Automatic Controllers & Control Modes
Automatic Controllers & Control Modes
III. The measured variable IV. The control signal V. The final correcting element
SET POINT
CONTROLLER
CONTROL SIGNAL
ACTION
FEEDBACK
SENSOR(FEEDBACK ELEMENT)
CONTROLLED VARIABLE
PROCESS
Process
Complex assembly of phenomenon that refers to some manufacturing sequence. It utilizes the resources to produce certain product. Many variables may be involved in such a process, some of which have to be controlled. Classification of processes. Process Based on variables to be controlled Single variable process Based on operation Continuous process
Process Behavior
The objective of process control is to cause a controlled variable to remain at a constant value at or near some desired set-point. The controlled variable changes because of: 1. A disturbance appears 2. Load demands varies or 3. Set points are adjusted. Several process variables are controlled at once in a typical production machine. Usually, only one individual feedback loop is required to control each variable. Single-variable control loops consist of the following elements: o Measuring device o Transducer/transmitter o Controller o Final Control Element
Feedback Elements(Sensors)
Strain gauge Piezo-electric Capacitance Bourdon Tube Mechanical Floats Guided Wave Weight (load cell) Ultrasonic Static Pressure Type of Signals Transmitters Pneumatic 3-15 PSI Electrical Current 4 20 mA 0 20 mA 10 50 mA Voltage 05V 15V 0 10 V Digital Thermocouples RTDs / Thermistors Filled Systems Bi-metallic ON/OFF Field Bus ModBus ProfiBus
Pressure
Level
Flow
Temperature Transmitter
Error Detector
Compares set point(reference signal) with the feedback signal.
Controller
The controller is the brain of the system. Receives error signal and develops output that causes the controlled variable to become equal to the set point value. Examples of controller PLC, Microprocessor, OP-AMP based controller. Different modes of controller are Controller modes Discontinuous mode Two position controller Multiposition controller Floating controller Continuous mode Proportional controller Proportional Integral controller Proportional Derivative controller Proportional Integral Derivative controller
Selection of a Controller
Controllers are designed to operate by using different control modes. Each of these modes has specific characteristics to provide different types of control actions. These control modes are: 1. On/Off 2. Proportional 3. Integral 4. Derivative The mode or combination of modes which is selected by the designer is determined by the requirement of the process
Continuous Control
On/Off control is acceptable for process where the variable is set between two limits. For processes where the variable needs to be kept at particular set point level, proportional control is used. Proportional action can be accomplished in two ways: Time Proportioning Method Amplitude Proportional Method
Time Proportioning
Is a method whereby the output of the controller is continually switched on and off. This method is also called as PWM(Pulse Width Modulation). Here the ratio of On time to Off time called as duty cycle is varied as per the changes in the feedback signal. On versus off times are varied dependent upon process requirements. Example: Speed control of DC Motor .
Amplitude Proportional
Most common technique to produce a proportional signal. The control signal is proportional in amplitude to the error signal. The signal may be amplified and the amplification may be referred to as proportional gain and proportional band.
Proportional Control
Smooth relationship exists between the controller output and the error.
P= Kp Ep + Po Where Kp- Proportional gain between error and the controller output Po- Controller output without error
The range of error to cover 0% to 100% controller output is called as proportional band. PB = 100/ Kp Disadvantage of proportional controller is offset or SSE or residual error.
The offset error limits use of proportional mode to only a few cases particularly where manual reset of the operating point is available to reset the offset.
It is generally used in process where large load changes are unlikely or with moderate to small process lag times.
Offset Error
Integral Control
Because of the introduction of offset in a control process, proportional control alone is not used. It is often used in conjunction with Integral control. Offset is the difference between set point and the measured value after corrective action has taken place.
Integral Control
The offset error of the proportional mode occurs because the controller can not adapt to changing external conditions i.e. changing loads. In other words the zero error output is a fixed value. The Integral mode eliminates this problem by allowing the controller to adapt to changing external conditions by changing zero error output. Integral action is provided by summing the error over time, multiplying that sum by a gain and adding the result to present controller output.
