PCS-931 MY Instruction Manual en General X R1.00 (En XLBH5104.0060.1101)
PCS-931 MY Instruction Manual en General X R1.00 (En XLBH5104.0060.1101)
PCS-931 MY Instruction Manual en General X R1.00 (En XLBH5104.0060.1101)
Preface
Introduction
This guide and the relevant operating or service manual documentation for the equipment provide
full information on safe handling, commissioning and testing of this equipment.
Documentation for equipment ordered from NARI-RELAYS is dispatched separately from
manufactured goods and may not be received at the same time. Therefore, this guide is provided
to ensure that printed information normally present on equipment is fully understood by the
recipient.
Before carrying out any work on the equipment, the user should be familiar with the contents of
this manual, and read relevant chapter carefully.
This chapter describes the safety precautions recommended when using the equipment. Before
installing and using the equipment, this chapter must be thoroughly read and understood.
Are familiar with the installation, commissioning, and operation of the equipment and of the
system to which it is being connected;
Are able to safely perform switching operations in accordance with accepted safety
engineering practices and are authorized to energize and de-energize equipment and to
isolate, ground, and label it;
Are trained in the care and use of safety apparatus in accordance with safety engineering
practices;
ii
Exposed terminals
Do not touch the exposed terminals of this equipment while the power is on, as the high voltage
generated is dangerous
z
Residual voltage
Hazardous voltage can be present in the DC circuit just after switching off the DC power supply. It
takes a few seconds for the voltage to discharge.
CAUTION!
z
Earth
Operating environment
The equipment must only be used within the range of ambient environment detailed in the
specification and in an environment free of abnormal vibration.
z
Ratings
Before applying AC voltage and current or the DC power supply to the equipment, check that they
conform to the equipment ratings.
z
Do not attach and remove printed circuit boards when DC power to the equipment is on, as this
may cause the equipment to malfunction.
z
External circuit
When connecting the output contacts of the equipment to an external circuit, carefully check the
supply voltage used in order to prevent the connected circuit from overheating.
z
Connection cable
Copyright
Manual: V1.00
P/N: EN_XLBH5104.0060.1101
Copyright NR 2009. All rights reserved
We reserve all rights to this document and to the information
contained herein. Improper use in particular reproduction and
dissemination to third parties is strictly forbidden except where
expressly authorized.
iii
Table of Contents
Preface ....................................................................................................................................... i
Introduction........................................................................................................................ i
Health and Safety .............................................................................................................. i
Instructions and Warnings ...............................................................................................ii
Table of Contents .....................................................................................................................iv
Chapter 1 Introduction .............................................................................................................1
1.1 Application ...................................................................................................................1
1.2 Function .......................................................................................................................2
1.3 Features........................................................................................................................3
Chapter 2 Technical Data .........................................................................................................5
2.1 Electrical Specifications .............................................................................................5
2.1.1 Analog Input Ratings.........................................................................................5
2.1.2 Power Supply .....................................................................................................5
2.1.3 Binary Input .......................................................................................................6
2.1.4 Binary Output.....................................................................................................6
2.1.5 Power Supply Output for Opto-coupler ...........................................................6
2.2 Mechanical Specifications ..........................................................................................6
2.3 Ambient Temperature and Humidity Range ..............................................................7
2.4 Communication Port ...................................................................................................7
2.4.1 Communication Port for RTU/SCADA .............................................................7
2.4.2 Communication Port for Print ..........................................................................8
2.4.3 RS-485 for Clock Synchronization ...................................................................8
2.5 Type Tests ....................................................................................................................8
2.5.1 Environmental Tests ..........................................................................................8
2.5.2 Mechanical Tests ...............................................................................................8
2.5.3 Electrical Tests ..................................................................................................8
2.5.4 Electromagnetic Compatibility .........................................................................9
2.6 Certifications ..............................................................................................................10
iv
vii
ix
xi
xii
Chapter 1 Introduction
Chapter 1 Introduction
1.1 Application
The PCS-931 is a digital EHV line differential relay with the main and back-up protection functions,
which mainly is designed for transmission line of 220KV and above.
PCS-931
PCS-931
Chapter 1 Introduction
PCS-931 can implement single-phase or three-phase trip and configurable auto-reclosing that can
implement 1-pole AR, 3-poles AR and 1/3-pole AR.
1.2 Function
1.
Main protection
2.
Backup protection
3.
Additional function
Auto-reclosing (79)
Chapter 1 Introduction
1.3 Features
1.
Chapter 1 Introduction
The unique DPFC distance element is integrated in the protective device, which can clear the
internal fault quickly with high sensitivity and high speed and is not affected by power swing.
Self-adaptive floating threshold which only reflects deviation of power frequency component
can defend system imbalance and system disturbance. Hence, it is both rather reliable and
very fast, and it is very sensitive but does not pickup frequently.
Main protection adopts integral transform to ensure high-speed; Back-up protection adopts
Fourier transform, which has an excellent filtering result, to ensure accuracy.
24 samples per cycle, all task including data measurement, protection calculation, logic
discrimination, event recording and protection logic calculation could be done within one
sampling period.
GPS clock synchronization PPS (pulse per second), PPM (pulse per minute) and IRIG-B
synchronization
2.
Communication
2~4 optional Ethernet ports, IEC 61850, or IEC 60870-5-103 over TCP/IP
3.
Event Recorder including 1024 tripping report, 1024 binary input change reports, 1024
self-supervision reports and 1024 control reports.
Disturbance recorder including 64 fault reports with waveforms (The file format of disturbance
recorder is compatible with international COMTRADE file.)
4.
User Interface
Friendly HMI interface with 320240-dot LCD and 9-button keypad on the front panel.
Analog current
Standard
IEC 60255-27:2005
Phase rotation
ABC
Nominal frequency
505Hz, 605Hz
Rated Current
1A
5A
Linear to
0.05In~40In
0.05In~40In
Thermal withstand
-continuously
-for 10s
-for 1s
-for half a cycle
4In
30In
100In
250In
4In
30In
100In
250In
Burden
2.
Analog voltage
Standard
IEC 60255-6:1988
100V, 110V
200V
Linear to
0.01Un~1.7Un
0.01Un~1.7Un
Thermal withstand
-continuously
-10s
-1s
2Un
2.6Un
3Un
1.1Un
1.9Un
2.1Un
Burden at rated
IEC 60255-11:2008
Rated Voltage
110V/125V, 220V/250V
Variation
80%Un~120%Un
Permissible AC ripple
voltage
Voltage
interruptions
short
Voltage dips
Burden
Quiescent condition
Operating condition
<20W
<25W
Maximal
voltage
pickup
70%Un
Minimum
voltage
dropout
55%Un
Maximum permissible
voltage
120%Un
Withstand
2000VAC, 3000VDC
Resolving
logic input
time
for
<1ms
Tripping contact
Output mode
Continuous carry
8A@250V AC
5A@30V DC
8A
Pickup time
<5ms
<10ms
Breaking capacity
0.05A@110V DC resistance
0.2A@220V DC resistance
Making
(L/R=40ms)
2000VA
3040VA
250V AC
30V DC
380V AC
250V DC
30A@0.5S
35A@0.5S
capacity
Maximal
voltage
system
Signal contact
IEC 60255-1
Rated Voltage
24V
Rated Current
200mA
Maximal current
500mA
Enclosure dimensions
(WHD)
Mounting Way
Flush mounted
Trepanning
dimensions (WH)
450179, M6 screw
Housing color
Silver grey
Approx. 20kg
Display language
English
Housing material
Aluminum
Location of terminal
Protection class
Standard
IEC 60225-1:2007
Front side
Other sides
IP30
IP20
IEC 60225-1:2007
Operating
temperature
-25C to +55C
-40C to +70C
Permissible humidity
Electrical
RS-485
(EIA)
Optical
(Optional)
Ethernet
Electrical
Port number
Baud rate
4800,9600,19200,38400,57600,115200
Transmission distance
<1000m@4800bps
Maximal capacity
32
Twisted pair
Protocol
IEC 60870-5-103:1997
Safety level
Port number
Connector type
ST
Baud rate
4800,9600,19200,38400,57600,115200
Transmission standard
100Base-FX
Transmission distance
<1500m
Multi-mode fibre
Wave length
850/820nm
Fibre size
Protocol
Safety level
Port number
Connector type
RJ-45
Transmission rate
100Mbits/s
Optical
(Optional)
Transmission standard
100Base-TX
Transmission distance
<100m
Protocol
Safety level
Port number
Connector type
SC
Transmission rate
100Mbits
Transmission standard
100Base-TX
Transmission distance
<1500m
Multi-mode or single-mode
Wave length
Fibre size
Protocol
Safety level
RS-232 (EIA)
Prot number
Baud Rate
Printer type
Safety level
RS-485 (EIA)
Port number
Transmission distance
<500m
Maximal capacity
32
Timing standard
PPS, IRIG-B
Safety level
Per IEC60068-2-1:2007
Per IEC60068-2-2:2007
Per IEC60068-2-30:2005
IEC 60255-27:2005
NANJING NARI-RELAYS ELECTRIC CO., LTD
Dielectric tests
Standard
IEC 60255-5:2000
Insulation resistance
measurements
Electrostatic
discharge test
Radio
frequency
interference tests
Fast
transient
disturbance tests
Conducted
Electromagnetic
Disturbance
Power
Magnetic
Immunity
RF
Frequency
Field
oscillatory
field
2.6 Certifications
z
ISO9001: 2000
ISO14001:2004
OHSAS18001: 1999
ISO10012:2003
CMMI L3
Send power:
-14.02.0 dBm
Receive sensitivity:
-35 dBm
<40kM
>-8 dBm
Using dedicated channel and transmission distance is greater than 40kM, PCS-931 is equipped
with 1550nm laser emitter.
FO type:
Send power:
-14.02.0 dBm
Receive sensitivity:
-35 dBm
<100kM
>-8 dBm
0.1In~0.5In
Accuracy:
10
0.1In~0.5In
Accuracy:
<5ms
<25ms
Operating time:
<10ms (UOP>2UZ)
Accuracy:
Time delay:
0s~10s
Accuracy:
1%Setting+40ms
Operating time:
20ms (Zone 1)
0.1In~20In
Accuracy:
Time delay:
0s~10s
Accuracy:
1%Setting+40ms
0.1In~20In
Accuracy:
Time delay:
0s~10s
Accuracy:
1%Setting+40ms
0.1In~20In
Accuracy:
Time delay:
0.5s~10s
11
Accuracy:
0.01s~10s
Accuracy:
1%Setting+40ms
2.7.12 Auto-Reclosing
Item
Range
Accuracy
Frequency difference
0.01~1.00 Hz
0.01 Hz
Phase difference
0~89 deg
2.0 deg
Voltage difference
0.02~0.8Un
1.0% Un
Item
Range
Reclosing time
0.01~50
0.01~50
0.01~250
0.01~250
0.01~250
Reset time
0.01~250
12
Accuracy
0.5%10ms
If any of the above fault detector elements operates, the GFD will operate to provide DC power
supply to the output relays to enable the output circuit.
(Equation 3.2-1)
13
Where:
IMAX: The maximum half-wave integration value of phase-to-phase current
ISet: The fixed threshold value (i.e. the setting [I_DPFC_OC_FD])
ITh: The floating threshold value
If operating condition is met, DPFC overcurrent element will operate to provide DC power supply
for output relay, and pickup signal will be kept 7 seconds after DPFC overcurrent element drops
out.
phase-to-phase voltage of VT. (UN means phase voltage; UNN means phase-to-phase
voltage)
ZZD
ZS+ZK
ZK
-ZS
15
a fault occurs in forward direction, which is the circle with the Zs as the center and theZs+Zzd
as the radius. When measured impedance Zk is in the circle, the DPFC distance element will
operate. The DPFC distance element has a large capability of enduring fault resistance. When
there is infeed current from power source at the other end in the fault resistance, the phase of IN
is the same as I and the phase of voltage of fault resistance is same as I, so the fault resistance
appears resistive and is in parallel with R axes. The overreaching problem that results from infeed
current can be prevented.
16
protection device can flexibly select dedicated optical fibre channel or multiplex channel. The
protection device can calculate channel delay in real time, and adjust sample instant to ensure
synchronism sampling of each end based on channel delay. The channel delay is calculated on
the premise that the routine of both directions (receiving and sending) shall be same to each other.
The communication rate used by protection device is 2048kbit/s. The maximum one-way channel
propagation delay is 20ms. A transfer trip and two transfer signals can be transmitted to the
remote end to fulfill some auxiliary functions via a communication channel.
Through capacitive current compensation, the sensitivity of current differential protection is
improved. Because capacitive current compensation depends on voltage, capacitive current
compensation will be disabled automatically if no voltage is input or VT circuit fails.
IDiff > IH
Equation 3.5-1
Where:
IDiff : The DPFC differential current ( IDiff = &IM + &IN )
1.5UN
)
X C1L
17
Operation criteria:
IDiff > 0.75 IBias
IDiff > IQ
Equation 3.5-2
Where:
IQ : Max([I_Diff],
1.25UN
)
X C1L
k=1
k=0.75
IQ
IBias
18
25ms.
3.5.2.3 Steady-state Current Differential Element (stage 1)
Operation criteria :
IDiff > 0.6 IBias
IDiff > IH
Equation 3.5-3
Where:
IDiff : The phase differential current ( IDiff = &IM + &IN )
IBias : The phase restraint current ( IBias = &IM &IN )
IH : Max(1.5[I_Diff],
1.5UN
)
X C1L
Operation criteria :
IDiff > 0.6 IBias
IDiff > IM
Equation 3.5-4
Where:
IM : Max([I_Diff],
1.25UN
)
X C1L
19
IDiff0 > IM
Equation 3.5-5
Where:
IDiff0 : The zero-sequence differential current
IDiff : The phase differential current
IBias0 : The zero-sequence restraint current ( IBias0 = &IM0 &IN0 )
IM : [I_Diff]
IBias is the same to those mentioned above
20
For the long transmission line whose capacitance current is very large, in order to increase the
sensitivity of zero-sequence current differential element when a ground fault associated with fault
resistance occurs, capacitance current must be compensated to eliminate the effect that
capacitance current has on differential current. The traditional method of compensating
capacitance current can only compensate steady-state capacitance current. However, during the
transient period, such as closing circuit breaker to no-load line, clearing external fault and so on,
there are large transient capacitance current in the line. The traditional method cannot
compensate the capacitance current completely, hence, a new method is available, which can
compensate transient component of capacitance current.
1.
Phase capacitance current of line can be derived from equivalent circuit. For normal operation
condition, closing circuit breaker to no-load line and clearing external fault, not only steady-state
component of capacitance current but also transient component of capacitance current can be
compensated. It can improve the sensitivity of differential protection.
21
For different system frequency, the capacitance current which is shown in above figure can be
calculated by:
ic = C
duc
dt
Equation 3.5-6
Where:
ic : Capacitance current flowing through each capacitance
C : Capacitance value
u c : Voltage between both ends of capacitance
Based on the result of above equation, i.e. Equation 3.5-6, capacitance of each phase can be gained.
2.
Because a part of capacitance current has been compensated by shunt reactor, reactance current
IL must be subtracted from capacitance current calculated by above equation, i.e. Equation 3.5-6.
diL (t)
dt
Equation 3.5-7
To perform integral operation for Equation 3.5-7 from t to t-t, IL can be calculated by:
iL (t) = iL (t - t) +
1
LP
[U (t) U (t)]dt
t t
Equation 3.5-8
Then,
ic = C
3.
duc
iL (t)
dt
Equation 3.5-9
Because capacitance current is very small, the sensitivity of current differential protection can still
22
meet the requirement. The function, capacitance current compensation, will be disabled
automatically if differential current is smaller than 01IN.
3.5.2.7 CT Supervision
If CT circuit failure occurs, delayed alarm will be issued. When CT circuit failure occurs on an end,
the FD and current differential protection on this end might operate at once. However, FD on
another end will not operate and not send any permissive signal of current differential relay.
Therefore, the current differential protection will not maloperate. Meanwhile the healthy end will
issue alarm signal [Alm_Diff_ChA] which will be treated as the same as the alarm [Alm_CTS].
However, if CT circuit failure associated with internal fault or pickup due to system disturbance is
detected, the protective device will show two kinds of behavior.
If logic setting [En_CTSBlkDiff] (differential protection being blocked during CT circuit failure) is set
as 1, the differential protection will be blocked.
If logic setting [En_CTSBlkDiff] is set as 0 and the differential current of the faulty phase is more
than the differential current setting [I_Diff_CTS] during CT circuit failure, the differential protection
will operate with alarm signal being issued at the same time.
3.5.2.8 CT Saturation
The incorrect operating of current differential protection would occur due to transient CT saturation
at the moment when external fault occurs. Hence, the protective device adopts high restraint
coefficient and self-adaptive floating restraint threshold, which can prevent current differential
protection from mal-operation even in serious saturation case.
3.5.2.9 Synchronous Sampling
One of the protection devices on both ends is set as reference end (the end whose ID code is
greater, [ID_Local]>[ID_Remote]) and normally called master; the device on the other end is set
as synchronous end (the end whose ID code is smaller, [ID_Local]<[ID_Remote]) and normally
called slave. The protection device exchanges information of both ends through synchronous
mode. The sampling interval of the reference end is fixed and the synchronous end will adjust
sampling interval at any time until the synchronization condition is satisfied.
The preconditions for synchronous sampling of the protection devices on both ends include:
1.
The maximum time delay of the single-directional transmission of the channel 20ms.
2.
The receiving and sending route of the channel shall be conformable (i.e. the transmission
time delay of the two directions shall be equivalent).
Side S sends a frame of message to side M, and meanwhile records the sending time tss on the
basis of relative clock on side S. When side M receives the message, it will take the relative clock
of the device on side M as the basis to record receiving time tmr of the message, and send a
frame of message to side S at next fixed time, meanwhile take tms-tmr as the content of
NANJING NARI-RELAYS ELECTRIC CO., LTD
23
message. Side S will receive the message from side M at the time tsr and obtain tms-tmr.
Therefore, we can obtain the time delay of the channel Td through calculation:
Td =
(t sr t ss ) (t ms t mr )
2
Measure the sampling time error of the protection devices on both ends through the slave and
adjust the slaves time of sampling pulse according to the time delay of the channel, to realize
synchronous sampling.
The master implements the sampling in fixed interval Tsm and meanwhile sends message to the
slave on the basis of internal clock of the protection device. When the slave receives the message
from the master, it can know the sampling time of the master according to the time delay of the
channel and obtain the sampling time error T of the protection devices on both ends according
to its current sampling time. It is shown in Figure 3.5-9. The slave adjusts the next sampling time to
make T0. When T is less than the error, we can think the protection devices on both ends
realize synchronous sampling.
Depending on the difference of the amount of optic fibre core and the distance permitted to
24
transmit, the protection device can select two modes including dedicated optical fibre channel and
multiplex channel. The multiplex channel is not recommended unless the receiver power does not
meet the requirement due to too long transmission line.
Dedicated 2048kbit/s channel is shown in Figure 3.5-10, Two fibre cores of optical cable are
dedicated to differential protection
Differential
Protection
RX
2048kbit/s
TX
Coaxial cable
Pig Tail
SDH Device
MUX2M
Pig Tail
E1Interface
Optic fibre
communication
net
Master-master mode
Slave-slave mode
Master-slave mode
One of them uses internal clock, the other uses external clock. (Not recommended)
Depending on the logic setting [En_InnClock_ChA], current differential protection selects the
communication clock mode. The inner clock is enabled automatically when the logic setting
[En_InnClock_ChA] is set as 1. Contrarily, the outer clock is enabled automatically when the
NANJING NARI-RELAYS ELECTRIC CO., LTD
25
In order to ensure reliability of protection device when digital communication channel is applied,
providing settings [ID_Local] and [ID_Remote] is used as identity code to distinguish uniquely
protection device in the remote end using same channel.
During normal operation, the identity code of protection device in the end should be different with
that of protection device in the remote end. In addition, it should be different with that of protection
device used to protect other transmission line. In one word, identity code of protection device, i.e.,
the setting [ID_Local], should have uniqueness in the power grid. The setting range is from 0 to
65535. Only under the test mode, they can be set as the same.
The end of which setting [ID_Local] should be same as the [ID_Remote] of the other and the
greater [ID_Local] between the two ends is chosen as a master end for sampling synchronism, the
other is a slave end. If the setting [ID_Local] is set as same as [ID_Remote], that means the
equipment in loopback testing state.
The setting [ID_Local] is packaged in the data frame and send to the remote end of line through
channel. When [ID_Local] received by protection device is same to the setting [ID_Remote] of this
protection device, the message received comes from the remote end of line certainly and is valid,
and protection information involved in message is read. When they are not equal, the message is
thought as invalid and protection information involved in message is ignored. corresponding
alarms [Alm_ID_ChA] and [Alm_ChA] will be issued.
3.5.2.13 Channel Statistics
The protection device has the function of channel statistics and can monitor the channel status on
line. The protection device can form a channel statistic report automatically at 9:00 every day and
the report can be printed for operator to understand the channel quality. The monitoring contents
of channel status are shown as follows, and they can be gained by the menu VALUES
COMM_CH_STATE.
1.
It shows the starting time of the channel status statistics of the protection device in the local end.
2.
It shows the ID information received by the device on this end under present conditions.
4.
26
It shows the calculated data of the channel time delay of the protection device on this end under
present conditions. (unit:us)
5.
It shows the total numbers of the wrong frames of the device on this end from starting time of
channel statistics till now. (the maximum is 65535, counted again from 0 if beyond 65535)
Error frame means that this frame fails in CRC check.
6.
It shows the total numbers of abnormal messages of the device on this end from starting time of
channel statistics till now. (the maximum is 65535, counted again from 0 if beyond 65535)
7.
It shows the total numbers of the invalid frames of the device on this end from starting time of
channel statistics till now. (the maximum is 65535, counted again from 0 if beyond 65535)
8.
messages
from
the
remote
end
of
channel
A,
It shows the total numbers of abnormal messages received from the remote end from starting time
of channel statistics till now. (the maximum is 65535, counted again from 0 if beyond 65535)
9.
