Ghana Journal of Science, Technology and Development | Vol. 8, Issue 2, December 2022
e-ISSN: 2343-6727
Ghana Journal of Science, Technology and Development |8.2|
Issahaku andSeptember
Kemausuor, 2022.
Received:
25, 2021
Accepted: August 6, 2022
DOI: https://doi.org/10.47881/291.967x
Techno-economic comparison of standalone solar PV and hybrid power systems for remote
outdoor telecommunication sites in northern Ghana
Mubarick Issahaku1, Francis Kemausuor2
1
Energy Technology Centre, School of Engineering, University for Development Studies, P. O. Box TL
1350, Tamale – Ghana
2
The Brew-Hammond Energy Center, College of Engineering, Kwame Nkrumah University of Science
and Technology, Kumasi – Ghana
Corresponding email: mubarick.issahaku@uds.edu.gh
ABSTRACT
Telecommunication services have continued to evolve to meet the ever-changing bandwidth
demand requirements. The electricity grid network of Ghana is faced with challenges, including
low voltages, a lack of quick fault response teams, and the proximity to specific locations. Using
diesel generators to address the shortfall in grid supply is expensive and has implications for
greenhouse gas emissions. This study evaluated the technical and economic benefits of using a
standalone solar photovoltaic (PV) system, hybrid (Solar PV/diesel), conventional diesel
generators (DG), and grid extension to power an off-grid outdoor telecommunication site. Power
solutions configurations were simulated using hybrid optimization of multiple electric renewables
(HOMER). The study found the optimum design to be a standalone solar PV/battery system with
56.3 kW solar PV array and Sixty (60) pieces of 12 V SAGM batteries of 135 Ah. The optimum
design had a net present cost (NPC) of US$ 88,176.00 and a cost of energy (COE) of US$
0.321/kWh. The COE and the NPC of the optimum system were approximately 50% less than the
design with DG only, which could significantly impact service tariff and improve access to digital
connectivity. The COE from the solar PV/battery system is not competitive with the grid power
supply (COE = US$0.12). However, considering the electric distance limit or breakeven distance
of 4.51km for grid extension, the solar PV/battery is preferred. Therefore, the stakeholders in
providing power solutions to off-grid locations should consider solar PV technology.
Keywords
Telecommunication, off-grid sites, Standalone solar PV, HOMER, electric distance limit, grid
extension
INTRODUCTION
The International Telecommunication Union
(ITU) estimates that 3.7 billion people in
2020 were utterly cut off from the internet
(digital communication systems) and left out
of
tapping
into
the
technology's
transformative power advantages. These
figures require urgent attention in the wake of
the COVID-19 pandemic as connectivity has
been tagged the "hidden hero" globally in
managing the spread of the deadly virus. The
dependence
on
information
and
communication
technologies
(ICTs)
networks and services has irrevocably
1
Ghana Journal of Science, Technology and Development |8.2|
reinforced the significant contribution of
connectivity to our society's survival
(Martins, 2020). ICT infrastructure networks
allowed us to work remotely, stay in touch
with relations, online schooling, collaborative
research, etc., to prevent the world's
unthinkable shutdown (Pokhrel & Chhetri,
2021; Shahzad et al., 2020; UCLG, 2020). It
is unequivocal that access and connectivity
are cardinal to sustaining our "new normal"
during and in the post-COVID-19 world.
Aside from the estimated populace
completely cut off from the digital space,
many developing countries struggle with
expensive, unreliable, and slow connectivity
challenges that disadvantaged them during
the
COVID-19
crisis(International
Telecommunication Union, 1999; Sambuli,
2016).
Africa
and
Commonwealth
Independent States (CIS) regions, according
to the ITU facts and figures report 2020, are
facing an enormous gap in access to mobilebroadband networks of 23% and 11%,
respectively
(International
Telecommunication Union, 2020). These
challenges in digital connectivity have
several dimensions and require a wholesome
approach to address. However, access to
power is fundamental to finding a solution to
ensure nobody is left behind in the universal
digital connectivity campaign. Access to
electricity in Africa is faced with technical,
political commitment, and financial issues
identified by Brew-Hammond (BrewHammond, 2010). These challenges have
seen significant improvement leading to
increased electricity access in some African
sub-Saharan regions, as reported in the
African Energy Outlook 2019. These
improvements are noticeable in a few
countries in the sub-region, such as Kenya,
Senegal, Rwanda, Ghana, and Ethiopia. In
Ghana and Kenya, the electricity access rate
as of 2019 was almost 85%. Grid connections
Issahaku and Kemausuor, 2022.
have accounted for most progress in Africa
over the last decade, but off-grid systems
have rapidly increased deployment to
augment
grid
extension
challenges
(International Energy Agency, 2020; Kumi,
2017b; USAID, 2020; World Bank, 2019).
There are, however, unelectrified areas due to
the high cost of grid extension and
remoteness.
Globally, mobile telephony has the most
intriguing success stories of technology
diffusion. Compared with fixed-line
telephony,
it
achieved
phenomenal
subscribers in a short period and became a
household technology (Bento, 2016; Kalba,
2008; Kauffman & Techatassanasoontorn,
2005). Since the introduction of mobile
cellular services into Ghana by Mobitel in
1992, it has immensely enhanced Ghana's
economy. Telecommunications services have
become an integral component of the daily
lives of Ghanaians, from traditional voice
calls to the payment of utility, data services,
medical advice, and mobile money services
(banking) (Chris et al. 2002; Haggarty,
Shirley, & Wallsten, 2005; Osei-Owusu,
2015; Osei-Owusu et al., 2002). The
country's telecom industry services consist of
fixed-line services, mobile 2G/3G/4G, and
Internet Service Providers (ISPs). Currently,
there are four 2G/3G/4G active, licensed
operators
in
Ghana.
Mobile
Telecommunication Network (MTN) has
over 50% of the market share in voice and
data services as of the first quarter of 2020
(National Communication Authority- Ghana,
2020). The country has a vibrant commercial
telecommunication industry providing the
platform for innovative services. The
capacity, coverage, and availability of their
infrastructure were tested in the wake of the
pandemic. Power availability is directly tied
to the performance of the telco and users.
2
Ghana Journal of Science, Technology and Development |8.2|
The services provided serve a considerable
populace, positively impacting broader
economic
growth
and
contributing
significantly to government finances(GSMA,
2019). As of 2016, Ghana's mobile
penetration rate stood at 131.9%, according to
the National Communication AuthorityGhana (2019). Estimates of the mobile
penetration rate of 2020 stood at 140% and
are expected to increase due to the pandemic's
increased demand for mobile connectivity
(Statista, 2020). The recorded mobile
penetration rate does not mean all Ghanaians
own a mobile phone; instead, an individual
could own multiple subscriber identity
modules (SIM). According to Groupe
Speciale Mobile Association (GSMA)
intelligence, the country has the highest
mobile penetration in the West African subregion, surpassing others in the region with an
adoption rate of 55%, higher than the regional
average 44.8% at the end of 2019.
Ghana's Telecom infrastructure, such as
towers and power systems, are either owned
or operated by the Mobile Network Operator
(MNO) or licensed tower companies
(National Communication Authority- Ghana,
2018); the latter is prominent. As of 2012,
there were 5,583 tower sites in the country,
with 638 sites, approximately 11%, deployed
in off-grid areas. One of the main challenges
for these telecommunication companies in
providing reliable and broader coverage is
access to an uninterrupted power supply.
Telcos operators achieve continuous power
supply by running diesel generators and
backup batteries. In Ghana, an average of
1,300 liters of diesel is consumed monthly by
an off-grid site against 450 liters for gridconnected cell sites(Green Power for Mobile,
2012). Apart from being expensive to
operate, diesel generators (DG) also have the
disadvantage of greenhouse gas emissions
with implications for global climate(Höök &
Tang, 2013; Johnsson et al., 2019; Williams,
2002; Wuebbles & Jain, 2001). Studies have
estimated that about 2-3% of the world's
Issahaku and Kemausuor, 2022.
energy consumption is on Information and
Communications
Technology
(ICT),
contributing to about 3% of the total CO2
emissions (Anayochukwu & Nnene, 2013;
Cunliff, 2020; Höök & Tang, 2013; Johnsson
et al., 2019; Lu, 2018). The continual
powering of these ICT appliances and
infrastructure on unclean energy sources
directly impacts the environment. Rising
fossil fuel prices, fuel spillage, fuel pilferage,
and the short life span associated with DG use
from the frequent start and shut down
procedures are challenges confronting MNO
and tower companies(Tebepah, 2015).
