FISCO
FISCO
FISCO
Fieldbus
FISCO
Fieldbus
Safety analysis for conventional intrinsically safe instrument loop using the Entity Concept
Hazardous area
IS certified device
Safe area
Intrinsic Safety Interface Centralised control equipment
Cc : 0.12 m F Lc : 4.1mH
IEC 60079/14 : calculate cable parameters compare safety descriptions prepare System Descriptive document
Co : 0.13 m F Lo : 4.2mH
SYSTEM : IIC/Group A T4
Fieldbus
Safety analysis for conventional intrinsically safe instrument loop using the Entity Concept
Hazardous area
IS certified device C:cable = 0.12 m F L:cable = 4.1mH
Safe area
Intrinsic Safety Interface Centralised control equipment
Certified IS interface : Intrinsically safe IIC/Group A Certificate for each field device required Uo : 28V Io : 93mA
Co : 0.13 m F Lo : 4.2mH
Fieldbus network
Fieldbus
recommends minimum input voltage current & power levels maximum input capacitance & input inductance
FF-816 Ui Ii Pi Ci Li
Ci
Fieldbus
A PTB report dated August 1994 provided details of the experimental evidence, from which the IEC standard has emerged
The resulting document covers all aspects of a low frequency Fieldbus system allows a system to be built with only a minimum analysis of the safety requirements allows very simple documentation
Fieldbus
Fieldbus network
Host interface Tree
Daisy-chain
Fieldbus
15 ohm 0.4 mH 80 nF
These limits are not difficult to achieve, since a typical Fieldbus trunk cable has parameters of : 50 /km, 0,8 mH/km & 120 nF/km The length of the trunk is usually determined by the operational requirements.
Fieldbus
18.4V V
Resistive
80 mA
MTL5053
non-FISCO
Fieldbus
17.5
Trapezoidal
Resistive
380
Fieldbus
The use of active semiconductors to limit the current results in power supplies being restricted to ib level of protection in accordance with IEC & CENELEC apparatus standards ie, system is not directly applicable to Zone 0 applications However, the design of MTL power supplies satisfies the North American requirement for intrinsically safe apparatus for Divisions 1 & 2
10
Fieldbus
17.5
Trapezoidal
Resistive
380
11
Fieldbus
FOUNDATION Fieldbus
FISCO Parameters
FF-816 Ui Ii Pi Ci Li
Ci
13
Fieldbus
14
Fieldbus
17
Fieldbus
The corresponding IIB power supply will supply 13 devices at the end of a 300m trunk demonstrating the desirability of a IIB gas classification where possible
18
In practice most instruments take less than 20 mA thus permitting an increase in population
Fieldbus
Terminators
FISCO power supplies typically contain a permanently connected terminator which defines one end of the IS trunk The field end of the IS trunk also requires to be terminated Terminators are used to present a 100 impedance to each end of the trunk to match the cable characteristic impedance to avoid reflections typical certification : ATEX Category II 1 CENELEC EEx ia IIC T4 FBT1-IS Typically, the terminator is FISCO approved, and hence can be used without any further consideration of the system safety
C Terminator
100 1 F
19
Fieldbus
Host
L N E
Typical application
DC supply
Power conditioner
T
Safe Area
The incoming
power supply is converted to an intrinsically safe supply to feed the IS trunk
The Fieldbus
signal, which is superimposed on the IS voltage, is fed via the interface device to & from the field devices
20
Fieldbus
Summary
FISCO serves all gas groups & hazardous areas The number of field devices that can be connected to a
fieldbus segment will be limited only by :
the power available the resistivity of the cable connection The segment can be extended without the need for new
calculations (within the boundaries of the FISCO model )
22
Fieldbus
FISCO Application
Line length limit : 1 Km in IIC : 1.9 Km in IIB (FF-816) Max spur length : 30 m ( 60 m proposed ) No cable parameter considerations required Simple interchange of devices
Tree Daisy-chain
Spur
31.25 kbit/s
23