Apache HVAC
Apache HVAC
Contents VE 6.4.0.8 Update 1 Introduction ...............................................................................................................................8 1.1 What is ApacheHVAC and where does it fit within the Virtual Environment? ........................8 1.2 ApacheHVAC Interface Overview .........................................................................................9
1.2.1 1.2.2 1.2.3 1.2.4 1.2.5 1.2.6 1.2.7 Virtual Environment Menu Bar .................................................................................................................... 9 ApacheHVAC Menu Bar ............................................................................................................................... 9 ApacheHVAC Toolbars ................................................................................................................................. 9 Model Workspace ...................................................................................................................................... 10 Mouse controls .......................................................................................................................................... 10 View Toolbar .............................................................................................................................................. 10 Component browser .................................................................................................................................. 11
1.3 A Component-based Approach to System Simulation ......................................................... 12 1.4 System Modeling Fundamentals ........................................................................................ 13
1.4.1 1.4.2 1.4.3 2.1.1 2.1.2 2.1.3 Preparation ................................................................................................................................................ 13 Constructing Systems ................................................................................................................................ 14 Room components..................................................................................................................................... 15 Waterside plant equipment and water loops ............................................................................................ 17 Airside plant equipment and system components .................................................................................... 17 Room units zone equipment applied within Room components ........................................................... 17
2.6.4 2.7.1 2.7.2 2.7.3 2.7.4 2.7.5 2.7.6 2.7.7 2.7.8 2.8.1 2.8.2 2.8.3 2.8.4 2.8.5 2.9.1 2.9.2 2.9.3 2.9.4 2.9.5 2.10.1 2.10.2 2.10.3 2.10.4 2.11.1 2.11.2 2.11.3 2.11.4 2.12.1 2.13.1 2.13.2 2.13.3 2.13.4 2.13.5 2.13.6 2.13.7 2.13.8 2.13.9 2.13.10 VE 6.4
Rated Condition ......................................................................................................................................... 56 Heat pump update ..................................................................................................................................... 59 Air-to-water heat pump (AWHP) and generic Air-source heat pump (ASHP) ........................................... 61 Air-to-water and air-source heat pump settings ....................................................................................... 62 Air-to-water and air-source heat pump performance ............................................................................... 63 Air-to-air heat pump (AAHP)...................................................................................................................... 63 Air-to-air heat pump settings .................................................................................................................... 65 Air-to-air heat pump performance ............................................................................................................ 66 Modeling heat pump temperature and part-load dependent performance ............................................. 67 Chilled water loop dialog ........................................................................................................................... 75 Chilled Water Loop tab .............................................................................................................................. 77 Pre-cooling tab ........................................................................................................................................... 81 Chiller Set tab............................................................................................................................................. 83 Heat Rejection tab ..................................................................................................................................... 87 Part load curve chiller definition ............................................................................................................... 96 Condenser Heat Recovery ......................................................................................................................... 98 Electrical power consumption for pumps and fans ................................................................................... 99 COP Temperature Dependence ............................................................................................................... 100 Part-load performance data for chiller and auxiliary equipment ............................................................ 100 Water-cooled chillers............................................................................................................................... 102 Chiller Performance ................................................................................................................................. 104 Design Condition ...................................................................................................................................... 112 Rated Condition ....................................................................................................................................... 114 Air-cooled chiller definition ..................................................................................................................... 117 Chiller Performance ................................................................................................................................. 119 Design Condition ...................................................................................................................................... 127 Rated Condition ....................................................................................................................................... 128 Dedicated waterside economizer settings dialog .................................................................................... 133 Pre-defined DX Cooling Types.................................................................................................................. 137 DX Cooling model .................................................................................................................................... 138 One-to-one relationship of DX Cooling model type and coil ................................................................... 139 DX Cooling COP and condenser fan power .............................................................................................. 140 DX Cooling type definition ....................................................................................................................... 140 Rated condition ....................................................................................................................................... 142 Design condition ...................................................................................................................................... 143 DX Cooling Performance curves: details and editing ............................................................................... 144 Cooling Capacity curve, fCAPtt(Tewb,Tect), details and editing ..................................................................... 144 EIR Temperature Dependence curve, fEIRtt(Tewb,Tect), details and editing ................................................ 146 ApacheHVAC 2
2.8 Chilled Water Loops, Pre-Cooling, Heat Rejection, and Chiller Sequencing .......................... 71
2.12 Dedicated Waterside Economizers (types)........................................................................ 131 2.13 DX Cooling (types) ........................................................................................................... 137
2.13.11 2.14.2 2.15.1 2.15.2 2.15.3 2.15.4 2.15.5 2.15.6 2.15.7 2.15.8 2.16.1 2.16.2 2.16.3 2.16.4 2.16.5 2.16.6 2.16.7 2.16.8 2.17.1 2.17.2 2.17.3
EIR Part-load Dependence curve, fEIRp(p), details and editing .................................................................. 148 Unitary Cooling System Performance Data ............................................................................................. 153 Background .............................................................................................................................................. 156 Simple Model ........................................................................................................................................... 156 Advanced Model ...................................................................................................................................... 156 Autosizing Process ................................................................................................................................... 157 Manual Sizing Process.............................................................................................................................. 157 Heating Coil Dialogs ................................................................................................................................. 157 Design Sizing Parameters for Simple Coil Model ..................................................................................... 160 Design Sizing Parameters for Advanced Coil Model ................................................................................ 161 Background .............................................................................................................................................. 163 Simple Model ........................................................................................................................................... 164 Advanced Model ...................................................................................................................................... 164 Autosizing Mode ...................................................................................................................................... 165 Manual Mode .......................................................................................................................................... 165 Cooling Coil Dialogs.................................................................................................................................. 165 Design Sizing Parameters for Simple Coil Model ..................................................................................... 170 Design Sizing Parameters for Advanced Coil Model ................................................................................ 171 Reference ................................................................................................................................................. 176 Spray Efficiency ........................................................................................................................................ 176 Circulation Pump Electrical Power ........................................................................................................... 177
2.14 Unitary Cooling Systems (types) ....................................................................................... 151 2.15 Heating Coils.................................................................................................................... 156
2.18 Steam Humidifiers ........................................................................................................... 178 2.19 Heat Recovery Devices ..................................................................................................... 179 2.20 Fans ................................................................................................................................. 181 2.21 Mixing Damper Set .......................................................................................................... 183 2.22 Return Air Damper Set ..................................................................................................... 190 2.23 Controlled Divergent T Junction (splitter damper) ......................................................... 191 2.24 Ductwork Heat Pick-up .................................................................................................... 192 2.25 Direct Acting Heater/Cooler ............................................................................................. 193 2.26 Hot Water Radiators ........................................................................................................ 195
2.26.2 2.26.3 2.26.4 2.26.5 Distribution Pump Consumption ............................................................................................................. 199 Material ................................................................................................................................................... 199 Total Radiator Weight .............................................................................................................................. 199 Water Capacity ........................................................................................................................................ 199
2.27 Chilled Ceilings ................................................................................................................ 200 3 Controllers.............................................................................................................................. 205 3.1 Working with controllers on the airside HVAC network .................................................... 206
3.1.1 3.1.2 VE 6.4 On/Off, Deadband, and Proportional control .......................................................................................... 206 Multiple control of single variable ........................................................................................................... 207 ApacheHVAC 3
3.2 Controller operation ........................................................................................................ 207 3.3 Controller parameters ..................................................................................................... 208
3.3.1 3.3.2 3.4.1 3.4.2 Controlled variables ................................................................................................................................. 209 Sensed variables ...................................................................................................................................... 210 Multiple controllers at a single network node......................................................................................... 212 Linking of controllers via logical AND and OR connections ..................................................................... 213
3.5 Airflow controllers ........................................................................................................... 213 3.6 Controller parametersterminology and general discussion ............................................ 214
3.6.1 3.6.2 3.6.3 3.6.4 3.6.5 3.6.6 Time Switch or On/Off Control ................................................................................................................ 214 Sensor (for on/off and proportional control) .......................................................................................... 215 Set Point (for on/off control) ................................................................................................................... 215 Proportional Control ................................................................................................................................ 217 AND Connections ..................................................................................................................................... 219 OR Connections ....................................................................................................................................... 219
3.7 Controller Algorithm ........................................................................................................ 220 3.8 Airflow control ................................................................................................................ 222 3.9 Independent Time Switch Controller ................................................................................ 223 3.10 Independent Controller with Sensor ................................................................................ 225
3.10.1 Proportional controls sequencing............................................................................................................ 228
3.11 Independent Differential Controller ................................................................................. 230 3.12 Dependent Time Switch Controller................................................................................... 231 3.13 Dependent Controller with Sensor ................................................................................... 232 3.14 Dependent Differential Controller .................................................................................... 233 4 Room Unit Controllers ............................................................................................................ 236 4.1 Hot Water Radiator Control ............................................................................................. 237
4.1.2 4.1.3 4.2.2 4.2.3 4.2.4 4.3.1 4.3.2 4.3.3 On/off and set point controls .................................................................................................................. 238 Proportional controls for water flow rate and temperature ................................................................... 239 Settings .................................................................................................................................................... 243 On/off and set point controls .................................................................................................................. 243 Proportional controls for water flow rate and temperature ................................................................... 244 Settings .................................................................................................................................................... 248 On/off and set point controls .................................................................................................................. 248 Proportional control for heating and/or cooling output ......................................................................... 249
5 HVAC Wizard .......................................................................................................................... 251 5.1 HVAC Wizard Interface .................................................................................................... 251
5.1.1 5.1.2 5.1.3 5.1.4 HVAC Wizard dialog ................................................................................................................................. 251 HVAC Wizard: Create New System .......................................................................................................... 252 Page 3 of the HVAC Wizard (Create New System) ................................................................................... 253 HVAC Wizard: Open Recent System ........................................................................................................ 254
6.5 Tabular Editing ................................................................................................................ 268 6.6 Node Numbering ............................................................................................................. 272 6.7 Delete Multiplex .............................................................................................................. 273 7 System Loads, Ventilation, and Autosizing .............................................................................. 274 7.1 Overview ......................................................................................................................... 274 7.2 Zone-level loads and sizing............................................................................................... 274
7.2.1 Zone-level system set up and autosizing steps ........................................................................................ 275
7.3 System-level loads and sizing ........................................................................................... 281 7.4 System Prototypes & Sizing workflow navigator............................................................... 282
7.4.1 System Prototypes & Sizing workflow summary ..................................................................................... 282
8 Prototype HVAC Systems (section under construction) ............................................................ 285 8.1 Prototype HVAC systems: System types and configurations.............................................. 287 8.2 Working with prototype systems ..................................................................................... 290
8.2.1 8.2.2 8.2.3 8.3.1 8.3.2 8.3.3 8.3.4 8.3.5 8.3.6 8.3.7 8.3.8 8.3.9 8.3.10 VE 6.4 Loading, saving, and retrieving prototype systems ................................................................................. 291 Selecting, moving, copying, and naming systems .................................................................................... 291 Modifying pre-define prototype systems ................................................................................................ 291 System-level or air handler vs. zone-level elements ............................................................................... 295 Outside air intake and outlet ................................................................................................................... 295 Airside energy recovery ........................................................................................................................... 295 Energy recovery and bypass damper section .......................................................................................... 296 Outside air ventilation damper and airside economizer ......................................................................... 298 Return air damper component ................................................................................................................ 309 Supply fan ................................................................................................................................................ 310 Return fan ................................................................................................................................................ 310 Cooling coil system level or AHU .......................................................................................................... 310 Heating coil system level or AHU .......................................................................................................... 310 ApacheHVAC 5
8.3.11 8.3.12 8.3.13 8.3.14 8.3.15 8.3.16 8.3.17 8.3.18 8.4.1 8.4.2 8.4.3 8.4.4 8.4.5 8.4.6 8.4.7 8.4.8 8.4.9 8.4.10 8.4.11
Duct heat gain/loss component zone level ........................................................................................... 310 Reheat coil and controller (or similar components) zone level ............................................................ 310 Zone or principal room component ..................................................................................................... 310 Return air plenum component ................................................................................................................ 310 VAV airflow controls ................................................................................................................................ 311 Exhaust fan .............................................................................................................................................. 312 Exhaust airflow controller ........................................................................................................................ 312 Transfer airflow controller ....................................................................................................................... 312 Packaged Terminal Air-Conditioning (PTAC) ............................................................................................ 313 Packaged Terminal Heat Pump (PTHP) .................................................................................................... 313 Single-zone air-conditioning system with furnace (PSZ-AC) .................................................................... 313 Single-zone heat pump system (PSZ-HP) ................................................................................................. 313 VAV-reheat using DX Cooling and HW boiler........................................................................................... 313 VAV using DX Cooling and parallel fan-powered boxes with electric heat .............................................. 313 VAV-reheat using water-cooled chiller and HW boiler ............................................................................ 313 VAV using water-cooled chiller and parallel fan-powered boxes with electric heat ............................... 313 Dedicated outside air system (DOAS) with four-pipe fan-coil units, EWC chiller and HW boiler. ........... 314 Indirect-direct evaporative cooling version of VAV-reheat system 5 above with backup DX cooling and zone-level CO2-based demand-controlled ventilation (DCV). ................................................................. 314 VAV-reheat with differential-enthalpy economizer set up for the public areas of a hotel or similar building with PTAC systems for individual guest/resident rooms drawing air from an atrium zone on the main VAV system. .................................................................................................................................... 314 Mixed-mode natural ventilation and VAV-reheat with zone temperature and zone CO2 overrides for nat-vent when it is insufficient ................................................................................................................ 314 Single-fan dual-duct and with zone-level mixing boxes........................................................................... 314 Dual-fan-dual-duct with zone-level mixing boxes. .................................................................................. 314 Underfloor air distribution with parallel fan-powered boxes for perimeter zones, leakage path, and heating-mode re-mixing of PFPb zones. .................................................................................................. 314 UFAD/DV system as above, plus heat pipe or run-around coil in AHU for free re-heat of sub-cooled (dehumidified) air after the AHU cooling coil. ......................................................................................... 314 Active chilled beams and DOAS for ventilation using electric water-cooled chiller with waterside economizer and condenser heat recovery; HW boiler and recovered heat for DOAS and zone baseboard fin-tube convectors. ................................................................................................................................. 316 Radiant heating and cooling panels (i.e., four-pipe system), plus DOAS with airside energy recovery and DCV. ......................................................................................................................................................... 316 Radiant panels and DOAS as above with heat pipe or run-around coil in AHU for free re-heat of subcooled (i.e., dehumidified) air after the AHU cooling coil. ...................................................................... 316
8.4.18 8.4.19
9 Appendix A: Rules for Air Flow Specification ........................................................................... 318 10 Appendix B: HVAC zone controller profile values relative to setpoints entered in the System Schedules dialog ......................................................................................................................... 320 11 Appendix C: Ground-Source Heat Pump Modeling using ApacheHVAC loads and Gaia Geothermal Ground-Loop Design ................................................................................................................... 321 12 Appendix D: Modeling VRV/VRF systems ................................................................................ 323 13 Appendix E: Hydronic Radiant Heating and Cooling Systems.................................................... 329
VE 6.4
ApacheHVAC
13.1 Modeling hydronic heated and/or cooled slabs using radiant panels (method 1) .............. 331 13.2 Modeling heated or cooled slabs using slab zones and hydronic loops (method 2) ............ 332
13.2.1 13.2.2 Hydronic Radiant Slab Zones ................................................................................................................... 332 ApacheHVAC Hydronic Loops and Controls for Radiant Slabs ................................................................. 336
14 Appendix F: Modeling UFAD and DV in ApacheHVAC (Work in Progress this section under construction) .............................................................................................................................. 338 15 Appendix G: Solar Hot Water Applications in ApacheHVAC ..................................................... 345 16 Appendix H: Thermal Storage for Cooling in ApacheHVAC (Work in Progress this section under construction) .............................................................................................................................. 346 17 Appendix I: HVAC Systems Modeling Guidance Specific to ASHRAE Standard 90.1-2007 .......... 347
17.1.1 17.1.2 17.1.3 Fan power for PRM Baseline systems ...................................................................................................... 347 DX Cooling EER and COP for PRM Baseline systems ................................................................................ 348 Baseline systems 2 and 4 Packaged Terminal Heat Pump (PTHP) and Packaged Single-Zone Heat Pump (PSZ-HP) ................................................................................................................................................... 349
18 References.............................................................................................................................. 359
VE 6.4
ApacheHVAC
Introduction
1.1 What is ApacheHVAC and where does it fit within the Virtual Environment?
ApacheHVAC is used for modeling heating, ventilating, and air-conditioning (HVAC) systems, and falls within the Virtual Environments Thermal application category.
Virtual Environment Thermal applications ApacheHVAC view
The ApacheHVAC supports the detailed definition, configuration, control, and modeling of HVAC systems. The simulation program itself is run from within Apache Thermal. ApacheHVAC is invoked as an adjunct to Apache Simulation by linking to a particular HVAC system file when the building model simulation is run, as described in the Apache User Guide. There are two distinct means of space conditioning and HVAC simulation in the IES Virtual Environment, and these are suitable for very different tasks, levels of analysis, and stages of design. Apache Systems Simplified system modeling for schematic design and code compliance in ApacheSim: Fully autosized and ideally controlled systems condition spaces exactly to set points via predefined HVAC system-type algorithms and minimal room, system, and plant inputs within ApacheSim. This simplified HVAC modeling is fully integrated with the thermal, solar, and bulkairflow modeling at every simulation time step. However, because the systems are approximated, it is far less representative of actual system equipment, configurations, and controls. Thus, while it may be very useful in early design phases and space loads analyses, this type of modeling is normally not used in design development, documentation of energy performance for the ASHRAE 90.1 performance rating method, thermal comfort studies, or other detailed analysis. Detailed dynamic modeling of systems, equipment, and controls in ApacheHVAC is also fully integrated with the thermal, solar, and bulk-airflow modeling at every simulation time step. Component-based system models can be built from scratch or by modifying autosizable prototype systems, or the prototype systems can be used in their pre-defined configuration.
When ApacheHVAC is invoked, all spaces in the model that are assigned to a room component in the active ApacheHVAC system at the time of simulation will be served by that system. So long as this is true, these rooms will not be served by the simpler systems otherwise defined in the Apache Systems dialog. Like infiltration, however, air changes or flow rates for Auxiliary ventilation and Natural ventilation as defined in the Air Exchanges tab of the Thermal Conditions template or Room Data remain in effect for all rooms to which they have been applied, regardless of whether or not these rooms are served by an ApacheHVAC system.
VE 6.4
ApacheHVAC
The toolbars provide quick access to menu functions, selection of components and controllers to be placed on the system schematic, creation and editing of system of multiplexes, and access to system prototypes. The multiplexing editing toolbar is active only when a multiplex is selected.
VE 6.4
ApacheHVAC
This provides functions for manipulating the view of the system schematic, including zoom to HVAC network extents, window, in, out, pan, previous, and next.
VE 6.4
ApacheHVAC
10
The component browser provides a listing of all components in the current ApacheHVAC file. This can be used to locate and/or select a particular type of component or controller within a large or complex HVAC network. Selecting the component or controller within the browser causes it to be highlighted on the network in the model space. The browser can also be useful in determining how many of a particular component or controller type are present. It is not necessary to hide the component browser for most HVAC system networks, as the speed of this has been significantly improved over earlier versions. When working on exceptionally large or complex HVAC networks, if the opening of component and controller dialogs does begin to slow noticeably, the component browser can be turned OFF by clicking the browser show/hide button on the toolbar. This will further increase the speed with which component and controller dialogs open.
VE 6.4
ApacheHVAC
11
Figure 1-1: A multi-zone HVAC networkin this case variable-air-volume with indirect-direct evaporative cooling, energy recovery, variation of static pressure with bypass of heat exchangers, duct heat gain, return air plenums, controls for mixed-mode operation with natural ventilation, and primary, transfer, and exhaust airflow paths available to each of the zones in the layered multiplex region. ApacheHVAC has been designed to impose minimal restrictions on the user in defining the system model. The user is offered a number of basic blocks, each describing a generic type of equipment (heating coil, fan, humidifier, etc.). These basic blocks can be assembled as required to model an actual system configuration, rather than an idealized simplification. The complexity of the model is limited only by the types of block available and some basic rules concerning their interconnection. Within these constraints, it is possible to assemble models of many different system and control configurations and to explore the benefits of variations on standard system types. An item of plant or control can be described once, and then copied or referenced as many times as may be required to define the system.
VE 6.4
ApacheHVAC
12
VE 6.4
ApacheHVAC
13
It is important to set up a Grouping Scheme in ModelIt that sorts thermal zones into groups such as System-1, -2, -3, etc. or AHU-1, -2, -3, etc. and other space types, such as Return air plenums, Solar chimney segments, Unconditioned zones, etc.
If the model includes UFAD of thermal displacement ventilation (DV), it is essential to ensure that the number and order of Stratified zones exactly matches the number and order of corresponding Occupied zones in any one AHU group. Doing so will facilitate system multiplexing, autosizing, and other fundamental aspects of system modeling. If there are some mixed (non-stratified zones) on the same system, either place them in a separate group of occupied zones or create dummy stratified zones (e.g., a series of small super-insulated boxes with no internal gains) in the model that can fill out the list of stratified zones to make it parallel the list of occupied zones on the same system. Occupied and Stratified should be in separate groups with the AHU Assignment scheme.
When first building an HVAC system, it is advisable to keep the system simple. This makes it easy to test the control principles involved. The system can later be expanded to introduce additional rooms and control refinements. Set up the minimum number of flow controls necessary to define the flow throughout the systemi.e., on all branches. In other words, airflow must be specified in all parts of the system, except where the flow can be deduced from other specified flows by addition and subtraction at junctions. Specifying more flows than are strictly necessary is not forbidden, but always ensure that the specified flows are mutually consistent. In most cases, it will be easier to allow flows to be calculated wherever they can be. In the case a room, it is only necessary to specify either the supply or the extract flow. The program will then set the other flow on the assumption of equality of inflow and outflow. In specialized applications, such as when MacroFlo is running in tandem with ApacheHVAC, the room inflow and outflow may be set to different values. Any imbalance between inflow and outflow will then be picked up by MacroFlo (if it is in use), and the difference will be made up with flows through openings in the building. An imbalance can also be meaningful if MacroFlo is not in use. For example, if more air is supplied to a room than is extracted, the excess will be assumed to be vented to outside. For a full account of the rules for airflow specification see Appendix A. The schematic may include multiple System Inlet and System Outlet components. These can be used to represent both the air inlet and outlet of a mechanical system and other paths, such as exfiltration in the case of a pressurized building. Most components placed on the airside network must have appropriate controllers attached in order to function. See component sections for details. The Check network button will identify most errors in the schematic. It also numbers the nodes of the network, providing a reference to the nodes that is useful when viewing simulation results. To remove the node numbering, if desired, simply re-open the same ApacheHVAC file.
Details of all equipment to be included in the simulation are entered in ApacheHVAC. The extent of data input depends on the scope of the simulation, which is at the discretion of the user. For instance if it is required to calculate the net energy consumption of an LTHW heating coil, it will be necessary to specify a coil and a heat source to serve it. However, it will not be necessary to input the characteristics of the LTHW system. In such a case the distribution losses of the LTHW system and pump power should be entered as zero and the heat source efficiency taken as 100%. Note that the duty of equipment for simulation purposes can be set as the components are placed or can be provided by the autosizing process. It is necessary only to specify a duty that equals or exceeds any requirement subsequently called for.
VE 6.4
a role in the dynamic thermal interaction with HVAC systems. Examples include a return-air plenum, an underfloor air distribution (UFAD) plenum, a segment within an earth tube, a space within a vented double-skin faade, or even a concrete slab that will be directly heated or cooled by a hydronic loop. It is permissible to use the same room component more than once in the air system network description, such as when more than one system supplies air to the same room. For example, consider a case where room type A has separate air supplies for heating and cooling; there may only be one actual room type A, but we can use two in the system network description one in the heating branch and one in the cooling branch. The result is exactly the same as if you had mixed the heating and cooling supply branches together through a combining junction and supplied this mixed air to a single room type A. The use of multiple room components in this way reduces the need for large numbers of mixing and dividing junctions. Once the system air has entered a room component, the program assumes that the air within the room (or bounded thermal zone assigned to a room component) is fully mixed. It is not possible to differentiate between, say, air entering from a ceiling diffuser and air entering from a perimeter unit or a floor outlet. You can, if you wish, describe a single room as several room types for the purposes of the computer simulatione.g., the core and perimeter zones of an open plan office could be described as separate room types. However, you should appreciate that there are a number of complex mechanisms of heat transfer involved in such a situation (wind, stack, and induced air movement, radiant heat exchange, etc.) and the program can only approximately analyze some of these. Some situations are best modeled by putting two room components in series. For example, you may wish to model a building in which the return air is extracted via the ceiling void. This can be achieved by describing the occupied space and the ceiling void as two separate room types and then connecting them in series.
VE 6.4
ApacheHVAC
16
Figure 2-1: HVAC components toolbar ApacheHVAC provides for modeling a comprehensive range of HVAC components, as listed below.
The first set of these are defined mainly in plant equipment dialogs. Components in the middle set are dealt with mainly on the airside network. The last set, room units, differ from other HVAC components in that they are defined in terms of types but then located within a room component or thermal zone (including in non-occupied space or a heated or cooled slab zone) rather than on the airside network.
VE 6.4
ApacheHVAC
17
The modeling of plant components is quasi-steady-state in that the program does not attempt to model transient behavior between simulation time steps. However, because time steps in ApacheSim are typically only 6-10 minutes, and can be as little as 1 minute, if desired, constant plant behavior over a time step is an appropriate assumption. Furthermore, there is interaction between the HVAC system and conditioned spaces (including natural ventilation, stack-vent double-skin facades, etc. when running MacroFlo) at every simulation time step. The solution algorithm also provides for modeling intentionally undersized heating and cooling plant equipment or sources. Coils and other connected devices on a hot or chilled water loop will receive offdesign water loop temperatures in keeping with the capability of the modeled plant equipment when the load exceeds the heating or cooling capacity. Data entered for fans represents a special case in that fans are not controlled directly and fan component inputs are used only to calculate consequential energy consumption and effect on air temperature. The value entered in a fan component does not determine airflow through the system. Rather, the fan component acts like a meter with a defined set of performance characteristics. The airflow through the fan is determined by flow controllers on network branches. Loads and sizing data for room/zone loads, ventilation rates, zone/terminal equipment, primary airside equipment, and heating and cooling plant are provided in design sizing reports. Simulation results are provided for each reporting time step (1 hour maximum; 6 minutes minimum). Results are reported separately for each plant equipment category and fuel/energy type. Coil psychrometrics can be assessed for each time step. Thermal, moisture, and air flow results for each airside node can be queried for individual time steps. Energy used by room units at each time step is accounted for and reported separately from airside HVAC heating and cooling components.
VE 6.4
ApacheHVAC
18
The Heat sources dialog provides for defining the first two of these. Air-to-air heat pump types are separately defined. Hot water loops are used to configure, sequence, and model heat sources involving hot water. A hot water loop has a heating equipment set comprising any number (up to 99) of pieces of equipment. The hot-water heating equipment may be of different types (hot water boiler, part load curve heating plant) and can be sequenced according to a user-specified sequencing scheme. Generic heat sources are used to model heating equipment that either does not involve hot water or for which the water loop modeling will be simplified. Examples include generic boilers, electrical resistance heat, furnaces, steam sources, water- or ground-source heat pumps with fixed thermal lift, or other nonconventional types of heating plant. A generic heat source is associated with a part load curve heating plant, without equipment sequencing. Both Hot water loops and Generic heat sources can serve domestic hot water loads (passed to ApacheHVAC from ApacheThermal). Both also have options for incorporating recovered condenser heat from chiller sets, air-to-water or air-source heat pumps, and combined heat & power systems (separately defined in ApacheThermal). When associated with Generic heat source, these simply address the load ahead of the primary heat source. In the case of hot water loops, these provide pre-heating as specifically located on the hot-water return pipe. Hot water loops also have the option for pre-heating with a solar hot-water system defined in ApacheHVAC. Except in the case of Air-to-air heat pumps (described elsewhere in this User Guide), components that present a heating load, such as heating coils and radiators, are assigned a heat source rather than an individual piece of heating plant equipment. Individual pieces of heating and pre-heating plant equipment coupled to or sequenced as part of a Heat source are separately definedi.e., they are not defined as types. Each item of heating plant is defined in the context of a heat source (generic or hot-water loop). Thus no individual item of heating plant equipment is permitted to serve or be an element of more than one heat source. Heating plant equipment can, however, be duplicated using the Copy button within a heating equipment set (in a hot water loop). An Import facility is provided for copying a defined heating plant items from one heat source to another (for both hot water loops and generic heat sources). Heat sources described in this section are accessed through the Heat sources toolbar icon below. Toolbar icon for heat sources list. This toolbar icon opens the Heat sources dialog (Figure 2-2). This provides access to all Hot water loop and Generic heat sources defined within the current ApacheHVAC file. It also indicates which of the listed Heat sources has been designated to serve domestic hot water (DHW) loads when passed to ApacheHVAC from Apache Systems. A heat source may be added, edited, removed or copied through the corresponding buttons in this dialog. The Heat sources list in Figure 2-2 shows the default Type to Add as Hot water loop.
VE 6.4
ApacheHVAC
19
Double clicking on an existing heat source (or clicking the Edit button after selection) opens the corresponding heat source dialog (either a Generic heat source dialog as shown in Figure 2-3 or a Hot water loop dialog as shown in Figure 2-8) for editing equipment, configurations, options, operational settings, sequencing, and other parameters.
Figure 2-2: Heat sources list for adding, selecting, copying, and removing Hot water loops and Generic heat sources.
VE 6.4
ApacheHVAC
20
1) As a backup for an air-to-air heat pump (AAHP). This is done by selecting a backup GHS heat source in the AAHP dialog. 2) With an air-source heat pump (ASHP) as a pre-heating device. This is done by ticking the Use airsource heat pump? checkbox in the GHS dialog and specifying the associated ASHP parameters. Generic heat sources can also be used to meet remaining load after the heat available from a combinedheat & power (CHP) system or condenser heat recovery (CHR, from the part load curve chiller or from the condenser water loop) has been consumed. The heating load collectively presented by the radiators, heating coils, etc. assigned to a particular generic heat source is summed at each time step to set the required instantaneous output from the heat source. An allowance is made for any pipe-work distribution losses (these loses do not accrue to the building interior, and thus this is most appropriately used for modeling losses to unconditioned spaces or similar). Heat available from any optional pre-heating devices (CHR, ASHP, and CHP) on the generic heat source is first in line to meet the load. The pre-heating devices have a set sequence: 1st CHR, 2nd ASHP, and 3rd CHP. The part load curve heating plant associated with that generic heat source is then used to cover the load remaining after the pre-heating capacity has been consumed. Thus the loading sequence on a generic heat source is (assuming all possible pre-heating devices are present): CHRASHPCHPPart load curve heating plant. Absent pre-heating devices will be skipped from the loading sequence. Note: If the load on a generic heat source is greater than its capacity (whether just part-load curve heating plant or that combined with capacity from various pre-heating devices), it will supply the additional heat with the energy efficiency remaining at the value associated with the maximum design capacity. In other words, a shortage of capacity on generic heat sources does not feed back to the components they serve. If loads (heating coils, radiators, etc.) on a generic heat source its design capacity, the demand will still be met. The source will be performing above its design capacity at constant efficiency. The total capacity of a generic heat source is therefore constrained only by the design capacity of the connected heating coils, radiators, etc. This differs from hot water loops wherein deficiencies in capacity feed back to the loads they serve as a reduction in hot-water supply temperature.
VE 6.4
ApacheHVAC
21
Figure 2-3: Generic heat source (GHS) editing dialog showing illustrative inputs 2.3.1.1 GHS Reference name
Enter a description of the component. The reference is limited to 100 characters. It is for your use when selecting, organizing, and referencing any component or controllers within other component and controller dialogs and in the component browser tree. These references can be valuable in organizing and navigating the system and when the system model is later re-used on another project or passed on to another modeler. Reference names should be informative with respect to differentiating similar equipment, components, and controllers.
VE 6.4
ApacheHVAC
22
Figure 2-4: An illustrative Part load curve heating plant dialog. Parameters, and inputs for this dialog are explained in section 2.5, following the Hot Water Loop and Heating Equipment Sequencing section.
VE 6.4
ApacheHVAC
23
2.3.2.1
Distribution Losses
Enter the losses due to heat distribution as a percentage of heating load. For example, if distribution losses are entered as 5% and the heat source is connected to 10 radiators presenting a total design heating load of 20kW, the distribution loss of 0.05 20 kW (1kW) is added to radiator heat demand to give a fuel consumption of 21 kW the heating plant efficiency at the design load. The losses, however, do not accrue to zones in the building; they are assumed to be losses to outdoor or unconditioned spaces. 2.3.2.2 Oversizing factor
This is the factor by which the heating plant size is increased relative to the peak load in the design sizing run. This is applied immediately following the System-level autosizing step that runs the ApacheHVAC system under heating and cooling design conditions via ASHRAE Loads. 2.3.2.3 Use this heat source for DHW?
Tick this box to designate this GHS to serve Domestic Hot Water (DHW) loads (otherwise sometimes referred to as service hot water). You must also tick the Is DHW served by ApacheHVAC boiler? checkbox in the Hot water tab for the Apache system that is used to simulate DHW loads, storage tanks, and dedicated solar-DHW systems in Apache Thermal view. This second step will pass the heating loads to the designated Heat source in ApacheHVAC.
VE 6.4
ApacheHVAC
24
Figure 2-5: Inputs for percentage availability/effectiveness and recipient for Condenser heat recovery in Heat rejection tab of the Chilled water loop dialog. 2.3.3.1 Use water-source heat pump?
If the water loop served by the heating plant receives heat recovered from a chiller condenser, this heat may be upgraded using a water source heat pump (See additional explanation immediately above). Specify this mode of operation by ticking the box. 2.3.3.2 Heat pump COP
Enter the COP of the water source heat pump that couples the condenser loop with the hot water loop. This should normally be the COP for this equipment when the condenser loop and hot-water return are at design temperatures; however, this may differ for some system designs.
VE 6.4 ApacheHVAC 25
2.3.3.3
Select the fuel, type of energy source, or energy end-use category for the water-source heat pump. For scratch-built systems, this will normally be Electricity and for pre-defined systems this is set to Heating (electricity), which is an end-use designation for the ASHRAE 90.1 Performance Rating Method reports (see section 8: Pre-Defined Prototype HVAC Systems and the separate user guide for the PRM Navigator).
Figure 2-6: Air-source heat pump dialog with illustrative inputs (described in section 2.7). 2.3.4.1 Use air-source heat pump?
Tick this checkbox to specify an air-source heat pump as a pre-heating device on the genetic heat source. The input parameters for Air-source heat pumps are described in section 2.7.
VE 6.4
ApacheHVAC
26
2.3.4.2
This displays the reference name of the Air-source heat pump associated with this Generic heat source. It is not editable directly in the GHS dialog and should be edited in the Air-source heat pump dialog, which is opened by clicking the Edit button to the right of this field. 2.3.4.3 Autosize air-source heat pump?
Tick this checkbox to autosize the associated air-source heat pump during a system sizing run. When this box is ticked, the peak required Generic heat source capacity determined by autosizing will be multiplied by the Percent of autosized heat source capacity (%) (see below) to determine the Air-source heat pump capacity. The resultant maximum heat pump capacity value will then be used to update the part-load air-source heat pump capacity values as with air-to-air heat pumps (the autosizing will reset the value in the bottom row and proportionally adjust all other values to maintain their relationships). Note that the autosized capacity of the Air-source heat pump is not subtracted from the overall Generic heat source capacity. The size of the Air-source heat pump size will not influence the size of the Part load curve Heating equipment component of the Generic heat source. 2.3.4.4 Percent of autosized heat source capacity (%)
During a system sizing run, if the Autosize air-source heat pump? checkbox (see above) is ticked, the sized Generic heat source capacity will be multiplied by the value in this field to set the Air-source heat pump capacity. The resultant maximum heat pump capacity value will then be used to update the part-load capacity (output) values in the Air-source heat pump dialog: The autosizing will reset the value in the bottom row and proportionally adjust all other values to maintain their relationships as load fractions. Once the generic heat source has been sized, edits made in this field will dynamically update the capacity of the Air-source heat pump, adjusting of all part-load Output values in the associated heat pump dialog to maintain their proportional relationships to the value in the bottom row. The autosized capacity fraction assigned to the Air-source heat pump is not subtracted from the overall Generic heat source capacity. In other words, the sizing of the Air-source heat pump size does not alter the size of the Part load curve Heating equipment component of the Generic heat source.`
Tick this box to indicate that loads served by this heat source will be met by available heat from a Combined heat & power (CHP) system prior to engaging the part-load curve Heating equipment. When present, heat available from CHP will be used to cover the load imposed on the generic heat source according to the following loading sequence: CHRASHPCHPPart load curve Heating equipment. A CHP system is defined within the CHP section of the Renewables dialog in the Apache Thermal view. 2.3.5.2 CHP sequence ranking
CHP sequence ranking determines the sequence in which heat available from CHP are used to cover heating loads imposed on the specified heat sources. Heat sources (Generic or Hot water loop) with lower values of this parameter will be switched in (to receive available heat from CHP) before those with higher values. The former will normally be the most efficient heat sources. If two ApacheHVAC heat sources have the same sequence ranking in this field, they will simultaneously receive available heat from the CHP system in Apache Thermal until either the loads are met or the CHP resource is fully utilized.
VE 6.4 ApacheHVAC 27
The Hot water loop (HWL) heat source can provide heat to any components that present a heating load, with the exception of steam humidifiers, which can be served only by a Generic heat source. Components that can be served by a Hot water loop range from heating coils (both simple and advanced type), radiators, radiant panels, and baseboard heaters to absorption chillers (via Part load curve chiller dialog). Hot water loops can also be designated to serve domestic hot water (DHW) loads from Apache Systems (DHW loads, tanks, associated losses, and DHW-specific solar HW systems are modeled in Apache Systems; resulting/remaining loads are then passed to ApacheHVAC). To designate a GHS to serve DHW loads, tick the Is DHW served by ApacheHVAC boiler? box in the Hot water tab in the Apache Systems dialog, then, in ApacheHVAC, check the Use this heat source for DHW? checkbox in the HWL dialog. 2.4.1.1 Overall sequencing
The sequenced Heating equipment set associated with a Hot water loop meets remaining load after heat available from solar water heating (SWH), condenser heat recovery (CHR), an air-to-water heat pump (AWHP), or combined-heat & power (CHP) system have been fully utilized. The heating load collectively presented by radiators, heating coils, etc. assigned to a particular hot water loop is summed at each time step to set the required instantaneous output from the hot water loop. An allowance is made for any pipe-work distribution losses. Heat available from any pre-heating devices (SWH, CHR, AWHP, and CHP) on the hot water loop is first used to meet the imposed load. Finally, any load left after the pre-heating devices are met by loading the sequenced equipment in the Heating equipment set (see Heating equipment set tab of the Hot water loop dialog). The pre-heating sequence on a hot water loop is therefore, assuming all possible pre-heating devices are present, as follows: SWHCHRAWHPCHPHeating equipment set. Unused pre-heating devices will be skipped in the loading sequence. 2.4.1.2 Heating capacity and feedback to heating components
If the load on a Hot water loop exceeds the combined capacity of Pre-heating devices and Heating equipment set, the Hot water loop will, for just one simulation time step (e.g., 6 minutes) supply the additional energy required, with efficiency remaining at the value associated with full capacity. However, at the very next simulation time step, any deficiency in overall Hot water loop capacity will result in a reduction of the hot water supply temperature, thus providing feedback to the components served by the loop. In other words, heat sources on a Hot water loop will always attempt to achieve the target supply water temperature. If the target supply water temperature cannot be reached, the components served
VE 6.4
ApacheHVAC
28
must attempt to meet heating loads with cooler water. This differs from Generic heat sources, in which case capacity shortages do not feed back to the components served. Presently (as of VE 6.4.0.5), the adjusted hot water supply temperature affects only certain types of components. Advanced heating coils respond to the adjusted supply temperature by reducing the amount of heat they are able to deliver. Radiators (including radiant panels and baseboard heaters) and zone-level hydronic heating loops are next in line to have this capability. Simple heating coils, and radiators in the current version, do not respond to the adjusted temperature. Their heat output is dictated by autosizing and user inputs within the component dialogs and the conditions on the air-side system or in the building spaces where they reside. Likewise, loads on a Hot water loop associated with domestic hot water and absorption chillers are insensitive to the hot water loop supply water temperature. For the time being, these loads must be constrained on the demand side in order to prevent the Heating equipment set on the hot water loop meeting an overcapacity load condition. 2.4.1.3 Hot water loop configurations and pump modeling Primary-only: Loop flow is maintained by a primary hot water pump that can be either a variablespeed pump (i.e., using a variable-speed drive) or constant-speed pump riding the pump curve. Primary-Secondary: Loop flow is maintained by a combination of primary and secondary pumps. The primary pump is assumed to have constant flow when it is on. The secondary pump can be either a variable-speed pump with VSD or a constant-speed pump riding the pump curve.
Two options are offered for the Hot water loop configuration:
For both Hot water loop configurations, when there is only a single boiler operating on the loop (i.e., without any pre-heating devices or other boilers operating), the pump or pumps is/are assumed to operate only when the boiler is operating. In all other cases (i.e., when there are pre-heating devices or multiple boilers operating), the pump operation will be independent of the boiler on/off cycling status. If a pump has variable flow rates (the primary pump in the Primary-only configuration or the secondary pump in the Primary-Secondary configuration), it will be subject to cycling on/off below the minimum flow rate permitted. If the pump has a constant flow when it is on (the primary pump in the Primary-Secondary configuration), this constant flow is multiplied by its specific pump power to determine the pump power. If the pump has variable flow (the primary pump in the Primary-only configuration, or the secondary pump in the PrimarySecondary configuration), its design pump power is calculated as the specific pump power multiplied by the design hot water flow rate. The design pump power is then modified by the pump power curve to get the operating pump power. The required variable flow featured in the pump power curve is calculated as the summation of required flow from all components served by the hot water loop (heating coils, radiators, etc.), subject to the minimum flow the pump permits. Required hot water flow rates for simple heating coils, radiators, absorption chillers, and DHW loads vary in proportion to their heating loads. Required hot water flow rates for advanced heating coils are determined by the detailed heat transfer calculation of the advanced heating coil model (radiators and other zone-level hydronic heating loops and devices are next in line to gain sensitivity to loop temperatures and to provide feedback regarding water flow rates). Figure 2-7 shows the conceptual hot water loop configuration. A Hot water loop with primary-secondary configuration is illustrated. On the secondary loop, hot water is supplied to heating devices connected in parallel to each other. Loads on the demand side (secondary loop in this illustration) can include: simple heating coils, advanced heating coils, hot water radiators/panels/heaters, hydronic heating loops, absorption chillers, and DHW loads from an Apache System. A solar water heater serving as pre-heating
VE 6.4 ApacheHVAC 29
equipment can be included on the return from the demand-side heating devices. As this is connected in series to the heating coils and before the secondary return pipe meets the common pipe, the solar HW heater inlet sees the lowest temperature available in the case of a space heating loop. On the primary loop, heat sources modeled in parallel to each other, and thus each of these sees the primary loop return temperature at its inlet. These are, however, engaged sequentially to raise the hot water return temperature to the hot water supply temperature set point. These heat sources can include: CHR (Condenser heat recovery), AWHP (Air-to-water heat pumps), CHP (Combined heat and power), PLE (Part load curve heating equipment), and HWB (Hot water boilers). When Primary only is selected as the Hot water loop configuration, this effectively removes the constantspeed primary loop pump and common pipe from the diagram below.
Key: CHR Tlbt Vb CHP PLE 1 Secondary pump Tldb gl water air AWHP
Common pipe
PLE 2
HWB 1
Heat sources
Figure 2-7: Hot water loop diagram: Primary-secondary configuration shown. 2.4.1.4 Hot water loop distribution losses
Distribution losses from the pipe work are considered as a user-specified percentage of the hot water loop load. Transfer of hot water pump heat gain to the loop is modeled according to a user input fraction for pump and motor heat gain to the hot water loop.
VE 6.4
ApacheHVAC
Advanced coil
Tedb ge
Absorption chiller
Simple coil
Radiator
DHW
30
2.4.2.1
Enter a description of the component. It is for your use when selecting, organizing, and referencing any component or controllers within other component and controller dialogs and in the component browser tree. These references can be valuable in organizing and navigating the system and when the system model is later re-used on another project or passed on to another modeler. Reference names should thus be informative with respect to differentiating similar equipment, components, and controllers.
VE 6.4
ApacheHVAC
31
Figure 2-8: Hot water loop dialog (shown with the Hot water loop tab selected)
2.4.3.1
Distribution Losses
Enter the hot water loop distribution lossesi.e., the loss due to distribution of heating from the heating plant to point of useas a percentage of heating demand. The loss entered here does not accrue to the conditioned spaces within the building. Rather, this heat is assumed to be lost to the outdoor to the outdoor environment.
Warning Limits (%) Error Limits (%) 0.0 to 20.0 0.0 to 75.0
2.4.3.2
Oversizing Factor
Following ASHRAE Loads autosizing, the factor by which the heating plant size is increased relative to the peak calculated value. 2.4.3.3 Use This Heat Source for DHW?
Tick this checkbox to designate this HWL to serve DHW loads. Also tick the Is DHW served by ApacheHVAC boiler? checkbox in the Hot water tab of an Apache system. 2.4.3.4 Design Hot Water Supply Temperature, Tlbtdes
Enter the design hot water supply temperature (leaving boiler water temperature). 2.4.3.5 Hot Water Supply Temperature Set Point Type
Three options are available for hot water supply temperature set point type: Constant, Timed, or Reset. 2.4.3.6 Constant Hot Water Supply Temperature Set Point
When Constant is selected for hot water supply temperature set point type, this field is automatically set by the program as the design hot water supply temperature. 2.4.3.7 Timed Hot Water Supply Temperature Set Point Profile
When Timed is selected for hot water supply temperature set point type, select the absolute profile to be applied to the hot water supply temperature set point, which are defined through the APPro facility (the Profiles Database). 2.4.3.8 Hot Water Supply Temperature Reset Type
When Reset is selected for hot water supply temperature set point type, select the hot water supply temperature reset type. Currently only one option is provided: Outdoor air temperature reset. When Outdoor air temperature reset type is selected, which is the default, you also need to specify three more reset parameters: Outdoor dry-bulb temperature low limit Outdoor dry-bulb temperature high limit Hot water supply temperature at or above high limit
The fourth parameter (Hot water supply temperature at or below low limit) required by Outdoor air temperature reset type is automatically set by the program as the hot water supply temperature at design condition.
VE 6.4
ApacheHVAC
33
2.4.3.9
When hot water supply temperature reset type is selected as Outdoor air temperature reset, enter the outdoor dry-bulb temperature low limit to be used by the reset. 2.4.3.10 Hot Water Supply Temperature at or below Low Limit
When hot water supply temperature reset type is selected as Outdoor air temperature reset, this parameter is automatically set by the program as the hot water supply temperature at design condition and does not need to be specified. 2.4.3.11 Outdoor Dry-Bulb Temperature High Limit
When hot water supply temperature reset type is selected as Outdoor air temperature reset, enter the outdoor dry-bulb temperature high limit to be used by the reset. 2.4.3.12 Hot Water Supply Temperature at or above High Limit
When hot water supply temperature reset type is selected as Outdoor air temperature reset, enter the hot water supply temperature at or above the outdoor dry-bulb temperature high limit to be used by the reset. 2.4.3.13 Design Hot Water Loop Temperature Difference (Tbdes)
Enter the design hot water loop temperature difference ( T bdes)i.e., the difference between the design hot water supply and return temperatures. 2.4.3.14 Loop Configuration
Select the loop configuration. Two options are offered: Primary-only and Primary-Secondary. 2.4.3.15 Primary Circuit Hot Water Specific Pump Power at Rated Speed
Enter the primary circuit hot water specific pump power at rated speed, expressed in W/(l/s) in SI units (or W/gpm in IP units). If the loop configuration is selected as Primary-only: Primary circuit hot water pump power will be calculated on the basis of variable flow, subject to the constraint that the pump will start cycling below the minimum flow rate it permits. The operating pump power will be based on its design pump power modified by the pump power curve. Its design pump power is calculated as the specific pump power multiplied by the design hot water flow rate. The default value for the specific pump power in this case is the total hot water specific pump power (19 W/gpm) as specified in ASHRAE 90.1 G3.1.3.5. The required variable flow featured in the pump power curve is calculated as the summation of required flow from all components (heating coils, radiators, etc.) served by the hot water loop, subject to the minimum flow the pump permits. Required hot water flow rates for simple heating coils, radiators, absorption chillers, and DHW loads vary in proportion to their heating loads. Required hot water flow rate for advanced heating coils are determined by the detailed heat transfer calculation of the advanced heating coil model. If the loop configuration is selected as Primary-Secondary: Primary circuit hot water pump power will be calculated on the basis of constant flow (when it operates). The model will be based on a specific pump power parameter, with a default value of 3.8
VE 6.4 ApacheHVAC 34
W/gpm. The default value is based on the total hot water specific pump power (19 W/gpm) as specified in ASHRAE 90.1 G3.1.3.5 and assuming a 20:80 split between the primary and secondary circuits. The primary circuit hot water loop flow rate will be calculated from the design heating capacity (Qdes) and the design hot water temperature change (Tbdes) of the hot water loop. 2.4.3.16 Primary Circuit Hot Water Pump Heat Gain to Hot Water Loop (fraction)
Enter the primary circuit hot water pump heat gain to hot water loop, which is the fraction of the motor power that ends up in the hot water. Its value is multiplied by the primary circuit hot water pump power to get the primary circuit hot water pump heat gain, which is deducted from the heating load of the hot water loop. 2.4.3.17 Primary Circuit Hot Water Pump Power Curve, fPv(v)
This field is only active when the loop configuration is selected as Primary-only. If this field is active: This is the primary circuit hot water pump power curve currently selected. Use the Select button to select the appropriate curve from the system database. Use the Edit button to edit the curve parameters if you like. The Edit button will pop up a dialog displaying the formula and parameters of the curve, allowing the curve parameters to be edited. You are allowed to edit the curve coefficients, in addition to the applicable ranges of the curve independent variables. When editing the curve parameters, it is important that you understand the meaning of the curve and its usage in the model algorithm. Also be careful that the edited curve has reasonable applicable ranges for the independent variables. A performance curve is only valid within its applicable ranges. In the case the independent variables are out of the applicable ranges you set, the variable limits (maximum or minimum) you specified in the input will be applied. The primary circuit hot water pump power curve fPv(v) is a cubic function of v = V/Ve where V = pump volumetric flow rate. Ve = design pump volumetric flow rate. And:
2 3 fPv(v) = (C0 + C1 v + C2 v + C3 v ) / Cnorm
where C0, C1, C2 and C3 are the curve coefficients Cnorm is adjusted (by the program) to make fPv(1) = 1
VE 6.4
ApacheHVAC
35
The primary circuit hot water pump power curve is evaluated for each iteration of the hot water loop, for each time step during the simulation. The curve value is multiplied by the design primary hot water pump power to get the operating primary pump power of the current time step, for the current fraction of pump volumetric flow rate. The curve should have a value of 1.0 when the operating pump volumetric flow rate equals rated pump volumetric flow rate (v = 1.0).
Figure 2-9: Edit dialog for the primary circuit hot water pump power curve (values for constant-speed pump are shown) 2.4.3.18 Secondary Circuit Hot Water Specific Pump Power at Rated Speed
This field is only active when the loop configuration is selected as Primary-Secondary. If this field is active: Enter the secondary circuit hot water specific pump power at rated speed, expressed in W/(l/s) in SI units (or W/gpm in IP units). The default value (15.2 W/gpm) is based on the total hot water specific pump power (19 W/gpm) as specified in ASHRAE 90.1 G3.1.3.5 and assuming a 20:80 split between the primary and secondary circuits.
