The LP bypass system provides effective control of reheat steam flow during startup, low load/part load operation, and sudden load rejection to enhance turbine protection and performance. It operates in parallel with the turbine to protect the condenser from excessive temperature and pressure. The LP bypass controller regulates reheater pressure to a fixed or variable setpoint using a combination of electrical and hydraulic controls. Upon load rejection, the turbine speed controller closes the control valves, increasing steam pressure. The LP bypass valves then open to safely route excess steam out of the system.
Download as PPT, PDF, TXT or read online on Scribd
100%(1)100% found this document useful (1 vote)
361 views
LP Bypass System
The LP bypass system provides effective control of reheat steam flow during startup, low load/part load operation, and sudden load rejection to enhance turbine protection and performance. It operates in parallel with the turbine to protect the condenser from excessive temperature and pressure. The LP bypass controller regulates reheater pressure to a fixed or variable setpoint using a combination of electrical and hydraulic controls. Upon load rejection, the turbine speed controller closes the control valves, increasing steam pressure. The LP bypass valves then open to safely route excess steam out of the system.
Download as PPT, PDF, TXT or read online on Scribd
You are on page 1/ 25
Design Criteria for
LP BYPASS SYSTEM
LP Bypass system provide a very
effective means of controlling reheat steam flow during
Startup Low-load / part load operation Sudden load rejection
It enhances fast starting
capability of turbines from all initial conditions e.g. Cold condition Warm condition Hot Condition
LP steam-bypass system operate in
parallel with the turbine
Protect Condenser from excessive
temperature and pressure that could result from sudden injection of superheated steam
Ensure coordinated control between HP
and IP turbine control valves and the steam bypass systems to operate at any remaining load Subsequently reloaded in a controlled manner
Schematic Diagram of Bypass System
The controls for LP Bypass system
are combination of electrical and well proven hydraulic system Electro-hydraulic converter provides the necessary link between hydraulic actuator and electrical system
The LPBypass Controller acts as a
maximum pressure Controller It regulates the reheater pressure either to the fixed set value or suitably derived variable set value If the reheater pressure exceeds this set value, the Controller causes the electro-hydraulic converter to operate and initiate bypass operation
Set Value formation
The Two set values fixed and variable are formed for the LPBypass control system set value to be used is determined by a maximum value selector For the formation of variable set point, a pressure transducer is used to measure the steam pressure in HP turbine
SEQUENCE OF EVENTS RESULTING
FROM LOAD REJECTION Upon receiving load rejection signal from electrical system: Turbine Speed Controller assumes control of the TG set It initiates fast closure of HP & IP turbine control valves through position controller Fast closure of turbine control valves cause an immediate decrease in HP 1st. Stage pressure
SEQUENCE OF EVENTS RESULTING
FROM LOAD REJECTION Pressure increases in main and reheat steam systems These pressure changes are sensed by HP and LP Bypass controllers Respective bypass valves are opened
If LP steam- bypass system
fails or the condenser cannot accept LP bypass steam , Safety Valves open and dump steam to atmosphere
Hydraulic Mode of Operation
The controller controls plunger coil of Electro
Hydraulic Converter With increase in voltage, the jet pipe is deflected towards right Converter piston moves downwards leading to generation of LPB signal oil through Follow-up pistons provided in the hydraulic control system
Hydraulic Mode of Operation
Two Follow-up Pistons actuate and open first stage
of water injection valve Remaining two Follow-up Pistons generate signal oil for opening LPBypass stop and control valve
ADJUSTMENT OF LPBYPASS CONVERTER
Design of LPBypass Valves for 210
MW Steam Turbine
Controlled by 8 bar mineral oil
Design of LPBypass Valve for 500 MW
Steam Turbine
Controlled by 36 bar FRF
Protection Devices
Low Vacuum Condensor Protection
Spray Water Pressure Switch Condensor Temperature Protection
Protection Devices cause closure of
bypass station in case of following eventualities a) Condensor vacuum is low ( > 0.6 bar absolute ) b) Spray water pressure is low (< 8.5 / 9.5 bar ) c) Temperature of condenser body is high (> 90 C )
Water Injection Valves operate in
two stages
Second stage Water Injection Valves open
when steam flow through LPBypass Valves increases more than 45 %