Oman Electricity Transmission Company Transmission Department Circuit Breaker Testing Sheet Date :9/12/2013 Time: 13.

00 Area: MUSCAT Type of Maintenance : City: MUSCAT Substation:MOBELLA Feeder: 2 TO A ( TX-2) 33kV
Plan. Preventive.M Break Down.M New Installation

C.B Description
Manufacture by: SIEMENS Type: VCB 3AH3 315-4

Year of Manufacturing: 2013


SF6 Rated pressure: NA bar/PSI/kg sqcm

Sr. No: 27375 Rated Voltage : 36kV

Out door Breaker

Indoor Breaker Cleaned Good Good


R-E :13.7T , Y-E : 14.5T, Y-E : 15.5T

01- Check Insulation surface for signs of chipping, dirt, smock & Clean if required. 02- Check operation mechanism, lubricate the sliding parts 03- Check spring charger motor for upnormal sound & movement.

04- Measure insulation resistance of each pole.( for 33kv C.Bs only) 05- Record the SF6 of gas pressure seen on the gage. 06- Check the condition of gas pipe for SF6 C.B 07- Check tightness of nut, bolts, terminal joints of C.B 08- Check earthing connections. 09- Record hydraulic oil Pressure 10- Check for any oil leak 11- Check painting

NA NA Ok/Good Ok/Good NA NA Ok/Good


Ok/Good Ok/Good Ok/Cleaned Ok/Good Ok/Good Ok/Good Ok/
bar-PSI- Kg/sq cm

Control Panel/ Local Control Panel


01- Check status indication lamps, fuses replaced if it required 02- Check the covers/doors are closing properly. 03- Clean dust by using vacuum cleaner & insulated hand brush. 04- Check condition of all selector, Control, and supply switches. 05- Check remote/Local Operation of the C.B 06- Check Earthing connection. 07- Check the C.B counter & record status values

221

* Trip circuit Checked * Close Circuit Checked * All Alarms Checked

Ok/Good Ok/Good Ok

PTW NO:1200869
* Any Remark/ Abnormalities observed: 1) 1 burning dot avilable on B Phase spout .

* Tested By: Vinod Vasudevan


Maintenance Engineer Ray Intl ( OETC Maint Project)

* Checked By: Er.Ahmed Shiyabi O&M Engineer

virsion 26/09/09 Preped by Namani

Test Result
Mobella 2TOA

Insulation Resistance
IR Value R- Earth 13.7 R 48.4 64 Y- Earth 14.5 Y 49.3 63.9 B- Earth 15.5 B 49.3 63.6 Unit T Unit mS mS

Timing Test
Tripping Closing

Contact Resistance
Resistance R- R 43 Y-Y 41 B- B 39 Unit