM surface motors lie within what is
usually referred to as efficiency class 1.
Performance levels according to EN 60034-1.
Back pull out design, impeller, adaptor and motor can be extracted without disconnecting the pump body
from the pipes.
For other characteristics, consult the relative dedicated technical catalogue.

SHF32, 40, 50, 65, 80 PUMP SERIES


Single impeller horizontal centrifugal pump with pump body and shaft made of AISI 316L stainless steel. End
suction and radial discharge ports.
Closed impeller made of AISI 316L stainless steel laser technology welded (for sizes 25, 32, 40, 50, 65-160/75
and 65-160/110A) or AISI CF8M cast stainless steel.
Hydraulic sizes and nominal diameter DN of suction and discharge ports according to EN 733 (ex DIN 24255).
Flanges according to EN 1092-1 (ex UNI 2236) and DIN 2532.
Motor: motor/pump coupling with bracket, support, flexible coupling with spacer coupling and aligning and
anchoring base. The performance levels of Lowara PLM surface motors lie within what is
usually referred to as efficiency class 1.
Performance levels according to EN 60034-1.
Back pull out design, impeller, adaptor and motor can be extracted without disconnecting the pump body
from the pipes.
For other characteristics, consult the relative dedicated technical catalogue.

Lowara
MAIN COMPONENTS
FIRE-FIGHTING SETS WITH HORIZONT
AL ELECTRIC PUMPS
HORIZONTAL
On/off valves on the delivery side of each pump, ball valves with lever handle for diameters up to and including
1" 1/2 butterfly valve with lever handle from DN50 to DN100 diameter, butterfly valve with handwheel and
reduction manual gear for DN125 diameter and above. Device for monitoring ON/OFF status included. Electrical
connections by customer.
(Lockable kit available on request).
Recirculation device for each service pump.
The re-circulation device allows a minimum capacity in order to prevent the pump overheating when working
with closed delivery. It includes the activation pressure switch for the alarms of the pumps running, the test valve
for checking the seal of the check valves, the couplings for any connecting pipes to the priming tank in the case
of suction lift installation. The connection of each re-circulation to the suction tank or the priming tank is to be
seen to by the person installing the equipment.
Pressure gauge on the delivery side of each service pump between check valve and on/off valve.
Inspectable check valve on the discharge side of each pump. Threaded coupling for diameters up to 1"1/2
included, flanged coupling for larger sizes.
Painted iron delivery manifold (PN 16) and threaded stubs with relative caps for connecting any 24 litre
membrane tanks. Blind and welding zinc-plated flanges.
Two start-up pressure switches for every service pump.
For the electric service pumps, start-up takes place through the pressure switch, but it must be manually stopped
using the key-operated selector switch on the panel (excluding the version with automatic shut-off). For the
electric jockey pump, if present, both start-up and stopping are determined by the pressure switch.
Start-up pressure switch circuit for the service pump, including connecting pipes for the delivery manifold,
recirculation circuit.
This circuit includes on/off valve, a non-return valve, a discharge valve and various pipe fittings. The
configuration of the circuit allows the pressure switch to intervene also when the relative on/off valve is closed.
Various pipe fittings (copper, zinc-plated steel).
Base made of bent sheet or structural iron with epoxy powder painting RAL 5010.
Control panel frame made of structural iron with epoxy powder painting RAL 5010.
Electric panel for each electric service pump.
Starting: Direct (DOL) up to and including 22 kW, star/triangle from 30 kW up.
A panel mounting bracket kit for floor mounting and a jockey pump kit can be supplied on request.
The control panels for the electric pumps up to 55 kW power supply are fixed on bracket. For higher powers, the
control panels for electric pump service are floor mounted, instead the jockey electric pump panel is wall mounted
fixed.

10

Lowara
SUCTION KIT
The set is supplied with its suction side free from components.
On request, for the SUCTION side of the individual service pump, TWO versions are available according to the
systems installation type:

T KIT
POSITIVE SUCTION HEAD and SUCTION LIF
LIFT
Kit suitable for positive suction head or suction lift installation.
The suction side of the individual pump includes:
- Anti-vibration joint to attach to the pump inlet.
- Eccentric cone or flanged stub pipe.
- Vacuum pressure gauge.
- On/off butterfly valve with lever handle for diameters up to DN100, butterfly valve with handwheel and
reduction manual gear for DN125 and higher. Device for monitoring ON/OFF status included.
Electrical connections by customer.
(Valve lock kit available on request).
- Weld-on flange.
Conforming to the requirements of the EN 12845 Standard (chapter 10.5 and chapter 10.6).
These requirements are connected with the type of installation and the measurement of the piping sections.
(see tables on pages 124-127).
OTHER VERSIONS
As well as the basic GENDB versions (direct start-up), GENYB (star triangle start-up), GENIB (impedance start-up),
the following versions are also available:
GEN..A
With periodic self-test function.
There is a self-test circuit including a weekly clock on the electric panel of each electric service pump. For the time
and date pre-set, the pump is started up and kept functioning for 1 minute. During this interval the check circuit
checks that the pressure in the re-circulation circuit closes the pressure switch contact of the pump which is
running. In the case of irregularities, the relative auxiliary self-test alarm relay available for remote signalling is
activated and memorised.
The EN12845 Standard does not provide for the presence of a self-test circuit but asks for periodic checks to be
carried out by the user, hence the periodic self-test function cannot substitute the above checks.
GEN..X (For fire hydrant systems, UNI 10779)
With automatic shut-off.
There is an automatic shut-off circuit on the electric panel of each electric service pump.
In certain situations, it allows automatic shut-off once the system pressure has been kept at higher values than the
start-up values for at least twenty minutes.
The self-test and automatic shut-off versions are available for each type of GEND.., GENY.., GENI.. start-up and in
combination between them (See identification codes page).

11

Lowara
ACCES
SORIES A
VAILABLE ON REQUEST
ACCESSORIES
AV
Protection against dry running for the electric jockey pump in
one of the following versions:
- Float switch, in case of suction lift.
- Probes kit in case of suction lift (needs optional probe module
in the electric jockey pump).
- Minimum pressure switch, in case of positive suction head.
Electric panel for remote status and alarm monitoring of one or
two Lowara pumps installed in GEN fire-fighting booster sets,
according to EN12845.
In the electric service pump mode, the following conditions are
visualised: Motor powered, pump start-up request, pump
running, failure to start.
In the diesel engine service pump mode, the following
conditions are visualised: switch in non-automatic position,
QAL12845 Panel
diesel engine fails to start after 6 attempts, pump running,
controller failure.
Additionally: minimum suction tank or fuel level, minimum
priming tank level, on-off valve on suction and discharge side
not fully open.
All the above conditions, required by EN12845, are visualised
with signal LEDs and buzzers.
A buzzer alarm reset button and LED tester button are
included.
The control unit is also fitted out to signal the following
general alarms, if present:
- General alarm for incorrect electrical connection in the
exchange contacts of: flow meter circuit valve, discharge
pump, jockey pump status.
- Fault in electrical connection in the exchange contact relative
to panel 1 (electric pump/diesel engine pump).
Flow meter
- Fault in electrical connection in the exchange contact relative
to panel 2 (electric pump/diesel engine pump).
- Jockey pump overload; - Jockey pump running; - Discharge pump overload;
- Battery low; - No communication with ModBus system.
All the above conditions are visualised with signal LEDs and on the display. The customer may decide to enable
the buzzer. Further information available on page 144.
Circuit for test flow of the service pumps. Includes the direct reading flow meter (sized according to the capacity
of the service pump) according to the type of flow meter, connecting piping and straight piping upline from the
instrument, on/off ball valve for diameters up to and including 2 butterfly valve with lever handle from DN65 to
DN100 diameter, butterfly valve with handwheel and reduction manual gear for DN125 diameter and above.
ON/OFF status monitoring included.
New model of flow meter (P6) for diameters up to and including DN80.
Diaphragm tank with relative ball valve, in the same number as that of the pumps present, for dampening any
pressure oscillations in the system. 24 litre model with maximum pressure 8.10 or 16 bar according to the
maximum head of the pumps.
Priming tank for each service pump, in the case of suction lift installation.
Accessories for the priming tank suck as float switch tap, level indicator, valves, automatic air discharger on each
service pump, in the case of suction lift installation.

All the main characteristics of the priming tanks, the flow meters and the available membrane tanks are shown in
the accessories section.

12

Lowara
SPECIAL EQUIPMENT ON REQUEST
(Contact the Sales and technical Assistance Service)
Sets for pumping sea water with electric pumps, valves, manifold and AISI 316 piping or compatible alloys.
Non-standard supply power sets.
Sets with separate electric jockey pump supplied as a kit.
Sets with different electric jockey pump from the standard one.
Sets installed inside prefabricated boxes for outdoor use.
Notes
The set is supplied without a suction manifold in accordance with the EN12845 Standard (points 10.6.2.2 and
10.6.2.3) which provides for independent suction for each pump.
Please see the EN12845 Standard on fixed systems and fire extinguishing Automatic sprinkler systems Design,
installation and maintenance?- for sizing the suction piping, define whether the installation is to be considered
suction lift or positive suction head for the use limits.
The Standard ask that, whenever possible, the pumps are installed with positive suction head, otherwise priming
tanks must be provided with suitable automatic devices for signalling and reintegration.
The EN12845 Standard states that the water pressure should not exceed 12 bar (point 8.2.1). In some applications
it is possible to have pressures of over 12 bar (point 8.2.2).
In this case, pump sets with higher pressures than those within the regulatory limit are used.
The catalogue also shows booster sets with pump closing head up to 150 metres suitable for such installations.

13

Lowara
SPECIAL EQUIPMENT ON REQUEST

14

Lowara
COMMAND P
ANEL FOR THE ELECTRIC SERVICE PUMP
PANEL
Painted metal casing (IP 54) complete with:
General door-locking switch.
Analogical ammeter.
MAN AUT 0 selector with extractable key only in
automatic position.
Keyboard for indicating electric voltage presence,
correct phase sequence (three phase power supply),
start-up request, pump functioning and no start-up,
through LED lamps, lamp test button and starting and
stopping buttons, according to the provisions of
EN12845 paragraph 10.8.6.
Inside:
12/24V transformer for auxiliary circuits and electronic
board.
Fuse holder and fuses for power and auxiliary circuits.
Line contact maker (direct start-up up to 22 kW
included), line and star/triangle contact makers (startriangle start-up), line contact makers and reactance
switching (impedance start-up).
Star/triangle exchanger timer or reactance switching.
Relay for signalling no phase.
Auxiliary relays.
Current transformer.
Terminal boards.
Clean contacts (max. 24V, 1A) for activating acoustic/
visual alarms for no phase, pump on demand, pump
running and start failure.
Cable glands (excluding the versions to be fixed to the
floor).
Wiring diagram.
On request digital trasmission card via RS485 serial by
ModBus comunication protocol.

15

Electric service pump panel

Lowara
COMMAND P
ANEL FOR THE ELECTRIC JOCKEY PUMP
PANEL
Painted metal casing (IP 55) complete with:
General door-locking switch.
Visual indicators for line, running, thermal shutdown.
Manual automatic selector excluded.
Inside:
Transformer for 24V auxiliary circuits.
Fuse holder and fuses for power and auxiliary circuits.
Line contact maker.
Overload cut-out switch.
Pump shut-off timer (0 90 s).
Terminal boards.
Cable glands.
Wiring diagram.
Suitable for connecting to a float switch or a minimum
pressure switch for preventing dry running. An optional
level control module (supplied on request) allows the
connection of probes with the possibility of regulating the
sensitivity according to the hardness of the water.

Electric jockey pump panel

OPTIONS A
VAILABLE ON REQUEST
AV
CP alternative
Series of clean contacts for checking the status of the electric service pump panel, as well as the contacts already
provided for signalling alarms:
No phase
Motor running
Selector position MAN-AUT-0
No start-up
Start-up request
Series of clean contacts for checking the status of the electric jockey pump:
Pump running
Thermal shutdown (overload)
No water
KV alternative
Control panel for the electric service pump with analogical voltmeter and with phase switch.
IP55 alternative
Electric service pump panel with extra IP55 protection.

The set is supplied already assembled, calibrated and factory tested. The set is supplied
complete with an instruction manual, pump manuals and wiring diagrams for the panels.
For the sets including floor panels, the electric panels are sent together with the set in a separate pack and
supplied with 5-metre long connecting cables (longer lengths available on request). The fitter is responsible for
preparing the routes and installing the cables.

16

Lowara
COMMAND P
ANEL DIMENSIONS
PANEL
SERVICE PUMP P
ANEL
PANEL

POWER (kW)

PROTECTION

CLASS
from 0,7 to 7,5

IP54

350

160

500

from 9,2 to 22

IP54

400

200

600

from 30 to 37

IP54

500

200

700

from 45 to 55

IP54

600

250

800

from 75 to 90

IP54

600

300

1500

from 110 to 160

IP54

800

400

1700

IP55: same dimensions as standard panels IP54

qe-serv-en_d_td

Power over 55 kW: floor cupboard

JOCKEY PUMP P
ANEL
PANEL

PROTECTION
CLASS

IP54

250

160

IP55: same dimensions as standard panels IP54

* The control panels are included in the supply.

17

H
300
qe-pil-en_b_td

Lowara
GEN SERIES OF BOOSTER SETS
CHOICE AND SELECTION
Criteria for choosing fire-fighting sets
The correct choice of a fire-fighting set must consider various factors, including the correct sizing of the performance
levels required for the system, local regulations and legislation, and especially the installation conditions relative to
the installation site and whether a suction lift or a positive suction head is involved.
Choosing the type of water supply
The type of water supply and, therefore, the type of booster set to select depends on the type of system involved and
is chosen according to the risk analysis performed by the designer.
There is no written rule for identifying the correct number of pumps to install.
GEN booster sets are normally designed so that every service pump can satisfy the following requirements:
100% of rated capacity with one or two pumps installed (one in service and the other in reserve).
If three pumps are installed, the capacity of the pump will be 50% of the total rated capacity and the third service
pump will be considered as a reserve. In these cases, when superior or duplicated water supplies are involved, only
one pump must be driven by an electric motor. This type of configuration is available on request.
Suction conditions of the booster set
The type of installation, suction lift or positive suction head, tends to affect (negatively or positively) the hydraulic
performance of the pump. Remembering that EN12845 recommends against using suction lift installations, the
following condition given by EN12845 must be satisfied in order to use the pump curve correctly:
NPSHd NPSHr +1 [m]
Where: NPSHd is defined available.
NPSHr is defined requested from the pump.
As the suction check condition must be made at the max. requested flow, there can be different performance levels
always respecting the NPSHd condition.
To select the booster set, consult the dedicated sections. Choice and selection. Hydraulic performance levels. Suction
lift or positive suction head installation.
Performance levels of booster sets: using the tables
The tables showing the hydraulic performance levels of booster sets indicate the flow values according to the risk
class for precalculated systems followed by the respective pressure value. This value does not refer to pump performance
but is net of the pressure drop on the pump discharge line, to the discharge manifold flange.
This field is shown in grey and the selection must be made here, where performance levels comply with the reference
standard which considers the following conditions:
Maximum water speed in the service pump discharge piping 6 m/sec.
NPSHd NPSHr + 1 at the maximum flow required.
Max. difference in level of water considered 3,2 m (for positive suction head).
Suction pressure drops due to valves, piping, suction kit 1,5 m (limit value).
The reference suction conditions are the severest and most extreme that can occur.
The values taken in the fields that are not in grey indicate booster set performance levels in areas outside the limits of
the standard and must not be used to choose the set.

18

Lowara
GEN SERIES OF BOOSTER SETS
CHOICE AND SELECTION
Method of selecting a fire-fighting booster set
Referring to EN 12845, after identifying the risk classes of the activity to protect and performing the precalculation
method, the flow and head values required for the fire-fighting system can be obtained.
This data is used as follows:
1. Configuration of the booster set, choice of the number of service pumps and relative type of motor/engine
(two pumps, one electric and the other driven by a diesel engine).
2. Installation conditions (e.g.. positive suction head), see performance levels for positive suction head installation.
3. Determination of service flow e.g.: 1100 l/min risk class OH3.
TABELLA DI PRESTAZIONI IDRAULICHE NETTE GRUPPI EN12845 SERIE FHF50 2 poli 50 Hz 1 POMPA DI SERVIZIO, INST SOPRAB

RATED

FHF..

POWER

ELECTRIC

PUMP

PUMP

OH3n

TYPE

OH2n

RISK CLASS

Q = DELIVERY
l/min 0

600

700

m3/h 0

36

42

725

850

1000

1100

1200

1300

1350

1400

1500

1600

44

51

60

66

72

78

81

84

90

96

H = TOTAL HEAD METRES COLUMN OF WATER

kW

11,8

3,7

15,8

8,0

4. Determining
the
head e.g.:
35GRUPPI
m. EN12845 SERIE20,2
TABELLA
DI PRESTAZIONI
IDRAULICHE
NETTE
FHF50 2 poli 50 Hz 1 13,1
POMPA DI SERVIZIO, INST SOPRAB
27,3

18,2

34,8

FHF..

POWER

ELECTRIC

PUMP

PUMP

42,8

31,2

49,9

38,6

OH3n

RATED

OH2n

TYPE

RISK 26,5
CLASS

60,4
69,5

48,8

Q = DELIVERY

58,8

l/min 0

600

700

725

850

1000

1100

1200

1300

1350

1400

1500

1600

m3/h 0

36

42

44

51

60

66

72

78

81

84

90

96

79,0

68,1

H = TOTAL HEAD METRES COLUMN OF WATER

kW

50-125/22

50-125/D119

1 x 2,2

16,8

13,7

12,3

11,8

9,5

6,2

3,7

0,9

50-125/30

50-125/D130

1x3

19,9

17,5

16,1

15,8

13,6

10,5

8,0

5,3

2,3

50-125/40

50-125/D139

1x4

24,3

21,8

20,6

20,2

18,3

15,3

13,1

10,5

7,7

6,2

4,6

50-160/55

50-160/D158

1 x 5,5

31,8

29,3

27,7

27,3

24,8

21,1

18,2

15,0

11,4

9,5

7,6

50-160/75

50-160/D174

1 x 7,5

39,8

36,6

35,2

34,8

32,5

29,1

26,5

23,5

20,2

18,5

16,7

50-200/110A 50-200/D197

1 x 11

50,6

45,6

43,4

42,8

39,5

34,8

31,2

27,3

23,1

20,9

18,6

50-200/110

1 x 11

58,0

52,6

50,5

49,9

46,7

42,1

38,6

34,7

30,4

28,1

25,7

50-200/D209

60,4

48,8

69,5

58,8

12,7
20,7

As can be seen, the required flow value enters the operating


area in accordance
with the standard, and the value of
79,0
68,1
the corresponding head enters the field in grey.
From the example shown above, we can identify the booster set that satisfies the request. The model is pump
50-200/110 providing a head of 38,6 m.

19

Lowara
GEN SERIES OF BOOSTER SETS
CHOICE AND SELECTION - POSITIVE SUCTION HEAD INST
ALLA
TION
INSTALLA
ALLATION
EN12845 recommends always installing pumps in suction lift conditions, where possible If this is not possible, the
pumps can be installed in positive suction head conditions according to the following rules:
The height of the minimum water level at the pump axis must not be greater than 3,2 m.
A foot valve must be installed in the lowest point of the suction piping.
If more than one pump is installed, the suction piping must not be interconnected.

Liv. normale
Normal
level

Max 3,2 m

Liv.level
Min XX
Min.

Fig. 1 positive suction head installation diagram


In accordance with EN 12845 (10.6.2.1), the suction piping, including all the valves and unions, must be designed to
ensure that the NPSH available at the pump inlet exceeds the required NPSH by at least 1 m at the maximum required
flow rate.
NPSHd NPSHr + 1
When selecting the type of pump to use for the boosters sets, the installation conditions must be considered as these
determine different pump performance levels.
An example of how to choose and check of the installation conditions is shown below:
considering the precalculation method, a suitable risk class for the system is identified, e.g.: OH3. For this risk class,
the rated flow is 1100 l/min (Qn), while the maximum requested flow is 1350 l/min (Qm). Being in a positive suction
head condition, the most difficult situation is considered, i.e.: the maximum difference in water level of 3,2 m, as
indicated in the standard.
Being aware of the rated flow 1100 l/min and the pressure required for the system (e.g.: 35 m), the pump is
selected according to the tables on page 44-45, making sure the performance rating lies inside the area shown in
grey. The pump that satisfies the required work point is FHF50-200/110.

20

Lowara
GEN SERIES OF BOOSTER SETS
CHOICE AND SELECTION - POSITIVE SUCTION HEAD INST
ALLA
TION
INSTALLA
ALLATION
At this point, the installation conditions (positive suction head) must be checked at the maximum required
flow.
flow
The following values are replaced in the known relation, NPSHd NPSHr + 1:
NPSHr can be deduced from the table on page 45 which in this case is 4,6 m at the maximum requested flow.
After replacing the value, the following will be true (water temperature around 15C):
NPSHd = 10,33 + (-3,2) - Hct
Where
10,33 atmospheric pressure
3,2 geodetic difference in level
Hct suction pressure drop ((valves, pipes, elbows..)
The value of Hct considers the pressure drops of the suction kit, inclusive of vibration-proof joint, reduction cone
and on-off valve (Hc), as well as the pressure drops relative to all the suction piping, foot valve, elbows, elbows,
etc...
The value of Hc at the maximum required flow of the selected pump can be found in the diagram on page 81.
This value is 0,16 m.
After entering it in the formula, we will have:
Hct = 0,16 + X
Where X is the pressure drop relative to all the suction piping
Hence
NPSHd NPSHr + 1. After replacing this, we will have:
10,33 + (-3,2) - Hct = 4,6 +1
10,33 + (-3,2) 0,16 - X = 4,6 +1 which gives
X = 1,37 m
Maximum value of total drops to consider on the inlet piping in order to respect the conditions of the standard.
Of course, this case was deliberately put in the worst suction conditions. The designer must check and set the
values in an attempt to optimise suction conditions.

21

Lowara
GEN SERIES OF BOOSTER SETS
CHOICE AND SELECTION - POSITIVE SUCTION HEAD INST
ALLA
TION
INSTALLA
ALLATION
Checking performance of the set at rated flow
flow..
The performance of the booster set must now be checked in the installation conditions of the example used up
until now.
Work point: Qn: 1100 l/min H = 35 m
The selected pump is FHF50-200/110
Starting from the usual relation given by the standard, we will have:
NPSHd NPSHr + 1
NPSHd = 10,33 + (-3,2) - Hct
NPSHr can be deduced from the table on page 45 which in this case is 2,9 m at the rated flow.
The value of Hct considers the pressure drops of the suction kit, inclusive of vibration-proof joint, reduction cone
and on-off valve (Hc), as well as the pressure drops relative to all the suction piping, foot valve, elbows, elbows,
etc...
The value of Hc at the rated required flow of the selected pump can be found in the diagram on page 81. This
value is 0,12 m.
After entering it in the formula, we will have:
Hct = 0,12 + X
Where X is the pressure drop relative to all the suction piping
Hence
NPSHd NPSHr + 1. After replacing this, we will have:
10,33 + (-3,2) - Hct = 2,9 +1
10,33 + (-3,2) 0,12 - X = 2,9 +1 which gives
X = 3,11 m
Value of the total drops to consider on the suction piping
Taking the pressure value of the selected set, the value corresponds to 38,6 m at the rated flow.
Therefore, the verification of the pressure values in the above suction conditions becomes:
H = 38,6 -0,12 -3,11 = 35,4 m > 35 m which is the pressure required for the system
The result satisfies the performance required for the system in the installation conditions of the example.

22

Lowara
GEN SERIES OF BOOSTER SETS
CHOICE AND SELECTION - SUCTION LIF
T INST
ALLA
TION
LIFT
INSTALLA
ALLATION
Suction lift installation
EN12845 recommends always installing pumps in suction lift conditions, where possible, according to the following
rules:
At least two thirds of the effective capacity of the suction tank must be above the level of the pump axis.
The pump axis must not be more than 2 m above the minimum water level in the suction tank.

Normal
level
Liv.
normale

2/3
2/3 della
of
capacit
effective
effettiva
capacity

Max 2 m
Min. Min
levelXX
Liv.

Fig. 2 suction lift installation diagram


In accordance with EN 12845 (10.6.2.1), the suction piping, including all the valves and unions, must be designed to
ensure that the NPSH available at the pump inlet exceeds the required NPSH by at least 1 m at the maximum required
flow rate.
NPSHd NPSHr + 1
When selecting the type of pump to use for the boosters sets, the installation conditions must be considered as these
determine different pump performance levels.
An example of how to choose and check of the installation conditions is shown below:
considering the precalculation method, a suitable risk class for the system is identified, e.g.: OH3. For this risk class,
the rated flow is 1100 l/min (Qn), while the maximum requested flow is 1350 l/min (Qm). Being in the suction lift
condition, a neutral situation is used in order to consider the water level on the same horizontal plane as the pump,
without benefiting from any positive suction head.

23

Lowara
GEN SERIES OF BOOSTER SETS
CHOICE AND SELECTION - SUCTION LIF
T INST
ALLA
TION
LIFT
INSTALLA
ALLATION
Being aware of the rated flow 1100 l/min and the pressure required for the system (e.g.: 35 m), the pump is selected
according to the tables on page 44-45, making sure the performance rating lies inside the area shown in grey.
The pump that satisfies the required work point is FHF50-200/110.
At this point, the installation conditions (suction lift) must be checked at the maximum required flow.
The following values are replaced in the known relation, NPSHd NPSHr + 1:
NPSHr can be deduced from the table on page 45 which in this case is 4,6 m at the maximum requested flow.
After replacing the value, the following will be true (water temperature around 15C):
NPSHd = 10,33 + (0) - Hct
Where
10,33 atmospheric pressure
0 geodetic difference in level
Hct suction pressure drop (valves, pipes, elbows...)
The value of Hct considers the pressure drops of the suction kit, inclusive of vibration-proof joint, reduction cone
and on-off valve (Hc), as well as the pressure drops relative to all the suction piping, foot valve, elbows, elbows, etc
The value of Hc at the maximum required flow of the selected pump can be found in the diagram on page 87.
This value is 0,32 m.
After entering it in the formula, we will have:
Hct = 0,32 + X
Where X is the pressure drop relative to all the suction piping
Hence
NPSHd NPSHr + 1. After replacing this, we will have:
10,33 + (0) - Hct = 4,6 +1
10,33 + (0) 0,32 - X = 4,6 +1 which gives
X = 4,41 m
Maximum value of total drops to consider on the inlet piping in order to respect the conditions of the standard.
Of course, the case in point was deliberately tested in neutral suction conditions that neither benefit nor optimise
suction.
The designer must check and set the values in an attempt to make suction conditions as efficient as possible.

24

Lowara
GEN SERIES OF BOOSTER SETS
CHOICE AND SELECTION - SUCTION LIF
T INST
ALLA
TION
LIFT
INSTALLA
ALLATION
Checking performance of the selected set at rated flow
flow..
The performance of the booster set must now be checked in the installation conditions of the example used up until
now.
Work point: Qn 1100 l/min H = 35 m
The selected pump is FHF50-200/110
Starting from the usual relation given by the standard, we will have:
NPSHd NPSHr + 1
NPSHd = 10,33 + (0) - Hct
NPSHr can be deduced from the table on page 45 which in this case is 2,9 m at the rated flow
flow.
The value of Hct considers the pressure drops of the suction kit, inclusive of vibration-proof joint, reduction cone
and on-off valve (Hc), as well as the pressure drops relative to all the suction piping, foot valve, elbows, elbows, etc...
The value of Hc at the rated required flow of the selected pump can be found in the diagram on page 87. This value
is 0,22 m.
After entering it in the formula, we will have:
Hct = 0,22 + X
Where X is the pressure drop relative to all the suction piping
Hence
NPSHd NPSHr + 1. After replacing this, we will have:
10,33 + (0) - Hct = 2,9 +1
10,33 + (0) 0,22 - X = 2,9 +1 which gives
X = 6,21 m
Value of the total drops to consider on the suction piping
Taking the pressure value of the selected set, the value corresponds to 38,6 m at the rated flow.
Therefore, the verification of the pressure values in the above suction conditions becomes:
H = 38,6 -0,22 -6,21 = 32,17 m < 35 m which is the pressure required for the system.
The value obtained, doesnt satisfy the performance necessary for the system, but as is evident, we have used deliberately
a neutral installation condition that it doesnt give benefits to the suction. It results that installed the pump with
positive suction of 3 m, we will have a pressure value of 35,17 m that it satisfied the relation.

25

Lowara

26

Lowara

GEN../FHF Series
Fire-fighting booster sets EN 12845
Horizontal Centrifugal electric pumps FHF series
equipped with high efficiency PLM motors
50 Hz

27

Lowara

28

Lowara
RANGE
GEN../FHF RANGE
The range of EN 12845 series fire-fighting booster sets includes
models with 1 or 2 electric service pumps and some with jockey
pumps for adapting to the specific requirements of each application.

GEN10 SERIES

Fire-fighting sets with a centrifugal


service pump horizontal axis and
body made of cast iron in the
FHF series.

Head up to 100 m.
Flow up to 650 m3/h.

GEN11 SERIES

Fire-fighting sets with a centrifugal


service pump horizontal axis and
body made of cast iron in the
FHF series and jockey pump.

Head up to 100 m.
Flow up to 650 m3/h.

GEN20 SERIES

Fire-fighting sets with two


centrifugal service pump horizontal
axis and body made of cast iron in
the FHF series.

Head up to 100 m.
Flow up to 1300 m3/h.

GEN21 SERIES

Fire-fighting sets with two


centrifugal service pump horizontal
axis and body made of cast iron in
the FHF series and jockey pump.

29

Head up to 100 m.
Flow up to 1300 m3/h.

Lowara
GEN../FHF BOOSTER SETS SERIES
TABELLA DI PRESTAZIONI IDRAULICHE POMPE PILOTA SV2-4 PER GRUPPI EN12845
HYDRA
ULIC PERFORMANCE T
ABLE A
T 50 Hz (JOCKEY PUMP)
HYDRAULIC
TABLE
AT
PUMP

NOMINAL

TYPE

POWER

Q = DELIVERY
l/min 0

20

30

40

50

60

70

100

120

133

m3/h 0

1,2

1,8

2,4

3,6

4,2

7,2

37,0

26,0

18,0

H = TOTAL HEAD METRES COLUMN OF WATER

kW

HP

SV2 04

0,55

0,75

42,5

37,5

34,0

30,5

26,0

20,5

SV2 06

0,75

64,0

56,0

51,0

45,5

38,5

31,0

22,0

SV2 09

1,1

1,5

96,0

84,0

76,5

68,5

58,0

46,5

32,5

SV2 12

1,5

128,0

112,0

102,0

91,0

77,0

62,0

44,0

SV2 14

2,2

150,0

131,0

119,0

106,0

90,0

73,0

52,0

SV2 15

2,2

160,2

140,3

128,2

114,0

97,4

78,2

55,9

SV4 07

1,1

1,5

70,0

59,5

56,0

53,0

51,0

SV4 09

1,5

90,0

76,5

73,0

68,5

65,5

47,0

33,5

23,0

SV4 13

2,2

131,0

111,0

105,0

99,0

95,0

68,0

48,0

34,0

15,0

Performance in accordance with the ISO 9906 - Annex A Standard.

EN12845_pp_sv2-4-2p50-en_b_th

TABELLA PRESTAZIONI IDRAULICHE POMPE PILOTA SV8 PER GRUPPI EN12845 2 p


PUMP

NOMINAL

TYPE

POWER

Q = DELIVERY
l/min 0
3

m /h 0
kW

100

120

133

150

167

200

233

7,2

10

12

14

33

H = TOTAL HEAD METRES COLUMN OF WATER

HP

SV8 05

2,2

68

62

60

57,5

55

51

43

SV8 06

82

74,5

71

69

66

61,5

52

40

SV8 07

5,5

95,9

87

88

80

76

71

60

46,2

SV8 09

5,5

123

112

107

104

97,5

92

78

60

Performance in accordance with the ISO 9906 - Annex A Standard.

EN12845_pp_sv8-2p50-en_a_th

30

Lowara
GEN../FHF 32-80 BOOSTER SETS SERIES
TABELLA ABBINAMENTI POMPA SERVIZIO FH32-80 - POMPA PILOTA GRUPPI GEN 1
SERVICE PUMP JOCKEY PUMP COMBINA
TIONS
COMBINATIONS
SERVICE PUMP

JOCKEY PUMP

PUMP

32-125/07
32-125/11
32-160/15
32-160/22
32-200/30
32-200/40
40-125/11
40-125/15
40-125/22
40-160/30
40-160/40
40-200/55
40-200/75
40-250/110A
40-250/110
40-250/150
50-125/22
50-125/30
50-125/40
50-160/55
50-160/75
50-200/110A
50-200/110
50-250/150
50-250/185
50-250/220
65-125/40
65-125/55
65-125/75
65-160/110A
65-160/110
65-160/150
65-200/150
65-200/185
65-200/220
65-250/220
65-250/300
65-250/370
80-160/150
80-160/185
80-200/220
80-200/300
80-250/370
80-250/450
80-250/550

SV8 09

SV8 07

SV8 06

SV8 05

SV4 13

SV4 09

SV4 07

SV2 15

SV2 14

SV2 12

SV2 09

FHF..
ELECTRIC

SV2 06

SV2 04

TYPE

PUMP

32-125/D119
32-125/D136
32-160/D150
32-160/D164
32-200/D188
32-200/D204
40-125/D112
40-125/D122
40-125/D143
40-160/D159
40-160/D171
40-200/D190
40-200/D209
40-250/D218
40-250/D233
40-250/D251
50-125/D119
50-125/D130
50-125/D139
50-160/D158
50-160/D174
50-200/D197
50-200/D209
50-250/D224
50-250/D237
50-250/D250
65-125/D121
65-125/D129
65-125/D140
65-160/D161
65-160/D168
65-160/D178
65-200/D187
65-200/D198
65-200/D210
65-250/D220
65-250/D241
65-250/D258
80-160/D163
80-160/D173
80-200/D189
80-200/D207
80-250/D225
80-250/D238
80-250/D256

12845-FHF32-80_ap-en_a_tc

31

Lowara
GEN../FHF 100-125 BOOSTER SETS SERIES
TABELLA ABBINAMENTI POMPA SERVIZIO FH100-125 - POMPA PILOTA GRUPPI GE
SERVICE PUMP JOCKEY PUMP COMBINA
TIONS
COMBINATIONS
SERVICE PUMP

JOCKEY PUMP

PUMP

100-160/185
100-160/220
100-160/300
100-200/185
100-200/300
100-200/370
100-200/450
100-250/300
100-250/450
100-250/550
100-250/750
100-250/900
125-200/300
125-200/450
125-200/550
125-270/750
125-270/900
125-270/1100
125-270/1320

SV8 09

SV8 07

SV8 06

SV8 05

SV4 13

SV4 09

SV4 07

SV2 15

SV2 14

SV2 12

SV2 09

FHF..
ELECTRIC

SV2 06

SV2 04

TYPE

PUMP

100-160/D150
100-160/D165
100-160/D185
100-200/D168
100-200/D192
100-200/D203
100-200/D213
100-250/D200
100-250/D221
100-250/D235
100-250/D254
100-250/D267
125-200/D180
125-200/D206
125-200/D216
125-270/D224
125-270/D237
125-270/D253
125-270/D266

12845-FHF100-125_ap-en_a_tc

32

Lowara
HYDRA
ULIC PERFORMANCE T
ABLE A
T 50 HZ (POSITIVE SUCTION HEAD)
HYDRAULIC
TABLE
AT
TABELLA DI PRESTAZIONI IDRAULICHE NETTE GRUPPO EN12845 SERIE FHF32 2 poli 50 Hz, 1 POMPA DI SERVIZIO, ASP ESCLUSA INS SOPRA
GEN../FHF 32 BOOSTER SETS SERIES
TYPE

RATED

FHF..

POWER

ELECTRIC

PUMP

PUMP

LHn

RISK CLASS

Q = DELIVERY
l/min 0

100

150

200

225

250

275

300

375

400

425

450

500

m3/h 0

12

14

15

17

18

23

24

26

27

30

H = TOTAL HEAD METRES COLUMN OF WATER

kW

32-125/07

32-125/D119

1 x 0,75

16,9

15,6

14,1

12,1

10,9

9,6

8,1

6,6

32-125/11

32-125/D136

1 x 1,1

21,9

20,5

19,1

17,2

16,1

14,9

13,5

12,1

7,1

5,2

32-160/15

32-160/D150

1 x 1,5

27,3

25,6

24,0

21,8

20,5

19,0

17,4

15,6

9,5

7,2

32-160/22

32-160/D164

1 x 2,2

34,7

33,1

31,5

29,3

27,9

26,5

24,9

23,2

17,3

15,0

12,7

10,2

32-200/30

32-200/D188

1x3

44,2

41,3

39,3

36,8

35,3

33,7

32,0

30,1

23,4

20,8

18,0

15,0

32-200/40

32-200/D204

1x4

54,4

51,7

49,5

46,8

45,2

43,5

41,7

39,7

33,2

30,8

28,2

25,6

20,0

Performance levels relative to set with 1 service pump running and compliant with ISO 9906 - Annex A.
12845_1pg-sp-fhf32-2p50-en_a_th
LHn = class of risk value referred to the required rated capacity (Tab.6 para 7.3.1 EN12845)
Inlet pressure drops must be deducted. Make sure that these drops, added to the difference in level (max. 3.2m), are less than 4.5m
The values shown identify performance levels according to the reference standard EN12845.

HYDRA
ULIC PERFORMANCE T
ABLE A
T 50 HZ (SUCTION LIF
T)
HYDRAULIC
TABLE
AT
LIFT)
TABELLA DI PRESTAZIONI IDRAULICHE NETTE GRUPPO EN12845 SERIE FHF32 2 poli 50 Hz, 1 POMPA DI SERVIZIO, ASP ESCLUSA INS SOTTO
GEN../FHF 32 BOOSTER SETS SERIES
TYPE

RATED

FHF..

POWER

ELECTRIC

PUMP

PUMP

LHn

RISK CLASS

Q = DELIVERY
l/min 0

100

150

200

225

250

275

300

375

400

425

450

500

m3/h 0

12

14

15

17

18

23

24

26

27

30

H = TOTAL HEAD METRES COLUMN OF WATER

kW

32-125/07

32-125/D119

1 x 0,75

16,9

15,6

14,1

12,1

10,9

9,6

8,1

6,6

32-125/11

32-125/D136

1 x 1,1

21,9

20,5

19,1

17,2

16,1

14,9

13,5

12,1

7,1

5,2

32-160/15

32-160/D150

1 x 1,5

27,3

25,6

24,0

21,8

20,5

19,0

17,4

15,6

9,5

7,2

32-160/22

32-160/D164

1 x 2,2

34,7

33,1

31,5

29,3

27,9

26,5

24,9

23,2

17,3

15,0

12,7

10,2

32-200/30

32-200/D188

1x3

44,2

41,3

39,3

36,8

35,3

33,7

32,0

30,1

23,4

20,8

18,0

15,0

32-200/40

32-200/D204

1x4

54,4

51,7

49,5

46,8

45,2

43,5

41,7

39,7

33,2

30,8

28,2

25,6

Performance levels relative to set with 1 service pump running and compliant with ISO 9906 - Annex A.
LHn = class of risk value referred to the required rated capacity (Tab.6 para 7.3.1 EN12845)
Inlet pressure drops must be deducted. Make sure these drops are less than 4.5m
The values shown identify performance levels according to the reference standard EN12845.

20,0

12845_1pg-st-fhf32-2p50-en_a_th

TABELLA DI PRESTAZIONI IDRAULICHE NPSHr GRUPPI EN12845 SERIE FHF32 2 poli 50 Hz

NPSH REQUIRED FOR PUMP SERIES FHF 32


TYPE

RATED

FHF..

POWER

ELECTRIC

PUMP

PUMP

LHn
LH

RISK CLASS

Q = DELIVERY
l/min 0

100

150

200

225

250

275

300

350

375

400

450

500

3
m /h 0

12

14

15

17

18

21

23

24

27

30

NPSHr [METRES COLUMN OF WATER]

kW

32-125/07

32-125/D119

1 x 0,75

1,6

1,6

1,7

1,8

2,0

2,2

32-125/11

32-125/D136

1 x 1,1

1,6

1,6

1,7

1,8

2,0

2,2

2,9

3,4

4,0

32-160/15

32-160/D150

1 x 1,5

2,2

2,4

2,5

2,7

2,8

3,0

3,6

3,9

4,4

32-160/22

32-160/D164

1 x 2,2

2,2

2,4

2,5

2,7

2,8

3,0

3,6

3,9

4,4

5,9

32-200/30

32-200/D188

1x3

2,7

2,9

3,1

3,3

3,5

3,8

4,3

4,6

4,9

5,5

32-200/40

32-200/D204

1x4

2,7

2,9

3,1

3,3

3,5

3,8

4,3

4,6

4,9

5,5

The declared NPSH values were obtained in the laboratory and refer to a single service pump
LHn = class of risk value referred to the required rated capacity (Tab.6 para 7.3.1 EN12845)
Check that NPSHd NPSHr+1m is satisfied

33

6,2

12845_1p-fhf32-2p50_NPSHr-en_a_th

Lowara
HYDRA
ULIC PERFORMANCE
T
ABLE
T 50
SUCTION
HEAD)
HYDRAULIC
TABLE
AT
TABELLA DI PRESTAZIONI
IDRAULICHE NETTE GRUPPI EN12845
SERIEA
FHF40
2 poliHZ
50 Hz(POSITIVE
1 POMPA DI SERVIZIO,
ASP ESCLUSA INST
SOPRAB
GEN../FHF 40 BOOSTER SETS SERIES
TYPE

RATED

FHF..

