Fundamentos y Componentes de La Oleohidráulica - Rexroth OCR
Fundamentos y Componentes de La Oleohidráulica - Rexroth OCR
Fundamentos y Componentes de La Oleohidráulica - Rexroth OCR
T.C. Frankenfield
"Operated, moved, or effected by means of water," ac cording to Webster, means that hydraulics is as ancient as water itself. By strict definition, hydraulics has existed ever since the first stream of water eroded the first section of earth. A more modem definition of hydraulics was first realized in the 17th century when it was discovered that a fluid under pressure could be used to transmit power. Hydrostatics, a contemporary definition of the principles of hydraulics, is a very simple term based on a discovery by Blaise Pascal (1623-1662)_ He discovered that if a fluid in a closed container receives a force over any area of that con tainer, the pressure is then transmitted throughout the system undiminished and equal in all direciions. From this simple system (for distribution of power and changes in its direction) an interesting technology has evolved, which is the most versatile means of power transmission known today.
Hydraulics energy
our natural resources, namely oil or coal. In physics the law of conservation states that energy can neither be created nor destroyed, although it can be converted from one form to another, with some forms more useful to us than others. In a hydraulic system the energy input is called a prime Examples of prime movers are electric motors and in ternal combustion engines. Prime movers and hydraulic pumps do not create energy, they simply put it in a form that can be utilized by a hydraulic system_
mover.
WORK
r Force
is probably the most unique method to transmit to do work. It is more compact than the line of sight methods which are unavoidable in mechanical trans missions. Likewise , hydraulics is considerably more precise in controlling energy, and has a broader adjustability range than either electrical or mechanical means. It is the purpose of this chapter to study the laws of physics governing fluids.
Distance
'--
( {
Ex ample of Work In defining energy we had to use the term work. Simply stated, work is done when something is moved. If we lift a book from the table we have done work, however, there are two components which must exist to do work on the book. First of all, if we are to move the book we must exert a force on it in the form of a push or a pull. This force must be equal in magnitude to the weight of the book and opposed in direc tion. Consequently, a force has the units of pounds (lbs.) and we must know the pounds of force required to do any type of work. Secondly, if we move the book it must move through some which can be measured in inches, feet or miles. Thus, we have defined the other unit of work; namely dis lances represented in inches or feet.
distance
ENERGY
One of the most important topics of today is energy and con servation thereof. However, most people discuss and debate the use of energy without under)t{lflding what oz:w.!:tyyrPa!JIJy is. By simple definition, energy is the ability to do work. Although energy shows itself in the form of mechanical, elec trical, sound. light. heat or chemical, its origin is usually from
If enough force in pounds (lbs.) is exerted to move the book through a distance (ft.), then work is done. WORK = FORCE (lbs.) x DISTANCE (ft.) = (ft. - lbs.)
-1-
Fa
d.
The total force which must be exerted by the cylinder during acceleration is:
body in motion to stay in motion,or if at rest to stay at rest, unless acted on by an external force. Inertial forces are di
rectly related to the mass or weight of an object. The heavier an object is. the harder (more force) it is to start that object moving or to stop it once it's in motion.
ACCELERATION FORCE
On high speed equipment it is often necessary to move relatively heavy objects from rest to high speed (or vice versa) in a short amount of time. This requires fast acceleration (or deceleration) rates. We must take into consideration the forces required for this acceleration. Isaac Newton's (16421727) second law of motion states that the force required is simply the product of the object's mass times the required ac celeration rate. It must be remembered in the English system of units, mass is the weight of an object in pounds divided by the acceleration due to gravity. Consequently:
Weight 32 _2 ft/sec'
POWER=
ft-Ibs. sec.
Example: A vertically acting cylinder is to moue a 5000 lb. load from rest. and is to achieve a velocity of 30 ft./sec. in 1.5 sec. What force must be exerted by the cylinder?
a. We know that to lift the load we must exert an upward force of at least 5000 lbs. to balance the weight of the object, but we must also add to this a force to accelerate the mass. If we are to achieve 30 ft./sec. in 1 .5 sec. we must ac celerate at the rate of:
The common method of measuring power is known as horsepower. Horsepower is defined as the amount of weight (lbs.) a horse could lift one foot in one second. By experiment it was found that the average horse could lift 550 lb s one foot in one second, consequently:
.
b.
!Second
2 0 ft./sec'
c.
1 ft .
-2-
If we first consider how motion is produced, we can think of the cylinder with the piston rod fully retracted. As oil flows into the blind end of the cylinder, the piston begins moving upward to allow room for the increased oil volume in the cylinder housing. It stands to reason that the faster we fill the cylinder with oil the faster the piston and rod assembly ex tends.
AREAS
It is well known that the area of a square or rectangular sur face is found by multiplying its length times its width dimen sion. If a rectangular table measures 30 inches by 40 inches then it is said to have a surface area of 1 . 200 square inches (in').
40" _
=--____ ____;-- _,
Likewise, to find the area of a circle, you must know its diameter:
0 The oil held inkthe other end ' 1 . Piston Rod returns to tan through i j' thline. 0
The oil pushes the piston upward as it fills the housing.
Area (in)' =
n x
r'
Example: Circle diameter = 10 inches Radius is 1/2 x 10 inches = 5 inches Area =nr' = 3.14 x 5 x 5 = 78.5 in'
VOLUME
The volume of a rectangular milk carton is found by multiplying its length dimension times its width dimension times its height dimension.
-3-
FLOW CALCULATION FOR HYDRAULIC CYLINDERS Re quired Piston Flow Area (in2) x Required Velocity (in/min.) Rate
=
GPM =
AxV 231
Height 1 0"
l
Volume = 78Vz in2 x 10"
=
FLOW RATE
We normally represent flow in hydraulics by the number of gallons that can move into a measuring container in a given amount of time.
FLOW =
Volume Time
or
Gallons Minute
or
min.
in3
To expand on what we first said about flow it is important to realize that the speed or the rate of doing work is dependent on flow rate without regard to pressure. Of course, the size of the actuator must also be taken into account, since for a given amount of flow . larger actuators would move slower than smaller ones. (see page 7).
.J__galtt)n
63 feet
_l..gal-h:ri} lJn.i-mi(e
60 sec
1. 0 ft/sec
If we do nothing more than use Vz" schedule 80 instead of schedule 40 the velocity changes drastically:
-4-
CDa stroke of At
1 GPM
0 0
or a velocity of 1 0ft/min.
0 0
A velocity of 10 ft/min.
5 ft.
'
1 GPM
-5-
W' schedule 80 has a diameter of .546 which relates to a cross sectional area of .2340 in2 It takes 82 feet of schedule 80 pipe to hold a volume of one gallon and to accomplish a 1 GPM flow rate, we have:
.l.-gattOi) 8 2 feet J.-.galt6il x _l..mintlte x .!.Jimrle 6 0 sec 1.37 feet/sec
less can keep up with the innermost stream. This results in flow streams that remain parallel. Laminar flow is a flow with parallel streams, resulting in the least loss of energy due to friction.
In this example a simple change in the schedule of Yz" pipe increases the velocity (and thus the heat loss, because of fric tion) by 37 percent. The following formula can be used to calculate the pressure drop per foot of pipe:
P=
VxF 18,300 n
V = viscosity in SSU F = flow in GPM D = inside diameter of pipe in inches P = pressure drop per foot in PSI
Turbulence, on the other hand, results when too much oil is being forced through a pipe with too small a cross sectional area. Under these conditions, there are big differences in speed between the innermost and outermost flow streams. This results in turbulence in the main flow of oil, where the oil molecules are forced to move in erratical paths, resulting in a high loss of energy.
If the flow rate in GPM and the desired oil velocity in feet per second (feet/sec.) are known the following formula can be used to calculate the inside area required:
Area =
Because available energy levels in different portions of the circuit vary, we recommend the following velocities to keep the energy loss to a small percentage of the total energy available:
Suction Lines Return Lines Working Lines (500 - 3000 PSI) Working Lines (3000 - 5000 PSI)
P=. A
-6-
With consideration to Pascal's Law, if we exert a force over an area of a fluid in a closed container, this pressure is then exerted perpendicular to, and undiminished in all directions,
1" 4"
on every unit area of that container. It is exactly this principle which not only lets us transmit energy through a fluid but at the same time get a multiplication of force. Assuming that we have a closed container of any shape, w1th two movable but sealed pistons, the output piston having a 4 times larger area than the input piston; for every pound input on the small piston we get a 4 pound potential output on the second. Since the pressure in the container is equal in all directions, the input to output force ratio is directly propor tional to the input and output area ratios. It is important to note, however, that to multiply force with a hydraulic system, we must sacrifice speed and distance. You will notice that for every inch of motion of the larger piston, the smaller piston must move 4 inches to displace the same volume of oil. The input work is 1 lb. moving 4 inches, or 4 in.lbs., while the output work is 4 lbs. moving 1 in., or 4 inlbs. Since the input work and output work is the same, we have complied with the fundamental law of physics that says energy can neither be created nor destroyed. The only thing lost is speed for force, or vice versa.
It is the responsibility of any basic hydraulics course to justify the often used myth that hydraulic pumps pump pressure. The only thing a pump does is to create a flow of fluid. Its maximum pressure rating only determines how much resistance to that flow the pump can withstand.
-7-
in the hydraulic cylinder. Since the load exerts a certain amount of force in pounds, and the piston in the cylinder has a certain area in in2 we have force over area or pressure. If the cylinder has a piston area of one square inch, and sup ports a 5000 pound load on a blocked column of fluid, then you can see that by Pascal's Law we have a pressure in the fluid of 5000 PSI. If, instead of a blocked column of fluid, we connect the cylin der to a hydraulic pump, then the 5000 PSI would be transmitted back to the inlet of the pump. For the pump to create a flow, it must be able to withstand this 5000 PSI resistance:
(D This load resists work because it does not want to move. 0 It does this by exerting a \ If we 0 with areplace.the pipe plug "\ pump . .
force of 5 000 lbs. over this area.
I
ORIFICES & PRESSURE Orifices in hydraulic systems are much like doorways in crowded hallways. The higher the flow rate in people/min. or the smaller the doorway, the more crowded it becomes at the entrance. lin2 With hydraulics when oil moues through a restriction (orifice) there is work being done to the oil. In doing this work, pressure is lost because it creates the force required to push the oil through the restriction. For a given orifice, an increase in pressure drop from inlet to outlet is always accompanied by an increase in flow. The pressure drop across an orifice can be affected by three variables (assuming constant viscosity):
when inlet
pressure equals . . .
Orifice 8 4
0 because a
0 becomes higher
than pressure here . . . 3000 PSI
-8-
1. An increase in load pressure at the outlet increases downstream pressure, and assuming inlet pressure remains at relief valve setting, has the effect of decreasing pressure difference from inlet to outlet. This means less flow, so that the system slows down with increased load. 2. An increase in the inlet pressure, by raising the relief valve setting, has the effect of increasing the pressure drop across the orifice. Assuming constant load pressure, the system speeds up. For this reason many think that to adjust speed in a hydraulic system, you adjust system pressure. The higher the number of restrictions a system has the better this method works. This, however. is the most ineffective and highly inef ficient means of trying to adjust speed. 3. By opening and closing the restriction we change the resistance to flow. The lesser the resistance, the less the pressure loss from inlet to outlet. This is the most
efficient way to tune system speed when the system has a fixed displacement pump (see page 10).
1500 PSI
----""":ii:=!I
Zero
When the restriction is wide open there is vir tually no resistance to flow, therefore, no pressure.
As the needle valve is closed, pressure builds up in the system and energy is converted to heat (since no useful work is being done). All the flow is still across the restriction since pressure isn't high enough to open the relief.
-9-
6 HP creates
9 G PM
n
\_
\J
Input 20HP
Input 20 HP
\ \I
When the restriction is closed sufficiently to in crease the inlet pressure to relief valve setting, some of the flow is diverted to tank via the relief valve. Notice that the horsepower which is con verted into heat by the two valves, equals the in put horsepower.
When a load is added to the circuit without chang ing the setting of the needle valve.more flow is diverted to tank over the relief because less flow can be pushed through the needle valve. due to the decrease in pressure drop. If the load is increased, the speed drops even further.
Power
In converting the units of hydraulic power: Flow (GPM) x Pressure (PSI) Theoretical Hydraulic Horsepower= - -'- ----' ---'----'1714
----
- 10 -
T = force x radius
Notice that the units of torque are written in lb-ft or lb-in. whereas the units of work (described earlier) are written in reverse, as ft-lbs or in-lbs. This is done purposely so as not to confuse two totally different concepts. The torque of a hydraulic motor is synonymous to the thrust of a hydraulic cylinder. Consequently both a torque and a force can exist without causing motion (doing work). Likewise, the pressure at the inlet of the hydraulic motor only builds to a sufficient level to cause a torque which will produce motion. In other words, the torque load is resisting rotary motion. thus deter mining the torque produced by the hydraulic motor. With hydraulic cylinders, we said the pressure level was determined by the load, and the square inch area of the piston in the cylinder. Likewise, with hydraulic motors. the pressure level is determined by the torque load, and the size of the hydraulic motor. The size of a hydraulic motor is determined by its geometric displacement in in3/rev. The displacement is the amount of oil the motor consumes in making one complete revolution. As with hydraulic cylinders, a larger motor will produce more torque at a given pressure level than will a smaller one. The following formulas are necessary for relating torque pressure and displacement:
2nT P= D or T = PxD 2n
Where:
D displacement in in' T =Torque in I b-ins P = Pressure in PSI TT = 3 . 14
=
Sometimes it is necessary to determine the power level of the rotary motion. If the torque for a given hydraulic motor is determined by pressure, and the speed (RPM) of the same motor is determined by the iiow rare. we now know the horsepower level of the motor. With reference to the above diagram, if you weighed 1 lbs. 00 and were sitting two feet from the balancing point (fulcrum) then you created a torque capability of 100 pounds x 2 ft or 200 lb-ft which tends to cause a clockwise rotation around the fulcrum. Now, if your girlfriend weighed only 80 lbs. then she had to sit 2Y2 feet from the fulcrum (80 lbs x 2Y2 ft 200 lb.-ft) in order to obtain an equal balancing torque in the counterclockwise direction.
=
HP output =
Flow l
;I x[et)
Consequently, torque is equal to the load multiplied by its distance from the center of rotation.
e t Enters into the equation because hydraulic motors by nature are not 100% efficient. The total efficiency (e t) is the product of the motor's mechanical efficiency (e m ) (losses because of friction and inertia) and its volumetric efficiency (ev). The volumetric efficiency is determined by the per centage of the inlet oil leaked to the case drain. and/or to the low pressure outlet of the motor. Basically. the following facts hold true for most hydraulic motors:
- 11 -
WI TH HYDRAULIC MOTORS: -Volumetric efficiency is higher at low pressures and falls off as you approach the maximum pressure capability of the motor. -Volumetric efficiency is highest at maximum speed. This is true because lea k age is mostly pressure dependent and consequently is a small percentage of the larger flow rate sup plied at higher speeds. -Mechanical efficiency is higher at lower speeds because of less friction. -Mechanical efficiency is higher at higher pressure because of better lubrication. -Dependent on motor design the starting torque may be as low as 60% of the motors running torque capabilities. The starting torque capabilities must always be considered when the motor must start under load.
In designing the actual machinery it will be helpful to know the following mechanical relationships between HP, Torque. and Speed (RPM).
100 ft-lb x 1000 RPM = Tout x 500 RPM Tout 100 x 000 = 200 I b - ft 50
Torque in I b-ins
Torque in lb-ft
Load 1
---- ' -
( Lengths of Pipe
'
-...
;:") f
" Increased /
Pressure
'he formulas as listed in the chart are theoretical values vithout consideration of mechanical inefficiencies. Of par icular interest the formulas clearly show that with a constant 1put torque the horsepower levels vary directly proportional o the speed. Likewise. for constant horsepower installations he speed must drop with increasing torque. lhese formulas are also useful in calculating gear box ap >lication. That is. assuming we get out of the gear box the .ame horsepower we put in (100% efficiency) we can write he following formula:
It should be noted that when the system becomes static, pressure will equalize at relief valve setting (in accordance with Pascal's Law).
PARALLEL CIRCUITS
Fluid flows through the path of least resistance when there is more than one possible flow path in the system. In the following circuit. the 1000 pound load will move first, because it requires the least amount of force. Pressure will build up only to the point where the 1000 pound load begins to move. The system will reach no higher pressure until the cylinder reaches the end of its stroke, and no more oil can flow into that cylinder. Then, the system becomes static in staneously, as the pressure builds up the 5000 PSI to move the 5000 pound load.
- 12 -
50001b. Load Equal Size Cylinder with 1 square inch piston areas
Hydraulic -= --Pump
HEAD PRESSURE
Atmosphere
Weight
7 341bs.
The earth has a diameter of 7920 miles or a radius of 3960 miles. Consequently, its surface area is: A = 4rrr' = 197,060,790 square miles or 791 ,098,480,000 , 000 , 000 sq. inches Static head pressure is a force over an area created by the weight of the fluid itself. If we were to weigh a one gallon volume of a typical hydraulic oil, we would find that it weighs approximately 7% lbs. Likewise, a container which holds one gallon of fluid at a one foot depth, has a bottom with a surface area of 19\1.1 square inches (approximately 4.8" x 4"). Consequently, we have a pressure on the bottom of the con tainer of 7% lbs. over 19\1.1 square inches or: Our Atmosphere= 7 _91 x 1 017 x 1 4_5 weighs lbs.
- 13 -
As with any object immersed in a fluid {either air or oil), we live in an atmosphere which exerts 14.7 pounds on every square inch of our body. Because we breathe. the pressure is also exposed internally so we don't feel the effect of this pressure. We do. however. feel the effects of static head pressure when we dive into the deep end of a swimming pool. This happens because we can't breath in the higher pressure water to equalize internal and external forces. Un der normal conditions . the forces created by head pressure are equal in all directions. and cancel the effects of each other.
BAROMETER
A barometer is a device used to measure the effects of the static head pressure of our atmosphere. Barometers measure the absolute pressure of the atmosphere and are usually calibrated in inches of mercury. A mercury barometer can be made by immersing a long test tube in a pool of liquid mercury. When all air is expelled, the tube is turned vertically with the open end still suspended in the poo l . In doing this. the mercury drops in the tube, leaving a near perfect vacuum in the top of the tube. The mercury is simply the media separating the atmospheric pressure from the vacuum. The gauge is read by measuring how high the ambient pressure pushes the mercury up the tube. Hence. the calibration in inches of mercury. Water could also be used in place of mer cury. However, 29.92 inches of mercury is equivalent to 34 feet of water which would require an extremely long test tube.
VACUUM
A perfect vacuum is a volume which is totally evacuated. In a perfect vacuum all air molecules are removed. Although a perfect vacuum is virtually impossible to achieve, partial vacuums can be used so that the static head pressure of our atmosphere can exert a force to do work. In comparison with a mechanical system. a vacuum and at mospheric pressure work together much like two people pushing on opposite sides of a door:
29.92 inches at sea level Atmospheric Pressure balances the weight of mercury.
0
t p-o-
Vacuum
Push----
----
Push
Therefore:
Absolute Pressure
- 14 -
Pumps available today, can normally create a vacuum con dition equivalent to six inches of mercury (3 PSI under at mospheric pressure . or 1 1 PSI absolute). Since 6 in-Hg is equivalent to 7.4 feet of oil (29.92 in-Hg = 37 ft-oil) the height of the inlet above the oil has a definite limit. Although 7.4 feet would be the absolute maximum height of the inlet above the oil level, we must reduce this dimension even fur ther when considering the pressure drop encountered in moving oil through the suction lines and strainers. Let us, for a minute, consider a 15 GPM pump capable of "lifting" 6 in-Hg that has a schedule 40 1 1;4'' pipe 48" long. First, schedule 40 1 1;4'' pipe has an inside diameter of 1 .38 inches. I f we were to use this pump with Mobil DTE 24 (a 150 ssu fluid) at 100F. we would have to calculate the pressure drop under the worst cold start up conditions. A ssuming the pump would have to start in a 300F ambient this same fluid would display a viscosity of approximately 1200 sus. Thus, we can calculate the pressure drop per foot as follows:
Vxf .6 P ft - 18300 o
_
18300 (1.38)4
1200 x 15
= .27 PSI/ft
For a 4 foot straight in suction line (not considering suction strainers or elbows) we would have an overall drop of:
3.4 feet
...
Although the suction characteristics vary from pump to pump, and must be checked for each application, a good rule of thumb is:
A hydraulic pump with adequately sized inlet pipe and strainer should never be mounted higher than 3 feet above the oil level.
- 15 -
height
Under these conditions ,strainer. suction line, and fittings still subtract from the total pressure available at the inlet under a flow condition . Therefore. the rotal pressure available is considerably higher because we are starting at a level above dtmospheric pressure.
1.01325 x 10 N/m2
In the metric system ,force is represented in newtons (N). and area is represented in square meters. In converting the units from newtons to pounds and square meters to square inches, we find that:
By definition. the atmosphere uses a vacuum as its base. so that pressure ratings in atmospheres are absolute pressures.
3.
The Bar is another system of measuring pressure in the metric system of units. The bar has been defined as the piessure equal to one million dynes force over an area of one square centimeter. In converting 1 million dynes force to pounds force, and one square centimeter to square inches, we come up with the conversion factor of:
3 1 5 bar gauge.
- 16 -
4.
Pascals are units of pressure measurement and have been defined as one newton per square meter or:
1 Pa = N/m2
Since this unit of measurement is quite small in 10 bar or 6897 Pa = 1 PSI ) this magnitude (1 pa method of pressure measurement is usually rep resented in kpa (kilo pascals). Hence:
=
Heat is generated when there is a drop in pressure as oil flows: - through pipes & fittings - through flow controls - over relief valves - across counter balance valves - internal leak age of pumps and motors
If we know the flow rate (GPM). and the loss in pressure (PSI). across any device which does not produce mechanical motion. we can calculate the heat generated. Since the hydraulic system either does work . or creates heat. the units of heat may be expressed in any units of work or energy. However, we more often see heat expressed in BTU (British Thermal Units) than we do in ft-lbs of heat.
5501!.:!2_ sec
.707 BTU 550 ft-lbs x 1 BTU 1 HP = sec 778 ft-lbs sec OR 707 BTU x 60 sec 42.4 BTU x 60 min 2545 BTU hr 1 hr min 1 min sec
.
Therefore ,
1 HP
2545 BTU hr
To make this more useful for those calculating the heat generated by a hydraulic system,we can write the following expression :
Unfortunately, the newcomer to hydraulics , until he gets burnt, so to speak, with his first system, really has no way of realizing just how efficient a heater a hydraulic system can be. We must remember that flow multiplied by pressure is the hydraulic equivalent to horsepower. Wherever we have flow from point A to point B in a system ,with any loss in pressure, there is an equivalent loss of horsepower between points A and B. Since, a pressure loss occurs without doing useful work (causing mechanical motion), a percentage of the input horsepower is wasted. This wasted horsepower shows up in the hydraulic system in the form of heat. Of course, the higher the pressure loss and the higher the flow , the more we waste horsepower. Some typical examples ithout doing useful work are sum where pressure is lost w marized as follows:
B.J = 1.5
GPM X PSI
where PSI is the loss in pressure for a given flow rate which does no useful work. Let us now consider the following hydraulic lift circuit as an example: Lift circuit parameters: Constant load variation, Duty cycle 50% full speed, 50% half speed , Maximum pump flow 20 GPM. Maximum pressure 3000 PSI
- 17 -
For 1/2 speed we have only to supply 1/2 the flow, or 1 0 GPM,at 1/2 the pressure , or 1500 PSI, to do the required work. With a fixed displacement pump, this means that the other 50 percent of the flow has to go over the relief valve to tank at the full 3000 PSI set pressure. Consequently, we develop a significant amount of heat:
lh speed position of
To Load
This creates:
22,500 BTU/hr
67,500 BTU hr
67,500 BTU/hr x
which is the same value we get by comparing input power and horsepower required to do useful work in the following chart , at the top of the next page. If we assume that at full speed and full load the horsepower required for upward motion is: Let us now find out how much heat we really generate if we were to run the lift up and down for 1 hour with a 50% load, at 50% speed.
HP
35 H P
UP = DOWN =
67 89
5 BTU x .5 hr
Since all the flow is required for full speed , and all the pressure is required to overcome the load, the relief valve stays closed and no heat is created. ( Assuming a totally efficient system with no pressure drop between the pump and the load). Let us now look at the 1/2 speed, 1/2 load - up condition.
0 BTU x .5 hr
- 18 -
DIRECTION OF CYLINDER
SPEED
LOAD
UP
FULL FULL FULL HALF HALF HALF FULL FULL FULL HALF HALF HALF
FULL HALF NONE FULL HALF NONE FULL HALF NONE FULL HALF NONE
DOWN
0' '
system could maintain a 7(J'F room temperature in an average 3 bedroom home on a (J' F winterday.
6. Add the BTU figures of step 5 and determine the average heat generated during a one hour period.
Referring to our circuit example, a 20 GPM pump in a good industrial hydraulic system would, more than likely, be mounted on a 60 gallon reservoir. Assuming that the 78,288 BTU/hr would be total trans ferred to the 60 gallons of oil , and that the maximum recommended temperature for mineral oil is approximately 140"F, you can readily see that the system would severely overheat in a matter of minutes.
HEAT DISSIPATION
Hydraulic reservoirs, pipes. hoses , and components radiate heat into the ambient air. Assuming that the heat generation rate from your system is low,it is possible that there is enough radiating surface to maintain stable oil temperature within the prescribed limits. Remember, for maximum oil life, the system should never be allowed to operate above 140"F. With free air convection ,a steel surface can radiate heat in an amount that can be calculated by using the following formula:
BTU/hr
where : BTU/hr = Area = T
2 . 5 4 x area x .6.T
the heat radiated . the surface area of the steel that is in contact with the oil in square feet. Desired oil temperature minus ambient air temperature in degrees Fahrenheit.
The problem with using the formula accurately is estimating the steel surface area that is in contact with the oil. Also, since the top plate of the reservoir has an air space between it and the oil, and the bottom is less efficient in its ability to radiate heat than the sides (remember heat rises), we can only estimate the radiation ability for a given system. A good guideline is to use only the vertical surface areas of the reser voir in your calculations. The heat radiated from piping, com-
- 19 -
ponents. and the top and bottom surface areas of the reser voir allows a safety factor for minor changes in ambient tern peratures. and inefficiencies overlooked in your estimation of heat generation. Once we know the rate of heat generation. and the ap proximate radiating ability of our reservoir. we can determine the extra cooling ability we will have to provide with either an air/oil ,or water/oi l. heat exchanger. Getting back to our example. a 60 gallon reservoir which is 3 ft. long and 2 feet wide holds 60 gallons at a depth of 16 inches (1 1/3 ft.). Therefore .the vertical surface area is 13 square feet. If the system is operating in an ambient which does not exceed 80F we have:
BTU/hr
= 2 . 54 x 13 x (140 - 80)
1981 BTU hr
= 1981 BTU/hr
78,288 BTU hr
76,307 BTU/hr
viscosity levels given here are only average values. it is im portant that you check the exact recommendations for the pump and motors you are using.
The second determining factor on the minimum cold start-up temperature of your system is the type of oil used. The two oil ratings you must concern yourself with at this point is the overall viscosity at operating temperature, and its viscosity index.
when operating at 50% speed and load. In actual practice . we would not want to design a system which creates this much heat. We only intended to show how a seemingly innocent circuit design can be nothing but a heat problem.
Before going to a heat exchanger manufacturer you will need the following information: 1. The heat in BTU/hr you wish to dissipate. 2. The amount of oil flow you will be passing through the heat exchanger. 3. The flow rate of water (GPM) you have available (assuming you are selecting a water/oil model).
4. The inlet temperature of the water (or the am bient air temperature for air/oil models) in F. In actual application. you will need to know the pressure rating of the selected model. and you probably will be in teres ted in the pressure drop for the flow rate you prescribed. In plumbing the unit, follow the recommendations of the manufacturer. but remember that it will do no good at all if
0 is uniformly
heated to l00F. Heating Element
0 1t then is allowed to
pass through a standard orifice.
hot oil can return to the reservoir without passing through the heat exchanger. Also. if you are piping case drain lines of
pumps and motors through the heat exchanger. the model selected must have a low pressure drop for the total com bined return flow. since most case drains cannot exceed 15
PSIG.
- 20 -
A fluid's viscosity is a measurement of its resistance to flow. For the purposes of this chapter we need only concern our selves with the most practical way of measuring relative viscosity; that being measuring the SUS viscosity of the fluid. Relative viscosity is nothing more than the measurement of time necessary for passing a given amount of the selected fluid through a standard orifice at a prescribed temperature. The SUS (saybolt universal second), a name derived from the type of viscometer used, is the time measurement of fluid passing through an orifice (u sually at 100F). Since thicker fluids will take more time to flow through this orifice than thinner ones, thicker fluids have the higher SUS number.
hydraulic pump. We now wish to point out the temperature limits for a 50 VI. 95 VI and a 150 VI oil. all of which display a 150 SUS at 1 00F viscosity.
95 VI 5F
1 50 VI 0F
Optimum 85 - 130F 80 - 135F 70 - l40F Temp. Range Max. Operating 1 5 5F 160F 175F
VISCOSITY INDEX
It's a well known fact that heated viscous fluids become thinner. With mineral oils, the viscosity varies drastically with relatively small temperature changes. The resistance of an oil to change viscosity with a change in temperature is denoted by an arbitrary measurement called the viscosity index. A fluid which is quite thick when cold and very thin when hot, has a low resistance to viscosity change, thus it is assigned a low viscosity index number. A fluid that has a relatively stable viscosity for a given change in temperature has a high resistance to a change in its viscosity, and would be given a high viscosity index number. High VI oils have a Viscosity In dex number over 80, medium VI fluids between 40 and 80, while low Viscosity Index fluids are given a number less than 40. The graph shows a comparison of fluids with both high and low V.I. numbers.
Tmp.
Although the viscosity is acceptable, the maximum operating temperature should be held to 140F, so that maximum oil life can be main tained. Also, most industrial hydraulic pumps,for mechanical reasons,are not allowed to operate above 160F.
If, in a system,the start-up temperature could allow the oil to approach the maximum viscosity limit of the pump. a provision should be made for heating or pre-heating of the fluid.
.so.ooo iii
:> '!! 10.000
.. 0 z 0 u "' ..
I'
... <
i'..,_
..
"' "'
r''.... :-., .. ..
:> i
:>
200
ISO
120 100
,.
<
60 50
"'
!: ;;; 0 ;;
40
35 20
!I!
so
J I :.r - !j 1 ..
.
'
.j
!d j!l t_
'' l i.
I
-
.1
.-
1.' '. - t
+ ;1
..
MINIMUM VISCOSITY
c !
100
I SO
TEMPERATURE.
1'1
200
IL A
250
..
