Clean Room 1
Clean Room 1
Clean Room 1
All the standards are based on the measurement of maximum number of particles of
varying sizes which may be present in a specified volume of air.
Class X clean room – means that particle count in the air is not more than X per
cubic feet ( ft3 ) of 0.5 µm and larger in size.
ISO X clean room - means that particle count in the air is not more than 10 X per
cubic meter ( m3 ) of 0.1 µm and larger in size.
1 35 1 ISO 3
10 350 10 ISO 4
ISO 1 10
ISO 2 100 4
ISO 3 1,000 35 Class 1
ISO 4 10,000 352 Class 10
ISO 5 100,000 3,520 29 Class 100
ISO 6 1,000,000 35,200 293 Class 1000
ISO 7 352,000 2,930 Class 10,000
ISO 8 3,520,000 29,300 Class 100,000
ISO 9 35,200,000 293,000 Room air
European Union Guide to GMP
maximum particles / m³
Microbial
Class
≥ 0.5 µm ≥5.0 µm growth(CFU)
A 3500 0 ‹1
B 350000 2000 ‹5
Ancillary Or 100,000 (Allowable particle 100,000, Washing and cleaning of product and accessories; product
Level III alert level 80,000) preparation and sterilization area.
Non classified Final inspection, labeling and packaging; warehouse for raw
materials and finished products.
Design of environmental contamination control system
HVAC
Heating, ventilation and air conditioning system is an integral part
of environmental contamination control system.
The purpose of HVAC system is to provide a specified set of
environmental conditions required for the manufacturing process.