KV System
2 X 25 KV AT SYSTEM
New
Technologies AUTO FAULT LOCATOR
Adopted
2
EMP 4: 2 X 25 KV HIGH RISE OHE
(Comparison:
(Comparison: Conventional
Conventional && DFC)
DFC)
Conventional 25 kV OHE 2X25 kV High Rise OHE
Catenary wire
Feeder wire
1.40 mtr
Catenary wire Earth wire
1.40 mtr Contact wire
Contact wire
7.54m
5.4m
3
SCOTT CONNECTED TRANSFORMER AUTO TRANSFORMER
4
2X25 KV AUTO TRANSFORMER FEEDING SYSTEM
ADVANTAGES:
1. Utilization of 54 KV traction
power instead of 25 KV with the
help of AT and feeder.
2. Less voltage drop in feeder
circuit.
3.Large spacing of traction
substations.
4. Less telecommunication
interferences.
4. Suitable for heavy haul and
high speed operation.
5
AUTO FAULT LOCATOR
6
AUTOMATIC POWER FACTOR POWER CORRECTION EQUIPMENT AT DFCC TSS:
PFC FOR IR – STATIC COMPENSATOR PFC FOR DFCC – STATIC & DYNAMIC COMPENSATOR
ADVANTAGE::
Power factor improvement: Conventional system improves power factor normally from .75
to .85, whereas APF improves power factor from .85 to .95
Avoids leading power factor (PF>1): To safeguard supply source
Reduction in maximum demand : Direct saving in Electricity Bill
7
Differences in Equipment:: DFCC SP and IR SP
Size of contact and catenary wire are 150 sq. mm & 129
Size of contact and catenary wire are 107 sq. mm & 65 sq. mm
Conductors sq. mm respectively and OHE current carrying capacity
respectively and OHE current carrying capacity is 600 Amp.
is 1000 Amp.
Feeder Wire 288 sq. mm AAAC Not reqd.
1250 A Double Pole, with distance between the Pole-
Isolator 800 A Double Pole with Distance between the Pole- 550 mm
1500 mm
Iterrupter 1600 A Double Pole 800 A Single Pole
Cross-Feeder Double run of 150 sq. mm Single run 150 sq. mm
Auto Transformer 8 MVA Not Provided
Circuit Breaker 1600 A Double Pole Single Pole 800/1250 A