Reactors
Reactors
References
1. REPORT
2. LOAD GENERATION BALANCE REPORT 2010-11 CEA 3. INSTALLED CAPACITY - CEA 4. JOURNAL - TECH NEWS AREVA 5. HV SHUNT REACTOR SECRETS FOR PROTECTION ENGINEERS Zoran Gaji , Birger Hillstrm, Fahrudin Meki ABB Sweden, Vsters, Sweden 6. IEEE Guide for the Protection of Shunt Reactors 7. APPLICATION OF NUMERICAL RELAYS FOR HV SHUNT REACTOR PROTECTION Z. Gaji, B. Hillstrm, M. Kockott , ABB Automation Technologies ,Sweden 8. TRANSIENTS DUE TO SWITCHING OF 400 KV SHUNT REACTOR Ivo Uglei, Sandra Hutter University of Zagreb Miroslav Krepela Siemens Boidar Filipovi- Gri Croatian National Electricity Franc Jakl University of Maribor 9. IS 5553 ( Part 2) 1990 10. IS 2026 ( Part 1 & 3) 11. Installation & commissioning of shunt reactor - BHEL
Series
REACTOR
Shunt
REACTOR
PURPOSE To reduce over voltage AREA OF APPLICATION Bus , Lines, Tertiary winging of ICT
Z Z
Acts as inductance and opposes the flow of short circuit current.
Shunt Reactors
Reason for high grid voltage in Southern grid during off peak period As per CEA report
Installed Capacity 44220 MW Peak Load demand 34224 MW Grid voltage lower than rated (Max 0.95PU or 399 KV)
Availability 28450 MW
11Hrs
15Hrs
22 Hrs
03 Hrs
Formula System Voltage Fault Current level Short Ckt MVA Max Bus voltage Acceptable Bus voltage Skv FkA
Data 420 KV 40 KA
Scc= 1.732 X Skv X FkA 29097 MVA V1 = 441 KV or (441/420) PU V2 = 416 KV or (416/420)PU 1.05 PU 0.99 PU
About 27 numbers of 63 MVAR shunt Nos of reactor required in southern grid to Sr / Sst 27 Nos reactor are required absorb reactive power for bringing down grid voltage from 441 KV to 416 KV during off peak period
Sst
63 MVAR
Commercial 1. Being a capital item, investment on this equipment will be adjusted in the fixed cost portion of tariff so that entire amount ( capital + interest ) will return within the operating period of the reactors.
Shunt Reactor acts as inductive load when it is connected to Bus/Line and draws current for active & reactive load. The reactive portion of current creates pulsating flux in the core and the power required for this purpose is known as reactive power (KVAR).
KVAR = Current X system voltage X Sin
Active current (I x Cos ) to active load (KW)
System Voltage
Reactive current (I x Sin ) to reactive load (KVAR)
Op e
ra tin g
The active portion of current causes I2R loss and the power loss due to heating is known as active power (KW).
KW = Current X system voltage X Cos
cu rre
nt (I)
Ir
Iy
Ib
2. Induced voltage (e) depends upon the construction and magnetization characteristic of the core 3. Shunt reactor is a device with the fixed impedance value. Therefore the individual phase current is directly proportional to the applied phase voltage (i.e. I=U/Z). 4. For balance three phase current (Ir + Iy + Ib = 0), no current flows through the neutral. 5.Only during fault when phase current becomes un balance (Ir + Iy + Ib 0), current less than 1 PU passes through the neutral. It is due to the fact that positive sequence reactance(X1) is more or less equal to zero sequence reactance (x0) in five limbs core configuration (Normally X1/Xo = 0.9). 6. During operation heat is produced as a result of copper loss ( due top I2R) and core Loss ( due to Hysteresis and eddy current) 7. Typical total core & copper loss (KW)= rating of reactor (MVAR) x 0.2% 8. Typical core loss & copper loss = 75% & 25% of total loss respectively
Reactor - 72.5 KV and above Star connected with solid / reactor grounding Oil cooled , gapped core Rating 30 to 300 MVAR Directly connected to bus / transmission line
Reactor - Below 72.5 KV Delta connected Air cooled , Air core Rating below 30 MVAR Directly connected to tertiary winding of transformer
2. Magnetization characteristic
VI linearity range
The flux produced by the core remains proportional to the current passes through the coil till the core gets saturated. After saturation of core it can not produce flux further with the increase of current. Because of this magnetic saturation of the core, reactor coil can not develop inductive voltage (e) further. In such condition impedance of the coil becomes lower with respect to the applied voltage and higher current drawn by the winding causing high I2R loss ( heat generation) or earth fault.
