C4: Control Terminologies
C4: Control Terminologies
C4: Control Terminologies
TERMINOLOGY
By
Oladokun Sulaiman
• Learning Objective: To be able to describe the
common TERMS OF CONTROL SYSTEMS
Specific Objectives:
System
Control components
Control elements
Performance of control system
Classification of control system
3.1 SYSTEM
INPUT • PNEUMATIC
CONTROLLER
FEED BACK
OUTPUT
CONTROL SYSTEM
• The operation of a system may be controlled externally (by an
operator) or automatically (by the system itself). When the control
action of a system is independent of the output, the system is said
to be an OPEN-LOOP control system. If It, it is called a CLOSED-
LOOP or FEEDBACK control system.
OUTPUT
INPUT
CONTROL
SYSTEM
The required The variable at
value of a the desired
variable value
• Within the boundary described by the box outline is the system and inputs to
the system are shown by arrows entering the box and outputs by arrows
leaving the box.
• outlet
CONTROL SYSTEM COMPONENTS
• A control system consists of a controller and a plant. We use the general
term plant to describe the machine, vehicle or process which is being
controlled.
• The controller can be a person, in which case we have a manual control
system.
• Alternatively, in an automatic control system the controller is a device,
electronic circuit, computer, or mechanical linkage, etc. Figure below shows
the general arrangement.
• The interface between the plant and the controller requires actuators
(control elements) to provide the control action.
• In addition, instrumentation, detectors and sensors (measurement elements)
are needed to provide information about the plant status to the controller.
• The information passing between the controller and the plant is in the form
of signals. These signals can be very diverse, for example electrical,
pneumatic or mechanical, etc.
• The term ‘transmitter’ is commonly used to describe the measurement
element in a process control system because the transmitter sends an
electrical or pneumatic signal representing the measured value to the
controller.
Control System Components
• Controllers are usually implemented electronically, either
using analogue circuits or a digital computer
(microprocessor).
• Pneumatic and hydraulic controllers are also to be found.
Actuators are commonly pneumatic, electric or hydraulic
depending on the application and power level required.
TRANSDUCER
VOLTAGE SIGNAL
THERMOCOUPLE AMPLIFIER THAT
REPRESENTS
THERMOMETER
3.3.2 TELEMETERING
• It may be defined as signal transmission over a
considerable distance.
• In measurement this involves information transfer from
detecting element to a central recording display station.
• In control this involves control operating devices and
related signal transfers.
• In telemetering systems the measuring unit is often
called the transmitter.
• Incorporating a transducer, and the recording unit some
distance away is then referred to as the receiver which
may have an associated transducer if required.
3.3.4 FEEDBACK
• In everyday life, feedback occurs when we are made aware of the
consequences of our actions. Feedback is so natural that we take it
for granted. Imagine trying to accomplish the simplest of tasks
without feedback, for example, trying to walk without visual
feedback. Feedback not only gives verification of our actions: it
allows us to cope with a changing environment by adjusting our
actions in the presence of unforeseen events and changing
conditions.
• Feedback has similar advantages when applied to automatic
control. Feedback occurs in automatic control systems when the
control action depends upon the measured state of the machine or
process being controlled. Feedback gives and automatic control
system the ability to deal with unexpected disturbances and
changes in the plant behaviour.
Actual
Desired course
fluid of travel
output
Error Tank
Human Valve
+ operator
-
Meter reading
FEEDBACK
• It is the measured value or
a multiplication of
measured value which is
brought back to the
comparator unit and X+ Error Y
compared with the G
required of reference
value. H
Y ( s)
G ( s) =
X (s)
3.3.6 GAIN
It is the ratio of “change of output” to “change of input”.
A controller’s input may be a function of time and of many forms, such as ramp,
sinusoidal, etc. As a result output will also be a function of time. Therefore gain
will also be a function of time.
• Proportional
• Integral
• Derivative
• PD
• PI
• PID
Type of Controller Actions
C = (Ki/s ) x e
‘e’ = MV-DV
DV MV
Change in load
offset
Proportional + Integral No
Control offset
Less recovery
time
Proportional + Integral +
Derivative Control
PROPORTIONAL BAND
P SET
ADJUSTING
SCREW
-k=V/ ө= 0.05MM/M
ө =1M UP
FLOAT
20 M
V=0.05 MM TRAVEL 10 M
DOWN
Regulating
unit
e
Controller Desired value
0.6m
Example of offset
• The system is trimmed so that with the valve half open, inflow and
outflow are the same, i.e. 60 litre per minute.
