DCBL Prc001 en
DCBL Prc001 en
DCBL Prc001 en
change in motor speed allows gradual changes to room temperature and minimizes fan blade sudden impact noise (compared to 20~25% rps change with conventional control and old fashioned 3-speed motors).
DCBL fan coil unit enables to deliver advance performance of airflow (green color curve with extension dash line) by excess power input, please consult Trane engineer for further technical support.
DCBL-PRC001-EN
H 1
F 2
C 3
A 03 A 4 5,6 7
N 8
A 1 N A N B 9 10 11 12 13 14
G = 4.0 (4.8) kW, Model 12~14 S = Special kW in bracket for 240V only R = STD. SUS / 15mm PE Insulation T = Long SUS / 15mm PE Insulation U = STD. Galvanized Steel / 15mm Non-Flammable BS476, Part7 Insulation V = Long Galvanized Steel / 15mm Non-Flammable BS476, Part7 Insulation W = STD. Galvanized Steel / 25mm Non-Flammable BS476, Part7 Insulation X = Long Galvanized Steel / 25mm Non-Flammable BS476, Part7 Insulation Y = STD. SUS / 25mm Non-Flammable BS476, Part7 Insulation Z = Long SUS / 25mm Non-Flammable BS476, Part7 Insulation S = Special Only A to V available for Exposed unit
DIGIT 1 - Position
H = Horizontal
DIGIT 3 - Casing
C = Concealed W = Exposed
DIGIT 10 - Voltage/Hertz/Phase
1 = 220-240 / 50 / 1 2 = 220-240 / 60 / 1 5 = 115 / 60 / 1 S = Special
Note:
1. HFCA will not support sweat connection for standard piping. 2. The wiring of thermostat or valves must be done on job site. 3. Non-flammable PU insulation meet the regulation of BS476 part7 class 1 and part6 class O.
DCBL-PRC001-EN
Performance Data
5C SH 3.19 2.92 2.62 4.81 4.45 4.08 5.32 4.86 4.39 6.92 6.38 5.81 8.42 7.60 6.66 10.34 9.41 8.43 11.19 10.30 9.35 TH 5.17 4.55 3.85 7.81 7.02 6.13 8.58 7.55 6.41 11.15 9.90 8.55 13.48 11.60 9.27 16.56 14.41 12.03 17.92 16.10 14.08 WFR 0.41 0.22 0.13 0.62 0.33 0.21 0.68 0.36 0.22 0.89 0.47 0.29 1.07 0.55 0.32 1.32 0.69 0.41 1.43 0.77 0.48 WPD 7.60 2.47 1.02 21.93 7.35 3.20 9.38 3.04 1.26 17.68 5.80 2.48 4.87 1.52 0.57 8.05 2.56 1.03 14.15 4.23 2.15
04
678
06
1018
08
1357
10
1696
12
2036
14
2366
Entering Water Temperature 7C WPD WFR TH SH 5.74 0.35 4.43 2.86 1.77 0.18 3.78 2.59 0.69 0.11 3.10 2.32 16.63 0.53 6.72 4.32 5.31 0.28 5.87 3.97 2.23 0.17 5.02 3.63 7.06 0.58 7.35 4.78 2.17 0.30 6.27 4.33 0.86 0.18 5.16 3.90 13.33 0.76 9.56 6.23 4.16 0.39 8.24 5.69 1.72 0.24 6.97 5.19 3.64 0.91 11.50 7.56 1.07 0.46 9.54 6.77 0.36 0.24 7.15 5.85 6.03 1.12 14.14 9.30 1.82 0.57 11.93 8.40 0.68 0.33 9.56 7.48 11.51 1.24 15.06 10.06 3.32 0.65 13.67 9.17 1.40 0.39 11.49 8.21
9C SH 2.54 2.30 2.06 3.84 3.52 3.22 4.24 3.85 3.46 5.55 5.06 4.62 6.71 5.98 5.12 8.26 7.46 6.62 8.93 8.04 7.13 TH 3.65 3.02 2.39 5.57 4.74 3.97 6.05 5.03 3.99 7.88 6.63 5.48 9.40 7.53 5.15 11.60 9.53 7.25 13.15 11.09 8.89 WFR 0.29 0.14 0.08 0.44 0.23 0.14 0.48 0.24 0.14 0.63 0.32 0.19 0.75 0.36 0.18 0.92 0.45 0.25 1.05 0.53 0.30 WPD 4.03 1.18 0.44 11.80 3.60 1.45 4.96 1.46 0.54 9.39 2.81 1.12 2.53 0.70 0.20 4.22 1.21 0.42 8.21 2.24 0.91
2.86 3.71 4.95 6.16 6.91 7.94 EWT=55C; EAT=21C; WFR=0.3L/S == Electric Sheathed Element 1.0 1.5 2 3 3.5 4 Available with high temperature cutout Plenum/Filters Return air plenum with filters-washable foam, PP nylon or aluminium Note: It reserves the right to change design and specification without notice.
