Chapter-3 Load Frequency Control, Control Area Concept
Chapter-3 Load Frequency Control, Control Area Concept
Introduction
Automatic Load frequency control (ALFC) in a power system regulates the power
flow between different areas while holding frequency constant. It divide the load
between the generators and control the tie line interchange schedules. The ALFC
loop will maintain control only during small and slow changes in load and
frequency. It will not provide adequate control during emergency situation when
large megawatt imbalance occurs. (Drawback of ALFC)
1) Speed changer
2) Speed governor
3) Hydraulic amplifier
Page 1
4) Control valve.
When speed raises, linkage movements will be: “A” moves downwards; “C” moves
upwards; “D” moves upwards; “E” moves downwards. This allows more steam or
water flow into the turbine resulting incremental increase in generator output
power.
When the speed drops, linkage movements will be: “A” moves upwards ; “B”
moves upwards “C” moves downwards; “D” moves downwards; “E” moves
upwards. This allows less steam or water flow into the turbine resulting decrease
in generator output power.
If Δf= change in
load
Generally governors have a speed regulation of 5.6% from zero to full load.
Unit of R is Hz/MW. The output of speed governor mechanism (ΔPg) is the
difference between the reference power (ΔPref) and change in load.
∆𝑃g = ∆𝑃𝑟𝑒ƒ − ∆𝑃
∆𝑃g ∆ƒ
= ∆𝑃𝑟𝑒ƒ −( )… … … (2)
𝑅
Taking Laplace transform of eq.(2) yields
1
∆𝑃 (𝑠) = ∆𝑃 ( ) ()
g 𝑟𝑒ƒ 𝑠 … … … (3)
The input position of the valve actuator(ΔXd) is the difference between governor
outputs (ΔPg) and the hydraulic actuator output (ΔPv)
For a small change in ΔPv, the oil flow into the hydraulic motor is proportional to
the position ΔXd of the pilot valve.
𝑑(∆𝑃𝑣)
𝑇ℎ𝑒𝑟𝑒ƒ𝑜𝑟𝑒, 𝛼 (∆X )
𝑑
𝑑𝑡
𝑑(∆𝑃𝑣)
= 𝐾 (∆X ) … … … (6)
𝑑𝑡 𝐻 𝑑
Where K is a constant depends upon the orifice, cylinder geometries and the fluid
pressure.
∫ 𝑑(∆𝑃𝑣) = 𝐾𝐻 ∫ ∆X𝑑 𝑑𝑡
Turbine generator
In normal steady state, the turbine power PT keeps zero acceleration and a
constant speed and frequency.
During transient state, let the change in turbine power be ΔPT and the
corresponding change in generator power be ΔPG
The turbine power increment ΔPT depends entirely upon the valve power
increment ΔPv and the characteristic of the turbine.
Different type of turbines will have different characteristics.
Taking transfer function with single time constant for the turbine, we can write
1
∆𝑃 (𝑠) = 𝐺 ∆𝑃 (𝑠) =
∆𝑃 (𝑠) … … … (13)
𝑇 𝑇 𝑣
1 + 𝑠𝑇𝑇 𝑣
The generator power increment ΔPG depends entirely upon the change in the load
ΔPD being fed from the generator.
The generator always adjusts its output so as to meet the demand changes ΔPD.
accelerating power
The control loop shown in Fig. is open, No information can be obtained about the
static performance of the speed governor.
The static performance can be obtained by letting s = 0.
From Fig.
∆𝑃𝑣
𝐺𝐻 = … … … (16)
∆𝑃g
Substituting GH=1, we get
Case-A: The generator is synchronized to a network of very large size and the
frequency will be independent of any changes in the power output of this individual
generator(infinite network).
∆ƒ0 = 0 … … … (22)
∆𝑃𝑟𝑒ƒ,0 = 0 … … … (24)
It is clear from equation (20), that for a constant setting of the speed changes, the
static increase in turbine power output is directly proportional to the static
frequency drop.