POWER

ELECTRIC

PUMP

PUMP

OH1n

RISK CLASS

Q = DELIVERY
l/min 0

300

350

375

540

600

700

725

750

800

900

1000

1100

m3/h 0

18

21

23

32

36

42

44

45

48

54

60

66

H = TOTAL HEAD METRES COLUMN OF WATER

kW

40-125/11

40-125/D112

1 x 1,1

13,9

11,3

10,0

9,3

3,4

40-125/15

40-125/D122

1 x 1,5

18,0

15,3

14,0

13,3

7,4

0,7
4,7

40-125/22

40-125/D143

1 x 2,2

25,3

21,8

20,5

19,8

14,0

11,4

6,4

5,0

3,6

40-160/30

40-160/D159

1x3

31,6

28,1

26,8

26,0

19,5

16,5

10,8

9,2

7,6

40-160/40

40-160/D171

1x4

38,3

35,1

33,7

32,9

26,5

23,6

18,1

16,5

15,0

0,6
11,7

40-200/55

40-200/D190

1 x 5,5

46,4

42,7

41,2

40,4

33,1

29,7

23,3

21,5

19,6

40-200/75

40-200/D209

1 x 7,5

57,5

53,1

51,6

50,7

43,8

40,7

34,8

33,2

31,5

28,0

40-250/110A 40-250/D218

1 x 11

63,6

57,8

56,2

55,2

47,8

44,5

38,2

36,5

34,8

31,1

40-250/110

40-250/D233

1 x 11

71,7

66,0

64,3

63,4

55,7

52,3

45,8

44,0

42,1

38,3

40-250/150

40-250/D251

1 x 15

85,0

78,6

76,9

76,0

68,4

65,0

58,6

56,8

55,0

51,1

42,6

Performance levels relative to set with 1 service pump running and compliant with ISO 9906 - Annex A.
12845_1pg-sp-fhf40-2p50-en_a_th
OHn = class of risk value referred to the required rated capacity (Tab.6 para 7.3.1 EN12845)
Inlet pressure drops must be deducted. Make sure that these drops, added to the difference in level (max. 3.2m), are less than 4.5m
The values shown identify performance levels according to the reference standard EN12845.

HYDRA
ULIC PERFORMANCE T
ABLE
A2 T
50 HZ (SUCTION LIF
T)
HYDRAULIC
TABLE
LIFT)
TABELLA DI PRESTAZIONI IDRAULICHE NETTE GRUPPI EN12845
SERIE FHF40AT
poli 50 Hz 1 POMPA DI SERVIZIO, ASP ESCLUSA
INST SOTTO
GEN../FHF 40 BOOSTER SETS SERIES
TYPE

RATED

FHF..

POWER

ELECTRIC

PUMP

PUMP

OH1n

RISK CLASS

Q = DELIVERY
l/min 0

300

350

375

540

600

700

725

750

800

900

1000

1100

m3/h 0

18

21

23

32

36

42

44

45

48

54

60

66

H = TOTAL HEAD METRES COLUMN OF WATER

kW

40-125/11

40-125/D112

1 x 1,1

13,9

11,3

10,0

9,3

3,4

40-125/15

40-125/D122

1 x 1,5

18,0

15,3

14,0

13,3

7,4

0,7
4,7

40-125/22

40-125/D143

1 x 2,2

25,3

21,8

20,5

19,8

14,0

11,4

6,4

5,0

3,6

40-160/30

40-160/D159

1x3

31,6

28,1

26,8

26,0

19,5

16,5

10,8

9,2

7,6

0,6

40-160/40

40-160/D171

1x4

38,3

35,1

33,7

32,9

26,5

23,6

18,1

16,5

15,0

40-200/55

40-200/D190

1 x 5,5

46,4

42,7

41,2

40,4

33,1

29,7

23,3

21,5

19,6

40-200/75

40-200/D209

1 x 7,5

57,5

53,1

51,6

50,7

43,8

40,7

34,8

33,2

31,5

28,0

40-250/110A 40-250/D218

1 x 11

63,6

57,8

56,2

55,2

47,8

44,5

38,2

36,5

34,8

31,1

11,7

40-250/110

40-250/D233

1 x 11

71,7

66,0

64,3

63,4

55,7

52,3

45,8

44,0

42,1

38,3

40-250/150

40-250/D251

1 x 15

85,0

78,6

76,9

76,0

68,4

65,0

58,6

56,8

55,0

51,1

Performance levels relative to set with 1 service pump running and compliant with ISO 9906 - Annex A.
OHn = class of risk value referred to the required rated capacity (Tab.6 para 7.3.1 EN12845)
Inlet pressure drops must be deducted. Make sure these drops are less than 4.5m
The values shown identify performance levels according to the reference standard EN12845.

34

42,6

12845_1pg-st-fhf40-2p50-en_a_th

Lowara
NPSH
REQUIRED
PUMP
FHF
TABELLA DI PRESTAZIONI
IDRAULICHEFOR
NPSHr GRUPPI
EN12845 SERIES
SERIE FHF40 2 poli
50 Hz 140
POMPA DI SERVIZIO

RATED

FHF..

POWER

ELECTRIC

PUMP

PUMP

OH1m

TYPE

OH1n

RISK CLASS

l/min 0

300

350

375

540

600

700

725

750

800

900

1000

1100

m3/h 0

18

21

23

32

36

42

44

45

48

54

60

66

Q = DELIVERY

NPSHr [METRES COLUMN OF WATER]

kW

40-125/11

40-125/D112

1 x 1,1

1,8

1,9

1,9

2,4

2,7

40-125/15

40-125/D122

1 x 1,5

1,8

1,9

1,9

2,4

2,7

3,7

40-125/22

40-125/D143

1 x 2,2

1,8

1,9

1,9

2,4

2,7

3,7

4,1

4,6

40-160/30

40-160/D159

1x3

1,9

1,9

1,9

2,4

2,9

4,1

4,5

5,0

6,3

40-160/40

40-160/D171

1x4

1,9

1,9

1,9

2,4

2,9

4,1

4,5

5,0

40-200/55

40-200/D190

1 x 5,5

2,0

2,1

2,2

2,9

3,4

4,5

4,9

5,3

6,2

40-200/75

40-200/D209

1 x 7,5

2,0

2,1

2,2

2,9

3,4

4,5

4,9

5,3

6,3

40-250/110A 40-250/D218

1 x 11

1,0

1,1

1,2

1,6

1,7

2,1

2,2

2,3

2,6

40-250/110

40-250/D233

1 x 11

1,0

1,1

1,2

1,6

1,7

2,1

2,2

2,3

2,6

40-250/150

40-250/D251

1 x 15

1,0

1,1

1,2

1,6

1,7

2,1

2,2

2,3

2,6

The declared NPSH values were obtained in the laboratory and refer to a single service pump
OHn, OHm = class of risk value referred to the required rated and maximum capacity (Tab.6 para 7.3.1 EN12845)
Check that NPSHd NPSHr+1m is satisfied at the maximum requested capacity

35

3,5

12845_1p-fhf40-2p50_NPSHr-en_a_th

Lowara
HYDRA
ULIC PERFORMANCE
T
ABLE
T 50
SUCTION
HYDRAULIC
TABLE
AT
TABELLA DI PRESTAZIONI
IDRAULICHE NETTE GRUPPI EN12845
SERIEA
FHF50
2 poliHZ
50 Hz(POSITIVE
1 POMPA DI SERVIZIO,
INST SOPRAB HEAD)
GEN../FHF 50 BOOSTER SETS SERIES
RATED

FHF..

POWER

ELECTRIC

PUMP

PUMP

OH3n

TYPE

OH2n

RISK CLASS

Q = DELIVERY
l/min 0

600

700

725

850

1000

1100

1200

1300

1350

1400

1500

1600

m3/h 0

36

42

44

51

60

66

72

78

81

84

90

96

H = TOTAL HEAD METRES COLUMN OF WATER

kW

50-125/22

50-125/D119

1 x 2,2

16,8

13,7

12,3

11,8

9,5

6,2

3,7

0,9

50-125/30

50-125/D130

1x3

19,9

17,5

16,1

15,8

13,6

10,5

8,0

5,3

2,3

50-125/40

50-125/D139

1x4

24,3

21,8

20,6

20,2

18,3

15,3

13,1

10,5

7,7

6,2

4,6

50-160/55

50-160/D158

1 x 5,5

31,8

29,3

27,7

27,3

24,8

21,1

18,2

15,0

11,4

9,5

7,6

50-160/75

50-160/D174

1 x 7,5

39,8

36,6

35,2

34,8

32,5

29,1

26,5

23,5

20,2

18,5

16,7

50-200/110A 50-200/D197

1 x 11

50,6

45,6

43,4

42,8

39,5

34,8

31,2

27,3

23,1

20,9

18,6

12,7

50-200/110

50-200/D209

1 x 11

58,0

52,6

50,5

49,9

46,7

42,1

38,6

34,7

30,4

28,1

25,7

50-250/150

50-250/D224

1 x 15

68,1

62,8

60,9

60,4

57,3

52,6

48,8

44,4

39,4

36,7

33,8

50-250/185

50-250/D237

1 x 18,5

76,5

71,7

70,0

69,5

66,6

62,3

58,8

54,7

50,0

47,4

44,7

38,6

50-250/220

50-250/D250

1 x 22

86,0

81,2

79,5

79,0

76,1

71,7

68,1

64,0

59,4

56,8

54,1

48,1

20,7

41,4

Performance levels relative to set with 1 service pump running and compliant with ISO 9906 - Annex A.
12845_1pg-sp-fhf50-2p50-en_a_th
OHn = class of risk value referred to the required rated capacity (Tab.6 para 7.3.1 EN12845)
Inlet pressure drops must be deducted. Make sure that these drops, added to the difference in level (max. 3.2m), are less than 4.5m
The values shown identify performance levels according to the reference standard EN12845.

HYDRA
ULIC PERFORMANCE T
ABLE
A2 T
50 HZ (SUCTION LIF
T)
HYDRAULIC
TABLE
LIFT)
TABELLA DI PRESTAZIONI IDRAULICHE NETTE GRUPPI EN12845
SERIE FHF50AT
poli 50 Hz 1 POMPA DI SERVIZIO, INST SOTT
GEN../FHF 50 BOOSTER SETS SERIES
RATED

FHF..

POWER

ELECTRIC

PUMP

PUMP

OH3n

TYPE

OH2n

RISK CLASS

Q = DELIVERY
l/min 0

600

700

725

850

1000

1100

1200

1300

1350

1400

1500

1600

m3/h 0

36

42

44

51

60

66

72

78

81

84

90

96

H = TOTAL HEAD METRES COLUMN OF WATER

kW

50-125/22

50-125/D119

1 x 2,2

16,8

13,7

12,3

11,8

9,5

6,2

3,7

0,9

50-125/30

50-125/D130

1x3

19,9

17,5

16,1

15,8

13,6

10,5

8,0

5,3

2,3

50-125/40

50-125/D139

1x4

24,3

21,8

20,6

20,2

18,3

15,3

13,1

10,5

7,7

6,2

4,6

50-160/55

50-160/D158

1 x 5,5

31,8

29,3

27,7

27,3

24,8

21,1

18,2

15,0

11,4

9,5

7,6

50-160/75

50-160/D174

1 x 7,5

39,8

36,6

35,2

34,8

32,5

29,1

26,5

23,5

20,2

18,5

16,7

50-200/110A 50-200/D197

1 x 11

50,6

45,6

43,4

42,8

39,5

34,8

31,2

27,3

23,1

20,9

18,6

12,7

50-200/110

50-200/D209

1 x 11

58,0

52,6

50,5

49,9

46,7

42,1

38,6

34,7

30,4

28,1

25,7

50-250/150

50-250/D224

1 x 15

68,1

62,8

60,9

60,4

57,3

52,6

48,8

44,4

39,4

36,7

33,8

50-250/185

50-250/D237

1 x 18,5

76,5

71,7

70,0

69,5

66,6

62,3

58,8

54,7

50,0

47,4

44,7

38,6

50-250/220

50-250/D250

1 x 22

86,0

81,3

79,5

79,0

76,1

71,7

68,2

64,1

59,5

56,9

54,2

48,2

Performance levels relative to set with 1 service pump running and compliant with ISO 9906 - Annex A.
OHn = class of risk value referred to the required rated capacity (Tab.6 para 7.3.1 EN12845)
Inlet pressure drops must be deducted. Make sure these drops are less than 4.5m
The values shown identify performance levels according to the reference standard EN12845.

36

20,7

41,6

12845_1pg-st-fhf50-2p50-en_a_th

Lowara
NPSH
REQUIRED
FOR
PUMP
SERIES
TABELLA DI PRESTAZIONI
IDRAULICHE
NPSHr GRUPPI
EN12845
SERIE FHF50 FHF
2 poli 50 50
Hz 1 POMPA DI SERVIZIO

POWER

Q = DELIVERY
l/min 0

ELECTRIC

PUMP

PUMP

OH3m

FHF..

OH3n

RATED

OH2n

TYPE

OH2m

RISK CLASS

m /h 0

600

700

725

850

1000

1100

1200

1300

1350

1400

1500

1600

36

42

44

51

60

66

72

78

81

84

90

96

NPSHr [METRES COLUMN OF WATER]

kW

50-125/22

50-125/D119

1 x 2,2

2,1

2,3

2,3

2,6

3,1

3,5

3,9

50-125/30

50-125/D130

1x3

2,1

2,3

2,3

2,6

3,1

3,5

3,9

4,4

50-125/40

50-125/D139

1x4

2,1

2,3

2,3

2,6

3,1

3,5

3,9

4,4

4,7

5,0

50-160/55

50-160/D158

1 x 5,5

1,9

2,1

2,2

2,5

2,9

3,2

3,6

4,2

4,6

5,1

50-160/75

50-160/D174

1 x 7,5

1,9

2,1

2,2

2,5

2,9

3,2

3,6

4,2

4,6

5,1

50-200/110A 50-200/D197

1 x 11

1,8

1,9

2,0

2,2

2,6

2,9

3,4

4,1

4,6

5,1

50-200/110

50-200/D209

1 x 11

1,8

1,9

2,0

2,2

2,6

2,9

3,4

4,1

4,6

5,1

50-250/150

50-250/D224

1 x 15

1,5

1,7

1,7

2,0

2,4

2,7

3,1

3,6

3,9

4,2

50-250/185

50-250/D237

1 x 18,5

1,5

1,7

1,7

2,0

2,4

2,7

3,1

3,6

3,9

4,2

5,1

50-250/220

50-250/D250

1 x 22

1,5

1,7

1,7

2,0

2,4

2,7

3,1

3,6

3,9

4,2

5,1

The declared NPSH values were obtained in the laboratory and refer to a single service pump
OHn, OHm = class of risk value referred to the required rated and maximum capacity (Tab.6 para 7.3.1 EN12845)
Check that NPSHd NPSHr+1m is satisfied at the maximum requested capacity

37

6,5
6,7

6,4

12845_1p-fhf50-2p50_NPSHr-en_a_th

Lowara
HYDRA
ULIC PERFORMANCE T
ABLE A
T 50 HZ (POSITIVE SUCTION HEAD)
HYDRAULIC
TABLE
AT
TABELLA DI PRESTAZIONI IDRAULICHE NETTE GRUPPI EN12845 SERIE FHF65 2 poli 50 Hz 1 POMPA DI SERVIZIO, ASP ESCLUSA INST SOPRAB
GEN../FHF 65 BOOSTER SETS SERIES
RATED

FHF..

POWER

ELECTRIC

PUMP

PUMP

OH4n

TYPE

OH3n

RISK CLASS

Q = DELIVERY
l/min 0

800

900

1000

1100

1200

1350

1400

1500

1800

2000

2100

2300

m3/h 0

48

54

60

66

72

81

84

90

108

120

126

138

H = TOTAL HEAD METRES COLUMN OF WATER

kW

65-125/40

65-125/D121

1x4

19,1

15,6

14,6

13,5

12,3

10,9

8,7

7,9

6,2

65-125/55

65-125/D129

1 x 5,5

22,7

19,6

18,8

17,8

16,7

15,5

13,5

12,7

11,2

5,7

65-125/75

65-125/D140

1 x 7,5

27,1

24,3

23,5

22,7

21,7

20,7

18,9

18,2

16,8

12,0

8,1

65-160/110A 65-160/D161

1 x 11

32,7

29,2

28,3

27,2

26,0

23,9

23,2

21,6

15,9

11,5

9,0

65-160/110

65-160/D168

1 x 11

35,9

32,5

31,5

30,5

29,4

27,4

26,7

25,2

19,8

15,6

13,3

65-160/150

65-160/D178

1 x 15

41,9

38,9

38,1

37,1

36,1

34,2

33,6

32,2

27,2

23,2

21,1

65-200/150

65-200/D187

1 x 15

45,2

43,4

42,3

41,1

39,7

37,3

36,4

34,6

28,4

23,8

21,3

65-200/185

65-200/D198

1 x 18,5

51,6

50,2

49,2

48,2

47,0

44,9

44,1

42,4

36,5

31,8

29,2

65-200/220

65-200/D210

1 x 22

59,1

57,2

56,3

55,3

54,2

52,1

51,4

49,8

44,1

39,6

37,1

65-250/220

65-250/D220

1 x 22

62,8

60,6

59,4

58,0

56,4

53,5

52,5

50,2

42,1

35,7

32,1

16,3

31,6

65-250/300

65-250/D241

1 x 30

76,4

75,0

73,9

72,6

71,1

68,5

67,5

65,4

57,8

51,6

48,2

40,6

65-250/370

65-250/D258

1 x 37

90,8

89,9

89,0

88,0

86,7

84,5

83,7

81,8

74,8

68,8

65,4

57,7

Performance levels relative to set with 1 service pump running and compliant with ISO 9906 - Annex A.
12845_1pg-sp-fhf65-2p50-en_a_th
OHn = class of risk value referred to the required rated capacity (Tab.6 para 7.3.1 EN12845)
Inlet pressure drops must be deducted. Make sure that these drops, added to the difference in level (max. 3.2m), are less than 4.5m
The values shown identify performance levels according to the reference standard EN12845.

HYDRA
ULIC PERFORMANCE T
ABLE A
T 50 HZ (SUCTION LIF
T)
HYDRAULIC
TABLE
AT
LIFT)
TABELLA DI PRESTAZIONI IDRAULICHE NETTE GRUPPI EN12845 SERIE FHF65 2 poli 50 Hz 1 POMPA DI SERVIZIO, ASP ESCLUSA INST SOTTOB
GEN../FHF 65 BOOSTER SETS SERIES
RATED

FHF..

POWER

ELECTRIC

PUMP

PUMP

OH4n

TYPE

OH3n

RISK CLASS

Q = DELIVERY
l/min 0

800

900

1000

1100

1200

1350

1400

1500

1800

2000

2100

2300

m3/h 0

48

54

60

66

72

81

84

90

108

120

126

138

H = TOTAL HEAD METRES COLUMN OF WATER

kW

65-125/40

65-125/D121

1x4

19,1

15,6

14,6

13,5

12,3

10,9

8,7

7,9

6,2

65-125/55

65-125/D129

1 x 5,5

22,7

19,6

18,8

17,8

16,7

15,5

13,5

12,7

11,2

5,7

65-125/75

65-125/D140

1 x 7,5

27,1

24,3

23,5

22,7

21,7

20,7

18,9

18,2

16,8

12,0

8,1

65-160/110A 65-160/D161

1 x 11

32,7

29,2

28,3

27,2

26,0

23,9

23,2

21,6

15,9

11,5

9,0

65-160/110

1 x 11

35,9

32,5

31,5

30,5

29,4

27,4

26,7

25,2

19,8

15,6

13,3

65-160/D168

65-160/150

65-160/D178

1 x 15

41,9

38,9

38,1

37,1

36,1

34,2

33,6

32,2

27,2

23,2

21,1

65-200/150

65-200/D187

1 x 15

45,2

43,4

42,3

41,1

39,7

37,3

36,4

34,6

28,4

23,8

21,3

65-200/185

65-200/D198

1 x 18,5

51,6

50,2

49,2

48,2

47,0

44,9

44,1

42,4

36,5

31,8

29,2

65-200/220

65-200/D210

1 x 22

59,1

57,2

56,3

55,3

54,2

52,1

51,4

49,8

44,1

39,6

37,1

65-250/220

65-250/D220

1 x 22

62,8

60,6

59,4

58,0

56,4

53,5

52,5

50,2

42,1

35,7

32,1

16,3

31,6

65-250/300

65-250/D241

1 x 30

76,4

75,0

73,9

72,6

71,1

68,5

67,5

65,4

57,8

51,6

48,2

40,6

65-250/370

65-250/D258

1 x 37

90,8

89,9

89,0

88,0

86,7

84,5

83,7

81,8

74,8

68,8

65,4

57,7

Performance levels relative to set with 1 service pump running and compliant with ISO 9906 - Annex A.
OHn = class of risk value referred to the required rated capacity (Tab.6 para 7.3.1 EN12845)
Inlet pressure drops must be deducted. Make sure these drops are less than 4.5m
The values shown identify performance levels according to the reference standard EN12845.

38

12845_1pg-st-fhf65-2p50-en_a_th

Lowara
NPSH
REQUIRED FOR PUMP SERIES FHF 65
TABELLA DI PRESTAZIONI IDRAULICHE NPSHr GRUPPI EN12845 SERIE FHF65 2 poli 50 Hz 1 POMPA DI SERVIZIO

POWER

Q = DELIVERY
l/min 0

ELECTRIC

PUMP

PUMP

OH4m

FHF..

OH4n

RATED

OH3n

TYPE

OH3m

RISK CLASS

m /h 0

800

900

1000

1100

1200

1350

1400

1500

1800

2000

2100

2300

48

54

60

66

72

81

84

90

108

120

126

138

NPSHr [METRES COLUMN OF WATER]

kW

65-125/40

65-125/D121

1x4

1,0

1,2

1,3

1,6

1,9

2,4

2,6

3,1

65-125/55

65-125/D129

1 x 5,5

1,0

1,2

1,3

1,6

1,9

2,4

2,6

3,1

5,1

65-125/75

65-125/D140

1 x 7,5

1,0

1,2

1,3

1,6

1,9

2,4

2,6

3,1

5,1

7,0

65-160/110A 65-160/D161

1 x 11

2,4

2,4

2,5

2,6

2,9

2,9

3,2

4,2

5,3

6,0

65-160/110

65-160/D168

1 x 11

2,3

2,4

2,5

2,7

2,8

2,9

3,1

3,7

4,4

4,9

65-160/150

65-160/D178

1 x 15

2,3

2,4

2,5

2,7

2,8

2,9

3,1

3,7

4,4

4,9

65-200/150

65-200/D187

1 x 15

1,8

1,9

2,0

2,1

2,3

2,4

2,6

3,4

4,5

5,3

65-200/185

65-200/D198

1 x 18,5

1,8

1,9

2,0

2,1

2,3

2,4

2,6

3,4

4,3

4,9

65-200/220

65-200/D210

1 x 22

1,8

1,9

2,0

2,1

2,3

2,4

2,6

3,4

4,3

4,9

65-250/220

65-250/D220

1 x 22

1,7

2,0

2,2

2,5

2,9

3,1

3,4

4,3

5,0

5,4

65-250/300

65-250/D241

1 x 30

1,7

2,0

2,2

2,5

2,9

3,1

3,4

4,3

5,0

5,4

6,2

65-250/370

65-250/D258

1 x 37

1,7

2,0

2,2

2,5

2,9

3,1

3,4

4,3

5,0

5,4

6,2

The declared NPSH values were obtained in the laboratory and refer to a single service pump
OHn, OHm = class of risk value referred to the required rated and maximum capacity (Tab.6 para 7.3.1 EN12845)
Check that NPSHd NPSHr+1m is satisfied at the maximum requested capacity

39

6,6

6,6

12845_1p-fhf65-2p50_NPSHr-en_a_th

Lowara
HYDRA
ULIC PERFORMANCE
T
ABLE
T 50
SUCTION
HEAD)
HYDRAULIC
TABLE
AT
TABELLA DI PRESTAZIONI
IDRAULICHE NETTE GRUPPI EN12845
SERIEA
FHF80
2 poliHZ
50 Hz(POSITIVE
1 POMPA DI SERVIZIO,
ASP ESCLUSA INST
SOPRA
GEN../FHF 80 BOOSTER SETS SERIES
RATED

FHF..

POWER

ELECTRIC

PUMP

PUMP

HH1n

TYPE

OH4n

RISK CLASS

Q = DELIVERY
l/min 0

1500

1650

1800

2050

2100

2200

2300

2600

3216

3500

3600

3650

m3/h 0

90

99

108

123

126

132

138

156

193

210

216

219

H = TOTAL HEAD METRES COLUMN OF WATER

kW

80-160/150

80-160/D163

1 x 15

32,9

30,2

29,1

27,8

25,4

24,9

23,8

22,7

18,8

9,4

4,4

80-160/185

80-160/D173

1 x 18,5

39,0

35,6

34,5

33,4

31,2

30,7

29,7

28,6

25,1

16,2

11,3

80-200/220

80-200/D189

1 x 22

48,0

44,7

43,4

41,8

39,0

38,3

37,0

35,6

30,9

19,2

12,8

80-200/300

80-200/D207

1 x 30

59,9

56,9

55,8

54,4

51,9

51,3

50,1

48,9

44,7

34,2

28,5

80-250/370

80-250/D225

1 x 37

70,8

67,3

65,8

63,9

60,4

59,6

57,9

56,1

50,1

34,7

26,1

9,5

8,5

26,4

25,3

80-250/450

80-250/D238

1 x 45

80,0

78,0

76,5

74,8

71,5

70,8

69,2

67,6

62,0

47,5

39,6

36,5

80-250/550

80-250/D256

1 x 55

88,9

89,9

88,8

87,5

84,8

84,2

82,9

81,5

76,7

64,0

56,7

54,0

52,6

Performance levels relative to set with 1 service pump running and compliant with ISO 9906 - Annex A.
12845_1pg-sp-fhf80-2p50-en_a_th
OHn, HHn = class of risk value referred to the required rated capacity (Tab.6 para 7.3.1, Tab.7 para 7.3.2 EN12845)
Inlet pressure drops must be deducted. Make sure that these drops, added to the difference in level (max. 3.2m), are less than 4.5m
The values shown identify performance levels according to the reference standard EN12845.

HYDRA
ULIC PERFORMANCE
T
ABLE
(SUCTION
LIF
T)
HYDRAULIC
TABLE
AT
LIFT)
TABELLA DI PRESTAZIONI
IDRAULICHE NETTE GRUPPI EN12845
SERIE FHF80A
2T
poli50
50 Hz HZ
1 POMPA
DI SERVIZIO, ASP ESCLUSA
INST SOTTO
GEN../FHF 80 BOOSTER SETS SERIES
RATED

FHF..

POWER

ELECTRIC

PUMP

PUMP

HH1n

TYPE

OH4n

RISK CLASS

Q = DELIVERY
l/min 0

1500

1650

1800

2050

2100

2200

2300

2600

3216

3500

3600

3650

m3/h 0

90

99

108

123

126

132

138

156

193

210

216

219

H = TOTAL HEAD METRES COLUMN OF WATER

kW

80-160/150

80-160/D163

1 x 15

32,9

30,2

29,1

27,8

25,4

24,9

23,8

22,7

18,8

9,4

4,4

80-160/185

80-160/D173

1 x 18,5

39,0

35,6

34,5

33,4

31,2

30,7

29,7

28,6

25,1

16,2

11,3

80-200/220

80-200/D189

1 x 22

48,0

44,7

43,4

41,8

39,0

38,3

37,0

35,6

30,9

19,2

12,8

80-200/300

80-200/D207

1 x 30

59,9

56,9

55,8

54,4

51,9

51,3

50,1

48,9

44,7

34,2

28,5

80-250/370

80-250/D225

1 x 37

70,8

67,3

65,8

63,9

60,4

59,6

57,9

56,1

50,1

34,7

26,1

9,5

8,5

26,4

25,3

80-250/450

80-250/D238

1 x 45

80,0

78,0

76,5

74,8

71,5

70,8

69,2

67,6

62,0

47,5

39,6

36,5

80-250/550

80-250/D256

1 x 55

88,9

89,9

88,8

87,5

84,8

84,2

82,9

81,5

76,7

64,0

56,7

54,0

Performance levels relative to set with 1 service pump running and compliant with ISO 9906 - Annex A.
OHn, HHn = class of risk value referred to the required rated capacity (Tab.6 para 7.3.1, Tab.7 para 7.3.2 EN12845)
Inlet pressure drops must be deducted. Make sure these drops are less than 4.5m
The values shown identify performance levels according to the reference standard EN12845.

40

52,6

12845_1pg-st-fhf80-2p50-en_a_th

Lowara
NPSH
REQUIRED FOR PUMP SERIES FHF 80
TABELLA DI PRESTAZIONI IDRAULICHE NPSHr GRUPPI EN12845 SERIE FHF80 2 poli 50 Hz 1 POMPA DI SERVIZIO

POWER

ELECTRIC

PUMP

PUMP

HH1m

FHF..

HH1n

RATED

OH4n

TYPE

OH4m

RISK CLASS

Q = DELIVERY
l/min 0

1500

1650

1800

2050

2100

2200

2300

2600

3216

3500

3600

3650

3
m /h 0

90

99

108

123

126

132

138

156

193

210

216

219

6,5

6,8

6,9

7,3

NPSHr [METRES COLUMN OF WATER]

kW

80-160/150

80-160/D163

1 x 15

3,7

3,8

3,9

4,0

4,1

4,2

4,2

4,5

5,4

6,2

80-160/185

80-160/D173

1 x 18,5

3,7

3,8

3,9

4,0

4,1

4,2

4,2

4,5

5,4

6,2

80-200/220

80-200/D189

1 x 22

2,8

3,0

3,1

3,3

3,4

3,5

3,6

3,9

5,1

6,3

80-200/300

80-200/D207

1 x 30

2,8

3,0

3,1

3,3

3,4

3,5

3,6

3,9

5,1

6,3

80-250/370

80-250/D225

1 x 37

3,0

3,1

3,3

3,6

3,6

3,8

3,9

4,4

6,0

7,4

80-250/450

80-250/D238

1 x 45

2,4

2,6

2,7

3,0

3,1

3,2

3,3

3,8

4,9

5,5

5,7

80-250/550

80-250/D256

1 x 55

2,4

2,6

2,7

3,0

3,1

3,2

3,3

3,8

4,9

5,5

5,7

The declared NPSH values were obtained in the laboratory and refer to a single service pump

OHn, OHm, HHn, HHm = class of risk value referred to the required rated and maximum capacity (Tab.6 para 7.3.1, Tab.7 para 7.3.2 EN12845)
Check that NPSHd NPSHr+1m is satisfied at the maximum requested capacity

41

5,8

12845_1p-fhf80-2p50_NPSHr-en_a_th

Lowara
HYDRA
ULIC PERFORMANCE T
ABLE A
T 50 HZ (POSITIVE SUCTION HEAD)
HYDRAULIC
TABLE
AT
GEN../FHF 100 BOOSTER SETS SERIES

POWER

ELECTRIC

PUMP

PUMP

HH4n

FHF..

HH3n

RATED

HH2n

TYPE

HH1n

RISK CLASS

l/min 0

1333

1500

1667

2300

2900

3050

3216

3800

4066

4266

4333

5000

5166

5316

5500

6000

m3/h 0

80

90

100

138

174

183

193

228

244

256

260

300

310

319

330

360

Q = DELIVERY

H = TOTAL HEAD METRES COLUMN OF WATER

kW

100-160/185

100-160/D150

1 x 18,5

26,7

26,0

25,6 25,2 22,9

19,9

19,0 18,0

13,9 11,8 10,2

9,6

3,5

1,8

100-160/220

100-160/D165

1 x 22

33,0

32,2

31,7 31,2 28,7

25,3

24,4 23,3

18,8 16,6 14,8 14,2

7,6

5,9

100-160/300

100-160/D185

1 x 30

42,3

41,2

40,8 40,3 37,8

34,6

33,6 32,5

28,2 26,0 24,2 23,6 16,9 15,1 13,5 11,4

100-200/185

100-200/D168

1 x 18,5

36,3

33,5 32,7 28,6

23,5

22,0 20,3

13,5 10,1

100-200/300

100-200/D192

1 x 30

49,0

47,5 46,9 43,7

39,5

38,3 36,8

31,0 28,0 25,5 24,7 15,5 12,9

100-200/370

100-200/D203

1 x 37

56,0

54,6 54,0 51,0

46,9

45,8 44,4

38,7 35,8 33,4 32,6 23,7 21,2 18,9 16,0

100-200/450

100-200/D213

1 x 45

61,0

60,0 59,5 57,1

53,6

52,6 51,4

46,3 43,7 41,5 40,7 32,3 29,9 27,7 24,8

100-250/300

100-250/D200

1 x 30

54,6

52,1 47,7

41,8

40,0 37,9

29,3 24,8 21,2 19,9

100-250/450

100-250/D221

1 x 45

68,8

66,9 63,5

58,7

57,2 55,4

48,1 44,2 41,0 39,9 27,2 23,6 20,3 15,9

100-250/550

100-250/D235

1 x 55

78,5

76,9 74,0

69,8

68,5 66,9

60,2 56,6 53,6 52,6 40,6 37,2 34,0 29,8

7,4

4,2

2,2
5,3

6,4

5,9

FHF..

POWER

ELECTRIC

PUMP

PUMP

Q = DELIVERY
l/min 0

1667

2500

3800

4150

4550

4700

4800

5000

5316

5500

6000

6366

6416

6500

6716

6750

m3/h 0

100

150

228

249

273

282

288

300

319

330

360

382

385

390

403

405

H = TOTAL HEAD METRES COLUMN OF WATER

kW

100-250/750

100-250/D254

1 x 75

100-250/900

100-250/D267

1 x 90

HH6n

RATED

HH5n

TYPE

HH4n

RISK CLASS

90,5

86,9 75,9 71,7

66,1

63,7 62,1

58,7 52,9 49,3 38,3 29,3 28,0

102,9 101,6

91,7

98,2 87,5 83,4

77,9

75,6 74,0

70,7 64,9 61,3 50,5 41,5 40,2 38,0 32,0

Performance levels relative to set with 1 service pump running and compliant with ISO 9906 - Annex A.
HHn = class of risk value referred to the required rated capacity (Tab.7 para 7.3.2 EN12845)
Inlet pressure drops must be deducted. Make sure that these drops, added to the difference in level (max. 3.2m), are less than 4.5m
The values shown identify performance levels according to the reference standard EN12845.

31,1

12845_1pg-sp-fhf100-2p50-en_a_th

HYDRA
ULIC PERFORMANCE T
ABLE A
T 50 HZ (SUCTION LIF
T)
HYDRAULIC
TABLE
AT
LIFT)
GEN../FHF 100 BOOSTER SETS SERIES

POWER

ELECTRIC

PUMP

PUMP

HH4n

FHF..

HH3n

RATED

HH2n

TYPE

HH1n

RISK CLASS

l/min 0

1333

1500

1667

2300

2900

3050

3216

3800

4066

4266

4333

5000

5166

5316

5500

6000

m3/h 0

80

90

100

138

174

183

193

228

244

256

260

300

310

319

330

360

Q = DELIVERY

H = TOTAL HEAD METRES COLUMN OF WATER

kW

100-160/185

100-160/D150

1 x 18,5

26,7

26,8

26,6

26,4 25,0

23,1

22,6 21,9

19,3

18,0 16,9 16,6 12,6 11,5

100-160/220

100-160/D165

1 x 22

33,0

33,0

32,7

32,4 30,8

28,6

28,0 27,2

24,3

22,8 21,6 21,1 16,8 15,6 14,5 13,1

100-160/300

100-160/D185

1 x 30

42,3

42,0

41,8

41,5 39,9

37,8

37,2 36,5

33,6

32,1 30,9 30,5 26,1 24,9 23,7 22,3

100-200/185

100-200/D168

1 x 18,5

36,3

34,5

33,9 30,7

26,7

25,6 24,2

18,9

16,2 14,1 13,4

100-200/300

100-200/D192

1 x 30

49,0

48,5

48,1 45,8

42,8

41,9 40,8

36,4

34,1 32,3 31,6 24,6 22,6

100-200/370

100-200/D203

1 x 37

56,0

55,5

55,2 53,1

50,2

49,3 48,3

44,1

41,9 40,2 39,6 32,8 30,9 29,2 26,9

100-200/450

100-200/D213

1 x 45

61,0

61,0

60,7 59,2

56,9

56,2 55,3

51,7

49,8 48,2 47,7 41,4 39,6 37,9 35,8

100-250/300

100-250/D200

1 x 30

54,6

53,3 49,8

45,0

43,5 41,8

34,7

30,9 27,9 26,8 15,0

100-250/450

100-250/D221

1 x 45

68,8

68,1 65,6

61,9

60,8 59,4

53,5

50,4 47,7 46,8 36,3 33,4 30,5 26,9

100-250/550

100-250/D235

1 x 55

78,5

78,1 76,2

73,0

72,0 70,8

65,6

62,8 60,4 59,5 49,7 46,9 44,2 40,7

18,2

FHF..

POWER

ELECTRIC

PUMP

PUMP

Q = DELIVERY
l/min 0

1667

2500

3800

4150

4550

4700

4800

5000

5316

5500

6000

6366

6416

6500

6716

6750

m3/h 0

100

150

228

249

273

282

288

300

319

330

360

382

385

390

403

405

H = TOTAL HEAD METRES COLUMN OF WATER

kW

100-250/750

100-250/D254

1 x 75

100-250/900

100-250/D267

1 x 90

HH6n

RATED

HH5n

TYPE

HH4n

RISK CLASS

89,4

81,3

78,1

73,7

71,8 70,6

67,9 63,2 60,2 51,3 43,8 42,8

102,9 102,8 100,6

91,7

91,7

92,9

89,8

85,5

83,7 82,5

79,8 75,2 72,3 63,4 56,0 54,9 53,1 48,1

Performance levels relative to set with 1 service pump running and compliant with ISO 9906 - Annex A.
HHn = class of risk value referred to the required rated capacity (Tab.7 para 7.3.2 EN12845)
Inlet pressure drops must be deducted. Make sure these drops are less than 4.5m
The values shown identify performance levels according to the reference standard EN12845.

42

47,3

12845_1pg-st-fhf100-2p50-en_a_th

Lowara
NPSH REQUIRED FOR PUMP SERIES FHF 100

HH4m

HH3m

HH2m

HH4n

POWER

HH1m

FHF..

HH3n

RATED

HH2n

TYPE

HH1n

RISK CLASS

Q = DELIVERY
l/min 0 1333 1500 1667 2300 2900 3050 3216 3800 4066 4266 4333 5000 5166 5316 5500 6000

ELECTRIC

100-160/185
100-160/220
100-160/300
100-200/185
100-200/300
100-200/370
100-200/450
100-250/300
100-250/450
100-250/550

m3/h 0

PUMP

PUMP

80

90

100

138

100-160/D150
100-160/D165
100-160/D185
100-200/D168
100-200/D192
100-200/D203
100-200/D213
100-250/D200
100-250/D221
100-250/D235

1 x 18,5
1 x 22
1 x 30
1 x 18,5
1 x 30
1 x 37
1 x 45
1 x 30
1 x 45
1 x 55

174

183

193

228

244

256

260

300

310

319

330

360

NPSHr [METRES COLUMN OF WATER]

kW

6,3
5,0
5,0

6,4
5,2
5,2
4,2
3,1
3,1
3,1

6,6
5,4
5,4
4,2
3,1
3,1
3,1
4,7
4,6
4,6

7,3
6,2
6,2
4,6
3,3
3,3
3,3
5,0
4,7
4,7

8,0
6,9
6,9
5,6
3,5
3,5
3,5
5,3
4,7
4,7

8,2
7,0
7,0
6,0
3,6
3,6
3,6
5,4
4,8
4,8

8,4
7,2
7,2
6,5
3,7
3,7
3,7
5,4
4,8
4,8

9,2
7,9
7,9
9,2
4,2
4,2
4,2
5,7
4,8
4,8

9,5 9,8 9,9 11,0 11,4


8,3 8,5 8,6 9,6 9,9 10,3 10,7
8,3 8,5 8,6 9,6 9,9 10,3 10,7 12,8
11,1 12,8 13,5
4,6 4,9 5,1 7,0 7,7
4,6 4,9 5,1 7,0 7,7 8,4 9,5
4,6 4,9 5,1 7,0 7,7 8,4 9,5
5,8 5,9 6,0 6,3
4,9 4,9 4,9 5,1 5,2 5,2 5,3
4,9 4,9 4,9 5,1 5,2 5,2 5,3
HH6m

HH5m

POWER

HH4m

FHF..

HH6n

RATED

HH5n

TYPE

HH4n

RISK CLASS

Q = DELIVERY
l/min 0 1667 2500 3800 4150 4550 4700 4800 5000 5316 5500 6000 6366 6416 6500 6716 6750

ELECTRIC

100-250/750
100-250/900

m3/h 0 100

PUMP

PUMP

150

228

249

100-250/D254
100-250/D267

1 x 75
1 x 90

273

282

288

300

319

330

360

382

385

390

403

405

6,6
6,6

6,7
6,7

6,9

7,8

7,9

NPSHr [METRES COLUMN OF WATER]

kW

4,6
4,6

4,7
4,7

4,8
4,8

4,9
4,9

5,0
5,0

5,0
5,0

5,0
5,0

5,1
5,1

5,2
5,2

The declared NPSH values were obtained in the laboratory and refer to a single service pump
HHn, HHm = class of risk value referred to the required rated and maximum capacity (Tab.7 para 7.3.2 EN12845)
Check that NPSHd NPSHr+1m is satisfied at the maximum requested capacity

43

5,3
5,3

5,8
5,8

12845_1p-fhf100-2p50_NPSHr-en_a_th

Lowara
HYDRA
ULIC PERFORMANCE T
ABLE A
T 50 HZ (POSITIVE SUCTION HEAD)
HYDRAULIC
TABLE
AT
TABELLA DI PRESTAZIONI IDRAULICHE NETTE GRUPPI EN12845 SERIE FHF125 2 poli 50 Hz 1 POMPA DI SERVIZIO, ASP ESCLUSA INST SOPRA
GEN../FHF 125 BOOSTER SETS SERIES
0

384

403

360

342

291

m3/h 0 120

kW

PUMP

PUMP

ELECTRIC

6716 6783 7500 7983 8400 8667 8966 9333 9583 10000 10333 10833

6400

6000

5700

Q = DELIVERY

POWER

HH10n

4850

FHF..

