Worked Examples To Eurocode 2
Worked Examples To Eurocode 2
Draft Version
All advice or information from The Concrete Centre is intended for those who will evaluate
the significance and limitations of its contents and take responsibility for its use and
application.
No liability (including that for negligence) for any loss resulting from such advice or
information is accepted by the Concrete Centre or their subcontractors, suppliers or
advisors.
Readers should note that this is a draft version of a document and will be subject to
revision from time to time and should therefore ensure that they are in possession of the
latest version.
1 Introduction
1.1 Aim
The aim of this publication is to illustrate through worked examples how Eurocode 2[1–4] may
be used in practice to design in-situ building structures. It is intended that these worked
examples will explain how calculations to BS EN 1992–1–1[1] may be performed. This will be
carried out within the environment of other relevant publications:
Eurocode 2.
Other Eurocodes.
Material and execution standards.
Publications by The Concrete Centre and others.
There are, therefore, many references to other documents and while it is intended that this
publication, referred to as Worked examples, can stand alone it is anticipated that users
may require several of the other references to hand, in particular, Concise Eurocode 2 [5],
which summarises the rules and principles that will be commonly used it the design of
reinforced concrete framed buildings to Eurocode 2.
Figure 1.1
Worked examples in context
The worked examples relate to in-situ concrete building structures. The designs are in
accordance with Eurocode 2 Part 1–1[1], as modified by the UK National Annex[1a] and explained
in PD 6687[5]. The design of other forms of concrete are covered in other publications[6–9].
Generally, the calculations are cross-referenced to the relevant clauses in Eurocode 2[1–4]
and, where appropriate, to other documents. See Table 1.1 for a guide to presentation and
Section 11 for references. All references in the margins are to Eurocode 2 Part 1–1[1] unless
indicated otherwise. References to BS 8110[10]refer to Part 1 unless otherwise stated.
Table 1.1
Guide to presentation
<6.4.4> Relevant clauses or figure numbers from Eurocode 2 Part
1–1 (if the reference is to other parts, other Eurocodes or
6.4.4 other documents this will be indicated)
<NA>
From the relevant UK National Annex (generally to
NA Eurocode 2 Part 1–1)
<6.4.4 &NA>
From both Eurocode 2 Part 1–1 and UK National Annex
6.4.4 & NA
<Fig. 2.1>
Relevant parts of this publication
Section 5.2
<SMDSC[22] >
Relevant parts of Standard method of detailing structural
SMDSC[22] concrete – a manual for best practice.
<Concise EC2>
Concise Eurocode 2
Concise EC2
As some of the detailing rules in Eurocode 2 are generally more involved than those to BS
8110, some of the designs presented in this publication have been extended into areas that
have traditionally been the responsibility of detailers. These extended calculations are not
necessarily part of ‘normal’ design but are included at the end of some calculations. It is
assumed that the designer will discuss and agree with the detailer areas of responsibility and
the degree of rationalisation, the extent of designing details, assessment of curtailment and
other aspects, that the detailer should undertake. It is recognised that in the vast majority of
cases, the rules given in detailing manuals[12,13] will be used. However, the examples are
intended to help when curtailment, anchorage and lap lengths need to be determined.
Figure 1.2
The Eurocode hierachy
BS EN 1990 provides the necessary information for the analysis of structures including
partial and other factors to be applied to the actions from BS EN 1991. It establishes the
principles and requirements for the safety, serviceability and durability of structures. It <BS EN 1990:
describes the basis for design as follows: 2.1>
A structure shall be designed and executed (constructed) in such a way that it will, during its
intended life, with appropriate degrees of reliability and in an economical way:
■ Sustain all actions and influences likely to occur during execution and use.
■ Remain fit for the use for which it is required.
In other words, it shall be designed using limit states principles to have adequate stability,
structural resistance (including structural resistance in fire), serviceability and durability.
For building structures, a design working life of 50 years is implied.
BS EN 1990 states that limit states should be verified in all relevant design situations,
persistent, transient or accidental. No relevant limit state shall be exceeded when design
values for actions and resistances are used in design. The limit states are:
■ Ultimate limit states (ULS), which are associated with collapse or other forms of
structural failure.
■ Serviceability limit states (SLS), which correspond to conditions beyond which specified
service requirements are no longer met.
All actions are assumed to vary in time and space. Statistical principles are applied to arrive
at the magnitude of the partial load factors to be used in design to achieve the required
reliability index (level of safety). There is an underlying assumption that the actions
themselves are described in statistical terms.
This publication is mainly concerned with designing for the actions defined by Part––1
Densities, self-weight, imposed loads for buildings.
Note
National Annexes and
explanatory documents
(e.g. PD 6687, and Non-
Contradictory
Complementary
Information – NCCI) are
not shown.
Figure 1.3
Eurocode 2 in context
Concise Eurocode 2 for the design of in-situ concrete framed buildings to BS EN 1992–1–
1: 2004 and its UK National Annex: 2005[11].
Generally each calculation is rounded and it is the rounded value that is used in any further
calculation.
The values of γc and γs, partial factors for materials, are indicated in Table 1.2.
Table 1.2
Partial factors for materials <Table 2.1 & NA>
Design situation γc – concrete γs – reinforcing steel
ULS – persistent and transient 1.50 1.15
Accidental – non-fire 1.20 1.00
Accidental – fire 1.00 1.00
SLS 1.00 1.00
Draft Version
All advice or information from The Concrete Centre is intended for those who will evaluate
the significance and limitations of its contents and take responsibility for its use and
application.
No liability (including that for negligence) for any loss resulting from such advice or
information is accepted by the Concrete Centre or their subcontractors, suppliers or
advisors.
Readers should note that this is a draft version of a document and will be subject to
revision from time to time and should therefore ensure that they are in possession of the
latest version.
2 Analysis, actions and load arrangements
2.1 Methods of analysis
At the ultimate limit state (ULS) the type of analysis should be appropriate to <5.1.1(7)>
the problem being considered. The following are commonly used:
Linear elastic analysis.
Linear elastic analysis with limited redistribution.
Plastic analysis.
At the serviceability limit state (SLS) linear elastic analysis may be used.
Within the limits set, coefficients for moment and shear derived from elastic
analysis may be used to determine forces in regular structures (see Appendix B).
The design of columns should be based on elastic moments without redistribution. <5.2.7>
Plastic analysis may be used for design at ULS provided that the required ductility <5.6.2>
can be assured, for example, by:
Limiting xu / d (to ≤ 0.25 for concrete strength classes ≤ C50/60).
Using Class B or C reinforcement.
Ensuring the ratio of moments at intermediate supports to moments in spans is
between 0.5 and 2.0.
2.2 Actions
Actions refer to loads applied to the structure as defined below:
Permanent actions refer to actions for which the variation in magnitude with
time is negligible.
Variable actions are actions for which the variation in magnitude with time is
not negligible.
Accidental actions are actions of short duration but of significant magnitude
that are unlikely to occur on a given structure during the design working life.
Imposed deformations are not considered in this publication.
2.4.3.1 General
Roofs do not qualify for load reductions. The method given below complies with the < BS EN 1991-1-1,
UK National Annex but differs from that given the Eurocode. 6.3.1.2 (10),
6.3.1.2 (10) & NA>
2.4.3.2 Area
A reduction factor for imposed loads for area αA may be used and should be
determined using
2.4.3.4 Use
According to the UK NA, αA and αn may not be used together. < BS EN 1991-1-1
6.3.1.2 (11) & NA>
s = μi Ce Cts k
where
μi = snow load shape factor
μ1 = undrifted snow shape factor
μ2 = drifted snow shape factor
For flat roofs, 0° = α (with no higher structures close or abutting),
μ1 = μ2 = 0.8
For shallow monopitch roofs, 0°< α < 30° (with no higher <BS EN 1991-1-3 5.3.1 ,
structures close or abutting), μ1 = 0.8, μ2 = 0.8 (1 + α/ 30) 5.3.2 & NA>
For other forms of roof and local effects refer to BS EN 1991–1–3
Sections 5.3 and 6
Ce = exposure coefficient <BS EN 1991-1-3 5.2(7),
For windswept topography Ce = 0.8 Table 5.1>
For normal topography Ce = 1.0
For sheltered topography Ce = 1.2
Ct = thermal coefficient, Ct = 1.0 other than for some glass-covered <BS EN 1991-1-3 5.2(8)>
roofs, or similar
sk = characteristic ground snow load kN/m2
= 0.15(0.1Z + 0.05) + (A+100) / 525 <BS EN 1991-1-3 NA 2.8>
where
Z = zone number obtained from the map in BS EN 1991–1–3 NA
Figure NA.1
A = site altitude, m
Figure NA.1 of the NA to BS EN 1991–1–3 also gives figures for sk at
100 m a.m.s.l. associated with the zones. For the majority of the
South East, the Midlands, Northern Ireland and the north of England
apart from high ground, sk = 0.50 kN/m2. For the West Country, West
Wales and Ireland the figure is less. For most of Scotland and parts of
the east coast of England, the figure is more. See Figure 2.1
Snow load is classified as a variable fixed action. Exceptional circumstances <BS EN 1991-1-3 2(1)
may be treated as accidental actions in which case reference should be made 5.2(3)>
to BS EN 1991–1–3
Figure 2.1
Characteristic ground snow load map
(Ground snow load at 100 m a.m.s.l. (kN/m2)
Figure 2.2 Map of fundamental Figure 2.3 Exposure factor Figure 2.4 Multiplier for
basic wind velocity, vb,map, (m/s) ce,flat(z) for sites in country or exposure correction for sites in
town terrain town terrain
Note
Subject to altitude correction.
<BS EN 1991-1-4 4.2(1) Note 2, <BS EN 1991-1-4 4.5(1) Note 1, NA <BS EN 1991-1-4 4.5(1) Note 1,
NA 2.4 (Fig. NA.1)> 2.17 (Fig. NA.7)> NA 2.17 (Fig. NA.8)>
Table 2.5 b) Typical area loads for concrete slabs and sheet materials
Typical area loads kN/m3 Typical area loads kN/m
Concrete slabs Plasterboard (12.5 mm) 0.09
P. C. solid units (100 mm) 2.50 Plasterboard (19 mm) 0.15
P. C. hollowcore unitsa (150 mm) 2.40 Plywood (12.5 mm) 0.08
P. C. hollowcore unitsa (200 mm) 2.87 Plywood (19 mm) 0.12
P. C. hollowcore unitsa (300 mm) 4.07 Quarry tiles including mortar bedding 0.32
P. C. hollowcore unitsa (400 mm) 4.84 Raised floor – heavy duty 0.50
Ribbed slabb (250 mm) 4.00 Raised floor – medium weight 0.40
Ribbed slabb (300 mm) 4.30 Raised floor – lightweight 0.30
Ribbed slabb (350 mm) 4.70 Render (13 mm) 0.30
Waffle slabc – standard moulds (325 mm) 6.00 Screed – 50 mm 1.15
Waffle slabc – standard moulds (425 mm) 7.30 Screed – lightweight (25 mm) 0.45
Waffle slabc – standard moulds (525 mm) 8.60 Stainless steel roofing (0.4 mm) 0.05
Sheet materials Suspended ceiling – steel 0.10
Asphalt (20 mm) 0.46 Suspended fibreboard tiles 0.05
Carpet and underlay 0.05 T&G boards (15.5 mm) 0.09
Chipboard (18 mm) 0.12 T&G boards (22 mm) 0.12
Dry lining on stud (20 mm) 0.15 Tiles – ceramic floor on bed 1.00
False ceiling – steel framing 0.10 Battens for slating and tiling 0.03
Felt (3 layer) and chippings 0.35 Tiles – clay roof (max) 0.67
Glass – double glazing 0.52 Tiles – natural slate (thick) 0.65
Glass – single glazing 0.30 Tiles – interlocking concrete 0.55
Insulation – glass fibre (150 mm) 0.03 Tiles – plain concrete 0.75
Linoleum (3.2 mm) 0.05 Key
Paving stones (50 mm) 1.20 a Hollowcore figures assume no topping
b Ribbed slabs: 150 web @ 750 centres with 100 mm thick
Plaster – two coat gypsum (12 mm) 0.21 flange/slab. Web slope 1:10
Plaster skim coat 0.05 c Waffle slabs: 150 ribs @ 900 centres with 100 mm thick
flange/slab. Web slope 1:10
where
γF = partial factor for the action according to the limit state under
consideration. Table 2.6 indicates the partial factors to be used in the
UK for the combinations of representative actions in building structures.
