Protection of HT & L T Transformer
Protection of HT & L T Transformer
Protection of HT & L T Transformer
(A) INTRODUCTION:
Power transformer is a very vital link in
power transmission system. The development of modern power system has been reflected in the advances in transformer designs. This has resulted in a wide range of transformers with sizes ranging from few KVA to Several hundred MVA being available for use in a wide variety of applications.
The consideration for a transformer protection vary with application & importance of transformer. To reduce the effect of thermal stress & electrodynamics forces, it is advisable to ensure that the protection package used minimizes the time for disconnection in .the event of a fault occurring within transformer. Small distribution transformer can be protected using fuses and over current relays. Time delayed fault clearance is not accepted on large power transformer due to system operation / stability and cost of repair or length of outages.
. A FAULT IN TRANSFORMER WINDING IS CONTROLLED IN MAGNITUDE BY THE FOLLOWING FACTORS. (i) Source Impedance (ii) Neutral Earthing impedance (iii) Transformer leakage reactance (iv) Fault voltage (v) Winding connection. Several distinct cases are as below
(e)
.
Interturn Faults :
In a low voltage transformer interturn insulation breakdown is unlikely to occur, unless the mechanical force on the winding due to external short circuit has caused insulation degradation or insulating oil has become contaminated by moisture.
transmission system will be subjected to a impulse voltage, arising from lighting strikes, faults & switching operation. A line surge which is several times the rated voltage will concentrate on the end turns of winding. Partial winding flashover is therefore more likely. The subsequent progress of fault, if not detected in early stage, may destroy the evidence of the true cause.
sufficient to cause winding insulation damage will also cause breakdown of oil with evolution of gas. This gas will escape to the conservator, and is used to operate a mechanical relay.
(E)
TANK FAULTS
dangerous condition, either because of a reduction in winding insulation or because of overheating due to loss of cooling.
OVER LOAD:Overload causes increased "copper loss" and a consequent temperature rise.
SYSTEM FAULTS :System circuit produce a relatively intense rate of heating of feeding transformer. Copper loss in such cases increases in proportion to the per unit fault current. Maximum mechanical stress on winding occurs during the first cycle of the fault.
OVER VOLTAGE
OVER VOLTAGE CONDITION ARE OF TWO KINDS a) Transient surge voltages. b) Power frequency over voltages. a) Transient over voltages arise from faults, switching; and lightning disturbances and are, liable to cause interturn faults. These over voltage are usually limited by providing surge diverters.
b) Power frequency over voltage cause both an increase in stress on the insulation and a proportionate increase in working flux. The latter effect causes an increase in iron loss and large increase in magnetizing current.
TRANSFORMER OVERHEATING
The rating of a transformer is based on
the temperature rise above an assumed maximum ambient temperature. Under this condition no sustained overload is usually permissible. Therefore winding must not overheat. A rise of 8 to 10 degrees in temp will halve the insulation life of the unit. Protection against this is based on winding temperature which is measured by thermal imaging technique.
Fault type
Primary winding Ph - ph fault Primary winding ph to earthfault Secondary winding phph fault
Protection used
Differential, over current Differential, over current Differential
Inter turn
Core Fault Tank fault
transformer, but larger one require over current protection using a relay & circuit breaker as fuses do not have the required fault breaking capacity.
transformer. For protection of large transformers over current relays are used. These relays are connected to current transformers. The contacts of these relays are used in circuit breaker control.
DIFFERNTIAL PROTECTION
This protection is usually employed for
large power transformers and is very effective & clears the fault very speedily. Current transformers on the primary and secondary sides are connected to form a circulating current system.
P1 S1
P2 S2 R
P2 S2 S1
P1
P1 S1
P2 S2 R
P2 S2 S1
P1
When fault is minor - Gas releases slowly When fault is severe - Rapid release of high
volume of Gases.
Buchholz Protection :
Buchholz protection is normally provided on all
transformer fitted with conservator. A typical buchholz relay will have two sets of contacts, Alarm and trip. When a major winding fault occurs, this causes a surge of oil which displaces the trip float & causes isolation of transformer by the tripping of circuit breaker. Buchholz will operate for a) All severe winding faults, either to earth or inter phase. b) Loss of oil if allowed to continue to a dangerous
pressure relief valve is provided which opens to allow discharge of oil if the pressure exceeds a set level, but closes automatically as soon as internal pressure falls below this level. If the abnormal pressure is relatively high, PRV can operate within few milliseconds & trips the switchgear with the help of suitable contacts fitted on it.
OTHER PROTECTIONS
OTI & WTI PROTECTION.
CONSERVATOR OIL LEVEL
PROTECTION
FIRE PROTECTION.