300
V I -. 95
\:1
so
- 21 -
system only operates in the warm-up mode until satisfactory temperatures have been reached.
PRE-HEATING
If the ambient temperature allows the oil to cool to a point
perature,the higher the temperature difference,and the more heat we radiate to the ambient. To avoid complicated ther modynamic calculations , the total wattage required can be estimated accurately enough , for our purposes , from the following equation :
where the oil viscosity exceeds the limits of the pump, it will be necessary to provide some means of pre-heating the oil. The usual method of pre-heating is to install one or more im mersion type electric heating elements in the lower part of the reservoir. Immersion heaters are normally controlled with a built-in thermostatic switch to avoid the possibility of ac cidental overheating of the oil.
The above formula estimates the kilowatts (kw) required to achieve the desired temperature in a given amount of time. The time allotted for heating should be at least 1 hour. however. if possible ,3 hours is preferred : The following conversion factors may be helpful in your calculations:
1 HP=
Thermostat
-J t
we:
eating Element
NPT Thread
254S BTU hr
CONCLUSION
In this chapter we have attempted to cover the physical elements which must be understood to properly apply hydraulics. It will be impor1ant for you to gain a basic un derstanding of the following terms:
plate ratings.
Example : A 480 volt. 4 kw heater with a heat density of 20 watts/in '. produces 1 kw at a heat density of 5 watts per square inch when operated on 240 volts.
Energy Force Torque Motion Velocity Load Resistance Inertia Acceleration Power Pressure Orifices and Pressure Drop Flow Series and Parallel Circuits Head Pressure Vacuum Absolute Pressure Gauge Pressure Viscosity Viscosity Index Heat
With a solid foundation of the concepts presented in this chapter. it will be relatively simple to understand the operation and proper application of the various hydraulic components. which will be covered, in detail, in subsequent chapters.
- 22 -
TORQUE:
lbs D = Distance in inches or feet units are expressed in (in lbs) or (It lbs)
F = force in
Ma
_ -
we1 ht (lb s ) g .
32_2 It/sec'
a = acceleration = It/sec'
LINEA R A CCELERA TION: a=v T
T = H P x 63025 7 RPM H P = T x RPM 7 63025 T = torque in (lb - in) T = H P x 5 2 5 2 7 RPM HP = T x RPM 7 5 2 5 2 T = torque in (lb - ft)
HEA T:
1
4 HP = 42. BTU
min
2 5 4 5 BTU
hr.
HORSEPO WER:
l HP =
r = radius in (in)
IT =
3.14
- 23 -
HYDRAULIC HORSEPOWER:
a) H PT
H P 0 1
G P M x PSI 1714 x (e t )
GPM
0.3208 A
HEA T GENERATION:
BTU/hr
=
1.5 x G P M x PSI
REQUIRED PRESSURE:
a) Cylinders:
F PSI = or F A
PSI x A
VxF 18300 o
KW= V x 6T SOO T 6T
T KW
v
P = pressure drop per foot V = viscosity in SUS D = inside diameter (in) F = flow in GPM
Tank capacity gallons (desired ambient) temperature in degrees Fahrenheit Time in hours Input heat required.
- 24 -
f"1k?
= 48 inches H: LENGT 1 inch = 2 5 . 4 mm 1 meter = 39.37 inches 1 micron = .000039 inches POWER: 1 H P = 1 .0 1 4 metric HP 1 H P = . 7 4 5 7 KW 1 H P =42.4 BTU/min 1 HP = 2545 BTU/Hr. 1 HP = 5 50 ft l b/sec FORCE: 1 N (newton) = 0.2248 1bs.
VOLUME: 1 gallon = 2 3 1 in.J 1 gallon = 3. 785 liters 1 1iter = 6 1 .02 in.J PRESSURE: 1 bar = 1 4 . 5 PSI 1 atmosphere = 1 4.7 PSI 1 kg/em' = 14 .2 PSI 1 inhg = . 49 1 2 PSI 1 bar = 1 00 kpa 1 PSI = 6.89 kpa SPEED: 1 ft/sec = 0.3048 M/sec
USEFUL DATA
HORSEPO WER INPUT TO PUMP : 1 HP = 1 GPM at 1500 PSI ENTRAINED AIR : At room temperature standard hydraulic oil contains 8 9% air by volume.
-
OIL COMPRESSIBILITY: 2 For every 1000 PSI there is a reduction in oil volume of 1/ % . OIL TEMPERA TURE : Oil temperature should never be allowed to exceed 140F. PUMP MOUNTING : Hydraulic pumps should never be mounted higher than 3 ft above the minimum oil level in the reservoir. PUMP & MOTOR CASE DRAINS : Most pump or motor case drains cannot exceed 1 5 PSIG. VISCOSITY A T S TART-UP : Maximum viscosity at start-up ranges from 1000 for inline piston pumps to 4000 SUS for gear and vane equipment.
FLOW VELOCITIES : Suction Lines 2-4 ft/sec Return lines 10-15 ft/sec Working lines (500 to 3000 PSI) 15 to 20 ft/sec Working lines (3000 to 5000 PSI) 20 to 30 ft/sec HEAD PRESSURE : Oil creates a pressure due to its weight of 0.4 PSI per foot of depth.
- 25 -
CHAPTER2
The sheer existence of the world in which we live, depends on the interaction and the balancing of forces. From baby's first breath, to the complex network of forces holding our solar system together, forces are constantly acting and re acting to keep energy in equilibrium. From the beginning of time, man's unyielding quest to understand and to manipulate the interdction of forces has made our world a better place. In Chapter 1. we have shown how pressure relates to force in a hydraulic system. This chapter will be devoted to an understanding of various pressure controls. and of how we can manipulate forces through the use of hydraulics. In general, there are five basic functions which can be per formed by pressure control valves, namely:
Relief Values: First, limit the maximum system pressure
which. in tum, protects system components, piping and tubing; and second, limit the maximum output force of the hydraulic system.
Reducing Values: are used to limit a certain branch of the hydraulic circuit to a pressure lower than the relief valve setting for the rest of the system. By reducing pressure in the secondary circuit, we can independently limit the out put force to that in the primary circuit. Sequence Values: are used to assure that one operation
has been completed before another function is performed. They operate by isolating the secondary circuit from the primary circuit until the set pressure is achieved. The flow of fluid is then sequenced from the first to the second cir cuit. Primary pressure must be maintained for the secon dary function to be performed. Sequence valves establish
an order for the interaction of forces. Counterbalance, ouercenter or brake values: are a broad range of pressure valves which control a load induced pressure to hold and control the motion of a load. This group of valves provides balancing forces which prevent the load from running away because of its own weight or because of inertia. Unloading Values: are usually used in circuits with two or more pumps or in circuits incorporating accumulators. The valve operates by sensing pressure in the system downstream of a check valve. Once a certain pressure level is obtained, the unloading valve unloads its pumps to tank. The check valve isolates the unloaded pump from the rest of the system. System pressure is then main tained by the accumulator or by a smaller volume higher pressure pump.
To balance this force, we use a spring which can be com pressed by some adjustable mechanical means. Com pression springs exert a force proportional to the amount they are compressed. Depending on the stiffness of the spring, the increase in force can be very high per inch of com pression, or it can be very low. For any given spring, a numerical value is assigned which indicates the spring stiff ness. This value is called the spring constant and has the units ( lbs / in). Consequently,
- 27 -
energy input. ince we-want to limit the energy source, the inlet of the pressure relief is usually piped into the hydraulic circuit as close to the outlet of the pump as possible. The valve is piped in parallel to the pump, which gives the output of the pump two possible flow paths, either to the system or over the relief, depending on which is the path of least resistance. The relief is a normally closed ualue which keeps the flow of fluid in the system until its pressure setting is reached. Once the valve opens and oil flows through it, energy in the pressurized fluid is expelled in the form of heat. Pressureless fluid from the relief valve's outlet is then returned to the reser voir through the tank port connection.
(D A
(D The inlet
To System
I \_']_I
one-hundred pound force, exerted on one square inch, develops 100 lbs. force on every square inch of the container.
0 The
0 However,
if the ball also has a one square inch area exposed to the fluid, and the spring only exerts a force of 50 lbs . . . .
valve being nor mally closed, keeps the flow of fluid in the system until the pressure setting has been reached.
50 PSI, because the ball will be pushed away from the end of the pipe, allowing the oil to escape.
Port reliefs are piped into the hydraulic system at the ac tuator the same way main system reliefs are piped into the
- 28 -
Make-Up Check
Crossport Reliefs
From Pump
system at the pump. Any pressure overload in the service line to which they are connected is simply relieved to tank at valve setting. In some applications. other circuit precautions must be taken to prevent cavitation in the low pressure side of the actuator. As shown in the example. a make-up check allows the actuator to draw oil from the reservoir as the piston is displaced downward. A second way of preventing cavitation in the actuator is sim ply to relieve its outlet port to its inlet. During the overrunning load condition. the actuator actually becomes a pump, drawing oil into its inlet and pumping pressurized fluid out of its outlet. A crossport relief value simply adds resistance to flow as it short circuits the outlet and inlet of the actuator. Although this works satisfactorily only with actuators which have equal displacements in both directions of operation (double rod cylinders, motors. and rotary actuators). cross port reliefs are almost mandatory when the rotary motion of a hydraulic motor is blocked by a closed center directional control. In selecting a valve to be used as a port or crossport relief. choose one which responds quickly and has little or no leakage when seated. Reliefs used in these applications should be set at least 150 PSI higher than maximum load in duced pressure. This assures that the relief will not influence normal operation of the system. while. at the same time. it will provide relief protection the moment pressure rises above that induced by the load. One last precaution for
crossport applications: a relief must be chosen which can withstand full system pressure on its tank port. By studying the previous example. you can see that under normal system conditions the tank port is exposed to full load induced pressure.
TERMS
In discussions involving relief valves. the following terms are used to describe their operating characteristics. A basic un derstanding of these terms is essential in understanding the features of various relief valve designs.
Full Flow Pressure is the pressure needed to pass all of the output flow of the pump through the relief. Pressure Override is the difference between full flow pressure
and cracking pressure for any particular valve. Pressure override is higher than cracking pressure for several reasons. First. the valve itself is a restriction (orifice). and the higher the flow across an orifice. the higher the pressure drop. Since
- 29 -
rne outlet ot the relief is exposed to atmospheric pressure. the increase in pressure drop. with increased flow. is solely an increase in pressure at the valve's inlet. Second. in any pressure control the ball. poppet. or spool is directly supported by a spring. If the spring tension is ad justed so that the valve just "cracks" at. say 3000 PSI. then the poppet moves just far enough from the seat to let the first drops of oil out of the system at this pressure. When a bigger opening is required to pass more of the output of the pump. the poppet must be moved further from its seat. In moving the poppet. the spring must be compressed more. which in tum increases spring force and hydraulic system pressure. A less obvious reason for pressure override is that a loss of effective area occurs as the poppet moves away from the seat. When the relief is closed. the effective area can be calculated by using the full inside diameter of the seat. However. when the poppet moves away from the seat. the theoretical point of pressure loss occurs along the per pendicular line between the poppet and the seat. As shown in the diagram, this can cause a substantial reduction in the effective area.
Hysteresis is pressure variation between pressure increase and pressure decrease as related to flow. Reseat Pressure is the pressure at which the valve closes again. Stability is the fluctuation in pressure at any given setting. Overshoot is the pressure rise above set pressure during the short time period when the valve is responding.
HOW IMPORTANT ARE THE VALVE'S PRESSURE OVERRIDE CHARACTERISTICS? In general. hysteresis. reseal pressure. and overshoot are values which are not detectable on a pressure gauge. Minor instability also has little influence on the satisfactory operation of the system. Therefore. unless you are looking for very precise control. you need not be too concerned with those items which need electronic equipment to detect. But.
Poppet
L
Theoretical Point Where Pressure Is Lost
- 30 -
\.f\
Overshoot
Reseat Pressure
Stability
1 f
50
TYPICAL PRESSURE vs. FLOW CHARACTERISTICS
1 00
150
how does pressure override affect the operation of a system? Let us now consider a 10 GPM pump operating with a relief valve which displays a 500 PSI override between cracking and full flow pressure. Although override characteristics are not perfectly linear. our example is intended only to show the effect of pressure override on the system. For convenience sake. we will eliminate all circuitry except for the pump. relief valve. cylinder and load.
First. if we are looking for maximum efficiency. we would want to set the relief valve at 1000 PSI since this is all the pressure that is needed to obta1n the required force. We lind. however. that when the cylinder bottoms out. our pump flow is relieved to tank at 1500 PSI rather than at the initial setting of lOOO PSI. Although all flow across a relief turns energy into heat. a 500 PSI override increases our energy loss by 33%. or a net increase of 3'12hp for this particular example.
1000
lbs.
-
GPM
10
-==---
-----
LIJ 0:: 0.
500
5
FLOW(GPM)
10
Second. if the cylinder encounters a slight increase in load. say 250 pounds. ideally. we would want our system to stall since it was our original intent to limit the output force to 1000 lbs. In actual practice. however. we lind that the
- 31 -
system will do the work at approximately half speed, while wasting the other 50% of our power input in the form of heat. as oil flows across the relief. When the load is mechanically stalled, our pressure again rises to 1500 PSI creating 500 lbs. more thrust than originally intended.
DIRECT ACTING RELIEF S Direct acting (operated) reliefs are valves i n which the spring force directly opposes the hydraulic pressure force. It stands to reason that a given spring constant can only be optimum for a given pressure level. Therefore, most direct operated valves have several spring options to cover the different operating pressure ranges. The spring constant has varying effects on the valve's operating characteristics. which are more or less related directly to the actual valve design. Under the worst conditions . the relief can have a very narrow ad justability range due to the spring constant's influence on pressure versus flow characteristics, hysteresis. and stability. With other designs, the only real effect is on sensitivity of ad justment. In the family of direct operated valves, several designs are offered by various manufacturers. We now wish to study the intended use and operation of the most popular designs.
(i; Q. 3000
0 1.5
FLOW (GPM)
3.0
Typical Pressure vs. Flow Characteristics for a Simple Poppet or Ball Style Relief. GUIDED POPPET DESIGN
Pressure Port
Tank Port
By guiding the poppet with a close tolerance fit, direct operated reliefs can technically be made to pass considerably more fluid without the instability problems associated with unguided models. A problem arises in mechanically guiding the poppet because the poppet guide blocks the free flow of fluid to tank once the valve opens. To overcome this problem, with most designs, the oil flows to tank through cross drillings in the poppet. This. of course, is a restriction which limits the maximum flow capacity of the valve. Although stability and noise are improved. this design still
- 32 -
has a problem in overcoming pressure override with in creased flow. In general. precautions must be taken not to exceed the recommended flow. since high velocities through the cross drillings in the poppet can cause a severe whistle. Although this design is basically intended for use as a remote pilot control. it can also be used as a main system relief in low powered systems. Before selecting this design. however. you should consider the effects pressure override will have on satisfactory system operations.
Pressure Port
Button
Port
Tank Port
Pressure Port
system pressure. The only effective area for system pressure to act upon is the ring area. which has an ID of the seat. and the OD of the sliding fit of the poppet guide. As you can see in the figure. the area can be easily changed by proper pop pet design to optimize the required spring force to balance the smaller hydraulic force. The only major problem with most differential piston designs is that once they open. the nose of the poppet enters the pressurized flow stream. A drastic increase in the effective area can occur. and the spring can no longer close the valve. To overcome this problem. the nose of the poppet has a but ton machined on it. which disturbs the flow path to the tank. This captures the velocity head of the fluid. which assists in closing the valve. Unfortunately. the poppet nose restricts the effective flow area to tank. This orificing can have a detrimental effect on the pressure override characteristics of the valve. Nevertheless. the advantages offered by the dif ferential piston are in some way incorporated in most high pressure. high flow. direct operated designs.
DIFFERENTIAL PISTON
We said before that the poppet area exposed to system pressure creates a force which is opposed by a spring. If we were able to design a valve in which the exposed poppet area was only a small percentage of the final open flow area. we could have a direct operated relief capable of handling larger flows with a relatively lighter spring than a basic poppet design. This is exactly the principle used in the differential piston design. The lighter spring has a lower spring constant. Hence. pressure override due to length of compression can be reduced. You will notice in the cross-sectional illustration. that by locating the pressure port on the same side of the seat as the poppet. the nose of the poppet. which extends through the seat. is exposed to atmospheric tank pressure rather than to
This direct operated relief valve overcomes the typical per formance problems which are normally associated with direct operated designs. As mentioned. the problems include
- 33 -
Q.
Ql .. = II) II) Ql ..
60
(GPM)
Noise
Two basic noise generators in relief valves are poppet and spring chatter and high velocity oil. As mentioned previously, we can mechanically guide the poppet. However, when this is done, the mechanical means incorporated can cause obstructions in the free flow path to tank. By placing a "nose guide" on the high pressure side of the seat. we take the guiding mechanism out of the oil path to tank, allowing a 360 divergent flow path as formed by the wing. High velocity through cross drillings is overcome, eliminating the whistle. Since the poppet is not allowed to move laterally, spring and poppet chatter is also eliminated. Consequently. the relieving function is quiet at any flow rate.
Stability
bad pressure override, noise, instability and a narrow range of adjustability. Let us now consider each problem in dividually, and the design feature incorporated to overcome this problem.
Pressure Override
We know that with direct operated reliefs, pressure override occurs because of increased spring force with additional compression, loss of effective area with poppet opening, and additional pressure drop due to increasing flows. All of these are physical facts which exist, and, therefore, must be dealt with to give good performance specification. With this guided poppet design, a wing is incorporated on the poppet just above the seat. The advantage of the wing is that a hydrodynamic lifting force, similar to the aerodynamic force which lifts an airplane wing, helps open the poppet after cracking pressure has been reached. The wing area and shape can be optimized so that the valve uses the kinetic energy, or momentum of the fluid at high velocity, to coun teract exactly the increased spring force and the loss of area. This results in a perfectly flat pressure vs. flow curve.
If you ever tried to hold your thumb over the stream of water coming from the end of a garden hose, you can understand how erratic the poppet position can be in the stream of oil. Each lateral or vertical motion of the poppet, no matter how small, compresses or relaxes the spring. This rapid changing of spring position shows up in instability on the pressure gauge. Guiding the poppet eliminates the possibility of lateral movement and helps the stability of the relief. However, we must also concern ourselves with erratic axial movement. The nose guide not only guides the poppet, but also serves as a shock absorber. System pressure fills the can in which the nose guide rides. Small metering notches on the guiding lands restricts the oil transfer from one side of the land to the other. Since the oil must transfer for poppet motion to occur, erratic axial motion of the poppet is dampened.
Adjustability Range
Although the guided poppet with dynamic assist does not conform to the basic design of differential piston relief
- 34 -
valves. you can see from the diagram that a hydrostatic balancing force exists which greatly reduces the effective area which is exposed to pressure. Since system pressure works only on a small area. the spring can be much lighter than that needed to balance the force created by the full area of the poppet. A lighter spring means fewer pounds per inch compression (spring constant k). and. therefore. a larger adjustability range. In actual practice. the higher pressure relief valves can be adjusted quite low without adversely effecting perfrxmance. A 3000 PSI spring can easily be adjusted from 300 to 400 PSI with only an ex peeled loss of adjustment accuracy.
SYMBOLS
The direct acting relief valve is represented by a square. The pressure sensing line (pilot line) is represented by the dash line. and is directly opposed by the spring force . The arrow position shows that the valve remains closed until the pressure force overcomes the spring force and pushes the arrow over so that the flow is directed to tank.
Large flow passage to tank w ith short poppet stroke. ---Arrow indicates adjustable spring force.
The arrow sho w s the Tank Port valve is closed until pressure exceeds the spring and moves the reaction force on poppet; thus, net area is reduced. Oil serves to dampen axial pop pet movement. arrow to connect the pressure to tank.
;;t:=":":'!=.::s::t
Cold rolling process provides a mechanical stroke limit on poppet; thus, over stress of the spring is prevented.
The pilot operated relief performs the same function as the direct operated design in that it serves to protect the system components from over pressure, and it limits the maximum outpurforce. This model, however. offers advantages in both versatility and performance which make it more desirable than direct operated valves. As already discussed. direct operated valves are limited in their capability to handle large flows at high pressures. Although some designs are more capable than others, the pilot operated design is really the only way to relieve flows of more than 75 GPM. The major disadvantage is that large
- 35 -
valves have larger poppet areas exposed to system pressure. This larger area multiplied by high pressure creates a need for an undesirably large spring. For this reason, pilot operated valves use the principle of the "hydraulic level" to multiply the force of a smaller spring.
of 10 square inches we have 10,000 lbs. force keeping the poppet closed.
8 If this spring
Large poppet area allows a big opening to tank when the valve opens
1 square inch . . . spring can be much smaller than the spring that would be needed to exert a 10,000 lbs. force on the big poppet ( 1000 PSI x 10 sq . in. = 10,000 lbs.).
junction with a small area exp.osed to system pressure. This makes the pilot valve capable of handling high pressures but very little flow. Should this section have to handle large flows. the stiff spring constant and small seat area would result in objectional pressure override.
- 36 -
Pascal's Law. In reference to the figure, the fluid above and below the main poppet is captive in a closed container. Since the area on top of the main poppet is somewhat larger than that on the bottom. there is a larger closing force than opening force. and the valve remains closed. A light spring force is incorporated above the poppet which not only keeps the valve closed during start-up. but also provides an ad ditional unbalancing force when pressures are equal above and below the poppet. Under these conditions. you can see that the valve is closed no matter whether there is 100 PSI or 10.000 PSI in the system.
A3
Pilot Relief
the 0 the poppet pressure on both sides. would keep closed against the seat . . (D If this area is slightly larger
equal
than . . .
0 this area, . . . 0since there is a bigger downward force 1 t than upward force. '
Valve body THE DYNAMIC OPENING OF THE RELIEF
B'l adding the high pressure low flow relief to the chamber above the main poppet, we can limit the pressure and thus the closing force. The pressure in the oil above the main poppet is regulated as follows:
Dynamic Condition
When pressure is sufficient to overcome the spring of the high pressure pilot relief, we immediately see a decay in pressure above the main poppet. This establishes a pressure imbalance across the orifice in the pilot circuit which necessitates a flow of oil across that orifice. This flow of oil tries to replenish the oil lost over the piloting relief. However. in trying to reestablish a static condition, this flow causes a pressure differential which is sufficient to open the main pop pet. This, in effect, relieves oil t o tank at the pressure setting
In reference to the diagram. system pressure is exposed to areas Al. A2 and A3. As pressure increases. it increases equally on all areas. As long as area A3 remains closed, there is no flow. and the pilot circuit conforms with the prin ciples of Pascal's Law. Under these conditions. we have a larger closing force than opening force; thus, the valve remains closed. Nevertheless, when pressure over area A3 exceeds the spring force. oil escapes from the previously closed container. which establishes a flow in the pilot circuit.
- 37 -
of the piloting relief. If, on the other hand, system pressure decays. the pilot relief will close. Equal pressure is re established on both sides of the main poppet due to the prin ciples of Pascal's Law. When pressures above and below the main poppet are equal, the main poppet closes because of the larger downward force. Remember. some of the closing force is created by the light spring above the main poppet.
If the main pilot relief is set for the highest possible system pressure. then the small direct operated relief, which can be mounted remotely in the operator's control console, can be used to adjust system pressure to anything lower than that set on the main valve.
piloting.
Since the force on the main poppet is controlled by pressure in the pilot circuit. it is possible to connect other small piloting relief valves in this piloting circuit. The maximum pressure of the main system is governed by the pilot relief with the lowest pressure setting.
Adjustment
determined by the remote relief, because it controls the maximum pressure in the pilot circuit.
System pressure
2000 PSI
- 38 -
When the solenoid valve is in this position, it blocks pressure from tank and the relief valve functions as a standard pilot operated valve.
When the solenoid shifts the directional /c ontrol to this osition , the pilot circuit is connected to tank, which unloads the main relief and allows the oil in the system to flow pressureless to the tank.
Normally closed valves, on the other hand, function in just the opposite manner. When de-energized, the relief functions as a standard pilot operated relief. The system is vented by energizing the solenoid.
In hydraulic circuits, it is more common to find normally open valves than it is to find those which are normally closed .The logic behind this is that a normally open valve is fail-safe in the event of a power failure in the control circuit. If something goes wrong in the control circuit of a normally closed valve. system pressure is at its highest rather than being vented as it would be with a normally opened valve.
Pilot Valve
Main Spool
This type of valve is commonly referred to as a solenoid vented relief. More often than not, the directional control is shifted from the blocked to the open position, or vice versa, by means of a solenoid. For purposes of this chapter, a solenoid is defined as a component which takes an electric current (the same that is used to light an ordinary household light bulb), and transforms that electrical energy into a linear force. This force is then used to change the position of (shifts) the directional control. In talking about solenoid vented relief valves, two terms are often encountered:
- 39 -
helpful in systems in which we must maintain pilot pressure for pilot operated directional controls.or in situations in which it is necessary to push oil through heat exchangers or filters while the system is idling.
As shown in the cross-sectional illustration. the lowest pressure is set on the main valve when we remotely adjust by using the "Y'' port. as opposed to the highest pressure setting on the main valve when using the "X" port. Precaution must be taken in using the "Y" port because there is no inherent safeguard preventing the operator from exceeding the maximum pressure rating of the valve. If. for example. both the pilot valve and the remote adjustment were to have spring settings of 3000 PSI: then the main relief would relieve at 6000 PSI. which is in excess of its pressure rating. Nevertheless. if this method of adjustment offers advantages to the system design. then adequate safeguards can be provided by proper component selection . Being aware of the possibility of overpressure. the designer can select a lockable pressure adjustment on the main pilot valve. In this manner. the resistance of the pilot valve's spring can be locked at its absolute minimum value (100 PSI). Then. by selecting a remote relief with the proper spring. you can be assured that the operator cannot exceed the maximum pressure rating.
I 3
Consequently, our lowest operating pressure is set on the main valve . . . d this poppet, resist the pilot oil flow to tank.
,_"
determining the pressure at which the valve relieves pressure in the main system. "Y" Port Pressure Adjustment
and higher pressures are adjusted by adding a back pressure to the spring chamber.
- 40 -
(I) I
1000 PSI
0 and at
'h
speed . . .
/ /
G) even
0 This
turns an excess of 13 + hp
0 so that we
- 41 -
0 This fixed orifice limits our pilot oil flow . . . I while this direct t operated relief limits
9
5 At 1100PSI here . . .
/ @maximuma3000 results in
PSI pressure here. 10 GPM 5 GPM
l/0
.t'
- 42 -
111e eaiiiJ uny naruuuce!> me posSIOIIHY or energy savtng .. ne by load sensing with the relief. With a little imagination, this concept could result in considerable energy savings in a multitude of applications. Our only warning is that the size of the fixed orifice limiting pilot oil feedback is extremely im portant to the proper operation of the system. Also, the pilot feedback lines should be rigid tubing (not hose). with lengths kept as short as possible.
tn reterence to me operational cross section, me spool must first move through the deadband region before pressure opens to tank. This makes the spool design considerably slower than the poppet. since a poppet begins opening with the first increment of motion. Another detriment to the response time of a spool design is the high mass of the spool as compared to the poppet. Since all reliefs respond to pressure in a small portion of a second, the poppet or spool must undergo drastic acceleration and deceleration forces. Acceleration and deceleration occur as the moving member goes from rest, in the closed position, to a stable opening in the dynamic position. Of course, any reduction in mass greatly improves the response characteristics of the valve. Consequently. with spool reliefs. if the pilot circuit is orificed large enough to give good opening response. the physical overshoot of the spool during deceleration to the dynamic open position requires a longer time period to achieve stability. The optimal compromise is an overall response time of approximately 150 milliseconds. Likewise. the overshoot characteristics of a relief valve are related to spool (or poppet) stroke as compared to valve opening. When it comes time to relieve oil, pressure can build to very high values almost instantaneously if the oil has nowhere to go. With spool designs, the pressure builds to the point where the pilot valve opens and creates the imbalance on the spool. Also, this imbalance must be high enough to achieve acceleration of the spool mass. The problem is that during the first moments of acceleration, the spool movement provides no opening. Since there is nowhere for the pump supply to go, pressure builds instantaneously to a high value. In other words. even if the spool mechanically responds quickly to increasing pressure. little or no opening during the initial response period shows up as a poor over shoot characteristic of the valve. Finally. the life expectancy of spool type reliefs is very susceptible to contamination. In any relief. oil passes to tank at extremely high velocities. Contaminants in the oil. traveling at these high velocities, have a sandblasting effect on the exposed steel surfaces. The close tolerances on the large land areas of a spool design are more susceptible to damage and subsequent seizure than is the line contact area of a poppet. When exposed to systems with the same level of contaminants. the spool relief will either seize or leak ex cessively much sooner than a poppet design.
by either of the basic poppet designs. we wish to mention its operating characteristics for reasons of comparison. The three major factors which led to its obsolescense were poor response. inherently bad overshoot. and sensitivity to con taminants in the oil.
Internal-External Drain
y
47
- 43 -
Pilot Orifice
In consideration of the cartridge's response characteristtcs. we said earlier that response is directly related to stroke vs. opening area. The short stroke means that very little oil has to be relieved by the pilot as the poppet moves upwards from its fully closed to its fully open position. Also. the low poppet mass means that movement occurs with a very minute decay in pressure in the pilot section. Low poppet mass. short pop pet stroke. and minimum oil displacement in the pilot sec tion. allow the cartridge poppet to respond in the 50 or 60 millisecond range. This is actually faster than most direct operated valves. Since the poppet provides a large flow path with 1ts first 1n crement of motion. overshoot is very low and of very short duration. Although overshoot is higher at lower operating pressures. the average overshoot is only 8 per cent of se1 pressure. This means that at 3000 PSI. the maximum pressure spike is in the neighborhood of 3250 PSI. Another advantage to this design is that there is an in significant change in effective area between the open and closed position of the valve. Consequently. the forces tend ing to open and close the poppet are always in balance and not affected by flow. The typical valve reseals within 30 PSI of its cracking pressure. and is inherently stable throughout the entire flow range. Likewise. minimum compression of the light spring force. and a poppet design which is virtually unaf fected by flow. result in a minimum pressure override. Finally. the cartridge poppet is extremely quiet in performing its relief function. This is a result of the fact that the flow
- 44 -
passage to tank is not onlv large. but it also creates a 360 divergent flow stream. The potential energy in the pressurized fluid is disipated quickly and quietly.
ditional piping hardware. it abo must be structurally sup ported by some type of valve panel. This additional cost must be weighed against future service costs m your con sideration.
SANDWICH MOUNTING
A dvantages
Sandwich mounted valves are through ported and mounted between the directional control valve and its subplate. Their porting configuration is accomplished through passages in the block. and they can relieve either the pump supply or the service lines to the actuator. Either crossport or relief to tank can be compactly accomplished in a single block. Ser viceability is equal to that of a subplate mounted valve with a smaller space requirement.
