Flow Element
Flow Element
of
Flow meters
By
Dinesh Dubey
GET - Electronics
Flow meter
The instrument to conduct flow
measurement is called
flow meter
Types of Flow
Reynolds number, Re= vD/ is the
key
parameter in determining whether
or not a
flow is laminar or turbulent
Laminar Flow = Re < 2000
Transient to Turbulent Flow =
2000<Re<4000
Turbulent Flow = Re > 4000
Want to know
Consumption
Product Quality
Energy Savings
Savings on Cost of
Material
DP Flow meter
Differential pressure transmitters
measure the difference between two
pressures,
In a pipe, the pressure drop is created
by constricting the flow stream. The
constricting device is called a primary
element.
A secondary element, the pressure
transmitter, measures the differential
pressure.
The flow rate is proportional to the
square root of the differential pressure
and relies on Bernoulli's equation.
m1 m2
m Av
1 A1v1 2 A2 v2
incompress ible
1 2
A1v1 A2 v2
Basic Equations:
a.) Continuity:
mass in = mass out
b.) Bernoullis Eqn.
Total pressure is
constant throughout
Bernoulli
P0 Total Pr essure const.
1 2
v P
2
1
1
2
2
1 v1 P1 2 v 2 P2 P0
2
2
P static pressure
P0 total pressure
1 2
v dynamic pressure
2
Y = Compressibility Factor
v2
Flow
2 P
1
A2
1
A1
Rate
1
Q A2v2 A2
A2
1
A1
2 P
For Re al Flow
1
Q YCA 2
A2
A1
2 P
Ideal
1
1
2
2
P P1 P2 2 v2 1v1
2
2
2
1
1 A2 2
2
v2
2 v2 1
2
2 A1
2
A2
1 2
v2 1
2
A1
when
1 2
Flow Pattern
Orifice Plate
Concentric
Pipe Size (in) >1.5
Steam
yes
Clean Gas
yes
Dirty Gas
no
Clean Liquid yes
dirty liquid
no
slurries
no
Accuracy
1-4%
Segmental
4 to 14
na
na
yes
na
na
na
2-4%
Eccentric
4 to 14
na
na
yes
na
na
na
2-4%
Flange taps
They are not recommended for use on pipelines under 2
inches
in diameter. They are preferred for convenience & space
saving,
but requires much higher values of Reynolds Number
(100,000 minimum)
Corner taps
Pipe taps
They detect the smallest pressure difference and, because of
the
tap distance from the orifice, the effects of pipe roughness,
dimensional inconsistencies, and, therefore, measurement
errors
are the greatest.
Venturi Tube
Venturi tube is used for large pipelines.It is more
accurate than the Orifice Plate, but considerably
more expensive and more difficult to install.
Pressure Taps are located at the points of max. &
min. pipe diameter.
Flow Nozzle
Features
Nozzles have superior durability and
larger flow coefficient in comparison
with
orifice plates
They are suitable for measuring
flow of high temperature, high pressure
and high velocity steam and water
They are mostly used for steam & water
line
application & air/gas flow in ducts,
where
pressure loss cannot be tolerated.
Typical Transmitter
Installation
Pitot Tube
The pitot tube measures the fluid flow velocity
by converting the kinetic energy of the flow
into potential energy. Pitot tubes sense two
pressures simultaneously, impact and static.
The impact unit consists of a tube with one
end bent at right angles toward the flow
direction. The static tube's end is closed, but a
small slot is located in the side of the unit
Features
Low cost
Absence of moving parts
Easy installation
Minimum pressure drop
Accuracy is 3 to 5 %
A disadvantage of Pitot tubes is
that they sample pressure at a
single point in the flow stream,
which limits accuracy. This is
overcome by using Annubar.
Annubar
Annubar is averaging Pitot tubes which
were developed to counteract the
limited accuracy of single-point Pitot
tubes.
The averaging Pitot tube computes an
average of pressures measured at a
number of points on the tube,
significantly improving accuracy
Features
Accuracy varies from 0.5% to 1.5%
Available for pipe sizes from 0.5in
to 150in
It is economical to install,
particularly in the larger pipe sizes
where pipe couplings can replace
large, expensive orifice flanges.
Poor performance with dirty or
sticky fluids.
Rotameter, variable-areaflowmeter
Force balance
Drag Force
Gravity
Buoyancy
(usually
negligible)
Features of Rotameter
Low Cost,ease of installation
Maintenance free & tends to have
a long operating life.
They are used in smaller sizes
They are used extensively on
purge applications & for many
process flow in pipe sizes 0.5 to
2.
They are not suitable for high
viscous liquids.
Disadvantages
It gives incorrect reading due to
variation in temp & pressure.
Larger the viscosity, higher the
error.
FEATURES
1. Flow of the electric conductive liquid is
measured without influences of
temperature, pressure, density or viscosity.
2. Pressure loss is none.
3. Because of no movable parts, it has a long
life.
4. Response is fast.
5. Measuring range is wide. (wide range
ability)
6. It is able to measure the both direction
(plus and minus) flows.
7. It is available for measurement of strong
corrosive liquid or slurry by selection of
lining materials.
Disadvantage
Current/Flow Calibration
depends on total ckt resistance
so that any change in fluid
conductivity could produce
large error.
It is not suitable for Gas or
vapour measurement.
Volumetric Flow
Rate =
Features
Doppler Flowmeter
no
no
no
yes
yes
yes
yes
no
4000
Questions/Comments/Suggestions