VE 6.4
ApacheHVAC
36
Secondary circuit hot water pump power will be calculated on the basis of variable flow, subject to the constraint that the pump will start cycling below the minimum flow rate it permits. The operating pump power will be based on its design pump power modified by the pump power curve. Its design pump power is calculated as the specific pump power multiplied by the design hot water flow rate. The design secondary circuit hot water loop flow rate is assumed equal to the design primary circuit hot water loop flow rate, which is calculated from the design heating capacity (Qdes) and the design hot water temperature change Tbdes. The required variable flow featured in the pump power curve is calculated as the summation of required flow from all components (heating coils, radiators, etc.) served by the hot water loop, subject to the minimum flow the pump permits. Required hot water flow rates for simple heating coils, radiators, absorption chillers, and DHW loads vary in proportion to their heating loads. Required hot water flow rate for advanced heating coils are determined by the detailed heat transfer calculation of the advanced heating coil model. 2.4.3.19 Secondary Circuit Hot Water Pump Heat Gain to Hot Water Loop (fraction)
This field is only active when the loop configuration is selected as Primary-Secondary. If this field is active: Enter the secondary circuit hot water pump heat gain to hot water loop, which is the fraction of the motor power that ends up in the hot water. Its value is multiplied by the secondary circuit hot water pump power to get the secondary circuit hot water pump heat gain, which is deducted from the heating load of the hot water loop. 2.4.3.20 Secondary Circuit Hot Water Pump Power Curve, fPv(v)
This field is only active when the loop configuration is selected as Primary-Secondary. If this field is active: This is the secondary circuit hot water pump power curve currently selected. Use the Select button to select the appropriate curve from the system database. Use the Edit button to edit the curve parameters if you like. The Edit button will pop up a dialog displaying the formula and parameters of the curve, allowing the curve parameters to be edited. You are allowed to edit the curve coefficients, in addition to the applicable ranges of the curve independent variables. When editing the curve parameters, it is important that you understand the meaning of the curve and its usage in the model algorithm. Also be careful that the edited curve has reasonable applicable ranges for the independent variables. A performance curve is only valid within its applicable ranges. In the case the independent variables are out of the applicable ranges you set, the variable limits (maximum or minimum) you specified in the input will be applied. The secondary circuit hot water pump power curve fPv(v) is a cubic function of v = V/Ve where V = pump volumetric flow rate. Ve = design pump volumetric flow rate.
VE 6.4
ApacheHVAC
37
and fPv(v) = (C0 + C1 v + C2 v + C3 v ) / Cnorm where C0, C1, C2 and C3 are the curve coefficients Cnorm is adjusted (by the program) to make fPv(1) = 1 The secondary circuit hot water pump power curve is evaluated for each iteration of the hot water loop, for each time step during the simulation. The curve value is multiplied by the design secondary hot water pump power to get the operating secondary pump power of the current time step, for the current fraction of pump volumetric flow rate. The curve should have a value of 1.0 when the operating pump volumetric flow rate equals rated pump volumetric flow rate (v = 1.0).
2 3
Figure 2-10: Edit dialog for the secondary circuit hot water pump power curve (values for constant-speed pump are shown)
VE 6.4
ApacheHVAC
38
Figure 2-11: Pre-heating tab on Hot water loop dialog showing all possible pre-heating options and Edit buttons that access dialogs for the Solar water heater and Air-to-water heat pump models.
VE 6.4
ApacheHVAC
39
2.4.4.1
Select the Location of pre-heating components on the hot water loop. Currently only one option is provided: On secondary return pipe.
Figure 2-12: Solar water heater dialog with illustrative inputs. 2.4.5.1 Use solar water heater?
Tick this checkbox to specify a solar water heater as a pre-heating device on the hot water loop. 2.4.5.2 Solar water heater
This displays the reference of the solar water heater associated with this hot water loop. It is not editable directly in the HWL dialog and should be edited in the solar water heater dialog, which is opened by clicking the Edit button to the right of this field.
VE 6.4
ApacheHVAC
40
VE 6.4
ApacheHVAC
41
Figure 2-13: Inputs for percentage availability/effectiveness and recipient for Condenser heat recovery in Heat rejection tab of the Chilled water loop dialog. 2.4.6.1 Use water source heat pump?
If the water loop served by the heating plant receives heat recovered from a chiller condenser, this heat may be upgraded using a water source heat pump (See additional explanation immediately above). Specify this mode of operation by ticking the box.
VE 6.4 ApacheHVAC 42
2.4.6.2
Enter the COP of the water source heat pump that couples the condenser loop with the hot water loop. This should normally be the COP for this equipment when the condenser loop and hot-water return are at design temperatures; however, this may differ for some system designs. 2.4.6.3 Heat pump fuel code
Select the fuel, type of energy source, or energy end-use category for the water-source heat pump. For scratch-built systems, this will normally be Electricity and for pre-defined systems this is set to Heating (electricity), which is an end-use designation for the ASHRAE 90.1 Performance Rating Method reports.
Figure 2-14: Air-to-water heat pump dialog with illustrative inputs (described in section 2.7). 2.4.7.1 Use air-to-water heat pump?
Tick this checkbox to specify an Air-to-water heat pump as a pre-heating device on the hot water loop. The input parameters for Air-to-water heat pumps are described in section 2.7.
VE 6.4
ApacheHVAC
43
2.4.7.2
This displays the reference name of the Air-to-water heat pump associated with this hot water loop. It is not editable directly in the HWL dialog and should be edited in the Air-to-water heat pump dialog, which is opened by clicking the Edit button to the right of this field. 2.4.7.3 Autosize air-to-water heat pump?
Tick this checkbox to autosize the associated Air-to-water heat pump during a system sizing run. When this box is ticked, the peak Hot water loop capacity determined by autosizing will be multiplied by the Percent of autosized heat source capacity (%) (see below) to determine the Air-to-water heat pump capacity. The resultant maximum heat pump capacity value will then be used to update the part-load capacity (output) values in the Air-to-water heat pump dialog: The autosizing will reset the value in the bottom row and proportionally adjust all other values to maintain their relationships as load fractions. Note that the capacity fraction assigned to the heat pump is not subtracted from the hot water loop capacity. In other words, the air-to-water heat pump size will not influence the size of the hot water loop. 2.4.7.4 Percent of autosized heat source capacity (%)
During a system sizing run, if the Autosize air-to-water heat pump? checkbox (see above) is ticked, the sized hot water loop capacity will be multiplied by the value in this field to get the heat pump capacity. The resultant heat pump capacity will then be used to update the air-to-water heat pump capacity in the normal way (re-set the value in the bottom row and adjust all other to maintain proportional relationships in the heat pump data lines). Once the hot water loop has been sized, edits made in this field will lead to automatic dynamic updating of the heat pump capacity and adjusting of all other data lines in the associated heat pump dialog, based on the hot water loop capacity. Note that the capacity fraction assigned to the heat pump is not subtracted from the hot water loop capacity. In other words, the Air-to-water heat pump size will not influence the Hot water loop sizing. 2.4.7.5 2.4.7.6 Combined heat & power Combined heat & power?
Tick this box to indicate that loads served by this heat source will be met by available heat from a Combined heat & power (CHP) system prior to engaging the Heating equipment set on the Hot water loop. When present, heat available from CHP will be used to cover the load imposed on the Hot water loop, according to the following loading sequence: SWHCHRAWHPCHPHeating equipment set. A CHP system is defined within the CHP section of the Renewables dialog in the Apache Thermal view. 2.4.7.7 CHP sequence ranking
CHP sequence ranking determines the sequence in which heat available from CHP are used to cover heating loads imposed on the specified heat sources. Heat sources (Generic or Hot water loop) with lower values of this parameter will receive available heat from CHP before those with higher values. The former will normally be the most efficient heat sources. If two ApacheHVAC heat sources have the same sequence ranking in this field, they will simultaneously receive available heat from the CHP system in Apache Thermal until either the loads are met or the CHP resource is fully utilized.
VE 6.4
ApacheHVAC
44
Figure 2-15: Heating equipment set tab on Hot water loop dialog with illustrative boiler sequencing A heating equipment sequencing table is provided to set the order in which heating equipment are turned on within any particular load range and to set the relative weighting of autosized capacities. Tick boxes are provided to activate up to 5 load ranges for sequencing and the cells with white background can be edited by double clicking. The cells containing heating equipment names in the heating equipment list column provide access to editing individual heating equipment.
VE 6.4
ApacheHVAC
45
2.4.8.1
This selection determines the type of heating equipment model to be added when clicking the Add button. Currently two model types are available: part load curve heating plant and hot water boiler. The Heating equipment set can include any combination of two different heating equipment types: Hot water boiler: uses editable pre-defined curves and other standard inputs, such as efficiency at rated condition, supply temperature, flow rate, and parasitic loads Part load curve heating plant: flexible generic inputs entered in a matrix of load-dependent efficiency and parasitic poweri.e., a data grid with efficiency and pump/parasitic power set relative to maximum and part-load values; can represent any device used to heat water
2.4.8.2
The heating equipment list column lists the heating equipment in the Heating equipment set for the current Hot water loop. Up to 99 separate pieces of heating equipment can be listed and sequenced. To open the Edit dialog for any particular heating equipment, double-click a heating equipment name on the list or select a heating equipment item and click the Edit button. 2.4.8.3 Heating equipment Type
The heating equipment type column indicates the model type for each piece of equipment on the list. The types are determined when the heating equipment is added. PLE = Part-load equipment HWB = Hot-water boiler 2.4.8.4 Part Load Range (up to %)
The part load range (%) values can be edited, with the exception of the last value (100%). Up to five partload ranges can be set. Apart from unused columnsthose with no check in the box at the bottom of the column, and thus grayed-out valuespart load range values must always increase from left to right. 2.4.8.5 Heating equipment Sequence Rank
Heating equipment sequence ranks are entered in the body of the table, for each heating equipment and for each part load range. These are integers in the range of 0 to 99 that determine the order in which heating equipment will be engaged during simulation. Within a specific part load range, heating equipment with lower sequence rank will be engaged first. At least one piece of heating equipment should have a nonzero sequencing rank in every column. When multiple heating equipment are specified to have the same sequence rank for a part load range, they will be engaged simultaneously within that part load range and will share the loop load in proportion to their design capacities. Within any range (except the last), if all the specified heating equipment are operating at maximum output, the sequencing moves to the next range. Note: If the load on a Hot water loop exceeds the combined capacity of Pre-heating devices and Heating equipment set, the Hot water loop will, for just one simulation time step (e.g., 6 minutes) supply the additional energy required, with efficiency remaining at the value associated with full capacity. However, at the very next simulation time step, any deficiency in overall Hot water loop capacity will result in a reduction of the hot water supply temperature, thus providing feedback to the components served by the loop. In other words, heat sources on a Hot water loop will always attempt to achieve the target supply
VE 6.4 ApacheHVAC 46
water temperature. If the target supply water temperature cannot be reached, the components served must attempt to meet heating loads with cooler water. This differs from Generic heat sources, in which case capacity shortages do not feed back to the components served. Presently (as of VE 6.4.0.5), the adjusted hot water supply temperature affects only certain types of components. Advanced heating coils respond to the adjusted supply temperature by reducing the amount of heat they are able to deliver. Radiators (including radiant panels and baseboard heaters) and zone-level hydronic heating loops are next in line to have this capability. Simple heating coils, and radiators in the current version, do not respond to the adjusted temperature. Their heat output is dictated by autosizing and user inputs within the component dialogs and the conditions on the air-side system or in the building spaces where they reside. Likewise, loads on a Hot water loop associated with domestic hot water and absorption chillers are insensitive to the hot water loop supply water temperature. For the time being, these loads must be constrained on the demand side in order to prevent the Heating equipment set on the hot water loop meeting an overcapacity load condition. 2.4.8.6 Heating Equipment Autosizing Capacity Weighting
Heating equipment autosizing capacity weighting is a column of values indicating the relative proportion of the load that each piece of heating equipment will take during autosizing. If the rightmost sequence rank is zero for any heating equipment, the corresponding autosizing capacity weighting will be set automatically to zero. Any heating equipment with a zero autosizing capacity weighting will not be autosized. The Distribute as % button normalizes the autosizing capacity weightings so that they sum to 100. When all the autosizing weightings are zero the Distribute as % button is disabled. It is not obligatory to use the Distribute as % button, as the values will be normalized automatically when applied. 2.4.8.7 Active Sequence Columns
Under each part load range column of the heating equipment sequencing table (except the 100% column), there is a checkbox indicating the current status of the column. These checkboxes can be ticked only from right to left and un-ticked only from left to right. When a check box is ticked, it will populate the column immediately above it with the data from the column to the right of it, thereby rendering the column immediately above it editable. The next checkbox for column immediately to the left of this checkbox will be enabled as well.
VE 6.4
ApacheHVAC
47
Figure 2-16: Part load curve heating plant editing dialog showing illustrative inputs
VE 6.4
ApacheHVAC
48
2.5.1.1
Enter a description of the component. The reference is limited to 100 characters. It is for your use when selecting, organizing, and referencing any component or controllers within other component and controller dialogs and in the component browser tree. These references can be valuable in organizing and navigating the system and when the system model is later re-used on another project or passed on to another modeler. Reference names should thus be informative with respect to differentiating similar equipment, components, and controllers. 2.5.1.2 Heating plant type
Choose from Boiler, Heat pump or Other heating plant. All these types are modeled in the same way, but their simulation results appear under different variables in Vista. 2.5.1.3 Fuel
Select the fuel, type of energy source, or energy end-use category for the part load curve heating plant. For scratch-built systems, this will normally be either Natural Gas or Electricity and for pre-defined systems this is, depending upon the equipment type, set to Heating (fossil fuel) or Heating (electricity), which are energy end-use designations for the ASHRAE 90.1 Performance Rating Method reports (see section 8: Pre-Defined Prototype HVAC Systems and the separate user guide for the PRM Navigator).
Enter up to ten load values to define the part-load efficiency characteristic. Important: The part-load values must be entered in increasing (ascending) order from top to bottom. If entered in the reverse order, only the first value with be used. 2.5.3.2 Efficiency
Enter an efficiency value for each part-load value. Linear interpolation is applied between the defined points. 2.5.3.3 Pump usage
This parameter is only applied for a part load curve heating plant used in the generic heat source. It is not used (disabled) for a part load curve heating plant used in the hot water loop. When this parameter is enabled, enter a pump usage percentage for each part-load value. Linear interpolation is applied between the defined points.
VE 6.4 ApacheHVAC 49
2.6.1.1
Reference
Enter a description of the component. The reference is limited to 100 characters. It is for your use when selecting, organizing, and referencing any component or controllers within other component and controller dialogs and in the component browser tree. These references can be valuable in organizing and navigating the system and when the system model is later re-used on another project or passed on to another modeler. Reference names should thus be informative with respect to differentiating similar equipment, components, and controllers. 2.6.1.2 Fuel
Select the fuel, type of energy source, or energy end-use category for the hot water boiler. For scratchbuilt systems, this will normally be either Natural Gas and for pre-defined systems this is set to Heating (fossil fuel), which is an end-use designations for the ASHRAE 90.1 Performance Rating Method reports (see section 8: Pre-Defined Prototype HVAC Systems and the separate user guide for the PRM Navigator).
Clicking this button to pop up a summary of the hot water boiler model as shown below:
Figure 2-18: Hot water boiler model description 2.6.2.2 Rated Condition is Design Condition
When this box is ticked, the rated condition data (see details in the Rated condition sub-tab) is a read-only copy of the current design condition data (see details in the Design condition sub-tab), including any unsaved edits you have made.
VE 6.4
ApacheHVAC
51
2.6.2.3
The boiler efficiency curve currently selected. Use the Select button to select the appropriate curve from the system database. Pre-defined efficiency curves Non-condensing boiler Condensing boiler Circa 1975 high temp boiler Circa 1983 mid temp boiler Newer low-temp boiler
The first, second, and last of the pre-defined efficiency curves above are the most likely to be applicable for modern hot-water boilers. Keep in mind that these curves describe performance via the shape of the curve, whereas the user input for Efficiency at the rated condition shifts the entire curve up or down. Use the Edit button to edit the curve parameters if needed. The Edit button will pop up a dialog displaying the formula and parameters of the curve, allowing the curve parameters to be edited. You are allowed to edit the curve coefficients, in addition to the applicable ranges of the curve independent variables. When editing the curve parameters, it is important that you understand the meaning of the curve and its usage in the model algorithm. Also be careful that the edited curve has reasonable applicable ranges for the independent variables. A performance curve is only valid within its applicable ranges. In the case the independent variables are out of the applicable ranges you set, the variable limits (maximum or minimum) you specified in the input will be applied.
VE 6.4
ApacheHVAC
52
Figure 2-19: Drop-down boiler type selection list for the hot water boiler model
VE 6.4
ApacheHVAC
53
Figure 2-20: Hot water boiler efficiency curves Edit dialog (part load and water temperature dependence) The boiler efficiency curve (part load and water temp dependence) fEpt(p,Tlbt) is a bi-cubic function of p = part-load ratio tlbt = Tlbt Tdatum
VE 6.4
ApacheHVAC
54
where Tlbt = hot water supply (leaving boiler) temperature Tdatum = datum temperature (0C or 0F), introduced for the convenience of units conversion of the curve coefficients. and fEpt(p,Tlbt) = (C00 + C10 p + C20 p2 + C30 p3 + C01 tlbt + C02 tlbt 2 + C03 tlbt 3 + C11 p tlbt + C21 p2 tlbt + C12 p tlbt ) / Cnorm where C00, C10, C20, C30, C01, C02, C03, C11, C21, and C12 are the curve coefficients Cnorm is adjusted (by the program) to make fEpt(1,Tlbtrat) = 1 Tlbtrat = rated hot water supply (leaving boiler) temperature. The boiler efficiency curve is evaluated for each time step during the simulation. The curve value is multiplied by the rated efficiency (Erat) to get the operating efficiency (E) of the current time step, for the specific part load ratio p and Tlbt temperature: E = Erat fEpt(p,Tlbt) The curve should have a value of 1.0 when the part load ratio equals 1.0 and the Tlbt temperature is at rated condition. A note on the applicable range of part-load ratio p: The minimum p is used by the program as the minimum part-load ratio for continuous operation, under which the boiler starts cycling on and off. The maximum p should usually be 1.0. During the simulation, a part-load ratio greater than 1.0 is a sign of boiler undersizing. Also note that the bi-cubic form of the boiler efficiency curve can be used in simplified forms. For example, to use it in a bi-quadratic form, simply specify C30, C03, C21, and C12 to be zero. To use it in a quadratic-linear form, simply specify C30, C03, C02, and C12 to be zero. 2.6.2.4 Parasitic Power, Wp
2
Enter the boiler parasitic power at full load. The parasitic power represents the parasitic electric power consumed by forced draft fans, fuel pumps, stokers, or other electrical devices associated with the boiler. For a natural draft gas fired boiler, Wp may be zero or close to zero. This parasitic power is consumed whenever the boiler is operating, and the model assumes that this parasitic power does not contribute to heating the water.
VE 6.4
ApacheHVAC
55
2.6.2.5
The ratio between the boiler design parasitic power consumption and the boiler design heating capacity. It is automatically derived by the program using the provided boiler parasitic power and the boiler design heating capacity, and does not need to be specified.
The design hot water supply temperature (leaving boiler water temperature) is specified in the associated hot water loop dialog (in the hot water loop tab) and is displayed here as a derived parameter. 2.6.3.2 Hot Water Flow Rate, Vbdes, Vbdes/Qdes, Tbdes
Vbdes, Vbdes/Qdes, andT bdes are three different options for specifying design hot water flow rate. Currently it is specified in terms of T bdes (the difference between the design hot water supply and return temperatures). It is specified in the associated hot water loop dialog (in the hot water loop tab) and is displayed here as a derived parameter. The other two options (Vbdes and Vbdes/Qdes (the ratio between design hot water flow rate (Vbdes) and design heating capacity (Qdes).) are automatically derived by the program based on the specified Tbdes and cannot be edited. Note: If there is an air-source heat pump or CH(C)P plant attached to the boiler loop, you should calculate what proportion of the total load the boiler takes at the peak condition (which is hard for the software to T determine automatically) and reduce bdes by this factor. (In general, bdes is the temperature rise T across the boiler, not the water loop.) 2.6.3.3 Heating Capacity, Qdes
When Rated condition is design condition is ticked, enter the design heating capacity. When Rated condition is design condition is not ticked, the design heating capacity is always a copy of heating capacity at rated condition and does not need to be edited. This parameter is autosizable. When this parameter is autosized, its value in the field and its autosizing label A become green. 2.6.3.4 Boiler efficiency, Edes
When Rated condition is design condition is ticked, enter the design boiler efficiency. When Rated condition is design condition is not ticked, the boiler design efficiency is automatically derived by the program using other design and rated condition data provided and does not need to be edited.
Figure 2-21: Hot water boiler efficiency curves Edit dialog (part load and water temperature dependence) To use catalogue boiler data, enter capacity and efficiency at the rated condition and read the derived capacity and efficiency at the design condition. The model sets the design capacity as equal to the rated capacity. Design efficiency, however, may differ from rated efficiency if the user specifies a design hot water supply temperature that is different from the rated hot water supply temperature. To size a boiler based on a design load, enter a capacity and efficiency at the rated condition; then adjust the efficiency to produce the desired derived efficiency at the design condition (allowing for a margin of over-sizing). Again, the Design capacity will always equal the rated capacity. If the rated condition and design condition are one and the same, tick the Rated condition is design condition checkbox, which makes the rated condition data a linked copy of the design condition data.
VE 6.4
ApacheHVAC
57
2.6.4.1
When Rated condition is design condition is ticked, the rated hot water supply temperature (leaving boiler water temperature) is a dynamic copy of the design hot water supply temperature. When Rated condition is design condition is not ticked, enter the rated hot water supply temperature. 2.6.4.2 Hot Water Flow Rate, Vbrat, Vbrat/Qrat, Tbrat
Vbrat, Vbrat/Qrat, and Tbrat are three different options for specifying rated hot water flow rate. Currently it is specified in terms T of brat (the difference between the rated hot water supply and return temperatures). The other two options (Vbrat and the ratio between rated hot water flow rate (Vbrat) and rated heating capacity (Qrat)) are automatically derived by the program based on the specifiedT brat and cannot be edited. When Rated condition is design condition is ticked, the rated hot water flow rate is a dynamic copy of the design hot water flow rate. When Rated condition is design condition is not ticked, enter the rated hot water flow rate. 2.6.4.3 Heating Capacity, Qrat
When Rated condition is design condition is not ticked, enter the rated heating capacity. When Rated condition is design condition is ticked, the rated heating capacity is always a copy of heating capacity at design condition and does not need to be edited. 2.6.4.4 Boiler efficiency, Erat
When Rated condition is design condition is ticked, the rated boiler efficiency is a dynamic copy of the design boiler efficiency. When Rated condition is design condition is not ticked, enter the rated boiler efficiency. The boiler efficiency (as a fraction between 0 and 1) is the efficiency relative to the higher heating value (HHV) of fuel at a part load ratio of 1.0 and the rated hot water supply temperature (leaving boiler). Manufacturers typically specify the efficiency of a boiler using the higher heating value of the fuel. For the rare case when a manufacturers (or particular data set) boiler efficiency is based on the lower heating value (LHV) of the fuel, multiply the thermal efficiency by the lower-to-higher heating value ratio. For example, assume a fuels lower and higher heating values are approximately 45,450 and 50,000 kJ/kg, respectively. For a manufacturers thermal efficiency rating of 0.90 (based on the LHV), the nominal thermal efficiency entered here is 0.82 (i.e. 0.9 multiplied by 45,450/50,000).
VE 6.4
ApacheHVAC
58
The air source for the air-source heat pumps is always assumed to be outside air.
VE 6.4
The maximum load percentage for the AAHP typethe bottom row value for Output (%)is fixed at 100%. Values in other rows for the Output (%) column must be between 0% and 100%. The assumption underlying this is that capacity increases with source temperature. When converting old ASHPs to the new AAHP type(s), a sharing rule is applied: when possible, the minimum number of AAHP types and GHS instances are created for each multiplexed ASHP. The sharing rule implies that there are two cases where the multiplexed ASHP with backup part-load heat source can be considered as having the same shape and therefore will be converted to a single AAHP type: 1. All the data fields contain identical values within the multiplexed ASHPs associated with a common part-load backup heat source. Obviously, these ASHPs will translate to the same AAHP type. This case happens when multiple ASHPs are replicated in the process of multiplexing a system with an ASHP on the initial layer, without any user edits in the individual ASHPs on subsequently created layers. 2. The first two columns of data (Source temp. and COP) in the ASHPs performance table are the same, and although the third column has different values, all data in this column are in the same proportionsi.e., if you transfer the last column data to percentage values expressed as a percentage of the capacity (setting the last row value to 100%), then you will get the same column of percentages. This is normally the result of autosizing an old system with multiplexed otherwise identical ASHPs serving multiplexed heating coils. The ASHP on each multiplex layer is likely to have a unique capacity after autosizing, with part-load values in other rows proportionally scaled, based on their previous values expressed as a fraction of the maximum. In all other cases, multiplexed ASHPs coupled to part-load backup heat sources are considered as having different shapes and are thus converted to separate AAHP types.
When updating an old ASHP to an Air-to-air heat pump (AAHP) in cases where this heat pump is associated with a single heating coil, the capacity from the old ASHP (the figure shown for Output in the last row of its performance table) is assigned to the associated heating coil in the updated system. This rule means that the capacity assigned to a coil may be changed by the updating process, so that if (at certain time steps) a heating coil reaches its capacity, it will behave differently in the updated system. However, this is better than changing the performance characteristics of the heat pump (which would be the result if the coil capacity remained unchanged), in which case the energy consumption at every time step would have to change.
VE 6.4
ApacheHVAC
60
2.7.2 Air-to-water heat pump (AWHP) and generic Air-source heat pump (ASHP)
The air-to-water heat pump (AWHP, in the context of a hot water loop and accessed from the Pre-heating tab of the Hot water loop dialog) or Air-source heat pump (ASHP, in the context of a generic heat source and accessed from the Generic heat source dialog) is essentially the old air source heat pump but interfaced in a different way. Instead of being drawn on the system air network, it is specified in the heat source dialogs (as shown above in the Generic heat source dialog and in the Pre-heating tab of the Hot water loop dialog). In the background of ApacheHVAC, air-to-water heat pumps are treated as actual components (instances) rather than types, in contrast to the Air-to-air heat pumps, which are treated as types, not instances. The new AWHP will always use outside air, rather than a user-selected location on the airside network, as its heat source (which is nearly always the case in reality). Note the change on where the link between an AWHP and a backup heat source is specified. Pre-v6.4.0.5, this was specified in the old ASHP dialog through the Backup heat source parameter. From v6.4.0.5 onward, it is determined in the heat source dialogs, given that the AWHP can be added only as a preheating device on a Hot water loop or similar option in the Generic heat source dialog. Although determined in a different location and having a more appropriate parent-child relationship from the user perspective, the one-to-one relationship (constraint) between an AWHP and a backup heat source still exists (for now): only one AWHP may be specified as the pre-heating device for a given generic heat source or hot water loop. In the case of an AWHP linked to an HWL the simulation will incur pumping power when the AWHP is running and the main (backup) heat source is not.
Figure 2-22: AWHP accessed from the Pre-heating tab of the Hot water loop dialog.
VE 6.4 ApacheHVAC 61
Figure 2-23: ASHP accessed from the Generic heat source dialog with illustrative values as might be used for domestic hot water (DHW) heating in a warm climate with an otherwise all-electric, cooling-centric space-conditioning system.
Enter a description of the component. The reference is limited to 100 characters. It is for your use when selecting, organizing, and referencing any component or controllers within other component and controller dialogs and in the component browser tree. These references can be valuable in organizing and navigating the system and when the system model is later re-used on another project or passed on to another modeler. Reference names should thus be informative with respect to differentiating similar equipment, components, and controllers. 2.7.3.2 Fuel Code
Select the fuel, type of energy source, or energy end-use category for the air-to-water or air-source heat pump. For scratch-built systems, this will normally be Electricity and for pre-defined systems this is set to the Heating (electricity) end-use designation for the ASHRAE 90.1 Performance Rating Method reports.
VE 6.4
ApacheHVAC
62
2.7.3.3
The heat pump is assumed to switch off completely when the source temperature drops below this value. Above this value, the heat pump is assumed to meet as much of the load as it can, with the heat source being brought in to top up this demand if required.
This line of information describes the variation in the performance of the heat pump as the source temperature varies. Enter the source temperature. Up to ten points may be used to define the variation of performance with source temperature. Enter the points in ascending order of source temperature. 2.7.4.2 Heat Pump COP
Enter the coefficient of performance of the heat pump at the corresponding source temperature. This value is the useful heat output divided by the total fuel energy consumption associated with the operation of this device (excluding electrical consumption of any distribution pumps included in heating plant components). 2.7.4.3 Output
Enter the maximum heat pump output at the corresponding source temperature. If the demand for heat output exceeds this value then the heat source is used to make up the extra demand.
VE 6.4
ApacheHVAC
63
Figure 2-24: Air-to-air heat pump (types) dialog This facility supports defining the performance characteristics of one or more AAHP types. The entities defined here are types. A single AAHP type may be assigned to many heating coils. At the time of simulation instance of the AAHP type is automatically created for each heating coil to which the AAHP type is assigned. In this respect AAHP differ from the AWHP attached to a hot water loop (or the ASHP attached to a generic heat source).
VE 6.4
ApacheHVAC
64
Figure 2-25: Air-to-air heat pump dialog with default inputs as provided for the AAHP in the pre-defined packaged single-zone heat pump (04 PSZ-HP) system when the autosized load range is >135 kBtu/h.
Enter a description of the component. The reference is limited to 100 characters. It is for your use when selecting, organizing, and referencing any component or controllers within other component and controller dialogs and in the component browser tree. These references can be valuable in organizing and navigating the system and when the system model is later re-used on another project or passed on to another modeler. Reference names should thus be informative with respect to differentiating similar equipment, components, and controllers.
VE 6.4 ApacheHVAC 65
2.7.6.2
Select the backup heat source for the AAHP type. Note that only heat sources of the generic type will be available to be selected as the backup heat source for an AAHP type. 2.7.6.3 Fuel Code
Select the fuel, type of energy source, or energy end-use category for the air-to-air heat pump. For scratch-built systems, this will normally be Electricity and for pre-defined systems this is set to the Heating (electricity) end-use designation for the ASHRAE 90.1 Performance Rating Method reports. 2.7.6.4 Minimum Source Temperature
The heat pump is assumed to switch off completely when the source temperature drops below this value. Above this value, the heat pump is assumed to meet as much of the load as it can, with the backup heat source being brought in to meet remaining demand as required. Typically, the minimum source temperature is the temperature at which the unit will be shut off to optimize overall system operating efficiency or similar. For example, this may be the outdoor temperature at which the heat pump COP would drop to 1.0 when the backup is electric resistance heat. Once the heat pump COP drops to 1.0 or near that value, it may no longer make sense to operate it when the much simpler and therefore less costly to operate electric resistance heating is equally efficient.
This line of information describes the variation in the performance of the heat pump as the source temperature varies. Enter the source temperature. Up to ten points may be used to define the variation of performance with source temperature. Enter the points in ascending order of source temperature. 2.7.7.2 Heat Pump COP
Enter the coefficient of performance of the heat pump at the corresponding source temperature. This value is the useful heat output divided by the total fuel energy consumption associated with the operation of this device (excluding electrical consumption of any distribution pumps included in heating plant components). 2.7.7.3 Output
Enter the maximum heat pump output at the corresponding source temperature. If the demand for heat output exceeds this value then the backup heat source (if present) is used to make up the extra demand. Note that AAHP Output is in the form of a percentage value. Output percentage is defined as the heat pump output (kW in SI units; kBtu/h in IP units) divided by the heat pump design capacity. Design capacity of an AAHP is specified as the capacity of a simple heating coil connected to an AAHP type.
VE 6.4
ApacheHVAC
66
Figure 2-26: Air-source heat pump dialog with illustrative inputs The air-source heat pump models (ASHP, AWHP, and AAHP) in ApacheHVAC provide straightforward and very clear means of modeling of the following relationships: Air-source-temperature dependent COP Air-source-temperature dependent output (heating capacity, not to be confused with load) Minimum source temperature for operation
This model does not, however, provide a direct means of accounting for the additional dimension of partload-dependent COP. The following method of doing so has been used in the pre-defined AAHPs as an illustration of one possible approach to this and can be reproduced by users as appropriate.
VE 6.4 ApacheHVAC 67
Figure 2-27: Air-source heat pump performance associated with illustrative inputs in Figure 2-26
VE 6.4
ApacheHVAC
68
Figure 2-28: Graphic representation of the illustrative inputs in Figure 2-26 Figures 2-26, 2-27, and 2-28 above show illustrative inputs for the ASHP dialog and the relationship between these and the heat pump capacity curve and full-load COP curve. To account for both change in performance (output and COP) with outdoor temperature and reduced COP at part load, it is useful to create simple graphs of the first two of these (green and purple lines in Figure 2-27) and then use simulation results to determine part-load values corresponding to outdoor temperature above the outdoor temperature at which the heat pump output is well matched to heating load. At lower outdoor temperatures, the heat pump will be fully loaded, and thus the model should use
VE 6.4 ApacheHVAC 69
the full-load COP (dashed yellow line segments in Figure 2-27). At higher outdoor temperatures, which normally are associated with reduced heating loads, the heat pump COP will tend to decrease with load (dashed orange and red line segments in Figure 2-27). If the heat pump is never to be fully loaded at the outdoor temperature associated with the rating condition (e.g., at 47 F), which is a function of design sizing condition and oversizing, it may be that the COP provided at the rating condition will never be applicable. In other words, because the COP will tend to decrease both with decreasing load (as the outdoor temperature rises above that which corresponds to the fully loaded condition) and with decreasing outdoor temperature below the rating condition, the heat pump COP will always be less than the COP when fully-loaded at the rating condition. Simulation results were used to determine that the load placed upon the ASHP after sizing would be 100% at 32 F, with supplemental heat from the backup heat source increasingly required below that temperature and, above 32 F, heating load gradually diminishing to 40% at an outdoor temperature of 62 F. This information was used to determine the part-load COP curve (dashed line) in Figure 2-27. To facilitate insertion of the autosized capacity (based upon the winter heating design day conditions for the project location) in the row associated with the ARI testing condition (47 F) used to determine the equipment capacity and COP, the curves are intentionally truncated to end at 47 F. In the example in Figures 2-26, 2-27, and 2-28 above, the COP for the fully loaded heat pump at the 47 F rating condition would be 4.0, and this is the outdoor temperature at which the full rated capacity would be available. However, when sized to meet the full load at 32 F, the heat pump load is 81% of full load at 47 F outdoor temperature for this example. Thus the maximum COP of 3.35 occurs at an outdoor temperature of approximately 37 F and 95% load and the COP is just 3.2 at 47 F and 81% load. The inputs in the ASHP dialog could be extended to warmer temperatures if needed. Because the dialog accepts just 10 rows of data, the spacing between data points would need to be revised to accommodate this. Because the model uses linear interpolation between the data points provided, and the COP and capacity curves are both relatively flat between about 17 and 32 F for this particular data set, this would be the best region of the curve to be represented by a reduced density of data points.
VE 6.4
ApacheHVAC
70
2.8 Chilled Water Loops, Pre-Cooling, Heat Rejection, and Chiller Sequencing
The chilled water loop tool provides access to selection, editing, and adding or removing named chilled water loops. Each individual chilled-water loop dialog then provides inputs for to following: primary and secondary chilled water loops and option to use just one of these pre-cooling devices such as integrated waterside economizers chillers and other similar cooling sources (adding, sequencing, and editing of cooling equipment on the primary chilled-water loop) heat-rejection loop (for water-cooled chillers) with cooling tower and options for waterside economizer and condenser heat recovery
A chilled water loop is associated with a chiller set comprising any number of chillers, which can include any combination of three different types: electric water-cooled chiller (uses editable pre-defined curves and other standard inputs) electric air-cooled chiller (uses editable pre-defined curves and other standard inputs) part-load-curve chiller (flexible generic inputs; can represent any device used to cool water via a matrix of load-dependent data for COP and associated usage of pumps, heat-rejection fans, etc., with the option of adding COP values for up to four outdoor DBT or WBT conditions)
Each chiller or similar piece of water cooling equipment is defined in the context of a chilled water loop. Thus no chiller is permitted to serve more than one primary chilled water loop. Chillers can be duplicated using the Copy button within a chiller set and an Import facility is provided for copying a defined chiller from one chilled-water loop to another. An optional condenser water loop is associated with each primary chilled water loop. This includes a cooling tower model and is required only when the chiller set includes an electric water-cooled chiller. An integrated waterside economizer is also available for condenser water loop systems. Air-cooled chillers use only the design temperatures (DBT and WBT) for heat rejection. Heat rejection for the generic partload-curve chiller type is described by the user via any combination of COP values, pump power, and fan power (all or any of which can be included in a composite COP) in the dialog for that type of equipment. Cooling coils and chilled ceilings are assigned a chilled water loop rather than a chiller. While the standard configuration uses a primary-plus-secondary loop configuration, the primary loop can be eliminated by zeroing out its pump power such that the system is modeled as a primary-only configuration using only the secondary loop as though it were the primary loop with whichever type of pump is selected for it. During simulation, chillers within a chiller set are switched in according to a user-specified sequence. During autosizing, sequenced chillers and the associated heat rejection plant and water flow rates are sized on the basis of user-specified percentages of the peak design load. Whether chillers are autosized or manually sized, the sizing of heat rejection equipment on the condenser water loop is always tied to the set cooling capacity of the chiller(s) that will operate maximum sequence load range. When electricwater-cooled chillers are included, and thus there is an associated cooling tower or fluid cooler, the chiller set may operate in waterside economizer mode (integrated or non-integrated modes are offered). Chilled water loops are accessed through the toolbar icon shown below. Toolbar icon for Chilled water loops. Clicking this toolbar icon opens up the Chilled water loops dialog (shown in Figure 2-17), which manages a set of chilled water loops. A chilled water loop may be added, edited, removed or copied through the
VE 6.4 ApacheHVAC 71
corresponding buttons in this dialog. Double clicking on an existing chilled water loop (or clicking the Edit button after selection of an existing chilled water loop) opens up the Chilled water loop dialog (shown in Figure 2-29), where chilled water loop parameters may be edited. The Chilled water loop dialog currently has three tabs: Chilled water loop tab: This tab manages the properties of the chilled water loop. Pre-cooling tab: This tab manages pre-cooling devices such as an integrated waterside economizer to provide pre-cooling prior to chiller set. Chiller set tab: This tab manages a list of chillers (a chiller set), which may be edited with chiller dialogs (see section 2.5, 2.6 and 2.7). Chiller sequencing ranks under variable part load ranges are also defined in this tab, together with chiller autosizing capacity weightings. Heat rejection tab: This tab manages information used for heat rejection. An optional condenser water loop for use by electric water-cooled chillers and (optionally) a waterside economizer can be defined in this tab.
Currently if a condenser water loop has been defined for a chilled water loop, at least one electric watercooled chiller must also be defined for the same chilled water loop. Electric water-cooled chillers belonging to the same chiller set share a common condenser water loop and cooling tower. The cooling tower model used is the same as that used for the Dedicated Water Side Economizer model, which is based on the Merkel theory. A condenser water pump is assumed to be included downstream of the cooling tower. When condenser water flow rate differs from the rated condenser water flow rate, an adjustment is made to the entering condenser water temperature used by the program to solve for the chiller performance in the iteration process. The adjustment is made based on the following principle: Set the effective entering condenser water temperature to the value which, for the given rate of heat rejection, would produce the same condenser water leaving temperature as a chiller operating with the rated condenser water flow rate.
The chilled water loop configuration is assumed to be a primary/secondary system, served by a primary circuit chilled water pump and a secondary circuit chilled water pump. Both condenser water pump and primary circuit chilled water pump are assumed to operate in line with the chiller. The condenser water flow rate and primary circuit chilled water flow rate are assumed to be constant (at the design values) when the chiller is on. They are multiplied by the corresponding specific pump power to get the condenser water pump power and the primary chilled water pump power respectively. The secondary circuit chilled water pump is assumed to operate in line with the chiller, subject to the constraint that the pump will start cycling below the minimum flow rate it permits. Required chilled water flow rates for simple cooling coils and chilled ceilings vary in proportion to their cooling loads. Required chilled water flow rate for advanced cooling coils are determined by the detailed heat transfer calculation of the advanced cooling coil model. Required chilled water flow rates from all cooling coils and chilled ceilings served by a chilled water loop are summed to get the required secondary circuit chilled water flow rate, subject to the minimum pump flow rate the pump permits. The design secondary chilled water pump power is calculated as the secondary specific pump power multiplied by the design secondary chilled water flow rate (assumed equal to design primary chilled water flow rate). It is then modified by the secondary circuit pump power curve to get the operating secondary pump power.
VE 6.4
ApacheHVAC
72
Distribution losses from the pipe work are considered as a user-specified percentage of the chilled water loop load. In addition, chilled water and condenser water pump heat gains are modeled by pump motor efficiency factors. Condenser heat recovery is included in the current model as a simple user-specified percentage of the thermal energy rejected to the condenser loop. This percentage represents heat-exchanger effectiveness. The available condenser heat is then assigned to a receiving heat source that will use this recovered heat first when a load is present. The user has the options to upgrade the hot-water temperature for the recovered heat on the receiving (HW loop) end with an electric water-to-water heat pump for use with typical space heating loads.
Figure 2-29: Chilled water loops dialog (shown with default and illustrative loops included with the predefined systems in VE 6.3)
VE 6.4
ApacheHVAC
73
Tlct L T1 Vc
PLC 1 PLC 2
Cooling tower
EWC 1
Chilled ceiling
Primary pump
Figure 2-30: Chilled water loop configuration drawn with a chiller set that includes all three types of chiller models (part-load-curve; electric water-cooled; electric air-cooled): only the electric water-cooled type is couple to the condenser water loop and cooling tower model. See 2.4.11 Primary Circuit Chilled Water Specific Pump Power for modeling systems having only a primary chilled water loopno secondary loop.
VE 6.4
ApacheHVAC
Advanced coil
Tedb ge
Simple coil
74
Figure 2-31: Chilled water loop editing dialog (shown with the Chilled water loop tab active)
VE 6.4
ApacheHVAC
75
Figure 2-32: Chilled water loop tab in the Chilled water loop dialog (shown with inputs for an illustrative loop configuration and settings as included with the pre-defined systems)
VE 6.4
ApacheHVAC
76
2.8.1.1
Enter a description of the component. It is for your use when selecting, organizing, and referencing any component or controllers within other component and controller dialogs and in the component browser tree. These references can be valuable in organizing and navigating the system and when the system model is later re-used on another project or passed on to another modeler. Reference names should thus be informative with respect to differentiating similar equipment, components, and controllers.
Enter the chilled water loop distribution lossesi.e., the loss due to distribution of cooling from the cooling plant equipment to point of useas a percentage of cooling demand. The loss entered here is not recouped in the building.
Warning Limits (%) Error Limits (%) 0.0 to 20.0 0.0 to 75.0
2.8.2.2
Oversizing Factor
This is the oversizing factor that will be used in the autosizing of this component. During autosizing the capacity will be set to the peak load multiplied by the oversizing factor. 2.8.2.3 Chilled Water Supply Temperature Reset Type
Select the chilled water supply temperature reset type. Currently two options are provided: No reset or Outdoor air temperature reset. When Outdoor air temperature reset type is selected, which is the default, you also need to specify four more reset parameters: Outdoor dry-bulb temperature low limit Chilled water supply temperature at or below low limit Outdoor dry-bulb temperature high limit Chilled water supply temperature at or above high limit
When No reset is selected, you need only specify the constant design chilled water supply temperature. 2.8.2.4 Chilled Water Supply Temperature
Enter the design chilled water supply temperature (leaving evaporator water temperature) if the chilled water supply temperature reset type is selected as No reset. When Chilled water supply temperature reset type is selected as Outdoor air temperature reset, this field becomes inactive. 2.8.2.5 Outdoor Dry-bulb Temperature Low Limit
When chilled water supply temperature reset type is selected as Outdoor air temperature reset, enter the outdoor dry-bulb temperature low limit to be used by the reset.
VE 6.4
ApacheHVAC
77
2.8.2.6
When chilled water supply temperature reset type is selected as Outdoor air temperature reset, enter the chilled water supply temperature to be used by the reset at or below the outdoor dry-bulb temperature low limit. 2.8.2.7 Outdoor Dry-bulb Temperature High Limit
When chilled water supply temperature reset type is selected as Outdoor air temperature reset, enter the outdoor dry-bulb temperature high limit to be used by the reset. 2.8.2.8 Chilled Water Supply Temperature at or above High Limit
When chilled water supply temperature reset type is selected as Outdoor air temperature reset, enter the chilled water supply temperature to be used by the reset at or above the outdoor dry-bulb temperature high limit. 2.8.2.9 Design Chilled Water Loop Temperature Difference (Tedes)
Enter the design chilled water loop temperature difference (Tedes)i.e., the difference between the design chilled water supply and return temperatures. 2.8.2.10 Primary Circuit Chilled Water Specific Pump Power at Rated Speed
Enter the primary circuit chilled water specific pump power at rated speed, expressed in W/(l/s) in SI units (or W/gpm in IP units). Primary circuit chilled water pump power will be calculated on the basis of constant flow (when the chiller operates). The model will be based on a specific pump power parameter, with a default value of 4.4 W/gpm. The default value is based on the total chilled water specific pump power (22 W/gpm) as specified in ASHRAE 90.1 G3.1.3.10 and assuming a 20:80 split between the primary and secondary circuits. The basis for this default split is described under Secondary Circuit Chilled Water Specific Pump Power at Rated Speed, below. The primary circuit chilled water loop flow rate will be calculated from the design cooling capacity (Qdes) and the design chilled water temperature change (Tedes) of the chilled water loop. Primary-only vs. Primary + Secondary loop configurations: To model a primary-only configuration with VSD pump, rather than the pre-set primary + secondary chilled water loop configuration (for version 6.3 through 6.4), first set the primary specific pump power to zero. Select the VSD curve for the secondary pump and set the specific pump power for the secondary loop as appropriate for the primary loop pump. This simply removes the primary pump from the system and allows the secondary pump to serve as the primary pump with VSD in the actual system. If, on the other hand, you were to include a specific power input for the primary pump and set the secondary pump specific power to zero, there would be no opportunity to use the VSD, as the primary pump is assumed (for version 6.3 through 6.4) to run at constant speed whenever the chiller operates. 2.8.2.11 Primary Circuit Chilled Water Pump Heat Gain to Chilled Water Loop (fraction)
Enter the primary circuit chilled water pump heat gain to chilled water loop, which is the fraction of the motor power that ends up in the Chilled water. Its value is multiplied by the primary circuit chilled water pump power to get the primary circuit chilled water pump heat gain, which is added to the cooling load of the chilled water loop.
VE 6.4 ApacheHVAC 78
2.8.2.12
Enter the secondary circuit chilled water specific pump power at rated speed, expressed in W/(l/s) in SI units (or W/gpm in IP units). The default value (17.6 W/gpm) is based on the total chilled water specific pump power (22 W/gpm) as specified in ASHRAE 90.1 G3.1.3.10 and assuming a 20:80 split between the primary and secondary circuits. The default 20:80 split between primary and secondary is based upon typical pump head values of 15 feet of for the primary loop and 60 feet of head for the secondary loop. Thus the default specific pump power values are 4.4 W/gpm or 69.7414 W/(l/s) for the primary loop, and 17.6 W/gpm or 278.9657 W/(l/s) for the secondary loop. However, while this default may be appropriate to 90.1 PRM Baseline models, it is otherwise just a typical starting point and should be adjusted to match the actual relative pump head values. Secondary circuit chilled water pump power at each simulation time step is calculated on the basis of variable flow. Required chilled water flow rates for simple cooling coils and chilled ceilings vary in proportion to their cooling loads, assuming a constant operating delta-T across the cooling coils. The same is true for chilled ceilings through version 6.4.x.x. Required chilled water flow rate for advanced cooling coils are determined by the detailed heat transfer calculation of the advanced cooling coil model. Required chilled water flow rates from all cooling coils and chilled ceilings served by a chilled water loop are summed to get the required secondary circuit chilled water flow rate, subject to the minimum pump flow rate the pump permits. The design secondary circuit chilled water loop flow rate is assumed equal to the design primary circuit chilled water loop flow rate, which is calculated from the design cooling capacity (Qdes) and the design chilled water temperature change Tedes. The design secondary chilled water pump power is calculated as the secondary specific pump power multiplied by the design secondary chilled water flow rate. It is then modified by the secondary circuit pump power curve to get the operating secondary pump power. 2.8.2.13 Secondary Circuit Chilled Water Pump Heat Gain to Chilled Water Loop (fraction)
Enter the secondary circuit chilled water pump heat gain to chilled water loop, which is the fraction of the motor power that ends up in the Chilled water. Its value is multiplied by the secondary circuit chilled water pump power to get the secondary circuit chilled water pump heat gain, which is added to the cooling load of the chilled water loop. 2.8.2.14 Secondary Circuit Chilled Water Pump Power Curve, fPv(v)
The secondary circuit chilled water pump power curve currently selected. Use the Select button to select the appropriate curve from the system database. Use the Edit button to edit the curve parameters if you like. The Edit button will pop up a dialog displaying the formula and parameters of the curve, allowing the curve parameters to be edited. You are allowed to edit the curve coefficients, in addition to the applicable ranges of the curve independent variables. When editing the curve parameters, it is important that you understand the meaning of the curve and its usage in the model algorithm. Also be careful that the edited curve has reasonable applicable ranges for the independent variables. A performance curve is only valid within its applicable ranges. In the case the independent variables are out of the applicable ranges you set, the variable limits (maximum or minimum) you specified in the input will be applied.
VE 6.4
ApacheHVAC
79
The secondary circuit chilled water pump power curve fPv(v) is a cubic function of v = V/Ve where V = pump volumetric flow rate. Ve = design pump volumetric flow rate. And:
2 3 fPv(v) = (C0 + C1 v + C2 v + C3 v ) / Cnorm
where C0, C1, C2 and C3 are the curve coefficients Cnorm is adjusted (by the program) to make fPv(1) = 1 The secondary circuit chilled water pump power curve is evaluated for each iteration of the chilled water loop, for each time step during the simulation. The design secondary chilled water pump power is multiplied by the curve value to get the operating secondary pump power of the current time step, for the current fraction of pump volumetric flow rate. The curve should have a value of 1.0 when the operating pump volumetric flow rate equals rated pump volumetric flow rate (v = 1.0). Example: The standard curve for a variable-speed pump at 60% of the design flow rate will return a value of 0.216. Assume for the example that the design flow rate were 100 gpm, thus 60% would be 60 gpm. If the specific pump power at the design flow rate were 15 W/gpm, this would equate to 1,500 W at design flow. Finally, the 1,500 W pump power at the design flow would be multiplied by 0.216 to yield 324 W pump power at 60% for the design flow rate. If the input for Minimum v in the pump performance curve Edit dialog were set to 0.600 or 60%, indicating a minimum 60%pump operating volume, this would cause the secondary pump power to remain at 324 W when the pump operates (subject to the 60% minimum setting for the volumetric flow rate). As noted in previous sections, the secondary circuit chilled water pump is assumed to operate in line with the chiller (when the chiller operates); however, regardless of whether or not the chiller has reached the minimum load fraction set point for continuous operation, the pump will cycle whenever the required flow rate is at or below the set minimum flow rate for the pump (Minimum v in the performance curve Edit dialog). When the pump is on, the pump power is calculated as the design pump power multiplied by the pump curve value for the minimum v point on the curve. When cycled off, the pump power is zero. Because the pump is assumed to operate in line with the chiller, it will also cycle on/off with the chiller when the loop cooling load is . The associated chiller cycling ratio will this be used in the pump power calculation when the pump is cycling on and off as a result of the chiller doing so. If the require water flow rate is also at or below minimum for the pump, the pump power calculated as the design pump power multiplied by the pump curve value at the minimum v will be further multiplied by the pump running fraction and chiller running fraction.
VE 6.4
ApacheHVAC
80
Figure 2-33: Edit dialog for the secondary circuit chilled water pump power curve (values for constantspeed pump are shown)
VE 6.4
ApacheHVAC
81
Figure 2-34: Pre-cooling tab on Chilled water loop dialog (shown with inputs for an illustrative integrated waterside economizer) 2.8.3.1 Location of Pre-cooling devices
Select the location of the pre-cooling device. Pre-cooling devices can be placed on the return of either the CWL primary or secondary circuits. If placed on the primary loop, the device is placed downstream of the primary pump. If placed on the secondary loop, the device is located immediately upstream of the primary-secondary common pipe junction. In its initial implementation, all pre-cooling devices must use the same location. 2.8.3.2 Integrated Waterside Economizer
An integrated waterside economizer (IWSE) can be specified as a pre-cooling device. The IWSE acts in series with the chiller water loop chillers to either pre-cool the return water to the chillers or, when its capacity is sufficient with respect to load, address the full cooling load for the chilled water loop. The IWSE attempts to provide all demanded chilled water loop cooling. If it cannot meet the full cooling load, the IWSE will pre-cool the return water to the chiller set and thereby reduce the cooling load on the chillers. If the IWSE shares the cooling tower with the chiller set, the condenser water flow (i.e., cooling tower flow) is apportioned between the IWSE and chiller set such that IWSE capacity is fully utilized and only remaining cooling load is placed on the chiller set. At least one electric water-cooled (EWC) chiller must be included in the chiller set in order for there to be a condenser water loop, and this is prerequisite to using the integrated waterside economizer, as the cooling tower for the integrated WSE is defined as part of the condenser water heat rejection apparatus.
VE 6.4
ApacheHVAC
82
2.8.3.3
Use WSE only we can meet the load in full (non-integrated WSE)?