It shows the total numbers of seriously error frame seconds of the protection device on this side
from starting time of the channel statistics till now. (the maximum is 65535, counted again from 0 if
beyond 65535)
10. Desynchronizing times of channel A, [N_LossSyn_ChA]
It shows the desynchronizing times of the protection device on this end from starting time of
channel statistics till now. (the maximum is 65535, counted again from 0 if beyond 65535)
27
Where:
DIFF Enable (Local end): local current differential protection is enabled
DIFF Enable (Remote end): remote current differential protection is enabled
IDiff>[I_Diff] (A)
&
Common differential condition (A)
IDiff>0.15IBias (A)
IDiff>[I_Diff] (B)
&
Common differential condition (B)
IDiff>0.15IBias (B)
IDiff>[I_Diff] (C)
&
Common differential condition (C)
IDiff>0.15IBias (C)
Where:
IDiff: differential current
IBias: restraint current
A: phase A
B: phase B
C: phase C
28
&
[En_CTSBlkDiff ]
>=1
CT circuit failure
>=1
[Alm_Diff_ChA]
&
DIFF Enable (Local end)
&
&
Differential condition 1 (A)
Common differential condition (A)
&
Differential condition 1 (B)
Common differential condition (B)
&
Differential condition 1 (C)
Common differential condition (C)
When binary input [EBI_DiffP], virtual binary input [VEBI_DiffP] and logic setting [En_DiffP_ChA]
are all set as 1, the signal DIFF Enable is valid. They can be visible or invisible in the protection
device through configuration based on different project. If they are invisible, the signal DIFF
Enable (Local end) is valid by default.
The signal DIFF Enable (Remote end) is an information from the remote end via optical fibre
channel, which is used to indicate whether current differential protection in the remote end is
enabled or not.
29
&
Op_DPFC_Diff1 (A)
&
Op_DPFC_Diff1 (B)
&
Op_DPFC_Diff1 (C)
>=1
Op_DPFC_Diff1 (B)
Op_DPFC_Diff1
Op_DPFC_Diff1 (C)
Where:
DPFC DIFF1: stage 1 of DPFC differential element
3.5.3.3 DPFC Differential Element (stage 2)
Differential condition 2 (A)
&
0ms
Op_DPFC_Diff2 (A)
25ms
0ms
Op_DPFC_Diff2 (B)
25ms
0ms
Op_DPFC_Diff2 (C)
&
25ms
&
>=1
Op_DPFC_Diff2 (B)
Op_DPFC_Diff2
Op_DPFC_Diff2 (C)
Where:
DPFC DIFF2: stage 2 of DPFC differential element
30
&
Op_Stdy_Diff1 (A)
&
Op_Stdy_Diff1 (B)
&
Op_Stdy_Diff1 (C)
>=1
Op_Stdy_Diff1 (B)
Op_Stdy_Diff1
Op_Stdy_Diff1 (C)
Where:
Steady-state DIFF1: stage 1 of steady-state differential element
3.5.3.5 Steady-state Differential Element (stage 2)
Differential condition 2 (A)
&
0ms
Op_Stdy_Diff2 (A)
25ms
0ms
Op_Stdy_Diff2 (B)
25ms
0ms
Op_Stdy_Diff2 (C)
&
25ms
&
>=1
Op_Stdy_Diff2 (B)
Op_Stdy_Diff2
Op_Stdy_Diff2 (C)
Where:
Steady-state DIFF2: stage 2 of steady-state differential element
31
&
40ms
0ms
Op_REF (A)
40ms
0ms
Op_REF (B)
40ms
0ms
Op_REF (C)
&
&
>=1
Op_REF (B)
Op_REF
Op_REF (C)
&
0ms
Op_PhSeg_RecvTT (A)
10ms
0ms
Op_PhSeg_RecvTT (B)
10ms
0ms
Op_PhSeg_RecvTT (C)
&
10ms
&
>=1
Op_PhSeg_RecvTT
Op_PhSeg_RecvTT (C)
32
At weak infeed end, current fault detector element maybe does not operate, weak infeed logic
determines whether weak infeed condition is met by distinguishing voltage and current conditions.
When three binary inputs [BI_52b_Pha], [BI_52b_Phb] and [BI_52b_Phc] are all energized, the
protection device thinks circuit breaker as be in open position.
33
4s
10s
4s
10s
100ms
>=1
Alm_TT
1s
&
Alm_NoValidFram_ChA
[En_DiffP_ChA]
[ID_Remote]Remote ID (CHA)
100ms
1s
&
Alm_ID_ChA
[En_DiffP_ChA]
Rate of error code >10E-5 (CH A)
10s
10s
&
Alm_CRC_ChA
[En_DiffP_ChA]
Loss data frame (CHA)
&
Fault detector
Alm_OutDiffP_ChA
[En_DiffP_ChA]
Alm_FrameLoss_ChA
>=1
Alm_ID_ChA
DiffP is out of service
Alm_ChA
&
1s
4s
[En_DiffP_ChA]
Common differential condition (A)
>=1
&
10s
10s
Alm_Diff_ChA
&
2s
10s
Alm_CompParam_ChA
Where:
CHA: channel A
Remote ID: received ID from the remote end
DiffP: differential protection
IdiffA: differential current of channel A
34
35
&
ROC DIR+
F0+
F0&
ROC DIR-
&
[En_ROC1]
Op_ROC1
[En_ROC2]
[t_ROC2]
&
Op_ROC2
T1
&
500ms
&
Op_ROC3
Op_ROC4
&
Tripping command
&
Fault detector
&
[En_ROC4_SOTF]
1
[En_Dir_ROC4]
[En_ROC4]
3I0Cal > [I_ROC4]
&
T2
500ms
&
Tripping command
&
Fault detector
&
&
[En_ROC4_SOTF]
Reverse direction
lm=-780
UJ
Forward direction
IJ
t=
( I / I p ) 1
TP
Where:
= Constant
= Constant
t = Operation time
NANJING NARI-RELAYS ELECTRIC CO., LTD
37
I = Measured current
Ip is the current threshold setting; the current setting of the stage 3 of phase overcurrent
protection [I_OC3] is used as the Ip in this relay. If the stage 4 overcurrent protection is used
as IDMT overcurrent protection.
Tp is the time multiplier setting; the time setting of the stage 3 of phase overcurrent protection
[t_OC3] is used as the Tp in this relay. If the stage 3 of phase overcurrent protection is used as
IDMT overcurrent protection.
Three types of IDMT characteristic curves are applied in this relay. The setting [Opt_InvOC3] can
be used to select the expected curve.
Opt_InvOC3
Curve Name
Standard Inverse
0.14
0.02
Very Inverse
13.5
Extremely Inverse
80
[En_Dir_OC1]
Max(IA, IB, IC)> [I_OC1]
&
[t_OC1]
&
[t_OC2]
&
[t_OC3]
Op_OC1
[En_OC1]
1
&
[En_Dir_OC2]
Max(IA, IB, IC)> [I_OC2]
Op_OC2
[En_ROC2]
1
&
[En_Dir_OC3]
Max(IA, IB, IC)> [I_OC3]
Op_OC3
[En_OC3]
38
t(I0 ) = TP (
0.14
)
I
( 0 )0.02 1
IP
Where:
TP : Time constant, i.e. the setting [t_InvROC]
IP : Reference current, i.e. the setting [I_InvROC]
F0+
&
&
[En_Dir_InvROC ]
IDMT
Op_InvROC
[En_InvROC ]
39
Figure 3.6-6 Logic diagram of zero-sequence/phase overcurrent protection when VT circuit failure
Please refer to Chapter 8 about the description of corresponding settings.
All stages of directional zero-sequence overcurrent protection are under the control of
zero-sequence overcurrent element, so the current setting for each stage should be greater than
[I_ROC_FD].
40
When VT circuit failure happens, the alarm [Alm_VTS] displayed, all distance protection
will be disabled.
Distance element with memorized polarization is an algorithm used when positive sequence
voltage reduces to 10% or less. There are only two possibilities for this condition: power swing or
three phase short circuit fault.
As the power swing will be identified by power swing blocking function, only three phase short
circuit should be considered and discussed herein.
Because three phase-to-ground impedance and three phase-to-phase impedance are equal in
case of three phase short circuit fault, so only phase-to-ground impedance should be measured.
Impedances of all three phase are usually equal. Nevertheless, in order to ensure fast tripping
even in the case of transition from bus fault to three phase line fault, all of three phase impedances
are calculated and operation of any phase element will lead to three phase tripping.
3.7.1.2 Operation Characteristic
Distance element with memorized polarization compares phasor angle between operating voltage
and polarized voltage.
1.
41
Figure 3.7-2 shows operation characteristic of measured impedance -ZK on R-X plane. This
characteristic is a circle with line connecting ends of ZZD and Z'S as the diameter. It will operate
only when -ZK is in the circle. Therefore directionality of the protection is explicit.
The conditions mentioned above are before fading of memorized voltage, in another word, they
are transient characteristic.
jX
ZZD
ZK
Figure 3.7-3 Steady state characteristic of three phase short circuit fault
When the memorized voltage fade, Figure 3.7-3 shows operation characteristic of measured
impedance ZK on R-X plane for forward direction fault as well as that of -ZK for reverse direction
fault. Since the circle covers the origin, the equipment will be just on the margin of operation for
fault on the bus or line outlet. In order to prevent the mal-operation for bus fault, especially the
three phase bus fault with arc resistance, zone1 and 2 of distance element is equipped with a
positive threshold. Voltage value of the threshold is equal to maximum voltage drop of the arc.
Moreover, when zone 1 or 2 of distance element operates, phase of the threshold voltage will be
inverted so that the origin can be enclosed in the characteristic circle to ensure the fault can be
fully cleared. In order to ensure backup protection of zone 3, phase of threshold voltage is always
inverted and the origin is always enclosed in the characteristic circle.
1.
Zone 1/2
This element use polarized positive sequence voltage which can improve the performance against
the fault resistance so that it cannot overreach when earth fault associated with high fault
resistance occurs.
43
1=0
ZZD
1=15
1=30
A
R
-ZS
Typical zero-sequence reactance characteristic is shown as the straight line A in Figure 3.7-4.
Therefore, directional impedance characteristic integrating with the zero sequence characteristic
are adaptive with the fault resistance.
Actually, zero sequence reactance characteristic line will incline downward for 12. Therefore, in
an actual system, even if zero sequence impedance angles of both ends of a line are not the same
and the phase difference exists between 3I0Cal and voltage drop on fault resistance, overreach
condition will not happen. If the directional distance element with phase shift 1 and zero
sequence reactance element operate simultaneously, zones 1 and 2 of distance element with
good directionality will operate.
3.
Zone 3
The no-memorized positive sequence voltage is used as polarized voltage because during earth
fault, positive sequence voltage is mainly formed by healthy phase and the phase of positive
sequence voltage is kept as it was before the fault. Therefore, characteristic of zone 3 of
phaseto-earth distance element is the same as the transient characteristic of distance element
with memorized polarization and have a very good directionality.
44
The sensitivity of phase-to-ground distance element with Mho characteristic may be not enough
during ground fault with extreme high resistance. So additional three-zone phase-to-ground
distance element with quadrilateral characteristic is adopted in the equipment to compensate the
sensitivity of Mho characteristic. The logic relationship between quadrilateral distance element and
Mho distance element is OR. It means that any ground fault in one of the two operation zones will
be cleared. The quadrilateral phase-to-ground distance element can significantly improve the
sensitivity to clear ground fault with extreme high resistance. The three zones of quadrilateral
characteristic can be enabled or disabled by the logic setting [En_ZPG1_Quad], [En_ZPG2_Quad]
and [En_ZPG3_Quad] respectively. The operation characteristic of quadrilateral distance element
is shown in Figure 3.7-5:
45
if the voltage is extreme low, the directionality of quadrilateral characteristic is not clear. However,
Mho characteristic of phase-to-ground distance element using polarized positive sequence voltage
has definite directionality. Therefore, In case that phase voltage is lower than 10% of rated voltage,
the quadrilateral characteristic will be disabled automatically and the Mho characteristic is
reserved.
Zone 1,2 of phase-to-phase distance element use polarized positive sequence voltage. Phase
shift 2 is introduced here for polarized voltage in zones 1 and 2 just like 1 in case of
phase-to-ground distance element. It is used also for improving performance against high fault
resistance in short line case. Value of 2 can be set as 0 or 15or 30.
3.7.3.2 Zone 3
If three-phase short circuit fault occurs, since the polarized voltage has not been memorized, its
operation characteristic is a circle passing through the origin (Please refer to Figure 3.7-3). If the
positive sequence voltage is low, the fault will be measured by impedance element with
memorized polarization. There is neither problem about dead zone nor loss of directionality for bus
fault in this case.
ZZD is impedance setting [Z_Rev] of reversal distance element, usually, which is set to 50% of the
protected line. In order to prevent existing dead zone in the protected zone, origin is included in
the operation characteristic which is shifted 0.5 ZZD toward forward direction.
ZZD
R
RZD
RZD
47
operate.
1.
If any of the following condition is matched, FD PSBR will operate for 160ms.
1) Positive sequence current is lower than the setting [I_OC_PSBR] before general fault detector
element operates.
2) Positive sequence current is higher than the setting [I_OC_PSBR] before general fault
detector element operates, but the duration is less than 10ms.
2.
If a three-phase fault occurs and FD PSBR is invalid (160ms after GFD operates), neither FD
PSBR nor UF PSBR will be able to operate to release the distance protection. Thus, SF PSBR is
provided for this case specially. This detection is based on measuring the voltage at power swing
center:
UOS=U1COS
Where:
: the angle between positive sequence voltage and current
U1: the positive sequence voltage
The criterion of SF PSBR element comprises the following two parts:
4.
When three-phase circuit breaker is in the unsymmetrical state, PD PSBR will operate if any of the
following conditions is met.
48
1)
The faulty phase selected by fault phase selection element is not the phase tripped.
2)
The difference of current deviation of power frequency component between two healthy
phases increases to certain value all of a sudden.
Figure 3.7-8 Logic diagram of PSBR for zone 1 and zone 2 of distance element
The logic setting [En_PSBR] is common for zone 1, 2 of distance element. If the logic setting
[En_PSBR] is set as 0, zone 1 and zone 2 of distance element is not blocked by PSBR and
PSBR for zone 1 and zone 2 of distance element will operate right now (i.e. output state of
[PSBR_Z1/2] is 1).
If the logic setting [En_PSBR] is set as 1, zone 1, 2 of distance element is controlled by PSBR.
After zone 2 of distance element operates and PSBR condition is also met, PSBR for zone 1 and
zone 2 of distance element will operate (i.e., output state of [PSBR_Z1/2] is 1).
49
50
Breaker failure protection consists of two stages. They have independent current setting and time
delay respectively. After short time delay [t_BFP1], local circuit breaker will be tripped. After longer
time delay [t_BFP2], all adjacent circuit breakers connected to the same busbar and line remote
end circuit breaker will be tripped.
Breaker failure protection with phase-segregated current element as auxiliary blocking condition
can be initiated by phase-segregated tripping contacts from line protection and three-phase
tripping contact from other protection device. To increase the reliability of BFP initiated by
phase-segregated tripping contacts from line protection, as phase overcurrent element is possibly
less than load current, zero-sequence overcurrent element can be enabled by the logic setting
[En_ROC_1P_BFP].
In order to increase the sensitivity of breaker failure protection for the fault occurring in the
transformer or shunt reactor and so on, zero-sequence overcurrent and negative-sequence
overcurrent elements can be selected by logic settings separately. When this protective function
operates, the protection device will issue three-phase tripping command to local circuit breaker
after the time delay of stage 1 [t_BFP1] is expired, and then issue tripping command to all adjacent
circuit breakers connected to the same busbar and the circuit breaker in the remote end of
transmission line after the time delay of stage 2 [t_BFP2] is expired.
51
existing fault. This is especially critical if the line in the remote station is grounded, since the
distance protection and directional zero-sequence overcurrent protection would not clear the fault
until their time delays had elapsed. In this situation, however, the fastest possible clearance is
desired.
The SOTF (switch onto fault) protection is a complementary function to the distance protection and
to the directional zero-sequence overcurrent protection. With the SOTF protection, a fast trip is
achieved for a fault on the whole line, when the line is being energized. It shall be responsive to all
types of faults anywhere within the protected line.
The SOTF protection shall be controlled by an reclosing logic using both voltage and current level
detectors. It shall be enabled for a period when the circuit is energized either manually or via a
auto-reclosing system.
100ms
&
Op_ROC_SOTF
Status of 1-pole AR
60ms
53
2.
3.
The logic makes the relay ideal for single-phase tripping applications.
Fault phase
UOPA
Phase A
UOPB
Phase B
UOPC
Phase C
UOPAB
Phase AB
UOPBC
Phase BC
UOPCA
Phase CA
55
Region
Fault phase
-60~60
A phase or BC phase
60~180
B phase or CA phase
180~300
C phase or AB phase
1. For single-phase earth fault, I0 and I2 of faulty phase are in-phase and its distance element
operates.
2. For two-phase earth fault, I0 and I2 of non-faulty phase are in-phase but its distance element
does not operate.
Trip confirmation
Trip confirmation means that tripping signal is issued and any phase current is smaller than 0.06IN
2.
2.
3.
4.
5.
When tripped phase current is greater than 0.06IN or corresponding phase [BI_52b_Phx]=0 (x
can be a, b or c), SOTF protection is initiated for 200ms
56
When threes currents, IA, IB and IC, are greater than 0.06IN or [BI_52b_Pha]=0,
[BI_52b_Phb]=0, [BI_52b_Phc]=0, SOTF protection is initiated for 200ms
2.
3.
Tripping logic 1
57
58
2.
Tripping logic 2
IP>0.06In
SOTF for reclosing manually
&
Op_Perisist1P
1
Op_ROC2
&
[En_ROC2_Blk_AR]
Op_ROC3
&
[En_ROC3_Blk_AR]
Op_ROC4
Op_BFP1
1
Op_BFP2
1
Op_InvROC
Op_OC_VTS
Op_3P_RecvTT
Op_Z2 (Phase-to-phase)
&
[En_ZPP2_Blk_AR]
Op_Z2 (Phase-to-ground)
&
[En_ZPG2_Blk_AR]
Op_Z3
Op_Z_Rev
Op_OC1
&
[En_3PTrpOC1_Blk_AR]
Op_OC2
&
[En_3PTrpOC2_Blk_AR]
Op_OC3
EBI_Lockout
1
PD and protection element operating
59
3.
60
Blocking AR logic
1
1
Op_Perisist1P
Op_OC1
&
[En_3PTrpOC1_Blk_AR]
Op_OC2
&
[En_3PTrpOC2_Blk_AR]
Op_OC3
[En_ZPP2_Blk_AR]
&
Op_Z2 (Phase-to-phase)
[En_ZPG2_Blk_AR]
1
&
Op_Z2 (Phase-to-ground)
Op_Z3
Op_Z_Rev
[En_ROC2_Blk_AR]
&
Op_ROC2
[En_ROC3_Blk_AR]
&
Op_ROC3
Op_ROC4
Op_InvROC
Op_3P_RecvTT
Op_OC_VTS
Op_BFP1
1
1
Op_BFP2
PD and protection element operating
&
[En_PDP_Blk_AR]
[En_PhSF_Blk_AR]
&
Op_PhSelFail
[EBI_Lockout]
Blocking AR
VT circuit failure
61
1.
2.
DPFC distance protection, zone 1 of distance protection and current differential protection
operate to implement selective tripping by phase selection element.
3.
Zone 2 of distance protection operates to trip three-phase circuit breaker and block AR when
logic setting [En_ZPP2_Blk_AR] or [En_ZPG2_Blk_AR] is set as 1 for phase-to-phase fault
or phase-to-ground fault respectively.
4.
5.
6.
Stage 1 of directional phase overcurrent protection operates to trip three-phase circuit breaker
and block AR when logic setting [En_3PTrpOC1_Blk_AR]
7.
Stage 2 of directional phase overcurrent protection operates to trip three-phase circuit breaker
and block AR when logic setting [En_3PTrpOC2_Blk_AR]
8.
If phase selection element fails and operation element cannot drop off, three-pole tripping
command caused by phase selection failure will be sent after 200ms delay.
9.
If any of the following conditions is matched, three-phase tripping signal will be sent directly.
10. Three-phase tripping will be used if two or three phases are selected by the phase selection
element.
11. Any fault occurs under following conditions, three-pole trip element will operate
62
12. When a serious fault occurs, auto-reclosing will be blocked under following conditions:
by
logic
setting
63
The no-voltage check is used to measure the amplitude of line voltage or busbar voltage at both
sides of the circuit breaker; after that, compare it with the voltage setting [V_Live] and the
no-voltage setting [V_Dead]; when the measured result is consistent with the setting, the
no-voltage check conditions can be outputted.
When the frequency difference, voltage difference, and phase difference of voltages of both sides
of the circuit breaker is calculated in the protective device, they can be used as input conditions of
the synchronism check. If the compared voltages at both sides of the circuit breaker are different,
such as, the bus voltage is phase-to-phase voltage and the line voltage is the phase voltage, it is
required to carry out the calculation after the bus voltage has been compensated as the phase
voltage.
The logic setting [En_SynChk_AR] is used to determine whether the synchronism check function
is enabled. When the synchronism check function is enabled and the voltage meets the
requirements of the voltage difference, phase difference, and frequency difference, it is regarded
that the synchronism check conditions are met.
The no-voltage check conditions have three types, namely, live-bus and dead-line check,
64
dead-bus and live-line check and dead-bus and dead-line check. The above three modes can be
enabled and disabled by logic settings [En_LvB_DdL_AR], [En_DdB_LvL_AR] and
[En_DdB_DdL_AR] respectively. The protection can calculate the measured bus voltage and line
voltage at both sides of the circuit breaker and compare them with the voltage setting [V_Live] and
no-voltage setting [V_Dead], when the voltage is higher than the voltage setting [V_Live], the
voltage conditions are established; when the voltage is lower than the no-voltage setting [V_Dead],
the no-voltage conditions are established.
[En_DdB_DdL_AR]
&
[En_LvB_DdL_AR]
&
[t_VoltChk]
VolChk OK
[En_DdB_LvL_AR]
&
ULineLow
ULineHigh
UBusHigh
UBusLow
VT circuit abnormal
65
disappear once the circuit is de-energized. Automatic reclosing systems are put into place to
re-energize and restore the faulted section of the transmission system once the fault is
extinguished (providing it is a temporary fault). For certain transmission systems, reclosing is used
to improve system stability by restoring critical transmission paths as soon as possible.
Before the reclaim time begins, the following conditions must be met:
1.
The circuit breaker is ready, such as, normal storage energy and no low pressure signal
2.
3.
Under normal conditions, if there is the signal input of low pressure, the automatic reclosure will
discharge with the time delay of 200ms. If there is the signal input of low pressure after the circuit
breaker tripping, the automatic reclosure will not discharge.