HH9n

l/min 0 2000 2500 4800

RATED

HH6n

TYPE

HH8n

RISK CLASS
HH7n

150

288

407

450

479

504

520

538

560

575

600

620

650

H = TOTAL HEAD METRES COLUMN OF WATER

125-200/300

125-200/D180

1 x 30

32,8 29,8 28,4

19,8

19,6

15,8

14,4

12,6 11,2 10,9

125-200/450

125-200/D206

1 x 45

47,2 44,8 43,5

34,8

34,6

30,3

28,6

26,4 24,5 24,1 19,7 16,6 13,9 12,1

7,6

125-200/550

125-200/D216

1 x 55

57,4 55,1 54,0

45,6

45,4

41,0

39,3

36,8 34,8 34,3 29,3 25,6 22,3 20,0 17,4 14,1

125-270/750

125-270/D224

1 x 75

65,1

63,7

56,0

55,8

51,5

49,8

47,3 45,3 44,8 39,8 36,1 32,7 30,5 27,9 24,6 22,3

125-270/900

125-270/D237

1 x 90

75,3

73,6

67,0

66,8

62,8

61,1

58,8 56,8 56,3 51,2 47,4 43,8 41,4 38,5 34,8 32,2

27,5

125-270/1100 125-270/D253

1 x 110

88,2

85,4

79,2

79,0

75,1

73,5

71,2 69,2 68,8 63,5 59,5 55,7 53,0 49,9 45,8 42,8

37,6

33,1

125-270/1320 125-270/D266

1 x 132

97,5

94,8

88,6

88,4

84,7

83,2

81,1 79,2 78,8 74,0 70,3 66,8 64,5 61,7 58,0 55,4

50,7

46,8

Performance levels relative to set with 1 service pump running and compliant with ISO 9906 - Annex A.
HHn = class of risk value referred to the required rated capacity (Tab.7 para 7.3.2 EN12845)
Inlet pressure drops must be deducted. Make sure that these drops, added to the difference in level (max. 3.2m), are less than 4.5m
The values shown identify performance levels according to the reference standard EN12845.

40,5

12845_1pg-sp-fhf125-2p50-en_a_th

HYDRA
ULIC PERFORMANCE T
ABLE A
T 50 HZ (SUCTION LIF
T)
HYDRAULIC
TABLE
AT
LIFT)
TABELLA DI PRESTAZIONI IDRAULICHE NETTE GRUPPI EN12845 SERIE FHF125 2 poli 50 Hz 1 POMPA DI SERVIZIO, ASP ESCLUSA INST SOTTOB
GEN../FHF 125 BOOSTER SETS SERIES
0

342

291

PUMP

403

m3/h 0 120

kW

ELECTRIC

384

360

PUMP

Q = DELIVERY

POWER

6716 6783 7500 7983 8400 8667 8966 9333 9583 10000 10333 10833

4850

FHF..

6400

l/min 0 2000 2500 4800

RATED

HH10n

6000

TYPE

HH9n

5700

HH7n

HH8n

RISK CLASS

HH6n

150

288

407

450

479

504

520

538

560

575

600

620

650

H = TOTAL HEAD METRES COLUMN OF WATER

125-200/300

125-200/D180

1 x 30

32,8 30,3 29,1

22,2

22,0

19,1

18,0

16,6 15,6 15,3 13,0

125-200/450

125-200/D206

1 x 45

47,2 45,3 44,2

37,1

37,0

33,5

32,2

30,4 28,9 28,6 25,2 22,7 20,6 19,2

125-200/550

125-200/D216

1 x 55

57,4 55,6 54,7

48,0

47,8

44,2

42,8

40,8 39,2 38,8 34,7 31,7 29,0 27,1 25,0 22,3

125-270/750

125-270/D224

1 x 75

65,1

64,4

58,4

58,2

54,7

53,3

51,3 49,7 49,3 45,2 42,2 39,5 37,6 35,5 32,8 30,9

125-270/900

125-270/D237

1 x 90

75,3

74,4

69,3

69,2

66,0

64,7

62,8 61,2 60,8 56,6 53,5 50,5 48,5 46,1 43,0 40,8

36,9

125-270/1100 125-270/D253

1 x 110

88,2

86,2

81,5

81,4

78,4

77,1

75,2 73,6 73,2 68,9 65,6 62,4 60,1 57,5 54,0 51,5

47,0 43,1

125-270/1320 125-270/D266

1 x 132

97,5

95,5

90,9

90,8

88,0

86,8

85,1 83,6 83,3 79,4 76,4 73,5 71,6 69,3 66,2 64,0

60,1 56,8

Performance levels relative to set with 1 service pump running and compliant with ISO 9906 - Annex A.
HHn = class of risk value referred to the required rated capacity (Tab.7 para 7.3.2 EN12845)
Inlet pressure drops must be deducted. Make sure these drops are less than 4.5m
The values shown identify performance levels according to the reference standard EN12845.

51,4

12845_1pg-st-fhf125-2p50-en_a_th

TABELLA DI PRESTAZIONI IDRAULICHE NPSHr EN12845 SERIE FHF125 2 poli 50 Hz 1 POMPA DI SERVIZIO

NPSH REQUIRED FOR PUMP SERIES FHF 125

PUMP

HH8m

HH9m

l/min 0

2000

2500

4800

4850

5700

6000

6400

6716

6783

7500

7983

8400

8667

8966

9333

9583

m3/h 0

120

150

288

291

342

360

384

403

407

450

479

504

520

538

560

575

HH7m

HH6m

PUMP

HH10n

ELECTRIC

HH9n

POWER

HH8n

FHF..

HH7n

RATED

HH6n

TYPE

HH10m

RISK CLASS

Q = DELIVERY
10000 10333 10833
600

620

650

NPSHr [METRES COLUMN OF WATER]

kW

125-200/300

125-200/D180

1 x 30

6,5

6,8

8,5

8,5

9,1

9,3

9,6

9,9

9,9

10,4

125-200/450

125-200/D206

1 x 45

6,1

6,2

7,1

7,1

7,6

7,7

8,0

8,3

8,3

8,9

9,5

10,0

10,4

125-200/550

125-200/D216

1 x 55

6,1

6,2

7,1

7,1

7,6

7,7

8,0

8,3

8,3

8,9

9,5

10,0

10,4

10,8

11,5

125-270/750

125-270/D224

1 x 75

7,8

8,3

8,3

8,5

8,6

8,7

8,8

8,9

9,3

9,7

10,1

10,5

11,1

11,9

12,7

125-270/900

125-270/D237

1 x 90

6,0

6,9

6,9

7,2

7,3

7,5

7,7

7,7

8,1

8,4

8,8

9,0

9,4

9,9

10,4

11,4

125-270/1100 125-270/D253

1 x 110

6,0

6,9

6,9

7,2

7,3

7,5

7,7

7,7

8,1

8,4

8,8

9,0

9,4

9,9

10,4

11,4

12,5

125-270/1320 125-270/D266

1 x 132

6,0

6,9

6,9

7,2

7,3

7,5

7,7

7,7

8,1

8,4

8,8

9,0

9,4

9,9

10,4

11,4

12,5

The declared NPSH values were obtained in the laboratory and refer to a single service pump
HHn, HHm = class of risk value referred to the required rated and maximum capacity (Tab.7 para 7.3.2 EN12845)
Check that NPSHd NPSHr+1m is satisfied at the maximum requested capacity

44

14,8

12845_1p-fhf125-2p50_NPSHr-en_a_th

Lowara
GEN../FHF 32-80 BOOSTER SETS
TABELLA DATI ELETTRICI GRUPPI GEN../FHF 2 poli 50 Hz
ELECTRICAL DA
TA T
ABLE A
T 50 Hz
DAT
TABLE
AT
ELECTRIC
SERVICE PUMP
3 X 400 V
TYPE
FHF..
ELECTRIC
PUMP

32-125/07
32-125/11
32-160/15
32-160/22
32-200/30
32-200/40
40-125/11
40-125/15
40-125/22
40-160/30
40-160/40
40-200/55
40-200/75
40-250/110A
40-250/110
40-250/150
50-125/22
50-125/30
50-125/40
50-160/55
50-160/75
50-200/110A
50-200/110
50-250/150
50-250/185
50-250/220
65-125/40
65-125/55
65-125/75
65-160/110A
65-160/110
65-160/150
65-200/150
65-200/185
65-200/220
65-250/220
65-250/300
65-250/370
80-160/150
80-160/185
80-200/220
80-200/300
80-250/370
80-250/450
80-250/550

PUMP

32-125/D119
32-125/D136
32-160/D150
32-160/D164
32-200/D188
32-200/D204
40-125/D112
40-125/D122
40-125/D143
40-160/D159
40-160/D171
40-200/D190
40-200/D209
40-250/D218
40-250/D233
40-250/D251
50-125/D119
50-125/D130
50-125/D139
50-160/D158
50-160/D174
50-200/D197
50-200/D209
50-250/D224
50-250/D237
50-250/D250
65-125/D121
65-125/D129
65-125/D140
65-160/D161
65-160/D168
65-160/D178
65-200/D187
65-200/D198
65-200/D210
65-250/D220
65-250/D241
65-250/D258
80-160/D163
80-160/D173
80-200/D189
80-200/D207
80-250/D225
80-250/D238
80-250/D256

ELECTRIC

CURRENT

JOCKEY PUMP
3 X 400 V

ABSORBED SET
3 X 400V

NOMINAL
POWER
Pn
kW

In
A

TYPE

Pn
kW

In
A

GEN..10
A

GEN..11
A

GEN..20
A

GEN..21
A

0,75
1,1
1,5
2,2
3
4
1,1
1,5
2,2
3
4
5,5
7,5
11
11
15
2,2
3
4
5,5
7,5
11
11
15
18,5
22
4
5,5
7,5
11
11
15
15
18,5
22
22
30
37
15
18,5
22
30
37
45
55

2,15
2,61
3,02
4,68
5,77
7,59
2,61
3,02
4,68
5,77
7,59
10,70
13,90
19,80
19,80
26,20
4,68
5,77
7,59
10,70
13,90
19,80
19,80
26,20
33,40
41,70
7,59
10,70
13,90
19,80
19,80
26,20
26,20
33,40
41,70
41,70
54,00
65,00
26,20
33,40
41,70
54,00
65,00
80,00
99,00

SV206
SV206
SV206
SV206
SV206
SV209
SV206
SV206
SV206
SV206
SV206
SV206
SV209
SV209
SV209
SV209
SV206
SV206
SV206
SV206
SV206
SV209
SV209
SV209
SV209
SV209
SV206
SV206
SV206
SV206
SV206
SV206
SV206
SV209
SV209
SV209
SV209
SV212
SV407
SV407
SV407
SV409
SV409
SV409
SV413

0,75
0,75
0,75
0,75
0,75
1,1
0,75
0,75
0,75
0,75
0,75
0,75
1,1
1,1
1,1
1,1
0,75
0,75
0,75
0,75
0,75
1,1
1,1
1,1
1,1
1,1
0,75
0,75
0,75
0,75
0,75
0,75
0,75
1,1
1,1
1,1
1,1
1,5
1,1
1,1
1,1
1,5
1,5
1,5
2,2

2,02
2,02
2,02
2,02
2,02
2,61
2,02
2,02
2,02
2,02
2,02
2,02
2,61
2,61
2,61
2,61
2,02
2,02
2,02
2,02
2,02
2,61
2,61
2,61
2,61
2,61
2,02
2,02
2,02
2,02
2,02
2,02
2,02
2,61
2,61
2,61
2,61
3,45
2,61
2,61
2,61
3,45
3,45
3,45
5,03

2,15
2,61
3,02
4,68
5,77
7,59
2,61
3,02
4,68
5,77
7,59
10,70
13,90
19,80
19,80
26,20
4,68
5,77
7,59
10,70
13,90
19,80
19,80
26,20
33,40
41,70
7,59
10,70
13,90
19,80
19,80
26,20
26,20
33,40
41,70
41,70
54,00
65,00
26,20
33,40
41,70
54,00
65,00
80,00
99,00

4,17
4,63
5,04
6,70
7,79
10,20
4,63
5,04
6,70
7,79
9,61
12,72
16,51
22,41
22,41
28,81
6,70
7,79
9,61
12,72
15,92
22,41
22,41
28,81
36,01
44,31
9,61
12,72
15,92
21,82
21,82
28,22
28,22
36,01
44,31
44,31
56,61
68,45
28,81
36,01
44,31
57,45
68,45
83,45
104,03

4,30
5,22
6,04
9,36
11,54
15,18
5,22
6,04
9,36
11,54
15,18
21,40
27,80
39,60
39,60
52,40
9,36
11,54
15,18
21,40
27,80
39,60
39,60
52,40
66,80
83,40
15,18
21,40
27,80
39,60
39,60
52,40
52,40
66,80
83,40
83,40
108,00
130,00
52,40
66,80
83,40
108,00
130,00
160,00
198,00

6,32
7,24
8,06
11,38
13,56
17,79
7,24
8,06
11,38
13,56
17,20
23,42
30,41
42,21
42,21
55,01
11,38
13,56
17,20
23,42
29,82
42,21
42,21
55,01
69,41
86,01
17,20
23,42
29,82
41,62
41,62
54,42
54,42
69,41
86,01
86,01
110,61
133,45
55,01
69,41
86,01
111,45
133,45
163,45
203,03

The current indicated is the maximum current absorbed by the electric pumps.

ENELP-FHF32-80_2p50-en_b_te

45

Lowara
GEN../FHF 100-125 BOOSTER SETS
TABELLA DATI ELETTRICI GRUPPI GEN../FHF 2 poli 50 Hz
ELECTRICAL DA
TA T
ABLE A
T 50 Hz
DAT
TABLE
AT
ELECTRIC
SERVICE PUMP
3 X 400 V
TYPE
FHF..
ELECTRIC

Pn

CURRENT
ABSORBED SET
3 X 400V

TYPE

Pn

In

GEN..10

GEN..11

GEN..20

GEN..21

kW

SV407
SV407
SV407
SV407
SV407
SV407
SV409
SV407
SV409
SV409
SV413
SV413
SV805
SV805
SV806
SV806
SV807
SV807
SV809

1,1
1,1
1,1
1,1
1,1
1,1
1,5
1,1
1,5
1,5
2,2
2,2
2,2
2,2
3
3
4
4
4

2,61
2,61
2,61
2,61
2,61
2,61
3,45
2,61
3,45
3,45
5,03
5,03
5,03
5,03
6,01
6,01
8,02
8,02
8,02

33,40
41,70
54,00
33,40
54,00
65,00
80,00
54,00
80,00
99,00
133,00
157,00
54,00
80,00
99,00
133,00
157,00
196,00
235,00

36,01
44,31
56,61
36,01
56,61
67,61
83,45
56,61
83,45
102,45
138,03
162,03
59,03
85,03
105,01
139,01
165,02
204,02
243,02

66,80
83,40
108,00
66,80
108,00
130,00
160,00
108,00
160,00
198,00
266,00
314,00
108,00
160,00
198,00
266,00
314,00
392,00
470,00

69,41
86,01
110,61
69,41
110,61
132,61
163,45
110,61
163,45
201,45
271,03
319,03
113,03
165,03
204,01
272,01
322,02
400,02
478,02

PUMP

PUMP

100-160/185
100-160/220
100-160/300
100-200/185
100-200/300
100-200/370
100-200/450
100-250/300
100-250/450
100-250/550
100-250/750
100-250/900
125-200/300
125-200/450
125-200/550
125-270/750
125-270/900
125-270/1100
125-270/1320

In

ELECTRIC
JOCKEY PUMP
3 X 400 V

100-160/D150
100-160/D165
100-160/D185
100-200/D168
100-200/D192
100-200/D203
100-200/D213
100-250/D200
100-250/D221
100-250/D235
100-250/D254
100-250/D267
125-200/D180
125-200/D206
125-200/D216
125-270/D224
125-270/D237
125-270/D253
125-270/D266

kW

18,5
22
30
18,5
30
37
45
30
45
55
75
90
30
45
55
75
90
110
132

33,40
41,70
54,00
33,40
54,00
65,00
80,00
54,00
80,00
99,00
133,00
157,00
54,00
80,00
99,00
133,00
157,00
196,00
235,00

The current indicated is the maximum current absorbed by the electric pumps.

ENELP-FHF100-125_2p50-en_b_te

46

Lowara
Fire-fighting
booster sets
EN 12845

MARKET SECTORS
CIVIL, INDUSTRIAL
APPLICA
TIONS
APPLICATIONS
Fixed fire-fighting systems.

Automatic Sprinkler systems.

GEN..10/FHF
Series

SPECIFICA
TIONS
SPECIFICATIONS
Flow up to 650 m3/h.
Head up to 100 m.
Panel supply power voltage:
3 x 400V 10%.

Motor start-up :

- Direct for powers up to 22 kW


inclusive for pump (GEND...).
- Star/Delta for higher
powers (GENY... set).

Electric service pump

Frequency: 50 Hz.
Voltage for controls outside panel:
24 Vac.

with horizontal axis


axis:
- FHF Series (motor protection
grade IP55).

Maximum running pressure:


12 bar.

Protection grade:

- electric panel: IP54.

Electric pumps maximum power


132 kW.

47

Lowara
GEN..10/FHF 32-80 SERIES
FIRE-FIGHTING BOOSTER SETS EN 12845

48

Lowara
GEN..10/FHF 32-80 SERIES
FIRE-FIGHTING BOOSTER SETS EN 12845
GEN..10

DRW

DNA

DNM

N
FHF32-125/07

R 2"

Rp 1" 1/2

740

80

212

360

820

773

1347

FHF32-125/11

R 2"

Rp 1" 1/2

740

80

212

360

820

773

1347

FHF32-160/15

R 2"

Rp 1" 1/2

840

80

232

390

920

813

1387

FHF32-160/22

R 2"

Rp 1" 1/2

840

80

232

390

920

813

1387

FHF32-200/30

R 2"

Rp 1" 1/2

840

80

260

390

920

861

1435

FHF32-200/40

R 2"

Rp 1" 1/2

840

80

260

390

920

861

1435

FHF40-125/11

65

65

740

80

212

360

820

994

1582

FHF40-125/15

65

65

840

80

212

390

920

994

1582

FHF40-125/22

65

65

840

80

212

390

920

994

1582

FHF40-160/30

65

65

840

80

232

390

920

1034

1622

FHF40-160/40

65

65

840

80

232

390

920

1034

1622

FHF40-200/55

65

65

940

100

260

450

1040

1082

1670

FHF40-200/75

65

65

940

100

260

450

1040

1082

1670

FHF40-250/110A

65

65

1175

100

280

540

1275

1147

1735

FHF40-250/110

65

65

1175

100

280

540

1275

1147

1735

FHF40-250/150

65

65

1175

100

280

540

1275

1147

1735

FHF50-125/22

65

65

840

100

232

390

940

1116

1704

FHF50-125/30

65

65

840

100

232

390

940

1116

1704

FHF50-125/40

65

65

840

100

232

390

940

1116

1704

FHF50-160/55

65

65

940

100

260

450

1040

1164

1752

FHF50-160/75

65

65

940

100

260

450

1040

1164

1752

FHF50-200/110A

65

65

1060

100

260

490

1160

1184

1772

FHF50-200/110

65

65

1060

100

260

490

1160

1184

1772

FHF50-250/150

65

65

1175

100

280

540

1275

1229

1817

FHF50-250/185

65

65

1175

100

280

540

1275

1229

1817

FHF50-250/220

65

65

1175

100

280

540

1275

1229

1817

FHF65-125/40

80

80

825

100

260

390

925

1221

1815

FHF65-125/55

80

80

925

100

260

450

1025

1221

1815

FHF65-125/75

80

80

925

100

260

450

1025

1221

1815

FHF65-160/110A

80

80

1175

100

260

540

1275

1241

1835

FHF65-160/110

80

80

1175

100

260

540

1275

1241

1835

FHF65-160/150

80

80

1175

100

260

540

1275

1241

1835

FHF65-200/150

80

80

1175

100

280

540

1275

1286

1880

FHF65-200/185

80

80

1175

100

280

540

1275

1286

1880

FHF65-200/220

80

80

1175

100

280

540

1275

1286

1880

FHF65-250/220

80

80

1160

100

310

540

1260

1341

1935

FHF65-250/300

80

80

1310

100

310

610

1410

1341

1935

FHF65-250/370

80

80

1310

100

310

610

1410

1341

1935

FHF80-160/150

100

100

1175

125

280

540

1300

1354

1961

FHF80-160/185

100

100

1175

125

280

540

1300

1354

1961

FHF80-200/220

100

100

1175

125

280

540

1300

1379

1986

FHF80-200/300

100

100

1325

125

310

610

1450

1409

2016

FHF80-250/370

100

100

1310

125

310

610

1435

1439

2046

FHF80-250/450

100

100

1310

125

365

610

1435

1494

2101

FHF80-250/550
2
100
Dimensions in mm. Tolerance 10 mm.

100

1510

125

390

660

1635

1519

2126
gen10_fhf-en_d_td

49

Lowara
GEN..10/FHF 100-125 SERIES
FIRE-FIGHTING BOOSTER SETS EN 12845

GEN..10

DRW

DNM

FHF100-160/185

125

125

1266

125

298

550

1391

1518

2138

FHF100-160/220

125

125

1315

125

298

550

1440

1518

2138

FHF100-160/300

125

125

1435

125

298

550

1560

1518

2138

FHF100-200/185

125

125

1266

125

273

550

1391

1493

2113

FHF100-200/300

125

125

1435

125

273

550

1560

1493

2113

FHF100-200/370

125

125

1435

125

273

550

1560

1493

2113

FHF100-200/450

125

125

1470

125

318

670

1595

1538

2158

FHF100-250/300

125

125

1435

140

298

550

1575

1518

2138

FHF100-250/450

125

125

1470

140

298

550

1610

1518

2138

FHF100-250/550

125

125

1575

140

343

670

1715

1563

2183

FHF100-250/750

125

125

1650

140

373

740

1790

1593

2213

FHF100-250/900

125

125

1650

140

373

740

1790

1593

2213

FHF125-200/300

150

150

1495

140

323

550

1635

1675

2309

FHF125-200/450

150

150

1530

140

343

670

1670

1695

2329

FHF125-200/550

150

150

1635

140

343

670

1775

1695

2329

FHF125-270/750

150

150

1710

140

423

750

1850

1815

2449

FHF125-270/900

150

150

1710

140

423

750

1850

1815

2449

FHF125-270/1100

150

150

1850

140

478

870

1990

1870

2504

150

1850

140

478

870

1990

1870

2504

FHF125-270/1320
150
Dimensions in mm. Tolerance 10 mm.

gen10_fhf100-en_c_td

50

Lowara
Fire-fighting
booster sets
EN 12845

MARKET SECTORS
CIVIL, INDUSTRIAL
APPLICA
TIONS
APPLICATIONS
Fixed fire-fighting systems.
Automatic Sprinkler systems.

GEN..11/FHF
Series

SPECIFICA
TIONS
SPECIFICATIONS
Flow up to 650 m3/h.
Head up to 100 m.
Panel supply power voltage:
3 x 400V 10%.

Motor start-up :

- Direct for powers up to 22 kW


inclusive for pump (GEND...).
- Star/Delta for higher
powers (GENY... set).

Electric service pump

Frequency: 50 Hz.
Voltage for controls outside panel:
24 Vac.

with horizontal axis


axis:
- FHF Series (motor protection
grade IP55).

ey pump
Electric jock
jockey

Protection grade:

- electric panel: IP54.

Electric pumps maximum power


132 kW.

with vertical axis


axis:
- SV Series (motor protection
grade IP55).

Maximum running pressure:


12 bar.

51

Lowara
GEN..11/FHF 32-80 SERIES
FIRE-FIGHTING BOOSTER SETS EN 12845

52

Lowara
GEN..11/FHF 32-80 SERIES
FIRE-FIGHTING BOOSTER SETS EN 12845
GEN..11

DRW DNA

DNP

DNM

A1

N
FHF32-125/07

R 2"

Rp 1"

Rp 1" 1/2 320

260

240

590

45

225

312 1400 370

950

955

873 1447

FHF32-125/11

R 2"

Rp 1"

Rp 1" 1/2 320

260

240

590

45

225

312 1400 370

950

955

873 1447

FHF32-160/15

R 2"

Rp 1"

Rp 1" 1/2 327

253

240

650

65

225

332 1400 370

950 1035 913 1487

FHF32-160/22

R 2"

Rp 1"

Rp 1" 1/2 327

253

240

650

65

225

332 1400 370

950 1035 913 1487

FHF32-200/30

R 2"

Rp 1"

Rp 1" 1/2 327

253

240

650

65

225

360 1400 370

950 1035 961 1535

FHF32-200/40

R 2"

Rp 1"

Rp 1" 1/2 327

253

240

650

65

225

360 1400 370

950 1035 961 1535

FHF40-125/11

65

Rp 1"

65

320

260

240

590

45

225

312 1400 370

950

FHF40-125/15

65

Rp 1"

65

327

253

240

650

65

225

312 1400 370

950 1035 1094 1682

FHF40-125/22

65

Rp 1"

65

327

253

240

650

65

225

312 1400 370

950 1035 1094 1682

FHF40-160/30

65

Rp 1"

65

327

253

240

650

65

225

332 1400 370

950 1035 1134 1722

FHF40-160/40

65

Rp 1"

65

327

253

240

650

65

225

332 1400 370

950 1035 1134 1722

FHF40-200/55

65

Rp 1"

65

338

222

240

710

85

245

380 1420 440 1000 1135 1202 1790

955 1094 1682

FHF40-200/75

65

Rp 1"

65

338

222

240

710

85

245

380 1420 440 1000 1135 1202 1790

FHF40-250/110A

65

Rp 1"

65

435

295

280

890

105

245

400 1420 440 1170 1375 1267 1855

FHF40-250/110

65

Rp 1"

65

435

295

280

890

105

245

400 1420 440 1170 1375 1267 1855

FHF40-250/150

65

Rp 1"

65

435

295

280

890

105

245

400 1570 440 1170 1375 1267 1855

FHF50-125/22

65

Rp 1"

65

327

253

240

650

65

225

332 1400 370

950 1055 1216 1804

FHF50-125/30

65

Rp 1"

65

327

253

240

650

65

225

332 1400 370

950 1055 1216 1804

FHF50-125/40

65

Rp 1"

65

327

253

240

650

65

225

332 1400 370

950 1055 1216 1804

FHF50-160/55

65

Rp 1"

65

338

222

240

710

85

245

380 1420 440 1000 1135 1284 1872

FHF50-160/75

65

Rp 1"

65

338

222

240

710

85

245

380 1420 440 1000 1135 1284 1872

FHF50-200/110A

65

Rp 1"

65

435

295

280

790

105

245

380 1420 440 1170 1275 1304 1892

FHF50-200/110

65

Rp 1"

65

435

295

280

790

105

245

380 1420 440 1170 1275 1304 1892

FHF50-250/150

65

Rp 1"

65

435

295

280

890

105

245

400 1570 440 1170 1375 1349 1937

FHF50-250/185

65

Rp 1"

65

435

295

280

890

105

245

400 1750 440 1170 1375 1349 1937

FHF50-250/220

65

Rp 1"

65

435

295

280

890

105

245

400 1750 440 1170 1375 1349 1937

FHF65-125/40

80

Rp 1"

80

323

187

240

650

50

225

360 1400 440

FHF65-125/55

80

Rp 1"

80

338

222

240

710

70

245

380 1420 440 1000 1120 1341 1935

950 1040 1321 1915

FHF65-125/75

80

Rp 1"

80

338

222

240

710

70

245

380 1420 440 1000 1120 1341 1935

FHF65-160/110A

80

Rp 1"

80

435

295

280

890

105

245

380 1420 440 1170 1375 1361 1955

FHF65-160/110

80

Rp 1"

80

435

295

280

890

105

245

380 1420 440 1170 1375 1361 1955

FHF65-160/150

80

Rp 1"

80

435

295

280

890

105

245

380 1570 440 1170 1375 1361 1955

FHF65-200/150

80

Rp 1"

80

435

295

280

890

105

245

400 1570 440 1170 1375 1406 2000

FHF65-200/185

80

Rp 1"

80

435

295

280

890

105

245

400 1570 440 1170 1375 1406 2000

FHF65-200/220

80

Rp 1"

80

435

295

280

890

105

245

400 1570 440 1170 1375 1406 2000

FHF65-250/220

80

Rp 1"

80

435

295

280

890

90

245

430 1750 440 1170 1360 1461 2055

FHF65-250/300

80

Rp 1"

80

430

250

280

990

115

245

430 1750 490 1170 1485 1461 2055

FHF65-250/370

80

Rp 1"

80

430

250

280

990

115

245

430 1940 490 1170 1485 1461 2055

FHF80-160/150

100 Rp 1" 1/4

100

435

295

280

890

105

245

400 1570 440 1170 1400 1474 2081

FHF80-160/185

100 Rp 1" 1/4

100

435

295

280

890

105

245

400 1750 440 1170 1400 1474 2081

FHF80-200/220

100 Rp 1" 1/4

100

435

295

280

890

105

245

400 1750 440 1170 1400 1499 2106

FHF80-200/300

100 Rp 1" 1/4

100

430

250

280

990

130

245

430 1750 490 1170 1525 1529 2136

FHF80-250/370

100 Rp 1" 1/4

100

430

250

280

990

115

245

430 1940 490 1170 1510 1559 2166

FHF80-250/450

100 Rp 1" 1/4

100

430

250

330

990

115

245

485 1940 490 1170 1560 1614 2221

FHF80-250/550
2
100 Rp 1" 1/4
Dimensions in mm. Tolerance 10 mm.

100

525

275

330 1120 155

265

530 1960 600 1400 1730 1659 2266


gen11_fhf-en_d_td

53

Lowara
GEN..11/FHF 100-125 SERIES
FIRE-FIGHTING BOOSTER SETS EN 12845

54

Lowara
GEN..11/FHF 100-125 SERIES
FIRE-FIGHTING BOOSTER SETS EN 12845
GEN..11

DRW DNA

DNP

DNM

A1

N
FHF100-160/185

125

Rp 1"1/4

125

411

269

291

890

85

245

418

1750 490 1170 1391 1638 2258

FHF100-160/220

125

Rp 1"1/4

125

411

269

190

1020

105

245

418

1750 490 1170 1440 1638 2258

FHF100-160/300

125

Rp 1"1/4

125

411

269

310

1020

105

245

418

1750 490 1170 1560 1638 2258

FHF100-200/185

125

Rp 1"1/4

125

411

269

291

890

85

245

393

1750 490 1170 1391 1613 2233

FHF100-200/300

125

Rp 1"1/4

125

411

269

310

1020

105

245

393

1750 490 1170 1560 1613 2233

FHF100-200/370

125

Rp 1"1/4

125

411

269

310

1020

105

245

393

1750 490 1170 1560 1613 2233

FHF100-200/450

125

Rp 1"1/4

125

451

249

215

1130

125

245

438

1750 600 1300 1595 1658 2278

FHF100-250/300

125

Rp 1"1/4

125

411

269

310

1020

105

245

418

1750 490 1170 1575 1638 2258

FHF100-250/450

125

Rp 1"1/4

125

411

269

345

1020

105

245

418

1750 490 1170 1610 1638 2258

FHF100-250/550

125

Rp 1"1/4

125

451

249

320

1130

125

245

463

1750 600 1300 1715 1683 2303

FHF100-250/750

125

Rp 1"1/4

125

620

220

400

1110

140

265

513

600 1440 1790 1733 2353

FHF100-250/900

125

Rp 1"1/4

125

620

220

400

1110

140

265

513

600 1440 1790 1733 2353

FHF125-200/300

150

Rp 1"1/2

150

411

269

370

1020

105

250

443

1750 490 1170 1635 1795 2429

FHF125-200/450

150

Rp 1"1/2

150

451

249

275

1130

125

250

463

1750 600 1300 1670 1815 2449

FHF125-200/550

150

Rp 1"1/2

150

451

249

380

1130

125

250

463

1750 600 1300 1775 1815 2449

FHF125-270/750

150

Rp 1"1/2

150

620

220

370

1400

80

270

563

FHF125-270/900

150

Rp 1"1/2

150

620

220

370

1400

80

270

563

600 1440 1850 1955 2589

FHF125-270/1100

150

Rp 1"1/2

150

650

220

510

1400

80

270

618

650 1520 1990 2010 2644

FHF125-270/1320
3
150 Rp 1"1/2
Dimensions in mm. Tolerance 10 mm.

150

650

220

510

1400

80

270

618

650 1520 1990 2010 2644

600 1440 1850 1955 2589

gen11_fhf100-en_d_td

55

Lowara

56

Lowara
Fire-fighting
booster sets
EN 12845

MARKET SECTORS
CIVIL, INDUSTRIAL
APPLICA
TIONS
APPLICATIONS
Fixed fire-fighting systems.
Automatic Sprinkler systems.

GEN..20/FHF
Series

SPECIFICA
TIONS
SPECIFICATIONS
Flow up to 1300 m3/h.
Head up to 100 m.
Panel supply power voltage:
3 x 400V 10%.

Motor start-up :

- Direct for powers up to 22 kW


inclusive for pump (GEND...).
- Star/Delta for higher
powers (GENY... set).

Electric service pump

Frequency: 50 Hz.
Voltage for controls outside panel:
24 Vac.

with horizontal axis


axis:
- FHF Series (motor protection
grade IP55).

Maximum running pressure:

Protection grade:

12 bar.

- electric panel: IP54.

Electric pumps maximum power


132 kW.

57

Lowara
GEN..20/FHF 32-80 SERIES
FIRE-FIGHTING BOOSTER SETS EN 12845

58

Lowara
GEN..20/FHF 32-80 SERIES
FIRE-FIGHTING BOOSTER SETS EN 12845
GEN..20

DRW

DNA

DNM

Q
1459

N
FHF32-125/07

R 2"

R 2"

345

240

590

45

312

1400

480

1170

955

879

FHF32-125/11

R 2"

R 2"

345

240

590

45

312

1400

480

1170

955

879

1459

FHF32-160/15

R 2"

R 2"

345

240

650

65

332

1400

480

1170

1035

919

1499

FHF32-160/22

R 2"

R 2"

345

240

650

65

332

1400

480

1170

1035

919

1499

FHF32-200/30

R 2"

R 2"

345

240

650

65

360

1400

480

1170

1035

967

1547

FHF32-200/40

R 2"

R 2"

345

240

650

65

360

1400

480

1170

1035

967

1547

FHF40-125/11

65

65

335

240

590

45

312

1400

540

1210

955

1094

1682

FHF40-125/15

65

65

335

240

650

65

312

1400

540

1210

1035

1094

1682

FHF40-125/22

65

65

335

240

650

65

312

1400

540

1210

1035

1094

1682

FHF40-160/30

65

65

335

240

650

65

332

1400

540

1210

1035

1134

1722

FHF40-160/40

65

65

335

240

650

65

332

1400

540

1210

1035

1134

1722

FHF40-200/55

65

65

335

240

710

85

380

1420

540

1210

1135

1202

1790

FHF40-200/75

65

65

335

240

710

85

380

1420

540

1210

1135

1202

1790

FHF40-250/110A

65

65

385

280

890

105

400

1420

630

1400

1375

1267

1855

FHF40-250/110

65

65

385

280

890

105

400

1420

630

1400

1375

1267

1855

FHF40-250/150

65

65

385

280

890

105

400

1570

630

1400

1375

1267

1855

FHF50-125/22

65

80

335

240

650

65

332

1400

540

1210

1055

1223

1817

FHF50-125/30

65

80

335

240

650

65

332

1400

540

1210

1055

1223

1817

FHF50-125/40

65

80

335

240

650

65

332

1400

540

1210

1055

1223

1817

FHF50-160/55

65

80

335

240

710

85

380

1420

540

1210

1135

1291

1885

FHF50-160/75

65

80

335

240

710

85

380

1420

540

1210

1135

1291

1885

FHF50-200/110A

65

80

385

280

790

105

380

1420

630

1400

1275

1311

1905

FHF50-200/110

65

80

385

280

790

105

380

1420

630

1400

1275

1311

1905

FHF50-250/150

65

80

385

280

890

105

400

1570

630

1400

1375

1356

1950

FHF50-250/185

65

80

385

280

890

105

400

1750

630

1400

1375

1356

1950

FHF50-250/220

65

80

385

280

890

105

400

1750

630

1400

1375

1356

1950

FHF65-125/40

80

100

335

240

650

50

360

1400

540

1210

1040

1333

1940

FHF65-125/55

80

100

335

240

710

70

380

1420

540

1210

1120

1353

1960

FHF65-125/75

80

100

335

240

710

70

380

1420

540

1210

1120

1353

1960

FHF65-160/110A

80

100

350

280

890

105

380

1420

700

1400

1375

1373

1980

FHF65-160/110

80

100

350

280

890

105

380

1420

700

1400

1375

1373

1980

FHF65-160/150

80

100

350

280

890

105

380

1570

700

1400

1375

1373

1980

FHF65-200/150

80

100

350

280

890

105

400

1570

700

1400

1375

1418

2025

FHF65-200/185

80

100

350

280

890

105

400

1570

700

1400

1375

1418

2025

FHF65-200/220

80

100

350

280

890

105

400

1570

700

1400

1375

1418

2025

FHF65-250/220

80

100

350

280

890

90

430

1750

700

1400

1360

1473

2080

FHF65-250/300

80

100

425

280

990

115

430

1750

700

1550

1485

1473

2080

FHF65-250/370

80

100

425

280

990

115

430

1940

700

1550

1485

1473

2080

FHF80-160/150

100

125

350

280

890

105

400

1570

700

1400

1400

1487

2107

FHF80-160/185

100

125

350

280

890

105

400

1750

700

1400

1400

1487

2107

FHF80-200/220

100

125

350

280

890

105

400

1750

700

1400

1400

1512

2132

FHF80-200/300

100

125

425

280

990

130

430

1750

700

1550

1525

1542

2162

FHF80-250/370

100

125

425

280

990

115

430

1940

700

1550

1510

1572

2192

FHF80-250/450

100

125

425

330

990

115

485

1940

700

1550

1560

1627

2247

FHF80-250/550
2
100
Dimensions in mm. Tolerance 10 mm.

125

430

330

1120

155

530

1960

820

1680

1730

1672

2292

gen20_fhf-en_e_td

59

Lowara

60

Lowara
Fire-fighting
booster sets
EN 12845

MARKET SECTORS
CIVIL, INDUSTRIAL
APPLICA
TIONS
APPLICATIONS
Fixed fire-fighting systems.
Automatic Sprinkler systems.

GEN..21/FHF
Series

SPECIFICA
TIONS
SPECIFICATIONS
Flow up to 1300 m3/h.
Head up to 100 m.
Panel supply power voltage:
3 x 400V 10%.

Motor start-up :

- Direct for powers up to 22 kW


inclusive for pump (GEND...).
- Star/Delta for higher
powers (GENY... set).

Electric service pump

Frequency: 50 Hz.
Voltage for controls outside panel:
24 Vac.

with horizontal axis


axis:
- FHF Series (motor protection
grade IP55).

ey pump
Electric jock
jockey

Protection grade:

- electric panel: IP54.

Electric pumps maximum power


132 kW.

with vertical axis


axis:
- SV Series (motor protection
grade IP55).

Maximum running pressure:


12 bar.

61

Lowara
GEN..21/FHF 32-80 SERIES
FIRE-FIGHTING BOOSTER SETS EN 12845

62

Lowara
GEN..21/FHF 32-80 SERIES
FIRE-FIGHTING BOOSTER SETS EN 12845
GEN..21

DRW

DNA

DNP

DNM

N
FHF32-125/07

R 2"

Rp 1"

R 2"

350

240

590

45

225

312

1400

370

1440

955

879

1459

FHF32-125/11

R 2"

Rp 1"

R 2"

350

240

590

45

225

312

1400

370

1440

955

879

1459

FHF32-160/15

R 2"

Rp 1"

R 2"

350

240

650

65

225

332

1400

370

1440 1035

919

1499

FHF32-160/22

R 2"

Rp 1"

R 2"

350

240

650

65

225

332

1400

370

1440 1035

919

1499

FHF32-200/30

R 2"

Rp 1"

R 2"

350

240

650

65

225

360

1400

370

1440 1035

967

1547

FHF32-200/40

R 2"

Rp 1"

R 2"

350

240

650

65

225

360

1400

370

1440 1035

967

1547

FHF40-125/11

65

Rp 1"

65

350

240

590

45

225

312

1400

370

1440

1094 1682

FHF40-125/15

65

Rp 1"

65

350

240

650

65

225

312

1400

370

1440 1035 1094 1682

FHF40-125/22

65

Rp 1"

65

350

240

650

65

225

312

1400

370

1440 1035 1094 1682

FHF40-160/30

65

Rp 1"

65

350

240

650

65

225

332

1400

370

1440 1035 1134 1722

FHF40-160/40

65

Rp 1"

65

350

240

650

65

225

332

1400

370

1440 1035 1134 1722

FHF40-200/55

65

Rp 1"

65

335

240

710

85

245

380

1420

440

1550 1135 1202 1790

FHF40-200/75

65

Rp 1"

65

335

240

710

85

245

380

1420

440

1550 1135 1202 1790

FHF40-250/110A

65

Rp 1"

65

400

280

890

105

245

400

1420

440

1680 1375 1267 1855

FHF40-250/110

65

Rp 1"

65

400

280

890

105

245

400

1420

440

1680 1375 1267 1855

FHF40-250/150

65

Rp 1"

65

400

280

890

105

245

400

1570

440

1680 1375 1267 1855

FHF50-125/22

65

Rp 1"

80

350

240

650

65

225

332

1400

370

1440 1055 1223 1817

FHF50-125/30

65

Rp 1"

80

350

240

650

65

225

332

1400

370

1440 1055 1223 1817

FHF50-125/40

65

Rp 1"

80

350

240

650

65

225

332

1400

370

1440 1055 1223 1817

FHF50-160/55

65

Rp 1"

80

335

240

710

85

245

380

1420

440

1550 1135 1291 1885

FHF50-160/75

65

Rp 1"

80

335

240

710

85

245

380

1420

440

1550 1135 1291 1885

FHF50-200/110A

65

Rp 1"

80

400

280

790

105

245

380

1420

440

1680 1275 1311 1905

FHF50-200/110

65

Rp 1"

80

400

280

790

105

245

380

1420

440

1680 1275 1311 1905

FHF50-250/150

65

Rp 1"

80

400

280

890

105

245

400

1570

440

1680 1375 1356 1950

FHF50-250/185

65

Rp 1"

80

400

280

890

105

245

400

1750

440

1680 1375 1356 1950

FHF50-250/220

65

Rp 1"

80

400

280

890

105

245

400

1750

440

1680 1375 1356 1950

FHF65-125/40

80

Rp 1"

100

335

240

650

50

225

360

1400

440

1550 1040 1333 1940

FHF65-125/55

80

Rp 1"

100

335

240

710

70

245

380

1420

440

1550 1120 1353 1960

FHF65-125/75

80

Rp 1"

100

335

240

710

70

245

380

1420

440

1550 1120 1353 1960

FHF65-160/110A

80

Rp 1"

100

400

280

890

105

245

380

1420

440

1680 1375 1373 1980

FHF65-160/110

80

Rp 1"

100

400

280

890

105

245

380

1420

440

1680 1375 1373 1980

FHF65-160/150

80

Rp 1"

100

400

280

890

105

245

380

1570

440

1680 1375 1373 1980

FHF65-200/150

80

Rp 1"

100

400

280

890

105

245

400

1570

440

1680 1375 1418 2025

FHF65-200/185

80

Rp 1"

100

400

280

890

105

245

400

1570

440

1680 1375 1418 2025

FHF65-200/220

80

Rp 1"

100

400

280

890

105

245

400

1570

440

1680 1375 1418 2025

FHF65-250/220

80

Rp 1"

100

400

280

890

90

245

430

1750

440

1680 1360 1473 2080

FHF65-250/300

80

Rp 1"

100

430

280

990

115

245

430

1750

490

1840 1485 1473 2080

FHF65-250/370

80

Rp 1"

100

430

280

990

115

245

430

1940

490

1840 1485 1473 2080

FHF80-160/150

100

Rp 1" 1/4

125

400

280

890

105

245

400

1570

440

1680 1400 1487 2107

FHF80-160/185

100

Rp 1" 1/4

125

400

280

890

105

245

400

1750

440

1680 1400 1487 2107

FHF80-200/220

100

Rp 1" 1/4

125

400

280

890

105

245

400

1750

440

1680 1400 1512 2132

FHF80-200/300

100

Rp 1" 1/4

125

430

280

990

130

245

430

1750

490

1840 1525 1542 2162

FHF80-250/370

100

Rp 1" 1/4

125

430

280

990

115

245

430

1940

490

1840 1510 1572 2192

FHF80-250/450

100

Rp 1" 1/4

125

430

330

990

115

245

485

1940

490

1840 1560 1627 2247

FHF80-250/550
2
100
Rp 1" 1/4
Dimensions in mm. Tolerance 10 mm.