ψFk may be considered as the representative action, Frep, appropriate to the
limit state being considered
where
ψ = a factor that converts the characteristic value of an action into a
representative value. It adjusts the value of the action to account
for the nature of the limit state under consideration and the joint
probability of the actions occurring simultaneously. It can assume
the value of 1.0 for a permanent action or ψ0 or ψ1 or ψ2 for a
variable action. Table 2.7 shows how characteristic values of
variable actions are converted into representative values. This
table is derived from BS EN 1990[13] and its National Annex[13a].
Fk = characteristic value of an action as defined in Sections 2.2 and 2.3.
Either
Exp. 6.10 1.35 Gk + 1.5 Qk,1
Action ψ0 ψ1 ψ2
Imposed loads in buildings
Category A: domestic, 0.7 0.5 0.3
residential areas
Category B: office areas 0.7 0.5 0.3
Category C: congregation areas 0.7 0.7 0.6
Category D: shopping areas 0.7 0.7 0.6
Category E: storage areas 1.0 0.9 0.8
Category F: traffic (area vehicle 0.7 0.7 0.6
weight ≤ 30 kN)
Category G: traffic area (30 kN < 0.7 0.5 0.3
vehicle weight ≤ 160 kN)
Category H: roofsa 0.7 0.0 0.0
Snow loads where altitude ≤ 0.5 0.2 0.0
1000 m a.m.s.l.a
Wind loadsa 0.5 0.2 0.0
Temperature effects (non-fire)a 0.6 0.5 0.0
Notes
1 The numerical values given above are in accordance with BS EN 1990 and its UK National
Annex.
2 Categories K and L are assumed to be as for Category H
Key
a On roofs, imposed loads, snow loads and wind loads should not be applied together. < BS
EN 1991–1–1–1 3.3.2>
Expression (6.10) leads to the use of γF = γG = 1.35 for permanent actions and γF =
γQ = 1.50 for variable actions (γG for permanent actions is intended to be constant
across all spans).
Expression (6.10) is always equal to or more conservative than the less favourable
of Expressions (6.10a) and (6.10b). Expression (6.10b) will normally apply when
the permanent actions are not greater than 4.5 times the variable actions (except
for storage loads, category E in Table 2.7, where Exp. (6.10a) always applies).
Note
Assuming ψ 0 = 0.7 i.e. applicable to all areas except storage.
Figure 2.5
When to use Exp. (6.10a) or Exp. (6.10b)
Compared with the use of Exp. (6.10), the use of either Exp. (6.10a) or (6.10b)
leads to a more consistent reliability index across lightweight and heavyweight
materials.
Again the designer may choose between using Exp. (6.10) or the less favourable of Exp. < BS EN 1990
(6.10a) or (6.10b). 6.4.3.2(3) >
Either:
Exp. (6.10) 1.35 Gk + 1.5 Qk,1 + Σψ0,i 1.5 Qk,i
or the worst case of:
Exp. (6.10a) 1.35 Gk + ψ0,I 1.5 Qk,1 + ψ0,i 1.5 Qk,i
and
Exp. (6.10b) 1.25 Gk – 1.5 Qk,1 + Σψ0,I 1.5 Qk,i
In the above, Qk,1 refers to the leading variable action and Qk,i refers to accompanying
independent variable actions. In general the distinction between the two types of
actions will be obvious (see Figure 2.6); where it is not, each load should in turn be
treated as the leading action. Also the numerical values for partial factors given in the
UK National Annex[13a] are used in the equations above. The value of ψ0 depends on the <BS EN 1990
use of the building and should be obtained from the UK National Annex for BS EN 1990 A1.2.2, A1.3.1
(see Table 2.7). & NA>
The expressions take into account the probability of joint occurrence of loads by
applying the ψ0,i factor to the accompanying variable action. The probability that
these combined actions will be exceeded is deemed to be similar to the
probability of a single action being exceeded.
If the two independent variable actions Qk,1 and Qk,2 are associated with different
spans and the use of Exp. (6.10b) is appropriate, then in one set of analyses
1.25Gk + 1.5Qk,1 should be applied to the ‘Qk,1’ spans with 1.25Gk + ψ0,i 1.5Qk,2
applied to the ‘Qk,2’ spans. In associated analyses, 1.25Gk + ψ0,i 1.5Qk,1 should be
applied to the ‘Qk,1’ spans and 1.25Gk + 1.5Qk,2 to the ‘Qk,2’ spans. See Example
2.11.2 (2 variable actions).
There are three combinations of actions at SLS (or Load combination at SLS).
These are given in Table 2.8. The combination and value to be used depends on
the nature of the limit state being checked. Quasi-permanent combinations are <BS EN 1990 6.5, Table
associated with deformation, crack widths and crack control. Frequent A1.4>
combinations may be used to determine whether a section is cracked or not.
The numeric values of ψ 0, ψ 1 and ψ 2 are given in Table 2.7.
Table 2.8
Partial factors to be applied in the verification of the SLS
Combination Permanent actions Gk Variable actions Qk
Unfavourablea Favourablea Leadingb Othersb
Characteristic Gk,sup Gk,inf Qk,1 ψ0,iQk,i
Frequent Gk,sup Gk,inf ψ1,1Qk,1 ψ2,iQk,i
Quasi-permanent Gk,sup Gk,inf ψ2,1Qk,1 ψ2,iQk,i
Key
a Generally Gk,sup and Gk,inf may be taken as Gk. See Section 2.4
b ψ factors are given in Table 2.7
When the variation of a permanent action is not small then the upper (Gkj,sup)
and the (Gkj,inf) characteristic values (the 95 and 5 percentile values <BS EN 1990 4.1.2>
respectively) should be established. This procedure is only necessary when the <BS EN 1990 4.1.2 (3)>
coefficient of variation (= 100 × standard deviation/mean) is greater than 10. In
terms of permanent actions, variations in the self-weight of concrete in
concrete frames are considered small.
At ULS where the variation is not small, γGk,sup should be used with Gkj,sup and
γGk,inf with Gkj,inf. Similarly, where the variation is not small, at SLS Gkj,sup should
be used where actions are unfavourable and Gkj,inf used where favourable.
Where checks, notably checks on static equilibrium (EQU), are very sensitive to <BS EN 1990 6.4.3 (4)>
variation of the magnitude of a permanent action from one place to another the
favourable and unfavourable parts of this action should be considered as
individual actions. γG,sup and γG,inf should be used in such ‘very sensitive’
verifications.
For building structures, design concentrates mainly on the ULS, the ultimate
limit state of strength (STR), and SLS, the serviceability limit state. However, it <BS EN 1990 3.3, 3.4,
is essential that all limit states are considered. The limit states of equilibrium 6.5>.
(EQU), strength at ULS with geotechnical actions (STR/GEO) and accidental <BS EN 1990 6.4>.
situations must be taken into account as appropriate.
Note
Whilst the use of Exp. (6.10) is indicated, these arrangements may equally be used with Exp. (6.10a) or
(6.10b).
Figure 2.7
Load arrangements for beams and slabs according to UK NA
Figure 2.8
Continuous beam in a domestic structure
Actions: kN/m
Permanent action, gk
Self weight, 175 mm thick slabs = 26.3
E/o self weight downstand 800 × 225 = 4.5
50 mm screed @ 22 kN/m3 = 6.6
Finishes and services = 3.0
Dividing wall 2.40 × 4.42 (200 mm dense blockwork with plaster = 10.6
both sides) = 51.0
Total
Variable action, qk
Imposed, dwelling @ 1.5 kN/m2 = 9.0
Ultimate load, n
Assuming use of Exp. 6.10, n = 1.35 × 51 + 1.5 × 9.0 = = 82.4
Assuming use of worst case of Exp. (6.10a) or Exp. (6.10b)
Exp. (6.10a): n = 1.35 × 51 + 0.7 × 1.5 × 9.0 = = 78.3
Exp. (6.10b): n = 1.25 × 51 + 1.5 × 9.0 = = 77.3
In this case Exp. (6.10a) would be critical1 and ∴n = 78.3
Determine the various arrangements of actions and magnitude of actions for ULS
verification of a continuous beam supporting a 175 mm slab @ 6 m centres. Note <BS EN 1991-1-1
that the variable actions are from two sources: 6.3.1.1 & NA>
Office use: 2.5 kN/m2, ψ0 = 0.7;shopping use: 4.0 kN/m2, ψ0 = 0.7 < BS EN 1990
A.1.2.2. & NA>
1
This could also be determined from Figure 2.1 or by determining that gk > 4.5qk
a) Load combination
Load combination Exp. (6.10a) or Exp. (6.10b) will be used, as either will produce a smaller
total load than Exp. (6.10). It is necessary to decide which expression governs.
Actions: kN/m
Permanent action
As before, Example 2.8.1 = 51.0
Variable action
Office @ 2.5 kN/m2 = 15.0
Shopping @ 4.0 kN/m2 = 24.0
Ultimate load, n
For office use:
Exp. (6.10a): n = 1.35 × 51 + 0.7 × 1.5 × 15.0 = 84.6
Exp. (6.10b): n = 1.25 × 51 + 1.5 × 15.0 = 86.3
For shopping use:
Exp. (6.10a): n = 1.35 × 51 + 1.5 × 0.7 × 24.0 = 94.1
Exp. (6.10b): n = 1.25 × 51 + 1.5 × 24.0 = 99.8
b) Arrangement of actions
i) Actions
As the variable actions arise from different sources, one is a leading variable action and
the other is an accompanying variable action. The unit loads to be used in the various
arrangements are:
Actions: kN/m
Permanent
1.25 × 51.0 = 63.8
Variable
Office use
as leading action, γQQk = 1.5 × 15 = = 22.5
as accompanying action, ψ0γQQk = 0.7 × 1.5 × 15 = = 15.75
♣
This could also be determined from Figure 2.1 or by determining that gk < 4.5qk
Figure 2.10
For maximum bending moment in span AB
Figure 2.11
For maximum bending moment in span CD
The arrangement of loads is shown in Figure 2.12. As both spans AB and BC receive load < BS EN 1991 6.3.1.1 (10)
from the same source, no reduction is possible (other than that for large area2). & NA>
Figure 2.12
For maximum bending moment at support B
2
Variable actions may be subjected to reduction factors: αA, according to A area
supported (m2), αA = 1.0 – A / 1000 ≥ 0.75. < BS EN 1991-1-1 6.3.1.2 (10) & NA>
Figure 2.13
For maximum bending moment at support D
Figure 2.14
For curtailment and hogging in span CD
Eurocode 2 requires that all spans should be loaded with either γG,supp or γG,inf (as per Table <2.4.3(2)>
2.6). As illustrated in Figure 2.14, using γG,inf, = 1.0 might be critical for curtailment and
hogging in spans.