Case-C: In general case, changes may occur in both the speed changer (reference
power) setting and frequency. In frequency generation graph, equation (21)
represents a family of sloping lines as shown in fig. Each line corresponds to a specific
reference power setting. It is clear from fig that the generators working in parallel on
the same network should have the same regulation in order to share load changes in
proportion to size.
Example 1
Solution:
The “old” load is a function of voltage magnitude and frequency. The old area load
depends on the frequency given by
6𝑃𝐷 𝑀W
𝐷= … … … (27)
6ƒ 𝐻𝑧
𝐷. 6ƒ = 6𝑃𝐷
For area power balance, the increase in turbine power is equal to the sum of old and
new load changes plus the rate of change of kinetic energy.
Turbine power = old load change + new load change + rate of change of kinetic energy
𝑑
∆𝑃 = ∆𝑃 + 𝐷∆ƒ + W … … (28)
𝑇 𝐷
𝑑𝑡 𝑘i𝑛
∆ƒ 2 ∆ƒ
0
=W 𝑘i𝑛 [1 + ( 0 ) + 2.1. 0 ] … … … (29)
ƒ ƒ
∆ƒ 2
( 0 ) ≈ 0 … … … (30)
ƒ
2∆ƒ
W = W0 [1 + ] … … … (31)
𝑘i𝑛 𝑘i𝑛
ƒ0
𝑑
∆𝑃 = ∆𝑃 + 𝐷∆ƒ + W
𝑇 𝐷 𝑘i𝑛
𝑑𝑡
𝑑 2∆ƒ
∆𝑃𝑇 = ∆𝑃𝐷 + 𝐷∆ƒ + W0 [1 + (32)
] …0… …
𝑑𝑡
𝑘i𝑛 ƒ
2 𝑑
∆𝑃 − ∆𝑃 = 𝐷∆ƒ + W0 (0 + ∆ƒ)
𝑇 𝐷 𝑘i𝑛
ƒ0 𝑑𝑡
2W 𝑘i𝑛 𝑑
∆𝑃 − ∆𝑃 = 𝐷∆ƒ + 0 ∆ƒ … … … (33)
𝑇 𝐷
ƒ0 𝑑𝑡
1
Wℎ𝑒𝑟𝑒, 𝐾𝑃 = … … … (41)
𝐷
2𝐻
𝑇𝑃 = … … … (42)
𝐷ƒ0
𝐾𝑃
𝐺𝑃 (𝑠) = 1 + 𝑠𝑇𝑃 … … … (43)
Equation (40) represents the missing link Δf(s) in the control loop of fig. the open loop
can be closed by adding a summing junction and a transfer block as shown in fig.
Static response of Primary ALFC loop
The basic objective of the primary ALFC loop is to maintain constant frequency in
spite of changing loads. The primary ALFC loop as shown in the fig. has one output
and two inputs. ΔPref(s) and ΔPD(s)
1
