HVAC Sequence of Operations
HVAC Sequence of Operations
CEE 243
Copyright 2012
Big idea
Modern energy management systems include a
combination of passive and active control of energy
distribution
Passive: constant (volume/flow)
Active: variable (volume/flow) under computer
control
Based on If-then conditional control rules of
general form
If setpoint value out of range and
Other conditions met
Then adjust control variable value
CEE 243
2
Copyright 2012
Jargon
Active beam
AHU
CAV
Cfm
Condition
Diffuser
Diff pressure
Fabric loss
Fan coil
Heat exchanger
JK-1
Natural ventilation
Radiant slab
Setpoint
Tempered hot/cold
water
U value
VAV
Zone
Zone splitter
CEE 243
3
Copyright 2012
Control basics
Typically active response components have a setpoint,
i.e., operating functional objective value
E.g., room temperature setpoint = 73 +- 3oF
Under computer control, the HVAC building management
system (BMS) adjusts value of active control components
to maintain the setpoint of response components
e.g., flow rate damper position = 0 100% open
BMS rules tell control system how to reach setpoint
BMS is linked to input sensors and output control signals
CEE 243
4
Copyright 2012
Heating similar
Reason for efficiency: heat capacity of
water >> that of air: 1 cubic foot
Air: heat capacity 37 JK-1
Water: heat capacity 20,050 JK-1.
heat/cool with much lower pumped
volume in smaller components
CEE 243
5
Copyright 2012
Heat if SP < 71 F
Cool if SP > 75 F
Deadband +/- 2 F
CEE 243
6
Copyright 2012
(Direct)
Response
variable
Deadband control
1000
120
900
100
700
80
600
500
400
60
Deadband
40
300
800
Control
variable
Air Flow
Cooling Valve
Heating Valve
200
20
100
0
0
65 66 67 68 69 70 71 72 73 74 75 76 77 78 79 80 81 82 83 84 85
Temperature degrees F
CEE 243
Setpoint
7
Copyright 2012
Active beams
Active (control) components: Cold and hot water valves, air
flow damper
Temperature control examples:
Occupied room air temperature setpoint user adjustable +/- 3F
Unoccupied setpoints: cooling =78F; heating = 65F
Control cold and/or hot water active beam valve position to
achieve room air temperature setpoint
Temperature control deadband of +/- 2F
User override can extend occupied hours by 2 hours
8
Copyright 2012
9
Copyright 2012
Baseboard radiators
Active components: hot water control valve
Temperature control examples:
Occupied temperature setpoint adjustable by
user +/- 3F
Unoccupied heating temperature setpoint: 65F
Control hot water valve position of baseboard
heater to achieve room air temperature setpoint
If outside air temperature > 78F close valve
at all times
User override extends occupied hours 2 hours
CEE 243
10
Copyright 2012
Conference rooms
Active beam control as in other rooms
Active component: inline supply fan
Additional CO2 level control
If CO2 concentration > max CO2 setpoint
open inline supply fan
Max CO2 setpoint = 500 ppm above outside
air CO2 concentration
CEE 243
11
Copyright 2012
Laboratories
Active components: damper, water coil valves
Air flow control
The greater of:
The required air changes (6 air changes/hr)
Amount needed for cooling
Sufficient makeup air for fume hoods (supply ~ exhaust)
Temperature control
+/- 2F deadband
CEE 243
12
Copyright 2012
Radiant floor
CEE 243
13
Copyright 2012
Radiant floor
Active components: Pump and valve
Pump off if outside air temperature > 78F
Otherwise
Turn on pump
To reach steady state:
Increase valve position by 10% (every 10 min) until
temperature setpoint of 71F is met
Decrease valve position by 5% (every 10 min) until
temperature setpoint of 71F is met
CEE 243
14
Copyright 2012
CEE 243
15
Copyright 2012
16
Copyright 2012
Serves:
Tempered water loop
Cooling coils
(AHU, FC, CVs, VAVs)
Server Rack
CEE 243
17
Copyright 2012
18
Copyright 2012
Serves:
Active beams
CEE 243
19
Copyright 2012
20
Copyright 2012
CEE 243
Serves:
Tempered water loop
Heating coils
(AHU, CVs)
Radiators
21
Copyright 2012
Temperature control
Maintain supply water temperature at 180F by
opening and closing value 1 (1/3 of flow) and
valve 2 (2/3 of flow)
CEE 243
22
Copyright 2012
CEE 243
Serves:
Tempered water loop
Heating coils
(AHU, CVs)
Radiators
23
Copyright 2012
Temperature control
Maintain supply water temperature at 110F
by opening and closing value
CEE 243
24
Copyright 2012
CEE 243
25
Copyright 2012
26
Copyright 2012
27
Copyright 2012
28
Copyright 2012
29
Copyright 2012
CEE 243
30
Copyright 2012
CEE 243
31
Copyright 2012
Cooling
if 1. Cool
HP
And 2. if
Intended
HP
damper
then 3. h
HP bypass damper position
the heat
damper
position
closed
closed
closed
closed
closed
closed
closed
closed
closed
closed
closed
position
OK?
OK
OK
OK
OK
OK
OK
OK
OK
OK
OK
OK
always
OK?
Ok
32
Copyright 2012
Cooling
if 1. Cooling coi
And 2. if the ou
then 3. heat pip
the heat pipe &
33
Copyright 2012
Mechanical ventilation
CEE 243
34
Copyright 2012
35
Copyright 2012
Natural ventilation
CEE 243
36
Copyright 2012
Natural ventilation
Active components: Operable windows, atria damper
Initial range for natural ventilation outside air temperature 68 85F
If outdoor temperature is within range & average space
temperature > 70F -> open dampers
For each zone where temperature > 70F open operable
windows
If zone temperature < 70F for at least 5 min close windows
If all windows around one atrium are closed close
corresponding atrium damper
Night purge (if daytime outside air temperature exceeds 75F)
During unoccupied hours open windows if Outside air
temperature < 65F and space temperature > 65F Close
windows if space temperature < 63F
CEE 243
37
Copyright 2012
CEE 243
38
Copyright 2012
CEE 243
39
Copyright 2012
Step 1
All Ok
Step 2
Synthesize functional
intent and data context
All Ok
Step 3
Summary assessment
All Ok
Step 4
Step 5
Else
All Ok
Step 6
CEE 243
All Ok
End
Steps 1-5 to
Clarify
40
Copyright 2012
Reading
ACCO engineered systems, HVAC Sequences of
Operation for Stanford SEQ2 Environment and Energy
Building, 2007
Abram, T., J. Kunz, J. ODonnell, and M. Garr, Energy
Performance Analyses of a Santa Clara County Facility
by CEE243 Student Groups, CIFE Technical Report
#TR204, 2011
CEE 243
41
Copyright 2012
Homework
For an assigned system, compare
patterns between different years (2008,
2009, 2010)
Classify pattern (red/yellow/green) re
assumed functional intent
CEE 243
42
Copyright 2012
Big idea
Modern energy management systems include a
combination of passive and active control of energy
distribution
Passive: constant (volume/flow)
Active: variable (volume/flow) under computer
control
Based on If-then conditional control rules of
general form
If setpoint value out of range and
Other conditions met
Then adjust control variable value
CEE 243
43
Copyright 2012