Figure 2.15
Propped cantilever beam and loading
Figure 2.16
EQU: maximum uplift at A
Note
γGk,inf gk = 1.0 gk may be critical in terms of curtailment of top bars BA.
Figure 2.17
ULS: maximum moment at B
Notes
1 Depending on the magnitude of gk, qk length AB and BC, γGkinf gk (= 1.0 gk) may be more critical
for span moment.
2 The magnitude of the load combination indicated are those for Exp. (6.10) of BS EN 1990. The
worse case of Exp (6.10a) and Exp (6.10b) may also have been used.
3: Presuming supports A and B were columns then the critical load combination for Column A
would be as Figure 2.18. For column B the critical load combination might be either as
Figure 2.17 or 2.18.
Figure 2.18
ULS: maximum span moment AB
Figure 2.19
SLS: maximum deformation at C
Note
Quasi-permanent load combinations may also be used for calculations of crack widths
or controlling cracking, i.e. the same load combinations as shown in Figures 2.19 and
2.20 may be used to determine SLS moment to determine stress in reinforcement. The
characteristic and/or frequent combinations may be appropriate for other SLS limit
states: for example, it is recommended that the frequent combination is used to
determine whether a member has cracked or not.
Figure 2.20
SLS maximum deformation AB
Figure 2.21
Frame configuration
Figure 2.23
Frame with roof variable action as leading variable action
Figure 2.24
Frame with wind as lead variable action
Draft Version
All advice or information from The Concrete Centre is intended for those who will evaluate
the significance and limitations of its contents and take responsibility for its use and
application.
No liability (including that for negligence) for any loss resulting from such advice or
information is accepted by the Concrete Centre or their subcontractors, suppliers or
advisors.
Readers should note that this is a draft version of a document and will be subject to
revision from time to time and should therefore ensure that they are in possession of the
latest version.
3.5 Flat slabs
This example is for the design of a reinforced concrete flat slab without column heads. The slab is part of
a larger floor plate and is taken from Guide to the design and construction of reinforced concrete flat
slabs[29], where finite element analysis and design to Eurocode 2 is illustrated. As with the Guide, grid line
C will be designed but, for the sake of illustration, coefficients will be used to establish design moments
and shears in this critical area of the slab.
The slab is for an office where the specified load is 1.0 kN / m2 for finishes and 4.0 kN / m2 imposed (no
partitions). Perimeter load is assumed to be 10 kN / m. Concrete is C30 / 37. The slab is 300 mm thick
and columns are 400 mm square and extend 4.5 m above and below. A 2 hour fire rating is required.
Figure 3.18
Part plan of flat slab
3.5.1 Actions
kN / m2
Permanent
Self-weight 0.30 × 25 7.5 <BS EN 1991-1-1 Table A1>
Finishes 1.0 <specified>
gk = 8.5
Variable
Offices
qk = 4.0 <specified & BS EN 1991-1-1 6.3.1.2(8)>
Figure 3.19
Panel centred on grid C
Ultimate load, n
By inspection, Exp. (6.10b) is critical. <Fig. 2.5>
n = 1.25 × 8.50 + 1.5 × 4.0 = 16.6 kN / m2 <BS EN 1990 Exp. (6.10b)>
Arrangement
Choose to use all-and-alternate-spans-loaded load cases and coefficients ‡‡. <5.1.3(1) & NA option b>
‡‡
The all-spans-loaded case with 20% redistribution of support moments would also have <5.3.1 & NA> been
acceptable but would have involved some analysis. The use of Table 5.9 in BS EN 1992–1–2 (Fire resistance of solid
flat slabs) is restricted to where redistribution does not exceed 15%: The coefficients presume 15% redistribution at
supports. <Concise Table 15.3>
Figure 3.20
Column and middle strips
Percentages
Column strip Middle strip
-ve (hogging) Long span = 70%§§ Long span = 30% <Table I.1, CS Flat slab
Short span = 75% Short span = 25% guide[29]>
+ve (sagging) 50% 50% <Table I.1>
Parallel to grid C, column strip is ly / 2 = 3 m wide. The middle strip is also 3 m wide. <NA.3[1a], Fig. I.1>
MEd
Column strip, 3 m wide Middle strip, 3 m wide
-ve (hogging) 0.70 × 952.8 / 3.0 = 222.3 kNm / m 0.30 × 952.8 / 3.0 = 95.3 kNm / m
+ve (sagging) 0.50 × 842.7 / 3.0 = 140.5 kNm / m 0. 50 × 842.7 / 3.0 = 140.5 kNm / m
§§
The Concrete Society Guide[29] recommends a percentage, k1, based on Lx / Ly Assuming Lx / Ly = 1.5 the distribution
of moments in the long span between column strips and middle strips is given as 70% and 30%.
♣
As punching shear force (rather than a beam shear force) ‘effective’ span is not appropriate.
***
Cladding and strip of slab beyond centre of support.
†††
Otherwise for flat slabs 8.5 / 9.5 = 0.89 as span > 8.5 m. <7.4.2(2)>
‡‡‡
In line with Note 5 to Table NA.5, 1.50 is considered to be a maximum for 310 / σs.
§§§
Note: Continuity into columns will reduce sagging moments and criticality of deflection check (see Section 3.5.14).
****
Note requirement for at least 2 bars in bottom layer to carry through column <9.4.1(3)>
††††
The hogging moment could have been considered at face of support to reduce the amount of reinforcement
required.
Figure 3.21
Edge panel on grid 1 (grid 3 similar)
Actions
Permanent from slab gk = 5 × 8.5 kN / m2 = 42.5 kN / m
Variable from slab qk = 5 × 4.0 kN / m2 = 20.0 kN / m
Percentages
Column strip, 1.7 m wide Middle strip <Table I.1, CS Flat slab guide [29]>
-ve (hogging) Short span = 75% Short span = 25%
+ve (sagging) 50% 50%
Short span moments:
MEd
Column strip, 1.7 m wide Middle strip, 3.3 m wide
-ve (hogging) (0.75 × 248.5 + 37.4) / 1.70 0.25 × 248.5 / 3.3
= 131.6 kNm / m = 18.8 kNm / m
+ve (sagging) (0.50 × 248.5 + 37.4) / 1.70 0.50 × 248.5 / 3.3
= 95.1 kNm / m = 37.6 kNm / m
(ρ = 0.15%)
Use H12 @ 300 T2 (376 mm2 / m)
‡‡‡‡
The hogging moment could have been considered at face of support to reduce the amount of reinforcement required. This
should be balanced against the effect of the presence of a 200 × 200 hole at some supports which would have the effect of
increasing K but not unduly increasing the total amount of reinforcement required in the column strip (a 1.5% increase in
total area would been required).
Figure 3.22
Internal panel on grid 2
Ultimate load, n
By inspection, Exp. (6.10b) is critical. <Fig. 2.5>
n = 1.25 × 77.4 + 1.5 × 36.4 = 151.4 kN / m <BS EN 1990 Exp. (6.10b)>
MEd
Column strip, 3.0 m wide Middle strip, 6.1 m wide
-ve (hogging) 0.75 × 453.2 / 3.0 0.25 × 453.2 / 6.1
= 113.3 kNm / m = 18.5 kNm / m
+ve (sagging) 0.50 × 453.2 / 3.0 0.50 × 453.2 / 6.1
= 75.5 kNm / m = 37.1 kNm / m
Punching shear force, VEd, as before
§§§§
The hogging moment could have been considered at face of support to reduce the amount of reinforcement
required.
*****
Column C2 is taken to be an internal column. In the case of a penultimate column, an additional elastic reaction factor
should have been considered.
†††††
At the perimeter of the column, vRd,max assumes the strut angle is 45°, i.e, that cot θ = 1.0.
Where cot θ = < 1.0, vRd,max is available from Concise EC2[10] Table 15.7.
Perimeter required such that punching shear links are no longer required: <Exp. (6.54)>
uout = VEd × β / (d × vRd,c)
uout = 1204.8 × 1.15 × 103 / (250 × 0.61) = 9085 mm
The values used here for ρlx, ρly ignore the fact that the reinforcement is concentrated over the support.
‡‡‡‡‡
Considering the concentration would have given a higher value of VRdc at the expense of further calculation to
determine ρlx, ρly at 3d from the side of the column.
§§§§§
vRd,c for various values of d and ρl is available from Concise EC2[10] Table 15.6.
******
Clause 6.4.5 provides Expression (6.52), which by substituting vEd for vRd,c, allows calculation of the area of required shear
reinforcement, Asw, for the basic control perimeter, u1. This should be considered as the required density of shear reinforcement. The
Check shear stress at basic perimeter u1 (2.0d from face of column) <6.4.2>
vEd = βVEd / u1d < vRd,c
where
β, VEd and d as before
u1 = control perimeter under consideration. <Fig. 6.15>
For punching shear at 2d from edge column
columns u1 = c2 + 2c1+ π × 2d = 2771 mm
vEd = 1.4 × 609.5 × 103 / 2771 × 250 = 1.23 MPa
vRd,c = 0.18 / γc × k × (100 ρlfck)0.333 <Exp. (6.47) & NA>
where
γc = 1.5
k = as before = 1 +(200 / 250)0.5 = 1.89
ρl = (ρlxρly)0.5
where <6.4.4.1(1)
ρlx, ρly = areas of bonded steel in a width of the column
plus 3d each side of column.
ρlx = (perpendicular to edge) 10 no.H20 T2 + 6 no. H12
T2 in 2 × 750 + 400, i.e. 3818 mm2 in 1900 mm.
ρlx = 3818 / (250 × 1900) = 0.0080
ρly = (parallel to edge) 6 no. H20 T1 + 1 no. T12 T1 in
400 + 750 i.e. 1997 mm2 in 1150 mm. ρlY = 1997 /
(250 × 1150) = 0.0069
ρl = (0.0080 × 0.0069)0.5 = 0.0074
area of shear reinforcement required for any other perimeter should be based on this value, Asw / u1 together with the
requirements for minimum reinforcement and spacing of shear reinforcement (see Clause 9.4.3).
Figure 3.23
Flexural tensile reinforcement adjacent to columns C1 (and C3)
††††††
vRd,c for various values of d and ρl is available from Concise EC2[10] Table 15.6.
Check shear stress at basic perimeter u1 (2.0d from face of column) <6.4.2>
vEd = βVEd / u1d < vRdc
where
β, VEd and d as before
u1 = control perimeter under consideration. For <Fig. 6.15>
punching shear at 2d from edge column columns u1
= c2 + 2c1+ π × 2d = 2771 mm
Allowing for hole
200 / (c1 / 2): x / ( c1 / 2 + 2d) <Fig. 6.14>
200 / 200: x / ( 200 + 500)
∴ x = 700 mm
u1 = 2771 – 700 = 2071 mm
vEd = 1.4 × 516.5 × 103 / 2071 × 250 = 1.40 MPa
vRd,c = 0.18 / γc × k × (100 ρlfck)0.333 <Exp. (6.47) & NA>
where
γc = 1.5
k = as before = 1 + (200 / 250)0.5 = 1.89
ρl = (ρlxρly)0.5
where
ρlx, ρly = areas of bonded steel in a width of the column plus 3d <6.4.4.1(1)
each side of column.
ρlx = (perpendicular to edge) 8 no.H20 T2 + 6 no.H12 T2 in
2 × 720 + 400 − 200, i.e. 3190 mm2 in 1640 mm.
ρlx = 3190 / (240 × 1640) = 0.0081
ρly = (parallel to edge) 6 no.H20 T1 (5 no. are effective)
+ 1 no. T12 T1 in 400 + 750 – 200, i.e. 1683 mm2 in 950 mm.