This selection restricts operation of the WSE to when it can meet the CWL cooling load in full. If the WSE cannot meet the load in full, this mode turns off. When the cooling tower is shared with the chiller set, the tower reverts to providing only chiller condenser water heat rejection. 2.8.3.4 Heat exchanger design effectiveness
This is the IWSE heat exchanger design effectiveness. This value sets the performance of the IWSE heat exchanger at design conditions. During simulation, this heat exchanger effectiveness is modulated to account for off-design conditionse.g., differing flow conditions or variation in the delta-T across the heat exchanger. 2.8.3.5 Cooling tower
This selection specifies whether the IWSE shares a cooling tower with the chillers set or has its own dedicated cooling tower. At the present, only a shared cooing tower is available. An optional dedicated cooling tower for the IWSE will be available in a subsequent version.
VE 6.4
ApacheHVAC
83
VE 6.4
ApacheHVAC
84
Chiller sequencing example Load range: Chiller A Chiller B Chiller C 20% 1 40% 1 60% 1 2 80% 100% 1 1 1 1 2 Autosizing capacity weighting (%) 40% 40% 20%
In the last column, Chiller autosizing capacity weighting values indicate the relative proportion of the chilled water loop load that each chiller will take during autosizing. This example will size and sequence the chillers in the set as follows: Chillers A and B will each have twice the autosized capacity of Chiller C. At less than 20% of design load, only Chiller C operates. Between 20% and 40% of design load, only Chiller A operates. From 40% to 60% of design load, Chiller C switches in as required to supplement Chiller A. From 60% to 80% of design load, Chillers A and B share the load in proportion to their share of the overall design capacity (indicated in the 100% column). Above 80% of design load, Chillers A and B initially share the load in proportion to their design capacities, with Chiller C switching on to top up as necessary.
In this example, Chiller C is a pony chiller sized for and operated only when loads are either very low or to supplement the two larger chillers. Above 20% of design load (presumably more common conditions), the chillers are sequenced to share the load and ideally also to optimize operating efficiency. Appropriate sequencing will depend upon the particular distribution of hours at any particular load, the part-load performance curves for selected equipment, and the intent of the operating scheme. When the active chillers within a part-load range reach maximum output, the sequencing moves automatically to the next range, until it reaches 100%. The example of three sequenced water-cooled chillers of two sizes shown in Figure 2-35 above, as included with the pre-defined systems, illustrates the intentional setting of load ranges that are offset with respect to the fraction of cooling capacity provided by each chiller in the set. This might be done, for example, to minimize the operation of any chiller Up through version 6.4.0.4, any load in excess of 100% will be met by the combination of all chillers active in the 100% column with operating performance held constant with respect to part-load curves. However, as of version 6.4.0.5, if the full load cannot not be met with all chillers operating a maximum output under the current outdoor conditions, etc., then the load will be underservedi.e., the supply water temperature will be warmer than the specified setpoint for this value.
VE 6.4
ApacheHVAC
85
2.8.4.1
Selection made in this combo list determines the model type of the chiller to be added by clicking the chiller Add button. Currently three model types are available: part load curve chiller, electric water-cooled chiller or electric air-cooled chiller. The chiller set can include any number of chillers or similar cooling sources defined using one of three models, and the set can include any combination of the three different model types: electric water-cooled chiller (uses editable pre-defined curves and other standard inputs) electric air-cooled chiller (uses editable pre-defined curves and other standard inputs) part-load-curve chiller (flexible generic inputs; can represent any device used to cool water via a matrix of load-dependent data for COP and associated usage of pumps, heat-rejection fans, etc., with the option of adding COP values for up to four outdoor DBT or WBT conditions)
2.8.4.2
Chiller List
The chiller list column lists the chillers and similar cooling sources in the chiller set for the current chilled water loop. To open the edit dialog for that chiller, double-click a chiller name on the list or select a chiller and click the Edit button. 2.8.4.3 Chiller Type
The chiller type column lists the types of the chillers defined for the chilled water loop. The chiller types are determined automatically by the program depending on the chiller model type selection when the chillers are added. Currently there are three chiller model types available: part load curve chiller, electric Water-cooled chiller, and electric air-cooled chiller. 2.8.4.4 Part Load Range (up to %)
The part load range (%) values can be edited, with the exception of the end value (100%). Part load range values must always be non-decreasing from left to right. The number of part load ranges is currently limited to a maximum of 5. 2.8.4.5 Chiller Sequence Rank
Chiller sequence ranks are entered in the body of the table, for each chiller and for each part load range. These are integers in the range (0, 99) defining the order in which the chillers will be sequenced during simulation. Within a specific part load range, chillers with lower sequence rank will be sequenced in first. At least one chiller should have a nonzero sequencing rank in every column. When multiple chillers are specified to have the same sequence rank for a part load range, the chillers will be sequenced in together in that part load range, and will share the loop load in proportion to their design capacities. Within any range (except the last), if all the specified chillers are operating at maximum output, it is automatically moved to the next range. For version 6.3, the cooling capacity of chillers is used to determine the top end of the performance curves (scaling the curves accordingly), but does not constrain output: any load exceeding the total available capacity at 100% of the design sizing cooling load will be met by the equipment sequenced ON in the 100% column using the performance values associated with the closest available point on the curves. In other words, the performance under a given set of conditions will be held constant as the
VE 6.4 ApacheHVAC 86
capacity exceed the maximum that was determined or set for sizing purposes. In this context, constrain of capacity is determined at the cooling coil or chilled ceiling. However, in subsequent versions the capacity of chillers and similar cooling sources can be constrained, such that the cooling devices served by them can be modeled as collectively falling short of addressing the total of all coincident loads. This is useful in modeling low energy systems, such as cooling systems with a cooling tower by no chiller, designed to be just capable of meeting the full load under particular design conditions, but not all anticipated conditions. 2.8.4.6 Chiller Autosizing Capacity Weighting
Chiller autosizing capacity weighting is a column of values indicating the relative proportion of the load that each chiller will take during autosizing. If the rightmost sequence rank is zero for any chiller, the corresponding autosizing capacity weighting will be set automatically to zero. Any chiller with a zero autosizing capacity weighting will not be autosized. The Distribute as % button normalizes the autosizing capacity weightings so that they sum to 100. When all the autosizing weightings are zero the Distribute as % button will be disabled. It is not obligatory to use the Distribute as % button as the values will be normalized automatically when applied. 2.8.4.7 Active Sequence Columns
Under each part load range column of the chiller sequencing table (except the 100% column), there is a checkbox indicating the current status of the column. These checkboxes can only be ticked in the order of right to left, and un-ticked from left to right. For a new chilled water loop, the first 3 checkboxes (under the 1st three columns from the left) are initially grayed out and the checkbox immediately to the left of the rightmost part load range column (the 4th one) will have an enabled state. When a check box is ticked, it will populate the column immediately above it with the data from the column to the right of it, thereby rendering the column immediately above it editable. Furthermore, a checkbox under a column to the left of this checkbox will be enabled simultaneously.
If the outdoor conditions exceed the design condition, with the heat-rejection device is fully loaded, including any oversizing factor applied when sizing the associated chiller(s), the return water from the tower back to the condenser will be warmer than the design condition and the chiller model will account for this in terms of both chiller capacity and energy consumption. If the cooling tower uses a single- or two-speed fan, results for energy consumption may still appear to vary with time, as an on/off cycling ratio will be applied to the fan power for the fan speed that is in use.
Figure 2-36: Heat rejection tab in the Chilled water loop dialog with the heat rejection device set to cooling tower.
VE 6.4 ApacheHVAC 88
2.8.5.1
Enter the design outdoor dry-bulb temperature. This parameter is autosizable. When this parameter is autosized, its value in the field and its autosizing label A become green. 2.8.5.2 Design Outdoor Wet-bulb Temperature
Enter the design outdoor wet-bulb temperature for the cooling tower. This parameter is autosizable. When this parameter is autosized, its value in the field and its autosizing label A become green. 2.8.5.3 Use Condenser Water Loop (Water-cooled)?
When this checkbox is not ticked, which is the default, all parameters regarding the condenser water loop are inactive. When this checkbox is ticked, all of the parameters for the condenser water loop become active. Currently, if this box is ticked, there must be at least one Electric Water-cooled (EW) chiller defined for the chilled water loop. 2.8.5.4 Design Condenser Entering Water Temperature, Tectdes
Enter the design condenser entering water temperature. This design value should not be confused with the set point value below. The design value is the entering CW temperature at the design condition. 2.8.5.5 Design Condenser Water Temperature Difference Tcdes
Enter the design condenser water temperature differenceT cdes (the difference between the condenser water leaving and entering temperatures at the design condition). 2.8.5.6 Entering Condenser Water Temperature Set Point
Entering condenser water temperature set point can be constant or set according to an absolute profile. The setpoint is often different from the design value at which capacity is determined. When the condenser water temperature set point is fixed, the cooling tower serving the condenser is controlled in an attempt to simply maintain a constant condenser water supply temperature (as limited by tower performance under off-design operating conditions). This can be seen as a more traditional or conventional control. The absolute profile option allows the flexibility of using other control strategies for the cooling tower. For example, it may be desirable to control the tower to maintain a constant difference between the condenser water supply temperature and the ambient wet bulb temperature (i.e., constant approach). The formula below is an example of using a ramp function to maintain a constant 8 F approach: ramp(twb, 30, 38, 90, 98) This sets CW temperature to 38 F when Outdoor wet-bulb temperature (twb) is 30 F and 98 F when Outdoor wet-bulb temperature (twb) is 90 F, with linear interpolation between these values. The upper and lower bounds should be set to reflect actual cooling tower performance and controls. 2.8.5.7 Condenser Water Specific Pump Power at Rated Speed
Enter the condenser water specific pump power at rated speed, expressed in W/(l/s) in SI units (or W/gpm in IP units).
VE 6.4
ApacheHVAC
89
Condenser water pump power will be calculated on the basis of constant flow (whenever the chiller operates). The model will be based on a specific pump power parameter, with a default value of 19 W/gpm as specified in ASHRAE 90.1 G3.1.3.11. The condenser water loop flow rate will be calculated from values of condenser water heat rejection load and condenser water temperature range through the condenser at the design condition. 2.8.5.8 Condenser Water Pump Heat Gain to Condenser Water Loop (fraction)
Enter the condenser water pump heat gain to the condenser water loop, which is the fraction of the pump motor power that ends up in the condenser water. Its value is multiplied by the condenser water pump power to get the condenser water pump heat gain, which is added to the heat rejection load of the cooling tower. (Condenser water pump is assumed to be on the supply side of the cooling tower.) 2.8.5.9 Condenser Heat Recovery (%)
This is the percentage of the heat rejected to the condenser water loop that can be recovered to a heat source circuit. You can specify any Condenser Heat Recovery (CHR) percentage between 0% and 100%. When the specified CHR percentage is non-zero, it is also necessary to specify the CHR Recipient, which is the heat source circuit that receives the recovered heat. If heat recovery from the chiller condenser circuit is not required, leave the CHR percentage as zero and the CHR Recipient will be grayed out. The amount of heat recovered at any given time is given by:
Heat Recovered =
(Ql + Qc ) p 100
Where, Ql is the load on the chilled water loop, Qc is the compressor power and p is percentage recovery. 2.8.5.10 Condenser Heat Recovery Recipient
This is the heat source circuit that receives the condenser heat recovered from the chiller condenser circuit. When the specified CHR percentage (see above) is non-zero, this parameter is active and needs to be specified. Choices available in the drop-down list will be the heat source circuits that have been defined in the system. If heat recovery from the chiller condenser circuit is not required, leave the CHR percentage as zero and the CHR Recipient will be grayed out. If one heat source circuit is specified to be the recipient of condenser heat recovery from multiple chiller condenser circuits, the condenser heat recovered from those chiller condenser circuits will be accumulated for this heat source circuit. 2.8.5.11 Heat rejection device
Select from the available options for heat rejection devices. Presently, these include an open cooling tower model or a closed-circuit fluid cooler. The open cooling tower model here is based on the Merkel theory, which is same as that used for the Dedicated waterside economizer component (see that section of the User Guide for details). The fluid cooler can be either wet, dry, or switch from wet to dry operation when outdoor temperature drops below a set threshold. The fields and their labels visible when the Cooling tower option is selected are described immediately below. Changing the selection to Fluid cooler replaces these input fields with a set specific to the Fluid cooler parameters (described following the cooling tower inputs).
VE 6.4
ApacheHVAC
90
2.8.5.12
This is the difference between the cooling tower leaving water temperature (T2) and the outdoor wetbulb temperature (towb) at the design condition. The design approach of the cooling tower is derived by the program using the provided condenser water loop design data and condenser water pump data on the Heat rejection tab, and does not need to be specified. 2.8.5.13 Cooling Tower Design Range
This is the difference between the cooling tower entering water temperature (T1) and the cooling tower leaving water temperature (T2) at the design condition. The design range of the cooling tower is derived by the program using the provided condenser water loop design temperature difference (delta-T c des) and condenser water pump data, and does not need to be specified. 2.8.5.14 Cooling Tower Design Heat Rejection, Qhrdes
This is the heat rejection load on the cooling tower at design condition. The design heat rejection load of the cooling tower is automatically derived by the program using the provided chilled water loop design data and condenser water pump data, and does not need to be specified. 2.8.5.15 Cooling Tower Fan Power, Wfan
Enter the power consumption of the cooling tower fan when running at full speed. 2.8.5.16 Cooling Tower Fan Electric Input Ratio, Wfan/Qhrdes
This is the ratio between the design fan power consumption and the design heat rejection load of the cooling tower. It is automatically derived by the program using the provided cooling tower fan power and the derived cooling tower design heat rejection load, and does not need to be specified. 2.8.5.17 Cooling Tower Fan control
Select the fan control type of the cooling tower. Three types of fan control are available: One-speed fan, Two-speed fan and VSD fan. When Two-speed fan is selected, you also need to specify two more parameters (see below): Low-speed fan flow fraction and Low-speed fan power fraction. 2.8.5.18 Cooling Tower Low-speed Fan Flow Fraction
Enter the fraction of the design flow that the cooling tower fan delivers when running at low speed. This parameter only needs to be specified when Fan control type is selected as Two-speed fan. 2.8.5.19 Cooling Tower Low-speed Fan Power Fraction
Enter the power consumed by the cooling tower fan when running at low speed, expressed as a fraction of the cooling tower design fan power. This parameter needs only to be specified when Fan control type is selected as Two-speed fan. Generally, the low-speed power fraction will be a lesser value than the lowspeed flow fraction. For example, if the low-speed flow fraction were 0.50, the low-speed power fraction would typically (depending on fan curves, motor performance, etc.) be on the order of 0.30.
VE 6.4
ApacheHVAC
91
Figure 2-37: Fluid Cooler option selected for Heat rejection device on the Heat rejection tab of the Chilled water loop dialog.
VE 6.4
ApacheHVAC
92
2.8.5.20
There are two types of a fluid cooler, categorised by the wetting conditions on the surface of the coil. A dry fluid cooler is one where the coil is permanently dryi.e., evaporative cooling is not included. This type of cooler tends to be used in areas where there are restrictions on the availability of water or where ambient conditions are particularly well suited to a dry cooler. A wet/dry fluid cooler is one where the coil is sprayed with water to provide indirect evaporative cooling. To prevent freezing of water on the coil and/or to make the most of cool conditions, the spray pump can be switched off at low outdoor temperatures. Under these conditions the cooler operates with a dry coil. This radio button group allows the type of fluid cooler to be selected. 2.8.5.21 Fluid Cooler Outdoor Temperature Wet/Dry Mode Switch
When a wet/dry fluid cooler has been selected this value is used to define the temperature at which the mode of the fluid cooler changes. When the outdoor dry-bulb temperature falls below the value specified, the fluid cooler will run in dry mode, the spray pump is turned off and the coil will be dry. When the outdoor dry-bulb temperature is above the value set, the spray pump will be in operation and the coil will be wet (evaporatively cooled). 2.8.5.22 Fluid Cooler Design Approach
When the fluid cooler is operating in wet/dry mode, this is the difference between the fluid cooler leaving water temperature (T2) and the outdoor wet-bulb temperature (towb) at the design condition. In dry mode, this value is the difference between the leaving water temperature (T2) and the outdoor dry-bulb temperature (todb) at the design condition. The design approach of the fluid cooler is automatically derived by the program using the provided chilled water loop design data and condenser water pump data, and does not need to be specified. 2.8.5.23 Fluid Cooler Design Range
This is the difference between the fluid cooler entering water temperature (T1) and the fluid cooler leaving water temperature (T2) at the design condition. The design range of the fluid cooler is automatically derived by the program using the provided chilled water loop design data and condenser water pump data. It does not need to be specified. 2.8.5.24 Fluid Cooler T
For the fluid cooler in wet/dry mode, this is the difference between the fluid cooler exiting wet-bulb air temperature and entering wet-bulb air temperature. In dry mode this is the difference between the exiting dry-bulb air temperature and the entering dry-bulb air temperature.
2.8.5.25
This is the heat rejection load on the fluid cooler at design condition. The design heat rejection load of the fluid cooler is automatically derived by the program using the provided chilled water loop design data and condenser water pump data, and does not need to be specified. 2.8.5.26 Fluid Cooler Fan Power, Wfan
The power consumption of the fluid cooler fan when running at full speed.
VE 6.4
ApacheHVAC
93
2.8.5.27
This is the ratio between the design fan power consumption and the design heat rejection load of the fluid cooler. It is automatically derived by the program using the provided fluid cooler fan power and the derived fluid cooler design heat rejection load. It does not need to be specified. 2.8.5.28 Fluid Cooler Fan control
Select the fan control type of the cooling tower. Three types of fan control are available: One-speed fan, Two-speed fan, and variable-speed (VSD) fan. When Two-speed fan is selected, you must also specify two additional parameters (see below): Low-speed fan flow fraction and Low-speed fan power fraction. 2.8.5.29 Fluid Cooler Low-speed Fan Flow Fraction
Enter the fraction of the design flow that the fluid cooler fan delivers when running at low speed. This parameter only needs to be specified when Fan control type is selected as Two-speed fan. 2.8.5.30 Fluid Cooler Low-speed Fan Power Fraction
Enter the power consumed by the fluid cooler fan when running at low speed, expressed as a fraction of the fluid cooler design fan power. This parameter needs only to be specified when Fan control type is selected as Two-speed fan. Generally, given the physics of fan performance, the low-speed fan-power fraction will be a relatively lesser value than the low-speed flow fraction. For example, if the low-speed flow fraction were 0.50, the low-speed power fraction would typically (depending on fan curves, motor performance, etc.) be on the order of 0.30. 2.8.5.31 Fluid Cooler Spray Power, Wpump
Enter the power consumption of the fluid cooler spray pump. This input needs only to be specified for a wet/dry fluid cooler. 2.8.5.32 Fluid Cooler Spray Pump Electric Input Ratio, Wpump/Qhrdes
This is the ratio between the fluid cooler pump power consumption and the design heat rejection load of the fluid cooler. It is automatically derived by the program using the provided fluid cooler spray pump power and the derived fluid cooler design heat rejection load. It does not need to be specified.
VE 6.4
ApacheHVAC
94
Figure 2-38: Chiller set tab of Chiller water loop dialog shown with two sequenced Part-load curve chiller models and current type to add set to part load curve.
VE 6.4
ApacheHVAC
95
VE 6.4
ApacheHVAC
96
Figure 2-39: Part load curve chiller editing dialog showing an illustrative example for which the cooling tower fan and condenser-water pump power are embedded in the COP values for each range of load and outdoor wet-bulb temperature and condenser heat recovery is also used. Important notes: All pump and/or fan power entered in the part load curve chiller dialog is independent of the loop pump and cooling tower energy calculated according to parameters set in the associated chilled water loop dialogi.e., pump power and heat-rejection fan power entered in the part load curve chiller dialog is in addition to that calculated based on similar parameters in the chilled water loop dialog.
VE 6.4
ApacheHVAC
97
Figure 2-40: Part load curve chiller editing dialog showing tick box for absorption chiller and associated selection of a driving heat source in place of fuel code or electricity. 2.9.1.1 Reference
Enter a description of the component. It is for your use when selecting, organizing, and referencing any component or controllers within other component and controller dialogs and in the component browser tree. These references can be valuable in organizing and navigating the system and when the system model is later re-used on another project or passed on to another modeler. Reference names should thus be informative with respect to differentiating similar equipment, components, and controllers. 2.9.1.2 Fuel
The energy source used by the chiller compressor. For the electric chillers, this should be either the more generic Electricity source or Cooling, which is an electrical end-use designation that is mapped to Cooling electricity in the reports for the ASHRAE 90.1 Performance Rating Method (see section 8: PreDefined Prototype HVAC Systems and the separate user guide for the PRM Navigator). When the Absorption Chiller? box is ticked, the Fuel selection will be replaced with a Heat source selection. 2.9.1.3 Absorption Chiller?
The part load curve chiller can be used to model an absorption chiller. To enable this option, tick the Absorption Chiller? checkbox. The Condenser Heat Recovery (%) parameter is then removed and the Fuel selection is replaced with the absorption chiller Heat source selection. The required energy input to the absorption chiller will be passed as load to the designated heat source. 2.9.1.4 Heat source
When the Absorption Chiller? checkbox is ticked, the Fuel selection is replaced with the absorption chiller Heat source selection. You need to select the heat source for the absorption chiller in this case. The required energy input to the absorption chiller will be passed as load to the designated heat source.
This is the percentage of the rejected heat that can be recovered to a heat source circuit. You can specify any Condenser Heat Recovery percentage between 0% and 100%. When the specified CHR percentage is non-zero, it is also necessary to specify the CHR Recipient (see below), which will be the heat source circuit that receives the recovered heat. If heat recovery from the chiller condenser circuit is not required, leave the CHR percentage as zero and the CHR Recipient combobox will be replaced with the Absorption Chiller? checkbox (see below).
VE 6.4
ApacheHVAC
98
Heat Recovered =
(Ql + Qc ) p 100
Where, Ql is the load on the chiller, Qc is the compressor power and p is percentage recovery. The Condenser Heat Recovery (%) parameter is hidden when the Absorption Chiller? checkbox is ticked. Condenser heat recovery is not available when modeling an absorption chiller. 2.9.2.2 Condenser Heat Recovery Recipient
This is the heat source circuit or loop that receives the recovered condenser heat. When the specified CHR percentage is set to a non-zero value, this parameter replaces the Absorption Chiller? checkbox and must then be specified. The drop-down list allows selection of heat sources or hot water loops that have been defined in the system. If heat recovery from the condenser is not required, leave the CHR percentage set to zero; CHR Recipient selection will be replaced by the Absorption Chiller? checkbox. If multiple chillers reference one heat source circuit as the recipient of condenser heat recovery, the heat recovered from those chillers will be accumulated for this heat source circuit or hot water loop.
Enter the maximum rate of electrical consumption of the chilled water circulation pumps. These are assumed to operate whenever there is a demand for chilled water from this cooling source. Pump power can be varied with cooling load by entering percentage values in the table of part-load performance data. The maximum power input for chilled water pumps is a generic input that could represent any electrical device with either constant power or power varying with cooling load; however, the energy consumed in this case with be reported in the distribution pumps category.
Warning Limits (kW) Error Limits (kW) 0.0 to 15.0 0.0 to 9999.0
2.9.3.2
Enter the maximum rate of electrical consumption of the condenser water pumps. These are assumed to operate whenever there is a demand for chilled water from this cooling source. Pump power can be varied with cooling load by entering percentage values in the table of part-load performance data. The input for condenser water pumps could be used to represent any powered heat-rejection device with either constant power or power varying with cooling load; the energy consumed in this case with be reported in the heat-rejection fans/pumps.
Warning Limits (kW) Error Limits (kW) 0.0 to 15.0 0.0 to 9999.0
VE 6.4
ApacheHVAC
99
2.9.3.3
Enter the maximum rate of electrical consumption of the cooling tower or condenser fans. These are assumed to operate whenever there is a demand for chilled water from this cooling source. Fan power can be varied with cooling load by entering percentage values in the table of part-load performance data.
Warning Limits (kW) Error Limits (kW) 0.0 to 15.0 0.0 to 9999.0
Use the drop-down selector to indicate if you will be entering temperature dependent COP values and whether these will be associated with outdoor dry-bulb or wet-bulb temperatures. 2.9.4.2 Number of Temperature Dependent COPs
Use the drop-down selector to indicate if you will be entering COP values for 1, 2, 3, or 4 outdoor dry-bulb or wet-bulb temperatures. 2.9.4.3 Temperatures T1 T4 for Temperature Dependent COPs
Enter 1 to 4 outdoor dry-bulb or wet-bulb temperatures for which you intend to include Temperature Dependent COPs in the performance table below.
Enter the chiller output and part-load values in kW or kBtu/h as appropriate. The output values must be entered in ascending order (for example, starting with 100 at the first or top row and ending with 900 at the bottom) so that all values will be used. Up to twenty data points (rows in the data table or matrix) may be used to define the variation of performance with part-load. Enter the points in ascending order of part-load. Use the Add, Insert, and Remove buttons at the bottom to change the number of rows in the data table.
Warning Limits (kW) Error Limits (kW) 0.0 to 2000.0 0.0 to 99999.0
2.9.5.2
Enter the percentage use of the chilled water distribution pumps that coincides with the output specified in Chiller Part-Load Output.
Warning Limits (%) Error Limits (%) 0.0 to 100.0 0.0 to 100.0
VE 6.4
ApacheHVAC
100
2.9.5.3
Enter the percentage use of the condenser water pumps that coincides with the output specified in Chiller Part-Load Output.
Warning Limits (%) Error Limits (%) 0.0 to 100.0 0.0 to 100.0
2.9.5.4
Enter the percentage use of the cooling tower or condenser fans which coincides with the output specified in Chiller Part-Load Output.
Warning Limits (%) Error Limits (%) 0.0 to 100.0 0.0 to 100.0
2.9.5.5
Enter the coefficient of performance associated with the part-load output value on each row. If you have selected options above and entered DBT or WBT values for temperature dependence of the COPs, enter the COP values associated with each temperature (T1 T4) in the appropriate columns.
Warning Limits (kW) Error Limits (kW) 0.8 to 5.0 0.25 to 10.0
VE 6.4
ApacheHVAC
101
Enter a description of the component. Reference names should be informative with respect to differentiating similar equipment. It is for your use when selecting, organizing, and referencing any equipment within other component and controller dialogs and in the component browser tree. These references can be valuable in organizing and navigating the system and when the system model is later re-used on another project or passed on to another modeler. 2.10.1.2 Fuel
Select the fuel or energy source used by the chiller compressor to determine the category for reporting energy consumption results. For scratch-built system models, this should normally be set to Electricity for the electric chillers. It will be pre-set to Cooling as an energy end-use category (consistent with LEED EA credit 1 submittal requirements) when working with the pre-defined prototype ApacheHVAC systems, as provided by the Prototype Systems Library, System Prototypes & Sizing facility, or the ASHRAE 90.1 PRM workflow navigator.
VE 6.4
ApacheHVAC
102
VE 6.4
ApacheHVAC
103
Clicking this button provides a summary of the electric water-cooled chiller model variables as shown below:
Figure 2-42: Electric water-cooled chiller model description 2.10.2.2 Rated Condition is Design Condition
When this box is ticked, the rated condition data (see details in the Rated condition sub-tab) is a read-only copy of the current design condition data (see details in the Design condition sub-tab), including any unsaved edits you have made. 2.10.2.3 Cooling Capacity Curve, fCAPtt(Tlet,Tect)
This field indicates the currently selected performance curve for chiller capacity as a function of leaving evaporator temperature and entering condenser temperature for a particular chiller equipment type. Use the Select button to choose the appropriate curve from the system database.
VE 6.4
ApacheHVAC
104
Figure 2-43: Electric water-cooled chiller dialog showing drop-down selection for cooling capacity curve. 2.10.2.4 Edit Cooling Capacity Curve, fCAPtt(Tlet,Tect)
The Edit button opens a dialog displaying the formula and parameters of the curve, allowing the curve parameters to be edited, if needed. However, this is recommended for advanced users only and requires both sufficient data from a manufacturer and an appropriate tool, such as MatLab, for generating the proper fit curve coefficients. For most users, selecting a representative curve for the chiller type and then entering appropriate performance characteristics (COP, cooling capacity, supply temperature, etc.) in the rated and design conditions tabs will be most appropriate.
VE 6.4
ApacheHVAC
105
When editing the curve parameters, it is important that you understand the meaning of the curve and its usage in the model algorithm. The edited curve should have reasonable ranges for the independent variables, as a given performance curve is only valid within its applicable ranges. If the independent variables are out of the set applicable ranges, the variable limits (maximum or minimum) specified in the input dialog will be applied.
Figure 2-44: Edit dialog for the cooling capacity curve of electric water-cooled chiller The cooling capacity curve fCAPtt(Tlet, Tect) is a bi-quadratic function of tlet = Tlet Tdatum tect = Tect Tdatum where Tect = entering condenser water temperature. Tlet = chilled water supply (leaving evaporator) temperature.
VE 6.4
ApacheHVAC
106
Tdatum = datum temperature (0C or 0F), introduced for the convenience of units conversion of the curve coefficients. And: fCAPtt(Tlet, Tect) = (C00 + C10 tlet + C20 tlet2 + C01 tect + C02 tect2 + C11 tlet tect) / Cnorm where C00, C10, C20, C01, C02 and C11 are the curve coefficients Cnorm is adjusted (by the program) to make fCAPtt(Tletrat, Tectrat) = 1 Tectrat = rated entering condenser water temperature. Tletrat = rated chilled water supply (leaving evaporator) temperature. The cooling capacity curve is evaluated at each iteration of the chiller performance, for each time step during the simulation. The curve value is multiplied by the rated cooling capacity (Qrat) to get the available (full-load) cooling capacity (Qcap) of the current time step, for the specific Tect and Tlet temperatures: Qcap = Qrat fCAPtt(Tlet,Tect) The curve should have a value of 1.0 when the temperatures are at rated conditions. 2.10.2.5 EIR (Water Temp Dependence) Curve, fEIRtt(Tlet,Tect)
This field indicates the currently selected performance curve for chiller Electric Input Ratio (EIR) as a function of leaving evaporator temperature and entering condenser temperature for a particular chiller type. Use the Select button to choose the appropriate curve from the system database. 2.10.2.6 Edit EIR (Water Temp Dependence) Curve, fEIRtt(Tlet,Tect)
The Edit button opens a dialog displaying the formula and parameters of the curve, allowing the curve parameters to be edited, if needed. However, this is recommended for advanced users only and requires both sufficient data from a manufacturer and an appropriate tool, such as MatLab, for generating the proper fit curve coefficients. For most users, selecting a representative curve for the chiller type and then entering appropriate performance characteristics (COP, cooling capacity, supply temperature, etc.) in the rated and design conditions tabs will be most appropriate. When editing the curve parameters, it is important that you understand the meaning of the curve and its usage in the model algorithm. The edited curve should have reasonable ranges for the independent variables, as a given performance curve is only valid within its applicable ranges. If the independent variables are out of the set applicable ranges, the variable limits (maximum or minimum) specified in the input dialog will be applied.
VE 6.4
ApacheHVAC
107
Figure 2-45: Edit dialog for the EIR (water temperature dependence) curve of electric water cooled chiller The chiller EIR (water temperature dependence) curve fEIRtt(Tlet, Tect) is a bi-quadratic function of tlet = Tlet Tdatum tect = Tect Tdatum where Tect = entering condenser water temperature. Tlet = chilled water supply (leaving evaporator) temperature. Tdatum = datum temperature (0C or 0F), introduced for the convenience of units conversion of the curve coefficients. And: fEIRtt(Tlet, Tect) = (C00 + C10 tlet + C20 tlet2 + C01 tect + C02 tect2 + C11 tlet tect) / Cnorm
VE 6.4
ApacheHVAC
108
where C00, C10, C20, C01, C02 and C11 are the curve coefficients Cnorm is adjusted (by the program) to make fEIRtt(Tletrat, Tectrat) = 1 Tectrat = rated entering condenser water temperature. Tletrat = rated chilled water supply (leaving evaporator) temperature. The chiller EIR (water temperature dependence) curve is evaluated for each iteration of the chiller performance, for each time step during the simulation. The curve value is multiplied by the rated EIR (= 1/ COPrat, where COPrat is the rated coefficient of performance) to get the full-load EIR of the current time step, for the specific Tect and Tlet temperatures. The curve should have a value of 1.0 when the temperatures are at rated conditions. 2.10.2.7 EIR (Part-load and water temperature dependence) curve, fEIRpt(p,TectTlet)
This field indicates the chiller Electric Input Ratio (EIR) part-load dependence curve currently selected. This is the performance curve for chiller Electric Input Ratio (EIR) as a function of part-load fraction, entering condenser temperature, and leaving evaporator temperature for a particular chiller type. Use the Select button to choose the appropriate curve from the system database. 2.10.2.8 Edit EIR (Part-load and water temperature dependence) curve, fEIRpt(p,TectTlet)
The Edit button opens a dialog displaying the formula and parameters of the curve, allowing the curve parameters to be edited, if needed. However, this is recommended for advanced users only and requires both sufficient data from a manufacturer and an appropriate tool, such as MatLab, for generating the proper fit curve coefficients. For most users, selecting a representative curve for the chiller type and then entering appropriate performance characteristics (COP, cooling capacity, supply temperature, etc.) in the rated and design conditions tabs will be most appropriate. When editing the curve parameters, it is important that you understand the meaning of the curve and its usage in the model algorithm. The edited curve should have reasonable ranges for the independent variables, as a given performance curve is only valid within its applicable ranges. If the independent variables are out of the set applicable ranges, the variable limits (maximum or minimum) specified in the input dialog will be applied.
VE 6.4
ApacheHVAC
109
Figure 2-46: Edit dialog for the EIR (part-load and water temperature dependence) curve of electric watercooled chiller The chiller EIR (part-load and water temperature dependence) curve fEIRpt(p,t) is a bi-quadratic function of p = Q/Qcap t = TectTlet where p = part-load fraction Q = cooling load Qcap = available (full-load) cooling capacity Tect = entering condenser water temperature. Tlet = chilled water supply (leaving evaporator) temperature.
VE 6.4
ApacheHVAC
110
And: f EIRpt(p,t) = (C00 + C10 p + C20 p2 + C01 t + C02 t2 + C11 p t) / Cnorm where C00, C10, C20, C01, C02 and C11 are the curve coefficients, Cnorm is adjusted (by the program) to make fEIRpt(1, TectratTletrat) = 1 Tectrat = rated entering condenser water temperature. Tletrat = rated chilled water supply (leaving evaporator) temperature. The chiller EIR (part-load and water temperature dependence) curve is evaluated in each iteration of the chiller performance, for each time step during the simulation. The curve value is multiplied by the rated EIR (= 1/ COPrat, where COPrat is the rated coefficient of performance) and the EIR (water temperature dependence) curve value to get the EIR of the current time step, for the specific Tect and Tlet temperatures and the specific part load ratio at which the chiller is operating: EIR = fEIRtt(Tlet,Tect) fEIRpt(p, TectTlet) / (pCOPrat) The curve should have a value of 1.0 when the part load ratio equals 1.0 and the temperatures are at rated conditions. A note on the applicable range of part-load ratio p: The minimum p is used by the program as the minimum unloading ratio, where the chiller capacity can no longer be reduced by normal unloading mechanism and the chiller must be false loaded to meet smaller cooling loads. A typical false loading strategy is hot-gas bypass. If this is the false loading strategy used by the chiller, the minimum p is the part load ratio at which hot gas bypass starts. The maximum p should usually be 1.0. During the simulation, a part-load ratio greater than 1.0 is a sign of chiller undersizing. 2.10.2.9 Minimum Part-load Ratio for Continuous Operation
This is the minimum part-load ratio at which the chiller can operate continuously. When the part-load ratio is below this point, the chiller will cycle on and off. 2.10.2.10 Compressor Heat Gain to Chilled Water Loop (fraction) This is the fraction of compressor electric energy consumption that must be rejected by the condenser. Heat rejected by the chiller condenser includes the heat transferred in the evaporator plus a portion or all of the compressor energy consumption. For electric chillers with hermetic compressors, all compressor energy consumption is rejected by the condenser, so the compressor heat gain factor should be 1.0. For chillers with semi-hermetic or open compressors, only a portion of the compressor energy used is rejected by the condenser, so the compressor heat gain factor should be less than 1.0.
VE 6.4
ApacheHVAC
111
Figure 2-47: Electric water-cooled chiller dialog showing design condition tab when Rated condition is Design condition tick box is ticked. When this is un-ticked, the inputs for Cooling capacity and COP are no longer edited here, but are editable in the Rated condition tab.
VE 6.4
ApacheHVAC
112
2.10.3.1
The design entering condenser water temperature is specified in the associated chilled water loop dialog (in the Heat rejection tab) and is displayed here as a derived parameter. 2.10.3.2 Condenser Water Flow Rate, Vc, Vc/Qdes, Tcdes
Vc, Vc/Qdes, and Tcdes represent three different possible means of specifying design condenser water flow rate. Currently, it is specified in terms of cdes (the difference between the design condenser water T leaving and entering temperatures). This temperature difference is specified in the Heat rejection tab of associated chilled water loop dialog and the design condenser-water flow rate is then displayed in the chiller dialog as a derived parameter. As such, condenser-water flow rate (Vc) and the ratio between design condenser water flow rate (Vc) and design cooling capacity (Qdes) or Vc/Qdes are derived by the program based on the specified Tcdes and cannot be directly edited. 2.10.3.3 Chilled Water Supply Temperature, Tletdes
The design chilled water supply temperature (leaving evaporator water temperature) is specified in the associated chilled water loop dialog (in the Chilled water loop tab) and is displayed here as a derived parameter. 2.10.3.4 Chilled Water Flow Rate, Ve, Ve/Qdes, Tedes
Ve, Ve/Qdes and Tedes are three different options for specifying design chilled water flow rate. Currently it is specified in terms of T edes (the difference between the design chilled water return and supply temperatures). It is specified in the associated chilled water loop dialog (in the Chilled water loop tab) and is displayed here as a derived parameter. The other two options (Ve and Ve/Qdes (the ratio between design chilled water flow rate (Ve) and design cooling capacity (Qdes).) are automatically derived by the program based on the specified Tedes and cannot be edited. 2.10.3.5 Cooling Capacity, Qdes
When Rated condition is design condition is not ticked, the design cooling capacity is automatically derived by the program using other design and rated condition data provided and does not need to be edited. When Rated condition is design condition is ticked, enter the design cooling capacity. This parameter is autosizable. When this parameter is autosized, its value in the field and its autosizing label A become green. 2.10.3.6 Coefficient of Performance, COPdes
When Rated condition is design condition is not ticked, the design coefficient of performance is automatically derived by the program using other design and rated condition data provided and does not need to be edited. When Rated condition is design condition is ticked, enter the design coefficient of performance.
VE 6.4
ApacheHVAC
113
VE 6.4
ApacheHVAC
114
Figure 2-48: Electric water-cooled chiller dialog showing Rated condition tab when Rated condition is Design condition tick box is not ticked. The white fields in the Rated condition tab are editable when not set equal to the design conditions.
VE 6.4
ApacheHVAC
115
2.10.4.1
When Rated condition is design condition is ticked, the rated entering condenser water temperature is a dynamic copy of the design entering condenser water temperature. When Rated condition is design condition is not ticked, enter the rated entering condenser water temperature. 2.10.4.2 Condenser Water Flow Rate, Vcrat, Vcrat/Qrat, Tcrat
Vcrat, Vcrat/Qrat, and T crat are three different options for specifying rated condenser water flow rate. Currently it is specified in terms of the ratio between rated condenser water flow rate (Vcrat) and rated cooling capacity (Qrat). The other two options (Vcrat and T crat (the difference between the rated condenser water leaving and entering temperatures)) are automatically derived by the program based on the specified Vcrat/Qrat and cannot be edited. When Rated condition is design condition is ticked, the rated condenser water flow rate is a dynamic copy of the design condenser water flow rate. When Rated condition is design condition is not ticked, enter the rated condenser water flow rate. 2.10.4.3 Chilled Water Supply Temperature, Tletrat
When Rated condition is design condition is ticked, the rated chilled water supply temperature (leaving evaporator water temperature) is a dynamic copy of the design chilled water supply temperature. When Rated condition is design condition is not ticked, enter the rated chilled water supply temperature. 2.10.4.4 Chilled Water Flow Rate, Verat, Verat/Qrat, Terat
Verat, Verat/Qrat, andT erat are three different options for specifying rated chilled water flow rate. Currently it is specified in terms of the ratio between rated chilled water flow rate (Verat) and rated cooling capacity (Qrat). The other two options (Verat and T erat (the difference between the rated chilled water return and supply temperatures)) are automatically derived by the program based on the specified Verat/Qrat and cannot be edited. When Rated condition is design condition is ticked, the rated chilled water flow rate is a dynamic copy of the design chilled water flow rate. When Rated condition is design condition is not ticked, enter the rated chilled water flow rate. 2.10.4.5 Cooling Capacity, Qrat
When Rated condition is design condition is ticked, the rated cooling capacity is a dynamic copy of the design cooling capacity. When Rated condition is design condition is not ticked, enter the rated cooling capacity. 2.10.4.6 Coefficient of Performance, COPrat
When Rated condition is design condition is ticked, the rated coefficient of performance is a dynamic copy of the design coefficient of performance. When Rated condition is design condition is not ticked, enter the rated coefficient of performance.
VE 6.4
ApacheHVAC
116
Energy consumption by condenser fans is included in the chillers Electric Input Ratio (EIR) and associated performance curves. A condenser fan Electric Input Ratio (EIRfan), representing the ratio of condenser fan power consumption to the total chiller power consumption, is used to split the energy consumption calculated by the performance curves into the condenser fan power consumption and chiller compressor energy consumption.
Enter a description of the component. Reference names should be informative with respect to differentiating similar equipment. It is for your use when selecting, organizing, and referencing any equipment within other component and controller dialogs and in the component browser tree. These references can be valuable in organizing and navigating the system and when the system model is later re-used on another project or passed on to another modeler. 2.11.1.2 Fuel
Select the fuel or energy source used by the chiller compressor to determine the category for reporting energy consumption results. For scratch-built system models, this should normally be set to Electricity for the electric chillers. It will be pre-set to Cooling as an energy end-use category (consistent with LEED EA credit 1 submittal requirements) when working with the pre-defined prototype ApacheHVAC systems, as provided by the Prototype Systems Library, System Prototypes & Sizing facility, or the ASHRAE 90.1 PRM workflow navigator.
VE 6.4
ApacheHVAC
117
VE 6.4
ApacheHVAC
118
Clicking this button provides a summary of the electric water-cooled chiller model variables as shown below:
Figure 2-50: Electric air-cooled chiller model description 2.11.2.2 Rated Condition is Design Condition
When this box is ticked, the rated condition data (see details in the Rated condition sub-tab) is a read-only copy of the current design condition data (see details in the Design condition sub-tab), including any unsaved edits you have made. 2.11.2.3 Cooling Capacity Curve, fCAPtt(Tlet,Todb)
This field indicates the currently selected performance curve for chiller capacity as a function of leaving evaporator water temperature and outdoor air dry-bulb temperature for a particular chiller equipment type. Use the Select button to choose the appropriate curve from the system database.
VE 6.4
ApacheHVAC
119
Figure 2-51: Electric air-cooled chiller dialog showing drop-down selection for cooling capacity curve. 2.11.2.4 Edit Cooling Capacity Curve, fCAPtt(Tlet,Todb)
The Edit button opens a dialog displaying the formula and parameters of the curve, allowing the curve parameters to be edited, if needed. However, this is recommended for advanced users only and requires both sufficient data from a manufacturer and an appropriate tool, such as MatLab, for generating the proper fit curve coefficients. For most users, selecting a representative curve for the chiller type and then entering appropriate performance characteristics (COP, cooling capacity, supply temperature, etc.) in the rated and design conditions tabs will be most appropriate.
VE 6.4 ApacheHVAC 120
When editing the curve parameters, it is important that you understand the meaning of the curve and its usage in the model algorithm. The edited curve should have reasonable ranges for the independent variables, as a given performance curve is only valid within its applicable ranges. If the independent variables are out of the set applicable ranges, the variable limits (maximum or minimum) specified in the input dialog will be applied.
Figure 2-52: Edit dialog for the cooling capacity curve of electric air-cooled chiller The cooling capacity curve fCAPtt(Tlet, Todb) is a bi-quadratic function of tlet = Tlet Tdatum todb = Todb Tdatum where Todb = outdoor air dry bulb temperature. Tlet = chilled water supply (leaving evaporator) temperature.
VE 6.4
ApacheHVAC
121
Tdatum = datum temperature (0C or 0F), introduced for the convenience of units conversion of the curve coefficients. And: fCAPtt(Tlet, Todb) = (C00 + C10 tlet + C20 tlet2 + C01 todb + C02 todb 2 + C11 tlet todb) / Cnorm where C00, C10, C20, C01, C02 and C11 are the curve coefficients Cnorm is adjusted (by the program) to make fCAPtt(Tletrat, Todbrat) = 1 Todbrat = rated outdoor air dry bulb temperature. Tletrat = rated chilled water supply (leaving evaporator) temperature. The cooling capacity curve is evaluated at each iteration of the chiller performance, for each time step during the simulation. The curve value is multiplied by the rated cooling capacity (Qrat) to get the available (full-load) cooling capacity (Qcap) of the current time step, for the specific Todb and Tlet temperatures: Qcap = Qrat fCAPtt(Tlet,Todb) The curve should have a value of 1.0 when the temperatures are at rated conditions. 2.11.2.5 EIR (Temp Dependence) Curve, fEIRtt(Tlet,Todb)
This field indicates the currently selected performance curve for chiller Electric Input Ratio (EIR) as a function of leaving evaporator temperature and outdoor dry-bulb temperature (for condenser heat rejection) for a particular chiller type. Use the Select button to choose the appropriate curve from the system database. 2.11.2.6 Edit EIR (Temp Dependence) Curve, fEIRtt(Tlet,Todb)
The Edit button opens a dialog displaying the formula and parameters of the curve, allowing the curve parameters to be edited, if needed. However, this is recommended for advanced users only and requires both sufficient data from a manufacturer and an appropriate tool, such as MatLab, for generating the proper fit curve coefficients. For most users, selecting a representative curve for the chiller type and then entering appropriate performance characteristics (COP, cooling capacity, supply temperature, etc.) in the rated and design conditions tabs will be most appropriate. When editing the curve parameters, it is important that you understand the meaning of the curve and its usage in the model algorithm. The edited curve should have reasonable ranges for the independent variables, as a given performance curve is only valid within its applicable ranges. If the independent variables are out of the set applicable ranges, the variable limits (maximum or minimum) specified in the input dialog will be applied.
VE 6.4
ApacheHVAC
122
Figure 2-53: Edit dialog for the EIR (temperature dependence) curve of electric air cooled chiller The chiller EIR (temperature dependence) curve fEIRtt(Tlet, Todb) is a bi-quadratic function of tlet = Tlet Tdatum todb = Todb Tdatum where Todb = outdoor air dry bulb temperature. Tlet = chilled water supply (leaving evaporator) temperature. Tdatum = datum temperature (0C or 0F), introduced for the convenience of units conversion of the curve coefficients. And: fEIRtt(Tlet, Todb) = (C00 + C10 tlet + C20 tlet2 + C01 todb + C02 todb 2 + C11 tlet todb) / Cnorm
VE 6.4
ApacheHVAC
123
where C00, C10, C20, C01, C02 and C11 are the curve coefficients Cnorm is adjusted (by the program) to make fEIRtt(Tletrat, Todbrat) = 1 Todbrat = rated outdoor air dry bulb temperature. Tletrat = rated chilled water supply (leaving evaporator) temperature. The chiller EIR (temperature dependence) curve is evaluated for each iteration of the chiller performance, for each time step during the simulation. The curve value is multiplied by the rated EIR (= 1/ COPrat, where COPrat is the rated coefficient of performance) to get the full-load EIR of the current time step, for the specific Todb and Tlet temperatures. The curve should have a value of 1.0 when the temperatures are at rated conditions. 2.11.2.7 EIR (Part-load Dependence) curve, fEIRpt(p,TodbTlet)
This field indicates the chiller Electric Input Ratio (EIR) part-load dependence curve currently selected. This is the performance curve for chiller Electric Input Ratio (EIR) as a function of part-load fraction, outdoor dry-bulb air temperature, and supply (leaving evaporator) water temperature for a particular chiller type. Use the Select button to choose the appropriate curve from the database. 2.11.2.8 Edit EIR (Part-load and temperature dependence) curve, fEIRpt(p,TodbTlet)
The Edit button opens a dialog displaying the formula and parameters of the curve, allowing the curve parameters to be edited, if needed. However, this is recommended for advanced users only and requires both sufficient data from a manufacturer and an appropriate tool, such as MatLab, for generating the proper fit curve coefficients. For most users, selecting a representative curve for the chiller type and then entering appropriate performance characteristics (COP, cooling capacity, supply temperature, etc.) in the rated and design conditions tabs will be most appropriate. When editing the curve parameters, it is important that you understand the meaning of the curve and its usage in the model algorithm. The edited curve should have reasonable ranges for the independent variables, as a given performance curve is only valid within its applicable ranges. If the independent variables are out of the set applicable ranges, the variable limits (maximum or minimum) specified in the input dialog will be applied. The chiller EIR (part-load and temperature dependence) curve fEIRpt(p,t) is a bi-quadratic function of p = Q/Qcap t = TodbTlet where p = part-load fraction Q = cooling load Qcap = available (full-load) cooling capacity Todb = outdoor air dry bulb temperature.
VE 6.4 ApacheHVAC 124
Figure 2-54: Edit dialog for the EIR (part-load and temperature dependence) curve of electric air-cooled chiller And: f EIRpt(p,t) = (C00 + C10 p + C20 p2 + C01 t + C02 t2 + C11 p t) / Cnorm where C00, C10, C20, C01, C02 and C11 are the curve coefficients, Cnorm is adjusted (by the program) to make fEIRpt(1, TodbratTletrat) = 1 Todbrat = rated outdoor air dry bulb temperature. Tletrat = rated chilled water supply (leaving evaporator) temperature.
VE 6.4
ApacheHVAC
125
The chiller EIR (part-load and temperature dependence) curve is evaluated in each iteration of the chiller performance, for each time step during the simulation. The curve value is multiplied by the rated EIR (= 1/ COPrat, where COPrat is the rated coefficient of performance) and the EIR (temperature dependence) curve value to get the EIR of the current time step, for the specific Todb and Tlet temperatures and the specific part load ratio at which the chiller is operating: EIR = fEIRtt(Tlet,Todb) fEIRpt(p, Todb Tlet) / (pCOPrat) The curve should have a value of 1.0 when the part load ratio equals 1.0 and the temperatures are at rated conditions. A note on the applicable range of part-load ratio p: The minimum p is used by the program as the minimum unloading ratio, where the chiller capacity can no longer be reduced by normal unloading mechanism and the chiller must be false loaded to meet smaller cooling loads. A typical false loading strategy is hot-gas bypass. If this is the false loading strategy used by the chiller, the minimum p is the part load ratio at which hot gas bypass starts. The maximum p should usually be 1.0. During the simulation, a part-load ratio greater than 1.0 is a sign of chiller undersizing. 2.11.2.9 Minimum Part-load Ratio for Continuous Operation
This is the minimum part-load ratio at which the chiller can operate continuously. When the part-load ratio is below this point, the chiller will cycle on and off. 2.11.2.10 Compressor Heat Gain to Chilled Water Loop (fraction) This is the fraction of compressor electric energy consumption that must be rejected by the condenser. Heat rejected by the chiller condenser includes the heat transferred in the evaporator plus a portion or all of the compressor energy consumption. For electric chillers with hermetic compressors, all compressor energy consumption is rejected by the condenser, so the compressor heat gain factor should be 1.0. For chillers with semi-hermetic or open compressors, only a portion of the compressor energy used is rejected by the condenser, so the compressor heat gain factor should be less than 1.0. 2.11.2.11 Condenser Fan Power, Wfan Enter the condenser fan power consumption. For application without condenser fans (condensers cooled by natural convection or wind), set this parameter to zero. Note that this input is used to change the calculated Condenser Fan EIR, the EIR value will be used to re-size this input if and when the chiller capacity is changed manually or by autosizing. 2.11.2.12 Condenser Fan Electric Input Ratio, EIRfan This is the ratio of the condenser fan power consumption to the total chiller power consumption, which is computed from the chiller performance curves.
VE 6.4
ApacheHVAC
126
Figure 2-55: Electric air-cooled chiller dialog showing design condition tab when Rated condition is Design condition tick box is ticked. When this is un-ticked, the inputs for Cooling capacity and COP are no longer edited here, but are editable in the Rated condition tab.