Ghana has a high access rate to grid
electrification, at approximately 85% in
2019. Remote communities that have not
been connected yet may remain so for the
foreseeable future due to the high cost of
extending the grid to these communities,
where productive use opportunities are
currently limited (Kumi, 2017a; Ministry of
Energy, 2017.). The potential to use
renewable energy resources for electrification
of rural and remote communities has been
espoused largely in literature with
confirmatory findings (Aboagye et al., 2021;
Brown & Hewitt, 2006; Opoku et al., 2020).
The country is located along the equator and
positioned to receive significant solar
irradiance. The average solar irradiation
ranges from 4 to 6 kWh/m² per day, ideal for
harnessing to create isolated/grid-connected
power systems to meet isolated communities'
load demands or supply the grid. The
potential has been identified and supported by
Ghana's renewable energy policy, which
focuses on improving cost-effectiveness and
creating favorable regulatory and fiscal
regimes for RE. It further seeks to support
local research and development to reduce
costs and promote solar PV power technology
in its renewable energy master plan and
action plans (ECREEE, 2015; Ministry of
Energy, 2019).
3
Ghana Journal of Science, Technology and Development |8.2|
Renewable energy systems offer a solution
that involves replacing part or wholly diesel
generators with renewable energy sources as
the main power supply for tower sites.
Powering a cell site with solar PV can be
achieved totally (standalone) or partially
(using a hybrid of electricity from the grid,
diesel generator, or other renewable energy
technologies). Hybrid systems use more than
one energy source, thereby taking advantage
of the benefits of those energy sources.
Several combinations of conventional and
renewable power system configurations are
implemented
for
telecommunication
purposes worldwide. Renewable power
options adopted are dependent on resource
availability at the site (Anayochukwu, 2013;
Anayochukwu & Ndubueze, 2021; V. Ani,
2017). In the northern part of Ghana, annual
solar radiation averages approximately 5.57
kWh/m2/day throughout the year (Energy
Commission, 2018). While wind speeds are
relatively high in the harmattan season
(between December and March every year),
there are no ground measurements to confirm
wind resource viability for commercial
electricity generation(Essandoh et al., 2014).
Techno-economic comparison of standalone
solar PV/ hybrid(diesel/wind) feasibility
studies has been conducted in countries with
unreliable grid networks in the African subSaharan extensively in Nigeria, using hybrid
optimization for multiple electric renewables
(HOMER). Lanre demonstrated in a study
that hybrid(solar PV, batteries, and diesel)
could supply the electricity requirement of a
health facility in Nigeria for an off-grid
community (Olatomiwa et al., 2018;
Olatomiwa & Mekhilef, 2015). In Nigeria,
Ani (2016) conducted a solar PV/hybrid
system feasibility for a residential home; the
finding suggested that the load could be
supplied
with
a
hybrid
solar
PV/batteries/diesel generator with the least
net present cost (NPC). Feasibility studies
have been carried out exploring solar PV,
wind, and diesel generators as a hybrid
Issahaku and Kemausuor, 2022.
system to power remote telecommunication
sites in Nigeria, suggesting that the hybrid
system was the optimum design. These
studies further suggested a reduction in
carbon-dioxide (CO2 ) released into the
environment. The economics of systems
played in favor of hybrid systems over the
system's life cycle. However, the hybrid
systems had the highest initial capital
investment compared with conventional
diesel generators. In these studies, the
numeral values of parameters of comparison
varied significantly due to varied load sizes
and system pricing (Anayochukwu &
Ndubueze, 2013; Babatunde et al., 2019;
Olatomiwa et al., 2015). Similar feasibility
studies in Malaysia with HOMER comparing
standalone and hybrid systems showed that
the hybrid system was sustainable,
economical, and environmentally-friendly
(Alsharif & Kim, 2016; Alsharif et al., 2015;
Halabi, Mekhilef, et al., 2017; Hossain et al.,
2017).
In Ghana, studies on the feasibility of
renewable energy systems solutions have
considered electrification of remote or island
off-grid communities, with results suggesting
the promising utilization potential. However,
challenges ranging from techno-economics to
socio-technical need to be addressed to reap
the
benefits
of
renewable
energy
solutions(Bukari et al., 2021; Gyamfi et al.,
2015; Kemausuor & Ackom, 2017; Nuru et
al., 2021). A feasibility study on a hybrid
mini-grid renewable energy system (
consisting of solar PV and biodiesel
generators) in Wa East district by Adaramola
et al. in 2017 using HOMER computer
application software showed a COE of US$
0.76/kWh from the system at full cost
(Adaramola et al., 2017). In recent times, a
standalone hybrid mini-grid system (solar
PV/battery/converter) feasibility study for an
off-grid community of Nkrankrom in the
Bono region with HOMER showed COE as
US$ 0.107/kWh making it the preferred
choice over grid extension to the community.
4
Ghana Journal of Science, Technology and Development |8.2|
The feasibility study results conducted by
Quansah et al. on powering an outdoor base
transceiver station (BTS) in the Eastern
region suggested a 48% saving on COE from
a standalone diesel power solution with a
hybrid (diesel/solar PV (Quansah et al. 2017).
Furthermore, in an attempt to explore
competitive alternate sources of power to
power a telecommunication site by OdoiYorke & Woenagnon, (2021) using HOMER
for a solar PV/fuel cells hybrid system, the
results show that the levelised COE (LCOE)
produced by the PV/fuel cell hybrid system is
about US$0.222/kWh. This LCOE outshines
the current average grid tariff (US$ 0.25
/kWh) paid by grid-connected telecom base
stations. Although many other studies have
been
reported
on
powering
telecommunication sites in other parts of the
country, there were no published studies in
our study area to the best knowledge of the
authors. This study went further to compare
the proposed power solutions to grid
extension referenced to the electric distance
limit (EDL)/breakeven distance.
Has this unfortunate turn of events favoured
renewable energy potential to provide power
to remote telecommunication sites in Ghana's
northern parts? This paper performed a
techno-economic analysis of a standalone
solar PV, hybrid power systems, and grid
extension option to determine if the current
rising fuel prices and the reducing cost of
solar PV system components have affected
previous studies' results. The findings
suggested that a standalone solar PV power
solution is affordable compared with other
solutions (hybrid, diesel only, and grid
extension) and would enhance universal
access to reliable digital connectivity towards
attaining sustainable development goals. The
study's outcome suggested a paradigm shift
for researchers and stakeholders in the
industry of the previous findings. It
contributed to the scientific literature on the
prospects and benefits of deploying
renewable energy. In the wake of the
Issahaku and Kemausuor, 2022.
COVID-19 pandemic, a revisit to past
research findings is key to informing policy
and regulation development to accelerate
renewable energy in Ghana and countries
with similar climatic conditions.
MATERIAL AND METHODS
The study employed a non-intrusive energy
audit technique to generate load profiles used
in HOMER software. HOMER software is an
excellent techno-economic feasibility studies
tool suitable for this study objective as used
in similar studies. It is a computer-based
model used in micropower systems design
and compares the cost of energy from
different power generation technologies. As
seen in the literature, HOMER is widely used
for techno-economic studies of renewable
energy systems and performs calculations
with high accuracy. It can model systems'
physical behavior and compare design
options based on their technical and
economic merits. (HOMER Energies, 2021).
HOMER simulates systems' operation by
making the energy balance calculation for
each of the 8760 hours in a year. The model's
primary inputs were monthly solar insolation,
cost of components, diesel price, daily load
profile, and other economic parameters. A list
of configurations sorted based on the Net
Present Cost (NPC) were presented.
