energies
Article
Investigation of the Effect of Winding Clamping
Structure on Frequency Response Signature of
11 kV Distribution Transformer
Avinash Srikanta Murthy 1 , Norhafiz Azis 1,2, *, Salem Al-Ameri 3 ID ,
Mohd Fairouz Mohd Yousof 3, *, Jasronita Jasni 1 and Mohd Aizam Talib 4
1
2
3
4
*
Centre of Electromagnetics and Lightning Protection Research (CELP), Department of Electrical and
Electronics Engineering, Faculty of Engineering, Universiti Putra Malaysia, UPM Serdang,
Selangor 43400, Malaysia; avinuday.asm@gmail.com (A.S.M.); jas@upm.edu.my (J.J.)
Institute of Advanced Technology (ITMA), Department of Electrical and Electronics Engineering,
Faculty of Engineering, Universiti Putra Malaysia, UPM Serdang, Selangor 43400, Malaysia
Faculty of Electrical and Electronics Engineering, Universiti Tun Hussein Onn Malaysia, Parit Raja,
Johor 86400, Malaysia; mgammal10@gmail.com
TNB Research, Kajang, Selangor 43000, Malaysia; aizam.talib@tnb.com.my
Correspondence: norhafiz@upm.edu.my (N.A.); fairouz@uthm.edu.my (M.F.M.Y.);
Tel.: +60-3-8946-4373 (N.A.); Tel.: +60-7-453-8334 (M.F.M.Y.)
Received: 16 July 2018; Accepted: 6 August 2018; Published: 2 September 2018
Abstract: This paper presents an investigation on the sensitivity of frequency response of a 500 kVA,
11/0.433 kV distribution transformer with and without the presence of a winding clamping structure.
Frequency response analysis (FRA) measurements of multiple test configurations were carried
out with and without the presence of a winding clamping structure. Statistical analyses based on
Pearson’s correlation coefficient (PCC), Spearman’s correlation coefficient (SCC), Kendall’s correlation
coefficient (KCC), cross-correlation coefficient (CCF), root mean square error (RMSE), absolute sum of
logarithmic error (ASLE), hypothesis test (F-test) and relative factor (RF) were applied to determine
the effect of the winding clamping structure. It was found that the removal of the winding clamping
structure has an impact on the frequency response signature at the frequency less than 2 kHz during
offline measurement. It was found that ASLE and F-test are suitable methods that can be used to
indicate the variation of frequency response caused by clamping structure removal of the distribution
transformer under study.
Keywords: frequency response analysis (FRA); distribution transformer; winding clamping structure;
statistical analysis
1. Introduction
Frequency response analysis (FRA) is a common non-destructive testing method used by utilities
to monitor the mechanical integrity of transformer windings [1]. FRA is often used to diagnose various
types of windings issues such as winding deformation, displacement, buckling, tilting, short circuit of
turns, clamping structure looseness and core movement [2]. FRA measurement is sensitive towards
mechanical changes in the winding. Several statistical and artificial intelligence (AI) techniques
have been proposed for interpretation of mechanical changes in transformer windings based on
FRA. Statistical techniques such as correlation coefficient (CC), absolute sum of logarithmic error
(ASLE), minimum-maximum ratio (MM) and absolute average difference (DABS) have been proposed
for the interpretation purpose in [3–9]. The Pearson’s correlation coefficient (PCC), Spearman’s
correlation coefficient (SCC) and Kendall’s correlation coefficient (KCC) are compared in [10–12] using
Energies 2018, 11, 2307; doi:10.3390/en11092307
www.mdpi.com/journal/energies
Energies 2018, 11, 2307
2 of 13
distributed dataset variables to distinguish the correlation characteristics. Expert techniques such as
data mining and artificial neural network (ANN) have also been proposed for monitoring the condition
of transformer windings [13]. In addition, evidential reasoning (ER) has been proposed to interpret the
failure in clamping [14].
Previously, it was shown that movement of clamping structure can lead to the variation of the
frequency response [15–18]. The clamping structure is used in the transformer for the stabilization of
the winding assembly on the transformer core. In addition, it can also reduce the vibrations caused
by electro-dynamic forces that exist during a transformer’s operations [19]. The effect of clamping
is normally represented by an increment of shunt capacitance in the FRA equivalent circuit [17,20].
End-to-end open circuit and short circuit tests are recommended by IEEE Std C57.149-2012 [21] for
FRA measurement of the transformer winding. A few studies have analyzed that looseness or breaking
of the clamping structure can lead to mechanical changes in the windings [22–25]. The effects due to
clamping faults are simulated based on lumped circuit model and the shunt conductance is varied
for both end-to-end open circuit and short-circuit tests in order to analyze the degree of clamping
faults [26].