Disadvantages
Because of the compact nature of these valves. their per formance characteristics are sometimes compromised. Likewise. because the valve is mounted close to the direc tiona! valve rather than to the pump or actuator. the reliefs ability to protect the system is somewhat reduced.
Advantages
The subplate mounted valves. by far. offer the best ser viceability. Since the rigid piping is made to the subplate and not to the valve. valve replacement is simply achieved by bolting a new valve to the subplate. Most subplate mounted valves conform to national and international standards. so retrofits are not a problem. In addition. the valve and its sub plate can be mounted away from the bulk of the system piping for easy operator access.
Disadvantages
The major disadvantages of subplate mounting show up in initial system cost and in space requirements. Not only is the subplate an additional purchase item. which also requires ad
- 45 -
r10uanrages
The through ported relief is the most economical relief when you consider initial system costs. With three ports. you simply have to pipe to the inlet from the pump. an outlet to the system. and a tank return. Since the number of fittings is reduced, so are the possible points for leakage.
Disaduantages
'
Disaduantages
Since the valve's physical location in rhe system is deter mined by the piping. adjustment access for the operator is not always easy to achieve. For serviceability. this valve idge construction. more than any other. should be of cartr since the housing is located in the main artery of the system. More often than not. servicing requires a maJor system disassembly.
CARTRIDGE UNITS
Care must be taken in "making-up" the fitting for this valve. as in the case with any line mounted valve. Over tightening of a tapered pipe thread can distort the valve housing. causing the valve to malfunction. Serviceability is also com plicated because the system has to be partially disassembled ro remove the valve. With a cartridge style line mounted valve. these problems are somewhat alleviated. because ser vicing can be accomplished simply by removing the cart ridges. Likewise. even if a valve housing is distorted by over tightening a pipe connection. the chances are that this distor tion will be isolated from the critical clearance in the cart ridge.
Port
''X''
Y Drain
''
''
P,
P,
- 46 -
Cartridge units are available today in two basic versions: the threaded insert. and the slip-in cartridge. Since both types offer the same advantages and disadvantages, we will discuss their merits as one.
Advantages
cannot be represented in this manner. Rexroth has developed and will be promoting the use of a new simplified symbol for representing pilot operated reliefs.
Although cartridges can be mounted in either a subplate mount. or a thread valve housing. they are basically intended for custom manifolding. The cartridge greatly improves the serviceability of the relief function no matter whether it is mounted in a custom manifold or in a standard valve housing.
Disadvantages
L...L...t___._1 1'1'
The cartridge in itself cannot function. Consequently. it must be used in conjunction with a standard valve housing. or with some type of custom manifold. Of course. due to the high cost of both engineering and low quantity machining. the cartridge is often not an economical consideration.
'-----L.:..._jt-
\---
The following are variations showing this sim plified symbol with various uses of the pilot cir cuit:
IL
L .J
I I I I 1 I _ _ _ _ _, _ _. _ _ _ _ _ _ _ _J _ I I *
L Q):
_
) :( _._
_.. I
-- -,
]
I '
L....!.....J
Pilot Operated
I I
L.:....J
This symbol is complete in showing the main poppet (low pressure. high volume relief). the pilot relief (high pressure. low volume). the orifices which establish pressure decay in the pilot circuit. and the solenoid valve for venting. In com mon practice. the industry does not use symbols of this com plexity. Over the years. it has become standard practice to represent both pilot operated and direct operated reliefs with the simpler direct operated relief valve symbol. This. however, often leads to confusion. since the total function
'__!__j
ote Pilot
- 47 -
5000
PSI
-- -- -- -- ._ -- -- -- -- ._
REDUCING VALVES
As previously stated. reducing valves are used to limit a branch circuit to a pressure lower than the main relief valve
setting ConsequenHy. output force can be regula!ed ln !he secondary circuit independent of (at a lower pressure level than) the rest of the system. Reducing valves are always sup plied with an ext.:!rnal drain on the spring chamber, since there is always pressure at the inlet and outlet working ports during valve operation.
Reducing valves. like relief valves. function by balancing a hydraulic force with a spring force. Consequently. they display similar operating characteristics to those of direct operated or pilot operated reliefs. Unlike relief valves. however. reducing valves are normally open. allowing oil en try to the secondary system. The valve senses the pressure level in the secondary system and tends to close. orificing the oil entering from the primary system. assuming that it is at a higher pressure level. Should the primary system be at a lower pressure level than the setting on the reducing valve. then the reducing valve would remain fully open. and both primary and secondary circuits would be at the pressure level of the primary system. Reducing valves. more than any other type of pressure con trol. modulate between fully open and fully closed positions to keep the outlet pressure constant. Once downstream pressure reaches thE reducing valve setting, the valve begins functioning as a self regulating orifice. The valve opens or closes its orifice which reduces or increases resistance to flow from inlet to outlet . Since a reducing valve is nothing more than a self regulating resistance to flow. energy is expelled in the form of heat as inlet pressure is reduced to a lower outlet pressure. The
2000
PSI
Reducing valves can take only a higher primary pressure and lower it for the secondary circuit.
- 48 -
higher the pressure level difference. the higher is the energy level difference and, therefore, the more energy is wasted in the form of heat. Large pressure differentials, especially with high flow rates, should be avoided through the use of a two pump system.
spring setting. Because the orifice can be relatively large for high flows, the spring has to be only slightly compressed. However, to establish an identical pressure drop for low flow, the spring must be compressed further to create a smaller passage through the valve. Consequently. higher downstream pressure results with a decreased flow due to in creased spring force. Since pressure vs. flow characteristics can only be kept within acceptable limits with low variations in flow. Rexroth only manufactures direct operated reducing valves up to 1/2" line sizes for flow capabilities up to 12 1/2 GPM. For higher flows. a pilot operated valve is used because of its per formance advantages.
G) this
- -
-,--
Q.
Q)
c--
Flow (GPM) Typical Pressure vs. Flow Graph for a Direct Operated Reducing Valve THREE- WAY CHARACTERISTICS OF DIRECT OPERATED VALVES
Because reducing valves are variable orifices. their basic design is usually a tapered (metering) spool, held in the open position in the valve housing by an adjustable spr ing force. For direct operated valves, outlet pressure is exposed to the spool end opposite the spring. and moves the spool toward a more closed position as downstream pressure exceeds the Another thing to consider about reducing valves is their ability to maintain reduced pressure in a fully static con dition. During actuator motion in the secondary circuit, we have explained how the reducing valve modulates between open and closed to maintain downstream pressure at the
-2.5
2.5
7.5
10
- 49 -
desired setting. A problem arises. however. when the secon dary circuit becomes static. and the reducing valve fully closes to separate the primary and secondary system pressures. Under these conditions, an increase in load, or leakage across the reducing valve control spool. could increase the pressure in the secondary circuit higher than is desired. Since the valve has an inlet at high pressure, and an outlet at reduced pressure. a third port must be provided to rid the secondary circuit of leakage oil and/or reverse flow from the actuator. Most reducing valve designs in some way vent this oil. which tends to increase pressure to the spring chamber. where the oil can be externally drained.
Some direct operated reducing valves have a three-way spool configuration. We previously stated that the reducing valve is normally open. and that it opposes the spring force with a hydraulic force from the secondary circuit. Depending on the pressure and flow potential at the valve inlet. the valve self-adjusts its orifice to obtain the required pressure loss. The valve closes only when the secondary circuit becomes static. A slight increase in outlet pressure above pressure set ting shifts the spool further against the spring into a third position where the outlet is connected to the spring chamber, thus relieving the secondary circuit to tank. The flow capability of this three-way feature is approximately 20% of the maximum flow capacity of the Rexroth valve. When the secondary circuit is stalled, and there is no increase in pressure due to leakage, thermal expansion. or increased load. the valve is closed without leaking excessive oil to tank.
- 50 -
In many hydraulic systems, the reducing function is only needed for one particular actuator. For instance, we may want to limit the torque output of a hydraulic motor, or to limit the thrust of a cylinder in one or both directions. For plumbing convenience in these types of circuits, reducing valves are available for sandwich mounting. These valves are simply mounted between the subplate and the directional control for that particular circuit function. Depending on the model selected, the pressure reduction can be in the pressure supply to the directional valve, or in one of the service lines from the directional control to the actuator. A "P" port sandwich reducer would offer reduced pressure to either direction of operation. Since the flow is always from the pump supply, through the reducing valve to the pressure port of the directional control, a reverse free flow check is not required. On the other hand, if the model selected reduces pressure in one of the service lines to the actuator, pressure control i s achieved only in one direction of operation. Full system pressure operates the actuator in the reverse direction. Of course. since flow must pass through this type of valve in both directions, a reverse free flow check valve must be in cluded. This allows the flow to by-pass the reducing valve mechanism in the reverse direction of actuator operation. Due to their compact design. sandwich mounted reducing valves normally drain their spring chambers to the tank port connection of the directional valve. Since pressure in the tank return line can influence the pressure setting, precautions should be taken to keep tank line pressure as low as possible in these systems.
Pressure Inlet
SECONDARY CONTROL
remains fully open, connecting the primary port to the secon dary system until secondary system pressure overcomes the spring setting of the pilot valve. When the piloting relief opens, a decay in pressure occurs above the main control spool , since a flow is created across the orifices in the pilot circuit. This causes an imbalance of forces on the main spool, which tends to move it vertically upward. An upward motion of the spool orients the center line of the radial drilling in the spool higher than the center line of the radial drilling in the stationary sleeve, in which it slides. The open area for flow is, thus, reduced, creating an orifice through which oil must flow in passing from the primary to the secondary port. Hence, a self-regulating pressure drop is imposed, in concert with the pressure levels dictated by the pilot circuit. Likewise, a full shut-off occurs when the secondary circuit becomes static.
- 51 -
primary pressure 0 so that restricted . . . here is RELIEVING ABILITY OF PILOT OPERATED REDUCING VALVES
Unfortunately, as you can see in the diagram, the pilot operated reducing valve has little ability to rapidly relieve a pressure build-up due to increased load. When the secondary circuit becomes static, the main spool is nearly closed, which
0
..__ ,_.,. _, __, _
=-
G) through a small
- 52 -
except for a small pilot flow, captures a column of fluid be tween the main spool and actuator. If, for some reason, the actuator encounters an increased load, the pressure down stream of the reducing valve will also increase. Since pilot operated reducing valves, in general, cannot relieve much more than a 112 GPM flow rate through their pilot circuits, a separate relief valve should be considered if an increase in load could occur after the secondary system becomes static.
will assure that the relief valve will remain closed during normal operation.
I
' li
Reducing Valve
To Actuator
4
0 at a pressure slightly
- 53 -
fonnance characteristics, and the possibility of a fail-proof pressure setting. With this type of circuitry, it is important, from an efficiency standpoint always to adjust the relief valve to a pressure slightly higher than that set on the reducing valve. By setting the relief so that it will crack at a pressure of 100 to 200 PSI higher, you can be assured that under nor mal operation, all the output flow of the reducing valve produces work. If the relief valve setting is too close to that of the reducing valve, you can easily see that the flow bypassed by the relief not only affects performance, but that, at the same time, it generates excessive heat. The circuit provides a single pressure adjustment, while at the same time it maintains a constant differential between the relief and reducing valve setting.
In the illustrated circuit, once the reducing valve closes, pressure can build in the fluid which is captured between the actuator and the closed spool. If this pressure builds to the point where the reducing valve pilot opens, the main spool will remain closed. Since we cannot safely assume that the spool will remain open under all circumstances, most reducing valves include a reverse free flow check as a stan dard feature.
than here . . .
(D
0 Even
if the pilot remains closed and the pressures re balanced above and below the main spool . . .
- 54 -
As shown in the cross-sectional drawing, the check valve simply bypasses the reducing valve mechanism under re verse flow conditions. During normal operation, the higher pressure at the valve's inlet keeps the check valve closed.
0 creates
'
Before we discuss the operation of a reducing valve with primary control, let us first consider the reason for this design. It is a known fact that when an orifice is introduced into a flow stream, turbulence is also introduced, down stream of the orifice. Of course, the higher the flow rate, the more turbulence downstream of any given orifice. With high flow, high pressure reducing valves, the turbulence downstream of the main control spool causes a loss in pressure at that point in the flow stream (Venturi effect ). This loss in pressure reduces the pressure drop across the pilot circuit orifices, which lessens the pilot oil flow. Under these conditions, a reducing valve with secondary control becomes ineffective in maintaining a constant downstream pressure .
.... : o - _ 12 ...
- c - c 0. -
:1
36
.
""' -
24
10 20 30 40 Main System Flow (GPM) Typical Graph Comparing Loss of Pilot Oil Flow With Main System Flow
Gauge Port /
As long as the inlet pressure is lower than the setting of the pilot relief, the pressure on top of the main spool is equal to the pressure at the inlet of the valve. This pressure force,
- 55 -
along with the spring force, holds the main spool in the wide open position, allowing free flow to the secondary circuit. As load induced pressure increases, so does the inlet pressure and the force holding the main spool open.
closed position. Under these conditions. the secondary outlet is totally isolated from the primary circuit and the pilot circuit of the valve. Of course. leakage across the sliding fits of the main control spool could cause the secondary system
0 The
pressure at the outlet is only slightly lower than that a t the inlet because of pressure drop due to flow.
pressure to equalize with that of the primary system. To avoid the possibility of pressure buildup in a static secon dary circuit, a small relief valve is incorporated in the main spool. This relief valve has its pressure port exposed to the secondary outlet, and relieves oil to the pilot circuit. The relief valve is nothing more than a ball held on its seat by a light spring force . To open this relief, the pressure in the secondary circuit must overcome the spring force (45 PSI) and the pressure in the pilot circuit working against the back side of the ball. However, since outlet pressure is equal to
The moment the inlet pressure exceeds the setting of the pilot relief, a constant pilot flow is established. The pressure determined by the pilot relief regulates the maximum pressure, holding the reducing valve in the open position. As load induced pressure increases on the opposite area of the main control spool, so does the force trying to close the valve. The moment the dosing force exceeds the forces holding the valve open, the main spool moves upward, or ificing the flow to the secondary circuit. Hence, secondary system pressure is maintained at a level which balances the pressure in the pilot circuit.
0 by this pressure
the outlet pressure on this area needed to close the main spool.
The main spool orifices flow to the secondary system, which keeps outlet pressure i n equilibrium with pilot pressure.
When the actuator on the reducing valve's outlet stalls, a slight increase in outlet pressure overcomes the forces holding the valve open, and moves the main spool to the fully
pilot pressure, the net result is that the relief valve opens when the secondary system reaches a pressure 45 PSI higher than setting. Since the relief valve relieves oil to the
- 56 -
pilot circuit, its maximum flow capability is limited to ap proximately 60 cubic inches per minute. Although this is satisfactory for relieving leakage oil, it cannot relieve a re verse flow from the actuator.
destroyed, the loss of energy shows up as heat in the hydraulic system. Of course, the lower the pressure in the secondary system, the more heat is generated. Remember:
(D When the
0 However,
BTU/hr
1 . 5 x GPM
P S I (Lost)
Consequently, it is left to the designer to keep the secondary system pressure as close to that in the primary system as possible. You can see that this becomes even more im portant in high flow systems. In these, if the pressure dif ferential is too great , it is worthwhile to consider a separate pump for the lower energy secondary system.
- 57 -
must always have a drain connection to its spring chamber, the "Y" port external drain is always shown.
SYMBOL
DESCRIPTION
Standard graphic symbol for a direct operated reducing valve, without a reverse free flow check. y
L'_j
lr-
------+-
Graphic symbol for a direct operated reducing valve with in tegral reverse free flow check.
y L..J
Graphic symbol for a direct operated reducing valve with a three-way relieving capability and integral reverse free flow check.
Pilot operated pressure reducing valve with integral reverse free flow check. The remote adjustment connection "X" shows that this valve has secondary pilot control.
- 58 -
Pilot operated reducing valve with Integral reverse free flow check. The lack of a remote "X" port shows that this valve has a primary pilot control.
Multi-function valves are quite similar to relief valves in that the spring holds the spool or poppet in the closed position. Internal or external pilot pressure, from various sources, works against the spring. and causes the valve to open when the pressure setting has been reached. The working direction of flow is from the valve's inlet to outlet, with both valve ports capable of withstanding full system pressure. Since these valves are often mounted in the service lines to the ac tuator, their housing is designed to accept an optional rever se free flow check. To better understand the various assem bly possibilities, let us consider the following cross-sectional illustration. Essentially, the valve consists of a spool which slides in a close fitting bore in the valve housing. The spool blocks the inlet from outlet. until the pressure on the right hand area of the spool overcomes the spring force. The small pilot spool serves to reduce the effective area on which pressure can work. You will notice that, with the spool installed, the net area is the same as the diameter of the pilot spool. Since the pilot spool slides in a clearance fit, oil leakage past this spool is connected to the drain passage. For lower pressure operation, the spool is removed, and the chamber on the right of the main spool is blocked from the drain passage with an internal plug. The valve will now shift at a considerably lower pressure, since the effective area is now the full diameter of the main spool.
XY
- 59 -
Pilot Spool
@ and replacing the orifice with a plug here . . . 0 and plugging the external ' 8
vers1on. By removing this plug . . .
" connection . . .
Back pressure in the spring chamber is additive to the pressure setting of the valve, as it is in any type of pressure control. Generally speaking, multi-function valves can be in ternally drained whenever the valve's outlet is connected to tank during the period when the valve is functioning. If an operating system pressure is developed in the valve's outlet, it must be externally drained. With some counterbalance and most unloading applications, the valve can be internally drained. The effects of internal or external draining are shown in the following examples of multi-pressure valves, connected in series:
- 60 -
FROM PUMP
.I
I
C?
Internally Drained Valves Function Like Resistances in Series SET AT 2000 PSI SET AT 1 500 PSI 500 PSI SET AT 500 PSI
FROM PUMP
Cf
The pilot operated version of the multi-function pressure control can handle larger flow rates, generally with less
- 61 -
Pilot Spool
closed as long as the pilot spool is held in position by the ad justable spring force.
against the spring, the top side of the poppet is vented to System II pressure. Under these conditions , the main poppet functions like a simple in-line check valve (Chapter 4). The valve allows flow from inlet to outlet as long as System I pressure is slightly higher (45 PSI) than that in System II. This pressure is needed to move the main poppet against the spring.
0 than here . . .
this area is vented to System II. When the pressure is 45 PSI higher here . . .
- 62 -
to set pressure for a given pilot spring, optimally occurs over a 100 to 150 PSI change in pilot pressure. In some higher pressure applications, a high flow potential exists in the "X" pilot line. This high energy potential could adversely affect proper operation by causing the pilot spool to shift too quickly. To avoid this possibility, an orifice is in stalled in the supply line to the pilot spool end. This limits the flow potential to or from the pilot spool, which, in tum, restricts its shifting speed.
"X" and
"
Y PORT CONNECTIONS
"
(D This valve is internally piloted and internally drained. 0 the springexternally chamber becomes
drained.
Spring
If we want the main poppet to open slowly, we must provide a gradual decay in pressure above it. Likewise, in closing, the reestablishment of the static condition must be achieved gradually. This function is easily achieved by using a properly designed spool working in conjunction with a relatively stiff spr ing. The pilot spool is designed with a slight taper on its sealing land. The edge of the land is also provided with 'V" grooved metering notches. The combination of "V" grooves and tapered land provides for a gradual opening of the top of the main poppet to System II. Although the pilot spool only strokes approximately 1/8", the stiff spring also aids in gradual valve opening. That is, pilot p ressure, which is sufficient to provide initial opening of the spool . may not be high enough to move it to the fully opened position . The net result is that, as pilot pressure builds on the left hand area of the pilot spool, the spool steadily strokes to the right against the spring. The top area of the poppet is vented through a gradually increasing orifice, which allows a smooth opening to System II. This opening, although related
(:;\
'-.V
Illustration is to show operating principles only. It does not depict the true port locations of NFPA standard mounting interfaces or access locations for internal plugs.
We have already discussed the possibility of converting in ternal and external pilot supplies and drains for the direct operated multi-function pressure controls . The cross sectional illustration shows that the same possibilities exist for the pilot operated versions. The use of these various arrangements will be discussed in the application descrip tions which follow.
- 63 -
HEMUTE PKESSUKE A U J U S I MN I
One precaution which should be considered is that multi function valves are not easily adjustable from an external source. First, we do not have an "X" port connection which can be used to modulate the pressure on top of the main poppet to a value lower than that set on the pilot valve. As already explained, the "X" port for multi-function valves serves an entirely different purpose.
::,econd, we cannot use the Y" port method ot remote ad justment. The problem here is that the only flow of oil into the spring chamber is leakage by the pilot spool. We do not have a positive oil supply as we did in the pilot section on either the pilot operated relief or the reducing valve. Con sequently, if remote adjustment is absolutely necessary, we must select an externally drained valve, and then supply the spring chamber with a positive pressure source. A s shown in the following example, this method can be quite cum bersome.
..
remote adjustment to higher pressure values can be made on this remote relief.
Positive oil supply from a separate pum p or other high pressure part of the system.
pressure, other precautions must be taken. These precautions could include sizing the actuators differently to obtain the desired force, or using a reducing valve in series with the System I actuator. The circuit shows a typical installation of a pressure se quence valve. A close look at the cross section will show you that most sequence valves are assembled with an internal pilot supply, but that they must always have an external drain . Upon actuation of the advance solenoid, the circuit automatically functions as follows: When the advance solenoid is energized, pump flow is di rected to the blind end of the clamp cylinder, and to the inlet port of the sequence valve. Initially, the pressure in the line supplying the clamping cylinder is not high enough to open the sequence valve; hence, the full pump flow is available for cylinder extention . Upon reaching the work piece, the clamp
- 64 -
External Drain
Retract Solenoid
cylinder stalls. Since the oil being supplied has nowhere to go, the pressure rises to the level which opens the sequence valve. The oil is then directed to the blind end of the punch cylinder. During extension of the punch, there is little or no resistance to flow, as the punch is traveling through free air. Without the sequence valve in the circuit, the tendency would be for the pressure to equalize in both the clamp and the punch cir cuit , at the pressure level needed to extend the punch. The sequence valve, however, will not allow this equalization of pressure to occur. The moment too much flow is allowed to enter the punch circuit. pressure drops slightly in the clamping circuit. This drop in pressure results in a relaxation of force holding the pilot spool in the original wide open p osition . The main poppet closes against the flow stream un til an orifice is created which will pass the full output of the pump at a pressure drop sufficient to maintain clamping pressure at valve setting.
When the punch reaches the work piece. pressure rises to whatever level is necessary to pierce the material. This pressure can be less than, equal to, or greater than the minimum pressure required for the clamp circuit. If the punch operates at any pressure lower than that required for the clamping circuit. the sequence valve modulates its orifice to maintain its inlet pressure at valve setting. At the same time. as load induced pressure increases in the punch circuit , the pressure drop across its main con trol spool decreases. Since the flow across an orifice is related to pressure drop, the sequence valve progressively moves its main poppet to a more open position, so that it can pass the full output flow of the pump. When punch presure is equal to, or greater than, sequence valve setting, sufficient pilot pressure exists to hold the valve in the wide open position. Pressure in both the clamp and punch circuits equalizes at the higher pressure needed for the punching operation.
- 65 -
Punch Cylinder
0 The punch
cylinder retracts first . . .
which will open this sequence valve, allowing return flow to tank.
Depending on the mechanical design of the clamping mechanism, and the punch operation being performed, this example circuit may or may not provide satisfactory operation. That is, when the cycle is reversed, there is no assurance as to which cylinder will retract first. This will depend on which circuit has the path of least resistance to flow. Our example is given only to highlight the operating principle of a sequence application. The example is but one of many sequence variations which could be used to solve the particular problem at hand. By the simple addition of two check valves in the circuit, we ass ure that during reversal of the ci cuit, the punch cylinder will r always be the first to retract. This circuit assures a specific order to the interaction of the clamp and punch circuits in both operating directions . It does not. however. assure a positive pre-determined clamping force in the retract mode. You will notice that the rod end of the clamp cylinder is also exposed to the pressure needed to retract the punch cylinder. Even though there is a captured column of fluid between the blind end of the clamp cylinder piston, the check valve, and the closed sequence valve, any leakage would create a tendency for the retraction of the clamping cylinder. Nevertheless, this circuit could provide sufficient clamping force for the withdrawal of the punch,
1.
2.
Be externally drained. Withstand an operating system pressure on its outlet (tank) port. The only problem is that during valve operation, a continuous flow in the "Y" drain port exists.
In comparing the pilot section of the relief valve with that of the multi-function valve, you will notice one important dif ference. To keep the relief valve open, the pilot relief must be relieving fluid from the chamber on top of the main poppet. Depending on valve design and size, this pilot flow can be in the neighborhood of 3/4 to 1 1/2 GPM. At 3000 PSI, this can result in an efficiency loss of two or three horsepower. This heat generation and loss of speed in System II are not a problem with a multi-function valve used in a sequence operation.
- 66 -
One important advantage of the multi-function valve's pilot head is that it opens and closes the main valve poppet with an insignificant amount of pilot flow. The actual flow required is only that which is displaced during stroking of the pilot spool . Likewise, the "Y" drain connection is only to rid
the spring chamber of the oil which leaks by the pilot spool . Consequently, we can add to the overall efficiency of the total system by selecting the proper valve for sequence ap plications .
0 valve is
closed . . .
0 This hydraulic
pressure balances the weight of the load.
J f
t
load
G) When this
0 by this
downward force . . .
Counterbalancing is required whenever gravity can move the load faster than the speed intended by the hydraulic system. One criteria for the energy conscious designer is that the load conditions causing motion should always be the same. Let us now take a closer look at a simple counterbalance valve in application . In this circuit, the basic counterbalance configuration of the multi-function valve is internally piloted and drained. In ac tuality, the valve is quite similar to a relief valve. The major difference is that a reverse free flow check valve is usually a necessity. The check valve permits a free flow of fluid towards the actuator in the reverse direction of operation. Counterbalance valves can usually be internally drained, since the outlet of the valve is connected to tank through the directional valve whenever the valve is functioning. However, there is nothing preventing the use of the external drai in n
- 67 -
systems with high or fluctuating return line pressures. In this example. when the directional control valve is cen tered, both the rod end of the cylinder, and the outlet of the multi-function valve, are connected to tank. It is important to choose a directional valve with this center configuration for two reasons. The first reason is that directional controls shift in a small fraction of a second. If the valve were to block the outlet of the counterbalance valve rapidly, even if the counterbalance were to remain open, the oil coming from the rod end of the cylinder would have nowhere to go. This would eliminate the cushion stopping of the cylinder, which is one of the main ad vantages of a counterbalance valve in the first place. If we allowed the outlet of the counterbalance to be connected to tank when the directional control is centered, a cushioned stopping of the load would occur. The second reason for using a directional control as shown is that it is important to preclude the possibility of a pressure build up on the top side of the cylinder. If the directional valve blocks all ports in center condition, high pressure from the pump could leak across t h e close tolerances of the spool and build on the blind end of the cylinder. As we will show, if the pressure builds high enough, the counterbalance valve will open, allowing the load to drift.
For a better understanding, let us assign some arbitrary values to the previous circuits. Assume that the load is pulling on the cylinder rod with enough force to generate a pressure over the rod end area of the piston of 3()(X) PSI. Under these conditions, the counterbalance valve would be set slightly higher (3100 PSI) so that it would remain closed, supporting the load on a captured column of fluid. At this point, it is important to note that although the load is supported by the counterbalance valves, it is not safe to assume that it is positively locked into position. Most in dustrial counterbalance valves are in some way related to a spool design. Leakage, although minimal, could allow the load to drift, especially if the load was held for extended time periods. As will be shown in Chapter 4, the line contact sealing of a pilot operated check valve is the only way to assure positive holding of the load. When the directional control is energized, pump flow is di rected to the blind end of the cylinder. Since the piston can not move against the blocked column of fluid on its opposite side, a resistance to flow causes the pressure to rise on the top side of the piston. This increases the downward force, which in tum increases the pressure on the block column of fluid at the rod end of the cylinder. Assuming proper setting of the counterbalance, a minimal pressure on the top of the piston opens the valve, allowing downward movement of the load.
- 68 -
The pressure override characteristics of the multifunction valve allow it to open gradually over a 100 to 150 PSI pressure increase on the top side of the piston. Since pressure must be maintained in the blind end of the cylinder to keep the load in motion, the counterbalance modulates to pass just enough fluid to keep the cylinder from running away from the pump supply. The gradual opening and closing of the counterbalance valve causes smooth ac celeration and deceleration of the load. In our initial description of the counterbalance valve, we said that load conditions should be more or less constant. Any suspended weight has potential energy, or, better still, a potential for doing work. Ideally, since potential energy is available for doing the work, no additional energy should have to be supplied by the hydraulic system. In actual prac tice, however, we have shown that some energy is necessary to override the counterbalance. Of course, the closer the
counterbalance is set to the actual load induced pressure, the more efficient the system becomes. In our previous example, if we were to remove the load, all of the downward force would have to come from the hydraulic system. Assuming that we did not alter the setting of the counterbalance, all this hydraulic energy would be un necessarily converted into heat as the pressurized fluid was forced over the counterbalance valve.
0 pressure
here . . . External Pilot Internal Drain pilots 0 open . this valve wide ..
- 69 -
over center loads, varying loads, and press applications where maximum tonnage is required. However, by externally piloting the counterbalance valve from the opposite supply line to the actuator, the overcenter counterbalance valve im proves both system performance and efficiency.
area of one square inch, then 3000 PSI pressure is created in the fluid being supplied by the pump. At any pressure over 100 to 200 PSI, the overcenter counterbalance valve is piloted wide open, offering little resistance to flow from the rod end of the cylinder. After the load moves past the center line, the geometry of the load forces now pulls on the cylinder rod. When the load is at the same angle on the other side of center, a 3000 lb. load force is trying to extend the cylinder. Since the effective area on the rod end of the cylinder is slightly less than one square inch, a pressure slightly higher than 3000 PSI is needed to keep the load from free falling. Because the overcenter type counterbalance is externally piloted, its opening and closing is not affected by pressure conditions in the rod end of the cylinder. It only responds to a pressure signal in its external pilot line. or, in this case, in the
OVERCENTER LOADS
The term ouercenter comes from the fact that, in many ap plications, the machinery's geometry causes the load con ditions to change from resistive to overrunning. This prin ciple is represented in the example. In the position shown, you can see that the load is resisting the extension of the cylinder. If a 3000 lbs. force is required at point A to move the load, and the cylinder has a piston
/ '
Overrunning Load
' '
'
'
' /
'
'
'
From Pump
To Tank
- 70 -
blind end of the cylinder. When the load goes overcenter, the load forces try to pull the cylinder's piston ahead of the oil supply from the pump. Under these conditions, there is no resistance to flow from the pump. In fact, the moment the piston gets ahead of the oil stream, a vacuum condition is created on the blind end of the cylinder. We said earlier that, because of the pressure override charac teristics of the multifunction valve, a change in pressure was necessary to fully open the valve. In our example, if the valve is set at 100 PSI cracking pressure. the full open position does not occur until a pilot pressure of 200 PSI is reached. As the load moves overcenter, pressure is lost in the blind end of the cylinder. Consequently. a tendency for the closing of the counterbalance valve exists. The counterbalance valve resists the motion of the load with whatever pressure is necessary to maintain a 100 to 200 PSI pressure in the fluid being supplied by the pump. You will notice that we have explained the operation of our overcenter counterbalance valve in only one direction of operation. For reverse motion of the load, a similar valve would have to be used on the blind end of the cylinder.
remote pilot, the pilot pressure 0 With a to open this valve can be set quite required low.