Integral mode controller action the rate of output change depends on the error.
Derivative Mode
For rapid load changes, the derivative mode is typically used to prevent oscillation in a process system. The derivative mode responds to the rate of change of the error signal rather than its amplitude. Derivative mode is never used by itself, but in combination with other modes. Derivative action cannot remove offset. P(t) = KD (dEp / dt)
The Derivative mode must be used with great care and usually with a small gain, because a rapid change of error can cause very large, sudden changes of controller output which can lead to instability. Derivative controller is not used alone because it provides no output when the error is constant. It is also called as rate controller or anticipatory control as it can take an action in advance depending upon the rate of error change.
The control algorithm can be altered so that derivative acts on the measurement and not on the error. This will reduce upsets.
Excessive noise and step changes in the measurements can be corrected by filtering out any change in the measurement that occurs faster than the maximum speed of response of the process. DCS system provides software with adjustable filters for each variable.
The time constant of these filters is usually adjusted from 0 to 100 seconds.
In analog system Inverse Derivative control mode is often used.
Inverse derivative can be added to PI Controller to stabilize the loops requiring very low proportional gains for stability. Inverse derivative should only be added when the loop is unstable at the minimum gain setting of the PI Controller. It is available in the separate unit can be added to the loop when stability problem occurs.
The addition of inverse derivative when proportionally tuned has little effect on the natural frequency of the loop.
Characteristics of PI Controller
This controller cannot eliminate the offset of proportional controllers , however it can handle fast process load changes.
Characteristics of PD Control
This mode eliminates the offset of the proportional mode and still provides fast response.
Electronic Controllers
1. On Off Controller with dead band Here VH = Vsp and VL = Vsp- (R1/R2) Vo
2. Proportional Controller We know that for proportional mode p = KP EP + PO For implementation of electronic controller we have Vout = Gp Ve + VO Where GP = R2/R1 = Gain of the controller
3. Proportional Integral Controller We know that the control mode equation for this mode is given as
4. Proportional Derivative Controller We know that for the PD Control mode the equation is given as
Pneumatic Relay
Also called as pneumatic amplifier or booster. It raises the pressure and /or air flow volume by some linearly proportional amount from the input signal.
Nozzle/Flapper system
It is used to convert the pressure to mechanical motion and vice versa.
Pneumatic Controllers
The pneumatic controller is based on the nozzle/flapper system. Here also we can implement different control modes. 1. Proportional Controller Pout= (x1/x2)* (A1/A2)*(Pin-Psp) + Po Where Kp= (x1/x2)* (A1/A2)
Control signal
Signal conditioning
Actuator
(motor)
Process
Trial-and-Error Tuning
Does not use mathematical methods, instead a chart recorder is used and several bump tests are made in the proportional and integral modes.
Trial-and-error tuning is very time consuming and requires considerable experience on the part of the technician or operator.
Mode Proportional
Proportional Integral (PI) Proportional Integral Derivative (PID)
Kp P/ NL
0.9 P/ NL 1.2 P/ NL
Ti = 1/ Ki
Td = 1/ Kd
3.33 L 2L 0.5 L
The method is based on the application of the Bode plot stability criterion and the effects that the proportional gain, integral time and derivative time have on the Bode plot.
Bode plot stability criterion 1. If the phase is less than 140 degrees at the unity gain frequency the system is stable. This then is 40 degrees phase margin from the limiting value of 180 degrees . 2. If the gain is 5 dB below unity when the phase lag is 180 degrees the system is stable. This is then 5 dB gain margin. Tuning : The operations of tuning using frequency response method involve adjustments of the controller parameters until the stability is proved by the appropriate phase and gain margins. Proportional Action : Multiplies gain curve by a constant and no effect on phase. Integral Action : Integral gain= Ki/ and Integral phase = - 90 degrees (lag) Derivative Action : Derivative gain = Kd* and Derivative phase=90 degrees (lead)