Lecture 30
Lecture 30
Obviously, V > V′ i.e., for given dimensions of the cable, a graded cable can be worked
at a greater potential than non-graded cable. Alternatively, for the same safe potential, the
size of graded cable will be less than that of non-graded cable. The following points may
be noted :
(i) As the permissible values of gmax are peak values, therefore, all the voltages in above
expressions should be taken as peak values and not the r.m.s. values.
• Disadvantage of this method is that there are a few high grade
dielectrics of reasonable cost whose permittivities vary over
the required range.
• Example A single-core lead sheathed cable is graded by
using three dielectrics of relative permittivity 5, 4 and 3
respectively. The conductor diameter is 2 cm and overall
diameter is 8 cm. If the three dielectrics are worked at the
same maximum stress of 40 kV/cm, find the safe working
• voltage of the cable.
• What will be the value of safe working voltage for an
ungraded cable, assuming the same conductor
• and overall diameter and the maximum dielectric stress ?
• Graded cable. As the maximum stress in the three dielectrics
is the same
This example shows the utility of grading the cable. Thus for the same conductor
diameter (d) and the same overall dimension (D), the graded cable can be operated
at a voltage (57·84 − 39·20) = 18·64 kV (r.m.s.) higher than the homogeneous
cable — an increase of about 47%.
Intersheath Grading
• In this method of cable grading, a homogeneous dielectric is used, but it is divided
into various layers by placing metallic intersheaths between the core and lead
sheath. This arrangement improves voltage
distribution in the dielectric of the cable and
consequently more uniform potential gradient is obtained
• Suppose that two intersheaths of
diameters d1 and d2 are inserted into the
homogeneous dielectric and maintained at some fixed
potentials. Let V1, V2 and V3 respectively be the voltage
between core and intersheath 1, between intersheath 1
and 2 and between intersheath 2 and outer lead sheath.
As there is a definite potential difference between
the inner and outer layers of each intersheath, therefore,
each sheath can be treated like a homogeneous single core
cable.
• Since the dielectric is homogeneous, the maximum stress in
each layer is the same i.e.,
• As the cable behaves like three capacitors in series, therefore,
all the potentials are in phase i.e.Voltage between conductor
and earthed lead sheath is
• V=V+V+V
1 2 3
• (ii) Short-circuit fault. When two conductors of a multi-core cable come in electrical contact
with each other due to insulation failure, it is called a short-circuit fault. Again, we can seek
the help of a megger to check this fault.
• For this purpose, the two terminals of the megger are connected to any two conductors.
• If the megger gives zero reading, it indicates short circuit fault between these conductors.
• The same step is repeated for other conductors taking two at a time.
• (iii) Earth fault
• When the conductor of a cable comes in contact with earth, it is called earth
fault or ground fault.
• To identify this fault, one terminal of the megger is connected to the
conductor and the other terminal connected to earth.
• If the megger indicates zero reading, it means the conductor is earthed.
• The same procedure is repeated for other conductors of the cable.
Loop Tests For Location
of Faults
• There are several methods for locating the faults in
underground cables. However, two popular
• methods known as loop tests are :
• (i) Murray loop test
• (ii) Varley loop test
• These simple tests can be used to locate the earth fault or
short-circuit fault in underground cables provided that a sound
cable runs along the faulty cable.
Quiz no. 2
• A 2-wire d.c. distributor ABCDEA in the form of a ring main is fed
at point A at 220 V and is loaded as under :
• 10A at B ; 20A at C ; 30A at D and 10 A at E.
• The resistances of various sections (go and return) are : AB = 0·1 Ω
; BC = 0·05 Ω ; CD = 0·01
• Ω ; DE = 0·025 Ω and EA = 0·075 Ω. Determine :
• current in each section of distributor
• A single core cable 5 km long has an insulation resistance of 0·4
MΩ. The core
• diameter is 20 mm and the diameter of the cable over the insulation
is 50 mm. Calculate the resistivity
• of the insulating material.
Murray Loop Test
• (i) Earth fault : Fig. shows the circuit diagram for locating
the earth fault by Murray loop test.
• Here AB is the sound cable and CD is the faulty cable; the earth fault
occuring at point F.
• The far end D of the faulty cable is joined to the far end B of the sound
cable through a low resistance link. Two variable resistances P and Q are
joined to ends A and C respectively and
• serve as the ratio arms of the Wheatstone bridge.
• Let R = resistance of the conductor loop upto the fault from the test end
• X = resistance of the other length of the loop
• Note that P, Q, R and X are the four arms of the Wheatstone bridge.
The resistances P and Q are varied till the galvanometer indicates zero
deflection.
In the balanced position of the bridge, we have,
• (ii) Short-circuit fault : Fig. 11.23 shows the circuit diagram
for locating the short-circuit fault by Murray loop test. :
Varley Loop Test
• The Varley loop test is also used to locate earth fault or short-
circuit fault in underground cables.
• Employs Wheatstone bridge principle.
• It differs from Murray loop test in that here the ratio arms P
and Q are fixed resistances.
• Balance is obtained by adjusting the variable resistance S
connected to the test end of the faulty cable
• For earth fault or short-circuit fault, the key K is first thrown to
2
Now key K2 is thrown to position 2 (for earth fault or short-circuit fault) and
bridge is balanced with new value of resistance S2. Then,
• Example In a test by Murray loop for ground fault on 500 m
of cable having a resistance of 1·6 Ω/km, the faulty cable is
looped with a sound cable of the same length and area of
crosssection.
• If the ratio of the other two arms of the testing network at
balance is 3 : 1, find the distance of the fault from the testing
end of cables.
Distance of fault from test end is
• In a test for a fault to earth on a 500 m length of cable having
a resistance of
• 1 Ω per 1000 m, the faulty cable is looped with a sound cable
of the same length but having a
• resistance of 2·25 Ω per 1000 m. The resistance of the other
two arms of the testing network at
• balance are in the ratio 2·75 : 1. Calculate the distance of the
fault from the testing end of the cable.
• Varley loop test is performed to locate an earth fault on a 20
km long cable.
• The resistance per km of the single conductor is 20 Ω. The
loop is completed with a similar healthy
• conductor. At balance, the variable resistance connected to the
faulty conductor is 200 Ω. The fixed
• resistors have equal values. Calcualte the distance of the fault
from the test end.