VE 6.4 ApacheHVAC 127
2.11.3.1
The design outdoor air dry bulb temperature is specified in the associated chilled water loop dialog (in the Heat rejection tab) and is displayed here as a derived parameter. This parameter is autosizable. When this parameter is autosized, its value in the field and its autosizing label A become green. 2.11.3.2 Chilled Water Supply Temperature, Tletdes
The design chilled water supply temperature (leaving evaporator water temperature) is specified in the associated chilled water loop dialog (in the Chilled water loop tab) and is displayed here as a derived parameter. 2.11.3.3 Chilled Water Flow Rate, Ve, Ve/Qdes, Tedes
Ve, Ve/Qdes and Tedes are three different options for specifying design chilled water flow rate. Currently it is specified in terms of T edes (the difference between the design chilled water return and supply temperatures). It is specified in the associated chilled water loop dialog (in the Chilled water loop tab) and is displayed here as a derived parameter. The other two options (Ve and Ve/Qdes (the ratio between design chilled water flow rate (Ve) and design cooling capacity (Qdes).) are automatically derived by the program based on the specified Tedes and cannot be edited. 2.11.3.4 Cooling Capacity, Qdes
When Rated condition is design condition is not ticked, the design cooling capacity is automatically derived by the program using other design and rated condition data provided and does not need to be edited. When Rated condition is design condition is ticked, enter the design cooling capacity. This parameter is autosizable. When this parameter is autosized, its value in the field and its autosizing label A become green. 2.11.3.5 Coefficient of Performance, COPdes
When Rated condition is design condition is not ticked, the design coefficient of performance is automatically derived by the program using other design and rated condition data provided and does not need to be edited. When Rated condition is design condition is ticked, enter the design coefficient of performance.
Figure 2-56: Electric air-cooled chiller dialog showing Rated condition tab when Rated condition is Design condition tick box is not ticked. The white fields in the Rated condition tab are editable when not set equal to the design conditions. A user wishing to use catalogue chiller data enters a capacity and COP at the rated condition and reads off the derived capacity and COP at the design condition.
VE 6.4
ApacheHVAC
129
A user wishing to size a chiller based on a design load enters a capacity and COP at the rated condition, then adjusts the capacity to produce the desired derived capacity at the design condition (allowing for a margin of over-sizing). If the rated condition and design condition are one and the same, the user ticks the checkbox of Rated condition is design condition, which makes the rated condition data a dynamic copy of the design condition data. The derivations of chiller capacity and COP are done using the user-entered performance curves and other data. 2.11.4.1 Outdoor air dry bulb temperature, Todbrat
When Rated condition is design condition is ticked, the rated outdoor air dry bulb temperature is a dynamic copy of the design outdoor air dry bulb temperature. When Rated condition is design condition is not ticked, enter the rated outdoor air dry bulb temperature. 2.11.4.2 Chilled Water Supply Temperature, Tletrat
When Rated condition is design condition is ticked, the rated chilled water supply temperature (leaving evaporator water temperature) is a dynamic copy of the design chilled water supply temperature. When Rated condition is design condition is not ticked, enter the rated chilled water supply temperature. 2.11.4.3 Chilled Water Flow Rate, Verat, Verat/Qrat, Terat
Verat, Verat/Qrat, andT erat are three different options for specifying rated chilled water flow rate. Currently it is specified in terms of the ratio between rated chilled water flow rate (Verat) and rated cooling capacity (Qrat). The other two options (Verat and T erat (the difference between the rated chilled water return and supply temperatures)) are automatically derived by the program based on the specified Verat/Qrat and cannot be edited. When Rated condition is design condition is ticked, the rated chilled water flow rate is a dynamic copy of the design chilled water flow rate. When Rated condition is design condition is not ticked, enter the rated chilled water flow rate. 2.11.4.4 Cooling Capacity, Qrat
When Rated condition is design condition is ticked, the rated cooling capacity is a dynamic copy of the design cooling capacity. When Rated condition is design condition is not ticked, enter the rated cooling capacity. 2.11.4.5 Coefficient of Performance, COPrat
When Rated condition is design condition is ticked, the rated coefficient of performance is a dynamic copy of the design coefficient of performance. When Rated condition is design condition is not ticked, enter the rated coefficient of performance.
VE 6.4
ApacheHVAC
130
VE 6.4
ApacheHVAC
131
VE 6.4
ApacheHVAC
132
VE 6.4
ApacheHVAC
133
Cooling tower
G T2 towb
T1
Heat exchanger mcoil Key: water air tedb ge tldb gl T1coil T2coil
Cooling coil
Enter a description of the component. The reference is limited to 100 characters. It is for your use when selecting, organizing, and referencing any component or controllers within other component and controller dialogs and in the component browser tree. These references can be valuable in organizing and navigating the system and when the system model is later re-used on another project or passed on to another modeler. Reference names should thus be informative with respect to differentiating similar equipment, components, and controllers. 2.12.1.2 Design cooling tower approach
The difference between the cooling tower leaving water temperature (T2) and the outside wet bulb temperature (towb) at the design condition. 2.12.1.3 Design cooling tower range
The difference between the cooling tower entering water temperature (T1) and the cooling tower leaving water temperature (T2) at the design condition. 2.12.1.4 Design outside wet bulb temperature
The outside wet bulb temperature at the design condition. 2.12.1.5 Design cooling tower load
The load on the cooling tower (and cooling coil) at the design condition. This is used to size the water flow rates in the system. Appropriate sizing is essential for accurate representation of the cooling tower.
VE 6.4 ApacheHVAC 134
2.12.1.6
The effectiveness of the heat exchanger. This is defined with respect to the water loop with the lower flow. If the coil loop has the lower flow, the effectiveness is coil, defined by T1coil = T2coil + coil (T2 - T2coil) If the tower loop has the lower flow, the effectiveness is tower, defined by T1 = T2 + tower (T2coil - T2) Here T1 is the tower entering water temperature T2 is the tower leaving water temperature T1coil is the coil entering water temperature T2coil is the coil leaving water temperature coil and tower are in the ratio of the flows in the coil and tower loops. The heat exchange effectiveness parameter is thus the smaller of these two effectivenesses. 2.12.1.7 Cooling coil design water delta-T
The difference between the cooling coil leaving and entering water temperatures (Tcoil2 and Tcoil1) at the design condition. This, together with the design cooling tower load, is used to size the cooling coil water flow. 2.12.1.8 Cooling tower design fan power
The power consumption of the cooling tower fan when running at full speed. 2.12.1.9 Low-speed fan flow fraction
The fraction of the design flow that the cooling tower fan delivers when running at low speed. 2.12.1.10 Low-speed fan power fraction The power consumed by the cooling tower fan when running at low speed, expressed as a fraction of the cooling tower design fan power. 2.12.1.11 Design pump power The design power consumption of the cooling tower pump. The pump operates when the system delivers cooling.
VE 6.4
ApacheHVAC
135
2.12.1.12 Economizer operates only when it can meet the load in full? When this box is ticked the economizer is switched off if it cannot meet the coil load in full. This setting is currently forced to true. 2.12.1.13 Backup chiller Use this setting to specify a chiller providing backup to the waterside economizer. If the economizer has switched off because it cannot meet the full load, and no backup chiller is specified, no cooling occurs. 2.12.1.14 Integrated Waterside Economizer An Integrated Waterside Economizer (IWSE) is available as part of the Chilled water loop specification (see Section 2.8.3). Both dedicated and integrated waterside economizers can be specified, however, each type will have its own cooling tower.
VE 6.4
ApacheHVAC
136
Figure 2-60: DX Cooling Types dialog The entities defined here are types. A single DX cooling type may be assigned to many cooling coils. At the time of simulation, a separate instance of the assigned type is automatically created for each cooling coil. This provides a one-to-one relationship between modeled DX cooling types and connected DX coils. In this respect, DX cooling components differ significantly from chillers.
These pre-defined systems differ in terms of size ranges and associated COPs. The COP values in the predefined DX Cooling types match ASHRAE 90.1-2007 requirements (according to the tables at the end of Chapter 6), as adjusted per CA Title-24 ACM Manual methods to remove the supply fan power from the EER that was determined for a packaged unit at ARI conditions. For reference, the EER with SA fan power include (i.e., straight from 90.1-2007 chapter 6) and the intermediate value EERnf (EER with no fan, per the Title-24 ACM Manual calculation) are included in the name of each type. EERnf is then converted to COP without the fan, which is the input used in the DX Cooling dialog.
VE 6.4 ApacheHVAC 137
Figure 2-61: DX Cooling edit dialog The DX cooling model simulates the refrigerant side of a DX cooling system. The DX cooling airside (the cooling coil or evaporator) is modeled with the current (simple) ApacheHVAC cooling coil model, using the total available DX cooling capacity calculated by the DX cooling model. This model uses default or userdefined DX cooling performance characteristics at rated conditions and three performance curves to determine DX cooling performance at off-rated conditions.
VE 6.4 ApacheHVAC 138
The three DX cooling performance curves are: DX cooling capacity (temperature dependence) curve DX cooling electric input ratio (EIR) (temp dependence) curve DX cooling electric input ratio (EIR) (part-load dependence) curve
The DX cooling model includes the compressor and outdoor (condenser) fan power and thus energy consumption. If the condenser type is set to be evaporatively cooled, the DX Cooling model also accounts for spray pump power and energy consumption. It does not include the indoor (supply) fan power. Supply fans for DX cooling systems must be modeled separately as an ApacheHVAC fan component (see above discussion of this with respect to ASHRAE standard EER values under Pre-defined DX Cooling types). The DX cooling model covers both air-cooled and evaporative-cooled condensers. Energy consumption by condenser fans (and spray pumps if evaporative-cooled) is included in the DX units Electric Input Ratio (EIR) and associated performance curves. A condenser fan (and spray pump when the evaporatively cooled condenser option is selected) Electric Input Ratio (EIRfan/pump), representing the ratio of condenser fan power consumption to the total DX unit power consumption, is used to split the calculated energy consumption into separate results for compressor vs. condenser fan (and spray pump when included). 2.13.2.1 DX cooling model description
The following information can be accessed via the DX Cooling model description button in the DX Cooling dialog. It describes the variables and some of the fundamental relationships in the DX Cooling model. Rated cooling capacity: Qrat Rated coefficient of performance: COPrat Entering coil wet bulb temperature: Tewb Entering condenser temperature*: Tect Variable cooling capacity: Qcap = Qrat fCAPtt (Tewb and Tect) Cooling load: Q Part-load ratio: p = Q/Qcap DX cooling Electric Input Ratio: EIR = fEIRtt(Tewb and Tect) fEIRp(p) / (p COPrat) Total DX cooling power, including compressor and condenser fan (& pump) power: W = EIR Q Condenser fan (and spray pump when evaporatively cooled) Electric Input Ratio: EIR fan/pump Condenser fan/pump power: W fan/pump = EIR fan/pump W Compressor power: Wcpr = W W fan/pump
*Equals outdoor air dry-bulb temperature Todb when condenser type is air-cooled; Equals outdoor air wetbulb temperature Towb when condenser type is evaporative-cooled.
Enter a descriptive name for the DX Cooling type. The reference is limited to 100 characters. It is for your use when referencing the current DX Cooling type within component and controller dialogs. These references can be valuable in organizing and navigating the system and when the system model is later re-used on another project or passed on to another modeler. Reference names should thus be informative with respect to differentiating similar equipment, components, and controllers. 2.13.5.2 Condenser type
Select either air-cooled (dry) or Evaporatively cooled. This automatically changes the available pre-defined performance curves and adds or removes the evaporative cooling spray pump component from the model. The differences here are further described in the DX Cooling Model section above. 2.13.5.3 Fuel
Select the fuel or energy source used by the DX Cooling type to determine the category for reporting energy consumption results. For scratch-built system models, this should normally be set to Electricity. It will be pre-set to Cooling as an Energy end-use category consistent with LEED EA credit 1 submittal requirements for the pre-defined prototype ApacheHVAC systems, as provided by the Prototype Systems Library, System Prototypes & Sizing facility, and the ASHRAE 90.1 PRM workflow navigator. 2.13.5.4 Operational model: DX Cooling Model Description
Click the DX Cooling model description button or see DX Cooling model and DX cooling model description above for description of model variables and fundamental relationships.
VE 6.4
ApacheHVAC
140
2.13.5.5
Allow the connected cooling coil capacity to override Rated and Design Cooling Capacities?
Tick this box (ticked by default) to allow the autosizing of the connected cooling coil to override Rated and Design Cooling capacity values for each individual instance of a given DX type. Any one DX Cooling type may be assigned to multiple cooling coils, thus generating an equal number of separate instances of a single type defined in this dialog. This tick box determines the relationship between a DX Cooling type and the instances of that type for each coil to which is has been assigned: When this box is not ticked, the coil(s) that have been assigned the DX Cooling type with this attribute will be constrained to the capacities at Rated and Design conditions, as defined in this dialog. The autosizing process will not be able to override this. When this box is ticked, the autosized capacity of the coil(s) that have been assigned the DX Cooling type with this attribute will be used to adjust the Rated and Design conditions, as defined in this dialog, such that the Design Cooling Capacity in the one instance of the type associated with a particular coil will be equal to the autosized Cooling Capacity value displayed in the component dialog for that coil.
2.13.5.6
Tick this box to set the Design values for Outdoor air dry-bulb temperature at the condenser and Entering wet-bulb temperature at the evaporator coil equal to those values for the Rated condition. 2.13.5.7 Cooling capacity curve
Using the drop-down <Select> menu, choose the most appropriate pre-defined Cooling capacity performance curve for the type of system you are modeling. The available choices for this will be constrained by the selection of Air-cooled vs. Evaporatively cooled condenser type (above). Advanced users: The Edit button provides access to editing the performance curve coefficients and other associated performance parameters. A separate section on DX Cooling Performance curves details and editing is provided below. 2.13.5.8 EIR temperature dependence curve
Using the drop-down <Select> menu, choose the most appropriate pre-defined temperature dependence performance curve for the type of system you are modeling. The available choices for this will be constrained by the selection of Air-cooled vs. Evaporatively cooled condenser type (above). Advanced users: The Edit button provides access to editing the performance curve coefficients and other associated performance parameters. A separate section on DX Cooling Performance curves details and editing is provided below. 2.13.5.9 EIR part-load dependence curve
Using the drop-down <Select> menu, choose the most appropriate pre-defined part-load dependence performance curve for the type of system you are modeling. The available choices for this will be constrained by the selection of Air-cooled vs. Evaporatively cooled condenser type (above). Advanced users: The Edit button provides access to editing the performance curve coefficients and other associated performance parameters. A separate section on DX Cooling Performance curves details and editing is provided below.
VE 6.4
ApacheHVAC
141
2.13.5.10 Minimum part-load ratio for continuous operation Enter the part-load ratio (fraction of 1.0) below which the compressor should cycle on/off to meet the load rather than operate continuously. This establishes the lower bound of the performance curves with respect to cooling load. 2.13.5.11 Condenser fan (spray pump) power Enter the condenser fan power (kW) at the rated condition. If the condenser is evaporatively cooled, include the spray pump power in this value. This is typically the maximum value for these parasitic loads. Because the Cooling capacity and COP at Rated condition, as reported by the manufacturer, normally include the condenser fan (and spray pump) power, the condenser fan (and spray pump) power is modeled as a fraction of the overall energy consumption of the DX Cooling equipment. See the DX Cooling Model section above and Condenser fan (spray pump) EIR below. Note: While changing this input immediately adjusts the Electric Input Ratio (EIR) for the condenser fan/spray pump (below), the calculated EIR will then be held constant and will be used to revise the condenser fan/spray pump power when the rated Cooling capacity is changed. 2.13.5.12 Condenser fan (spray pump) Electric Input Ratio This field displays the calculated Electric Input Ratio Enter (EIR) the condenser fan (and spray pump when included) as a fraction of the overall electric power input required for the DX Cooling equipment at the rated cooling capacity and rated condition. The input for Condenser fan (spray pump) power determines this EIR. The calculated EIR is then used to adjust the condenser fan/spray pump power when the input for rated Cooling capacity is changed (maintaining the relationship between these), It is also used at each simulation time step to determine the condenser fan/spray pump power as a fraction of the overall energy consumption of the DX Cooling equipment at any particular part-load condition.
The design condition, on the other hand, is the condition at the time of peak design cooling load. To use catalogue DX cooling data, enter a cooling capacity and COP at the rated condition and read the derived capacity and COP at the design condition.
VE 6.4
ApacheHVAC
142
2.13.6.1
DX Cooling capacity
Enter the Cooling capacity at the Rated condition. This value is used both in simulation and to calculate Cooling capacity at the Design condition (inputs on the Design condition tab are enabled by un-checking the Rated condition is Design condition tick box). This parameter is indirectly autosizable, maintaining an appropriate relationship to the rating conditions, for each instance of a DX Cooling type when the Allow the connected cooling coil capacity to override Rated and Design Cooling Capacities? checkbox is ticked. 2.13.6.2 Coefficient of performance (COP)
Enter the COP at the Rated condition. This is the ratio of cooling capacity to the electric energy required, including compressor and condenser fan (plus spray pump, if any), to provide this cooling output at the rated condition. This value is used both in simulation and to calculate COP at the Design condition (inputs on the Design condition tab are enabled by un-checking the Rated condition is Design condition tick box). 2.13.6.3 Condenser: Outdoor air dry-bulb (wet-bulb) temperature
Enter the Outdoor air dry-bulb temperature as seen by the condenser at the rated condition. If the condenser is evaporatively cooled, enter the Outdoor air wet-bulb temperature at the rated condition. 2.13.6.4 Evaporator: Entering air wet-bulb temperature
Enter the Entering air wet-bulb temperature seen by the evaporator coil at the rated condition.
The latter two user inputs on the Design condition tab are enabled by un-checking the Rated condition is Design condition tick box just above the performance curve selections near the top of the dialog. 2.13.7.1 Design Cooling capacity
To size a DX unit type based upon a design cooling load at design conditions other than the rated condition, complete the following steps:
VE 6.4
Ensure that the Rated condition is Design condition tick box just above the performance curve selections near the top of the dialog is empty (not checked). Enter a capacity and COP at the rated condition. Enter the design conditions Adjust the rated capacity to produce the require derived capacity at the design condition (allowing for over-sizing, etc.).
ApacheHVAC 143
Provided that the Allow the connected cooling coil capacity to override Rated and Design Cooling Capacities? checkbox is ticked, the system autosizing facility does essentially this with respect to each instance of a DX Cooling typei.e., it sizes the evaporator coil according to the design load with oversizing factor and then adjusts the design and rated capacities for that particular instance of DX cooling to provide sufficient cooling at the simulated design condition. If the rated condition and design condition are one and the same, tick the checkbox for Rated condition is design condition, which makes the design condition data a dynamic copy of the rated condition data. 2.13.7.2 Condenser: Outdoor air dry-bulb (wet-bulb) temperature
Enter the Outdoor air dry-bulb temperature seen by the condenser at the Design condition. If the condenser is evaporatively cooled, enter the Outdoor air wet-bulb temperature at the Design condition. 2.13.7.3 Evaporator: Entering air wet-bulb temperature
Enter the Entering air wet-bulb temperature seen by the evaporator coil at the Design condition.
2.13.8 DX Cooling Performance curves: details and editing 2.13.9 Cooling Capacity curve, fCAPtt(Tewb,Tect), details and editing
Use the Edit button to view and edit the curve parameters. The Curve Editing dialog displays the formula and parameters of the curve and provides for editing of the curve parameters. You are permitted to edit the curve coefficients and the applicable ranges of the independent variables. When editing the curve parameters, it is important that you understand the meaning of the curve and its usage in the model algorithm. Ensure that the edited curve has reasonable ranges for the independent variables. A performance curve is valid only within its applicable ranges. If the independent variables are outside of the ranges that you set, the specified variable limits (maximum or minimum values) will be used.
VE 6.4
ApacheHVAC
144
Figure 2-62: Edit dialog for the cooling capacity curve of DX cooling type The cooling capacity curve fCAPtt(Tewb, Tect) is a bi-quadratic function of tewb = Tewb Tdatum tect = Tect Tdatum where Tewb = entering coil wet bulb temperature. Tect = entering condenser temperature. It equals outdoor air dry-bulb temperature Todb when condenser type is air-cooled; or equals outdoor air wet-bulb temperature Towb when condenser type is evaporative-cooled. Tdatum = datum temperature (0C or 0F), introduced for the convenience of units conversion of the curve coefficients.
VE 6.4 ApacheHVAC 145
And: fCAPtt(Tewb, Tect) = (C00 + C10 tewb + C20 tewb 2 + C01 tect + C02 tect 2 + C11 tewb tect) / Cnorm where C00, C10, C20, C01, C02 and C11 are the curve coefficients Cnorm is adjusted (by the program) to make fCAPtt(Tewbrat, Tectrat) = 1 Tectrat = rated entering condenser temperature. Tewbrat = rated entering coil wet bulb temperature. The cooling capacity curve is evaluated at each time step during the simulation. The curve value is multiplied by the rated cooling capacity (Qrat) to get the available (full-load) cooling capacity (Qcap) of the current time step, for the specific Tewb and Tect temperatures: Qcap = Qrat fCAPtt(Tewb, Tect) The curve should have a value of 1.0 when the temperatures are at rated conditions.
VE 6.4
ApacheHVAC
146
Figure 2-63: Edit dialog for the EIR temperature dependence curve of DX cooling type The DX cooling EIR (temperature dependence) curve fEIRtt(Tewb, Tect) is a bi-quadratic function of tewb = Tewb Tdatum tect = Tect Tdatum where Tewb = entering coil wet bulb temperature. Tect = entering condenser temperature. It equals outdoor air dry-bulb temperature Todb when condenser type is air-cooled; or equals outdoor air wet-bulb temperature Towb when condenser type is evaporative-cooled. Tdatum = datum temperature (0C or 0F), introduced for the convenience of units conversion of the curve coefficients.
VE 6.4 ApacheHVAC 147
And: fEIRtt(Tewb, Tect) = (C00 + C10 tewb + C20 tewb 2 + C01 tect + C02 tect 2 + C11 tewb tect) / Cnorm where C00, C10, C20, C01, C02 and C11 are the curve coefficients Cnorm is adjusted (by the program) to make fEIRtt(Tewbrat, Tectrat) = 1 Tectrat = rated entering condenser temperature. Tewbrat = rated entering coil wet bulb temperature. The DX cooling EIR (temperature dependence) curve is evaluated at each time step during the simulation. The curve value is multiplied by the rated EIR (= 1/ COPrat, where COPrat is the rated coefficient of performance) to get the full-load EIR of the current time step, for the specific Tewb and Tect temperatures. The curve should have a value of 1.0 when the temperatures are at rated conditions.
VE 6.4
ApacheHVAC
148
Figure 2-64: Edit dialog for the EIR part-load dependence curve of DX cooling type The DX cooling EIR (part-load dependence) curve fEIRp(p) is a bi-quadratic function of p = Q/Qcap where p = part-load fraction Q = cooling load Qcap = available (full-load) cooling capacity And: f EIRp(p) = (C0 + C1 p + C2 p2 + C3 p3) / Cnorm
VE 6.4
ApacheHVAC
149
where C0, C1, C2, and C3 are the curve coefficients, Cnorm is adjusted (by the program) to make fEIRp(1) = 1 The DX cooling EIR (part-load dependence) curve is evaluated at each time step during the simulation. The curve value is multiplied by the rated EIR (= 1/ COPrat, where COPrat is the rated coefficient of performance) and the EIR (temperature dependence) curve value to get the EIR of the current time step, for the specific Todb and Tlet temperatures and the specific part load ratio at which the DX cooling unit is operating: EIR = fEIRtt(Tewb, Tect) fEIRp(p) / (pCOPrat) The curve should have a value of 1.0 when the part load ratio equals 1.0 and the temperatures are at rated conditions. A note on the applicable range of part-load ratio p: The minimum p is used by the program as the minimum unloading ratio, where the DX cooling unit capacity can no longer be reduced by normal unloading mechanism and the DX unit must be false loaded to meet smaller cooling loads. A typical false loading strategy is hot-gas bypass. If this is the false loading strategy used by the DX unit, the minimum p is the part load ratio at which hot gas bypass starts. The maximum p should usually be 1.0. During the simulation, a part-load ratio greater than 1.0 is a sign of DX cooling units undersizing.
VE 6.4
ApacheHVAC
150
VE 6.4
ApacheHVAC
151
Figure 2-66: Unitary cooling system (types) editing dialog. The unitary cooling system is a unitary split vapor compression cycle cooling system serving one zone. It consists of an outdoor air-cooled condensing unit, a compressor and an indoor evaporator coil. On the outdoor side there is a heat rejection fan and on the indoor side a supply fan, which is downstream of the evaporator coil. The system does not incorporate a fresh air supply and it does not provide heating. On the schematic a unitary cooling system should be set up by placing a cooling coil in a loop circulating air through a room and assigning a suitable unitary cooling system type to the cooling coil. The supply fan will then be placed automatically in the duct following the cooling coil, but it is not shown on the schematic. In the intended mode of operation the compressor and both fans cycle to maintain the desired room set point. While the system is on it delivers cooling at a rate determined by the outside air dry bulb temperature and the condition of the air entering the evaporator coil. This control regime should be set up in ApacheHVAC by setting an unattainably low temperature set point for the cooling coil (for example 0C) and modulating the coil airflow on a proportional band in response to room temperature. The airflow through the coil will then be a time average, which is achieved in the real system by on/off cycling. Other control regimes are possible, but deviation from the intended mode of operation may invalidate the performance map on which the algorithm depends.
VE 6.4 ApacheHVAC 152
The default data for this component is taken from ASHRAE 140-2004 [1], which specifies a series of tests for building energy simulation programs. The data used is from Table 26d of the standard, where the data is expressed in IP units. 2.14.1.1 Reference
Enter a description of the component. The reference is limited to 100 characters. It is for your use when selecting, organizing, and referencing any component or controllers within other component and controller dialogs and in the component browser tree. These references can be valuable in organizing and navigating the system and when the system model is later re-used on another project or passed on to another modeler. Reference names should thus be informative with respect to differentiating similar equipment, components, and controllers. 2.14.1.2 Compressor fuel code
The fuel used by the compressor. This will normally be Electricity, but other fuels, such as Miscellaneous A, may sometimes be appropriate. 2.14.1.3 Airflow rate
The flow rate through the evaporator coil under design conditions. The flow through the coil during simulation must be no greater than this. When it is less, the flow reduction is assumed to be achieved on a time average by cycling the fan operation. 2.14.1.4 Scale performance parameters with design airflow rate?
If this box is ticked any change to the design airflow rate will cause all the performance parameters expressed in power units to be scaled in proportion. This allows the performance of a similar unit of a different size to be modeled to a good approximation.
Values of evaporator coil entering (thermodynamic) wet bulb temperature at which the system performance is specified. 2.14.2.3 Entering dry bulb temperature
Values of evaporator coil entering dry bulb temperature at which the system performance is specified. 2.14.2.4 Gross Total Capacity
The total (sensible plus latent) cooling output of the evaporator coil when the system is operating at capacity (that is, at design supply airflow) under conditions when the evaporator coil is wet. This is referred to as gross total capacity because it is offset by the supply air fan gain. This value does not apply
VE 6.4 ApacheHVAC 153
when the evaporator coil is dry, and in this case the gross sensible capacity is equal to the gross sensible capacity. A dry coil is indicated by the figure for gross sensible capacity being greater than the figure for gross total capacity. In general, interpolation of the performance map is required to determine whether the coil is wet or dry. This interpolation is done automatically by the simulation algorithm. 2.14.2.5 Gross Sensible Capacity
The sensible cooling output of the evaporator coil when the system is operating at capacity (design supply airflow). As with gross total capacity, the term gross is applied because the cooling effect is offset by the supply air fan gain. 2.14.2.6 Compressor Power
The power required to drive the compressor when the system is operating at capacity. 2.14.2.7 Use extrapolation?
If this box is ticked, which is the recommended setting, the program will extrapolate the performance parameters gross total capacity, gross sensible capacity and compressor power when the operating condition lies outside the bounds of the performance map. The extrapolation is applied using data from the cell of the performance map that lies closest to the operating condition. If the box is not ticked the performance parameters are set to those at the nearest point of the performance map. 2.14.2.8 Heat rejection fan power
The power consumption of the outdoor heat rejection fan. This is accounted for as system electricity. 2.14.2.9 Supply fan power
The power consumption of the indoor supply air fan. All the heat from the supply fan is assumed to enter the air stream. This is accounted for as system electricity. 2.14.2.10 Low load COPr degradation factor At part load, when the supply fan is cycling, there is a degradation of system efficiency. This is modeled using a degradation factor applied to the refrigeration coefficient of performance, COPr, defined by COPr = (gross total coil load) / (compressor power) At part load, COPr is reduced by a load-dependent multiplicative COPr degradation factor, CDF: COPr = COPrfull * CDF where COPrfull is the value of COPr at full load (for a given outside and on-coil condition). CDF is assumed to be a linear function of part load ratio, PLR: CDF = CDF0 + (1 - CDF0)*PLR where PLR is defined as PLR = (gross total coil load) / (gross total coil capacity)
VE 6.4 ApacheHVAC 154
and CDF0 is a dimensionless constant with a value in the range (0,1) - the low load COPr degradation factor. The COPr degradation factor also has an effect on fan power consumption and supply air fan gain. This effect is modeled by assuming that the COPr degradation is due to a start-up period preceding each operational period, during which the evaporator coil attains its equilibrium value and effectively contributes nothing to cooling. During this start-up period the compressor, and both the supply and heat rejection fans, are assumed to be on.
VE 6.4
ApacheHVAC
155
2.15.1 Background
ApacheHVAC provides two levels of heating coil models for use in HVAC systems. A Simple heating coil model uses a simplified approach to determining coil heat transfer characteristics and assumes constant waterside temperature change through the coil. An Advanced model more explicitly models both airside and waterside heat transfer providing a more detailed and accurate calculation of coil heat transfer and corresponding airside/waterside properties. The Advanced model provides the necessary modeling detail to support explicit waterside modeling contained in Hot Water Loop configurations. The Advanced model also provides more detailed coil specification methods so that coils may be better sized or selected from manufacturer data for specific HVAC system configurations. This facilitates more accurate determination coil design and off-design performance. Both Simple and Advanced heating coil models are accessed through the heating coil icon tool bar icon and the heating coil dialog. A HVAC system configuration can contain both Simple and Advanced modes, however, multiplexed systems must only contain models of the same type (i.e., all Simple OR all Advanced models). Simple models can be served by Hot Water Loops and Generic Heat Sources. Advanced models can only be served by Hot Water Loop systems.
new sizing parameters, Hot water design flow and Heating capacity, immediately displayed. A Sizing status message box indicates the state of the sizing process including error conditions resulting from outof-range or inconsistent input parameters.
VE 6.4
ApacheHVAC
157
Figure 2-67: Simple heating coil model dialog with coil served by hot water loop
Figure 2-68: Simple heating coil dialog with coil served by a generic heat source The user may select the Advanced coil model from the Simple model dialog. Once selected, the Advanced model dialog will open automatically upon selecting the particular coil. The Advanced model dialog is shown below.
VE 6.4 ApacheHVAC 158
Figure 2-69: Advanced heating coil dialog The upper portion of both the Simple and Advanced model dialogs contain information for specifying the reference name, coil model type, and system type serving the coil. The lower section of the dialog contains the Design sizing parameters appropriate for each model type. Detailed descriptions of these parameters are provided below. 2.15.6.1 Reference
2.15.6.3
System type
Select a system type serving the coil, Generic heat source or Hot water loop. Note that Advanced heating coils may only be served by Hot water loops. 2.15.6.4 System name
Enter the maximum Heating capacity of the heating coil. The simulation will limit the output from the coil to this maximum capacity, even if the controls are calling for more. In cases where there is no proportional control, the output device will be set to this value whenever the on/off control of the coil is on. 2.15.7.2 Over-sizing factor (all system types)
Specify the factor by which the heating coil capacity is increased relative to the peak calculated value.
Default Values Typical Range Error Limits 1.25 1.00 to 1.50 0.00 to 5.00
VE 6.4
ApacheHVAC
160
The Sizing status message box provides information on the state of the coil sizing process. This includes error messages for out-of-range or inconsistent design parameters. A summary of the Sizing status messages is provided below.
Calculation successful Entering air DBT must be less than or equal to leaving DBT Entering air dry bulb temperature must be less than the leaving HWL temperature. Leaving air dry bulb temperature must be less than the entering HWL temperature
2.15.8.2
Air flow rate is the volumetric air flow entering the coil. In the Autozing process, peak air flow rate is determined by the System Sizing process. When an autosized air flow rate is displayed, the value and Autosize indicator will be indicated in green However, air flow rate still be edited from the autosized values (the value will return to black with corresponding A). Note that this air flow rate is only used in for determining the coil heat transfer parameters and not used by any flow controllers associated with the HVAC system on which the coil resides.
Default Values Typical Range Error Limits 2831.68 l/s 94.39 to 14158.42 l/s 0.00 to 471950.00 l/s 6000.00 CFM 200 to 30000 CFM 0.00 to 1,000,000.00 CFM
2.15.8.3
Entering air dry (DB) is the air stream condition entering the coil. These temperatures must be specified in both the Autosizing/Manual process. In Autozing, peak design value for this temperature can be determined by the System Sizing process. When an autosized temperature is displayed, the value and Autosize indicators will be shown in green. However, the temperature can still be edited from the autosized value (the value will return to black with corresponding A).
Default Values Typical Range Error Limits 12.78 C -17.78 to 50.00 C -100.00 to 100.00 C 55.00 F 0.00 to 80.00 F -148.00 to 212.00 F
VE 6.4
ApacheHVAC
161
2.15.8.4
Leaving air dry (DB) is the condition of the air steam exiting the coil. Leaving air DB temperature must be specified in both Autosizing/Manual processes. In Autosizing, required leaving air DB temperature to meet the system load can be determined by the System Sizing process. When the Autosized temperature is displayed, the value and Autosize indicators will be shown in green. However, the temperature can still be edited from the autosized value (the value will return to black with corresponding A).
Default Values Typical Range Error Limits 32.22 C 26.67 to 37.78 C -100.00 to 100.00 C 90.00 F 80.00 to 100.00 F -148.00 to 212.00 F
2.15.8.5
Hot water loop supply temperature and Hot water loop delta temperature
Hot water loop supply temperature is the design hot water temperature entering the coil. Hot water loop delta temperature is the design hot water temperature drop through the coil. Both values are linked to the corresponding Hot water loop parameters (see HWL Sec. 2.4) serving the coil and non-editable in the Advanced heating coil dialog. These parameters may be edited in the corresponding HWL dialog and the edited values automatically updated in the Advanced heating coil dialog. 2.15.8.6 Hot water loop flow rate
Hot water loop flow rate is the design hot water flow rate serving the coil. This value is calculated from the other coil design sizing parameters. Note that this value is adjusted by the Over-sizing factor specified. In the simulation, the necessary hot water flow rate is determined by the coil model to meet the relevant control requirements. However, the simulation will limit the hot water flow rate to the coil at this value even if the associated control requirements are greater. 2.15.8.7 Heating capacity
Heating capacity is the design heat transfer capacity of the coil. This value is calculated from the other coil design sizing parameters. Note that this value is adjusted by the Over-sizing factor specified. 2.15.8.8 Oversizing factor
The factor by which the coil design values for hot water flow rate and heating capacity are increased relative to the autosized values. Airside parameters (flow rate, entering air DB temperature, and leaving air DB temperature) are NOT adjusted by the over-sizing factor. The coil design heat transfer with the over-sizing factor is:
Q coil ,des = mair ,des hair ,enter hair ,leave = mwater ,des cp,water ,des THWL
Default Values Typical Range Error Limits 1.25 1.00 to 1.50 0.00 to 5.00
VE 6.4
ApacheHVAC
162
2.16.1 Background
ApacheHVAC provides two levels of cooling coil models for use in HVAC systems. A Simple cooling coil model uses a simplified approach to determining coil heat transfer characteristics and assumes constant waterside temperature change through the coil. An Advanced model more explicitly models both airside and waterside heat transfer providing a more detailed and accurate calculation of coil heat transfer and corresponding airside/waterside properties. This includes modeling the coil in for dry (sensible), wet (latent), and partial dry/wet conditions. The Advanced model provides the necessary modeling detail to support explicit waterside modeling contained in Chilled Water Loop configurations. The Advanced model also provides more detailed coil specification methods so that coils may be better sized or selected
VE 6.4 ApacheHVAC 163
from manufacturer data for specific HVAC system configurations. determination coil design and off-design performance.
Both Simple and Advanced cooling coil models are accessed through the cooling coil icon tool bar icon and the cooling coil dialog. A HVAC system configuration can contain both Simple and Advanced modes, however, multiplexed systems must only contain models of the same type (i.e., all Simple OR all Advanced models). Simple models can be served by Chilled Water Loops, Unitary cooling systems, Waterside economizers, and DX cooling systems. Advanced models can only be served by Chilled Water Loops systems.
VE 6.4
ApacheHVAC
164
For each sizing mode, there are a set of derived parameters that are calculated upon user edit of any design parameter. For example, in Autosize mode the user sets (or can rely on System Sizing data) the entering airflow, entering air dry and wet-bulb temperatures, the leaving dry bulb temperature, and contact factor. The resulting leaving air wet-bulb temperature, chilled water loop flow, and cooling capacity are instantly calculated and displayed. If, for example, the resulting cooling capacity is too low, the user might increase the air mass flow or modify the contact factor to achieve greater cooling. In Manual mode, the user has full capability to set all the design parameters on the airside and waterside of the coil. From these design parameters, the resulting coil contact factor, chilled water flow rate, and cooling capacity are calculated and displayed. Again, if for example, the cooling capacity is too low, the user might input a higher air mass flow. Switching between the two design sizing modes is simply done by selecting the desired sizing mode button. The default dialogue mode is to only show the design parameter set for the selected mode, however, the user can display both modes data by specifying the Display mode to both. Finally, the user can hold autosized values when they switch to Manual mode.
VE 6.4
ApacheHVAC
165
Figure 2-70: Simple cooling coil model dialog with coil served by chilled water loop
Figure 2-71: Simple cooling coil dialog with coil served by a dedicated waterside economizer (this is distinct from the Integrated WSE mode available for chiller sets including water-cooled chillers on a chilled water loop, which can be used only with Advanced cooling coils)
VE 6.4
ApacheHVAC
166
Figure 2-73: Simple cooling coil model dialog (coil served by unitary cooling system) The user may select the Advanced coil model from the Simple model dialog. Once selected, the Advanced model dialog will open automatically upon selecting the particular coil. The Advanced model dialog is shown below for both Autosizing and Manual sizing modes.
VE 6.4
ApacheHVAC
167
Figure 2-74: Advanced model cooling coil dialog: Autosizing mode (note that the display format setting at the bottom of the dialog allows for both modes to be shown at once, if desired).
VE 6.4
ApacheHVAC
168
Figure 2-75: Advanced model cooling coil dialog: Manual sizing mode (note that the display format setting at the bottom of the dialog allows for both modes to be shown at once, if desired). The upper portion of both the Simple and Advanced model dialogs contain information for specifying the reference name, coil model type, and system type serving the coil. The lower section of the dialog contains the Design sizing parameters appropriate for each model type. Detailed descriptions of these parameters are provided below. 2.16.6.1 Reference
VE 6.4
ApacheHVAC
169
2.16.6.2
Coil model type may be either Simple or Advanced. 2.16.6.3 System type
Select a system serving the coil from those available on the list. 2.16.6.4 System name
The contact factor is used to describe the way air flows over the coil, and is used to calculate the balance of sensible to latent heat removal of the air passing over the coil. The contact factor specifies what proportion of the total airflow is contacted by the coil and so follows an ideal psychrometric process of cooling along a constant moisture content line until the saturation curve is met, and then following the saturation line. The balance of the airflow is assumed to be unaffected by the cooling coil but is then mixed with the cooled air upon leaving the coil. Typical values of contact factor are in the range 0.7 - 0.95. For a given flow rate, higher contact factors will tend to be associated with coils that either have more rows of fins or a larger face area, and thus lower face velocity. A higher contact factor has the advantage of achieving the desired leaving air temperature (LAT) with relatively warmer water from the chiller. As the contact factor is reduced, the required coil temperature, and thus also water temperature, is lower, which has implications for chiller operating efficiency and chilled-water reset controls. On the other hand, a low contact factor also has the same effect as intentionally bypassing some of the air around the coil so that the cooling coil can be operated at a very low temperature for maximum dehumidification, and then mixing the bypass fraction with the very dry air off the coil to get a final LAT. While the bypass air is obviously also more humid, the net result will be a lower leaving wet-bulb temperature (WBT) for the same dry-bulb LATi.e., greater wet-bulb depression. This can be readily seen in ApacheHVAC system simulation results for higher and lower cooling coil contact factors in a humid climate. 2.16.7.2 Cooling capacity (if coil served by Chilled water loop, waterside economizer, or DX)
200.00 kW 0.50 to 250.00 kW 0.05 to 1000.00 kW 682.43 kBTU/h 1.71 to 853.04 kBTU/h 0.17 to 3412.14 kBTU/h
Enter the maximum duty of the cooling coils. The simulation will limit the output from the coil to this maximum capacity, even if the controls are calling for more. In cases where there is no proportional control, the output device will be set to this value whenever the on/off control of the coil is on.
VE 6.4
ApacheHVAC
170
2.16.7.3
Specify the factor by which the cooling coil capacity is increased relative to the peak calculated value.
Default Values Typical Range Error Limits 1.15 1.00 to 1.50 0.00 to 5.00
2.16.7.4
When a unitary cooling system model is assigned to the cooling coil, this model includes a supply fan downstream of the cooling coil that is not shown on the schematic. The parameters of this fan are defined in the properties of the unitary cooling system. See Unitary Cooling Systems section.
The Sizing status message box provides information on the state of the coil sizing process. This includes error messages for out-of-range or inconsistent design parameters. A summary of the Sizing status messages is provided below.
Required input values have been entered. Coil has been sized with input values.
Entering air WB temperature is too low for the corresponding entering DB temperature Leaving air WB temperature is too low for the corresponding leaving DB temperature Entering air WB temperature is greater than the entering air DB temperature Leaving air WB temperature is greater than the leaving air DB temperature
Calculation successful
Not Possible: Leaving WBT too low Not Possible: Entering WBT > Entering DBT Entering air WB temperature is greater than the entering air DB temperature
VE 6.4
ApacheHVAC
171
Not Possible: Entering DBT < Leaving CWL temperature Not Possible: Leaving DBT < Entering CWL temperature Not Possible: Conditions not consistent with input Contact factor
Entering air DB temperature must be lower than the leaving Chilled Water Loop temperature Leaving air DB temperature must be lower than the entering Chilled Water Loop temperature The input airside conditions will not yield a cooling process consistent with the input Contact factor.
Not Possible: Entering DBT < Leaving CWL temperature Not Possible: Leaving DBT < Entering CWL temperature
Entering air DB temperature must be lower than the leaving Chilled Water Loop temperature Leaving air DB temperature must be lower than the entering Chilled Water Loop temperature The input airside conditions are not feasible for a cooling only process, i.e., the exiting air would have to be heated to reach the desired combination of DBT/WBT.
2.16.8.2
Air flow rate is the volumetric air flow entering the coil. Air flow rate must be specified in both Autosizing/Manual modes. In Autozing mode, peak air flow rate can be determined by the System Sizing process. When an autosized air flow rate is displayed, the value will be indicated in green with a A. However, air flow rate still be edited from the autosized values (the value will return to black with corresponding A). Note that this air flow rate is only used in for determining the coil heat transfer parameters and not used by any flow controllers associated with the HVAC system on which the coil resides.
Default Values Typical Range Error Limits 9438.95 l/s 94.39 to 14158.42 l/s 0.00 to 474500.00 l/s 20000.00 CFM 200 to 30000 CFM 0.00 to 1,000,000.00 CFM
2.16.8.3
Entering air dry (DB) and wet-bulb (WB) temperatures are the air stream conditions entering the coil. These temperatures must be specified in both Autosizing/Manual modes. In Autozing mode, peak design values for these temperatures can be determined by the System Sizing process. When autosized temperatures are displayed, the value will be indicated in green with a A. However, the temperatures can still be edited from the autosized values (the values will return to black with corresponding A).
Default Values Typical Range Error Limits 26.67 C 15.00 to 50.00 C 0.00 to 100.00 C 80.00 F 60.00 to 120.00 F 32.00 to 212.00 F
2.16.8.4
Leaving air dry (DB) and wet-bulb (WB) temperatures are the conditions of the air steam exiting the coil. Leaving air DB temperature must be specified in both Autosizing/Manual modes. In Autosizing mode, required leaving air DB temperature to meet the system load can be determined by the System Sizing process. When an autosized temperature is displayed, the value will be indicated in green with a A. However, the temperature can still be edited from the autosized values (the values will return to black with corresponding A).
VE 6.4
ApacheHVAC
172
In Autosize mode, the leaving air WB temperature is calculated from other entered parameters (i..e., Contact factor) and non-editable. In Manual mode, leaving air WB temperature must be specified.
Default Values Typical Range Error Limits 19.44 C 5.00 to 40.00 C 0.00 to 100.00 C 67.00 F 40.00 to 100.00 F 32.00 to 212.00 F
2.16.8.5
The coil Contact factor is as described in Section 2.10.3.5. In Autosizing mode, Contact factor is a user input. In Manual mode, Contact factor is calculated from the specified airside parameters. In Manual mode, if the user specifies a set of airside parameters that require a process not achievable by cooling alone (i.e., reheat would be needed to achieve the air leaving conditions), the Contact factor will indicated as Not Feasible.
Default Value Typical Values Error Limits 0.91 0.70 to 0.95 0.01 to 1.0
2.16.8.6
Chilled water loop supply temperature is the design chilled water temperature entering the coil. In Autosize mode, this value is linked to the corresponding Chilled water loop supply temperature (see CWL section xxx) serving the coil and non-editable. In Manual mode, this value is editable, however, the edited value is local to the cooling coil and does not affect the corresponding Chilled water loop specified value.
Default Values Typical Range Error Limits 6.67 C 2.00 to 18.00 C 0.00 to 100.00 C 44.00 F 34.00 to 62.00 F 32.00 to 212.00 F
2.16.8.7
Chilled water loop supply delta temperature is the design chilled water temperature rise through the coil. In Autosize mode, this value is linked to the corresponding Chilled water loop delta temperature (see Chilled Water Loop section 2.4.10) serving the coil and non-editable. In Manual mode, this value is editable, however, the edited value is local to the cooling coil and does not affect the corresponding Chilled water loop specified value.
Default Values Typical Range Error Limits 6.67 K 4.00 to 8.00 K 0.00 to 16.67 K 12.00 F 8.00 to 14.00 F 0.00 to 30.00 F
2.16.8.8
Chilled water loop flow rate is the design chilled water flow rate serving the coil. This value is calculated from the other coil design sizing parameters. Note that this value is adjusted by the Over-sizing factor specified. In the simulation, the necessary chilled water flow rate is determined by the coil model to meet the relevant control requirements. However, the simulation will limit the chilled water flow rate to the coil at this value even if the associated control requirements are greater.
VE 6.4
ApacheHVAC
173
2.16.8.9
Cooling capacity
Cooling capacity is the design heat transfer capacity of the coil. This value is calculated from the other coil design sizing parameters. Note that this value is adjusted by the Over-sizing factor specified. 2.16.8.10 Oversizing factor
The factor by which the coil design values chilled water flow rate and cooling capacity are increased relative to the autosized values. Airside parameters (flow rate, entering air DB temperature, entering air WB temperature, leaving air DB temperature, and leaving air WB temperature) are NOT adjusted by the over-sizing factor. The coil design heat transfer with the over-sizing factor is: Q coil,des = mair,des hair,enter hair,leave Oversizing factor = mwater,des cp,water,des Tchilled water loop,des
The over-sizing factor is only pertinent to the Autosizing mode to allow the user to oversize the coil from an autosized design values. For the Manual sizing mode, no over-sizing factor is necessary since the coil design parameters can be set directly to consider additional capacity if desired.
Default Values Typical Range Error Limits 1.15 1.00 to 1.50 0.00 to 5.00
2.16.8.11
The Hold autosizing parameters? tick box is provided so that if switching between Autosizing and Manual sizing modes, the current set of autosized values will be held. 2.16.8.12 Advanced Model Design Parameters Summary
The Advanced model design parameters for Autosize and Manual sizing modes are summarized below.
VE 6.4
ApacheHVAC
174
Leaving air DB temperature Leaving air WB temperature Contact factor Chilled water supply temperature Chilled water loop delta T Chilled water flow rate Cooling capacity Over-sizing factor
Autosized Value Editable Derived Value Non Editable User Input Editable From CWL Non Editable From CWL Non Editable Derived Value Non Editable Derived Value Non Editable User Input Editable
Derived Value Non-editable User Input Editable User Input Editable Derived Value Non Editable Derived Value Non Editable User Input Editable Editable but edits are limited to the coil model only, i.e., do not alter the CWL values entered in the CWL dialog. Dialogue will check for errors and consistency
User Selected
Autosized parameters will be held as the user switches between Autosize and Manual sizing modes.
Not Applicable
VE 6.4
ApacheHVAC
175
Spray chamber component. Note that spray humidifiers either run wild or are off, i.e. it is not possible to control moisture input or offcoil conditions.
2.17.1 Reference
Enter a description of the component. The reference is limited to 100 characters. It is for your use when selecting, organizing, and referencing any component or controllers within other component and controller dialogs and in the component browser tree. These references can be valuable in organizing and navigating the system and when the system model is later re-used on another project or passed on to another modeler. Reference names should thus be informative with respect to differentiating similar equipment, components, and controllers.
VE 6.4
ApacheHVAC
177
Enter a description of the component. The reference is limited to 100 characters. It is for your use when selecting, organizing, and referencing any component or controllers within other component and controller dialogs and in the component browser tree. These references can be valuable in organizing and navigating the system and when the system model is later re-used on another project or passed on to another modeler. Reference names should thus be informative with respect to differentiating similar equipment, components, and controllers.
Enter the maximum rate of moisture input from the steam humidifiers to the air stream.
Warning Limits (kg/s) Error Limits (kg/s) 0.005 to 1.0 0.001 to 5.0
VE 6.4
ApacheHVAC
178
2.18.1.3
Total Efficiency
Enter the total efficiency of the steam humidifiers. This parameter is used to relate the total heat input to the air stream to the energy used to generate that input (i.e. it is used to take the energy input to the air stream back to a primary energy consumption.)
Warning Limits (%) Error Limits (%) 65.0 to 100.0 20.0 to 100.0
2.18.1.4
In actual applications, steam injection is normally limited to avoid the risk of condensation in the downstream duct. This RH high-limit cut-out value should be entered here.
Warning Limits (%) Error Limits (%) 70.0 to 95.0 50.0 to 100.0
2.18.1.5
A steam humidifier may be supplied with steam from a heat source. If this is the case then enter the reference of the heat source. If you do not select a heat source the humidifier uses local electric heating.
Heat recovery
VE 6.4
ApacheHVAC
179
2.19.1.1
Reference
Enter a description of the component. The reference is limited to 100 characters. It is for your use when selecting, organizing, and referencing any component or controllers within other component and controller dialogs and in the component browser tree. These references can be valuable in organizing and navigating the system and when the system model is later re-used on another project or passed on to another modeler. Reference names should thus be informative with respect to differentiating similar equipment, components, and controllers.
2.19.1.3
Enter the latent heat effectiveness. Note that a negative latent effectiveness is permitted, but should be used only in the case of modeling a desiccant that is being actively dried or regenerated, thus allowing latent energy to be transferred in an uphill direction.
Warning Limits (%) Error Limits (%) -60 to 90.0 -100.0 to 100.0
2.19.1.4
Enter the electrical power consumed when operating. This might be the pump power for a run-around coil, the motor power for a thermal wheel, etc.
Warning Limits (kW) Error Limits (kW) 0.0 to 15.0 0.0 to 9999.0
VE 6.4
ApacheHVAC
180
2.20 Fans
The fan module is used to determine the required fan power at a given flow rate, and thus energy consumption of the fan, and to account for the temperature rise in the air stream.
Toolbar icon for placement of left and right intake fans. Left and right intake fan components. The fan component does not actively influence the flow rate; the values entered here do not determine airflow through the system. Rather, these values are used solely to calculate the consequential energy consumption and effect on air temperature at a given flow rate. Pressure, in this case, refers to the total static pressure (internal plus external) to be overcome by the fan. Efficiency includes both the mechanical efficiency of the fan and the electrical efficiency of the motor and associated power electronics (e.g., a variable-speed drive). For variable-volume systems, the flow, pressure, and efficiency characteristics need to be defined at multiple points on the fan curve.
Figure 2-79: Fan dialog with illustrative inputs for an ASHRAE 90.1 baseline fan
VE 6.4
ApacheHVAC
181
The combination of flow, pressure, and efficiency is used during the simulation to calculate the electrical power consumption and fan heat input to the air stream as follows:
Power =
Where
Flow is airflow in kg/s Pressure is the pressure resistance against which the fan has to work in Pa at Flowtypically between 50 and 200 Pa for local fans and between 500 and 2000 Pa for ducted fans.
