Control Sequences For HVAC
Control Sequences For HVAC
Control Sequences For HVAC
Design Standards
PART 1. GENERAL
1.04 SUBMITTALS
A. Refer to Section 25 5500 and Division 01 for submittal requirements for
control shop drawings and what is to be contained in them.
1. Occupied Period: The period of time when the area served by the specific
control system or zone is in use and occupied. Unless indicated otherwise,
this is the default period and is defined as 6:00 AM to 6:00 PM 7 days per
PART 2. PRODUCTS
PART 3. EXECUTION
3.02 GENERAL
Provide building level software button for all systems to shutdown per
building, and campus level software button for all system on campus to
shutdown. Integrate manual shutdown button in central plant with campus
level shutdown sequence.
B. Logic Strategies: The BAS shall fully control the air handlers. Generally,
the BAS shall energize the AHU (start the fans and activate control loops)
as dictated for each air handler. The following indicates when and how the
BAS shall energize the AHUs and control various common aspects of
them:
1. Scheduled Occupancy: BAS shall determine the occupancy periods
(occupied, unoccupied, preoccupancy, and setback) as defined above.
The following details the common control aspects related to the
scheduled occupancy.
a) Occupied Period: BAS shall energize the AHU during all occupied
periods. Note that the beginning of the occupancy period shall be
set sufficiently before the actual start of occupancy to obtain the
required building component of ventilation per ASHREA 62.
Minimum OA flow setpoint shall be as scheduled on the drawings.
“Normal” setpoints shall apply.
b) Unoccupied Period: Minimum OA flow shall be 0 CFM or the
minimum OA damper position shall be 0%. If during the unoccupied
period there is a request for occupancy override, the occupancy
mode shall become active for an adjustable period. The
unoccupied period and the preoccupancy period will typically
overlap.
c) Setback Period: the BAS shall deenergize the unit except as
required to maintain a setback temperature as indicated in the
individual sequences with a 5°F cycle differential. Generally, where
setback temperatures apply in multiple zones, the worst zone shall
control the system. Setback setpoints generally apply except
during preoccupancy [and night purge]. If during the unoccupied
period there is a request for occupancy override, the occupancy
mode shall become active for an adjustable period.
d) Preoccupancy: BAS shall energize the AH continuously during the
preoccupancy period. Minimum OA flow shall be 0 CFM or the
minimum OA damper position shall be 0%. “Normal” setpoints shall
apply. Preoccupancy duration shall be one of the following as
specified by reference:
1) Fixed: The duration of the preoccupancy period shall be fixed
as scheduled by the operator.
2) Optimum: The duration of the morning warm-up period shall
vary according to outside air temperature and space
temperature such that the space temperature rises to
a) Dry Bulb Switch: Economizer mode shall be active while the unit is
energized AND when outside air temperature falls below the
switching setpoint of 55°F (adj.) (with 5F cycle differential).
Economizer mode shall be inactive when outside air temperature
rises above switching setpoint, dampers shall return to their
scheduled minimum positions as specified above.
5. Sequenced Heating and Cooling: BAS shall control the heating and
cooling coils and air side economizer as detailed for the AH. Program
logic shall directly prohibit the heating and cooling valves as well as the
heating valve and economizer damper to be open (or above minimum)
simultaneously. This does not apply to cooling and reheat valves that
are used simultaneously for dehumidification.
6. Mixed Air Low Limit Override: BAS shall override the signal to the OA
damper via a proportional only loop to maintain a minimum mixed air
temperature of 45°F (adj.) (loop shall output 0% at 45°F which shall be
passed to the output via a low selector).
7. Freeze Safety: Upon operation of a freezestat the following sequence
shall occur:
a) The unit fans shall be deenergized. Typically supply and return
fans where applicable shall be deenergized via a hardwired
interlock, and an indication of the operation shall be displayed by
the BAS.
b) All hot water valves and chilled water valves will be commanded to
100% open. Steam preheat valves shall modulate to maintain
minimum preheat/mixed air plenum temperature.
c) All hot water coil pumps and chilled water coil pumps will be
commanded to run.
d) Outside air dampers shall fully close and return air dampers shall
fully open.
e) BAS shall enunciate appropriate alarm and remove and lock out the
start command, which shall initiate "fan failure" alarms.
8. Smoke Safety: Upon indication of smoke by a smoke detector, FAC
shall override all AH control. FAC shall not rely on BAS for
implementation of smoke control sequences unless specifically
approved. Smoke detector shall notify the fire alarm system and BAS,
shut down the fans, and close the smoke dampers via hard-wired
interlock.