Components of Reactor
WTI OTI
1. 2. 3. 4. 5. 6. 7. 8. 9.
400KV,1250 Amps OIP HV bushings (3 Nos) 145 KV ,1250 amps neutral bushing (1No) Air cell type conservator tank with silica gel breather Radiator banks (8 Nos) with ONAN type cooling Buchholtz relay, Pressure relief valve and sudden pressure valve for protection Floor mounted marshalling box for providing WTI,OTI and required control circuit for protection Provision of line side and neutral side CT terminals in each phase Two numbers treated earth pit for earthing neutral through steel flat Two number earth grid terminals for earthing reactor tank and other metal structure.
Components of reactor
The core sections between consecutive air gaps are moulded in epoxy
resin to prevent movement between individual laminations. The spacers forming the air gaps are blocks of ceramics with a high modules of elasticity and the whole stacking of core modules is cemented together during the assembly to form a solid column without possibility of rocking , or rubbing between individual parts.
M4
M5
M6
Hi-B grade
Thickness 0.3- 0.5 mm , Flux Density 1.6 Tesla Frequency 50 Hz, Gray colour ,E Carlite insulating laminated core
Interleaved disc winding has been used for rated voltages 220 KV
and above. This type of winding configuration provides better impulse voltage distribution. For lower voltage classes a continuous disc winding or a multi layer helical winding are used.
Vibration in reactor
1. As a result of magnetization of core, a magnetic attraction force (F=107xB2)/8 N / m2) approximately equal to (107x1.62)/8 N/m2 or 104 Ton / m2 is produced in the air gap between the core sections. This force pulsates at double frequency (2 X 50 Hz = 100 Hz) due to sinusoidal flux of frequency 50 Hz. Because of this double frequency pulsating force in the core sections, high vibration and noise is observed in reactor during operation.
2.
3.
To reduce the vibration within the limit ( 200 micron) following measures are taken during construction 1. Air gap are filled with ceramic materials 2.
Earthing of Reactor
To earthing grid
LA
LA
LA
To earthing grid
Cooling of reactor
Approximate heat generation during operation of reactor due to core and copper loss = 0.2% x MVAR rating = 120 KW
Copper loss due to I2R loss is about 25% of total loss i.e. 0.25X120 = 30 KW Core loss due to hysteresis & eddy current is about 75% of total loss i.e. 0.75X120 = 90 KW
50000 Litre of oil absorb the heat and rise the top oil temperature to maximum 45 Deg C
8 nos radiator banks reduces oil temperature to 15 Deg C by ONAN cooling process.
Significance of parameters
1. Capacity (S) As reactor is used as inductive load which only absorb reactive power, it capacity is given in MVAR .
2. Impedance / Positive sequence Impedance (X1) It is the per phase AC resistance of the winding which decides the magnitude of per phase current. X1 = U / I = {420000/(1.732X86.6)} =2800 Ohms 3. Zero sequence Impedance (X0) It is the AC resistance of the neutral path which decides the magnitude of earth fault current through neutral. The value of X0 depends on the construction of core. For five limbs core, the value of X0 lays between 90% and 100% of positive sequence impedance (X1). Therefore X0 = 0.9 . X1 = 0.9 X 2800 =2520 Ohms. Because of high zero sequence impedance earth fault current is restricted within 1 PU 4. Winding resistance (R) It is the per phase DC resistance of the winding which decides copper loss (I2R). Measured winding resistance per phase = ---------------Ohms 5. Total loss It is the total active power consumed by the reactor and converted in to heat. Total loss (core and copper loss) = 110KW 6. Power Factor Cos = 110 / 63000 =
0.17%
A KV 000 630
630000KVAR
110KW
Operation
400KV Bus
ICT
230KV Bus
Mines Feeder
Under excitation
to absorb reactive power for decreasing terminal voltage
Increasing tap
to deliver reactive power for increasing bus voltage Switchyard Bus 395 415KV Delivers reactive power to boost up voltage C A P
Decreasing tap
to absorb reactive power for decreasing terminal voltage
R E C
t ren r Cu
1. Reduce excitation 2. Reduce GT tap 3. Switch on reactor 4. Disconnect lines 5. Reduce Gen load 100% Grid Voltage (420KV)
Cur ren t
Inductive loading
1. Increasing excitation 2. Increase GT tap 3. Switch on Capacitor 4. Reduce gen load 95% Grid Voltage (380KV)
WHENEVER THE BUS VOLTAGE RAISES TO 4%TO 5% MORE THAN THE RATED VOLTAGE, SHUNT REACTOR IS TO BE KEPT IN SERVICE AND 2% TO 3% LESS THAN THE RATED VOLTAGE THIS MAY BE KEPT OUT OF SERVICE.