This study aims to investigate the effect of clamping on the frequency response signature of a
distribution transformer. The frequency responses of the transformer winding based on multiple test
configurations with and without clamping are measured and analyzed based on different types of
statistical methods.
2. Methodology
2.1. Experiment Setup
The transformer under study was a 500 kVA, 11/0.433 kV distribution transformer as shown
in Figure 1. The vector type of the transformer is Delta (∆)–Wye (Y)–11. The tank was removed
before the FRA measurement was carried out. Figure 1 shows the images of the transformer with and
without the clamping structure. The transformer winding with the clamping structure can be seen
in Figure 1a,b. In this study, only the top clamping structure was removed as shown in Figure 1c,d.
Other elements remained unchanged and no other components had been loosened. The motivation
of the study was not to simulate the damage on the clamping structure but to reduce or loosen the
clamping pressure on the winding and core which can represent the condition of aged transformers.
Although the winding and core clamping pressure has been loosened, a transformer may continue
to operate normally. However, it is now highly vulnerable to radial and axial forces from large fault
current which may physically damage the winding.
According to CIGRE WG A2/26 [19], IEEE Std C57.149-2012 [21] and IEC 60076-18 [27], there
are 4 test connections for FRA measurement. In this study, both end-to-end open circuit and short
circuit tests were conducted according to IEEE Std C57.149-2012 [21]. However, the capacitive and
inductive inter-winding tests were not carried out in this study. The FRA measurement was carried out
by Omicron FRANEO 800 for both high-voltage (HV) and low-voltage (LV) windings in the frequency
range from 20 Hz to 2 MHz. The test configurations between the transformer and FRA analyzer for
end-to-end open circuit test on HV and LV windings are shown in Figure 2a,b. Under end-to-end open
circuit test, magnetizing inductance of the core has an effect on the frequency response [28–31]. On the
other hand, under an end-to-end short circuit test, the effect of the mutual coupling between HV and LV
windings is neutralized for frequency below 2 kHz as shown in Figure 2c. For this reason, the response
at low-frequency range would be only influenced by the winding inductance, and therefore the FRA
plot of the end-to-end short circuit test was expected to be similar for both the with and without
clamping structure. The end-to-end open circuit response of phase R-Y HV winding was measured by
injection of a 10 V AC input signal at different frequencies (20 Hz to 2 MHz) at terminal R through
source cable. The response cable measured the output signal at terminal Y as shown in Figure 2a.
The other terminals were left open. The same approach was carried out for end-to-end open circuit LV
Energies 2018, 11, 2307
3 of 13
winding with the source and reference cables connected to the r terminal for measurement of the r
phase while the response cable was connected to the neutral terminal as shown in Figure 2b. For an
end-to-end short circuit test of the HV winding, the same connection as in the end-to-end open circuit
test was applied except for LV winding terminals, which were short-circuited as shown in Figure 2c.
The FRA analyzer used in this study can be seen in Figure 2d.
(a)
(b)
(c)
(d)
Figure 1. 500 kVA, 11/0.433 kV distribution transformer: (a) with top clamping—front view; (b) with
top clamping—side view; (c) without top clamping—front view; (d) without top clamping—side view.
(a)
(b)
(c)
(d)
Figure 2. Frequency response analysis (FRA) measurement configurations: (a) end-to-end open circuit
high-voltage (HV) winding; (b) end-to-end open circuit low-voltage (LV) winding; (c) end-to-end short
circuit HV; (d) FRA analyzer.
Energies 2018, 11, 2307
4 of 13
2.2. Statistical Analysis
Statistical methods such as Pearson’s/Spearman’s/Kendall’s tau/cross correlation coefficients,
relative factor (RF), absolute sum of logarithmic error (ASLE), root mean square error (RMSE),
hypothesis test (F-test) were used for interpretation of the changes observed in the winding structure
before and after removal of the clamping structure. These methods were proposed by various standards
such as Chinese standard DL/T 911, CIGRE WG A2.26, and IEEE Std C59.149-2012 [18,19,21]. To use
the statistical methods, the frequency range of the response needs to be divided into three frequency
bands: low, medium and high. The frequency range of each band considered in this study was based
on measured FRA plots. On the other hand, the RF method in the Chinese standard DL/T 911 used a
predefined frequency band.
