Voltech Engineers Pvt. Ltd. conducted testing on a vacuum circuit breaker for Jindal Steel and Power Ltd. The test report summarizes the equipment details, inspection results, insulation resistance testing in open and closed conditions, contact resistance testing, timing interval testing for opening and closing, coil resistances, operational checks for manual and electrical operation, and functional checks. All tests and checks were found to be okay and the breaker was found to be functioning properly.
Voltech Engineers Pvt. Ltd. conducted testing on a vacuum circuit breaker for Jindal Steel and Power Ltd. The test report summarizes the equipment details, inspection results, insulation resistance testing in open and closed conditions, contact resistance testing, timing interval testing for opening and closing, coil resistances, operational checks for manual and electrical operation, and functional checks. All tests and checks were found to be okay and the breaker was found to be functioning properly.
Voltech Engineers Pvt. Ltd. conducted testing on a vacuum circuit breaker for Jindal Steel and Power Ltd. The test report summarizes the equipment details, inspection results, insulation resistance testing in open and closed conditions, contact resistance testing, timing interval testing for opening and closing, coil resistances, operational checks for manual and electrical operation, and functional checks. All tests and checks were found to be okay and the breaker was found to be functioning properly.
CIRCUIT BREAKER CLIENT : M/S VOLTTECH ENGINEERING WORKES DATE :27.12.2013 PROJECT : JINDAL STEEL AND POWER LTD RAIGARH Sheet No.: 1 of 2
Test Performed by: VEPL Witnessed by: VOLTTECH Witnessed by: JSPL Name :Mr.T.Balaji Name : Name : Designation : Senior commissioning Engineer Designation : Designation : Signature & Date Signature & Date Signature & Date
1. Equipment Details
Make : Schneider Electric Sl. No. : 7306083303-02-06 Rated Current : 1250 A Rated voltage : 6.6KV Short Circuit breaker current : 40KA Short Circuit current duration : 3 Sec Closing coil Supply Voltage : 110V DC Tripping coil Supply Voltage : 110V DC Motor Supply Voltage : 110V DC Mfg Year : 2013 2. Feeder Name : 350 KW Motor Feeder 3. Location : FES 6.6KV Switch board#2 (Panel No-06) 4. General Inspection : Ok
Terminal Values R ph-Earth >1 T Y ph- Earth >1 T B ph- Earth >1 T R ph-Y ph >1 T Y ph-B ph >1 T B ph-R ph >1 T
VOLTECH ENGINEERS PVT. LTD. TEST REPORT FOR VACUUM CIRCUIT BREAKER CLIENT : M/S VOLTTECH ENGINEERING WORKES DATE :27.12.2013 PROJECT : JINDAL STEEL AND POWER LTD RAIGARH Sheet No.: 2 of 2
Test Performed by: VEPL Witnessed by: VOLTTECH Witnessed by: JSPL Name :Mr.T.Balaji Name : Name : Designation : Senior commissioning Engineer Designation : Designation : Signature & Date Signature & Date Signature & Date
6. Contact Resistance Test:
Terminal Values R-R 21.47 Y-Y 19.97 B-B 22.54
7. Timer Interval Test:
Operations R ph-R ph Y ph-Y ph B ph-B ph Close 36 ms 36 ms 36 ms Open 32 ms 32 ms 32 ms Close-Open 41 ms 41 ms 41 ms
8. Closing Coil Resistance : 0.663 M 9. Tripping Coil Resistance : 6.530 M
VOLTECH ENGINEERS PVT. LTD. TEST REPORT FOR VACUUM CIRCUIT BREAKER CLIENT : M/S VOLTTECH ENGINEERING WORKES DATE :27.12.2013 PROJECT : JINDAL STEEL AND POWER LTD RAIGARH Sheet No.: 3 of 2
Test Performed by: VEPL Witnessed by: VOLTTECH Witnessed by: JSPL Name :Mr.T.Balaji Name : Name : Designation : Senior commissioning Engineer Designation : Designation : Signature & Date Signature & Date Signature & Date
10. Operational Check:
a. Manual Close OK Open OK b. Electrical Close OK Open OK Protection Tripping OK
11. Functional Check:
ON-OFF Indication OK Spring charge Limit Switch OK CB Aux. contacts OK Trip circuit healthy OK Antipumping function OK