Closing point of BRK for Lowest inrush current . Closing point of BRK for Highest inrush current .
Due to closing of breaker poles in three phases at different point of cycle, unsymmetrical current is developed in three phases which persist for approximately 1 sec As a result of unsymmetrical current, 3rd harmonic current passes through the neutral that may cause spurious tripping on earth fault.
Due to unsymmetrical current, DC off set current is produced which decrease slowly because of low loss in reactor and may cause saturation of CT
Switching off
During switching off operation of reactor high transient over voltage is developed due to breaking of inductive current. This switching transients are inversely proportional to the shunt reactor rated power
Switching transients overvoltage can be reduced considerably by installing surge reactor and control switching operation i.e switching off during zero crossing. Frequent transients overvoltage due to switching off operation always have the impact on the dielectric life of reactor and breakers.
Internal fault
Phase to ground fault at line side
External fault
Inter turn short circuit fault Over load due to over voltage and harmonics
N
Zero seq current (<1 PU)
Shunt reactor is a device with the fixed impedance value. Therefore the individual phase current is directly proportional to the applied phase voltage (i.e. I=U/Z). During external fault voltage of the faulty phase becomes lower than other phases and a result of that unbalance is created in the phase current. Because of unbalance phase current , zero seq. current less than 1 PU passes through the neutral.
Low zero sequence current through neutral due to unbalance in the phase current
1. Short circuit current flow through the line side faulty phase and causes unbalance in the phase current 2. Zero sequence current typically 1 PU flow through the neutral due to unbalance phase current
Shunt reactor winding impedance is approximately proportional to the square of the number of active turns. Short circuit between some number of turns will cause the decrease of the winding impedance only in the faulty phase and corresponding small raise of the shunt reactor neutral point current. Currents during turn-to-turn fault are of the small magnitude and they will not produce any sufficient unbalance voltage. Sufficient unbalance voltage is produced only when number of turn-to-turn short is high. In such condition it is possible to detect turn to turn fault with the help of sensitive directional zero seq relay connected on the HV side of the reactor.
Summary protection
CAUSES EFFECTS RESULTS IN PROTECTION ACTUATES
Switching ON
Zero sequence 3rd Restricted Earth fault with time delay Unsymmetrical harmonic current through the neutral inrush current Diff protection Saturation of CT due to slow decaying of DC offset current Transient over High voltage stress on No protection is voltage the dielectric of the recommended for this reactor & circuit purpose. breaker. Lower than rated current through the faulty phase Unbalance in three Line side residual phase line current current protection Low zero sequence Differential protection current ( 1PU) passes through the neutral Line side residual current protection line side over current protection Differential protection
Switching OFF
Internal High current at Unbalance in three phase to line side in the phase line current ground faulty phase Low zero sequence fault at line current ( 1PU) side passes through the neutral
Internal High current at Rated current at line Neutral side over phase to line neutral side phases current protection ground side High current at Differential protection fault at neutral side neutral side Internal As the chance of this fault is very remote due constructional Phase to feature of the reactor , protection for this fault is not phase short recommended. circuit Inter turn fault Low magnitude voltage unbalance Small rise in neutral No protection is side current recommended since the magnitude of fault
Reactor protection
PURPOSE OF SHUNT REACTOR PROTECTION The purpose of the protection relaying is to disconnect the reactor and limit damage in case of internal short circuits, earth faults, inter turn faults and over voltage or over load. The reactor forms certain impedance for rated frequency, and as it is shunt connected, as over load may be caused by over voltage or harmonics in voltage and current. PROTECTION DEVICES INBUILT OR MOUNTED ON REACTOR a) Oil immersed reactor usually have a gas detector and oil surge detector (Buchholz alarm & trip devices), which are excellent for detecting internal faults. b) Temperature monitors for oil & winding provide good over load protection. c) Pressure relief device is provided to safe guard the reactor from high pressures.
