Chapter 2 Controller Principle
Chapter 2 Controller Principle
Actuating signal - the control action of he control loop and is equal to the
algebraic sum of th reference input signal and feedback signal. This is also
called the “error signal.”
Disturbance - undesirable input signal that upset the value of the controlled
output of the plant.
CHAPTER 2 : CONTROLLER PRINCIPLE
PERFORMANCE CRITERIA
• Various measurable parameter that indicate how good or bad the control system
•Divided 2 type
• transient / moving parameter
• path the controlled variable takes when going from one position to the next
• Steady state / not changing parameter
• final position
CHAPTER 2 : CONTROLLER PRINCIPLE
Classification of Controllers
•dead zone
CHAPTER 2 : CONTROLLER PRINCIPLE
Classification of Controllers
Multiposition modes
• controllers that have at least one other possible position in addition
to on and off.
•operate similarly to discrete controllers, but as set point is
approached, the multistep controller takes intermediate steps.
•Therefore, the oscillation around set point can be less dramatic
when multistep controllers are employed than when discrete
controllers are used
CHAPTER 2 : CONTROLLER PRINCIPLE
Classification of Controllers
•Continuous modes
10
General Control System Arrangement
11
So, what is a Controller?
• A controller is a device that generates an
output signal based on the input signal it
receives.
• The input signal is actually an error signal,
which is the difference between the measured
variable and the desired value, or set point.
• See figure below for the Controller.
12
Structure of a Controller
• This input error signal represents the amount
of deviation between where the process
system is actually operating and where the
process system is desired to be operating.
• The controller provides an output signal to the
final control element, which adjusts the
process system to reduce this deviation.
• The characteristic of this output signal is
dependent on the type, or mode, of the
controller.
13
Modes of Controllers
• The mode of control is the manner in which a control
system makes corrections relative to an error that exists
between the desired value (set point) of a controlled
variable and its actual value.
• The mode of control used for a specific application depends
on the characteristics of the process being controlled. For
example, some processes can be operated over a wide
band, while others must be maintained very close to the set
point.
• Deviation is the difference between the set point of a
process variable and its actual value. This is a key term used
when discussing various modes of control.
14
Four Modes of Controllers
• Four modes of control commonly used for
most applications are:
– Proportional (P)
– Proportional plus Reset (PI)
– Proportional plus Rate (PD)
– Proportional plus Reset plus Rate (PID)
15
Proportional Controllers (P)
• Each mode of control has characteristic
advantages and limitations.
• The modes of control are discussed in this and
the next several sections of this module.
• In the proportional (throttling) mode, there is a
continuous linear relation between value of
the controlled variable and position of the final
control element.
• In other words, amount of valve movement is
proportional to amount of deviation.
16
Proportional Controllers
• Three terms commonly used to describe the proportional
mode of control are proportional band, gain and offset.
• Proportional band, (also called throttling range), is the change
in value of the controlled variable that causes full travel of the
final control element.
• Gain, also called sensitivity, compares the ratio of amount of
change in the final control element to amount of change in the
controlled variable.
• Mathematically, gain and sensitivity are reciprocal to
proportional band.
17
Proportional Controllers
21
Integral Flow Rate Controller
22
23
Properties of Integral Control
• The major advantage of integral controllers is that they have
the unique ability to return the controlled variable back to the
exact set point following a disturbance.
• Disadvantages of the integral control mode are that it
responds relatively slowly to an error signal and that it can
initially allow a large deviation at the instant the error is
produced.
• This can lead to system instability and cyclic operation. For this
reason, the integral control mode is not normally used alone,
but is combined with another control mode.
24
Proportional Plus Reset Control (PI)
• Proportional plus reset control is a
combination of the proportional and integral
control modes.
• This type control is actually a combination of
two previously discussed control modes,
proportional and integral.
• Combining the two modes results in gaining
the advantages and c o m p e n s a t i n g f o r t
h e disadvantages of the two individual modes.
26
Characteristics of the PI
• The main advantage of the proportional control mode is that
an immediate proportional output is produced as soon as an
error signal exists at the controller as shown in Figure below.
• The proportional controller is considered a fast-acting device.
• This immediate output change enables the proportional
controller to reposition the final control element within a
relatively short period of time in response to the error.
• See below figure for the response of the PI Control
27
Eng R. L. Nkumbwa, Copperbelt University,
4/6/2019 28
School of Technology
Disadvantages of the
Proportional Control
29
Disadvantages of the
Proportional Control
30
PI Characteristics
4/6/2019 31
Characteristics of the PI
33
Effects of Disturbance on Reverse Acting
Controller
4/6/2019 34
Proportional plus Rate control (PD)
35
PD Controller
4/6/2019 36
Proportional plus Rate control (PD)
39
Rate Control Output
40
Rate Control Output
44
Eng R. L. Nkumbwa, Copperbelt University,
4/6/2019 45
School of Technology
Example of the Proportional Plus rate Control
4/6/2019 48
Industrial Applications
• Proportional plus rate control is normally used with large
capacity or slow-responding processes such as temperature
control.
• The leading action of the controller output compensates for
the lagging characteristics of large capacity, slow processes.
• Rate action is not usually employed with fast responding
processes such as flow control or noisy processes because
derivative action responds to any rate of change in the error
signal, including the noise.
• Proportional plus rate controllers are useful with processes
which are frequently started up and shut down because it is
not susceptible to reset windup.
49
Proportional Plus Integral Plus Derivative Control
(PID)
50
Proportional Plus Integral Plus Derivative Control
(PID)
• However, there are some processes that
cannot tolerate offset error, yet need good
stability.
• The logical solution is to use a control mode
that combines the advantages of proportional,
reset, and rate action.
• This chapter describes the mode identified as
proportional plus reset plus rate, commonly
called Proportional-Integral-Derivative (PID).
51
Controller Action
52
Eng R. L. Nkumbwa, Copperbelt University,
4/6/2019 53
School of Technology
Controller Action
• Assume the error is due to a slowly increasing measured
variable. As the error increases, the proportional action of the
PID controller produces an output that is proportional to the
error signal.
• The reset action of the controller produces an output whose
rate of change is determined by the magnitude of the error.
• In this case, as the error continues to increase at a steady rate,
the reset output continues to increase its rate of change.
• The rate action of the controller produces an output whose
magnitude is determined by the rate of change. When
combined, these actions produce an output as shown in Figure
above.
54
Controller Action
• As you can see from the combined action
curve, the output produced responds
immediately to the error with a signal that is
proportional to the magnitude of the error
and that will continue to increase as long as
the error remains increasing.
55
PID Controller Response Curves
4/6/2019 56
PID Response Curves
• Figure above demonstrates the combined
controller response to a demand disturbance.
• The proportional action of the controller
stabilizes the process.
• The reset action combined with the
proportional action causes the measured
variable to return to the set point.
• The rate action combined with the
proportional action reduces the initial
overshoot and cyclic period.
57
PID Controller
59
PID Controller Characteristics
61