Energy loss = Electrical power (1 Efficiency) Fan heat pickup = Electrical power (1 Efficiency) Airstream heat pickup % Where Power is electricity consumption as calculated in the first fan equation, above. Efficiency is total combined efficiency at a given flow rate for both the fan and motor. Airstream heat pickup is the fraction of total fan and motor losses that go into the air stream. It is important to realize that the fan curve data must account for the system layout (total pressure) and the type of airflow and fan controls. For example, the same fan would performance depending on whether it is controlled by a downstream damper or by variable-speed drive. In the system with speed control, the pressure either will drop with flow or will be maintained at a constant value as the basis for fan speed control (in either case, power and heat will fall with flow); whereas the damper-controlled system will have roughly constant speed, and therefore the pressure must rise as flow is reduced. 2.20.1.1 Reference
Enter a description of the component. The reference is limited to 100 characters. It is for your use when selecting, organizing, and referencing any component or controllers within other component and controller dialogs and in the component browser tree. These references can be valuable in organizing and navigating the system and when the system model is later re-used on another project or passed on to another modeler. Reference names should thus be informative with respect to differentiating similar equipment, components, and controllers.
VE 6.4
ApacheHVAC
182
2.20.1.2
Depending on whether the fan motor is in the airstream or not, there will be a greater or smaller heat pickup by the air across the fan. For fans whose motor is located in the airstream, a figure of 100% should be used. For fans where the motor is not located in the airstream, this will be less than 100%.
Warning Limits (%) Error Limits (%) 10.0 to 100.0 0.0 to 100.0
2.20.1.3
Flow
Enter the fan flow rate. Up to five points may be defined on the fan characteristic curve.
Warning Limits (l/s) Error Limits (l/s) 0.0 to 25000.0 0.0 to 900000.0
2.20.1.4
Pressure
Enter the total fan static pressure at this flow rate, including both internal pressure (resulting from filters, coils, and other air handler components) and external pressure (from ductwork, terminal units, etc.).
Warning Limits (Pa) Error Limits (Pa) 150.0 to 2000.0 10.0 to 90000.0
2.20.1.5
Efficiency
Enter the fan total efficiency at this flow rate. This figure is used to calculate the electrical consumption of the fan at any instant, by dividing the work done on the air by the efficiency. The value entered here should be the product of the efficiencies of the impeller, drive, and motor.
Warning Limits (%) Error Limits (%) 25.0 to 90.0 10.0 to 99.0
VE 6.4
ApacheHVAC
183
The minimum flow from the left branch is entered in the damper component dialog, and can be scheduled and even modulated via the modulating profile referenced in this dialog.
Figure 2-80: Mixing damper set dialog (top) and associated controller dialog (bottom) as set up for modulating the damper to a target mixed-air dry-bulb temperature for a typical outside air economizer. Note that the controller also has an AND reference to a dependent controller with sensor that provides a similar outdoor air dew-point temperature high limit. In this example, the controller will modulate the damper, mixing outside air and return air to get as close as it can to achieving a target mixed-air temperature of 55F.
VE 6.4 ApacheHVAC 184
In the case of outside-air economizer damper applications, the flow into the left-hand branch is subject to the minimum value specified by the Minimum flow parameter, with three exceptions: The flow from the left branch will be less than the set minimum when the total demand for outflow (mixed-air) is less than the minimum outside air value. In this case, the flow into the left-hand branch is simply equal to the outflow at any given time step. The flow on the left-hand inlet branch will be increased above the minimum, such as in the case of airside economizer free cooling, CO2-based demand-controlled ventilation (DCV), as determined by a controller pointed to the downstream (mixed-air) node of the damper set. The controlled variable for economizer operation is normally a target mixed-air temperature, for DCV it is usually a percentage flow. See the DCV examples illustrated below for systems that combine OA economizer and DCV operation. An RA Damper component connected to the vertical (bottom) inlet branch on the Mixing Damper will override the set minimum outside air when the total demand for supply air at the mixed-air node exceeds the total of available return air plus the minimum OA. This is intended mainly for use in building, such as laboratories, for which there are multiple means of exhaust/extract from spaces served by the system. While it would be possible to create a detailed schedule for the minimum OA makeup air requirement, this is not necessary at the system OA damper, so long as the air balance is always provided for at the zone level.
The Mixing Damper is used to determine the fraction of downstream flow demand that is drawn from the left inlet branch vs. the bottom inlet branch. The mixing damper component can be used only where total flow at the mixed-air (outlet) is determined downstream of the damper set, and not where flow is otherwise determined on either upstream branch. In other words, while flow paths, sources, and conditions can be determined upstream of a mixing damper, and mixing dampers can be used in series, the actual airflow volume at the downstream node of a mixing damper must be determined on a downstream branch. Configurations for which flow is otherwise determined on either inlet branch upstream of the mixing damper will pass a network check, but will not run at simulation time. Therefore, this component will, in most cases, be used only at or near the system inlet. When the controllers profile is on, the damper set component modulates the flow into its left-hand branch (normally the fresh air inlet) either to a percentage of the flow leaving the device or to get as close as it can to a target mixed-air temperature. The leaving flow rate will have been determined by flow demands downstream. The time switch profile within the controller that is controlling the damper modulation is interpreted as an on/off switch, ON when the profile value is greater than 50% and OFF otherwise. This is in contrast to the behavior of a time switch profile used either to schedule or to modulate the minimum flow on the left branch or when a volume flow controller. Percentage flow control can be applied only to mixing damper sets and divergent T junctions (which can thus act as flow-splitting dampers), and must be applied at the control node immediately downstream of the mixing damper set. 2.21.1.1 Reference
Enter a description of the component. The reference is limited to 100 characters. It is for your use when selecting, organizing, and referencing any component or controllers within other component and controller dialogs and in the component browser tree. These references can be valuable in organizing and navigating the system and when the system model is later re-used on another project or passed on to another modeler. Reference names should thus be informative with respect to differentiating similar equipment, components, and controllers.
VE 6.4 ApacheHVAC 185
2.21.1.2
This parameter sets a minimum value for the flow into the left-hand branch of the damper set. Independent of whether the on/off control within the associated controller used to modulate the damper position above the minimum flow is on or off, the flow into the left-hand branch will be subject to a minimum which is the lesser of this minimum value and the flow rate demanded at the damper outlet by downstream controllers.
Warning Limits (l/s) Error Limits (l/s) 0.0 to 25000.0 0.0 to 900000.0
2.21.1.3
Modulating Profile A schedule can be used to enforce the minimum outside air (flow from the left branch) during only occupied hours of building operation, thus allowing the outside air damper to close completely during unoccupied hours. This is a typical means of avoiding unnecessary heating of outside air when system fans switch on the middle of the night or weekends to maintain a setback temperature. A modulating profile can be used to vary the minimum flow rate based upon either a schedule or a formula profile referencing a value such as outdoor dry-bulb temperature.
The modulating profile in the mixing damper set can serve at least two functions:
Demand-controlled ventilation based upon zone-level CO2 is provided not by modulating profile, but by attaching a proportional controller to the damper set with a CO2 sensor on the downstream node of the occupied zone(s)/room(s) as illustrated below. Note the branch of the damper set to which the controller is pointed. 2.21.1.4 Mixing Damper Application: CO2-based Demand-Controlled Ventilation (DCV) example
For CO2-based demand-controlled ventilation, the controlled variable for outside air (OA) can be either flow rate (cfm or l/s) into the left branch of the damper set or the fraction from the left branch as a percentage of the total mixed-air flow rate. However, the latter is much more flexible and useful, as it allows independent zone-level controllers with CO2 sensors to vote on the system-level outside-air damper position, without having to know at any given time step what the actual flow rate at that damper is. If there are multiple zones voting on the fraction of outside air as a function of individual CO2 levels (via multiplexed controllers responding to sensed room CO2 levels), the controlled variable will normally be percentage flow. For 100% outside air systems, as in the second example below, zone-level flow rates can be controlled to maintain desired CO2 levels. No OA damper is required. If outside airflow above the minimum required for ventilation and/or makeup air is controlled to a target mixed-air temperature, as is most typical means of outside air economizer control, a duplicate damper will need to be included for raising the fraction of outside air when demanded by zone CO2 levels. This is because all controllers pointing to a given node must use the same controlled variable in order to facilitate voting. In the application illustrated below, each zone votes for additional OA at the system level as the zone CO2 exceeds a set threshold (see the highlighted controller and associated controller dialog). A second damper component, in additional to the normal OA economizer, just below and to the left of the OA economizer damper. This represents a second copy of the same actual damper, but with a different controlled variable. While the OA economizer is controlled to modulate the fraction of outside air to meet a desired
VE 6.4 ApacheHVAC 186
mixed-air target temperature, with an outside temperature high-limit, at or above which it will shut down to the set minimum OA flow, the added DCV damper can add more OA based on zone demand. The zonelevel DCV controllers vote on the amount of additional OA needed at any give time. The highest vote from zone-level DCV controllers modulates the system DCV damper from 0 to 100% as zone CO2 concentration rises from 1,000 to 1,400 ppm. In other words, when it is desirable to bring in more OA to maintain the set mixed-air temperature, the first damper will prevail. When it is desirable for maintenance of appropriate zone CO2 levels to introduce more OA than otherwise provided by the thermally driven OA economizer, the added damper will prevail. Neither can ever bring in more OA than is demanded by the system. Both will have equal priority in determining how much OA is brought in at any given time.
Figure 2-81: Illustrative HVAC network configuration with added outside-air damper and controller for CO2-based demand-controlled ventilation in a mixing (recirculating) system.
VE 6.4
ApacheHVAC
187
Figure 2-82: Illustrative controller dialog for CO2-based demand-controlled ventilation in a mixing (recirculating) system. This controls the percentage flow in the added copy of the outside-air damper, thus overriding the outside-air flow rate otherwise determined by thermal considerations for the normal economizer damper operation, as needed to maintain set zone CO2 levels. A second example (below) illustrates an appropriate configuration for control of the zone-level outside air ventilation rate with a 100% outside air system. This is typical for ventilation systems used with fan-coil units, active chilled beams, and similar terminal equipment. In this case, some zones can use constantvolume ventilation and others can have ventilation rate varied according to CO2 concentration in the zone.
VE 6.4
ApacheHVAC
188
Figure 2-83: The system network example above illustrates a configuration for CO2-based demandcontrolled ventilation in a 100% outside air system (i.e., with no recirculation). This example is a fan-coil system, but could easily be modified to model active chilled beams (induction units), passive chilled beams, or chilled ceiling panels. For all zones with DCV, the highlighted controller must use room CO2 as the sensed variable for control of the primary zone airflow rate. Other zones can simply use a fixed flow rate (e.g., identical values for the flow rate at min and max sensor signals). Note that the damper set at the system inlet is a face & bypass damper for the energy recovery device, and has no influence on the fraction of outside air. A separate controller in this example determines the fraction of air that air passes through or around the heat/enthalpy recovery device based upon zone temperatures, and thus whether additional fan energy is consumed as a result of added static pressure when recovering thermal energy.
VE 6.4
ApacheHVAC
189
RA Damper component on the network. The Return Air (RA) Damper Set component incrementally increases the minimum flow of outside air (makeup air) entering the system via the economizer damper when required. In other words, it can, as needed, override the minimum OA setting in the intake air mixing damper component. The RA Damper Set is intended for use only with the Mixing Damper Set, and this is assumed to be when the latter is functioning as an outside air (OA) economizeri.e., when it is mixing OA and RA flows. The RA Damper has no user inputs and performs its function only when paired with the Mixing Damper Set. In order for the two to be linked, the RA Damper must be present on the vertical branch entering the OA economizer damper. There can be no junctions between them. If it is not paired with the Mixing Damper in this configuration, and thus linked the OA damper, it will revert to functioning as a simple T junction. The capability of the RA damper link to automatically override the minimum OA setting within the OA damper is useful in the case of any system for which the sum total of RA plus minimum OA available to the system may occasionally be less than the collective demand for primary supply airflow to the conditioned zones. This may occur, for example, when there are separately exhausted zones (lavatories, copy rooms, janitors closet, locker rooms, etc.) or variable-volume vent/fume hoods (e.g., in laboratories, hospitals, industrial environments, etc.) removing air from the system according to schedules or sensed variables that are independent of the primary airflow controls to the conditioned zones that feed them. Another way to think of this is that the RA Damper can override the minimum OA setting when the total demand for supply air at the mixed-air node exceeds the total of available return air plus the minimum OA. This is intended mainly for use in buildings, such as laboratories, for which there are multiple means of exhaust/extract from spaces served by the system. While it would be possible to create a detailed schedule for the minimum OA makeup air requirement, this is not necessary at the system OA damper, so long as the air balance is always provided for at the zone level. The RA damper does not, however, obviate the need to otherwise specify airflow rates so that other braches on the system, such as transfer air paths, are not starved of airflow when the minimum flow from upstream branches, or the schedule thereof, constrains what is available downstream.
VE 6.4
ApacheHVAC
190
Divergent T junction components. When the flows for a junction component are set to be divergent, the junction can be controlled to function as a fixed or variable percentage-flow splitter damper. Until a percentage flow controller is pointed to the downstream node at one of two outlets on a divergent junction, it functions as a simple uncontrolled junction of airflow paths. Attaching a percentage flow controller to either one of the two outlets provides a controlled split of the flow, regardless of the current flow rate. It is important the percentage-flow control is applied to only one of the two downstream nodes, and not both. Furthermore, the flow must not also be determined by a flow-rate controller on the same downstream branch, as this would create an over-constrained path.
Clicking on the red arrows in the Junction flow direction dialog determines divergent rather than convergent flows in junction components. Percentage flow control can be used only in the case of divergent junctions.
Divergent T junction component with percentage flow controller attached to one of two outlets.
VE 6.4
ApacheHVAC
191
Toolbar icons for ductwork heat pick-up (horizontal and vertical components). Ductwork heat pick-up component. 2.24.1.1 Reference
Enter a description of the component. The reference is limited to 100 characters. It is for your use when selecting, organizing, and referencing any component or controllers within other component and controller dialogs and in the component browser tree. These references can be valuable in organizing and navigating the system and when the system model is later re-used on another project or passed on to another modeler. Reference names should thus be informative with respect to differentiating similar equipment, components, and controllers.
VE 6.4
ApacheHVAC
192
2.24.1.2
2.24.1.3
Enter the average U-value of the duct. The duct U-value is used together with the duct surface area to calculate the heat transfer between the duct and the adjacent room (or outside).
Warning Limits (W/mK) Error Limits (W/mK) 0.1 to 10.0 0.01 to 99.0
2.24.1.4
Location
Select either external to building (outside the conditioned envelope) or contained with room (including non-occupied spaces, such as return air plenums). 2.24.1.5 Room Containing Duct
Select an indoor location of the ductwork (an actual space in the model), if the location is not set to external. The flow of heat between the duct and room is modeled for both the air system and the room.
VE 6.4
ApacheHVAC
193
Enter a description of the component. The reference is limited to 100 characters. It is for your use when selecting, organizing, and referencing any component or controllers within other component and controller dialogs and in the component browser tree. These references can be valuable in organizing and navigating the system and when the system model is later re-used on another project or passed on to another modeler. Reference names should thus be informative with respect to differentiating similar equipment, components, and controllers.
VE 6.4 ApacheHVAC 194
2.25.1.2
Radiant Fraction
Enter the radiant fraction of the heat emitted (or cooling effect) from the device. See Table 13 for typical values. 2.25.1.3 Efficiency
Enter efficiency for the direct acting heater. 2.25.1.4 Uses CHP?
Tick this box to indicate that the heater can accept heat input from a CHP system (if present). 2.25.1.5 Sequence ranking
Sequence ranking determines the sequence in which the loads on various heat sources will be addressed by CHP-supplied heat. The loads assigned to heat sources with low values of this parameter will be first in line to receive heat from the CHP. If two heating sources have the same sequence ranking, they will be served simultaneously, with the CHP input supplying the same fraction of the heating load for both.
VE 6.4
ApacheHVAC
195
Figure 2-87: Radiator types dialog (showing illustrative inputs for a group of convective fin-tube baseboard heaters)
VE 6.4
ApacheHVAC
196
Figure 2-88: Radiator editing dialog showing inputs for a group of small wall-mounted steel radiators.
Figure 2-89: Radiator editing dialog showing inputs for set of 8 overhead radiant heating panels.
VE 6.4 ApacheHVAC 197
2.26.1.1
Reference
Enter a description of the component. The reference is limited to 100 characters. It is for your use when selecting, organizing, and referencing any component or controllers within other component and controller dialogs and in the component browser tree. These references can be valuable in organizing and navigating the system and when the system model is later re-used on another project or passed on to another modeler. Reference names should thus be informative with respect to differentiating similar equipment, components, and controllers. 2.26.1.2 Orientation
Select an orientation to describe the orientation of the radiator. Standard radiators are vertically orientated, which will tend to increase the convective heat transfer coefficient within the overall heat transfer calculation. You may want to define the radiator with horizontal orientation if it is being used to model an overhead radiant panel or a hydronic radiant heating floor system. 2.26.1.3 Radiant Fraction
Enter the radiant fraction of the heat emitted from the device. For typical values see Table 13: Heat Emitter Radiant Fraction in the Apache Tables User Guide. 2.26.1.4 Reference Temperature Difference
Manufacturers data commonly gives heat output of the radiator for a reference unit-room temperature difference. Enter the reference temperature difference in this cell. For example, the data may state that the heating output is 2.5 kW for a temperature difference of 60C. 2.26.1.5 Heating Output at Reference Temperature Difference
Enter the reference heating output in this cell. For the example given above, the heating output is 2.5 kW for at the reference temperature difference of 60C. The program uses this data to calculate an effective area for use in the calculation of the convective heat transfer as follows: A standard convective heat transfer coefficient HCIs is first calculated for the standard radiator-room temperature difference, Tu using the Alamdari and Hammond equations: HCIs = F_HCIs (ORI,Tsu,Tsr,CHARL) where Tsr Tsu ORI CHARL F_HCIs is the standard room temperature (set to 20C) is the standard unit temperature (= Tsr + Tu) is the Orientation is the characteristic length (set to 0.1m) is a function implementing the equations.
Enter the maximum input from heat source serving the radiator. Because of the way in which heat source loads are calculated in the program, maximum heat source capacity cannot be specified. Instead, a maximum must be allocated to each heat emitter, coil, etc. The sum of the maximum capacities for all the devices on a heat source circuit should equal the maximum capacity of the heat source.
2.26.3 Material
Select the material from which the chilled ceiling panels or passive chilled beams are made (steel or aluminum). The material is used together with the 'Total weight' and the water capacity to calculate of the total thermal capacity of the radiator.
VE 6.4
ApacheHVAC
199
Output from the chilled ceiling component is calculated from the temperature difference between the metal surface and the room temperature. The software uses the Alamdari and Hammond equations to set up the form of the variation of the heat transfer coefficient as the chilled panel and room temperatures vary. Thus the output varies with the temperature difference between the panel and the room. In this calculation the room temperature is an average of air and radiant temperatures, weighted by convective and radiant heat transfer coefficients that vary with time according to conditions in the room. For characterization of the radiant panel device and for the purpose of the design calculation, the room air and radiant temperatures are assumed to be the same, and equal to the metal temperature plus the reference temperature difference. During the subsequent simulation, the room air and radiant temperatures will tend not to be equal: Whereas it would be typical in summer for all room surfaces in room with an all-air cooling system to be somewhat warmer than the room air, when radiant cooling is engaged, most interior surfaces that can see the radiant panel will be cooler than the room air temperature; however, certain surfaces, such as window glass heated by direct solar radiation, may still be considerably warmer than the air temperature. The situation will therefore differ to some extent from the assumed design condition. Exactly how it differs is a function of room gains, room dynamics, and the dynamics of the waterside system and controls. These factors can't be fully anticipated in advance, so there will be some departure from the assumed design behavior. However, this can be corrected for by adjusting the design temperature difference in the light of simulation results at times of high loade.g., for a space with a high fraction a radiant loads and cooling panels that also have a high radiant fraction for their cooling effect, setting the device radiant fraction appropriately in the Chilled Ceiling Types dialog and reducing the reference temperature difference will increase the cooling effect.
VE 6.4
ApacheHVAC
200
VE 6.4
ApacheHVAC
201
Enter a description of the component. The reference is limited to 100 characters. It is for your use when selecting, organizing, and referencing any component or controllers within other component and controller dialogs and in the component browser tree. These references can be valuable in organizing and navigating the system and when the system model is later re-used on another project or passed on to another modeler. Reference names should thus be informative with respect to differentiating similar equipment, components, and controllers. 2.27.1.3 Panel Orientation
Select an orientation for the panels: horizontal for mainly horizontal panelsi.e. the majority of the chilled surface faces down toward the floor; vertical for wall-mounted panels or those with surface area mainly perpendicular to the floor and ceiling. Vertical beams are mainly convective and horizontal beams are mainly radiative in their cooling effect. The selected option therefore affects the default radiative fraction in the next cell. It is also used as a parameter to the Alamdari and Hammond convective heat transfer coefficient equations in the determination of the form of the variation of the convective heat transfer coefficient with beam temperature.
2.27.1.4
Radiant Fraction
Enter the radiant fraction of the heat emitted from the device. See Table 13 for some typical values.
Warning Limits Error Limits 0.0 to 0.9 0.0 to 1.0
2.27.1.5
Manufacturers data commonly gives the cooling output of the unit at a reference temperature difference. Enter the reference temperature in this cell. For example, the data may state that the cooling output is 2.5 kW for a unit-room temperature difference of 6Ki.e., when the cooling surface of the unit is 6K below the room air temperature. In this case enter 6 in this cell.
Default (C) Warning Limits (C) Error Limits (C) 5 2.0 to 20.0 1.0 to 100.0
2.27.1.6
Manufacturers data commonly states cooling output for a given unit-room temperature difference. Enter this reference cooling output in this cell. For example the data may state that the cooling output is 2.5 kW for a temperature difference of 6K. In this case enter 2.5 in this cell. The program uses this data to calculate an effective area for use in the calculation of the convective heat transfer as follows: A standard convective heat transfer coefficient HCIs is first calculated for the standard panel-to-room temperature difference, Tb using the Hammond and Alamdari equations: HCIs = F_HCIs(ORI,Tsb,Tsr,CHARL) where Tsr Tsb is the standard room temperature (set to 22C) is the standard beam temperature (= Tsr - Tb)
ORI is the Orientation CHARL F_HCIs is the characteristic length (set to 0.1m) is a function implementing the equations
VE 6.4
ApacheHVAC
203
Note that the Alamdari and Hammond equations are used to set up the form of the variation of the convective heat transfer coefficient as the beam and room temperatures vary and not to calculate absolute values from first principles. When the beam is at Tbs and the room is at Trs, the convective heat output from the unit is Qstd x (1 - rf).
Warning Limits (kW) Error Limits (kW) 0.35 to 100.0 0.05 to 9999.0
2.27.1.7
Enter the maximum input from chiller. In an actual application, this will be limited by the water temperature and flow rate. The parameters can also be controlled, and thus limited (see Room Unit Controllers section), however, this parameters allows opportunity for setting a hard limit in terms of available cooling capacity. Because of the way in which chiller loads are calculated in the program, a maximum chiller capacity cannot be specified. Instead, a maximum limit must be allocated to each chilled ceiling, cooling coil, etc. Except where considerable diversity of cooling loads is anticipated, the sum of all the maximum capacities of all the devices on a cooling circuit should equal the maximum capacity of the chiller. 2.27.1.8 Distribution Pump Consumption
This item is included to allow for the electrical pumps on a zone-level secondary (or tertiary) hydronic loop. Whenever the flow rate on/off controller is on, irrespective of the actual flow rate, then the full electrical power specified here is assumed to apply. This allows the modeling of zoned control of coldwater distribution to chilled ceilings using local constant-speed pumps. Alternatively, such when only valves and not pumps are use at the zone loop level, pump power can be included on the secondary chilled-water loop at the system modeling level. 2.27.1.9 Panel Material
Select the material from which the chilled ceiling panels or passive chilled beams are made (steel or aluminum). The material is used together with the 'Total weight' and the water capacity' to calculate of the total thermal capacity of the beam. 2.27.1.10 Panel Weight Enter the weight of the panels, excluding the weight of water in the system. This data is used to calculate thermal capacity. 2.27.1.11 Panel Water Capacity Enter the water capacity of the panels or passive chilled beams. This is used to calculate the thermal capacity.
VE 6.4
ApacheHVAC
204
Controllers
Controllers are used in ApacheHVAC to govern the operation of the HVAC system. Their function is to control airflows and the behavior of devices such as coils, mixing dampers, flow splitters, energy-recovery heat exchangers, spray chambers, and steam humidifiers.
Figure 3-1: The example of a VAV system with mixed-mode controls above illustrates the broad range of ApacheHVAC controller applications and configuration. The brown boxes and lines represent controllers. The control leads with arrowheads point to controlled nodes for airflows and equipment; those with a round bulb at the end are sensors. Thin dashed green lines are logical AND connections. Controllers can include various combinations of sensors, a control point (if independent), as well as logical AND connections and OR connections to other controllers. Controllers can be variously placed within or outside of the multiplexed region of a system (see section 6.1.1 Rules for Multiplexes and controllers within them), which determines whether just one or multiple control signals will be voting on the controlled variable at a particular node (see section 3.4.1 Multiple controllers at a single network node). In this example, four controls have been added to a standard VAV system to create an advanced mixedmode system: The primary mixed-mode control senses the difference between the room or zone temperature and outdoor temperature. This is coupled by an AND connection to prevent the VAV damper opening for mechanical cooling air supply when conditions are appropriate for natural ventilation. A dependent time switch controller coupled by an OR connection (thin dashed blue line) is used to enable or disable mixed-mode controls during autosizing of the mechanical system. There are two additional mixed-mode controls coupled via OR connections to turn the mechanical air supply back on again when natural ventilation is insufficient to address either thermal or ventilation demands, as determined by room temperature and CO2 concentration.
VE 6.4
ApacheHVAC
205
It is not necessary to define local control loops at individual components. Indeed, it is likely to cause control instability if you control a variable as a direct function of a value measured at the same node. For example, if you want a heating coil to warm an airstream to 25C, do not control heat output in response to the measured off-coil air temperature. Instead, you should control temperature directly. Ideally, all feedback control loops should have a slow responding component such as a room somewhere in the loop. There will be occasions when this is not possible (for example when the ratio of outside air to return air is controlled as a function of the mixed air temperature); in such cases damping can be added to the proportional controller to encourage control stability, but you should check the program output carefully to ensure that the system is behaving correctly. Once controllers are in place their behavior may be modified with AND and OR connections from other controllers.
VE 6.4
VE 6.4
ApacheHVAC
207
Controllers are of three basic types: time switch controller, controller with sensor, and differential controller. Each type has independent and dependent variants: Independent controllers directly control a component or airflow rate. They also generate a switching signal which can be used as an input to other controllers via AND and OR connections. Dependent controllers generate only a switching signal for input to other controllers. With the exception of ducts, passive junctions, rooms and fans, every HVAC component needs a controller. Controllers are also required to set airflow rates, and this may be done at any node (not necessarily at a fan). Controllers switch components on or off and govern their performance. System variables that may be controlled include airflow, heat output, temperature and humidity. Controllers are required throughout the ApacheHVAC model to control the system components and to move air through the network. The control may be no more than a simple time switch (on at certain hours of the day, off at others). In other cases it will modulate the operation of a component in response to conditions sensed by a thermostat or other type of sensor. The following components will operate only if a control connection has been made to their downstream node: Heating coil Cooling coil Spray humidifier Steam humidifier Heat recovery device Damper set (economizer)
The downstream connection is interpreted as a connection to the component itself, and causes it to control the condition at the controlled node. Note that Fans are not directly controlled; flow rate is controlled anywhere on a network branch (See section 3.5 Airflow controllers, below).
Node Being Sensed Variable Being Sensed Percentage Profile for Time Switch Value for Maximum Control Signal Value for Minimum Control Signal Constant or Timed Set point Set point Deadband High Sensor Input Logical 'OR' Control Combination Logical 'AND' Control Combinations Variable Being Controlled
ApacheHVAC 208
Constant or Timed Midband Midband Proportional Bandwidth Maximum Change per Time Step
The selection and application of parameters differs depending on the controller type. If a controller is required simply to hold a variable at a constant value, the controller specification need only include the value to be maintained and the hours during which the value is to be maintained. It will act as a simple time switch with the variable held constant as specified for value for maximum control signal whenever the controller is the ON state. For example, to simulate a heating coil with a constant leaving air temperature requires only a controller to activate the coil over the required period and to set the off-coil temperature. Where it is required to switch a device ON or OFF in accordance with the value of a sensed variable, the controller specification will include a set point and other parameters, such as a control deadband (hysteresis). This type of control would be typical for a thermostat controlling a room heater. It may also be augmented by proportional control (see below) if, in this example, the output of the heater is variable. The controller set point can be constant or can vary according to an absolute profile. A time varying set point can be used to specify night setback and certain types of optimum start algorithme.g., using a formula profile to vary the time for changing from night setback to the occupied-hours set point according to the outdoor temperature. Proportional controls are used where there is need for continuously varying the control value in relation to a sensed signal. This will be typical for control of VAV boxes, demand-controlled ventilation, bypass dampers for heat recovery, and so forth. They can also be used very generically to control one flow in proportion to another, such as in an active chilled beam for which the induced airflow is to be 2.5 times the primary airflow, regardless of the primary airflow rate. A similar application would be the approximation of exfiltration through a pressurized building envelope at a rate, for example, of 1.8% of the primary airflow to each zone. For any controller that includes a sensor for either set-point control or proportional control, the sensed variable can be any of those available (see list below) and ultimately will depend upon the sensor location. For example room temperature, CO2, relative humidity, etc., outdoor variables, such as wet-bulb temperature, dew-point temperature, etc., or relative variables, such as the difference in enthalpy between return air and outdoor air.
VE 6.4
ApacheHVAC
209
Applicable control variables for each type of component on the airside HVAC network Component Heating coil Cooling coil Heat recovery Spray chamber Steam humidifier Mixing damper set Return Air damper Divergent junction Active duct Fan Network branch Dry-bulb Relative Wet-bulb Dew-point % Temp. Humidity Temp. Temp. Flow Yes Yes Yes No No Yes n/a No n/a n/a No No No No Yes Yes No n/a No n/a n/a No No No No Yes No No n/a No n/a n/a No No Yes No Yes No No n/a No n/a n/a No No No No No No Yes n/a Yes n/a n/a No Heat Moisture Enthalpy Transfer input Yes Yes No No No No n/a No n/a n/a No No No No Yes Yes No n/a No n/a n/a No No No No No No Yes n/a No n/a n/a No Flow rate No No No No No No n/a No n/a n/a Yes
Table 3-1: Controlled variables allowed for each type of componenti.e., at the network node immediately downstream. As an example, Percentage Flow Rate is permitted only at the outlet of a damper set or at one outlet of a divergent (flow-splitting) junction. However, dry-bulb-temperature and enthalpy are also permitted at the outlet of a mixing damper set, where they are interpreted as targets to be achieved, to the extent this can be done by mixing the available inlet streams. Note that Active Duct components are not controlled at all, Fan components are not directly controlled, and flow rate can be controlled anywhere on a network branch.
If the sensed variable is dry-bulb temperature, the sensor radiant fraction must also be specified. Sensed CO2 concentration in a space at any simulation time step is a function of the outdoor concentration (assumed to be 360 ppm), CO2 addition from occupants, and the extent to which the mechanical system recirculates the air and/or mixes it with air from other spaces. Occupant CO2 production is, in turn, a function of the number of occupants in the space and the occupant activity level in keeping with combined sensible and latent gain per person that has been set for People under Internal Gains in the Thermal Conditions template or Room Data dialogs. CO2 concentration is not available for Room Unit controllers, as these control only hydronic devices that cannot influence room air CO2 concentration.
VE 6.4
ApacheHVAC
210
Two additional sensed variables are available for room unit controllers: Solar radiation Surface temperature
For Solar radiation, Sensor location must be External and the orientation and slope of the receiving surface must be specified. Note: While Flow rate is on the Room Unit controller selection list of Sensed variables and does cause gpm or l/s units to be displayed, this sensed variable is not yet available for Room Unit controllers. Error limits for the three additional parameters:
Radiant Fraction Orientation (azimuth) Slope (angle from horizontal) 0.0 1.0 0.0 360.0 0.0 180.0 0.0 1.0 0.0 360.0 0.0 180.0
Figure 3-2: Adding a surface temperature sensor tag Surface temperature sensors require a room/zone location to be selected within the controller dialog. For the sensor to function, this location requires a tag to be set in Apache Thermal view indicating which adjacency in the zone/room should have the sensor. For example, for a room with a floor that overlaps multiple other zones, just one section of the floor can be tagged as the sensed surface within that room.
VE 6.4 ApacheHVAC 211
The selected adjacency can be within a non-occupied space, such as a return or underfloor supply plenum. In the case of a hydronic heated or cooled slab, the sensor would go on the floor or ceiling of the adjacent occupied space, such that it is measuring the temperature of the thermo-active surface that occupants can see. The surface temperature sensor tag is added by selecting the appropriate adjacency while in the Apache Thermal view and then right clicking to access the surface temperature sensor option. Once set, a red T will be displayed next to the adjacency, parent surface for that adjacency (typically a floor or ceiling), and the room or zone that contains that surface. See Figure 3-2, above.
Where two or more controllers are attached to one node, their on/off control signals and their controlled variable values are combined as follows: The component (or flow) is turned on if any (one or more) of the attached controllers outputs an ON signal. Any controller providing an ON signal also outputs a value for the controlled variable, which is then subject to a polling process.
The effect on the controlled variable depends on the type of this variable and the component it applies to. In the case of flow control, the flow through the node is set to the maximum of the flows calculated by the attached controllers. In the case of a damper set, this principle applies to the flow calculated for the branch entering the mixing box from the left on the schematic (which often represents the outside air intake). In the case of a heating coil, steam humidifier, spray chamber, or heat recovery device, the controlled variable (for instance, off-coil temperature) is set to the maximum of the controlled values output by the attached controllers. In the case of a cooling coil, the controlled variable is set to the minimum of the controllers output values. As such, the multiple attached controllers effectively vote on the resulting control value. The resulting outcomes described above are summarized Table 3-2, below.
VE 6.4
ApacheHVAC
212
Dominant control value when multiple controls point to a single network node Component Heating coil Cooling coil Heat recovery Spray chamber Steam humidifier Mixing damper set Return Air damper Divergent junction Active duct Fan Network branch Dry-bulb Relative Wet-bulb Dew-point % Temp. Humidity Temp. Temp. Flow Max Min Max Max n/a n/a n/a Max Max n/a n/a n/a n/a n/a n/a Min Max n/a n/a n/a Max n/a Max n/a n/a Heat Moisture Enthalpy Transfer input Max Min n/a n/a n/a Max Max n/a n/a n/a Max n/a n/a n/a Flow rate n/a n/a n/a Max
Table 3-2: The dominant value when multiple controllers point to a single node or component.
VE 6.4
ApacheHVAC
213
This parameter, which is present for all independent controllers, specifies the variableflow rate, drybulb temperature, relative humidity, etc.to be controlled at the controlled node. It is not necessary to define local control loops at individual components and, indeed, it is likely to cause control instability if you control one variable at a node as a direct function of a value measured at the same node. For example, if you want a heater coil to warm the air up to 25C, do not control heat output in response to the measured off-coil air temperature. Instead, you should directly control temperature. Ideally, all feedback control loops should have a slow responding component (e.g. a room) somewhere in the loop. There will be occasions when this is not possible (e.g. when the ratio of outside air to return air is controlled as a function of the mixed air temperature). In such cases damping can be added to the proportional controller to encourage control stability, but you should check the program output carefully to ensure that the system is behaving correctly. None of the 'active' components defined in the network (with the exception of fans) will perform a function unless a controller is specified at the node immediately downstream of that component. The controls react with the components as follows: When the controller is OFF, a particular component will have no effect on the air passing over it. If the airflow on a network branch is OFF, there will be no load placed upon any components on that particular branch. If the airflow ALL downstream network branches are OFF, there will be no load on any components located on the upstream path that feeds them. When the controller is ON: If under proportional control, the condition of the air leaving the component will depend on the value corresponding to the control signal coming from the proportional controller at any instant in time. If no proportional control, the condition of the air leaving the component will depend on the control value indicated at the maximum sensed signal.
3.6.1.2
This parameter is present for all independent controllers. It has a different function for on/off (set point) controllers and proportional control. In the case of on/off control, which applies when the Proportional Control box is not ticked, the value for maximum signal specifies the numerical control signal. The controlled variable will take this value whenever the switching signal is on (provided that such a value can be achieved within the physical constraints, which include the maximum duty of the component).
VE 6.4 ApacheHVAC 214
In the case of proportional control, which applies when the Proportional Control box is ticked, the value for maximum signal specifies the value of the numeric control signal output when the sensed variable is at or above the upper end of the proportional band. The response characteristic for proportional control is shown in Figures 3-4 and 3-9, below. Note that if you want to control the temperature of the air from a heating or cooling coil, this should be done directly by choosing dry-bulb temperature for the variable being controlled cell and the required temperature for value for maximum control signal. ApacheHVAC will calculate the heat needed to maintain this temperature (subject to the limit imposed by the capacity of the component). The same principle applies to the control of relative humidity, wet-bulb and dewpoint temperatures by cooling coils and humidifiers. 3.6.1.3 Time Switch Profile
You must specify a percentage profile to indicate the schedule of operation for the controller. For most types of controlled variable this is interpreted as follows. When the profile has a value greater than 50% it will be ON, subject to other parameters that may override the time switch. Otherwise, it is OFF. The controller output is always off when the profile value is less than or equal to 50%. An exception to this rule applies in the case of air and water flow controllers. Here the profile has a modulating rather than just a switching role, the profile value being applied as a factor on the flow rate.
Select the variable that is to be monitored at the sensed node. This will be fed into the on/off (set point) or proportional control. 3.6.2.2 Radiant fraction
When the sensed variable is dry-bulb temperature, an input field is available to set the radiant fraction of sensed temperature. As an example, if the radiant fraction were set to 0.5, the sensor would effectively be sensing dry resultant temperaturei.e., operative temperature in still air conditions.
Tick this box to enable on/off control. This may operate in conjunction with, or as an alternative to, proportional control. On/off control must be enabled for direct acting heaters, radiators and chilled beams. 3.6.3.2 Set Point Variation
The set point for on/off control may be constant or variable. Select Constant or Timed as appropriate.
VE 6.4
ApacheHVAC
215
Deadband
Characteristic illustrated for High Sensor Input = OFF OFF Set point Sensed variable
Figure 3-3: On/off (set point) control characteristic 3.6.3.3 Set Point
Set Point defines the behavior of the switching signal generated by the controller as a function of the sensed variable when on/off control is used. The response characteristic for on/off control is shown in Figure 3-3 and Figure 3-12. A constant value for Set Point is entered as a number and a variable value by an absolute profile specifying the value of the set point throughout the year. The units in which the values are expressed must be appropriate to the variable being sensed, and when the set point is entered directly, the value must lie within the appropriate warning and error limits shown below: 3.6.3.4 Deadband
Deadband defines the range of sensed variable values over which switching occurs in on/off control. The response characteristic for on/off control is shown in Figure 3-3 and Figure 3-12. The deadband enables the program to model switching hysteresis. If it is specified as zero the control will switch between the ON and OFF states whenever the value of the sensed variable passes through the set point. If a non-zero deadband is specified, the control will change its state as the sensed variable rises through the upper end of the deadband or falls through the lower end of the deadband. 3.6.3.5 High Sensor Input
This parameter relates to on/off (set point) control and specifies whether the switching signal output by the controller is ON or OFF for high values of the sensed variable. The response characteristic for on/off control shown in Figure 3-3 and Figure 3-12 is drawn for the case where High Sensor Input set to OFF. When this parameter is set to ON the characteristic is inverted.
VE 6.4
ApacheHVAC
216
Heaters and humidifiers usually have High Sensor Input set to OFF so that the device switches off at high values of sensed temperature or humidity. Cooling coils, whether used for cooling or dehumidification, usually have High Sensor Input set to ON.
Tick this box to enable proportional control. Proportional control features are used within the ApacheHVAC system model to allow components to mimic the operation of real controls. Proportional control usually gives better quality control than on/off (set point) controli.e., it is generally more stable and provides better maintenance of the target value for the controlled variable. Proportional control is used to adjust the value of a controlled variable smoothly as a function of the value of a sensed variable. Examples of this type of control are the modulation of a VAV supply airflow rates and CAV supply temperatures.
Controlled variable Value at minimum signal
Proportional bandwidth
The midband for proportional control may be constant or variable (timed). Select Constant or Timed as appropriate. 3.6.4.3 Midband
The midband parameter specifies the value of the sensed variable at the center of the proportional band (see Figure 3-4 above). A constant value for midband is entered as a number. A variable value is provided by an absolute profile specifying the value of the midband throughout the year.
VE 6.4
ApacheHVAC
217
3.6.4.4
Proportional Bandwidth
The proportional bandwidth is the width of the band used for proportional control - that is, the movement in the sensed variable between the values that generate the maximum and minimum control signals. This proportional bandwidth is centered about the midband. The response characteristic for proportional control is shown in Figure 3-4 above, and further described using examples in relation to Figure 3-11. By way of illustration, if a heater coil is being controlled on outside air temperature, such that at an outside temperature of -1C requires an off heater temperature of 35C, and at 10C outside the off heater temperature is reduced to 28C, then the midband would be 4.5K (4.511/2=10,-1), and the proportional band would be 11K (10-(-1)=11). It should be noted that the value for the minimum control signal would be 35C, and for the maximum control signal, 28C. ApacheHVAC can model simple switching (on/off) control and ideal proportional control. Because ApacheHVAC simplifies the HVAC system it can model the 'ideal' translation of a control signal directly to the required change in a physical quantity. In this respect, ApacheHVAC proportional control is actually closer in reality to real PID and direct digital control than it is to real proportional control. In reality, to control the heat input from a heater coil, a sensor might be positioned somewhere in the system and configured to adjust the position of a valve which varies the flow of hot water through it. The controls engineer will choose a control system which gives the most precise match of control signal (measured temperature) to required condition (heat input). In a well designed control system, there will be a one to one correspondence. ApacheHVAC proportional controllers model this situation because a control signal can be translated directly into heat input or off-coil temperature according to a linear relationship, without any of the lag typically introduced by the water side of the system. 3.6.4.5 Maximum Change per Time Step
This parameter specifies the maximum fractional change that the controller can carry out in each simulation time step. The fraction is with respect to the overall range of control between the value at Max signal and the value at Min signal. This parameter provides a form of damping and should be adjusted to a lower value in situations where a closed-loop feedback between the sensor and controller may cause 'hunting'. The program will try to automatically compensate for this type of control instability, but it is advisable to take steps to avoid the problem arising. Never use a feedback loop to control a component when open loop could be used instead. When closedloop feedback control is essential or valuable, there are a number of precautions that will facilitate control stability: Ensure that the controlled components are not oversized or that the range of controlled values is no greater than is necessary to meet design conditions; Keep proportional bands as wide as is reasonable and appropriate; If possible, include a room in the loop (the mass of air and materials in a room provides very much slower response times than other components) Specify a small value for the 'maximum change per time step' (e.g. 0.05 to 0.2)
Note that the effect of the maximum change per time step value entered will vary depending on the time step. Thus if you change the time step you should also change the value entered here.
VE 6.4 ApacheHVAC 218
3.6.4.6
The value for minimum control signal applies to proportional control only. It specifies the value of the numerical control signal output when the sensed variable is at or below the lower end of the proportional band. The response characteristic for proportional control is shown in Figure 3-4 above, and further described using additional examples in relation to Figure 3-11. Example: A controller is sensing temperature in a room with a midband of 22C and a proportional bandwidth of 4K and the airflow at a node is to be controlled to 500 l/s when the room is at 20C and to 1500 l/s when it is at 24C. Here the value for minimum signal is 500 and the value for maximum signal is 1500. Note that the distinction between a direct acting and a reverse-acting proportional control is made by exchanging the value at minimum signal with the value at maximum signal. The value at minimum signal is generated for low values of the sensed variable and the value at maximum signal for high values of the sensed variable.
3.6.6 OR Connections
The effect of an OR connection to a controller with a sensor is to make the controller generate an ON switching signal if either its own on/off controller OR the signals from one or more other attached controllers is ON. To attach an OR connection click on the OR connection icon and drag a line from the controller generating the signal to the controller receiving the signal. OR connections can be applied to all controllers with sensors (independent, differential, or dependent), but not time switch controllers. OR connections do not override the Time Switch Profile for the controller. When the Time Switch Profile is OFF the switching signal is OFF. The signals from all OR connections are computed before combining the result with signals from any AND connections.
VE 6.4
ApacheHVAC
219
OR connections are less commonly used than AND connections. One application is in frost protection, where they can be used to detect when any one of a set of rooms falls below a given temperature threshold. OR connections attached to the current controller are listed in the dialog, and may be deleted using the Remove button.
Normally the only reason for using both the set point and proportional tick boxes on the same controller is in order to allow the signal for the set point to be modified by AND or OR connection. However, an exception applies in the case of radiators and chilled ceilings. If proportional control is used for these components the controller must have the set point box ticked, and its control parameters must be such as to give an ON signal when the device is scheduled to operate.
VE 6.4
ApacheHVAC
220
Start
Does the sensed variable in conjunction with the set point return an ON signal?
NO
YES
Does the current time fall within the Time Switch Profile?
YES
YES
NO
ON Control Signal
VE 6.4
ApacheHVAC
221
Flow rate is subject to a further type of control that does not apply to other controlled variables. Flow rate is not only switched between on and off states by the control profile it is modulated by it. Thus if the percentage flow controller has a value of 70% at a particular time, the flow value calculated from the control parameters will be multiplied by 0.7. This feature has been introduced to provide additional flexibility in flow specification. For other controlled variables, the Time Switch profile is interpreted as an on/off switch, being on when the profile has a value greater than 50% and off otherwise. This principle applies whether or not proportional control is used. Once a controller has been used to establish the flow rate at a node, the program feeds that information forwards and backwards along the air distribution path until it reaches a junction (i.e. it assumes the flow rate into any component equals the flow rate out, except at junctions). At junctions, the program must know the flow rates at all the connected nodes except one. It can then calculate the unknown flow from the known ones. In this way the program can calculate the flow rates at every point in the system, provided there are sufficient controllers appropriately positioned. It is usually sufficient to place flow controllers only at those nodes which are immediately upstream of rooms, and at one other node to establish the ratio of outside to recirculated air. From this, the program can work backwards through the system network calculating the flow rates elsewhere by addition and subtraction at junctions. In constant volume systems the ratio of outside air can be controlled without the use of a damper component by simply specifying the absolute value of flow rate at the outside air inlet. In variable air volume systems it is typically necessary to use a Damper set component in the fresh air inlet to control the percentage of outside air. At the node immediately downstream of a damper set, either percentage flow control for the outside air branch or a target dry-bulb temperature for the mixed air must be used to control the outside air ventilation rate (in as much as it exceeds the minimum setting in the damper). In some systems for example dual duct systems additional flow controllers are required to specify flows in the system branches. If flow rates cannot be calculated at all nodes, an error will be reported. For the full set of rules on setting flow rates see Appendix A: Rules for airflow specification.
VE 6.4
ApacheHVAC
222
Figure 3-6: Independent Time Switch Controllers (without and with an AND connection) This is the simplest type of controller. It controls a variable at a constant value at prescribed times (subject to physical feasibility and the optional addition of AND connections). When it is attached immediately downstream of a component such as a heating coil it controls the coil in such a way as to set the off-coil temperature, provided this is feasible given the on-coil condition, the airflow rate and the coils capacity. The term independent is used to denote that the controller feeds its signal directly into a component (in this case a preheat coil and a mixing damper set). Independent controllers generate two types of signal: a switching signal and a numerical signal. The switching signal turns the controlled device on or off and the numerical signal indicates the value to be set for the controlled variable. The switching signal is ON when the time switch profile is ON (subject to provisos detailed below). The numerical signal is the value of the parameter V at maximum signal, where V denotes the controlled variable. AND and OR connections attached as outputs from the controller may be used to feed its switching signal into other controllers. If AND connections are input to an independent time switch controller they affect the switching signal in the following way. The controller gives an ON signal when, and only when: and all the input AND connections (if any are present) are ON AND and OR connections only convey a switching signal, not a numerical signal. the time switch profile is ON
VE 6.4
ApacheHVAC
223
Figure 3-7: Example parameters for Time Switch Controller In the example shown in Figure 3-7 the switching signal will be ON at all times, provided the switching signal from the controller named Mixed-air < 53F = OFF (2-F deadband), which is coupled by an AND connection, is also ON. The numeric control signal will then be 53F. The independent time switch controller has been illustrated here first using temperature control as an example. When the controlled variable is airflow rate, as in Figure 3-8) two special conditions apply.
Figure 3-8: Time Switch Controller with Flow Rate as controlled variable
VE 6.4 ApacheHVAC 224
First, an airflow rate controller may be attached to any airflow path on the network, where it will have the effect of setting the flow to the numerical control signal. Second, the time switch profile has a special function in airflow control. Rather than being interpreted as ON (as denoted by a value greater than 50%) or OFF (other values), the profile is treated as a modulating function multiplying the numerical control signal. This feature can prove useful as a means of setting timevarying flow rates.
This type of controller responds to a variable sensed at a system node. In the case illustrated in Figure 3-9, the controller monitors room temperature and feeds its signal into a heating coil on the primary air supply to the room. After placing the controller, select the controlled node (indicated by an arrow), followed by the sensed node. The control parameters shown in Figure 3-10 are set up to provide proportional control. When the Time Switch Profile is on, the off-coil temperature is adjusted between 28C and 14C the values set for the parameters Dry-bulb temperature at minimum signal and Dry-bulb temperature at maximum signal as the room air temperature varies over a proportional band centered on 20C (the midband) and with a width of 2K (the proportional bandwidth). The control characteristic for proportional control is shown graphically in Figure 3-11.
VE 6.4
ApacheHVAC
225
Proportional bandwidth
In the preceding example the set-point control has been turned off in favor of proportional control. Set point (on/off) control is an alternative to proportional control in which the signal fed into the controlled device can take only two values: ON or OFF. The control characteristic for on/off control is shown in Figure 3-12.
On/off control signal ON
Deadband
Characteristic illustrated for High Sensor Input = OFF OFF Set point Sensed variable
Figure 3-12: On/off (set point) control characteristic The state of the on/off controller switches between ON and OFF as the sensed variable rises through the upper limit or falls through the lower limit of the deadband. Within the deadband the signal retains its current value. The characteristic gives rise to hysteresis: the value of the control signal in the deadband depends on the history of the sensed variable as well as its current value. The overall shape of the on/off characteristic is set by the parameter High Sensor Input. If this is OFF (as in Figure 3-12) the signal is OFF at high values of the sensed variable. If it is ON the characteristic is inverted. The on/off logical control signal is subject to modification by optional AND and OR connections feeding into it. These connections also govern the operation of the controller when proportional control is used. The controller gives an ON signal (and operates in proportional control mode) when, and only when: the time switch profile is ON and the on/off control signal, or at least one OR connection, is ON, or the on/off (set point) control is not ticked and all the input AND connections (if any are present) are ON AND and OR connections attached as outputs from the controller may be used to feed its switching signal into other controllers.
VE 6.4
ApacheHVAC
227
Figure 3-13: Plot of typical VAV cooling airflow control and SAT reset.
VE 6.4
ApacheHVAC
228
Figure 3-14: Controller inputs for typical VAV cooling airflow control.
Figure 3-15: Controller inputs for typical VAV heating airflow control.
VE 6.4
ApacheHVAC
229
Figure 3-16: Independent Differential Controller The independent differential controller takes as its input the difference between variables sensed at two system nodes. In other respects it behaves like an independent controller with sensor. After placing the controller, select the controlled node (indicated by an arrow), followed by the two sensed nodes. The order of selecting the sensed nodes is important: the input signal is the value at the node selected first minus the value at the node selected second. On the graphic the first-selected node is shown attaching to the control box below the second-selected node. This type of controller is used less often than the dependent differential controller. In the case illustrated in Figures 3-16 and 3-17, it senses the difference between flows sensed in two network branches and sets a third flow equal to this difference when it is positive.
VE 6.4
ApacheHVAC
230
Figure 3-18: Dependent Time Switch Controller (shown with both with input AND connection and output OR connection) This controller operates like the independent time switch controller, but is not directly attached to a component. Its purpose is to generate a switching signal to be fed into one or more other controllers via AND and OR connections. The control signal is a function of the profile and any input AND connections.
VE 6.4
ApacheHVAC
231
Figure 3-19: Dependent Controller with Sensor (with output AND connection) This controller operates like an independent controller with sensor but is not directly attached to a component. Its purpose is to generate a switching signal to be fed into one or more other controllers via AND and OR connections. The switching signal is a function of the profile, the sensed variable any input AND or OR connections. Proportional control is not an option with this type of controller, as it does not generate a numeric control signal.
VE 6.4
ApacheHVAC
232
In the example shown in Figure 3-20, the controller monitors outside dew-point temperature and gives an ON signal when it exceeds 56F. In this case, there is no deadband, as the control will not influence the outdoor air condition, and thus there will be no possibility of a feedback loop.