REACTOR DIFFERENTIAL PROTECTION It is widely used as instantaneous protection for short circuit faults with in the differential zone. this is treated as main-1 protection for reactor. It can be of high impedance type or of a sensitive current stabilized type. High impedance differential protection relays require an equal CT turns ratio on the phase and neutral side. Sensitivity is 5% of nominal reactor CT current. BACK-UP PROTECTION A variety of relays are available a) Over current & earth fault protection. ( 50, 50N, 51, 51N, 67, 67N any combination of these) b. Under impedance / distance ( z<)(21r). c. Neutral displacement protection (un>) RESTRICTED EARTH FAULT PROTECTION If, for some reason, a sensitive differential protection not chosen, a restricted earth fault protection can be utilized.
Reactor REF Protection. I) shall be single Pole. ii) Have an operating current sensitivity at least 10% of nominal current. iii) Shall be tuned with system frequency. iv) Have a suitable non-linear resistor to limit the peak voltage during in-zone faults in case of high impedance type. v) Shall be high or low impedance Principle type. vi) Connection of restricted earth fault protection on the neutral side shall be from residually connected Bushing CTs or from the ground side CT.
Reactor Backup Protection (Impedance type) I) Shall be Triple pole type. ii) Shall be single step Polarized MHO or Impedance Distance relay suitable for Measuring Phase to Ground and Phase to Phase to faults. iii) Shall grounds a Characteristic angle between 60-80 deg. iv) Shall have adjustable definite time delay with setting range of 0.2 to 2.0 sec. v) Shall have a suitable range for covering 60% of Reactor impedance. vi) Typical setting : Reach - 60% of Reactor Impedance, Time setting - 1 sec OR Reactor Backup Protection (Definite Time O/L & E/F). i) Shall be single stage Definite Time 3 Pole, Over Current relay with adjustable current and Time. ii) Shall be connected for 2 O/C and 1 E/F connection and shall be non-directional with reset ratio and low Transient Overreach. iii) Typical settings of o/c relays are: Current Setting- 1.3 x Rated current , Time setting - 1 sec
Protection of bus reactor for double bus & transfer bus scheme
Bus I
Bus II
Transfer bus
R E A C T O R I
51N 21 87BB1
87BB2
87U
R E A C T O R II
51N 21 87BB1
87BB2
87U
1. Differential protection
Purpose :Internal / external phase to ground fault.
U1 1s1 V1 1s1 1s2 W1 1s1 1s2 N
Line side CT 1
1s2
DP 87
Neutral side CT 1
1s1 1s2 U2 V2
1s1 1s2 W2
1s1 1s2
CT Specification 1. Ratio: 200/1A 2. Class: PS 3. Knee point voltage: 200V 4. Magnetizing current: 40 mA 5. Secondary resistance: 1 Ohms
Type of relay : High impedance differential relay Setting : operating current sensitivity at least 10% of nominal current. operating time not grater than 30 m sec at 5 times of setting.
2.
1. External phase to ground fault.( Unbalance phase current) 2. Internal phase to ground fault at line side .( Unbalance phase current) 3. Circuit breaker pole discrepancy.( Unbalance phase current)
N U1 V1 W1
1s1 1s2
1s1 1s2
1s1 1s2
Instantaneous Residual over Current Relay (50N) Or AC Time residual Over Current relay (51N)
CT Specification 1. Ratio: 200/1A 2. Class: PS 3. Knee point voltage: 200V 4. Magnetizing current: 40 mA 5. Secondary resistance: 1 Ohms U2 V2 W2
Typical relay setting Set low set to 20% with time delay in between0.6s and 1s or even longer. Use 2nd harmonic blocking. Set high set to 175% with time delay of 0.1s.