2.2.1. Pearson’s Correlation Coefficient (PCC)
The Pearson’s correlation coefficient (PCC) can be used to identify the linear potential association
between two continuous data variables [32]. It is defined as the ratio between two set of data variables
covariance (σx,y ) and product of its individual standard deviations (ρ). PCC can be obtained based on
Equation (1):
n ∑in=1 [ xi ·yi ] − ∑in=1 xi · ∑in=1 yi
(1)
PCC = rh
ih
i,
2
2
n
n
n
n
2
2
n ∑ i =1 x i − ( ∑ i =1 x i ) · n ∑ i =1 y i − ( ∑ i =1 y i )
where n is the total points of the dataset variables and xi and yi are the i-th value of two dataset
variables x and y. The range of CC can be from −1 to +1. If CC is −1 or +1, a good positive or negative
correlation between two data variables is obtained. If the value of CC is 0, no linear correlation between
the data variables is found.
2.2.2. Spearman’s Correlation Coefficient (SCC)
The Spearman’s correlation coefficient (SCC), rs computes the correlation between two ranked
variables which is obtained from PCC [33,34]. The calculation can be computed by Equation (2):
∑in=1 ( rank( xi ) − rank( x ) × rank(yi ) − rank(y) )
rs = rh
i
h
i,
2
2
n
n
∑i=1 (rank( xi ) − rank( x )) × ∑i=1 (rank(yi ) − rank(y))
(2)
where rank(xi ) and rank(yi ) are the ranks of the selected sample. SCC can be from −1 to +1 which
indicates the correlation of the absolute value of rs . The positive and negative sign indicate the
direction of the variables either associated to x or y. If rs is 0 or near to 0, there is no correlation, or the
correlation is weak between the two datasets. SCC can be 0, if there is no monotonic relationship
between two datasets, similar to PCC. However, SCC can still be 1 if the two datasets are non-linear
but monotonically related, unlike in PCC [10].
2.2.3. Kendall’s Tau Correlation Coefficient (KCC)
The Kendall’s tau correlation coefficient (KCC) is used to compute the correlation between two
variables which have independent intervals [10–12]. KCC is denoted by τ and is given by Equation (3):
τ=
1,
where sgn xi − x j =
0,
−1,
∑in=1 ∑nj=1 sgn Xi − X j × sgn Yi − Yj
n ( n − 1)
,
1,
i f Xi − X j > 0
0,
i f Xi − X j = 0 ; and sgn yi − y j =
−1,
i f ( Xi − X ) < 0
(3)
i f (Yi − Y ) > 0
i f (Yi − Y ) = 0 .
i f Yi − Yj < 0
Energies 2018, 11, 2307
5 of 13
The range of KCC correlation coefficients can be between −1 to +1. τ indicates the strength of
correlation between two datasets.
2.2.4. Cross-Correlation Coefficient (CCF)
The cross-correlation coefficient (CCF) [31] computes the correlations between two datasets to
determine the dependency between actual and predicted dataset variables. CCF can be in the range
−1 to +1. CCF will be +1 for positive correlation, 0 for no correlation, and −1 for negative correlation.
CCF is given by Equation (4):
∑in=1 Xi − X × Yi − Y
CCF =
2
2 ,
∑in Xi − X × ∑in Yi − Y
(4)
where X and Y are the two dataset variables.
2.2.5. Root Mean Square Error (RMSE)
It is defined as the standard deviation (SD) of the residual errors which is the measure of the
differences between regression data points. RMSE should be 1 if the 2 dataset variables have a good
correlation. RMSE can be determined based on Equation (5):
RMSE =
s
2
∑iN=1 ( X (i ) − Y (i ))
,
N−1
(5)
where N is the total number of points in two dataset variables and X(i) and Y(i) are the i-th value of the
two dataset variables X and Y.
2.2.6. Absolute Sum of Logarithmic Error (ASLE)
ASLE compares two dataset variables in logarithmic scale which includes the property of mean
square error (MSE). ASLE can be determined based on Equation (6). The ASLE output should be close
to zero if two dataset variables are similar:
ASLE( X,Y ) =
∑iN=1 |20log10 Yi − 20log10 Xi |
,
N
(6)
where Xi and Yi are the i-th value of the two dataset variables x and y.
2.2.7. F-Test
F-test is normally used to compare the SD of two dataset variables. The F-test performs analysis
of variance (ANOVA) to compare the mean of two datasets. A statistical hypothesis is taken into
consideration while performing the F-test [5]. Null hypothesis (H0) is the case when the variances of
the two dataset samples correlate and will be one. Otherwise, alternate hypothesis (H1) is given and
the variances will be close to either 1 or 0. The output depends on the specific confidence level of either
95% or 99% set by the user. The hypothesis used for the F-test is given by Equations (7) and (8):
null hypothesis: σ12 = σ22 ,
(7)
alternate hypothesis: σ12 6= σ22 .