CB Closed
[t_CBClsd_AR]
[BI_LowPres_AR]
AR Inprogress
Any trip
AR ON
AR Ready
&
AR Block element
Manual tripping
66
The check conditions are not met yet till the incomplete sequence time expires
3.14.2.2 Initiation
When the system is applied with the 1-pole reclosing or the 1/3-pole reclosing, the 1-pole reclosing
will be active during the single phase fault. When only the single phase is tripped, that is, when the
device receives the single phase tripping contact and the contact drops off to initiate 1-pole
reclosing condition, the 1-pole reclosing will be initiated. If the three-phase are tripped or the
three-phase 52b are energized, the 1-pole reclosing shall not be initiated.
Generally, the auto-reclosing is initiated by the tripping signal from line protection, and this
initiating signal can be the interior tripping logic or the exterior tripping command. When there is
the tripping command, it can be kept in the device, and the automatic reclosure will be initiated
NANJING NARI-RELAYS ELECTRIC CO., LTD
67
Single-phase Trip
1
&
1-pole AR Initiation
&
3-pole AR Initiation
Any trip
3-pole AR Initiate
1-pole AR
CB Ready
Reset Logic
&
Three-phase Trip
1
Any trip
3-pole AR
CB Ready
When the time of the reclosing expires, as far as the 3-pole reclosing, if the synchronism check is
enabled, the reclosing signal shall be determined whether is issued or not based on the result of
synchronism check. When the synchronism check function is disabled, the synchronism check will
be established always. With regard to the 1-pole reclosing, the result of synchronism check will not
be judged, and the reclosing signal will be directly outputted after delay time is used up.
The reclosing pulse width of the automatic reclosure can be set through the setting [t_PW_AR].
With regard to the circuit breaker without the anti-pump circuit, the adjustment function of the
reclosing pulse width can be enabled. Namely, when the tripping occurs during the reclosing, the
reclosing pulse will drop off immediately, so as to prevent reclosing into the fault over and over
when the minimum reclosing pulse width is not lower than 50ms.
After the reclosing command is sent and the automatic reclosure can reset after the time delay
[t_Reclaim_AR], the another reclosing can be conducted.
68
1
AR Pulse
&
[t_Unsuc_AR]
CB closed
200ms
AR Unsuccess
AR Ready
&
Any trip
69
TX
RX
Transfer trip is the sending of a trip signal via a communication channel to the remote end of
transmission line. It is very reliable due to using of dedicated byte compensation check and bit
compensation check during transferring binary input. For the local end, when binary input
[BI_Send_TT] is energized, a trip signal will be sent to the remote end. For the remote end, when
such a trip signal received, the state of binary input [BI_RecvTT] will change from 0 to 1. The
trip signal will result in tripping directly when logic setting [En_FD_Ctrl_TT] set as 0, or with the
guard of general fault detector element when logic setting [En_FD_Ctrl_TT] set as 1, at the same
time auto-reclosing will be locked out.
BI
Optical fibre
Transfer trip
TJB-1
BO
TJC-1
TX
RX
TJA-1
Transfer trip
+DC
PCS-931
PCS-931
TX
+DC
Optical fibre
Transfer signal 1
RX
Besides the tripping signal, other signals can also be sent to remote end via communication
channel between. For the local end, when binary input [BI_Send1_TS] or [BI_Send2_TS] is
energized, a binary signal will be sent to the remote end. For the remote end, when such a binary
signal is received, the status of binary input [VBI_RecvTS1] or [VBI_RecvTS2] will change from 0
to 1, and corresponding binary output contacts of BO module will close.
YC1-1
BO
YC1-2
Transfer signal 1
TX
Transfer signal 2
Transfer signal 2
RX
BI
YC2-1
BO
YC2-2
PCS-931
PCS-931
If the protective device is blocked or alarm signal is sent during operation, please do find
out its reason with the help of self-diagnose record. If the reason cannot be found at site,
please notice the factory NARI-RELAYS. Please Do not simply press button TARGET
RESET on the protection panel or re-power on the protective device.
Table 4.2-1 List of alarms information
No.
Item
LED
HEALTHY
ALARM
VT ALARM
Block Relay
71
No.
Item
LED
HEALTHY
ALARM
VT ALARM
Block Relay
Alm_Abnor_Smpl_MON
YES
Alm_Abnor_Smpl_CPU
YES
Alm_TrpOut
YES
Alm_Setting
YES
Alm_VTS
Alm_PersistI0
Alm_PersistFD
Alm_VTS_Ux
Alm_CTS
10
Alm_52b
11
Alm_Pwr_Opto
12
Alm_ExTrp_BI
13
Alm_DSP_CPU
YES
14
Alm_DSP_MON
YES
15
Alm_ID_ChA
16
Alm_ChA
17
Alm_NoValidFram_ChA
18
Alm_CRC_ChA
19
Alm_OutDiffP_ChA
20
Alm_Diff_ChA
21
Alm_CompParam_ChA
22
Alm_TT
23
Alm_Connect_ChA
24
Alm_EquipConfig
25
Alm_Setting_Out-of-Scope
26
Alm_BoardConfig
27
Alm_SynChkFail_AR
28
GAlm_NetStorm_NetA
29
GAlm_NetStorm_NetB
30
GAlm_Disc_NetA
31
GAlm_Disc_NetB
32
GAlm_CfgUnmatch
33
GAlm_NetA_GOOSExx
34
GAlm_NetB_GOOSExx
35
GAlm_CfgUnmatch_GOOSExx
YES
Item
Handing suggestion
NANJING NARI-RELAYS ELECTRIC CO., LTD
No.
Item
Handing suggestion
Alm_Abnor_Smpl_MON
Alm_Abnor_Smpl_CPU
Alm_TrpOut
Alm_Setting
Alm_VTS
Alm_PersistI0
Alm_PersistFD
Alm_VTS_Ux
Alm_CTS
10
Alm_52b
11
Alm_Pwr_Opto
12
Alm_ExTrp_BI
13
Alm_DSP_CPU
14
Alm_DSP_MON
15
Alm_ID_ChA
16
Alm_ChA
17
Alm_NoValidFram_ChA
18
Alm_CRC_ChA
19
Alm_OutDiffP_ChA
20
Alm_Diff_ChA
21
Alm_CompParam_ChA
22
Alm_TT
23
Alm_Connect_ChA
24
Alm_EquipConfig
25
Alm_Setting_Out-of-Scope
26
Alm_BoardConfig
27
Alm_SynChkFail_AR
Prompting message
28
GAlm_NetStorm_NetA
29
GAlm_NetStorm_NetB
30
GAlm_Disc_NetA
31
GAlm_Disc_NetB
32
GAlm_CfgUnmatch
No.
Item
Handing suggestion
network.
33
GAlm_NetA_GOOSExx
34
GAlm_NetB_GOOSExx
35
GAlm_CfgUnmatch_GOOSExx
The following binary signals are only thought as a kind of report stored in the self-supervision
report. They do not need to handle and are only used for commissioning and test.
No.
1
Item
BO_BlkAR
Description
Blocking auto-reclosing
BO_Fail_AR
Auto-reclosing is failure
BO_Inprog_AR
Initiating auto-reclosing
BO_Lockout
Blocking auto-reclosing
74
75
1.
2.
enable phase overcurrent protection and zero-sequence overcurrent protection for VT circuit
failure
3.
4.
disable stage 3 of directional zero-sequence overcurrent protection when the logic setting
[En_Dir_ROC3] is set as 1
5.
6.
7.
8.
disable auto-reclosing
9.
The alarm [Alm_VTS] will be reset automatically with a time delay of 10s after all three phases
voltage resume to normal condition.
If 3I0 is less than 0.75 times 3I0Cal or 3I0Cal is less than 0.75 times 3I0, after 200 ms, an alarm
[Alm_CTS] will be issued.
If 3I0Cal exists (3I0>0.1In) but 3U0Cal derived is nearly zero (3U0Cal<3V) and there is a phase whose
current is zero at least, after 10s, an alarm [Alm_CTS] will be issued.
When CT circuit failure is detected, the protection device will implement the following tasks
automatically.
1.
2.
3.
4.
3U0Cal: zero-sequence voltage calculated depending on the summation of UA, UB and UC. (i.e.,
3U0Cal=UA+UB+UC)
77
78
RMS Values
Measured directly
Phase current from the remote end via optical fibre channel A (Ia_Rmt_ChA, Ib_Rmt_ChA,
Ic_Rmt_ChA)
Calculated by DSP
Access path: Press key to enter main menu firstly. Select the item VALUES and press key
ENT to enter submenu CPU_METERING, and then press key ENT. The corresponding
metering values mentioned above are displayed on the LCD.
2.
Phase angle
Measured directly
79
Phase angle between local phase current not compensated by capacitive current and remote
phase current not compensated by capacitive current (Ang(Ia-Iar), Ang(Ib-Ibr), Ang(Ic-Icr))
Phase angle between local phase current compensated by capacitive current and remote
phase current compensated by capacitive current (Ang(Ia-Iar)_Comp, Ang(Ib-Ibr)_Comp,
Ang(Ic-Icr)_Comp)
In PHASE_ANGLE, the phase angles displayed by three-phase current and three-phase voltage
are based on Phase A voltage.
No.
Definition
Ang(Ua)
Ang(Ub)
Ang(Uc)
Ang(Ux)
Ang(Ia)
Ang(Ib)
Ang(Ic)
Ang(Ia-Iar)
Phase angle difference for the local phase-A current (Ia) relative to
the remote phase-A current (Iar) (not compensated by capacitive
current)
Ang(Ib-Ibr)
Phase angle difference for the local phase-B current (Ib) relative to
the remote phase-B current (Ibr) (not compensated by capacitive
current)
Ang(Ic-Icr)
Phase angle difference for the local phase-C current (Ic) relative to
the remote phase-C current (Icr) (not compensated by capacitive
current)
11
Ang(Ia-Iar)_Comp
Phase angle difference for the local phase-A current (Ia) relative to
the remote phase-A current (Iar) (compensated by capacitive
current)
12
Ang(Ib-Ibr)_Comp
Phase angle difference for the local phase-B current (Ib) relative to
the remote phase-B current (Ibr) (compensated by capacitive
current)
10
80
Symbol
13
Ang(Ic-Icr)_Comp
Phase angle difference for the local phase-C current (Ic) relative to
the remote phase-C current (Icr) (compensated by capacitive
current)
Access path: Press key to enter main menu firstly. Select the item VALUES and press key
ENT to enter submenu PHASE_ANGLE, and then press key ENT. The corresponding phase
angles mentioned above are displayed on the LCD.
Event recorder
2.
Disturbance recorder
3.
Present recorder
These records are displayed on the LCD of the relay front panel or on the local or remote PC.
Navigate the menu to view the report through LCD screen.
The protective device can store the latest 1024 tripping report, the latest 1024 binary input change
report, the latest 1024 self-supervision report and the latest 1024 control report respectively. All
the records are stored in non-volatile memory, and when the available space is exhausted, the
oldest report is automatically overwritten by the latest one.
5.2.2.2 Tripping Report
When any protection element operating or drop out, such as fault detector, distance protection and
so on, they will be logged in event recorder.
5.2.2.3 Self-supervision Report
The protective device is under automatic supervision all the time. If there are any failure or
abnormal condition detected, such as, chip damaged, VT circuit failure and so on, it will be logged
in event recorder.
5.2.2.4 Binary Input Change Report
When there is binary input is energized or de-energized, i.e., its state has changed from 0 to 1
or from 1 to 0, it will be logged as an event recorder.
5.2.2.5 Control Report
If operator implements some operation, such as reboot protective device, modify setting, and so
on, they will be logged as an event recorder.
NANJING NARI-RELAYS ELECTRIC CO., LTD
81
Use the disturbance recorder to achieve a better understanding of the behavior of the power
network and related primary and secondary equipment during and after a disturbance. An analysis
of the recorded data provides valuable information that can be used to improve existing equipment.
This information can also be used when planning for and designing new installations.
5.2.3.2 Design
Disturbance recorder is consisted of fault report and fault waveform. Disturbance recorder is
initiated by fault detector element.
Disturbance recorder has two types:
1.
2.
The protective device can store up to 64 fault reports with waveform in non-volatile memory. If a
new fault occurs when 64 faults report have been stored, the oldest fault report will be overwritten
by the latest one.
For each fault report, the following items are included:
1.
Sequence number
Each operation will be recorded with a sequence number in the report and displayed on LCD
screen.
2.
The time resolution is 1ms using the relay internal clock synchronized via GPS if connected.
Initiating date and time is when a protective fault detection operates.
3.
An operating time (not including the operating time of output relays) is recorded in the report.
4.
Faulty phase
5.
Fault location
To get accurate result of fault location, the following settings shall be set correctly:
1)
2)
3)
4)
82
5)
6.
protection elements
MON module can store 64 fault waveform in non-volatile memory. If a new fault occurs when 64
fault waveform recorders have been stored, the oldest will be overwritten by the latest one.
Each fault record consists of all analog and digital quantities related to protection, such as original
current and voltage, differential current, alarm elements, and binary inputs and etc.
Each time recording includes 2-cycle waveform pre-fault and 14-cycle waveform after fault
detector pickup, and this 16-cycle waveform is high-frequency recording at a rate of 1200Hz (24
points per cycle). If no protection element operates, after the above 16-cycle waveform recording
is finished, the protection device will switch into low-frequency recording at a rate of 50Hz (only
magnitude). If some protection element operates, 14-cycle waveform after protection operation will
be recorded which are high-frequency recording waveform. When the protection device is not in
high-frequency recording state, it will switch into low-frequency recording state automatically. If the
total 1024 points are recorded, this recording waveform is finished.
The sampling rate of high-frequency recording is 24 points per cycle and that of low-frequency
recording is 1 point per cycle to record RMS magnitude of current or voltage.
83
84
xx
VT ALARM
xx
AR READY
xx
CH A ALARM
xx
CH B ALARM
xx
TRIP A
xx
TRIP B
xx
TRIP C
xx
RECLOSE
xx
PCS - 931
LINE DIFFERENTIAL RELAY
ENT
ESC
xx
ALARM
GR
P
HEALTHY
NR1123E
NR1123D
TX
NR1403
NR1502
NR1550
NR1551
NR1551
NR1560
NR1301
5V
BJ
BJJ BSJ
DANGER
1 COM1
2
3
BSJ1
BJJ1
4 COM2
RX
BSJ2
BJJ2
24V
8 24VGND
9
10 PWR+
11 PWR12 FGND
Figure 6.1-2 Rear view of PCS-931 (conventional CT/VT and conventional binary output)
85
NR1123F
NR1126A
TX
RX
NR1502
NR1301
5V
BJ
BJJ BSJ
TX
TX
RX
RX
TX
1 COM1
TX
RX
2
3
BSJ1
BJJ1
4 COM2
RX
BSJ2
BJJ2
24V
8 24VGND
9
ETHERNET1
10 PWR+
11 PWR12 FGND
ETHERNET2
Figure 6.1-3 Rear view of PCS-931 (ECVT and GOOSE binary output)
According to output method and sampling method of the protection device, output method
including conventional binary output and GOOSE binary output, and sampling method including
conventional CT/VT and ECVT (electronic current and voltage transformer), PCS-900 series
provide standard modules and optional module for different protection device.
Table 6.1-1 Hardware configuration
No.
ID
Name
Function Description
Remark
NR1102
MON
Communication interface
standard module
NR1123
DSP
standard module
NR1123
DSP
standard module
NR1403
AI
optional module
NR1126
GOOSE
optional module
NR1502
BI
standard module
NR1502
BI
optional module
NR1552
BO
standard module
NR1551
BO
optional module
10
NR1560
BO
optional module
11
NR1301
PWR
DC power supply
standard module
86
*
52b
409
410
411
412
413
414
401
402
403
404
405
406
407
408
Ua
Ub
Uc
Un
Ux
Ux'
Ia
Ia'
Ib
Ib'
Ic
Ic'
I0
I0'
Current Input
Voltage Input
AI Module
ETHERNET 1
001
COMMON1
002
BSJ-1
003
BJJ-1
004
COMMON2
005
BSJ-2
006
BJJ-2
007
24V OPTO+
008
24V OPTO-
PC
HMI
GND
103
RS485A
104
RS485B
105
GND
106
RS485A
107
RS485B
108
GND
109
RS232R
110
RS232T
111
GROUND
112
010
220/110V DC+
011
220/110V DC-
012
GROUND
GPS
DC
102
COM2
009
101
RS485B
MON Module
LCD
KEYPAD
RS485A
COM1
PWR Module
To BI
Module
ETHERNET 2
Serial Port
PTINTER
GROUND BUS
DB 9
PTR
RS232
2.
87
ECVTRemote Module
Phase C
Phase B
Phase A
Merging Unit
RX
RX
TX
TX
Receiving sampling data through multi-mode optical fibre from merging unit
TX
RX
TX
RX
FO transmitting
FO Receiving
FO transmitting
FO Receiving
DSP Module
DSP Module
ETHERNET 1
001
COMMON1
002
BSJ-1
003
BJJ-1
RS485A
101
004
COMMON2
RS485B
102
005
BSJ-2
GND
103
006
BJJ-2
RS485A
104
007
24V OPTO+
RS485B
105
008
24V OPTO-
GND
106
RS485A
107
RS485B
108
PC
To BI
Module
ETHERNET 2
LCD
KEYPAD
009
DC
010
220/110V DC+
011
220/110V DC-
012
GROUND
RS232
GROUND BUS
GND
109
RS232R
110
RS232T
111
GROUND
112
Serial Port
DB 9
88
from merging unit respectively through the optical-fibre interface to complete the protection
function calculation and fault detector logic calculation.
The difference between the hardware platform based on ECVT and the hardware platform based
on conventional CT/VT lies in the receiving module of sample data only, and the protective device
receives the sampling data of merging unit through multi-mode optical fibre.
Conventional CT/VT
A/D
Opto-coupler
External
Binary Input
DSP
ECVT
Output
Relay
Conventional CT/VT
A/D
DSP
ECVT
QDJ
ETHERNET
LCD/Power Supply
PRINT
CPU
GPS
+E
SERIAL PORT
89
NR1102D
ETHERNET 1
ETHERNET 1
FO 1
NR1102H
ETHERNET 2
FO 2
RX
To SAS
ETHERNET 2
TX
TX
FO 1
RX
To SAS
TX
FO 2
RX
To SAS
ETHERNET 3
NR1102I
TX
ETHERNET 1
ETHERNET 1
To SAS
ETHERNET 4
To SAS
ETHERNET 2
ETHERNET 2
SYN+
01
SYN+
01
SYN+
01
SYN+
01
SYN-
02
SYN-
02
SYN-
02
SYN-
02
SHLD
03
SHLD
03
SHLD
03
SHLD
03
GND
04
GND
04
GND
04
GND
04
RTS
05
RTS
05
RTS
05
RTS
05
TXD
06
TXD
06
TXD
06
TXD
06
SGND
07
SGND
07
SGND
07
SGND
07
Module ID
To GPS
To PRINT
Memory
To GPS
To PRINT
Interface
To GPS
To PRINT
128M DDR
2 RJ45 Ethernet
NR1102D
128M DDR
4 RJ45 Ethernet
NR1102H
128M DDR
2 RJ45 Ethernet
2 FO Ethernet
Optical fibre SC
NR1102I
128M DDR
2 RJ45 Ethernet
2 FO Ethernet
Optical fibre TC
01
485-1B
02
SHLD
03
GND
04
SYN+
01
SYN-
02
SHLD
03
GND
04
RTS
01
TXD
02
SGND
03
GND
04
485-1A
GPS
To PRINT
COM
To GPS
Physical Layer
NR1102C
To SAS
RX
90
Pin No.
Symbol
~01
SYN+
~02
SYN-
~03
SHLD
~04
GND
Description
EIA
RS-485
standardized
interface
for
clock
synchronization, PPS and IRIG-B signals are permitted.
Grounded connection of this protection device
NANJING NARI-RELAYS ELECTRIC CO., LTD
Pin No.
Symbol
~05
RXD
~06
TXD
~07
SGND
Description
The correct method of connection is shown in Figure 6.3-2. Generally, the shielded cables with two
pairs of twisted pairs inside shall be applied. One pair of the twisted pairs are respectively used to
connect the + and terminals of difference signal; the other pair of twisted pairs are used to
connect the signal ground of the interface, i.e. connect the signal groundings of all the devices
connected with the bus to the twisted pair. The module reserves a free terminal for all the
communication ports; the free terminal has no connection with any signal of the device; it is used
to connect the external shields of the two cables when connecting multiple devices in series. The
external shield of cable shall be grounded at one of the ends.
91
CT/VT Type
FO Interface
NR1123D
Conventional CT/VT
No
NR1123E
Conventional CT/VT
Yes
NR1123F
Single ECVT
No
NR1123G
Single ECVT
Yes
NR1123K
Double ECVT
No
Remark
6.3.4 AI Module
The protection device which supports ECVT should not be equipped with this module. The slot
numbers of the module are 4 and 5. The AI module (NR1401) is applicable for the plant or station
with analog VT and CT.
IA, IB, IC and 3I0 are phase current and zero sequence current input to AI module separately with
rating 5 A or 1 A. Please declare which kind of AI module is needed before ordering. It is assumed
that forward direction of CT should be pointed from busbar to line.
3I0 derived is used for calculation of zero-sequence directional element and zero-sequence
overcurrent element, but 3I0 measured is used for zero-sequence current fault detector element.
Therefore, 3I0 measured shall be connected to the equipment, otherwise all relevant zero
sequence current protection will be disabled. Because only the magnitude of 3I0 measured is used,
the directionality of 3I0 measured can be forward direction or reverse direction. Maximum linear
range of the current converter is 30In. Table 6.3-1 lists the pin number and its definition of AI
module.
92
Ia
01
Ian
02
Ib
03
Ibn
04
Ic
05
Icn
06
3I0
07
3I0n
08
Ua
09
Ub
10
Uc
11
Un
12
Ux
13
Uxn
14
GND
15
Definition
Definition
401
Ia
402
Ian
403
Ib
404
Ibn
405
Ic
406
Icn
407
I0
408
I0n
Zero-sequence current
409
Ua
410
Ub
411
Uc
412
Un
413
Ux
414
Uxn
415
GND
UA, UB, and UC are phase voltage used to protection function calculation. Ux is the synchronism
voltage and used for synchronism check, it could be any phase-to-ground voltage or
phase-to-phase voltage, and terminal 213 is the polarity mark. If the auto-reclosing is disabled or
enabled but without any check, the voltage Ux should be disconnected.