Even if the load varies, the hydraulic system adds an insignificant amount of heat, since the pressure he.e ;s always low.
0 because of flow at
a pressure drop across this valve. this load is lowered, --L...I-- 7 7 8 ft.-lbs. 7 7 8 lbs. of potential energy must L------.--_J The energy is transformed be dissipated. into 1 BTU of heat . . . 1 ft. From Pump
(D When
- 71 -
high pressure
;-: - - !:.' 1 ,
Wo<
end of the cylinder. Under these conditions, the total pressing force available is calculated by adding the weight of the platen to the force due to system pressure over the top area of the piston.
- 72 -
UNLOADING VALVES
Unloading valves are used in hydraulic circuits to offer high speeds up to a predetermined pressure level. At valve set ting, a remote pressure signal unloads part of the original flow source to tank. A prime example of an unloading ap plication is a two pump "hi-low" unloading circuit. In many applicat ions, where high speed and high force are not needed simultaneously, you can achieve a considerable savings of installed horsepower by selecting a two pump system. The first pump supplies high flow at lower operating pressures. and the second pump offers higher pressures. but at a lower flow. Remember that:
You can see that, at low pressure and high flow, the calculated horsepower can be the same as it would be if the system were operating at high pressure and low flow. Let us now take a look at a circuit which accomplishes this task. As shown in the example, a multifunction valve with external pilot and internal drain can be used to unload the high volume pump. As long as the system is operating at a pressure lower than that set on the unloading valve, the valve remains closed. Under these conditions, the output of the high volume pump supplements the output of the small pump, and the system operates at full speed. As the system offers an increased resistance to flow, pressure builds on the outlet of both pumps, and on the pilot spool in the unloading valve. When the pressure i s high enough to move the pilot spool again st the spring setting, the output of the high volume pump is connected to tank. Whenever the main system is operating at a pressure of approximately 1 00 PSI over the setting of the unloading valve, the output of the high volume pump is circulated back to tank at minimum pressure. If, for some reason, the system pressure drops
HP
To system
- 73 -
8 When this
spring
r G B T TI: m B B W B =
high and can hold the spool in the wide open position.
pressure 0 which increases thevolume at which the high pump circulates its output to tank.
To Tank
below the setting of the unloading valve, the circuit automatically shifts itself into high speed operation .
unloading valve, and how it is affected by back pressure at its outlet. In unloading applications, the efficiency of the system de pends on the minimum pressure at which the high volume pump circulates oil. If, for instance, we were to unload a 1 00 GPM pump at 50 PSI, our horsepower to drive the pump would be a little less than 3 HP. The same pump, with a 200 PSI resistance to flow in the unloaded condition, would require almost 1 2 HP to circulate the oil. This not only draws unnecessary power from the prime mover, but, in tum, it generates an equal amount of heat. A slight modification to the pilot spool of a standard multifunction pressure control optimizes the minimum pressure at which the valve unloads its pump.
0 and
draining the top of the main poppet externally through these cross drillings . . .
which is the minimum pressure Jw. - required to move the main lr- poppet against this spring.
- 74 -
High pressure closes this check valve after the high flow pump is unloaded . . . To System Orifice
- 75 -
course, the time period during which the drop in pressure oc curs establishes the flow rate available from the ac cumulator. Remember:
connected directly to the hydraulic reservoir. If you want to pass the return flow through filters or heat exchangers, you should use an external drain for the spring chamber of the pilot. Assuming that the pilot spring seats the pilot poppet, the main poppet is also closed, due to the hydraulic pressure balance and the light spring force. The valve delivers flow to the system over the isolating check valve, which in tum charges the accumulator as pressure in the system increases. You will notice that as long as there is flow, a higher pressure exists on the right hand area of the unloading piston than on the left, due to the pressure drop across the isolating check valve. The unloading piston is held in the left most position, and has no effect on the relieving function.
To System
From Pump
Tank
- 76 -
Under these conditions. the pump circulates oil freely to tank while pressure in the system is maintained by the ac cumulator.
small pressure differential between open and closed positions would set up a rapid cycling of the pump between the loaded and unloaded condition s. To overcome this problem. the pilot head of an accumulator unloading valve is designed with differential effective areas between the pilot relief and the unloading piston. The illustration shows how the accumulator unloading valve allows system pressure to fall to a predetermined minimum value before reloading the pump. Since the effective area of the pilot poppet is smaller than that of the unloading piston. a higher pressure is needed to initially move the pilot poppet against the spring force. Once the right hand area of the
the pressure keeping the valve unloaded can drop to 83% of the original pressure (2490 PSI) before the pilot poppet will reseat.
If it takes 3000 PSI here to cause the initial opening of the pilot . . .
- 77 -
unloading piston is vented over the opened pilot poppet , system pressure becomes effective on the larger area of the unloading piston. Of course. the larger area means more available force. so that we can keep the pilot poppet un seated with a somewhat lower pressure. The area ratio is usually in the neighborhood of 1 7 % .
PRECAUTIONS
The function of the accumulator unloading valve should not be confused with that of an accumulator safety valve. Once the accumulator is charged, the unloading valve has no means of bleeding the accumulator charge to tank if the system is shut down. Likewise, a fully charged accumulator is not protected from over pressure due to increased load or thermal expansion. The accumulator unloading valve only provides pressure protection in regard to the pump's capability to pressurize the system.
Since the function of a multifunction valve so closely resem bles that of a relief valve, you will notice that the symbols are quite similar. Of course, most multifunction valves include a reverse free flow check, which must also be represented in symbolic form. In the following examples, you will un derstand the specific valve function being represented by paying strict attention to the arrangement of pilot lines.
Description
Internal pilot and internal drain, with built-in reverse free flow check. Probable use: counterbalance.
Internal pilot and external drain, with built-in reverse free flow check. Probable uses: sequence, coun terbalance.
- 78 -
External pilot and internal drain, with built in reverse free flow check valve. Possible uses: overcenter coun terbalance or unloading valve.
External pilot and external drain, with built-in reverse free flow check. Possible uses: overcenter coun terbalance, unloading valve, or remote sequence.
Description
1 I
,-
--J
---' _
_
P, (H.P .)
P. (L.P.)
I j
'
I
I
__
__ _
+- --' L.'_j T
- 79 -
- - -
I I I
---- - -- ,
Pilot operated accumulator unloading valve. with normally open solenoid venting. Internally drained.
--- - ---
CONCLUSION
This chapter has been devoted to an in-depth study of how to manipulate forces by controlling pressure. With a thorough understanding of the five basic pressure valve func tions, the design engineer's ability to control the interaction of forces is limited only by his imagination. Hydraulic systems. when properly designed, put tons of force under precise, finger-tip control. In reviewing your knowledge of pressure control, you should be able to differentiate between the five basic control func tions, namely: relieving, reducing, sequencing, coun terbalancing, and unloading. Likewise, you should un derstand that. no matter how complex the function. all pressure controls operate by balancing a hydraulic force with a spring. This spring balancing is readily apparent in direct operated valve design s, but it is also the key operating prin ciple in pilot operated version s. In reviewing the different pilot operated functions, you will
discover that no matter what the design or desired function. pilot operation always works on the principle of creating either balanced or unbalanced pressure conditions across the main control element. More specifically. in relation to pilot operated pressure reliefs. you should know what is meant by the terms remote piloting. venting. and high vent option. You should also un derstand the three uses of the external pilot drain: for more stable pressure adjustments. for remote pressure control. and for load sensing. The important points covered in our discussion of pressure reducing valves were: first. the relieving ability of a pressure reducing valve. and. second, the differences between pilot operated versions witly either primary or secondary control. We also mentioned the inherent ability of the reducing valves to generate heat in the hydraulic system. In addition to your knowledge of relief and reducing func tions, you should also have a good understanding of the ver satility offered by the multi-function family of direct and pilot
- 80 -
operated valves. You should know the assembly variations and application requirements in using the valve in sequence, counterbalance. overcenter counterbalance, or unloading functions. In addition, you should realize the special requirements of accumulator circuits.
The hydraulic specialist. who understands pressure and how to control it. knows just about half of everything there is to know in his field. When he combines this knowledge with the principles of flow.
his fingertips. Chapter 3 wi\l deal with 1\ow and its relation to speed in the hydraulic system.
- 81 -
CH APTER 3
FLOW CONTROLS
By controlling the volume of oil supplied to the hydraulic ac tuator. we control its speed. In order to further develop the concept of flow control as previously introduced. this chapter will cover, in detail, the construction and application of various flow control components. Flow, although it is func tionally independent of pressure, is influenced in many ways by the existing pressure conditions. For this reason, it is im portant that you have a solid understanding of the fact that pressure is a resistance to flow. We now wish to cover the construction. performance, and applications of both non compensated and pressure compensated flow controls.
0 1 0 gpm
Pump
Y
If, after the performance, the attendants open all the doors. there is almost no resistance to the flow of people, and everyone can exit in a short amount of time. Under the same conditions, if more and more doorways are left locked. the time it will take for the people to exit the room will become longer and longer. That is, the flow rate of people/minute to the outside is reduced as more and more of the exits are closed. If the flow of people is restricted severely enough, the patience of the people who would be last to leave becomes so short, that they elect to sneak out the fire exits. The inlet conditions of a flow control can be thought of as a short tem pered crowd, where pushing and shoving is forcing the maximum number of people out the main exit (orifice), while the others elect to exit via the fire exits (relief valve)_ As shown in the above example, orifices in hydraulic circuits are nothing more than rest ctions which offer an increased . resistance to flow. Smce pressure IS reqUired to push the oil through the orifice, work (force + motion) is being done on the oiL For a given orifice, an increase in pressure drop from inlet to outlet is always accompanied by an increase in flow.
.
- 83 -
500 PSI
Actually, the use of non-compensated flow controls are limited to applications where feed rates are not critical and where load induced pressure is relatively constant This is true because the pressure drop across an orifice, and thus the flow, can be affected by four variables:
1 . An increase in load pressure at the outlet increases downstream pressure, and. assuming inlet pressure remains at relief valve setting. has the effect o f decreasing the pressure dif ference from inlet to outlet. This means less flow, and the system slows down with increased load. 2. An increase in the inlet pressure. by raising the relief valve setting. has the effect of increasing the pressure drop across the orifice, assuming constant load in 3. By opening and closing the orifice. we change the
resistance to flow. The lower the resistance, the less pressure drop we need from inlet to outlet for any par ticular flow. 4. The temperature of a fluid affects its viscosity, and in turn. the fluid's resistance to flow. It is well known that hot oil is more "fluid" than cold oil. Consequently. like water and molasses. hot oil flows more easily through a given restriction than does cold oil. This is the reason why some systems are sluggish on cold mor ning start ups. and may not achieve full speed for several hours.
NEEDLE VALVES
Although a flow control can be nothing more than a pipe plug with a hole drilled through it, it is usually desirable to be able to make an adjustment of the size of the opening. The needle valve, as shown in the cross-sectional illustration, is the simplest and least expensive way to create a variable orifice.
- 84 -
(Dro achieve equal advance and retract speeds . . . 0 because this cylinder end holds more oil than the rod end.
-- -- -- -- -- L- - -- -- -- .- --
Radial Drilling for Flow Area this flow control must have a larger opening . . .
(retract mode shown) In this circuit, we need to have flow controls that control flow in only one direction. If we had needle valves without reverse free flow checks , the setting of the flow control on the rod end of the cylinder would also control the speed of the cylinder in the extend mode, because it would be metering the oil being forced out the rod end. Likewise. in retracting, both flow controls would have a part in influencing the cylinder's speed.
0 sinc oil commg from f4\ by free the rod V flowing end can over this .---I bypass check this valve. restric tion . . . 0 only this flow control affects cylinder speed . .
The cross-sectional illustration shows a typical flow control with reverse free flow check. In this model, by rotating the outside sleeve, more or less of the radial drilling flow areas can be exposed. As you can see, flow in the opposite direc tion opens the check valve, thus by-passing the metering area in the valve.
Valve A
Valve B
As shown, valve "A" would be almost completely open in two turns of the adjustment, while with valve "B" a very minute change occurs during two revolutions of the hand-
- 85 -
knob. As shown in the graph, valve "B" requires many more turns from fully closed to fully open. Consequently, it has the
30 25
f;
20
i:i: 1 5
10 5
v V"
2 3
I L_ Valve B :J r;:,q_ (,j "' / Valve A I II -vy If I tnl 7 7 If / <"'\ J o.J : t I [7 / / / I v v 7 I J' Y l7 7 /' / / V ---- vv--""' ___.17' Y_.,_,- !..- .,.
1/
Q,
o.:, _ \.
II
l'V
Q.
II
6 5 Throttle Position
8 (no. of turns )
11 10 Valve A Valve S -
12
..
Since. in most applications, we want to control the speed of the actuator in both directions, the logical place to install the flow controls is in the lines supplying the actuator from the directional control . For piping convenience, dual flow con trols with reverse free flow checks are available for sandwich mounting between the directional control and its subplate. These valves are usually non-pressure compensated.
As shown in the cross-sectional illustration, the pressure supply (red) and the tank return (blue) from the directional e valve are allowed to pass through the valve unrestric d. In the illustration of the top view of the valve, you can se e that flow control is achieved when the poppet's position is ad justed laterally to cause a partial blockage of the "A" and "B" cylinder lines.
- 86 -
A PB To Actuator
_[ 0
This poppet is backed off, so there is little resistance to flow in its cylinder passage.
0 a partial blockage occurs in this passage, which increases the resistance to flow. Top View of Sandwich Valve
Since space is at a premium with sandwich mounted valves, the poppet which controls flow in one direction also serves
- 87 -
holds the poppet in the passage, which causes the flow control function.
than it is here.
the pressure is higher here . . . Since a pressure drop always exists as oil flows across a restriction . . . while the return passes unrestricted through the valve.
__ .
----,
You will notice that, when the directional control is shifted to cause the cylinder to retract, the conditions of pressure on the flow control poppets are reversed. This allows an in dependent speed adjustment in the retract mode. As shown, we are metering the oil being supplied to the cylinder. This is commonly referred to as meter-in. For directional controls
with symmetrical porting patterns, the position of the flow control can be reversed by 1 80, so that the oil returning from the actuator is controlled, while the supply oil enters unrestricted. Meter-in and meter-out circuits will be covered in detail later in the chapter.
- 88 -
with increased pressure at its outlet. In some flow control in stallations. it is possible that the decrease in output flow of the pump will show up as an additional decrease in speed with increasing load. Like motor leakage, pump leakage can be isolated so that it will not affect adjusted output speed. Consequently. this variable is also circuit dependent. We now want to take a closer look at ways to eliminate the variables in order to obtain the highest accuracy and/or best efficiency in speed control circuits. Since component selec lion plays only one part in overall efficiency or accuracy. a trade-off of accuracy for efficiency or vice versa is left to the designer.
ACTUATOR CURACY
EFFICIENCY
AFFECTS
SPEED
AC
The third cause of speed loss is related to the efficiency of the actuator. With most cylinder circuits. the volumetr ef ic ficiency approaches 100%. which results in very minute speed losses because of leakage in the acutator. We must. however. take into account the volumetric efficiency when we are dealing with hydraulic motors as our actuators. The motors volumetric efficiency can add to the overall speed variation with increased load. This is true because, as load induced pressure increases. we have a higher pressure drop across the clearance fits in the motor. resulting in a higher case drain flow. Since actuator leakage can be isolated so as not to affect adjusted speed. this variable is circuit dependent.
The two way pressure compensated flow control consists of an adjustable control orifice which is mounted downstream and in series with a pressure reducing valve spool. called a hydrostat. You will notice in the operational cross-section. the hydrostat is a spool type reducing valve. which ifo nor mally open. allowing the inlet of the valve to be diredly con nected to the inlet of the main control orifice. The spool is held in the open position by a light spring force. which.
- 89 -
Inlet
Hydrostat
would be no net differential force on the spool. However. by adding to the outlet pressure a supplemental spring force of 60 PSI, the spool would be in equilibrium when inlet pressure is 60 PSI higher than outlet pressure. Let us look at a situation in which a cylinder is moving a load at the rate set on the main control orifice, which has a 60 PSI differential pressure from inlet to outlet, as established by the hydrostat. The moment some of the load was taken from the cylinder, a tendency to increase speed would exist because of increased pressure drop across the main control orifice. However, the loss in outlet pressure would also be sensed on the outlet side of the hydrostat. This loss in pressure would mean a loss in force holding it in the previous equilibrium condition. Consequently, inlet pressure exerting the higher force would move the hydrostat against the spring. A movement to the left would close the flow area between the spool land and the valve housing, which would cause a higher pressure drop from valve inlet to control orifice inlet. The inlet pressure at the control orifice would be reduced only to the point at which equilibrium on the hydrostat were reestablished. The net result would be that cylinder speed remains constant, since the pressure drop across the control orifice is automatically adjusted. On the other hand, if we were to increase the load on the cylinder, the outlet pressure on the flow control would also increase. This would cause the hydrostat to move to the right, which would open the flow area between its spool land, and the valve housing. This would subtract from the original resistance to flow that was being imposed by the hydrostat until inlet pressure increased to the equilibrium condition, when inlet pressure is 60 PSI higher than outlet pressure.
ANTI-LUNGE DEVICE
An undesirable operating characteristic of pressure com pensated flow controls often occurs when the flow control is mounted in the actuator supply lines from the directional control. Under these conditions, when the directional control is centered, it is possible that the inlet and outlet of the flow control could be at zero pressure. In a static no-flow con dition, the spring would hold the hydrostat in the fully open position. If the directional valve were energized for a short time period, too much flow and pressure potential would be exposed at the inlet of the control orifice. since the hydrostat could not respond fast enough from its wide open position. The net result would be that the cylinder lunged forward uncontrolled during the time period necessary to establish equilibrium on the hydrostat. The response of the hydrostat is dependent on the oil volume downstream of the flow control and can range from 60 ms to over a second. This characteristic is plotted on the velocity time graph below:
- 90 -
Set Velocity
Time
Also, in actual application. the condition is more severe when a low flow setting is adjusted on a relatively large valve. This is true because. under these conditions. the hydrostat has to be displaced further to achieve its equilibrium con dition for a low flow state. To eliminate or drastically reduce the lunge. pressure com pensated flow controls can be supplied with stroke limiters o the hydrostat. which are commonly referred to as anti n lunge adjustments. The theory behind their function is that if we limit the stroke of the hydrostat to its maximum open position during dynamic operation. when the flow control goes from no flow to dynamic operation the initial pressure drop will exist because of mechanical positioning of the spool. Likewise. the spool displacement to achieve equilibrium. under anv slower operating condition. is shortened. This reduces the response time of the valve.
just reestablished.
LOCKING ADJUSTMENT
On complicated machinery. machine set-up can be a multi step procedure. Likewise. since each step in the set up sequence is dependent on the previous setting. it is desirable to preclude the possibility of unauthorized adjustments of an intermediate speed setting. On the other hand. even simple machinery. if allowed to operate at too high a speed. could endanger the operator. the final product. or the equipment it self. For these reasons. most flow control manufacturers of fer some type of locking mechanism for their flow control ad justments.
Pressure and Temperature Compensated Flow Control SETTING THE ANTI-LUNGE ADJUSTMENT
Since spool positioning can only be optimum for one flow setting. the best lunge control is achieved by setting the ad justment according to the following procedure. each time the main control setting is changed. If this is inconvenient. the anti-lunge control can be set for the maximum operating speed of the machine. The compromise is that at a lower speed setting. the lunge characteristics although reduced. are not completely eliminated.
1 . Be sure anti-lunge adjustment is backed off all the way. 2. Operate actuator at full load and set the desired speed on the main control orifice. 3. While cycling in the speed control mode under full load. tum the anti-lunge adjustment inward until a noticeable decrease in speed occurs. 4. Back off on the adjustment until the desired speed is
- 91 -
Since a key is needed to engage the adjustment mechanism. pipe wrenches. hack saws. and bolt cutters can be left out of the criminals tool kit.
RECTIF I ER SANDWICH
Any given flow setting can be achieved in both directions by using a rectifier sandwich plate. which mounts between the flow control and its subplate.
r_L
L
- /
'
Bimetallic Rod
Although the illustration is only a theoretical representation of this type of temperature compensation. you can see that the orifice must offer more of a resistance to a low viscosity fluid than it does to a colder fluid. at a h1gher viscosity. Tem perature compensation is accomplished because the bimetallic rod tends to close the orifice when it is heated and to open it as it cools. The problem with this type of temperature compensation is that the flow control is used with fluids of different viscosity indexes (see Hydraulic Principles Chapter). Although the orifice and bimetal rod could be designed for optimum per formance with any given fluid. it would be impractical to design a different valve for all the different fluids available. The result is that a compromise is incorporated. and the valve is designed for the average fluid. which makes its ac curacy fluid dependent .
- 92 -
Long Restriction
Short Restriction
pressure drop for a given amount of flow than would water. But since friction is related to length, each time we cut the length in half, the less sensitive it becomes to viscosity changes. In theory, as we approach an orifice with a length dimension of zero, we become immune to changes in viscosity. Unfortunately, it is impossible to manufacture an orifice with a length dimension of zero. We must, therefore, accept the fact that an orifice with a very sharp edge will display flow characteristics which are somewhat dependent on viscosity. In actual practice, though, we find that as we vary the temperature between 65 and 160"F the maximum variation in flow because of viscosity changes is between 1 and 1 . 5%. This accuracy is more than acceptable for even the most sophisticated hydraulic circuits.
..
with a length dimension "L". we see. through experiment a tion.that high viscosity fluids resist flowing through this orifice much more than do lower viscosity ones. This is true because of the high kinetic friction between the fluid molecules themselves, and the pipe, as they are forced through the reduced diameter for the given length. It stands to reason that if we cut the length of the orifice in half, we considerably reduce the friction and thus make the orifice less sensitive to viscosity. Of course, since we still have fric tion involved, a fluid like molasses would still require more
METER-IN CIRCUITS
Meter-in circuits are limited to applications where the load
- 93 -
always offers a resistive force. In these circuits. the piston in the hydraulic cylinder (or rotary group in a hydraulic motor) is held captive between the pressurized fluid and the load. If for some reason the load conditions change. there is nothing to prevent the load and piston from running away from the fluid being supplied to the actuator.
1 5 GPM
r L
1 GPM
S GPM
9 GPM
an increase in load causes the speed to drop . . . Without altering the setting of the flow control or relief . . . 1 500 PSI not only, because of a higher case drain leakage . . .
,.,.
1 5 GPM
because there is less flow 0 but alsothe a across needle valve due to smaller p .
7 GPM
2 GPM
6 GPM
- 94 -
we did not need all of its output flow in the first place. It does not matter whether weforcetheexcess oil over the relief valve or cause it to be leaked out the case drain of the pump. Our output speed is only influenced by the oil which passes through the flow control. On the other hand. meter-in circuits have no means of sup plying more oil to make up for increased actuator leakage with increased load. For this reason, meter-in circuits are considerably more accurate on cylinder circuits than they are with hydraulic motors. In meter-in motor circuits. the volumetric efficiency has a definite influence on the overall speed variation with in creased load. As load pressure increases. a higher pressure drop across the clearance fits in the motor exists. This in tum. creates a higher case drain flow. Even if we use a very accurate pressure and temperature compensated flow con trol on our meter-in circuit. we can see a considerable decrease in speed because of motor leakage. Remember. flow which leaks out of the case drain cannot create revolution of the motor. If a non-compensated flow control is used. the speed accuracy is considerably worse.
In circuits without actuator leakage. meter-in control is as ac
steady state flow is maintained to the actuator. This would not be the case with meter-out control. since pressure surges would have to pass through the actuator before they would be taken out by the hydrostat.
.6V
where: .6V = V= .6 P = (J =
V x .6P /3
curate as any type of flow control circuit. Likewise, when ex tremely fine feed rates are required. as found in machine tool drives. the meter-in circuit has definite advantages. Since we are talking about extremely fine control. we must discuss these circuits on the assumption that we are using a high quality pressure and temperature compensated flow control.
change in volume (in3) original volume (in3) pressure change ( PSI ) bulk modulus of the fluid
Since we are more concerned with the lunge characteristic (.6S). we can write the above formula as follows: .6S = where:
.6V
A
.6S = change in stroke (in) .6V = change in volume (in3) A = net area of piston (in2)
V x .6P
A{J
V = Vp + (A x S) .6P = .6L A
Consequently, the formula for change in stroke (lunge) can be written as follows: .6S .6S = Vp = A= S= .6L = {J =
Al fJ
lunge (in) volume in pipe (in3) net piston area (in2) stroke (in) load change (lbs) bulk modulus of the fluid
- 95 -
As suming we can calculate the change in stroke, we can also determine the change in velocity (6V), if we know how long it takes for the load to change.
6V
6S . 60
6T
6 V = velocity change (in/min.) 6S = lunge (in) 6T time for load change (seconds)
=
Let us now apply these formulas to the meter-in and meter out circuits at different stroke lengths, under the following operating conditions . Parameters: a) Cylinder 2Yz" Bore x 13/4" Rod x 36" Stroke
A, = Area of the blind end = 4.9 in 2 A2 = Net area of the rod end = 2.5 in2 S = Stroke 6S = Lunge (which can be positive or negative, depending on the direction of the load change) b) Load Change L, = Full load = 3000 lbs. = Reduced load = 1000 lbs. 6L = Load change 2000 lbs. c) Time for load change: 6T = 1 second d) Volume of oil in lines: 3/4" tubing x .049" wall x 9' length Vp = 36 in' e) Bulk modulus of the oil: {J 2.0 x 10> lb/in2
= =
METER-IN
METER-OUT
I--- s
v,
6L
+--
6L
A,
From
Pump
Vp
Vp
(4.9)1 (2.0 X l )
6V
Stroke = 1 8"
0.052" 6S 6V
x 2000 = 0 . 1 30. .
- 96 -
( 9 ( 0 X 10)5 4. )2 2.
b.V
- O 064 , .
_ '
l!.S
0 . 1 06"
l!.V
0 . 1 06 " x 60 1
6.3 in/min.
Stroke = 12" (36 + (4.9 X 12)) X 2000 = 0.039" b.S (4.9)2 X2.0 X 105 b.V 0.039" x 60 1 2.4 in/min.
Stroke = 36" - 1 2 " = 24" {36 + (2.5 X 2 4 X 2000 H l!.S 0 (2.5)2 x 2.0 x 1 5 t!.V
0 1 54"
The above calculations show that when we are extending cylinders with very precise control, metering-in to the larger uolume on the blind end of the cylinder, we considerably reduce lunge (or hesitation) as the load changes.
Meter-out circuits prevent run-away but can also create problems with excessive rod end pressure. control, as shown in the above illustration. The only dif ference is that with meter-out circuits, the flow control is mounted in series after the actuator. The back pressure created by the flow control is exposed on the annulus area of the rod end side of the piston, which captures the piston, so that it can move only at the rate which the flow control will allow. As in meter-in circuits. the load affects the differen tial pressure across the flow control in meter-out installations. With meter-out circuits, however, the outlet of the flow con trol is more or less at constant pressure (atmospheric), while the inlet pressure varies with changes in loads. Let us now take a closer look at how the load affects the inlet pressure of the flow control on meter-out applications. When the flow control is in the wide open position, it offers little or no resistance to the flow leaving the opposite end of the cylinder. The cylinder will extend at maximum speed, assuming that load induced pressure is less than the relief valve setting. Under these conditions, it would be possible for a negative load to run ahead of the pump. When the load induced pressure approaches relief valve set ting, it causes speed control to begin the moment the flow
METER-OUT CIRCUITS
A long standing rule-of-thumb in the hydraulic industry states, "When in doubt, meter-out". Unfortunately, meter-out circuits frequently created problems with cylinder damage or leakage because of rod end pressure intensification.
- 97 -
Load
Load
Back Pressure
control back pressures the annulus area on the rod end. The total force required to extend the cylinder is the force needed to move the load, plus the artifical force created by the back pressure offered by the flow control, over the net piston area of the rod end. If we reduce the load, a non-compensated flow control would allow the cylinder to increase its speed. This happens with reduced loads, since more of the resis tance to flow has to be provided by the flow control. The higher the back pressure the meter-out flow control must of fer, the higher the pressure drop across it to tank. This dif ferential pressure is amplified by the area ratio (pressure in tensification) of the cylinder. As the load decreases the speed increases more than it would with a meter-in circuit. Likewise, for a given speed, we must see an increase in back pressure when a pressure compensated valve is used.
======4=== Load
Artificial Load Created by Flow Control
Controlled Speed
the load induced pressure (2900 PSI ) is close to relief valve setting.
{!) Consequently, it takes very little back t::====::: the relief ( 1pressure) to open 00 PSI so that
it will by-pass the excess pump flow . Setting 3000 PSI
.,
___, .___. ___J
I
When this pressure and temperature compensated flow control is set to pass 5 GPM . . .
l O GPM
5 GPM
5 GPM
- 98 -
500 0 only aacrossPSI pressure drop the motor is needed to create the required torque.
G)
L...J This can double the bearing load on the motor with high pressure on both ports.
4=======:::.._..::::=:
'----1-+---J 0
5 GPM
5 GPM
- 99 -
By applying a differential cylinder to our pressure com pensated meter-out circuit, we find that pressure levels in the system can become dangerously high. With overrunning load
the intensified "push of the pump" is added to the "pull of the load" to create extremely high rod end pressures.
0 operating at
full load . . .
0) 3000 PSI is
needed to open the relief so that it can pass the excess of 5 GPM .
since it takes PSI to create the additional PSI needed in the blind end.
100
200
t
Under the above conditions, you can see that pressure levels are acceptable, and the system will operate satisfactorily and
5 GPM 5 GPM
safely. If the load is removed, our seemingly innocent PSI system, turns into a 6000 PSI hazard.
3000
(D
0 the pressure
-,
J
- 100 -
l0
1
As seen in the previous example, pressure intensification can become a serious problem, with pressure compensated meter-out circuits used on large rod cylinders. This does not preclude non-compensated circuits , or smaller rod cylinders . A non-compensated flow control would not allow the poten tial energy, in the form of pressure, to build as high, since some of the excess energy would show up as an increase in speed , due to a higher pressure drop across the orifice. Needless to say, the rod end pressure can still become dangerously high with non-compensated valves.