125

450

330

1120

155

265

530

1960

600

2100 1730 1672 2292

955

gen21_fhf-en_e_td

63

Lowara
GEN..21/FHF 100-125 SERIES
FIRE-FIGHTING BOOSTER SETS EN 12845

64

Lowara
GEN..21/FHF 100-125 SERIES
FIRE-FIGHTING BOOSTER SETS EN 12845
GEN..21

DRW

DNA

DNP

DNM

N
FHF100-160/185

125

Rp 1"1/4

150

430

291

890

85

245

418

1750

490

1840 1391 1652 2286

FHF100-160/220

125

Rp 1"1/4

150

430

190

1020

105

245

418

1750

490

1840 1440 1652 2286

FHF100-160/300

125

Rp 1"1/4

200

430

310

1020

105

245

418

1750

490

1840 1560 1678 2337

FHF100-200/185

125

Rp 1"1/4

150

430

291

890

85

245

393

1750

490

1840 1391 1627 2261

FHF100-200/300

125

Rp 1"1/4

150

430

310

1020

105

245

393

1750

490

1840 1560 1627 2261

FHF100-200/370

125

Rp 1"1/4

150

430

310

1020

105

245

393

1750

490

1840 1560 1627 2261

FHF100-200/450

125

Rp 1"1/4

200

470

215

1130

125

245

438

1750

600

2140 1595 1698 2357

FHF100-250/300

125

Rp 1"1/4

150

430

310

1020

105

245

418

1750

490

1840 1575 1652 2286

FHF100-250/450

125

Rp 1"1/4

200

430

345

1020

105

245

418

1750

490

1840 1610 1678 2337

FHF100-250/550

125

Rp 1"1/4

200

470

320

1130

125

245

463

1750

600

2140 1715 1723 2382

FHF100-250/750

125

Rp 1"1/4

200

590

400

1110

140

265

513

600

2380 1790 1773 2432

FHF100-250/900

125

Rp 1"1/4

200

590

400

1110

140

265

513

600

2380 1790 1773 2432

FHF125-200/300

150

Rp 1"1/2

200

430

370

1020

105

250

443

1750

490

1840 1635 1821 2480

FHF125-200/450

150

Rp 1"1/2

200

470

275

1130

125

250

463

1750

600

2140 1670 1841 2500

FHF125-200/550

150

Rp 1"1/2

200

470

380

1130

125

250

463

1750

600

2140 1775 1841 2500

FHF125-270/750

150

Rp 1"1/2

250

590

370

1400

80

225

563

600

2380 1850 2008 2694

FHF125-270/900

150

Rp 1"1/2

250

590

370

1400

80

225

563

600

2380 1850 2008 2694

FHF125-270/1100

150

Rp 1"1/2

250

650

510

1400

80

225

618

650

2600 1990 2063 2749

FHF125-270/1320
3
150
Rp 1"1/2
Dimensions in mm. Tolerance 10 mm.

250

650

510

1400

80

225

618

650

2600 1990 2063 2749


gen21_fhf100-en_d_td

65

Lowara
GEN../FHF 32-80 SERIES
DIMENSIONS FOR FL
OOR FIXING
FLOOR

66

Lowara
GEN../FHF 32-80 SERIES
DIMENSIONS FOR FL
OOR FIXING
FLOOR
GEN..10

PUMP

GEN..11

GEN..20

GEN..21

FHF 32-125/07

320

540

20

130

770

540

90

25

990

540

90

25

1260

540

90

25

FHF 32-125/11

320

540

20

130

770

540

90

25

990

540

90

25

1260

540

90

25

FHF 32-160/15

350

600

20

150

770

600

90

25

990

600

90

25

1260

600

90

25

FHF 32-160/22

350

600

20

150

770

600

90

25

990

600

90

25

1260

600

90

25

FHF 32-200/30

350

600

20

150

770

600

90

25

990

600

90

25

1260

600

90

25

FHF 32-200/40

350

600

20

150

770

600

90

25

990

600

90

25

1260

600

90

25

FHF 40-125/11

350

600

20

150

770

540

90

25

1030

600

90

25

1260

540

90

25

FHF 40-125/15

350

600

20

150

770

600

90

25

1030

600

90

25

1260

600

90

25

FHF 40-125/22

350

600

20

150

770

600

90

25

1030

600

90

25

1260

600

90

25

FHF 40-160/30

350

600

20

150

770

600

90

25

1030

600

90

25

1260

600

90

25

FHF 40-160/40

350

600

20

150

770

600

90

25

1030

600

90

25

1260

600

90

25

FHF 40-200/55

400

660

25

170

960

585

20

55

1170

585

20

55

1510

585

20

55

FHF 40-200/75

400

660

25

170

960

585

20

55

1170

585

20

55

1510

585

20

55

FHF 40-250/110A

490

840

25

205

1130

765

20

55

1360

765

20

55

1640

765

20

55

FHF 40-250/110

490

840

25

205

1130

765

20

55

1360

765

20

55

1640

765

20

55

FHF 40-250/150

490

840

25

205

1130

765

20

55

1360

765

20

55

1640

765

20

55

FHF 50-125/22

350

600

20

150

770

600

90

25

1030

600

90

25

1260

600

90

25

FHF 50-125/30

350

600

20

150

770

600

90

25

1030

600

90

25

1260

600

90

25

FHF 50-125/40

350

600

20

150

770

600

90

25

1030

600

90

25

1260

600

90

25

FHF 50-160/55

400

660

25

170

960

585

20

55

1170

585

20

55

1510

585

20

55

FHF 50-160/75

400

660

25

170

960

585

20

55

1170

585

20

55

1510

585

20

55

FHF 50-200/110A

440

740

25

190

1130

665

20

55

1360

665

20

55

1640

665

20

55

FHF 50-200/110

440

740

25

190

1130

665

20

55

1360

665

20

55

1640

665

20

55

FHF 50-250/150

490

840

25

205

1130

765

20

55

1360

765

20

55

1640

765

20

55

FHF 50-250/185

490

840

25

205

1130

765

20

55

1360

765

20

55

1640

765

20

55

FHF 50-250/220

490

840

25

205

1130

765

20

55

1360

765

20

55

1640

765

20

55

FHF 65-125/40

350

600

20

150

820

600

90

25

1030

600

90

25

1370

600

90

25

FHF 65-125/55

400

660

25

170

960

585

20

55

1170

585

20

55

1510

585

20

55

FHF 65-125/75

400

660

25

170

960

585

20

55

1170

585

20

55

1510

585

20

55

FHF 65-160/110A

490

840

25

205

1130

765

20

55

1360

765

20

55

1640

765

20

55

FHF 65-160/110

490

840

25

205

1130

765

20

55

1360

765

20

55

1640

765

20

55

FHF 65-160/150

490

840

25

205

1130

765

20

55

1360

765

20

55

1640

765

20

55

FHF 65-200/150

490

840

25

205

1130

765

20

55

1360

765

20

55

1640

765

20

55

FHF 65-200/185

490

840

25

205

1130

765

20

55

1360

765

20

55

1640

765

20

55

FHF 65-200/220

490

840

25

205

1130

765

20

55

1360

765

20

55

1640

765

20

55

FHF 65-250/220

490

840

25

205

1130

765

20

55

1360

765

20

55

1640

765

20

55

FHF 65-250/300

550

940

30

230

1130

865

20

55

1510

685

20

55

1800

865

20

55

FHF 65-250/370

550

940

30

230

1130

865

20

55

1510

685

20

55

1800

865

20

55

FHF 80-160/150

490

840

25

205

1130

765

20

55

1360

765

20

55

1640

765

20

55

FHF 80-160/185

490

840

25

205

1130

765

20

55

1360

765

20

55

1640

765

20

55

FHF 80-200/220

490

840

25

205

1130

765

20

55

1360

765

20

55

1640

765

20

55

FHF 80-200/300

550

940

30

230

1130

865

20

55

1510

685

20

55

1800

865

20

55

FHF 80-250/370

550

940

30

230

1130

865

20

55

1510

685

20

55

1800

865

20

55

FHF 80-250/450

550

940

30

230

1130

865

20

55

1510

685

20

55

1800

865

20

55

FHF 80-250/550

600

1060

30

270

1360

950

20

90

1640

985

20

55

2100

950

20

90

Dimensions in mm. Tolerance 10 mm.

inter_fhf-en_b_td

67

Lowara
GEN../FHF 100-125 SERIES
DIMENSIONS FOR FL
OOR FIXING
FLOOR

68

Lowara
GEN../FHF 100-125 SERIES
DIMENSIONS FOR FL
OOR FIXING
FLOOR
GEN..10

PUMP

GEN..11

GEN..20

GEN..21

FHF 100-160/185

500

700

25

200

1130

795

20

25

1510

795

20

25

1800

795

20

25

FHF 100-160/220

500

830

25

220

1130

925

20

25

1510

925

20

25

1800

925

20

25

FHF 100-160/300

500

830

25

220

1130

925

20

25

1510

925

20

25

1800

925

20

25

FHF 100-200/185

500

700

25

200

1130

795

20

25

1510

795

20

25

1800

795

20

25

FHF 100-200/300

500

830

25

220

1130

925

20

25

1510

925

20

25

1800

925

20

25

FHF 100-200/370

500

830

25

220

1130

925

20

25

1510

925

20

25

1800

925

20

25

FHF 100-200/450

610

940

30

240

1260

845

20

25

1800

1035

20

25

2100

1035

20

25

FHF 100-250/300

500

830

25

220

1130

925

20

25

1510

925

20

25

1800

925

20

25

FHF 100-250/450

500

830

25

220

1130

925

20

25

1510

925

20

25

1800

925

20

25

FHF 100-250/550

610

940

30

240

1260

845

20

25

1800

1035

20

25

2100

1035

20

25

FHF 100-250/750

680

1050

30

260

1380

930

30

90

1940

930

30

90

1900

930

30

90

FHF 100-250/900

680

1050

30

260

1380

930

30

90

1940

930

30

90

1900

930

30

90

FHF 125-200/300

500

830

25

220

1130

925

20

25

1510

925

20

25

1800

925

20

25

FHF 125-200/450

610

940

30

240

1260

845

20

25

1800

1035

20

25

2100

1035

20

25

FHF 125-200/550

610

940

30

240

1260

845

20

25

1800

1035

20

25

2100

1035

20

25

FHF 125-270/750

700

1200

25

200

1380

1080

30

90

1940

1080

30

90

2320

1080

30

90

FHF 125-270/900

700

1200

25

200

1380

1080

30

90

1940

1080

30

90

2320

1080

30

90

FHF 125-270/1100

820

1200

25

200

1490

1080

30

90

2190

1080

30

90

2540

1080

30

90

FHF 125-270/1320

820

1200

25

200

1490

1080

30

90

2190

1080

30

90

2540

1080

30

90

Dimensions in mm. Tolerance 10 mm.

inter_fhf100-en_a_td

69

Lowara

70

Lowara
GEN../FHF SERIES OF BOOSTER SETS (POSITIVE SUCTION HEAD)
Hc PRES
SURE DROP CURVE IN SUCTION KIT
PRESSURE
2900 [rpm]

0
0

20

40

20

ISO 9906 - Annex A

60

40

80

60

80

Q [US gpm]
120

100

0,25

20

40

20

ISO 9906 - Annex A

60

40

Q
[Imp gpm]
100

80

60

80

Q [US gpm]
120

100

0,25

0,8

H [ft]

Hc [m]

0,8

Hc [m]

2900 [rpm]

FH 32 - 160

Q [Imp gpm]
100

0,20

H [ft]

FH 32 - 125

0,20
0,6

0,6

0,15

0,15
0,4

0,4

0,10

0,10

0,2

0,2

0,05

0,05

0,00
6

0,0

0,00
10

0,0

30
8
15

25

4
NPSHr [m]

NPSHr [ft]

NPSHr [m]

15
4

NPSHr [ft]

20

6
10

10
5
2

0
0

10
100

15
200

20
20

25

300

40
40

60
60

0
0
0

ISO 9906 - Annex A


80

80

Q [m3/h]
30
Q [l/min]
500

400

2900 [rpm]

FH 32 - 200
0

20

100

10
100

15
200

100

Q120
[Imp gpm]

Q [US gpm]
140

400

100

Q [l/min]
500

ISO 9906 - Annex A


150

100

Q [m3/h]
30

150

200

Q [Imp gpm]

Q [US
250 gpm]

200

0,4

1,5

H [ft]

H [ft]

1,5

Hc [m]

0,5

Hc [m]

0,5

50
50

25

300

2900 [rpm]

FH 40 - 125

120

20

76475_A_CH

76474_A_CH

0,4

1,0

0,3

1,0

0,3

0,2

0,2
0,5

0,5

0,1

0,1

0,0
10

0,0

0,0
15

0,0

30
40

8
25
10

20

NPSHr [ft]

NPSHr [m]

15
4

NPSHr [ft]

NPSHr [m]

30

20

10

10

0
0
0

10
100

15
200

20
300

25
400

30

Q [m3/h]
35

500

Q [l/min]

0
0
0

10
200

20

30
400

40
600

The declared performance value are valid for liquids with density = 1.0 Kg/dm3 and kinematic viscosity = 1 mm2/sec.
The NPSHr values required for the service pump were obtained in the laboratory. When using them for EN 12845 for fire-fighting systems, increase the value by 1 m.
Hc: Pressure drop curve in suction kit.

71

50
800

Q [m3/h]
60
Q 1000
[l/min]

76477_A_CH

76476_A_CH

Lowara
GEN../FHF SERIES OF BOOSTER SETS (POSITIVE SUCTION HEAD)
Hc PRES
SURE DROP CURVE IN SUCTION KIT
PRESSURE
2900 [rpm]

FH 40 - 160
0
0

50

100

50

ISO 9906 - Annex A


150

100

150

200

Q [US
250 gpm]

200

2900 [rpm]

FH 40 - 200

Q [Imp gpm]

50

0,5

ISO 9906 - Annex A

100

50

150

100

150

200

Q [Imp gpm]

Q [US
250 gpm]

200

0,4

H [ft]

Hc [m]

1,5

H [ft]

Hc [m]

0,6

0,5
1,5
0,4

1,0

0,3

1,0

0,3
0,2
0,2

0,5

0,5
0,1

0,1

0,0
15

0,0

0,0
15

0,0

40

40

10

10

20
5

0
0
0

10

20

200

30
400

50

100

50

50

600

Q 1000
[l/min]

0
0

150

200

20

200

30

Q [Imp gpm]

50

600

100

Q 1000
[l/min]

ISO 9906 - Annex A

200

100

Q [m3/h]
60

800

2900 [rpm]

0
0

40

400

FH 50 - 125

Q [US
250 gpm]

200

10

ISO 9906 - Annex A


150

100

Q [m3/h]
60

800

2900 [rpm]

FH 40 - 250
0

40

76456_A_CH

10

76478_A_CH

10

Q [Imp gpm]

300

200

300

400

Q [US gpm]

Hc [m]

H [ft]
0,5

1,5

H [ft]

0,5

0,6
Hc [m]

NPSHr [ft]

NPSHr [m]

20

30
NPSHr [ft]

NPSHr [m]

30

0,4
1,5

0,4
1,0

0,3
1,0

0,3

0,2
0,2

0,5
0,5
0,1

0,1

0,0
15

0,0

0,0
15

0,0

40

40

10

10

20

NPSHr [ft]

NPSHr [m]

20

30
NPSHr [ft]

NPSHr [m]

30

0
0
0

10
200

20

30
400

40
600

50
800

Q [m3/h]
60
Q 1000
[l/min]

0
0
0

20
200

40
400

600

60
800

1000

80
1200

The declared performance value are valid for liquids with density = 1.0 Kg/dm3 and kinematic viscosity = 1 mm2/sec.
The NPSHr values required for the service pump were obtained in the laboratory. When using them for EN 12845 for fire-fighting systems, increase the value by 1 m.
Hc: Pressure drop curve in suction kit.

72

1400

Q [m3100
/h]
1600
Q [l/min]

76481_A_CH

10

76457_A_CH

10

Lowara
GEN../FHF SERIES OF BOOSTER SETS (POSITIVE SUCTION HEAD)
Hc PRES
SURE DROP CURVE IN SUCTION KIT
PRESSURE
2900 [rpm]

FH 50 - 160
0

100

ISO 9906 - Annex A

200

100

300

200

300

400

2900 [rpm]

FH 50 - 200

Q [Imp gpm]

Q [US gpm]

100

100

300

200

400

300

Q [Imp gpm]

Q
[US gpm]
500

400

0,4

1,5
0,4

1,0

0,3

1,0

0,3

0,2

0,2
0,5

0,5

0,1

0,1

0,0
15

0,0

0,0
15

0,0

40

40

10

10

20

NPSHr [ft]

NPSHr [m]

20

30
NPSHr [ft]

NPSHr [m]

30

0
0
0

20
200

40
400

600

800

80

1000

1200

2900 [rpm]

FH 50 - 250
0

60

100

200

100

1400

Q
1600
[l/min]

0
0

300

400

40

60

500

Q [Imp gpm]

0
0

100
1500

2900 [rpm]

100

200

100

300

Q [l/min]
2000

ISO 9906 - Annex A

300

200

3
Q [m120
/h]

Q
[Imp gpm]
500

400
400

Q [US
600 gpm]

500

H [ft]
0,5

H [ft]

0,6
Hc [m]

0,6

80

1000

FH 65 - 125

Q
[US gpm]
500

400

20

ISO 9906 - Annex A


300

200

3
Q [m100
/h]

76483_A_CH

10

76482_A_CH

10

0,5

1,5

1,5

0,4

0,4

1,0

0,3

1,0

0,3

0,2

0,2
0,5

0,5

0,1

0,1

0,0
15

0,0

0,0
15

0,0

40

40

10

10

20

NPSHr [ft]

NPSHr [m]

20

30
NPSHr [ft]

NPSHr [m]

30

0
0
0

20

40
500

60
1000

80

100
1500

3
Q [m120
/h]

10

76484_A_CH

10

0
0

Q [l/min]
2000

20

40
500

60
1000

80

100
1500

The declared performance value are valid for liquids with density = 1.0 Kg/dm3 and kinematic viscosity = 1 mm2/sec.
The NPSHr values required for the service pump were obtained in the laboratory. When using them for EN 12845 for fire-fighting systems, increase the value by 1 m.
Hc: Pressure drop curve in suction kit.

73

120

0
3
Q [m140
/h]

2000

Q [l/min]

76485_A_CH

Hc [m]

H [ft]

H [ft]

1,5

Hc [m]

0,5

Hc [m]

0,5

200

ISO 9906 - Annex A

Lowara
GEN../FHF SERIES OF BOOSTER SETS (POSITIVE SUCTION HEAD)
Hc PRES
SURE DROP CURVE IN SUCTION KIT
PRESSURE
2900 [rpm]

FH 65 - 160
0
0

100
100

200
200

ISO 9906 - Annex A

300
300

400
400

500

500

Q [US
gpm]
700

600

100

200

100

ISO 9906 - Annex A

300

200

300

400
400

Q [Imp gpm]

500

500

Q [US
gpm]
700

600

H [ft]
0,5

H [ft]

0,6
Hc [m]

0,6

0,5

1,5

1,5

0,4

0,4

1,0

0,3

1,0

0,3

0,2

0,2
0,5

0,5

0,1

0,1

0,0
15

0,0

0,0
15

0,0

40

40

10

10

20

187

65-160/150
178

20

5
65-200/220
65-200/185

178

0
0

20

40

500

60
1000

100
100

100

120

1500

200
200

400
400

3
Q [m160
/h]

0
0

2500
Q [l/min]

500

500

600

198

10

ISO 9906 - Annex A

300
300

140

2000

2900 [rpm]

FH 65 - 250
0

80

210

10

20

40
500

60
1000

Q [Imp gpm]

0
0

1500

120

200
200

400
400

140

2000

2500
Q [l/min]

ISO 9906 - Annex A


600

600

0
3
Q [m160
/h]

Q [Imp gpm]

800
800

1000

Q [US gpm]

0,5
H [ft]

Hc [m]

0,6

100

2900 [rpm]

FH 80 - 160

Q [US
gpm]
700

80

76487_A_CH

168

76486_A_CH

65-160/150
65-160/110

Hc [m]

65-200/150

NPSHr [ft]

65-160/150
178

30
NPSHr [ft]

NPSHr [m]

161

NPSHr [m]

30
65-160/110A

0,5

1,5

H [ft]

Hc [m]

2900 [rpm]

FH 65 - 200

Q [Imp gpm]

0,4
1,5

0,4
1,0

0,3
1,0

0,3

0,2
0,2

0,5
0,5
0,1

0,1

0,0
15

0,0

0,0
15

0,0

40

40

10

10

65-160/150
178

20

NPSHr [ft]

20

NPSHr [m]

65-160/150
178

30
NPSHr [ft]

NPSHr [m]

30

0
0
0

20

40
500

60
1000

80

100
1500

120
2000

140

3
Q [m160
/h]

2500
Q [l/min]

0
0
0

50
1000

100

150
2000

200
3000

The declared performance value are valid for liquids with density = 1.0 Kg/dm3 and kinematic viscosity = 1 mm2/sec.
The NPSHr values required for the service pump were obtained in the laboratory. When using them for EN 12845 for fire-fighting systems, increase the value by 1 m.
Hc: Pressure drop curve in suction kit.

74

3
Q [m250
/h]

Q 4000
[l/min]

76489_A_CH

10

76488_A_CH

10

Lowara
GEN../FHF SERIES OF BOOSTER SETS (POSITIVE SUCTION HEAD)
Hc PRES
SURE DROP CURVE IN SUCTION KIT
PRESSURE
2900 [rpm]

FH 80 - 200
0

200

ISO 9906 - Annex A

400

200

600

400

600

800
800

1000

2900 [rpm]

FH 80 - 250

Q [Imp gpm]

Q [US gpm]

200

400

200

600

400

600

Q [Imp gpm]

800

1000 Q [US gpm]

800

0,4

1,5

H [ft]

H [ft]

1,5

Hc [m]

0,5

Hc [m]

0,5

ISO 9906 - Annex A

0,4

1,0

0,3

1,0

0,3

0,2

0,2
0,5

0,5

0,1

0,1

0,0
15

0,0

0,0
15

0,0

40

40

10

10

80-250/370

225

65-160/150
178

20

NPSHr [ft]

20

NPSHr [m]

65-160/150
178

30
NPSHr [ft]

NPSHr [m]

30

5
80-250/550
80-250/450

256
238

0
50

100

1000

3000

2900 [rpm]

200
200

400
400

600
600

Q 4000
[l/min]

0
0

1000

1000

1400

1600 Q [US gpm]

0,25

150

1000

2000

3000

2900 [rpm]

200
200

400
400

600
600

0
3
Q [m250
/h]

200

ISO 9906 - Annex A

800
800

Q 4000
[l/min]

1000

1000

Q
[Imp gpm]
1400

1200

1200

1400

1600 Q [US gpm]

0,25

0,8

H [ft]

Hc [m]

0,8

Hc [m]

100

FH 100 - 200

Q
[Imp gpm]
1400

1200

1200

50

ISO 9906 - Annex A

800
800

3
Q [m250
/h]

200

2000

FH 100 - 160
0

150

0,20

H [ft]

76491_A_CH

10

76490_A_CH

10

0,20
0,6

0,6

0,15

0,15
0,4

0,4

0,10

0,10

0,2

0,2

0,05

0,05

0,00
15

0,0

100-160/185

0,00
15

0,0

40

135/165

100-200/185

10

40

141/195

10

65-160/150
178

20

65-160/150
178
100-200/450
100-200/370
100-200/300

213
203
189/195

0
0

50
1000

100

150
2000

200
3000

250
4000

300
5000

350
6000

0
3
Q [m400
/h]
Q [l/min]

10

76492_A_CH

10

20

NPSHr [ft]

159/171

30

0
0
0

50
1000

100

150
2000

200
3000

250
4000

300
5000

The declared performance value are valid for liquids with density = 1.0 Kg/dm3 and kinematic viscosity = 1 mm2/sec.
The NPSHr values required for the service pump were obtained in the laboratory. When using them for EN 12845 for fire-fighting systems, increase the value by 1 m.
Hc: Pressure drop curve in suction kit.

75

350
6000

0
3
Q [m400
/h]
Q [l/min]

76493_A_CH

185

NPSHr [m]

100-160/300
100-160/220

NPSHr [ft]

NPSHr [m]

30

Lowara
GEN../FHF SERIES OF BOOSTER SETS (POSITIVE SUCTION HEAD)
Hc PRES
SURE DROP CURVE IN SUCTION KIT
PRESSURE
2900 [rpm]

500

ISO 9906 - Annex A

1000

500

1000

Q [US gpm]

1500

0,25

2900 [rpm]

FH 125 - 200

1500 Q [Imp gpm]

500
500

1000
1000

ISO 9906 - Annex A

1500
1500

Q2500
[Imp gpm]

2000
2000

Q3000
[US gpm]

2500

0,25

0,8

Hc [m]

H [ft]

Hc [m]

0,8

0,20

H [ft]

FH 100 - 250

0,20
0,6

0,6

0,15

0,15
0,4

0,4

0,10

0,10

0,2

0,2

0,05

0,05

0,00
15

0,0

0,00
15

0,0

125-200/300

162/194

40

40

10
200

30

20

125-200/550
125-200/450

NPSHr [m]

65-160/150
178

NPSHr [ft]

NPSHr [m]

100-250/300

205

65-160/150
178

20

5
267
254

10

221

0
0

100

200
2000

6000

2900 [rpm]

500
500

1000
1000

Q [l/min]

0
0
0

100
2000

200

300
4000

400
6000

500
8000

ISO 9906 - Annex A

1500
1500

0
3
Q [m500
/h]

400

4000

FH 125 - 270

300

10

2000
2000

2500

2500

Q [Imp gpm]

3000

Q [US
3500gpm]

0,25

H [ft]

Hc [m]

0,8

0,20
0,6
0,15
0,4
0,10

0,2
0,05

0,00
20

0,0

60

50

15

125-270/750

216/230

125-270/1320 266
65-160/150
125-270/1100 253
178
125-270/900 237

30

NPSHr [ft]

40
10

20
5

0
0
0

100
2000

200

300
4000

400
6000

500
8000

600
10000

700

0
3
Q [m800
/h]

12000

Q [l/min]

76496_A_CH

10

The declared performance value are valid for liquids with density = 1.0 Kg/dm3 and kinematic viscosity = 1 mm2/sec.
The NPSHr values required for the service pump were obtained in the laboratory. When using them for EN 12845 for fire-fighting systems, increase the value by 1 m.
Hc: Pressure drop curve in suction kit.

76

600
10000

0
3
Q [m700
/h]
Q [l/min]

76495_A_CH

235

76494_A_CH

100-250/900
100-250/750
100-250/550
100-250/450

NPSHr [m]

30

216

NPSHr [ft]

10

Lowara
GEN../FHF SERIES OF BOOSTER SETS (SUCTION LIF
T)
LIFT)
Hc PRES
SURE DROP CURVE IN SUCTION KIT
PRESSURE
2900 [rpm]

FH 32 - 125
0
0

20

40

20

ISO 9906 - Annex A

60

40

80

60

80

Q [US gpm]
120

100

2900 [rpm]

FH 32 - 160

Q [Imp gpm]
100

0,5

20

40

20

ISO 9906 - Annex A

60

40

Q
[Imp gpm]
100

80

60

80

Q [US gpm]
120

100

0,4

H [ft]

Hc [m]

1,5

H [ft]

Hc [m]

0,6

0,5
1,5
0,4

1,0

0,3

1,0

0,3
0,2
0,2

0,5

0,5
0,1

0,1

0,0
6

0,0

0,0
10

0,0

30
8
15

25

4
NPSHr [m]

NPSHr [ft]

NPSHr [m]

15
4

NPSHr [ft]

20

6
10

10
5
2

0
0

10
100

15
200

20
20

25

300

40
40

60
60

100

10
100

15
200

100

Q120
[Imp gpm]

120

Q [US gpm]
140

20

50

100

50

25

300

400

2900 [rpm]

FH 40 - 125

Q [l/min]
500

ISO 9906 - Annex A


150

100

Q [m3/h]
30

150

200

Q [Imp gpm]

Q [US
250 gpm]

200

H [ft]
0,5

H [ft]

0,6
Hc [m]

0,6
Hc [m]

0
0

ISO 9906 - Annex A


80

80

Q [m3/h]
30
Q [l/min]
500

400

2900 [rpm]

FH 32 - 200
0

20

76452_A_CH

76451_A_CH

0,5

1,5

1,5

0,4

0,4

1,0

0,3

1,0

0,3

0,2

0,2
0,5

0,5

0,1

0,1

0,0
10

0,0

0,0
15

0,0

30
40

8
25
10

20

NPSHr [ft]

NPSHr [m]

15
4

NPSHr [ft]

NPSHr [m]

30

20

10

10

0
0
0

10
100

15
200

20
300

25
400

30

Q [m3/h]
35

500

Q [l/min]

0
0
0

10
200

20

30
400

40
600

The declared performance value are valid for liquids with density = 1.0 Kg/dm3 and kinematic viscosity = 1 mm2/sec.
The NPSHr values required for the service pump were obtained in the laboratory. When using them for EN 12845 for fire-fighting systems, increase the value by 1 m.
Hc: Pressure drop curve in suction kit.

77

50
800

Q [m3/h]
60
Q 1000
[l/min]

76454_A_CH

76453_A_CH

Lowara
GEN../FHF SERIES OF BOOSTER SETS (SUCTION LIF
T)
LIFT)
Hc PRES
SURE DROP CURVE IN SUCTION KIT
PRESSURE
2900 [rpm]

FH 40 - 160
0
0

50

100

50

ISO 9906 - Annex A


150

100

150

200

Q [US
250 gpm]

200

50

ISO 9906 - Annex A

100

50

150

100

150

200

Q [Imp gpm]

Q [US
250 gpm]

200

H [ft]
0,5

H [ft]

0,6
Hc [m]

0,6

0,5

1,5

1,5

0,4

0,4

1,0

0,3

1,0

0,3

0,2

0,2
0,5

0,5

0,1

0,1

0,0
15

0,0

0,0
15

0,0

40

40

10

10

20
5

0
0
0

10

20

200

30
400

50

100

50

50

600

Q 1000
[l/min]

0
0

150

200

20

200

30

Q [Imp gpm]

600

100

800

Q 1000
[l/min]

ISO 9906 - Annex A

200

100

Q [m3/h]
60

Q [Imp gpm]

300

200

300

400

Q [US gpm]

H [ft]
0,5

H [ft]

0,6
Hc [m]

0,6

50

2900 [rpm]

0
0

40

400

FH 50 - 125

Q [US
250 gpm]

200

10

ISO 9906 - Annex A


150

100

Q [m3/h]
60

800

2900 [rpm]

FH 40 - 250
0

40

76456_A_CH

10

76455_A_CH

10

0,5

1,5

1,5

0,4

0,4

1,0

0,3

1,0

0,3

0,2

0,2
0,5

0,5

0,1

0,1

0,0
15

0,0

0,0
15

0,0

40

40

10

10
NPSHr [m]

20

30
NPSHr [ft]

NPSHr [m]

30

20

NPSHr [ft]

Hc [m]

NPSHr [ft]

NPSHr [m]

20

30
NPSHr [ft]

NPSHr [m]

30

0
0
0

10
200

20

30
400

40
600

50
800

Q [m3/h]
60
Q 1000
[l/min]

10

76457_A_CH

10

0
0
0

20
200

40
400

600

60
800

1000

80
1200

The declared performance value are valid for liquids with density = 1.0 Kg/dm3 and kinematic viscosity = 1 mm2/sec.
The NPSHr values required for the service pump were obtained in the laboratory. When using them for EN 12845 for fire-fighting systems, increase the value by 1 m.
Hc: Pressure drop curve in suction kit.

78

1400

0
3
Q [m100
/h]
1600
Q [l/min]

76458_A_CH

Hc [m]

2900 [rpm]

FH 40 - 200

Q [Imp gpm]

Lowara
GEN../FHF SERIES OF BOOSTER SETS (SUCTION LIF
T)
LIFT)
Hc PRES
SURE DROP CURVE IN SUCTION KIT
PRESSURE
2900 [rpm]

FH 50 - 160
0

100

ISO 9906 - Annex A

200

100

300

200

300

400

Q [US gpm]

100

200

100

ISO 9906 - Annex A


300

200

400

300

Q [Imp gpm]

Q
[US gpm]
500

400

H [ft]
0,5

H [ft]

0,6
Hc [m]

0,6

0,5

1,5

1,5

0,4

0,4

1,0

0,3

1,0

0,3

0,2

0,2
0,5

0,5

0,1

0,1

0,0
15

0,0

0,0
15

0,0

40

40

10

10

20
5

0
0

20
200

40
400

600

800

100

1000

200

100

1200

1400

Q
1600
[l/min]

0
0

300

400

40

60

500

Q [Imp gpm]

0
0

100
1500

2900 [rpm]

100

200

100

300

Q [l/min]
2000

ISO 9906 - Annex A

300

200

3
Q [m120
/h]

Q
[Imp gpm]
500

400
400

Q [US
600 gpm]

500

H [ft]
0,5

H [ft]

0,6
Hc [m]

0,6

80

1000

FH 65 - 125

Q
[US gpm]
500

400

20

ISO 9906 - Annex A


300

200

0
3
Q [m100
/h]

80

2900 [rpm]

FH 50 - 250
0

60

76473_A_CH

10

76459_A_CH

10

0,5

1,5

1,5

0,4

0,4

1,0

0,3

1,0

0,3

0,2

0,2
0,5

0,5

0,1

0,1

0,0
15

0,0

0,0
15

0,0

40

40

10

10
NPSHr [m]

20

30
NPSHr [ft]

NPSHr [m]

30

20

NPSHr [ft]

Hc [m]

NPSHr [ft]

NPSHr [m]

20

30
NPSHr [ft]

NPSHr [m]

30

0
0
0

20

40
500

60
1000

80

100
1500

3
Q [m120
/h]

Q [l/min]
2000

10

76460_A_CH

10

0
0
0

20

40
500

60
1000

80

100
1500

The declared performance value are valid for liquids with density = 1.0 Kg/dm3 and kinematic viscosity = 1 mm2/sec.
The NPSHr values required for the service pump were obtained in the laboratory. When using them for EN 12845 for fire-fighting systems, increase the value by 1 m.
Hc: Pressure drop curve in suction kit.

79

120

0
3
Q [m140
/h]

2000

Q [l/min]

76461_A_CH

Hc [m]

2900 [rpm]

FH 50 - 200

Q [Imp gpm]

Lowara
GEN../FHF SERIES OF BOOSTER SETS (SUCTION LIF
T)
LIFT)
Hc PRES
SURE DROP CURVE IN SUCTION KIT
PRESSURE
2900 [rpm]

FH 65 - 160
0
0

100
100

200
200

ISO 9906 - Annex A

300
300

400
400

500

500

Q [US
gpm]
700

600

100

200

100

ISO 9906 - Annex A

300

200

300

400
400

Q [Imp gpm]

500

500

Q [US
gpm]
700

600

H [ft]
0,5

H [ft]

0,6
Hc [m]

0,6

0,5

1,5

1,5

0,4

0,4

1,0

0,3

1,0

0,3

0,2

0,2
0,5

0,5

0,1

0,1

0,0
15

0,0

0,0
15

0,0

40

40

10

10

20

187

65-160/150
178

20

5
65-200/220
65-200/185

178

0
20

40

500

60
1000

100
100

100

120

1500

200
200

3
Q [m160
/h]

2500
Q [l/min]

0
0
0

ISO 9906 - Annex A

300
300

140

2000

2900 [rpm]

FH 65 - 250
0

80

400
400

500

500

600

198

10

0
0

210

10

20

40
500

60
1000

Q [Imp gpm]

0
0

1500

120

200
200

400
400

140

2000

2500
Q [l/min]

ISO 9906 - Annex A


600

600

0
3
Q [m160
/h]

Q [Imp gpm]

800
800

1000

Q [US gpm]

H [ft]
0,5

H [ft]

0,6
Hc [m]

0,6

100

2900 [rpm]

FH 80 - 160

Q [US
gpm]
700

80

76463_A_CH

168

76462_A_CH

65-160/150
65-160/110

0,5

1,5

1,5

0,4

0,4

1,0

0,3

1,0

0,3

0,2

0,2
0,5

0,5

0,1

0,1

0,0
15

0,0

0,0
15

0,0

40

40

10

10

20

NPSHr [m]

65-160/150
178

30
NPSHr [ft]

NPSHr [m]

30

65-160/150
178

20

NPSHr [ft]

Hc [m]

65-200/150

NPSHr [ft]

65-160/150
178

30
NPSHr [ft]

NPSHr [m]

161

NPSHr [m]

30
65-160/110A

0
0
0

20

40
500

60
1000

80

100
1500

120
2000

140

3
Q [m160
/h]

2500
Q [l/min]

10

76464_A_CH

10

0
0
0

50
1000

100

150
2000

200
3000

The declared performance value are valid for liquids with density = 1.0 Kg/dm3 and kinematic viscosity = 1 mm2/sec.
The NPSHr values required for the service pump were obtained in the laboratory. When using them for EN 12845 for fire-fighting systems, increase the value by 1 m.
Hc: Pressure drop curve in suction kit.

80

3
Q [m250
/h]

Q 4000
[l/min]

76465_A_CH

Hc [m]

2900 [rpm]

FH 65 - 200

Q [Imp gpm]

Lowara
GEN../FHF SERIES OF BOOSTER SETS (SUCTION LIF
T)
LIFT)
Hc PRES
SURE DROP CURVE IN SUCTION KIT
PRESSURE
2900 [rpm]

FH 80 - 200
0

200

ISO 9906 - Annex A

400

200

600

400

600

800
800

1000

Q [US gpm]

200

ISO 9906 - Annex A

400

200

600

400

600

Q [Imp gpm]

800

1000 Q [US gpm]

800

H [ft]
0,5

H [ft]

0,6
Hc [m]

0,6

0,5

1,5

1,5

0,4

0,4

1,0

0,3

1,0

0,3

0,2

0,2
0,5

0,5

0,1

0,1

0,0
15

0,0

0,0
15

0,0

40

40

10

10

80-250/370

225

65-160/150
178

20

NPSHr [ft]

20

NPSHr [m]

65-160/150
178

30
NPSHr [ft]

NPSHr [m]

30

5
80-250/550
80-250/450

256
238

0
50

100

1000

3000

2900 [rpm]

200
200

400
400

600
600

Q 4000
[l/min]

0
0

1000

1000

1400

1600 Q [US gpm]

0,25

150

1000

2000

3000

2900 [rpm]

200
200

400
400

600
600

0
3
Q [m250
/h]

200

ISO 9906 - Annex A

800
800

Q 4000
[l/min]

1000

1000

Q
[Imp gpm]
1400

1200

1200

1400

1600 Q [US gpm]

0,25

0,8

H [ft]

Hc [m]

0,8

Hc [m]

100

FH 100 - 200

Q
[Imp gpm]
1400

1200

1200

50

ISO 9906 - Annex A

800
800

3
Q [m250
/h]

200

2000

FH 100 - 160
0

150

0,20

H [ft]

76467_A_CH

10

76466_A_CH

10

0,20
0,6

0,6

0,15

0,15
0,4

0,4

0,10

0,10

0,2

0,2

0,05

0,05

0,00
15

0,0

100-160/185

0,00
15

0,0

40

135/165

100-200/185

10

40

141/195

10

159/171

65-160/150
178

20

30

65-160/150
178
100-200/450
100-200/370
100-200/300

213
203
189/195

0
0

50
1000

100

150
2000

200
3000

250
4000

300
5000

350
6000

0
3
Q [m400
/h]
Q [l/min]

10

76468_A_CH

10

20

NPSHr [ft]

185

NPSHr [m]

100-160/300
100-160/220

NPSHr [ft]

NPSHr [m]

30

0
0
0

50
1000

100

150
2000

200
3000

250
4000

300
5000

The declared performance value are valid for liquids with density = 1.0 Kg/dm3 and kinematic viscosity = 1 mm2/sec.
The NPSHr values required for the service pump were obtained in the laboratory. When using them for EN 12845 for fire-fighting systems, increase the value by 1 m.
Hc: Pressure drop curve in suction kit.