ρlY = 1683 / (260 × 950) = 0.0068
ρl = (0.0081 × 0.0068)0.5 = 0.0074
fck = 30
vRd,c = 0.18 / 1.5 × 1.89 × (100 × 0.0074 × 30)0.333 = 0.64 MPa <Concise EC2 Table 15.6‡‡‡‡‡‡>
‡‡‡‡‡‡
vRd,c for various values of d and ρl is available from Concise EC2 [10] Table 15.6
Figure 3.24
Flexural tensile reinforcement adjacent to columns D1 and D3
Perimeter required where punching shear links no longer required <Exp. (6.54)>
uout = 516.5 × 1.4 × 10 / (250 × 0.64) = 4519 mm
3
Shear reinforcement:
As before, sr max. = 175 mm; st max. = 350 mm and fywd,ef = 312 MPa <9.4.3(1) 9.4.3(2)>
For perimeter u1
Asw ≥ (vEd – 0.75vRd,c) sr u1 / 1.5fywd,ef) per perimeter <Exp. (6.52)>
= (1.40 – 0.75 × 0.64) × 175 × 2071 / (1.5 × 312) = 712 mm2 per perimeter
Asw,min ≥ 0.08 × 300.5 (175 × 350) / (1.5 × 500) = 36 mm2
Asw / u1 ≥ 712 / 2071 = 0.34 mm2 / mm
Using H8 (50 mm2) max. spacing = min[50 / 0.3; 1.5d]
= min[147; 375] = 147 mm cc No good
Try using H10, max. spacing = 78.5 / 0.34 = 231 mm cc, say 175 cc
∴ Use min. H10 (78.5 mm2) legs of links at 175 mm cc around perimeters
perimeters at 175 mm centres
Check min. 9 H10 legs of links (750 mm2) in perimeter u1, 2d from column face.
Note: As the requirement for these columns is for H10 links
change ALL links to H10 to avoid potential problems on site
Interior support:
Column strip centre: H20 @ 200 T2* H16
Column strip outer: @ 250 T2
Middle strip: H12 @ 300 T2
Punching shear
Internal (e.g. at C2):
Use H10 legs of links in perimeters at max. 175 mm centres.
Max. tangential spacing of legs of links, st max. = 270 mm
Last perimeter, from column face, min. 767 mm
Edge (e.g. at C1, C3 assuming no holes):
Use H10 legs of links in perimeters at max. 175 mm centres.
Max. tangential spacing of legs of links, st max. = 175 mm
Last perimeter, from column face, min. 940 mm
Edge (e.g. at D1, D3 assuming 200 × 200 hole on face of column):
Use H10 legs of links in perimeters at max. 175 mm centres.
Max. tangential spacing of legs of links, st max. = 175 mm
Last perimeter, from column face, min. 1123 mm
Note
* rationalise centre of bars in column strips T2 and B2 to 175 mm centres to suit punching shear links.
Figure 3.26
Punching shear links at column C2 (102 no links) (column D2 similar)
Method of analysis
The use of coefficients in the analysis would not usually be advocated in the design of such a
slab. Nonetheless, coefficients may be used and unsurprisingly, their use leads to higher
design moments and shears, as shown below.
These higher moments and shears result in rather more reinforcement than when using other
more refined methods. For instance, the finite element analysis used in Guide to the design
and construction of reinforced concrete flat slabs[29] for this bay, leads to:
H16 @ 200 B1 in spans 1-2 (cf. H20 @ 200 B1 using coefficients),
H20 @ 125 T1 at support 2 (cf. H20 @ 100 T1 using coefficients) and
3 perimeters of shear links at C2 for VEd = 1065 kN (cf. 5 perimeters using coefficients)
2 perimeters of shear links at C3 (cf. 7 perimeters using coefficients)
Shear reinforcement
H10 punching shear links are required for columns D1 and D3. Whilst the other columns were
found to require only H8s, H10s have been adopted throughout to avoid confusion in
detailing or on site. The cost differential would have been marginal.
With added area, the numbers of links could have been reduced on the other columns. A
rectangular arrangement (300 × 175 grid) of H10 links would have been possible. However,
as the grid would need to change orientation around the columns and as the reinforcement
in B2 and T2 is essentially at 175 centres, it is considered better to leave the regular square
grid arrangement.
Use of shear reinforcement in a radial arrangement, e.g. using stud rails, would have
simplified the shear reinforcement requirements.
Curtailment of reinforcement
In this design, the reinforcement would be curtailed and this would be done either in line
with previous examples or more practically in line with other guidance [20, 21].
Draft Version
All advice or information from The Concrete Centre is intended for those who will evaluate
the significance and limitations of its contents and take responsibility for its use and
application.
No liability (including that for negligence) for any loss resulting from such advice or
information is accepted by the Concrete Centre or their subcontractors, suppliers or
advisors.
Readers should note that this is a draft version of a document and will be subject to
revision from time to time and should therefore ensure that they are in possession of the
latest version.
3 Slabs
3.1 General
The calculations in this section are presented in the following Sections:
3.2 A simply supported slab showing what might be deemed typical hand calculations.
3.3 A detailed version of the same simply supported slab but designed, and curtailment
lengths determined, strictly in accordance with the provisions of BS EN 1992–1–1.
3.4 A continuous ribbed slab designed, and curtailment lengths determined, strictly in
accordance with the provisions of BS EN 1992–1–1.
3.5 A bay of a flat slab.
They are intended to be illustrative of the Code and not necessarily best practice.
A 175 mm thick slab is required to support screed, finishes, an office variable action of 2.5
kN / m2 and demountable partitions (@ 2 kN / m). The slab is supported on load-bearing
block walls. fck = 30, fyk = 500. Assume a 50-year design life and a requirement for 1 hour
resistance to fire.
3.2.1 Actions
kN / m2
Permanent
Self-weight 0.175 × 25 = 4.4 <BS EN 1991-1-1 Table A1>
50 mm screed = 1.0
Finishes, services = 0.5
gk = 5.9
Variable
Offices, general use B1 = 2.5
Movable partitions @ 2.0 kN / m = 0.8 <BS EN 1991-1-1 Tables 6.1, 6.2
& NA>
qk = 3.3 <BS EN 1991-1-1, 6.3.1.2 (8)>
3.2.2 Cover
Nominal cover, cnom
3.2.4 Analysis
Design moment
MEd = 12.3 × 4.82 / 8 = 35.4 kNm
Shear force
V = 12.3 × 4.8 / 2 = 29.5 kN / m
3.2.6 Deflection
Check span-to-effective-depth ratio
Basic span-to-effective-depth ratio for ρ = 0.41% = 20 <Table 7.4N & NA>
As,prov / As,req = 645 / 599 = 1.08 <Exp. (7.17)>
Max. span = 20 × 1.08 × 144 = 3110 mm i.e. < 4800 mm ∴ no good
3.2.7 Shear
By inspection, OK
However, if considered critical
V = 29.5 kN / m as before
VEd= 29.5 ‒ 0.14 × 12.3 = 27.8 kN / m <6.2.1(8)>
vEd = 27.8 × 103 / 144 × 103 = 0.19 MPa
vRd,c =0.53 MPa <6.2.2(1), Concise Table 15.6>
∴ No shear reinforcement required
Figure 3.2
Simply supported slab: summary
Note
It is presumed that the detailer would take this design and detail the slab to normal best
practice, e.g. to SMDSC[21]. This would usually include dimensioning and detailing
curtailment, laps, U-bars and also undertaking the other checks detailed in Section 3.2.9.
( 0.15%)
∴ H12 @ 175 B1 OK
Crack control
OK by inspection <Table 7.2N & NA>
Curtailment main bars
Curtail main bars 50 mm from or at face of support. <SMDSC[21] Fig. 6.4; How to,
Detailing>
At supports
50% of As to be anchored from face of support <9.3.1.2.(1)>
Use H12 @ 350 B1 T1 U-bars
In accordance with SMDSC[21] detail MS3 lap U-bars 500 mm
with main steel, curtail T1 leg of U-bar 0.1l (= say 500 mm) from
face of support.
A 175 mm thick continuous slab is required to support screed, finishes, an office variable
action of 2.5 kN / m2 and demountable partitions (@ 2 kN / m). The slab is supported on
200 mm wide load-bearing block walls at 6000 mm centres. fck = 30, fyk = 500 and the design
life is 50 years. A fire resistance of 1 hour is required.
Figure 3.3
Continuous solid slab
3.3.1 Actions
kN / m2
Permanent
As Section 3.2 gk = 5.9
Variable
As Section 3.2 qk = 3.3 <BS EN 1991-1-1
6.3.1.2(8)>
3.3.2 Cover
Nominal cover, cnom
‡
A free unsupported edge is required to use ‘longitudinal and transverse reinforcement’ <9.3.1.4(1)>
generally using U-bars with legs at least 2h long. For slabs 150 mm deep or greater, SMDSC [21]
standard detail recommends U-bars lapping 500 mm with bottom steel and extending 0.1l top into
span.
3.3.4 Analysis
Clear span, lk = 5800
a1 = min[h / 2; t / 2] = min[175 / 2; 200 / 2] = 87.5 <5.3.2.2(1)>
a2 = min[h / 2; t / 2] = min[175 / 2; 200 / 2] = 87.5
leff = 5975
Bending moment
End span MEd = 0.086 × 12.3 × 5.9752 = 37.8 kNm / m <5.1.1(7), Concise Table 15.2>
1st internal support MEd = 0.086 × 12.3 × 5.9752 = 37.8 kNm / m <5.1.1(7), Concise Table 15.2>
Internal spans and supports
MEd = 0.063 × 12.3 × 5.9752 = 27.7 kNm / m <5.1.1(7), Concise Table 15.2>
Shear
End support VEd = 0.40 × 12.3 × 5.975 = 29.4 kN / m <5.1.1(7), Concise Table 15.2>
1st interior support VEd = 0.60 × 12.3 × 5.975 = 44.1 kN / m <5.1.1(7), Concise Table 15.2>
§
The use of Concise Table 15.2 implies certain amounts of redistribution which are defined in Concise
table 15.14.
3.3.8 Shear
Design shear force, VEd
At d from face of end support
VEd = 29.4 ‒ (0.144 + 0.0875) × 12.3 = 26.6 kN / m <6.2.1(8)>
At d from face of 1st interior support
VEd = 44.1 ‒ (0.144 + 0.0875) × 12.3 = 41.3 kN / m
Figure 3.4
Continuous solid slab: design summary
Note
It is presumed that the detailer would take this design and detail the slab to normal best practice. This would usually include rationalising,
dimensioning and detailing curtailment, laps, U-bars and also undertaking the other checks detailed in 3.3.10 to 3.3.14. The determination
of curtailment lengths, anchorages and laps is shown in detail using the principles in Eurocode 2. In practice these would be determined
from published tables of data or by using reference texts [12, 21].
d) Crack control
As slab < 200 mm, measures to control cracking are <7.3.3(1)>
unnecessary.
3.3.11 Curtailment
a) End span, bottom reinforcement
Assuming end support to be simply supported, 50% of As
should extend into the support. <9.3.1.2(1) >
50% × 639 = 320 mm2 / m
Try H12 @ 300 (376 mm2 / m) at supports
In theory, 50% curtailment of reinforcement may take place al <9.3.1.2(1) Note, 9.2.1.3 (2)>
from where the moment of resistance of the section with the
remaining 50% would be adequate to resist the applied
bending moment. In practice, it is usual to determine the
curtailment distance as being al from where MEd = MEd,max / 2.