{[∆𝑃𝑟𝑒ƒ (𝑠) − (𝑠)] 𝐺𝐻 (𝑠)𝐺𝑇(𝑠) − ∆𝑃𝐷 (𝑠)} 𝐺𝑃 (𝑠) = (𝑠) … … … (46)
∆ƒ𝑅 ∆ƒ
Therefore,
1
{[0 − ∆ƒ(𝑠)] 𝐺𝐻 (𝑠)𝐺𝑇(𝑠) − ∆𝑃𝐷 (𝑠)} 𝐺𝑃 (𝑠) = (𝑠)
𝑅 ∆ƒ
1
− (𝑠)𝐺𝐻 (𝑠)𝐺𝑇 (𝑠)𝐺𝑃 (𝑠) − ∆𝑃𝐷 (𝑠)𝐺𝑃 (𝑠) = ∆ƒ(𝑠)
∆ƒ𝑅
1
∆ƒ(𝑠) [1 + 𝐺𝐻 (𝑠)𝐺𝑇 (𝑠)𝐺 (𝑠)] = (𝑠)𝐺𝑃 (𝑠)
𝑅 𝑃 −∆𝑃𝐷
𝐺𝑃(𝑠)
∆ƒ(𝑠) = − ∆𝑃
(𝑠) … … … (47)
1
[1 + 𝐺 (𝑠)𝐺 (𝑠)𝐺 (𝑠)] 𝐷
𝐻 𝑇 𝑃
𝑅
For a step load change of constant magnitude,
∆𝑃𝐷 = 𝑀 = 𝑎 𝑐𝑜𝑛𝑠𝑡𝑎𝑛𝑡
by,
𝐺𝑃(𝑠) 𝑀
∆ƒ = lim 𝑠 [−
0 1
𝑠→0 [1 + (𝑠)𝐺 (𝑠)𝐺
𝐺 𝑇 𝑃
𝐻
𝑅
𝐺𝑃(𝑠)𝑀
∆ƒ = lim [− ]… … … (51)
0 1
𝑠→0 [1 + (𝑠)𝐺 (𝑠)𝐺 (𝑠)]
𝐺
𝐻 𝑇 𝑃
𝑅
But
𝐾𝑃
𝐺𝑃 (𝑠) = 1 + 𝑠𝑇𝑃 … … … (52)
1
𝐺𝐻 (𝑠) = … … … (53)
1+
𝑠𝑇𝐻
𝐺𝑇 1 … … … (54)
(𝑠) =
1+
𝑠𝑇𝑇
1 +𝐾𝑠𝑇
𝑃
𝑃.
∆ƒ0 = lim [− ]… … … (55)
𝑠→0
𝑀 1 1 1 𝐾𝑃
[1 + . . . ]
𝑅 1 + 𝑠𝑇𝐻 1 + 𝑠𝑇𝑇 1 + 𝑠𝑇𝑃
𝐾𝑃
.𝑀
0 𝐾𝑃𝑀
∆ƒ0 = [− ]=
− 1 1 1 𝐾𝑃 𝐾
[1 + . . . ] [1 +
𝑃
]
𝑅 1 1 1 𝑅
∆ƒ0 1 𝑀 𝑀
=− 𝑀=− 1 =− 𝐻𝑧 … … … (56)
1 1 [𝐷 + 𝛽
[] + ]
𝐾𝑃 𝑅 𝑅
Where,
1
𝐷= … … … (57)
𝐾𝑃
1
𝐾𝑃 = … … … (58)
𝐷
1 ( )
𝑃=𝐷+ = 𝑎𝑟𝑒𝑎 ƒ𝑟𝑒𝑞𝑢𝑒𝑛𝑐𝑦 𝑟𝑒𝑠𝑝𝑜𝑝𝑛𝑠𝑒 𝑐ℎ𝑎𝑟𝑎𝑐𝑡𝑒𝑟i𝑠𝑡i𝑐 𝐴𝐹𝑅𝐶 … … (59)
𝑅
From the static response, frequency accuracy is obtained.
Dynamic response of ALFC loop gives information about tracking ability and stability
of the loop.
In eq(36), GH(s), GT(s) and GP(s) contains atleast one time constant each. Therefore,
the denominator will be of 3 rd order and the analysis will be complex. To simplify the
analysis, it is to be assumed that the action of speed governor plus the turbine
generator is instantaneous. Since the action of speed governor and turbine generator
is instantaneous the time constant for speed governor (TH) and the time constant for
turbine generator TT is equal to zero.
∴ 𝑇𝐻 = 𝑇𝑇 = 0 … … … (60)
1 +𝐾𝑠𝑇
𝑃
𝑃
𝑀
∆ƒ(𝑠) = − . … … … (61)
1 1 1 𝐾𝑃 𝑠
[1 + . . . ]
𝑅 1 + 𝑠𝑇𝐻 1 + 𝑠𝑇𝑇 1 + 𝑠𝑇𝑃
𝐾𝑠𝑇
1+ 𝑃 𝑀
𝑃
∆ƒ(𝑠) = − .