However, the system configuration based on
TNPC could vary depending on selected
sensitivity variables. The software repeats the
optimization process for every selection of
sensitivity variables. In this study, the
sensitivity variables were fuel price, discount
rate, and cost of solar system components.
The optimal solution from HOMER for a
renewable energy system is the feasible
system with the lowest TNPC(Gilman &
Lilienthal, 2006).
5
Ghana Journal of Science, Technology and Development |8.2|
Study area
Ghana's Northern part is characterized by low
laying landscape with few escarpments and
savannah vegetation. The region's climate is
relatively dry, with a single rainy season in
May and ends in October. The amount of
rainfall recorded annually varies between 750
mm and 1,050 mm. The dry season starts in
November and ends in March/April, with the
highest temperatures recorded towards the
end of the dry season (March-April) and the
lowest temperatures recorded in December
and January(Cudjoe et al., 2013). The dry
season features dust that could settle on solar
panels. A previous study on the effect of dust
on solar panels' performance showed a
significant portion of solar radiation blocked
by dust particles(Styszko et al., 2019). The
study community is Keto - Daboya in the
North Gonja district (lies between Lat 9ᵒ 39'
01" N, Long 1ᵒ 23' 23") in the Savannah
Region of Ghana. The community is along
the Daboya river, a tributary to the White
volta. Access to communities in these
catchment areas is characterized by
inadequate network coverage and bad road
conditions and is usually cut off in the rainy
season.
Solar resource assessment and input
The average annual solar irradiance in the
region is 5.57 kWh/m2/day, with monthly
averages provided in Table 1. The study
area's estimated solar energy potential is
2,033 kWh/m2/year based on the detailed
solar data. From December to early February,
the Sahel's harmattan winds significantly
impact temperatures in the region, causing a
variation between 14˚C at night and 40˚C
during the day(Cudjoe et al., 2013). These
temperatures are within the operating
temperature of 47˚C for flat plate solar
panels.
Issahaku and Kemausuor, 2022.
TABLE 1. Average global horizontal solar
irradiance of the study area
Month
Clearness
Index
Daily radiation
(kWh/m2/Day
January
February
March
April
May
June
July
August
September
October
November
December
0.607
0.607
0.591
0.569
0.563
0.548
0.478
0.473
0.51
0.592
0.641
0.628
5.44
5.842
6.058
5.984
5.843
5.596
4.9
4.913
5.242
5.777
5.819
5.476
Furthermore, the region under study has a
good clearness index. The clearness index
measure approaches the optimum value of 1,
indicating that more solar radiation can
penetrate the atmosphere to fall on the solar
PV panels. Its value increases under clear,
sunny conditions and decreases under cloudy
conditions. Considering the effect of
temperature on panels' output, HOMER
computes the PV array's output power as
shown in Equation 1.
Ḡ𝑡
PPV = YPV ƒ PV(Ḡ𝑡,𝑆𝑇𝐶 ) [1 + αp (Tc –Tc, STC)]
………………………………….…….. (1)
Where:
PPV is the output power, YPV is the rated
capacity of PV array under standard
conditions [kW], ƒ PV is PV derating factor [%]
which represents effect of dust falling on
panels, wiring losses, shading, ageing, etc.
ranging from 0.5 to 0.95, Ḡt represents the
solar radiation incident on the PV array in
current time step [kW/m2], Ḡt, STC is the
incident solar radiation at standard test
conditions (STC)[kW/m2], αp is temperature
coefficient of power [%/˚C], Tc PV cell
6
Ghana Journal of Science, Technology and Development |8.2|
temperature in current time step [˚C] and Tc,
STC is PV cell temperature under standard test
conditions [25˚C](Islam, Akhter, & Rahman,
2018). A monocrystalline solar panel was
used in the simulation due to the excellent
efficiency of an average value of 16.4% at
standard test conditions.
Solar resource input for simulation
This part requires information on the solar
resource available on the site to model,
simulate, and assess the performance of a
system. HOMER software downloaded the
site's solar resource from the National
Aeronautical Space Administration (NASA)
Surface Meteorology satellite. The area
receives an annual daily average of 4.9
kWh/m2 to 6.058 kWh/m2 of global sun
irradiation. This choice was made because
there was no publicly available found data on
solar radiation measured from the ground
were available for the specified site
(Asuamah et al., 2021)
Electric load demand of site
To minimize the effect of error in load
estimation of the study, a non-intrusive
energy audit technique was employed at
existing sites to generate the load profile. The
electric load demand at a site depends on its
capacity, active traffic, and additional
functions. A hop/hub site linking other sites
via a microwave transmission radio or fibre
optic systems or both would have higher
power consumption compared to a terminal
site. This assertion might not always be
accurate as a terminal site installed in a
densely populated community might have
several base transceiver stations impacting its
power consumption considerably. To check
this uncertainty of terminologies, the study
considered the electric load demand of ten
(10) outdoor cell sites base transceiver station
(BTS) (2G/3G) of a telecommunication
operator. An outdoor site does not necessarily
mean the site is a hop/hub or terminal site but
refers to the provision of shelter space with
air cooling systems to control equipment
Issahaku and Kemausuor, 2022.
temperature. The absence of air-cooling
systems (air conditioners) in outdoor sites
reduces its electricity demand making it the
preferred
choice
in
modern
telecommunication site design. Good load
forecasting is crucial to the design of power
systems. Electricity demand estimation was
based on ratings of equipment. The criteria
for the selection of sites are presented in
Table 2.
Table 2. Selection criteria for sites
Selection criteria
Outdoor site
BTS 900/1800/Node B
Transmission radio
Standby diesel generator
An outdoor site BTS 900/1800/Node B single
cabinet with three (3) sectors each and two (2)
plesiochronous digital hierarchy (PDH)
microwave radios for transmission was
selected for the study. The aforementioned
equipment constituted the main equipment of
the site with an additional auxillary load such
as power outlets, aviation warning lights, and
security floodlights, as summarized in Table
3.
Alternating Current (AC) loads on a direct
current (DC) source power requires an
inverter for conversion, introducing losses in
the process. A DC load is preferred for an
optimum solar PV system; however, this is
not the case in some sites. Air conditioners for
shelter are usually AC load, and their motors
require a high startup current, about three (3)
to five (5) times its rated current. The site
selected for the study is a modern outdoor
BTS using DC fans for cooling, thereby
eliminating the energy cost of air
conditioners. A rectifier is required in a
hybrid (Solar PV/diesel generator) system to
convert AC from the generator to DC. Table
3 shows details of equipment of the selected
site with the power rating of the equipment.
7
Ghana Journal of Science, Technology and Development |8.2|
Issahaku and Kemausuor, 2022.
TABLE 3. Load estimation of outdoor (900/1800/Node B) cell site
Power equipment description
Rated
Power (W)
Quantity
Duration of
usage (h/day)
Daily power
(Wh/day)
BTS (900/1800/Node B)
PDH transmission radio
Aviation warning light
2640
125
15
1
2
2
24
24
12
63,360
6,000
360
Security/flood lights
100
1
12
1,200
Total
70,920
Daily load curve input estimation
The main loads of a telecom site (BTS and
PDH transmission radio) run continuously for
24 hours per day, with varied power
consumption. The energy consumption of the
BTS is linked to traffic processing. The traffic
profile varies for sites depending on the
demographics. For example, an urban center,
especially in educational institutions where
students patronize promotional calls (voice
and video) and data packages, will vary
significantly compared to a farming
community. BTS's energy demands reduce by
80 - 85% during idle periods as most sectors
are off, leaving the baseband unit for
signaling(ZTE Corporation, 2003). The BTS
solemnly operates at rated capacity;
therefore, the rated power used in the study
will account for the system's tolerance.
Auxiliary loads such as lighting used during
certain day hours (6:00 pm -6:00 am) were
factored into the hourly load profile. The
tolerance or error margin will account for the
stochastic
powering
of
measuring
instruments and computers for corrective and
preventive maintenance. The load profile of
an outdoor site is shown in Figure 1.