U1
V1
W1
1s1 1s2
1s1 1s2
1s1 1s2
21R 3Ph, REACTOR BACKUP IMPEDANCE RELAY OF SUITABLY SHAPED CHARECRESTICS EITHER SINGLE / DOUBLE ZONE TYPE
CT Specification 1. Ratio: 200/1A 2. Class: PS 3. Knee point voltage: 200V 4. Magnetizing current: 40 mA 5. Secondary resistance: 1 Ohms U2 V2 W2
Set low set to 130% with time delay in between 0.6s and 1s. Set high set to 250% with time delay of 0.1s.
U1
V1
W1
Line Side
Instantaneous Over Current Relay (50) Or AC time over current relay (51) Over current protection
U2
V2
W2
Neutral Side
Typical relay setting Set low set to 130% with time delay in between 0.6s and 1s. Set high set to 200% with time delay of 0.1s.
Measurement of WR
Purpose - To measure DC resistance per phase of coil for calculating I2R loss in the coil, which in turns decides the temperature rise. The measurement also shows whether the winding joints are in order and the windings are correctly connected.
Measuring methods 1. 2. 3. 4. Only at the stable value of current (I), corresponding voltage (V) value is taken for measuring the value of resistance ( R = V/I). Applied current must not be higher than 15% of the rated current % error in measurement increases with increases of applied current due to increases in I2R loss at higher current. Value to be measured between (R N) , (Y-N), and (B-N), and all the measured value must be equal.
Measurement of IR
Purpose - To ascertain minimum insulation strength (IR Value) and dryness level (PI Value) of the winding required to charge the reactor.
5 KV IR measuring Kit (Megger) Procedure Measure IR and PI value between (R-E),(Y-E),(B-E) and (R+Y+B) (Tank + E) with 5 KV Megger and confirm the minimum IR and PI value as per the table given below.
Minimum Below 6.6 KV 6.6 - 11KV IR value K = 1.00 30 Deg C 200 M 400 M 22 33 KV Above 66 KV
500 M
600 M
K = 1.65 40 Deg C
121 M
242 M
303 M
363 M
K = 2.60 50 Deg C
77 M
153 M
192 M
230M
K = 4.20 60 Deg C
47 M
95M
119 M
142 M
30 M 19 M
60 M 38 M
75 M 47 M
90 M 57M
Isolation test
Purpose - To ascertain that the reactor core is insulated from the tank and core frame.
CC CL
Core clamp Core Bolt Core Tank
Procedure :
1.Disconnect the closing link that connects the two terminals CL-G. 2.Connect the tank with earth 3. Use a Megger and measure IR value between CL and CC + G by applying 3.5 KV for 1 minute 4. The measured IR value shall be minimum 1000 kohms ( 1 M Ohms) 5. There is no general requirement on the insulation level CC-G .
Reactor windings
100/5A 1.0032mH
8.92 H
2800 Ohms
Measurement of loss and current at rated voltage and ambient temperature Purpose: To measure the loss ( core & copper loss) in reactor at rated operating condition.
Reactors windings
U1 M3 CN C4 R4
100/5A 1.0032mH
Inductance (Lx) Impedance (Z) Tan delta ( D) Loss at rated voltage (P) Loss at rated Current
KV
50 Hz, AC Generator
Method
Test voltage from a 50 Hz, sinusoidal source is applied at neutral terminal through a step up transformer keeping the phase under test open and other two phases & tank grounded. ( 400 KV /1.732) or 230 KV rms 60 sec
Measurement Direct reading for RMS type voltmeter or of test (Reading / 2) for Peak type voltmeter voltage (KV) Confirmation The test is declared to be successful if the test voltage does not collapse during the test.
Induced over voltage withstand test with PD indication at 364 KV AC (1.5/3 PU ) for 30 minutes during which the PD level shall not exceed 500pc ( Method 2)
PURPOSE : To verify the power frequency voltage withstanding capacity of the minor
insulation (Paper ) used in line terminals & windings and the maximum level of PD observed during the test.