On the other hand. we do not have to isolate meter-out cir cuits from cylinders, since the effects of pressure in tensification are considerably reduced when using cylinders with small rod diameters. Nevertheless, since the most readily available cylinders are rated at 3000 to 5000 PSI, the possibility of pressure intensification must always be con sidered.
0 lf a one GPM
leakage occurs . . .
5 GPM
1 1 00 PSI Setting
- 101 -
set speed, is influenced by the same factors which cause speed fluctuations in meter-in circuits, namely: change in pressure drop, changes in viscosity, and changes in actuator leakage. On the other hand, both types of circuits are relatively unaffected by pump leakage. However, meter-out circuits usually experience greater speed variation when con sidering actuator leakage with variable loads.
pressure sides of the rotary group. To avoid a lengthy ex planation of the various types of motors, at this point, we will consider cross port leakage of cylinders only. We can safely assume that cross port leakage would have the same in 2 fluence on the output speed of a hydraulic motor. For J.JUr poses of clarity, our cross port leakage will be allowed via a hole drill in the piston. To explain the effects of cross port leakage with meterout control, the flow control and the leakage path by the piston can be thought of as two orifices in series . The meterout flow control back pressures the leakage path, thus in fluencing the pressure drop across it. Initially as we reduce the load, cross port leakage reduces towards zero since in creasing rod end pressure lowers the pressure drop on the leakage path. However, during low loads, no load, and overrunning load operations, the actuator leakage will cause an increase in actuator speed. Because oil would be regenerated to the blind end,
would still be less than 5 GPM, but it would be faster than the meter-in circuit.
we would have less than 1 GPM leakage, because we have a lower pressure drop across the leakage path.
- 102 -
the speed would increase when the leak occured. This hap pens when pressure intensification causes higher pressure on the rod end than the blind end, thus causing leakage to the blind end. This supplement s the supply which causes an in crease in speed. Hydraulic motors are always affected by cross port leakage
to a greater or lesser extent, determined by their efficiency. As a motor goes from no load to its full torque capability, cross port leakage causes a decrease in speed. However, since we are back pressuring the motor's outlet, the .D.P across the clearance fits is less and we get less cross port leakage than we would with a meter-in circuit.
Leakage Port
Bearing Set
compensate for any type of speed variation which occurs due to leakage downstream. In this example, if the 1 GPM leak were occurring at 50% load, the speed would drop off considerably as load induced pressure increased the .D.P across the leakage path. It is even possible that a highly inef ficient motor would stall, because there would be less resistance to flow through the case drain leakage path than would exist in trying to cause rotation of the motor.
Relief Valve
l O GPM
ct
5 GPM
- 103 -
With meter-out circuits leakage from the motors outlet port side to the case drain causes the speed to increase above the desired. An increase in leakage occurs at low loads because
a higher resisitance to flow must be created by the flow con trol. Since the speed is determined by how much oil leaves the motors outlet, the speed increases with decreasing loads.
I O GPM
l GPM
O GPM
(D From no
load . . . to full load . . .
0 GPM
5 GPM
3 GPM
l GPM
.l l t1 1 I
I I I
(j) this
- 104 -
lO GPM
_. ._ .. _. --
load
Flow through
O GPM
longer can pass over the smaller restriction in the flow con trol at load pressure, is diverted to the cylinder, causing an in crease in speed. Of course, the exact opposite happens when we open the flow control and cause a lesser resistance to flow. You can easily see that the only heat generated by this system is that which is caused by the flow across the flow control at load induced pressure. It stands to reason. that at low actuator speeds we have maximum heat generation, because of maximum flow through the flow control. The ad vantage is that with low loads we have low heat generation. as opposed to the maximum heat generation by series con trol at low speeds and low load.
Q and
motor .
_j
O GPM
'-h
little or no load
I I
@ The system
GPM
3 GPM
- 105 -
@ high load
8 GPM
increases leakage here . . . r L
pressure . . .
3 GPM
Full Load
at operating temperature . . .
1I
I
I I
2GPM
OGPM 3 GPM
and here
. . . 11
2 GPM
3 GPM
0 this
pressure compensated flow controls . They are generally better when used with cylinder circuits and highly volumetric efficient pumps.
By adding a third port, and modifying the hydrostat of the 2-way pressure compensated valve (discussed earlier in this chapter), we can obtain a completely different flow control function. Since the method of sensing and maintaining pressure drop has already been discussed, we will now con cern ourselves only with the hydrostat and its operating func tion. We said that the hydrostat of the 2-way pressure com pensated valve was essentially a normally open self regulating pressure reducing valve. This valve self-adjusts to maintain the inlet pressure at the main control orifice at a constant value (45 to 170 PSI) higher than outlet pressure. Actually, the function of a 3-way hydrostat is not that dif ferent. It stands to reason that if we can regulate the inlet pressure of the controlling orifice by reducing supplv pressure, we can also regulate this pressure by relieving the excess flow to tank. A 3-way by-pass style flow regulator is essentially a main control orifice mounted in series with the load and downstream of a self regulating pressure relief valve hydrostat. In the operational cross section, you can see that down stream pressure is sensed on one area of the hydrostat, while the inlet pressure opposes this force on the opposite, but
- 106 -
Inlet
Unloading Port
As shown in the operational illustration, the cartridge type direct operated relief has its pressure port connected to the spring chamber side of the hydrostat By limiting the pressure in this chamber, we limit the maximum force holding the hydrostat in the closed position. The moment the inlet pressure increases to the point where it will exceed this limited pressure on the downstream side, the hydrostat shifts, relieving pump flow to tank. Because of the spring on the downstream side of the hydrostat, the pump relieves at a
As shown in the following illustration, the "X" port can be used exactly like the "X" port of a pilot operated relief. When the solenoid is de-energized, the spring chamber side of the hydrostat is connected to tank, and the pump unloads at minimum pressure. Upon enerigization, we block the free flow to tank, which loads the pump and causes the normal
- 107 -
3-way function to occur. As in a pilot operated relief, the "X" port could also be used for remote pressure adjustment or multiple pressure selection (see Chapter 2).
t
3 way by-pass flow regulator pressure and temperature compensated
10,000
lbs.
10 sq. in.
10 GPM
5 GPM
- 108 -
CD A
meter-in circuit under the same conditions offers equivalent accuracy . . . 1 0,000 lbs.
0 to which we must add the heat generated1 by a 2000 PSI b.P across the flow control . 5 x
2000 x 5 =1 5000 BTU/hr.
10 GPM
5 GPM
the excess flow to tank but 0 at a passesPSI drop which heats at 3000 the rate of 1 . 5 x 3000 x 5 BTU/hr . . .
=
22,500
Assuming that our residual pressure is at a minimum, it sometimes can be isolated from the actuator by a standard check valve with a high cracking pressure. The check valve is simply mounted in the supply line to the actuator, and in troduces a 65 to 75 PSI pressure drop requirement before oil can flow towards the actuator. A better but slightly more expensive way to prevent "creep" is to use an adjustable sequence valve in place of the check valve. The adjustment capability allows the "creep" possibility to be adjusted out of the system, no matter what residual pressure may exist. Another advantage of using the sequence is that the valve will be wide open once set pressure is reached, because its spring chamber is externally drained. This means that less heat would be generated under high flow operation than would be when the check valve is used.
- 109 -
siderably more. That is, in low pressure circuits, each time we have a pressure drop across a valve. fitting, or length of pipe, the pressure drop occurs at a higher flow rate (higher horsepower loss) than it does in a high pressure circuit. The saving goes even further. Although cubic inch for cubic inch, high pressure com ponents are sometimes more expensive than are low pressure components, we must remember that high pressure components, job for job, can often be several frame sizes smaller. Likewise, smaller high pressure components have less area for internal leakage. which considerably increases overall efficiency. If, in our example, we chose a 43 GPM vane or gear pump, we would find that it has an overall ef ficiency of between 80 to 85 percent. The 5000 PSI piston pump required by the high pressure system would be over 90% in overall efficiency. Since both our circuits are doing work at the rate of 121fz HP, pump selection alone can mean a 2 to 3 horsepower savings.
a) Due to flow control 1 . 5 x 2 1 . 5 GPM x 75 PSI = 2 4 1 9 BTU/hr. b) Due to relief 1 . 5 x 2 1 . 5 GPM x 5 7 5 PSI = 1 8,544 BTU/hr. c) A total of 20,963 BTU/hr.
0
0 and would
require a pump flow of 43 GPM
43 G
At 1h speed a pressure and f4\ temperature comp ens ated v would have a load induced pressure of flow control introduces a 500 PSI . . . 75 PSI D.P . . .
- 110 -
Ci)
a) Due to flow control 1 . 5 x 2 . 1 5 GPM x 7 5 PSI = 242 BTU/hr. b) Due to relief 1 6,367 1 . 5 X 2.1 5 GPM X 5075 PSI BTU/hr. c) A total of 1 6,609 BTU/hr.
=
0 and would
0 would have a load induced 0 so our relief must be set at 507 5 PSI.
pressure of 5000 PSI . . .
High Pressure Low-Flow Circuit FLOW CONTROLS WHICH CONTROL ACCELERATION AND DECELERATION
In many applications we must avoid abrupt starting and stopping of the mechanical motion we wish to perform. To achieve this type of control, we can make use of a specialized flow control which is called a deceleration valve.
-r------.,
movement of this spool gradually closes this orifice, which causes the cylinder to slow down. Reverse free flow is permitted by this check valve Final creep speed is adjustable on this secondary throttle when the primary orifice is fully closed.
- 111 -
Deceleration valves are really nothing more than cam operated orifices. The valve is physically mounted close to the work being done, and can be piped into the hydraulic system in either meter-in, meter-out, or a by-pass flow con trol arrangement. It should be noted, however, that because of the load's inertia, meter-in circuitry with a counterbalance (or brake) valve (Chapter 2) is more often desired, in order to prevent excessive cylinder pressures. In cylinder circuits. for instance. as the load reaches the end of its travel. a mechanical cam positions the orifice in the deceleration valve to a more restrictive position. The time for the deceleration period is determined by the cam design. the velocity of the cam, and the stroke length as related to metering characteristics of the valve. As shown in the previous illustration, deceleration valves are usually tapered spools which slide in close fitting bores. Depending on the spool design. a normally open value meters flow as the plunger is depressed. while normally closed values increase their orifice size as the cam depresses the plunger. The choice of normally open or normally closed depends upon the cam design selected. It is easy to see that proper operation depends on how ac curately the cam arrangement positions the orifice. As shown in the illustration. the height of the cam is directly related to actuator speed. Likewise. the time period for deceleration is dependent on three variables, namely: cam velocity, cam angle cr, and stroke distance. Needless to say, considerable time and money can be spent in designing the mechanical linkage and proper cam for a specific installation. It becomes even more complicated if adjustable acceleration or deceleration rates are required. Fortunately, deceleration valves can be ordered with adjustment options which can facilitate cam design.
Velocity
(
This lever multiplies stroking distance by the ratio of 1:3 Variables to be considered in cam design
I
a
Sleeve
Return Spring
Primary Speed Adjustment Reverse Free Flow Check Secondary Speed Adjustment
- 112 -
The spool slides inside a sleeve, which also has a rectangular opening. In the wide open position of the valve, the rec tangular openings are lined up with those in the spool.
Primary flow adjustment is made by rotating the outside sleeves position with respect to the spool.
I
1
!: -::_-_-_ -_
I I
J - ---- 1
!: -J--J
I I I I
::-_,
: [j l
-
I
I
(' - - - I
1
....,
I
! ;
I I
I I I
I I
I I
I 1
I 1
I ' - "I I
I I
I I I
I
t
. - -= =-- _..)
c = :: :.
- 113 -
This flow control meters out of the actuator, thus controlling opening time. Energizing this solenoid opens the main orifice.
Time lminutesl
.
2 3
- 114 -
Initially. the flow control is at minimum, and the directional valve is centered. Solenoid 7, which increases speed on the flow control, is energized at the same time that the "advance" solenoid 2 is actuated on the directional valve. The cylinder will accelerate at the rate set on pilot flow control 3. Limit switch #1 is tripped towards the end of the stroke, dropping out solenoid 7 and energizing solenoid 1 . This initiates deceleration at the rate set on flow control 4. Maximum speed can be adjusted on stroke limiter 5, while kissing speed is set on stroke limiter 6. The cycle is duplicated in the reverse direction by energizing solenoid 7 with solenoid 8.
Deceleration begins with limit switch #2 in the reverse direc !ion. The particular advantage that this type of valve offers over cam operated deceleration valves is that mechanical linkage and complicated cam design is replaced simply and com pactly by limit switches. Likewise, adjustable acceleration and deceleration rates, which would necessitate a different cam angle in the mechanical system. are easily set on their respective flow controls in the pilot circle.
SYMBOLS
SYMBOL
'--./
EXPLANATION
,-
'
L_
.i
Lc)- _j )( )
J ;f'
---,
I
Adjustable orifice with reverse free flow check; not pressure or temperature compensated.
-
I
Dual sandwich flow control, with reverse free flow checks; not pressure or temperature compensated.
- 115 -
Meter-in orientation
-
_
_j
Meter-out orientation.
S implifi ed
-+-+- Jl f2_ _
----=lF--- t -41 ,
Sharp edged orifice with reverse free flow check; temperature, but not pressure compensated.
Detai led
r - - - - -,
0---'_ j
I
- 116 -
Simplified
Bi-metallic Rod
1>---_j -'
Pressure and temperature compensated restrictive type flow control, with reverse free flow check.
Simplified
. ILJ-
L!_j
----r--- I
*]
_j
or
L__
Detailed
Ll.J
- - - -
) I( I ""1
- 117 -
Detailed
- --- -
---
L_
I
-rL_
-
_ _
zy
J_
I -e -1
I I
NORMALLY OPEN
NORMALLY CLOSED
_j
Pressure and temperature compensated by-pass style flow regulator, with integral pilot relief.
DECELERATION VALVES
r - - -,
I
.
,.
.
With primary flow adjustment, secondary flow control, and reverse free flow check.
ri l:
_____
With primary and secondary flow adjustment, without reverse free flow check.
With secondary flow adjustment, only with reverse free flow check.
r.
-+-......-!+-- >it-+-+- II
j - - --
.
- 118 -
Hydraulically actuated pressure and temp erature compensated, restrictive type flow regulator, with reverse free flow check, opening and closing time adjustments, directional control, and maximum and minimum flow limiters.
CONCLUSION
In this chapter. we have covered the construction and operation of various flow control components. along with their applications in various types of installations. A good general knowledge of flow controls and their applications would include an understanding of the following points:
Pressure as resistance to flow. Non-compensated valves. Pressure drop across a n orifice. Needle valve. Reasons for reverse free flow checks. Adjustment sensitivity. Sandwich mounting flow controls. Variables affecting accuracy of speed setting. Restrictive type pressure compensation. By-pass type pressure compensation. Hydrostat.
Anti-lunge adjustment. Methods of achieving temperature compensation. Meter-in, a nd its merits. Meter-out, a nd its merits. By-pass circuits. Heat generation. Pressure intensification. Higher efficiency through higher pressure. Acceleration and deceleration control. Symbol terminology.
- 119 -
CHAPTER 4
CHECK VALVES
Check valves are one of the easiest understood components in the hydraulic industry. In fact. in Chapters 2 and 3 we have already mentioned their use. without fully explaining their function. However. we must not let simplicity of a check valve detract, in our minds. from its importance to the hydraulic system. Although check valves are normally used to control the direction of fluid flow. their operation and possible applications are similar to those of a direct operated relief. This chapter will be devoted to an explanation of operation and application possibilities for both check and pilot operated check valves. We will then cover prefill valves and logic elements. which are speciality components related to the basic check valve function.
The operating principle of the simple check valve is quite similar to that of the direct operated relief. as discussed in Chapter 2. As shown in the cross-sectional illustration, the check valve consists of a stationary seat, a moveable poppet, and a spring. The valve is closed against flow until pressure at its inlet. working over the exposed area of the poppet. creates sufficient force to overcome the spring. Once the poppet is forced from its seat. the flow of hydraulic fluid is around and through the poppet to the outlet of the valve. It is interesting to note that the valve remains closed. except when there is sufficient pressure and flow potential at its inlet. For instance, we said in Chapter 1 that the moment flow stops. pressure in all parts of the hydraulic system equalizes under the principle of Pascal's Law. As pressure equalizes. the hydraulic forces on both sides of the poppet are nearly equal. We say nearly. because the valve actually closes when pressure at its outlet. plus spring force. equals inlet pressure. In actual application in a static system. the pressure at the outlet is lower than the inlet pressure. in the amount equal to the cracking pressure of the valve. Ideally, this means that we can capture a pressurized column of fluid between a stalled actuator and a check valve. Of course. we must assume that the cylinder is perfectly rigi when stalled. We must also assume that there is no leakage in either the actuator or the valve itself. In addition to being similar in operation to a relief valve, a check valve can also be used to control the direction of flow. You can see that the example (page 4-2) would have little practical use. because the check valve would never allow the return of the cylinder's piston. Actually. the more we tried to force oil backward through the check valve. the harder we would press the poppet into its seat. In the hydraulic in dustry. when we refer to this non-return feature. we call it checking reverse flow.
- 121 -
'l
0 as outlet pressure . . .
this light spring closes the poppet.
poppet is usually considerably harder than its respective seat. In the closed position. hydraulic pressure forces the poppet into the seat. thus forcing the seat to assume the exact contour of the poppet nose. This guarantees a metal to metal contact around the full circumferential contact area. virtually eliminating the possibility of leakage.
The basic check valve. like the direct operated relief. is available in ball. poppet. or guided poppet designs. However. since check valves incorporate a relatively weak spring. they cannot produce the same high performance characteristics as a relief nor are they intended to do so. For this reason. we normally are not too concerned with the stability or pressure override characteristics of a check valve. Nevertheless. there are two reasons w h y a guided poppet check valve is usually preferred. The first reason is that guided poppet designs have a con
DESIGN VARIAT I O N S
- 122 -
siderably longer life expectancy. This is true because the poppet always contacts the seat squarely. and in the same position . By protecting the contact area in this manner. the leakfree life of the valve is greatly extended. Likewise. most guided poppet designs limit the stroke of the poppe t . This. of course. prevents over-stressing and breaking the spring. The second reason for choosing a guided poppet check becomes apparent when the valve is subjected to high flow rates. In the unguided models. the high flow rate causes the ball or poppet to chatter in the flow stream. creating a source of noise in the hydraulic system. This does not occur in the guided poppet design.
Return line filters and heat exchangers usually have a low pressure rating.
0 This valve protects the low pressure housings from over pressure . . .
clogs either of these components, 0 If dirtincreased resistance to return flow . there is an .. by bypassing flow to tank, when inlet pressure reaches 7 5 PSI.
- 123 -
precaution must be taken in checking the valves pressure versus flow characteristics. and sizing the component ac cordingly. For instance. a check valve which cracks at 75 PSI may provide a 1 50 PSI resistance to flow when passing 10 GPM. This. of course, could damage a heat exchanger. if it had a shell pressure rating of 100 PSI.
NO SPRING VERSIONS
The third option is to obtain a check valve with no spring at all. The use of these valves, however, should be limited to applications where the check valve function is required, with an absolute minimum resistance to flow in the free flow direction. A foot valve for facilitating pump priming, although not required for most hydraulic pumps, is a typical ap plication.
If your system requires the use of a check valve without a spring, the valve should be mounted with its outlet vertical and upward. When it is mounted this way. gravity will assist in closing the poppet. Needless to say. if it is mounted in any other position. the only available closing force would be that of the dynamic flow of fluid. It is possible that the valve would remain open if it were subjected to relatively low re verse flow rates. especially if the inlet were to be mounted vertically and upward.
Line Mounted
Check valves and pilot operated checks are available with in-line threaded connections up to 1 Y line sizes. Above z" 1 Y they are supplied with flanged connections for pipe z". sizes up to 6". Usually, line mounted valves are stamped with an arrow on their housing which indicates the direction of free flow.
This centrifugal pump must have its inlet full of oil before starting.
Subplate Mounted
For service convenience, or for custom manifolding, the
- 124 -
check valve unit can also be supplied in a housing for use in subplate mounting. Subplate mounted valves up to 1 W' are ataiJabJe w ith mounting configurations which conform to ANSI/NFPA and International Standard interfaces. Above 1 w the valves are designed specifically far custom manifolding since there are no standard interfaces for the larger valve sizes. Also, for simplified installation, check valves are available in sandwich housings for mounting be tween the directional control valve and its subplate. These sandwich units can be supplied with check functions in one or more of the port connections to the directional control valve. with either direction of free flow.
CARTRIDGE UNITS
A
The pilot operated check performs the same function as the simple check valve in that it allows free flow in one direction and checks reverse flow. Like the simple check, it can also be supplied with different springs for various cracking pressures. In contrast to the simple check, however, a pilot operated check can be piloted open when a reverse flow is required. As shown in the illustration, the valve has two distinct sec tions: the check valve section and the pilot section. The check valve allows free flow from port A to port B, while checking flow from B to A, sealing without leakage. When it is necessary to allow a flow from port B to port A, the valve can be piloted open by supplying a pilot pressure signal at port "X". Pilot pressure works over the area of the pilot piston, and forces the piston rod against the check valve poppet. This unseats the poppet, allowing free flow from port B to port A .
lnline Cartridge
In addition to inline, subplate, and sandwich mounted valves, cartridge units are available for installation internally in custom manifold blocks. The cartridges are supplied with seat, poppet, and spr ing in two configurations. These two different cartridges are available for design convenience, with one style for use in an inline passage, and the second style for use in passages which meet at right angles.
PILOT RATIO
In working with pilot operated check valves, you will have to consider the pilot ratio of the valve. The pilot ratio is
- 125 -
DECOMPRESSION FEATURE
In order to determine the pilot pressure requirements of the valve more accurately. we can first total up all the forces which tend to close the poppet. In the same manner, we can also add up any constant forces which aid in opening the poppet. Then, by assuming that the closing forces are greater than the opening forces, we can subtract the one from the other, and determine the additional opening force required by the pilot piston. By distributing this force over the area of the pilot piston, we then determine the pilot pressure requirements. Although there are other forces which tend to close the main poppet, the major closing force is caused by pressure at port B. exposed over the effective area of the main poppet. In some applications, such as in press circuits, the pilot pressure requirements can be reduced by bleeding off pressure behind the main poppet before opening the main flow path. This loss of pressure before opening is referred to as decompression and can easily be accomplished by using a valve with a two stage poppet.
basically a comparison of the effective area of the pilot piston with the effective area of the check valve poppet, which is being pressurized by the system. When you are estimating the pilot pressure needed to open the valve. remember that the pressure at port X is simply the pressure at port B divided by the pilot ratio. In our example. the pilot pressure requirements would be:
Pp
3 000 PS I = 7 50 PS I 4
'\
It must be mentioned that the above formula can only be used to estimate pilot pressure conditions. As will be shown later, the pilot pressure requirements are closely related to the actual application in which the valve is used. It is im portant that pilot pressure not only be sufficient to open the valve fully, but also to keep it open during the required por tion of the cycle. However, we will postpone further discussion of pilot pressure requirements in the system until we introduce two other important construction details .
A two stage poppet is nothing more than a smaller decom pression poppet built into the main poppet. It takes con siderably less force to open this decompression poppet, since it has less effective area exposed to the pressure at port B. As will be shown in our discussion of pilot operated check valve applications, the decompression feature is quite im portant when it is necessary to release the stored potential energy in a pressurized volume of fluid.
to overcome pressure a t port B . . . small ( working over the the effective area of decompression poppet. . {,;\ this ptston has only enough force . . . \!:)
To Tank
can no longer resist the force created by pilot pressure working on this area.
(i}
- 126 -
When we study the illustration, we will have enough in formation to determine more accurately the pilot pressure requirements for internally drained valves. We can do this simply by comparing opening forces to closing forces, with the following formula:
P -
Ps - PA + pA + C Area Ratio
Since C differs for different valves, this constant factor is usually given by the valve manufacturer. If no value is available, it is usually safe to'a-ssume that C is equal to or less than 75 PSI. We said earlier that the area ratio of the pilot operated check valve is the comparison of the area of the pilot piston to the area of the check valve main poppet. For valves with two stage decompression poppets, the increased ratio of the pilot piston to decompression poppet can be used only if the cir cuit allows a decay in B port pressure once the decom pression poppet opens. In actual application, internally drained pilot operated check valves must have the A port connected directly to tank when
0
area . . .
- 127 -
/<
operates at reduced speed by causing some oil to pass over the main system relief.
From Pump
1_ ---J
operating in the piloted open condition. If. for instance, we back pressured the A port with a meter-out flow control. the check valve could open and close erratically as the cylinder was extended. This. of course. would cause the actuator to stop and start with an undesirable jerky motion. You can see from the two examples that the circuit will oscillate automatically between the open and closed positions of the pilot operated check. To avoid this com plication, we must place the flow control on the B side of the valve. or use a n externally drained pilot operated check.
0J and givi
3
In many applications , proper operation is obtained simply by draining the rod end of the pilot cylinder to the tank separately. Being isolated from the pilot piston, the A port can now be pressurized by using a flow control or coun terbalance valve. The pilot piston is spring returned to the closed position when pilot pressure is released, and the spring closes the check valve poppet. In some applications, however, accelerated closing can be achieved by connecting a 4-way directional control to the X and L ports of the pilot section. In powering the pilot cylinder
to its retracted position, more force is available to displace the oil which must be moved out of the pilot cylinder's blind end. However, this method of pilot operation can only be used with valves which can accept an operating pressure on their drain port. The operational illustration shows that the pilot piston is hydraulically moved out of the path of the main poppet, so that full spring force is available for closing the valve. This should not be confused with a pilot to close check valves.
control is in this
.. 0 since this piston is moved out of the way .-- and does not resist the force of this spring. G) pressure here . . .
CALCULATING PILOT PRESSURE FOR EXTERNALLY DRAINED VALVES
In determining the pilot pressure requirements for an ex ternally drained valve, we find that residual pressure in the A port actually helps open the valve. Assuming a negligible pressure in the L port during valve opening, the pilot pressure formula for externally drained valves becomes:
p b (A I ) + p . (A 4 -A d
A3
--
+c
or Pb - P +p A4 +C A3
-----
Area Ratio
--
As in the internally drained model, C is a constant factor which usually can be assumed to be 75 PSI. Also, the area of the decompression poppet can be used in determining the pilot ratio, only if a decay in pressure occurs at port B after opening the decompression poppet.
APPLICATIONS O F PILOT O PERATE D CHECK VALVES Opening Forces Must Equal Closing Forces
Basically, the pilot operated check valve is used in a hydraulic circuit to perform one of two basic functions. In
- 129 -
Possible Load Conditions Which Require a Pilot Operated Check for Positive Holding
either case. the intended operation depends on its use with a high quality hydraulic cylinder with leak free piston sealing. Let us now consider the pilot operated check valve in each of its two basic applications: in load holding. and in decom pression type hydraulic press circuits.
Load
decompression poppet, since load induced pressure would not decay once the first stage poppet opened. That is. if we only supplied enough pilot pressure to open the decom pression poppet, the load would move downward only at the rate oil could flow through the small decompression flow area, at a pressure drop of 3000 PSI. Throughout the stroke of the cylinder, 3000 PSI load induced pressure would be
- 130 -
When this side of the cylinder reaches 1 075 PSI . . . From pump
Load
0 which is turn
maintained behind the main poppet. Consequently. to assure full opening. we must use the full area of the main poppet. In our example. let us assume the pilot ratio is 3 : 1 . so that our pilot pressure calculation will be as follows:
P 1,
Pp =
Our tvpical circuit is designed so that when we want to move the load downward. pump flow will be directed to the top of the cylinder. and to the X port of the pilot operated check. Initially. the load will not move. since pressure on top of the cylinder piston will not be high enough to pilot open the check valve. However. since the supply oil has nowhere to go. pressure will build rapidly both on the blind end of the cylinder and the X port of the valve. We will find. however. that the load still will not move when pressure on top of the cylinder reaches 1075 PSI. or the pressure level at which the check valve was supposed to open. On closer examination. we will see that as pressure is being developed on the pilot port of the check valve. it is also in creasing on the B port of the valve. If we looked at the pressures in the system. just before the 1075 PSI pilot pressure was reached. we would find that. due to in tensification of pressure across the main cylinder. B port pressure has increased to:
By the time we reach a pilot pressure of 1478 PSI. the B port pressure would increase the pilot pressure requirements even further. At first glance. it appears as if we have a condition in which the pilot operated check valve will never open. Nevertheless. if we successively calculate pilot pressure. and its effect on pressure at the B port. we will find that we eventually reach a point of equilibrium. What happens is that for each increase in pressure the force caused by the pilot section of the check increases more than the force caused by the pressure in tensification of the cylinder. This is true because the pilot section has the larger area ratio. To avoid lengthy calculations. we can determine the point at which the valve will open by using the following formula:
---- =
1 720 PSI
(1 -
- 131 -
P b = L.P. + P, (AR c )
p-
LP - P. +P. +C AR .. AR c - ( 1 - - -=Where
25)
Where: P, LP A R, A R, C P., Pilot pressure required (PSI) = Load-induced pressure (PSI) = Pilot piston to main poppet area ratio of the pilot operated check. = Blind end to rod end area ratio of the cylinder. = Constant factor of pilot operated check (PSI) = Residual pressure at A port of the valve (PSI)
=
AR,= Blind end to rod end area ratio of cylinder. In our example. it looked. at first. as if 3000 PSI components would adequately handle the job. Nevertheless. our pressure calculation indicated that 5000 PSI components were required. If. however. pressures are calculated to be in ex cess of readily available components. several options are left open. First. we can choose a pilot operated check valve with a larger pilot piston to maintain poppet ratio. Or. second. we can select a cylinder with a smaller area ratio. Also. by selecting a large cylinder bore. we can reduce the required
Once the pilot pressure point at which the valve opens has been determined. it will be necessary to check the pressure at the B port just before the valve opens. In many cases. you may find that it considerably exceeds the pressure rating of the components you initially intended to use. For example:
\
VALVE TYPE
APPLICATION
LP - P . --- + P . + C AR .. - - -= - = - - -:- - AR,
LP - P.
\
pp
AR
+ P.
AI A _.,
+C
(1 - - )
AR ,
(1 and P
AR,
AR .. '
and
.....