The no-voltage check conditions will be met when the line voltage is less than the setting [V_Dead],
and the voltage conditions of synchronism check will be met when the line voltage is more than the
setting [V_Live]. If the automatic reclosure is disabled or the no check for automatic reclosure is
enabled, the line voltage could be disconnected. When the automatic reclosure is enabled and the
no-voltage check and synchronism check is applied, check whether the input voltage is higher
than the setting [V_Dead] during the normal operation of device. If it is, the alarm of VT circuit
NANJING NARI-RELAYS ELECTRIC CO., LTD
93
failure will be issue with a time delay of 10s and the alarm relay is triggered to work.
Terminal 415 is ground point. It shall be connected to ground bus.
The protection device can support to configure up to 8 sending modules, and it is recommended to
configure 1 sending module. To facilitate the site debugging, the maximized configuration, i.e. 12
isolator links used for sending function of GOOSE, are available in the protection device. When
corresponding isolator link is open, the associated GOOSE sending information will be reset. Each
GOOSE sending information includes the GOOSE sending information and the state information
of binary input [BI_BlkComm] of the protection device, so as to judge whether the receiving signal
is used effectively at the receiving side. At present, the GOOSE sending information in the
protection device includes the following signals, trip A, trip B, trip C, blocking AR, reclosing,
transfer signal 1, transfer signal 2 and channel alarm. To meet different requirements, 12 isolator
links and various sending information can be combined with each other flexibly, and the
corresponding short address is shown as in the table below:
Signal
Isolator Link
Signal 0
Signal 1
Trip A
Trip B
EBI_Send_GOOSE00
B02.SwitchOut_F0.Go_S0_BIN0
B02.SwitchOut_F0.Go_S0_BIN1
EBI_Send_GOOSE01
B02.SwitchOut_F0.Go_S1_BIN0
B02.SwitchOut_F0.Go_S1_BIN1
EBI_Send_GOOSE02
B02.SwitchOut_F0.Go_S2_BIN0
B02.SwitchOut_F0.Go_S2_BIN1
EBI_Send_GOOSE03
B02.SwitchOut_F0.Go_S3_BIN0
B02.SwitchOut_F0.Go_S3_BIN1
EBI_Send_GOOSE04
B02.SwitchOut_F0.Go_S4_BIN0
B02.SwitchOut_F0.Go_S4_BIN1
EBI_Send_GOOSE05
B02.SwitchOut_F0.Go_S5_BIN0
B02.SwitchOut_F0.Go_S5_BIN1
EBI_Send_GOOSE06
B02.SwitchOut_F0.Go_S6_BIN0
B02.SwitchOut_F0.Go_S6_BIN1
EBI_Send_GOOSE07
B02.SwitchOut_F0.Go_S7_BIN0
B02.SwitchOut_F0.Go_S7_BIN1
EBI_Send_GOOSE08
B02.SwitchOut_F0.Go_S8_BIN0
B02.SwitchOut_F0.Go_S8_BIN1
EBI_Send_GOOSE09
B02.SwitchOut_F0.Go_S9_BIN0
B02.SwitchOut_F0.Go_S9_BIN1
EBI_Send_GOOSE10
B02.SwitchOut_F0.Go_S10_BIN0
B02.SwitchOut_F0.Go_S10_BIN1
EBI_Send_GOOSE11
B02.SwitchOut_F0.Go_S11_BIN0
B02.SwitchOut_F0.Go_S11_BIN1
Signal 2
Signal 3
Trip C
Reclosing
Signal
Isolator Link
EBI_Send_GOOSE00
94
B02.SwitchOut_F0.Go_S0_BIN2
B02.SwitchOut_F0.Go_S0_BIN3
EBI_Send_GOOSE01
B02.SwitchOut_F0.Go_S1_BIN2
B02.SwitchOut_F0.Go_S1_BIN3
EBI_Send_GOOSE02
B02.SwitchOut_F0.Go_S2_BIN2
B02.SwitchOut_F0.Go_S2_BIN3
EBI_Send_GOOSE03
B02.SwitchOut_F0.Go_S3_BIN2
B02.SwitchOut_F0.Go_S3_BIN3
EBI_Send_GOOSE04
B02.SwitchOut_F0.Go_S4_BIN2
B02.SwitchOut_F0.Go_S4_BIN3
EBI_Send_GOOSE05
B02.SwitchOut_F0.Go_S5_BIN2
B02.SwitchOut_F0.Go_S5_BIN3
EBI_Send_GOOSE06
B02.SwitchOut_F0.Go_S6_BIN2
B02.SwitchOut_F0.Go_S6_BIN3
EBI_Send_GOOSE07
B02.SwitchOut_F0.Go_S7_BIN2
B02.SwitchOut_F0.Go_S7_BIN3
EBI_Send_GOOSE08
B02.SwitchOut_F0.Go_S8_BIN2
B02.SwitchOut_F0.Go_S8_BIN3
EBI_Send_GOOSE09
B02.SwitchOut_F0.Go_S9_BIN2
B02.SwitchOut_F0.Go_S9_BIN3
EBI_Send_GOOSE10
B02.SwitchOut_F0.Go_S10_BIN2
B02.SwitchOut_F0.Go_S10_BIN3
EBI_Send_GOOSE11
B02.SwitchOut_F0.Go_S11_BIN2
B02.SwitchOut_F0.Go_S11_BIN3
Signal 4
Signal 5
Blocking AR
Transfer trip 1
Signal
Isolator Link
EBI_Send_GOOSE00
B02.SwitchOut_F0.Go_S0_BIN4
B02.SwitchOut_F0.Go_S0_BIN5
EBI_Send_GOOSE01
B02.SwitchOut_F0.Go_S1_BIN4
B02.SwitchOut_F0.Go_S1_BIN5
EBI_Send_GOOSE02
B02.SwitchOut_F0.Go_S2_BIN4
B02.SwitchOut_F0.Go_S2_BIN5
EBI_Send_GOOSE03
B02.SwitchOut_F0.Go_S3_BIN4
B02.SwitchOut_F0.Go_S3_BIN5
EBI_Send_GOOSE04
B02.SwitchOut_F0.Go_S4_BIN4
B02.SwitchOut_F0.Go_S4_BIN5
EBI_Send_GOOSE05
B02.SwitchOut_F0.Go_S5_BIN4
B02.SwitchOut_F0.Go_S5_BIN5
EBI_Send_GOOSE06
B02.SwitchOut_F0.Go_S6_BIN4
B02.SwitchOut_F0.Go_S6_BIN5
EBI_Send_GOOSE07
B02.SwitchOut_F0.Go_S7_BIN4
B02.SwitchOut_F0.Go_S7_BIN5
EBI_Send_GOOSE08
B02.SwitchOut_F0.Go_S8_BIN4
B02.SwitchOut_F0.Go_S8_BIN5
EBI_Send_GOOSE09
B02.SwitchOut_F0.Go_S9_BIN4
B02.SwitchOut_F0.Go_S9_BIN5
EBI_Send_GOOSE10
B02.SwitchOut_F0.Go_S10_BIN4
B02.SwitchOut_F0.Go_S10_BIN5
EBI_Send_GOOSE11
B02.SwitchOut_F0.Go_S11_BIN4
B02.SwitchOut_F0.Go_S11_BIN5
Signal 6
Signal 7
Transfer signal 2
Channel alarm
Signal
Isolator Link
EBI_Send_GOOSE00
B02.SwitchOut_F0.Go_S0_BIN6
B02.SwitchOut_F0.Go_S0_BIN7
EBI_Send_GOOSE01
B02.SwitchOut_F0.Go_S1_BIN6
B02.SwitchOut_F0.Go_S1_BIN7
EBI_Send_GOOSE02
B02.SwitchOut_F0.Go_S2_BIN6
B02.SwitchOut_F0.Go_S2_BIN7
EBI_Send_GOOSE03
B02.SwitchOut_F0.Go_S3_BIN6
B02.SwitchOut_F0.Go_S3_BIN7
EBI_Send_GOOSE04
B02.SwitchOut_F0.Go_S4_BIN6
B02.SwitchOut_F0.Go_S4_BIN7
EBI_Send_GOOSE05
B02.SwitchOut_F0.Go_S5_BIN6
B02.SwitchOut_F0.Go_S5_BIN7
EBI_Send_GOOSE06
B02.SwitchOut_F0.Go_S6_BIN6
B02.SwitchOut_F0.Go_S6_BIN7
EBI_Send_GOOSE07
B02.SwitchOut_F0.Go_S7_BIN6
B02.SwitchOut_F0.Go_S7_BIN7
EBI_Send_GOOSE08
B02.SwitchOut_F0.Go_S8_BIN6
B02.SwitchOut_F0.Go_S8_BIN7
EBI_Send_GOOSE09
B02.SwitchOut_F0.Go_S9_BIN6
B02.SwitchOut_F0.Go_S9_BIN7
EBI_Send_GOOSE10
B02.SwitchOut_F0.Go_S10_BIN6
B02.SwitchOut_F0.Go_S10_BIN7
EBI_Send_GOOSE11
B02.SwitchOut_F0.Go_S11_BIN6
B02.SwitchOut_F0.Go_S11_BIN7
For example, if the isolator link [EBI_Send_GOOSE01] is defined as the isolator link of tripping
output, the reclosing signal controlled by this isolator shall be configured with the short address
NANJING NARI-RELAYS ELECTRIC CO., LTD
95
The protection device supports to configure up to 12 GOOSE receiving modules, and each
receiving module is configured with one virtual enabling binary input setting (VEBI setting) used to
receive. At present, the GOOSE signal supported to receive is shown as follows.
No.
1
GOOSE BI
GBI_Lockout1
Remark
BI via OPTO
Valid BI
GBI_Lockout2
GBI_Lockout3
GBI_Lockout4
GBI_Lockout5
GBI_52b_PhA
7
8
9
GBI_Send_TT1
10
GBI_Send_TT2
11
GBI_Send_TT3
12
GBI_Send_TT4
13
GBI_Send1_TS1
14
GBI_Send1_TS2
15
GBI_Send1_TS3
16
GBI_Send1_TS4
17
GBI_Send2_TS1
18
GBI_Send2_TS2
19
GBI_Send2_TS3
20
GBI_Send2_TS4
21
GBI_TrpA_Other
BI_TrpA_Other_OPT (807)
BI_TrpA_Other
22
GBI_TrpB_Other
BI_TrpB_Other_OPT (811)
BI_TrpB_Other
23
GBI_TrpC_Other
BI_TrpC_Other_OPT (812)
BI_TrpC_Other
24
GBI_3PTrp_Line
BI_3PTrp_Line_OPT (807)
BI_3PTrp_Line
25
GBI_3PTrp_G/T1
26
GBI_3PTrp_G/T2
27
GBI_3PTrp_G/T3
BI_3PTrp_G/T
28
GBI_3PTrp_G/T4
The relation is
BI_3PTrp_G/T_OPT (817)
OR among them
29
GBI_3PTrp_G/T5
30
GBI_LowPres_AR
EBI_Lockout_OPT (810)
The relation is (This binary input is always
EBI_Lockout
OR among them valid no matter whether
GOOSE function is enabled)
BI_52b_PhA_OPT (822)
BI_52b_Pha
GBI_52b_PhB
BI_52b_PhB_OPT (823)
BI_52b_Phb
GBI_52b_PhC
BI_52b_PhC_OPT (824)
BI_52b_Phc
The relation is
BI_Send_TT_OPT (826)
OR among them
BI_Send_TT
The relation is
BI_Send1_TS_OPT (827)
OR among them
BI_Send1_TS
The relation is
BI_Send2_TS_OPT (828)
OR among them
BI_Send2_TS
To facilitate the site debugging, the GOOSE binary inputs in the table above are the receiving
signal of GOOSE itself. It is necessary to combine with GOOSE VEBI setting of GOOSE receiving,
the state of GOOSE receiving link and the state of binary input [BI_BlkComm] to judge whether the
GOOSE binary input is valid. The concrete relationship is shown as follows:
The received GOOSE valid information=([BI_BlkComm]=1 at both sending end and receiving
96
end[BI_BlkComm]=0 at both sending end and receiving end) & GOOSE receiving information &
corresponding GOOSE VEBI setting & corresponding communication link is normal.
When the sending GOOSE link is interrupted, GOOSE VEBI setting is set as 0, and the state of
binary input [BI_BlkComm] at the sending end is not consistent with that at the receiving end, the
open position of circuit breaker will maintain its original value.
3.
Item
Description
N_RecvdFrame
N_SentFrame
N_Err_RecvdDMA
N_Err_SentDMA
N_Err_Recvd_Misc
N_Err_Sent_Misc
N_Err_RecvdMemData
N_NetStorm_GOOSE
3
4
5
6
7
8
4.
Item
Description
N_Fail_SentGOOSE
N_Err_DecodeGOOSE
Item
Description
GAlm_NetStorm_NetA
GAlm_NetStorm_NetB
GAlm_Disc_NetA
GAlm_Disc_NetB
GAlm_CfgUnmatch
97
NR1126B
NR1126C
NR1126D
SC Interface
100M FX
SC Interface
100M FX
ST Interface
100M FX
ST Interface
100M FX
SC Interface
100M FX
SC Interface
100M FX
ST Interface
100M FX
ST Interface
100M FX
RX1
ST Interface
IRIGB
Module ID
Interface
NR1126A
2 Ethernet
2 Ethernet
IRIGB
ST
2 Ethernet
2 Ethernet
IRIGB
ST
NR1126B
NR1126C
NR1126D
Physical Layer
RX1
ST Interface
IRIGB
Description
6.3.6 BI Module
Intelligent binary input module (NR 1502) can supervise 25 binary inputs at the same time and
transmit binary inputs to other modules by inner bus. For NR 1502D, the rated work voltage of all
binary inputs are 24V, and for NR 1502A, the rated work voltage of all binary inputs are 220/110V.
When the voltage of binary input is greater than 70% of rated work voltage, the binary input is
energized and when the voltage of binary input is smaller than 60% of rated work voltage, the
binary input is de-energized.
98
Pin No.
Sign
BI_2
02
BI_1
01
BI_4
04
BI_3
03
BI_6
06
BI_5
05
BI_8
08
BI_7
07
BI_10
10
BI_9
09
BI_12
12
BI_11
11
BI_14
14
13
16
BI_15
15
BI_18
18
BI_17
17
BI_20
20
BI_19
19
BI_22
22
BI_21
21
BI_24
24
BI_23
23
BI_26
26
BI_25
25
BI_28
28
BI_27
27
30
BI_29
29
Description
01
BI_Pulse_GPS
02
BI_Print
BI_BlkComm
Binary
input
of
blocking
communication
between
the
protective device and SAS
03
04
BI_RstTarg
05
BI_Opt1_ActiveGrp
06
BI_Opt2_ActiveGrp
14
Opto_H+
Optp_H-
EBI_DiffP
EBI_DistP
EBI_ROC
EBI_OC
EBI_Z1
15
07~11,
12,
17~29
Remark
Power supply
Configurable binary
input (if these binary
inputs
are
not
configured,
their
default state are 1)
99
BI_TrpA_Other
BI_TrpB_Other
BI_TrpC_Other
EBI_Opt1_AR
EBI_Opt2_AR
EBI_Lockout
BI_3PTrp_Line
BI_3PTrp_G/T
BI_TrigOscillog
BI_MCB_VT_Line
BI_MCB_VT_Bus
BI_52b_Pha
BI_52b_Phb
BI_52b_Phc
BI_LowPres_AR
BI_Send_TT
BI_Send1_TS
BI_Send2_TS
13
Blank
16
Blank
30
Blank
1.
100
Configurable binary
input (if these binary
inputs
are
not
configured,
their
default state are 0)
Terminal 814
The positive pole of opto-coupler, which should be connected with the positive pole of DC power
supply (PWR module: terminal 001). It is used to supervise whether DC power supply is normal or
not. The positive pole of PWR module should be connected to common of all binary inputs.
2.
Terminal 815
The negative pole of opto-coupler, which should be connected with the negative pole of DC power
supply (PWR module: terminal 102).
3.
Terminal 801
Terminal 802
Terminal 803
Terminal 804
Terminal 805
Terminal 806
101
It is used to switch active setting group associating with binary input [Bl_Opt1_ActiveGrp].
Table 6.3-2 Switchover of active setting group
Terminal
Binary input
Group 0
Group 1
Group 2
Group 3
805
[Bl_Opt1_ActiveGrp]
806
[Bl_Opt2_ActiveGrp]
All binary inputs mentioned below are configurable binary inputs, and they can be pointed to any
terminal except terminal 01~06, 13, 16 and 30 by software RCS-PC. The configuration method
can refer to section 7.3.2.
1.
It is used to initiate BFP of phase A, and is usually from phase-A tripping contact of other
protection device. The tripping contact is instantaneous operation contact, i.e. it will drop out
immediately after operation.
7.
It is used to initiate BFP of phase B, and is usually from phase-B tripping contact of other
protection device. The tripping contact is instantaneous operation contact, i.e. it will drop out
immediately after operation.
8.
It is used to initiate BFP of phase C, and is usually from phase-C tripping contact of other
protection device. The tripping contact is instantaneous operation contact, i.e. it will drop out
immediately after operation.
9.
It is used to select mode of auto-reclosing through switch associated with binary input
[EBI_Opt2_AR] when logic setting [En_SetOpt_AR] is set as 0.
102
It is used to select mode of auto-reclosing through switch associated with binary input
[EBI_Opt1_AR] when logic setting [En_SetOpt_AR] is set as 0.
The below table shows the relation between the state of binary input and AR mode.
Pin No.
Binary input
1-Pole AR
3-Pole AR
1/3-Pole AR
Disable
808
EBI_Opt1_AR
809
EBI_Opt2_AR
When binary inputs [EBI_Opt1_AR] and [EBI_Opt2_AR] are both energized, only the
auto-reclosing function of the protective device is disabled but selection of faulty phase is still valid.
The auto-reclosing function is still finished by the other protective device. The auto-reclosing
function of the protected line can be locked out through energizing the binary input [EBI_Lockout].
When logic setting [En_SetOpt_AR] is set to 1, the binary inputs [EBI_Opt1_AR] and
[EBI_Opt2_AR] are disabled.
11. Binary input: [EBI_Lockout]
It is used to lockout the auto-reclosing function of the protected line. Three-phase tripping is
implemented and the auto-reclosing function will be locked out for any type of fault when it is
energized.
12. Binary input: [BI_3PTrp_Line]
It is used to initiate BFP of three phases, and is usually from three-phase tripping contact of line
protection. The tripping contact is instantaneous operation contact, i.e. it will drop out immediately
after operation.
13. Binary input: [BI_3PTrp_G/T]
It is used to initiate BFP of three phases, and is usually from three-phase tripping contact of all
protection device except line protection, such as generator, transformer, and so on, which will not
initiate auto-reclosing.
14. Binary input: [BI_TrigOscillog]
It is normally closed auxiliary contact of phase A of circuit breaker and is used to indicate the status
NANJING NARI-RELAYS ELECTRIC CO., LTD
103
It is normally closed auxiliary contact of phase B of circuit breaker and is used to indicate the
status of circuit. It is provided by interposing relay, for example, CZX-12R.
19. Binary input: [BI_52b_Phc]
It is normally closed auxiliary contact of phase B of circuit breaker and is used to indicate the
status of circuit. It is provided by interposing relay, for example, CZX-12R.
20. Binary input: [BI_LowPres_AR]
It is connected with auxiliary contact of circuit breaker, which is used to supervise closing pressure
of circuit breaker. The auto-reclosing will be blocked after 200ms when it is energized. If
auto-reclosing of protective device is disabled, it need not be connected.
21. Binary input: [BI_Send_TT]
It is common connected with tripping contact from other protective device, such as breaker failure
protection. It is used to transfer tripping signal and trip remote circuit breaker through the channel.
22. Binary input: [BI_Send1_TS]
It is common connected with tripping contact from other protective device, such as breaker failure
protection. It is used to transfer signal and trip remote circuit breaker through the channel
associated with auxiliary criterion of other protective device, for example, RCS-925 voltage relay.
23. Binary input: [BI_Send2_TS]
It is common connected with tripping contact from other protective device, such as breaker failure
protection. It is used to transfer signal and trip remote circuit breaker through the channel
associated with auxiliary criterion of other protective device, for example, RCS-925 voltage relay.
Pin No.
104
Binary input
Pin No.
Binary input
801
BI_Pulse_GPS
816
802
BI_Print
817
BI_3PTrp_Line
803
BI_BlkComm
818
BI_3PTrp_G/T
804
BI_RstTarg
819
BI_TrigOscillog
805
Bl_Opt1_ActiveGrp
820
BI_MCB_VT_Line
806
Bl_Opt2_ActiveGrp
821
BI_MCB_VT_Bus
807
BI_TrpA_Other
822
BI_52b_Pha
808
EBI_Opt1_AR
823
BI_52b_Phb
809
EBI_Opt2_AR
824
BI_52b_Phc
810
EBI_Lockout
825
BI_LowPres_AR
811
BI_TrpB_Other
826
BI_Send_TT
812
BI_TrpC_Other
827
BI_Send1_TS
813
828
BI_Send2_TS
814
829
BI_Reserved
815
830
6.3.7 BO Module
NR1521B
01
02
03
04
05
06
07
08
09
10
11
12
13
14
15
16
17
18
19
20
21
22
Configurable BO1
Configurable BO2
Configurable BO3
Configurable BO4
Configurable BO5
Configurable BO6
Configurable BO7
Configurable BO8
Configurable BO9
Configurable BO10
Configurable BO11
The module provides 11 groups of normally open contacts, which are all configurable binary output.
Apart from configurable BO10 and BO11, all contacts provided by this module are controlled by
general pick-up relay.
105
Any operation signal, alarm signal, intermediate signal or combination signal (support
programmable logic) can be pointed to any output channel, which can fulfill that some special
requirement that specific signal must be output to trip circuit breaker or issue signal. The
configuration method can refer to section 7.3.3.
6.3.8 BO Module
NR1552A
Pin No.