Figure 3-21: Dependent Differential Controller (with output AND connection) The dependent differential controller takes as its input the difference between variables sensed at two system nodes. In other respects it behaves like a dependent controller with sensor. A common use for this type of controller is to detect whether fresh air is warmer or cooler than return air as the basis for recirculation decisions. After placing the controller, select the two sensed nodes. The order of selecting the sensed nodes is important: The input signal is given by the value at the first node selected minus the value at the second node selected. In Figure 3-21, the first sensed node is shown attaching to the control box below the second sensed node. This will always be true, regardless of the lefthand vs. righthand orientation of the differential controller box. In the case illustrated in Figure 3-21 and the first of the two example control dialogs in Figure 3-22, the controller senses the difference between temperatures in the return and fresh air inlet ducts and returns an ON signal if the return air enthalpy is greater than the outside air enthalpy. This signal is fed, via an AND connection, into the damper set controlling outside air intake.
VE 6.4
ApacheHVAC
233
Figure 3-22: Example parameters for Dependent Differential Controllers: The first (top) generates an ON signal if Enthalpy Sensor 1 Enthalpy Sensor 2 = positive value greater than 0.01. This is typical of damper controls intended to introduce more than the minimum outside air only when it has a lower enthalpy than the return air. The second (bottom) example generates an ON signal if the value at the outdoor air
VE 6.4 ApacheHVAC 234
Temperature Sensor is greater than or equal to the value at a room temperature sensor 3 F. This is a typical control for mechanical fan systems in mixed-mode building that are intended to operate only when the conditions are unfavorable for natural ventilation (e.g., when the outside air is not at least 3F cooler than the room air). This second example also includes OR connections to dependent controllers with sensors meant to override it (providing an ON signal when this controller would otherwise not do so) if either the room temperature exceeds an elevated setpoint or a CO2 threshold, in either case suggesting that the windows are not open when they should be or that, despite favorable outdoor temperatures, there is not enough air movement to meet cooling or ventilation demand via the operable windows. Note that while the Setpoint value when sensing temperature (DBT, WBT, or DPT) will be expressed in K (indicating a differential) when in metric units mode, in IP units the differential will be expressed in F, as there is no differential IP unit for temperature.
VE 6.4
ApacheHVAC
235
Figure 4-1: Room component dialog, including facilities for selecting defined Room Units and examples of unit types (note that this is for illustration only, as it would be very unusual to place room units from all three categories in a single space within the model). Individual instances of a Room unit Type are indicated within the Room component dialog. The type must be defined before this action will be available for a given category of room unit. A Room component can represent any occupied or unoccupied 3D space in the model, including normal rooms or thermal zones, faade cavities, supply plenums, and heated or cooled ceiling or floor slabs. The user-defined types are effectively components sitting on a shelf, but not active until placed within a room component. Each time a room unit type is placed within a room component, an additional instance of that type is created. The room unit controllers below are thus specific to each separate instance of a particular room unit type.
VE 6.4 ApacheHVAC 236
Figure 4-2: Radiator control dialog with illustrative inputs for a fin-tube hydronic baseboard heater using set-point and set-back temperatures for thermostatic on/off control in occupied and unoccupied hours, a fixed supply water temperature, and proportional control of water flow rate to modulate the output of the device. In this case sensors have been located in the local room, however, they can be located in other spaces or outside of the building. 4.1.1.1 Reference
Enter a description of the controller. The reference is limited to 100 characters. It is for your use when selecting, organizing, and referencing any component or controllers within other component and
VE 6.4 ApacheHVAC 237
controller dialogs. These references can be valuable in organizing and navigating the system and when the system model is later re-used on another project or passed on to another modeler. Reference names should thus be informative with respect to differentiating similar equipment, components, and controllers. 4.1.1.2 Radiator type reference
Select a radiator device for placement in the room from the list of previously defined types. 4.1.1.3 Heat source
Select the reference of the previously defined heat source from list, which will serve the radiator placed in the room from the radiators list.
Enter the flow rate that corresponds to the maximum control signal from the controller. If no proportional control is to be used, enter the flow rate that occurs whenever this radiator is on. Note that for reverseacting proportional control where the sensed variable is room temperature (typical for heating devises), this value is lower than that in the water temperature at minimum control signal.
Warning Limits (l/s) Error Limits (l/s) 0.001 to 2.5 0.0 to 99.0
4.1.2.2
Enter the water temperature which corresponds to the maximum control signal from the controller. If no proportional control was specified, enter the temperature of the radiator supply water. Note that for reverse-acting proportional control where the sensed variable is room temperature (typical for heating devises), this value is lower than that in the water temperature at minimum control signal.
Warning Limits (C) Error Limits (C) 30.0 to 85.0 0.0 to 250.0
4.1.2.3
Specify the time switch profile that will be used to schedule the operation of the controller. 4.1.2.4 Sensor location
The sensor may be internal (contained in a room or on a surface in a room) or external. An external sensor would be the equivalent of a weather compensated system or outdoor temperature reset. Several radiators may use the same internal sensore.g., all rooms on the west faade of a building may be controlled by a single sensor. As would be appropriate for a hydronic loop in a conditioned slab, one surface temperature sensor per zone is available for use with on/off or proportional controls. The surface vs. zone location of the sensor is determined by selection of the sensed variable and tagging of the sensed surface within the Apache Thermal view. For more information on using surface temperature sensors, see section 3.3.2 Sensed variables. Select an appropriate sensor location.
VE 6.4
ApacheHVAC
238
4.1.2.5
Sensed variable
Select the variable that is to be used in the on/off (set point) control. Surface temperature is available as a sensed variable for use with on/off or proportional controls, as would be appropriate for a hydronic loop in a conditioned slab. The surface vs. zone location of the sensor is determined by selection of the sensed variable. The specific surface adjacency for the sensor location must also be tagged within the Apache Thermal view. For more information on using surface temperature sensors, see section 3.3.2 Sensed variables. Note: While Flow rate is on the Room Unit controller selection list of Sensed variables and does cause gpm or l/s units to be displayed, this sensed variable is not yet available for Room Unit controllers. 4.1.2.6 Radiant fraction
When the sensed variable is dry-bulb temperature, an input field is available to set the radiant fraction of sensed temperature. As an example, if the radiant fraction were set to 0.5, the sensor would effectively be sensing dry resultant temperaturei.e., operative temperature in still air conditions. Enter an appropriate value for a radiant fraction. 4.1.2.7 Set point variation
The set point for on/off control may be Constant or Variable. Select Constant or Timed as appropriate 4.1.2.8 Set point or variation profile
Enter a set point value when the set point is Constant or select a timed profile when the set point variation is timed. This can be a formula profile. 4.1.2.9 Deadband
Deadband defines the controller hysteresis or range of sensed variable values over which switching occurs in on/off control (see section 3.6.3.4). Enter an appropriate deadband value. 4.1.2.10 High sensor input (resulting on/off action)
This parameter relates to on/off (set point) control and specifies whether the switching signal output by the controller is ON or OFF for high values of the sensed variable. (See section 3.6.3.5). Enter the appropriate sensor input.
Tick the box next to this item to use proportional control of the water flow rate in the radiator. Then click on the item to enter and edit parameters for the proportional controller. If proportional control of water flow rate is not used, the water flow rate will be fixed at the value given in the Flow at Max Control Signal input.
VE 6.4 ApacheHVAC 239
4.1.3.2
Tick the box next to this item to use proportional control of the water temperature in the radiator. Then click on the item to enter and edit parameters for the proportional controller. If proportional control of water temperature is not used, the water temperature will be fixed at the value given in the Temp at Max Control Signal input. 4.1.3.3 Sensor location
The sensor may be internal (contained in a room or on a surface in a room) or external. An external sensor would be the equivalent of a weather compensated system or outdoor temperature reset. Several radiators may use the same internal sensore.g., all rooms on the west faade of a building may be controlled by a single sensor. As would be appropriate for a hydronic loop in a conditioned slab, one surface temperature sensor per zone is available for use with on/off or proportional controls. The surface vs. zone location of the sensor is determined by selection of the sensed variable and tagging of the sensed surface within the Apache Thermal view. For more information on using surface temperature sensors, see section 3.3.2 Sensed variables. Select an appropriate sensor location. This must be done separately for both Proportional Flow and Temperature controllers when they are included. 4.1.3.4 Sensed variable
Select the variable that is to be used in the proportional control. This must be done separately for both Proportional Flow and Temperature controllers when they are included. Surface temperature is available as a sensed variable for use with on/off or proportional controls, as would be appropriate for a hydronic loop in a conditioned slab. The surface vs. zone location of the sensor is determined by selection of the sensed variable. The specific surface adjacency for the sensor location must also be tagged within the Apache Thermal view. For more information on using surface temperature sensors, see section 3.3.2 Sensed variables. Note: While Flow rate is on the Room Unit controller selection list of Sensed variables and does cause gpm or l/s units to be displayed, this sensed variable is not yet available for Room Unit controllers. 4.1.3.5 Midband variation
The midband for proportional control may be constant or variablei.e., timed, scheduled, or determined by a formula profile (see section 3.6.4.2). Select Constant or Timed as appropriate. This must be completed for Proportional Flow and Temperature controllers when they are used. 4.1.3.6 Midband or variation profile
Enter a fixed midband value if Constant or select an appropriate midband variation profile if the variation is timed (see section 3.6.4.3). This must be completed for Proportional Flow and Temperature controllers when they are used. 4.1.3.7 Proportional bandwidth
The proportional bandwidth is the width of the band used for proportional controli.e., the range of, the sensed variable over which the proportional control will vary as bounded by maximum and minimum sensed values. This proportional bandwidth is centered about the midband (see section 3.6.4.4). Enter the bandwidth as appropriate.
VE 6.4 ApacheHVAC 240
This must be completed for Proportional Flow and Temperature controllers when they are used. 4.1.3.8 Maximum change per time step
This parameter specifies the maximum fractional change that the controller can carry out in each simulation time step. The fraction is with respect to the overall range of control between the value at Max signal and the value at Min signal (see section 3.6.4.5). Enter a value as needed to maintain stable operation of the unit. This must be complete for Proportional Flow and Temperature controllers when they are used. A good starting point is 0.2 to 0.3. If operation is unstable, reduce this value as needede.g., to 0.1 or 0.05. 4.1.3.9 Flow at Minimum Control Signal
When proportional Flow control is used, enter the water flow rate that corresponds to the minimum signal from the proportional controller. If no proportional Flow controller is specified, the value entered here will be ignored. The minimum control signal is generated when the sensed value is at or below the midband minus half the proportional band. 4.1.3.10 Temperature at Minimum Control Signal
When proportional Temperature control is used, enter the water temperature that corresponds to the minimum signal from the proportional controller. If no proportional controller was specified, the value entered here will be ignored. Note that the minimum control signal is generated when the sensed value is at or below the midband minus half the proportional band. 4.1.3.11 Radiant fraction (for sensor)
When the sensed variable is dry-bulb temperature, an input field is available to set the radiant fraction of temperature sensor. As an example, if the radiant fraction were set to 0.5, the sensor would effectively be sensing dry resultant temperaturei.e., operative temperature in still air conditions. Enter an appropriate value for a radiant fraction. 4.1.3.12 Orientation
When the sensed variable is Solar radiation, enter the orientation or azimuth of the surface containing the sensor in degrees (0 deg = North and 180 deg = South) 4.1.3.13 Slope
When the sensed variable is Solar radiation, enter the slope (angle from horizontal) of the surface containing the sensor in degrees (0 deg = horizontal and 90 deg = vertical) 4.1.3.14 AND References
Add/Remove logical AND connections to other controllers as appropriate (see section 3.6.5). 4.1.3.15 OR Reference
VE 6.4
ApacheHVAC
241
VE 6.4
ApacheHVAC
242
4.2.1.1
Reference name
Enter a descriptive name for the controller. The reference is limited to 100 characters. It is for your use when selecting, organizing, and referencing any component or controllers within other component and controller dialogs. These references can be valuable in organizing and navigating the system and when the system model is later re-used on another project or passed on to another modeler. Reference names should thus be informative with respect to differentiating similar equipment, components, and controllers.
4.2.2 Settings
4.2.2.1 Chilled Ceiling Type Reference
Select a chilled ceiling device for placement in the room from the list of previously defined types. 4.2.2.2 Chiller
Select the chilled water loop that will serve the chilled ceiling device.
Enter the flow rate that corresponds to the maximum control signal from the controller. If no proportional control is to be used, enter the flow rate that occurs whenever this chilled ceiling device is on. Note that for direct acting proportional control where the sensed variable is room temperature (typical for a cooling device), this value is higher than that in the water temperature at minimum control signal, and for reverse-acting control, it is lower.
Warning Limits (l/s) Error Limits (l/s) 0.001 to 2.5 0.0 to 99.0
4.2.3.2
Enter the water temperature that corresponds to the maximum control signal from the proportional controller. If no proportional controller was specified, enter the temperature of the chilled ceiling supply water. Note that for direct acting proportional control where the sensed variable is room temperature (typical for a cooling device), this value is higher than that in the water temperature at minimum control signal, and for reverse-acting control, it is lower. 4.2.3.3 Time switch profile
Specify the time switch profile that will be used to schedule the operation of the controller. 4.2.3.4 Sensor location
The sensor may be internal (contained in a room or on a surface in a room) or external. An external sensor would be the equivalent of a weather compensated system or outdoor temperature reset. Several chilled ceiling panel arrays may use the same internal sensore.g., chilled ceilings in all rooms on the west faade of a building may be controlled by a single sensor. As would be appropriate for a hydronic loop in a conditioned slab, one surface temperature sensor per zone is available for use with on/off or proportional controls. The surface vs. zone location of the sensor is determined by selection of the sensed variable and
VE 6.4
ApacheHVAC
243
tagging of the sensed surface within the Apache Thermal view. For more information on using surface temperature sensors, see section 3.3.2 Sensed variables. Select an appropriate sensor location. 4.2.3.5 Sensed variable
Select the variable that is to be used in the on/off (set point) control. Surface temperature is available as a sensed variable for use with on/off or proportional controls, as would be appropriate for a hydronic loop in a conditioned slab. The surface vs. zone location of the sensor is determined by selection of the sensed variable. The specific surface adjacency for the sensor location must also be tagged within the Apache Thermal view. For more information on using surface temperature sensors, see section 3.3.2 Sensed variables. Note: While Flow rate is on the Room Unit controller selection list of Sensed variables and does cause gpm or l/s units to be displayed, this sensed variable is not yet available for Room Unit controllers. 4.2.3.6 Radiant fraction
When the sensed variable is dry-bulb temperature, an input field is available to set the radiant fraction of sensed temperature. As an example, if the radiant fraction were set to 0.5, the sensor would effectively be sensing dry resultant temperaturei.e., operative temperature in still air conditions. Enter an appropriate value for a radiant fraction. 4.2.3.7 Set point variation
The set point for on/off control may be Constant or Variable. Select Constant or Timed as appropriate 4.2.3.8 Set point or variation profile
Enter a set point value when the set point is Constant or select a timed profile when the set point variation is timed. This can be a formula profile. 4.2.3.9 Deadband
Deadband defines the controller hysteresis or range of sensed variable values over which switching occurs in on/off control (see section 3.6.3.4). Enter an appropriate deadband value. 4.2.3.10 High sensor input (resulting on/off action)
This parameter relates to on/off (set point) control and specifies whether the switching signal output by the controller is ON or OFF for high values of the sensed variable. (See section 3.6.3.5). Enter the appropriate sensor input.
VE 6.4
ApacheHVAC
244
4.2.4.1
Tick the box next to this item to use proportional control of the water flow rate in the chilled ceiling (panel, hydronic loop, etc.). Then click on the item to enter and edit parameters for the proportional controller. If proportional control of water flow rate is not used, the water flow rate will be fixed at the value given in the Flow at Max Control Signal input. 4.2.4.2 Proportional Temperature Controller
Tick the box next to this item to use proportional control of the water temperature in the chilled ceiling (panel, hydronic loop, etc.). Then click on the item to enter and edit parameters for the proportional controller. If proportional control of water temperature is not used, the water temperature will be fixed at the value given in the Temp at Max Control Signal input. 4.2.4.3 Sensor location
The sensor may be internal (contained in a room or on a surface in a room) or external. An external sensor would be the equivalent of a weather compensated system or outdoor temperature reset. Several chilled ceiling panel arrays or radiant slabs may use the same internal sensore.g., chilled surfaces in all rooms on the west faade of a building may be controlled by a single sensor. As would be appropriate for a hydronic loop in a conditioned slab, one surface temperature sensor per zone is available for use with on/off or proportional controls. The surface vs. zone location of the sensor is determined by selection of the sensed variable and tagging of the sensed surface within the Apache Thermal view. For more information on using surface temperature sensors, see section 3.3.2 Sensed variables. Select an appropriate sensor location. This must be done separately for both Proportional Flow and Temperature controllers when they are included. 4.2.4.4 Sensed variable
Select the variable that is to be used in the proportional control. This must be done separately for both Proportional Flow and Temperature controllers when they are included. Surface temperature is available as a sensed variable for use with on/off or proportional controls, as would be appropriate for a hydronic loop in a conditioned slab. The surface vs. zone location of the sensor is determined by selection of the sensed variable. The specific surface adjacency for the sensor location must also be tagged within the Apache Thermal view. For more information on using surface temperature sensors, see section 3.3.2 Sensed variables. Note: While Flow rate is on the Room Unit controller selection list of Sensed variables and does cause gpm or l/s units to be displayed, this sensed variable is not yet available for Room Unit controllers. 4.2.4.5 Midband variation
The midband for proportional control may be constant or variablei.e., timed, scheduled, or determined by a formula profile (see section 3.6.4.2). Select Constant or Timed as appropriate. This must be completed for Proportional Flow and Temperature controllers when they are used. 4.2.4.6 Midband or variation profile
Enter a fixed midband value if Constant or select an appropriate midband variation profile if the variation is timed (see section 3.6.4.3). This must be completed for Proportional Flow and Temperature controllers when they are used.
VE 6.4
ApacheHVAC
245
4.2.4.7
Proportional bandwidth
The proportional bandwidth is the range of, the sensed variable over which the proportional control will vary as bounded by maximum and minimum sensed values. This proportional bandwidth is centered about the midband (see section 3.6.4.4). Enter the bandwidth as appropriate. This must be completed for Proportional Flow and Temperature controllers when they are used. 4.2.4.8 Maximum change per time step
This parameter specifies the maximum fractional change that the controller can carry out in each simulation time step. The fraction is with respect to the overall range of control between the value at Max signal and the value at Min signal (see section 3.6.4.5). Enter a value as needed to maintain stable operation of the unit. This must be complete for Proportional Flow and Temperature controllers when they are used. A good starting point is 0.2 to 0.3. If operation is unstable, reduce this value as needede.g., to 0.1 or 0.05. 4.2.4.9 Flow at Minimum Control Signal
When proportional Flow control is used, enter the water flow rate that corresponds to the minimum signal from the proportional controller. If no proportional Flow controller is specified, the value entered here will be ignored. The minimum control signal is generated when the sensed value is at or below the midband minus half the proportional band. 4.2.4.10 Temperature at Minimum Control Signal
When proportional Temperature control is used, enter the water temperature that corresponds to the minimum signal from the proportional controller. If no proportional controller was specified, the value entered here will be ignored. Note that the minimum control signal is generated when the sensed value is at or below the midband minus half the proportional band. 4.2.4.11 Radiant fraction (for sensor)
When the sensed variable is dry-bulb temperature, an input field is available to set the radiant fraction of temperature sensor. As an example, if the radiant fraction were set to 0.5, the sensor would effectively be sensing dry resultant temperaturei.e., operative temperature in still air conditions. 4.2.4.12 Orientation
When the sensed variable is Solar radiation, enter the orientation or azimuth of the surface containing the sensor in degrees (0 deg = North and 180 deg = South) 4.2.4.13 Slope
When the sensed variable is Solar radiation, enter the slope (angle from horizontal) of the surface containing the sensor in degrees (0 deg = horizontal and 90 deg = vertical) 4.2.4.14 AND References
Add/Remove logical AND connections to other controllers as appropriate (see section 3.6.5). 4.2.4.15 OR Reference
VE 6.4
ApacheHVAC
246
Figure 4-4: Direct-acting heater/cooler control with illustrative inputs. The illustrative inputs in the Direct-acting heater/cooler control in Figure 4-4 proportional provide both heating and cooling at opposite ends of a continuous control band (heating operation at Min signal and gradual transition to cooling operation at Max signal). In this example, Set point control is effectively forced to ON by using High-sensor = Off and a very high value for the set point. Thus the Time Switch schedule and the Proportional Control can fully determine the operation.
VE 6.4
ApacheHVAC
247
4.3.1 Settings
4.3.1.1 Reference
Enter a description of the controller. The reference is limited to 100 characters. It is for your use when selecting, organizing, and referencing any component or controllers within other component and controller dialogs and in the component browser tree. These references can be valuable in organizing and navigating the system and when the system model is later re-used on another project or passed on to another modeler. Reference names should thus be informative with respect to differentiating similar equipment, components, and controllers. 4.3.1.2 Heater (cooler)
Select the reference of a previously defined direct acting heater/cooler type for placement in the room from the direct acting heaters list.
Enter the heat (or cooling, as a negative value) output that corresponds to the maximum control signal from the controller. Note that for direct acting proportional control this value is greater than that in the Output at minimum control signal' field, and for reverse acting it is smaller. 4.3.2.2 Time switch profile
Specify the time switch profile that will be used to schedule the operation of the controller. 4.3.2.3 Sensor location
The sensor may be internal (contained in a room or on a surface in a room) or external. An external sensor would be the equivalent of a weather compensated system or outdoor temperature reset. Several directacting heater/coolers may use the same internal sensore.g., heater/coolers in all rooms on the west faade of a building or all radiant slab zones associated with a larger space may be controlled by a single sensor. As would be appropriate for a hydronic loop in a conditioned slab, one surface temperature sensor per zone is available for use with on/off or proportional controls. The surface vs. zone location of the sensor is determined by selection of the sensed variable and tagging of the sensed surface within the Apache Thermal view. For more information on using surface temperature sensors, see section 3.3.2 Sensed variables. Select an appropriate sensor location. 4.3.2.4 Sensed variable
Select the variable that is to be used in the on/off (set point) control. 4.3.2.5 Radiant fraction
When the sensed variable is dry-bulb temperature, an input field is available to set the radiant fraction of sensed temperature. As an example, if the radiant fraction were set to 0.5, the sensor would effectively be sensing dry resultant temperaturei.e., operative temperature in still air conditions. Enter an appropriate value for a radiant fraction.
VE 6.4 ApacheHVAC 248
4.3.2.6
The set point for on/off control may be Constant or Variable. Select Constant or Timed as appropriate 4.3.2.7 Set point or variation profile
Enter a set point value when the set point is Constant or select a timed profile when the set point variation is timed. This can be a formula profile. 4.3.2.8 Deadband
Deadband defines the controller hysteresis or range of sensed variable values over which switching occurs in on/off control (see section 3.6.3.4). Enter an appropriate deadband value. 4.3.2.9 High sensor input (resulting on/off action)
This parameter relates to on/off (set point) control and specifies whether the switching signal output by the controller is ON or OFF for high values of the sensed variable. (See section 3.6.3.5).
Tick the box next to this item to use proportional control of the output. If proportional control is not used, the output will be fixed at the value set in the Output at Max Control Signal field. 4.3.3.2 Sensor location
The sensor may be internal (contained in a room or on a surface in a room) or external. An external sensor would be the equivalent of a weather compensated system or outdoor temperature reset. Several radiators may use the same internal sensore.g., all rooms on the west faade of a building may be controlled by a single sensor. As would be appropriate for a hydronic loop in a conditioned slab, one surface temperature sensor per zone is available for use with on/off or proportional controls. The surface vs. zone location of the sensor is determined by selection of the sensed variable and tagging of the sensed surface within the Apache Thermal view. For more information on using surface temperature sensors, see section 3.3.2 Sensed variables. 4.3.3.3 Sensed variable
Select the variable that is to be fed into the proportional control. Surface temperature is available as a sensed variable for use with on/off or proportional controls, as would be appropriate for a hydronic loop in a conditioned slab. The surface vs. zone location of the sensor is determined by selection of the sensed variable. The specific surface adjacency for the sensor location must also be tagged within the Apache Thermal view. For more information on using surface temperature sensors, see section 3.3.2 Sensed variables. Note: While Flow rate is on the Room Unit controller selection list of Sensed variables and does cause gpm or l/s units to be displayed, this sensed variable is not yet available for Room Unit controllers.
VE 6.4
ApacheHVAC
249
4.3.3.4
Midband variation
The midband for proportional control may be constant or variablei.e., timed, scheduled, or determined by a formula profile (see section 3.6.4.2). Select Constant or Timed as appropriate. 4.3.3.5 Midband or variation profile
Enter a fixed midband value if Constant or select an appropriate midband variation profile if the variation is timed (see section 3.6.4.3). 4.3.3.6 Proportional bandwidth
The proportional bandwidth is the range of, the sensed variable over which the proportional control will vary as bounded by maximum and minimum sensed values. This proportional bandwidth is centered about the midband (see section 3.6.4.4). Enter the bandwidth as appropriate. 4.3.3.7 Maximum change per time step
This parameter specifies the maximum fractional change that the controller can carry out in each simulation time step. The fraction is with respect to the overall range of control between the value at Max signal and the value at Min signal (see section 3.6.4.5). Enter a value as needed to maintain stable operation of the unit. This must be complete for Proportional Flow and Temperature controllers when they are used. A good starting point is 0.2 to 0.3. If operation is unstable, reduce this value as needede.g., to 0.1 or 0.05. 4.3.3.8 Output at Minimum Control Signal
When proportional control is used, enter the output (heating as a positive value or cooling as a negative value) that corresponds to the minimum signal from the proportional controller. If no proportional control is specified, the value entered here will be ignored. The minimum control signal is generated when the sensed value is at or below the midband minus half the proportional band. 4.3.3.9 Radiant fraction (for sensor)
When the sensed variable is dry-bulb temperature, an input field is available to set the radiant fraction of temperature sensor. As an example, if the radiant fraction were set to 0.5, the sensor would effectively be sensing dry resultant temperaturei.e., operative temperature in still air conditions. 4.3.3.10 Orientation
When the sensed variable is Solar radiation, enter the orientation or azimuth of the surface containing the sensor in degrees (0 deg = North and 180 deg = South) 4.3.3.11 Slope
When the sensed variable is Solar radiation, enter the slope (angle from horizontal) of the surface containing the sensor in degrees (0 deg = horizontal and 90 deg = vertical) 4.3.3.12 AND References
Add/Remove logical AND connections to other controllers as appropriate (see section 3.6.5). 4.3.3.13 OR Reference
Add/Remove logical OR connections to other controllers as appropriate (see section 3.6.6). VE 6.4 ApacheHVAC 250
HVAC Wizard
Figure 5-1: HVAC Wizard page 1 5.1.1.1 Create New System Select this to create a new system
VE 6.4
ApacheHVAC
251
5.1.1.2
5.1.1.3
Next Select to view next page in the HVAC Wizard Cancel Select to exit from the HVAC Wizard without opening or creating a HVAC system
5.1.1.4
Figure 5-2: HVAC Wizard New system page 2 Select type of system required from the list of available systems.
VE 6.4
ApacheHVAC
252
5.1.3.1
Add Zone
Click to add rooms to the HVAC system. Choose the required room from the drop down list. Note that this approach should not be used for systems that will be multiplexed: The multiplex structure provides stacked duplicates of all components and controllers on the original base layer in the multiplexed region of the HVAC network (see section 6. Multiplexing HVAC System Networks). 5.1.3.2 Reset
Click to reset the HVAC system to the starting single zone system 5.1.3.3 Finish
VE 6.4
ApacheHVAC
253
5.1.4
Figure 5-4: Recent Systems view within the HVAC Wizard. This dialog shows recently used, modified, or opened system models in the order in which they were accessed. These files may be in any combination of currently available folders. Select a system to open and click Finish. If the system selected is from a previous project or is to be significantly modified, it is advisable to proceed from here to Save As before making any changes.
VE 6.4
ApacheHVAC
254
Figure
6-1:
Non-
VE 6.4
ApacheHVAC
255
Figure 6-2: Equivalent ApacheHVAC network with Multiplex. The image on the right is depicting the additional layers that are effectively hidden under the currently selected Display Layer.
Step 1: Position the green multiplex box at the bottom left corner of the area of network that you wish to multiplex.
Step 2: Holding down the left mouse button drag the green multiplex box from the bottom left to the top right of the desired multiplex region and release the button.
VE 6.4
ApacheHVAC
256
VE 6.4
ApacheHVAC
257
Step 3: Once the rectangular boundary for the multiplex region of the system has been dragged over the network components, the Create Multiplex dialog will appear.
Rooms or thermal zones in the model are assigned to multiplex layers either by adding layers and manually selecting the spaces from the Principal Room drop-down list on each layer or by using the Assign from Room Group feature. These are described in more detail under Create Multiplex, below.
VE 6.4
ApacheHVAC
258
Step 4: Once a multiplex has been created, the network components and controllers can be populated with input values appropriate to the zones and desired control functions on each layer. Calculated flow rates, set points, cooling coil capacities, reference formula profiles, etc. can be entered into the network controllers layer by layer (Local editing), in all currently selected layers (Global editing), or pasted from a spreadsheet into a range of selected layers via a tabular Data Table edit view (Global editing). For autosizing of values within multiplexed components and controllers, see the System Prototypes & Sizing section of this User Guide.
VE 6.4
ApacheHVAC
259
Figure 6-3: Disallowed use of connector segments through a multiplex and between multiplexes Figure 6-3 provides examples of network branches consisting solely of connecting segments that are not permitted within a multiplex. In cases such as that shown on the left, either re-route the connectors around the anticipated multiplex region or move the controller box downwards so that the multiplex with not overlap the upper path. Direct connections between multiplexes consisting solely of connecting
segments (straight or elbow), such as illustrated on the right-hand side of this figure, are not permitted. The network must be revised so that there is a junction or other component between the multiplexes.
VE 6.4
ApacheHVAC
260
Note: It will be common to have multiple-layer instances of a controller pointing to one component control node. In such cases, the controller will compete for or vote on the value of the controlled variable at every simulation time step. The value that prevails depends upon the controlled variable and type of component being controlled. For example, while the highest temperature will prevail in the case of a heating coil, the lowest temperature will prevail for a cooling coil. Warning: Where multiple airflow controls are present on one branch, these must all point to the same node if their operation will ever compete for control. An attempt to simultaneously control airflow from two different nodes on a single branch will result in an over-constrained flow.
6.2.1 Description
Enter a name and description here to make it easier to identify the multiplex and manage complex systems.
6.2.3 Layers
Assign from Room Group, as described the section dedicated to that below, is the most efficient way to add and populate the correct number of layers in a system multiplex. Alternatively, simply select the number of layers to be added to or inserted into the multiplex, then click Insert Layer (new layers are inserted at the selected layer) or Add Layer (layers are appended to the bottom of the list). Select layers then click Delete Layers to remove them from the list (note it is not possible to delete all layers from a multiplex) The Ctrl and Shift keys are used to add or remove individual layers to or from the current selection set and to hold the view from scrolling when there are more layers than can be viewed at once. 6.2.3.1 Lock Layer Selection
When multiple layers are selected (selection must be set while in Global Edit mode) tick Lock Layer Selection to avoid accidentally editing an unselected layere.g., after switching layers on the toolbar. The locked state applies to both Global and Local edit modes.
VE 6.4
ApacheHVAC
262
When including more than one room component on each multiplex layer, the principal Room is typically the occupied space with which a thermostat or other sensors and controls are associated. Example 1: It is common to have a return air (RA) plenum void in commercial spaces. This should be modeled as a separate thermal zone over top of all of the zones it serves. There may, for example, be one plenum for each floor of the building. These RA plenums would be represented by a non-principal room component directly downstream of the occupied space on all multiplex layers. However, the Principal Room component on each layer will typically be assigned a different space in the model. Therefore, if there were one RA plenum for entire 1st floor, it would need to be associated with all occupied thermal zones on that floor, and thus the same RA plenum space in the model should be assigned to the plenum room components on each of the layers that contain a room on the first floor that has a return-air grill. If there are spaces on the first floor in this example that have supply air and either a ducted return or no return (perhaps they are exhausted), they would not be coupled with the RA plenum. For layers assigned to these spaces, the RA plenum component should be set as an Adiabatic duct.
VE 6.4
ApacheHVAC
263
Example 2: There may be a principal room that contains a thermostat (sensors and controllers) and an adjacent room, such as a lavatory, that draws transfer air from the principal room and has no thermostat or other sensors associated with it. There must, however, be means of determining the airflow through it, even if the flow is intentionally set to zero. Typically, such rooms will have a path to either an exhaust fan or a return fan. This will draw air from an adjacent space, as in the lavatory in the illustration to the right. As it is very unlikely that there would be a lavatory or similar space drawing transfer air adjacent to the Principal Room on every layer, this non-principal room component would be set as an Adiabatic duct on all layers for which it is to remain unused. Example 3: In the case of an underfloor air distribution (UFAD) system, each layer would typically include the UFAD supply plenum, an occupied zone, a stratified zone, and possibly also a return-air (RA) plenum. The occupied spaces would normally be the Principal Room on each layer. As the UFAD plenum would be before this on the network, the component representing the occupied zone on the network would need to be changed from a nonprincipal room to the Principal Room for all layers, as described above. As with the RA plenum in Example 1, each UFAD supply plenum serving more than one zone would be assigned to the designated UFAD plenum component on more multiple layers (the same layers as the occupied zones it serves). For occupied zones served by the UFAD plenum, there would be a corresponding stratified zone assigned to a non-principal room component downstream of the Principal Room. If there is an RA plenum, this would be yet another non-principal room downstream of the stratified zone. If there are spaces receiving supply air from the same airside system but not via the UFAD plenum, the UFAD plenum would be set to Adiabatic on those layers. Similarly, if those or other spaces were to be fully mixed zones using overhead diffusers, the stratified zone room component would be set to Adiabatic on those layers.
VE 6.4
ApacheHVAC
264
Select a Grouping Scheme and Room Group then click the OK button to assign each room or thermal zone in the selected Group as a Principal Room on a multiplex layer. If there are more rooms in the group than layers in the multiplex, the option is given to create layers for each additional room. This is an efficient way to add layers.
Click Yes to add the required number of layers. This is an efficient way to add layers to a multiplex. Click No to assign the rooms from the group to just the existing layers in the multiplex. When the OK button is clicked to complete multiplex creation, the Editing mode and layer selection will be reflected in the multiplex toolbar and subsequent edits.
VE 6.4
ApacheHVAC
265
Room(s) assigned The column of check boxes at the right-hand side of the Create/Edit Multiplex dialog indicates whether or not all Room components on a given multiplex layer have been assigned. The check boxes are not user-editable, but will include a check mark when assignments are complete for a layer. Assigning an Adiabatic duct rather than an actual space in the model to a Room component does count as an assignment.
6.3.1.1
Edit Multiplex
This button opens the Edit Multiplex dialog. 6.3.1.2 Display Layer
The currently active layer is displayed here. This can be identified by layer number and principal room. It is the layer that one can be altered in Local Edit mode and is the layer that will be viewed and serves as the Global Edit interface (prior to entering the Data Table edit view) when in Global Edit mode. Toggle through layers using the arrow buttons or expand the dropdown to select a layer from the list. The current display layer can be changed while a room, component, or controller dialog is active, and the contents of that dialog will update to reflect the newly selected layer. 6.3.1.3 Edit Mode
Choose between Local or Global Editing. Local Edit Mode edits apply only to the current Display Layer. Global Edit Mode edits apply to all currently selected layers, as shown in the Create/Edit multiplex dialog and on the multiplex toolbar.
When multiple layers are selected (selection must be set while in Global Edit mode) tick Lock Layer Selection to avoid accidentally editing an unselected layer. The locked state will apply to both Global and Local edit modes. When cycling through layers on the multiplex toolbar while the selection is locked, a warning will be displayed if any locked layer is selected. The user has the option to unlock that layer or revert to the previously selected current display layer.
VE 6.4 ApacheHVAC 266
room unit exists in the rooms on the other layers). Clicking OK in a Room Unit controller when in Global Edit mode will apply not only newly edited values but ALL inputs and settings in that dialog to all corresponding room unit controllers. In the Room dialog, the column to the left of the room units description indicates the unit type for each particular room unit instance in that room. This type plays an important role: Whenever a room unit is selected for editing or deleting while in Global Edit mode, it is associated with corresponding room units in each of the other selected layers by means of its type and position within the ordered list of units of that type. For example, editing the second instance of radiator type Rad1_14-kW in the principal room on the display layer would result in the edits being applied to the second radiator of type Rad1_14-kW within the principal room on each currently selected layer in the multiplex. 6.4.3.1 Copying only modified parameters
As of version 6.3, only those parameters just modified on the display layer to be copied to the matching Room units (if any) in all selected layers when OK is clicked.
Figure 6-4: In Global Edit mode there are two OK buttons for multiplexed Room unit controller dialogs, as shown here. OK & Copy All replicates the data in all the controller fields on the display layer to controllers for corresponding room units on other currently selected layers, whereas OK replicates only the data that has just been modified and not yet saved.
To select multiple variables for tabular editing, hold the Shift key and select the desired variables; then click the Multiple Edit button. This opens a data table displaying the values for the selected parameter(s) and/or variable(s) of the component or controller on each selected layer.
VE 6.4
ApacheHVAC
268
Figure 6-5: Illustration of Multiple Edit function in the dialog of a multiplexed component or controller
VE 6.4
ApacheHVAC
269
VE 6.4
ApacheHVAC
270
Figure 6-6: Illustration of using copy & paste from a spreadsheet to tabular edit view
Figure 6-7: Copy & paste from a CSV file to tabular edit view Note: If the Paste is performed without first clicking on any cell in the Data Table, and multiple variables have been selected for inclusion in the Data Table view, the copied values will be assigned to the last variable column (at the right side of the table). The paste will begin with the current Display Layer (row highlighted in yellow) and continue downwards, entering new values on each layer up to the total number of values present in the copied selection set. Note: It is possible to paste numeric or text characters. However, any pasted text must exactly match the available options for that input (e.g., Profile names must exactly match the names of available profiles in the ApPro database; Boiler names must exactly match those defined in the Heat Sources dialog; etc.). Note: Tabular Editing of Room Unit controller parameters and input data is not yet supported. Room Unit controllers should be edited in Local Edit mode with just one exception: Use Global Edit mode when the intent is to apply ALL settings within a particular Room Unit controller to ALL other controllers for that unit Type within the currently selected Rooms.
VE 6.4
ApacheHVAC
271
Figure 6-8: Node numbering in a multiplexed system Node numbers are not always sequential across multiplex boundaries. This is merely an artifact of how the multiplexed network is handled by the software, and may change in future versions. As viewed either in Vista Results or in an error message, node numbers within a multiplexed ApacheHVAC network are numbered 1, 2, 3, as in a normal network, but with the layer number appended to indicate the layere.g., the nodes on layer zero are 1/0, 2/0, 3/0, and on layer 1 are 1/1, 2/1. 3/1, and on layer 2 are 1/2, 2/2, 3/2,.and so forth.
VE 6.4
ApacheHVAC
272
Note: Some non-multiplexed nodes may be numbered 1/ , with layer zero being assumed. This is most likely to be seen in a message regarding insufficient flow definition, over-constrained flow, or similar.
Figure 6-9: When de-multiplexing or deleting a multiplex, a pop-up dialog requires a choice between deleting the entire multiplex and all items within it, or simply de-multiplexing. 6.7.1.1 Delete multiplex
The multiplex is removed and all components and controllers within the multiplex are completely deleted from the network. 6.7.1.2 De-multiplex
The multiplex is removed but the current Display Layer is retained in the network (on layer zero). This is the default action. Prior to de-multiplexing, check the currently selected layer if you intend to retain a layer containing a particular set of inputs to components and controllers.
VE 6.4
ApacheHVAC
273
7.1 Overview
Pre-defined prototype ApacheHVAC systems can be imported and autosized at both the zone and system levels. These two levels of loads analysis and autosizing can also be applied successfully to a broad range of user-modified variants of the pre-defined prototype systems. All systems, including any user-defined configuration, can be autosized with respect to system coils, fans, water loops, and plant equipment. For pre-defined systems and variants thereof, the autosizing process sizes a broad range of system elements in two stagesfirst at the room/zone level, then at the system/plant levelwith opportunity for user intervention between the two. ASHRAE Loads calculations are linked to target ApacheHVAC systems for both stages of the sizing process: Zone-level loads and sizing must be completed either manually or through the autosizing procedure described below. The resulting values for airflows and other controller settings must be assigned to the HVAC system in order for the spaces to be adequately conditioned. System-level loads and sizing, which applies to coils, fans, water loops, chillers, DX cooling, boilers, heat pumps, and other heat sources, must be completed in order to appropriately scale equipment capacities and performance data to obtain appropriate performance and energy consumption (unless the equipment sizing/capacities are otherwise manually set).
While any pre-defined prototype system can be modified without losing autosizing capabilities, retaining the zone-level autosizing capability requires maintaining pre-defined controller applications, controller reference name prefix with colon (e.g., MC4: . ), and relationships to the Loads Data spreadsheet for each system. The use of the Loads Data spreadsheet is further described below. System-level autosizing for coils, fan components, DX Cooling, HW and CHW loops, Heat transfer loops, boilers, chillers, heat pumps, and most other heating and cooling sources that see a load during the sizing run, applies to all ApacheHVAC systems, regardless of how and when they were created.
zone-level heating and cooling load oversizing factors zone-level airflow for VAV boxes, fan-coil units, fan-powered boxes, active chilled beams, etc. outside-air ventilation rates as well as CO2 sensor control thresholds, where DCV is employed exhaust airflow and inter-zonal transfer airflows (typically as make-up air for exhausted air) reheat coil leaving air temperatures and flow rates radiator and chilled ceiling panel water flow rates (as of version 6.5) outside-air economizer damper minimum flow rates (incl. optional ASHRAE 62.1 calculations) outside-air economizer dry-bulb temperature high limits* energy recovery engagement, sensible and latent effectiveness, and device power* coil leaving air temperatures, temperature resets, and zone humidity control*
ApacheHVAC 274
For prototype systems, the zone-level autosizing process provides means of engaging or disengaging system features, such as outside air economizers and airside energy recovery, from within the System Parameters dialog, in a addition to manually changing these within the Loads Data spreadsheet for each system or within the ApacheHVAC airside network itself. The controllers in pre-defined systems also use pre-defined control profiles (which you may also use as you see fit). This allows system-operating schemes for unoccupied hourse.g., temperature setback only, setback with fan cycling, or setback with fan cycling but no outside airto be selected along with system schedules and setpoints. While these parameters and operating schemes can be manually changed, the dialogs provide basic inputs and automation for pre-defined systems. The System Schedules dialog (see additional description below) sets room heating and cooling set points, operating schedules, including start-up and after-hours operation, and the control scheme to be used during unoccupied hours. It does so via automated editing of a pre-defined set of profiles that are referenced within the prototype systems and also applied to Room Data in the Apache Thermal view. The application of heating and cooling set points from the System Schedules dialog to Room Data for each conditioned space provides the fundamental basis for autosizing. The System Parameters dialog (see additional description below) provides initial inputs for many of the zone- and system-level parameters in the list above, such as zone load oversizing factors and both airhandler and zone coil leaving air temperatures, as inputs to the autosizing of zone-level airflows, etc. It should be noted that oversizing factors are separately set with coils, water loops, and other heating and cooling equipment that is autosized only in the system-level stage of the process. While otherwise accessible to any ApacheHVAC user, the ASHRAE 90.1 Performance Rating Method (PRM) Navigator in the VE provides additional interface dialogs and tools for ASHRAE 62.1 ventilation rates, exhaust airflow settings, and application of PRM Baseline fan curve inputs. The PRM Navigator interface is described in a separate user guide. The more manual approach to these parameters is described below. IMPORTANT: Through version 6.4 and variants thereof, the automated zone-level sizing procedure requires that the target ApacheHVAC system file is named proposed.asp. This file name must be in place prior to using either System Parameters or Room Load Calculations in the System Prototypes & Sizing navigator. If not, the parameter changes and/or sizing process will not populate the Loads Data spreadsheet according to the rooms or zones assigned to the correct target system. The target system name of proposed.asp must also remain in place (or be reinstated) for the Assign system parameters and room sizing data action in the sizing navigator. The ApacheHVAC file name can be subsequently changed without consequence. For version 6.5 an onward, this naming convention will not be required, nor is it required for the System-level loads and sizing process described below.
VE 6.4
ApacheHVAC
275
Figure 7-1: Open a blank ApacheHVAC file, load selected systems from the HVAC Prototype Systems Library, as needed, and save the file as proposed.asp (see note below). When using the System Prototypes & Sizing navigator, creation and naming of the proposed.asp file and opening of the Systems Library are automatically executed by the Prototype System action item in the navigator. If needed, additional systems can be loaded at any time. Prototype systems can be modified or used as resources from which to copy elements for customizing or extending the capabilities of a particular system. For all but advanced users, however, it is recommended that initial system sizing and brief test simulations are completed prior to modifying the system configuration, components, or controls. As noted above: Through all variants of version 6.4, the automated zone-level sizing procedure requires that the target ApacheHVAC system file is named proposed.asp. This file name must be in place prior to using either System Parameters or Room Load Calculations in the System Prototypes & Sizing navigator. The target system name proposed.asp must also remain in place (or be reinstated) for the Assign system parameters and room sizing data action in the sizing navigator. The ApacheHVAC file name can be subsequently changed without consequence. For version 6.5 an onward, this naming convention will not be required, nor is it required for the System-level loads and sizing process described below.
VE 6.4 ApacheHVAC 276
Figure 7-2: Use Edit Multiplex to assign groups of rooms or zones to the prototype system.
Figure 7-3: System Schedules dialog edits coordinated profiles used in system controllers and Room Data.
VE 6.4 ApacheHVAC 277
Figure 7-4: Opening the System Parameters dialog generates a Loads Data spreadsheet for each system (one per multi-zone system or set of single-zone systems) and provides access to setting essential parameters for system sizing and operation via the spreadsheets. Edited parameters are recorded in the respective Loads Data spreadsheet for use in subsequent steps of the processi.e., edits to these parameters are not immediately reflected in the ApacheHVAC system components and controllers.
VE 6.4
ApacheHVAC
278
Figure 7-5: The Room Load Calculations step in the System Prototypes & Sizing navigator runs ASHRAE Loads and populates the Loads Data spreadsheet for each network with loads results and other relevant data, such as room volumes. Calculations for zone airflows and similar parameters use the loads data and previously recorded settings from the System Parameters dialog. There are optional features in the spreadsheet for zone-specific airflow configurations and calculation of ASHRAE 62.1 ventilation rates.
VE 6.4 ApacheHVAC 279
Figure 7-6: The Assign System Parameters and Room Sizing Data step assigns values to system components and controllers. This is the essential final step in the zone-level autosizing. Viewing the zone heating or cooling airflow rates for all multiplex layers confirms that this stage of autosizing is complete.
VE 6.4 ApacheHVAC 280
Figure 7-7: ApacheHVAC system loads analysis type in ASHRAE Loads dialog
VE 6.4 ApacheHVAC 281
VE 6.4
Model preparation: Having defined internal gains, assigned constructions, and selected design weather data, the user sets up room or zone groups in Model-IT, using a grouping scheme that organizes spaces in the model according to the systems that will serve them. Grouping spaces according to system assignment is the key to efficient addition and assignment of zones to systems in ApacheHVAC. Assign rooms/zones: This step simply provides informational instruction regarding the use of the Edit Multiplex facility in ApacheHVAC to assign rooms or zones from groups in the model to particular systems. This is meant to emphasize the value of grouping spaces according to system assignment prior to loading and setting up systems in ApacheHVAC. Prototype system: Clicking this link opens a blank ApacheHVAC file named proposed.asp and launches the library of detailed prototype HVAC system models to choose from. This is required for the zone-level sizing process through v6.4 (in v6.5 and onward, the user simply selects a target system at the zone level the same as for the system level). System schedules: This dialog provides inputs for system operating schedules and set points in terms of occupied and unoccupied times, setback temperatures, start-up and post-occupancy space conditioning, and system operating schemes for unoccupied hours. It includes a facility for generating an alternate set of these inputs that can be separately applied to specific zones and systems. The SYS profiles linked to this dialog are also used for checking unmet load hours (via Range Check in Vista Results for any project; included in 90.1 PRM Navigator reports). System parameters: System-level parameters, such as global setting zone heating and cooling load oversizing factors, air-handler coil leaving-air-temperature settings, operation as a 100% outside-air system, inclusion of energy recovery, and related inputs can be changed using the System Parameter dialog. Opening this dialog generates a Loads Data spreadsheet for each ApacheHVAC system (if not already present) as a repository for these parameters settings. Room/zone-level load calculations: This link initiates zone-level loads calculation using the ASHRAE heat-balance method to determine heating and cooling loads. This is quasi-dynamic with respect to heating loads (the outdoor design temperature is held constant) and fully dynamic with respect to cooling loads (i.e., outdoor temperatures, solar loads, internal gains all vary as they would in a dynamic thermal and energy simulation). Loads are for an ideal system that meets the space temperature setpoints under all conditions. If it is not yet present in the project, a separate copy of the Loads Data spreadsheet will be generated for each system in the proposed.asp file (or in the current open ApacheHVAC file for v6.5) and saved within the project directory. The system-specific spreadsheets are auto-populated with zone heating and cooling loads and data on setpoints, zone volumes, ventilation, rates, and so forth. Access loads data spreadsheet and ASHRAE 62.1 ventilation: This link opens the project folder of Loads Data spreadsheets created for each system in the proposed.asp file (in the selected HVAC file as of version 6.5) and updated by the last two steps. The Loads Data spreadsheet is used to determine zone-level airflows, ventilation requirements, and related parameters. It is a repository for the inputs, such as oversizing factors, from the System Parameters dialog. It also includes many more detailed optional inputs and settings. For example, the spreadsheet includes inputs for manipulating code-required minimum primary air-change rates, transfer airflow rates, the basis for calculating maximum VAV turn-down, and other similar parameters. There is also a facility in the spreadsheet for calculation of ASHRAE 62.1 outdoor air ventilation rates using the Table 6.3 method. The calculated results for parameters edited within either the System Parameters dialog or the spreadsheet itself are assigned to systems components and controllers using the next step in the navigator (repeating these steps as necessary).
VE 6.4
ApacheHVAC
283
Assign system parameters room/zone-level sizing data: This assigns component and controller inputs from the spreadsheet to their respective ApacheHVAC systems in the proposed.asp file (or the selected target file in v6.5). As the additional inputs and settings available within the Loads Data spreadsheet for each system are optional, this step can be completed immediately following the Room/zone-level load calculations step. The user can repeatedly re-size systems after changes to the building model. So long as individual autosized values are manually overridden within the spreadsheet, these overrides can be maintained in future sizing runs and sizing data assignments. The user is free, as always, to manually edit component and controller parameters and inputs within ApacheHVAC. While appropriate knowledge and experience are highly recommended, system, component, and controller configurations can also be substantially modified without breaking the autosizing functionality. System/plant loads calculation and sizing: The fully detailed system(s) within the selected ApacheHVAC file are run in a dynamic simulation of the model under the selected design day conditions (steady state OA temperature for heating loads and typically sinusoidal variation, as in ASHRAE design weather data, for multiple cooling design days). The system operates within the bounds of current zone-level sizing for airflow controls, coil leaving temperatures, etc. to meet design loads. This step records system loads data for reports and updates the selected ApacheHVAC file with respect to fan airflows, coil capacities (and sizing conditions for advanced coils), water loops capacities, and capacities for all heating and cooling equipment. Sizing reports: The action generates and displays reports for system-level sizing runs. These reports list equipment loads (excluding equipment oversizing factors entered in ApacheHVAC) as seen by the equipment at the peak design conditions. When Detailed room loads is ticked within the Report preferences dialog in Vista Results, the reports include details of room/zone loads, conditions, and airflows, as well as basic engineering checks. ASHRAE 62.1 report: This action opens a report of ventilation rates and indicates whether these meet or exceed ASHRAE 62.1 requirements (this requires selection of appropriate space occupancy types in the 62.1 Calcs tab of the Loads Data spreadsheet or via the PRM navigator).
Finally, the user returns to the ApacheThermal view to simulate the building and systems. Whether in system-level autosizing or subsequent simulation for thermal comfort and energy analyses, there is interaction between the building zone loads (outdoor conditions, solar gain, room air nodes, surface temperatures, constructions, and internal gains), detailed solar calculations (if SunCast has been run), detailed daylighting data for sensors placed in the spaces (when RadianceIES sensors have been set up), bulk-airflow modeling of natural ventilation (when MacroFlo openings are included), and ApacheHVAC systems at each simulation time step. Time steps can be anywhere from 30 minutes for rough initial runs down to 1 minute for detailed analyses, with 6 minutes recommended for final runs in most projects. Simulations can be carried out for the entire building project or just a small subset of it, as might be desirable when setting up and optimizing system configurations and zone-level controls. Having optimized the system using a small number of select zones and select dates or conditions from the simulation weather file, the user can assign additional zones to the ApacheHVAC systems, repeat the zone-level sizing run, and then perform system-level sizing for coil loads, plant equipment, and so forth. Because systems within ApacheHVAC are created or modified independently of the thermal model, the VE allows users to create multiple systems that can be run with same the thermal model in Apache Sim. Section 7.5 - Details of Zone and System-Level Loads, Ventilation, and Autosizing has been temporarily removed for a major overhaul and will be reinstated when revisions are complete.