Thus: for a single simply supported span supporting a UDL of n,
MEd,max = 0.086nl 2 ; RA = 0.4nl
At distance, X, from end support, moment,
MEd@X = RAX – nX 2 / 2
∴ when M@X = MEd,max / 2:
0.086nl 2 / 2 = 0.4nlX – nX 2 / 2
Assuming X = xl
0.043nl 2 = 0.4nlxl – nx 2 l 2 / 2
0.043 = 0.4x – x2 / 2
0 = 0.043 − 0.4x + x2 / 2
**
Detail MS2 of SMDSC[21], suggests 50% of T1 legs of U-bars should extend 0.3l (= say 1800 mm)
from face of support by placing U-bars alternately reversed.
††
Detail MS2 of SMDSC[21], suggests 50% of T1 legs of U-bars should extend 0.3l (= say 1800 mm)
from face of support by placing U-bars alternately reversed.
Figure 3.5
Curtailment of bottom reinforcement: actions, bending moments, forces in reinforcement and
curtailment
‡‡
Maximum z = 0.947 at mid span and greater towards support.
3.3.13 Laps
Lap H12 @ 300 U-bars with H12 @ 150 straights
Tension lap, l0 = α1 α2 α3 α5 α6 lb,rqd α l0min <Exp. (8.10)>
where
α1 = 1.0 (straight bars) <Table 8.2>
α2 = 1 − 0.15 (cd − φ) / φ
where
cd = min(pitch, side cover or cover) <Fig. 8.4>
= 25 mm
φ = bar diameter
= 12 mm
α2 = 0.84 <Table 8.2>
α3 = 1.0 (no confinement by reinforcement)
α5 = 1.0 (no confinement by pressure)
α6 = 1.5 <Table 8.3>
<Exp. (8.3)>
lb,rqd = (φ / 4) σsd / fbd
where
Figure 3.6
Continuous solid slab: reinforcement details
Figure 3.8
Continuous ribbed slab example
This 300 mm deep ribbed slab is required for an office to support a variable action of 5 kN / m2.
It is supported on wide beams that are the same depth as the slab, as shown in Figure 3.9.
Figure 3.9
Long section through slab
One hour fire resistance required: internal environment. Ribs are 150 mm wide @ 900 mm
cc. Links are required in span to facilitate prefabrication of reinforcement. Assume that
Using UDLs simplifies the analysis and remains popular. One method is to ignore the
weight of the solid part of the slab in the analysis of the ribbed slab (and the weight of
the solid area added to the supporting beam actions). This ignores the effect the solid
areas have on bending in the ribbed slab.
Alternatively the weight of the solid part of the slab is spread as a UDL over the whole
span. This is conservative both in terms of moment and shears at solid/shear interfaces
but underestimates hogging in internal spans.
The advent of computer analysis has made analysis using patch loads more viable and
the resulting analysis more accurate.
The ribbed part of the slab may be designed to span between solid areas. (The ribs span
d / 2 into the solid areas which are assumed to act as beams in the orthogonal
direction.) However, having to accommodate torsions induced in supporting beams and
columns usually makes it simpler to design from centreline of support to centreline of
support.
Analysis programs can cope with the change of section and therefore change of stiffness
along the length of the slab. Moments would be attracted to the stiffer, solid parts at
supports. However, the difference in stiffnesses between the ribbed and the solid parts
is generally ignored.
In line with good practice analysis, this example is carried out using centreline of support to
centreline of support and patch loads§§. Constant stiffness along the length of the slab has
been assumed.
3.4.1 Actions
Permanent: UDL kN / m2
Self-weight:
Rib 0.15 × 0.2 × 25 / 0.9 = 0.833
Slope 2 × (1 / 2) × 0.2 / 10 × 0.2 × 25 / 0.9 = 0.112
Slab 0.1 × 2.5 = 2.500
Cross rib 0.19 × 0.71 × 0.2 × 25 / (0.9 × 7.5) = 0.100
Total self-weight = 3.545 3.55
Ceiling 0.15
Services 0.30
Raised floor 0.30
Total permanent actions = 4.30
§§
In this case, assuming the patch load analysis is accurate, assuming the weight of solid area is
spread over the whole span would overestimate span and support moments by 6 – 8% and shears at
the solid/rib interface by 8 – 9%. Ignoring the weight of the solid area in the analysis of this ribbed slab
would lead to underestimates of span moments by 1%, support moments by 3% and no difference in
the estimation of shear at the solid shear interface. This may have been the preferred option!
3.4.2 Cover
Nominal cover, cnom
Figure 3.10
Section AA: section through ribbed slab
Arrangement
Choose to use all-and-alternate-spans-loaded <5.1.3(1) & NA option b>
3.4.4 Analysis
Analysis by computer, includes 15% redistribution at support and <BS EN 1990 A1.2.2
none in the span.*** & NA, 5.3.1 (6)>
Figure 3.11
Bending moment diagrams
Figure 3.12
Redistributed shears, kN / m
At solid/rib interface
AB @ 550 mm from A
MEd (sagging) = 20.4 kNm / m ≡ 18.3 kNm / rib
VEd = 32.5 kN / m ≡ 29.3 kN / rib
***
Note 1: A ribbed slab need not be treated as discrete elements provided rib spacing ≤ 1500 mm, depth of
the rib ≤ 4 × its width, the flange is > 0.1 × distance between ribs and transverse ribs are provided at
a clear spacing not exceeding 10 × overall depth of the slab.
Note 2: As 7.5 m < 85% of 9.0 m, coefficients presented in Concise Eurocode 2[10] are not applicable.
K = MEd / bd2fck
where
b = 900 mm
d = 300 − 25 – 8 – 20 / 2 = 257
assuming 8 mm link at H20 in span
fck = 35
= 55.5 × 106 / (900 × 2572 × 35) = 0.027
K′ = 0.207 <Appendix A1>
or restricting x / d to 0.45
K′ = 0.168
K ≤ K′ ∴ section under-reinforced and no compression
reinforcement required.
z = (d / 2) [1 + (1 − 3.53K)0.5] ≤ 0.95d <Appendix A1>
= (257 / 2) (1 + 0.951) ≤ 0.95 × 257
= 251 ≤ 244 ∴ z = 244 mm
But z = d – 0.4x <Appendix A1>
∴ x = 2.5(d − z) = 2.5(257 − 244) = 33 mm
∴ By inspection, neutral axis is in flange
As = MEd / fydz
where
fyd = 500 / 1.15 = 434.8 MPa
= 55.5 × 106 / (434.8 × 244) = 523 mm2 / rib
Try 2 no.H20 / rib (628 mm2 / rib)
Span AB - Deflection
Allowable l / d = N × K × F1 × F2 × F3 <Concise Sec. 15.7>
where
N = Basic l / d: check whether ρ > ρ0 and whether to <7.4.2(2)>
use Exp. (7.16a) or Exp. (7.16b)
ρ0 = fck0.5 / 1000 = 350.5 / 1000 = 0.59%
ρ = As / Ac††† = As,req / [bwd + (beff − bw)hf] <PD 6687>
where
bw = min. width between tension and compression
chords. At bottom assuming 1 / 10 slope to rib:
= 150 + 2 × (25 + 8 + 20 / 2) / 10
= 159 mm
Section 2.18 of PD 6687 [5] suggests that ρ in T-beams should be based on the area of concrete
†††
‡‡‡
In analysis, 15% redistribution of support moments led to redistribution of span moments:
δ = 61.7 / 65.3 = 0.94
§§§
Both As,prov / As,req and any adjustment to N obtained from Exp. (7.16a) or Exp. (7.16b) is restricted
to 1.5 by Note 5 to Table NA.5 in the UK NA. Therefore, 310 / σs is restricted to 1.5.
****
An alternative method would have been to calculate the reinforcement required to resist MEd at the
shift distance, al, from the interface
Figure 3.14
Section through rib
††††
Both As,prov / As,req and any adjustment to N obtained from Exp. (7.16a) or Exp. (7.16b) is restricted
to 1.5 by Note 5 to Table NA.5 in the UK NA.
Figure 3.15
Summary of design
(0.17%)
∴ Use A142 in flange (say OK) <BS 8666[28]>
b) Secondary reinforcement
Not applicable
d) Crack control
Loading is the main cause of cracking ∴ use Table 7.2N or <7.3.3(2)
Table 7.3N for wmax = 0.3 mm and max. σs = 200 MPa (see 7.3.1.5>
deflection check)
Max. bar size = 25 mm <Table 7.2N>
or max. spacing = 250 mm <Table 7.3N>
OK by inspection.
e) Effects of partial fixity
Assuming partial fixity exists at end supports, 15% of As is <9.3.1.2(2)>
required to extend 0.2 × the length of the adjacent span.
As,req = 15% × 525 = 79 mm2 / rib
For the rib in tension:
As,min = 0.26 × 0.30 × 300.666 × 159 × 257 / 500 = 55 mm2 / rib
3.4.11 Curtailment
Wherever possible simplified methods of curtailing reinforcement would be followed. The
following is intended to show how a rigorous assessment of curtailment of
reinforcement might be undertaken.
End support A: bottom steel at support
Check anchorage
As simply supported, 25% of As should be anchored in support. <9.3.1.1(4), 9.3.1.2(1) & Note,
25% × 595 = 148 mm2 9.2.1.4(1) & NA>
Use 1 no.H20 / rib (314 mm2 / rib)
Check anchorage length
Envelope of tensile force:
To resist envelope of tensile force, provide reinforcement to al <9.3.1.1(4), 9.2.1.3(1), 9.2.1.3(2),
or lbd beyond centreline of support. 9.2.1.3(3) Fig. 9.2>
For members without shear reinforcement, al = d = 232 <9.2.1.3>
By inspection, σsd = 0, lbd = lbd,min = max(10φ, 100 mm)
Indirect support:
As anchorage may be measured from face of indirect support, <9.3.1.1(4), 9.2.1.4(2), 9.2.1.4(3),
check, force to be resisted at solid/rib interface: Fig. 9.3b>
Fs = MEd / z + FE
Anchorage length
lbd = αlb,rqd ≥ lb,min <8.4.4, Exp. (8.4)>
where:
α = conservatively 1.0
lb,rqd = (ϕ / 4) (σsd / fbd) <Exp. (8.3)>
where
ϕ = 20
σsd = design stress in the bar at the ULS
= 121.1 × 1000 / 314 = 385 MPa
fbd = ultimate bond stress
= 2.25 η1 η2 fct,d <8.4.2 (2)>
where
η1 = 1.0 for good bond conditions
η2 = 1.0 for bar diameter ≤ 32 mm
<3.1.6 (2),Tables 3.1 and 2.1 and
fct,d = αct fct,k / γc
NA>
= 1.0 × 2.2 / 1.5
= 1.47 MPa
fbd = 2.25 × 1.47 = 3.31 MPa
∴ lb,rqd = (20 / 4) (385 / 3.31) = 581 mm <Fig. 9.3>
lb,min = max[10ϕ; 100 mm] = 200 mm
∴ lbd= 581 mm measured from solid/rib intersection.
i.e. 31 mm beyond centreline of support‡‡‡‡.
End support A: top steel
Assuming partial fixity exists at end supports, 15% of As is required <9.3.1.2(2)>
to extend at least 0.2 × the length of the adjacent span§§§§.
As,req = 15% × 525 = 79 mm2 / rib
As,min = 0.26 × 0.30 × 350.666 × 159 × 257 / 500 = 68 mm2 / rib <9.3.1.1
9.2.1.1(1), Exp. (9.1N)>
Use 2 no. H12 T1 / rib in rib and 2 H10 T1 / rib between ribs
(383 mm2 / rib)
Support B (and C): top steel
At the centreline of support (2 H16 T + 3 H12 T) / rib are
required. The intention is to curtail in two stages, firstly to 2
H16 T / rib then to 2 H12 T / rib.