Sign
BSJ-1
02
COM1
01
XTJ-1
04
BJJ-1
03
COM2
06
XHJ-1
05
BJJ-2
08
BSJ-2
07
COM4
10
COM3
09
TDGJ-1
12
TDGJ-2
11
YC1-1
14
YC2-1
13
YC1-2
16
YC2-2
15
YC1-2
18
YC2-2
17
TJ-1
20
COM
19
BCJ-1
22
TJABC-1
21
TJ-2
24
COM
23
BCJ-2
26
TJABC-2
25
TJ-3
28
COM
27
BCJ-3
30
TJABC-3
29
Description
01
COM1
01~02
BO_Fail_1
01~03
BO_Alm_Abnor_1
01~04
BO_Trp_1
01~05
BO_Cls_1
06
COM2
06~07
BO_Fail_2
06~08
BO_Alm_Abnor_2
09
COM3
09~11
BO_Alm_Ch_2
09~13
BO_Recv2_TS_1
15~17
BO_Recv2_TS_2
10
COM4
10~12
BO_Alm_Ch_1
10~14
BO_Recv1_TS_1
16~18
BO_Recv1_TS_2
106
19
COM
19~20
BO_Trp1P_1
19~21
BO_Trp3P_1
19~22
BO_Lockout_1
23
COM
23~24
BO_Trp1P_2
23~25
BO_Trp3P_2
23~26
BO_Lockout_2
27
COM
27~28
BO_Trp1P_3
27~29
BO_Trp3P_3
27~30
BO_Lockout_3
Local signal
Transfer signal 1
BO_Fail_1
Transfer signal 2
10
02
BO_Alm_Ch_1
03
BO_Recv1_TS_1
BO_Alm_Abnor_1
11
BO_Alm_Ch_2
12
BO_Trp
13
BO_Recv2_TS_1
14
09
04
BO_Cls
16
05
BO_Recv1_TS_2
15
BO_Recv2_TS_2
18
17
01
Load Shedding
Auto-reclosing 1
BO_Trp1p_3
Auto-reclosing 2
BO_Trp1P_1
28
BO_Trp3P_3
BO_Trp1P_2
BO_Trp3P_1
29
BO_BlkAR_3
24
20
BO_Trp3P_2
21
BO_BlkAR_1
25
BO_BlkAR_2
30
22
26
27
19
23
Remote signal
BO_Fail_2
07
BO_Alm_Abnor_2
08
06
107
BO_Trp_2 and BO_Trp_3. BO_Trp_1 and BO_Trp_2 can be used to initiate auto-reclosing of other
protective device by connecting with binary input [BI_ExTrp1P_AR].
When there is any protective element operating to trip three-phase circuit breaker, trip signal will
be issued by closing the normally open contact BO_Trp3P_1, BO_Trp3P_2 and BO_Trp3P_3.
BO_Trp3P_1 and BO_Trp3P_2 can be used to initiate auto-reclosing of other protective device by
connecting with binary input [BI_ExTrp3P_AR].
When the conditions that is used to block auto-reclosing is met, the normally open contact
BO_BlkAR_1, BO_BlkAR_2 and BO_BlkAR_3 will be closed.
Transfer signal relay retransmits transfer signals and provides two normally open contacts
respectively. When the binary input [VBI_Recv1_TS] or [VBI_Recv2_TS] is energized, these
contacts BO_Recv1_TS_1 and BO_Recv1_TS_2 or BO_Recv2_TS_1 and BO_Recv2_TS_2 will
be closed.
Channel alarm relay outputs channel alarm signal and provides two normally open contacts:
[BO_Alm_Ch_1] and [BO_Alm_Ch_2]. When the protective device does not receive the signal
from remote end, data frame is abnormal during data transmission, the settings related with
channel of protective device on both ends are wrong, including [Equip_ID], [ID_Local],
[ID_Remote] and [En_InnClock_ChA], or error rate of channel is greater than 0.1%, these contacts
will be closed.
6.3.9 BO Module
NR1551A
COM1
COM2
02
COM
03
04
06
TJA-1
05
TJA-2
08
TJB-1
07
TJB-2
10
TJC-1
09
TJC-2
12
HJ-1
11
14
Pin No.
Sign
01
COM5
16
13
TJA
15
TJC
18
TJB
17
COM3
20
TJA-3
19
TJC-3
22
TJB-3
21
COM4
24
TJA-4
23
TJC-4
26
TJB-4
25
HJ
28
HJ
27
HJ-2
30
HJ-2
29
Description
02
COM1
02~05
BO_TrpA_1
02~07
BO_TrpB_1
02~09
BO_TrpC_1
04
COM2
108
04~08
BO_TrpA_2
04~10
BO_TrpB_2
04~12
BO_TrpC_2
20
COM3
20~19
BO_TrpA_3
20~21
BO_TrpB_3
20~22
BO_TrpC_3
24
COM4
24~23
BO_TrpA_4
24~25
BO_TrpB_4
24~26
BO_TrpC_4
16
COM5
16~15
BO_TrpA_5
16~17
BO_TrpB_5
16~18
BO_TrpC_5
01~11
BO_Cls_1
27~28
BO_Cls_3
29~30
BO_Cls_2
Tripp 1
Trip 2
BO_TrpA_1
Remote signal
BO_TrpA_2
05
BO_TrpA_5
08
15
BO_TrpB_5
17
BO_TrpB_1
BO_TrpB_2
07
BO_TrpC_5
10
18
16
BO_TrpC_1
BO_TrpC_2
BO_Cls_3
09
12
02
04
27
28
Trip 3
Trip 4
BO_TrpA_3
Reclosing 1
BO_TrpA_4
19
BO_TrpB_3
BO_Cls_1
11
23
BO_TrpB_4
21
BO_TrpC_3
25
BO_TrpC_4
22
26
20
24
01
Reclosing 2
BO_Cls_2
29
30
109
breaker arrangement, the normally open contact BO_TrpA_2, BO_TrpB_2 and BO_TrpC_2 are
used to trip the second circuit breaker.
6.3.10 BO Module
NR1551B
COM1
02
01
COM2
04
03
06
Pin No.
Sign
TJA-5
05
TJA-6
08
TJB-5
07
TJB-6
10
TJC-5
09
TJC-6
12
11
14
13
COM3
16
TJA-7
15
TJC-7
18
TJB-7
17
COM4
20
TJA-8
19
TJC-8
22
TJB-8
21
24
23
26
25
28
27
30
29
Description
02
COM1
02~05
BO_TrpA_5
02~07
BO_TrpB_5
02~09
BO_TrpC_5
04
COM2
04~08
BO_TrpA_6
04~10
BO_TrpB_6
04~12
BO_TrpC_6
16
COM3
16~15
BO_TrpA_7
16~17
BO_TrpB_7
16~18
BO_TrpC_7
20
COM4
20~19
BO_TrpA_8
20~21
BO_TrpB_8
20~22
BO_TrpC_8
110
6.3.11 BO Module
NR1560A
Pin No.
BO1
02
BO1
01
BO2
04
BO2
03
06
05
08
07
BO3
10
BO3
09
BO4
12
BO4
11
BO5
14
BO5
13
BO6
16
BO6
15
BO7
18
BO7
17
BO8
20
BO8
19
BO9
22
BO9
21
BO10
24
BO10
23
26
25
28
27
30
29
Sign
Description
01~02
BO1
03~04
BO2
09~10
BO_Trp3P_Lockout_1
11~12
BO_Trp3P_Lockout_2
13~14
BO_Inprog_AR_1
15~16
BO_Inprog_AR_2
111
17~18
BO_BI_Lockout_1
19~20
BO_BI_Lockout_2
21~22
BO_Fail_AR_1
23~24
BO_Fail_AR_2
automatic reclosure
Binary output 2 of receiving the external signal of blocking
automatic reclosure
BO1
BO_Trp3P_Lockout_1
01
09
02
BO2
10
BO_Trp3P_Lockout_2
11
03
04
Auto-reclosing in progress
12
Blocking auto-reclosing
BO_Inprog_AR_1
BO_BI_Lockout_1
13
17
18
14
BO_Inprog_AR_2
BO_BI_Lockout_2
15
19
16
20
Fail in auto-reclosing
BO_Fail_AR_1
BO_Fail_AR_2
21
23
22
24
please check the rated input voltage of the power supply module is the same as the voltage of
control power supply.
The power supply module provides terminal 012 and ground screw for the grounding of device.
Firstly, please connect the terminal 012 to the ground screw, and then use special ground wire to
connect it to the grounding copper busbar of cabinet. Good grounding is the most important
measure for keeping the device free from electromagnetic interference, hence, before the
application of the device, we must ensure that it has been well grounded.
NR1301A
COM1
01
BSJ1
02
BO_Fail_1
02
BO_Alm_Abnor_1
BJJ1
03
COM2
04
BSJ2
05
03
01
BO_Fail_2
05
BO_Alm_Abnor_2
BJJ2
06
06
24V+
07
04
24V-
08
09
DC+
10
DC-
11
GND
12
Grounding Screw
Grounding Bus
Sign
Description
01
Common_1
Common terminal 1
02
BO_Fail_1
03
BO_Alm_Abnor_1
04
Common_2
Common terminal 2
05
BO_Fail_2
06
BO_Alm_Abnor_2
07
Opto_L+
08
Opto_L-
09
Blank
10
11
12
Pwr+
Pwr-
GND
Ground
113
114
elements for lighting up, including protection elements, alarm elements and binary input
elements.
3. Use the column
resetting must be performed by the resetting button once it is lit. In case of No selected, the
signals will reset automatically once the input signal returns.
4. If users hope the User_defined_LED_1 is lit and held when DPFC differential element
operates, configure it as per the following picture.
5. The label of the User_defined_LED_1 can be edited by double-click it.
6. The signal in the column of Signal can be moved up, moved down, inserted or deleted by
right-click, and then left-click to execute corresponding command (up, down, insert, delete).
115
(unit: ms) of the corresponding binary inputs, which can be set separately.
3. The column
inputs provided, which needs the user to configure. User can draw it from the right list.
4. The signal in the column of Destination can be deleted by right-click, and then left-click to
execute delete command.
116
at the right to
point to a or several binary output contact. The optional signals include: Trip Elements, Alarm,
Binary Change and Other Type (Reserved).
3. In the event that user want to use the contact
as alarm
output contacts of channel A abnormality, find the corresponding alarm element in the right
tree structure and draw it to the corresponding position as below.
4. The signal added in the column of Source can be deleted by right-click, and then left-click to
execute delete command.
117
118
Chapter 8 Settings
Chapter 8 Settings
The equipment has 10 setting groups for protection to coordinate with the mode of power system
operation, one of which is assigned to be active. However, equipment parameters are common for
all protection setting groups.
Note!
All current settings in this chapter are secondary current converted from primary current by
CT ratio. Zero sequence current or voltage setting is configured according to 3I0 or 3U0
and negative sequence current setting according to I2 or U2.
Overview
Item
Range
IP_Addr_NetA
Subnet_Mask_A
En_NetA
IP_Addr_NetB
Subnet_Mask_B
En_NetB
IP_Addr_NetC
Subnet_Mask_C
En_NetC
10
IP_Addr_NetD
11
Subnet_Mask_D
12
En_NetD
13
Comm_Addr
0~255
14
COM1_Baud
4800,9600,19200,38400,57600,115200
15
COM2_Baud
4800,9600,19200,38400,57600,115200
16
COM1_Protocol
0, 1 or 2
17
COM2_Protocol
0, 1 or 2
18
En_BlkComm
0 or 1
19
Printer_Baud
20
En_Auto_Print
0 or 1
21
En_HiSpeed_Print
0 or 1
22
Opt_TimeSync
0, 1 or 2
119
Chapter 8 Settings
No.
23
Item
En_DualNet_GOOSE
Range
0 or 1
Setting Description
1.
Comm_Addr
Communication address between the protective device with the SCADA or RTU via RS-485
5.
COM1_Baud
COM2_Baud
COM1_Protocol
COM2_Protocol
En_BlkComm
It is set as 1 when the device is in maintenance. During such period, the fault report due to test
will not be sent upstream through communication ports, while local display and printing will not be
affected.
It is set as 0 when the device is in service. The relation between this setting and binary input
[BI_BlkComm] is OR, i.e. as long as one of them is set as 1, such information as fault report
and waveform will not be sent upstream.
120
Chapter 8 Settings
10. Printer_Baud
If automatic print is required for fault report after protection operating, it is set as 1. Otherwise, it
should be set to 0.
12. En_HiSpeed_Print
It is set as 0 for common printing with high definition, while it is set as 1 for high-speed printing.
13. Opt_TimeSync
1: Enable both net A link and net B link of the GOOSE module, and then the GOOSE module is
able to work in dual Ethernet mode.
0: Disable net B link of the GOOSE module, and then the GOOSE module can only work in single
Ethernet mode.
Overview
1.
Item
Range
1~10
Set Value
ActiveGrp
Equip_ID
I1N
0~9999 A
1200A
I2N
1A or 5 A
1A
U1N
0~1200 kV
220V
En_BI_GOOSE
0 or 1
Line2
ActiveGrp
It is current active setting group. 10 setting groups are provided for selecting, group number from 0
to 9. Equipment parameter is shared for 10 setting groups.
2.
Equip_ID
It is intended to set Chinese character field codes (12 bits) or ASCII codes (last 6 bits), which can
NANJING NARI-RELAYS ELECTRIC CO., LTD
121
Chapter 8 Settings
be recognized by the device automatically. Such setting is used for printing messages.
3.
I1N
I2N
U1N
En_BI_GOOSE
This setting is usually used for the case that GOOSE scheme is adopted in the bay level of digital
substation. When it is set as 1, the binary signal is valid received from GOOSE net and is invalid
received via opto-coupler, but corresponding binary input change report is still generated if the
status of binary input is changed. When it is set as 0, the binary signal is invalid received from
GOOSE net and is valid received via opto-coupler, but corresponding binary input change report is
still generated if the status of binary input is changed.
Overview
Item
Remark
Range
Unit
I_DPFC_OC_FD
I_ROC_FD
Z_DPFC
K_Corr_CT
I_Diff
I_Diff_CTS
ID_Local
0~65535
ID_Remote
0~65535
K0
zero-sequence
coefficient
0.00~2.00
10
I_OC_PSBR
122
ohm
0.20~10.00
compensation
Chapter 8 Settings
11
Z_PG1
of
12
Z_PG2
of
13
t_PG2
14
Z_PG3
15
t_PG3
16
Z_PP1
of
17
Z_PP2
of
18
t_PP2
19
Z_PP3
20
t_PP3
21
Z_Rev
22
t_Rev
23
R_Blinder
ohm
R1_Quad
ohm
R2_Quad
ohm
26
R3_Quad
ohm
27
phi1_Reach
Deg
28
phi0_Reach
Deg
29
phi_Shift_ZPG
of
0~30
Deg
30
phi_Shift_ZPP
of
0~30
Deg
31
I_ROC1
24
25
of
of
(0.00~220.00)/In
ohm
(0.00~220.00)/In
ohm
(0.00~220.00)/In
s
ohm
s
(0.00~220.00)/In
ohm
(0.00~220.00)/In
ohm
(0.00~220.00)/In
s
ohm
s
ohm
s
A
123
Chapter 8 Settings
I_ROC2
33
t_ROC2
34
I_ROC3
35
t_ROC3
36
I_ROC4
37
t_ROC4
38
I_InvROC
current
setting
of
inverse-time
(0.02~40.00)In
zero-sequence overcurrent protection
39
t_InvROC
time
delay
of
inverse-time
0.00~10.00
zero-sequence overcurrent protection
40
I_ROC_SOTF
41
I_OC_VTS
42
I_ROC_VTS
43
t_OC/ROC_VTS
44
I_OC1
45
t_OC1
46
I_OC2
47
t_OC2
48
I_OC3
49
t_OC3
50
Opt_InvOC3
51
I_OC_BFP1
124
of
(0.02~40.00)In
Chapter 8 Settings
52
I_ROC_BFP1
53
I_NegOC_BFP1
54
I_OC_BFP2
55
I_ROC_BFP2
56
I_NegOC_BFP2
A
s
t_BFP1
58
t_BFP2
59
phi_Diff_SynChk
Deg
60
phi_Fix_Diff
Deg
61
f_Diff_SynChk
frequency
difference
synchronism check
57
62
V_Diff_SynChk
limit
of
0.02~1.00
Hz
63
V_Dead
64
V_Live
65
t_VoltChk
66
t_SynChk
time delay
condition
0.01~50.00
67
t_1P_AR
68
t_3P_AR
69
t_CBClsd_AR
70
t_Unsuc_AR
waiting
time
before
announcing
0.00~250.00
unsuccessful auto-reclosing
71
t_Wait_SynChk
72
t_PW_AR
73
t_Reclaim_AR
minimum
of
time
synchronism
required
check
0.00~50.00
0.00~50.00
between 0.00~250.00
125
Chapter 8 Settings
X1L
ohm
75
R1L
ohm
76
X0L
(0.00~550)/In
ohm
77
R0L
(0.00~550)/In
ohm
78
XC1L
positive-sequence
impedance of the line
(40~65535)/In
ohm
79
XC0L
ohm
80
Z_Reac_Local
ohm
81
Z_GndReac_Local
ohm
82
Z_Reac_Remote
ohm
83
Z_GndReac_Remote
ohm
84
LineLength
0.00~655.35
85
Line_ID
0-65535
Setting Description
1.
I_DPFC_OC_FD
capacitive
kM
I_ROC_FD
Z_DPFC
I_Diff
Chapter 8 Settings
Setting principle: it shall be greater than the maximum unbalance current under the maximum load
conditions, and 400A~700A (primary current) is recommended. When the logic setting
[En_CapCurrComp] is set as 0, it can be appropriately increased, and 500A~800A (primary
current) is recommended.
5.
ID_Local
6.
ID_Remote
Used to confirm that equipments at both ends of line are compatible. The end of which setting
[ID_Local] should be same as the [ID_Remote] of the other and the greater [ID_Local] between
the two ends is chosen as a master end for sampling synchronism, the other is a slave end. If the
setting [ID_Local] is set as same as [ID_Remote], that means the equipment in loopback testing
state.
7.
K_Corr_CT
The ratio of CTs on two terminals of the line could be different. it could be corrected by setting
[K_Corr_CT].
Setting principle: Suppose CT ratio, Terminal M: kM=IM1n : IM2n; Terminal N: is and kN=IN1n : IN2n
IM1n: primary rated current of terminal M, IM2n: secondary rated current of terminal M
IN1n: primary rated current of terminal N, IN2n: secondary rated current of terminal N
If IM1n>= IN1n, then set [K_Corr_CT]
Terminal M: [K_Corr_CT]=1.00
Terminal N: [K_Corr_CT]=IN1n / IM1n
For example:
Terminal M: CT ratio=2500:1, its setting [K_Corr_CT] is set as 1.0
Terminal N: CT ratio=1250:5, its setting [K_Corr_CT] is set as 0.5
8.
I_Diff_CTS
K0
127
Chapter 8 Settings
Setting principle: Setting of the impedance and time delay of these zones should meet
requirements between various zones and operation should be ensured even for fault at end of the
line.
21. Z_Rev
Chapter 8 Settings
Setting step: 1
Phase angle of positive and zero sequence impedance of the line. Set as they should be.
29. phi_Shift_ZPG
Setting step: 1
Phase shift of zone 1 and 2 phase-to-ground distance element. Recommended value: 30for
length of the line < 10 km, 15for length 10 km and 0for length 40 km.
30. phi_Shift_ZPP
Setting step: 1
Phase shift of zone 1 and 2 phase-to-phase distance element. Recommended value: 30for
length of the line < 2 km, 15for length 2 km and 0for length 10 km.
31. I_ROC1
32. I_ROC2
33. t_ROC2
34. I_ROC3
35. t_ROC3
129
Chapter 8 Settings
36. I_ROC4
37. t_ROC4
Current settings and time delay of stage 1~4 of directional zero-sequence overcurrent protection.
38. I_InvROC
It is set according to the fault condition via maximum fault resistance (i.e. maximum fault
resistance takes 100 for 220kV transmission line and 300 for 500kV transmission line), and it
shall be greater than the maximum unbalanced current during the normal operation condition,
usually not greater than 300A.
39. t_InvROC
It is the time constant of normal IDMT equation and the following criterion shall be met:
t 0ZDinv TS + t
t 0ZDinv t 0ZD2XL + t
Where:
t 0ZDinv : The time delay of the inverse-time zero-sequence overcurrent protection
t 0ZD2XL : The time delay of zone 2 of directional zero-sequence overcurrent protection in the
adjacent line
Chapter 8 Settings
Time setting of phase and zero sequence overcurrent elements for VTS.
44. I_OC1
45. t_OC1
46. I_OC2
47. t_OC2
48. I_OC3
49. t_OC3
Current settings and time delay of stage 1~4 of directional zero-sequence overcurrent protection.
50. Opt_InvOC3
131
Chapter 8 Settings
Setting step: 1
Phase difference limit for synchronism check
60. phi_Fix_Diff
Setting step: 1
The line voltage can be phase or phase-to-phase voltage, and this setting is referred to the angle
that line voltage is lagged behind the busbar voltage during synchronism check.
For example, in case busbar voltage adopts phase A voltage, the fixed phase difference between
UB and UL is as follows:
UL
AB
BC
CA
phi_Fix_Diff
120
240
330
90
30
61. f_Diff_SynChk
Chapter 8 Settings
Setting principle: the setting should be set according to actual conditions, and is generally set as
80%Un.
65. t_VoltChk
133
Chapter 8 Settings
72. t_PW_AR
Setting step: 1
Setting principle: when the logic setting [En_CapCurrComp] is set as 1, they must be set
according to actual parameters of total transmission line (secondary value). If no actual measured
value is provided, the following table can be as a reference.
Capacitive impedance and current of overhead per 100KM based on different voltage class
Voltage Class
XC1
XC0
Capacitance current
220kV
3700
5260
34A
330kV
2860
4170
66A
500kV
2590
3790
111A
750kV
2242
3322
193A
However, when the logic setting [En_CapCurrComp] is set as 1, they can be set as any value
within its setting range, or [XC0L]=1.5Un/[I_Pkp_Diff]; [XC1L]=Un/[I_Pkp_Diff].
It is worth of attention that [XC1L] must be smaller than [XC0L].
80. Z_Reac_Local
Setting step: 1
Setting principle: if shunt reactor is equipped with the local substation, it shall be set as the
134
Chapter 8 Settings
secondary value of shunt reactor of local substation, otherwise, it can be set as 6000. When
the logic setting [En_CapCurrComp] is set as 0, this setting can be set as any value within its
setting range.
81. Z_GndReac_Local
Setting step: 1
Setting principle: if ground reactor is equipped with the local substation, it shall be set as the
secondary value of ground reactor of local substation, otherwise, it can be set as 6000. When
the logic setting [En_CapCurrComp] is set as 0, this setting can be set as any value within its
setting range.