2.9
kW
2.85
2.8
2.75
2.7
2.65
Time of day
FIGURE 1. DC hourly load profile
8
Ghana Journal of Science, Technology and Development |8.2|
Issahaku and Kemausuor, 2022.
Economic input variables
Mobile Network Operators (MNO) and
Tower Companies lease land or rooftop of
buildings for site construction for five (5)
years with options to renew. In this study,
area or space for construction is assumed to
have been acquired and therefore not
considered economic input for the power
system. However, the land/space allocated
for a site intended to use solar PV systems
must be adequate to accommodate the
installation. Currently, the leased land area is
typically 100m2 or 144m2, which houses the
tower, shelter/cabinets, diesel generator
(DG), etc. This setup limits space for solar PV
panel installation. The system fixed capital
cost in HOMER includes the capital cost of
equipment,
installation
labour
cost,
replacement cost, operation and maintenance
(O&M) cost, transportation cost, and
additional components cost. The economic
constraints set for the simulation were; the
inflation rate of 7.9%, annual interest rate of
16%, as stated by the Bank of Ghana(Bank of
Ghana, 2020). The cost curve was taken to be
linear; thus, as component size increases, the
component's price increases, and vice versa.
A typical system life span of 25 years was
assumed for the study.
Prices of diesel generators vary greatly from
manufacturers, brands, and features. Diesel
price per liter considered for the financial
analysis was the average price from
September 2019 to January 2020, with a 10 %
adjustment for transport to the site estimated
at GH₵ 5.94 per liter, equivalent to US$
1.0925/liter at the prevailing exchange
rate(Bank of Ghana, 2020). Other diesel
prices used for the sensitivity analysis were
based on the country's diesel price
history(Statista, 2022). Table 3 shows the
cost used in the simulation of the system.
TABLE 3. Economic inputs variables for components of systems
Components
Size
Capital cost
(US$)
Replacement
cost (US$)
O&M
(US$/year)
Source
Diesel Generator
10 kW
3,000.00
3000.00
263
Flat plate
Monocrystalline Solar PV
Storage Battery SAGM
12 135
1kW
750.00
750.00
5
12 V
/200
Ah
5 kW
(48V)
339.00
300.00
5
(MANTRAC,
2022)
(HTC Ghana,
2021)
(Yeboah et al.,
2021)
867.00
800.00
-
System converter
Economic indicator – Levelized cost of energy (LCOE)
This indicator is computed as the average cost
per kWh useable electrical energy produced
by the system under study using the following
equation in HOMER (Quansah et al., 2017).
LCOE =
(2)
𝐶𝑎𝑛𝑛,𝑡𝑜𝑡−𝐶𝑏𝑜𝑖𝑙𝑒𝑟 𝐸 𝑡ℎ𝑒𝑟𝑚𝑎𝑙
𝐸𝑝𝑟𝑖𝑚,𝐴𝐶+𝐸𝑝𝑟𝑖𝑚,𝐷𝐶+𝐸𝑑𝑒𝑓+𝐸 𝑔𝑟𝑖𝑑,𝑠𝑎𝑙𝑒𝑠
(Yeboah et al.,
2021)
Where;
Cann,tot is the total annualized cost [$/yr], cboiler
is the boiler marginal cost [$/kWh], Ethermal is
the total thermal load served [kWh/yr],
Eprim,AC is the AC primary load served
[kWh/yr], Eprim,DC is the DC primary load
served [kWh/yr], Edef is the deferrable load
9
Ghana Journal of Science, Technology and Development |8.2|
served [kWh/yr], and Egrid,sales Egrid,sales is
the total grid sales [kWh/yr]. Terms that do
not apply to this study were set to zero (0) in
equation (2) by HOMER in the model.
Grid extension estimates to community
The grid extension cost in Bono region of
Ghana was estimated at US$ 10,607.3/km by
Yeboah et al. (2021) based on the study
conducted by Longe et al. (2014) for an offgrid community with mountainous terrain
called uMhlabuyalingana in South Africa of
$20,000/km for 11 kV line extension. Yeboah
et al. (2021) argued that their estimation was
lower because the site/area under study had a
good terrain without mountains. The
challenges associated with mountainous
terrain are expected to increase the extension
cost. This study adjusted the estimate of
Yeboah et al. (2021) by 10% to cater for the
difference in location and river crossing. The
resulting estimate for the 11kV was
US$11,668.03/km with an operation and
maintenance price of US$260. The Savannah
region which is the study area region, is
characterized by a low-laying landscape and
savannah vegetation.
HOMER system simulations
The HOMER software's simulation process
addresses the uncertainties associated with
renewable energy sources, load demands, and
input variables. It is achieved in three folds of
tasks:
simulation,
optimization,
and
sensitivity analysis. Firstly, it determines
whether the system is feasible and calculates
its net present cost (NPC). It considers the
system viable if it can adequately feed the
load (electrical power in this instance) and
meet any other constraints specified.
Secondly, it performs multiple simulations on
different system configurations using the
Graham algorithm. It estimates the system's
life-cycle cost as the total cost of installing
and operating the system over its lifetime.
The best possible or optimal system
configuration is the one that satisfies the user-
Issahaku and Kemausuor, 2022.
specified constraints at the lowest Total Net
Present Cost (TNPC). Finally, it assesses the
effect of uncertainties of variables beyond the
designer's control, such as interest rates,
system component cost prices, and fuel
prices, by performing several optimizations
under given assumptions to assess the extent
of changes in the designer's inputs. It executes
different combinations of these defined input
parameters in Table 3 and optimal
configuration combination with the least
TNPC determined. It also determines the
excess electricity generated by the energy
sources when the minimum output surpasses
the system's load demand and energy storage
facilities. A limitation of HOMER is that it
does not model electrical transients or other
dynamic effects, which would require much
smaller time steps.
Operating strategy of systems
The current design configuration for most
grid-connected sites is grid-battery-DG, with
the battery and DG serving as a backup power
source due to the unreliable grid supply. None
of the on-grid sites were initially designed to
run solely on the grid or grid-battery hybrid
power system.
The study considered
powering a new off-grid telecom outdoor site
on;
1. Solar PV with backup batteries as a
standalone system
2. A hybrid system comprising solar PV
and a diesel generator with backup
batteries.
3. Grid extension to the site
The telecom load requires uninterrupted
power to ensure continuous network service;
therefore, there was no deferrable load. The
standalone system uses a backup battery to
remedy the intermittent nature of the solar PV
system. Figure 2 illustrates the schematic
diagram of the power solutions simulated.
The four system configuration scenarios
considered were as follows;
1. A standalone solar PV system.
10
Ghana Journal of Science, Technology and Development |8.2|
2. A hybrid system with a cycle
charging strategy (CCS) is used. In
this dispatch strategy, the generator is
operated to serve the initial load at
full output power. The surplus
electrical power produced goes into
charging the battery bank.
3. A DG with backup batteries as a base
case for comparison.
4. Grid extension
Issahaku and Kemausuor, 2022.
TABLE 4. Sensitivity variables ranges used
for analysis
Input variables
Unit
Ranges of
sensitivity
Price of diesel
$/L
Component cost
Discount rate
Load annual growth
Solar radiation monthly
scale average
*
%
%
1.0925,
1.25
1, 0.9
16, 10
25
%
30
RESULTS AND DISCUSSIONS
FIGURE 2. Schematic diagram of the power
system configuration in HOMER.
Input variables for sensitivity cases
The Intergovernmental Panel on Climate
Change (IPCC) report showed that the trend
of solar systems costs over the last 30 years
had seen more than a 10% annual decrease;
however, it is still not competitive with
conventional power systems(IPCC, 2012).
The sensitivity analysis of solar system
components was done with a 10% decreasing
multiplier based on the IPCC report on solar
PV system components such as PV panels,
converters, and batteries. Sensitivity analysis
performed on fuel price was based on the
rising trend (Statista, 2022). It was carried out
to investigate the behaviors of the proposed
systems under uncertainties. Table 4 shows
the sensitivity ranges considered in the study.