1 𝐾𝑃 1 1 𝑠
[1 + . . . ]
𝑅 1 + 𝑠𝑇𝑃 1 + 0 1 + 0
𝐾𝑃
1 + 𝑠𝑇𝑃 𝑀 𝑀 𝐾𝑃
∆ƒ(𝑠) = − . = − × 𝑅(1 + 𝑠𝑇𝑃)
1 𝐾𝑃 𝑠 × (𝑅 + 𝐾 ) + 𝑅𝑠𝑇
[1 + . ] 𝑠 1+ 𝑃 𝑃
𝑠𝑇𝑃
𝑅 1 + 𝑠𝑇𝑃
𝑀 𝐾𝑃𝑅 𝑀 𝐾𝑃 1
∆ƒ(𝑠) = − × =− [ ]
𝑠 𝑃 𝑅𝑠𝑇𝑃 + (𝑅 + 𝑠 𝑇𝑃 𝑅 + 𝐾𝑃
𝑅𝑇 [ 𝑠 + 𝑅𝑇𝑃
𝐾𝑃)
]
𝑅𝑇𝑃
𝑀𝐾𝑃
− 𝑇𝑃 𝐵
∆ƒ(𝑠) = = 𝐴
𝑅 + 𝐾𝑃 + … … … (62)
𝑠 (𝑠 + ) 𝑠 𝑠 + 𝑅 + 𝐾𝑃
𝑅𝑇𝑃 𝑅𝑇𝑃
On solving
𝑀𝑅𝐾𝑃
𝐴=− … … … (63)
𝑅 + 𝐾𝑃
𝑀𝑅𝐾𝑃
𝐵= … … … (64)
𝑅 + 𝐾𝑃
−𝑅𝑀𝑅𝐾
+ 𝐾𝑃𝑃 𝑅𝑀𝑅𝐾
+ 𝐾𝑃𝑃
∆ƒ(𝑠) = + … . . (65)
𝑠 𝑅 + 𝐾𝑃
𝑠+
𝑅𝑇𝑃
Fig shows the dynamic response of the primary ALFC loop to a step load increase.
It is clear that
The system can be made faster by reducing the value of R i.e. by increasing the value
of the static loop again.
If the response of the turbine is not disregarded then the response will not be purely
exponential as shown in fig. above.
When the load is suddenly increased by 1% (20 MW), where did this power come
from? Certainly it must have come from somewhere as the load increase of 20 MW has
been met with instantaneously. In the milliseconds following the closure of the
switch, the frequency has not changed a measureable amount, speed governor
would not have acted and hence turbine power would not have increased. In those
first instants the total additional load demand of 20 MW is obtained from the stored
kinetic energy, which therefore will decrease at an initial rate of 20 MW. Release of
KE will result in speed and frequency reduction. As seen in eq.(66),
𝑀𝑅𝐾𝑃
∆ƒ(𝑡) = − −(
𝑅+𝐾𝑃
)𝑡
𝑅 + 𝐾𝑃 [1 − 𝑅𝑇𝑃 ]… . . (66)
𝑒
Initially frequency reduces. The frequency reduction causes the steam valve to open
and result in increased turbine power. In conclusion, the contribution to the load
increase of 20 MW is made up of three components:
Initially the components 2 and 3 are zero. Finally, the frequency and hence the KE
settle at a lower value and the component 1 becomes zero. In between, component 1
keeps decreasing and components 2 and 3 keep increasing.
It is seen from the previous discussion for a given speed changer setting, there is
considerable frequency drop for increased system load. So much change in frequency
cannot be tolerated. In fact, it is expected that the steady state frequency change must
be zero. In order to maintain the frequency at the scheduled value, the speed changer
setting must be adjusted automatically by monitoring the frequency changes.For this
purpose, INTEGRAL CONTROLLER is included. In this case, the speed changer is
commanded by a signal obtained by first amplifying and then integrating the
frequency error.
∆𝑃𝑟𝑒ƒ = ∫(∆ƒ) 𝑑𝑡
Area Control Error(ACE): the signal fed into the integrator is referred to as area
control error(ACE) i.e. ACE=Δf.