(8)
The ratio of variances of two dataset variables, FValue is given by Equation (9):
FValue =
σ12
,
σ22
(9)
Energies 2018, 11, 2307
6 of 13
where H0 is not considered when Fvalue < Fn1 −1,n2 −1,α/2 or Fvalue > Fn1 −1,n2 −1,α/2 , α is the confidence
level, and n1 and n2 are the total points in the dataset variables.
2.2.8. Relative Factor (RF)
Relative factor method is given in Chinese standard DL/T 911 [18]. Based on the computed relative
factor, the condition of the transformer can be classified according to Table 1 [33,35]. The relative factor
Rxy of the two data variables X and Y can be calculated based on Equation (10):
R xy =
(
10, 1 − LR XY < 10−10
−log10 (1 − LR XY ), others
.
(10)
Table 1. The relationship between the winding deformation degree and relative factor.
Degree of Winding Deformation
Relative Factors, Rxy
Severe Deformation
Obvious Deformation
Slight Deformation
Normal Winding
RLF < 0.6
1.0 > RLF ≥ 0.6 or RMF < 0.6
2.0 > RLF ≥ 1.0 or 0.6 ≤ RMF < 1.0
RLF ≥ 2.0, RMF ≥ 1.0 and RHF ≥ 0.6
The normalization covariance factor LRXY , can be carried out based on Equations (11)–(14):
LR XY = √
CXY
1
=
N
N −1
∑
k =0
"
1
X (k) −
N
N −1
∑
k =0
"
1
DX =
N
N −1
1
DY =
N
N −1
∑
k =0
∑
k =0
CXY
,
DX DY
X (k)
#2
×
1
X (k) −
N
"
1
Y (k) −
N
"
(11)
1
Y (k) −
N
N −1
∑
X (k)
#2
Y (k)
#2
k =0
N −1
∑
k =0
,
N −1
∑
k =0
Y (k)
#2
,
(12)
(13)
(14)
where X(k) and Y(k) are the kth values of two data variables X and Y.
The frequency bands of RF method at low (RLF ), medium (RMF ) and high frequencies (RHF ) are
(1 kHz–100 kHz), (100 kHz–600 kHz) and (600 kHz–1000 kHz) respectively.
3. Frequency Response Plot
3.1. End-to-End Open Circuit Test
The frequency response plot at terminals R-Y, Y-B, and B-R of a HV winding based on an
end-to-end open circuit test connection can be seen in Figure 3a–c. Since the HV winding was
delta connected, the input voltage was applied at terminal phase R and measured at terminal phase
Y. Similarly, measurements were taken at terminals Y-B and B-R. At terminals R-Y, the frequency
response plot magnitude of without clamping structure is slightly lower than with clamping structure
at frequency less than 2 kHz as shown in Figure 3a. At terminals Y-B, the frequency response plot
magnitude of without the clamping structure is lower than with clamping structure at frequency
around 2 kHz as shown in Figure 3b. The same pattern as terminals R-Y is observed at terminals B-R
as shown in Figure 3c.
Energies 2018, 11, 2307
7 of 13
(a)
Figure 3. End-to-end open circuit test on HV winding. Measurement at terminals: (a) R-Y for phase R;
(b) Y-B for phase Y; (c) B-R for phase B.
The frequency response plot of without clamping structure is almost the same as with clamping
structure under an LV end-to-end open circuit test as shown in Figure 4a–c. There is a slight deviation of
response between without and with clamping structures at a frequency range between 150 Hz–1.5 kHz
as shown in Figure 4a. At the same frequency range, the magnitude of that without a clamping
structure is lower than that with a clamping structure, as shown in Figure 4b. The same pattern
Energies 2018, 11, 2307
8 of 13
as phase r is observed for phase b, as shown in Figure 4c. In addition, there is a slight deviation
of frequency response between without and with clamping structures at a higher frequency range
between 1 MHz and 2 MHz.
Figure 4. End-to-end open circuit test on the LV winding. Measurement at terminals (a) r-n for phase r;
(b) y-n for phase y; (c) b-n for phase b.
Energies 2018, 11, 2307
9 of 13
3.2. End-to-End Short Circuit Test
The frequency response of the equipment without clamping structure matches quite well that
with clamping structure for HV winding end-to-end short circuit tests at terminals R-Y as shown in
Figure 5. Under the end-to-end short circuit test, the effect of mutual coupling between HV and LV
windings is neutralized due to the fact that the LV terminal is short-circuited which leads to the same
frequency responses between without and with clamping structures. The FRA responses for Y-B and
B-Y phases are not shown, since both would be similar to R-Y.
Figure 5. End-to-end short circuit test on HV winding. Measurement at terminals R-Y for phase R.