81

350
6000

0
3
Q [m400
/h]
Q [l/min]

76469_A_CH

Hc [m]

2900 [rpm]

FH 80 - 250

Q [Imp gpm]

Lowara
GEN../FHF SERIES OF BOOSTER SETS (SUCTION LIF
T)
LIFT)
Hc PRES
SURE DROP CURVE IN SUCTION KIT
PRESSURE
2900 [rpm]

500

ISO 9906 - Annex A

1000

500

1000

Q [US gpm]

1500

0,25

2900 [rpm]

FH 125 - 200

1500 Q [Imp gpm]

500
500

1000
1000

ISO 9906 - Annex A

1500
1500

Q2500
[Imp gpm]

2000
2000

Q3000
[US gpm]

2500

0,25

0,8

Hc [m]

H [ft]

Hc [m]

0,8

0,20

H [ft]

FH 100 - 250

0,20
0,6

0,6

0,15

0,15
0,4

0,4

0,10

0,10

0,2

0,2

0,05

0,05

0,00
15

0,0

0,00
15

0,0

125-200/300

162/194

40

40

10
200

30

20

125-200/550
125-200/450

NPSHr [m]

65-160/150
178

NPSHr [ft]

NPSHr [m]

100-250/300

205

65-160/150
178

20

5
267
254

10

221

0
0

100

200
2000

6000

2900 [rpm]

500
500

1000
1000

Q [l/min]

0
0
0

100
2000

200

300
4000

400
6000

500
8000

ISO 9906 - Annex A

1500
1500

0
3
Q [m500
/h]

400

4000

FH 125 - 270

300

10

2000
2000

2500

2500

Q [Imp gpm]

3000

Q [US
3500gpm]

0,25

H [ft]

Hc [m]

0,8

0,20
0,6
0,15
0,4
0,10

0,2
0,05

0,00
20

0,0

60

50

15

125-270/750

216/230

125-270/1320 266
65-160/150
125-270/1100 253
178
125-270/900 237

30

NPSHr [ft]

40
10

20
5

0
0
0

100
2000

200

300
4000

400
6000

500
8000

600
10000

700

0
3
Q [m800
/h]

12000

Q [l/min]

76472_A_CH

10

The declared performance value are valid for liquids with density = 1.0 Kg/dm3 and kinematic viscosity = 1 mm2/sec.
The NPSHr values required for the service pump were obtained in the laboratory. When using them for EN 12845 for fire-fighting systems, increase the value by 1 m.
Hc: Pressure drop curve in suction kit.

82

600
10000

0
3
Q [m700
/h]
Q [l/min]

76471_A_CH

235

76470_A_CH

100-250/900
100-250/750
100-250/550
100-250/450

NPSHr [m]

30

216

NPSHr [ft]

10

Lowara

GEN../SHF Series
Fire-fighting booster sets EN 12845
Horizontal Centrifugal electric pumps SHF series
equipped with high efficiency PLM motors
50 Hz

83

Lowara

84

Lowara
RANGE
GEN../SHF RANGE
The range of EN 12845 series fire-fighting booster sets includes
models with 1 or 2 electric service pumps and some with jockey
pumps for adapting to the specific requirements of each application.

GEN10 SERIES

Fire-fighting sets with a centrifugal


service pump horizontal axis and
body made of stainless steel in the
SHF series.

Head up to 100 m.
Flow up to 220 m3/h.

GEN11 SERIES

Fire-fighting sets with a centrifugal


service pump horizontal axis and
body made of stainless steel in the
SHF series and jockey pump.

Head up to 100 m.
Flow up to 220 m3/h.

GEN20 SERIES

Fire-fighting sets with two


centrifugal service pump horizontal
axis and body made of stainless
steel in the SHF series.

Head up to 100 m.
Flow up to 440 m3/h.

GEN21 SERIES

Fire-fighting sets with two


centrifugal service pump horizontal
axis and body made of stainless
steel in the SHF series and jockey
pump.

85

Head up to 100 m.
Flow up to 440 m3/h.

Lowara
GEN../SHF BOOSTER SETS SERIES
TABELLA DI PRESTAZIONI IDRAULICHE POMPE PILOTA SV2-4 PER GRUPPI EN12845
HYDRA
ULIC PERFORMANCE T
ABLE A
T 50 HZ (JOCKEY PUMP)
HYDRAULIC
TABLE
AT
PUMP

NOMINAL

TYPE

POWER

Q = DELIVERY
l/min 0

20

30

40

50

60

70

100

120

133

m3/h 0

1,2

1,8

2,4

3,6

4,2

7,2

37,0

26,0

18,0

H = TOTAL HEAD METRES COLUMN OF WATER

kW

HP

SV2 04

0,55

0,75

42,5

37,5

34,0

30,5

26,0

20,5

SV2 06

0,75

64,0

56,0

51,0

45,5

38,5

31,0

22,0

SV2 09

1,1

1,5

96,0

84,0

76,5

68,5

58,0

46,5

32,5

SV2 12

1,5

128,0

112,0

102,0

91,0

77,0

62,0

44,0

SV2 14

2,2

150,0

131,0

119,0

106,0

90,0

73,0

52,0

SV2 15

2,2

160,2

140,3

128,2

114,0

97,4

78,2

55,9

SV4 07

1,1

1,5

70,0

59,5

56,0

53,0

51,0

SV4 09

1,5

90,0

76,5

73,0

68,5

65,5

47,0

33,5

23,0

SV4 13

2,2

131,0

111,0

105,0

99,0

95,0

68,0

48,0

34,0

Performance in accordance with the ISO 9906 - Annex A Standard.

15,0

EN12845_pp_sv2-4-2p50-en_b_th

86

Lowara
GEN../SHF BOOSTER SETS SERIES
TABELLA ABBINAMENTI POMPA SERVIZIO SH32-80 - POMPA PILOTA GRUPPI GEN 1
SERVICE PUMP - JOCKEY PUMP COMBINA
TIONS
COMBINATIONS

32-125/07
32-125/11
32-160/15
32-160/22
32-200/30
32-200/40
32-250/55
32-250/75
32-250/110
40-125/11
40-125/15
40-125/22
40-160/30
40-160/40
40-200/55
40-200/75
40-250/110A
40-250/110
40-250/150
50-125/22
50-125/30
50-125/40
50-160/55
50-160/75
50-200/110A
50-200/110
50-250/150
50-250/185
50-250/220
65-160/40
65-160/55
65-160/75
65-160/110A
65-160/110
65-200/150
65-200/185
65-200/220
65-250/300
65-250/370
80-160/110
80-160/150
80-160/185
80-200/220
80-200/300
80-200/370
80-250/450
80-250/550
80-250/750

SV8 09

SV8 07

SV8 06

SV8 05

SV4 13

SV4 09

SV4 07

SV2 15

SV2 14

SV2 12

ELECTRIC
PUMP

SV2 04

TYPE
SHF

SV2 09

JOCKEY PUMP
SV2 06

SERVICE PUMP

PUMP

32-125/D121
32-125/D136
32-160/D150
32-160/D168
32-200/D188
32-200/D204
32-250/D222
32-250/D242
32-250/D256
40-125/D112
40-125/D126
40-125/D143
40-160/D159
40-160/D171
40-200/D190
40-200/D209
40-250/D218
40-250/D233
40-250/D251
50-125/D119
50-125/D130
50-125/D139
50-160/D158
50-160/D174
50-200/D197
50-200/D209
50-250/D224
50-250/D237
50-250/D250
65-160/D119
65-160/D129
65-160/D137
65-160/D168
65-160/D177
65-200/D192
65-200/D203
65-200/D215
65-250/D240
65-250/D255
80-160/D169
80-160/D177
80-160/D186
80-200/D198
80-200/D215
80-200/D226
80-250/D237
80-250/D252
80-250/D270

12845-SHF_ap-en_a_tc

87

Lowara
HYDRA
ULIC PERFORMANCE T
ABLE A
T 50 HZ (POSITIVE SUCTION HEAD)
HYDRAULIC
TABLE
AT
TABELLA DI PRESTAZIONI IDRAULICHE NETTE GRUPPI EN12845 SERIE SHF32 2 poli 50 Hz 1 POMPA DI SERVIZIO, ASP ESCLUSA SOPRABATT
GEN../SHF 32 BOOSTER SETS SERIES
TYPE

RATED

SHF..

POWER

LHn

RISK CLASS

Q = DELIVERY
l/min 0

ELECTRIC

PUMP

PUMP

m /h 0

150

180

200

225

300

350

375

400

416

425

450

540

11

12

14

18

21

23

24

25

26

27

32

15,2

13,1
24,1

H = TOTAL HEAD METRES COLUMN OF WATER

kW

32-125/07

32-125/D121

1 x 0,75

16,7

14,0

12,9

12,1

11,0

7,6

5,1

3,7

1,9

32-125/11

32-125/D136

1 x 1,1

21,6

19,0

17,9

17,0

15,9

12,3

9,6

8,1

6,2

32-160/15

32-160/D150

1 x 1,5

27,6

24,2

22,9

21,8

20,5

16,3

13,0

11,3

9,1

32-160/22

32-160/D168

1 x 2,2

35,0

32,0

30,9

29,9

28,7

24,7

21,5

19,7

17,5

16,1

32-200/30

32-200/D188

1x3

43,8

38,1

36,4

35,1

33,4

28,0

23,9

21,6

18,8

17,1

32-200/40

32-200/D204

1x4

53,6

48,6

47,1

45,9

44,4

39,3

35,1

32,8

29,9

28,1

27,0

32-250/55

32-250/D222

1 x 5,5

61,7

56,3

54,6

53,2

51,6

46,0

41,7

39,3

36,4

32-250/75

32-250/D242

1 x 7,5

74,1

68,4

66,7

65,3

63,6

58,1

53,8

51,4

48,6

46,9

45,8

32-250/110

32-250/D256

1 x 11

86,3

79,8

77,9

76,5

74,7

69,0

64,7

62,3

59,5

57,8

56,7

54,0

Performance levels relative to set with 1 service pump running and compliant with ISO 9906 - Annex A.
12845_1pg-sp-shf32-2p50-en_a_th
LHn = risk class value referred to the required rated capacity (Tab.6 para 7.3.1 EN12845)
Inlet pressure drops must be deducted. Make sure that these drops, added to the difference in level (max. 3.2m), are less than 4.5m
The values shown identify performance levels according to the reference standard EN12845.

HYDRA
ULIC PERFORMANCE T
ABLE A
T 50 HZ (SUCTION LIF
T)
HYDRAULIC
TABLE
AT
LIFT)
TABELLA DI PRESTAZIONI IDRAULICHE NETTE GRUPPI EN12845 SERIE SHF32 2 poli 50 Hz 1 POMPA DI SERVIZIO, ASP ESCLUSA SOTTOBATT
GEN../SHF 32 BOOSTER SETS SERIES
TYPE

RATED

SHF..

POWER

ELECTRIC

PUMP

PUMP

LHn

RISK CLASS

Q = DELIVERY
l/min 0

150

180

200

225

300

350

375

400

416

425

450

540

3
m /h 0

11

12

14

18

21

23

24

25

26

27

32

15,2

13,1
24,1

H = TOTAL HEAD METRES COLUMN OF WATER

kW

32-125/07

32-125/D121

1 x 0,75

16,7

14,0

12,9

12,1

11,0

7,6

5,1

3,7

1,9

32-125/11

32-125/D136

1 x 1,1

21,6

19,0

17,9

17,0

15,9

12,3

9,6

8,1

6,2

32-160/15

32-160/D150

1 x 1,5

27,6

24,2

22,9

21,8

20,5

16,3

13,0

11,3

9,1

32-160/22

32-160/D168

1 x 2,2

35,0

32,0

30,9

29,9

28,7

24,7

21,5

19,7

17,5

16,1

32-200/30

32-200/D188

1x3

43,8

38,1

36,4

35,1

33,4

28,0

23,9

21,6

18,8

17,1

32-200/40

32-200/D204

1x4

53,6

48,6

47,1

45,9

44,4

39,3

35,1

32,8

29,9

28,1

27,0

32-250/55

32-250/D222

1 x 5,5

61,7

56,3

54,6

53,2

51,6

46,0

41,7

39,3

36,4

32-250/75

32-250/D242

1 x 7,5

74,1

68,4

66,7

65,3

63,6

58,1

53,8

51,4

48,6

46,9

45,8

32-250/110

32-250/D256

1 x 11

86,3

79,8

77,9

76,5

74,7

69,0

64,7

62,3

59,5

57,8

56,7

Performance levels relative to set with 1 service pump running and compliant with ISO 9906 - Annex A.
LHn = risk class value referred to the required rated capacity (Tab.6 para 7.3.1 EN12845).
Inlet pressure drops must be deducted. Make sure these drops are less than 4.5m
The values shown identify performance levels according to the reference standard EN12845.

88

54,0

12845_1pg-st-shf32-2p50-en_a_th

Lowara
NPSH REQUIRED FOR PUMP SERIES SHF 32
TABELLA DI PRESTAZIONI IDRAULICHE NPSHr GRUPPI EN12845 SERIE SHF32 2 poli 50 Hz

TYPE

RATED

SHF..

POWER

LHn

RISK CLASS

Q = DELIVERY
l/min 0

ELECTRIC

PUMP

PUMP

m /h 0

150

180

200

225

300

350

375

400

416

425

450

540

11

12

14

18

21

23

24

25

26

27

32

4,4

5,2
6,9

NPSHr [METRES COLUMN OF WATER]

kW

32-125/07

32-125/D121

1 x 0,75

1,0

1,0

1,1

1,2

1,6

2,1

2,3

2,7

32-125/11

32-125/D136

1 x 1,1

1,0

1,0

1,1

1,2

1,6

2,1

2,3

2,7

32-160/15

32-160/D150

1 x 1,5

1,5

1,6

1,7

1,9

2,5

3,0

3,2

3,5

32-160/22

32-160/D168

1 x 2,2

1,2

1,4

1,5

1,6

2,2

2,8

3,3

3,8

4,2

32-200/30

32-200/D188

1x3

1,7

1,8

1,9

2,1

2,8

3,7

4,3

5,2

5,8

32-200/40

32-200/D204

1x4

1,6

1,8

2,0

2,2

2,8

3,4

3,9

4,6

5,1

5,5

32-250/55

32-250/D222

1 x 5,5

2,8

3,2

3,5

3,8

5,1

6,2

6,9

7,7

32-250/75

32-250/D242

1 x 7,5

2,7

3,0

3,2

3,5

4,5

5,3

5,8

6,3

6,6

6,9

32-250/110

32-250/D256

1 x 11

2,7

3,0

3,2

3,5

4,5

5,3

5,8

6,3

6,6

6,9

The declared NPSH values were obtained in the laboratory and refer to a single service pump
LHn = risk class value referred to the required rated capacity (Tab.6 para 7.3.1 EN12845)
Check that NPSHd NPSHr+1m is satisfied

89

7,5

12845_1p-shf32-2p50_NPSHr-en_a_th

Lowara
HYDRA
ULIC PERFORMANCE T
ABLE A
T 50 HZ (POSITIVE SUCTION HEAD)
HYDRAULIC
TABLE
AT
TABELLA DI PRESTAZIONI IDRAULICHE NETTE GRUPPI EN12845 SERIE SHF40 2 poli 50 Hz 1 POMPA DI SERVIZIO, ASP ESCLUSA, INST SOPRA
GEN../SHF 40 BOOSTER SETS SERIES
TYPE

RATED

SHF..

POWER

ELECTRIC

PUMP

PUMP

OH1n

RISK CLASS

Q = DELIVERY
l/min 0

300

375

540

640

677

700

725

750

800

833

850

1000

m3/h 0

18

23

32

38

41

42

44

45

48

50

51

60

H = TOTAL HEAD METRES COLUMN OF WATER

kW

40-125/11

40-125/D112

1 x 1,1

13,9

11,3

10,0

9,3

3,4

0,7

40-125/15

40-125/D126

1 x 1,5

18,0

15,3

14,0

13,3

7,4

4,7

40-125/22

40-125/D143

1 x 2,2

25,3

21,8

20,5

19,8

14,0

11,4

6,4

5,0

3,6

40-160/30

40-160/D159

1x3

31,6

28,1

26,8

26,0

19,5

16,5

10,8

9,2

7,6

40-160/40

40-160/D171

1x4

38,3

35,1

33,7

32,9

26,5

23,6

18,1

16,5

15,0

40-200/55

40-200/D190

1 x 5,5

46,4

42,7

41,2

40,4

33,1

29,7

23,3

21,5

19,6

40-200/75

0,6
11,7

40-200/D209

1 x 7,5

57,5

53,1

51,6

50,7

43,8

40,7

34,8

33,2

31,5

28,0

40-250/110A 40-250/D218

1 x 11

63,6

57,8

56,2

55,2

47,8

44,5

38,2

36,5

34,8

31,1

40-250/110

40-250/D233

1 x 11

71,7

66,0

64,3

63,4

55,7

52,3

45,8

44,0

42,1

38,3

40-250/150

40-250/D251

1 x 15

85,0

78,6

76,9

76,0

68,4

65,0

58,6

56,8

55,0

51,1

42,6

Performance levels relative to set with 1 service pump running and compliant with ISO 9906 - Annex A.
12845_1pg-sp-shf40-2p50-en_a_th
OHn = risk class value referred to the required rated capacity (Tab.6 para 7.3.1 EN12845)
Inlet pressure drops must be deducted. Make sure that these drops, added to the difference in level (max. 3.2m), are less than 4.5m
The values shown identify performance levels according to the reference standard EN12845.

HYDRA
ULIC PERFORMANCE T
ABLE A
T 50 HZ (SUCTION LIF
T)
HYDRAULIC
TABLE
AT
LIFT)
TABELLA DI PRESTAZIONI IDRAULICHE NETTE GRUPPI EN12845 SERIE SHF40 2 poli 50 Hz 1 POMPA DI SERVIZIO, ASP ESCLUSA, INST SOTT
GEN../SHF 40 BOOSTER SETS SERIES
TYPE

RATED

SHF..

POWER

ELECTRIC

PUMP

PUMP

OH1n

RISK CLASS

Q = DELIVERY
l/min 0

300

375

540

640

677

700

725

750

800

833

850

1000

m3/h 0

18

23

32

38

41

42

44

45

48

50

51

60

H = TOTAL HEAD METRES COLUMN OF WATER

kW

40-125/11

40-125/D112

1 x 1,1

13,9

11,3

10,0

9,3

3,4

40-125/15

40-125/D126

1 x 1,5

18,0

15,3

14,0

13,3

7,4

0,7
4,7

40-125/22

40-125/D143

1 x 2,2

25,3

21,8

20,5

19,8

14,0

11,4

6,4

5,0

3,6

40-160/30

40-160/D159

1x3

31,6

28,1

26,8

26,0

19,5

16,5

10,8

9,2

7,6

40-160/40

40-160/D171

1x4

38,3

35,1

33,7

32,9

26,5

23,6

18,1

16,5

15,0

40-200/55

40-200/D190

1 x 5,5

46,4

42,7

41,2

40,4

33,1

29,7

23,3

21,5

19,6

40-200/75

0,6
11,7

40-200/D209

1 x 7,5

57,5

53,1

51,6

50,7

43,8

40,7

34,8

33,2

31,5

28,0

40-250/110A 40-250/D218

1 x 11

63,6

57,8

56,2

55,2

47,8

44,5

38,2

36,5

34,8

31,1

40-250/110

40-250/D233

1 x 11

71,7

66,0

64,3

63,4

55,7

52,3

45,8

44,0

42,1

38,3

40-250/150

40-250/D251

1 x 15

85,0

78,6

76,9

76,0

68,4

65,0

58,6

56,8

55,0

51,1

Performance levels relative to set with 1 service pump running and compliant with ISO 9906 - Annex A.
OHn = risk class value referred to the required rated capacity (Tab.6 para 7.3.1 EN12845)
Inlet pressure drops must be deducted. Make sure these drops are less than 4.5m
The values shown identify performance levels according to the reference standard EN12845.

90

42,6

12845_1pg-st-shf40-2p50-en_a_th

Lowara
NPSH
REQUIRED FOR PUMP SERIES SHF 40
TABELLA DI PRESTAZIONI IDRAULICHE GRUPPI EN12845 SERIE SHF40 2 poli 50 Hz 1 POMPA DI SERVIZIO

RATED

SHF..

POWER

ELECTRIC

PUMP

PUMP

OH1m

TYPE

OH1n

RISK CLASS

l/min 0

300

375

540

640

677

700

725

750

800

833

850

1000

m3/h 0

18

23

32

38

41

42

44

45

48

50

51

60

Q = DELIVERY

NPSHr [METRES COLUMN OF WATER]

kW

40-125/11

40-125/D112

1 x 1,1

0,7

1,0

1,5

2,0

40-125/15

40-125/D126

1 x 1,5

0,7

1,0

1,5

2,0

2,3

2,5

40-125/22

40-125/D143

1 x 2,2

0,7

1,0

1,5

2,0

2,3

2,5

2,8

3,1

40-160/30

40-160/D159

1x3

1,1

1,4

2,1

2,6

2,9

3,2

3,5

3,8

40-160/40

40-160/D171

1x4

1,1

1,4

2,1

2,6

2,9

3,2

3,5

3,8

4,9

40-200/55

40-200/D190

1 x 5,5

1,4

1,8

2,7

3,4

3,7

3,9

4,2

4,5

5,4

40-200/75

40-200/D209

1 x 7,5

1,4

1,8

2,7

3,4

3,7

3,9

4,2

4,5

5,4

6,4

40-250/110A 40-250/D218

1 x 11

1,4

1,4

1,7

3,0

4,1

5,0

40-250/110

40-250/D233

1 x 11

1,3

1,4

1,6

1,8

1,9

40-250/150

40-250/D251

1 x 15

1,3

1,4

1,6

1,8

1,9

2,2

2,5

3,3

4,3

2,1

The declared NPSH values were obtained in the laboratory and refer to a single service pump
OHn, OHm = risk class value referred to the required rated and maximum capacity (Tab.6 para 7.3.1 EN12845)
Check that NPSHd NPSHr+1m is satisfied at the maximum requested capacity

91

5,0

12845_1p-shf40-2p50_NPSHr-en_a_th

Lowara
HYDRA
ULIC PERFORMANCE T
ABLE A
T 50 HZ (POSITIVE SUCTION HEAD)
HYDRAULIC
TABLE
AT
TABELLA DI PRESTAZIONI IDRAULICHE NETTE GRUPPI EN12845 SERIE SHF50 2 poli 50 Hz 1 POMPA DI SERVIZIO, ASPESCLUSA INST SOPRA
GEN../SHF 50 BOOSTER SETS SERIES
RATED

SHF..

POWER

ELECTRIC

PUMP

PUMP

OH3n

TYPE

OH2n

RISK CLASS

Q = DELIVERY
l/min 0

600

680

725

1000

1100

1200

1300

1350

1380

1400

1450

1500

m3/h 0

36

41

44

60

66

72

78

81

83

84

87

90

12,5

10,4

H = TOTAL HEAD METRES COLUMN OF WATER

kW

50-125/22

50-125/D119

1 x 2,2

17,2 13,2

12,0

11,3

5,9

3,6

1,2

50-125/30

50-125/D130

1x3

21,7 17,4

16,1

15,3

9,8

7,6

5,2

50-125/40

50-125/D139

1x4

25,6 21,8

20,6

19,8

14,4

12,1

9,8

7,3

6,0

5,3

4,7

50-160/55

50-160/D158

1 x 5,5

34,0 29,3

27,8

26,9

20,4

17,5

14,4

11,1

9,4

8,3

7,6

50-160/75

2,8

50-160/D174

1 x 7,5

40,7 36,1

34,7

33,9

27,6

24,7

21,6

18,1

16,3

15,2

14,4

50-200/110A 50-200/D197

1 x 11

34,0 29,3

27,8

26,9

20,4

17,5

14,4

11,1

9,4

8,3

7,6

50-200/110

50-200/D209

1 x 11

40,7 36,1

34,7

33,9

27,6

24,7

21,6

18,1

16,3

15,2

14,4

12,5

50-250/150

50-250/D224

1 x 15

70,3 65,5

64,0

63,0

54,6

50,4

45,4

39,6

50-250/185

50-250/D237

1 x 18,5

80,1 73,8

72,1

71,1

62,8

58,7

54,1

48,9

46,0

44,2

50-250/220

50-250/D250

1 x 22

88,9 83,2

81,6

80,6

72,3

68,4

64,0

59,1

56,4

54,7

53,6

50,6

Performance levels relative to set with 1 service pump running and compliant with ISO 9906 - Annex A.
12845_1pg-sp-shf50-2p50-en_a_th
OHn = risk class value referred to the required rated capacity (Tab.6 para 7.3.1 EN12845)
Inlet pressure drops must be deducted. Make sure that these drops, added to the difference in level (max. 3.2m), are less than 4.5m
The values shown identify performance levels according to the reference standard EN12845.

HYDRA
ULIC PERFORMANCE T
ABLE A
T 50 HZ (SUCTION LIF
T)
HYDRAULIC
TABLE
AT
LIFT)
TABELLA DI PRESTAZIONI IDRAULICHE NETTE GRUPPI EN12845 SERIE SHF50 2 poli 50 Hz 1 POMPA DI SERVIZIO, ASPESCLUSA INST SOTTO
GEN../SHF 50 BOOSTER SETS SERIES
RATED

SHF..

POWER

ELECTRIC

PUMP

PUMP

OH3n

TYPE

OH2n

RISK CLASS

Q = DELIVERY
l/min 0

600

680

725

1000

1100

1200

1300

1350

1380

1400

1450

1500

m3/h 0

36

41

44

60

66

72

78

81

83

84

87

90

12,5

10,4

H = TOTAL HEAD METRES COLUMN OF WATER

kW

50-125/22

50-125/D119

1 x 2,2

17,2 13,2

12,0

11,3

5,9

3,6

1,2

50-125/30

50-125/D130

1x3

21,7 17,4

16,1

15,3

9,8

7,6

5,2

2,8

50-125/40

50-125/D139

1x4

25,6 21,8

20,6

19,8

14,4

12,1

9,8

7,3

50-160/55

50-160/D158

1 x 5,5

34,0 29,3

27,8

26,9

20,4

17,5

14,4

11,1

9,4

8,3

7,6

50-160/75

50-160/D174

1 x 7,5

40,7 36,1

34,7

33,9

27,6

24,7

21,6

18,1

16,3

15,2

14,4

50-200/110A 50-200/D197

1 x 11

34,0 29,3

27,8

26,9

20,4

17,5

14,4

11,1

9,4

8,3

7,6

50-200/110

50-200/D209

1 x 11

40,7 36,1

34,7

33,9

27,6

24,7

21,6

18,1

16,3

15,2

14,4

12,5

50-250/150

50-250/D224

1 x 15

70,3 65,5

64,0

63,0

54,6

50,4

45,4

39,6

50-250/185
50-250/220

50-250/D237
50-250/D250

1 x 18,5
1 x 22

80,1 73,8
88,9 83,2

72,1
81,6

71,1
80,6

62,8
72,3

58,7
68,4

54,1
64,0

48,9
59,1

46,0
56,4

44,2
54,7

53,6

50,6

Performance levels relative to set with 1 service pump running and compliant with ISO 9906 - Annex A.
OHn = risk class value referred to the required rated capacity (Tab.6 para 7.3.1 EN12845)
Inlet pressure drops must be deducted. Make sure these drops are less than 4.5m
The values shown identify performance levels according to the reference standard EN12845.

92

6,0

5,3

4,7

12845_1pg-st-shf50-2p50-en_a_th

Lowara
NPSH REQUIRED FOR PUMP SERIES SHF 50
TABELLA DI PRESTAZIONI IDRAULICHE NPSHr GRUPPI EN12845 SERIE SHF50 2 poli 50 Hz 1 POMPA DI SERVIZIO

POWER
3

PUMP

PUMP

600

680

725

1000

1100

1200

1300

1350

1380

1400

1450

1500

36

41

44

60

66

72

78

81

83

84

87

90

6,5

7,6

Q = DELIVERY
l/min 0

ELECTRIC

OH3m

SHF..

OH3n

RATED

OH2m

TYPE

OH2n

RISK CLASS

m /h 0

NPSHr [METRES COLUMN OF WATER]

kW

50-125/22

50-125/D119

1 x 2,2

1,6

1,8

1,9

2,8

3,4

4,3

50-125/30

50-125/D130

1x3

1,6

1,8

1,9

2,7

3,1

3,7

4,6

50-125/40

50-125/D139

1x4

1,6

1,8

1,9

2,7

3,1

3,7

4,6

5,2

5,7

6,0

50-160/55

50-160/D158

1 x 5,5

2,0

2,1

2,1

2,8

3,2

3,7

4,7

5,4

5,9

6,3

50-160/75

50-160/D174

1 x 7,5

1,9

2,1

2,2

2,8

3,1

3,6

4,3

4,9

5,3

5,6

50-200/110A 50-200/D197

1 x 11

2,0

2,1

2,1

2,8

3,2

4,0

5,2

6,1

6,7

7,2

50-200/110

50-200/D209

1 x 11

1,9

2,1

2,2

2,8

3,2

3,7

4,7

5,4

5,9

6,3

7,5

50-250/150

50-250/D224

1 x 15

1,6

1,7

1,8

2,3

2,7

3,3

4,8

50-250/185

50-250/D237

1 x 18,5

1,5

1,7

1,8

2,4

2,7

3,1

3,7

4,1

4,4

50-250/220

50-250/D250

1 x 22

1,5

1,7

1,8

2,4

2,7

3,1

3,7

4,1

4,7

5,4

The declared NPSH values were obtained in the laboratory and refer to a single service pump
OHn, OHm = risk class value referred to the required rated and maximum capacity (Tab.6 para 7.3.1 EN12845)
Check that NPSHd NPSHr+1m is satisfied at the maximum requested capacity

93

4,4

12845_1p-shf50-2p50_NPSHr-en_a_th

Lowara
HYDRA
ULIC PERFORMANCE T
ABLE A
T 50 HZ (POSITIVE SUCTION HEAD)
HYDRAULIC
TABLE
AT
TABELLA DI PRESTAZIONI IDRAULICHE NETTE GRUPPI EN12845 SERIE SHF65 2 poli 50 Hz 1 POMPA DI SERVIZIO, ASP ESCLUSA INST SOPRA
GEN../SHF 65 BOOSTER SETS SERIES
RATED

SHF..

POWER

ELECTRIC

PUMP

PUMP

OH4n

TYPE

OH3n

RISK CLASS

Q = DELIVERY
l/min 0

800

900

1000

1100

1350

1500

1800

1900

2000

2050

2100

2200

m3/h 0

48

54

60

66

81

90

108

114

120

123

126

132

H = TOTAL HEAD METRES COLUMN OF WATER

kW

65-160/40

65-160/D119

1x4

19,6

15,9

14,9

13,8

12,6

9,4

7,3

2,9

65-160/55

65-160/D129

1 x 5,5

24,2

20,5

19,5

18,4

17,2

13,9

11,7

7,0

5,4

65-160/75

65-160/D137

1 x 7,5

28,2

25,1

24,2

23,1

22,0

18,8

16,7

12,0

10,4

65-160/110A 65-160/D168

1 x 11

38,2

34,3

33,0

31,5

29,8

25,2

22,0

15,2

12,9

39,7

38,4

36,9

35,3

30,6

27,4

20,5

18,1

47,5

45,9

44,1

38,9

35,3

27,1

24,1

65-160/110

65-160/D177

1 x 11

42,9

65-200/150

65-200/D192

1 x 15

53,0

8,7
15,6

65-200/185

65-200/D203

1 x 18,5

60,2

55,2

53,6

51,9

46,9

43,4

35,5

32,6

29,5

65-200/220

65-200/D215

1 x 22

68,0

63,0

61,6

60,0

55,2

51,9

44,3

41,5

38,5

37,0

35,5

65-250/300

65-250/D240

1 x 30

83,7

80,2

78,9

74,9

71,9

64,4

61,4

58,3

56,6

54,9

65-250/370

65-250/D255

1 x 37

96,7

93,6

92,2

88,0

84,9

77,4

74,6

71,7

70,1

68,5

65,2

Performance levels relative to set with 1 service pump running and compliant with ISO 9906 - Annex A.
12845_1pg-sp-shf65-2p50-en_a_th
OHn = risk class value referred to the required rated capacity (Tab.6 para 7.3.1 EN12845)
Inlet pressure drops must be deducted. Make sure that these drops, added to the difference in level (max. 3.2m), are less than 4.5m
The values shown identify performance levels according to the reference standard EN12845.

HYDRA
ULIC PERFORMANCE T
ABLE A
T 50 HZ (SUCTION LIF
T)
HYDRAULIC
TABLE
AT
LIFT)
TABELLA DI PRESTAZIONI IDRAULICHE NETTE GRUPPI EN12845 SERIE SHF65 2 poli 50 Hz 1 POMPA DI SERVIZIO, ASP ESCLUSA INST SOTTO
GEN../SHF 65 BOOSTER SETS SERIES
RATED

SHF..

POWER

ELECTRIC

PUMP

PUMP

OH4n

TYPE

OH3n

RISK CLASS

Q = DELIVERY
l/min 0

800

900

1000

1100

1350

1500

1800

1900

2000

2050

2100

2200

m3/h 0

48

54

60

66

81

90

108

114

120

123

126

132

H = TOTAL HEAD METRES COLUMN OF WATER

kW

65-160/40

65-160/D119

1x4

19,6

15,9

14,9

13,8

12,6

9,4

7,3

2,9

65-160/55

65-160/D129

1 x 5,5

24,2

20,5

19,5

18,4

17,2

13,9

11,7

7,0

5,4

65-160/75

65-160/D137

1 x 7,5

28,2

25,1

24,2

23,1

22,0

18,8

16,7

12,0

10,4

65-160/110A 65-160/D168

1 x 11

38,2

34,3

33,0

31,5

29,8

25,2

22,0

15,2

12,9

39,7

38,4

36,9

35,3

30,6

27,4

20,5

18,1

47,5

45,9

44,1

38,9

35,3

27,1

24,1

65-160/110

65-160/D177

1 x 11

42,9

65-200/150

65-200/D192

1 x 15

53,0

8,7
15,6

65-200/185

65-200/D203

1 x 18,5

60,2

55,2

53,6

51,9

46,9

43,4

35,5

32,6

29,5

65-200/220

65-200/D215

1 x 22

68,0

63,0

61,6

60,0

55,2

51,9

44,3

41,5

38,5

37,0

35,5

65-250/300

65-250/D240

1 x 30

83,7

80,2

78,9

74,9

71,9

64,4

61,4

58,3

56,6

54,9

65-250/370

65-250/D255

1 x 37

96,7

93,6

92,2

88,0

84,9

77,4

74,6

71,7

70,1

68,5

Performance levels relative to set with 1 service pump running and compliant with ISO 9906 - Annex A.
OHn = risk class value referred to the required rated capacity (Tab.6 para 7.3.1 EN12845)
Inlet pressure drops must be deducted. Make sure these drops are less than 4.5m
The values shown identify performance levels according to the reference standard EN12845.

94

65,2

12845_1pg-st-shf65-2p50-en_a_th

Lowara
NPSH
REQUIRED FOR PUMP SERIES SHF 65
TABELLA DI PRESTAZIONI IDRAULICHE NPSHr GRUPPI EN12845 SERIE SHF65 2 poli 50 Hz 1 POMPA DI SERVIZIO

POWER

ELECTRIC

PUMP

PUMP

OH4m

SHF..

l/min 0

800

900

1000

1100

1350

1400

1500

1800

1900

2000

2100

2200

m3/h 0

48

54

60

66

81

84

90

108

114

120

126

132

OH4n

RATED

OH3m

TYPE

OH3n

RISK CLASS

Q = DELIVERY

NPSHr [METRES COLUMN OF WATER]

kW

65-160/40

65-160/D119

1x4

1,9

1,8

1,9

1,9

2,5

2,7

3,3

7,4

65-160/55

65-160/D129

1 x 5,5

1,9

1,9

1,9

1,9

2,4

2,6

3,1

5,4

6,6

65-160/75

65-160/D137

1 x 7,5

1,9

1,9

1,9

1,9

2,4

2,6

3,1

5,4

6,6

65-160/110A 65-160/D168

1 x 11

1,3

1,4

1,6

1,7

2,1

2,1

2,4

3,5

4,2

1,3

1,4

1,6

1,7

2,1

2,1

2,4

3,5

4,2

1,7

1,7

1,6

1,7

1,7

1,9

4,1

6,4

65-160/110

65-160/D177

1 x 11

65-200/150

65-200/D192

1 x 15

8,0
5,2

65-200/185

65-200/D203

1 x 18,5

1,7

1,7

1,6

1,7

1,7

1,9

3,0

3,9

5,3

65-200/220

65-200/D215

1 x 22

1,7

1,7

1,6

1,7

1,7

1,9

3,0

3,9

5,3

7,5

65-250/300

65-250/D240

1 x 30

1,3

1,3

1,4

1,5

1,7

3,2

4,1

5,4

7,0

65-250/370

65-250/D255

1 x 37

1,3

1,3

1,3

1,4

1,6

2,9

3,7

4,8

6,2

The declared NPSH values were obtained in the laboratory and refer to a single service pump
OHn, OHm = risk class value referred to the required rated and maximum capacity (Tab.6 para 7.3.1 EN12845)
Check that NPSHd NPSHr+1m is satisfied at the maximum requested capacity

95

8,1

12845_1p-shf65-2p50_NPSHr-en_a_th

Lowara
HYDRA
ULIC PERFORMANCE T
ABLE A
T 50 HZ (POSITIVE SUCTION HEAD)
HYDRAULIC
TABLE
AT
TABELLA DI PRESTAZIONI IDRAULICHE NETTE GRUPPI EN12845 SERIE SHF80 2 poli 50 Hz 1 POMPA DI SERVIZIO, ASP ESCLUSA INST SOPRA
GEN../SHF 80 BOOSTER SETS SERIES
RATED

SHF..

POWER

ELECTRIC

PUMP

PUMP

80-160/110
80-160/150
80-160/185
80-200/220
80-200/300
80-200/370
80-250/450
80-250/550
80-250/750

Q = DELIVERY
l/min 0

1200

1500

1800

2100

2300

3216

3300

3500

3600

3700

3800

4000

m3/h 0

72

90

108

126

138

193

198

210

216

222

228

240

14,1
20,2
31,1
40,4
44,6
59,6
77,0

12,4
29,3
38,5

27,4
36,6

32,7

57,3
74,8

72,5

H = TOTAL HEAD METRES COLUMN OF WATER

kW

80-160/D169
80-160/D177
80-160/D186
80-200/D198
80-200/D215
80-200/D226
80-250/D237
80-250/D252
80-250/D270

1 x 11
1 x 15
1 x 18,5
1 x 22
1 x 30
1 x 37
1 x 45
1 x 55
1 x 75

HH1n

TYPE

OH4n

RISK CLASS

33,0
39,5
46,4
51,9
62,2
69,8
82,2
93,9
109,7

30,9
37,8
44,7

69,9

28,6
35,6
42,6
48,5
59,7
68,1
79,1
91,9
108,6

25,7
32,7
39,8
45,8
57,1
65,7
76,2
89,2
106,0

22,2
29,4
36,6
42,5
53,9
62,8
72,6
85,9
102,7

19,7
26,9
34,2
40,1
51,5
60,5
69,8
83,2
100,2

6,2
13,2
20,7
26,7
37,8
47,2
53,3
67,7
85,0

4,8
11,8
19,3
25,3
36,4
45,7
51,5
66,0
83,3

8,4
15,9
21,9
32,9
42,2
47,0
61,8
79,2

Performance levels relative to set with 1 service pump running and compliant with ISO 9906 - Annex A.
12845_1pg-sp-shf80-2p50-en_a_th
OHn = risk class value referred to the required rated capacity (Tab.6 para 7.3.1 EN12845)
Inlet pressure drops must be deducted. Make sure that these drops, added to the difference in level (max. 3.2m), are less than 4.5m
The values shown identify performance levels according to the reference standard EN12845.

HYDRA
ULIC PERFORMANCE T
ABLE A
T 50 HZ (SUCTION LIF
T)
HYDRAULIC
TABLE
AT
LIFT)
TABELLA DI PRESTAZIONI IDRAULICHE NETTE GRUPPI EN12845 SERIE SHF80 2 poli 50 Hz 1 POMPA DI SERVIZIO, ASP ESCLUSA INST SOTTO
GEN../SHF 80 BOOSTER SETS SERIES
RATED

SHF..

POWER

ELECTRIC

PUMP

PUMP

80-160/110
80-160/150
80-160/185
80-200/220
80-200/300
80-200/370
80-250/450
80-250/550
80-250/750

Q = DELIVERY
l/min 0

1200

1500

1800

2100

2300

3216

3300

3500

3600

3700

3800

4000

m3/h 0

72

90

108

126

138

193

198

210

216

222

228

240

14,1
20,2
31,1
40,4
44,6
59,6
77,0

12,4
29,3
38,5

27,4
36,6

32,7

57,3
74,8

72,5

H = TOTAL HEAD METRES COLUMN OF WATER

kW

80-160/D169
80-160/D177
80-160/D186
80-200/D198
80-200/D215
80-200/D226
80-250/D237
80-250/D252
80-250/D270

1 x 11
1 x 15
1 x 18,5
1 x 22
1 x 30
1 x 37
1 x 45
1 x 55
1 x 75

HH1n

TYPE

OH4n

RISK CLASS

33,0
39,5
46,4
51,9
62,2
69,8
82,2
93,9
109,7

30,9
37,8
44,7

69,9

28,6
35,6
42,6
48,5
59,7
68,1
79,1
91,9
108,6

25,7
32,7
39,8
45,8
57,1
65,7
76,2
89,2
106,0

22,2
29,4
36,6
42,5
53,9
62,8
72,6
85,9
102,7

19,7
26,9
34,2
40,1
51,5
60,5
69,8
83,2
100,2

6,2
13,2
20,7
26,7
37,8
47,2
53,3
67,7
85,0

Performance levels relative to set with 1 service pump running and compliant with ISO 9906 - Annex A.
OHn = risk class value referred to the required rated capacity (Tab.6 para 7.3.1 EN12845)
Inlet pressure drops must be deducted. Make sure these drops are less than 4.5m
The values shown identify performance levels according to the reference standard EN12845.