KV
50 Hz, AC Generator
Method
Test voltage from a 100Hz ( to avoid saturation of core), sinusoidal source is applied at line terminals through a step up transformer keeping neutral terminal open and tank grounded.. ( 1.5 x 420KV /1.732) or 364 KV rms 30 minutes in steps at various voltages level as shown below Direct reading for RMS type voltmeter or (Reading / 2) for Peak type voltmeter (V)
The test is declared to be successful if the test voltage does 5 during the test. and the PD level is observed not collapseSec within 500pC 30 Minutes 5 Minutes 420KV 364KV
364KV
Full wave lighting impulse voltage withstand test at 1300 KVp on line terminal
PURPOSE : To verify the impulse voltage withstanding capacity of the major
insulation ( pressboard) used between the windings, line terminals caused by lighting strike.
Impulse Generator
+
5 0 0
Recorder Method Test voltage from an impulse generator is applied at line terminals keeping neutral grounded through 500 resister and other terminals directly grounded. The sequence for applying impulse is - one impulse of a voltage between 50% and 75 % of the full test voltage, and three subsequent impulses at full voltage 1300 KV peak with Front time T1 = 1,2s 30% and Time to half-value T2 = 50 s 20% The test is successful if the test voltage does not collapse during the test.
Impulse Generator
+
5 0 0
Recorder Method Test voltage from an impulse generator is applied at line terminals keeping neutral grounded through 500 resister and other terminals directly grounded. The sequence for applying impulse is - one impulse of a voltage between 50% and 75 % of the full test voltage, and three subsequent impulses at full voltage
Test voltage 1050 KV peak Duration of test Front time Tp> 100s , Time above 90% Td> 200s and Time to the first zero passage T0> 500s ( preferably 1000 s )
Confirmation The test is successful if the test voltage does not collapse during the test.
Type Test
1. Temperature rise test along with DGA before and after test 2. Full wave lighting impulse voltage withstanding test at 550 KVp on neutral terminal 3. Measurement of zero sequence reactance 4. Measurement of acoustic noise level 5. Magnetizing curve test / knee voltage measurement 6. Measurement of capacitance and tan delta between winding and tank
Cold winding resistance at T deg C Hot winding resistance after switched off (to be derived from graph) Ambient temperature after switched off Calculated winding temp Average steady state hot oil temp Hot oil temp after switch off Drop in average oil temp Corrected winding temperature Winding temperature rise
R1 R2
Full wave lighting impulse voltage withstanding test at 550 KVp on neutral terminal
PURPOSE : To verify the impulse voltage withstanding capacity of the major and
minor insulation (Pressboard and paper) used in neutral terminals and side of the winding caused by switching operation.
Impulse Generator
+
5 0 0
Recorder Method Test voltage from an impulse generator is applied at neutral terminals keeping other terminals grounded through 500 resister and tank directly grounded. The sequence for applying impulse is - one impulse of a voltage between 50% and 75 % of the full test voltage, and three subsequent impulses at full voltage
Test voltage 550 KV peak Duration of test T1 = 1,2s 30% and Time to half-value T2 = 50 s 20%
Confirmation The test is successful if the test voltage does not collapse during the test.
A N R Y B
50 Hz, AC Generator
Method
Two phase AC supply is applied between line terminals and neutral through a step up transformer which is fed by a generator. Applied voltage is increased till rated current flow through the line terminals. At this voltage current through the neutral is measure. (3 x Applied voltage) / Neutral current.
1 Meter
2 Meter
A sound spectrum analyses is used for measuring sound level. The sound spectrum indicates the magnitude of sound components as a function of frequency. The sound pressure level is the measured at various points around at a distance (D) of 30 cm for ONAN or 2 m for ONAF cooling system spaced at an interval (X) of 1 meter.
Limit Sound level Vibration level Within 81db Within 200 microns
Test procedure
Each phase of the reactor is charged one by one with direct current. When the maximum test current reached, supply is switched off and the reactor winding is short-circuited simultaneously by DC current breaker. The decaying current in the circuit is registered by a computer assisted data acquisition system. The saturation curve Flux () / Flux () nom. versus I/Inom is then determined using the formula.