• Now if the outlet valve is further opened so that the outflow is now
90 lpm. With 60 lpm flowing into tank the level will obviously drops,
and will not stop dropping until the input flow is 90 lpm. This can
only occur if the level is much below than 0.6 m.
• The controller will now be in equilibrium with the control point offset
from the desired value
• The level can not rise any more because at that value the controller
will regulate to cause less inflow than 90 lpm, subsequently level
falls.
Integral Control Action
•
Integral Control (I)
Controller output proportional to integral of
error signal ‘e’
C ∝ ƒ e dt
Integral Control Response
(P + I ) Control
(P+I) Control
Controller action combination of (P)
and (I) actions
C ∝ ( e + ƒ e dt)
C = (Kp + Ki/s) e
(P + I) Control System
P+I -Controller output
PROPORTIONAL + INTEGRAL CONTROLLER
DV MV
contd
• (P + I + D) Control
– Controller action is combined effect of (P)
(I) and (D) control actions.
c ∝ ( P + ƒ e dt + de/dt)
C = (Kp + Ki/s + Kd x s) e
Most accurate control, but very complex
(P + I +D ) Control system
PNEUMATIC THREE TERM CONTROLLER (P + I + D)
INTEGRAL RESTRICTOR
DERIVATIVE
RESTRICTOR
RELAY VALVE
DV MV
CORRECTING
UNIT
ONE CAN ADJUST THE OVERALL GAIN OF THE CONTROLLER BY ADJUSTING THE INTEGRAL AND
DERIVATIVE RESTRICTOR.
SINGLE ELEMENT CONTROL
AIR SUPPLY
Controller
SW IN
valve
SW OUT
Single elements means the controlled element (variable) is controlled by a
single sensing element- For example it senses the Jacket Cooling Water inlet
temperature and tries to maintain this temperature at constant set level
Based on Structure
Process
Measuring
Regulating
unit
unit
• 2) Closed loop: Feedback of measure values is
compared with desired value and the error is used as
input signal of the controller.
Process
Measuring unit
Regulating
unit e
Controller Desired value
Cascade Control
2. CASCADE C
Master Controller
M/E
Slave Controller
LO Sump
ATC
ATO
Steam Valve SW VV
L.O Pump
Digital Control System
• All the signals flowing through control system
are converted into digital form
• This is done to simplify processing of plant
parameters to achieve better control
• All the signals flowing into the final control
elements are reconverted from digital to analog
form
• System utilises A/D and D/A converters
• Control functions are distributed rather than
centralised
Digital Control System
Consists of a number of microprocessors based control
modules that work together
Control modules distributed geographically
Reduces risk and improves reliability
5. DIGITALCONTROL
DCS Configuration
Essential features of Distributed
Control Syetm(DCS)
• Distributes its functions into smaller sets of
semi-autonomous subsystems which
cover specific process or area of the plant
• Performs following functions-
• Process analysis and supervision
• Data Logging
• Process control
• Storage and retrieval of Data
• Presentation of information and reports
Basic DCS functions
• DCS is connected to primary control
elements such as temperature and
pressure transmitters, flow meters, gas
analysers etc
• From these field devices, it receives
electrical signals, such as 4-20 mA, 1-5 V
DC etc
• DCS converts these signals into
equivalent digital form
Contd
• Digitized signals can be used by the
computer to variety of use, such as
• Control loops
• Execute special programmable logic
• Monitor inputs
• Set alarm operations through use limiters
• Trend,Log and report Data
• Perform many other functions to implem-
ent superior control strategy
Feedback Control
Measured
Controlled signal Process or outputs
System to be
Controlled
Desired Measured
Controlled signal
Value outputs
Error Control System Process or
+ (analog or System to be
-
digital) Controlled
Motor Control Process
Desired
Angle
Error Motor Voltage Angle
+ Microcontroller Motor Assembly
-
Process Control
From R. Stenz and U. Kuhn, Automation of a Batch Distillation Column Using Fuzzy and Conventional
Control," IEEE Transactions on Control Systems Technology, vol. 3, no. 2, June 1995, page 172.
Power System
• Questions???