Excel Program For Timber Structures
Excel Program For Timber Structures
Milano
BSCE-5 Timber Excel Program
*note:the boxes in yellow should be inputed by the designer,while blue ones are computed by the program.=)
DESIGN OF PURLINS
DATA: LOADINGS:
Type of wood: pahutan Wind Pressure 0.96 kPa
Bending and Tension(Fb) 13.80 MPa Minimum Roof Live Load 0.80 kPa
Shear(Fv) 1.34 MPa GI roofing 0.15 kPa
Compression(Fc) 8.14 MPa Residential Live Load 2.00 kPa
Modulus of Elasticity(E) 9100.00 MPa
Relative Density(G) 0.55
Specific Gravity 5.40 kN/m3 SPACING:
Purlins 0.40 m
Truss 2.75 m
Floor Joist 0.40 m
W nt
W n2
θ W DL+LL
LOADINGS:
Live load 0.32 Kn/m
Roofing 0.06 Kn/m
Purlin weight 0.04 Kn/m
W DL+LL 0.42 Kn/m
Load Combinations:
Condition 1: DL + LL
W DL+LL = 0.37 kN/m governs!!
Condition 2: DL + LL + WL
W DL+LL+WL= 0.22 kN/m LOAD COMBINATION:
Windward:
Pn = 1.3(sinq - 0.5)P 0.11 kN/m
Leeward:
MOMENTS: Pn = -0.5P -0.48 kN/m
Mn = Mx = 1/8(W nLx2) 0.64 Kn-m
(WW) W n1 = Pn(Spacing) 0.04 kN/m
Mt = My = 1/12(W nLy2) 0.12 Kn-m (LW) W n1 = Pn(Spacing) -0.19
W n2 = WDL+LL(cosq) 0.37 kN/m
W nt = WDL+LL(sinq) 0.20 kN/m
SHEAR:
W N = Wn1 + Wn2 0.41 kN/m
Vx = (1/2)W nLx 0.69 Kn W t = Wnt 0.20 kN/m
TRIAL DIMENSION:
75 x 200 mm
I= 5.00E+07 mm4
Loadings:
GI roofing = 1.74 Kn
Wt. of Purlins = 0.11 Kn
Min. Roof LL = 9.3 Kn
total = 11.16 Kn
Weight of truss:
Overall Length of Truss = 44.52 m
Weight of Truss = 3.6 Kn
TOTAL 14.76 Kn
Windward 0.607
wind load = 1.28 Kn/m
fx = 0.15 Kn 1.283
fy = 0.28 Kn θ
1.130
Leeward
wind load = -5.58 Kn/m
fx = 0.66 Kn
fy = 1.23 Kn
4.92
2.64
Forces Due to DL + LL
7.38 KN
3.690 Kn 3.69 Kn
3.690 Kn 3.690 Kn
3.69
3.69 Kn
ceiling load
0.8
0.8
7.45 m
0.95
Forces Due to Wind Load
0.28
0.81 0.28
v
J
0.1517 0.66
0.28 K 0.28
v
0.1517 I
L 0.66
0.28 0.28
H v
A G
B C D E F
Reactions due to DL + LL
Summary of Bar Forces:
TRIAL DIMENSION:
75 x 200 mm
I= 5.00E+07 mm4
P= -9.526 Kn
L= 1395.00 mm
L/d = 18.6
.5
π E
= 10.72 since L/d>K and L/d>11 it is long column
K =
4 6 fc
To be safe:
Fc >= fc
π2 E
Fc = 2
L
36
d
Fc = 7.21
fc = P/A = 0.64 < 7.21 it is safe!=)
TRIAL DIMENSION:
75 x 200 mm
I= 5.00E+07 mm4
P= 8.419 Kn
L= 1.24 mm
L/d = 0.02
.5
π E
= 10.72 since L/d<K and L/d<11 it is short column
K =
4 6 fc
To be safe:
Fc >= fc
π2 E
Fc = 2
L
36
d
Fc = 9126784.44
fc = P/A = 0.56 < 9126784 it is safe!=)
DESIGN OF Verticals
TRIAL DIMENSION:
75 x 200 mm
I= 5.00E+07 mm4
P= -10.680 / -0.560 Kn
L= 0.64 mm
L/d = 0.01
.5
π E
= 10.72 since L/d<K and L/d<11 it is short column
K =
4 6 fc
To be safe:
Fc >= fc
π2 E
Fc = 2
L
36
d
Fc = 3.43E+07
fc = P/A = 0.71 < 3.43.E+07 it is safe!=)
Fb >= ft
Fb = 13.80 MPa
P
ft =
(3 / 5) Ag= 0.06 < 13.80 it is safe!=)
DESIGN OF Diagonals
TRIAL DIMENSION:
75 x 200 mm
I= 5.00E+07 mm4
P= 5.780 / 0.390 Kn
L= 1.40 mm
L/d = 0.02
.5
π E
= 10.72 since L/d<K and L/d<11 it is short column
K =
4 6 fc
To be safe:
Fc >= fc
π2 E
Fc = 2
L
36
d
Fc = 7.21E+06
fc = P/A = 0.39 < 7.21.E+06 it is safe!=)
Fb >= ft
Fb = 13.80 MPa
P
ft =
(3 / 5) Ag= 0.04 < 13.80 it is safe!=)
At Truss supports
DL + LL WL DL + LL + WL
A -26.7 -0.66 -27.36
B -26.7 -0.28 -26.98
At Girder Supports -9.98 0 -9.98 4P= Interior posts carries a max of
4 girders
4P= ### Kn
L/d= 15.75
.5
π E
K =
= 10.72
4 6 fc
since L/d > K and L/d > 11 it is long column.