This section presents and discusses the
study's findings in the form of tables and
figures geared toward the study's objectives.
The discussions would follow the lines of
technical and economic comparison of the
study's system scenarios regarding the
performances of the conventional diesel
generator's base system. The results capture
the system configurations' economic,
technical, and GHG emissions, standalone
PV, hybrid (PV/DG), grid extension, and DG
from HOMER.
Optimization results
HOMER results are presented in two parts;
the sensitivity cases and optimization results.
The optimization results showed that all the
systems models considered by HOMER were
feasible and capable of meeting the load
specified under all settings. The results were
presented based on each category's best and
presented the best among the categories at the
top of the list. The system with the least Net
present Cost (NPC) is the best. Figure 4
illustrates the optimization results of the
study generated by HOMER from the
simulation. A standalone solar PV system
comprising 56.3 kW solar PV, 60 pieces of
SAGM 12V 135Ah batteries having NPC of
US$ 88,176.00 at the cost of energy of US$
0.321/kWh. The choice of system to meet an
11
Ghana Journal of Science, Technology and Development |8.2|
off-grid load; thus, solar PV/battery system is
the same as in previous studies (Asuamah et
al., 2021; Longe et al., 2014). However, there
are variations in figures, for example, COE
with those studies. This variation could be
due to the cost of components and load size
with the current research. It is interesting to
note that previous studies suggested that
hybrid systems were the best to meet the load
demand of telecommunication sites, as
aforementioned in the introduction of this
work. Apart from the difference in system
type, the COE of this study is less than the
findings in the work of Quansah et al. (2017)
for a telecommunication site in Ghana. It
further suggests that decreasing solar PV and
Issahaku and Kemausuor, 2022.
rising fuel prices in the wake of COVID-19
have impacted the results of previous studies.
If this trend continues, it would make
investment in solar PV systems competitive. .
According to Ghana's Energy 2020 Energy
outlook, the average end-user tariff as of the
end of 2019 was GHp 71.6, an equivalent
prevailing rate of US$ 0.12/kWh
(Commission, 2020) for electricity supplied
from the national grid. Therefore, COE from
the standalone solar PV/battery system is still
high compared to COE for grid-connected
cell sites. It further suggests that the solar
PV/battery system is not competitive in the
grid-connected areas but suitable for remote
locations.
FIGURE 4. Optimization results generated by HOMER for scenarios being compared
Cost summary and comparison of systems
Table 5 summarizes the three proposed
configurations' simulation results for
comparative analysis with the DG system as
the base system.
12
Ghana Journal of Science, Technology and Development |8.2|
Issahaku and Kemausuor, 2022.
TABLE 5. Comparative analysis of proposed configuration
Description
Parameter
Cost of Energy (COE) (US$)
Net Present Cost (US$)
Cost Summary
Operating Cost (US$)
Initial Capital (US$)
Compare
economics
with DG as
the base case
system
Electrical
Emission
Battery
Fuel Summary
System Configurations
Hybrid (Solar
Standalone
PV & Diesel
Diesel Generator
Solar PV
Generator)
0.321
0.505
0.672
88,176.00
138,826.00
184,675.00
2,677.00
9,305.00
15,653.00
58,351.00
35,163.00
10,298.00
Present Worth (US$)
Annual worth (US$/yr)
Return on Investment (%)
Internal Rate of Return (%)
Simple Payback (year)
Generic flat plate PV (kWh/yr)
DG (kWh/yr)
Excess Electricity (kWh/yr)
Unmet load (kWh/yr)
Capacity shortage (%)
Renewable Percentage
Carbon Dioxide (kg/yr)
Carbon Monoxide (kg/yr)
Unburnt Hydrocarbons (kg/yr)
Particulate matter (kg/yr)
Sulfur Dioxide (kg/yr)
Nitrogen Oxides (kg/yr)
Autonomy (hr)
Expected lifespan (year)
Total fuel Consumed per year (L)
Average Fuel per day (L/day)
Average Fuel per hour (L/hr)
107,513.00
9,651.00
23.5
28.7
3.34
93,348
66,426
17
23.1
100
0
0
0
0
0
0
28.6
6.25
-
56,864.00 5,104.00
22.7
28.4
3.39
35,908
10,952
20,562
21.7
24.6
76.6
13,676
103
3.77
6.27
33.6
118
23.8
8.32
5235
14.3
0.598
27,536
16.4
17
24
0
26,067
197
7.18
12
64
224
8.58
1.97
9,978
27.3
1.14
13
Ghana Journal of Science, Technology and Development |8.2|
Issahaku and Kemausuor, 2022.
FIGURE 5. Cash flow comparison of the simulated systems
14
Ghana Journal of Science, Technology and Development |8.2|
Summary of economic analysis
The results summarized in Table 5 show the
feasible systems comparing their cost
summary values, economics compared with a
diesel generator as a base system, the
electrical parameters, emissions, batteries,
and fuel summary where applicable. The
comparison gives an insight into the
economics of the systems from HOMER for
decision making and the implication of
choice. Figure 5 illustrates the systems' cash
flow trend in the optimization results, which
suggest the diesel generator solution's
continuous and high operating cost. The
standalone solar PV system had the highest
initial capital, battery quantity, and operating
cost. Sustaining the site load solely on solar
PV would require more panels and batteries
to generate and store power. It has
implications on the initial capital and system
replacement cost, thereby increasing its life
cycle cost. The standalone PV system's
running cost is low because there is no
additional cost incurred in fuel purchase for
running the system. The popularity of DG in
the current sites is explained by the
attractively low initial capital, proven
technology, and stable power generation.
However, the operating cost is high, mostly
attributed to fuel purchases. The high quantity
of fuel consumed by DG has a corresponding
effect on GHG emissions. Although
technically viable, the economics of the DG
system suggests it's not the best among the
options available. The NPC and COE of DG
are about twice the cost of the standalone
solar PV system.
The study area is characterized by dust in the
dry season, which is about half the year. The
presence of dust in the atmosphere reduces
radiation reaching the panel, thereby
affecting power generation from the panels.
To assess the impact of dust on the system,
the sensitivity of a reduction in solar radiation
Issahaku and Kemausuor, 2022.
resource showed an increased COE and
TNPC as radiation reduced. The increase in
cost is from increased capacity to supply the
load demand. This information is vital in
developing a maintenance schedule for the
solar PV systems to ensure competitive
system cost, long life span, and sustainability.
Although load growth is essential in system
design consideration, the solar PV system's
modular nature addresses the challenge. It
also suggests that new sites could be designed
with solar PV power solutions.
Grid extension breakeven distance analysis
The addition to the study is the comparison of
the proposed power solutions with grid
extension to the site. The cost associated with
grid extension was compared to determine the
distance at which grid extension is better than
the isolated power solution, called the
breakeven distance. The breakeven distance,
or Electric Distance Limit (EDL), between a
standalone power solution and grid extension
was determined and summarized in Table 6 in
this investigation. This means that for an
isolated power solution to be more costeffective and efficient, the distance from the
nearest grid network must exceed the EDL.
Although the country has achieved
impressive electricity access, there are still
communities with proximity to the nearest
grid network of over ten (10) km. The
distance between the Keto community to the
Daboya, the district capital with a grid
substation, is 18 km, greater than the
breakeven distances of all the systems
considered. Furthermore, the cost of grid
connection continues to rise. In contrast, the
market's price of renewable energy sources
continues to fall, making a stronger case for
electrification of off-grid sites with
standalone solar PV systems competitive.
15
Ghana Journal of Science, Technology and Development |8.2|
Issahaku and Kemausuor, 2022.