4. Statistical Analysis
The FRA response obtained with a clamping structure is considered as the fingerprint response or
reference. The frequency responses of the 3 phases for both the LV and HV windings slightly deviate
from its fingerprint responses at a low frequency band less than 2 kHz. One of the reasons for these
variations is due to the difference in flux for the middle and side phases of the transformer [9]. The effect
of the clamping structure is normally detected at the frequency region less than 20 kHz [17,36,37].
Statistical tests such as the PCC, SCC, KCC, CCF, RMSE, ASLE, F-test and RF are conducted to
examine the extent of the variations. For this purpose, only outputs from the end-to-end open circuit
test is taken since there is no deviation of the frequency response between without and with clamping
structure for the end-to-end short circuit test. The frequency range and sub band under study is
based on measured FRA plots except for the RF method. The outputs of the PCC, SCC, KCC, CCF,
RMSE, ASLE, F-test and RF are given in Tables 2–4. For PCC, SCC and KCC, the suggested coefficient
should be higher than 0.98 for a normal condition [36]. For CCF, the normal condition is defined based
on a coefficient higher than 0.95 where values between 0.95 and 0.7 indicate slight deformation in
the winding [31]. RMSE defines ranges between 0–3 as the normal condition [38]. The threshold for
normal condition ASLE was proposed at a value less than 0.6 [36]. The F-test should be 1 for a normal
condition and 0 for certain deformations of the winding structure [5].
Table 2. Comparison of statistical methods for frequency response interpretation of HV winding.
Test Configuration
Frequency Range
PCC
SCC
KCC
CCF
RMSE
ASLE
F-Test
HV R-Y
20 Hz–2 kHz
2 kHz–400 kHz
400 kHz–2 MHz
0.9981
0.9999
0.9872
0.9977
0.9998
0.9905
0.9841
0.9965
0.9312
0.9982
0.9994
0.9766
0.4816
0.1722
1.4203
1.6715
0.7407
0.8155
0.6742
0.9397
0.7324
HV Y-B
20 Hz–1.5 kHz
1.5 kHz–450 kHz
450 kHz–2 MHz
0.9971
0.9986
0.9766
0.9990
0.9999
0.9841
0.9907
0.9971
0.9158
0.997
0.9985
0.9766
0.5308
0.7856
1.7513
2.2633
1.1532
1.213
0.0072
0.5466
0.3021
HV B-R
20 Hz–2 kHz
2 kHz–450 kHz
450 kHz–2 MHz
0.9982
0.9998
0.9345
0.9982
0.9998
0.9591
0.9865
0.9971
0.8666
0.9982
0.9998
0.9344
0.4599
0.2735
2.7098
1.3665
0.6346
0.9446
0.3748
0.9014
0.4024
Energies 2018, 11, 2307
10 of 13
Table 3. Comparison of statistical methods for frequency response interpretation of LV winding.
Test Configuration
Frequency Range
20 Hz–1.5 kHz
0.9701
0.9931
0.9679
0.9707
0.3377
0.7739
0.0000
LV r-n
1.5 kHz–1 MHz
0.9999
0.9997
0.9897
0.9999
0.1470
0.3384
0.6274
1 MHz–2 MHz
0.9986
0.9968
0.9656
0.9986
0.2971
0.3791
0.5096
20 Hz–1.5 kHz
0.9858
0.9573
0.8848
0.9863
0.1954
1.3230
0.0002
1.5 kHz–1 MHz
0.9995
0.9987
0.9783
0.9995
0.2945
0.5848
0.5205
1 MHz–2 MHz
0.9976
0.9954
0.9613
0.9976
0.3419
0.6492
0.1454
LV y-n
LV b-n
PCC
SCC
KCC
CCF
RMSE
ASLE
F-Test
20 Hz–1.5 kHz
0.9827
0.9919
0.9656
0.9829
0.2533
0.6625
0.0029
1.5 kHz–1 MHz
0.9992
0.9998
0.9915
0.9992
0.3747
0.3748
0.2105
1 MHz–2 MHz
0.9865
0.9906
0.9358
0.9865
0.9179
0.5742
0.0426
Table 4. Relative factors at different frequency regions/test configurations and the suggested
winding condition.
Test Configuration
HV R-Y
HV Y-B
HV B-R
LV r-n
LV y-n
LV b-n
Relative Factor, Rxy
LF
MF
HF
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
Suggested Winding Condition
Normal
The coefficients of PCC and SCC indicate that there is no effect of clamping structure removal for
the majority of the frequency ranges, as shown in Tables 2 and 3. Only HV B-R (450 kHz–2 MHz), LV r-n
(20 Hz–1.5 kHz) and LV y-n (20 Hz–1.5 kHz) indicate that there is a slight deviation in the winding. KCC
shows that a slight deviation in the winding exists at high frequency range (450 kHz–2 MHz). For CCF,
most of the values show no deviation in the winding except for HV B-R (450 kHz–2 MHz). RMSE
indicates the normal condition for both HV and LV windings. It is known that RMSE underestimates
the frequency variations especially in the low frequency regions [39]. Loose connections in the
measuring instrument can contribute to the variation of the frequency responses [8]. In addition,
noises due to the connection cables and difference in grounding systems can also affect the frequency
responses [4,21]. These factors could be the possible reasons for the frequency response variations
computed by PCC, SCC, KCC and CCF.