American Standard Inc. 2006
9.26 4
DCBL-PRC001-EN
Note : 1. Dimensions in mm. 2. C1 is the dimension of long drain pan. 3. Right hand coil connection shown. 4. Wiring connection same side as coil and drain connections. 5. Access door below unit required to service fan motor. 6. Wiring controls and junction box not supplied by Trane. 7. A terminal strip is supplied for main control board only. 8. An addition terminal strip for optional electric heater only.
External Dimensions(mm) A 480 730 865 1150 1320 1570 1650 B 530 780 915 1200 1370 1620 1700 C 665 915 1050 1335 1505 1755 1835
Number of
Net Weight(Kg)
Operating Weight(Kg) 3Row 21 26 28.8 35.4 45.7 51.2 54.4 4Row 22.3 28.3 31.4 38.1 49.6 56.3 59.5
2Row 3Row 4Row 2Row 3Row 4Row 2Row 19 20 21 22 23 24 19.7 23 25 26 27 29 30 24.7 25 27 29 31 33 35 26.2 30 33 35 38 41 43 31.6 40 43 46 48 51 54 41.8 44 48 52 55 58 63 46.2 47 51 55 59 62 67 49.3
DCBL-PRC001-EN
Connection / Piping
Motor Type
Normal
Hi-Static
Hz 63 125 250 500 1000 2000 4000 8000 dBA 63 125 250 500 1000 2000 4000 8000 dBA Model Rated 35 48 46 47 44 42 35 31 49.1 39 54 52 53 49 48 37 36 54.7 03 Min 21 23 23 27 29 24 18 14 31.8 27 28 29 33 35 36 29 18 40.2 04 06 08 10 12 Rated 36 49 47 48 45 43 35 32 50.1 39 52 48 50 49 47 39 36 53.4 Min 22 23 25 28 30 23 18 14 32.3 27 29 30 34 36 37 30 19 41.2 Rated 39 52 47 48 46 44 37 32 50.8 44 59 58 59 58 55 44 41 62.0 Min 22 28 29 31 30 23 21 16 33.4 23 29 33 38 40 39 34 24 44.3 Rated 41 54 52 53 50 49 39 38 55.4 44 59 58 59 58 55 44 41 62.0 Min 25 29 29 32 30 24 22 18 33.9 21 29 34 40 42 40 33 26 45.7 Rated 39 52 51 52 49 46 41 35 53.9 42 56 56 58 54 52 47 42 59.6 Min 25 26 26 30 30 26 18 12 33.3 26 30 33 40 41 39 32 24 44.8 Rated 44 56 52 53 51 47 41 36 55.3 48 61 57 59 57 55 47 40 61.7 Min 26 27 26 31 31 28 20 16 34.7 28 31 33 41 42 39 34 26 45.6 Cooling & Heating Coil Connection Dimensions Unit Size 03~14
Left / Right
3 Row ( A B
Rated 46 57 53 55 52 49 42 37 56.8 49 63 58 60 57 56 48 41 62.4 14 Min 27 27 25 32 30 32 22 20 36.2 30 30 34 40 43 40 34 26 46.2 Notes : 1. Data referenced to 10-12 watts. 2. Above performance determined with both Normal static motor and Hi-static motor operating against 0 Pa ESP.