When frequency error is reduced to zero, then the integrator output and the speed
changer position attains a constant value.
The gain constant K1 controls the rate of integration and thus the speed of response of
the loop. For this signal ΔF(s) is fed to an integrator whose output controls the speed
changer position resulting in the block diagram configuration shown in fig.
As long as an error remains, the integrator output will increase, causing the speed
changer to move. When the frequency error has been reduced to zero, the integrator
output ceases and the speed changer position attains a constant value. Integral
controller will give rise to ZERO STEADY STATE FREQUENCY ERROR following a step
load change because of the reason stated above.
Referring to the block diagram of single control area with integral controller shown in
fig. input to GHT is 1
𝑘1 ( ) ( ) 𝑘1 1
− ( )
∆𝐹 𝑠 − ∆𝐹 = − [ + ] ∆𝐹 … … … (69)
𝑠 𝑠 𝑅 𝑠 𝑠 𝑅
Using this equation the block diagram in fig can be reduced as shown in fig.
Load frequency control, as the name signifies, regulates the power flow
between different areas while holding the frequency constant.
The transmission lines that connect an area to its neighboring area are called tie-lines.
Power sharing between two areas occurs through these tie-lines.
10. What are the components used for the automatic load frequency control of a
single area system.
11. What are typical conditions needed to be taken care of while distributing
loads among the plants of a system?
12. Why frequency should remain constant? Explain in brief.
Reasons for the need of maintaining constant frequency:
(i) The speed of a.c. motors are directly related to the frequency.
(ii) If the normal operating frequency is 50 Hz and the turbines run at speeds
corresponding to frequencies less than 47.5 Hz or above 52.5 Hz, then the
blades of the turbines may get damaged.
(iii) The operation of a transformer below the rated frequency is not desirable.
When frequency goes below rated frequency at constant system voltage then
the flux in the core increases and then the transformer core goes into the
saturation region.
(iv) With reduced frequency the blast by ID fans and FD fans decrease, and so
the generation decreases and thus it becomes a multiplying effect and may
result in shut down of the plant.
25. What is the advantage of AVR loop over ALFC loop? AVR loop is much faster
than the ALFD loop and therefore there is a tendency, for the AVR dynamics to
settle down before they can make themselves felt in the slower load –frequency
control channel.
Numerical:
Example-1
Two generators rated 200MW and 400MW are operating in parallel. The drop
characteristics of their governors are 4% and 5% respectively from no load
to full load. Assuming that the governors are operating at 50Hz at no load,
how would a load of 600MW be shared between them? What will be the
system frequency at this load? Assume free governor operation.
Solution:
Since the generators are operating in parallel, they will operate at the same
frequency at steady load.
∆ƒ 0.04 × 50
𝑥= 200 … … … (1)
From equation(1), ∆ƒ 0.05 × 50
600 − = 400 … … … (2)
𝑥
0.04 × 50
∆ƒ = ×𝑥………
(3) 200
From equation(2),
0.05 × 50
∆ƒ = × (600 − 𝑥) … … … (4)
400
0.04 × 50 0.05 × 50
200 × 𝑥 = 400 × (600 − 𝑥)
𝑥 = 231𝑀W
Solution:
Since the generators are operating in parallel, they will operate at the same
frequency at steady load.
Reduction in frequency = Δf
∆ƒ 0.0415 × 50
𝑥= 221 … … … (1)
From ∆ƒ 550 − 𝑥
equati
on(1),
0.0535 × 50 429
= … … … (2)
0.0415 × 50
∆ƒ = × 𝑥 … … … (3)
221
From equation(2),
0.0535 × 50
∆ƒ = × (550 − 𝑥) … … …
(4)
429
0.0415 × 50 0.0535 × 50
221 ×𝑥= 429 × (550 − 𝑥)
𝑥 = 219.493 𝑀W
System frequency =
0.0415 × 50
50 − × 𝑥 = 46. 896 𝐻z
221
Example-03
Example-04
Example-05
Example-06
Example-07
Example-08
Example-09