Considering these factors, ASLE is quite a promising approach to determine the effect of clamping
structure based on the frequency responses measurement. ASLE estimates the correlation of two
dataset variables based on similarity in shapes and not magnitudes. The coefficients for ASLE is
highest for the low frequency region followed by medium and high frequency regions for both HV
and LV windings. It is also found that an existing ASLE limit of 0.6 may not be practical in the current
study. Therefore, new ASLE limits are suggested for HV and LV windings which are 1.37 and 0.66,
respectively. These limits are proposed based on the lowest coefficients of the low-frequency region
(20 Hz–1.5/2 kHz) for both HV and LV windings. However, in order to draw any conclusion on
the proposed limits, it can be validated based on the frequency response measurements of other
transformers with similar or different types of faults.
The values of the F-test at the low-frequency region are closer to 0 for both HV and LV windings.
This signifies changes in the mechanical structure of the winding. Based on the case study, the statistical
analyses reveal that ASLE and F-tests are the most sensitive approaches that can be used to detect
mechanical changes in the windings related to clamping structure.
There is no effect of clamping structure removal based on the RF method. The relative factor Rxy
is 10 for all phases, as shown in Table 4. This complies with the condition of RLF ≥ 2.0, RMF ≥ 1.0 and
Energies 2018, 11, 2307
11 of 13
RHF ≥ 0.6 as in Table 1 which suggests that the winding is in a normal condition. This is true since the
RF method is only accurate for winding damage analyses and not faulty core or clamping structure.
5. Conclusions
The study indicates that the frequency responses of the transformer winding without clamping
structure has variations at a frequency less than 2 kHz under an end-to-end open circuit test for both
HV and LV windings. Under a end-to-end short circuit test, the frequency response of the without a
clamping structure has no variation as compared to that with a clamping structure. Statistical methods
such as PCC, SCC, KCC, CCF, RMSE and RF methods are not sensitive to indicate frequency response
variation caused by removal of the clamping structure based on the case study. Only the ASLE and
F-tests are sensitive enough to indicate changes in the winding that are caused by the clamping
structure. For the ASLE method, updated threshold limits of 1.37 and 0.66 are proposed for HV and
LV windings. However, further validation on the threshold limits will be carried out in future for
transformers with a similar condition or different types of faults. The outcome of the study can assist
engineers and technical personnel to interpret winding conditions, especially for aged transformers.
Author Contributions: The research study was carried out successfully with contributions from all authors.
The main research idea, simulation/experimental works and manuscript preparation were contributed by A.S.M.
and S.A.-A. N.A. and M.F.M.Y. contributed on the manuscript preparation and research idea. J.J. assisted in
finalizing the research work and manuscript. M.A.T. gave several suggestions from the industrial perspective.
All authors revised and approved the publication of the paper.
Funding: The research was funded by PUTRA Berimpak (GPB/2017/9570300) and the FRGS scheme
(03-01-16-1787FR).
Acknowledgments: The authors would like to express their sincere gratitude to the Ministry of Education
Malaysia, CELP UPM and UTHM for technical and financial support to this research.
Conflicts of Interest: The authors declare no conflicts of interest.
References
1.
2.
3.
4.
5.
6.
7.
8.
9.
Amini, A.; Das, N.; Islam, S. Impact of buckling deformation on the FRA signature of power transformer.
In Proceedings of the 2013 Australasian Universities Power Engineering Conference (AUPEC), Hobart, TAS,
Australia, 29 September–3 October 2013; pp. 1–4.
Bagheri, M.; Naderi, M.S.; Blackburn, T. Advanced transformer winding deformation diagnosis: Moving
from off-line to on-line. IEEE Trans. Dielectr. Electr. Insul. 2012, 19, 1860–1870. [CrossRef]
Reykherdt, A.A.; Davydov, V. Case studies of factors influencing frequency response analysis measurements
and power transformer diagnostics. IEEE Electr. Insul. Mag. 2011, 27, 22–30. [CrossRef]
Bagheri, M.; Phung, B.; Blackburn, T.; Naderian, A. Influence of temperature on frequency response analysis
of transformer winding. In Proceedings of the 2013 IEEE Electrical Insulation Conference (EIC), Ottawa, ON,
Canada, 2–5 June 2013; pp. 1393–1404.