96

4,8
11,8
19,3
25,3
36,4
45,7
51,5
66,0
83,3

8,4
15,9
21,9
32,9
42,2
47,0
61,8
79,2

12845_1pg-st-shf80-2p50-en_a_th

Lowara
NPSH REQUIRED FOR PUMP SERIES SHF 80

TABELLA DI PRESTAZIONI IDRAULICHE GRUPPI EN12845 SERIE SHF80 2 poli 50 Hz 1 POMPA DI SERVIZIO

POWER

ELECTRIC

PUMP

PUMP

80-160/110
80-160/150
80-160/185
80-200/220
80-200/300
80-200/370
80-250/450
80-250/550
80-250/750

l/min 0

1200

1500

1800

2100

2300

3216

3300

3500

3600

3700

3800

4000

m3/h 0

72

90

108

126

138

193

198

210

216

222

228

240

6,1
4,9
4,4
4,4
4,6
4,6
4,6

6,8
4,7
4,7

5,0
5,0

6,0

5,1
5,1

6,0

Q = DELIVERY

NPSHr [METRES COLUMN OF WATER]

kW

80-160/D169
80-160/D177
80-160/D186
80-200/D198
80-200/D215
80-200/D226
80-250/D237
80-250/D252
80-250/D270

1 x 11
1 x 15
1 x 18,5
1 x 22
1 x 30
1 x 37
1 x 45
1 x 55
1 x 75

HH1m

SHF..

HH1n

RATED

OH4m

TYPE

OH4n

RISK CLASS

2,3
2,3
2,3

2,0

2,5
2,5
2,5
2,2
2,2
2,2
1,9
1,9
1,9

2,7
2,7
2,7
2,4
2,4
2,4
2,2
2,2
2,2

3,0
2,9
2,9
2,7
2,6
2,6
2,4
2,4
2,4

3,2
3,0
3,0
2,8
2,8
2,8
2,6
2,6
2,6

5,9
4,3
4,3
3,9
3,7
3,7
3,6
3,6
3,6

6,5
4,6
4,6
4,1
3,8
3,8
3,7
3,7
3,7

5,5
5,5
4,6
4,2
4,2
4,2
4,2
4,2

The declared NPSH values were obtained in the laboratory and refer to a single service pump
12845_1p-shf80-2p50_NPSHr-en_a_th
OHn, OHm, HHn, HHm = risk class value referred to the required rated and maximum capacity (Tab.6 para 7.3.1, Tab.7 para 7.3.2 EN12845)
Check that NPSHd NPSHr+1m is satisfied at the maximum requested capacity

97

Lowara
GEN../SHF 32-80 BOOSTER SETS
TABELLA DATI ELETTRICI GRUPPI GEN../SHF 2 poli 50 Hz
ELECTRICAL DA
TA T
ABLE A
T 50 Hz
DAT
TABLE
AT
ELECTRIC

ELECTRIC

CURRENT

SERVICE PUMP

JOCKEY PUMP

ABSORBED SET

3 X 400 V

3 X 400V

3 X 400 V
TYPE

NOMINAL

SHF..
ELECTRIC

POWER
PUMP

PUMP

32-125/07
32-125/11
32-160/15
32-160/22
32-200/30
32-200/40
32-250/55
32-250/75
32-250/110
40-125/11
40-125/15
40-125/22
40-160/30
40-160/40
40-200/55
40-200/75
40-250/110A
40-250/110
40-250/150
50-125/22
50-125/30
50-125/40
50-160/55
50-160/75
50-200/110A
50-200/110
50-250/150
50-250/185
50-250/220
65-160/40
65-160/55
65-160/75
65-160/110A
65-160/110
65-200/150
65-200/185
65-200/220
65-250/300
65-250/370
80-160/110
80-160/150
80-160/185
80-200/220
80-200/300
80-200/370
80-250/450
80-250/550
80-250/750

32-125/D121
32-125/D136
32-160/D150
32-160/D168
32-200/D188
32-200/D204
32-250/D222
32-250/D242
32-250/D256
40-125/D112
40-125/D126
40-125/D143
40-160/D159
40-160/D171
40-200/D190
40-200/D209
40-250/D218
40-250/D233
40-250/D251
50-125/D119
50-125/D130
50-125/D139
50-160/D158
50-160/D174
50-200/D197
50-200/D209
50-250/D224
50-250/D237
50-250/D250
65-160/D119
65-160/D129
65-160/D137
65-160/D168
65-160/D177
65-200/D192
65-200/D203
65-200/D215
65-250/D240
65-250/D255
80-160/D169
80-160/D177
80-160/D186
80-200/D198
80-200/D215
80-200/D226
80-250/D237
80-250/D252
80-250/D270

Pn

In

kW

0,75
1,1
1,5
2,2
3
4
5,5
7,5
11
1,1
1,5
2,2
3
4
5,5
7,5
11
11
15
2,2
3
4
5,5
7,5
11
11
15
18,5
22
4
5,5
7,5
11
11
15
18,5
22
30
37
11
15
18,5
22
30
37
45
55
75

2,15
2,61
3,02
4,68
5,77
7,59
10,70
13,90
19,80
2,61
3,02
4,68
5,77
7,59
10,70
13,90
19,80
19,80
26,20
4,68
5,77
7,59
10,70
13,90
19,80
19,80
26,20
33,40
41,70
7,59
10,70
13,90
19,80
19,80
26,20
33,40
41,70
54,00
65,00
19,80
26,70
33,40
41,70
54,00
65,00
80,00
99,00
133,00

TYPE

SV206
SV206
SV206
SV206
SV206
SV209
SV209
SV209
SV209
SV206
SV206
SV206
SV206
SV206
SV206
SV209
SV209
SV209
SV209
SV206
SV206
SV206
SV206
SV206
SV209
SV209
SV209
SV209
SV209
SV206
SV206
SV206
SV206
SV206
SV209
SV209
SV209
SV209
SV212
SV407
SV407
SV407
SV407
SV409
SV409
SV409
SV413
SV413

Pn

In

GEN..10

GEN..11

GEN..20

kW

0,75
0,75
0,75
0,75
0,75
1,1
1,1
1,1
1,1
0,75
0,75
0,75
0,75
0,75
0,75
1,1
1,1
1,1
1,1
0,75
0,75
0,75
0,75
0,75
1,1
1,1
1,1
1,1
1,1
0,75
0,75
0,75
0,75
0,75
1,1
1,1
1,1
1,1
1,5
1,1
1,1
1,1
1,1
1,5
1,5
1,5
2,2
2,2

2,02
2,02
2,02
2,02
2,02
2,61
2,61
2,61
2,61
2,02
2,02
2,02
2,02
2,02
2,02
2,61
2,61
2,61
2,61
2,02
2,02
2,02
2,02
2,02
2,61
2,61
2,61
2,61
2,61
2,02
2,02
2,02
2,02
2,02
2,61
2,61
2,61
2,61
3,45
2,61
2,61
2,61
2,61
3,45
3,45
3,45
5,03
5,03

2,15
2,61
3,02
4,68
5,77
7,59
10,70
13,90
19,80
2,61
3,02
4,68
5,77
7,59
10,70
13,90
19,80
19,80
26,20
4,68
5,77
7,59
10,70
13,90
19,80
19,80
26,20
33,40
41,70
7,59
10,70
13,90
19,80
19,80
26,20
33,40
41,70
54,00
65,00
19,80
26,70
33,40
41,70
54,00
65,00
80,00
99,00
133,00

4,17
4,63
5,04
6,70
7,79
10,20
13,31
16,51
22,41
4,63
5,04
6,70
7,79
9,61
12,72
16,51
22,41
22,41
28,81
6,70
7,79
9,61
12,72
15,92
22,41
22,41
28,81
36,01
44,31
9,61
12,72
15,92
21,82
21,82
28,81
36,01
44,31
56,61
68,45
22,41
29,31
36,01
44,31
57,45
68,45
83,45
104,03
138,03

4,30
5,22
6,04
9,36
11,54
15,18
21,40
27,80
39,60
5,22
6,04
9,36
11,54
15,18
21,40
27,80
39,60
39,60
52,40
9,36
11,54
15,18
21,40
27,80
39,60
39,60
52,40
66,80
83,40
15,18
21,40
27,80
39,60
39,60
52,40
66,80
83,40
108,00
130,00
39,60
53,40
66,80
83,40
108,00
130,00
160,00
198,00
266,00

6,32
7,24
8,06
11,38
13,56
17,79
24,01
30,41
42,21
7,24
8,06
11,38
13,56
17,20
23,42
30,41
42,21
42,21
55,01
11,38
13,56
17,20
23,42
29,82
42,21
42,21
55,01
69,41
86,01
17,20
23,42
29,82
41,62
41,62
55,01
69,41
86,01
110,61
133,45
42,21
56,01
69,41
86,01
111,45
133,45
163,45
203,03
271,03

The current indicated is the maximum current absorbed by the electric pumps.

GEN..21

ENELP-SHF_2p50-en_b_te

98

Lowara
Fire-fighting
booster sets
EN 12845

MARKET SECTORS
CIVIL, INDUSTRIAL
APPLICA
TIONS
APPLICATIONS
Fixed fire-fighting systems.

Automatic Sprinkler systems.

GEN..10/SHF
Series

SPECIFICA
TIONS
SPECIFICATIONS
Flow up to 220 m3/h.
Head up to 100 m.
Panel supply power voltage:
3 x 400V 10%.

Motor start-up :

- Direct for powers up to 22 kW


inclusive for pump (GEND...).
- Star/Delta for higher
powers (GENY... set).

Electric service pump

Frequency: 50 Hz.
Voltage for controls outside panel:
24 Vac.

with horizontal axis


axis:
- SHF Series (motor protection
grade IP55).

Maximum running pressure:


12 bar.

Protection grade:

- electric panel: IP54.

Electric pumps maximum power


75 kW.

99

Lowara
GEN..10/SHF 32-80 SERIES
FIRE-FIGHTING BOOSTER SETS EN 12845

100

Lowara
GEN..10/SHF 32-80 SERIES
FIRE-FIGHTING BOOSTER SETS EN 12845
GEN..10

DRW

DNA

DNM

N
SHF32-125/07

R 2"

Rp 1" 1/2

740

80

212

360

820

773

1347

SHF32-125/11

R 2"

Rp 1" 1/2

740

80

212

360

820

773

1347

SHF32-160/15

R 2"

Rp 1" 1/2

840

80

232

390

920

813

1387

SHF32-160/22

R 2"

Rp 1" 1/2

840

80

232

390

920

813

1387

SHF32-200/30

R 2"

Rp 1" 1/2

840

80

260

390

920

861

1435

SHF32-200/40

R 2"

Rp 1" 1/2

840

80

260

390

920

861

1435

SHF32-250/55

R 2"

Rp 1" 1/2

1045

100

280

490

1145

926

1500

SHF32-250/75

R 2"

Rp 1" 1/2

1045

100

280

490

1145

926

1500

SHF32-250/110

R 2"

Rp 1" 1/2

1175

100

280

540

1275

926

1500

SHF40-125/11

65

65

740

80

212

360

820

994

1582

SHF40-125/15

65

65

840

80

212

390

920

994

1582

SHF40-125/22

65

65

840

80

212

390

920

994

1582

SHF40-160/30

65

65

840

80

232

390

920

1034

1622

SHF40-160/40

65

65

840

80

232

390

920

1034

1622

SHF40-200/55

65

65

940

100

260

450

1040

1082

1670

SHF40-200/75

65

65

940

100

260

450

1040

1082

1670

SHF40-250/110A

65

65

1175

100

280

540

1275

1147

1735

SHF40-250/110

65

65

1175

100

280

540

1275

1147

1735

SHF40-250/150

65

65

1175

100

280

540

1275

1147

1735

SHF50-125/22

65

65

840

100

232

390

940

1116

1704

SHF50-125/30

65

65

840

100

232

390

940

1116

1704

SHF50-125/40

65

65

840

100

232

390

940

1116

1704

SHF50-160/55

65

65

940

100

260

450

1040

1164

1752

SHF50-160/75

65

65

940

100

260

450

1040

1164

1752

SHF50-200/110A

65

65

1060

100

260

490

1160

1184

1772

SHF50-200/110

65

65

1060

100

260

490

1160

1184

1772

SHF50-250/150

65

65

1175

100

280

540

1275

1229

1817

SHF50-250/185

65

65

1175

100

280

540

1275

1229

1817

SHF50-250/220

65

65

1175

100

280

540

1275

1229

1817

SHF65-160/40

80

80

825

100

260

390

925

1221

1815

SHF65-160/55

80

80

925

100

260

450

1025

1221

1815

SHF65-160/75

80

80

925

100

260

450

1025

1221

1815

SHF65-160/110A

80

80

1175

100

260

540

1275

1241

1835

SHF65-160/110

80

80

1175

100

260

540

1275

1241

1835

SHF65-200/150

80

80

1175

100

280

540

1275

1286

1880

SHF65-200/185

80

80

1175

100

280

540

1275

1286

1880

SHF65-200/220

80

80

1175

100

280

540

1275

1286

1880

SHF65-250/300

80

80

1310

100

310

610

1410

1341

1935

SHF65-250/370

80

80

1310

100

310

610

1410

1341

1935

SHF80-160/110

100

100

1175

125

280

540

1300

1354

1961

SHF80-160/150

100

100

1175

125

280

540

1300

1354

1961

SHF80-160/185

100

100

1175

125

280

540

1300

1354

1961

SHF80-200/220

100

100

1175

125

280

540

1300

1379

1986

SHF80-200/300

100

100

1325

125

310

610

1450

1409

2016

SHF80-200/370

100

100

1310

125

310

610

1435

1439

2046

SHF80-250/450

100

100

1310

125

365

610

1435

1494

2101

SHF80-250/550

100

100

1510

125

390

660

1635

1519

2126

100

1710

125

420

730

1835

1549

SHF80-250/750
2
100
Dimensions in mm. Tolerance 10 mm.

2156
gen10_shf-en_d_td

101

Lowara

102

Lowara
Fire-fighting
booster sets
EN 12845

MARKET SECTORS
CIVIL, INDUSTRIAL
APPLICA
TIONS
APPLICATIONS
Fixed fire-fighting systems.
Automatic Sprinkler systems.

GEN..11/SHF
Series

SPECIFICA
TIONS
SPECIFICATIONS
Flow up to 220 m3/h.
Head up to 100 m.
Panel supply power voltage:
3 x 400V 10%.

Motor start-up :

- Direct for powers up to 22 kW


inclusive for pump (GEND...).
- Star/Delta for higher
powers (GENY... set).

Electric service pump

Frequency: 50 Hz.
Voltage for controls outside panel:
24 Vac.

with horizontal axis


axis:
- SHF Series (motor protection
grade IP55).

ey pump
Electric jock
jockey

Protection grade:

- electric panel: IP54.

Electric pumps maximum power


75 kW.

with vertical axis


axis:
- SV Series (motor protection
grade IP55).

Maximum running pressure:


12 bar.

103

Lowara
GEN..11/SHF 32-80 SERIES
FIRE-FIGHTING BOOSTER SETS EN 12845

104

Lowara
GEN..11/SHF 32-80 SERIES
FIRE-FIGHTING BOOSTER SETS EN 12845
GEN..11

DRW DNA

DNP

DNM

A1

N
SHF32-125/07

R 2"

Rp 1"

Rp 1" 1/2

320

260

240

590

45

225

312 1400 370

950

955

873 1447

SHF32-125/11

R 2"

Rp 1"

Rp 1" 1/2

320

260

240

590

45

225

312 1400 370

950

955

873 1447

SHF32-160/15

R 2"

Rp 1"

Rp 1" 1/2

327

253

240

650

65

225

332 1400 370

950 1035 913 1487

SHF32-160/22

R 2"

Rp 1"

Rp 1" 1/2

327

253

240

650

65

225

332 1400 370

950 1035 913 1487

SHF32-200/30

R 2"

Rp 1"

Rp 1" 1/2

327

253

240

650

65

225

360 1400 370

950 1035 961 1535

SHF32-200/40

R 2"

Rp 1"

Rp 1" 1/2

327

253

240

650

65

225

360 1400 370

950 1035 961 1535

SHF32-250/55

R 2"

Rp 1"

Rp 1" 1/2

448

282

240

790

90

245

400 1420 440 1170 1220 1046 1620

SHF32-250/75

R 2"

Rp 1"

Rp 1" 1/2

448

282

240

790

90

245

400 1420 440 1170 1220 1046 1620

SHF32-250/110

R 2"

Rp 1"

Rp 1" 1/2

459

271

280

890

105

245

400 1570 440 1170 1375 1046 1620

SHF40-125/11

65

Rp 1"

65

327

253

240

590

45

225

312 1400 370

950

SHF40-125/15

65

Rp 1"

65

327

253

240

650

65

225

312 1400 370

950 1035 1094 1682

SHF40-125/22

65

Rp 1"

65

327

253

240

650

65

225

312 1400 370

950 1035 1094 1682

SHF40-160/30

65

Rp 1"

65

327

253

240

650

65

225

332 1400 370

950 1035 1134 1722

SHF40-160/40

65

Rp 1"

65

327

253

240

650

65

225

332 1400 370

950 1035 1134 1722

SHF40-200/55

65

Rp 1"

65

338

222

240

710

85

245

380 1420 440 1000 1135 1202 1790

SHF40-200/75

65

Rp 1"

65

338

222

240

710

85

245

380 1420 440 1000 1135 1202 1790

SHF40-250/110A

65

Rp 1"

65

459

271

280

890

105

245

400 1570 440 1170 1375 1267 1855

SHF40-250/110

65

Rp 1"

65

459

271

280

890

105

245

400 1570 440 1170 1375 1267 1855

SHF40-250/150

65

Rp 1"

65

459

271

280

890

105

245

400 1570 440 1170 1375 1267 1855

SHF50-125/22

65

Rp 1"

65

327

253

240

650

65

225

332 1400 370

950 1055 1216 1804

SHF50-125/30

65

Rp 1"

65

327

253

240

650

65

225

332 1400 370

950 1055 1216 1804

SHF50-125/40

65

Rp 1"

65

327

253

240

650

65

225

332 1400 370

950 1055 1216 1804

SHF50-160/55

65

Rp 1"

65

338

222

240

710

85

245

380 1420 440 1000 1135 1284 1872

SHF50-160/75

65

Rp 1"

65

338

222

240

710

85

245

380 1420 440 1000 1135 1284 1872

SHF50-200/110A

65

Rp 1"

65

448

282

280

790

105

245

380 1570 440 1170 1275 1304 1892

SHF50-200/110

65

Rp 1"

65

448

282

280

790

105

245

380 1570 440 1170 1275 1304 1892

SHF50-250/150

65

Rp 1"

65

459

271

280

890

105

245

400 1570 440 1170 1375 1349 1937

SHF50-250/185

65

Rp 1"

65

459

271

280

890

105

245

400 1750 440 1170 1375 1349 1937

SHF50-250/220

65

Rp 1"

65

459

271

280

890

105

245

400 1750 440 1170 1375 1349 1937

SHF65-160/40

80

Rp 1"

80

323

237

240

650

50

225

360 1400 440 1000 1040 1321 1915

SHF65-160/55

80

Rp 1"

80

338

392

240

710

70

245

380 1420 440 1170 1120 1341 1935

SHF65-160/75

80

Rp 1"

80

338

392

240

710

70

245

380 1420 440 1170 1120 1341 1935

SHF65-160/110A

80

Rp 1"

80

459

271

280

890

105

245

380 1570 440 1170 1375 1361 1955

SHF65-160/110

80

Rp 1"

80

459

271

280

890

105

245

380 1570 440 1170 1375 1361 1955

SHF65-200/150

80

Rp 1"

80

459

271

280

890

105

245

400 1570 440 1170 1375 1406 2000

SHF65-200/185

80

Rp 1"

80

459

271

280

890

105

245

400 1750 440 1170 1375 1406 2000

SHF65-200/220

80

Rp 1"

80

459

271

280

890

105

245

400 1750 440 1170 1375 1406 2000

SHF65-250/300

80

Rp 1"

80

453

227

280

990

115

245

430 1750 490 1170 1485 1461 2055

SHF65-250/370

80

Rp 1"

80

453

227

280

990

115

245

430 1750 490 1170 1485 1461 2055

SHF80-160/110

100 Rp 1" 1/4

100

459

271

280

890

105

245

400 1570 440 1170 1400 1474 2081

SHF80-160/150

100 Rp 1" 1/4

100

459

271

280

890

105

245

400 1570 440 1170 1400 1474 2081

SHF80-160/185

100 Rp 1" 1/4

100

459

271

280

890

105

245

400 1750 440 1170 1400 1474 2081

SHF80-200/220

100 Rp 1" 1/4

100

459

271

280

890

105

245

400 1750 440 1170 1400 1499 2106

SHF80-200/300

100 Rp 1" 1/4

100

453

227

280

990

130

245

430 1750 490 1170 1525 1529 2136

SHF80-200/370

100 Rp 1" 1/4

100

453

227

280

990

115

245

430 1750 490 1170 1510 1559 2166

SHF80-250/450

100 Rp 1" 1/4

100

453

227

330

990

115

245

485 1940 490 1170 1560 1614 2221

SHF80-250/550

100 Rp 1" 1/4

100

525

275

330 1120 155

265

530 1960 600 1400 1730 1659 2266

SHF80-250/750
2
100 Rp 1" 1/4
Dimensions in mm. Tolerance 10 mm.
(1) Dimensions on request.

100

(1)

(1)

270 1260 185

265

560

600

(1)

955 1094 1682

1840 1689 2296


gen11_shf-en_d_td

105

Lowara

106

Lowara
Fire-fighting
booster sets
EN 12845

MARKET SECTORS
CIVIL, INDUSTRIAL
APPLICA
TIONS
APPLICATIONS
Fixed fire-fighting systems.
Automatic Sprinkler systems.

GEN..20/SHF
Series

SPECIFICA
TIONS
SPECIFICATIONS
Flow up to 440 m3/h.
Head up to 100 m.
Panel supply power voltage:
3 x 400V 10%.

Motor start-up :

- Direct for powers up to 22 kW


inclusive for pump (GEND...).
- Star/Delta for higher
powers (GENY... set).

Electric service pump

Frequency: 50 Hz.
Voltage for controls outside panel:
24 Vac.

with horizontal axis


axis:
- SHF Series (motor protection
grade IP55).

Maximum running pressure:

Protection grade:

12 bar.

- electric panel: IP54.

Electric pumps maximum power


75 kW.

107

Lowara
GEN..20/SHF 32-80 SERIES
FIRE-FIGHTING BOOSTER SETS EN 12845

108

Lowara
GEN..20/SHF 32-80 SERIES
FIRE-FIGHTING BOOSTER SETS EN 12845
GEN..20

DRW

DNA

DNM

N
SHF32-125/07

R 2"

R 2"

345

240

590

45

312

1400

480

1170

955

879

1459

SHF32-125/11

R 2"

R 2"

345

240

590

45

312

1400

480

1170

955

879

1459

SHF32-160/15

R 2"

R 2"

345

240

650

65

332

1400

480

1170

1035

919

1499

SHF32-160/22

R 2"

R 2"

345

240

650

65

332

1400

480

1170

1035

919

1499

SHF32-200/30

R 2"

R 2"

345

240

650

65

360

1400

480

1170

1035

967

1547

SHF32-200/40

R 2"

R 2"

345

240

650

65

360

1400

480

1170

1035

967

1547

SHF32-250/55

R 2"

R 2"

385

240

790

90

400

1420

630

1400

1220

1052

1632

SHF32-250/75

R 2"

R 2"

385

240

790

90

400

1420

630

1400

1220

1052

1632

SHF32-250/110

R 2"

R 2"

385

280

890

105

400

1570

630

1400

1375

1052

1632

SHF40-125/11

65

65

335

240

590

45

312

1400

540

1210

955

1094

1682

SHF40-125/15

65

65

335

240

650

65

312

1400

540

1210

1035

1094

1682

SHF40-125/22

65

65

335

240

650

65

312

1400

540

1210

1035

1094

1682

SHF40-160/30

65

65

335

240

650

65

332

1400

540

1210

1035

1134

1722

SHF40-160/40

65

65

335

240

650

65

332

1400

540

1210

1035

1134

1722

SHF40-200/55

65

65

335

240

710

85

380

1420

540

1210

1135

1202

1790

SHF40-200/75

65

65

335

240

710

85

380

1420

540

1210

1135

1202

1790

SHF40-250/110A

65

65

385

280

890

105

400

1570

630

1400

1375

1267

1855

SHF40-250/110

65

65

385

280

890

105

400

1570

630

1400

1375

1267

1855

SHF40-250/150

65

65

385

280

890

105

400

1570

630

1400

1375

1267

1855

SHF50-125/22

65

80

335

240

650

65

332

1400

540

1210

1055

1223

1817

SHF50-125/30

65

80

335

240

650

65

332

1400

540

1210

1055

1223

1817

SHF50-125/40

65

80

335

240

650

65

332

1400

540

1210

1055

1223

1817

SHF50-160/55

65

80

335

240

710

85

380

1420

540

1210

1135

1291

1885

SHF50-160/75

65

80

335

240

710

85

380

1420

540

1210

1135

1291

1885

SHF50-200/110A

65

80

385

280

790

105

380

1570

630

1400

1275

1311

1905

SHF50-200/110

65

80

385

280

790

105

380

1570

630

1400

1275

1311

1905

SHF50-250/150

65

80

385

280

890

105

400

1570

630

1400

1375

1356

1950

SHF50-250/185

65

80

385

280

890

105

400

1750

630

1400

1375

1356

1950

SHF50-250/220

65

80

385

280

890

105

400

1750

630

1400

1375

1356

1950

SHF65-160/40

80

100

335

240

650

50

360

1400

540

1210

1040

1333

1940

SHF65-160/55

80

100

335

240

710

70

380

1420

540

1210

1120

1353

1960

SHF65-160/75

80

100

335

240

710

70

380

1420

540

1210

1120

1353

1960

SHF65-160/110A

80

100

350

280

890

105

380

1570

700

1400

1375

1373

1980

SHF65-160/110

80

100

350

280

890

105

380

1570

700

1400

1375

1373

1980

SHF65-200/150

80

100

350

280

890

105

400

1570

700

1400

1375

1418

2025

SHF65-200/185

80

100

350

280

890

105

400

1750

700

1400

1375

1418

2025

SHF65-200/220

80

100

350

280

890

105

400

1750

700

1400

1375

1418

2025

SHF65-250/300

80

100

425

280

990

115

430

1750

700

1550

1485

1473

2080

SHF65-250/370

80

100

425

280

990

115

430

1750

700

1550

1485

1473

2080

SHF80-160/110

100

125

350

280

890

105

400

1570

700

1400

1400

1487

2107

SHF80-160/150

100

125

350

280

890

105

400

1570

700

1400

1400

1487

2107

SHF80-160/185

100

125

350

280

890

105

400

1750

700

1400

1400

1487

2107

SHF80-200/220

100

125

350

280

890

105

400

1750

700

1400

1400

1512

2132

SHF80-200/300

100

125

425

280

990

130

430

1750

700

1550

1525

1542

2162

SHF80-200/370

100

125

425

280

990

115

430

1750

700

1550

1510

1572

2192

SHF80-250/450

100

125

425

330

990

115

485

1940

700

1550

1560

1627

2247

SHF80-250/550

100

125

430

330

1120

155

530

1960

820

1680

1730

1672

2292

SHF80-250/750
2
100
Dimensions in mm. Tolerance 10 mm.
(1) Dimensions on request.

125

(1)

270

1260

185

560

(1)

(1)

1840

1702

2322

gen20_shf-en_e_td

109

Lowara

110

Lowara
Fire-fighting
booster sets
EN 12845

MARKET SECTORS
CIVIL, INDUSTRIAL
APPLICA
TIONS
APPLICATIONS
Fixed fire-fighting systems.
Automatic Sprinkler systems.

GEN..21/SHF
Series

SPECIFICA
TIONS
SPECIFICATIONS
Flow up to 440 m3/h.
Head up to 100 m.
Panel supply power voltage:
3 x 400V 10%.

Motor start-up :

- Direct for powers up to 22 kW


inclusive for pump (GEND...).
- Star/Delta for higher
powers (GENY... set).

Electric service pump

Frequency: 50 Hz.
Voltage for controls outside panel:
24 Vac.

with horizontal axis


axis:
- SHF Series (motor protection
grade IP55).

ey pump
Electric jock
jockey

Protection grade:

- electric panel: IP54.

Electric pumps maximum power


75 kW.

with vertical axis


axis:
- SV Series (motor protection
grade IP55).

Maximum running pressure:


12 bar.

111

Lowara
GEN..21/SHF 32-80 SERIES
FIRE-FIGHTING BOOSTER SETS EN 12845

112

Lowara
GEN..21/SHF 32-80 SERIES
FIRE-FIGHTING BOOSTER SETS EN 12845
GEN..21

DRW

DNA

DNP

DNM

Q
1459

N
SHF32-125/07

R 2"

Rp 1"

R 2"

350

240

590

45

225

312

1400

370

1440

955

879

SHF32-125/11

R 2"

Rp 1"

R 2"

350

240

590

45

225

312

1400

370

1440

955

879

1459

SHF32-160/15

R 2"

Rp 1"

R 2"

350

240

650

65

225

332

1400

370

1440 1035

919

1499

SHF32-160/22

R 2"

Rp 1"

R 2"

350

240

650

65

225

332

1400

370

1440 1035

919

1499

SHF32-200/30

R 2"

Rp 1"

R 2"

350

240

650

65

225

360

1400

370

1440 1035

967

1547

SHF32-200/40

R 2"

Rp 1"

R 2"

350

240

650

65

225

360

1400

370

1440 1035

967

1547

SHF32-250/55

R 2"

Rp 1"

R 2"

400

240

790

90

245

400

1420

440

1680 1220 1052 1632

SHF32-250/75

R 2"

Rp 1"

R 2"

400

240

790

90

245

400

1420

440

1680 1220 1052 1632

SHF32-250/110

R 2"

Rp 1"

R 2"

400

280

890

105

245

400

1570

440

1680 1375 1052 1632

SHF40-125/11

65

Rp 1"

65

350

240

590

45

225

312

1400

370

1440

SHF40-125/15

65

Rp 1"

65

350

240

650

65

225

312

1400

370

1440 1035 1094 1682

SHF40-125/22

65

Rp 1"

65

350

240

650

65

225

312

1400

370

1440 1035 1094 1682

SHF40-160/30

65

Rp 1"

65

350

240

650

65

225

332

1400

370

1440 1035 1134 1722

SHF40-160/40

65

Rp 1"

65

350

240

650

65

225

332

1400

370

1440 1035 1134 1722

SHF40-200/55

65

Rp 1"

65

335

240

710

85

245

380

1420

440

1550 1135 1202 1790

SHF40-200/75

65

Rp 1"

65

335

240

710

85

245

380

1420

440

1550 1135 1202 1790

SHF40-250/110A

65

Rp 1"

65

400

280

890

105

245

400

1570

440

1680 1375 1267 1855

SHF40-250/110

65

Rp 1"

65

400

280

890

105

245

400

1570

440

1680 1375 1267 1855

SHF40-250/150

65

Rp 1"

65

400

280

890

105

245

400

1570

440

1680 1375 1267 1855

SHF50-125/22

65

Rp 1"

80

350

240

650

65

225

332

1400

370

1440 1055 1223 1817

SHF50-125/30

65

Rp 1"

80

350

240

650

65

225

332

1400

370

1440 1055 1223 1817

SHF50-125/40

65

Rp 1"

80

350

240

650

65

225

332

1400

370

1440 1055 1223 1817

SHF50-160/55

65

Rp 1"

80

335

240

710

85

245

380

1420

440

1550 1135 1291 1885

SHF50-160/75

65

Rp 1"

80

335

240

710

85

245

380

1420

440

1550 1135 1291 1885

SHF50-200/110A

65

Rp 1"

80

400

280

790

105

245

380

1570

440

1680 1275 1311 1905

SHF50-200/110

65

Rp 1"

80

400

280

790

105

245

380

1570

440

1680 1275 1311 1905

SHF50-250/150

65

Rp 1"

80

400

280

890

105

245

400

1570

440

1680 1375 1356 1950

SHF50-250/185

65

Rp 1"

80

400

280

890

105

245

400

1750

440

1680 1375 1356 1950

SHF50-250/220

65

Rp 1"

80

400

280

890

105

245

400

1750

440

1680 1375 1356 1950

SHF65-160/40

80

Rp 1"

100

335

240

650

50

225

360

1400

440

1550 1040 1333 1940

SHF65-160/55

80

Rp 1"

100

335

240

710

70

245

380

1420

440

1550 1120 1353 1960

SHF65-160/75

80

Rp 1"

100

335

240

710

70

245

380

1420

440

1550 1120 1353 1960

SHF65-160/110A

80

Rp 1"

100

400

280

890

105

245

380

1570

440

1680 1375 1373 1980

SHF65-160/110

80

Rp 1"

100

400

280

890

105

245

380

1570

440

1680 1375 1373 1980

SHF65-200/150

80

Rp 1"

100

400

280

890

105

245

400

1570

440

1680 1375 1418 2025

SHF65-200/185

80

Rp 1"

100

400

280

890

105

245

400

1750

440

1680 1375 1418 2025

SHF65-200/220

80

Rp 1"

100

400

280

890

105

245

400

1750

440

1680 1375 1418 2025

SHF65-250/300

80

Rp 1"

100

430

280

990

115

245

430

1750

490

1840 1485 1473 2080

SHF65-250/370

80

Rp 1"

100

430

280

990

115

245

430

1750

490

1840 1485 1473 2080

SHF80-160/110

100

Rp 1" 1/4

125

400

280

890

105

245

400

1570

440

1680 1400 1487 2107

SHF80-160/150

100

Rp 1" 1/4

125

400

280

890

105

245

400

1570

440

1680 1400 1487 2107

SHF80-160/185

100

Rp 1" 1/4

125

400

280

890

105

245

400

1750

440

1680 1400 1487 2107

SHF80-200/220

100

Rp 1" 1/4

125

400

280

890

105

245

400

1750

440

1680 1400 1512 2132

SHF80-200/300

100

Rp 1" 1/4

125

430

280

990

130

245

430

1750

490

1840 1525 1542 2162

SHF80-200/370

100

Rp 1" 1/4

125

430

280

990

115

245

430

1750

490

1840 1510 1572 2192

SHF80-250/450

100

Rp 1" 1/4

125

430

330

990

115

245

485

1940

490

1840 1560 1627 2247

SHF80-250/550

100

Rp 1" 1/4

125

470

330

1120

155

265

530

1960

600

2140 1730 1672 2292

SHF80-250/750
2
100
Rp 1" 1/4
Dimensions in mm. Tolerance 10 mm.

125

505

270

1260

185

265

560

600

2210 1840 1702 2322

955

1094 1682

gen21_shf-en_e_td

113

Lowara
GEN../SHF 32-80 SERIES
DIMENSIONS FOR FL
OOR FIXING
FLOOR

114

Lowara
GEN../SHF 32-80 SERIES
DIMENSIONS FOR FL
OOR FIXING
FLOOR
GEN..10

PUMP

GEN..11

GEN..20

GEN..21

SHF 32-125/07

320

540

20

130

770

540

90

25

990

540

90

25

1400

495

90

25

SHF 32-125/11

320

540

20

130

770

540

90

25

990

540

90

25

1400

495

90

25

SHF 32-160/15

350

600

20

150

770

600

90

25

990

600

90

25

1400

555

90

25

SHF 32-160/22

350

600

20

150

770

600

90

25

990

600

90

25

1400

555

90

25

SHF 32-200/30

350

600

20

150

770

600

90

25

990

600

90

25

1400

555

90

25

SHF 32-200/40

350

600

20

150

770

600

90

25

990

600

90

25

1400

555

90

25

SHF 32-250/55

440

740

25

190

1130

665

20

55

1360

665

20

55

1640

665

20

55

SHF 32-250/75

440

740

25

190

1130

665

20

55

1360

665

20

55

1640

665

20

55

SHF 32-250/110

490

840

25

205

1130

765

20

55

1360

765

20

55

1640

765

20

55

SHF 40-125/11

350

600

20

150

770

540

90

25

1030

600

90

25

1400

495

90

25

SHF 40-125/15

350

600

20

150

770

600

90

25

1030

600

90

25

1400

555

90

25

SHF 40-125/22

350

600

20

150

770

600

90

25

1030

600

90

25

1400

555

90

25

SHF 40-160/30

350

600

20

150

770

600

90

25

1030

600

90

25

1400

555

90

25

SHF 40-160/40

350

600

20

150

770

600

90

25

1030

600

90

25

1400

555

90

25

SHF 40-200/55

400

660

25

170

960

585

20

55

1170

585

20

55

1510

585

20

55

SHF 40-200/75

400

660

25

170

960

585

20

55

1170

585

20

55

1510

585

20

55

SHF 40-250/110A

490

840

25

205

1130

765

20

55

1360

765

20

55

1640

765

20

55

SHF 40-250/110

490

840

25

205

1130

765

20

55

1360

765

20

55

1640

765

20

55

SHF 40-250/150

490

840

25

205

1130

765

20

55

1360

765

20

55

1640

765

20

55

SHF 50-125/22

350

600

20

150

770

600

90

25

1360

765

20

55

1400

555

90

25

SHF 50-125/30

350

600

20

150

770

600

90

25

1360

765

20

55

1400

555

90

25

SHF 50-125/40

350

600

20

150

770

600

90

25

1360

765

20

55

1400

555

90

25

SHF 50-160/55

400

660

25

170

960

585

20

55

1360

765

20

55

1510

585

20

55

SHF 50-160/75

400

660

25

170

960

585

20

55

1360

765

20

55

1510

585

20

55

SHF 50-200/110A

440

740

25

190

1130

665

20

55

1360

765

20

55

1640

665

20

55

SHF 50-200/110

440

740

25

190

1130

665

20

55

1360

765

20

55

1640

665

20

55

SHF 50-250/150

490

840

25

205

1130

765

20

55

1360

765

20

55

1640

765

20

55

SHF 50-250/185

490

840

25

205

1130

765

20

55

1360

765

20

55

1640

765

20

55

SHF 50-250/220

490

840

25

205

1130

765

20

55

1360

765

20

55

1640

765

20

55

SHF 65-160/40

400

660

25

170

960

585

20

55

1170

585

20

55

1510

585

20

55

SHF 65-160/55

440

740

25

190

1130

665

20

55

1170

585

20

55

1640

665

20

55

SHF 65-160/75

440

740

25

190

1130

665

20

55

1170

585

20

55

1640

665

20

55

SHF 65-160/110A

490

840

25

205

1130

765

20

55

1360

765

20

55

1640

765

20

55

SHF 65-160/110

490

840

25

205

1130

765

20

55

1360

765

20

55

1640

765

20

55

SHF 65-200/150

490

840

25

205

1130

765

20

55

1360

765

20

55

1640

765

20

55

SHF 65-200/185

490

840

25

205

1130

765

20

55

1360

765

20

55

1640

765

20

55

SHF 65-200/220

490

840

25

205

1130

765

20

55

1360

765

20

55

1640

765

20

55

SHF 65-250/300

550

940

30

230

1130

865

20

55

1510

865

20

55

1800

865

20

55

SHF 65-250/370

550

940

30

230

1130

865

20

55

1510

865

20

55

1800

865

20

55

SHF 80-160/110

490

840

25

205

1130

765

20

55

1360

765

20

55

1640

765

20

55

SHF 80-160/150

490

840

25

205

1130

765

20

55

1360

765

20

55

1640

765

20

55

SHF 80-160/185

490

840

25

205

1130

765

20

55

1360

765

20

55

1640

765

20

55

SHF 80-200/220

490

840

25

205

1130

765

20

55

1360

765

20

55

1640

765

20

55

SHF 80-200/300

550

940

30

230

1130

865

20

55

1510

865

20

55

1800

865

20

55

SHF 80-200/370

550

940

30

230

1130

865

20

55

1510

865

20

55

1800

865

20

55

SHF 80-250/450

550

940

30

230

1130

865

20

55

1510

865

20

55

1800

865

20

55

SHF 80-250/550

600

1060

30

270

1360

950

20

90

1640

985

20

55

2100

950

20

90

SHF 80-250/750

670

1200

30

300

(1)

(1)

(1)

(1)

(1)

(1)

(1)

(1)

2170

1090

20

90

Dimensions in mm. Tolerance 10 mm.

inter_shf-en_a_td

(1) Dimensions on request

115

Lowara

116

Lowara
GEN../SHF SERIES OF BOOSTER SETS (POSITIVE SUCTION HEAD)
Hc PRES
SURE DROP CURVE IN SUCTION KIT
PRESSURE
2900 [rpm]

0
0

20
20

40

ISO 9906 - Annex A

60

40

80

60

80

Q [US gpm]
120

100

0,25

20
20

40

ISO 9906 - Annex A

60

40

100 Q [Imp gpm]

80

60

80

Q [US gpm]
120

100

0,25

0,8

H [ft]

Hc [m]

0,8

Hc [m]

2900 [rpm]

SH 32 - 160

Q [Imp gpm]
100

0,20

H [ft]

SH 32 - 125

0,20
0,6

0,6

0,15

0,15
0,4

0,4

0,10

0,10

0,2

0,2

0,05

0,05

0,00
6

0,0

0,00
8

0,0
25

15

20

15
32-160/15

150

65-160/150
32-160/15 178
164

10

NPSHr [ft]

NPSHr [m]

10

NPSHr [ft]

NPSHr [m]

2
5

0
5

10

15

100

200

20
20

25

300

400

2900 [rpm]

SH 32 - 200
0

20

40
60

Q [l/min]
500

0
0

80
80

100

100 Q [Imp gpm]

0
0

15

100

200

300

40

400

60

Q [l/min]
500

ISO 9906 - Annex A

60

40

Q [m330
/h]

25

2900 [rpm]

20
20

20

100 Q [Imp gpm]

80
80

Q [US gpm]
120

100

0,25

0,8

H [ft]

Hc [m]

0,8

Hc [m]

10

SH 32 - 250

Q [US gpm]
120

0,25

ISO 9906 - Annex A

60

40

Q [m3/h]
30

0,20

H [ft]

0,20
0,6

0,6

0,15

0,15
0,4

0,4

0,10

0,10

0,2

0,2

0,05

0,05

0,00
8

0,0

0,00
8

0,0

25

25

32-250/55

20

222

20

15
4
32-200/40 204
65-160/150
178

10

NPSHr [m]

188

15
4
65-160/150
178

10

NPSHr [ft]

32-250/110 256
32-250/75 242

NPSHr [ft]

32-200/30

0
0
0

10
100

15
200

20
300

25
400

Q [m330
/h]
Q [l/min]
500

76519_A_CH

0
0
0

10
100

15
200

20
300

The declared performance value are valid for liquids with density = 1.0 Kg/dm3 and kinematic viscosity = 1 mm2/sec.
The NPSHr values required for the service pump were obtained in the laboratory. When using them for EN 12845 for fire-fighting systems, increase the value by 1 m.
Hc: Pressure drop curve in suction kit.