Curtailment of 2 H16 T / rib at support (capacity of 2 H12 T / rib + shift rule)
‡‡‡‡
Whilst this would comply with the requirements of Eurocode 2, it is common practice to take
bottom bars 0.5 × a tension lap beyond the centreline of support (= 250 mm beyond the centreline of
support; see MS1 in SMDSC[21]).
§§§§
It is usual to curtail 50% of the required reinforcement at 0.2l and to curtail the remaining 50%
at 0.3l or line of zero moment (see MS2 in SMDSC[21]).
Figure 3.16
Curtailment of top reinforcement at B per rib
3.4.12 Laps
At AB, check lap 1 no.H20 B to 2 no.H20 B in rib full tension lap
l0 = α1 α6 lb,rqd > l0,min <Exp. (8.10)>
where
α1 = 1.0 (cd = 45 mm, i.e. < 3ϕ) <Table 8.2>
α6 = 1.5 (as > 50% being lapped)
lb,rqd = (ϕ / 4) (σsd / fbd)
where
ϕ = 20
σsd = 434.8
fbd = 3.0 MPa as before
l0,min = max. 10ϕ or 100 = 200 Exp. (8.6)
l0 = 1.0 × 1.5 × (20 / 4) × 434.8 / 3.0
= 1087 mm, say = 1200 mm <SMDSC[21]>
At BA and BC, check lap 2 no. H12 T to 2 no. H16 T in rib – full tension lap
l0 = α1 α6 lb,rqd > l0,min <Exp. (8.10)>
where
α1 = 0.7 (cd = 45 mm, i.e. > 3ϕ) <Table 8.2>
α6 = 1.5 (as > 50% being lapped)
lb,rqd = (ϕ / 4) (σsd / fbd)
where
ϕ = 12
σsd = 434.8
fbd = 2.1 (3.0 MPa as before but η1 = 0.7 for not <8.4.2 (2)>
good bond conditions)
l0,min = max. 10ϕ or 100 = 120 Exp. (8.6)
Figure 3.17
Curtailment of flexural reinforcement in ribbed slab
Draft Version
All advice or information from The Concrete Centre is intended for those who will evaluate
the significance and limitations of its contents and take responsibility for its use and
application.
No liability (including that for negligence) for any loss resulting from such advice or
information is accepted by the Concrete Centre or their subcontractors, suppliers or
advisors.
Readers should note that this is a draft version of a document and will be subject to
revision from time to time and should therefore ensure that they are in possession of the
latest version.
6 Walls
6.1 General
Walls are defined as being vertical elements whose lengths are four times greater than
their thicknesses. Their design does not differ significantly from the design of columns in
that axial loads and moments about each axis are assessed and designed for.
Generally, the method of designing walls is as follows:
1. Determine design life. <BS EN 1990 & NA Table NA 2.1>
2. Assess actions on the column. <BS EN 1991 (10 parts) & UK
NAs>
3. Determine which combinations of actions <BS EN 1990 & NA Tables NA
apply. A1.1 & NA A1.2(B)>
4. Assess durability requirements and determine <BS 8500–1>
concrete strength.
5. Check cover requirements for appropriate fire <Approved Document B
resistance period. BS 1992–1–2>
6. Determine cover for fire, durability and bond. <BS EN 1992–1–1 Cl. 4.4.1>
7. Analyse structure for critical combination <BS EN 1992–1–1 Section 5>
moments and axial forces.
8. Check slenderness and determine design <BS EN 1992–1–1 Section 5.8>
moments.
9. Determine area of reinforcement required. <BS EN 1992–1–1 Section 6.1>
10. Check spacing of bars <BS EN 1992–1–1 Sections 8 & 9>
Example 6.2 shows the design of a simple linear shear wall as typically used in medium rise
buildings. Similar principals may be applied to walls that are shaped as C, L, T, Z and rectangles
in-plan but issues of limiting flange dimensions and shear at corners need be addressed. The
example shows only ULS design as, apart from minimum areas of steel to control cracking, SLS
issues are generally non-critical in medium-rise structures. For shear walls in high-rise
structures, reference should be made to specialist literature (ref to CIRIA R102 Design of shear
wall buildings).
Figure 6.1
Typical floor plan
Qk = αn × 196.1
where
αn = 1.1 – n / 10
where
n =no. of storeys qualifying for reduction* <BS EN 1991-1-1 6.3.1.2(11) & NA>
=3
= 1.1 – 3 / 10 = 0.8
∴Qk = 0.8 × 196.1 = 156.9 kN Qk /m = 156.9 / 4.4 = 35.7 kN /m
Check relative stiffness of lift shaft and wall A to determine share of load on wall A.
Lift shaft: ILS = 2.44 / 12 – 2.04 / 12 – 0.2 × 1.63 / 12
= 1.36 m4
Wall A: IWallA = 0.2 × 4.43 / 12
= 1.41 m4
∴ Wall A takes = 1.41 / (1.41 + 1.36) = 51% of wind load.
Check shear centre to resolve the effects of torsion.
Determine centre of reaction of lift shaft
Area x Ax
2.4 × 2.4 = 5.76 1.2 6.912
–2.0 × 2.0 = –4.00 1.2 –4.800
–1.6 × 0.2 = –0.32 2.3 –0.732
1.44 1.38
*
Includes storeys supporting Categories A (residential & domestic), B (office), C (areas of
congregation) and D (shopping) but excludes E (storage and industrial), F (traffic), G (traffic) and H
(roofs).
†
Assuming centreline of wall A is 50 mm to right hand side of grid.
‡
For medium rise shear walls there are a number of methods of design. Cl. 9.6.1 suggests strut-and-
tie (see Section xx). Another method [ref to Concrete Buildings Design manual] is to determine elastic
tensile and compression stresses from NEd/bL +/– 6MEd/bL2 and determine reinforcement
requirements based on those maxima. The method used here assumes a couple, consisting of 1.0 m of
wall either end of the wall. The reinforcement in tension is assumed to act at the centre of one end and
the concrete in compression (with a rectangular stress distribution) acts at the centre of the other
end. The forces generated by the couple add or subtract from the axial load in the 1 m ends of the
walls. The method is useful for typical straight shear walls of say 2.5 to 5.0 m in length.
§
As Hi derives mainly from permanent actions its resulting effects are considered as being a
permanent action too.
Figure 6.8 Plan of wall A and location of sections Figure 6.9 Section A – A
A – A and B – B
Section A – A @ 1st floor.
The slab frames into the wall. For the purposes of assessing fixed end moments, the width of slab
contributing to the moments in the wall is assumed to be the length of the wall plus distances half
way to adjacent supports either end. Therefore, consider the fixed end moment for 1.50/2 + 4.40 +
1.30/ 2 = 5.8 m width of adjoining slab framing into the 4.4 m long shear wall (see Figure 6.8).
**
FEM Fixed End Moment for 1 m width of adjoining slab.
FEM
Assuming variable action is a leading action:
= 302.8 / 2 = 151.4 kNm
kw =I/l
= 2200 × 2003 / (12 × 1650) = 8.88 × 105
††
Ignoring effect of landing.
‡‡
Assuming wind load is lead variable action.
§§
Strictly incompatible with Qk = 0. However, allow Qk= 0.
Figure 6.12 Stresses and strains in wall subject to tension and out of plane moment
Restoring moment
Mk = (1021.0 + 5.0 x 1.2 x 0.9 x 25 + 0 x 225.1 ) x (0.3 + 2.2)
= 2890 kNm
At ULS of EQU,
Overturning moment
= fn(γQ,1Qk1 + γG,supGk) <BS EN 1990 Table
= 1.5 x 1057.5 + 1.1 x 211.0 = 1818.4 kNm A1.2(A) & NA>
Restoring moment
= fn(γG,infGk) <BS EN 1990 Table
= 0.9 x 2890 = 2601 kNm i.e. > 1818.4 kNm A1.2(A) & NA>
∴ OK
Draft Version
All advice or information from The Concrete Centre is intended for those who will evaluate
the significance and limitations of its contents and take responsibility for its use and
application.
No liability (including that for negligence) for any loss resulting from such advice or
information is accepted by the Concrete Centre or their subcontractors, suppliers or
advisors.
Readers should note that this is a draft version of a document and will be subject to
revision from time to time and should therefore ensure that they are in possession of the
latest version.
5 Columns
5.1 General
The calculations in this section illustrate:
5.2 Design of a non-slender column using design charts.
5.3 Design of a perimeter column using iteration of equations to determine reinforcement
requirements.
5.4 Design of an internal column with high axial load.
5.5 Design of a slender column requiring a two hour fire resistance.
In general axial loads and first order moments are assumed to be available. The designs
consider slenderness in order to determine design moments, MEd. The columns are designed
and checked for biaxial bending. The effects of allowing for imperfections are illustrated.
A general method of designing columns is as follows:
Figure 5.1
Forces in edge column
*
Effective lengths are covered in Eurocode 2 Section 5.8.3.2 and Exp (5.15). The effective length of most columns
will be l/2< l0 < l < Figure 5.7f)>. PD 6686[ref to] Cl 2.10 suggests that using the procedure outlined in
Eurocode 2 and <5.8.3.2(3) 5.8.3.2(5)> leads to similar effective lengths to those tabulated in BS 8110[ref
to] and reproduced in Table 5.1 of Concise EC2. For simplicity tabular values are used in this example. However,
experience suggests that these tabulated values are conservative.
a = 1.48 by interpolating between values given for NEd / NRd= 0.1 ,(1.0) and NEd / <5.8.9(4), Notes to
NRd = 0.7, (1.5) Exp. (5.39)>
(MEdz / MRdz)a + (MEdy / MRdy)a = (38.5 / 76.1)1.48 + (32.4 / 76.1)1.48 <Exp. (5.39)>
= 0.36 + 0.28
= 0.64 ∴ OK.
∴ 4 no. H25 OK.
Figure 5.2
Design summary: edge column
5.3.1 Cover
cnom = cmin + Δcdev <Exp. (4.1)>
where
cmin = max[cmin,b, cmin,dur]
where
cmin,b = diameter of bar. Assume 32 mm bars and 8 mm links <4.4.1.2(3)>
= 32 mm to main bars, 32 − 8 = 24 mm to links
= say 25 mm
cmin,dur = minimum cover due to environmental conditions. Assume XC1.
cmin,dur = 15 mm
cmin = 25 mm
Δcdev = 10 mm <4.4.1.3(3)>
Therefore cnom = 25 + 10 = 35 mm to links cnom= 35 mm to links
Check validity of using Method B and Table 5.2b: <BS EN 1992–1–2: 5.3.3>
emax = 0.25b = 75 mm ∴ no good.
Use BS EN 1992–1–2 Annex C Tables C1 – C9. <BS EN 1992–1–2: Annex C>
2 †
Assume min. 4 no. H25 = 1964 mm (≡ 2.2%)
ω = Asfyd / Acfcd = 0.022 × (500 / 1.15) / (0.85 × 30 / 1.5) <BS EN 1992–1–2: 5.3.3(2)>
= 0.56
e ≈ 0.25b and ≤ 100 mm
λ = l0 / i <BS EN 1992–1–2: 5.3.3(2),
where 5.3.3(3)>
l0 = 0.7 × 3.325 = 2327 mm
i = radius of gyration = (I / A)0.5 = h / 120.5
= 300 / 120.5 = 87 mm
λ = 2327 / 87 = 276
n = N0Ed,fi / 0.7(Acfcd + Asfyd) <BS EN 1992–1–2: 5.3.3(2)>
= 0.7 × 1129.6 / 0.7(3002 × 0.85 × 30 / 1.5 + 1964 × 500 / 1.15)
= 1129.6 / 2383.9
= 0.47
∴ interpolate for λ = 30 and n = 0.47 between
Table C5 (ω = 0.5, e = 0.25b) ⇒ bmin = 235, a = 35 mm
†
Using 4 no. H20 gives ω = 0.34, n = 0.54 and bmin = 310 mm ∴ no good!