Hand
69.6 104.2 138.8 173.6 59.8 171.3 134.2 97 4 Row ( A B 3 Row Cooling ) 1 Row Heating C D E F G H
Hand
Wiring Diagram
2 Row Coil 3 Row Coil 4 Row Coil A C E F A C E F A C E F 57 178 51 181 57 178 51 181 41 174 60 176
Hand
DCBL-PRC001-EN
Product Specification
=General
Fabricated with a rigid galvanized steel casing. The DIDW centrifugal fans have balanced, galvanized steel, and forward curved blades. The fan board and the top of coil casing have insulation of 6mm thickness, 108 kg/m3 high-density non-flammable PU foam. Interchangable coil direction to match water connections on the field. An optional return air plenum is available to allow the connection different types of filter. IEC 60335 safety certified.
The operating motor maintains low casing temperature (less thermal loss) and low noise (less friction). The motor lead-out wires are enclosed by flexible metal conduit and providing protection against damage.
=Control Unit
The control unit consists of Main Control Board at FCU side panel and wall mounted LCD Thermostat to achieve step-less control for fan motor. With microprocessor and applying PI (Proportional-Integration) logic for standalone control unit, which enables to deliver fast signal response and accurate controls. Applicable to either 2-pipe system (cooling only/ cooling and heating/ cooling and electric heater) or 4-pipe system (cooling and heating).
The LCD thermostat able to display 1) room temperature, 2) set temperature, 3) status of fan mode and speed, and 4) failure codes for trouble-shooting and maintenance purpose. PCB DIP switch setting for 1) autorestart function for fan motor operating again by resuming power, 2) Key-card function - stop or still operating beneath unoccupied mode at default setting temperature by remove keycard (the default setting temperature is adjustable at job site from 16~32 deg. C), and 3) customize thumb wheel (variable resistor/ analog signal) set temperature Customer wiring for unit remote on/off and control cable distance up to 100 meters. Optional back light of blue color.
=Coil
The coil can have 2,3 or 4 rows, with copper tubes mechanically bonded into slit aluminum fin collars. Water inlet / outlet connections are 3/4-inch female pipe thread (JIS B 0203-1966). Header assembly is a one-piece casting, which enables to connect steel pipe directly. Coil assembly is tested over 20 kg/cm2. A manual air vent is fitted with a drain line to the drain pan to avoid any water drips when venting. A water drain is located at the bottom of the coil header.
=Drain Pan
The drain pan is 25mm depth with 0.8mm thickness galvanized steel c/w internal epoxy resin coating. For sure without leakage occur, the fabrication of drain pan by one-piece stamping process with seamless and no joint. The standard insulation material is 5mm thickness, 27 kg/m3 density PE foam. The drain pan has one 3/4-inch male pipe thread (JIS B 0203-1966) connection.
=LCD Thermostat
Full features of 1) power on/off, 2) room temperature setting, 3) cool/ heat/ fan operating mode, 4) auto/ 3-speed fan mode, 5) timer on and off, and 6) sleep mode.
Converter / Driver
Motor
DCBL-PRC001-EN
Options
=Heater
Two types of heating device are available: hot water and electric sheathed heating element. Please check technical data for such different types of heating capacity. Meet Australia safety code AS 1668.1 (Section 2.9), and AS 3102.
Since 1885, Trane has been at the technological forefront of air conditioning. The company's pioneering spirit, commitment to research and pursuit of quality have made it a world leader in the manufacture of water chillers. Over 70 years ago Trane produced the first fan coil unit and in so doing created a product which is now built worldwide. The universal acceptance of this product has prompted Trane to focus the same engineering experience to the fan coil as given to the refrigeration products.
=Plenum & Filters =S430(Standard) / S304(Option) Stainless Steel Drain Pan =Blue Fin
The blue fin with vinyl-epoxy-based coating that has been tested under ASTM B117, and thus of higher corrosion resistance than aluminum fin stock.
FM 38631 ISO 9001 Qualified factory - Trane Taiwan Trane A business of American Standard Companies http : // www.trane.com Stocking location Taipei, Taiwan Literature Order Number File Number Supersedes DCBL-PRC001-EN-0106 DCBL-TS-4 DCBL-PRC001-EN-1204
An American-Standard Company
Since The Trane Company has a policy of continuous product improvement, it reserves the right to change design and specifications without notice.