82. Z_Reac_Remote
Setting step: 1
Setting principle: if shunt reactor is equipped with the remote substation, it shall be set as the
secondary value of shunt reactor of remote substation, otherwise, it can be set as 6000. When
the logic setting [En_CapCurrComp] is set as 0, this setting can be set as any value within its
setting range.
83. Z_GndReac_Remote
Setting step: 1
Setting principle: if ground reactor is equipped with the remote substation, it shall be set as the
secondary value of ground reactor of remote substation, otherwise, it can be set as 6000.
When the logic setting [En_CapCurrComp] is set as 0, this setting can be set as any value within
its setting range.
84. LineLength
Total length of the line. The actual total length of the line km, used for calculation of fault location.
85. Line_ID
Number of the line. The actual identification number of the transmission line in site, only used for
printing report.
Note!
For impedance setting, even if some zones of distance element are disabled, these
settings must meet the following relation:
[Z_PP3][Z_PP2][Z_PP1]
[Z_PG3][Z_PG2][Z_PG1]
Impedance setting of zone 3 of distance element should be sensitive to fault at end of the
line.
135
Chapter 8 Settings
Note!
All zero-sequence current settings should be greater than that of zero-sequence current
fault detector element. These settings must meet the following relation:
[I_ROC1][I_ROC2][I_ROC3][I_ROC4][I_ROC_FD]
[I_OC1][I_OC2][I_OC3]
Item
En_Z_DPFC
En_DiffP_ChA
En_DPFC_Diff1
En_DPFC_Diff2
En_Stdy_Diff1
En_Stdy_Diff2
En_REF
En_PhSeg_RecvTT
En_3P_RecvTT
10
En_CompCurr
136
Remark
Chapter 8 Settings
11
En_CTSBlkDiff
12
En_InnClock_ChA
13
En_FD_Ctrl_TT
14
En_LineVT
0: disable
enable differential protection blocked during CT circuit
failure
1: enable
0: disable
enable inner clock of channel A
1: enable
0: disable
transfer trip controlled by local fault detector
1: enable
0: disable
primary voltage of VT deriving from line voltage
1: from line VT
0: from busbar VT
En_PSBR
En_ZPG1
En_ZPG2
18
En_ZPG3
19
En_ZPP1
20
En_ZPP2
En_ZPP3
En_ZPG_Rev
23
En_ZPP_Rev
24
En_Blinder
En_ZPG1_Quad
15
16
17
21
22
25
137
Chapter 8 Settings
En_ZPG2_Quad
27
En_ZPG3_Quad
28
En_BI_Z1_Vld
29
En_Z2SOTF_AR3P
30
En_Z3SOTF_AR3P
En_ROC1
En_ROC2
En_ROC3
En_ROC4
of
directional
En_Dir_ROC3
of
directional
En_Dir_ROC4
37
En_InvROC
38
En_Dir_InvROC
26
31
32
33
34
35
36
138
Chapter 8 Settings
0: disable
En_ROC3_SOTF
40
En_ROC4_SOTF
41
En_OC1
42
En_OC2
En_OC3
En_Dir_OC1
En_Dir_OC2
En_Dir_OC3
En_InvOC3
En_BFP
En_ROC_1P_BFP
50
En_ROC_BFP
51
En_NegOC_BFP
39
43
44
45
46
47
48
49
139
Chapter 8 Settings
52
En_BFP_12
53
En_3PTrip
En_ZPP2_Blk_AR
En_ZPG2_Blk_AR
En_ROC2_Blk_AR
En_ROC3_Blk_AR
En_3PTrpOC1_Blk_AR
En_3PTrpOC2_Blk_AR
En_PhSF_Blk_AR
61
En_PDF_Blk_AR
62
En_MPF_Blk_AR
54
55
56
57
58
59
60
140
Chapter 8 Settings
1: enable
0: disable
En_3PF_Blk_AR
64
En_PhVolt_Syn
65
En_SynChk_AR
66
En_DdB_DdL_AR
En_LvB_DdL_AR
En_DdB_LvL_AR
En_NoChk_AR
En_AR
enable auto-reclosing
1: enable
0: disable
En_SetOpt_AR
En_1P_AR
En_3P_AR
En_1/3P_AR
63
67
68
69
70
71
72
73
74
Setting Description
1.
En_Z_DPFC
141
Chapter 8 Settings
For short transmission line, if the secondary value of line impedance is less than 1/IN, DPFC
distance protection should be disabled.
2.
En_FD_Ctrl_TT
If the setting is set as 1, transfer tripping controlled by local fault detector. Local trip circuit could
be active by remote command (i.e. [VBI_RecvTT]=1) only when local fault detector initiates. if do
not use transfer tripping, the setting should be set as 1.
3.
En_LineVT
If three-phase voltage used for protection measurement comes from line side (for example, 3/2
breaker), it should be set as 1. If three-phase voltage comes from busbar side, it should be set as
0.
1: Three phase voltage is from line voltage, synchronism voltage is single-phase voltage from bus
voltage
0: Three phase voltage is from bus voltage, synchronism voltage is single-phase voltage from line
voltage
Note!
The setting must be set carefully. The no-voltage check and the synchronous check will
determine the locations of line voltage and busbar voltage on the basis of the setting. If the
setting is mistaken, the mistaken judgment may be made.
4.
En_PSBR
The function of power swing blocking for zone 1,2 of distance element;
1: enable; zone 1,2 of distance element is controlled by PSB element.
0: disable; zone 1,2 of distance element is not controlled by PSBR element, and power swing
blocking for zone 1,2 of distance element is released all along.
5.
En_Z2SOTF_AR3P
6.
En_Z3SOTF_AR3P
If the setting is set as 1, zone2, 3 of distance element for auto-reclosing SOTF is enabled. If the
power swing does not occur after reclosing, the corresponding zone of distance protection which is
not controlled by power swing block will trip after a shorter time delay than [t_PG2] or [t_PP2] and
[t_PG3] or [t_PP3].
7.
En_3P_Trip
If it is set as 1, three-pole tripping will be implemented for any fault but auto-reclosing is not
blocked.
8.
En_SetOpt_AR
When the setting is set as 1, AR mode can be selected by logic settings [En_1P_AR], single-pole
142
Chapter 8 Settings
AR, [En_3P_AR], three-pole AR, and [En_1/3P_AR], single-pole and three-pole AR. Conversely, if
it is set as 0, AR mode can be selected by switch on the panel. Please refer to section 6.3.6.
1.
VEBI setting
Remark
En_Remote_Cfg
0: disable
1: enable
VEBI_DiffP
VEBI_DistP
VEBI_ROC
VEBI_OC
VEBI_Lockout
En_Remote_Cfg
This setting is used to determine whether the protection settings can be modified remotely via
SCADA or RTU. 1 means that settings can be remotely configured via SCADA or RTU, otherwise,
it should be set to 0.
Each VEBI setting is one of the conditions that decide whether the relevant protection is in service,
when this relay is energized. Through SAS or RTU, the VEBI settings can be set as 1 or 0;
and it means that the relevant protection can be in service or out of service through remote
command. It provides convenience for operation management.
These virtual binary inputs provide a convenient way for the operator to put the function in service
or out of service remotely away from an unattended substation.
Except for [VEBI_Lockout], logic relation between these virtual enable binary inputs mentioned in
the table and corresponding logic setting is AND. If it is set as 1, auto-reclosing will be locked out.
It should be set as 0 generally.
143
Chapter 8 Settings
No.
GOOSE VEBI
Range
Remark
GVEBI_Remote_Cfg
0, 1
GVEBI_Recv_xx
0, 1
0, 1
144
GVEBI_Send_xx
9.1 Overview
The human-machine interface consists of a human-machine interface (HMI) module which allows
a communication to be as simple as possible for the user. The HMI module helps to draw your
attention to something that has occurred which may activate a LED or a report displayed on the
LCD. Operator can locate the data of interest by navigating the keypad.
5
ALARM
xx
VT ALARM
xx
AR READY
xx
CH A ALARM
xx
CH B ALARM
xx
TRIP A
xx
TRIP B
xx
TRIP C
xx
RECLOSE
xx
PCS - 931
LINE DIFFERENTIAL RELAY
ENT
ESC
xx
GR
P
HEALTHY
3
4
Item
Description
LCD
LED
Keypad
Numeric keypad and command keys for full access to the relay
Communication port
145
Logo
2.
3.
ESC:
ENT:
GRP
4.
5.
6.
Page up/down
When the protection device runs normally after it is energized, the HEALTHY LED should be on
all the time. Only with serious fault (such as chip damage, check error of setting, etc.) will the
146
When the protection device runs normally after it is energized, the ALARM LED should go out.
Only when abnormal situations except channel abnormity and VT circuit failure happen, will the
signal indicator lamp be lightened. This signal lamp goes out automatically when the abnormal
situations disappear.
After the protection device is energized, if it works normally, the VT ALARM LED shall not be on.
Only when the secondary circuit of busbar VT or line VT fails, will the VT ALARM LED be
lightened. Moreover, it will go out automatically in 10 seconds after the abnormal situations
disappear.
After the protection device is energized, the AR READY LED shall go out. Only when all the
charging conditions for automatic reclosure are met can the AR READY LED be lightened after
10s. After the reclosing is executed for one shot, the AR READY LED will go out automatically.
When the protection device runs normally after it is energized, the CH A ALARM LED should go
out. Only when the channel A has error codes or invalid data frames, etc. will the signal indicator
lamp be lightened.
When the protection device runs normally after it is energized, the CH B ALARM LED should go
out. Only when the channel B has error codes or invalid data frames, etc. will the signal indicator
lamp be lightened.
After the protection device is energized, normally the TRIP A LED should go out. Only when the
protection device sends out phase A tripping signal will the signal lamp be lightened.
After the protection device is energized, normally the TRIP B LED should go out. Only when the
protection device sends out phase A tripping signal will the signal lamp be lightened.
147
After the protection device is energized, normally the TRIP C LED should go out. Only when the
protection device sends out phase A tripping signal will the signal lamp be lightened.
After the protection device is energized, normally the RECLOSE LED should go out. Only when
the protection device sends out reclosing signal will the signal lamp be lightened.
Note!
Another 10 LED indicators are programmable and user can configure them to be lit by
signals of operation element, alarm element and binary output contact according to
requirement through PCS-PC software.
9.1.4 Communication
The MON module is comprised by embedded processor of high performance, FLASH, SRAM,
SDRAM, Ethernet controller and other peripheral equipments. It can realize the management,
human machine interface, communication and waveform recording of the whole device. The MON
module uses the data of other modules in the receiver device of internal bus, and communicates
with LCD panel via RS-485 bus.
148
NR1102C
ETHERNET 1
ETHERNET 2
ETHERNET
Network A
Network B
SYN+
SYNSHLD
GND
RXD
TXD
SGND
GND
101
SYN+
102
SYN-
103
SHLD
104
GND
105
RXD
106
TXD
107
SGND
108
GND
Connect the printer; both the receiving and sending directions of which are
stated on the basis of the device.
149
again, one command menu will be recorded in the quick menu after its first execution. Five latest
menu commands can be recorded in the quick menu. When the five menu commands are
recorded, the latest menu command will cover the earliest one, adopting the first in first out
principle. It is arranged from top to bottom and in accordance with the execution order of command
menus. Press to enter the main menu with the interface as shown in the following diagram:
For the first powered protective device, there is no recorded shortcut menu. Press to enter the
main menu with the interface as shown in the following diagram:
INTERFACE
TEST_MODE
VERSION
CLOCK
LOCAL_CTRL
SETTINGS
PRINT
REPORT
VALUES
150
151
Under the main interface, press to enter the main menu, and select submenu by pressing ,
and ENT. The command menu adopts a tree shaped content structure. The above diagram
provides the integral structure and all the submenus under menu tree of the protection device.
9.2.2 VALUES
This menu is mainly used to display the real time sampling value of current, voltage and phase
angle and the state of binary inputs (including binary inputs via opto-coupler and GOOSE binary
inputs) and alarm signals in the protection device. Besides, the communication state of optical
fibre channel and sampling channel by ECVT are also be checked. This menu fully reflects the
running environment of the protection device. As long as the displayed values consist with the
actual running situation, basically, the protection device can work normally. This menu is set to
greatly facilitate the debugging and maintenance of people on site.
This menu includes the following command menus.
No.
Item
Function description
CPU_METERING
MON_METERING
PHASE_ANGLE
BI_STATE
Display the state of binary inputs which are the result of AND
operation of GOOSE BI STATE and OPT BI STATE
OPT_BI_STATE
GOOSE_BI_STATE
ALM_STATE
COMM_CH_STATE
SMPL_CH_STATE
9.2.3 REPORT
This menu is used to display the fault reports, self-supervision reports, binary input change reports
and control reports, so that the operator can load to view and use as the reference of analyzing
accidents and maintaining the protection device. All the reports are stored in non-volatile memory,
it can still record the reports even if it loses its power.
This menu includes the following command menus.
No.
Item
Function description
TRP_REPORT
ALM_REPORT
BI_CHG_REPORT
CTRL_REPORT
152
9.2.4 PRINT
This menu is used for printing device description, setting, fault reports, self-supervision reports,
binary input change reports, waveform, information related with IEC60870-5-103 Protocol,
channel state and channel statistic.
This menu includes the following command menus and submenus.
No.
Item
Function description
EQUIP_DESCRON
SETTINGS
TRP_REPORT
ALM_REPORT
BI_CHG_REPORT
CH_SELF_CHECK
CH_STATISTIC
PRESENT_VALUES
WAVEFORM
10
PROTOCOL
11
CANCEL_PRINT
Cancel print
Item
Function description
EQUIP_SETTINGS
EQUIP_VEBI_SETTINGS
GOOSE_VEBI_SETTINGS
SYS_SETTINGS
PROT_SETTINGS
ALL_SETTINGS
153
parameters, protection
GOOSE VEBI settings
7
LATEST_MODIFIED
settings,
VEBI
settings
and
Item
Function description
CHA
Item
Function description
Print the statistic report of optical fibre channel A, which is formed A.M.
9:00 every day
CHA
Item
Function description
SMPL_WAVE
9.2.5 SETTINGS
This menu is used to check the equipment parameters, system parameters, protection settings,
VEBI settings and GOOSE VEBI settings, as well as modifying any of the above setting items.
Moreover, it can also execute the setting copy between different setting groups.
This menu includes the following command menus.
No.
Item
Function description
EQUIP_SETTINGS
EQUIP_VEBI_SETTINGS
GOOSE_VEBI_SETTINGS
SYS_SETTINGS
PROT_SETTINGS
COPY_SETTINGS
Item
Function description
TARG_RESET
TRIG_OSCILLOG
CLR_STATE
DOWNLOAD
CLR_GOOSE_RPT_STA
CONF_SMPL_CH_DLY
9.2.7 CLOCK
It is used to display and modify the current date and time of the protection device.
9.2.8 VERSION
It is used to check the information like the program version of each intelligent module in the
protection device and the program generating time.
9.2.9 TEST_MODE
This menu is mainly used for developers to debug the program and for engineers to maintain the
protection device. It can be used to check module information and tripping reports item by item,
and fulfill the communication test function. It is also used to generate all kinds of reports or events
to transmit to the SAS without any external input, so as to debug the communication on site.
This menu includes the following command menus.
No.
Item
Function description
BOARD_INFO
COMM_TEST
ITEM_TRP_REPORT
TRP_REPORT
ALM_REPORT
BI_CHG_REPORT
CH_REPORT
GOOSE_COMM_STATE
GOOSE_RPT_STA
155
9.2.10 INTERFACE
This menu is mainly used to set LCD display language. This menu includes the following
command menus.
No.
Item
LANGUAGE
Function description
The displayed content of the interface contains: the current date and time of the protection device
156
(with a format of yy-mm-dd hh:mm:ss:), the currently valid setting group number, the three-phase
current sampling value, the zero-sequence current sampling value, the three-phase voltage
sampling value, the zero-sequence voltage sampling value, the line voltage sampling value, line
frequency and bus frequency. if all the sampling values of the voltage and the current cant be fully
displayed within one screen, theyll be scrolling-displayed automatically from the top to the bottom.
If the device has detected any abnormal state, it will display the self-check alarm information.
Item
Description
Op_Z_DPFC
Op_DPFC_Diff1
Op_DPFC_Diff2
Op_Stdy_Diff1
Op_Stdy_Diff2
Op_REF
Op_PhSeg_RecvTT
Op_3P_RecvTT
157
Op_TT
10
Op_Z1
11
Op_Z2
12
Op_Z3
13
Op_Z_SOTF
14
Op_Prot_PDF
15
Op_ROC_SOTF
16
Op_OC1
17
Op_OC2
18
Op_OC3
19
Op_BFP1
20
Op_BFP2
21
Op_Z_Rev
Op_ROC1
Op_ROC2
Op_ROC3
Op_ROC4
22
23
24
25
26
Op_InvROC
Inverse-time
operating
27
Op_ROC_VTS
28
Op_OC_VTS
29
Op_PhSelFail
30
Op_1PTrpFail
31
Op_Persist1P
32
Op_AR
Auto-reclosing operating
33
Op_FD
34
Alm_Oscillog_CPU
35
Alm_Oscillog_MON
36
Op_ManTrigOscillog
Recording
waveform
TRIG_OSCILLO
37
BI_TrigOscillog
Recording
158
zero-sequence
waveform
overcurrent
initiated
initiated
protection
through
through
binary
menu
input
[BI_TrigOscillo]
38
BO_Fail_AR
Auto-reclosing is failure
Item
Description
Alm_Abnor_Smpl_CPU
Alm_Abnor_Smpl_MON
Alm_Setting
Alm_DSP_CPU
Alm_DSP_MON
Alm_PersistI0
Alm_PersistFD
Alm_VTS
Alm_VTS_Ux
10
Alm_CTS
CT circuit failure
11
Alm_52b
12
Alm_TrpOut
13
Alm_Pwr_Opto
14
Alm_ExTrp_BI
15
Alm_ID_ChA
16
Alm_ChA
17
Alm_NoValidFram_ChA
18
Alm_CRC_ChA
19
Alm_Connect_ChA
20
Alm_OutDiffP_ChA
21
Alm_Diff_ChA
22
Alm_CompParam_ChA
23
Alm_TT
24
Alm_EquipConfig
25
Alm_Setting_Out-of-Scope
[BI_52b_Phb]
and
159
26
Alm_BoardConfig
27
Alm_SynChkFail_AR
28
GAlm_NetStorm_NetA
29
GAlm_NetStorm_NetB
30
GAlm_Disc_NetA
31
GAlm_Disc_NetB
32
GAlm_CfgUnmatch
33
GAlm_NetA_GOOSExx
34
GAlm_NetB_GOOSExx
35
GAlm_CfgUnmatch_GOOSExx
36
BO_BlkAR
Blocking auto-reclosing
37
BO_Inprog_AR
Initiating auto-reclosing
38
BO_Lockout
Blocking auto-reclosing
Item
Description
EBI_DiffP
EBI_DistP
EBI_ROC
The
binary
input
of
enabling/disabling
zeros-sequence overcurrent protection
EBI_OC
EBI_Z1
EBI_Opt1_AR
EBI_Opt2_AR
160
directional
EBI_Lockout
BI_Opt1_ActiveGrp
10
BI_Opt2_ActiveGrp
BI_TrpA_Other
BI_TrpB_Other
BI_TrpC_Other
14
BI_3PTrp_Line
15
BI_3PTrp_G/T
16
BI_52b_Pha
17
BI_52b_Phb
18
BI_52b_Phc
19
BI_LowPres_AR
20
BI_TrigOscillog
21
BI_MCB_VT_Line
22
BI_MCB_VT_Bus
23
BI_Send_TT
24
BI_Send1_TS
25
BI_Send2_TS
26
VBI_RecvTT_ChA
27
VBI_RecvTS1_ChA
28
VBI_RecvTS2_ChA
29
VBI_RecvTT
30
VBI_RecvTS1
31
VBI_RecvTS2
32
VBI_DiffP_Rmt
33
VEBI_DiffP
34
VEBI_DistP
35
VEBI_ROC
The
VEBI
setting
of
enabling/disabling
zero-sequence overcurrent protection
11
12
13
directional
161
36
VEBI_Lockout
37
VEBI_OC
38
BI_Pulse_GPS
39
BI_Print
40
BI_BlkComm
41
BI_RstTarg
pulse
signal
communication
for
time
between
Note!
For binary signals [BI_Pulse_GPS], [BI_Print], [BI_BlkComm] and [BI_RstTarg], they are
not logged in the event recorder and only are viewed on the LCD through menu BI
STATE
Table 9.3-4 Binary input signals via opto-coupler
No.
Item
Description
EBI_Lockout_OPT
BI_TrpA_Other_OPT
BI_TrpB_Other_OPT
BI_TrpC_Other_OPT
BI_3PTrp_Line_OPT
BI_3PTrp_G/T_OPT
BI_52b_PhA_OPT
BI_52b_PhB_OPT
BI_52b_PhC_OPT
10
BI_LowPres_AR_OPT
11
BI_Send_TT_OPT
12
BI_Send1_TS_OPT
13
BI_Send2_TS_OPT
162
14
BI_Sparexx_OPT
No.
Item
Description
GBI_Lockout1
GBI_Lockout2
GBI_Lockout3
GBI_Lockout4
GBI_Lockout5
GBI_TrpA_Other
GBI_TrpB_Other
GBI_TrpC_Other
GBI_3PTrp_Line
10
GBI_3PTrp_G/T1
11
GBI_3PTrp_G/T2
12
GBI_3PTrp_G/T3
13
GBI_3PTrp_G/T4
14
GBI_3PTrp_G/T5
15
GBI_52b_PhA
16
GBI_52b_PhB
17
GBI_52b_PhC
18
GBI_LowPres_AR
19
GBI_Send_TT1
20
GBI_Send_TT2
21
GBI_Send_TT3
22
GBI_Send_TT4
23
GBI_Send1_TS1
24
GBI_Send1_TS2
25
GBI_Send1_TS3
26
GBI_Send1_TS4
27
GBI_Send2_TS1
28
GBI_Send2_TS2
29
GBI_Send2_TS3
30
GBI_Send2_TS4
31
GVEBI_Recv_xx
32
GVEBI_Send_xx
163
Item
Description
Reboot
Reset_Target
Settings_Chg
ActiveGrp_Chgd
Report_Cleared
Waveform_Cleared
SubProcess_Exit
2.
Press the or to move the cursor to the VALUES menu, and then press the
ENT or to enter the menu;
3.
