Basic Generator Control Loops
Basic Generator Control Loops
Basic Generator Control Loops
Pm(s) _
1/2Hs
(s)
Pe(s)
In a power plant, the size of generators can vary fro 50 MW to 1500 MW.
PL(s)
Pm(s)
1/(2Hs+D)
(s)
PV(s)
1/(1+TTs)
Pm(s)
rotating system. The reduction in kinetic energy causes the turbine speed and, consequently, the generator frequency to fall. The change in speed is sensed by the turbine governor which acts to adjust the turbine input valve to change the mechanical power output to bring the speed to a new steady-state. The earliest governors were the watt governors which sense the speed by means of rotating flyballs and provide mechanical motion in response to speed changes. However, most modern governors use electronic means to sense speed changes. Figure 3.4 shows schematically the essential elements of a conventional Watt governor which consists of the following major parts.
1. Speed governor: The essential parts are centrifugal flyballs driven directly or
through
gearing by the turbine shaft. The mechanism provides upward and downward vertical movements proportional to the change in speed.
2. Linkage Mechanism: These are links for transforming the flyballs movement to the turbine valve through a hydraulic amplifier and providing a feedback from the turbine valve movement.
3. Hydraulic Amplifier: Very large mechanical forces are needed to operate the steam valve. Therefore, the governor movements are transformed into high power forces via several stages of hydraulic amplifiers. 4. Speed Charger: the speed charger consist of servomotor which can be operated manually or automatically for scheduling load at nominal frequency. By adjusting this set point, a desired load dispatch can be scheduled at nominal frequency.
PL(s)
_
Governor Turbine Rotating mass and load
1/R
When the load on the system is increased, the turbine speed drops before the governor can adjust the input of the steam to the new load. As the change in the value of speed diminishes, the error signal becomes smaller and position of the governor falls gets closer to the point required to maintain a constant speed. However the constant speed will not be the set point, and there will be offset. One way to restore the speed or frequency to its nominal value is to add an integrator.
The integral unit monitors the average error over a period of time and will overcome the offset. Because of its ability to return a system to its set point, integral action is known as the rest action. Thus, as the system load change continuously, the generation is adjusted automatically to restore the frequency to the nominal value .This scheme is known as the automatic generation control (AGC).
In an interconnected system consisting of several pools, the role of the automatic generation control (AGC) is to divide the loads among system, station generators so as to achieve maximum economy and correctly control the scheduled interchanges of tie-line power while maintaining a reasonably uniform frequency. During large transient disturbances and emergencies, AGC is bypassed and other emergency controls are applied.
Modern power system network consists of a number of utilities interconnected together & power is exchanged between utilities over tie-lines by which they are connected. Automatic generation control (AGC) plays a very important role in power system as its main role is to maintain the system frequency and tie line flow at their scheduled values during normal period and also when the system is subjected to small step load perturbations. Many investigations in the field of automatic generation control of interconnected power system have been reported over the past few decades.
Governor
Turbine
1/R
KI/s
During normal operation, the real power transferred over the tie line is given by P12 = |E1| |E2| sin12 X12
Where X12 = X1+ Xtie+ X2, and 12= 1 - 2. The tie line power deviation then takes on the form P12 = Ps(1 - 2) The tie line power flow appears as a load increase in one area and a load decrease in the other area, depending on the direction of the flow. The direction of the flow. The direction of flow is dictated by phase angle difference; if 1 > 2, the power flows from area 1 to area 2. A block diagram representation for the two-area system with LFC containing only the primary loop is shown in Figure 4.3.
Conventional LFC is based upon tie-line bias control, where each area tends to reduce the area control error (ACE) to zero. The control error for each area tends to consists of linear combination of frequency and tie-line error. ACEi = nj=1 Pij +Ki The area bias Ki determines the amount of interaction during a disturbance in the neighboring areas. An overall satisfactory performance is achieved when K is selected equal to the frequency bias factor of that area, i.e., Bi =1/Ri +Di . Thus, the ACEs for a two area systems are ACE1 = P12 +B1 1 ACE1 = P21 +B2 2 Where P12 and P21 are departures from scheduled interchanges. ACEs are used as actuating signals to activate changes in the reference power set points, and when steady state is reached, P12 and will be zero. The integrator gain constant must be chosen small enough so as not cause the area to go into a chase mode. The block diagram of a simple AGC for two area system is shown in Figure 4.4