‡
See Section 5.2.1
§
The effects of imperfections need only be taken into account in the most unfavourable direction.
<5.8.9(2)>
Figure 5.4
Section in axial compression and bending <Fig. 6.1>
Figure 5.5
Design summary: perimeter column
The suspended slabs (including the ground floor slab) are 300 mm thick flat slabs at 4500
mm vertical centres. Between ground and 5th floors the columns at C2 are 500 mm square;
above 5th floor they are 465 mm circular. Assume an internal environment, 1 hour fire
resistance and fck = 50 MPa.
Axial load to Exp. (6.10b) <BS EN 1990 Exp. (6.10) & NA>
NEd = ξγGGk + γQQk1 + ψ0,1γQQki
assuming the variable action of the roof is an independent variable action:
= 0.925 × 1.35 × 5553.6 + 1.5 × (2279.5 − 42.0) × 0.6 + 0.7 × 1.5 × 42.0
= 1.25 × 5553.6 + 1.5 × 2237.5 × 0.6 + 0.7 × 1.5 × 42.0
= 6942.1 + 2013.8+ 44.1
= 9000.0 kN
To Exp. (6.10b), NEd= 9000.0 kN
Modified
diagram
3 2 1 required
Figure 5.7
Subframe on column C2 along grid C
**
According to BS EN 1991–1–1 6.3.1.2(11) the imposed load on the roof is category H and therefore
does not qualify for reduction factor αn.
where
b = breadth d = depth L = length
lc = lower column uc = upper column
23 = beam 23 21 = beam 21
0.54 / 4.5
=
2 × 0.5 / 4.5 + 0.75 × 6.1 × 0.33 / 8.6 + 0.75 × 6.1 × 0.33 / 9.6
4
Modified
diagram
required
B C D
6200
Figure 5.8
Subframe on column C2 along grid 2
††
FEM 23 = Fixed end moment in span 23 at 2
‡‡
Using design actions to Exp (6.10) would have resulted in a requirement for 8500 mm2.
5.4.13 Links
Minimum diameter of links: = φ / 4 = 32 / 4 <9.5.3 & NA>
= 8 mm
Spacing: either
a) 0.6 × 20 × φ = 12 × 32 = 384 mm <9.5.3(3), 9.5.3(4)>
b) 0.6 × h = 0.6 × 500 = 300 mm or
c) 0.6 × 400 = 240 mm
∴ use H8 links at 225 mm cc.
Number of legs:
Bars at 127 mm cc i.e. < 150 mm ∴ no need to restrain bars in face but good <9.5.3(6)
practice suggests alternate bars should be restrained SMDSC 6.4.2>
∴ use single leg on face bars both ways @ 225 mm centres.
§§
Gk = 562.1; Qk = 755.6 × αn = 755.6 × 0.9; NEd = 562.1 × 1.25 + 755.6 × 0.9 × 1.5 = 1722.7 kN
5.5.1 Cover
Nominal cover, cnom
cnom = cmin + Δcdev <Exp. (4.1)>
where
cmin = max[cmin,b, cmin,dur]
where
cmin,b = diameter of bar. Assume 32 mm main bars and 10 mm links <4.4.1.2(3)>
cmin,dur = minimum cover due to environmental conditions. Assuming <BS 8500–1 Table
primarily XC3 / XC4, secondarily XF1, cmin,dur = 25 mm A4>
Δcdev = allowance in design for deviation
= 10 mm
∴ try cnom = 32 + 10 = 42 mm to main bars
or = 25 + 10 = 35 mm to 8 mm links
Try cnom = 35 mm to 8 mm links
c) As additional check, check adequacy of section to Annex B3 and Annex C. <BS EN 1992–1–2:
Using BS EN 1992–1–2 Table C.8 5.3.3(1), Annex C &
NA>
For ω = 1.0, e = 0.25b, R120, λ = 30 <BS EN 1992–1–2:
and interpolating between n = 0.3 and n = 0.5, Annex C(2)>
bmin = 350 mm, amin = 48 mm.
∴ Axis distance = 43 mm + φ / 2 is OK
∴ 4 no. H32 + 4 no. H25 with 35 mm cover to 8 mm links
(a = 55 mm min.) OK.
Figure 5.13
First order moments
***
With reference to Exp. (5.13N), ϕef may be taken as equal to 2.0. However, for the purpose of
illustration the full derivation is shown here.
†††
Imperfections need to be taken into account in one direction only. <5.8.9(2)>
Figure 5.14
Design summary: small perimeter column
Draft Version
All advice or information from The Concrete Centre is intended for those who will evaluate
the significance and limitations of its contents and take responsibility for its use and
application.
No liability (including that for negligence) for any loss resulting from such advice or
information is accepted by the Concrete Centre or their subcontractors, suppliers or
advisors.
Readers should note that this is a draft version of a document and will be subject to
revision from time to time and should therefore ensure that they are in possession of the
latest version.
4 Beams
4.1 General
The calculations in this Section are presented in the following parts:
4.2 A simply supported continuous beam showing what might be deemed typical hand
calculations.
4.3 A heavily loaded L-beam.
4.4 A wide T-beam. This example is analysed and designed strictly in accordance with the
provisions of BS EN 1992–1–1.
They are intended to be illustrative of the Code and not necessarily best practice.
A 450 mm deep × 300 mm wide rectangular beam is required to support office loads of gk =
30.2 kN / m and qk = 11.5 kN / m over 2 no. 6 m spans. fck = 30 MPa, fyk = 500 MPa. Assume
300 mm wide supports, a 50-year design life and a requirement for a 2-hour resistance to
fire in an external but sheltered environment.
Figure 4.2
Section through beam
4.2.1 Actions
kN / m
Permanent
gk = 30.2
Variable
qk = 11.5
4.2.2 Cover
Nominal cover, cnom
cnom = cmin + Δcdev <Exp. 4.1>
where
cmin = max[cmin,b; cmin,dur]
where
<4.4.1.2(3)>
cmin,b = minimum cover due to bond
= diameter of bar.
Assume 25 mm main bars
cmin,dur = minimum cover due to environmental conditions.
Assuming XC3 (moderate humidity or cyclic wet and <Table 4.1 BS 8500-1
dry) and secondarily XF1 (moderate water saturation Table A4, How to xxxx[20]>
without de-icing salt) using C30/37 concrete ,
cmin,dur = 25 mm
Δcdev= allowance in design for deviation. Assuming no
measurement of cover Δcdev= 10 mm <4.4.1.2(3)>
∴ cnom = 25 + 10 = 35 mm
Fire:
Check adequacy of section for 2 hours fire resistance (i.e. R = 120)
For bmin = 300 mm, minimum axis distance, a = 35 mm ∴ OK <BS EN 1992-1-2, 5.6.3(1),
Table 5.6>
cnom = 35 mm
4.2.4 Analysis
Design moments
Spans
MEd = (1.25 × 30.2 × 0.090 + 1.5 × 11.5 × 0.100) × 6.02 <Concise EC2 Table 15.3>
= 122.3 + 62.1 = 184.4 kNm
Support <Concise EC2 Table 15.3>
MEd = 50.8 × 0.106 × 6.02 = 193.8 kNm
Shear force
VAB = 0.45 × 6.0 × 50.8 = 137.2 kN
VAB = 0.63 × 6.0 × 50.8 = 192.0 kN
Table 4.1
Coefficients for use with beams (See Concise EC2 Table 15.3)
Coefficient Location
Outer Near middle At 1st At middle At interior
support of end span interior of interior supports
support spans
Moment gk and qk 25% spana — 0.094 — 0.075
Moment gk — 0.090 — 0.066 —
Moment qk — 0.100 — 0.086 —
Shear 0.45 — 0.63:0.55 — 0.50:0.50b
Conditions
For beams and slabs, 3 or more spans. (They may also be used for 2 span beams but support moment coefficient =
0.106 and internal shear coefficient = 0.63 both sides.)
Key
a At outer support ‘25% span’ relates to the UK Nationally Determined Parameter for BS EN 1992-1-1 9.2.1.2(1)
for minimum percentage of span bending moment to be assumed at supports in beams in monolithic
construction. 15% may be appropriate for slabs (see BS EN 1992-1-1 Cl 9.3.1.2).
b For beams of five spans, 0.55 applies to centre span.
4.2.6 Shear
Support B (critical)
Shear at central support = 192.0 kN
At face of support
VEd = 192.0 − (0.300 / 2 + 0.392) × 50.8 = 164.50 kN <6.2.1(8)>
vEd = VEd / bd
= 164.5 × 103 / (392 × 300) = 1.40 MPa
Maximum shear capacity
‡
K′ is limited to 0.208. However, if, as is usual practice in the UK, x / d is limited to 0.45, z / d is as a
consequence limited to 0.82 and K′ to 0.168.
Shear reinforcement
Assuming z = 0.9 d <6.2.3(1)>
Asw / s ≥ VEd / (0.9 d × fywd × cot θ) <6.2.3(3), Exp. (6.8)>
≥ 164.5 × 103 / (0.9 × 392 × (500 / 1.15) × 2.5) = 0.429
More accurately, <6.2.3(3), Exp. (6.8)>
Asw / s ≥ VEd / (z × fywd × cot θ)
≥ 164.5 × 103 / (333 × 1087) = 0.454
Minimum shear links, <9.2.2(5)>
Asw,min / s = 0.08bwfck0.5 / fyk
= 0.08 × 300 × 300.5 / 500 = 0.263 Not critical
Max. spacing = 0.75d = 0.75 × 392 = 294 mm <9.2.2(6)>
Use H8 @ 200 (Asw / s = 0.50)
Support A (and C)
Shear at end support = 137.2 kN
At face of support
VEd = 137.2 − (0.150 + 0.392) × 50.8 = 109.7 kN <6.2.1(8)>
By inspection,shear reinforcement required and cot θ = 2.5 <Concise EC2 Fig. 15.1a>
Asw / s ≥ VEd / (z × fywd × cot θ) <Concise EC2 15.5.3>
≥ 109.7 × 103 / [353 × (500 / 1.15) × 2.5] = 0.285
Use H8 @ 200 (Asw / s = 0.50) throughout††
Figure 4.3
Continuous rectangular beam: Summary of design
Note
It is presumed that the detailer would take this design and detail the slab to normal best practice, e.g.
to Standard method of detailing structural concrete[21]. This would usually include dimensioning and
detailing curtailment, laps, U-bars and also undertaking the other checks detailed in Section 4.2.8.
§
The absolute maximum for vRd,max (and therefore the maximum value of vEd) would be 5.28 MPa when
cot θ would equal 1.0 and the variable strut angle would be at a maximum of 45°.
**
For determination of VRd,max see Section 4.3.10.
††
As maximum spacing of links is 294 mm, changing spacing of links would appear to be of limited
benefit.
