Emergency Lighting Legislation and Design
Emergency Lighting Legislation and Design
Emergency Lighting Legislation and Design
ICEL 1006
EMERGENCY LIGHTING
Legislation and design
EMERGENCY
LIGHTING
STANDARDS
STRUCTURE
CHART
Other
Standards
CONVENTIONAL
Lighting requirements
CEN/TC 169/WG3
BS 5266pt 7 /EN1838
Application standard
CENELEC BTTF 62-8
BS 5266 pt1/ EN 50172
EN 50272-2
Safety
requirements
- Battery
Systems
Wiring standards
TC 64 HD 384
Product
standard
central battery
systems
EN 50171
Product
standard
generators
ISO/TC70
ISO 8528
Emergency Lighting
Standby Lighting
Escape Route
Lighting
(Previously called
Defined Escape Routes)
Emergency Escape
Lighting
1975
1990
1996
5.1-5.5
H(Height of panel)
H
Siting of Luminaires
BS 5266pt7/EN 1838 4.1
Near stairs
Siting of Luminaires
BS 5266pt7/EN 1838 4.1
Siting of Luminaires
BS 5266pt7/EN 1838 4.1
Siting of Luminaires
BS 5266pt7/EN 1838 4.1
Siting of Luminaires
BS 5266pt7/EN 1838 4.1
Siting of Luminaires
BS5266 pt7/EN 1838 4.1
Siting of Luminaires
BS 5266pt7/EN 1838 4.1
Up to
2m wide
1 Lux min. on
Centre Line of
Escape Route
1 Lux to Wall
0.5 Lux
+
0.5 Lux
1 Lux min. on
Centre Line of
Escape Route
Trans.
Spacing
to Wall
Transverse Spacing
Between Luminaires
Core Area
(excludes 0.5m border)
0.5 Lux
minimum
The horizontal illuminance shall not be less than 0.5 lux of the
core area excluding a border of 0.5m of the perimeter of the area
Axial to
Axial Spacing wall
0.3
0.3
Transverse
to wall
2
0.5 Lux
Isolux Covering
Core Area
0.5m
border
2
0.3
2
0.3
Transverse
spacing
2.5
3
4
5
1.8
1.5
-
5.6
5.5
-
Axial
to wall
Axial
spacing
1.5
1.2
-
4.7
4.6
-
Transverse Transverse
to wall
spacing
2.1
2.0
1.7
0.8
5.6
5.8
5.8
5.4
Axial
to wall
1.7
1.7
1.5
0.6
Axial
spacing
4.6
4.8
4.9
4.6
Response Time
BS 5266pt7/EN 1838 4.2.6,4.3.6
1 Lux
Escape Routes
0.5 Lux
Open Areas
50%
100%
5 secs
60 secs
Full Duration
Acid baths
Steps
Flat floor
Glare Zone
600
Glare Zone
Glare Zone
Up to 2.5m
3.0m
4.0m
5.0m
500
900
2500
5000
Max. Luminous
Intensity
(cd)
Normal lighting
Un-switched supply
Emergency lighting
Places of Entertainment
Minimum duration 3 hours or a rest mode circuit as EN 60598-2-22
System Records
- must be retained for
pr EN 50172 7.
Inspection by Fire Authorities
7. Drawings of the emergency lighting
installation to be provided on the premises.
Signed by a competent person for the design.
7.1 Annually a test certificate to be
provided by person responsible for site
7.2 A log book shall be on the premises
and available for inspection containing Commissioning certificate
Date and result of system tests.
Date and details of service action.
Date and details of any remedial action.
Date and details of any system alterations.
Details of Automatic testing system used.
Records
Luminaires
Inspected for
cleanliness
and
efficiency
status.
Relevant Standards
Emergency Lighting
Product Standard
EN60598-2-22:
1999
Central System
EN 50171 2001
Maintained or non-,maintained
Duration of Luminaires (1 HR min)
BS 5266 -1 1999