Table 6. Electric Distance limit for grid extension to the site at Keto
Proposed system
Breakeven distance (km)
Standalone Solar PV/battery
4.51
Hybrid - Solar PV/battery/diesel generator
Diesel Generator only
8.28
11.69
Green House Gas (GHG) emissions of
systems
Combustions of fossil fuels by DG emit
harmful gases and particulate matter that
negatively affect the environment. The GHG
emission levels are shown in Table 5. In terms
of GHG emissions from the systems, the
standalone system is considered clean since
its operation does not emit GHGs. The results
summarized in Table 5 show that the
standalone system has zero emissions, as
solar PV does not emit any GHG. The hybrid
system also has a medium emission from low
fuel consumption. DG usage contributes
26,067 kg/year of Carbon dioxide from the
combustion of 9,978 L/year of diesel. These
figures represent an insignificant portion of
the MtCO2e unit of measure; however, the
numbers increase when these figures are
scaled to the total number of sites running on
diesel generators. Data on fuel-related
emissions from the Environmental Protection
Agency (EPA) shows an annual increase of
2.1% from 1990 to 2016(EPA, 2019). The
increase is attributed to fossil fuel combustion
from the country's electricity and transport
sectors. There is, therefore, the need for
conscious efforts to minimize fossil fuel use
and commit more to the use of renewables in
the
commitment
to
fight
climate
change(Abokyi et al., 2019).
Other positive impacts of the availability of
electricity to the community
Aside from the benefits derived from services
of connecting to the digital space. The
network availability in the Keto community
has other benefits for the locals. The network
signals would extend to neighboring
communities that stand to benefit and
facilitate the general wellbeing of the
inhabitants. The results also suggested
significant excess electricity from the
proposed system. The excess electricity with
appropriate arrangements with the locals
could power floodlights near the site to
support night studies for students and phone
charging.
CONCLUSION
The study found that a standalone solar
PV/battery system was the most economical
option
for
powering
an
off-grid
telecommunication site. Although the system
choice has an initial high investment cost, the
NPC is the least. The base case system has the
least initial capital cost but has the highest
TNPC, operating cost, and COE. In addition
to the economic benefits of the standalone
solar PV/battery system, it has a minimal
environmental impact on the environment as
it does not emit greenhouse gases in
operation. Therefore, there is a need for
government intervention in the form of
subsidies and waives if solar PV technology
is to achieve parity in COE.
The power solution choice is different from
previous studies, with a COE from the
solution approximately 50% less. In
comparison with the cost of grid extension to
the site, the breakeven distance was about
four times the distance to the community of
Keto in the North Gonja District, further
16
Ghana Journal of Science, Technology and Development |8.2|
making a substantial augment for renewable
energy power solutions
Renewable energy technologies should be
promoted for cell sites, in line with the
government's policies to promote renewable
energy, as in Ghana's Renewable Energy Law
and the Renewable Energy Masterplan.
Heavy dependence on fossil fuels continues
to increase humanity's carbon footprint. Solar
PV/hybrid systems will reduce the national
electric load to augment the deficit in
generating capacity even in grid-connected
areas. Therefore, there is a need to invest in
renewables to meet today's needs without
affecting the survival of future generations.
Sustainable development is achieved with a
balance of the economy, society, and
environment. The study's findings further
promote universal access to digital
connectivity and contribute to the fight
against climate change.
Limitations of study
The variation of electricity consumption with
seasons and traffic was not factored in this
study. Although the study's objectives have
been achieved by the methods employed,
there is a need for the simulation to be
conducted using intrusive load profiling to
capture the variation of electricity
consumption with varying traffic at the site.
In the long run, off-grid viability is contingent
on a variety of other issues, including the
availability of spare parts, maintenance
personnel, security of batteries, and
insurance, which were not examined in this
study.
Acknowledgements
We are most grateful to the developers of
HOMER software which aided my study and
the field Engineers of the telecommunication
companies for their support, and Mr. Asare
Baffour of Strategic Power Systems – Accra
for readily providing us with relevant
Issahaku and Kemausuor, 2022.
information on the pricing and installation
cost of main systems components.
Funding sources
This research did not receive any specific
grant from funding agencies in the public,
commercial, or not-for-profit sectors
Declaration of competing interest
The authors declare that they do not have
any competing interest
REFERENCES
Aboagye, B., Gyamfi, S., Ofosu, E. A., &
Djordjevic, S. (2021). Status of
renewable energy resources for
electricity supply in Ghana. Scientific
African,
11,
e00660.
https://doi.org/10.1016/j.sciaf.2020.e00
660
Abokyi, E., Appiah-Konadu, P., Abokyi, F.,
& Oteng-Abayie, E. F. (2019). Industrial
growth and emissions of CO2 in Ghana:
The role of financial development and
fossil fuel consumption. Energy
Reports,
5,
1339–1353.
https://doi.org/10.1016/j.egyr.2019.09.0
02
Adaramola, M. S., Quansah, D. A., AgelinChaab, M., & Paul, S. S. (2017).
Multipurpose
renewable
energy
resources based hybrid energy system
for remote community in northern
Ghana.
Sustainable
Energy
Technologies and Assessments, 22, 161–
170.
https://doi.org/10.1016/j.seta.2017.02.0
11
Alsharif, M. H., & Kim, J. (2016). Optimal
solar power system for remote
telecommunication base stations: A case
study based on the characteristics of
south Korea's solar radiation exposure.
17
Ghana Journal of Science, Technology and Development |8.2|
Sustainability (Switzerland), 8(9), 1–21.
https://doi.org/10.3390/su8090942
Alsharif, M. H., Nordin, R., & Ismail, M.
(2015). Energy optimisation of hybrid
off-grid
system
for
remote
telecommunication
base
station
deployment in Malaysia. Eurasip
Journal on Wireless Communications
and Networking, 2015(1), 1–15.
https://doi.org/10.1186/s13638-0150284-7
Anayochukwu, A. V. (2013). Optimal sizing
and application of renewable energy
sources at GSM base station site.
International Journal of Renewable
Energy Research, 3(3), 579–585.
https://doi.org/10.20508/ijrer.95440
Anayochukwu, A. V., & Ndubueze, N. A.
(2013). Potentials of optimized hybrid
system in powering off-grid macro base
transmitter station site. International
Journal of Renewable Energy Research,
3(4),
861–871.
https://doi.org/10.1234/ijrer.v3i4.885.g
6216
Anayochukwu, A. V., & Ndubueze, N. A.
(2021). The potential of standalone PV /
wind hybrid energy systems for power
supply to remote rural areas in Nigeria.
(March).
https://doi.org/10.1615/InterJEnerClean
Env.2012004922
Anayochukwu, A. V., & Nnene, E. A. (2013).
Measuring the Environmental Impact of
Power Generation at GSM Base Station
Sites. Electronic Journal of Energy &
Environment,
1(1).
https://doi.org/10.7770/ejee-v1n1art522
Ani, V. (2017). The Potential of a Mix of
Renewable ( PV / Wind ) Energy System
for an Information and Communication
Technology ( ICT ) Centre in a Rural
Environment.
(December
2013).
Issahaku and Kemausuor, 2022.
https://doi.org/10.7770/ejee-V1N3art682
Ani, V. A. (2016). Design of a Reliable
Hybrid (PV/Diesel) Power System with
Energy Storage in Batteries for Remote
Residential Home. Journal of Energy,
2016,
1–16.
https://doi.org/10.1155/2016/6278138
Asuamah, E. Y., Gyamfi, S., & Dagoumas, A.
(2021). Potential of meeting electricity
needs of off-grid community with minigrid solar systems. Scientific African,
11,
e00675.
https://doi.org/10.1016/j.sciaf.2020.e00
675
Babatunde, O. M., Denwigwe, I. H.,
Babatunde, D. E., Ayeni, A. O.,
Adedoja, T. B., & Adedoja, O. S. (2019).
Techno-economic
assessment
of
photovoltaic-diesel
generator-battery
energy system for base transceiver
stations loads in Nigeria. Cogent
Engineering,
6(1).
https://doi.org/10.1080/23311916.2019.
1684805
Bank of Ghana. (2020). Home page.
Retrieved
from
https://www.bog.gov.gh/
Bento, N. (2016). Calling for change?
Innovation, diffusion, and the energy
impacts of global mobile telephony.