VE 6.4
ApacheHVAC
284
Figure 8-1: The Prototypes Systems Library facilitates loading any pre-defined or user-defined system. ApacheHVAC includes a range of pre-defined systems for which numerous parameters (controller inputs, flow rates, coil sizes, temperature resets, fan sizes, heating and cooling plant equipment capacities, etc.) can be autosized with respect to setpoints, design loads, ventilation rates, operating schemes, and so forth. There also capability for autosizing coils, fans, and heating & cooling equipment in fully custom-built systems. Section 7: System Loads, Ventilation, and Autosizing, describes the auto-sizing process, opportunities for user intervention, and the setting of associated system schedules, operating schemes for unoccupied hours, economizer operation, and other system parameters. IMPORTANT: While the pre-defined prototype systems will run as provided, with only the assignment of rooms or zones having been completed, appropriate results depend upon completion of sizing at two levels. This sizing process, as described in the previous section, is completed in two separate stages: Zone-level sizing for airflow controllers and other similar system elements must be completed either manually or through the largely automated process described in the previous section, in order for the spaces to be adequately ventilated and conditioned. System-level loads calculation and sizing, which applies to coils, fans, chillers, DX cooling, boilers, heat pumps, etc., must be completed in order to appropriately scale this equipment capacities and performance curves and thus to obtain performance and energy consumption
ApacheHVAC 285
VE 6.4
results that reflect real-world applications. While rooms may be adequately conditioned with only the first stage of sizing completed, energy consumption for grossly over or undersized equipment will be far from what is should be. This will be particularly true in the case of performance for grossly oversized hot-water boilers and air-cooled or water-cooled chillers using pre-defined bi-quadratic performance curves. PLEASE NOTE: This section of the ApacheHVAC User Guide is presently still under construction. Please be sure to check for updates.
VE 6.4
ApacheHVAC
286
VE 6.4
ApacheHVAC
287
not enough cooling or ventilation is provided via operable windows, perhaps because there is insufficient wind, in spite of favorable indoor-outdoor thermal conditions). Single-fan dual-duct and with zone-level VAV mixing boxes. Dual-fan-dual-duct with zone-level VAV mixing boxes. Underfloor air distribution with parallel fan-powered boxes for perimeter zones, and re-mixing of PFPb zones when theyre in heating mode. Can also be used for thermal displacement ventilation by simply omitting the PFPbs, UFAD plenum, and re-mixing in heating mode. UFAD/DV system as above, plus heat pipe or run-around coil in AHU for free re-heat of subcooled (dehumidified) air after the AHU cooling coil. Active chilled beams with DOAS for ventilation, both using electric water-cooled chiller with waterside economizer and condenser heat recovery; recovered heat and HW boiler for DOAS heating coil and zone baseboard fin-tube convectors. 4-pipe version of the active beams system (chilled and heated beams). Advanced variant of 4-pipe active beams system (chilled and heated beams) with multiple zones on a single VAV box for primary airflow, but each zone having separate control over water flow to heating and cooling coils in active beams. Radiant heating and cooling panels (i.e., four-pipe system), plus DOAS with airside energy recovery and DCV. Radiant panels and DOAS as above with heat pipe or run-around coil in AHU for free re-heat of sub-cooled (i.e., dehumidified) air after the AHU cooling coil. Heat & vent only DOAS systems with options for gas boiler, furnace, or electric resistance heat and either DCV or constant-volume ventilation.
While some autosizing features are constrained to particular component and controller applications or configurations, all of the pre-defined systems can be extensively modified. This includes combining features from multiple systems into one, directly coupling systems, or adding custom component and control configurations. For example, the pre-defined DCV controls, heat pipes, or controllers for mixed-mode operation could be drag & drop copied from other pre-defined systems to the Active chilled beams system. The air supply for the system could be drawn from an atrium or other space on another system. The heat recovery could then be modified to model a desiccant wheel regenerated by heat recovered from the condenser loop on the electric water-cooled chiller, which can also me set to use a waterside economizer (waterside free cooling). There are also special features for advanced modeling, such as surface temperature (e.g., ceiling or floor slab) sensors for control of hydronic components. Airside componentscoils, mixing dampers, spray chambers, heat exchangers, fans, flow splitters, etc. sensors and controllers can be arranged as needed to model custom configurations, such as an earth tube or subterranean labyrinth for pre-conditioning intake air, series or dual-mode rather than parallel fan-powered boxes, a DX cooling and dehumidification system with desiccant wheel regenerated by waste heat from the DX condenser coil, staged dual-max and triple-max VAV controls, specialized temperature resets, or a laboratory with exhaust air changes made up by a combination of supply air and transfer air from adjacent spaces. All available waterside and plant equipment selections, options, and parameters, including user-defined equipment, can be added or modified within any pre-defined prototype system without detracting from the autosizing and simulation capabilities. (Note that hydronic room units, such as radiators and chilled ceilings will be autosizable within prototype systems as of version 6.5.)
VE 6.4 ApacheHVAC 288
For chillers, boilers, and DX cooling there are both detailed models with editable pre-defined performance curves and models using a matrix of part-load data. There is detailed modeling of chilled water loops, flexible sequencing of separately defined boilers, chillers, and other sources of hot or chilled water, and detailed hot-water and chilled-water coil models with autosize and design sizing modes. There are also editable models for cooling towers and fluid coolers, and various options for modeling pumps on primary, secondary, and tertiary (hydronic unit/zone) water loops. Part-load data matrices are provided for modeling generic and non-standard heating and cooling sources. For this type of model, cooling COP can vary both with load and outdoor conditions. Part-load cooling sources can also use the chilled-water loop model and associate pump modeling, but do not share the detailed condenser-water loop and cooling tower models used by the full electric water-cooled chiller model. Like hot-water boilers, part-load heat source models can use recovered chiller condenser heat must presently still modulate associated pump power according to heating load. Any heat source can serve space heating and/or domestic hot water loads, and a solar thermal hot water model with storage tank is available to use as the first source of heat for domestic hot water. Presently, mapping of results for any given node in the HVAC system on a psychrometric chart must still be done by transferring state points to a separate psychrometric chart tool. However, this data is available for every simulation time step and the Vista Results view supports graphing selected zone and system-level node variables on the same graph. Room conditions and outdoor variables can similarly be added to the same graph. Anything that can be graphed can also be viewed, copied, and exported to other tools as a table of results data for each time step.
The pre-defined systems added in 6.3 include versions of systems 1 & 2 using the more detailed Unitary Cooling System Model, a more advanced configuration of system 5 with enthalpy economizer and directly coupled copies of system 1 for residence/hotel rooms, and a range of eight more advanced non-conventional systems. These include the following:
Packaged terminal air conditioning using the detailed Unitary Cooling System (UCS) model (appropriate for small single-zone units with fixed-speed fans that cycle on and off, such as through-the-wall AC), with a hot-water heating coil coupled to a central boiler. Packaged terminal heat pump using the detailed Unitary Cooling System (UCS) model (appropriate for small single-zone units with fixed-speed fans that cycle on and off, such as through-the-wall AC) in cooling mode and an air-source heat pump in heating mode, with electric-resistance backup heating coil. Indirect-direct evaporative cooling VAV-reheat system with backup DX cooling coil, dew-pointtemperature OA economizer high-limit control, zone-level humidity high-limit control, and CO2based demand-controlled ventilation (DCV) using zone-level sensors to first force individual VAV boxes further open and the request additional outside air at the system level. VAV-reheat with differential-enthalpy economizer set up for the public areas of a hotel, dormitory, or similar building with PTAC systems for individual rooms drawing air from and atrium zone prior to the return path of the main VAV system. Mixed-mode natural ventilation and VAV-reheat with zone temperature and zone CO2 overrides to re-introduce system air supply when nat-vent mode is insufficient (e.g., when the room occupancy is very high or wind-driven pressure differentials are too low) in spite of indoor-outdoor thermal conditions that are appropriate for ventilation and cooling via operable openings.
VE 6.4
ApacheHVAC
289
Dual-fan-dual-duct system with dew-point-temperature OA economizer high-limit control and zone-level mixing boxes (reduces fan energy and avoids the need for reheat, but requires second set of ducts). Underfloor air distribution with parallel fan-powered boxes (PFPbs) for perimeter zones, leakage path, and re-mixing of otherwise thermally stratified PFPb zones when in heating mode. Underfloor air distribution as above, plus heat pipe or run-around coil in the AHU for free re-heat of sub-cooled (i.e., dehumidified) air after the AHU cooling coil, and accounting for added static pressure seen by the supply fan when airflow passes through the heat pipe/coil (i.e., when it is not bypassed). Active chilled beams (zone-level induction units with cooling coils and induced flow in proportion to the primary airflow) and a Dedicated Outside Air System (DOAS) for temperate ventilation air. Radiant heating & cooling panels (multiple two-pipe or four-pipe units can be placed in each zone; 2 types are pre-defined for both heating and cooling as examples), plus DOAS with zone CO2-based DCV. Radiant panels and DOAS as above with heat pipe or run-around coil in AHU for free re-heat of sub-cooled (i.e., dehumidified) air after the AHU cooling coil, accounting for added static pressure seen by the supply fan when airflow passes through the heat pipe/coil (i.e., when it is not bypassed).
All 22 predefined systems will now load via the System Prototypes S button in ApacheHVAC and the System Prototypes & Sizing Navigator. When the tabbed views have been provided in ApacheHVAC, users will load these predefined systems individually, as needed.
VE 6.4
ApacheHVAC
290
VE 6.4
ApacheHVAC
291
If any autosized or autosizable values (with an A next to the input field) are manually edited in the ApacheHVAC system file, care should be taken to prevent these being overwritten if the user wants to avoid losing the changes if/when a subsequent Assign system parameters and room sizing data action is used to update other numbers in the same ApacheHVAC system file. If this is a concern and the user may again want to apply the Assign system parameters and room sizing data action for a particular ApacheHVAC system file, then preserving manual edits to a component or controller requires removing the alpha-numeric designation and colon at the beginning of its reference name e.g., deleting the S2: or MC3: bit of the component or controller name.
Avoid unnecessarily deleting and replacing controllers in autosizable systems; however, if a controller does need to be replaced and the intent is to preserve relationships to the room/zone-level sizing spreadsheet for the system elements listed above, the following rules apply:
Any controller mapped for autosizing (having an A next to one or more input fields) must retain the alpha-numeric designation and colon at the beginning of its reference name, as in MC3: , in order for the autosizing function to be retained for those values. The controller must be the same type with the same active elementse.g., with Proportional control enabledif the same input fields are to receive autosized values that would have gone into the pre-defined controller. Users can also add controllers that re-use the alpha-numeric designation and colon at the beginning of the reference name, as in MC3: , if they would like to have the newly added controller pick up the same autosized values as the identically designated controller of the same type within the same HVAC system category. o For example, if it is helpful for some reason to have the Heating Airflow values in MC4 for system type 07 show up in a controller that is be added to a customized version of a predefined system that has a 07 at the beginning of the name, the new control would need to be the same type as the pre-defined controller and would need to have MC4: at the beginning of its reference name. Once the new controller is added and properly named, clicking Save for the ApacheHVAC file will complete the link and a black A should show up next to the corresponding input fields (the same fields that receive the autosized values in the pre-defined controller that normally uses the chosen alpha-numeric designation).
Users can substitute non-autosized controllers, if desired. This is a workable approach in the case of any controller for which inputs will be the same for all or most multiplex layer instancese.g., a supply temperature reset controller that will be set to have a range of 58 to 68 F for all layers in the multiplexor when the system has a very small number of layers, which makes manual editing much more straightforward. Maintaining connection to referenced schedules and profiles
8.2.3.2
VE 6.4
ApacheHVAC
292
VE 6.4
ApacheHVAC
293
OA economizer dewpoint high-limit control Energy recovery bypass damper OA economizer dry-bulb high-limit control Outside air economizer damper set Outside air inlet SA fan copy to account for added pressure on path through energy recovery Supply fan SA fan min flow control for night-cycle operation Zone re-heat coil Cooling coil SAT reset per zone temperature Cooling coil SAT reset per zone % humidity Cooling VAV airflow Heating VAV airflow Duct heat gain/loss AHU cooling coil AHU heating coil and control Transfer airflow control Principal room or zone in which sensors and thermostats are located (usually occupied zone) Multiplex layers use the name of the space assigned here.
Energy recovery bypass control Energy recovery controls Return fan or common exhaust fan Fan and outlet for separately exhausted spaces (volume not available for recirculation or transfer)
Figure 8-2: Many elements shown here are common to other pre-defined prototype systems. The sections below describe these and many others.
VE 6.4 ApacheHVAC 294
8.3.3.2
8.3.3.3
8.3.3.4
8.3.3.5
8.3.3.6
VE 6.4
ApacheHVAC
295
Target temperatures for the energy recovery bypass damper and for the heating and cooling for modes of the energy recovery device are based upon the leaving air temperature (LAT) set for the AHU Heating Coil. Normally, this leaving air temperature is the minimum temperature that the system is permitted to deliver to the zonese.g., 55 to 65 F or a similar cool-to-neutral value (heat, above and beyond this tempering, is most typically provided at the zone level). If the LAT at the AHU Heating Coil is set to 55 F, for example, the target values will be as follows 50 F (simply 55 5 )for the energy recovery in cooling mode 70 F (simply (55 5) + 20 ) for the energy recovery in heating mode 50 F at Max signal (when the RA is warmer) and 70 F at Min signal (when the RA is cooler) for the bypass damper proportional control.
VE 6.4
ApacheHVAC
296
Note that the energy recovery heating and cooling mode target temperatures are intended to be unattainable targets, just beyond the reach of the capability of the device to pre-heat or pre-cool the incoming outdoor air with recovered heat or coolth. For the example above, when in heating mode (based upon a sensed RA temperature of 71 F or less) the energy recovery would not be expected to be able to heat the outside air all the way to 70 F with heat recovered from return/exhaust air that is itself 71 F or cooler. Similarly, the energy recovery would certainly not be expected to cool the outside air all the way to 50 F by rejecting heat from it to the return/exhaust air that is itself 73 F or warmer. SC5 uses the same values at Min and Max signal as the energy recovery targets in SC4 and SC5. For the controllers on the energy recovery device, SC4 and SC5, the targets could be more extreme with no effect, as they are almost certainly unattainable. However, if the target temperatures at the high and low ends of the proportional control band for the bypass damper are set to overly extreme values, this will have the effect of making the useful part of the proportional band ramp very quick (over a nary range of sensed values) from the lowest to the highest attainable values, or vice versa. The most important number in these three controllers is the setpoint in the energy recovery mode controls and midband value for the proportional control in the bypass and the bypass damper control, as it determines the changeover from heating to cooling logic for energy recovery based upon the RA temperature. Note that, apart from the energy-intensive intentional reheat after sub-cooling to dehumidify the intake air, it is unlikely you would set the LAT for the AHU heating coil in a pre-defined system configuration to a value warmer than the lowest LAT for the cooling coil immediately upstream of it (e.g., 55 F): If set to a warmer LAT, the heating coil will simply consume energy reheating the air just cooled by the cooling coil. If, however, you chose to replace the fixed-temperature controller on the AHU heating coil with one that, for example, used a sensor to re-set the SAT according to zone temperatures, etc., then you would replace the autosized controller with one of your own. The following graph of intake air flow rate and temperatures on either side of the energy recovery device on a hot summer day.
Teal = outside air (node 21) Blue = intake air after the energy recovery device (node 22) Purple = return/exhaust air (node 40) Red = exhaust air after receiving rejected heat from the intake air (node 41) Gold = intake air flow rate (node 21)
It can be seen that the intake air matches the outside air temperature until the point at which the outside air is actually warmer than the exhaust air from the building. At this crossover point, the energy recovery device begins, by virtue of this temperature differential, to transfer heat from the incoming outdoor air to the outgoing exhaust air. The effect increases with the delta-T in keeping with the heat exchanger effectiveness input. This rejection of unwanted heat continues until the system airflow is reduced to zero
VE 6.4 ApacheHVAC 297
at the end of the day. It can also be seen that in the early evening the temperature of the intake air rises with a rise in the temperature of the return/exhaust air, and thus also a drop in useful delta-T and the rate of heat rejection to the exhaust.
The minimum outside ventilation rate is set for pre-defined systems within the mixing damper S1: OA Economizer - min OA per 62.1. While this component includes per 62.1 in its name, the 62.1 calculations are used only if the user asks for this within the 62.1 OA Calcs tab of the Loads Data spreadsheet and is otherwise the ventilation rate set up by the user in the VE thermal templates/room data or in this component. The default HVAC EP1 - Economizer (Timeswitch: Sys 3--8) profile used in the OA damper set is linked to the System Schedules dialog and provides means of setting the minimum OA value to zero in the unoccupied hours (depending upon the operating/set-back strategy selected in this dialog for unoccupied hours). As described below, this profile can be modified to modulate the minimum OA value for scheduled changes in ventilation rate and certain similar DCV strategies. 8.3.5.2 Demand-controlled ventilation
For systems with demand-controlled ventilation (DCV), building codes may permit the use of a modulated minimum outside air setting or even a minimum setting of zero outside air. Depending on what type of DCV control is used, however, the OA ventilation/economizer damper component will most often still have a set design minimum airflow value. How this is modulated depends upon the type of DCV control. Occupancy schedule: For systems that serve spaces with dependably predictable occupancy schedules, a modulating profile (ranging from 1.0 to some fraction of 1.0) can be used to reduce the OA ventilation rate to a fraction the design airflow set point when permitted by reduced occupancy. This is similar to the standard profile that is used to reset the OA damper to zero flow during scheduled unoccupied hours, such as nights and weekends. When starting with a pre-defined prototype system, therefore, the modulating profile for schedule-based
VE 6.4
ApacheHVAC
298
DCV should be either a modification or user-defined replacement for the default HVAC EP1 Economizer (Timeswitch: Sys 3--8) profile used in the OA damper set. Note that changing the name of this profile precludes it being edited along with other HVAC profiles via the System Schedules dialog. Simply modifying it maintains the connection, but can be overwritten when the System Schedule inputs are subsequently saved by clicking OK in the System Schedules dialog. Occupancy sensors: Because any model of building operation will use schedule profiles to simulate variations in occupancy for rooms and thermal zones, this type of DCV will also be modeled using a schedule-based modulating profile in the OA damper. The one difference from the profile used to represent spaces with occupancy sensors is that it will most often be appropriate to create a modulating profile that represents some overlap and some diversity in the timing of occupancy for spaces on the system. This should reflect the building program. CO2 sensors single-stage control: This type of control adjust the system-level outside air setting based upon a critical zone (the zone with the highest sensed CO2 value). So long as there are CO2 sensors and a means of modulating the mix of outside vs. recirculated air, this can be used on single- or multi-zone systems with either variable or constant-volume airflow. This is modeled via a zone-level controller with CO2 sensor that votes on the position of the system OA damper. Whichever zone votes for the most open position of the OA damper wins the vote, and thus becomes the critical zone, as it is determining the system OA damper position at that time. In the cases of a single-zone system, the percentage OA is simply modulated in response to the zone CO2 concentrationno voting is required. The OA modulation is performed via a damper component providing a bypass around the main OA economizer damper. In a real-world application, these would most likely be one in the same. The separate damper set is used in the system model simply to allow the controlled variable to be a target leaving air temperature for the economizer operation and a percentage damper opening to the left branch of the component for the DCV control (one damper component cannot be controlled according to more than one controlled variable type). The two dampers are, in effect, one damper with two overlapping modes and means of control. CO2 sensors dual-stage control: The two-stage DCV control is appropriate in multi-zone VAV systems for which the primary air supply is at least partially recirculated air and there is both a zone-level damper to modulate primary airflow and a system-level outside-air damper. The first stage forces the VAV damper for any given zone to open more, to the extent it is not already fully open, to minimize CO2 accumulation as the CO2 level in that zone approaches the set CO2 ppm threshold. Once the VAV damper is fully open, if the CO2 level in the zone continues to rise, exceeding the setpoint, this will initiate a second stage that votes for a more open position of the system OA damper. As long as the CO2 level continues to rise, this second stage will continue to request a greater fraction of outside air from the system air handler until the system is at 100% OA. The first stage resembles the proportional controller for VAV zone cooling airflow in terms of min and max airflow, but uses the CO2 level in the room as the sensed value and CO2 setpoint minus 200 ppm (a default that can be overridden) as its midband. The second stage is modeled as a second outside air damper providing a bypass of sorts around the main OA/economizer damper. This is, as in the single-stage DCV control. All zones with DCV sensors enabled will vote on the position of second damper for additional ventilation air. Whichever zones votes for the most open damper position wins the vote. The reason this uses a separate damper set is, once again, to allow the controlled variable to be a
ApacheHVAC 299
VE 6.4
target leaving air temperature for the economizer operation and a damper opening percentage (for air from the left branch) for the DCV control. The two dampers are, in effect, one damper with two overlapping modes and means of control. If desired, a lesser maximum OA percentage can be entered either in the Loads Data spreadsheet for the system, and then applied with an update of other linked controllers, or simply edited in the Percentage flow at Max Signal field within controller MC12: Demandcontrolled ventilation (DCV) per zone CO2 levels - stage 2 - demand more system OA. CO2 sensors single stage control for dedicated 100% outside air systems (DOAS): For these systems, there is no recirculation path at the system level and thus the air handler is always delivering 100% outside air to the conditioned zones. Therefore, for this fundamental category of system configuration the sensed zone CO2 level is simply used to directly control the system airflow to just that zone. If the air handler is delivering only tempered air having a relatively neutral temperature to the zones, it may be acceptable for the system airflow to modulate to zero so long as this does not cause CO2 levels to rise above the ppm setpoint. The default calculations in the Loads Data spreadsheet set the lower bound at 30% of the maximum airflow, however, this can be easily overridden by setting the Flow rate at Minimum Signal in controller MC3 to an alternate value, including zero. When this type of DCV is set up to modulate all the way to zero airflow, the zone damper will normally begin to open again as the CO2 levels approach the ppm setpoint. The default proportional control bandwidth of 400 ppm, which can also be readily overridden in the controller (MC3 for any system type 09), causes the damper to begin to open at 200 ppm below the setpoint and to reach fully open at 200 ppm above the setpoint.
8.3.5.2.1 Adding CO2-based demand-controlled ventilation to a multi-zone system Demand controlled ventilation with zone CO2 sensors can be included in any system. To add zone-CO2 based DCV to multi-zone system that does not have these controls (see components and controls highlighted in the screen captures on subsequent pages), the appropriate source file or example to work from depends upon whether your proposed system will have a dedicated outside air handler or DOAS without recirculation (e.g., prototype systems in the 09 category [at left in the image below]) or will include a recirculation path (e.g., prototype systems in the 0508 categories[at right in the image below]).
VE 6.4
ApacheHVAC
300
A typical overall room CO2 setpoint might, for example, be in the range of 1,000 ppm, depending upon the application, codes, etc. A single stage control for spaces served by a dedicated outside air system without recirculation (e.g., one of the 09 prototype systems) would simply use this value as the midband to ramp zone ventilation air between minimum and maximum values in keeping with CO2 levels for that zone. A two-stage control for VAV system configurations 05 and 07 (with recirculation) might force the zone VAV box all the way open using a ramp with midband of 900 ppm and then have a second stage ramp with midband of 1,100 ppm used to gradually demand more system OA if the zone CO2 levels continue to rise.
VE 6.4
ApacheHVAC
301
Adding zone-CO2 based DCV to prototype systems in the 09 category is, where applicable, a matter of enabling variable flow for the ventilation air to the zone. This is accomplished by simply setting Flow at Min Signal to a value that is less than Flow at Max Signal. This control (MC3) is pre-defined for all category 09 prototype systems other than active chilled and 4-pipe beams (induction units). In those with DCV in the name, the default inputs before autosizing illustrate typical control of ventilation between min and max values (see screen captures below). For those without DCV in the name, the default inputs before autosizing provide constant-volume ventilation flow rate (flow at min signal = flow at max signal), thus negating the influence of the CO2 sensor until the flow rates are revised to distinct high and low values.
Specific instructions for category 09 active chilled beam and 4-pipe active beam systems, as well as other prototype system categories, follow below.
VE 6.4
ApacheHVAC
302
For the active chilled beam and 4-pipe active beam systems, the MC3 controller with CO2 sensor is replaced by MC10: Primary airflow to active beam, which modulates primary airflow according to a zone temperature. Because there is also supply air temperature reseteffectively a water flow control valve on the cooling coil (and heating coil for 4-pipe beams), the MC3 controller with CO2 sensor used on other category 09 systems can be used with these systems without losing space conditioning control. If the DCV airflow is to replace the thermostat-based control of primary airflow to the beam, the setting and reference name within MC10 should be revised to match those of MC3 in any category 09 prototype system with DCV in the name. One means of accomplishing this is to delete MC10, import one of the systems with DCV, and copy the MC3 controller. In any case, if you wish to have the controller pick up the DCV inputs from the Loads Data spreadsheet during autosizing, it is essential that the reference name of the controller begin with MC3:, including the colon. If the DCV is to be added as a secondary means of modulating the airflow to the active beam, the MC3 controller should be manually added as shown in the illustration and dialog below. Again, if you wish to have the controller pick up the DCV inputs from the System Parameters dialog and the Loads Data spreadsheet during autosizing, it is essential that the reference name of the controller begin with MC3:, including the colon. Also, the HVAC PP2 or similar user-defined time-switch profile is needed to ensure that the ventilation air does not get stuck on at the minimum flow rate when the building is unoccupied and the ventilation is meant to be off.
VE 6.4
ApacheHVAC
303
To add zone-CO2 based DCV to systems in categories 0508, begin by importing system 05b IDDE VAVr CO2-DCV from the HVAC library into your file. Copy the additional damper set and two multiplexed zone-level controllers (MC11 and MC12) from that system to the system to which you would like to apply DCV, as described below.
Figure 8-3: Two-stage DCV components in prototype system 5b are highlighted in this screen capture.
VE 6.4
ApacheHVAC
304
To add zone-CO2 based DCV to multi-zone VAV system 5 or 7 configurations (including most variants): 1. Delete the three connectors marked with a red X in step in the image above and move the SA fan, OA/economizer damper, and associated controls one cell to the right. 2. Select and copy the junction, connectors, damper set, and both MC11 and MC12 controllers (pointing to primary airflow path and DCV damper, respectively) as highlighted an placed in step above. This will provide two-stage DCV-based control that first forces the zone VAV box more open and then (when the VAV box is fully open) demands more system OA at the air handler, consistent with the descriptive Reference names for controllers MC 11 and MC12. 3. Because systems 5 & 7 share the same fundamental configuration as system 5b, the MC11 and MC12 controllers copied from that system to any derivative of either 5 or 7 will remain linked to the Sys 5,7 tab in the Loads Data spreadsheet. When data is assigned from the spreadsheet to the controllers in the system, they will pick up min and max VAV airflows and CO2 midbands bracketing the target CO2 level set in the System Parameters dialog.
VE 6.4
ApacheHVAC
305
To add zone-CO2 based DCV to multi-zone VAV + fan-powered boxes system 6 or 8 configurations: 1. Delete the three connectors marked with a red X in step in the image above and move the SA fan, OA/economizer damper, and associated controls one cell to the right. 2. Select and copy the junction, connectors, damper set, and just the MC12 controller (the controller pointing to the DCV damper) as shown in step above. This step will provide the DCV-based system OA control, consistent with the labeling of MC12, Demand-controlled ventilation (DCV) per zone CO2 levels - stage 2 - demand more system OA 3. To include the initial stage of DCV control that first forces the zone VAV box to open further (until fully open) before demanding additional outside air at the system air-handler, you will also need the MC11 controller; however, because there is loop with fan for the zone fan-powered box in systems 6 and 8, this control needs to occupy a different location on the canvas. 4. Version 6.5 will include stretchable controller leads for the controlled and sensed nodes, which allows for copying the MC11 controller from system 5b and stretching lead to fit it as shown (figure at right). In releases prior to v6.5, however, the MC11 controller needs to be re-created so as to include the same sensed and controlled variables, etc. as in system 5b. Place the new controller as shown above so that it senses room/zone temperature and controls airflow at the same nodes as the primary airflow VAV control, but without falling on top of the loop for the fan-powered box.
VE 6.4
ApacheHVAC
306
5. Use the dialog for system 5b (shown above) as an example for appropriate sensed and controlled variables, CO2 midband, flow rates, and time switch profile. a) The sensed variable is CO2 Concentration b) The controlled variable is Flow Rate c) Proportional control bandwidth should indicate the range of sensed CO2 concentration (ppm) over which the VAV damper for primary airflow will modulate in response to zone-level CO2. As the zone CO2 rises, this control will be voting on the VAV damper position along with the VAV cooling airflow controller (the highest value at any time step will prevail). To facilitate straightforward coordination of control midbands, set this bandwidth to the same value as used in MC12 (e.g., 400 ppm). d) The proportional control midband sets the midpoint of the range of sensed CO2 concentration (ppm) over which the VAV damper for primary airflow will modulate in response to zone-level CO2. If this control is to take effect prior to MC12, fully opening the VAV box prior to requesting additional outside air at the system level, and assuming the bandwidths for MC 11 and MC 12 are the same, this midband should be set to one bandwidth less than the midband for MC12. The two proportional bands will then be immediately adjacent, but not overlapping with respect to the sensed value for zone CO2 concentration. e) Flow Rate at Max Signal and Flow Rate at Min Signal in MC11 should match the values in MC3: Zone VAV cooling airflow control with night-cycle on when set-up temp is exceeded for all multiplex layers. For autosized systems, these values can be copied as a column of numbers from the system Loads Data spreadsheet to the tabular edit or Data table view of input fields within the controller dialog (see Chapter 6 for description of multiplex editing).
VE 6.4 ApacheHVAC 307
f)
If a non-zero airflow rate is used for the Flow Rate at Min Signal value, as in the autosized controllers, then the time switch profile should be HVAC PP1 or an equivalent profile that will force the minimum flow rate on only when the system airflow is required for space ventilation. This will set the timing the same as any exhaust and/or transfer airflow controls.
g) To disable or enable DCV control (stage 1 and/or stage 2) for any given set of layers, select those layers in the Multiplex Edit dialog while in Global Edit mode and then set the Time Switch Profile in the controllers to either OFF continuously or HVAC PP1 (or user equivalent). 6. Because there are no pre-defined systems in categories 6 and 8 with DCV, there is also no shortcut to the DCV inputs provided for these system configurations within the System Parameters dialog. Parameters related to DCV for these systems should be edited as described above. The two-stage MC11 and MC12 controls are used only for multi-zone systems with a recirculation path; the DOAS systems have a single-stage control on the ventilation air at the zone level. The MC13 controller is used only on the prototype 07b Mixed-Mode system wherein it forces the mechanical ventilation to override the natural ventilation when the latter is insufficient to maintain the CO2 levels below the setpoint (subject to a deadband on the order of 200 ppm). This controller could also be copied to another mixed-mode configuration and would be similarly autosized so long as this is based upon a category 05 or 07 configuration. 8.3.5.3 Airside economizer controls Damper position modulation according to target mixed-air temperature with outside air drybulb temperature high limit. Damper position modulation according to target mixed-air temperature with outside air dewpoint temperature high limit. Damper position modulation according to the relative difference in enthalpy between the return and outside air.
The pre-defined standard and ASHRAE Baseline HVAC systems modulate the economizer damper position according to a target mixed-air temperature and include an outside air dry-bulb temperature high limit. Many of the standard pre-defined HVAC systems also include an outdoor dew-point temperature high limit controller (coupled to the DBT high limit control by a logical OR connection); however, this additional controller has an excessively high default DPT high limit that effectively disables it. To enable the DPT high limit, simply change the Set Point input to an appropriate value, such as 55F or similar.
VE 6.4
ApacheHVAC
308
The image above shows an example of a differential enthalpy control for the OA economizer damper. In this example the differential enthalpy control is used as a limiting device with a logical AND connection to the standard dry-bulb high-limit economizer control with mixed-air target temperature. If the dry-bulb high limit is not to be used, either set the high limit to an exceptionally high value (effectively no limit) or replace the standard controller with a simply time switch that set the target temperature for the OC economizer modulation. Light the dry-bulb high-limit control, the differential enthalpy control coupled by a logical AND connection will simply force the OA damper to its minimum OA setting whenever the OA enthalpy is greater than the return-air enthalpy. When the either sensible heat or enthalpy recovery is enabled via the heat exchanger in the lower left corner of the system, the comparison is between the OA enthalpy after this heat exchanger and that of the return air. This example is from the library HVAC system 5c VAV hotel/dorm public areas plus PTAC rooms, and can be copied from that system.
VE 6.4
ApacheHVAC
309
8.3.8 Return fan 8.3.9 Cooling coil system level or AHU 8.3.10 Heating coil system level or AHU 8.3.11 Duct heat gain/loss component zone level 8.3.12 Reheat coil and controller (or similar components) zone level 8.3.13 Zone or principal room component 8.3.14 Return air plenum component
VE 6.4
ApacheHVAC
310
Profiles for proportional control midbands Timed variation of values provides nighttime set-back/set-up.
VE 6.4
ApacheHVAC
311
Using a constant static pressure in each row of the fan component dialog, as we do by default, achieves this for a system wherein the fan speed will always be re-set so as maintain the specified static pressure after any downstream adjustment of VAV airflows. This is typical of a a system wherein fan speed is adjusted to maintain a static pressure set point. If the specified static pressure to be maintained by adjusting fan speed is to differ according to fan speedsome fans operate more efficiently or effectively with a particular pressure and speed relationshipthen different static pressure numbers can be entered on the rows corresponding to the appropriate fan speed ranges in the fan dialog.
8.3.16 Exhaust fan 8.3.17 Exhaust airflow controller 8.3.18 Transfer airflow controller
VE 6.4
ApacheHVAC
312
VE 6.4
ApacheHVAC
313
8.4.9 Dedicated outside air system (DOAS) with four-pipe fan-coil units, EWC chiller and HW boiler. 8.4.10 Indirect-direct evaporative cooling version of VAV-reheat system 5 above with backup DX cooling and zone-level CO2-based demand-controlled ventilation (DCV). 8.4.11 VAV-reheat with differential-enthalpy economizer set up for the public areas of a hotel or similar building with PTAC systems for individual guest/resident rooms drawing air from an atrium zone on the main VAV system. 8.4.12 Mixed-mode natural ventilation and VAV-reheat with zone temperature and zone CO2 overrides for nat-vent when it is insufficient
8.4.12.1 Temperature and CO2-based overrides when not enough cooling or ventilation is provided via operable windows, in spite of favorable indoor-outdoor thermal conditions
8.4.13 Single-fan dual-duct and with zone-level mixing boxes. 8.4.14 Dual-fan-dual-duct with zone-level mixing boxes. 8.4.15 Underfloor air distribution with parallel fan-powered boxes for perimeter zones, leakage path, and heating-mode re-mixing of PFPb zones.
8.4.15.1 Can be used for thermal displacement ventilation by simply omitting the PFPbs, UFAD plenum, leakage path, and re-mixing in heating mode.
8.4.16 UFAD/DV system as above, plus heat pipe or run-around coil in AHU for free re-heat of subcooled (dehumidified) air after the AHU cooling coil.
VE 6.4
ApacheHVAC
314
OA economizer dewpoint high-limit control Energy recovery bypass damper Outside air inlet SA fan copy to account for added pressure on path through energy recovery OA economizer dry-bulb high-limit control OA economizer damper set Supply fan
Cooling coil SAT reset per zone temperature Cooling coil SAT reset per zone % humidity Cooling VAV airflow De-stratification control to remix stratified and occupied zones when fan-powered box operates to provide heat Principal room or zone in which sensors and thermostats are located (usually occupied zone) Multiplex layers use the name of the space assigned here. De-stratification (local remixing) path connecting stratified & occupied zones Exhaust airflow control
Energy recovery device System air outlet Bypass damper for heat pipe / runaround coil Heat pipe, z-coil, or runaround coil
Transfer air control AHU heating coil Fan-powered box (parallel configuration) Fan-powered flow control AHU cooling coil Stratified zone (UFAD and DV) Return air plenum
Energy recovery bypass control Energy recovery controls Return fan or common exhaust fan
SA fan copy to account for added pressure on path through heat pipe or runaround coil
Fan and outlet for separately exhausted spaces (volume not available for recirculation or transfer)
Figure 8-4: Many elements shown here are common to other pre-defined prototype systems. The sections below describe these and many others.
VE 6.4 ApacheHVAC 315
8.4.17 Active chilled beams and DOAS for ventilation using electric water-cooled chiller with waterside economizer and condenser heat recovery; HW boiler and recovered heat for DOAS and zone baseboard fin-tube convectors. 8.4.18 Radiant heating and cooling panels (i.e., four-pipe system), plus DOAS with airside energy recovery and DCV. 8.4.19 Radiant panels and DOAS as above with heat pipe or run-around coil in AHU for free re-heat of sub-cooled (i.e., dehumidified) air after the AHU cooling coil.
PLEASE NOTE: This section of the ApacheHVAC User Guide is presently still under construction. Please be sure to check for updates.
VE 6.4 ApacheHVAC 316
VE 6.4
ApacheHVAC
317
Important note: Airflow is not set by the fans or by any other type of component. You should check before simulating a system that all flows in the system can be determined by applying these rules. Over-specification of flows is tolerated, but there should be no inconsistencies in the numerical values of flows. In the case of rooms, the assumption of flow continuity is qualified by additional rules introduced to allow ApacheHVAC to interact with MacroFlo. If MacroFlo is running in tandem with ApacheHVAC, it will detect any imbalance between the system flows entering and leaving each room, and make up the surplus or deficit with air flowing through the building through openings in the fabric (provided that suitable openings exist). In order to allow such imbalances to be set up, the following additional rules are applied relating to the assumption of flow continuity across rooms: In a first pass, ApacheHVAC makes no assumption about flow continuity across rooms. Within this constraint, all possible flow deductions are made. If some system airflows remain undetermined at this stage, a second pass is made in which the program allows room outflow to be set equal to room inflow. All possible flow deductions are then made under this assumption.
VE 6.4
ApacheHVAC
318
If some system airflows still remain undetermined, a third pass is made in which the program allows room inflow to be set equal to room outflow, or room outflow to be set equal to room inflow. All possible flow deductions are again made. After this process, all airflows should be determined for a well-specified system. If this is not the case, an error message is displayed. By delaying the application of the room flow continuity assumption, these rules allow flow imbalances to be set up to simulate a variety of mechanical ventilation and mixed-mode regimes. When using ApacheHVAC and MacroFlo in tandem, it is important to note that ApacheHVAC can set flows in MacroFlo, but not vice versa. All ApacheHVAC flows must be set within ApacheHVAC. There are instances when room flow imbalances may meaningfully be set up without invoking MacroFlo. If the supply rate for a room is greater than the extract rate, the deficit will tacitly be assumed to be lost to outside. Note, however, that if the extract rate is greater than the supply, the deficit will not be assumed to be made up with air from elsewhere unless MacroFlo is running and suitable openings are present.
VE 6.4
ApacheHVAC
319
Heating
Heating airflow control Occ un-Occ CV CV CT CT Heating coil control Occ un-Occ Overall control variation from setpoints (sp) Occ un-Occ sp -1 sp -1
10 Appendix B: HVAC zone controller profile values relative to setpoints entered in the System Schedules dialog
VE 6.4
sp -1 sp -1 CV CV CT CT sp -2 sp -2 sp -2 sp -2 sp -2 always on to maintain minimum 55 F SAT sp -2 sp -2 sp -2 always on to maintain minimum 55 F SAT 70 60 (sp) (sp) mid of 2 F ctrl band HP2 70 60 (sp) (sp) mid of 2 F ctrl band HP2 71 60 (sp +1) (sp) mid of 2 F ctrl band HP4 2-stage no variable ctrl 70 60 (sp) (sp) mid of 2 F ctrl band HP2 always on to maintain minimum 55 F SAT sp -2 sp -2 71 60 (sp +1) (sp) mid of 2 F deadband HP5 70 60 (sp) (sp) mid of 2 F ctrl band HP2 71 60 (sp +1) (sp) mid of 2 F deadband HP5 always on to maintain minimum 55 F SAT 71 60 (sp +1) (sp) mid of 2 F ctrl band HP4 2-stage no variable ctrl 71 60 (sp +1) (sp) mid of 2 F ctrl band HP4 Cooling coil SAT reset Occ un-Occ FCU Cooling coil ON Occ un-Occ 70 60 (sp) (sp) mid of 2 F ctrl band HP2 sp -2 sp -2 70 60 (sp) (sp) mid of 2 F ctrl band HP2 69 59 (sp -1) (sp -1) mid of 2 F ctrl band* HP1* 69 59 (sp -1) (sp -1) mid of 2 F ctrl band* HP1* 69 59 (sp -1) (sp -1) mid of 2 F ctrl band HP1 69 59 (sp -1) (sp -1) mid of 2 F ctrl band** HP1** 69 59 (sp -1) (sp -1) mid of 2 F ctrl band HP1 69 59 (sp -1) (sp -1) mid of 2 F ctrl band** HP1** 68 58 (sp -2) (sp -2) 2-sp step OR mid of ctrl HP7 71 60 (sp +1) (sp) mid of 2 F deadband HP5 70 60 (sp) (sp) mid of 2 F deadband HP2 71 60 (sp +1) (sp) mid of 2 F deadband HP5 70 60 (sp) (sp) mid of 2 F deadband HP3 sp -2 sp -2 FCU Cooling coil SAT Cooling SAT reset per RH Occ un-Occ Occ un-Occ Overall control variation from setpoints (sp) Occ un-Occ sp +2 sp +2 NA sp +2 NA NA NA 55% NA NA mid of 10% ctrl band 55% NA NA mid of 10% ctrl band 55% NA NA mid of 10% ctrl band 55% NA NA mid of 10% ctrl band 55% NA NA mid of 10% ctrl band 55% NA NA mid of 10% ctrl band 55% mid of 10% ctrl band 74 80 (sp -1) (sp) mid of 2 F ctrl band CP5 74 80 (sp -1) (sp) mid of 2 F ctrl band CP4 sp +2 sp +3 sp +2 sp +3 sp +2 sp +3 sp +2 sp +3 sp +2 sp +3 sp +1 sp +1 sp +1 sp +1 sp +2 NA NA Cooling airflow ON above Occ un-Occ CV*** CV*** via UCS via UCS zero flow at bottom of airflow control band*** CV*** CV*** via UCS via UCS zero flow at bottom of airflow control band*** always on 80 for vent (sp) no deadband CP7 always on 80 for vent (sp) no deadband CP7 always on 80 for vent (sp) no deadband CP7 always on 80 for vent (sp) no deadband CP8 always on 80 for vent (sp) no deadband CP7 always on 80 for vent (sp) no deadband CP8 74 80 (sp -1) (sp) mid of 2 F deadband CP5 75 80 (sp) (sp) mid of 2 F ctrl band CP1 75 80 (sp) (sp) mid of 2 F ctrl band CP1 76 82 (sp +1) (sp +2) mid of 2 F ctrl band CP3 76 82 (sp +1) (sp +2) mid of 2 F ctrl band CP3 76 82 (sp +1) (sp +2) mid of 2 F ctrl band CP3 76 82 (sp +1) (sp +2) mid of 2 F ctrl band CP3 76 82 (sp +1) (sp +2) mid of 2 F ctrl band CP3 Cooling airflow control Cooling coil ON above Occ un-Occ Occ un-Occ 75 80 (sp) (sp) mid of 4 F ctrl band*** NA CP1 75 80 (sp) (sp) mid of 4 F ctrl band*** NA CP1 74 80 75 80 (sp -1) (sp) (sp) (sp) mid of 2 F ctrl band* mid of 2 F deadband CP4* CP2 74 80 75 80 (sp -1) (sp) (sp) (sp) mid of 2 F ctrl band* mid of 2 F deadband CP4* CP2 always on when 74 80 there is airflow to (sp -1) (sp) mid of 2 F ctrl band maintain SAT CP4 per zone-based reset always on when 74 80 there is airflow to (sp -1) (sp) mid of 2 F ctrl band maintain SAT CP4 per zone-based reset always on when 74 80 there is airflow to (sp -1) (sp) mid of 2 F ctrl band maintain SAT per zone-based reset CP4 always on when 74 80 there is airflow to (sp -1) (sp) mid of 2 F ctrl band maintain SAT CP4 per zone-based reset always on when 76 80 there is airflow to (sp +1) (sp) 2-sp step OR mid of ctrl maintain SAT CP6 per zone-based reset
Default setpoints (sp) Control strategy (default) Occ un-Occ 70 60 CV unit fan and heat come on together; ventilation always on per exhaust fan
02 PTAC
70
60
CV unit fan and heat come on together; ventilation always on per exhaust fan
03 PSZ-AC
70
60
CV* airflow on in occ hours and cycle on with heat un-occ hours.
04 PSZ-HP
70
60
CV* airflow on in occ hours and cycle on with heat un-occ hours.
Heating coil ON below Occ un-Occ 70 60 (sp) (sp) mid of 2 F deadband with fan 70 60 (sp) (sp) mid of 2 F deadband with fan 70 60 (sp) (sp) mid of 2 F deadband HP2 70 60 (sp) (sp) mid of 2 F deadband HP2
Heating coil ON below Baseboard ON below Baseboard heater control Occ un-Occ Occ un-Occ Occ un-Occ 70 60 (sp) (sp) mid of 2 F deadband with fan 70 60 (sp) (sp) mid of 2 F deadband with fan 70 60 (sp) (sp) mid of 2 F deadband HP2 70 60 (sp) (sp) mid of 2 F deadband HP2
05 VAV-reheat-DX-Boiler
70
60
06 VAV-fpb-DX-Elec
70
60
07 VAV-reheat-Chiller-Boiler
70
60
08 VAV-fpb-Chiller-Elec
70
60
09 DOAS-FCU-Chiller-Boiler
70
60
VAV airflow on at min flow rate in occ hours, cycle on with heat in un-occ hours; coil-first, then add airflow when heat is required. Primary airflow on in occ hours and cycles with cooling in un-occ; 2-stage elec heat on with parallel FPB (CV or VSD) for all hours. VAV airflow on at min flow rate in occ hours, cycle on with heat in un-occ hours; coil-first, then add airflow when heat is required. Primary airflow on in occ hours and cycles with cooling in un-occ; 2-stage elec heat on with parallel FPB (CV or VSD) for all hours. CV or DCV airflow from DOAS in scheduled hours; coil-first, then 2-speed or VSD FCU boosts flow as more heat is required.
Heating airflow ON below Occ un-Occ 70 60 (sp) (sp) mid of 2 F deadband HP2 70 60 (sp) (sp) mid of 2 F deadband HP2 always on 60 for vent (sp) no deadband HP6 always on 60 for vent (sp) no deadband HP6 always on 60 for vent (sp) no deadband HP6 71 60 (sp +1) (sp) mid of 2 F deadband HP5 always on 60 for vent (sp) no deadband HP6 71 60 (sp +1) (sp) mid of 2 F deadband HP5 70 60 (sp) (sp) mid of 2 F deadband HP2
Cooling
ApacheHVAC
02 PTAC
03 PSZ-AC
Default setpoints (sp) Control strategy Occ un-Occ 75 80 CV*** fan is included in UCS model and thus runs with cooling; ventilation always on per exhaust fan 75 80 CV*** fan is included in UCS model and thus runs with cooling; ventilation always on per exhaust fan 75 80 CV* airflow on in all occ hours and cycle on with cooling un-occ hours.
04 PSZ-HP
75
80
CV* airflow on in all occ hours and cycle on with cooling un-occ hours.
05 VAV-reheat-DX-Boiler
75
80
06 VAV-fpb-DX-Elec
75
80
07 VAV-reheat-Chiller-Boiler
75
80
08 VAV-fpb-Chiller-Elec
75
80
09 DOAS-FCU-Chiller-Boiler
75
80
VAV airflow on at min in occ hours, cycles with cool in un-occ; airflow ramps up first with cooling demand, SAT then reset downward if needed. VAV airflow on at min in occ hours, cycles with cool in un-occ; airflow ramps up first with cooling demand, SAT then reset downward if needed. VAV airflow on at min in occ hours, cycles with cool in un-occ; airflow ramps up first with cooling demand, SAT then reset downward if needed. VAV airflow on at min in occ hours, cycles with cool in un-occ; airflow ramps up first with cooling demand, SAT then reset downward if needed. DOAS ventilation is CV or DCV with SAT reset per zone demand; FCU on first at low speed; more demand more flow; less resets coil temp up.
320
Notes: * For systems 3 and 4, the initial configuration in the Baseline.asp file is illustrative of VAV operation using the HP1 and CP4 airflow control midband profiles. However, unless specified in the Loads Data\Proposed\PR03...xls file, the Assign system parameters and room sizing data action will set the minimum flow = maximum flow, assuming CV operation in keeping with the 90.1 PRM and negating the midband profile for variable airflow control. ** For systems 6 and 8, the initial configuration in the Baseline.asp file allows for VSD operation of the fan-powered box using the HP1 control midband profile. However, unless specified in the Loads Data\Proposed\PR06...xls file, the Assign system parameters and room sizing data action will set the minimum flow = maximum flow, assuming CV operation in keeping with the 90.1 PRM and negating the midband profile for variable airflow control. *** While the controller for cooling airlfow in the PTAC and PTHP systems must be continouously variable from zero to the design flow rate, the resulting flow at each simulation time step is modeled within
11 Appendix C: Ground-Source Heat Pump Modeling using ApacheHVAC loads and Gaia Geothermal Ground-Loop Design
Capability for transferring hourly equipment loads and final results between the IES Virtual Environment and Gaia Geothermals Ground Loop Design (GLD) provides for comprehensive and detailed modeling and design of ground-source heat pump HVAC systems. For more information on GLD software, go to: www.gaiageo.com If you are interested in using this coupling of Gaia Geothermal and the IES VE, be sure to check with the distributor of Gaia GLD, Thermal Dynamics Inc., at sales@groundloopdesign.com for discounts that have been and may still be available to licensed IES-VE users.
Modeling Ground-Source Heat Pump HVAC Systems
There is not yet an explicit ground-source heat pump model within ApacheHVAC; however, loads results can be read into Gaia Geothermals Ground-Loop Design tool. This provides detailed modeling of heat pump equipment and bore fields. Begin by modeling the building as you would otherwise in the VE and the appropriate HVAC system in ApacheHVAC, including all controls, air-side components, coils, terminal units, hydronics, water loops, etc. and a boiler and chiller to provide the hot and cold supply water with suitable water loop flow rates and temperatures. Include any loop temperature rest schemes that will be used with the ground-source heat pump (GSHP) system. The ApacheHVAC boiler and chiller components are a placeholder that will simply record loads for the GSHP, ground-source loops and pumps, geo-exchange bore fields, backup heating and cooling equipment (boiler and cooling tower), and time-of-use (TOU) demand-based heat pump controls that can be modelled in GLD 2010. Prior to running the simulation, set the ApacheSim reporting interval to 60 minutes. Having completed up to a full year of simulation in the IES Virtual Environment, instructions from Gaia Geothermal are as follows: Import the .aps results file from the VE into GD via either of the GLD Loads modules (Average Block or Zone Manager). Clicking the Import button (arrow that goes down to the left) opens a dialog that allows import of .aps or .csv files into the Loads module. The .csv option allows for manipulation of loads between the VE and GLD using a spreadsheet to account for an uncommon heating or cooling source or scheme that is not yet available in either the VE or GLD, and thus which would reduce the load passed on to the GSHP.
Do not use the Loads > Import Loads Menu item in GLD to import .aps files, as Gaia Geothermal have not set this up yet to work with .aps files. The .asp file import for boiler and chiller loads from the VE must be done through one of the Loads modules (Average Block or Zone Manager).
Create a Borehole Design project and make sure it is properly linked to the correct Loads projecti.e., it is populated from the .aps or .csv file that contains the loads from the VE. From this point forward, use GLD as you would otherwise to model the complete GSHP system, including detailed bore field design and manufacturer heat pump performance data. Once the analysis in GLD is complete, you can export from GLD to an .aps file that IES VE can then read for display and further analysis of results. The steps for that are as follows:
1. Completed the Hourly simulation in GLD 2. Go to the main File menu > Export File > Export APS and save the data generated by GLD as an .aps file that can be read by IES VE. VE 6.4 ApacheHVAC 321
The following requirements must be adhered to for exporting APS files from GLD for use with the IES VE:
A. Make sure you run the GLD program as an Administrator on Windows Vista or Windows 7 B. Must run an Hourly Simulation in the BoreHole Designer C. Do not exceed a 1-year modelling period (Prediction Time) D. Make sure that the "APS FIles" Folder exists in the GLD2010 directory.
Note: A quick way to test the Hourly simulation and the ability to export the .aps files is to use a very short prediction time in GLD, such as 0.1 years, so that you dont have to wait a long time for the full year analysis.