Figure 4.4
Continuous rectangular beam: RC details
Figure 4.5
Heavily loaded L-beam
This edge beam supports heavy loads from storage loads. The variable point load is
independent of the variable uniformly distributed load. The beam is supported on 350 mm
square columns 4000 mm long. fck = 30 MPa; fyk = 500 MPa. The underside surface is subject
to an external environment and a 2 hour fire resistance requirement. The top surface is
internal subject to a 2 hour fire resistance requirement. Assume that any partitions are
liable to be damaged by excessive deflections.
Figure 4.6
Section through L-beam
4.3.1 Actions
Permanent:
UDL from slab and cladding gk = 46.0 kN / m
Fire:
Check adequacy of section for 2 hours fire resistance R120 <BS EN 1992-1-2 5.6.3>
By inspection, BS EN 1992–1–2 Table 5.6 web thickness OK <BS EN 1992-1-2, Table 5.6>
Axis distance, a, required = 35 mm OK by inspection <BS EN 1992-1-2, Table 5.6>
∴ Try 35 mm nominal cover bottom and sides to 10 mm link
4.3.4 Analysis
Analysis by computer, assuming simple supports and including 15% redistribution at <BS EN 1990 A1.2.2 & NA,
supports (with, in this instance, consequent redistribution in span moments). 5.3.1 (6)>
Table 4.2
Elastic and redistributed moments kNm
Span number 1 2
Elastic M 1168 745
Redistributed M 1148 684
δ 0.98 0.92
Figure 4.7
Redistributed envelope, kNm
‡‡
Note: 350 × 350 is a minimum for columns requiring a fire resistance of 120 minutes
<BS EN 13670
Table 5.2a>
§§
The distance l0 is described as the distance between points of zero moment, ‘which may <5.3.2.1(2)>
be obtained from Figure 5.2’. In this case l0 = 0. (see figure 4.11) <Figure 5.2>.
Figure 4.9
Distance ‘A’
where
ϕ = 32
σsd = design stress in the bar at the ULS
= 434.8 × 1012 / 1608 = 274 MPa
fbd = ultimate bond stress <8.4.2 (2)>
= 2.25 η1 η2 fct,d
where
η1 = 1.0 for good bond conditions
η 2 = 1.0 for bar diameter ≤ 32 mm <3.1.6 (2),Tables 3.1 & 2.1, &
fct,d = αct fctk / γc NA>
= 1.0 × 2.0 / 1.5
= 1.33 MPa
fbd = 2.25 × 1.33 = 3.0 MPa
lb,rqd = (32 / 4) (274 / 3.0) = 731 mm***
lb,min =max[10ϕ; 100 mm] = 250 mm
∴ lbd = 731 mm i.e. < 1006 mm ∴ OK
Use 2 no. H32 U-bars
***
Anchorage lengths may be obtained from published tables. In this instance, a figure of 900 mm may
be obtained from Table 13 of the How to on Detailing. <How to: Detailing [12]>
Figure 4.10
<Fig. 5.3>
Effective flange width beff
Figure 4.11
<Fig. 5.2>
Elevation showing definition of lo for calculation of flange width
†††
The distance l0 is described as the distance between points of zero shear, ‘which may <5.3.2.1(2)>
be obtained from Figure 5.2’. From the analysis, l0 could have been taken as 7200 mm. <Figure 5.2>
Figure 4.12
Span AB bottom reinforcement
= 11 + 7.2 + 0 = 18.2
K = (end span) = 1.3 <Table 7.4N & NA>
F1 = (beff / bw = 1780 / 350 = 5.1) = 0.80 <7.4.2(2), Concise EC2 10.5.2>
F2 = 7.0 / leff (span > 7.0 m) <7.4.2(2)>
where
leff = 9000 mm <5.3.2.2(1)>
F2 = 7.0 / 9.0 = 0.77
F3 = 310 / σs
where
σs in simple situations = (fyk / γs) (As,req / As,prov) (SLS loads / ULS loads)
(1 / δ). However in this case separate analysis at SLS would be
required to determine σs. Therefore as a simplification use the
conservative assumption:
310 / σs = (500 / fyk) (As,req / As,prov) <Exp. (7.17)>
= (500 / 500) × (4824 / 4158) = 1.16
∴ Permissible l / d = 18.2 × 1.3 × 0.80 × 0.77 × 1.16 = 16.9
Actual l / d = 9000 / 668 = 13.5
As permissible less than actual
∴ OK
∴ 4 no. H32 B1 + 2 no. H32 B3 (4824 mm2) OK
2.18 of PD 6687[5] suggests that ρ in T sections should be based on the area of concrete above the
‡‡‡
Figure 4.13
Support B reinforcement
where
b = beff = beff1 + bw + beff2 <5.3.2.1, Fig. 5.3>
where
beff1 = (0.2b1 + 0.1l0) ≤ 0.2 l0 ≤ b1
where
b1 = distance between webs / 2.
Assuming beams at 7000 mm cc <Fig. 5.2>
= (7000 – 350) / 2 = 3325 mm
l0 = 0.85 × l1 = 0.85 × 8000 = 6800 mm
beff1 = 0.2 × 3325 + 0.1 × 6800 ≤ 0.2 × 6800 ≤ 3325
= 1345 ≤ 1360 ≤ 3325
= 1360 mm
bw = 350 mm
beff2 = (0.2b2 + 0.1l0) ≤ 0.2 l0 ≤ b2
where
b2 = 0 mm
beff2 = 0 mm
∴ b = 1360 + 350 + 0 = 1710 mm
Figure 4.14
Summary of L-beam design
Figure 4.16
Continuous wide T-beam
This central spine beam supports the ribbed slab in Example 3.4. The 300 mm deep ribbed
slab is required for an office to support a variable action of 5 KN/m2. The beam is the same
depth as the slab and is supported on 400 mm square columns, see Figure 4.17. fck = 35 MPa;
fyk = 500 MPa. 1 hour fire resistance required, internal environment. Assume that partitions
are liable to be damaged by excessive deflections.
Figure 4.17
Section through T-beam
4.4.2 Cover
Nominal cover, cnom
∴ cnom = 15 + 10 = 25 mm to links
or = 25 + 10 = 35 mm to main bars
Use 10 mm diameter links to give cnom = 35 mm to main bars
and 25 mm to links (as per ribbed slab design)
Fire:
Check adequacy of section for REI 60 <BS EN 1992-1-2 5.6.3>
<BS EN 1992-1-2
Table 5.6>
Axis distance required
Minimum width bmin = 120 mm with a = 25mm <BS EN 1992-1-2
or bmin = 200 mm with a = 12 mm Table 5.6>
∴ at 2000 mm wide (min.) a < 12 mm
By inspection, not critical
Use 25 mm nominal cover to links
§§§
The actions may also have been estimated assuming an elastic reaction factor of 1.1 for the slab
viz:
Permanent: UDL kN / m
Loads from ribbed slab (7.50 + 9.0) / 2 × 4.30 × 1.1 = 39.0
Self-weight/patch load extra over solid 2.0 × 4.17 = 8.3
47.3
Variable
Imposed (7.50 + 9.0) / 2 × 5.00 × 1.1 = 45.4
4.4.4 Analysis
Analysis by computer, assuming simple supports and including 15% redistribution <BS EN 1990 A1.2.2 &
at supports (with in this instance consequent redistribution in span moments). NA, 5.3.1 (6) >
Table 4.3
Elastic and redistributed moments, kNm
Span number 1 2 3 4
Elastic M 641.7 433.0 433.0 641.7
Redistributed M 606.4 393.2 393.2 606.4
δ 0.945 0.908 0.908 0.945
Figure 4.18
Redistributed envelope, kNm
****
cf. 126.7 kN / m from analysis of slab
= 11 + 6.8 + 0 =17.8
K = (end span) = 1.3 <Table 7.4N & NA>
F1 = (beff / bw = 4057 / 2000 = 2.03) = 0.90 <7.4.2(2), Concise EC2 10.5.2>
F2 = 7.0 / leff (span > 7.0 m) <7.4.2(2)>
where <5.3.2.2(1)>
leff = 7100 + 2 × 300 / 2 = 7400 mm
F2 = 7.0 / 7.4 = 0.95
F3 = 310 / σs
where
σs = (fyk / γs) (As,req / As,prov) (SLS loads / ULS loads) (1 / δ)
= 434.8 × (5835 / 5892) [(47.8 + 0.3 × 45.8) / (1.25 ×
47.8 + 1.5 × 45.8)] × (1 / 0.945)
= 434.8 × 0.99 × 0.48 × 1.06
= 219 MPa
F3 = 310 / σs <Exp. (7.17)>
= 310 / 219 = 1.41
∴ Permissible l / d = 17.8 × 1.3 × 0.90 × 0.95 × 1.41 = 27.9
2.18 of PD 6687[5] suggests that ρ in T sections should be based on the area of concrete above
††††
‡‡‡‡
Both As,prov / As,req and any adjustment to N obtained from Exp. (7.16a) or Exp. (7.16b) is restricted
to 1.5 by Note 5 to Table NA.5 in the UK NA.
where
b = beff = beff1 + bw + beff2 <5.3.2.1, Fig. 5.3>
where
beff1 = (0.2b1 + 0.1l0) ≤ 0.2 l0 ≤ b1
where
b1 referring to Figure 3.9
= (7500 – 1000 – 550) / 2 = 2975 mm
l0 = 0.70 × l2 = 0.7 × 7500 = 5250 mm <Fig. 5.2>
beff1 = (0.2 × 2975 + 0.1 × 5250 ≤ 0.2 × 5250 ≤ 2975
= 1120 ≤ 1050 ≤ 2975
= 1050 mm
bw = 2000 mm
beff2 = (0.2b2 + 0.1l0) ≤ 0.2 l0 ≤ b2
where
b2 = distance between webs / 2
Referring to Figure 3.9
= (9000 – 1000 – 550) / 2 = 3725 mm
l0 = 5250 mm as before
beff2 = 0.2 × 3725 + 0.1 × 5250 ≤ 0.2 × 5250 ≤ 3725
= 1270 ≤ 1050 ≤ 3725
= 1270 mm
b = 1050 + 2000 + 1270 = 4320 mm
§§§§
2.18 of PD 6687[5] suggests that r in T sections should be based on the area of concrete above
the centroid of the tension steel.
*****
12 no. H20 B (3768 mm2) used to suit final link arrangements.
†††††
12 no. H25 used to suit final arrangement of links.
‡‡‡‡‡
(2000 mm – 2 × 25 mm cover − 10 mm diameter) / 175 = 11 spaces, ∴ 12 legs
Check shear stress at basic perimeter u1 (2.0d from face of column) <6.4.2>
vEd = βVEd / u1d < vRdc
where
β, VEd, d as before <Fig. 6.13>
u1 = control perimeter under consideration. For
punching shear at 2d from interior columns
= 2(cx + cy) + 2π × 2d
= 1600 + 2π × 2 × 235 = 4553 mm
vEd = 1.15 × 1087.0 × 103 / 4553 × 235 = 1.17 MPa
vRdc = 0.18 / γc × k × (100 ρlfck)0.333 <Exp. (6.47) & NA>
where
γc = 1.5
k = 1 + (200/d)0.5 ≤ 2
k = 1 +(200 / 235)0.5 = 1.92
ρl = (ρlx ρly)0.5 <6.4.4.1(1)
where
ρlx = areas of bonded steel in a width of the column
§§§§§
In this case, at the perimeter of the column, it is assumed that the strut angle is 45°, i.e. that
cot θ = 1.0. In other cases, where cot θ < 1.0, vRd,max is available from Concise EC2[10] Table 15.7.
Figure 4.21
Shear links and punching shear perimeter u1
******
vRd,c for various values of d and ρl is available from Concise EC2[10] Table 15.6
Figure 4.22
Summary of design
Figure 4.23
Section X–X