LS2 - Variation in Refrigeration Coefficient of Performance at Various Operating Conditions
LS2 - Variation in Refrigeration Coefficient of Performance at Various Operating Conditions
02-20012
QH
.
Wnet
QL
Low Temperature Reservoir, TL
Refrigeration duty is another term for the cooling effect of the refrigeration system, which is the rate
of heat being removed from the low temperature region with specified evaporation and
condensation temperatures. The unit for duty measurements is in Watts (for 1 ton of
refrigeration = 3517W).
Condensation of the high pressure vapour during which heat is transferred to the
high temperature region.
Adiabatic throttling of the condensed vapour from the condensing to the
evaporating pressure.
Evaporation of the low pressure liquid during which heat is absorbed from the low
temperature source.
Isentropic compression of the vapour, from the evaporating to the condensing
pressures.
Expansion Valve
q2-3 = h3 h2 + w
w = 0, therefore q 2-3 = h2 h3 and process is assumed adiabatic q 0
therefore h2 = h3
Evaporator
q34 = h4 h3 + w
w = 0 therefore q34 = h4 h3 and rate of heat absorbed Q34 = ( h4 h3 )
COPref =
q3 4
h4 h3
=
w
h1 h4
6. PROCEDURES
6a) Condenser-water and evaporator-water
a. Select water as a heat source by opening valves AVS-4 and AVS-5.Then click START
b. Adjust the water flow rate at the condenser to 5 L/m and 3 L/m at the evaporator
(evaporator load).
c. Then click COMPRESSOR
d. When the system is stabilized, start recording the data by click START SAVING
e. Set the sampling rate at 120 second per sample.
f. Record the data for six minutes (3 samples @ 360 second). STOP SAVING
g. Then increase evaporator load to 5 L/m and repeat step (c) to step (f).
6b) Condenser-water and evaporator-air
a. Select air as a heat source by opening valves AVS-3 and AVS-5.Then click START
b. Adjust the water flow rate at the condenser to 5 L/m and adjust the air flow of the
evaporator until 50% of the maximal flow (evaporator load).
c. Then click COMPRESSOR
d. When the system is stabilized, start recording the data by click START SAVING
e. Set the sampling rate at 120 second per sample.
f. Record the data for six minutes (3 samples @ 360 second). STOP SAVING
g. Then increase evaporator load to 100% and repeat step (c) to step (f).
6c) Condenser-air and evaporator-air
a. Select air as a heat source by opening valves AVS-3 and AVS-6. Then click START
b. Adjust the air flow of the condenser to maximum flow (100%) and 50% of the maximal
flow at the evaporator (evaporator load).
c. Then click COMPRESSOR
d. When the system is stabilized, start recording the data by click START SAVING
e. Set the sampling rate at 120 second per sample.
f. Record the data for six minutes (3 samples @ 360 second). STOP SAVING
g. Then increase evaporator load to 100% and repeat step (c) to step (f).
6d) Condenser-air and evaporator-water
a. Select water as a heat source by opening valves AVS-4 and AVS-6.Then click START
b. Adjust the air flow of the condenser to maximum flow (100%) and adjust the water flow
rate at the evaporator to 3 L/m (evaporator load).
c. Then click COMPRESSOR
d. When the system is stabilized, start recording the data by click START SAVING
e. Set the sampling rate at 120 second per sample.
f. Record the data for six minutes (3 samples @ 360 second). STOP SAVING
g. Then increase evaporator load to 5 L/m and repeat step (c) to step (f).
By using data obtained from the experiments, show sample calculations of the parameters
below and complete the results summary table.
(a)
(b)
(c)
(d)
Average COPref
240
360
240
360
Cond - Water
Evap - Water
Cond - Water
Evap - Air
SC-2 = 5 L/m
Cond - Air
Evap - Air
Cond - Air
Evap - Water
120
SC-2 = 5 L/m
120
Time (s)
360
SC-3 = 5 L/m
240
120
SC-3 = 3 L/m
360
120
Fan power at
evap. = 100%
240
Fan power at
evap. = 50%
360
Fan power at
evap. = 100%
240
Fan power at
evap. = 50%
360
SC-3 = 5 L/m
240
SC-3 = 3 L/m
360
120
Evaporator
heat load
240
120
Condenser
cooling load
360
120
a
Working fluid
Exp #
240
120
SW-1
(W)
SC-1
(L/h)
SP-2
(bar)
SP-1
(bar)
ST-4
(oC)
ST-3
(oC)
ST-2
(oC)
Time (s)
Exp #
Vref
(m3/s)
v2 (table)
(m3/kg)
mref (kg/s)
= Vref/v2
h3 (kJ/kg)
h4 (kJ/kg)
Qevap (kW)
= mref (h4 h 3)
120
240
360
Average COP
a
120
240
360
Average COP
120
240
360
Average COP
b
120
240
360
Average COP
120
240
360
Average COP
c
120
240
360
Average COP
120
240
360
Average COP
d
120
240
360
Average COP
COP =
Qevap/ (SW1/1000)
b.
What is the effect of cooling medium on the average refrigeration COP? Why?
c.
What do you understand by the term load? Give examples of actual loads in refrigeration
practice in a domestic fridge, in a room, and in a factory.
d.