Press the or to move the cursor to any command menu, and then press the
ENT to enter the menu;
4.
Press the or to page up/down (if all information cannot be displayed in one
display screen, one screen can display 14 lines of information at most);
5.
6.
Press the ENT or ESC to exit this menu (returning to the VALUES menu);
164
1.
2.
Press the or to move the cursor to the REPORT menu, and then press the
ENT or to enter the menu;
3.
Press the or to move the cursor to any command menu, and then press the
ENT to enter the menu;
NANJING NARI-RELAYS ELECTRIC CO., LTD
4.
5.
6.
7.
Press the ENT or ESC to exit this menu (returning to the REPORT menu);
For the fault report, view the single item tripping report by the command menu
ITEM_TRP_REPORT, and the item tripping report produces with change of any item of fault
report. The item tripping reports can save for 1024 times at most.
The operation is as follows:
1.
2.
Press the or to move the cursor to the TEST_MODE menu, and then press the
ENT or to enter the menu;
3.
4.
5.
Press the ESC to exit this menu (returning to the TEST_MODE menu).
2.
Press the or to move the cursor to the TEST_MODE menu, and then press the
ENT or to enter the menu;
3.
Press the or to move the cursor to the command menu BOARD_INFO, and
then press the ENT to enter the menu;
4.
5.
Press the ENT or ESC to exit this menu (returning to the TEST_MODE menu).
2.
Press the or to move the cursor to the PRINT menu, and then press the ENT
or to enter the menu;
3.
Press the or to move the cursor to any command menu, and then press the
ENT to enter the menu;
165
Press the or to select pervious or next record. After pressing the ENT, the LCD will
display Start Printing..., and then automatically exit this menu (returning to the menu PRINT). If
the printer does not complete its current print task and re-start it for printing, and the LCD will
display Printer Busy. Press the ESC to exit this menu (returning to the menu PRINT).
Press the or to move the cursor. Press the or to select the starting and ending
numbers of printing message. After pressing the ENT, the LCD will display Start Printing..., and
then automatically exit this menu (returning to the menu PRINT). Press the ESC to exit this
menu (returning to the menu PRINT).
4.
5.
If selecting the WAVEFORM or SETTINGS, press the ENT or to enter the next
level of menu;
6.
After entering the submenu SETTINGS, press or to move the cursor, and then
press the ENT to print the corresponding default value. If selecting the
PROT_SETTINGS or ALL_SETTINGS:
Press the or to select the setting zone to be printed. After pressing the ENT, the LCD will
display Start Printing..., and then automatically exit this menu (returning to the menu
SETTINGS). Press the ESC to exit this menu (returning to the menu SETTINGS).
7.
After entering the submenu WAVEFORM, press the ENT to enter the SMPL_WAVE.
Without waveform data, the LCD will display No Wave Form Data! (Before executing
the command menu SMPL_WAVE, it is necessary to execute the command menu
TRIG_OSCILLOG in the menu LOCAL_CTRL, otherwise the LCD will display No
Waveform Data!). With waveform data existing:
Press the or to select pervious or next record. After pressing the ENT, the LCD will
display Start Printing..., and then automatically exit this menu (returning to the menu
WAVEFORM). If the printer does not complete its current print task and re-start it for printing, and
the LCD will display Printer Busy. Press the ESC to exit this menu (returning to the menu
WAVEFORM).
166
1.
2.
Press the or to move the cursor to the SETTINGS menu, and then press the
ENT or to enter the menu;
3.
Press the or to move the cursor to any command menu, and then press the
ENT to enter the menu;
4.
5.
6.
7.
Press the ESC to exit this menu (returning to the menu SETTINGS).
Note!
If the displayed information exceeds 14 lines, the scroll bar will appear on the right side of
the LCD to indicate the quantity of all displayed information of the command menu and the
relative location of information where the current cursor points at.
2.
Press the or to move the cursor to the SETTINGS menu, and then press
the ENT or to enter the menu;
3.
Press the or to move the cursor to any command menu, and then press the
ENT to enter the menu;
4.
5.
6.
7.
Press the ESC to exit this menu (returning to the menu SETTINGS );
8.
If selecting the command menu EQUIP_SETTINGS, move the cursor to the setting
item to be modified, and then press the ENT;
Press the or to modify the value (if the modified value is of multi-bit, press the or
to move the cursor to the digit bit, and then press the or to modify the value), press the
ESC to cancel the modification and return to the displayed interface of the command menu
EQUIP_SETTINGS. Press the ENT to automatically exit this menu (returning to the displayed
interface of the command menu EQUIP_SETTINGS).
Move the cursor to continue modifying other setting items. After all setting values are modified,
press the , or ESC, and the LCD will display Save or Not?. Directly press the ESC or
press the or to move the cursor. Select the Cancel, and then press the ENT to
automatically exit this menu (returning to the displayed interface of the command menu
EQUIP_SETTINGS).
Press the or to move the cursor. Select No and press the ENT, all modified setting item
will restore to its original value, exit this menu (returning to the menu SETTINGS).
Press the or to move the cursor to select Yes, and then press the ENT, the LCD will
NANJING NARI-RELAYS ELECTRIC CO., LTD
167
Password:
For different setting items, their displayed interfaces are different but their modification
methods are the same. The following is ditto.
9.
If
selecting
the
command
menu
EQUIP_VEBI_SETTINGS
or
GOOSE_VEBI_SETTINGS, move the cursor to the setting to be modified, and then
press the ENT;
10. If selecting the command menu EQUIP_SETTINGS, move the cursor to the default
item to be modified, press the ENT
Note!
After modifying the parameter settings of the device, the HEALTHY indicator lamp of the
protection device will go out, and the protection device will automatically restart and
re-check the protection setting. If the check does not pass, the protection device will be
blocked.
11. If selecting the command menu PROT_SETTING, the LCD will display the following
interface:
168
5. PROT_SETTINGS
Please Select Group for Config
Active Group:
01
Selected Group:
02
Press the or to modify the value, and then press the ENT to enter it. Move the cursor to
the setting item to be modified, press the ENT to enter.
Note!
After modifying the equipment parameter of the device, the HEALTHY indicator lamp of
the protection device will go out, and the protection device will automatically restart and
re-check the protection setting. If the check does not pass, the protection device will be
blocked.
2.
Press the or to move the cursor to the SETTINGS menu, and then press the
ENT or to enter the menu;
3.
Press the or to modify the value. Press the ESC, and return to the menu SETTINGS.
Press the ENT, the LCD will display the interface for password input, if the password is incorrect,
continue inputting it, press the ESC to exit the password input interface and return to the menu
SETTINGS. If the password is correct, the LCD will display Copy Settings Success!, and exit
this menu (returning to the menu SETTINGS).
2.
169
Press the or to modify the value, and then press the ESC to exit this menu (returning to
the main menu). After pressing the ENT, the LCD will display the password input interface. If the
password is incorrect, continue inputting it, and then press the ESC to exit the password input
interface and return to its original state. If the password is correct, the HEALTHY indicator lamp
of the protection device will go out, and the protection device will re-check the protection setting. If
the check does not pass, the protection device will be blocked. If the check is successful, the LCD
will return to its original state.
2.
Press the , , , and ENT; Press the ESC to exit this menu (returning to
the original state). Press the ENT to carry out the deletion.
Note!
The operation of deleting device message will delete all messages saved by the protection
device, including fault report, self-supervision report and binary input change report.
Furthermore, the message is irrecoverable after deletion, so the application of the function
shall be cautious.
2.
Press the or to move the cursor to the CLOCK menu, and then press the
ENT to enter clock display
3.
4.
Press the + or - to modify value, and then press the ENT to save the modification
and return to the main menu;
5.
Press the ESC to cancel the modification and return to the main menu.
170
1.
2.
Press the or to move the cursor to the VERSION menu, and then press the
ENT to display the software version;
3.
2.
Press the or to move the cursor to the TEST_MODE menu, and then press the
ENT or to enter the menu;
3.
Press the or to move the cursor to the command menu COMM_TEST, and
then press the ENT to enter the menu, at this moment, the LCD will display Entering
Communication Test;
4.
Press the or to move the cursor to select the corresponding command menu All
Test, Trip Test, Alarm Test and BI Test.
Note!
If no input operation is carried out within 60s, exit the communication test and return to the
TEST_MODE menu, at this moment, the LCD will display Communication Test Timeout
and Exiting.
5.
If selecting the All Test, press the ENT, and the device will successively carry out the
Trip Test, Alarm Test and BI Test.
6.
If selecting the Trip Test, Alarm Test or BI Test, press the ENT.
7.
Press the + or - to page up/down, and then press the or to move the scroll bar.
(taking the Trip Test as an example):
Move the cursor to select the corresponding protection elements. Press the ENT to execute the
communication test one by one, the SAS will receive the corresponding fault report, and view the
fault report produced by communication test in the command menu ITEM_TRP_REPORT.
Note!
If no input operation is carried out within 60s, exit the communication transmission and
return to the TEST_MODE menu, at this moment, the LCD will display Communication
Test Timeout and Exiting.
If selecting the Alarm Test or BI Test, not only the SAS can receive the corresponding
self-check report or binary signals, but also the self-check report or binary signals
produced by communication test can be respectively viewed by the two command menus
of ALM_REPORT and BI_CHG_REPORT in the menu REPORT.
8.
Press the ESC to exit this menu (returning to the menu TEST_MODE, at this moment,
the LCD will display Communication Test Exiting.
Note!
171
The LCD interface provided in this chapter is a mere reference and available for explaining
specific definition of LCD. The displayed interface of the actual protection device may be
different from it, so you shall be subject to the actual protection device.
172
Chapter 10 Communications
Chapter 10 Communications
10.1 General Description
This section outlines the remote communications interfaces of NR Relays. The protective device
supports a choice of three protocols via the rear communication interface (RS-485 or Ethernet),
selected via the model number by setting. The protocol provided by the protective device is
indicated in the submenu EQUIP_SETTINGS.
The rear EIA RS-485 interface is isolated and is suitable for permanent connection of whichever
protocol is selected. The advantage of this type of connection is that up to 32 protective devices
can be daisy chained together using a simple twisted pair electrical connection.
It should be noted that the descriptions contained within this section do not aim to fully detail the
protocol itself. The relevant documentation for the protocol should be referred to for this
information. This section serves to describe the specific implementation of the protocol in the relay.
The EIA RS-485 two-wire connection provides a half-duplex fully isolated serial connection to the
product. The connection is polarized and whilst the products connection diagrams indicate the
polarization of the connection terminals it should be borne in mind that there is no agreed
definition of which terminal is which. If the master is unable to communicate with the product, and
the communication parameters match, then it is possible that the two-wire connection is reversed.
10.2.1.2 Bus Termination
The EIA RS-485 bus must have 120 (Ohm) Watt terminating resistors fitted at either end
across the signal wires (refer to Figure 10.2-1). Some devices may be able to provide the bus
terminating resistors by different connection or configuration arrangements, in which case
separate external components will not be required. However, this product does not provide such a
facility, so if it is located at the bus terminus then an external termination resistor will be required.
173
Chapter 10 Communications
The EIA RS-485 standard requires that each device is directly connected to the physical cable that
is the communications bus. Stubs and tees are expressly forbidden, such as star topologies. Loop
bus topologies are not part of the EIA RS-485 standard and are forbidden by it also.
Two-core screened cable is recommended. The specification of the cable will be dependent on the
application, although a multi-strand 0.5mm2 per core is normally adequate. Total cable length must
not exceed 500m. The screen must be continuous and connected to ground at one end, normally
at the master connection point; it is important to avoid circulating currents, especially when the
cable runs between buildings, for both safety and noise reasons.
This product does not provide a signal ground connection. If a signal ground connection is present
in the bus cable then it must be ignored, although it must have continuity for the benefit of other
devices connected to the bus. At no stage must the signal ground be connected to the cables
screen or to the products chassis. This is for both safety and noise reasons.
10.2.1.4 Biasing
It may also be necessary to bias the signal wires to prevent jabber. Jabber occurs when the signal
level has an indeterminate state because the bus is not being actively driven. This can occur when
all the slaves are in receive mode and the master is slow to turn from receive mode to transmit
mode. This may be because the master purposefully waits in receive mode, or even in a high
impedance state, until it has something to transmit. Jabber causes the receiving device(s) to miss
the first bits of the first character in the packet, which results in the slave rejecting the message
and consequentially not responding. Symptoms of these are poor response times (due to retries),
increasing message error counters, erratic communications, and even a complete failure to
communicate.
Biasing requires that the signal lines be weakly pulled to a defined voltage level of about 1V. There
should only be one bias point on the bus, which is best situated at the master connection point.
The DC source used for the bias must be clean; otherwise noise will be injected. Note that some
devices may (optionally) be able to provide the bus bias, in which case external components will
not be required.
Note!
174
Chapter 10 Communications
It is extremely important that the 120 termination resistors are fitted. Failure to do so will
result in an excessive bias voltage that may damage the devices connected to the bus.
As the field voltage is much higher than that required, NARI-RELAYS cannot assume
responsibility for any damage that may occur to a device connected to the network as a
result of incorrect application of this voltage.
Ensure that the field voltage is not being used for other purposes (i.e. powering logic inputs)
as this may cause noise to be passed to the communication network.
It is recommended to use twisted screened eight-core cable as the communication cable. A picture
is shown bellow.
Each equipment is connected with an exchanger via communication cable, and thereby it forms a
star structure network. Dual-network is recommended in order to increase reliability. SCADA is
also connected to the exchanger and will play a role of master station, so the every equipment
which has been connected to the exchanger will play a role of slave unit.
175
Chapter 10 Communications
Initialization (reset)
Time synchronization
General interrogation
General commands
Disturbance records
10.3.2 Initialization
Whenever the protective device has been powered up, or if the communication parameters have
been changed, a reset command is required to initialize the communications. The protective
device will respond to either of the two reset commands (Reset CU or Reset FCB), the difference
is that the Reset CU will clear any unsent messages in the transmit buffer.
The protective device will respond to the reset command with an identification message ASDU 5,
the COT (Cause Of Transmission) of this response will be either Reset CU or Reset FCB
depending on the nature of the reset command.
176
Chapter 10 Communications
All spontaneous events can be gained by printing, implementing submenu PROTOCOL in the
menu PRINT.
177
Chapter 10 Communications
Device Description
Device Parameter
Setting Group
Setting
Virtual Enabling BI
Measurement
10
Fault Data
11
Net Setting
12
Enabling BI
13
Operation Element
14
Alarm Info
15
178
Chapter 10 Communications
IEC 61850-5: Communications and requirements for functions and device models
These documents can be obtained from the IEC (http://www.iec.ch). It is strongly recommended
that all those involved with any IEC 61850 implementation obtain this document set.
MMS protocol
IEC 61850 specifies the use of the Manufacturing Message Specification (MMS) at the upper
(application) layer for transfer of real-time data. This protocol has been in existence for a number
of years and provides a set of services suitable for the transfer of data within a substation LAN
environment. Actual IEC 61850-7-2 abstract services and objects are mapped to MMS protocol
services in IEC61850-8-1.
2.
Client/server
This is a connection-oriented type of communication. The connection is initiated by the client, and
communication activity is controlled by the client. IEC61850 clients are often substation computers
running HMI programs or SOE logging software. Servers are usually substation equipment such
as protection relays, meters, RTUs, transformer, tap changers, or bay controllers.
NANJING NARI-RELAYS ELECTRIC CO., LTD
179
Chapter 10 Communications
3.
Peer-to-peer
A substation configuration language is a number of files used to describe IED and communication
system realized according to IEC 61850-5 and IEC 61850-7. Each configured device has an IEC
Capability Description (ICD) file and a Configured IED Description (CID) file. The substation single
line information is stored in a System Specification Description (SSD) file. The entire substation
configuration is stored in a Substation Configuration Description (SCD) file. The SCD file is the
combination of the individual ICD files and the SSD file, moreover, add communication system
parameters (MMS, GOOSE, control block, SV control block) and the connection relationship of
GOOSE and SV to SCD file.
The GGIO logical node is available in the PCS-900 series relays to provide access to digital status
points (including general I/O inputs and warnings) and associated timestamps and quality flags.
The data content must be configured before the data can be used. GGIO provides digital status
points for access by clients. It is intended that clients use GGIO in order to access digital status
values from the PCS-900 series relays. Clients can utilize the IEC61850 buffered reporting
features available from GGIO in order to build sequence of events (SOE) logs and HMI display
screens. Buffered reporting should generally be used for SOE logs since the buffering capability
reduces the chances of missing data state changes. All needed status data objects are transmitted
to HMI clients via buffered reporting, and the corresponding buffered reporting control block
(BRCB) is defined in LLN0.
10.5.3.2 Analog values
Most of analog measured values are available through the MMXU logical nodes, and metering
values in MMTR, the else in MMXN, MSQI and so on. Each MMXU logical node provides data
from a IED current/voltage source. There is one MMXU available for each configurable source.
MMXU1 provides data from CT/VT source 1(usually for protection purpose), and MMXU2 provides
180
Chapter 10 Communications
data from CT/VT source 2 (usually for monitor and display purpose). All these analog data objects
are transmitted to HMI clients via unbuffered reporting periodically, and the corresponding
unbuffered reporting control block (URCB) is defined in LLN0. MMXUx logical nodes provide the
following data for each source:
MMXU.MX.Hz: frequency
The following list describes the protection elements for all PCS-900 series relays. The specified
relay will contain a subset of protection elements from this list.
PTUC: undercurrent
PTOC: phase overcurrent, zero sequence overcurrent and overcurrent when CTS
PTUV: undervoltage
PTUF: underfrequency
RSYN: Synchronism-check
The protection elements listed above contain start (pickup) and operate flags, instead of any
element has its own start (pickup) flag separately, all the elements share a common start (pickup)
flags PTRC.ST.Str.general. The operate flag for PTOC1 is PTOC1.ST.Op.general. For the
PCS-900 series relay protection elements, these flags take their values from related module for
181
Chapter 10 Communications
the corresponding element. Similar to digital status values, the protection trip information is
reported via BRCB, and it also locates in LLN0.
10.5.3.4 LLN0 and other logical nodes
Logical node LLN0 is essential for an IEC61850 based IED. This LN shall be used to address
common issues for Logical Devices. Most of the public services, the common settings, control
values and some device oriented data objects are available here. The public services may be
BRCB, URCB and GSE control blocks and similar global defines for the whole device; the
common settings include all the setting items of communication settings. System settings and
some of the protection setting items, which can be configured to two or more protection elements
(logical nodes). In LLN0, the item Loc is a device control object, this Do item indicates the local
operation for complete logical device, when it is true, all the remote control commands to the IED
will be blocked and those commands make effective until the item Loc is changed to false. In
PCS-900 series relays, besides the logical nodes we describe above, there are some other logical
nodes below in the IEDs:
LPHD: Physical device information, the logical node to model common issues for physical
device.
PTRC: Protection trip conditioning, it shall be used to connect the operate outputs of one or
more protection functions to a common trip to be transmitted to XCBR. In addition or
alternatively, any combination of operate outputs of protection functions may be combined to
a new operate of PTRC.
RDRE: Disturbance recorder function. It triggers the fault wave recorder and its output refers
to the IEEE Standard Format for Transient Data Exchange (COMTRADE) for Power System
(IEC 60255-24). All enabled channels are included in the recording, independently of the
trigger mode.
IEC61850 buffered and unbuffered reporting control blocks locate in LLN0, they can be configured
to transmit information of protection trip information (in the Protection logical nodes), binary status
values (in GGIO) and analog measured/calculated values (in MMXU, MMTR and MSQI). The
reporting control blocks can be configured in CID files, and then be sent to the IED via an
IEC61850 client. The following items can be configured.
182
Chapter 10 Communications
MMS file services are supported to allow transfer of oscillography, event record or other files from
a PCS-900 series relay.
10.5.4.3 Timestamps
The timestamp values associated with all IEC61850 data items represent the time of the last
change of either the value or quality flags of the data item.
10.5.4.4 Logical node name prefixes
IEC61850 specifies that each logical node can have a name with a total length of 11 characters.
The name is composed of:
Complete names are of the form xxxxxxPTOC1, where the xxxxxx character string is configurable.
Details regarding the logical node naming rules are given in IEC61850 parts 6 and 7-2. It is
recommended that a consistent naming convention be used for an entire substation project.
10.5.4.5 GOOSE services
IEC61850 specifies the type of peer-to-peer data transfer services: Generic Object Oriented
Substation Events (GOOSE). IEC61850 GOOSE services provide virtual LAN (VLAN) support,
Ethernet priority tagging, and Ether-type Application ID configuration. The support for VLANs and
priority tagging allows for the optimization of Ethernet network traffic. GOOSE messages can be
given a higher priority than standard Ethernet traffic, and they can be separated onto specific
NANJING NARI-RELAYS ELECTRIC CO., LTD
183
Chapter 10 Communications
VLANs. Devices that transmit GOOSE messages also Devices that transmit GOOSE messages
also function as servers. Each GOOSE publisher contains a GOOSE control block to configure
and control the transmission.
The transmission is also controlled via device setting GOOSE Group ID in the setting submenu
EQUIP SETUP. The GOOSE Group ID setting item defines a definite IED group in which the
IED can communicate with each other via GOOSE protocol, and if GOOSE Group ID is configured
to 0, GOOSE service is blocked in this IED. IEC61850 recommends a default priority value of 4
for GOOSE. Ethernet traffic that does not contain a priority tag has a default priority of 1. More
details are specified in IEC61850 part 8-1. IEC61850 recommends that the Ether-type Application
ID number be configured according to the GOOSE source.
The PCS-931 series relays support IEC61850 Generic Object Oriented Substation Event (GOOSE)
communication. All GOOSE messages contain IEC61850 data collected into a dataset. It is this
dataset that is transferred using GOOSE message services. The GOOSE related dataset is
configured in the CID file and it is recommended that the fixed GOOSE be used for
implementations that require GOOSE data transfer between PCS-900 series relays.
IEC61850 GOOSE messaging contains a number of configurable parameters, all of which must be
correct to achieve the successful transfer of data. It is critical that the configured datasets at the
transmission and reception devices are an exact match in terms of data structure, and that the
GOOSE addresses and name strings match exactly.
The general steps required for transmission configuration are:
1.
2.
3.
2.
