VOLTECH ENGINEERS PVT. LTD.

TEST REPORT FOR CABLE


CLIENT : M/S VOLTTECH ENGINEERING WORKES DATE :16.11.2013
PROJECT : JINDAL STEEL AND POWER LTD RAIGARH Sheet No.: 1 of 2

Test Performed by: VEPL Witnessed by: JSPL Witnessed by: VOLTTECH
Name :Mr.T.Balaji Name : Name :
Designation : Senior
commissioning Engineer
Designation : Designation :
Signature &
Date
Signature &
Date
Signature &
Date

1. Equipment Details

Voltage rating : 6.6KV/6.6KV
Size : 3C X 300 Sq.mm

2. Location : 2 MVA Transformer To Isolator


3. General Inspection : Ok



4. Insulation Resistance Test:( Applied Voltage 10 KV DC)


Terminal Values For 1 minute
Measured Leakage
Current (nA)
R ph-Earth 1.36 T 25.1
Y ph- Earth 5.47 T 2.14
B ph- Earth 3.76 T 2.78
R ph-Y ph >10.5 T 1.00
Y ph-B ph 9.41 T 1.27
B ph-R ph 9.17 T 1.12



5. Remarks: Cable Check found ok