Energy Research and Social Science,
21,
84–100.
https://doi.org/10.1016/j.erss.2016.06.0
16
Brew-Hammond, A. (2010). Energy access in
Africa: Challenges ahead. Energy
Policy,
38(5),
2291–2301.
https://doi.org/10.1016/j.enpol.2009.12.
016
Brown, M., & Hewitt, A. (2006). Sustainable
Energy Sources for Rural Ghana. 1–92.
Bukari, D., Kemausuor, F., Quansah, D. A.,
18
Ghana Journal of Science, Technology and Development |8.2|
& Adaramola, M. S. (2021). Towards
accelerating the deployment
of
decentralised renewable energy minigrids in Ghana : Review and analysis of
barriers. Renewable and Sustainable
Energy Reviews, 135(November 2019),
110408.
https://doi.org/10.1016/j.rser.2020.1104
08
Chris, A.-N., Haggarty, L., Shirley, M. M., &
Wallsten, S. (2002). 3G M Obile Policy :
the Case of Ghana. (November), 27.
Commission, E. (2020). 2020 Energy (
Supply and Demand ) Outlook for
Ghana.
Retrieved
from
http://cleancookstoves.org/binarydata/RESOURCE/file/000/000/83-1.pdf
Cudjoe, S. N., Azure, T., Assem, C., &
Nortey, E. N. (2013). 2010 Population
and Housing Census Northern Regional
Analytical Report. Ghana Statistical
Service, 1–135.
Cunliff, C. (2020). Beyond the Energy
Techlash: The Real Climate Impacts of
Information Technology. July 6, 2020,
(July),
1–36.
Retrieved
from
https://itif.org/publications/2020/07/06/
beyond-energy-techlash-real-climateimpacts-information-technology
ECREEE. (2015). National Renewable
Energy Action Plans ( NREAPs ) (
Ghana ). (November 2015), 59.
Energy Commission. (2018). Solar Radiation
in Ghana. Retrieved April 11, 2021,
from Energy Commission, Ghana
website:
http://energycom.gov.gh/files/Solar
Data - final(1).pdf
EPA. (2019). Ghana' s Fourth National
Greenhouse Gas Inventory Report
National Greenhouse Gas Inventory to
the United Nations Framework
Convention on Climate Change.
Issahaku and Kemausuor, 2022.
Retrieved from www.epa.gov.gh
Essandoh, E. O., Osei;, Yeboah, E., Adam;,
& Wahib, F. (2014). Prospects of wind
power
generation
in
Ghana.
International Journal of Mechanical
Engineering and Technology, 3(2), 24–
35.
Gilman, P., & Lilienthal, P. (2006).
Micropower System Modeling with
HOMER. In G. S. Felix A Farret (Ed.),
Integration of Alternative Sources of
Energy (pp. 379–418). John Wiley and
Sons, Inc.
GSMA Green Power for Mobile. (2012).
Powering Telecoms: West African
Market Analysis, Sizing the potential for
Green Telecoms in Nigeria and Ghana.
In International Finance Corporation.
https://doi.org/10.1063/1.5018969
Gyamfi, S., Modjinou, M., & Djordjevic, S.
(2015). Improving electricity supply
security in Ghana - The potential of
renewable energy. Renewable and
Sustainable Energy Reviews, 43, 1035–
1045.
https://doi.org/10.1016/j.rser.2014.11.1
02
Haggarty, L., Shirley, M. M., & Wallsten, S.
J. (2005). Telecommunications Reform
in Ghana. SSRN Electronic Journal,
(March).
https://doi.org/10.2139/ssrn.373960
Halabi, L. M., Mekhilef, S., Olatomiwa, L., &
Hazelton, J. (2017). Performance
analysis of hybrid PV/diesel/battery
system using HOMER: A case study
Sabah, Malaysia. Energy Conversion
and Management, 144, 322–339.
https://doi.org/10.1016/j.enconman.201
7.04.070
HOMER Energies. (2021). HOMER - Hybrid
Renewable and Distributed Generation
System Design Software. Retrieved
19
Ghana Journal of Science, Technology and Development |8.2|
April 11, 2021, from HOMER Energies
website:
https://www.homerenergy.com/
Höök, M., & Tang, X. (2013). Depletion of
fossil fuels and anthropogenic climate
change-A review. Energy Policy, 52,
797–809.
https://doi.org/10.1016/j.enpol.2012.10.
046
Hossain, M., Mekhilef, S., & Olatomiwa, L.
(2017). Performance evaluation of a
standalone
PV-wind-diesel-battery
hybrid system feasible for a large resort
center in South China Sea, Malaysia.
Sustainable Cities and Society, 28, 358–
366.
https://doi.org/10.1016/j.scs.2016.10.00
8
HTC Ghana. (2021). Solar Panels: Save
Money And Let The Sun Pay Your Bills.
Retrieved February 13, 2022, from Web
page website: https://htcghana.com/buysolar-panels-to-save-money-on-yourbills/
International Energy Agency. (2020). Access
to electricity – SDG7: Data and
Projections – Analysis. In IEA Flagship report. Paris. Retrieved from
https://www.iea.org/reports/sdg7-dataand-projections/access-to-electricity
International Telecommunication Union.
(1999). Executive Summary: Challenges
to
the
Network:
Internet
for
Development 1999. Retrieved April 11,
2021, from ITU News website:
https://www.itu.int/ITUD/ict/publications/inet/1999/ExeSum.ht
ml
International Telecommunication Union.
(2020). Measuring digital development
Facts and figures. In ITU Publications.
IPCC. (2012). Renewable Energy Sources
and Climate Chanage mitigation:
Issahaku and Kemausuor, 2022.
Special Report of Intergovernmental
Panel on Climate change. New York.
Islam, M. S., Akhter, R., & Rahman, M. A.
(2018). A thorough investigation on
hybrid application of biomass gasifier
and PV resources to meet energy needs
for a northern rural off-grid region of
Bangladesh: A potential solution to
replicate in rural off-grid areas or not?
Energy,
145,
338–355.
https://doi.org/10.1016/j.energy.2017.1
2.125
Johnsson, F., Kjärstad, J., & Rootzén, J.
(2019). The threat to climate change
mitigation posed by the abundance of
fossil fuels. Climate Policy, 19(2), 258–
274.
https://doi.org/10.1080/14693062.2018.
1483885
Kalba, K. A. S. (2008). The Adoption of
Mobile Phones in Emerging Markets:
Global Diffusion and the Rural
Challenge. International Journal of
Communication, 2(0), 31.
Kauffman, R. J., & Techatassanasoontorn, A.
A. (2005). International diffusion of
digital mobile technology: A coupledhazard
state-based
approach.
Information
Technology
and
Management,
6(2–3),
253–292.
https://doi.org/10.1007/s10799-0055882-3
Kemausuor, F., & Ackom, E. (2017). Toward
universal electrification in Ghana. Wiley
Interdisciplinary Reviews: Energy and
Environment,
6(1),
1–14.
https://doi.org/10.1002/wene.225
Kumi, E. N. (2017a). Challenges and
Opportunities CGD Policy Paper 109
September 2017. Center for Global
Development, (September). Retrieved
from
www.energycom.gov.gh/planning/datacenter/energy-outlook-for20
Ghana Journal of Science, Technology and Development |8.2|
ghana?download=76:energy-outlookfor-ghana-2018.pdf
Kumi, E. N. (2017b). The Electricity
Situation in Ghana: Challenges and
Opportunities. Center for Global
Development, (September). Retrieved
from www.cgdev.orgwww.cgdev.org
Longe, O. M., Ouahada, K., Ferreira, H. C.,
& Chinnappen, S. (2014). Renewable
Energy Sources microgrid design for
rural area in South Africa. 2014 IEEE
PES
Innovative
Smart
Grid
Technologies Conference, ISGT 2014,
(February).
https://doi.org/10.1109/ISGT.2014.681
6378
Lu, W. C. (2018). The impacts of information
and communication technology, energy
consumption, financial development,
and economic growth on carbon dioxide
emissions in 12 Asian countries.