Client
Server
PCS-900 Series
Client-Server Roles
B11 Server side (of Two-party Application-Association)
C1
C1
SCSMS Supported
B21 SCSM: IEC 61850-8-1 used
B22
B23
B24
SCSM: other
B12
Chapter 10 Communications
B31
Publisher side
B32
Subscriber side
Subscriber side
Y
Y
N
N
Where:
C1: Shall be "M" if support for LOGICAL-DEVICE model has been declared
O: Optional
M: Mandatory
Y:
Client
Server
PCS-900 Series
M1
Logical device
C2
C2
M2
Logical node
C3
C3
M3
Data
C4
C4
M4
Data set
C5
C5
M5
Substitution
M6
Reporting
M7
M7-1
sequence-number
M7-2
report-time-stamp
M7-3
reason-for-inclusion
M7-4
data-set-name
M7-5
data-reference
M7-6
buffer-overflow
M7-7
entryID
M7-8
BufTm
M7-9
IntgPd
M7-10
GI
M8
M8-1
sequence-number
M8-2
report-time-stamp
M8-3
reason-for-inclusion
M8-4
data-set-name
M8-5
data-reference
M8-6
BufTm
M8-7
IntgPd
185
Chapter 10 Communications
Logging
M9
Log control
M9-1
IntgPd
M10
Log
M12
GOOSE
M13
GSSE
M14
Multicast SVC
M15
Unicast SVC
M16
Time
M17
File transfer
GSE
Where:
C2: Shall be "M" if support for LOGICAL-NODE model has been declared
C3: Shall be "M" if support for DATA model has been declared
C4: Shall be "M" if support for DATA-SET, Substitution, Report, Log Control, or Time models has
been declared
C5: Shall be "M" if support for Report, GSE, or SMV models has been declared
M: Mandatory
Y:
Server/Publisher
PCS-900 Series
Server
S1
ServerDirectory
Application association
S2
Associate
S3
Abort
S4
Release
Logical device
S5
LogicalDeviceDirectory
Logical node
S6
LogicalNodeDirectory
S7
GetAllDataValues
S8
GetDataValues
S9
SetDataValues
S10
GetDataDirectory
S11
GetDataDefinition
Data
186
Chapter 10 Communications
Data set
S12
GetDataSetValues
S13
SetDataSetValues
S14
CreateDataSet
S15
DeleteDataSet
S16
GetDataSetDirectory
Substitution
S17
SetDataValues
SelectActiveSG
M/O
S19
SelectEditSG
M/O
S20
SetSGValuess
M/O
S21
ConfirmEditSGValues
M/O
S22
GetSGValues
M/O
S23
GetSGCBValues
M/O
Reporting
Report
S24-1
data-change
S24-2
qchg-change
S24-3
data-update
S25
GetBRCBValues
S26
SetBRCBValues
Report
S27-1
data-change
S27-2
qchg-change
S27-3
data-update
S28
GetURCBValues
S29
SetURCBValues
Logging
GetLCBValues
S31
SetLCBValues
S32
QueryLogByTime
S33
QueryLogAfter
S34
GetLogStatusValues
Log
SendGOOSEMessage
S36
GetGoReference
187
Chapter 10 Communications
S37
GetGOOSEElementNumber
S38
GetGoCBValues
S39
SetGoCBValuess
S51
Select
S52
SelectWithValue
S53
Cancel
S54
Operate
S55
Command-Termination
S56
TimeActivated-Operate
Control
File transfer
S57
GetFile
M/O
S58
SetFile
S59
DeleteFile
S60
GetFileAttributeValues
M/O
Time
SNTP
The PCS-900 series relays support IEC61850 logical nodes as indicated in the following table.
Note that the actual instantiation of each logical node is determined by the product order code.
Nodes
PCS-900 Series
YES
YES
YES
188
YES
YES
Chapter 10 Communications
YES
PTOV: Overvoltage
YES
YES
PTUC: Undercurrent
PTUV: Undervoltage
YES
PTUF: Underfrequency
YES
YES
YES
YES
RREC: Autoreclosing
YES
YES
CILO: Interlocking
YES
YES
189
Chapter 10 Communications
YES
MMTR: Metering
MMXU: Measurement
YES
YES
YES
190
ZBAT: Battery
ZBSH: Bushing
ZCON: Converter
ZGEN: Generator
ZMOT: Motor
ZREA: Reactor
Chapter 10 Communications
In order to ensure the real-time property and reliability of GOOSE service, GOOSE message
adopts ASN.1 code which relates to basic encoding rule (BER) and transmit data directly in
Ethernet link layer without passing through TCP/IP protocol and also adopts special
receiving/sending mechanism.
Sending of the GOOSE message adopts heartbeat message and position-altering message fast
resending combination mechanism. If the data in GOOSE data sets is not changed, the heartbeat
message whose interval is T0 will be sent, the status number (stnum) in message will not be
changed and the sequence number (sqnum) will be increased progressively. If the data in GOOSE
data set is changed, after sending a frame of position-altering message, the position-altering
message will be fast resent in the interval of T0, T1, T2, and T3. The status number (stnum) in the
message whose data is position-altered will be increased, and the sequence number (sqnum) will
be started from zero.
The GOOSE receiving can detect link interrupt according to the TATL (Time Allow to Live) in the
GOOSE message. The GOOSE data receiving mechanism can be divided into single frame
receiving and dual-frames receiving. The intelligent operation box uses dual-frames receiving
mechanism and update data after receiving two frames of messages with the same GOOSE data.
Other protection and monitoring devices use single frame receiving mechanism and update data
immediately after receiving position-altering message (stnum changed). If the status number
(stnum) in the received message is not changed, dual-frames message confirmation will be used
to update data.
NANJING NARI-RELAYS ELECTRIC CO., LTD
191
Chapter 10 Communications
2.
GOOSE Alarm
GOOSE will alarm the abnormal conditions produced during receiving/sending process, the
GOOSE alarms mainly include: GOOSE network A/B network link breaking alarm, GOOSE
configuration inconformity alarm and GOOSE network A/B network-storm alarm.
The GOOSE network A/B link breaking alarm is: this alarm will be produced when correct GOOSE
message is not received in 2 times of the TATL (Time Allow to Live).
The GOOSE configuration inconformity alarm is: the attribute of GOOSE control block of GOOSE
publisher and subscriber like configuration version number must be identical. Otherwise this
GOOSE configuration inconformity alarm will be produced.
The GOOSE network A/B network-storm alarm is: when network-storm is produced in GOOSE
network, if data flow of network port is beyond normal range and abnormal message is produced,
this GOOSE network A/B network-storm alarm will be produced.
3.
GOOSE Service
When service status of the device is set to 1, the GOOSE message sent by the device has a Test
Flag and receiving terminal can obtain service status of sending terminal by the test flag of
message. When the service status of sending terminal conforms to that of receiving terminal, the
device will carry out normal processing to the received GOOSE data. When the service status of
sending terminal doesnt conform to that of receiving terminal, the device will process the received
GOOSE data accordingly to ensure that the serviced device will not influence the normal running
of device, improving the flexibility and reliability of GOOSE service.
192
193
careful during certain operations in order to avoid human injuries or damage to equipment.
Warning signs
Warning!
Strictly follow the company and country safety regulations. Working in a high voltage
environment requires serious approach to avoid human injuries and damage to
equipment.
Do not touch circuitry during operation. Potentially lethal voltages and currents are
present.
Always avoid touching the circuitry when the cover is removed. The product contains
electronic circuitries which can be damaged if exposed to static electricity (ESD). The
electronic circuitries also contain high voltage which is lethal to humans.
Always use suitable isolated test pins when measuring signals in open circuitry.
Potentially lethal voltages and currents are present.
Never unmount the front or back cover from a powered equipment or from a protection
equipment connected to powered circuitry. Potentially lethal voltages and currents are
present.
Caution signs
Caution!
194
Always transport modules using certified conductive bags. Always handle modules using
a conductive wrist strap connected to protective ground and on a suitable antistatic
surface. Electrostatic discharge (ESD) may cause damage to the module.
Do not connect live wires to the protection equipment. Internal circuitry may be damaged.
Always use a conductive wrist strap connected to protective ground when replacing
modules. Electrostatic discharge (ESD) may damage the module and protection
equipment circuitry.
Take care to avoid electrical shock if accessing wiring and connection protection
equipment when installing and commissioning.
Note signs
Note!
Changing the active setting group will inevitably change the protection equipments
operation. Be careful and check regulations before making the change.
The protection assembly is designed for a maximum continuous current of four times
rated value.
Activating the other setting group without proper configuration may seriously affect the
protection equipments operation.
11.3 Overview
The settings for each function must be calculated before the commissioning task can start. A
configuration, made in the configuration and programming tool, must also be available if the
protection equipment does not have a factory configuration downloaded.
The protection equipment is unpacked and visually checked. It is preferably mounted in a cubicle.
The connection to the protection system has to be checked in order to verify that the installation
was successful.
The installation and commissioning task starts with configuring the digital communication modules,
if included. The protection equipment can then be configured and set, which means that settings
and a configuration has to be applied if the protection equipment does not have a factory
configuration downloaded. Then the operation of each included function according to applied
settings has to be verified by secondary injection. A complete check of the configuration can then
be made. A conformity test of the secondary system has also to be done. When the primary
system has been energized a directionality check should be made.
2.
1)
Carefully examine the protection panel, protection equipment inside and other parts inside to
see that no physical damage has occurred since installation.
195
2)
3)
The rating information of other auxiliary protections should be checked to ensure it is correct
for the particular installation.
Panel wiring
Check the conducting wire used in the panel to assure that their cross section meet the
requirement. Carefully examine the wiring to see that they are no connection failure exists.
Label
Check all the isolator links, terminal blocks, ferrules, indicators, switches and push buttons to
make sure that their labels meet the requirements of this project.
Check each plug-in module of the equipments on the panel to make sure that they are well
installed into the equipment without any screw loosened.
Earthing cable
Check whether the earthing cable from the panel terminal block is safely screwed to the panel
steel sheet.
Check whether all the switches, equipment keypad, isolator links and push buttons work normally
and smoothly.
3.
Check that all items are included in accordance with the delivery documents
The user is requested to check that all software functions are included according to the delivery
documents after the terminal has been energized.
4.
These product checks cover all aspects of the protection, which should be checked to ensure that
the protection not only has not been physically damaged prior to commissioning but also functions
correctly and all input quantity measurements are within the stated tolerances.
196
maintenance and future modifications. Flush mounted protection equipment should be mounted
so that equipment modules can be added and replaced without excessive demounting.
11.5.2 Dimensions
101.6
177.0
The equipment adopts IEC standard chassis and is rack with modular structure. It uses an integral
faceplate and plug terminal block on backboard for external connections. PCS-931 series is IEC
4U high and 19 wide. Figure 11.5-1 shows its dimensions and Figure 11.5-2 shows the panel
cut-out.
465.0
4-6.8
450.0
Figure 11.5-2 panel cut-out of PCS-931
197
In order to minimize these influences as far as possible, certain standards have to be observed
with respect to grounding, wiring and screening.
Note!
All these precautions can only be effective if the station ground is of good quality.
If the above conditions are not fulfilled, there is a possibility of the cubicle or parts of it
forming a resonant circuit at certain frequencies that would amplify the transmission of
interference by the devices installed and also reduce their immunity to induced
interference.
Movable parts of the cubicle such as doors (front and back) or hinged equipment frames must be
effectively grounded to the frame by three braided copper strips (refer to Figure 11.5-3).
The metal parts of the cubicle housing and the ground rail are interconnected electrically
conducting and corrosion proof. The contact surfaces shall be as large as possible.
Note!
For metallic connections please observe the voltage difference of both materials according
to the electrochemical code.
The cubicle ground rail must be effectively connected to the station ground rail by a grounding strip
(braided copper).
198
199
Heavy-duty terminal block, M4 threaded terminal ends. VT circuit must be connected with the
protective device through an MCB.
2.
Auxiliary power cords cross can be directly screwed fixed on the rear panel of DC board. Refer to
section 6.3.12.
3.
Welding terminals. Those devices are supplied with sufficient M4 screws for making connections
to the rear mounted terminal blocks using ring terminals, with a recommended maximum of two
ring terminals per relay terminal.
To meet the insulation requirements of the terminal block, for the sake of safety, an insulating
sleeve should be fitted over the ring terminal after crimping.
The wire used for all connections to the welding terminal blocks and heavy duty terminal blocks,
except the EIA RS-485 port, should have a minimum voltage rating of 300Vrms.
It is recommended that the auxiliary power circuit wiring should be protected by using a 16A high
rupture capacity (HRC) fuse of type NIT or TIA. For safety reasons, current transformer circuits
must never be open.
4.
Connect the unit to the grounding bar of the cubicle with green/yellow conductor; connected to the
protective Earthing terminal at the back of the DC board. Refer to section 6.3.12. Attend that the
earth wire must be as short as possible. All cautions have to be taken to ensure the best electrical
200
conductivity, particularly the contact quality, stainless conductor. The impedance between the relay
Earthing terminal and the Earth must be less than 20m under 12Volt, 50Hz. What matters is that
the device has to be only grounded at one point. Loop grounding from unit to unit is not allowed.
5.
Connectors are generally color coded; connect blue or dark grey cable connectors to blue or dark
grey (receive) back-side connectors. Connect black or grey cable connectors to black or grey
(transmit) back-side connectors.
Fiber optical cables are sensitive to handling. Do not bend too sharply. The minimum curvature
radius is 15 cm for plastic fibers and 25 cm for glass fibers. If cable straps are used, apply with
loose fit.
Note!
Always hold the connector, never the cable, when connecting or disconnecting optical
fibres. Do not twist, pull or bend the fibre. Invisible damage may increase fibre damping
thus making communication impossible.
6.
When using galvanic connection between protective relay and communication equipment or
point-to-point galvanic connection between two protective relays it is essential that the cable
installation is carefully done. This is true regardless of type of module used, only the possible
length of the cable differs. The factors that must be taken into account is the susceptibility for noise
disturbance, due to that the levels of the communication signal are very low. For a best result, a
cable with twisted pairs with screen should be used.
RS485 serial communication interface, a termination 120-ohm resistor has to be connected at
each extremity of the bus. Refer to Chapter 10.
Check that the wiring is in strict accordance with the supplied wiring diagram.
Test the circuitry. The following tests are recommended:
1)
Polarity check
2)
3)
Grounding check
201
The polarity check verifies the integrity of the circuits and the phase relationship. The check should
be performed as close as possible to the relay. The primary injection test verifies the CT ration and
the wiring all the way through from the primary system to the relay. Injection must be performed for
each phase-to-neutral circuit and each phase-to-phase pair. In each case currents in all phases
and the neutral line are measured.
2.
Check that the value of the auxiliary supply voltage remains with the permissible range under all
operating conditions. Check that the polarity is correct according to the instruction manual on the
rear plate of DC board.
3.
Preferably, disconnect the binary input connector form the binary input cards. Check all connected
signals so that both input level and polarity are in accordance with the relays specifications.
Note!
The binary inputs may be energized from an external dc auxiliary supply (e.g. the station
battery) in some installations. Check that this is not the case before connecting the field
voltage otherwise damage to the protection may result. The status of each binary input can
be viewed using either tool software installed in a portable PC or by checking the front
man-machine interface LCD. When each binary input is energized the display will change
to indicate the new state of the inputs.
4.
Preferably, disconnect the binary output connector form the binary output cards. Check all
connected signals so that both load and polarity are in accordance with the relays specifications.
The liquid crystal display (LCD) is designed to operate in a wide range of substation ambient
temperatures. For this purpose, this relay has an automatic LCD contrast adjusting feature,
which is capable to adjust LCD contrast automatically according to the ambient temperature.
202
Connect the relay to DC power supply correctly and turn the relay on. Check program version and
forming time displayed in command menu to ensure that are corresponding to what ordered.
2.
If the time and date is not being maintained by substation automation system, the date and time
should be set manually.
Set the date and time to the correct local time and date using menu item CLOCK.
In the event of the auxiliary supply failing, with a battery fitted on CPU board, the time and date will
be maintained. Therefore when the auxiliary supply is restored the time and date will be correct
and not need to set again.
To test this, remove the auxiliary supply from the relay for approximately 30s. After being
re-energized, the time and date should be correct.
3.
On power up, the green LED HEALTHY should have illuminated and stayed on indicating that
the protective device is healthy.
The relay has latched signal relays which remember the state of the trip, auto-reclosing when the
relay was last energized from an auxiliary supply. Therefore these indicators may also illuminate
when the auxiliary supply is applied. If any of these LEDs are on then they should be reset before
proceeding with further testing. If the LED successfully reset, the LED goes out. There is no testing
required for that that LED because it is known to be operational.
It is likely that alarms related to voltage transformer supervision will not reset at this stage.
Download from a PC or laptop with tool software or remotely by SCADA. Front port
communication has to be established before the settings can be downloaded.
2.
To change settings through the local HMI need a password which is +, , and - keyboard
on the front panel.
Unless previously agreed to the contrary, the customer will be responsible for determining the
application-specific settings to be applied to the protection and for testing of any scheme logic
applied by external wiring and/or configuration of the protections internal programmable scheme
logic.
203
Multifunctional dynamic current and voltage injection test set with interval timer.
Multimeter with suitable AC current range and AC/DC voltage ranges of 0-440V and 0-250V
respectively.
Modern test set may contain many of the above features in one unit.
Optional equipment:
An electronic or brushless insulation tester with a DC output not exceeding 500 V (for
insulation resistance test when required).
A portable PC, with appropriate software (this enables the rear communications port to be
tested, if this is to be used, and will also save considerable time during commissioning).
EIA RS-485 to EIA RS-232 converter (if EIA RS-485 IEC60870-5-103 port is being tested).
At the same time, the calculated settings, substation configuration diagram, the protective device
diagram and the instruction manual is essential to test the protective device.
The relay has to be set before the testing can start. Only the functions that are used should be
tested.
The response from a test can be viewed in different ways:
204
All used setting groups should be tested. The user can release the functions to be tested and
prevent other functions from operation by setting the corresponding parameters. The user could
also energize the binary input [BI_BlkComm] to disable communication function to ensure that no
events are reported to remote station during the test.
The setting checks ensure that all of the application-specific protection settings (i.e. both the
protections function and programmable scheme logic settings), for the particular installation, have
been correctly applied to the protection.
DC power supply
Output contacts
Communication ports
To unplug all the terminals sockets of this protective device, and do the Insulation resistance test
for each circuit above with an electronic or brushless insulation tester.
On completion of the insulation resistance tests, ensure all external wiring is correctly reconnected
to the protection
This test verifies that the accuracy of current measurement is within the acceptable tolerances.
Checking its magnitude using a multimeter. The corresponding reading can then be checked
either in the protections submenu CPU_METERING column or a portable computer connected
to the front communication port with tool software.
The measurement accuracy of the protection is 5%. However, an additional allowance must be
NANJING NARI-RELAYS ELECTRIC CO., LTD
205
This test verifies that the accuracy of voltage measurement is within the acceptable tolerances.
Checking its magnitude using a multimeter. The corresponding reading either in the protections
submenu CPU_METERING or a portable computer connected to the front communication port
with tool software.
The measurement accuracy of the protection is 5%. However, an additional allowance must be
made for the accuracy of the test equipment being used.
206
207
208
Chapter 12 Maintenance
Chapter 12 Maintenance
NARI-RELAYS numerical relay PCS-931 is designed to require no special maintenance. All
measurement and signal processing circuit are fully solid state. All input modules are also fully
solid state. The output relays are hermetically sealed.
Since the device is almost completely self-monitored, from the measuring inputs to the output
relays, hardware and software defects are automatically detected and reported. The
self-monitoring ensures the high availability of the device and generally allows for a corrective
rather than preventive maintenance strategy. Therefore, maintenance checks in short intervals are
not required.
Operation of the device is automatically blocked when a hardware failure is detected. If a problem
is detected in the external measuring circuits, the device normally only provides alarm messages.
209
Chapter 12 Maintenance
When handling a module, take anti-static measures such as wearing an earthed wrist band
and placing modules on an earthed conductive mat. Otherwise, many of the electronic
components could suffer damage. After replacing the MON module, check the settings.
1)
Replacing a module
Short circuit all AC current inputs and disconnect all AC voltage inputs
Hazardous voltage can be present in the DC circuit just after switching off the DC power
supply. It takes approximately 30 seconds for the voltage to discharge.
2)
Unplug the ribbon cable on the front panel by pushing the catch outside.
3)
210
Chapter 12 Maintenance
After replacing the DSP module, input the application-specific setting values again.
Warning!
Units and modules may only be replaced while the supply is switched off and only by
appropriately trained and qualified personnel. Strictly observe the basic precautions to
guard against electrostatic discharge.
Warning!
When handling a module, take anti-static measures such as wearing an earthed wrist band
and placing modules on an earthed conductive mat. Otherwise, many of the electronic
components could suffer damage. After replacing the DSP module, check the settings.
Danger!
After replacing modules, be sure to check that the same configuration is set as before the
replacement. If this is not the case, there is a danger of the unintended operation of
switchgear taking place or of protections not functioning correctly. Persons may also be
put in danger.
12.5 Cleaning
Before cleaning the relay, ensure that all AC/DC supplies, current transformer connections are
isolated to prevent any chance of an electric shock whilst cleaning. Use a smooth cloth to clean
the front panel. Do not use abrasive material or detergent chemicals.
12.6 Storage
The spare relay or module should be stored in a dry and clean room. Based on IEC standard
211
Chapter 12 Maintenance
60255-6 the storage temperature should be from -25oC to 70oC, but the temperature of from -10oC
to 40oC is recommended for long-term storage.
212
Switching off
To switch off the PCS-931, switch off the external miniature circuit breaker of the power supply.
2.
Disconnecting Cables
Disconnect the cables in accordance with the rules and recommendations made by relational
department.
Danger!
Before disconnecting the power supply cables that connected with the DC module of the
PCS-931, make sure that the external miniature circuit breaker of the power supply is
switched off.
Danger!
Before disconnecting the cables that are used to connect analog input module with the
primary CTs and VTs, make sure that the circuit breaker for the primary CTs and VTs is
switched off.
3.
Dismantling
The PCS-931 rack may now be removed from the system cubicle, after which the cubicles may
also be removed.
Danger!
When the station is in operation, make sure that there is an adequate safety distance to
live parts, especially as dismantling is often performed by unskilled personnel.
13.2 Disposal
In every country there are companies specialized in the proper disposal of electronic waste.
Note!
Strictly observe all local and national regulations when disposing of the device.
213
214
Manual Version
R1.00
V1.00
Source
Documentation
Modification Recorder
Manual Version
Section
Page No.
V1.00
Description of change
Note
Original release
215