Behjat, V.; Mahvi, M. Statistical approach for interpretation of power transformers frequency response
analysis results. IET Sci. Meas. Technol. 2015, 9, 367–375. [CrossRef]
Nirgude, P.M.; Ashokraju, D.; Rajkumar, A.D.; Singh, B.P. Application of numerical evaluation techniques
for interpreting frequency response measurements in power transformers. IET Sci. Meas. Technol. 2008, 2,
275–285. [CrossRef]
Tang, W.H.; Shintemirov, A.; Wu, Q.H. Detection of minor winding deformation fault in high frequency
range for power transformer. In Proceedings of the IEEE PES General Meeting, Providence, RI, USA,
25–29 July 2010; pp. 1–6.
Ryder, S.A. Diagnosing Transformer Faults Using Frequency Response Analysis. IEEE Electr. Insul. Mag.
2003, 19, 16–22. [CrossRef]
Wimmer, R.; Tenbohlen, S.; Feser, K.; Kraetge, A.; Krüger, M.; Christian, J. Development of algorithms to
assess the FRA. In Proceedings of the 15th International Symposium on High Voltage Engineering, Ljubljana,
Slovenia, 27–31 August 2007; pp. 1–6.
Energies 2018, 11, 2307
10.
11.
12.
13.
14.
15.
16.
17.
18.
19.
20.
21.
22.
23.
24.
25.
26.
27.
28.
29.
30.
31.
12 of 13
Bolboaca, S.D.; Jäntschi, L. Pearson versus Spearman and Kendall’s tau correlation analysis on
structure-activity relationships of biologic active compounds. Leonardo J. Sci. 2006, 5, 179–200.
Hauke, J.; Kossowski, T. Comparison of values of Pearson’s and Spearman’s correlation coefficients on the
same sets of data. Quaest. Geogr. 2011, 30, 87–93. [CrossRef]
Shong, N. Pearson’s Versus Spearman’s and Kendall’s Correlation Coefficients for Continuous Data.
Master’s Thesis, University of Pittsburgh, Pittsburgh, PA, USA, 2010.
Vaca Vargas, P.; Mombello, E. Time-Frequency Analysis for the Interpretation of FRA Measurements.
In Proceedings of the VDE High Voltage Technology 2016, ETG-Symposium, Berlin, Germany,
14–16 November 2016; pp. 390–394.
Shintemirov, A.; Tang, W.H.; Wu, Q.H. Transformer winding condition assessment using frequency response
analysis and evidential reasoning. IET Electr. Power Appl. 2010, 4, 198–212. [CrossRef]
Abu-Siada, A.; Islam, S. A novel online technique to detect power transformer winding faults. IEEE Trans.
Power Deliv. 2012, 27, 849–857. [CrossRef]
Yousof, M.F.M.; Ekanayake, C.; Saha, T.K. Study of transformer winding deformation by frequency response
analysis. In Proceedings of the IEEE Power and Energy Society General Meeting, Vancouver, BC, Canada,
21–25 July 2013; pp. 1–5.
Abu-Siada, A.; Hashemnia, N.; Islam, S.; Masoum, M. Understanding power transformer frequency response
analysis signatures. IEEE Electr. Insul. Mag. 2013, 29, 48–56. [CrossRef]
Kraetge, A.; Krüger, M.; Fong, P. Frequency response analysis—Status of the worldwide standardization
activities. In Proceedings of the International Conference on Condition Monitoring and Diagnosis CMD,
G-05, Beijing, China, 21–24 April 2008; pp. 651–654.
Picher, P.; Lapworth, J.; Noonan, T.; Christian, J. Mechanical Condition Assessment of Transformer Windings
Using Frequency Response Analysis (FRA); CIGRE: Paris, France, 2008.
Islam, S.M. Detection of shorted turns and winding movements in large power transformers using frequency
response analysis. In Proceedings of the 2000 IEEE Power Engineering Society Winter Meeting, Singapore,
23–27 January 2000; pp. 2233–2238.
Institute of Electrical and Electronics Engineers. IEEE Std. C57.149-2012—IEEE Guide for the Application and
Interpretation of Frequency Response Analysis for Oil-Immersed Transformers; IEEE Power and Energy Society:
Park Avenue, NY, USA, 2013; pp. 1–72.
Mohammad, M.S.; Samimi, H.; Tenbohlen, P.S. The Numerical Indices Proposed for the Interpretation of the
FRA Results: A Review. In Proceedings of the VDE High Voltage Technology 2016, ETG-Symposium, Berlin,
Deutschland, 14–16 November 2016; pp. 377–383.