Mitigation and Adaptation Strategies for
Global Change, 23(8), 1351–1365.
https://doi.org/10.1007/s11027-0189787-y
MANTRAC.
(2022).
MANTRAC
GENERATORS
POWERED
BY
CAT® – Mantrac Ghana. Retrieved
February 13, 2022, from Web page
website:
https://shop.mantracghana.com/collecti
ons/power
Martins, D. B. (2020). More urgent than ever:
Universal connectivity to bring 3.7
billion people online - My ITU.
Retrieved April 11, 2021, from ITU
News
website:
https://www.itu.int/en/myitu/News/202
0/12/11/08/36/Universal-connectivityurgency-billions-offline-DoreenBogdan-Martin
Ministry of Energy. (n.d.). Sector Overview |
Ministry of Energy. Retrieved April 11,
2021,
from
2019
website:
Issahaku and Kemausuor, 2022.
https://www.energymin.gov.gh/sectoroverview
Ministry of Energy, E. C. (2019). Ghana
Renewable Energy Master Plan. Ghana
Renewable Energy Master Plan.
National Communication Authority- Ghana.
(2018). Masts & Towers » National
Communications Authority. Retrieved
April 11, 2021, from National
Communication Authority website:
https://www.nca.org.gh/industry-data2/masts-and-towers/
National Communication Authority- Ghana.
(2020). Telecom Voice Subscription »
National Communications Authority.
Retrieved April 11, 2021, from
https://nca.org.gh/industry-data2/market-share-statistics-2/telecomvoice/
Nuru, J. T., Rhoades, J. L., & Gruber, J. S.
(2021). The socio-technical barriers and
strategies for overcoming the barriers to
deploying solar mini-grids in rural
islands:
Evidence
from
Ghana.
Technology in Society, 65(April),
101586.
https://doi.org/10.1016/j.techsoc.2021.1
01586
Odoi-Yorke, F., & Woenagnon, A. (2021).
Techno-economic assessment of solar
PV/fuel cell hybrid power system for
telecom base stations in Ghana. Cogent
Engineering,
8(1).
https://doi.org/10.1080/23311916.2021.
1911285
Olatomiwa, L., Blanchard, R., Mekhilef, S.,
& Akinyele, D. (2018). Hybrid
renewable energy supply for rural
healthcare facilities: An approach to
quality healthcare delivery. Sustainable
Energy Technologies and Assessments,
30(February),
121–138.
https://doi.org/10.1016/j.seta.2018.09.0
07
21
Ghana Journal of Science, Technology and Development |8.2|
Olatomiwa, L., & Mekhilef, S. (2015).
Techno-economic feasibility of hybrid
renewable energy system for rural health
centre (RHC): The wayward for quality
health delivery. 2015 IEEE Conference
on Energy Conversion, CENCON 2015,
504–509.
https://doi.org/10.1109/CENCON.2015.
7409596
Olatomiwa, L., Mekhilef, S., Huda, A. S. N.,
& Sanusi, K. (2015). Techno-economic
analysis of hybrid PV–diesel–battery
and PV–wind–diesel–battery power
systems for mobile BTS: The way
forward for rural development. Energy
Science and Engineering, 3(4), 271–
285. https://doi.org/10.1002/ese3.71
Opoku, R., Adjei, E. A., Obeng, G. Y.,
Severi, L., & Bawa, A.-R. (2020).
Electricity
Access,
Community
Healthcare Service Delivery, and Rural
Development Nexus: Analysis of 3
Solar Electrified CHPS in Off-Grid
Communities in Ghana. Journal of
Energy,
2020,
1–10.
https://doi.org/10.1155/2020/9702505
Osei-Owusu, A. (2015). The Analysis of the
Ghana
Telecom
Industry.
26th
European Regional Conference of the
International
Telecommunications
Society (ITS): "What Next for European
Telecommunications?", Madrid, Spain,
24th-27th June, 2015. Madrid, Spain:
International
Telecommunication
Society.
Issahaku and Kemausuor, 2022.
Higher Education for the Future, 8(1),
133–141.
https://doi.org/10.1177/2347631120983
481
Quansah, D. A., Woangbah, S. K., Anto, E.
K., Akowuah, E. K., & Adaramola, M.
S. (2017). Techno-economics of solar
pv-diesel hybrid power systems for offgrid outdoor base transceiver stations in
Ghana. International Journal of Energy
for a Clean Environment, 18(1), 61–78.
https://doi.org/10.1615/InterJEnerClean
Env.2017019537
Sambuli, N. (2016). Challenges and
opportunities for advancing Internet
access in developing countries while
upholding net neutrality. Journal of
Cyber
Policy,
1(1),
61–74.
https://doi.org/10.1080/23738871.2016.
1165715
Shahzad, A., Hassan, R., Aremu, A. Y.,
Hussain, A., & Lodhi, R. N. (2020).
Effects of COVID-19 in E-learning on
higher education institution students: the
group comparison between male and
female.
Quality
and
Quantity,
(0123456789).
https://doi.org/10.1007/s11135-02001028-z
Solargis. (n.d.). Solar resource maps and GIS
data for 200+ countries | Solargis.
Retrieved April 11, 2021, from
https://solargis.com/maps-and-gisdata/download/ghana
Osei-Owusu, A., Haggarty, L., Shirley, M.
M., Wallsten, S. J., Chris, A.-N.,
Haggarty, L., … Wallsten, S. J. (2002).
3G M Obile P Olicy : the Case of Ghana.
SSRN Electronic Journal, (November),
27. https://doi.org/10.2139/ssrn.373960
Statista. (2022). Ghana: weekly diesel fuel
prices 2020-2022 trend. Retrieved
February 13, 2022, from Web page
website:
https://www.statista.com/statistics/1200
092/weekly-diesel-oil-prices-in-ghana/
Pokhrel, S., & Chhetri, R. (2021). A
Literature Review on Impact of COVID19 Pandemic on Teaching and Learning.
Styszko, K., Jaszczur, M., Teneta, J., Hassan,
Q., Burzyńska, P., Marcinek, E., …
Samek, L. (2019). An analysis of the
dust deposition on solar photovoltaic
22
Ghana Journal of Science, Technology and Development |8.2|
modules. Environmental Science and
Pollution Research, 26(9), 8393–8401.
https://doi.org/10.1007/s11356-0181847-z
Tchao, E. T., Agyekum, K. A. P., & Diawuo,
K.
(2017).
Techno-Economic
Evaluation of Power Systems for offGrid Telecommunications Infrastructure
in Remote Locations in Ghana.
Communications
on
Applied
Electronics,
7(7),
22–27.
https://doi.org/10.5120/cae2017652694
Issahaku and Kemausuor, 2022.
telecommunications
system
ztetechnologies. Retrieved April 11,
2021,
from
https://www.zte.com.cn/global/about/m
agazine/ztetechnologies/2003/11/en_318/161244.h
tml
Tebepah, E. (2015). The Cost of
Telecommunications
Evolution in
Nigeria.
Journal
of
Energy
Technologies and Policy, 5(10), 17–26.
UCLG. (2020). Digital Technologies and the
COVID-19 pandemic. In Live Learning
Experience: Beyond the immediate
response to the outbreak of COVID-19.
USAID. (2020). Power Africa in Ghana Power Africa, U.S. Agency for
International Development. Retrieved
April 11, 2021, from USAID website:
https://www.usaid.gov/powerafrica/gha
na
Williams, L. O. (2002). Fossil fuels. An End
to
Global
Warming,
1–31.
https://doi.org/10.1016/b978008044045-3/50007-4
World Bank. (2019). Access to electricity (%
of population) - Ghana, Data. Retrieved
April
11,
2021,
from
https://data.worldbank.org/indicator/EG
.ELC.ACCS.ZS?locations=GH
Wuebbles, D. J., & Jain, A. K. (2001).
Concerns about climate change and the
role of fossil fuel use. Fuel Processing
Technology,
71(1–3),
99–119.
https://doi.org/10.1016/S03783820(01)00139-4
ZTE Corporation. (2003). Development of
power
supply
for
mobile
23