9. Smoke Pressurization Cycle: When pressurization is commanded by
the interface to the fire alarm system, supply fan shall start and deliver
100% outside air to the space. Return fan shall remain off. Hardwired
interlock from safeties may still interrupt fan operation. (See damper
D. Coordinate which loads are available for shedding with the Owner.
E. Load shedding commands priority:
1. The first load shed command shall reset terminal level equipment space
temperature set points to their set back values over a [5] minute (adj.)
period.
2. The second load shed command shall reset VAV air handler down duct
static set points to their minimum value over a [10] minute (adj.) period.
3. The third load shed command shall reset central plant equipment to their
minimum capacity set points over a [30] minute (adj.) period.
E. Proof of Chiller Operation: BAS shall prove the operation of the chillers via
chiller status and alarm points. When a chiller is assessed as failed, the
run command shall be locked out and shall require manual
acknowledgment at the operator interface before it is restarted. BAS shall
then start the next chiller in rotation. The following conditions shall result
in the assessment that the chiller has failed:
1. Loss of chiller status for more than 15s (adj.) while it is requested.
2. Closure of chiller failure input.
3. Leaving chilled water temperature exceeds chiller setpoint plus 8°F for
10 min. continuously.
4. Chiller environment is unacceptable for 10 min. as specified below.
F. Chiller Environment Monitoring: BAS shall monitor the “environment” of all
active (not starting or stopping) chillers and remove the run command
when the environment is assessed as unacceptable. An unacceptable
environment will include any of the following:
1. Loss of status on the associated primary pump (pump proof debounce
time shall not apply).
2. Condenser water entering temperature below CHW supply plus 12°F
or above 100°F.
3. Condenser water flow below a minimum setpoint GPM where such
flow is measured.
4. Chilled water flow below a minimum setpoint GPM.
G. When the environment is assessed as unacceptable, the BAS shall
enunciate an alarm, remove chiller run command (not the chiller request;
all supporting equipment shall continue to operate) and start a timer. If the
environment is still unacceptable after 10 min. (adj.), fail the chiller.
H. Chiller Request: A chiller request is the request for a chiller and the
associated equipment. A chiller request is issued before the actual run
command to the chiller, which is the closure of the physical point that
enables the chiller.
I. Chilled Water Temperature Control: The chilled water temperature shall be
controlled as specified below.
A. BAS shall control the starting and stopping of chillers to meet the
demands of the [secondary] chilled water systems. Whenever cooling is
requested, a minimum of one chiller shall be requested. Chillers shall be
started per the chiller start sequence and stopped per the chiller stop
sequence specified below.
Once the conditions merit starting or stopping a chiller, BAS shall
complete the starting or stopping sequence regardless of temperature
fluctuations during the sequence. Additional chillers shall be started
based on SCHW load as follows:
1. An additional chiller shall be requested and started per the chiller start
sequence specified below when:
a. The average cooling load rises above 90% of the nominal capacity
of the active chillers for 5 min. (adj.) continuously, AND
b. More than 30 min. (adj.) has elapsed since the start of the last
chiller.
2. Chillers shall be stopped, per the chiller stop sequence specified below,
based on the averaged cooling load as follows:
a. One chiller shall be stopped when the load falls below (Total
Nominal Capacity-(Nominal Capacity of Last Chiller) * 1.2), AND
2. Drive shall be configured for auto-restart on power return when the run
command is indicated.
5. Drive shall be configured such that upon loss of BAS speed reference
signal the drive shall stop.
6. Preset speed signal shall be set up to limit the operating speed of the
drive to an adjustable parameter (typically 25 Hz) when there is an
open contact across it. This value shall be adjusted during Cx to
ensure smooth transitions into an operating header and a safe
pressure against the dead head of the dampers.
and the supply discharge damper via a “drive running” output. The
drive shall limit the speed of the fan to the safe preset speed
(programmed in the drive) until all dampers are proven open. Once
the damper end switches prove open dampers, the drive shall allow
the fan to accelerate at the controlled rate to the BAS drive
reference signal that is sent via hard-wired interface from the BAS.
b) In HAND Mode: The same logic shall apply as VFD Mode when the
drive speed signal is in HAND mode and manually controlled
through the VFD panel. Preset speed limit shall apply whenever
the Inverter is active.
- END OF SECTION -