117

25
400

Q [m330
/h]
Q [l/min]
500

76520_A_CH

NPSHr [m]

76518_A_CH

76517_A_CH

Lowara
GEN../SHF SERIES OF BOOSTER SETS (POSITIVE SUCTION HEAD)
Hc PRES
SURE DROP CURVE IN SUCTION KIT
PRESSURE
2900 [rpm]

50

ISO 9906 - Annex A

100

50

150

100

200 Q [US gpm]

150

0,25

50

ISO 9906 - Annex A

100

50

Q [Imp gpm]

150

100

200 Q [US gpm]

150

0,25

0,8

H [ft]

Hc [m]

0,8

Hc [m]

2900 [rpm]

SH 40 - 160

Q [Imp gpm]

0,20

H [ft]

SH 40 - 125

0,20
0,6

0,6

0,15

0,15
0,4

0,4

0,10

0,10

0,2

0,2

0,05

0,05

0,0

0,00
8

0,0

25

20

10

NPSHr [m]

15
4

20

NPSHr [ft]

15
4
10
2

10
100

20
200

300

30
400

50

500

600

2900 [rpm]

SH 40 - 200

700

150

100

Q800
[l/min]

0
0
0

ISO 9906 - Annex A

100

50

Q [m3/h]
50

40

Q [Imp gpm]

0,25

200

0
0

30

300

40

400

500

600

2900 [rpm]
50

100

50

Q [m3/h]
60

50
700

Q800
[l/min]

ISO 9906 - Annex A


200 Q [Imp gpm]

150

100

150

Q [US
250gpm]

200

0,25

0,8

H [ft]

Hc [m]

0,8

Hc [m]

100

20

SH 40 - 250

Q [US gpm]
200

150

10

0,20

H [ft]

0,20
0,6

0,6

0,15

0,15
0,4

0,4

0,10

0,10

0,2

0,2

0,05

0,05

0,0

0,00
8

0,0

25

25

20

10

NPSHr [m]

15
4

20

NPSHr [ft]

40-250/110A

15

216

4
65-160/150
178
40-250/150
40-250/110

251
233

0
0
0

10
100

20
200

300

30
400

40
500

50
600

700

Q [m3/h]
60
Q800
[l/min]

76523_A_CH

10

NPSHr [ft]

0,00
8

NPSHr [m]

76522_A_CH

76521_A_CH

0
0
0

10
200

20

30
400

40
600

The declared performance value are valid for liquids with density = 1.0 Kg/dm3 and kinematic viscosity = 1 mm2/sec.
The NPSHr values required for the service pump were obtained in the laboratory. When using them for EN 12845 for fire-fighting systems, increase the value by 1 m.
Hc: Pressure drop curve in suction kit.

118

50
800

Q [m360
/h]
Q [l/min]
1000

76524_A_CH

NPSHr [m]

25

NPSHr [ft]

0,00
8

Lowara
GEN../SHF SERIES OF BOOSTER SETS (POSITIVE SUCTION HEAD)
Hc PRES
SURE DROP CURVE IN SUCTION KIT
PRESSURE
2900 [rpm]

100

ISO 9906 - Annex A

200

100

300

200

Q [US gpm]
400

300

100

0,25

ISO 9906 - Annex A

200

100

Q [Imp gpm]

300

200

Q [US gpm]
400

300

0,25

0,8

H [ft]

Hc [m]

0,8

Hc [m]

2900 [rpm]

SH 50 - 160

Q [Imp gpm]

0,20

H [ft]

SH 50 - 125

0,20
0,6

0,6

0,15

0,15
0,4

0,4

0,10

0,10

0,2

0,2

0,05

0,05

0,00
8

0,0

0,00
10

0,0

25
30
8
20

15
50-125/40 139
50-125/30
130
65-160/150
178

10

50-160/55

20

119

15
65-160/150
178
50-160/75
174

NPSHr [ft]

119

NPSHr [m]

NPSHr [m]

50-125/22

25

NPSHr [ft]

10
2
2

0
0
0

20
200

40
400

600

60
800

1200

2900 [rpm]

SH 50 - 200
0

100

1000

1400

Q
1600
[l/min]

300

200

Q [Imp gpm]

200

40
400

600

60
800

100

1000

1200

1400

Q
1600
[l/min]

ISO 9906 - Annex A

200

100

3
Q [m100
/h]

80

2900 [rpm]

Q [US gpm]
400

300

20

SH 50 - 250

Q [Imp gpm]

300

200

Q [US gpm]
400

300

H [ft]
0,25

0,8

0,20

H [ft]

0,30
Hc [m]

0,30

0,25

0,8

0,20
0,6

0,6

0,15

0,15
0,4

0,4

0,10

0,10
0,2

0,05

0,00
10

0,2

0,05

0,0

0,00
10

0,0

30

30

8
25

50-200/110 209
65-160/150
178

15

20

6
50-250/150

224

15
65-160/150
178

10

50-250/220
50-250/185

250

NPSHr [ft]

20
NPSHr [m]

NPSHr [m]

197

NPSHr [ft]

50-200/110A

25

10

237

0
0
0

20
200

40
400

600

60
800

1000

80
1200

1400

3
Q [m100
/h]

Q
1600
[l/min]

5
76527_A_CH

0
0
0

20
200

40
400

600

60
800

1000

80
1200

The declared performance value are valid for liquids with density = 1.0 Kg/dm3 and kinematic viscosity = 1 mm2/sec.
The NPSHr values required for the service pump were obtained in the laboratory. When using them for EN 12845 for fire-fighting systems, increase the value by 1 m.
Hc: Pressure drop curve in suction kit.

119

1400

3
Q [m100
/h]

Q
1600
[l/min]

76528_A_CH

Hc [m]

0
0

ISO 9906 - Annex A

200

100

3
Q [m100
/h]

80

76526_A_CH

76525_A_CH

Lowara
GEN../SHF SERIES OF BOOSTER SETS (POSITIVE SUCTION HEAD)
Hc PRES
SURE DROP CURVE IN SUCTION KIT
PRESSURE
2900 [rpm]

SH 65 - 160
0

100

200

100

ISO 9906 - Annex A

300

200

300

400
400

Q [US600
gpm]

500

100

200

100

ISO 9906 - Annex A

300

200

300

Q
[Imp gpm]
500

400
400

Q [US600
gpm]

500

Hc [m]

H [ft]
0,25

1,2

H [ft]

0,4

0,30
Hc [m]

2900 [rpm]

SH 65 - 160

Q
[Imp gpm]
500

0,8
1,0

0,3
0,20
0,6

0,8
0,2

0,15

0,6
0,4
0,10

0,4
0,1
0,2

0,05

0,2

0,00
10

0,0

0,0
10

0,0

30

30

8
25

15

NPSHr [m]

NPSHr [m]

65-160/40 139
65-160/30 130
65-160/150
178

20

15
65-160/150
178

10

10

65-160/110 177
65-160/110A 168

0
0
0

20
200

40

400

600

60
800

1000

100

1200

100

1400

1600

2900 [rpm]

SH 65 - 200
0

80

200

100

300

1800

2000

3
Q [m140
/h]

Q
2200
[l/min]

0
0
0

ISO 9906 - Annex A

300

200

120

5
76529_A_CH

200

40

400

Q [US600
gpm]

500

20

600

60
800

1000

0,4

100
100

80
1200

100

1400

1600

200
200

2000

3
Q [m140
/h]

Q
2200
[l/min]

ISO 9906 - Annex A

300
300

120
1800

2900 [rpm]

SH 65 - 250

Q
[Imp gpm]
500

400
400

NPSHr [ft]

20

76530_A_CH

119

NPSHr [ft]

65-160/22

25

400
400

Q [Imp gpm]

500

500

600 Q [US gpm]


700
H [ft]

Hc [m]

H [ft]

Hc [m]

0,6
1,2

0,5
1,5

1,0

0,3

0,4
0,8
0,2

1,0

0,3
0,6
0,2

0,4

0,5

0,1

0,0
10

0,2

0,1

0,0

0,0
10

0,0

30

30

8
25

15
65-160/150
178

65-250/300

240

65-250/370

255

10
65-200/220
65-200/185

10

215
203

20
200

400

40
600

60
800

1000

80
1200

1400

100
1600

120
1800

2000

3
Q [m140
/h]

Q
2200
[l/min]

5
76531_A_CH

15

65-160/150
178

0
0
0

20

40
500

60
1000

80

100
1500

120
2000

The declared performance value are valid for liquids with density = 1.0 Kg/dm3 and kinematic viscosity = 1 mm2/sec.
The NPSHr values required for the service pump were obtained in the laboratory. When using them for EN 12845 for fire-fighting systems, increase the value by 1 m.
Hc: Pressure drop curve in suction kit.

120

140

3
Q [m160
/h]

2500
Q [l/min]

76532_A_CH

20

6
NPSHr [m]

192

NPSHr [ft]

65-200/150

NPSHr [ft]

20

6
NPSHr [m]

25

Lowara
GEN../SHF SERIES OF BOOSTER SETS (POSITIVE SUCTION HEAD)
Hc PRES
SURE DROP CURVE IN SUCTION KIT
PRESSURE
2900 [rpm]

SH 80 - 160
0
0

200
200

400
400

ISO 9906 - Annex A


600

800

600

Q [US gpm]
1000

800

2900 [rpm]

SH 80 - 200

Q [Imp gpm]

200

400
400

600
600

1000 Q [Imp gpm]

800
800

Q [US gpm]
1200

1000

1,0

0,3

H [ft]

H [ft]

1,2

Hc [m]

0,4

Hc [m]

0,4

200

ISO 9906 - Annex A

0,3

1,5

0,2

1,0

0,1

0,5

0,0
10

0,0

0,8
0,2
0,6

0,4
0,1
0,2

0,0
10

0,0

30

30

8
25

80-160/185
80-160/150

186
177

20

198

80-200/370 225
65-160/150
80-200/300
215
178

10

10

0
0

50

100

1000

3000

2900 [rpm]
200

200

400
400

3
Q [m250
/h]

200

2000

SH 80 - 250
0

150

Q4000
[l/min]

0
0
0

50
1000

100

150
2000

200
3000

ISO 9906 - Annex A


600

600

800

Q [Imp gpm]

Q [US gpm]
1000

800

1,2

H [ft]

Hc [m]

0,4

1,0

0,3

0,8
0,2
0,6

0,4
0,1
0,2

0,0
10

0,0

30
8
25

15
65-160/150
178

NPSHr [ft]

20

10
2

0
0
0

50
1000

100

150
2000

200
3000

3
Q [m250
/h]

4000
Q [l/min]

76535_A_CH

The declared performance value are valid for liquids with density = 1.0 Kg/dm3 and kinematic viscosity = 1 mm2/sec.
The NPSHr values required for the service pump were obtained in the laboratory. When using them for EN 12845 for fire-fighting systems, increase the value by 1 m.
Hc: Pressure drop curve in suction kit.

121

250
4000

3
Q [m300
/h]

Q [l/min]
5000

76534_A_CH

5
76533_A_CH

NPSHr [m]

15

NPSHr [ft]

15
65-160/150
178

80-200/220

6
NPSHr [m]

NPSHr [m]

20

169x15

NPSHr [ft]

80-160/150

25

Lowara
GEN../SHF SERIES OF BOOSTER SETS (SUCTION LIF
T)
LIFT)
Hc PRES
SURE DROP CURVE IN SUCTION KIT
PRESSURE
2900 [rpm]

SH 32 - 125
0
0

20
20

40

ISO 9906 - Annex A

60

40

80

60

80

Q [US gpm]
120

100

2900 [rpm]

SH 32 - 160

Q [Imp gpm]
100

0,4

20
20

40

ISO 9906 - Annex A

60

40

100 Q [Imp gpm]

80

60

80

Q [US gpm]
120

100

H [ft]

Hc [m]

H [ft]

Hc [m]

0,6

0,5

1,0

0,3

1,5
0,4

0,2

1,0

0,3
0,5
0,2

0,5

0,1
0,1

0,0
6

0,0

0,0
8

0,0
25

15

20

15
32-160/15

150

65-160/150
32-160/15 178
164

10

NPSHr [ft]

NPSHr [m]

10

NPSHr [ft]

NPSHr [m]

2
5

0
0

10

15

100

200

20
20

25

300

400

2900 [rpm]

SH 32 - 200
0

20

40
60

Q [l/min]
500

80
80

100

10

15

100

100 Q [Imp gpm]

Q [US gpm]
120

300

40

400

60

Q [l/min]
500

ISO 9906 - Annex A

60

40

Q [m330
/h]

25

2900 [rpm]

20
20

20

200

SH 32 - 250

100 Q [Imp gpm]

80
80

Q [US gpm]
120

100

H [ft]
0,5

H [ft]

0,6
Hc [m]

0,6

0,5

1,5

1,5

0,4

0,4

1,0

0,3

1,0

0,3

0,2

0,2
0,5

0,5

0,1

0,1

0,0
8

0,0

0,0
8

0,0

25

25

32-250/55

20

20

15
4
32-200/40 204
65-160/150
178

10

NPSHr [m]

188

15
4
65-160/150
178

10

NPSHr [ft]

32-250/110 256
32-250/75 242

NPSHr [ft]

NPSHr [m]

32-200/30

222

0
0
0

10
100

15
200

20
300

25
400

Q [m330
/h]
Q [l/min]
500

76499_A_CH

0
0
0

10
100

15
200

20
300

The declared performance value are valid for liquids with density = 1.0 Kg/dm3 and kinematic viscosity = 1 mm2/sec.
The NPSHr values required for the service pump were obtained in the laboratory. When using them for EN 12845 for fire-fighting systems, increase the value by 1 m.
Hc: Pressure drop curve in suction kit.

122

25
400

Q [m330
/h]
Q [l/min]
500

76500_A_CH

Hc [m]

0
0

ISO 9906 - Annex A

60

40

Q [m3/h]
30

76498_A_CH

76497_A_CH

Lowara
GEN../SHF SERIES OF BOOSTER SETS (SUCTION LIF
T)
LIFT)
Hc PRES
SURE DROP CURVE IN SUCTION KIT
PRESSURE
2900 [rpm]

SH 40 - 125
0

50

ISO 9906 - Annex A

100

50

150

100

200 Q [US gpm]

150

50

ISO 9906 - Annex A

100

50

Q [Imp gpm]

150

100

200 Q [US gpm]

150

H [ft]
0,5

H [ft]

0,6
Hc [m]

0,6

0,5

1,5

1,5

0,4

0,4

1,0

0,3

1,0

0,3

0,2

0,2
0,5

0,5

0,1

0,1

0,0

0,0
8

0,0

25

20

10

NPSHr [m]

15
4

20

NPSHr [ft]

15
4
10
2

0
0
0

10
100

20
200

300

30
400

50

500

600

2900 [rpm]

SH 40 - 200

700

150

100

Q800
[l/min]

Q [Imp gpm]

100

20
200

Q [US gpm]
200

150

10

30

300

40

400

500

50

100

50

Q [m3/h]
60

50
600

2900 [rpm]

SH 40 - 250

0,6

700

Q800
[l/min]

ISO 9906 - Annex A


200 Q [Imp gpm]

150

100

150

Q [US
250gpm]

200

0,5

H [ft]

Hc [m]

0,6
H [ft]

Hc [m]

0
0

ISO 9906 - Annex A

100

50

Q [m3/h]
50

40

0,5

1,5

1,5

0,4

0,4

1,0

0,3

1,0

0,3

0,2

0,2
0,5

0,5

0,1

0,1

0,0
8

0,0

0,0
8

0,0

25

25

20

10

NPSHr [m]

15
4

20

NPSHr [ft]

NPSHr [m]

76502_A_CH

76501_A_CH

40-250/110A

15

216

4
65-160/150
178
40-250/150
40-250/110

251
233

0
0
0

10
100

20
200

300

30
400

40
500

50
600

700

Q [m3/h]
60
Q800
[l/min]

76503_A_CH

10

NPSHr [ft]

NPSHr [m]

25

NPSHr [ft]

0,0
8

0
0
0

10
200

20

30
400

40
600

The declared performance value are valid for liquids with density = 1.0 Kg/dm3 and kinematic viscosity = 1 mm2/sec.
The NPSHr values required for the service pump were obtained in the laboratory. When using them for EN 12845 for fire-fighting systems, increase the value by 1 m.
Hc: Pressure drop curve in suction kit.

123

50
800

Q [m360
/h]
Q [l/min]
1000

76504_A_CH

Hc [m]

2900 [rpm]

SH 40 - 160

Q [Imp gpm]

Lowara
GEN../SHF SERIES OF BOOSTER SETS (SUCTION LIF
T)
LIFT)
Hc PRES
SURE DROP CURVE IN SUCTION KIT
PRESSURE
2900 [rpm]

SH 50 - 125
0

100

ISO 9906 - Annex A

200

100

300

200

Q [US gpm]
400

300

100

ISO 9906 - Annex A

200

100

Q [Imp gpm]

300

200

Q [US gpm]
400

300

H [ft]
0,5

H [ft]

0,6
Hc [m]

0,6
Hc [m]

2900 [rpm]

SH 50 - 160

Q [Imp gpm]

0,5

1,5

1,5

0,4

0,4

1,0

0,3

1,0

0,3

0,2

0,2
0,5

0,5

0,1

0,1

0,0
8

0,0

0,0
10

0,0

25
30
8
20

15
50-125/40 139
50-125/30
130
65-160/150
178

10

50-160/55

20

119

15
65-160/150
178
50-160/75
174

NPSHr [ft]

119

NPSHr [m]

NPSHr [m]

50-125/22

25

NPSHr [ft]

10
2
2

0
0
0

20
200

40
400

600

60
800

1200

2900 [rpm]

SH 50 - 200
0

100

1000

1400

Q
1600
[l/min]

300

200

Q [Imp gpm]

200

40
400

600

60
800

100

1000

1200

1400

Q
1600
[l/min]

ISO 9906 - Annex A

200

100

3
Q [m100
/h]

80

2900 [rpm]

Q [US gpm]
400

300

20

SH 50 - 250

Q [Imp gpm]

300

200

Q [US gpm]
400

300

H [ft]
0,5

H [ft]

0,6
Hc [m]

0,6

0,5

1,5

1,5

0,4

0,4

1,0

0,3

1,0

0,3

0,2

0,2
0,5

0,5

0,1

0,1

0,0
10

0,0

0,0
10

0,0

30

30

8
25

50-200/110 209
65-160/150
178

15

20

6
50-250/150

224

15
65-160/150
178

10

50-250/220
50-250/185

250

NPSHr [ft]

20
NPSHr [m]

NPSHr [m]

197

NPSHr [ft]

50-200/110A

25

10

237

0
0
0

20
200

40
400

600

60
800

1000

80
1200

1400

3
Q [m100
/h]

Q
1600
[l/min]

5
76507_A_CH

0
0
0

20
200

40
400

600

60
800

1000

80
1200

The declared performance value are valid for liquids with density = 1.0 Kg/dm3 and kinematic viscosity = 1 mm2/sec.
The NPSHr values required for the service pump were obtained in the laboratory. When using them for EN 12845 for fire-fighting systems, increase the value by 1 m.
Hc: Pressure drop curve in suction kit.

124

1400

3
Q [m100
/h]

Q
1600
[l/min]

76508_A_CH

Hc [m]

0
0

ISO 9906 - Annex A

200

100

3
Q [m100
/h]

80

76506_A_CH

76505_A_CH

Lowara
GEN../SHF SERIES OF BOOSTER SETS (SUCTION LIF
T)
LIFT)
Hc PRES
SURE DROP CURVE IN SUCTION KIT
PRESSURE
2900 [rpm]

SH 65 - 160
0

100

200

100

ISO 9906 - Annex A

300

200

300

400
400

Q [US600
gpm]

500

100

200

100

ISO 9906 - Annex A

300

200

300

Q
[Imp gpm]
500

400
400

Q [US600
gpm]

500

H [ft]
0,5

H [ft]

0,6
Hc [m]

0,6

0,5

1,5

1,5

0,4

0,4

1,0

0,3

1,0

0,3

0,2

0,2
0,5

0,5

0,1

0,1

0,0
10

0,0

0,0
10

0,0

30

30

8
25

15

NPSHr [m]

15
65-160/150
178

10

10

65-160/110 177
65-160/110A 168

0
0
0

20
200

40

400

600

60
800

1000

100

1200

100

1400

1600

2900 [rpm]

SH 65 - 200
0

80

200

100

300

1800

2000

3
Q [m140
/h]

Q
2200
[l/min]

Q
[Imp gpm]
500

400
400

200

40

400

Q [US600
gpm]

500

20

600

60
800

1000

100
100

80
1200

100

1400

1600

200
200

2000

3
Q [m140
/h]

Q
2200
[l/min]

ISO 9906 - Annex A

300
300

120
1800

2900 [rpm]

SH 65 - 250

400
400

Q [Imp gpm]

500

500

600 Q [US gpm]


700

H [ft]
0,5

H [ft]

0,6
Hc [m]

0,6
Hc [m]

0
0

ISO 9906 - Annex A

300

200

120

5
76510_A_CH

0,5

1,5

1,5

0,4

0,4

1,0

0,3

1,0

0,3

0,2

0,2
0,5

0,5

0,1

0,1

0,0
10

0,0

0,0
10

0,0

30

30

8
25

20
192

15
65-160/150
178

20

6
NPSHr [m]

65-200/150

NPSHr [ft]

6
NPSHr [m]

25

65-250/300

240

65-250/370

255

10
65-200/220
65-200/185

10

215
203

20
200

400

40
600

60
800

1000

80
1200

1400

100
1600

120
1800

2000

3
Q [m140
/h]

Q
2200
[l/min]

5
76512_A_CH

15

65-160/150
178

NPSHr [ft]

NPSHr [m]

65-160/40 139
65-160/30 130
65-160/150
178

20

NPSHr [ft]

20

76511_A_CH

119

NPSHr [ft]

65-160/22

25

0
0
0

20

40
500

60
1000

80

100
1500

120
2000

The declared performance value are valid for liquids with density = 1.0 Kg/dm3 and kinematic viscosity = 1 mm2/sec.
The NPSHr values required for the service pump were obtained in the laboratory. When using them for EN 12845 for fire-fighting systems, increase the value by 1 m.
Hc: Pressure drop curve in suction kit.

125

140

3
Q [m160
/h]

2500
Q [l/min]

76513_A_CH

Hc [m]

2900 [rpm]

SH 65 - 160

Q
[Imp gpm]
500

Lowara
GEN../SHF SERIES OF BOOSTER SETS (SUCTION LIF
T)
LIFT)
Hc PRES
SURE DROP CURVE IN SUCTION KIT
PRESSURE
2900 [rpm]

SH 80 - 160
0
0

200
200

400
400

ISO 9906 - Annex A


600

800

600

Q [US gpm]
1000

800

200
200

400
400

ISO 9906 - Annex A

600
600

1000 Q [Imp gpm]

800
800

Q [US gpm]
1200

1000

H [ft]
0,5

H [ft]

0,6
Hc [m]

0,6

0,5

1,5

1,5

0,4

0,4

1,0

0,3

1,0

0,3

0,2

0,2
0,5

0,5

0,1

0,1

0,0
10

0,0

0,0
10

0,0

30

30

8
25

80-160/185
80-160/150

186
177

20

198

80-200/370 225
65-160/150
80-200/300
215
178

10

10

0
0

50

100

1000

3000

2900 [rpm]
200

200

400
400

3
Q [m250
/h]

200

2000

SH 80 - 250
0

150

Q4000
[l/min]

0
0
0

50
1000

100

150
2000

200
3000

ISO 9906 - Annex A


600

600

5
76514_A_CH

800

Q [Imp gpm]

Q [US gpm]
1000

800

H [ft]

Hc [m]

0,6

0,5
1,5
0,4

1,0

0,3

0,2
0,5
0,1

0,0
10

0,0

30
8
25

15
65-160/150
178

NPSHr [ft]

20

6
NPSHr [m]

15

NPSHr [ft]

15
65-160/150
178

80-200/220

6
NPSHr [m]

NPSHr [m]

20

169x15

NPSHr [ft]

80-160/150

25

10
2

0
0
0

50
1000

100

150
2000

200
3000

3
Q [m250
/h]

4000
Q [l/min]

76516_A_CH

The declared performance value are valid for liquids with density = 1.0 Kg/dm3 and kinematic viscosity = 1 mm2/sec.
The NPSHr values required for the service pump were obtained in the laboratory. When using them for EN 12845 for fire-fighting systems, increase the value by 1 m.
Hc: Pressure drop curve in suction kit.

126

250
4000

3
Q [m300
/h]

Q [l/min]
5000

76515_A_CH

Hc [m]

2900 [rpm]

SH 80 - 200

Q [Imp gpm]

Lowara

ACCESSORIES

127

Lowara
DIAPHRAGM T
ANKS
TANKS
The booster sets are ready for installation, directly on the manifold, of 24-litre diaphragm tanks, one for each
pump. The sets are also equipped with caps to close off the unused couplings. Larger tanks can also be connected
to the unused end of the discharge manifold. For proper sizing of the tank please refer to the technical appendix.
Kit featuring the following accessories are available on request
request:
diaphragm tank;
on-off ball valve;
operating instructions;
packaging.

DIAPHRAGM
T
ANK KITVESSEL KIT
TANK
STANDARD DIAPHRAGM
DIMENSIONS (mm)

Materials

Volume

PN

Litres

bar

Valve

Diaphragm

Vessel

Valve

205

390

1" FF

EPDM

Painted steel

Nickel-plated brass

24

270

555

1" FF

EPDM

Painted steel

Nickel-plated brass

24

10

270

555

1" FF

EPDM

Painted steel

Nickel-plated brass

24

16

270

555

1" FF

EPDM

Painted steel

Nickel-plated brass

24

10

270

575

1" FF

Butyl

Stainless steel

AISI 316 Stainless steel


gcom-vmb_en_b_td

COUNTERFLANGE KIT
Counterflange coupling kits made of zinc-plated or stainless steel are available on request.
The counterflange kits are equipped with:
- N. 2 flanges.
- gasket and bolts/screws.

THREADED COUNTERFLANGES
DIMENSIONI KIT CONTROFLANGE TONDE FI
DIMENSIONS (mm)

KIT

HOLES

TYPE

DN

PN

2"

50

Rp 2

125

16

165

24

18

25

2"

65

Rp 2

145

16

185

23

18

16

3"

80

Rp 3

160

17

200

27

18

16

Gcom-ctf-tonde-f-en_a_td

DIMENSIONI KIT CONTROFLANGE TONDE A SALDARE


-ON COUNTERFLANGES
WELD-ON
WELD
DIMENSIONS (mm)

KIT

HOLES

TYPE

DN

PN

2"

50

61

125

19

165

18

16

2"1/2

65

77

145

20

185

18

16

3"

80

90

160

20

200

18

16

4"

100

116

180

22

220

18

16

5"

125

141,5

210

22

250

18

16

6"

150

170,5

240

24

285

22

16

8"

200

221,5

295

26

340

22

12

16

10"

250

276,5

355

29

405

26

12

16

12"

300

327,5

410

32

460

26

12

16

Gcom-ctf-tonde-s-en_c_td

128

Lowara
ACCES
SORIES FOR BOOSTER SETS
ACCESSORIES
SUCTION SIDE KIT
The EN 12845 fire-fighting booster sets are supplied without valves and stubs on the suction side of the service pump
and can be completed with suitable kits that depend on legal standards.
These requirements are expressed by EN 12845 (chapter 10.5 and chapter 10.6) and are connected with the maximum
speed value of the water in the pipes, their minimum section and type of installation - suction lift or positive suction
head.
To provide for one suction kit for each duty pump.
The suction side kit are equipped with:
- Anti-vibration joint to attach to the pump inlet.
- Eccentric cone or flanged stub pipe.
- Vacuum pressure gauge.
- On/off butterfly valve with lever handle for diameters up to DN100, butterfly valve with handwheel and
reduction manual gear for DN125 and higher. Device for monitoring ON/OFF status included. Electrical
connections by customer.
(Valve lock kit available on request).
- Weld-on flange.
The following table summarises the pump type installed on the fire-fighting sets and the kit that corresponds to the
installation type.

129

Lowara
GEN../ SERIES OF FIRE-FIGHTING BOOSTER SETS
SUCTION SIDE KIT DIMENSIONS T
ABLE
TABLE

SUCTION
DIMENSIONS

KIT
TYPE

DNS

PN

DNA

PN

L (mm)

H (mm)

50 X 32

50

16

32

16

340

50 X 40

50

16

40

16

340

65 X 32

65

16

32

16

395

17

65 X 40

65

16

40

16

375

14

65 X 50

65

16

50

16

355

80 X 32

80

16

32

16

445

23

80 X 40

80

16

40

16

425

20

80 X 50

80

16

50

16

395

14

80 X 65

80

16

65

16

365

100 X 40

100

16

40

16

520

33

100 X 50

100

16

50

16

500

27

100 X 65

100

16

65

16

470

19

100 X 80

100

16

80

16

435

13

125 X 50

125

16

50

16

605

40

125 X 65

125

16

65

16

565

32

125 X 80

125

16

80

16

540

25

125 X 100

125

16

100

16

455

13

150 X 65

150

16

65

16

675

46

150 X 80

150

16

80

16

640

40

150 X 100

150

16

100

16

565

27

150 X 125

150

16

125

16

520

14

200 X 80

200

10

80

16

830

65

200 X 100

200

10

100

16

755

52

200 X 125

200

10

125

16

710

40

200 X 150

200

10

150

16

620

25

250 X 100

250

10

100

16

965

79

250 X 125

250

10

125

16

930

67

250 X 150

250

10

150

16

840

52

300 X 125

300

10

125

16

1120

92

300 X 150

300

10

150

16

1040

78

350 X 150

350

10

150

16

1160

94

400 X 150

400

10

150

16

1375

119

Dimensions in mm. Tolerance 10 mm.

kit-asp-en_b_td

130

Lowara
GEN../FHF 32-80 SERIES FIRE-FIGHTING BOOSTER SETS
SUCTION SIDE KIT DIMENSIONS T
ABLE
TABLE
SUCTION LIFT
PUMP

POSITIVE SUCTION HEAD

RISK

SUCTION

RISK

SUCTION

RISK

SUCTION

RISK

CLASS *

KIT

CLASS *

KIT

CLASS *

KIT

CLASS *

TYPE

TYPE

TYPE

SUCTION
KIT
TYPE

FHF 32-125/07

LH

65 X 50

LH

80 X 50

FHF 32-125/11

LH

65 X 50

LH

80 X 50

FHF 32-160/15

LH

65 X 50

LH

80 X 50

FHF 32-160/22

LH

65 X 50

LH

80 X 50

FHF 32-200/30

LH

65 X 50

LH

80 X 50

FHF 32-200/40

LH

65 X 50

LH

80 X 50

FHF 40-125/11

OH1

80 X 65

OH1

100 X 65

FHF 40-125/15

OH1

80 X 65

OH1

100 X 65

FHF 40-125/22

OH1

80 X 65

OH1

100 X 65

FHF 40-160/30

OH1

80 X 65

OH1

100 X 65

FHF 40-160/40

OH1

80 X 65

OH1

100 X 65

FHF 40-200/55

OH1

80 X 65

OH1

100 X 65

FHF 40-200/75

OH1

80 X 65

OH1

100 X 65

FHF 40-250/110A

OH1

80 X 65

OH1

100 X 65

FHF 40-250/110

OH1

80 X 65

OH1

100 X 65

FHF 40-250/150

OH1

80 X 65

OH1

100 X 65

FHF 50-125/22

OH2

100 X 65

OH2

125 X 65

FHF 50-125/30

OH2

100 X 65

OH2

125 X 65

FHF 50-125/40

OH3

125 X 65

OH2

100 X 65

OH3

150 X 65

OH2

125 X 65

FHF 50-160/55

OH3

125 X 65

OH2

100 X 65

OH3

150 X 65

OH2

125 X 65

FHF 50-160/75

OH3

125 X 65

OH2

100 X 65

OH3

150 X 65

OH2

125 X 65

FHF 50-200/110A

OH3

125 X 65

OH2

100 X 65

OH3

150 X 65

OH2

125 X 65

FHF 50-200/110

OH3

125 X 65

OH2

100 X 65

OH3

150 X 65

OH2

125 X 65

FHF 50-250/150

OH3

125 X 65

OH2

100 X 65

OH3

150 X 65

OH2

125 X 65

FHF 50-250/185

OH3

125 X 65

OH2

100 X 65

OH3

150 X 65

OH2

125 X 65

FHF 50-250/220

OH3

125 X 65

OH2

100 X 65

OH3

150 X 65

OH2

125 X 65

FHF 65-125/40

OH3

125 X 80

OH3

150 X 80

FHF 65-125/55

OH3

125 X 80

OH3

150 X 80

FHF 65-125/75

OH3

125 X 80

OH3

150 X 80

FHF 65-160/110A

OH4

150 X 80

OH3

125 X 80

OH4

200 X 80

OH3

150 X 80

FHF 65-160/110

OH4

150 X 80

OH3

125 X 80

OH4

200 X 80

OH3

150 X 80

FHF 65-160/150

OH4

150 X 80

OH3

125 X 80

OH4

200 X 80

OH3

150 X 80

FHF 65-200/150

OH4

150 X 80

OH3

125 X 80

OH4

200 X 80

OH3

150 X 80

FHF 65-200/185

OH4

150 X 80

OH3

125 X 80

OH4

200 X 80

OH3

150 X 80

FHF 65-200/220

OH4

150 X 80

OH3

125 X 80

OH4

200 X 80

OH3

150 X 80

FHF 65-250/220

OH4

150 X 80

OH3

125 X 80

OH4

200 X 80

OH3

150 X 80

FHF 65-250/300

OH4

150 X 80

OH3

125 X 80

OH4

200 X 80

OH3

150 X 80

FHF 65-250/370

OH4

150 X 80

OH3

125 X 80

OH4

200 X 80

OH3

150 X 80

FHF 80-160/150

HH1

200 X 100

OH4

150 X 100

HH1

200 X 100

OH4

200 X 100

FHF 80-160/185

HH1

200 X 100

OH4

150 X 100

HH1

200 X 100

OH4

200 X 100

FHF 80-200/220

HH1

200 X 100

OH4

150 X 100

HH1

200 X 100

OH4

200 X 100

FHF 80-200/300

HH1

200 X 100

OH4

150 X 100

HH1

200 X 100

OH4

200 X 100

FHF 80-250/370

HH1

200 X 100

OH4

150 X 100

HH1

200 X 100

OH4

200 X 100

FHF 80-250/450

HH1

200 X 100

OH4

150 X 100

HH1

200 X 100

OH4

200 X 100

FHF 80-250/550

HH1

200 X 100

OH4

150 X 100

HH1

200 X 100

OH4

* For the risk classes refer to para 6, UNI EN12845.

200 X 100
kit-asp-fhf-en_b_td

- the pumps must be chosen according to the performance levels indicated in Tab. 6 para 7.3.1, Tab.7 para 7.3.2 and the classes of risk.
- some pump models can satisfy the conditions of one or more classes of risk.
- always check the correct selection of the pump depending on the performance level of the set.
** Insert the 50 mm minimal thickness under the GEN10 fire-fighting booster sets only.

131

Lowara
GEN../FHF 100-125 SERIES FIRE-FIGHTING BOOSTER SETS
SUCTION SIDE KIT DIMENSIONS T
ABLE
TABLE
SUCTION LIFT
PUMP

POSITIVE SUCTION HEAD

RISK

SUCTION

RISK

SUCTION

RISK

SUCTION

RISK

CLASS *

KIT

CLASS *

KIT

CLASS *

KIT

CLASS *

TYPE

TYPE

TYPE

SUCTION
KIT
TYPE

FHF 100-160/185

HH3

250 X 125

HH2

250 X 125

HH3

250 X 125

HH2

250 X 125

FHF 100-160/220

HH4

250 X 125

HH3

250 X 125

HH4

300 X 125**

HH3

250 X 125

FHF 100-160/300

HH4

250 X 125

HH3

250 X 125

HH4

300 X 125**

HH3

250 X 125

FHF 100-200/185

HH3

250 X 125**

HH2

250 X 125**

HH3

250 X 125**

HH2

250 X 125**

FHF 100-200/300

HH3

250 X 125**

HH2

250 X 125**

HH3

250 X 125**

HH2

250 X 125**

FHF 100-200/370

HH4

250 X 125**

HH3

250 X 125**

HH4

300 X 125**

HH3

250 X 125**

FHF 100-200/450

HH4

250 X 125

HH3

250 X 125

HH4

300 X 125**

HH3

250 X 125

FHF 100-250/300

HH3

250 X 125

HH2

250 X 125

HH3

250 X 125

HH2

250 X 125

FHF 100-250/450

HH4

250 X 125

HH3

250 X 125

HH4

300 X 125**

HH3

250 X 125

FHF 100-250/550

HH4

250 X 125

HH3

250 X 125

HH4

300 X 125

HH3

250 X 125

FHF 100-250/750

HH5

300 X 125

HH4

250 X 125

HH5

300 X 125

HH4

300 X 125

FHF 100-250/900

HH6

300 X 125

HH5

300 X 125

HH6

300 X 125

HH5

300 X 125

FHF 125-200/300

HH7

300 X 150

HH6

300 X 150

HH7

300 X 150

HH6

300 X 150

FHF 125-200/450

HH9

300 X 150

HH8

300 X 150

HH9

400 X 150**

HH8

350 X 150**

FHF 125-200/550

HH10

350 X 150**

HH9

300 X 150

HH10

400 X 150**

HH9

400 X 150**

FHF 125-270/750

HH10

350 X 150

HH9

300 X 150

HH10

400 X 150

HH9

400 X 150

FHF 125-270/900

HH10

350 X 150

HH9

300 X 150

HH10

400 X 150

HH9

400 X 150

FHF 125-270/1100

HH10

350 X 150

HH9

300 X 150

HH10

400 X 150

HH9

400 X 150

FHF 125-270/1320

HH10

350 X 150

HH9

300 X 150

HH10

400 X 150

HH9

400 X 150

* For the risk classes refer to para 6, UNI EN12845.

kit-asp-fhf100-en_a_td

- the pumps must be chosen according to the performance levels indicated in Tab. 6 para 7.3.1, Tab. 7 para 7.3.2 and the classes of risk.
- some pump models can satisfy the conditions of one or more classes of risk.
- always check the correct selection of the pump depending on the performance level of the set.
** Insert the 50mm minimal thickness under the GEN10 fire-fighting booster sets only.

132

Lowara
GEN../SHF 32-80 SERIES FIRE-FIGHTING BOOSTER SETS
SUCTION SIDE KIT DIMENSIONS T
ABLE
TABLE
SUCTION LIFT
PUMP

POSITIVE SUCTION HEAD

RISK

SUCTION

RISK

SUCTION

RISK

SUCTION

RISK

CLASS *

KIT

CLASS *

KIT

CLASS *

KIT

CLASS *

TYPE

TYPE

TYPE

SUCTION
KIT
TYPE

SHF 32-125/07

LH

65 X 50

LH

80 X 50

SHF 32-125/11

LH

65 X 50

LH

80 X 50

SHF 32-160/15

LH

65 X 50

LH

80 X 50

SHF 32-160/22

LH

65 X 50

LH

80 X 50

SHF 32-200/30

LH

65 X 50

LH

80 X 50

SHF 32-200/40

LH

65 X 50

LH

80 X 50

SHF 32-250/55

LH

65 X 50

LH

80 X 50

SHF 32-250/75

LH

65 X 50

LH

80 X 50

SHF 32-250/110

LH

65 X 50

LH

80 X 50

SHF 40-125/11

OH1

80 X 65

OH1

100 X 65

SHF 40-125/15

OH1

80 X 65

OH1

100 X 65

SHF 40-125/22

OH1

80 X 65

OH1

100 X 65

SHF 40-160/30

OH1

80 X 65

OH1

100 X 65

SHF 40-160/40

OH1

80 X 65

OH1

100 X 65

SHF 40-200/55

OH1

80 X 65

OH1

100 X 65

SHF 40-200/75

OH1

80 X 65

OH1

100 X 65

SHF 40-250/110A

OH1

80 X 65

OH1

100 X 65

SHF 40-250/110

OH1

80 X 65

OH1

100 X 65

SHF 40-250/150

OH1

80 X 65

OH1

100 X 65

SHF 50-125/22

OH2

100 X 65

OH2

125 X 65

SHF 50-125/30

OH2

100 X 65

OH2

125 X 65

SHF 50-125/40

OH3

125 X 65

OH2

100 X 65

OH3

150 X 65

OH2

125 X 65

SHF 50-160/55

OH3

125 X 65

OH2

100 X 65

OH3

150 X 65

OH2

125 X 65

SHF 50-160/75

OH3

125 X 65

OH2

100 X 65

OH3

150 X 65

OH2

125 X 65

SHF 50-200/110A

OH3

125 X 65

OH2

100 X 65

OH3

150 X 65

OH2

125 X 65

SHF 50-200/110

OH3

125 X 65

OH2

100 X 65

OH3

150 X 65

OH2

125 X 65

SHF 50-250/150

OH2

100 X 65

OH2

125 X 65

SHF 50-250/185

OH3

125 X 65

OH2

100 X 65

OH3

150 X 65

OH2

125 X 65

SHF 50-250/220

OH3

125 X 65

OH2

100 X 65

OH3

150 X 65

OH2

125 X 65

SHF 65-160/40

OH3

125 X 80

OH3

150 X 80

SHF 65-160/55

OH3

125 X 80

OH3

150 X 80

SHF 65-160/75

OH3

125 X 80

OH3

150 X 80

SHF 65-160/110A

OH3

125 X 80

OH3

150 X 80

SHF 65-160/110

OH3

125 X 80

OH3

150 X 80

SHF 65-200/150

OH3

125 X 80

OH3

150 X 80

SHF 65-200/185

OH3

125 X 80

OH3

150 X 80

SHF 65-200/220

OH4

150 X 80

OH3

125 X 80

OH4

200 X 80

OH3

150 X 80

SHF 65-250/300

OH4

150 X 80

OH3

125 X 80

OH4

200 X 80

OH3

150 X 80

SHF 65-250/370

OH4

150 X 80

OH3

125 X 80

OH4

200 X 80

OH3

150 X 80

SHF 80-160/110

HH1

200 X 100

OH4

150 X 100

HH1

200 X 100

OH4

200 X 100

SHF 80-160/150

HH1

200 X 100

OH4

150 X 100

HH1

200 X 100

OH4

200 X 100

SHF 80-160/185

HH1

200 X 100

OH4

150 X 100

HH1

200 X 100

OH4

200 X 100

SHF 80-200/220

HH1

200 X 100

OH4

150 X 100

HH1

200 X 100

OH4

200 X 100

SHF 80-200/300

HH1

200 X 100

OH4

150 X 100

HH1

200 X 100

OH4

200 X 100

SHF 80-200/370

HH1

200 X 100

OH4

150 X 100

HH1

200 X 100

OH4

200 X 100

SHF 80-250/450

HH1

200 X 100

OH4

150 X 100

HH1

200 X 100

OH4

200 X 100

SHF 80-250/550

HH1

200 X 100

OH4

150 X 100

HH1

200 X 100

OH4

200 X 100

SHF 80-250/750

HH1

200 X 100

OH4

150 X 100

HH1

200 X 100

OH4

* For the risk classes refer to para 6, UNI EN12845.

