Modeling of Turbine, Generator and Governing System
Modeling of Turbine, Generator and Governing System
Modeling of Turbine, Generator and Governing System
The amount of speed drop as the load on the turbine is increased from no load to its full-
load value is (No–N), where No is the speed at no load and N is the speed at rated load.
The steady-state speed regulation in per unit is given by
The value of R varies from 2% to 6% for any generating unit. Since the frequency and speed
are directly related, the speed regulation can also be expressed as the ratio of the change in
frequency from no load to its full load to the rated frequency of the unit:
i.e.,
i.e.,
The unit of R is taken as Hz per MW. In practice, power is measured in per unit and
hence R is in Hz/p.u. MW.
ADJUSTMENT OF GOVERNOR CHARACTERISTIC OF PARALLEL OPERATING UNITS
When two generators are running in parallel, the governor characteristic of the first unit
(Line 1) is shown towards the right, while that of the second unit (Line 2) is shown towards
the left of the frequency axis as shown in Fig.
The characteristics are obviously different and hence corresponding to the rated
frequency fr, the two units carry loads P1 and P2 so that the system load PD = P1 + P2. If the
system load is now increased to P′D, the system frequency will drop down to f ′, since the
units can only increase their output by decreasing the speed.
To restore the system frequency, the characteristic of one of the unit’s say of Unit 1 needs
to be shifted upwards as indicated by the dotted characteristic, so that it can carry the
increased load. The share of Unit 1 will be P1′ and that of Unit 2 will be P2 so that the
increased total load, PD′ = P1′ + P2.
PROBLEM-2
A 100-MW generator with R50.02 Hz/MW has its frequency fallen by 0.1 Hz. By how much
the reference power setting be changed if the turbine power remains unchanged.
Solution:
PROBLEM-3
Two generators with ratings 100 and 300 MW operate at 50 Hz frequency. The system load
increases by 100 MW when both the generators are operating at about half of their
capacity. The frequency then falls to 49.5 Hz.
If the generators are to share the increased load in proportion to their ratings, what should
be the individual regulations? What should be regulations if expressed in per-unit Hertz/
per-unit MW?
Solution:
Problem-6
Two generators of rating 100 and 200 MW are operated with a droop characteristic of 6%
from no load to full load. Determine the load shared by each generator, if a load of 270 MW
is connected across the parallel combination of those generators.
Solution:
The two generators are operating with parallel connection; the % drop in frequency from
two generators due to different loads must be same.
Let power supplied by (100 MW) Generator-1 = x
Percentage drop in frequency = 6%
Percent drop in frequency (or speed) of both machines must be the same:
Solution
Speed-governor system
With the movement of A moves in the downward direction by ΔXA, the link point C move
upwards by an amount Δ XC
Temporarily if B is fixed then
The constants K1 and K2 depend upon the length of linkage arms AB and BC and also
depend upon the proportional constants of the speed changer and the speed governor.
The movement of link point D, ΔXD is the amount by which the pilot valve opens and it is
contributed by the movement of point C, ΔXC, and movement of point E, ΔXE.
l l
X D 3 X E 4 X C
l3 l 4 l3 l 4
X D K 3 X C K 4 X E (4)
The movement ΔXD, results in the opening of the pilot valve, which leads to the admission
of high-pressure oil into the hydraulic amplifier cylinder; then the downward movement of
the main piston takes place and thus the steam valve opens by an amount ΔXE.
Two assumptions are made to represent the mathematical model of the movement of point
E:
The main piston and steam valve have some inertial forces, which are negligible when
compared to the external forces exerted on the piston due to high-pressure oil. Because of
the first assumption, the amount of oil admitted into the cylinder is proportional to the port
opening ΔXD, i.e., the volume of oil admitted into the cylinder is proportional to the time
integral of ΔXD.
t
Volumeof oil admitted 1
X D dt
area of cross sec tionof the piston A 0
X E
In Equation (5), the negative sign represents the movements of link points D and E in the
opposite directions. For example, the small downward movement of ΔXD causes the
movement ΔXE in the positive direction (i.e., upwards).
Taking the Laplace transform of Equations (3), (4), and (5), we get
Eliminating ΔXC(s) and ΔXD(s) in the above equations and substituting ΔXD(s) from
Equation (7) in Equation (8), we get
TURBINE MODEL
We are interested not in the turbine valve position but in the generator power
increment ΔPG. The change in valve position ΔXE causes an incremental
increase in turbine power ΔPT and due to electromechanical interactions
within the generator, it will result in an increased generator power ΔPG, i.e.,
ΔPT = ΔPG, since the generator incremental loss is neglected.
In this model, the turbine can be characterized by a single gain constant Kt and
a single time constant τt as
Therefore,
The above block diagram gives the derivation of an incremental or small signal model. The
model is adopted for large signal use by adding a saturation-type non-linear element, which
introduces the obvious fact that the steam valve must operate between certain limits. The
valve can neither be more open than fully open nor more closed than fully closed.
This model may also be modified to account for reheat cycles in the turbine and more
accurate representation of fluid dynamics in the steam inlet pipes or in the hydraulic
turbines in the penstock.
Reheat type of steam turbines
Modern generating units have reheat-type steam turbines as prime movers for higher
thermal efficiency.
The time constant τr has a value in the range of 10 s and approximates the
time delay for charging the reheat section of the boiler. Kr is a reheat
coefficient and is equal to the proportion of torque developed in the high-
pressure section of the turbine
Let H be the inertia constant of a generator (MW-s/MVA) and Pr the rating of the turbo-
generator (MVA):
W0KE = H × Pr (MW-s or M-J)-----------(2)
Hence, Equation (1) becomes
(ii) The load on the motors increases with increase in speed. The load on the system being
mostly motor load, hence some portion of the surplus power is observed by the motor
loads. The rate of change of load with respect to frequency can be regarded as nearly
constant for small changes in frequency.
dPD
f Bf (4)
df
Where the constant B is the area parameter in MW/Hz and can be determined empirically.
B is positive for a predominantly motor load.
Now, the surplus power can be expressed as
Solution