Load Load P, LP - P . AR ,
= LP + P , (A R , ) LP - P . A R ._. A4 P-+C . A1
}
---
+ Pd + C
= ------(1 1
(AR .. ) (AR c l )
pp
=_ _ _ _ _ _ _ _
( H - (AR..) (AR c )
)
--- +
and
and
AR < = Blind End Area 7 Rod End Area AR .. = Pilot Piston Area 7 Main Poppet Area
- 132 -
load induced pressure. The condition described also occurs when we use a pilot operated check valve on the blind end of a hydraulic cylinder. However, under these conditions, the area ratio of the cylin der works with, rather than against. the valve opening. At this point, we will avoid lengthy discussions of internally drained valves used on the blind end, or of externally drained valves used on the rod end or the blind end of a cylinder. We will simply list the formulas for each, and let the reader come to his own decisions by working through each application ac cording to the previously described process.
operated check also indicates that we must prevent the load from overrunning. Unfortunately, a pilot operated check valve opens at the required pressure and closes the moment pilot pressure is lost. The valve has no means of modulating a flow orifice to prevent the load from free falling. If some method of preventing the load from running ahead of the pump supply is not provided, the valve will open and close erratically as the load is lowered. In order to overcome this problem, load holding pilot operated check applications should always incorporate either a counterbalance valve (Chapter 2), or a meter-out flow control (Chapter 3). Remember, with an internally drained pilot operated check valve, the resistance to flow must be added upstream of the valve's B port. Likewise, with a remotely piloted or externally drained counterbalance valve, the valve must be used downstream of an externally drained pilot operated check. If it is used between the ac
With no resistance to flow here . . . creating a bigger volume here than can be supplied by the pump.
From Pump
D.
Load
To Tank
- 133 -
tuator and a pilot operated check, there would be a leakage path to tank (Y port) or to the opposite side of the actuator (X port), which would allow the load to drift.
you can choose. However, only a few of them are suitable for use with pilot operated checks. The reason is that the direc tional control must, at the very least, vent the X port to tank in its center position. This will allow pilot oil to escape from the blind end of the pilot piston, so that the piston can return from its previously open position. The main poppet can then close, preventing drifting of the load due to gravity. When a pilot operated check is used with the wrong direc tiona! control, the load may sometimes drift upward against gravity. This happens when a leakage path is established from the high pressure pump circuit, across the directional valve, through the free flow direction of the pilot operated check valve, to the actuator. To prevent this possibility, we suggest that you select a directional control which also vents the A port of the pilot operated check in the load holding position. With both the X and the A port vented, load holding is assured by the free movement of the main poppet.
AND
PILOT
You must be cautious when you ue the pilot operated check valve in applications where the actuator is exposed to changes in temperature. Such exposure can take place, for
0
0
the pilot piston is vented . . . cannot build pressure here . . .
- 134 -
example, in mobile equipment sitting idle on a hot summer day, or in industrial cylinders on furnace doors. In these kinds of applications, the increase in ambient temperature causes the hydraulic fluid to warm up. Of course, as the oil is heated, it has a tendency to expand. The problem is that a pilot operated check seals leak free, leaving no room for expansion in the captive column of fluid. This, in tum, increases the pressure in the fluid to the point where it will move the load in order to prov ide more room in the actuator for the expanded fluid. Needless to say, if the motion of the load is obstructed, the fluid pressure will sim ply increase until something breaks. To avoid damage to either the load or the hydraulic system, because of possible changes in ambient temperatures, it is good practice to install a port relief between the pilot operated check and its actuator. To prevent the load from drifting under normal operating conditions, the relief should be set somewhat higher than maximum load induced pressure, and it should be a leak free direct acting poppet design. Since expansion rates are usually relatively low, a thermal relief normally does not have to relieve high flow rates. Consequently, a ':!.!" or Y relief is normally adequate. z"
As a convenience item, particularly for load holding ap plications, a dual pilot operated check valve sandwich is available for mounting between the directional control valve and its subplate. As shown in the operational cross section, the valve housing incorporates two check valve assemblies with a single pilot piston common to both. In the center position of the directional control , both sides of the pilot piston, and the nose area of both check valve pop pets, are vented to the tank. The cylinder is positively locked against motion in either direction, since the check valve pop pets are close and capture a column of fluid on both ends of the actuator.
A, 6
B,
A A
SANDWICH MOUNTED DOUBLE PILOT OPERATED CHECK VALVES
'V B
- -
When the directional control valve is shifted into a position, which causes the cylinder to advance or retract, pump flow is directed to either the A, or B, port of the valve. At the same time, it connects the opposite side of the pilot piston to tank. As shown, pump flow over one of the check valve pop pets establishes a flow path to the actuator, while, at the same time, it exposes pressure to the full area of the pilot piston. When sufficient pilot pressure is achieved, the other poppet is piloted open, and the actuator motion begins . I t i s important to note that sandwich mounted dual pilot operated check valves are influenced by the same factors that determine pilot pressure requirements and the proper operation of internally drained pilot operated check valves. Consequently, the built-in two-stage poppet does not reduce the pilot pressure requirements in load holding applications, but it serves to allow for smoother acceleration of the ac tuator during opening of the check valve poppet.
Directional Valve
- 135 -
G)
holds approximately 1 05 gallons of oil at 5000 PSI. the pressure decays gradually . . . 5000 PSI to open the decompression poppet . . .
h ::z::l a
If the pilot pressure . . . as the extra 5 gallons pass through the decompression orifice.
In press applications, a major problem arises from the fact that oil is not perfectly rigid. Actually, for each 1000 PSI in crease in pressure, mineral oil reduces its original volume by / approximately 1 2 percent. It takes energy to moue this oil in to a smaller space. Although part of this energy is wasted in the form of heat given off during compression, most of it is stored in the pressurized fluid. This storage of energy is iden tical in principle to the manner in which potential mechanical energy is stored in a compressed spring.
Let us assume that we have calculated the captive volume of fluid in our system, and found that between the piston of the ram and the poppet of the pilot operated check we have a 100 gallon volume of pressurized fluid. Using the 1 % figure, there would be an additional 5 gallons of compressed oil in our system at 5000 PSI. Of course, these 5 gallons of pressurized fluid represent stored potential energy. Let us now consider what happens as this energy is released. In the above example, the stored potential energy in the com pressed fluid is released gradually as the 5 gallons are bled through the decompression orifice. If you were to watch a pressure gauge as the decompression poppet was opened, you would see a gradual decay in pressure from 5000 PSI to zero . What is actually happening is that pressure is forcing the compressed fluid to flow across the area of the decom pression poppet. The pressure reaches zero the moment the last of the compressed fluid is forced through the orifice. At this point, we could then open the large poppet area and let the rest of the 100 gallons of pressureless fluid return to the tank during retraction of the cylinder. Needless to say, in this examle, the stored potential energy is converted into heat as the 5 gallons flow across the decompression orifice. The amount of heat generated is equivalent to the initial potential energy of the system. Since the pressure decays while the compressed fluid is
Although mineral oil actually compresses only 1;2 percent by volume per 1000 PSI, it is safer to estimate this compression at 1 % per 1000 PSI. This margin of safety compensates for mechanical stretching of the press frame and aeration of the hydraulic fluid. Needless to say, the more air entrained in the fluid, the more compressible it becomes.
tional to the initial volume of oil and pressure in the system. It is relatively easy to calculate the volume of fluid being held under pressure in the ram. Likewise, we can estimate with reasonable accuracy the volume of fluid in the pipe between the main ram and the pilot operated check. By adding the two volumes, we obtain the final volume of pressurized fluid. Assuming that we know the pressure at which the system will operate, we can now calculate the increase in oil volume obtained as we lower the pressure to atmospheric con ditions.
- 136 -
released, the average pressure can be assumed to be 2500 PSI. This means that the initial potential energy was ap proximately:
5 Gallons x 231 in.' x 2500 lbs. x ___!_1L 12 in. Gallon in.> 240,625 Ft.-Lbs.
=
778
You can easily see that some heat is developed as the press circuit decompresses. The fact is that the smaller the decom pression orifice, the longer it takes to transform the potential energy. On the other hand, the larger we make the decom pression orifice, the faster the potential energy is trans formed. The actual time required for decompression can be calculated from the following formula:
_ -
A (6.3 X 10)
v ff
Where: T = Ttme (seconds) V = Volume of compressed fluid (in3 ) A = Area of decompression orifice (in') (6.3 x 100) = Conversion constant P = Initial system pressure (PSI) (Note: This formula assumes an orifice coefficient of .6 with a fluid having a specific gravity of .895 and a bulk modulus of
In order to avoid the detrimental effects of decompression, we must allow time for the potential energy to be converted into heat. In addition, we can use a short pipe between the pilot operated check and the tank, so that there is no large oil mass to accelerate. In this way, the oil column becomes the weakest link, and prevents overstressing of the piping.
(D
If pilot pressure . . .
creates enough force to open the main poppet . . . explodes with a damaging effect into the system here. working over this area . . .
- 137 -
time.
Initially, pressure here . . . relaxes the output force . . . working over this area . . .
0 to open
0
From Pump
which opens the decompression poppet against the initial preload pressure . . .
- 138 -
In the illustrated circuit, preloaded pressure is bled from the blind end of the cylinder once the decompression orifice opens. When preload pressure drops to the point where it can no longer balance main system pressure working on the rod end area of the cylinder, the cylinder begins to retract. Its speed is limited by the amount of flow which is allowed to pass over the decompression orifice. In functioning like a meter out flow control (see Chapter 3), the back pressure in the blind end is at the level necessary to resist the flow en tering the rod end of the cylinder, up to the point at which the main system relief is opened. Assuming no load on the cylin der, this back pressure can be determined simply by using the area ratio of the cylinder. We are now faced with the fact that our pilot pressure must also be high enough to open the main poppet against this residual back pressure. By now, it should be apparent that the design engineer must be aware of what is happening at the 8 port of the valve whenever a pilot operated check is being piloted from the line supplying the opposite end of a cylinder actuator. It is im portant to realize that decompression circuits, alt hough dif ferent from load holding circuits, can be influenced by pressure conditions on the opposite end of the actuator. In reference to our previous circuit, let us assign some arbitrary values and then calculate our pilot pressure requirements.
P b = 0 + 3000 PSI
Consequently:
1 - = 2575 PSI 1 . 1 65
Pb - P ARv
v
Where AR becomes 3 :
Parameters: Cylinder: 4" 0 bore x 1 1/2" 0 rod Cylinder: area ratio: 1 . 165 : 1 Pilot piston to decompression poppet area ratio: 1 2 : 1 Pilot piston to main poppet area ratio: 3 : 1 Main system pressure: 3000 PSI Preload pressure: 3000 PSI P. = O PSI Lp = Load induced pressure = 0 P = Pump pressure (PSI)
Initially, the pilot pressure must be high enough to open the decompression poppet against the preloaded pressure, or:
This means that for satisfactory operation of our previous circuit, the optimum setting of our pressure reducing valve would be the higher of the two figures, or 933 PSI. At this pressure, the pilot piston would fully open the decom pression poppet, but would stall against the main poppet until 8 port pressure decayed to the 2575 PSI level. If the pressure reducing valve were set any lower than 933 PSI, only the decompression poppet would open, never allowing the cylinder to retract at full speed. Likewise, if the pressure were set higher than 933 PSI, the main poppet would open sooner, which would increase the decompression shock. You can easily see that by adding a load induced pressure during retraction of the cylinder, you would also cause a change in your optimum pilot pressure. This, of course, makes pilot pressure adjustment a somewhat sensitive operation. In most press application s, the pilot oil for the pilot operated check valve is taken from a separate pilot source, or from the rod end of a cylinder with a large area ratio. In fact, most press circuits use separate "kicker" cylinders to push back a single acting ram. In these applications, the transmittal of pressure across the actuator's piston is so insignificant that the formulas for calculating pilot pressure reduce simply to:
Pu - P +p ARv
+C
12: 1
However, when the cylinder begins moving, and we want to open the main poppet, our pilot pressure requirements become:
pp
Where:
+ P . +C
P P = Pilot Pressure (PSI) P b Preloaded Pressure (PSI) P . = A Port Pressure (PSI) Pilot Piston area divided by decompression poppet AR area
= v =
- 139 -
USING A
Pb - P A 4 + p ( - ) +C A3 AR
v
A second, sometimes preferred method of adjusting decom pression is to control the speed of opening by using a meter in flow control to the valve's X port. The advantage of this method is that the adjustment is time related, and is somewhat less sensitive that the force balancing method of pressure controL By simply putting a flow control in series with the valve's X port, we can sZverely restrict the speed at which the pilot piston first opens the decompression poppet Then, at some later time, the piston contacts and opens the main poppet The time period between contact with the nose of the decompression poppet and contact with the main pop pet allows for decompression of the cylinder.
75 PSI
0 0
- 140 -
control controls the speed of the pilot piston . . . This adjusts the time period for decompressing this fluid.
When this method is not used, the valve may not close quickly enough when the circuit is required to build tonnage. Actually, with a standard pilot operated check valve, the only force available to move the oil out of the pilot section is that of the spring behind the main poppet. This force, when distributed over the full area of the pilot piston, may not generate enough pressure to open the reverse free flow check valve of the flow or pressure regulator in the valve's X port. Needless to say, the closing time of the main poppet can be severely restricted.
is 50 or 16.6 PSI.
and this pilot the maximum pressure which can be created by the spring here . . .
- 141 -
PREFILL VALVES
In addition, prefill valves include a housing design for mounting directly into the body of the cylinder with which the valve is used, and a single acting spring returned pilot piston.
. .
As the ram is being prefilled, the inlet is subject to the same conditions that exist at the inlet of a hydraulic pump (Chap ter 1 ) . This means that proper sizing of components and lines is of utmost import ance for the proper operation of the system. The problem is that if the inlet is undersized, the flow rate is not high enough to fill the cylinder completely as it is extended. When the ram meets its resistance, too much time is required to finish the prefilling cycle so that tonnage can be developed. We have found the following facts helpful in achieving the proper applications. First of all, a 14" prefill valve means that the minimum flow area through the valve is equivalent to an orifice with a diameter of 14". This is not always true for standard pUot operated check valves, where the actual flow area can be somewhat smaller than the nominal port size. Consequently, for prefill valves, we can calculate our oil velocity from the formula given in Chapter 1 .
The operation of a prefill valve is identical to that of a standard pilot operated check. As shown in the cross sectional illustration, the valve allows a free flow of oil from port A to port B. You can achieve reverse flow through the valve by supplying a pilot pressure at port X sufficient to open the main poppet. The major difference between a prefill and a pilot operated check is that a prefill is only capable of handling high pressure on its B side. The high pressure capability on the A port is replaced with a larger low pressure housing, which of fers less resistance to flow in the free flow direction. Like wise, the cracking pressure in the free flow direction is ap proximately 3 PSI, which is considerably less than the cracking pressure in a standard pilot operated check valve.
Namely. v
GPM X 0.3208 A
Where: V = oil velocity in F.P.S. A = flow area in square inches In 99% of all press applications, the minimum height of the oil level in the reservoir is aboue the top of the ram. In these flooded suction applications, we have found that proper prefilling will normally occur as long as the oil velocity is kept below 1 2 F.P.S. for mineral oil or 8 F.P.S. for phosphate
- 142 -
causes prefilling of the main ram with a high flow rate here.
,-:c,
I
When the main ram is extended by these cylinders . . . . a vacuum condition here . . .
I I I I II I
- - -
Counterbalance Valve
From Pump
To Tank
- 143 -
0
,--- -
I I
- - - - - - -
I I I I I I I I I I I I I I I I I I I I I
G)
- 144 -
ester fluids. Remember, the only pressure we have available to cause a flow to occur is the atmospheric pressure and the static head pressure of the oil. Likewise, we must subtract from the available pressure the 3 PSI which is necessary to open the main poppet of the pre fill valve. On the other hand, it is possible to prefill with a higher flow rate for a given valve size if the reservoir is designed so that the oil can be pressurized to approximately 100 PSI. Here you can easily see that considerably more pressure is available for prefilling the main ram. For these prefill ap plications, oil velocities up to 20 F.P.S. provide satisfactory operation. Assuming the kicker cylinders can supply enough force, the main ram has the capability of pulling a nearly perfect vacuum. We must consider this fact and size our prefill lines and components so that we fill the cylinder with oil rather than pulling an excessive vacuum. When you are sizing a valve of this nature, we ask that you consider the information as pre!'nted under Suction Conditions for Hydraulic Pumps in Chapter 1 .
Secondly, it is virtually impossible to open the main poppet of a prefill valve before decompression of the main ram oc curs. The circuit is protected from damaging decompression shock because, unlike the pilot operated check valve, the main poppet has an area advantage ouer the pilot piston. Even if full system pressure is put on the pilot port, the pilot piston can only generate enough force to open the decom pression poppet. This assures high pressure bleeding before the opening of the large flow area. The area ratio of the pilot piston to the main poppet of a typical prefill valve is in the order of 0.25 : 1 . Assuming that the pilot pressure is equal to the preloaded pressure on the main ram, even at 5000 PSI, the pilot piston will not open the main poppet until the preloaded pressure is bled to 1 250 PSI. Since satisfactory decompression is assured at virtually any pilot pressure, the time related speed control method of decompression is usually preferred in prefill circuitry. In calculating the minimum pilot pressure requirements to open the decompression poppet, we must remember that we are working against a spring returned pilot piston which requires a minimum pressure of 75 PSI. However, this shows up in our formula simply as a larger valve constant. For the area ratio of the valve, we divide the pilot piston area by the decompression poppet area. This figure is typically in the order of 10: 1 . Consequently, our minimum pilot pressure can be calculated simply from the following formula:
AR .
+C
Where: P P = Minimum pilot pressure at port X (PSI) P = Preloaded pressure on main ram (PSI) ARv= Pilot piston area (in.) -:- decompression poppet area (in) C = Valve constant which is usually equal to 1 50 PSI.
will be pushed over - - (): ::::;) - , = this reverse free flow check . . .
- 145 -
which are designed on the modular concept. ln applications with limited space requirements, the functional parts can be integrated into the cap of the cylinder. On larger installations, plumbing can be simplified because the low pressure housing module can be rotated so that the A port can be aligned with the high flow plumbing throughout 360 of housing rotation. The following are but a few examples of possible in stallations.
Housing Port A
Cylinder
__
- 146 -
Pilot section
From - oil tank Cylinder cap pressure pump to pressure gauge High pressure flange Prefill valve cartridge assembly Cylinder A
Valve cartridge assembly and pilot section mounted into the cylinder cap
Cross section of a prefill valve with low pressure housing which can be rotated through 360
Cross section of a prefill valve for mounting directly in a tank which is located on top of the cylinder
- 147 -
Cross section of a prefill valve main poppet without control cylinder, for use as an antica vitation check valve.
LOGIC ELEMENTS
As shown in the operational cross section, the basic logic element is a three-piece assembly consisting of a poppet, bushing, and a spring. The standard poppet is machined n i graduated steps, so that when positioned inside its bushing, there are three separate areas for pressure to act upon. Depending on the prevailing pressure conditions at port X, A, and B, the poppet is either open, closed, or in some modulating position between fully open and fully closed. In defining the surface areas, the nose of the poppet is area A, , which we will assume is 100%. The ring area, A,, is then defined as the area which has the ID of the seat diameter and the OD of the poppet guide. Depending on the model selected this area can be either 7% or 50% of the nose area, A, . Ob ously, the third effective area, A3, is that of the full diameter of the poppet. Likewise, this area is dependent on poppet design, and is either 107% or 1 50% of the nose area, A, . For any given element size, area A3 has the same diameter. Consequently, the area ratios of A, and A, are changed by modifying the maximum diameter of the poppet nose. As shown, a logic element which has an A, area which is 50% of area A, has considerably less flow area when open than an element with a 7% A, area.
The logic element revitalizes some of the early concepts which led to development of the hydraulic industry as we know it today. In the infancy of hydraulics, water was the medium used to transfer energy. Spool type directional con trois, which will be discussed in Chapter 5, found universal application only after the introduction of oil hydraulics many years later. Since economic conditions are again causing us to consider water as our hydraulic medium, many manufac turers are reconsidering the poppet valve as the controlling element. In combining the older poppet theory with modem technology, we find that the logic element provides economical solutions to hydraulic systems incorporating either water or oil. The modem day logic element is a cartridge poppet which must be mounted in a manifold block. Although its operation is dependent on a custom designed manifold, its simplicity provides technical and economical solutions to many hydraulic problems. It is especially desirable on high speed equipment with high flow hydraulic circuits. Let us now take a closer look at how it works.
vl
Needless to say, pressure working over area AJ creates a force which tends to seat the poppet and block the flow path from A to B. Opening forces, on the other hand, are established by pressure working over areas A, or A,. Of course, if pressure exists in the A and B ports simultaneously, the force trying to open the valve poppet is the sum total of both of these pressures.
- 148 -
A,
0
A Port Area A2 is 50% of Area A, Flow Area when open Area A2 is 7 % of Area A,
As will be shown, depending on the method of piloting, the elem11ts can be used to perform check, directional, or flow control functions . In addition, some forms of pressure con trol can be obtained. However, when strict pressure control functions are required, two variations of the basic logic element give more precise control. more force to close the poppet than was initially required to hold it closed. In the dynamic position, the pilot section can only determine one closing pressure force working over area A3 . Consequently, once opened, the standard logic cartridge would inherently become unstable, since the exact balance of forces necessary for stable operation would be lost. For this reason, a logic element is available which has an area A, which is equal to the area A3 . For pressure control functions this design is inherently stable, since hydraulic forces tending to open or close the poppet are always in balance.
Area A3
Logic Cartridge For Normally Closed Pressure Control Functions NORMALLY OPEN LOGIC ELEMENT CARTRIDGES
In performing reducing valve functions, the cartridge must be normally open, allowing flow from inlet to outlet. When pressure in Chamber A3 reaches a predetermined limit, as established by the pilot network, the cartridge spool must modulate toward a closed position. This causes a pressure drop across the orifices established by the cross drillings, so that downstream pressure remains at the required setting. To provide stable operation, area A, is equal to area A3 .
- 149 -
With the A port being the reduced pressure port, hydraulic forces above and below the cartridge spool are always stably in balance during dynamic operation.
Area A, = Area A,
Pilot passages X & Y can be drilled to connect with required pilot source.
- 150 -
element poppet can be cushioned. In addition, when a san dwich mounted pressure control is used, directional and pressure control functions can be combined into one element.
A,
/ {1
Tank Return
- 151 -
Shuttle Valve
Optional Orifice
To X Pilot Source
To Y Pilot Source
When the flow control function is used with logic elements, a cover is available which will adjust the maximum opening stroke of the poppet. We must be aware, however, that the flow control function may not be as precise as it is when we use a valve designed specifically for performing flow control. That is, even if a very fine thread were used on the stroke limiter, the logic poppet, because of its design, would open a large flow area in a very short stroke. This would definitely limit the accuracy of adjustment, as discussed in Chapter 3. Nevertheless, a logic element used with a stroke limiter cover is a good example to bring home the fact that logic elements can be an economical solution to some problems in high flow hydraulic circuits. The following circuit not only replaces the large spool type directional control and two meter out flow controls economically, but it also provides a leak free hydraulic locking of the cylinder. In addition, because the logic elements are held closed by a limited system pressure, the cylinder is automatically protected from being over loaded.
This assures that the poppet will always be closed until area A3 is vented to tank by the directional control. In our ex ample, if area A3 were only piloted from the B passage, high pressure at port A could open the poppet and allow a flow from A to B.
G)
200 GPM
Conventional Circuit
- 152 -
the
I
I
I
I
..
..
I I I I I I
L- -L --- --
which in turn would open this element first, and relieve the overload through the main relief. Return oil is metered from the rod end . . .
r1 I I I
--
- - ..
IGit +
.. - - - .
--- L- -L --
- 153 -
be achieved by using a relief, sequence, or reducing pilot valve in conjunction with either the normally closed or nor mally open pressure control logic element.
work will be worth the effort, because it will put you well on your way to working with the most modem hydraulic system in our industry.
SYMBOLS
Symbols for check valves clearly represent the intended function. As shown in the chart, the seat is represented by a symbol similar to an arrowhead, while the poppet is represented by a circle. To avoid confusion, be aware that the arrowhead is not to be interpreted as an arrow indicating the direction of free flow. Free flow is that which pushes the poppet (circle) away from the seat (arrowhead). When you are trying to interpret a circuit function, you can also avoid confusion by paying attention to the symbol representing the spring. In actual practice, though. the cracking pressure springs are seldom used in design drawings. For this reason, we recommend that when cracking pressure is important to the circuit function, the cracking pressure in PSI should be listed next to the valve symbol.
SYMBOL
DESCRIPTION
--<:iWAlternate
--(:>----:-
PSI
y W-x
- 154 -
-X
SYMBOL Detailed:
DESCRIPTION
c)
A I
0
IB
I
B
X
Prefill valve
xi
"'
<: I
Y.
r s
: :r-
- 155 -
llv \
A
X , .
CONCLUSION
This chapter has compared the operation of a simple check valve to that of a low pressure direct operated relief. Although the main purpose of a check valve is to provide leak free directional control, we have shown how some pressure control functions can also be achieved. In addition to the discussion of a simple check valve, the operation and application of pilot operated valves have been discussed. When working with pilot operated check valves, we must understand how pilot ratios, decompression pop pets, and external drains affect the operation of the valve. In actual application, we must also consider the pilot pressure requirements needed to open the main poppet. We should be aware of the pilot pressure considerations for both load holding and decompression applications. Circuit examples for venting the X port and pressure or flow control ad-
justment of decompression have been explained. Prefill valves are quite similar to pilot operated check valves, but are designed specifically for use in press applications. The basic design variations allow considerably high flow rates with minimum pressure drop in the free flow direction. Because of its specialized application, the decompression features of a prefill valve are somewhat sophisticated. In this chapter we have also introduced the logic element as a viable means of controlling hydraulic circuits. The simplicity of the logic element poppet often allows us to combine direc tional, flow and pressure control in one unit. However, since the open or close position of the poppet is determined strictly by the prevailing pressure conditions, pilot circuit design in this case, is somewhat complicated. Nevertheless, the ad vantage the logic element offers in interfacing small control circuits with high flow systems makes it an interesting technology in modem hydraulic control.
- 156 -
CHAPTER S
DIRECTIONAL CONTROL
One of the most versatile aspects of hydraulics is the ease with which the direction of energy transfer can be manipulated. No other method of power transmission provides as many control options for reciprocating linear motion or reversing a rotary drive. Virtually hundreds of horsepower can be made to change direction almost in stantaneously at the flick of a wrist. On the other hand, the machi e function can also be totally automated by in n terfacing th directional control components with hydraulic, pneumatic, electrical or electronic control circuits. The check valve, as outlined in Chapter 4, is but one of a multitude of components available for controlling the direc tion of flow in hydraulics. In this chapter, the components and methods used to control the direction of work output will be studied. The chapter is divided into two parts in order to study both sliding spool type and poppet style directional controls. The discussion has been limited to valve control, leaving the discussion of the possibility of pump control of direction for Chapter 6.
Work Ports To Actuator A This Spool Position Disconnects All Flow Paths B
Tank Port
From Pump
Valve Housing
- 157 -
or linear actuator which normally has two port connections. Likewise, we know that if oil is pumped into one of the ports while the other port is connected to tank, the actuator will move in one direction. To reverse its direction of motion, the pump and tank connections at the actuator must be re versed. Over the years , sliding spool type directional controls have been found to be the most acceptable way to ac complish this change in plumbing compactly and quickly.
BASIC OPERATION
The sliding spool directional control has a cylindrical piece called a spool which slides in a machined bore in the valve housing. The housing has a number of ports to which the pump, tank and working lines for the actuator are connected. Internally, the ports are connected to cast or machined
so that P opens to A . . .
Valve Housing Basic Operation P-+A & B-+T This reverses the flow the actuator. When the spool moves to the far right . . .
5
Basic Operation
- 158 -
passages in the valve housing which terminate at the machined bore where the spool is located. The number of ports designates the valve type. For instance, a 4 ported valve is referred to as a 4-way valve, while a valve with 3 working port connections would be called a 3-way. The sliding spool is closely fitted into the machined bore so that when its maximum diameter is in line with a port chan nel, flow to or from that channel is blocked by the spool. As the spool is repositioned, the previously blocked port can be nterconnected with another port in the valve housing i through machined undercuts in the spool. As shown in the basic directional valve cross section, the larger diameters of the spool are referred to as lands.
housing. This disconnects all ports since the lane. block all possible flow paths. It stands to reason that if we machine spools with lands and undercuts of different dimensions, we can achieve any num ber of different flow paths. For instance, if we wanted our ac tuator to float in the center position of the directional control, all we need do is machine the spool with shorter lands. As you can see, this would connect both actuator ports to tank in the center position, so that oil could enter or leave the ac tuator as required during motion of the cylinder's piston. The basic 4-way function would be maintained if the spool were repositioned to the left or the right.
- 159 -
Although we have not yet described the methods available to shift the spool to its various positions, we can mention the fact that most three position valves are held in the center or neutral position by a set of centering springs. The valve is then shifted to one of its end positions by some external ac tuator force. In symbol terminology, the port connections to the valve are normally connected to the square which represents the valve's center or deactivated position. As shown in our symbol for a three position closed center direc tional valve, arrows are used to indicate flow paths in the shifted position. The springs indicate that the valve self cen ters when the shifting force is removed. Our symbol at this point indicates the flow positions only, since actuator sym bolism will be discussed later in this chapter.
I I I
Push Pin
Electric Solenoid
Electric Solenoid
Centering Spring
Centering Spring
- 160 -
and A to tank. A B
0 0
G) 0
----:.___
p
connecting P with B . . .
This spring returns the valve to the closed center condition when the shifting force is removed.
(D
TYPICAL
FLOW
PATHS
AVAILABLE
Closed Center
Open Center
Tandem Center
Float Center
Regenerative Center
- 161 -
The spool chart shows that most three position valves cause forward and reverse operation of the actuator in their two end positions. The flow paths indicated in the center positions actually designate the spool type. Discussion of the possible applications of various spool types will be post poned until other important operating details have been covered.
The three position valve is quite popular in industrial hydraulic systems. The flexibility of the three position valves lies in the fact that it not only provides forward and reverse motion of the actuator, but it also allows a neutral position, where any number of possibilities of holding or unloading the actuato{ and/or pump are possible. However, there are a multitude of applications in which a neutral position is not required. Two examples are cylinders which only have to ex tend and retract to their fullest positions, and hydraulic motors which only run in forward or reverse direction. For these applications, all that is needed is a two position direc tional control. Actually, two position valves are quite similar in design to three position valves. The only real difference is that the two position valve has no way to stop or to hold the valve in its center position. In these valves, as the spool shifts from one extreme to the other, the center position is simply crossed
ouer.
As shown in symbol form, one of several methods to achieve the two position function is to hold the spool in one end position by a light spring force. Then, by actuating the valve with a force opposite the spring, the spool is moved into its second position.
An actuator force on this end of the spool . . . When the actuator force is removed .
Depending on the type of actuator and the required control, it is sometimes advantageous to have a two position valve which has its spool position determined only by the valve ac tuator. This method of operation is most popular with direc tiona! controls which have two electric solenoid actuators. Since spool position is determined only by the external ac tuator force, Bernoulli flow forces could cause the spool to self-shift if both actuator forces were simultaneously relaxed. For this reason two position no spring versions are normally used on high cycling applications, and the valve should always be mounted with its spool in a horizontal position. As
which creates this flow path. A I 8 This spring holds the spool in one end position . . .