200 X 100
kit-asp-shf-en_a_td

- the pumps must be chosen according to the performance levels indicated in Tab. 6 para 7.3.1, Tab. 7 para 7.3.2 and the classes of risk.
- some pump models can satisfy the conditions of one or more classes of risk.
- always check the correct selection of the pump depending on the performance level of the set.
** Insert the 50mm minimal thickness under the GEN10 fire-fighting booster sets only.

133

Lowara
ALARMS CONTROL ELECTRICAL P
ANEL
PANEL
Electric panel for remote status and alarm monitoring of one or two Lowara pumps installed in GEN fire-fighting
booster sets, according to EN12845.
In the electric service pump mode, the following conditions are visualised:
- Motor powered.
- Pump start-up request.
- Pump running
- Failure to start.
Additionally: minimum suction tank level, minimum priming tank level, on-off valve on suction and discharge side
not fully open. The valves are complete with status monitor.
In the diesel engine service pump mode, the following conditions are visualised, as required by EN12845:
- Switch on diesel engine pump control panel in non-automatic position.
- Diesel engine ails to start after 6 attempts.
- Pump running
- Controller fault.
Additionally: minimum fuel or suction tank level, minimum priming tank level, on-off valve on suction and
discharge side not fully open. The valves are complete with status monitor.
All the above conditions, required by EN12845, are visualised with signal LEDs and buzzers. A buzzer alarm reset
button and LED tester button are included.
The control unit is also fitted out to signal the following general alarms, if present:
- General alarm for incorrect electrical connection in the exchange contacts of: flow meter circuit valve, discharge
pump, jockey pump status.
- Fault in electrical connection in the exchange contact relative to panel 1 (electric pump/diesel engine pump)
- Fault in electrical connection in the exchange contact relative to panel 2 (electric pump/diesel engine pump)
- Jockey pump overload (*).
- Jockey pump running(*)
- Discharge pump overload (*).
- Battery voltage low.
- Communications failure with ModBus system.
All the above conditions are visualised with signal LEDs and on the display. The customer may decide to enable
the buzzer.
The panel comprises a plastic casing (IP55), battery, battery charger, alarms and pump status display, if connected
with 485 serial communication.
Fitted to transmit alarms for GSM or PC module.
The electric connection between the contacts on the electric alarms control panel and other electric panels is to be
seen to by the person installing the equipment.
(*) Check that the electric control panel combined with the electric pump is complete with clean contacts for
pump running and overload signals.

QUADRO TAMPONE ALLARMI


TIONS
SPECIFICATIONS
TECHNICAL SPECIFICA

275

DESCRIPTION

Input voltage (single-phase)

VALUE

(1F+N) 230V +/-10%, 50-60 Hz

V
L1/

V
+

L2/

L2/

V
L3

A
L3

N.P.

INCREASE

Absorbed

0,1A

Rated battery voltage

A
L1/

370 x 275 x 160 mm

Protection grade
Battery

ENTER

DECREASE / MENU'

IP55

370

Dimensions

SHIFT

Hermetic lead
12 Vcc

LAMPS TEST
PROVA
LAMPADE

BUZZER
SWITCH OFF
TACITAZIONE
SIRENA

ELECTRIC PUMP / POMPA ELETTRICA

L2
L1

JOCKEY PUMP

L3

Type

DSRC

Plant Type:
Tipo impianto:

GA11E+1D

POWER ON
PRESENZA TENSIONE
-

2,3 Ah ( uncharged in 20 h)

Dimensions of battery

178 x 34 x 66 mm

Sound emission levels

75dB

Control panel weight

1,5kg

+ UNDER THRESHOLD
SOTTO SOGLIA
PUMP ON
POMPA IN MARCIA

INTERRUPTED LINES
LINEE INTERROTTE

Voltage 230 V - 50-60 Hz


Battery 12 V 2,3 Ah

Code N. 32.000.10.0
Buzzer 12Vcc 90mA 75dB(A)

L2

OVERLOAD
SOVRACCARICO
SPRINKLER PUMPS ROOM
SPRINKLER SALA POMPE
PUMP SET ON DEMAND
RICHIESTA DI AVVIAMENTO
SELECTOR NOT IN
AUT. FUNCTION
SELETTORE NON IN AUT.

!
OFF

!
OFF
1

DIESEL PUMP / MOTOPOMPA

POMPA COMPENSAZIONE

Rated battery capacity

L3

L1

Circ. N. 17.029.001.0
0,2 A

IP 55

PHASE SEQUENCE FAILURE


ERRATA SEQUENZA FASE

MINIMUM FUEL LEVEL


MIN. LIVELLO COMBUSTIBILE

START FAILURE
MANCATO AVVIAMENTO

SWITCHBOARD FAILURE
GUASTO QUADRO

!
OFF
1

!
OFF
2

MINIMUM LEVEL SUCTION TANK


MINIMO LIVELLO VASCA ASPIRAZIONE
MINIMUM LEVEL PRIMING TANK
MINIMO LIVELLO VASCA ADESCAMENTO
PARTIALLY OPENED SUCTION VALVE
VALVOLA IN ASPIRAZIONE NON
COMPLETAMENTE APERTA
PARTIALLY OPENED DISCHARGE VALVE
VALVOLA IN MANDATA NON
COMPLETAMENTE APERTA

12845_002_D_DD

12845-qal-en_b_td

134

SPRINKLER DRAINAGE
PUMPS ROOM FAULT PUMP

ACCORDING TO EN12845

Lowara
FL
OW METER KIT
FLOW
The flow meter is supplied as part of the assembly kit. The EN 12845 standard requires the presence of the flow meter
for checking the hydraulic performance during the test stage and duration periodic inspections. The suction side kit
are equipped with:
- Direct reading flow meter.
- On/off ball valve for diameters up to 2" inclusive, butterfly valve with lever handle from DN65 to DN100
diameter, butterfly valve with handwheel and reduction manual gear for DN125 diameter and above. Device
for monitoring ON/OFF status included. Electrical connections by customer. (Valve lock kit available on request).
- Connection piping.
The meter is available in various sizes according to the flow of a service pump and suitable for being connected to the
offtake of the head manifold. For a correct match, identify the type as shown in the set size tables. The flow meter
must be installed, where possible, in a stretch of piping with a steady flow and sufficient back pressure at the
discharge outlet. The assembly and the discharge piping towards the tank and discharge outlet are to be seen to by
the person installing the equipment.

A
SHAPE B
C
TABELLASHAPE
DIMENSIONALE
KIT_FLUSSIMETRO
GRUPPISHAPE
EN12845

SHAPE D

DIMENSIONS (mm)

DIMENSIONS (mm)

TYPE

TYPE
DN

DNAS

SHAPE

DN

DNAS

SHAPE

32X25P

32

25

90

605

100X40P

100

40

300

760

32X32P

32

32

90

625

100X50P

100

50

300

750

32X40P

32

40

90

645

100X65P

100

65

340

410

40X25P

40

25

100

605

100X80P

100

80

340

410

40X32P

40

32

100

630

100X125

100

125

340

945

40X40P

40

40

100

645

125X50P

125

50

300

760

40X50P

40

50

100

640

125X65P

125

65

340

425

50X25P

50

25

105

610

125X80P

125

80

340

425

50X32P

50

32

105

635

125X125

125

125

340

755

50X40P

50

40

105

655

125X150

125

150

340

1085

50X50P

50

50

105

645

150X65P

150

65

380

435

65X25P

65

25

300

700

150X80P

150

80

380

440

65X32P

65

32

300

725

150X125

150

125

380

770

65X40P

65

40

300

740

150X150

150

150

380

900

65X50P

65

50

300

730

150X200

150

200

380

1380

65X65P

65

65

340

390

200X80P

200

80

380

465

65X80P

65

80

340

595

200X125

200

125

380

795

80X40P

80

40

300

745

200X150

200

150

380

925

80X50P

80

50

300

735

200X200

200

200

380

1170

80X65P

80

65

340

400

250X125

250

125

440

825

80X80P

80

80

340

400

250X150

250

150

440

950

80X125

80

125

340

910

250X200

250

200

440

1195

12845_kit_flux-acc-en_a_td

135

Lowara
TABLE OF COMBINA
TIONS FOR FL
OW METER KIT
COMBINATIONS
FLOW
AND FHF SERVICE PUMP SERIES
ELECTRIC

TYPE

COMBINATION

TYPE

COMBINATION

FHF..

FLOW METER KIT

FHF..

FLOW METER KIT

GEN..

PUMP

PUMP

10

11

ELECTRIC
20

21

GEN..

PUMP

PUMP

10

11

20

21

32-125/07

32-125/D119

40X25P 40X25P 50X25P 50X25P 65-200/150

65-200/D187

80X80P 80X80P 100X80P 100X80P

32-125/11

32-125/D136

40X32P 40X32P 50X32P 50X32P 65-200/185

65-200/D198

80X80P 80X80P 100X80P 100X80P

32-160/15

32-160/D150

40X32P 40X32P 50X32P 50X32P 65-200/220

65-200/D210

80X80P 80X80P 100X80P 100X80P

32-160/22

32-160/D164

40X32P 40X32P 50X32P 50X32P 65-250/220

65-250/D220

80X80P 80X80P 100X80P 100X80P

32-200/30

32-200/D188

40X32P 40X32P 50X32P 50X32P 65-250/300

65-250/D241

80X80P 80X80P 100X80P 100X80P

32-200/40

32-200/D204

40X32P 40X32P 50X32P 50X32P 65-250/370

65-250/D258

80X80P 80X80P 100X80P 100X80P

40-125/11

40-125/D112

65X40P 65X40P 65X40P 65X40P 80-160/150

80-160/D163

100X80P 100X80P 125X80P 125X80P

40-125/15

40-125/D122

65X40P 65X40P 65X40P 65X40P 80-160/185

80-160/D173

100X125 100X125 125X125 125X125

40-125/22

40-125/D143

65X50P 65X50P 65X50P 65X50P 80-200/220

80-200/D189

100X80P 100X80P 125X80P 125X80P

40-160/30

40-160/D159

65X40P 65X40P 65X40P 65X40P 80-200/300

80-200/D207

100X125 100X125 125X125 125X125

40-160/40

40-160/D171

65X50P 65X50P 65X50P 65X50P 80-250/370

80-250/D225

100X80P 100X80P 125X80P 125X80P

40-200/55

40-200/D190

65X40P 65X40P 65X40P 65X40P 80-250/450

80-250/D238

100X125 100X125 125X125 125X125

40-200/75

40-200/D209

100X125 100X125 125X125 125X125

65X50P 65X50P 65X50P 65X50P 80-250/550

80-250/D256

40-250/110A 40-250/D218

65X50P 65X50P 65X50P 65X50P 100-160/185

100-160/D150 125X125 125X125 150X125 150X125

40-250/110

40-250/D233

65X50P 65X50P 65X50P 65X50P 100-160/220

100-160/D165 125X125 125X125 150X125 150X125

40-250/150

40-250/D251

65X50P 65X50P 65X50P 65X50P 100-160/300

100-160/D185 125X150 125X150 200X150 200X150

50-125/22

50-125/D119

65X50P 65X50P 80X50P 80X50P 100-200/185

100-200/D168 125X125 125X125 150X125 150X125

50-125/30

50-125/D130

65X65P 65X65P 80X65P 80X65P 100-200/300

100-200/D192 125X125 125X125 150X125 150X125

50-125/40

50-125/D139

65X65P 65X65P 80X65P 80X65P 100-200/370

100-200/D203 125X125 125X125 150X125 150X125

50-160/55

50-160/D158

65X65P 65X65P 80X65P 80X65P 100-200/450

100-200/D213 125X125 125X125 200X125 200X125

50-160/75

50-160/D174

65X65P 65X65P 80X65P 80X65P 100-250/300

100-250/D200 125X125 125X125 150X125 150X125

50-200/110A 50-200/D197

65X65P 65X65P 80X65P 80X65P 100-250/450

100-250/D221 125X125 125X125 200X125 200X125

50-200/110

50-200/D209

65X65P 65X65P 80X65P 80X65P 100-250/550

100-250/D235 125X125 125X125 200X125 200X125

50-250/150

50-250/D224

65X65P 65X65P 80X65P 80X65P 100-250/750

100-250/D254 125X150 125X150 200X150 200X150

50-250/185

50-250/D237

65X65P 65X65P 80X65P 80X65P 100-250/900

100-250/D267 125X150 125X150 200X150 200X150

50-250/220

50-250/D250

65X65P 65X65P 80X65P 80X65P 125-200/300

125-200/D180 150X150 150X150 200X150 200X150

65-125/40

65-125/D121

80X65P 80X65P 100X65P 100X65P 125-200/450

125-200/D206 150X200 150X200 200X200 200X200

65-125/55

65-125/D129

80X65P 80X65P 100X65P 100X65P 125-200/550

125-200/D216 150X200 150X200 200X200 200X200

65-125/75

65-125/D140

80X65P 80X65P 100X65P 100X65P 125-270/750

125-270/D224 150X200 150X200 250X200 250X200

65-160/110A 65-160/D161

80X80P 80X80P 100X80P 100X80P 125-270/900

125-270/D237 150X200 150X200 250X200 250X200

65-160/110

65-160/D168

80X80P 80X80P 100X80P 100X80P 125-270/1100 125-270/D253 150X200 150X200 250X200 250X200

65-160/150

65-160/D178

80X80P 80X80P 100X80P 100X80P 125-270/1320 125-270/D266 150X200 150X200 250X200 250X200
12845_kit_flux-fhf_10-21-en_b_th

136

Lowara
TABLE OF COMBINA
TIONS FOR FL
OW METER KIT
COMBINATIONS
FLOW
AND SHF SERVICE PUMP SERIES

ELECTRIC

TYPE

COMBINATION

TYPE

COMBINATION

SHF..

FLOW METER KIT

SHF..

FLOW METER KIT

GEN..

PUMP

PUMP

10

11

ELECTRIC
20

21

GEN..

PUMP

PUMP

10

11

20

21

32-125/07

32-125/D121

40X32P 40X32P 50X32P 50X32P 50-200/110A 50-200/D197

65X65P 65X65P 80X65P 80X65P

32-125/11

32-125/D136

40X32P 40X32P 50X32P 50X32P 50-200/110

50-200/D209

65X65P 65X65P 80X65P 80X65P

32-160/15

32-160/D150

40X32P 40X32P 50X32P 50X32P 50-250/150

50-250/D224

65X65P 65X65P 80X65P 80X65P

32-160/22

32-160/D168

40X32P 40X32P 50X32P 50X32P 50-250/185

50-250/D237

65X65P 65X65P 80X65P 80X65P

32-200/30

32-200/D188

40X32P 40X32P 50X32P 50X32P 50-250/220

50-250/D250

65X65P 65X65P 80X65P 80X65P

32-200/40

32-200/D204

40X32P 40X32P 50X32P 50X32P 65-160/40

65-160/D119

80X65P 80X65P 100X65P 100X65P

32-250/55

32-250/D222

40X32P 40X32P 50X32P 50X32P 65-160/55

65-160/D129

80X65P 80X65P 100X65P 100X65P

32-250/75

32-250/D242

40X32P 40X32P 50X32P 50X32P 65-160/75

65-160/D137

80X65P 80X65P 100X65P 100X65P

32-250/110

32-250/D256

40X32P 40X32P 50X32P 50X32P 65-160/110A 65-160/D168

80X65P 80X65P 100X65P 100X65P

40-125/11

40-125/D112

65X40P 65X40P 65X40P 65X40P 65-160/110

65-160/D177

80X65P 80X65P 100X65P 100X65P

40-125/15

40-125/D126

65X40P 65X40P 65X40P 65X40P 65-200/150

65-200/D192

80X65P 80X65P 100X65P 100X65P

40-125/22

40-125/D143

65X40P 65X40P 65X40P 65X40P 65-200/185

65-200/D203

80X65P 80X65P 100X65P 100X65P

40-160/30

40-160/D159

65X40P 65X40P 65X40P 65X40P 65-200/220

65-200/D215

80X80P 80X80P 100X80P 100X80P

40-160/40

40-160/D171

65X50P 65X50P 65X50P 65X50P 65-250/300

65-250/D240

80X80P 80X80P 100X80P 100X80P

40-200/55

40-200/D190

65X50P 65X50P 65X50P 65X50P 65-250/370

65-250/D255

80X80P 80X80P 100X80P 100X80P

40-200/75

40-200/D209

65X50P 65X50P 65X50P 65X50P 80-160/110

80-160/D169

100X80P 100X80P 125X80P 125X80P

40-250/110A 40-250/D218

65X40P 65X40P 65X40P 65X40P 80-160/150

80-160/D177

100X80P 100X80P 125X80P 125X80P

40-250/110

65X40P 65X40P 65X40P 65X40P 80-160/185

80-160/D186

100X125 100X125 125X125 125X125

40-250/D233

40-250/150

40-250/D251

65X50P 65X50P 65X50P 65X50P 80-200/220

80-200/D198

100X125 100X125 125X125 125X125

50-125/22

50-125/D119

65X50P 65X50P 80X50P 80X50P 80-200/300

80-200/D215

100X125 100X125 125X125 125X125

50-125/30

50-125/D130

65X65P 65X65P 80X65P 80X65P 80-200/370

80-200/D226

100X125 100X125 125X125 125X125

50-125/40

50-125/D139

65X65P 65X65P 80X65P 80X65P 80-250/450

80-250/D237

100X125 100X125 125X125 125X125

50-160/55

50-160/D158

65X65P 65X65P 80X65P 80X65P 80-250/550

80-250/D252

100X125 100X125 125X125 125X125

50-160/75

50-160/D174

65X65P 65X65P 80X65P 80X65P 80-250/750

80-250/D270

100X125 100X125 125X125 125X125


12845_kit_flux-shf_10-21-en_b_th

137

Lowara
PRIMING T
ANK
TANK
The priming tank is used in suction lift installations and carries out the function of maintaining the pump body
and suction pipe full of water even if there are leaks through the bottom valve.
Each pump must have its own independent priming tank, placed at a higher level than the pump. The tank must
be connected to a water source for adding water and keeping it full. The diameter of the connecting pipe to the
pump depends on the use class. The return piping for re-circulation can be connected to the tank, which must
also provide for discharge if it is too full.
A level indicator automatically actions the service pump if the level of the tank drops and is not reintegrated.
The hydraulic connections must be seen to by the person installing the equipment.
The horizontal 500 l tank is made of zinc-plated steel.

ACCES
SORIES PRIMING T
ANK KIT
ACCESSORIES
TANK
The available accessories kit includes:
- Filling and discharge valves, reductions, non-return valve, closing plugs and automatic air discharger.
- Float switch tap complete with ring nut for fixing to the hole through the tank.
- Level indicator to connect to the electric panel and assembly instruction sheet.
Available on request tank support, height 75, 100, 150, 200 cm.
Example of connection to the tank and accessories:

1
2
3
4
5
6
7

DESCRIPTION

Pump priming tank


Pipe return from pump delivery side
Floating valve
In flow on-off valve
In flow
Low level switch
Drain

8
9
10
11
12
13
14

DESCRIPTION

Priming supply non return valve


Priming supply on-off valve
Over flow
Pressure switch
Pump
To trunk main
Pipe connection to delivery side of the pump
En-acc-adesc-en_b_tc

138

Lowara
ELECTRIC JOCKEY PUMP KIT
The jockey pump or compensation pump has the job of keeping the system under pressure and compensating for
any small loses without the intervention of the service pumps. In fact, the jockey pump is commanded by an
automatic shut-off panel. Should an electric jockey pump of a different size from the standard be required or
should it be installed later on sets which are not predisposed, or should non-standard different size requirements
be required, it is possible to configure the booster set with just the service pumps and add the electric jockey
pump, also later on.
The kit includes:
- the hydraulic components for installing the electric pump (base, valves, pressure switch).
- the pre-chosen electric pump and the relative electric panel.
The hydraulic connection to the set can be easily carried out using one of the couplings on the delivery manifold
for the membrane tanks using an adaptor.
Kits are available for the vertical electric jockey pumps SV2, SV4, SV8 series and submersed series 2GS, 4GS, 6GS.
The diagram illustrates some connection examples:

1
2
3
4
5

DESCRIPTION

Electric pump
Control Box
Connection to trunk main
Pipe connection to delivery side of the jockey pump
To trunk main
acc-kit-fil-en_a_tc

139

Lowara
PANEL BRACKET KIT
The electric command panels supplied separately, for example in
the sets with submersed pumps, are suitable for being mounted
on the wall. Universal bracket kit are available, upon request, for
supporting the panels; it must be fixed to the floor using blocks.

GU_ACC_M0001_A_SC

HYDRA
ULIC CONNECTION FOR FIRE-FIGHTING EN 12845 SETS
HYDRAULIC

1
2
3
4

DESCRIPTION

Suction piping kit *


Delivery manifold
Drain
From priming tank *

5
6
7
8

* See the instruction sheets.

DESCRIPTION

Flow meter kit *


Drain
Open discharge
To trunk main
En-acc-gener-en_a_tc

140

Lowara
ACCES
SORIES
ACCESSORIES

NEW RATE OF FLOW


INDICATOR < DN100

FLOATS

MONITORED VALVES

VALVES

HYDRO TUBE

FLOW METER

RATE OF FLOW INDICATOR

ELASTIC JOINTS

141

PRESSURE SWITCHS

Lowara
PRODUCT DESCRIPTION B
Y TECHNICAL SPECIFICA
TIONS
BY
SPECIFICATIONS
Description EN 12845 fire-fighting booster set
Series : GEN
Model: electric service pump
jock
ey or compensation pump
jockey
The pump station will comprise the following components:
- N1 electric jockey pump;
- N1 electric service pump;
- One electrical power and control panel for the electric service pump;
- One electrical power and control panel for the electric jockey pump;
- Components and materials required for perfect operation and assembly;
IT
T Lowara booster sets are CE-certified and comply with the following directives:
ITT

Machinery Directive 98/37/EC.


Low V
oltage Directive 2006/95/EC.
Voltage
Electromagnetic Compatibility Directive 89/336/EEC as amended.
The hydraulic pump complies with the following standard:

ISO 9906-A Rotodynamic pumps hydraulic performance acceptance tests.


The fire-fighting booster set complies with European standard EN 12845-2009 :
Fixed fire-fighting installations
Automatic sprinkler systems, design, installation and maintenance.
V
ersion with automatic switch-off according to UNI 10779 Hydrant systems
Version
design, installation and operating.

142

Lowara
PRODUCT DESCRIPTION B
Y TECHNICAL SPECIFICA
TIONS
BY
SPECIFICATIONS
Basic version with periodic auto-test, Series GEN..A.
Electronic auto-test circuit with weekly programmer in the electrical panel of the service pump. The pump is turned
on an kept working for a minute at the previously established time and date.
During this interval the check circuit checks that the pressure in the re-circulation circuit closes the pressure switch
contact of the pump which is running. In the case of irregularities, the relative auxiliary self-test alarm relay available
for remote signalling is activated and memorised.
The EN 12845 Standard does not provide for the presence of a self-test circuit but asks for periodic checks to be
carried out by the user, hence the periodic self-test function cannot substitute the above checks.
For the precalculated HHP and HHS risk class systems and in the integrally calculated systems, the pump must be able
to provide, at 140% of rated capacity, a pressure of not less than 70% of the rated pressure of the pump.
Each pump generally backs up the other even if much depends on the chosen type of water supply. If the service
pump fails, or a blackout occurs, system pressure will decrease and the backup diesel pump will start. The pumps are
started automatically by the pressure switches while they are manually stopped from the electrical panel (key switch).

Fire-fighting set components: electric pump

Electric service pump comprising:


End-suction horizontal centrifugal pump, model FHF
FHF....................., single impeller, with cast iron body and
AISI316L stainless steel shaft. End suction and radial discharge ports. Impeller in AISI316L stainless steel or cast
iron. Hydraulic sizes and nominal diameter DN of suction and discharge ports according to EN 733 (ex DIN
24255).
Flanging to EN 1092-2 (formerly UNI2236) and DIN2532. Maximum running pressure: 12 bar. Mechanical seal
according to EN12756 (formerly DIN 24960) in Ceramic/Carbon/NBR lubricated with recirculation duct between
discharge and seal housing.
The pump is directly coupled to the respective motor with an elastic spacer joint (back pull out version) and
alignment and anchor base.
B3 three-phase electric motor with short circuit squirrel cage, totally enclosed, fan-cooled. The performance levels of
the electric motors lie within what is usually referred to as efficiency class 1. Protected to IP55, insulation class F.

143

Lowara
PRODUCT DESCRIPTION B
Y TECHNICAL SPECIFICA
TIONS
BY
SPECIFICATIONS
Main characteristics of the electric service pump:
TABELLA MATERIALI POMPA SERVIZIO FHF PER CAPITOLATI TECNICI
Brand
Model:
Flow rate
Head:
Pump body:
Seal housing:
Impeller:
Shaft:
Elastomers:
Mechanical seal:
Motor power:
Input voltage:
Frequency:
Rated current input:
Speed of rotation:
Max. ambient temp:
Protection class:
Insulation class:

ITT LOWARA
FHF
m3/h
m.c.a.
Cast iron, EN 1561-GJL-200 (JL1030)
Cast iron, EN 1561-GJL-200 (JL1030)
Cast iron, EN 1561-GJL-200 (JL1030)
Stainless steel EN10088-1-X2 CrNiMo17-12-2
NBR
Ceramic/Carbon/NBR
Kw
V
Hz
A
r.p.m.
C

400 / 3
50
2900
40
IP 55
F

tec_FHF-en_a_tm

Electric jock
ey pump comprising:
jockey
Multi-cell vertical centrifugal Jockey pump, SV
SV... with metal parts in contact with liquid in stainless steel,
pump body and shaft in AISI 304 stainless steel, impeller in AISI 304 stainless steel, mechanical seal in Carburundum/
carbon/EPDM.
Three-phase electric motor, shape B14, performance values within what is referred to as efficiency class 2, short
circuit squirrel cage motor, closed aluminium casing and external ventilation, performance according to EN 60034-1,
directly coupled to the vertical pump. Protected to IP55, insulation class F.

144

Lowara
PRODUCT DESCRIPTION B
Y TECHNICAL SPECIFICA
TIONS
BY
SPECIFICATIONS
Main technical characteristics of the jock
ey pump:
jockey
TABELLA MATERIALI POMPA SERVIZIO SV PER CAPITOLATI TECNICI
Brand:
Model:
Flow rate:
Head:
Pump body:
Impeller:
Diffuser:
Shaft:
Outer sleeve:
Mechanical seal:
Motor power:
Input voltage:
Frequency:
Rated current:
Speed:
Max. ambient temp.:
Protection class:
Insulation class:

ITT LOWARA
SV..
m3/h
m.c.a.
Stainless steel (1.4301)
Stainless steel (1.4301)
Stainless steel (1.4301)
Stainless steel (1.4301)
Stainless steel (1.4301)
Silicon carbide/Carbon/EPDM
Kw
V
Hz
A
r.p.m.
C

400 / 3
50
2900
40
IP - 55
F

tec_SV-en_a_tm

Electric panels

Electric service pump panel


Painted metal casing (IP54) complete with:
-

General door-locking switch.


Analogical ammeter.
MAN AUT 0 selector with extractable key only in automatic position.
Keyboard for indicating electric voltage presence, correct phase sequence (three phase power supply), start-up
request, pump functioning and no start-up, through LED lamps, lamp test button and starting and stopping
buttons, according to the provisions of EN12845 paragraph 10.8.6.

Inside:
-

12/24V transformer for auxiliary circuits and electronic board.


Fuse holder and fuses for power and auxiliary circuits.

145

Lowara
PRODUCT DESCRIPTION B
Y TECHNICAL SPECIFICA
TIONS
BY
SPECIFICATIONS
-

Line contact maker (direct start-up), line and star/delta contact makers (star/delta start-up), line contact makers
and reactance switching (impedance start-up).
Star/delta exchanger timer or reactance switching.
Relay for signalling no phase.
Auxiliary relays.
Current transformer.
Terminal boards.
Clean contacts (max 24V, 1A) for activating acoustic/ visual alarms for no phase, pump on demand, pump
running and start failure.
Cable glands (excluding the versions to be fixed to the floor).
Wiring diagram.

Jock
ey pump electrical panel
Jockey
Painted metal casing (IP55) complete with:

General door-locking switch.


Visual indicators for line, running, thermal shutdown.
Manual automatic selector excluded.

Inside:

Transformer for auxiliary circuits at 24 V.


Fuse holder and fuses for power and auxiliary circuits.
Line contact maker.
Overload cut-out switch.
Pump shut-off timer (0 90 s).
Terminal boards.
Cable glands.
Wiring diagram.

Suitable for connecting to a float switch or a minimum pressure switch for preventing dry running. An optional level
control module (supplied upon request) allows the connection of probes with the possibility of regulating the sensitivity
according to the hardness of the water.
Series of clean contacts for checking the status of the electric service pump panel, as well as
the contacts already provided for signalling alarms (on request):

No phase.
Motor running..
Selector position Man-Aut-0.
Failure to start.
Start-up request.

Series of clean contacts for checking the status of the electric jock
ey pump (on request)
jockey
- Pump running.
- Thermal shutdown (overload).
- No water.

146

Lowara
PRODUCT DESCRIPTION B
Y TECHNICAL SPECIFICA
TIONS
BY
SPECIFICATIONS
Electrical alarms panel
Plastic casing protected to IP55 with an electronic board at the front for the visual and acoustic signalling of the
status of one or two service pumps. The following alarms are signalled :
Electric pump
Power off.
Start-up request.
Pump running.
No start-up.
The electric panel is fitted with a buzzer with reset button, signal LED test button, battery charger and battery and is
fitted out to signal the following general alarms, if present:
- General alarm for incorrect electrical connection in the exchange contacts of:
status of flow measurement circuit valve, drain pump, jockey pump.
- Fault in electrical connection in the exchange contact relative to panel 1 (electric pump/diesel engine pump).
- Fault in electrical connection in the exchange contact relative to panel 2 (electric pump/diesel engine pump).
- Jockey pump overload.
- Jockey pump running.
- Discharge pump overload.
- Battery voltage low.
- Communications failure with ModBus system.
GSM modem system status transmission module and RS232/485 converter module available on request.

QUADRO TAMPONE ALLARMI


TIONS
SPECIFICATIONS
TECHNICAL SPECIFICA

275

DESCRIPTION

Input voltage (single-phase)

VALUE

(1F+N) 230V +/-10%, 50-60 Hz

V
L1/

V
+

L2/

L2/

V
L3

A
L3

N.P.

INCREASE

Absorbed

Rated battery voltage

A
L1/

370 x 275 x 160 mm

Protection grade
Battery

ENTER

DECREASE / MENU'

IP55

370

Dimensions

SHIFT

0,1A

Hermetic lead
12 Vcc

SPRINKLER DRAINAGE
PUMPS ROOM FAULT PUMP

ACCORDING TO EN12845
LAMPS TEST
PROVA
LAMPADE

BUZZER
SWITCH OFF
TACITAZIONE
SIRENA

ELECTRIC PUMP / POMPA ELETTRICA

L2
L1

JOCKEY PUMP

L3

DSRC
GA11E+1D

POWER ON
PRESENZA TENSIONE
-

Rated battery capacity

2,3 Ah ( uncharged in 20 h)

Dimensions of battery

178 x 34 x 66 mm

Sound emission levels

75dB

Control panel weight

1,5kg

+ UNDER THRESHOLD
SOTTO SOGLIA
PUMP ON
POMPA IN MARCIA

INTERRUPTED LINES
LINEE INTERROTTE

Voltage 230 V - 50-60 Hz


Battery 12 V 2,3 Ah

Code N. 32.000.10.0
Buzzer 12Vcc 90mA 75dB(A)

L2

OVERLOAD
SOVRACCARICO
SPRINKLER PUMPS ROOM
SPRINKLER SALA POMPE
PUMP SET ON DEMAND
RICHIESTA DI AVVIAMENTO
SELECTOR NOT IN
AUT. FUNCTION
SELETTORE NON IN AUT.

!
OFF

!
OFF
1

DIESEL PUMP / MOTOPOMPA

POMPA COMPENSAZIONE

Type

Plant Type:
Tipo impianto:

L3

L1

Circ. N. 17.029.001.0
0,2 A

IP 55

PHASE SEQUENCE FAILURE


ERRATA SEQUENZA FASE

MINIMUM FUEL LEVEL


MIN. LIVELLO COMBUSTIBILE

START FAILURE
MANCATO AVVIAMENTO

SWITCHBOARD FAILURE
GUASTO QUADRO

!
OFF
1

!
OFF
2

MINIMUM LEVEL SUCTION TANK


MINIMO LIVELLO VASCA ASPIRAZIONE
MINIMUM LEVEL PRIMING TANK
MINIMO LIVELLO VASCA ADESCAMENTO
PARTIALLY OPENED SUCTION VALVE
VALVOLA IN ASPIRAZIONE NON
COMPLETAMENTE APERTA
PARTIALLY OPENED DISCHARGE VALVE
VALVOLA IN MANDATA NON
COMPLETAMENTE APERTA

12845_002_D_DD

12845-qal-en_b_td

Control instruments and hydraulic accessories

The main components of the sets are:

On/off valves on the delivery side of each pump, ball valves with lever handle for diameters up to 11/4" inclusive,
butterfly valve with lever handle from DN65 to DN100 diameter, butterfly valve with handwheel and reduction
manual gear for DN125 diameter and above.
- Re-circulation device for each service pump.
The re-circulation device allows a minimum capacity in order to prevent the pump overheating when working with
closed delivery. It includes the activation pressure switch for the alarms of the pumps running, the test valve for
checking the seal of the check valves, the couplings for any connecting pipes to the priming tank in the case of
suction lift installation. The connection of each re-circulation to the suction tank or the priming tank is to be seen
to by the person installing the equipment.

147

Lowara
PRODUCT DESCRIPTION B
Y TECHNICAL SPECIFICA
TIONS
BY
SPECIFICATIONS
-

Pressure gauge on the delivery side of each service pump between check valve and on/off valve.

Check valve be inspected type, on the delivery side of each pump. Threaded connector up to and including a
diameter of 11/4". Flanged connector for larger diameters.

Painted iron delivery manifold (PN 16) and threaded stubs with relative caps for connecting any 24 litre
membrane tanks. Blind and welding zinc-plated flanges.

Two start-up pressure switches for every service pump.


For the electric service pumps, start-up takes place through the pressure switch, but it must be manually
stopped using the key-operated selector switch on the panel (excluding the version with automatic shut-off).
For the electric jockey pump, if present, both start-up and stopping are determined by the pressure switch.

Start-up pressure switch circuit for the service pump, including connecting pipes for the delivery manifold,
recirculation circuit. This circuit includes on/off valve, a non-return valve, a discharge or test valve and various
pipe fittings. The configuration of the circuit allows the pressure switch to intervene also when the relative on/off
valve is closed.

Various pipe fittings (copper, zinc-plated steel).

Base made of bent sheet or structural iron with epoxy powder painting RAL 5010.

Control panel frame made of structural iron with epoxy powder painting RAL 5010.

The control panels for the electric pumps up to 55 kW power supply are fixed on bracket. For higher powers, the
control panels for electric pump service are floor mounted, instead the jockey electric pump panel is wall mounted
fixed.

Electric panel for each electric service pump.

148

Lowara
PRODUCT DESCRIPTION B
Y TECHNICAL SPECIFICA
TIONS
BY
SPECIFICATIONS
Flow meter
The flow meter is supplied as part of the assembly kit. The EN 12845 standard requires the presence of the flow
meter for checking the hydraulic performance during the test stage and duration periodic inspections. The kit
comprises:
- Direct reading flow meter.
- On/off ball valve for diameters up to 2 inclusive, butterfly valve with lever handle from DN65 to DN100 diameter,
butterfly valve with handwheel and reduction manual gear for DN125 diameter and above.
- Straight plastic connection piping.
IThe flow meter is available in various sizes according to the flow of a service pump and suitable for being connected
to the offtake of the head manifold. For a correct match, identify the type as shown in the set size tables.
The assembly and the discharge piping towards the tank and discharge outlet are to be seen to by the person
installing the equipment.
The following illustration shows the type and size of flow meter:

Dimensions (mm):
DN =
DNAS =
L=
H=
Qmax (m3/h) =

149

Lowara
PRODUCT DESCRIPTION B
Y TECHNICAL SPECIFICA
TIONS
BY
SPECIFICATIONS
Diaphragm tanks
The booster sets are ready for installation, directly on the manifold, of 24-litre diaphragm tanks, one for each pump.
The sets are also equipped with caps to close off the unused couplings. Larger tanks can also be connected to the
unused end of the discharge manifold.
The kit is made up of the following accessories:

Diaphragm tank;
On-off ball valve;
Instructions manual;
Packaging.

Suction kit
The EN 12845 fire-fighting booster sets are supplied without valves and stubs on the suction side of the service pump
and can be completed with suitable kits that depend on legal standards.
These requirements are expressed by EN 12845 (chapter 10.5 and chapter 10.6) and are connected with the
maximum speed value of the water in the pipes, their minimum section and type of installation - suction lift or
positive suction head. To provide for one suction kit for each duty pump.
The kit comprises:

Anti-vibration joint to attach to the pump inlet.


On/off butterfly valve with lever handle for diameters up to DN100, butterfly valve with handwheel and reduction
manual gear for DN125 and higher.
Eccentric cone.
Vacuum pressure gauge.
Weld-on flange.

The following illustration shows the suction kit:

Dimensions (mm):

DNA =
DNS =

L=
H=

150

Lowara
PRODUCT DESCRIPTION B
Y TECHNICAL SPECIFICA
TIONS
BY
SPECIFICATIONS

The set is supplied already assembled, calibrated and factory tested. The set is supplied
complete with an instruction manual, pump manuals and wiring diagrams for the panels.
F
or the sets including floor panels, the electric panels are sent together with the set in a
For
separate pack and supplied with 5-metre long connecting cables (longer lengths
available on request). The fitter is responsible for preparing the routes and installing the
cables.

151

Lowara
ITT Lowara part of ITT Corporation and headquarters of Residential and
Commercial Water - EMEA.
World leading in offering high reliable fluid handling solutions for Building
Services, Irrigation and Industrial applications. We provide a complete range of
high quality pumps, packaged systems and controls and are specialized in
engineering and manufacturing stainless steel products.
ITT Lowara is headquartered in Vicenza, Italy and operates in more than 80
countries across the world with own plants in Italy, Austria, Poland and Hungary.
The company has 1.300 employees and generated 2008 sales exceeding $440
million. ITT Lowara is wholly owned by the ITT Corporation of White Plains, New
York, and is the EMEA headquarter of ITTs Residential and Commercial Water
division. ITT Corporation is a high-technology engineering and manufacturing
company operating on all seven continents in three vital markets: water and fluids
management, global defense and security, motion and flow control. ITT
Corporation generated 2008 sales of $11.7 billion

ITT RESIDENTIAL AND COMMERCIAL WATER DIVISION - EMEA


Headquarters
LOWARA S.r.l.
Via Dott. Lombardi, 14
36075 Montecchio Maggiore
Vicenza - Italy
Tel. (+39) 0444 707111
Fax (+39) 0444 492166
e-mail: lowara.mkt@itt.com
http: //www.lowara.com
AUSTRIA
ITT AUSTRIA GmbH
A-2000 STOCKERAU
Ernst Vogel-Strae 2
Tel. (+43) 02266 604
Fax (+43) 02266 65311
e-mail: info.ittaustria@itt.com
http://www.ittaustria.com
FRANCE
LOWARA FRANCE S.A.S.
BP 57311
37073 Tours Cedex 2
Tel. (+33) 02 47 88 17 17
Fax (+33) 02 47 88 17 00
e-mail: lowarafr.info@itt.com
http://www.lowara.fr
GERMANY
LOWARA DEUTSCHLAND GMBH
Biebigheimer Strae 12
D-63762 Groostheim
Tel. (+49) 0 60 26 9 43 - 0
Fax (+49) 0 60 26 9 43 - 2 10
e-mail: lowarade.info@itt.com
http://www.lowara.de

For additional addresses, please visit


www.lowara.com

cod. 191000001
191000451 PW07/09
11/09

Lowara reserves the right to make modifications


without prior notice.

IRELAND
ITT IRELAND
50 Broomhill Close
Airton Road
Tallaght
DUBLIN 24
Tel. (+353) 01 4524444
Fax (+353) 01 4524795
e-mail: lowara.ireland@itt.com http://www.lowara.ie
NEDERLAND
LOWARA NEDERLAND B.V.
Zandweistraat 22
4181 CG Waardenburg
Tel. (+31) 0418 65 50 60
Fax (+31) 0418 65 50 61
e-mail: sales.nl@itt.com
http://www.lowara.nl
POLAND
LOWARA VOGEL POLSKA Sp. z o.o.
PL 57-100 Strzelin
ul. Kazimierza Wielkiego 5
Tel. (+48) 071 769 3900 - Fax (+48) 071 769 3909
e-mail: info.lowarapl@itt.com http://www.lowara-vogel.pl

PORTUGAL
ITT PORTUGAL, Lda
Praeta da Castanheira, 38
4475-019 Barca
Tel. (+351) 22 9478550
Fax (+351) 22 9478570
e-mail: info.pt@itt.com
http://www.itt.pt
RUSSIA
LOWARA RUSSIA
Kalanchevskaya st. 11 b.2, off. 334
107078 Moscow
Tel. (+7) 495 631 55 15
Fax (+7) 495 631 59 72
info.lowararu@itt.com - www.lowara.ru
UK
LOWARA UK LTD.
Millwey Rise, Industrial Estate
Axminster - Devon EX13 5HU UK
Tel. (+44) 01297 630200
Fax (+44) 01297 630270
e-mail: lowaraukenquiries@itt.com
http://www.lowara.co.uk

You might also like