What Are the Key Elements of HVAC Efficient Design for High Ambient Conditions
Design Conditions Indoor Design Conditions Outdoor Design Condition Envelop Optimization beyond code compliance Roof & Wall Insulation and U factor Fenestration Light transmittance and U factor Glass to Wall Ratio Glass Shading Tightness of Envelop Ventilation (Fresh & Exhaust Air) Why some standards encourage to exceed Ashrae 62.1 by 30% or more? Heat Recovery between fresh and exhaust air. Variable speed fans operation. Double Skin Commercial Hood??
492.1
482.3
7.3%
5.1%
458.8
1,2
BASE
Fresh Air Cooling Coil Load (TR) for ~ 30,000 CFM (14,200 l/s)
Indoor Conditions 74F (23.3C) / 50% rh 76F (24.4C) / 50% rh Outdoor Conditions
76.8
84
-12.9%
-4.8%
81.0
-8.2%
88.2
Outdoor Conditions
BASE
94 / 86 F (34.4 / 30 C)
568.9
566.3
11.0%
10.5%
504.1 502.7
512.5
BASE
Thermally brake Glass have little impact on the thermal performance especially with 4 sided silicon structure glass where there is no exposed aluminum structure and in general was designed as a solution for winter condensation in colder countries. Use whenever code requires that as in the case of Sharjah.
Codes are calling for smaller Glass to Code Ratios Ashrae std. 90.1 recommends 40% maximum glass to wall ratio while IBC for AUH limit it to 30% . However Architects and Buildings owners and developers still prefer higher ratios such as:
70% G to W Ratio
50% G to W Ratio
<50% G to W Ratio
Notice Cladding Design Heat Transmission - Watt per m2 & Glass Colors
Exposure South West
Coeficient
North
East
Wall
12.1 5.6
11.3 7.6
14.6 12.9
17.0 8.8
Glass
Solar Conductance Solar Transmission Subtotal Glass
Glass / Wall Heat Transmission (U=0.1) Glass / Wall Heat Transmission (U=0.056)
3.8 8.3
6.4 9.5
7.7 8.7
5.9 11.5
6.0 9.5
Fresh Air > 30% of Ashrae Std 62.1 Supplied at around 13OC
Notice Cladding & Glass Colors
BAG FILTER
SUPPLY AIR
EXHAUST AIR
RETURN AIR
COOLING COIL
2" FILTER
Why are This type of AHUs still being specified and used?!!!
Residential Kitchen hood should be a circulating hood while permanent kitchen exhaust of 50 CFM should be installed at the kitchen ceiling plenum level.
Residential Kitchens and Toilet exhaust can utilize the same duct and both should be used for heat recovery. Fresh air of 2 ACH should be supplied to lift lobbies to stop any cooking smell mitigation.
Double Skin Commercial kitchen hoods are controversial where the rule of thumb state that 80% make up air portion can be used in commercial kitchen is a recipe of trouble
Peripheral perforated plenum with low velocity is recommended withCladding the Notice possibility to cool the air down to 30 deg. C. & Glass Colors
Preference to use UL listed hood with minimum exhaust flow and make use of transfer air from dinning areas. VFD on both exhaust and make up air fans.
Recommended