MDBFP
MDBFP
MDBFP
SERIAL NO 32050532
Pa 6945 KW
U1 109 / 32
U2 690/53 Z2/Z1
M 10000 Kg
MDBFP AOP FILTER Specification
Equipment Name MDBFP AOP FILTER
TYPE
DU 1001.30803.25G.10.B.P-FSA-.-AV
TCR:4222711001
ELEMENT-N2 306608
FABRICATION-N2 244919-7(05/05)
• Keep the top most vent (FDV-127, FDV-128) at Feed Water Control Station Open.
• Keep close all atmospheric drains of suction and discharge feed water lines (FDV-109, FDV-
110, FDV-111, FDV-112, FDV-113, FDV-114, FDV-117, FDV-118, FDV-121, FDV-122, FDV-147,
FDV-148, FDV-129, FDV-130, FDV-131, and FDV-132).
• Keep open inlet & outlet water box air vents for all HP Heaters (FDV-115, FDV-116, FDV-123,
FDV-124, FDV-119, FDV-120, FDV-125, FDV-126, FDV-107 and FDV-108).
• Keep open inlet and outlet of HP heaters- 5A & 6A (FDV-7, FDV-8) and HP heaters- 5B & 6B
(FDV-9, FDV-10) and open HP heater bypass valves (FDV-11, FDV-12) for charging.
• Open discharge valve bypass of MDBFP (FDV-6A) and by gravity charge the feed water line up
to the feed water control station.
Start MDBFP AOP and observe lube oil and working pressure.
Observe for any leakage and monitor MDBFP HC oil level.
Keep Scoop in 0 position and check for all starting permissive.
Ensure power source channel selection for the pump is normalized and after getting clearance from
the local, start the pump in recirculation.
Check auto opening of motor cooler MOV (DMCW-41).
Observe for any abnormal noise/vibration in the running equipment’s.
Observe working oil & lube oil pressure / suction & discharge pressure / bearing temperature in DCS
and local gauges.
Ensure recirculation flow through the pump.
Monitor bearing temperature rise, oil pressure & temperature, winding temperature of motor,
suction filter DP.
By opening discharge valve and its bypass maintain drum level. For initial operation use 30% line for
controlling drum level. At a drum pressure of > 80 kg/cm², change to 100 % line (FDV-16) and isolate
30% line (FDV-13, FDV-14 and FDV-15).
Before stopping the pump ensure scoop in 0 position and ensure discharge and its bypass valve
(FDV-6, FDV-6A) closed.
Stop the pump and observe MDBFP AOP started in auto.
Apply local EPB.
ISOLATION PROCEDURE:
BY
RANJITH KUMAR . R
TURBINE FIELD ENGINEER
SEPC POWER PVT LTD