G)
.. j
- 162 -
shown in the valve symbol for a double solenoid operated two position valve, the spring return is simply replaced by a
second actuator.
G
T
Annular Groove
holding force on the spool. The actuator force can then be relaxed, since the spool is held in position by the detent. The valve will remain in this position until the opposite actuator "clicks" the spool out of its original position into the second detented flow position.
Detent Assembly
The detented spool is an option commonly used with two position valves with dual actuators. Mechanically, the detent is nothing more than a set of spring loaded balls which ride on the spool shaft. For each of the two spool positions, an annular groove is machined on the spool shaft. These grooves are lined up with the ball detent assembly when the spool is shifted to one of its two flow positions. That is, when the actuator shifts the spool into one of the flow positions, the detent ball clicks into its groove, providing a
B
METERING NOTCHES If we go back for a moment to our basic representation of directional valve operation, we find that, as the spool is shifted from its closed center position, there is a dead band region where spool movement provides no valve opening. Then, when the edge of the spool land meets the leading edge of the port opening in the valve housing, an annular flow area opens quite rapidly. The fact is that there are ac-
- 163 -
tually two flow areas opening simultaneously: one from the pump to the actuator and one from the actuator to tank.
A problem arises when the ports which are being connected are at considerably different pressure levels. Because energy is stored in pressurized fluid by compression, an explosion of
fluid will occur as the high pressure port opens to a port at lower pressure. Of course, the faster the opening occurs, the quicker the energy will exchange. This will cause a water hammer, which will stress pipe joints, fittings, and hoses, and which can eventually cause them to either leak or break.
)..
r-
- ,-------""===-
(j)
<.! --"------== -
0
and this port, are at low pressure.
UO::'- GIU""'
In order to obtain a smoother valve shift, metering notches can be machined onto the edge of the spool lands. During the time when the spool land and the housing are still overlapped, a number of equally spaced notches will provide small flow passage connections between the two ports.
Pressure differences between the two ports will gradually equalize, prior to the opening of the full flow area. In valves which incorporate metering notches on the spool, a more gradual transfer of energy will occur as the spool is shifted from one position to another.
- 164 -
0 and a gradual
decay in pressure here . . . Load
..
overlap.
Whenever three or more ports are influenced by the movement of the spool, land dimensions will determine how the ports interconnect and disconnect. Since the operation of the actuator is affected by spool overlap, the crossover con dition for the control function at hand must be considered. One type of spool overlapping is referred to as positive We will consider how the pressure port P will be discon nected from the A port and connected to the B port as the spool moves to the right. As illustrated, pressure will be X, less than X2
Diagram Showing the Principle of Positive Overlapping
- 165 -
blocked from the A port when the spool moves to the right through dimension X, . It must, however, move through dimension X, to allow pressure to connect with port B . In matching the spool so that dimension X, will be less than dimension X2, A will be disconnected from P before P opens to B. This means that during the crossover condition, all ports will be momentar isolated from each other. With this ily type of overlapping, there will be no loss in pressure since the ports are never interconnected. In applications with overhung loads, the actuator cannot drift during crossover. The disadvantage with positive overlapping, however, is that during the short time period of crossover, pump flow has nowhere to go. Besides, the duration of crossover is usually less than the response time required for opening the relief valve. An unavoidable pressure surge is created, which ap pears in the system as an audible pressure knock. Never theless, the damaging affects of this pressure surge can be reduced by metering notches on the spool lands and capacitances in the system. Hoses for instance, dampen the knock, 6ince they can stretch slightly during the pressure surge.
ten offset by one serious disadvantage. In the example, during the crossover period, both ports of the actuator are in terconnected. If the actuator is exposed to an overhung load, the directional control, in itself, cannot prevent drift during crossover. Since holding pressure can be lost, negatively overlapped valves are often used with some type of counter balance or with a pilot operated check valve.
0 0
Likewise, before it is r- - B is - ----= opened to B . blocked .....---7--rr--r--r-r----.n from T . . . Actuator ........_ --r' Force T before A is connected to T.
Notice that the crossover condition is separated from the symbols for the actual flow position by dash lines. This is done in order to avoid confusing the symbol with that of a 3
- 166 -
position closed center spool. The crossover condition for two and three position valves with a positive and negative
SYMBOL
IXi II IX!H!I II
.000039 inches (39 millionths of an inch. The exact con version is: 1 micron equals 39.37008 micro-inches).
Since the lower limit of visibility with the unaided eye is ap proximately 40 microns, it is difficult to visualize a dimension of 1 micron. Some familiar items can, however, be described in micron dimensions . For instance, this page is printed on paper which is approximately 120 microns thick. Also, if you are a normal human being, the hair on your head ranges somewhere between 65 and 75 microns in diameter; your white blood cells have a diameter of approximately 25 microns; your red blood cells measure in at about 8 microns. We will now consider the dimensional criteria for a standard hydraulic directional control valve.
- 167 -
hurr an red blood cell from passing from one port to another. Actually, the clearance fit of a directional control is nothing more than a flow orifice, and, for any particular valve and fluicl, the leakage rate is influenced by the orifice size as well as by the pressure differential. Since we cannot change the prevailing pressure conditions , the orifice size and shape will determine the leakage characteristics of the valve.
Although the clearance fit of the spool drastically influences the leakage characteristics of the valve, it is not the only determining factor. For instance, if the two similar valves are compared, we find that the clearance between the spool and valve housing is 8 microns nominal for both valves. Never theless, when tested for leakage, it has been found that valve A leaks considerably more than valve B.
2500 PSI
- 168 -
Viscosity 120 SUS @ 1 00 F. Pressure At Port(s) Leakage Measured At Ports 750 PSI 1 500 PSI 3000 PSI 4500 PSI
Actually, two -additional dimensional considerations have an important influence on a valve's leakage characteristics. If, for instance, the shape of the leakage orifice is considered, it is easy to see how both concentricity and length of overlap will affect leakage rates. In production, it is important to maintain a concentricity tolerance of about 2 microns. Of course, this tolerance must be maintained on both the bore and spool diameters. As shown, if the concentricity varies too greatly, the resulting flow area can be considerably enlarged. It is important to note that both valves can display similar nominal clearances.
Ideal Concentricity
Likewise, the fact must also be considered that the length of the leakage orifice affects the overall leakage performance of the valve. I t has been shown in Chapter 3 (in the discussion of temperature compensation) how the length of an orifice af feels the flow rate at a particular pressure drop. In directional controls, the flow through the leakage orifice must be minimized. Consequently, the more the spool land overlaps the bore in the valve housing, the longer is the length of the resulting leakage orifice. This increases the resistance to leakage because of increased friction in the flow path.
- 169 -
material should not be removed from either the bore or the spool in the repair process. This means that nothing more should be done than to polish the sliding surfaces. This can be accomplished by buffing the surface with a very fine automotive type polishing compound or a ( l A to 6A) lapping compound. Of course, proper cleaning after polishing is of utmost importance. Emery cloth or similar abrasives should not be used.
forced against the side wall of the bore. Inevitably, this can cause wear and subsequent seizure. The balancing grooves provide a path whereby high pressure fluid can equalize around the diameter of the spool. This balances the forces on the spool so that it remains concentric with the bore. Although adequate lubrication can occur under pressure with oil films as thin as Y of a micron, the balancing grooves also 2 aid in lubricating the closed tolerance fit. Under low pressure operating conditions, the oil which is stored in the groove is distributed over the slidi g surfaces as the valve is operated. n
BALANCING GROOVES
You may notice that, on most spool lands, there are a num ber of grooves cut around the circumference of the land. These grooves serve to center the spool in its bore, while simultaneously providing better lubrication between the sliding surfaces.
In a spool type directional control, pressure conditions tend to unbalance the spool. The net result is that the spool is
- 170 -
housing, spool diameter and spool stroke also influence the maximum flow capability of the valve. It is easy to see that i when a spool is shifted to n terconnect two ports, the size of the flow area which is opened is determined by the diameter of the bore in the valve housing. Of course, the larger the diameter of the bore, the larger the final flow area. As shown in the illustration, stroke length of the spool also influences the final flow area.
Modern Cast Iron And Innovative Coring Techniques Allow For Larger Internal Flow Passages.
..__
This diameter . . .
CD
- 171 -
G)
tends to shift the spool to the left.
0
BERNOULLI'S THEOREM In the 18th century, a Swiss scientist named Daniel Ber noulli, developed a theory for the relationship between fluid
velocity, pressure and elevation. Although it is beyond the scope of this text to fully explain this theory, we will attempt to explain how this principle affects the maximum flow capacity of a spool type directional control.
and a relatively high velocity because of a small crosssectional flow a rea . . . Bernoulli's Theorem
increases . . .
- 172 -
Based on the fact that energy cannot be created or destroyed (chapter 1), Bernoulli implied that the energy level in a hydraulic system is always constant. However, since oil moves through the hydraulic system, this energy exists in two forms: Kinetic energy and potential energy. Potential energy has the potential for doing work and is stored in the hydraulic system in the form of pressure. Kinetic energy, on the other hand, is energy in motion and is related to the mass and velocity of the fluid. ln a hydraulic system with a constant flow rate, this means that for each decrease in pressure (potential energy), there must be an increase in fluid velocity (kinetic energy). Likewise, when fluid velocity increases, pressure must decrease to maintain the constant balance between kinetic and potential energy. This, of course, is based on the assumption that the system is 100% efficient, and does not convert any energy into heat because of friction.
spool types G H T P A 8 P-A A-T P-B B-T 225 ,-- - e:_ --,- ---r -= GHTp
0 ... 'tl
1 50 f------i,--i-+r--t-+---l
=
Q,
fll fll G) Q:
7 5 t---+--n""t-:,_rr7"'----t
-= - - -'-- -' 0 ....... =- --L - 10 15 20 5 Flow (GPM)
the fluid conductor changes, there is a change in the velocity of the fluid. In tum, changes in the pressure levels occur, however, they are not easily detectable. The problem is that friction will convert more and more of the potential energy (pressure) into heat as the fluid passes through the system. This conversion of energy has the tendency to camouflage the effects of the Bernoulli principle. Nevertheless, velocity changes are prevalent as oil passes through spool type directional controls. These velocity changes, in turn, unbalance the pressure forces in the valve. Consequently, at some maximum flow, the change in fluid velocities upsets the pressure balance so drastically that the axial forces on the spool, due to flow, are greater than the shifting force of the actuator. This ultimately results in malfunction of the valve.
t
This flow passage w induces a pressure loss of 60 PSI . . . 10 GPM
'
This is known as a loop-drop of 165 PSI, all of which is turned into heat. Loop-Drop
A second area of concern is establishing the maximum flow at which the selected valve will malfunction. Unfortunately.
- 173 -
this value cannot be simply stated as some maximum flow in GPM. The maximum flow value is dependent on both the pressure at which the valve will operate and the application in which the valve is used. As shown in the chart labeled "Maximum Performance Data," the maximum flow value decreases as operating pressure increases. Likewise, the figures are based on using the directional control in a pure
4-way function with equivalent simultaneous flows. If the valve is used with large rod cylinders or as a 3-way valve (one cylinder port plugged), the maximum flow value could be considerably lower. If the valve under consideration appears marginal for the application, a larger valve should be se lected.
Maximum Performance Data at pressure (PSI) of Flow (GPM) for spool types E, C/O, D/0 J,H,M,C,L,Q,W,U,V G,D,R,F,P,T A,B 750 21 21 19.8 13.2 1 500 21 21 1 8.5 1 1. 9 3000 19.8 19.8 1 5.8 9.3 3750 1 5.8 1 3.2 1 3.2 7.9 4500 1 5.8 1 1 .9 1 1 .9 6.6
0
by an actuator force against this push pin
. . .
Centering springs, offset springs, or detents are located in these cavities (spring centered shown). Cross Section Of A Direct Acting Valve Housing Without Actuators
- 174 -
Double Solenoid
T 8 A T
oP
Solenoid
Housing
\._ Solenoid
Ac c
c
. 0 UJJJ} -
UJ
- -i -:w.
<>
r Spool j
Push Pins
.
Detent
rnrm
Cent
- rr-. m
U-Cup Seal
....__)
Single Solenoid
T 8 A T
p -
Housing )
- 175 -
Direct acting valves are those in which the shifting force of the actuator works directly on the valve spool. Up to this point, the directional spool valve function has been described in terms of some external force being available for positioning the spool in the valve housing. Although the methods of positioning have been discussed (spring cen tered, spring offset, no spring, and detented), the different types of actuators have not yet been covered. A great deal of circuit design flexibility is offered by different types of ac tuators. In addition, operator convenience and safety depend on the selection of the proper actuator for the intended ap plication. We will now discuss a representative cross section of the various actuators available. In general , direct operated valve actuators can be classified as mechanical, pilot operated or electrical solenoid. In tum, each classification can be subdivided into distinctly different types of actuators. For instance, if only mechanical actuators were considered, a selection could be made from three basic types: hand lever, rotary hand knob, and roller cam operators. l.Jnfortunately, it would be impractical to discuss the intricacies of each type of actuator. For this reason, we have selected representatives from each group for discussion of operation and application. The subject matter will be devoted directly to the actuator itself with the assumption that its purpose is to position the spool in the valve housing.
Mechanical actuators are used to interface shifting force working on the spool with a mechanical command from the machine, or a manual command from the machine operator. Manual actuators are intended for mounting at the operator's control station, and, they take the form of a hand lever, rotary knob or palm button. On the other hand, mechanical operators are intended to operate automatically during the machine's cycle, and they usually take the form of a roller cam operator, mounted on the machinery. The hand lever actuator is by far the most popular manual control. It is one of the few valve actuators which pushes and pulls on the spool to achieve the desired spool position. In fact, most actuators, other than manual, are only capable of pushing on the spool.
MECHANICAL ACTUATORS
The operational cross section shows a three position, spring centered, hand lever actuator. When no force is applied by the operator, the spool is centered by the two centering springs which position the hand lever in the vertical position. As shown in the illustration, when the operator pushes on the hand lever, the force passes through the ball pivot joint and moves the slide so that the spool is pulled to the left, compressing the left hand centering spring. Then, when the hand lever is pulled, the slide will push the spool to the right. In addition to the spring centered version, the same actuator can be used with a two position spring offset spool. In this application, a different set of springs would push the spool to the far left position, which in turn would position the hand lever in the right most position. When the operator pulls on the hand lever, the spool will move to the right, compressing the offsetting spring. A third type of operation, which can only be achieved with a push-pull type manual operator, is a three position detent. This .detent assembly is located in the actuator itself rather than on the spool, as has already been discussed for de tented valves with double actuators. Unlike push type ac tuators, the hand lever allows the operator to position the spool in any one of the three flow positions. This position is then maintained by the detent. Mechanically, the detent is achieved by having a spring loaded ball position itself in grooves machined on the slide in
- 176 -
Pull
(
Hand Lever
achieved by operating the valve with a cam which follows the stroke of a cylinder. Time sequenced operation can also be achieved by operating one or more directional valves with a motor driven cam. An important fact to consider when you deal with cam operated directional controls is that it is relatively difficult to achieve a pulling force for positioning the spool. For this reason, cam operated valves are usually spring offset to one
- 177 -
end position, even if the valve being used is a three position valve. In this way, the cam pushes the spool approximately half stroke to achieve the center flow conditions, while re verse flow in the third position is achieved when the cam pushes the spool full stroke against the spring. As shown in the cross-sectional illustration of a three position, cam operated directional control, the spool is shifted from one position to another in a total stroke of ap-
proximately 1/8 of an inch. Since all three positions must be achieved in 1/4" of travel, the cam must be designed and manufactured quite accurately. Likewise, since there is no allowance for over travel, precautions must be taken, especially during set-ups, so that the cam cannot force the spool past its fully depressed position. Also, as shown in the example, the approach angle of the cam must be limited to 30" in order to minimize the radial forces on the plunger.
Center Position
this type of actuator is a hydraulic system which must be operated in an explosive atmosphere. In this type of ap plication, it is usually more economical to use a pneumatic or hydraulic control circuit, than an explosion proof electrical solenoid control. The cross-sectional illustration shows a typical two position
Detent
Return Spring T A P B T
- 178 -
detented valve with two opposing pilot actuators. The ac tuator is a push type design, consisting of a housing sealed piston and return spring. As shown, pilot pressure on the left-hand actuator pushes the spool to the right, connecting P with B and A with tank. Notice that when the spool is moved into position, it is held by the ball detent assembly on the left hand side of the valve. Even if pilot pressure is lost in the left actuator, the spool will remain in this position until a pressure signal activates the opposite actuator. When pilot pressure is applied to the right-hand actuator, the spool is pushed into its second detented position. The spring return in the actuator overcomes the static friction of the piston seal, and causes the piston to retract when the pressure signal is removed. Normally, pilot actuators are not capable of withstanding full system pressure. Consequently, the pressure in the control circuit must be limited to the pressure rating of the pneumatic or hydraulic actuator . The hydraulic actuator, for instance, will operate satisfactorily within a range of 60 to 900 PSI. A similar pneumatic actuator will work in a range of 60 to 180 PSI. The pilot actuators, as shown, require a minimum of 60 PSI to assure that there will be sufficient force available for shift ing the spool. The upper pressure limit ( 180 PSI pneumatic, or 900 PSI hydraulic) is simply the maximum pressure rating of the piston seal and/or housing. With pneumatics, it is sometimes advantageous to operate the directional valve within a considerably lower pressure range. This is ac complished by using an actuator with a larger piston area. The large piston provides-adequate shifting force with a sup ply pressure somewhere between 22 and 90 PSI.
relays, limit switches and programmable timers are relatively inexpensive electrical components which simplify control cir cuit design. Likewise, compactness, aesthetics, remote con trol, and the ability to intermix manual and automated con trol are all facts in favor of solenoid actuators. The solenoid, although simple in principle, is offered in a variety of styles. Since different solenoid designs offer dif ferent advantages, depending on the application, we will discuss the most popular models. In general, solenoids are available for a variety of voltages (and frequencies) in both AC and DC versions. Both air gap solenoids and wet pin solenoids have application dependent advantages.
ELECTRICAL ACTUATORS
Electric solenoid actuators are by far the most popular of all poss\b\e actuators {or direct operated directional controls. Automation has caused a trend toward electrical and away from manual or mechanical controls. Automatic or semi automatic control is far more versatile and more easily ac com9lished with electrical control circuitry. Push buttons,
- 179 -
Secondly, the magnetic field flows more readUy through a magnetic material such as iron or steel than it does through air. Therefore, the magnetic field can be concentrated by adding a "C-frame" of iron around the outside of the coil. Now, if a movable iron plunger is placed inside the coil, the magnetic field will be more intense when the plunger is in such a position that the C-frame and plunger are totally within the magnetic field . The magnetic force of the solenoid will develop when the coil is energized. This attraction will pull the plunger to its point of equilibrium w ithin the magnetic field.
DC SOLENOIDS
DC electricity, such as found in battery operated electrical systems, always has a constant polarity. In other words, using a flash light as our example, the electricity flows from the negative post of the battery, through the bulo, to the positive side of the battery, whenever the switch is in the on position. In a DC solenoid, this type of current develops a magnetic field which is constant in polarity, or, more specifically, has a definite north and south pole. When current is applied to a DC solenoid, the north and south poles of the C-frame simply attract the south and north poles of the plunger respectively. This moves the plunger against the push pin in the directional valve, causing the spool to shift.
0 which
::::lllillr 0
-
f"i'...) \..!.
and here.
Directional Valve
When you are selecting a DC solenoid, you will discover that solenoids are available for virtually any voltage requirement . Although the solenoid will function satisfactorily over a broad range of voltage fluctuations, you must remember that if voltage increases, the current draw will also increase, since the windings for a given coil offer a fixed resistance. If the voltage is in excess of the solenoid rating, the extra current draw will produce heat which will eventually cause the solenoid to bum out. On the other hand, if supply voltage is below rating, a related loss in current may not create suf ficient magnetic force to cause spool shift in the directional valve. The DC solenoid, although slower in response when com pared to an equivalent AC model (DC solenoids respond in the 50 to 60 ms range), can be cycled up to 15,000 cycles per hour without fear of overheating. The DC solenoid is also immune to burn-out problems associated with AC models. If a stuck spool prevents the solenoid from shifting, it will not bum out because of excessive current draw. This is true
"\
position . . .
so that the magnetic field can pass 100% through the iron. Principle Of Basic Solenoid Operation
- 180 -
because DC current draw is simply related to the supply voltage and to the fixed resistance of the coil.
To eliminate "buzz" and to increase the solenoid's holding power, most AC solenoids incorporate what is known as a shading coil. A magnetic field passing through a coil of wire induces an electric current in the same way that electric current passing through a coil of wire creates a magnetic field. The flow of current in the shading coil in tum creates its own magnetic field. Due to a phenomenon in AC circuits which is called inductance, the current produced in the shading coil lags behind the applied current to the coil. When the applied current passes through zero in its change from one polarity to another, the current, and, thus, the magnetic field of the shading coil, is at its maximum. When the solenoid is used within its force rating, the magnetic field of the shading coil is sufficient in strength to keep the plunger in position, thus eliminating the buzz.
C-Frame
AC SOLENOIDS
Although the AC solenoid functions in the same basic man ner as the DC model, its magnetic field is influenced by the alternating current supply. In the United States, an A C solenoid operates on a voltage which alternates its polarity from positive through zero to negative at the rate of 60 cycles per second. (In most European countries, the rate is 50 cycles per second.) This has the net result of changing the polarity of the magnetic field at the same rate. Unfortunately, the magnetic force is high only when the AC current is at its positive or negative peak. As the current changes from p ositive to negative, or vice-versa, it must pass through a neutral point at which there is no current flow. During this short period of time, a point is reached at which there is no magnetic force. Without this magnetic attraction, the load can push the plunger slightly out of equilibrium. Then as the current builds up, the magnetism increases and pulls the plunger back into position. This movement of the solenoid in and out at a high cycle rate creates noise which is commonly referred to as "buzz."
Shading Coils
North Pole
I I I
, '
I I
South Pole
'
'-,
I ,'
60 Cycles Second
- 181 -
- ""-------
Holding
-
Time (m.s.)
can be continuously dissipated by the solenoid. If the plunger is not alloweq to close due to a mechanical problem, the in sulation will bum and the coil will short out. Since con tinuous duty AC solenoids can only dissipate the heat which is generated by the lower holding current, it is important that the plunger always achieves its closed position when the solenoid is energized. Another problem created by the inrush characteristic of AC solenoids is overheating due to excessive cycling of the solenoid between the on and off positions. Each time the plunger closes, the coil winding is subjected to a high inrush current. If these inrush currents come too quickly, the heat will generate faster than it can be dissipated. Eventually, this will lead to failure of the solenoid. A typical class B AC solenoid can be cycled no more than two times per second, or 7200 cycles per hour, while class A solenoids are limited to approximately 4800 cycles per hour. To avoid any confusion, it must be mentioned at this point that solenoids which are too hot to touch are more than likely operating at a perfectly satisfactory temperature. NEMA (National Electrical Manufacturers Association) has developed standard classifications for wire insulation. Of the four classes established by NEMA, wire used in solenoid coils is usually either class A or class B. Insulation which falls into the class A catagory must be suitable for operating con tinuously at temperatures up to 105 C (221 F). Class B in sulation must be suitable for use up to 1 30 C (266 F). (The other two classes are class F - 155 C (31 1 F) and class H which is 1 80 C (356 F). The temperatures suitable for operation are far above the touchable limit of 120" F to 1 30" F. Normally, solenoids with class B insulation offer superior life expectancy and are recommended for all high cycling ap plications.
o
normally only have to concern ourselves with two different frequencies, those being either 50 or 60 cycles. For maximum performance, coils can be wound for either a 50 o r 60 cycle operation, but not for both. Now let us examine this further. A 1 10V-50hz solenoid, when operating on 1 10V-60hz, draws too little current, and will not produce its rated force. On the other hand, a 120V-60hz coil, when subjected to 1 20V-50hz, will comsume too much current, causing it to overheat and bum out. If 50hz and 60hz are looked at graphically, it is easy to see that a 50 cycle current will last longer during each increment of polarity change, but will oc cur less frequently during a 1 second period.
Time
- 182 -
using 60hz;
l lOV x !_ = 1 32V 5
A 120V-60hz solenoid, on the other hand, has more turns on its coil than does the 50hz modeL The longer duration of a 50hz current saturates the magnetic field of a 60hz coiL This, in turn, lessens the impedance of the AC solenoid, which draws excessive current Nevertheless, the thermal overload problem can be eliminated by reducing the applied voltage to 5/6 of the solenoid's rating, hence:
Dual frequency coils (50-60hz) are actually wound for 1 10V-50hz and then used on valves where their reduced performance at 1 20V-60hz is adequate for proper valve operation. This dual frequency compromise is possible only because there is not too great of a difference in power and frequency between the 50 cycle and 60 cycle operation, and most 50 cycle voltage is 100 volts, while most 60 cycle voltage is rated at 120 volts. The previous explanation showed that if Europe operated on 1 10V-50hz and the U.S. operated on 1 32V-60hz, there would be no need for different solenoids. Unfortunately, this compromise does not leave the end user much margin of safety for fluctuations in supply voltage. In addition, if the 50hz solenoid attains sufficient shifting force when operated on .60hz, it will have too much force when operated at 50hz. This extra force can actually cause the solenoid to hammer itself to pieces.
120V x!_ 6
This means that the 1 20V-60hz solenoid will not overheat if operated on 100V-50hz.
t ::::: :
Extra Destructive Impact Must Be Absorbed Here
5 Lbs.
Up to now, we have assumed that our solenoids are ac tuators which are simply bolted to the exterior valve housing. Like any of the mechanical or pilot actuators, they work against a pushpin which is dynamically sealed against leakage of oil from the tank port of the valve. These solenoids dissipate heat to the surrounding air and are com monly referred to as air gap solenoids. The wet pin solenoid
- 183 -
is slightly different in design since it allows tank port oil to communicate between the housing of the valve and the housing of the solenoid. This offers several major ad vantages.
u-cup or o-ring seal on the pushpin, the leakage problem caused by seal wear is completely eliminated. Also, by eliminating the pressurized dynamic sealing, the overall shifting force is considerably reduced for both the solenoid and the return springs.
Q U I ET OPERATION
Quiet operation is another feature of wet pin solenoids. Although the clicking of a single solenoid is not all that ob jectionable, noise does become a problem on high cycling machines which may incorporate twenty or more directional controls. The reason for the quiet operation of wet pin solenoids is that the motion of the plunger is dampened by the hydraulic oil. As shown in the cross-sectional illustration, oil must be displaced for motion of the plunger to occur. The plungers are manufactured with axial holes or milled slots which provide a path for this oil transfer. Generally speaking, the path for oil flow through the plunger is relatively large for an AC solenoid, so as to allow the plunger to be pulled into position as quickly as possible. This, of course, lessens the heat generation by reducing the time during which the solenoid will draw a high inrush current. On the other hand, DC solenoids have a more restrictive path, which allows for extremely smooth valve shift. Typical response times are 20 to 30 m.s. for a wet pin AC solenoid, and 45 to 70 m.s. for DC versions.
All Moving Parts Are Isolated From lower Operating Forces Damage Due To Moisture For Both Solenoids And Springs Better Heat Dissipation - longer life Features Of Wet Pin Solenoids
- 184 -
feature available for convenience in troubleshooting a hydraulic system. In fact, most solenoids offer the manual override as a standard feature. As shown, the manual override is located in the end of the solenoid cover, and simply provides a mechanical means to apply an external shifting force to the plunger in the solenoid. This is an in valuable tool when it is necessary to feel if the solenoid is shifting the valve. The manual override can also be used to find out whether or not there is any type of mechanical ob struction. In some systems, emergency operation can be ac complished by using the manual override in the event of a power failure in the control circuit. Some manual overrides are push button type, while others require the use of a small screw driver, allen wrench, or welding rod for actuation.
INDICATOR LIGHTS
SOLEN OlD LIFE EXPECTANCY
'
In the foregoing discussion, we have mentioned several fac tors which can cause premature failure of the solenoid. The major problems are summarized as follows:
-Plunger is mechanically prevented from shifting -Excessive cycling -Too low or too high supply voltage -Operation on the wrong frequency -Short circuiting due to moisture
These variables make it quite difficult to project a life ex pectancy for any given solenoid. For this reason, we offer the following laboratory results for comparison of the different solenoid types.
AC Air Gap Solenoids: DC Air Gap Solenoids: AC Wet Pin Solenoids: DC Wet Pin Solenoids:
S OLENOID ACCESSORIES
In selecting solenoid operators, there are several options which will aid you in troubleshooting and in servicing of the valve. Manual overrides, indicator lights, and a variety of plugin connectors are readily available and should be con sidered.
Indicator lights are either incandescent or neon bulbs which are wired parallel to the electrical solenoid. They are in tended only to indicate when power is being supplied to the solenoid. Indicator lights are helpful in determining whether a malfunction has occured because of a valve failure or a problem in the electrical control circuit. If the valve is not shifting, but the light continues to function, a valve failure is indicated. However, if the light is not illuminated, chances are that the malfunction has occured in the control circuit. During proper operation of the equipment, indicator lights can be used to indicate what portion of the cycle the machine is in. Indicator lights are usually added to the electrical junc tion box and positioned adjacent to the solenoid with which they are connected.
PLUG-IN CONNECTORS
The plug-in connector is an optional feature which simplifies the replacement of a malfunctioning valve. The valve is simply unplugged, removed from its subplate and then replaced with an equivalent model. In the past, a single plug connection was made to the central electrical box on top of the valve body. This, of course, facilitates the replacement of
MANUAL OVERRIDES
Manual overrides are probably the single most important
- 185 -
pressure at the valve's tank port. Needless to say, since these housings are usually constructed of molded plastic, the T port pressure must be restricted. When the directional control is used to perform a pure 4-way function in a properly designed system, the tank port pressure should not exceed 300 to 500 PSI. Under these conditions, we would be well within the T port rating of any directional control. However, when the directional control is used in a series circuit (P port of the second valve connected to the T port of the first valve), or to perform a function other than its intended 4-way usage, the following points must be considered.
the complete valve, but requires unwiring of the solenoid during va!ve repair. Although this method is still quite popular (and will remain so), another type of plug-in con nection is gaining in popularity. Today, particularly with wet pin solenoids, it is not un common to see the coil molded into a plastic housing. With this design, it is also relatively simple to mold an inexpensive male portion of the plug in the same housing. In this way, the plug-in connection is individually made to each solenoid on a double solenoid valve. Repair can be made simply by un plugg the solenoid and removing it from the valve housing. ing
G)
0-RING SEALS
The o-ring is the major sealing device used in all hydraulic components. The o-ring is nothing more than a molded ring of snythetic rubber which has a round cross section when in its free state. Although generally intended for high pressure
- 186 -
The o-ring is installed in a machined groove housing . . in the {;;\ and is slightly compressed . . .