To be safe:
Fc >= fc
Fc = 8.14 Mpa
fc = P/A
= 2.75 Mpa
4.23
2.00 m
3.73 m
kn
0.66
rt column
rt column
rt column
CARMEL B. SABADO CE-164 PROF.Allan E. Milano
BSCE-5 Timber Excel Program
*note:the boxes in yellow should be inputed by the designer,while blue ones are computed by the program.=)
DESIGN OF T & G
0.03
0.4 m
LOADINGS:
Dead Load (Weight of T&G) = Area X S.G. = 0.01 kN/m
Live Load (Residential LL) = 0.2 kN/m
W DL+LL = 0.21 kN/m
Fvact = (3/2)(Vmax/bh)
= 0.03
Fv= 1.34 ****Since Fvact is less than Fvallowable, it is safe=)
DATA:
Specific Gravity = 7.26 kN/m3
Modulus of Elasticity = 14600.0 MPa
Length of joist = 2.75 m
Joist Spacing = 0.50 m
Residential Live Load = 2.00 kPa
TRIAL DIMENSION:
50 x 175 mm
I= 2.23E+07 mm4
0.50 m
0.05 m
Dead Loads:
Live Load:
Floor LL = 1 Kn/m
Fact = 6Mmax/bh2
= 4.275 Mpa
Fb= 13.80 Mpa ****Since Fact is less than Fallowable, it is safe=)
Fvact = (3/2)(Vmax/bh)
= 0.27208 Mpa
Fv= 1.34 Mpa ****Since Fact is less than Fallowable, it is safe=)
DESIGN OF GIRDER
DATA: TRIAL DIMENSION:
Specific Gravity = 5.40 kN/m 3
150 x 300 mm
Modulus of Elasticity = 9100.00 MPa I= 3.38E+08 mm4
Length of Girder = 2.75 MPa Weight of the girder: = Area X Specific Gravity
Joist Spacing = 0.40 m = 0.24 kn-m
Residential Live Load = 2.00 kPa
Weight
of girder
2.75 m
9.98 kn 9.98 kn
Fvact = (3/2)(Vmax/bh)
= 0.33 Mpa
Fv= 1.34 Mpa ****Since Fact is less than Fallowable, it is safe=)
DESIGN OF TREAD
Analytical Model:
w= 0.45 Kn
1.1 m
Fact = 6Mmax/bh2
= 0.21 Kn
Fb= 13.80 Kn ****Since Fact is less than Fallowable, it is safe=)
Fvact = (3/2)(Vmax/bh)
= 0.04 Kn
Fv= 1.34 Kn ****Since Fact is less than Fallowable, it is safe=)
DESIGN OF CARRIAGE
TRIAL DIMENSION:
50 x 200 mm
I= 3.33E+07 mm4
Theta, θ = 36.87
Length of Carriage = 4.5 m
Weigth of Carriage = 0.05 Kn
Analytical Model:
2.7
m
Theta, θ = 36.87
3.6 m
w= 0.41 Kn/m
L= 4.50 m
concrete landing
Fact = 6Mmax/bh2
= 12.34 Kn
Fb= 13.80 Kn ****Since Fact is less than Fallowable, it is safe
Fvact = (3/2)(Vmax/bh)
= 0.14 Kn
Fv= 1.34 Kn ****Since Fact is less than Fallowable, it is safe