Sardar, S.; Kumar, A.; Chatterjee, B.; Dalai, S. Application of Statistical Interpretation Technique for Frequency
Response Analysis and Detection of Axial Displacement in Transformer Winding. In Proceedings of the 2017
IEEE Calcutta Conference (CALCON), Kolkata, India, 2–3 December 2017; pp. 461–464.
Patel, M.R. Dynamic Response of Power Transformers Under Axial Short Circuit Forces Part II—Windings
and Clamps as a Combined System. IEEE Trans. Power Appar. Syst. 1973, PAS-92, 1567–1576. [CrossRef]
Patel, M.R. Dynamic Response of Power Transformers Under Axial Short Circuit Forces Part I—Winding
and Clamp as Individual Components. IEEE Trans. Power Appar. Syst. 1973, PAS-92, 1558–1566. [CrossRef]
Hashemnia, N.; Abu-Siada, A.; Masoum, M.A.S.; Islam, S.M. Characterization of transformer FRA signature
under various winding faults. In Proceedings of the 2012 IEEE International Conference on Condition
Monitoring and Diagnosis (CMD), Bali, Indonesia, 23–27 September 2012; pp. 446–449.
International Electrotechnical Commission. IEC 60076-18, Power Transformers—Part 18: Measurement of
Frequency Response; International Electrotechnical Commission: Geneva, Switzerland, 2012.
Mukherjee, P.; Satish, L. Estimating the Equivalent Air-cored Inductance of Transformer Winding from
Measured FRA. IEEE Trans. Power Deliv. 2018, 33, 1620–1627. [CrossRef]
Yousof, M.F.M. Frequency Response Analysis for Transformer Winding Condition Monitoring. Ph.D. Thesis,
The University of Queensland, St Lucia, QLD, Australia, 2015.
Myers, J.L.; Well, A.; Lorch, R.F. Research Design and Statistical Analysis; Routledge: Abingdon, UK, 2012.
Saleh, S.M.; EL-Hoshy, S.H.; Gouda, O.E. Proposed diagnostic methodology using the cross-correlation
coefficient factor technique for power transformer fault identification. IET Electr. Power Appl. 2017, 11,
412–422. [CrossRef]
Energies 2018, 11, 2307
32.
33.
34.
35.
36.
37.
38.
39.
13 of 13
Mahvi, M.; Behjat, V.; Rahimpour, E. New statistical approach to interpret power transformer frequency
response analysis: Non-parametric statistical methods. IET Sci. Meas. Technol. 2016, 10, 364–369.
Yousof, M.F.M.; Riang, S.; Uyup, M.K.A. The influence of data size in statistical analysis of power transformer
frequency response. In Proceedings of the 2016 IEEE International Conference on Power and Energy (PECon),
Melaka, Malaysia, 28–29 November 2016; pp. 595–599.
Tarimoradi, H.; Gharehpetian, G.B. Novel calculation method of indices to improve classification of
transformer winding fault type, location, and extent. IEEE Trans. Ind. Inform 2017, 13, 1531–1540. [CrossRef]
Kennedy, G.M.; Mcgrail, A.J.; Lapworth, J.A. Using Cross-Correlation Coefficients to Analyze Transformer
Sweep Frequency Response Analysis. In Proceedings of the IEEE Power Engineering Society Conference
and Exposition in Africa—PowerAfrica, Johannesburg, South Africa, 16–20 July 2007; pp. 1–6.
Yousof, M.F.M.; Ekanayake, C.; Saha, T.K. Frequency response analysis to investigate deformation of
transformer winding. IEEE Trans. Dielectr. Electr. Insul. 2015, 22, 2359–2367. [CrossRef]
Yousof, M.F.M.; Ekanayake, C.; Saha, T.K. Locating inter-disc faults in transformer winding using frequency
response analysis. In Proceedings of the 2013 Australasian Universities Power Engineering Conference
(AUPEC), Hobart, TAS, Australia, 29 September–3 October 2013; pp. 1–6.
Badgujar, K.P.; Kulkarni, S.V. Fuzzy Logic Based Identification of Deviations in Frequency Response of
Transformer Windings. pp. 1–6. Available online: http://www.iitk.ac.in/npsc/Papers/NPSC2012/papers/
12145.pdf (accessed on 5 April 2018).
Kim, J.W.; Park, B.; Jeong, S.C.; Kim, S.W.; Park, P. Fault diagnosis of a power transformer using an improved
frequency-response analysis. IEEE Trans. Power Deliv. 2005, 20, 169–178. [CrossRef]
© 2018 by the authors. Licensee MDPI, Basel, Switzerland. This article is an open access
article distributed under the terms and conditions of the Creative Commons Attribution
(CC BY) license (http://creativecommons.org/licenses/by/4.0/).