Maximum value of decaying current Minimum value of decaying current Measured value
I
N R Y B 10 KV Tan Delta Kit
+ + + Ir +
Ic
I = total current drawn by the capacitor formed between winding and tank and the value of capacitance is [(I/2 f V ) x Cos ] (pF) Ic = Capacitor charging current Ir = Current flow through the capacitor due to impurities / disintegration of the insulation between winding and tank. As this current is in phase with applied voltage, it is dissipated in heat. Tan = Sin =Cos (PF) 0 0.002 0.004 0.006 0.007 0.008 1.0 Condition of the insulation Pure capacitor Very good Good Fairly good Acceptable Not acceptable Pure resistance
Ir
Angle 0.0 Deg 0.5 Deg 0.5 Deg 0.5 Deg 0.5 Deg 0.5 Deg 90.0 Deg
Capacitance (pF) [(I/2 f V ) x Cos ] (I / 3140) x 1.000 (I / 3140) x 0.999 (I / 3140) x 0.999 (I / 3140) x 0.999 (I / 3140) x 0.999 (I / 3140) x 0.999 0
Special Test
1. FRA test 2. DGA test before and after electrical test 3. Vacuum test on reactor tank 4. Oil leak test 5. Snap back test on HV bushing
FRA test
Purpose- Frequency Response Analysis (FRA) is carried out to detect displacement (or movement) of the windings. Usually the first measurement in the factory is used as a fingerprint. Results of later measurements are compared with the first one in the factory.
The software controlled sine wave generator produces output voltage of max. 4 Vrms with frequency range of 50 Hz to 1 MHz. It has 75 output impedance. Input impedance is 75 . Voltage from the generator is applied to the one transformer terminal (one winding end) and response voltage is measured on another terminal (the other winding end).
Or attenuation A (or damping) in dB (20 log (Uoutput / Uinput ) versus frequency is plotted on the diagram with indication of terminals with applied and response voltage.
The reactor is said to be healthy if no deviation is observed between the results taken in factory and field
DGA test
Chemical analysis of gas : The gas analyser loaded with these solution is connected to the top pet cock. Small quantities of gas collected in the gas relay (Bucholtz relay) is allowed to pass through the two solutions.
A week solution of ammonia in water is slowly added to 100 ml of solution 1, until a white curdled precipitate which forms first disappears in the mixture.
FFT
Methods : Two nos. Piezoelectric accelerometer were mounted 90 degree apart at the bottom of the bushing, one in the direction of applied force (X) and other 90 degree to the applied force (Y). A force of 250 Kg was applied at the top and then it was cut-off. The resulting vibrations were recorded on the FFT. The recorded signals were analyzed on FFT Analyzer to determine the natural frequency and damping factor of the bushing.
X direction Natural From FFT reading frequency 3.25 Y direction 3.25
Damping [(100 / 2 n) * log (Y 1 / Yn+1)] Where: n = No. 1.421% 2.03% factor of cycle Y n+1 = Amplitude of (n+1) cycle peak Y1 = Amplitude of The test is successful if no evidence of physical damage is observed on 1st after peak the bushing cycle the test
Final Observations
Though oil immersed, shunt reactor and power transformer are viewed alike, there are distinct differences between construction and operating characteristics of these two devices. As NLC is going to install two numbers 63 MVAR bus reactor for the first time in TS II and the operating and maintenance staffs are not properly exposed to its operating data, following information need to be collected from any southern grid thermal power plant ( not from substation) presently operating with similar capacity bus reactors for successful and trouble free operation of reactor in TS II Average number of switching operation of the reactor per day Numbers of operating hours achieved since commissioning Numbers of forced / planned shutdown taken after commissioning Protection co-ordinations and its settings Number of false/actual tripping, if any, since commissioning and its reasons Maximum & minimum bus voltage for switching in and out of reactors Reduction in leading MVAR and bus voltage after switching in of the reactor Any abnormalities observed in generator excitation during switching in/out Average reactor current, winding and oil temperature Any failure of parts like bushings, LA, gaskets etc since commissioning Remarks of the operating staff on the performance of the reactors
Thank you