GLD results exported to the IES VE .aps file should appear in Vista Results as in the screen capture above. If you have followed the steps above without success, first check that the .aps file from the VE does in fact include boiler and/or chiller loads to be addressed by the heat pump system. If you have confirmed these loads are present in the file, but are still having difficulty, Gaia Geothermal has expressed willingness to provide technical assistance to GLD users to address any import/export issues.
VE 6.4 ApacheHVAC 322
Note that as of version 6.3, the part-load-curve chiller will need to be on a chilled water loop; however, the water loop is readily made irrelevant by setting the W/gpm values to zero for both primary and secondary loop pumps and using the Simple cooling coil model (selected in the cooling coil dialog), which conveys load but is not sensitive to water flow and temperature. The Heat rejection tab should be left with no cooling tower. In the Chiller set, simply Add a Part-load curve chiller model. 2. Use a Generic heat source component for the heating mode. Depending upon whether heating mode performance varies more significantly with load fraction or outdoor temperature, the part-load-curve Heating equipment inputs or Air-source heat pump (both accessed from within the Generic heat source dialog) can be used to model the heating mode (addressing heating loads when rejected heat from cooling-mode operation is not available). In a warm climate where the variation of outdoor source temperature does not significantly influence capacity and COP, the ability to model COP variation with part-load fraction may be most valuable. Efficiency values (which can be in excess of 100%e.g., 350% to represent a COP of 3.5) in the Part load curve heating plant dialog are used to indicate up to 10 part-load COP values. If there is backup electric resistance heating, this can be represented by a 100% efficiency value in the last (bottom) row, with the 9th data point representing the heat pump function a maximum output. There should be very small increment for the load range between the 9th and 10th data points so that the model makes a very steep transition rather than smooth ramp of the COP value between these point.
VE 6.4
ApacheHVAC
323
When outdoor temperature is the primary driver for heating mode performance (after using recovered heat when there is simultaneous heating and cooling), the Air-source heat pump (ASHP) may be the preferable option when outdoor temperature is the primary driver for heating mode performance (after using recovered heat when there is simultaneous heating and cooling). The reasons for this are that the ASHP model varies according to outdoor temperature (and thus thermal lift) and also has a setting for the Minimum source temperature below which the unit will cease to operate and will depend fully upon the backup heat source. The ASHP model can still account in some respect for variation of COP with load fraction; however, this must be entered as data points on a single composite curve that indicates both the COP and heat output available for each outdoor temperature. The curve is once again represented by up to 10 data points. For each point, users need to indicate the outside-air source temperature, COP, and heat output available at that temperature. While there are benefits in accounting for variation of performance with outdoor temperature, some analysis may be required to determine appropriate part-load adjustments to the otherwise full-load COP with relatively higher outdoor source temperatures. In other words, the user must first determine how much, assuming otherwise typical operation of the building, the heating load will be reduced from the full-load condition as outdoor temperatures rise. This can then be used to adjust COP according to load fraction for data points associated warmer outdoor temperatures. When using the ASHP, the Part load curve heating plant (see Heating equipment Edit button) within the Generic heat source dialog can be used to represent just the backup heat source. Typically this will be electric resistance heat (efficiency = 100%). 3. Distribution losses associated with refrigerant lines can be accounted for in the Heat source dialog. Airside distribution losses are better accounted for by using the Ductwork heat pickup (heat gain/loss) component on the HVAC network. 4. In the cooling source (part-load curve chiller model), you can specify COP values dependent upon both load and OA dry-bulb conditions. Set the pump and tower fan power to zero. 5. The Condenser Heat Recovery percentage in the part-load curve chiller dialog should be 100% (indicating that all of the heat extracted from zones in cooling can be rejected to zones in heating) and the CHR recipient should point to the Generic heat source you have set up for the heating mode. 6. In the Part-load curve heating plant dialog for the Generic heat source (when using this rather than the ASHP to model heating mode) COP values will be expressed as efficiency valuese.g., 350% to indicate a COP of 3.5). 7. In the Generic heat source dialog, leave the tick box for Use water source heat pump? unticked, as you will already have determined the electrical energy needed to extract this recovered heat on the cooling side. Set the Heating plant type to Other heating plant to keep energy consumption results separate from boilers or DHW heat sources, if any, in the project. The heat load will be apportioned in the following sequence: a. Recovered heat from the part-load cooling source, to the extent it is available b. ASHP, if used rather than a Part-load heat source c. Part-load heat source or backup ER heat-source for ASHP, if the ASHP is used
VE 6.4
ApacheHVAC
324
This method can account for the benefits of moving heat from one zone to another and variation of COP with both load and outdoor temperature (it will account for the degradation of COP and heating capacity with low outdoor temperatures only if the ASHP is used for the heating mode). While the COP for cooling operation will, when outdoor temperature dependence is included, always be a function of both outdoor conditions and load, rather than strictly indoor conditions, as would be the case when transferring heat from one location to another in common-loop VRF/VRV system operation, this method should provide a reasonable approximation of the system performance. Although the CHR facility does allow for modeling energy consumption according to a COP associated with upgrading heat from a condenser loop to a heating loop (e.g., as in a WSHP), this is not necessary in this case, as the heating coils will effectively operate as the condenser for the DX cooling when heat is being transferred via CHR. There is also an input within the part-loadcurve chiller dialog for the percentage of condenser heat available for recovery. When there is no heat exchanger required in the refrigerant system, and thus no exchanger effectiveness to model, and no alternate means of rejecting condenser heat when it is being routed to condenser coils that are directly heating spaces, the available CHR percentage ought to be approaching 100%. The compressor COP should account for losses associated with compressor heat rejection directly to the surrounding air. As a small amount of heat will be lost in the distribution of refrigerant to coils in heat rejection (heating) mode, an appropriate value for available CHR percentage might be on the order of 95%, depending on the system components, configuration, and installation.
The graph below shows results for a modest 25-zone office building on a day where heating and cooling loads overlap. There is one air-source heat pump (ASHP) acting as the heating mode of the VRV system and one part-load-curve chiller as the cooling mode of the VRV. These components within ApacheHVAC are permitted to serve multiple heating and cooling coils, as would be the case in a VRV system. In the illustrated example, the ASHP and part-load cooling sources are coupled to heating and cooling coils in a multiplexed stack of 25 packaged single-zone systems for the individual zones. These are created from either the prototype Packaged single-zone system 04 or prototype Packaged terminal heat pump system 02, as provided in pre-defined configuration. With just two exceptions, the pre-defined configurations remain unchanged: Switch the cooling coil from the dedicated DX cooling model to the part-load curve chiller model of similar characteristics set up to represent the VRV cooling mode and that includes the condenser heat recovery (CHR) capability. Set pump power in both the chiller model dialog and chilled water loop dialog to zero. This provides the capability for having many cooling coils connected to one cooling source. o The dedicated DX Cooling model using performance curves and accounting for the entering air WBT at the DX evaporator coils provided as of VE 6.1.1 is thus far set up to run only with one DX evaporator coil per DX cooling source (compressor & condenser) and without any form of CHR to be passed to an ASHP. Therefore, the default assignment of DX coils to this model in a pre-defined system needs to be changed.
Change the System type for the heating coils to Generic heat source and select the generic source that you have set up to represent the VRV heating mode. o Note that as of VE 6.4.1 the ASHP is no longer placed on the airside network and has been replaced by two separate dedicated components: an air-to-air heat pump (AAHP) and airto-water heat pump (AWHP). The former, like the DX Cooling Types, has a one-to-one relationship between the heat pump and heating coils. Thereforeuntil a dedicated VRV
ApacheHVAC 325
VE 6.4
model is providedthe connection to multiple coils for a VRV model requires using the Air-source heat pump (ASHP) accessed from within the Generic heat source dialog. The condenser heat recovery (CHR) acts as the common refrigerant loop to pass heat from the zones in cooling mode to those requiring heat. The CHR points to a Generic heat source representing the VRV heating mode (via options described above) and electric-resistance backup heat. The ER backup is third in line to meet heating loads after the CHR and VRV heating mode (part-load-curve or ASHP) capacity are fully used. Because the backup heat source will always have an infinitely expandable capacity, any limitation of heating capacity needs to be specified in terms of the capacity of the each heating coils. Maximum cooling capacity is similarly limited by the capacity specified for each simple cooling coil (advanced coils, water loops, and detailed chiller models must be used to model the cooling performance of under-served coils in the case of intentionally constrained plant equipment capacity). The graph below shows the recovered heat from the cooling mode (green line) taking precedence over the ASHP (VRV heating mode) to meet heating load. It also shows that the cooling system is accounting for the energy required to extract this heat via an evaporator coil in zones where cooling is taking place and then pumping it to the heating side. Thus the electrical energy consumption for this extraction of heat from zones in cooling mode does not need to be counted separately on the heating side.
VE 6.4
ApacheHVAC
326
In working out the these methods, our observation is that for many building types and configurations, if the systems are suitably controlled, there should be very little temporal overlap of heating and cooling modes in a building effectively served by a large number of single-zone systems sharing a common outdoor component. It would therefore appear that, in many applications, much of the efficiency (or perhaps better referred to as efficacy) of VRV/VRF systems stems from their avoidance of the one-sizefits-all plus re-heat outcome typical of a multi-zone packaged VAV system. In other words, the commonloop aspect of the configuration often seems to be secondary, in terms of providing reduced energy consumption, to other aspects of VRV, such as obviating the need for re-heat. The table of results below shows another means of confirming the transfer of recovered heat from zones in cooling mode to zones in heating mode: When there is a cooling load present and the cooling load (total for all zones presently in cooling mode) times the cooling COPi.e., the amount of heat that needs to be rejected by the VRV system in cooling modeis equal to or greater than the heating coils load (total for all zones presently in heating mode), then the part-load heat source or heat pump load should go to zero, as should the backup heat source if using the ASHP with backup electric heat.
The two graphs on the next page show additional examples of results variables that can be examined to analyze the performance of VRV performance for particular project. Results such as these can be used as a quick reality check to see that the system is behaving as expects. They can also be used to provide more detailed analysis of what sort of performance might be expected under various conditions.
VE 6.4
ApacheHVAC
327
VE 6.4
ApacheHVAC
328
All chilled ceiling panel systems, all four-pipe heating/cooling panel systems, all radiator/panel and fintube convector heating, and most heating-only slabs can use the first and simpler one of these two options. In the case of heating-only slabs, the panel-based method is often adequate given that the thermal and energy performance for most heating-only systems does not depend significantly on taking advantage of thermal mass and off-peak operation of equipment. However, there are cases, such as a space with a heated floor slab that also receives significant direct solar gain, for which is will be important to use the second method to accurately model the thermodynamics of the floor slab. In other words, if the slab is likely to become thermally saturated by direct solar gain, this will both provide buffering of peak solar gain and alter the delta-T between the hydronic loops and the slab material, thus affecting the load profile for the heating source. Modeling radiant cooling systems requires further considerations, and thus drives the need for using the second method in all cases where there are cooled elements of the building fabric (e.g., a floor or ceiling slab) rather than a cooled metal ceiling panel. Furthermore, it is common for cooled slabs to have surface temperature sensors, and these can be modeled only with the second method. Combined heating/cooling systems are subject to the same considerations as cooling-only systems, plus additional care with respect to sensors signals and controls to avoid inefficient consecutive operation of heating and cooling modes.
VE 6.4 ApacheHVAC 329
There are seven essential considerations in selecting the appropriate method. The last three of these are significant mainly with respect to actively cooled concrete slabs or similar elements of the building fabric: 1. Type of hydronic radiant system: lightweight panels vs. thermally massive slabs? 2. Design phase: in conceptual or schematic design, simpler panel models may more often be sufficient 3. Location of cooled surfaces or building elements relative to the occupied space a. Location of panels relative to the occupied space: horizontal (overhead) or vertical panels b. Location of slabs relative to occupied space, ground, and outdoors: ceiling, floor, and/or walls 4. Operating modes: heating-only, cooling-only, or both? 5. Interaction of chilled slabs with solar loads: will active slabs frequently receive direct solar gain? 6. Level of accuracy: model the slab cooling capacity or use pre-determined value per delta-T? 7. Significance of slab material thickness: e.g., is there intent to assess potential for pre-cooling? 8. Physical coupling with other systems and building elements; for example: Is there an underfloor air distribution (UFAD) plenum on top of the radiant slab through which the supply air will exchange heat with the slab? Is there a warm return air plenum under a chilled floor slab? Is the use of thermal displacement ventilation (DV) or a UFAD system likely to increase the delta-T, and thus the convective heat transfer, at the surface of a chilled ceiling? Modeling of radiant cooling, with and/or without heating, should facilitate or account for the following: Radiant and convective heat transfer to and from cooled panels and/or slabs Orientation of panels (horizontal or vertical) and physical location and orientation of active slabs Differing characteristics (capacity at delta-T, radiant/convective split) of various panel options Thermal mass and absorption of direct solar gain for actively cooled slabs Rate of heat transfer resulting from hydronic tube spacing and depth in radiant slabs Slab surface and occupied zone temperatures Control of water temperatures and flow rates in zone-level hydronic loops according to slab core or surface temperature, occupied space temperature, and/or outdoor temperature resets Modeling of chilled and hot-water sources, loops, and pumps, including heating and cooling sources Potential effectiveness of low-energy heating and cooling water sources that take advantage of the moderate water temperature usable (and often required) in radiant systemse.g. indirect evaporative cooling, waterside economizers, condenser heat recovery, condensing boilers, and solar hot water. Potential for nighttime and early morning pre-cooling of chilled slabs Assessment of occupant thermal comfort, including dry-resultant or operative temperature both during peak cooling demand and in early morning occupied hours where pre-cooling is included Integrated operation and control of hydronic and airside systems, including dedicated outside air systems (DOAS) for ventilation, latent loads/condensation control, and energy recovery Controls for mixed-mode systems (natural ventilation plus radiant), where applicable Capability for modeling stratified thermal environments, with or without displacement ventilation, where appropriate to space type and or system design Controls for automated shading devices and/or of modeling user-operated shading, daylight-based dimming of electric lights, and other active load-control strategies
All of the above are supported within the IES <Virtual Environment>.
VE 6.4 ApacheHVAC 330
To the extent they are present in the system, all heated or chilled ceiling and wall panels, four-pipe heating/cooling panels, radiators, fin-tube convector heating, and most heating-only radiant slabs can be appropriately modeled using the first (panel-component-based) method. With this method, only radiant slabs require special considerations to mimic the performance of the massive slab and to appropriately constrain output when the active slab is a floor or similar surface that occupants will be in contact with. These considerations are described in the next section below. All of the other hydronic terminal unit devices mentioned above can be modeled without any special considerations.
13.1 Modeling hydronic heated and/or cooled slabs using radiant panels (method 1)
This method approximates the performance of a hydronic radiant slab using radiant heating and cooling panels within the conditioned space. There are no slab zones and nothing inside of any floor or ceiling construction. Panel performance parameters are treated much as they would with actual heating and cooling panels, with two very important exceptions: the panels representing the slab will be massive and, if the slab is a floor, the surface of the panels must be treated as a floor with people walking on it and sitting immediately above it. Radiator and Chilled ceiling Types dialogs: Orientation should be horizontal if this is to mimic a ceiling or floor; vertical if an active wall element. Radiant fraction should be set according to the split of convective vs. radiant effect. The faction will tend to be higher for a cooled floor or heated ceiling than for a cooled ceiling or heated floor, given the convective heat transfer characteristics of floor and ceiling surfaces. When using a model of radiant panels to mimic a heated and/or cooled slab the reference surface-toair delta-T and associated heating or cooling capacity must be constrained by the need to maintain slab surface temperatures within the range desired for human thermal comforttypically 64F (18C) minimum in cooling mode and 75F (24C) in heating mode. Given room air temperature of around 75F (24C) when in cooling mode and 68F (20C) when in heating mode, the reference delta-T values would be just 11F (6 K) and 7F (4 K) for cooling and heating modes, respectively. The heat or cooling output at the reference temperature should then be set at a reasonable value for this modest delta-T. In the case of a heated floor, the convective heat transfer coefficient will be higher, and thus capacity will be better than a heated ceiling slab. In the case of a cooled floor, unless there is direct-beam sun striking the floor to present the load very directly, the cooled floor will have less cooling effect than a cooled ceiling, given convective heat transfer will be very limited in the downward direction. Sensible cooling capacity for typical slab-to-space temperature differentials is on the order of 24 Btu/hr-ft2 (~7 W/ft2 or 77 W/m2) of active surface, not including associated ventilation systems or strategies. When even a relatively low-cooling-capacity ventilation system, such as DV, is also accounted for, cooling capacities begin to approach those of conventional all-air VAV systems. Water capacity should be the volume in each radiant loop/zone, within reason, as the effect of this will be dwarfed by the effect of the massive floor. The weight should reflect the approximate mass of the heated/cooled floor construction. Again, very rough numbers can be used at this stage just to approximate the thermal inertia of the slab. Additional general technical information such as that provided above, along with many references for further reading, is available in a paper authored by ApacheHVAC Product Manager, Timothy Moore, prior to his joining IES. This paper is available from the UC Berkeley Center for the Built Environment at www.cbe.berkeley.edu/research/pdf_files/IR_RadCoolScoping_2006.pdf
ApacheHVAC 331
VE 6.4
13.2 Modeling heated or cooled slabs using slab zones and hydronic loops (method 2)
For the second methoddetailed modeling of heated and or/cooled hydronic radiant slabsthere are a number of specialized steps that must be taken. The following provides guidelines for these within the VE.
VE 6.4
the U-value adjustment tool) to appropriately represent the sum of all potential heat transfer paths through the ground to the outside air (see below).
If the conditioned slab is in contact with the ground, user the Ground-contact U-value adjustment facility within the Ground-contact/Exposed Floors section of the constructions database (ApCdb) to add an appropriate U-value adjustment layer. Both EN-ISO and F-Factor methods are provided. Whether there is to be perimeter or under-slab insulation in the project, this facility will add an additional layer of insulation in the construction to represent the resistance of the average path from the average underside of your building to the outside air. This layer is best added beyond the 30 (0.75 m) of earth normally included in ground-contact constructions. For hydronic slabsespecially if uninsulated belowthe thermal mass of this soil is important with to include adjacent to the floor. The inside surface for both the slab top and bottom (ceiling and floor, which will be the ceiling of the room below for non-ground-floor stories of the building) need to have internal air-film resistance set to 0.0001 ft2-hr-F/Btu (or 2 0.0001 m K/W, effectively zero, but not zero). This facilitates modeling the water in direct contact with the construction. Conductivity for the concrete material in slab top and bottom constructions should be reduced (adjusted to an appropriate lower value) to account for the spacing and depth of the tubes within the slab, plus the resistance of the PEX tubing wall. This is best done with a 2D finite-element model of just two tubes in a cross-section of the slab top and slab bottom using LBNLs free THERM tool. This tool provides a quick and accurate means of determining an overall U-value for the combination of all heat-transfer paths between the slab surface and the water in the tubes. Typically, depending upon hydronic tube material, depth, and spacing, the conductivity value for the concrete material will need to be reduced about 20 to 60%---i.e., to about 40 to 80% of its initial value. Whereas the unadjusted value would over-predict heat transfer, too small a value will under-predict it.
VE 6.4
ApacheHVAC
333
The THERM model and spreadsheet calculations above are used to determine the correct adjusted conductivity for the concrete slab or other material in which the hydronic tubing is embedded. The THERM model is relatively simple and the spreadsheet calculations are simply used to convert U-value to resistance, then subtract the resistance of the water film in the tube and air film on the exposed surface, convert resistance to conductance, and finally use this to calculate the adjusted conductivity value for the concrete material. This final number will be entered into the concrete layer of the construction in the VE and will account for the tube material, diameter, depth from the surface, and spacing within the slab. The following excerpt from SIMULATION OF RADIANT COOLING PERFORMANCE WITH EVAPORATIVE COOLING SOURCES (T. Moore, May 2008; Center for the Built Environment) provides further explanation of the simple slab and hydronic tube model preparation in THERM. Following that within this appendix is a section (12.2.2) on setting up hydronic loops and controls for radiant slabs in ApacheHVAC. Additional information on both of these topics can be found in SIMULATION OF RADIANT COOLING PERFORMANCE WITH EVAPORATIVE COOLING SOURCES, available from the UC Berkeley Center for the Built Environment at: www.cbe.berkeley.edu/research/pdf_files/Moore2008-RadCoolSimulations.pdf
VE 6.4
ApacheHVAC
334
Lower half of cast concrete ceiling/floor slab material: The upper half mirrors the dimensions and heat transfer pathways from the embedded hydronic tubing to the cooling surface; adjacent portions of the slab to each side repeat this cell in keeping with the tube spacing.
Chilled ceiling surface boundary condition with adjacent air at 25C (77.4F)
Radiation enclosure with facing surfaces at 24C (75F) Figure 144a: A cross-section of the concrete slab with embedded hydronic tubing is described in THERM as a repeatable segment bounded by the chilled surface (bottom), center of the tubing (top), and midpoint between tubes (either side). Boundaries other than the tube interior and chilled surface are adiabatic.
Figure 13b: Isothermal contours indicate the distribution of temperatures resulting from the finite-element model of two-dimensional heat transfer between boundary conditions.
Figure 13c: Isothermal contours as graduated colored/grayscale fills provide a visualization of continuous temperature gradients throughout a cross-section of the chilled slab material.
VE 6.4
ApacheHVAC
335
VE 6.4
The airside network branch that couples the slab zones must have a time switch controller with Flow Rate set to zero. Temperature sensor locations for hydronic slab heating and cooling loop controllers (Radiators and Chilled Ceilings) should be determined by design. These locations can include any combination of slab core (local or within the slab zone), slab surface, the adjacent occupied space conditioned by the slab, any other space in the building where the thermostat would be located, and/or external to the building (for modeling water temperature reset based upon outdoor temperature). Water temperatures for heating and cooling should be set appropriate to radiant slab design parametersi.e., to avoid thermal discomfort or condensation issuesand in keeping with any limitations imposed by low-energy heating and cooling sources used in the project. When using room temperature sensors rather than a surface temperature sensor assigned to the surface of the slab itself, the radiant fraction in the controllers should normally be set to a small fraction of 1, or about 0.10.2 for a typical wall-mounted thermostat. However, if the project will use a specialized thermostat that approximates operative temperature, a more appropriate value for the sensor radiant fraction may be in the range of 0.40.5. Flow rates for hydronic loop controls are, as of VE 6.4, not yet autosized; however, they can be relatively easily calculated using the standard formulas [gpm = Btu/h / (500 x delta-T)] and results of the ASHRE Loads analysis (either from the VE directly or in the Loads Data spreadsheet generated for a custom version an otherwise pre-defined prototype ApacheHVAC system).
VE 6.4
ApacheHVAC
337
14
The pre-defined UFAD systems in ApacheHVAC include a re-mixing path and control This can also be used in a baseline version of the same systems to destroy the stratification all of the time and more completely, rather than just when in heating mode and to the extent the fan-powered box operates. The tricky part is to get the autosizing process to calculate the correct zone-level airflow rates for both the proposed and baseline models.
**** separate **** 1. If you want to use the remixing path for the baseline system (or some version of the proposed that is not meant to be stratified), then you do need to have the zone-level loads of occupied and stratified zones combined by adding a column that does this in the Loads data spreadsheet for any affected system in order to have the zone airflows properly sized. This is not as difficult as it might sounds. Example:
VE 6.4
ApacheHVAC
338
2. As for whether or not to include the UFAD plenum in the model, there are a number of advantages in terms of modeling how UFAD systems actually work. In my judgment, it is valuable and perhaps even essential to model the plenum whenever one or more of the following is true: a. The raised floor top surface of the UFAD plenum sees direct-beam solar gain. b. The UFAD plenum is sitting on a floor deck that has a return plenum below it, as in many multistory projects. In either of these two cases, there will be significant gain to the plenum, and thus the supply air temperature to the zone will not be the same as the leaving temperature from the AHU (regardless of whether youre including duct heat gain). As the plenum area is generally large, gain to the plenum can be as well. A study by CBE showed that, even for a core zone, as much as 40% of gain in a typical multi-story office space with RA plenum below can end up in the supply air before it reaches the diffusers. When direct beam solar is striking the raised floor, the effect can be much greater. **** separate **** The re-mixing path and control is used primarily to de-stratify the model in spaces that are served by a UFAD system and have a fan-powered box for reheat (such as perimeter zones or private offices) that is able to stir the space. This may be by extracting room air as an induced secondary airflow into the fan-powered box (how our prototype is set up by default) or simply by coupling the fan-powered box to a diffuser that blows air up the glazed perimeter wall. In any case, if the UFAD system is design and implemented properly, there will be good stratification in cooling mode and little to no stratification in heating mode so you dont waste any of that nice warm air when you need it! The modeling of this is intended to de-stratify the space when and only when the fan-powered box is operating. The remixing path is highlighted in yellow below. The controller for this is in red, including the logical AND connection to the fan-powered box controller, and the controller dialog is at right.
VE 6.4
ApacheHVAC
339
The version that you have n your model requires one minor fix (as has been implemented in version 6.4.0.8): The logical AND connection needs to be moved from the re-heat coil controller to the fanpowered box controller. Simply open the re-mixing controller, select and remove the AND connection, and then replace it by selecting the AND tool and clicking and dragging the connection from the flow controller on the FPB loop to the controller on the re-mixing path. In addition to what I noted previously, if you want to use the remixing path for the baseline system (or some version of the proposed that is not meant to be stratified), then you do need to do two things: o Combine the zone-level loads of occupied and stratified zones by adding a column that does this in the Loads data spreadsheet for any affected system in order to have the zone airflows
VE 6.4
ApacheHVAC
340
properly sized. The reason for this is that the ApacheHVAC system does not actually run yet when you are doing the zone-level stage of system sizing. o Remove the logical AND connection from the controller on the re-mixing path so that it will run continuously at the time of simulation.
Also, heres a fully labeled image of the prototype UFAD system as it appears in version 6.5 (different graphics, but youll get the idea), in case this is of any help.
**** separate **** The radiant fraction of an internal gain is seen by all surfaces in the space to which the gain is assigned. I put surfaces in quotes, as this includes the hole that connects the occupied and stratified zones in each room. As such, if, for example, the ceiling above and hole at the base of the stratified zone in a particular room were to account for 80% of the total surface area of that stratified zone, then 40% of the radiative energy would initially strike the ceiling and 40% would strike the hole as a surface. The remaining 20% would be distributed among the walls of the stratified zone in proportion to their surface area. In other words, as a proxy for actual view factors, which can get very computationally weighty, the radiant energy is distributed to surfaces as an area-weighted proportion of the total.
VE 6.4
ApacheHVAC
341
Once the radiative energy from the internal gain has been distributed, along with other radiative inputs, surface temperatures and the differences thereof are used to calculate radiant exchange between surfaces. When the hole as a pseudo surface between occupied and stratified zones receives radiation from the lights, it cannot heat up and store energy to then convectively heat the adjacent air, as it has no thermal capacity of its own; however, it does communicate the radiation it receives to all of the surfaces that it can see. This re-distribution is done in proportion to surface area and temperature of receiving surfaces, as with other radiant exchanges. As such, the hole acts somewhat like a diffusing lens that scatters the radiation passing through it according the area and relative temperature of the surfaces it can see. In the case your model of a commercial office space with UFAD system, Option 1 is the method that would be appropriate for lightsassuming the lights are either surface mounted or pendant fixtures. The convective gain will be 100% in the stratified zone and the 40% of the overall gain that you have indicated as radiant will be distributed as described above. Because the hole connecting the occupied and stratified zones has no surface area as a floor for that space in the 3D model, if the lighting gain in the stratified is to set in terms of W/m^2, this needs to be done prior to creating the 100% hole in the partition separating the occupied and stratified zones. Once these gains have been specified in W/m^2, select all stratified zones and use the Tabular Room Data tool in the Apache Thermal view with all rows selected in that window to simultaneously change the Input Mode for all lighting gains in the stratified zones from W/m^2 to W. Youll need to do the same for the stratified fraction of equipment and task-light loads (see below) prior to adding the holes between zones, otherwise these gains will be set to zero when you replace the floor partition for the stratified zone with a hole of the same area. If you have a return plenum at the ceiling AND the light fixtures are mounted within the drop ceiling such that a fraction of the radiant and convective go directly to the RA plenum, then you need to have one more separate lighting gain defined for the plenum. If, for example, you had 10 W/m^2 total lighting gain with 20% overall going to the plenum and 40% overall radiative, you would have two lighting gains defined: Stratified zone = 8 W/m^2 and 40% radiative and Plenum zone = 2 W/m^2 and 40% radiative. This assumes that the top surface of the fixture is white painted metal or plastic, etc., such that is has typical emissivity and thus the portion of gain directed up into the plenum as radiant energy will be similar to that directed down into the room. For a UFAD system (of DV or radiant cooling) including the radiant fractions for these gains is important, as the top and bottom constructions (raised floor and floor deck below) will be cooled by the supply air much like a radiant cooling slab. The same is true for DV systems that gently pour cool air to form a more or less continuous shallow pool of cool air on the floor. The floor gets cool. As the raised floor of a UFAD plenum is cooler than the ceiling it can see above, which is surrounded by the stratified zone and RA plenum, it will received radiant heat from the ceiling. As long as there is thermal stratification, this will be true for the model and in the real world. Similarly, in a multi-story building, because the floor deck under the UFAD plenum will be cooled by the supply airlike an air-cooled version of a hydronic radiant slabit will receive both radiative and convective gain from the much warmer RA plenum below. The result of gain at the top and bottom of the UFAD plenum is gain in the supply air, just as in the real-world plenum. Even when there is no direct-beam sun striking the raised floor surface, gain to the supply air in the plenum can account for as much as about 14% of the gain removed from the space. When there is directbeam solar striking the raised floor, this can be much greater. In keeping with the logic above for lighting in a commercial office space, gains for both equipment/task lights and people will need to be appropriately distributed. Because equipment and task lights tend to be stationary, these will have stronger and more consistent thermal plumes. Therefore, depending upon the
VE 6.4 ApacheHVAC 342
mix of actual devices, the plume factor for these might be on the order of 70%i.e., 70% of their gain should be directly assigned to the stratified zone. As for radiant fraction, however, only the portion of the gain assigned to the occupied zone (the actual location of the equipment As noted above, if equipment/task-light gains are to be specified in W/m^2, the fraction of the gain that will be assigned to the stratified zone needs to be placed there and converted to an absolute gain (expressed in Watts) prior to replacing the partition surface with a hole. As people are much less consistent with respect to thermal plumes (they tend to fidget, move about, and sometime breath with some force, thus making for inconsistent thermal plumes), the above approach to lighting, equipment, and task lights will account for much of the dependable thermal stratification from internal gains. What to do with the occupant gains then becomes a bit of a judgment call with respect to providing a fair approximation of real-world thermodynamics for the particular type of space, use, and occupancy. If the space is relatively lightly occupied, as with mainly office spaces, simply placing all occupant gains in the occupied zone introduces a modest conservatism, but simplifies inputs for occupant gains as well as occupancy-based ventilation calculations and inputs. The contribution of CO2 from occupants, which is calculated in proportion to combined sensible and latent gains for the occupants in a space at any given simulation time step, will also accrue 100% to the occupied space when all people gains are placed there. On the other hand, if the space is densely occupied and occupants will be mainly sedentary, it may be worth splitting the loads such that 3060% of occupant gains are assigned to the stratified zone, along with lighting and/or equipment. This may be particularly important for a theater or similar space conditioned by a thermal displacement ventilation (DV) system. If a separate people gain is used to assign a portion of heat from occupants to the stratified zone, the split between the occupied zone and stratified zone gains should be done as follows: Lets use the example of a relatively densely occupied call center with each occupant given 4 m^2 of space (about 40 sf/person). Lets assume that, given available research or CFD modeling, it was judged that an average of 50% of the sensible thermal gains from occupants would accrue to the stratified zone in the form of thermal plumes, thus bypassing the occupied air volume and thermostat. Lets also assume that, given the slightly tense and stressful nature of the call center work, the sensible gain per occupant was estimated to average 120 W/person and the 75 W/person latent gain will be omitted from consideration with respect to thermal plumes (although this is a bit of a simplification, all latent gain will be assumed to be mixed with the occupied air volume by occupant breathing and movement, rather than some of it being transferred immediately to the stratified zone). Begin, before replacing the partition between occupied and stratified zones with a hole, by creating separate people gains for the occupied and stratified zones. Both should use the full occupant density of 4 m^2 per person, which will aid in other occupant-dependent inputs and calculations for the occupied zone; however, both will use only 50% of the sensible gain (60 W/person for each). While full 75 W/person latent gain will be used for the occupied zone people gain, the latent gain will be set to zero W/person for the stratified zone (the latent gain, as with CO2 added to the occupied zone, will eventually pass through the stratified zone, but only after being fully mixed with the occupied zone air and then diluted and displaced by introduction of supply air). Where the space is densely occupied and de-humidification will be controlled according to the relative humidity in the occupied zone, it will be important to also split the latent gains so that they accrue to both occupied and stratified zones. In the example above, it may be appropriate to include roughly 40 W/person latent gain in the occupied zone people gain and 35 W/person latent gain in the stratified zone people gain.
VE 6.4
ApacheHVAC
343
Where CO2-based demand-controlled ventilation controls are to be modeled to reflect CO2 sensors that will actually be placed in the occupied zone of the built spaces, it will be important to maintain the people gain type in the stratified zone in order to have CO2 accrue to both occupied and stratified zones in proportion to the combined. Note that whenever the people gain type is used for internal gains directly assigned to the stratified zone, care should be taken to zero out any occupancy-based calculation of fresh air for stratified zones. The fresh air should be calculated for and introduced into only the occupied zones. The proper calculation of fresh air ventilation rates for the occupied zone is the primary reason for placing the full occupant density (number of occupants) in both occupied and corresponding stratified zones, and then adjusting the sensible and latent gains per person to reflect the thermal plume factorsi.e., reducing each to split the gains appropriately.
VE 6.4
ApacheHVAC
344
Typical configurations
The initial configuration for Solar Hot Water in ApacheHVAC (as of VE 6.4.1) will most often be used in low-temperature heating systems, such as hydronic radiant floors, for which the return water temperature is quite low. This solar HW application is normally paired with a condensing boiler as the backup heat source, so as to maximize the opportunity for actual condensing operation, which also required a moderate return temperature. Solar hot water panels as a pre-heating system on the HW loop return is also a configuration sometimes used for natatoriums. However, a heat pump or heat-recovery chiller may more sense in such cases as means of handling latent loads from pool evaporation on the evaporator side, with condenser heat being rejected to the pool. This is because the majority of heat loss from swimming pools is typically in the form of latent heat and the air then needs to be dried to avoid condensation on windows and other components of the building fabric.
Advanced configurations
Then there are more complex strategies, such as that implemented for a regional hospital project in BC Canada, that use hot, cold, and temperate water loops with two water-to-water heat pumps to facilitate recovery of heat from low-temperature sources, such as the exhaust air stream, to heat both DHW and occupied spaces. A strategy such as this presents an opportunity for solar heating of both DHW (heating cold water from the mains) and for putting heat into the heat recovery loop that is then a resource for water-source heat pumps. The range of applications for the solar HW in ApacheHVAC will further expand as IES adds water-to-water heat pumps and additional configuration options. Presently, however, users can model heat-recovery chillers and can upgrade the temperature of condenser heat from a chiller set via a single-COP heat pump option on the HW loop.
VE 6.4
ApacheHVAC
345
16 Appendix H: Thermal Storage for Cooling in ApacheHVAC (Work in Progress this section under construction)
With version 6.5, the water-source heat exchanger (WSHX) will provide opportunity for a new method: Users can create a thermal zone outside the building that mimics the tank in terms of thermal capacity of the water or brine in the tank, wall materials, insulation, and ground-contact thermal effects. Then place two hydronic unitsa radiator/heating panel and a chilled-ceiling panelwithin this zone to add and subtract heat. The chilled panel can be on a either a dedicated loop or the chilled water loop that with operate at night to build up the stored coolth. This may be easiest is connected to the separate Dedicated WSE cooling tower model, otherwise there might be a challenge keeping the chiller from coming on as a backup. The hydronic cooling of this storage tank zone will be controlled to be cooled as much as the cooling tower can cool it (down to some set point). Because the HVAC system cannot yet draw coolth as a resource from this pre-cooled tank zone when cooling loads are present, a formula profile should be used to relay the temperature of the tank zone at each time step to the water-source heat exchanger (WSHX). Any profile (schedule) can contain a formula that is scheduled for use at any particular time of day/date range, and the formula can include references to both outdoor climate variables and conditions in specified rooms or thermal zones. The WSHX needs a profile for the source/sink temperature. The last bit that is needed is to account for the depletion of coolth stored in the tank. This can be accomplished by running the hydronic heating device (a hot-water radiator defined to have purely convective heat transfer) in the tank whenever and to the extent to which conditioned spaces on the system need cooling. Logical OR connections to the controllers for space cooling need to be used to tell this device to heat the tank whenever the system should be drawing coolth from it. The extent of heating should be proportionally controlled in keeping with the extent of cooling needed either at the zone level or at some point in the system, depending upon the system configuration. This is broadly similar to a supply air temperature reset control. In essence, the hydronic heating device should add heat with appropriate water temperature and flow rate to approximate the daytime rejection of heat to the storage tank. The formula profile referencing the tank zone is used to provide this temperature to the WSHX serving as the pre-cooling device on the chilled water loop. While a little rough and not entirely simple, this method can a dynamic model of the thermal mass of the water in the tank, the tank construction and its coupling to the ground, the cooling of the tank volume, the available water temperature of the tank as a pre-cooled resource, the rejection of heat to the tank, and therefore the warming of the tank as heat is rejected to it.
VE 6.4
ApacheHVAC
346
VE 6.4
ApacheHVAC
347
The COP values in the pre-defined DX Cooling types match ASHRAE 90.1-2007 requirements (according to the tables at the end of Chapter 6), as adjusted per CA Titlte-24 ACM Manual methods to remove the supply fan power from the EER that was determined for a packaged unit at ARI conditions. This is the same as what is done for older 90.1 EER numbers (with fan) provided as pre-defined options in the eQuest Wizard and subsequent conversion of these to EIR without fan in the detailed interface. The difference in ApacheHVAC is that, rather than presenting an EER with SA fan and converting it to an EIR without SA fan, the DX Cooling Type dialog provides the EER with SA fan from 90.1 chapter 6 tables only in the reference name of the DX Cooling Type. The actual number used in the input field for that dialog is the COP without the fani.e., after applying the Title-24 ACM method for removing the supply fan power.
VE 6.4
ApacheHVAC
348
17.1.3 Baseline systems 2 and 4 Packaged Terminal Heat Pump (PTHP) and Packaged Single-Zone Heat Pump (PSZ-HP)
Default autosizing for pre-defined Heat Pumps in ApacheHVAC sets the heating capacity at ARI rating condition of 47 F equal to the full heating load assigned to the HP in the Heating Design Sizing run. Using the default performance curves, the capacity actually available from the HP alone at the design heating outdoor condition will be significantly less (on the order of 30 to 60% of the rated capacity, depending on climate, etc.). The remaining load will be met by the backup heat source, which, by default, is electric resistance heating with infinite capacity. For ASHRAE 90.1 PRM Baseline Systems, check that the default autosized capacity does not significantly conflict with the following considerations: Generally, the ASHP heating capacity should be within about +/- 10 to 20% of the cooling capacity to mimic the behavior of actual equipment. Heating capacity for actual equipment is often, but not always, on the order of 15% less than cooling capacity. Using this as a guideline, rather than exactly matching the sizes or sizing the heating capacity larger to meet more of the winter heating load without backup (as such equipment can be selected), will cause the electric resistance heat to begin sharing the load at a temperature closer to the 40 F outdoor maximum permitted for electric backup operation. For ASHRAE 90.1 PRM Baseline Systems, the ASHP heating capacity should must be sufficient to maintain the space heating setpoint without solar or internal gains when the outdoor temperature is 40 F, such that the backup electric heat never supplements the heat pump when the outdoor temperature is 40 F or higher. If the required heating capacity to maintain the 40 F upper limit for backup heat source operation is significantly greater than the cooling capacity (e.g., ), the cooling capacity should be increased so that the heating and cooling capacities are more fairly representative of actual equipment. This will cause the simulated DX cooling mode to operate at a lower part-load fraction and may require revision of the cooling mode COP if the cooling capacity is shifted to a higher range with respect to ASHRAE 90.1-2007 tables 6.8.1B and 6.8.1D. For actual applications, this will typically be a function of the equipment selection and sizingoften, but not always, prioritized for Design Cooling Loadswith the heating and cooling capacity both determined by sizing at 100 to 125% of the cooling load. However, for heating, the NRCAN recommended outdoor temperature balance point (OA temp at which capacity equals space-conditioning load) should be in the range of 23 to 32 F (-5 to 0 C). To maintain dehumidification capability in humid climates, and thus consistency with industry best practice, heat pump cooling capacity should be oversized no more than 125%.
VE 6.4
ApacheHVAC
349
As noted in the more general section describing these pre-defined ApacheHVAC systems, the 90.1 PRM requirements for sizing and operation of air-source heat pumps (ASHPs) are based in part upon DOE-2 parameters and default inputs to eQuest rather than standard industry practice for sizing and operation of ASHPs. These defaults and the sizing approach that they imply can lead to unrealistic simulation results, regardless of what simulation tool is being used. The following considerations are therefore essential to using these pre-defined systems in the context of the PRM baseline requirements. This discussion addresses the following section G3.1.3.1 text from ASHRAE 90.1: Heat Pumps (Systems 2 and 4). Electric air-source heat pumps shall be modeled with electric auxiliary heat. The systems shall be controlled with multistage space thermostats and an outdoor air thermostat wired to energize auxiliary heat only on the last thermostat stage and when outdoor air temperature is less than 40F. IES has provided a new set of default values for the Air-Source Heat Pump (ASHP) component as of VE 6.3 (default values are shown in the figure below); however, in light of the complications with ASHRAE requirements vs. both real-world and simulation-based sizing considerations detailed below, fully automating the sizing and performance curve inputs to meet the ASHRAE-90.1 PRM requirements for ASHPs in PRM baseline systems 2 and 4 will come in future versions. The current method therefore combines autosizing with manual inputs to size baseline ASHPs within the current version of the VE.
VE 6.4
ApacheHVAC
350
The sizing process for the ASHP should be as follows (if needed, see further explanation below): For these systems, the ASHP component and DX cooling provide the heating and cooling modes of the reversible heat pump. The electric resistance backup heat source has unlimited capacity. Complete the standard design sizing runs for spaces and then for the system(s) with the oversizing factors set to their default values of 1.15 for cooling equipment and 1.25 for heating equipment, as required by the 90.1 PRM. This will autosize the capacity ASHP and DX cooling to meet the full extent of the oversized loads at the respective design conditions. For each zone with an ASHP, compare the autosized capacity for the ASHP component in the range of typical balance point temperatures (e.g., 25 to 40 F, depending on the climate) with the sized capacity of the corresponding DX cooling coil. These capacities are shown in the Heat Pump component dialog or, for many zones at once, in tabular edit view thereof, and in the Cooling Coil dialog or tabular edit view thereof. Note that the connected DX Cooling type covers a range of possible baseline sizes having a common COP, and therefore the capacity indicated in the type dialog may be overridden by autosizing for each instance of that type (if permitted). If the ASHP capacity within the range of typical balance points does not and DX cooling coil capacities do not differ significantly* (e.g., by 20% or more), adjust as indicated below.
VE 6.4
ApacheHVAC
351
If the ASHP component and DX cooling coil capacities differ significantly* (e.g., by 20% or more), adjust as indicated below. o If the autosized cooling coil capacity is significantly greater than the ASHP capacity, adjust the ASHP capacity upward to match the cooling capacity. If the ASHP is within 20% of the DX cooling, it is probably not worth making an adjustment, as this serves only to scale the ASHP performance curve with respect to efficiency. If the heating design day outdoor temperature is 40 F or higher, check the simulation results to ensure that the backup electric
System heating Capacity from sizing runs, modified as required to accommodate the following considerations: For actual applications, this will typically be a function of the equipment sizing as prioritized for Design Cooling Loads, with the heating and cooling capacity both determined by sizing at 100 to 125% of the cooling load. However, for heating, the NRCAN recommended outdoor temperature balance point (OA temp at which capacity equals space-conditioning load) should be in the range of 23 to 32 F (-5 to 0 C). For ASHRAE 90.1 PRM Baseline Systems, in order to have the electric resistance heat share the load at a temperature closer to the 40 F outdoor maximum for electric backup operation, the ASHP heating capacity should be thr great of: A) the sized cooling capacity B) sufficient to maintain the space heating setpoint without solar or internal gains when the outdoor temperature is 40 F. If the heating design day OA temp is significantly below 30 F, and additional design sizing run with OA temperature between 30 and 40 F may be justified to determine an ASHP capacity and balance point that will engage the electric backup below the design temperature when internal and solar gains are not present. If the required heating capacity to satisfy B is greater than the cooling capacity, A, the cooling capacity should be increased up To maintain consistency with industry best practice, the cooling capacity should be oversized no more than 125%, unless this is required to match sizing of heating capacity in a PRM baseline system to avoid operation of the backup electric heat when the OA temperature is above 40 F. The sizing process for ASHPs tends to differ significantly from that of other HVAC equipment. The ASHRAE PRM specification is unfortunately unclear with respect to the sizing this type of equipment for baseline systems (more on this below). Thus there is a degree of interpretation required here, and you are free to
VE 6.4 ApacheHVAC 352
re-interpret this as you see fit. The numbers you are seeing in the ASHP component dialog are simply a starting point, and will require modification. If the ASHP were sized for typical design heating indoor conditions (zero solar and internal gains) and an outdoor temperature between 23 and 40 F, this would be consistent with both. However, if the outdoor condition for the heating design day is significantly below 32 F, heating this is inconsistent with the way in which equipment is normally sized in a simulation environmenti.e., its a departure from the standard procedure of sizing of heating equipment to meet heating loads at the standard design heating conditions. The 90.1 PRM requires adequately sizing the ASHP plus backup heat source to avoid excessive unmet load hours, and does not permit any electric backup heat when the outdoor temperature is 40 F or higher. Thus the balance point (the outdoor temperature at which the full output of the ASHP just meets the space heating load) needs to be below 40 F under all circumstances of varying internal gains, solar gains, etc. The PRM goes on to specify that the electric backup should be the last resort with respect to maintaining the desired room temperature when the air-source heat pump cant fully meet the load. The specified incrementally lower thermostat setpoint for engaging the backup heat is but one means of accomplishing this. Addressing these together requires a bit of a sizing balancing act. And, the 40 F ASHRAE is referring to is very different than the Minimum source temperature in the ASHP dialog. Both of these are explained below. It is important not to be misled by the PRM reference to 40 F as the maximum outdoor temperature for operation of the backup electric resistance heating. The PRM is not saying that the ASHP should be off below this temperature, only that the electric resistance heat should be off at above it. Assuming the former, which may be implied by the combination of the PRM language regarding the and the eQuest default for Minimum HP Heat Temp in the eQuest Supplemental Heat dialog (see below), can significantly skew results for the model. The following bar graph shows annual energy consumption by end use for autosized heating and cooling as predicted by eQuest version 3.63 with location set to Minneapolis, MN and HVAC system type set to PTAC and heat source set to heat pump (i.e., system type is PTHP). All other inputs, including the building geometry, remained at pre-set version 3.63 default values.
VE 6.4
ApacheHVAC
353
In this particular illustration of how the default eQuest version 3.63 ASHP input values can lead to unrealistic results for a baseline system, the default building in Minneapolis, MN used 75 times as much energy (390 MBTU vs. 5.2 MBTU) for supplemental electric resistance space heating as it did for heating via the specified PTHP systems.
The screen captures above show how the default Minimum HP Heat Temp has been reduced to 10 F to avoid this particular problem. Because we have found no justification for cutting the heat pump off at even 10 F when the backup heat source is electric resistance, the default value in ApacheHVAC as of VE 6.3 is 0 F.
VE 6.4 ApacheHVAC 354
For one particular zone (the top floor core zone of the default 2-story office building), the default ASHP inputs and sizing beget particularly skewed results, as indicated by the annual load served by the Supplemental heat source vs. that served by the total load on the Heat pump unit in the SS-Q report above.
An outdoor temperature sensor is used to shut off the heat pump when the temperature falls below the preset limit. Only the supplementary heat source operates below this temperature. This is the Minimum source temperature setting for the ASHP component in ApacheHVAC. Note: While real-world ASHP applications do sometimes, as noted above, restrict operation of the ASHP below a specified temperature, it is very unusual to restrict the backup heat source operation in building for which the ASHRAE 90.1 PRM is applicable. While an individual homeowner may be given the option to prevent the use of the backup heat above a set outdoor temperature, the occupants of heated spaces in larger buildings generally expect the heating setpoint to be met by whatever means is available to do so, regardless of the particular outdoor temperature at the time.
ASHP sizing
For actual applications, ASHP sizing and selection is a combined function of design cooling Loads and heating balance point. The cooling loads are usually the priority in a climate with significant cooling load, especially if it is a humid climate. On the other hand, the preferred heating balance point (the lowest outdoor temperature at which the ASHP meets the entire heating load) is typically in the 22 to 32 F range. If driven purely by cooling requirements, both heating and cooling capacity would be sized at about 100 to 110% of the cooling load. This approach is meant to provide efficient cooling operation and effective dehumidification. In climates with mild winters, this may provide ample capacity to meet all heating loads. In colder climates, however, this approach to sizing will tend to address some significant fraction of the heating load, but not all of it. The rest will be addressed by a backup heat source. To minimize dependence on the backup heat source, a somewhat larger unit may be selected in order to provide a lower heating balance point with respect to outdoor temperature. However, where the climate is not all that cold, oversizing with respect to heating to achieve a low balance point temperature may reduce seasonal heating efficiency if it leads to a majority of operating hours at low part-load fractions, which is significantly less efficient than operating the heat pump at or near full load. Furthermore, partload operation at low outdoor temperatures is doubly inefficient: at an outdoor temperature of 37 F, the COP for a typical heat pump can drop below 1.0 if the load is less than about 30%. Finally, if dehumidification is anticipated when in cooling mode (i.e., in all but notably dry climates), best practice, even when seeking a lower heating balance point, is to avoid sizing the unit greater than 125% of the cooling load. Getting this right requires a somewhat sophisticate bit of logic.
VE 6.4
ApacheHVAC
356
Heat load
HP Cap
Design temp
25 to 35 F ?
47 F
Maybe best to simply size ASHP capacity at 47 F OA source temp to equal required heating capacity at design heating condition. Until we build some or all of this logic into the software, user intervention will be required to determine appropriate sizing of the ASHP component in ApacheHVAC. As of VE 6.4, the ASHP capacity at 47 F outdoor temperature will, for systems 2 & 4 when used in an ASHRAE 90.1 PRM Baseline model or when requested by the user, be set equal to the DX cooling capacity. However, in the rare case of spaces with both moderate cooling loads and substantial heating loads occurring when outdoor temperatures are above 40 F, it will be incumbent upon the user to check that these heating loads are not exceeding the ASHP capacity and causing use of backup heat when outdoor temperatures are greater than 40 F. The reason for this is that the backup heating for ASHPs in ApacheHVAC does not include an arbitrary high limit input for the backup heat source. Rather, the backup supplements the ASHP when the latter cannot fully meet the load. A further refinement will extend this logic as follows, using an additional special-purpose heating design sizing run with the outdoor temperature forced to 40 F. For true PRM Baseline systems (i.e., only when such system are used in PRM Baseline models), in order to have the electric resistance heat share the load at a temperature closer to the 40 F outdoor maximum for back operation, the ASHP heating capacity should be the greater of the following: 1) the associated cooling capacity 2) heating capacity sufficient to maintain the space heating setpoint without solar or internal gains when the outdoor temperature is 40 F When the heating capacity must greater than the desired cooling capacity such that the backup source will never be required when the outdoor temperature is above 40 F (#2 above), the associated DX cooling capacity will need to be increased to match the heating capacity. This scales the performance curves in the DX cooling dialog so that the part-load efficiencies are correct. The ASHRAE PRM specification includes the very clear statement regarding controls to prevent backup electric heat operation above outdoor temperatures of 40 F; however, this applies only to software that is incapable of modeling a true back heat source that is used only when the primary (ASHP) heat source is unable to meet the load as a function of outdoor conditions and/or indoor heating loads.
VE 6.4 ApacheHVAC 357
The PRM is also unclear with respect to the actual sizing of heat pump equipment for baseline systems. If, for example, ASHP is required by ASHRAE to be 25% oversized beyond that required just to meet the space conditioning load at the design condition
VE 6.4
ApacheHVAC
358
18 References
ASHRAE 140-2004 Standard Method of Test for the Evaluation of Building Energy Analysis Computer Programs. ASHRAE 2004. ISSN 1041-2336. ASHRAE 140-2007 Standard Method of Test for the Evaluation of Building Energy Analysis Computer Programs. ASHRAE 2007. ISSN 1041-2336. ASHRAE 90.1-2007 Energy Standard for Buildings Except Low-Rise Residential Buildings. ASHRAE 2007. ISSN 1041-2336 ASHRAE Handbook of Fundamentals, Heat Balance Method
VE 6.4
ApacheHVAC
359