.
\!:.)
Valve Housing
Subplate
static sealing. it can also provide adequate sealing for short stroke reciprocating motion at lower operating pressures. In static applications (such as those found between the direc tional valve's housing and its subplate), the seal must only provide a leak free seal between the mating surfaces, which are rigidly in contact. Since there is virtually no clearance, the o-ring is fully contained in the annular groove formed by the mating surfaces. Pressure deforms the o-ring equally, causing it to fill any imperfections between the two surfaces.
Stationary Guide
- 187 -
Pressure Working From This Direction Cannot Be Sealed Cross Section Of A U-Cup Seal U-CUP PACKING
The modem u-cup packing has evolved from the com pression packing, which was one of the first methods used in sealing hydmulic systems. The u-cup gets its name from the shape of its cross section, which has the shape of a U, or sometimes of a V . U-cup packings are ideal for sealing parts which move axially with one another. Typical examples of their use are rod seals for hydraulic cylinders or in pushpin seals for direct operated directional controls. As shown in the cross-sectional illustration, the u-cup, when installed in a properly dimen sioned groove, is effective for sealing against high pressure, but only in one direction. The sealing effectiveness increases with increased pressure.
PT PT
Hand Lever Actuator Double Solenoid Actuators Complete Valve Symbol For A Three Position Spring Centered Directional Control
A B
AB
- 188 -
SYMBOL
-A Spring
-A Plunger or Tracer
-A Roller
-A Foot Pedal
-A Push Button (Palm Button) -A Manual Actuator Without Indication of Control Type Pilot Operation By Means Of:
-A Hydraulic Pilot
-A Pneumatic Pilot
- 189 -
theory, it would be possible to make direct acting valves in larger sizes. However, in so doing, the solenoid actuator would become excessively large. For this reason, direct acting valves are usually used in systems of up to 20 to 25 GPM. For higher flow systems, pilot operated directional controls are used exclusively, because of their more compact design.
_r. -- +- -- =, r- -- --
(D
'YA
.p
,& B 'Y Y
(!)
is drained to tank . . .
- 190 -
It is important to realize that the main spool is hydraulically returned to its offset position when the pilot valve returns to its spring offset position. The spool is then held in position by the pilot pressure which is dead-headed against the right hand end of the spool. If for some reason, there is a loss of pilot pressure, the slave spool could shift due to high flow forces. It is also important to mount these valves with the spool in a horizontal position. This will prevent the spool from shifting because of gravity in the event that pilot pressure is lost.
XT A P B Y
SPRING OFFSET SLAVE SPOOLS For economical reasons, the hydraulically offset slave spool is the most t:ommon two position pilot operated valve. However, for fail-safe applications, or in circuits where pilot pressure may be lost during a portion of the cycle, a spring offset slave spl option is available. As shown in the cross sectional illustration, this option includes an end cap with a large spring cavity. The heavy spring automatically positions the slave spool in the offset position, should pilot pressure be lost.
Two Position Spring Offset, Pilot Operated 4-Way Valve (Shown De-energized)
It must be remembered, however, that the spring must be compressed when the slave spool is shifted to the opposite flow position. This increases the minimum pilot pressure requirements two-fold. For example, the minimum pilot pressure requirement for a typical two position hydraulically offset valve is 75 PSI. However, with the spring offset slave spool option, the minimum pilot pressure requirement in creases to 150 PSI.
G)
this end of the slave spool is exposed to pressure . . .----:1!....! P-B & A-T
Two Position Hydraulically Offset, Pilot Operated 4-Way Valve (Shown Energized)
- 191 -
DOUBLE SOLENOID TWO POSITION PILOT OPERATED VALVES In the cross-sectional illustrations, the hydraulically offset or spring offset pilot operated directional controls were shown to have spring offset pilot valves. For convenience in control circuit design, two position main valves are also available with double solenoid two position pilots, with or without detents. In either of the double solenoid pilots, you must remember that the main section is still the same (either hydraulically offset or spring offset). The words "double solenoid" and "detented" only described the positioning method for the pilot ualue spool. A complete description of these methods of positioning has been discussed previously in this chapter.
valve housing. With this design, a three position pilot valve is used, which vents both spring cavities to tank in its center position. As shown in the cross-sectional illustrations, the spring force pushes on the spool until the spring plate bot toms-out on the shoulder in the valve housing. Although the centering is shown from only one direction of operation, an identical spring force operates from the right-hand side when the slave spool is shifted in the opposite direction. The spring forces are high enough to center the slave spool against the Bernoulli flow forces when the valve is passing its maximum rated flow. This, in turn, determines the minimum pilot pressure required to shift the slave spool against the cen tering springs. The minimum pilot pressure ranges from 60 PSI for smaller pilot operated valves to approximately 200 PSI for the largest spring centered versions. It is important that the circuit be designed so that the minimum pilot pressure is always provided.
THREE POSITION SPRING CENTERED SLAVE SPOOLS For three position pilot operated directional controls, suf ficient centering force can normally be achieved by using relatively heavy centering springs in the end caps of the main
HYDRAULICALLY CENTERED THREE POSITION VALVES For the new generation high flow directional controls, and for larger pilot operated directional valves (nominal port size 3"
X T
- 192 -
and above), sufficient centering force cannot always be achieved through the use of centering springs. For these valves, the necessary higher forces are achieved through hydraulic centering. On large valves, the hydraulic centering is an integral part of the main valve design. However, on smaller valves, which can be ordered with either spring or hydraulic centering, the hydraulic centering device is in tegrated into an optional end cap. Two of the most common methods of achieving hydraulic centering will now be discussed.
12
- 193 -
G) pressurizes
When this shoulder on the centering bushing is not bottomed in the valve housing . . .
- 194 -
pressure. However, even though the force due to pressure on area A, is higher, the spool cannot be moved out of its center position to the left. This is because the outside sleeve is carried along with the spool when it moves to the left. The moment the outside sleeve loses contact with the valve housing, the force due to pressure on the full area A3 is di reeled to the spool. Consequently, the spool is captured in its center position between pressure working against the two piece piston assembly on the left, and the pressure force on the spc0l land on the right. The center position is determined by the point at which the left-hand spool land, the valve housing shoulder, and the outside sleeve come in contact. The springs used in conjunction with the hydraulic centering device provide additional centering forces and hold the spool in its center position when there is no pilot pressure (during start-up, for instance). However, they are not required for proper operation of the hydraulic centering device under pressurized conditions. The L drain port must also be con nected directly to tank for proper operation of the valve. The operation of the valve in its shifted position is shown in the cross-sectional illustration which follows. Tum to page 5-40
PILOT PRESSURE SUPPLY AND DRAIN Up to this point, the cross-sectional illustrations have shown the pilot valve with separate connections for its pressure and tank ports. In fact, most pilot operated directional controls have small passages through the main valve housing so that external pressure and tank connections can be made to the pilot valve through the main valve's subplate. The pilot pressure supply port has a X designation, while the tank con nection to the pilot valve is called a Y drain port. To facilitate plumbing, it is sometimes possible to pilot and/or to drain the piloting directional valve from the same pressure and tank passages which supply the main valve. This is referred to as internally piloted and/or internally drained. Most pilot operated directional valves can be field converted from an external to an internal pilot, and from an external to an internal drain, or vice versa. Since a valve which is assembled for one type of pilot and drain will not work on a system designed for the other, it is important that we know how to make this conversion. The two cross sections which follow show a typical valve, the first assembled with the external pilot and external drain
- 195 -
Drain Connection For ----1----.....c Hydraulic Centering Device B Pilot Operated Directional Valve With Hydraulic Centering Device
unbalances the spool, causing it to shift to the left. 3 Position Hydraulically Centered Valve Shown With Slave Spool Shifted To The Left
- 196 -
(i)
3 Position Hydraulically Centered Valve Shown With Slave Spool Shifted To The Right
G) With an
With the pilot spool in this position, the valve is externally piloted . . .
0 through the X
port in the main valve's sub plate . . .
Pilot Operated Valve With External Pilot And External Pilot Drain
- ]] LJ S JtW 1] !1 ]i I IM L
- 197 -
_.fi
and plugging th42-4--external X port . . . L!...l Pilot Operated Valve With Internal Pilot and Internal Drain
configuration. The second view shows the internal pilot and internal drain variation. Of course, the other two possibilities are internal pilot, external drain (which is quite popular), and external pilot, internal drain. The method of conversion shown in the cross-sectional illustrations is a relatively modern technique. Access to the pilot spool is simply achieved by removal of the end cap on the X port side of the valve. Also, to gain access to the in ternal plug for internal/external drain conversion, the pilot valve is simply removed. Another method of converting from one type of piloting (or draining) to the other is by installing pipe plugs internally in the main valve housing. A larger external pipe plug is used to allow access to these internal plugs. The two plug method of conversion has always been an ac ceptable method for making the internal/external drain con version. Many times, however, it has proven to be un satisfactory for making the X port conversion. The problem is that the internal plug is exposed to pressure on both sides when the valve is in operation. When the pipe plug is pressur ized from its top side, the tapered threads are forced together as the plug is pushed into the taper. Eventually, this makes removal of the internal plug difficult, if not impossible. This is generally not a problem in the Y drain conversion since pressures are relatively low.
Internal Plug 1 / 1 6 " NPTF For Internal Pilot Drain, Plug 1/16" NPTF To Be Removed And Port Y In The Subplate Plugged Two Plug Method of Converting Internal Pilot Drain Conversion
(Note: Cross Section Is An End View Of The Main Valve Housing)
- 198 -
Main Valve
In designing a system, sufficient pilot pressure must exist during the portion of the cycle when the pilot operated direc tiona! valve i s required to shift and to remain shifted. This means that sufficient pilot pressure must be supplied to the X port for an externally piloted valve, or at the main P port for internally piloted valves. Unfortunately, this is often overlooked in the initial system design stage. This is par ticularly true of designs with internal piloting and an open or tandem center slave spool. In a internal pilot design, there must always be a resistance to flow entering the P port of the valve. If there is no re sistance to flow, there is no pilot pressure, and the valve will not shift. The examples which follow show a three position valve with a fully open center spool, and a two position valve with an open center cross-over. In the first example, it is easy to see that the pump freely circulates flow to tank in the cen ter position. This means that the valve, as shown, cannot be shifted out of its center position. However, the same slave spool assembled without springs, with a two position spring
G)
open center spool is spring cen tered . . . Three Position Spring Center Valve With Open Center Slave Spool And Internal Pilot
- 199 -
pilot pressure is directed to this passage, and the slave spool begins to move.
(j)
crossover position . . .
X J&"fff T
G)
c .... . <I) -0
s.et.e
.. ,
0 113 c 0
...
cartridge is supplied with a cracking pressure equivalent to the minimum pilot pressure requirements of the directional valve (see Chapter 4 for a complete description of cracking pressure). With the back pressure check valve installed in the tank port cavity, pump flow is circulated to tank at the pressure required to open the check valve poppet. The P port of the pilot valve is exposed to this back pressure, and it is sufficient to pilot the slave spool into its shifted position (s).
- 200 -
0
the residual 65 PSI is directed to -+- this spool end.
there is little or no
Internal Pilot
From Pump
Pilot Operated Valve With Back Pressure T Port Check Valve Must Be Externally Drained
When you use a back pressure check, be sure the pilot operated directional valve is externally drained. If the valve were to be internally drained, the pressure at the T port of the pilot valve would be equal to the pressure at the P port. When the pilot valve shifted in an attempt to move the slave spool, both ends of the spool would be equally exposed to the back pressure. Since the shifting force would be bal anced, the slave spool would not move. this cartridge P port sequence (pageS-46).
P PORTSEQUENCE VALVES
Modem coring techniques have recently allowed valve manufacturers to cast valve housings with intricate internal passages. For this reason, it is now possible to supply direc tional controls with P port sequence valves for maintaining minimum pilot pressure requirements. The advantage of maintaining pilot pressure with a P port sequence cartridge is that a directional valve with internal pilot and open or tan dem center spools can also be internally drained. In many ap plications, this eliminates the need for piping a separate drain line. The cross-sectional illustration shows the installation of
- 201 -
pressure here . . .
Pilot Operated Valves With P Port Sequence Valves For Maintaining Pilot Pressure Can Be Internally Drained
Section A-A
A major concern in selecting directional valves for a series circuit is that they must be large enough to pass the required flow with little pressure loss. Since resistances in series are additive, the sum of the individual pressure drops dictates the pressure at the outlet of the pump when the circuit is cir culating flow to tank. Remember, this pressure at the rated flow converts into heat. For this reason, it is not desirable (nor is it necessary) to use a pilot pressure insert in each of the valves. If, for instance, we had ten valves in ser ies, each with its own 65 PSI pressure insert, the circulating pressure at the pump would be a minimum of 650 PSI. This is, of course, unnecessarily high. All that need be done to maintain pilot pressure for all valves in the series circuit is to place a pressure insert in the last valve in the series (this valve can be either a P port sequence or a T port back pressure check). As shown in the circuit illustration, the back pressure which is generated is maintained throughout the system (upstream of the back pressure valve) at a pressure equivalent to the cracking pressure of the cartridge insert. Since the pressure at both the P port and T port is equal for all valves in the series circuit, they must be externally drained.
- 202 -
To Actuator 1 Titndem Center Slave Spool Pilot Valve P Port Pressure Sequence
To Actuator 2
Internal Pilot
Drain
Drain
External
- 203 -
the pilot valve. A typical 3/4" valve with an AC solenoid pilot shifts from center to end position in 40 m.s. at 700 PSI pilot pressure, with the time period dropping to 25 m.s. at 3000 PSI. However, for most applications, this time period is too fast for smooth system operation. When flows in excess of 25 GPM are being handled at a relatively high pressure, the decompression shock at the time of valve shift has an important influence on smooth system operation. On valves designed to handle large flows, the "metering-notches," as discussed earlier in this chapter, become a major design consideration. However, even if the slave spool is notched sufficiently, shifting too fast may not allow enough time for pressure equalization to occur (see "Metering Notches"). In general, there are two accessories available for pilot operated directional valves, both of which slow down the shifting speed of the slave spool. This, in turn, tunes out the "water-hammer" associated with fast response.
between the main valve and the pilot (see Chapter 3). The flow control is usually mounted in a meter-out orientation and allows independent shifting speed adjustment for both directions of spool shift. If the flow from the end caps is suf ficiently restricted, this type of speed control not only eliminates "water-hammer," but it also allows for an ad justment of acceleration or deceleration for the actuator. The adjustment adjacent to note 8 in the drawing influences the speed of the slave spool whenever it moves to the right. In effect, this controls both the time period required for the spring to return the spool to its center position, and the time required for pilot pressure to move the spool to its right-hand shifted position. Since the setting can be optimum for only one mode of operation, this adjustment must be a com promise. On the other hand, if you want only to control the shifting speed from center to either end position, the cen tering spring will center the spool at maximum speed (ap proximately 50-60 m.s.) if the flow control is mounted in the "meter-in" orientation . One last consideration when you use the sandwich flow con trol to control shifting time is that severe restriction of the pilot flow will show up as a dwell period when energization of the solenoid causes no initial actuator response. The reason for this is that the severely restricted flow causes the slave spool to move slowly through its overlap. This time delay can be undesirably long, if the adjustment is not set properly.
Pilot Orifice
STROKE LIMITER AND SPOOL POSITION INDICATORS
'
The simplest and most inexpensive method to lower the response time of the pilot operated directional control is to install a non-adjustable orifice in the P port of the pilot valve. This causes a meter-in flow control function, which slows the shifting of the slave spool equally in both directions. In general, a number of different orifice diameters are available to meet the need of various system requirements. Un fortunately, selection of the proper orifice requires some ex perience with the system, and may require some initial ex perimentation w different orifices. ith
Early in this chapter (in our discussion of "Maximum Flow Rate for Directional Controls"), we showed how spool diameter and spool stroke affect the final maximum flow area in a shifted position. Consequently, a crude, but ad justable, flow control function can be achieved by in corporating an adjustable stroke limited on the slave spool. Although this flow control setting is not very sensitive, it can provide adequate speed control for many applications in one compact package. If speed control is required for both direc tions of actuator motion, both end caps can be replaced with stroke limiter covers. However, if speed control is desired only in one direction of operation, a spool position indicator can be installed in the opposite end cap. This facilitates the setting of the flow control by giving the operator a visual reference. Since most stroke limiters incorporate a static o ring seal, adjustment should not be attempted while the end cap is pressurized.
- 204 -
(D
--.j;i
pilot oil free flows over this check valve . . . adjustment controls acceleration -:;,.,..,.--- in the opposite : direction of motor rotation.
which causes these flow areas to open gradually. The motor accelerates in this direction . . .
plied that the pilot valve always has solenoid actuators. However, it is not uncommon to replace the solenoid ac tuated pilot valve with one which has manual, mechanical or pneumatic operators. Notice that we have eliminated hydraulic actuators from the list. If the method of operation is to be hydraulic, it would be repetitious to have a hydraulically piloted pilot valve operating a hydraulically piloted slave spool. Fortunately, a simple cover plate will allow us to hydraulically pilot the slave spool directly. As shown in the cross-sectional illustration, the cover simply interconnects the X port with one spool end, while con
- 205 -
Cover Plate
This Spool Is Assembled For External Pilot Pilot Pressure Applied At This Port Shifts Spool To The Right Pilot Pressure At This Port Shifts Spool To The Left
- 206 -
necting the Y port to the opposite side. The remote pilot con nections are simply made through the X and Y ports in the subplate of the main valve. The slave spool can be hydraulically offset, spring offset, spring centered or
hydraulically centered. Shifting speed can be adjusted by using a sandwich flow control between the main valve housing and the cover plate.
Descriptions
-- - - - -
I L----I I
I I
I I _, I
-t J
y
Two Position Hydraulically Offset Slave Spool With Spring Offset Single Solenoid Pilot Valve
p T
A B Two Postion Spring Offset Slave Spool With Spring Offset Single Solenoid Pilot
- - - - P T Y X
A B Two Position Hydraulically Offset Slave Spool With Double Solenoid Two Position Pilot
L - - - - -
._ _ - - -
I II I 1 1- I
- -
p T y
A B
I , I -1 -'
...
1 1
Two Position Hydraulically Offset Slave Spool With Double Solenoid Detented Pilot
- 207 -
Three Position Valves (Only Closed Center Conditions Are Shown) Symbol A
B
Description
tx
,y
'
iftx
I
p
A
T
B
-
- _ L .! I
center position of the directional valve influences the braking ability of a counterbalance valve, and why it is necessary to incorporate port or cross port reliefs when using directional valves which block the actuator ports. Again, in Chapter 4, we have shown that the operating characteristics of a pilot operated check valve demand the selection of the proper directional valve center position. In this chapter, we have outlined the flow paths made available by differently machined spools. We have discussed float center and regenerative center spool applications as pilots for spring centered and pressure centered pilot operated directional controls, respectively. We have also outlined the conditions for pilot operated, tandem center spool valves in series circuits. Since it would be impractical to cover the multitude of application examples possible for various spool types, the examples here will outline only a few of the less obvious applications and the associated complications.
- 208 -
PARALLEL CIRCUITS
When two or more directional valves are piped with a com mon pressure source (and tank return), they are said to be piped "in paralleL" In selecting the directional valves for use in parallel circuits, you must remember that three position valve spools must block their pressure port in the center spool position. In addition, two position valves can be used in parallel circuits only if they are to control the direction of a cylinder which will "bottom-out" If these two points are not observed, the pump flow will simply take the path of least resistance. This path could be free flow to tank over the cen ter position of an incorrectly selected three position valve. On the other hand, if a hydraulic motor has little or no load and is being controlled by a two position directional valve, it would be impossible to build pressure in the rest of the parallel circuit. A typical example of a two valve parallel cir cuit is shown in the following illustration. In this circuit, the solenoid vented relief valve unloads the pump to tank whenever the actuators are not in operation. Its solenoid is electrically interlocked with solenoids one, two and three on the directional valves, so that it is energized
whenever one of the other three solenoids are actuated. Let us assume the machine cycle is as follows: Solenoid 3 is actuated first, which causes cylinder B to "clamp" a work piece into position. Solenoid three remains energized, while solenoid 1 is actuated to extend the "punch" cylinder A. After punching is complete, solenoid 1 is de energized, and cylinder A retracts. After full retraction of cylinder A, solenoid two is energized to unclamp the work piece. De-energization of solenoid 2 completes the cycle, and the solenoid relief vents pump flow to tank_ Cylinder B is controlled by a "float center" spool so that the cylinder can be positioned manually during machine set up. You will notice that both directional valves in this circuit have P port check valves. Check valve A holds cylinder A in its retracted position when the relief valve is vented. Check valve B is required to maintain clamping force while cylinder A is travelling through free air. It should be noted that the P port pressure insert for pilot operated valves can also be used as a P port check valve in this type of circuit_ In parallel circuits, the P port check valve is not necessary for main taining pilot pressure, since the main valve cannot be open center. It does, however, offer a compact and economical
Cylinder S
Check Valve A
- 209 -
nected to tank .The cylinder will retract at the rate of: (formulas are explained in Chapter 1).
V=
_ _ _ _ _
_ _
= 210 in./min.
However, during retraction, the directional valve must also be large enough to handle the flow from the blind end of the cylinder, which is:
GPM= A x V =
231
When the solenoid is energized, pump flow i s simultaneously directed to both ends of the cyli der. However, because the n blind end of the cylinder has the larger area, it also has the larger force at equal pressure. The cylinder will extend, creating a flow of oil from the rod end port. Due to the piping, the rod end oil supplements the pump flow and passes through the directional valve to the blind end of the cylinder. Consequently, the directional valve must be capable of handling this combined flow. Although, at first glance, the flow calculations may appear to be complicated, using a logical approach will make the calculation of flow quite sim-
3000 PSI
- 210 -
pie. Since no oil is lost as the cylinder extends, the oil which is forced out of the rod end can be thought of as filling an equivalent volume on the blind end. This means that the ex tra volume on the blind end side must be supplied by the pump. Geometrically, this volume is equivalent to that which is displaced by the rod. During regeneration, the cylinder bore has nothing to do with the cylinder speed, thus we can think of the cylinder as having a rod without a piston. Con sequently, the cylinder extends at the rate of:
V =GPM x 23 1 = 5 x 23 1 = 1 63.59 in./min. 7.06 A (rod)
Now that we know the velocity at which the cylinder ex tends, we can also calculate flow coming from its rod end.
GP M= A x V = 5.5 x 163.59 = 3 .89 GPM 23 1 231
This spool type is generally used only in high cycling ap plications, and where the cylinder does not have to be stopped in midposition. It should be noted that the cylinder will only remain retracted if the left solenoid remains energized. Likewise, the pump flow cannot be unloaded by the directional valve.
SPOOL WITH REGENERATIVE END POSITION
Consequently, the directional valve must handle the com bined flow of 8.89 GPM (3.89 GPM + 5 GPM). Without a doubt, this is a relatively small valve, and is in proportion to other components in the system. However, if you go through the calculation using a 4" 0 bore x 1" rod cylinder with the same pump, plumbing and valve size must become con siderably larger. The calculated solution to the cylinder's velocity is 1471 in./min., with a combined flow of 80 GPM! To achieve a 30 F.P.S. oil velocity, the nominal port size would be approximately 1" diameter. On the other hand, in the regenerative circuit with the 4" bore x 3" rod cylinder, the line size and valve could be as small as 3/8". In regenerative circuits, the increase in speed is accompanied by a decrease in maximum output force capability of the cylinder during the regeneration portion of the cycle. Pressure only works on the effective area of the rod during regeneration. Consequently, regeneration is normally used only to move the cylinder to the work quickly. When the working position is reached, the circuit vents the rod end of the cylinder to tank so that fuel tonnage can be developed. Some of the directional valves which can be used to ac complish this function will be looked at.
REGENERATIVE CENTER SPOOL
The spool with a regenerative end advances the cylinder in regeneration when the right-hand solenoid is energized, and retracts the cylinder in the conventional manner, when the left-hand solenoid is actuated. The advantage that this spool offers is that the cylinder can be stopped in midstroke, since the valve has a closed center configuration. However, this spool alone cannot be used to advance the cylinder under full tonnage. The slow speed full tonnage cycle can only be ac complished if a second two position 4-way valve is added to the circuit.
The regenerative center valve spool produces three cylinder functions: regenerative forward, slow speed forward, and retract. In reference to the schematic illustration, the cylinder extends during regeneration when the valve is in its center position. When the valve is shifted to the left, slow speed and full tonnage result because the rod end of the cylinder is con nected to tank. Likewise, when the valve is shifted to the right, the cylinder will retract.
- 211 -
In this circuit, when solenoid 3 is not actuated, the cylinder will extend in regeneration when solenoid 2 is energized. :...ikewise, when only solenoid 1 is actuated, the cylinder will retract. Full tonnage, however, is developed in the slow ,;peed mode when solenoids 2 and 3 are simultaneously energized. Of course, de-energization of all solenoids stops the cylinder in any position. This circuit can be automated by energizing solenoid 3 by means of either a pressure switch or a limit switch. The pressure switch would be connected to the blind end side of the cylinder, and would automatically put the circuit into full tonnage when the predetermined load induced pressure has been reached. If the pressure switch were set properly, this changeover would occur just before the load resistance caused the cylinder to stall in regeneration. If load induced pressure fell below the adjustable differential of the pressure switch (see Chapter 8), the cylinder would automatically return to high speed regeneration. On the other hand, a limit switch can be used simply to take the cylinder out of regenertion at a preselected stroke. There are many other methods available for accomplishing a regenerative circuit. However, for the purposes of this chap ter, we only intend to discuss the use of directional valves, which are designed specifically for this purpose.
is larger than the 392 lbs. of force due to pressure here. The cylinder extends . . .
0 theexposed pressure is
equally here . . . valve centered . . .
2 ::::::-----_: " R0 d
From Pump
In a single valve circuit, the fully open center spool can be used to allow the actuator to "float", while, at the same time, it unloads the pump flow to tank. In other words, the func tions of a float center and tandem center spool are com bined. Although this spool works well with hydraulic motors, you must be careful in applying it to a single rod cylinder with differential areas. Likewise, the open center spool should never be used to replace a tandem center spool in a "series" circuit. In the circuit shown, the open center valve back pressures both ends of the single rod cylinder. If the cylinder has little or no load, it will extend because the forces, due to pressure, are unbalanced. In the example, the cylinder would extend with a force potential of only 314 lbs. However, higher back pressure or larger differential areas in the cylinder could make this extension force considerably higher.
be used at extremely high pressures, even with low viscosity fluids. In fact, by manufacturing the component parts from stainless steel, the basic design can be used with pure water at operating pressures up to 7000 PSI. However, before proceeding to the actual valve construction and operation, we would like to point out a few basic differences between mineral oil and water hydraulics.
Examples Where Leak Free Directional Control Is Required
It is possible to apply the poppet style directional control whenever a leak free directional function is required. Likewise, because of its leak free sealing capabilities, it can
- 212 -
pressurized water with a close tolerance fit is a problem which has not yet been overcome. Although high pressure water pumps are available today, they are 10 times the size of an equivalent oil hydraulics pump. The advent of pure water hydraulics will not be possible until component designs and materials are developed to overcome these problems compactly and economically.
Scissor Lifts
To further understand the sealing of pressurized water with close tolerance fits, consider the following facts. First, if a typical mineral oil were to be chosen, it would have a viscosity of 150 SUS at 100" F. On the other hand, water at 100" F. has a viscosity which approaches 0 SUS. If we were to take the two fluids and try to hold pressure with a spool type directional control, the leakage rate with water would be approximately 40 times higher than it would be with oil. This clearly limits the application of spool valves in water hydraulic systems. A second problem created for the spool design by the low viscosity of water is that high fluid velocity, out of necessity, accompanies the high leakage rate. This high velocity fluid quickly erodes the close fitting metal surfaces. In hydraulics, this erosion process is referred to as "wire drawing," most likely because of the appearance of the eroded surface. The quick deterioration of the metal surfaces produces a valve which can soon leak the entire output flow of the pump. On the other hand, the advantages offered by water hydraulics cannot be discounted. For instance, with a typical mineral oil, as the temperature is raised from 32" F to 212" F, the viscosity changes from 3300 SUS to 46 SUS. This causes the system to react sluggishly at start-up, in creasing its speed as temperatures warm up. Water's viscosity remains constant between 32" F and 212" F. This means that a water hydraulic system is virtually immune to fluc tuation in speed because of temperature changes.
Workshop Crane
Fairground Carousels
Apart from their technical or environmental advilntages, water systems are also desirable where fire resistance is necessary. Typical examples are hot rolling mills, forging and extrusion presses, continuous casting machines, and furnace door applications. Other examples are machines on which the products being manufactured are inflammable, such as particle board presses, rubber vulcanizing presses and plastic injection molding machines.
- 213 -
Q)
Heavy Spring
T A P Internal Actuating Pin Valve Adjustment Single Ball, Normally Open 3-Way Valve
- 214 -
The cross-sectional illustration of a normal open valve shows a single ball double seat arrangement of the internal pieces. The ball type poppet is held against the left-hand seat by a relatively heavy spring force. Pressure is opened to the A port, while the tank connection is blocked without leakage. When the solenoid is energized, the mechanical lever lifts the ball from the left-hand seat and presses it into the right-hand seat. This causes P to be blocked from A, and opens A to T. The valve displays open center crossover characteristics in that all ports are intrconnected while the ball is being moved from one seat to the other. External sealing of the actuating pin is achieved through the use of two u-cup seals which are constantly pressurized by the pressure at port P in the valve. Also, the mechanical lever is incorporated to give the solenoid a mechanical force ad vantage of 6:1. The ball at the lower end of the mechanical lever is necessary to eliminate a side loading which otherwise could be transmitted to the actuating pin.
are blocked by a check valve function. Therefore, sufficiently high pressure at port A could lift the poppet from its seat causing a free flow to port P. For this reason, a cartridge check valve can be installed in the P port of the main valve. This assures leak free sealing, even if A port pressure becomes higher than that at port P.
Pilot Valve
The 4-Way Sandwich Plate P Port .; Check Valve , Cartridge Two Ball, Normally Closed 3-Way Valve
The cross-sectional illustration of a normally closed valve shows it to be similar to a normally open valve in basic operation. However, in this assembly, the seats are reversed, and two balls are used in the moving member. The right hand ball is held against the right-hand seat by the heavy spring force. This blocks P from A and opens A to tank. Energization of the solenoid presses the left-hand ball n to its i respective seat and also unseats the right-hand ball. The A port is connected to P and blocked from T in the shifted position. In this flow pattern, it should be noted that the P and A ports The cross-sectional illustration shows that a sandwich plate is mounted between the three-way poppet valve and its subplate. When used with the normally open three-way poppet, the flow pattern is P to A through the pilot valve, and B to tank through the sandwich plate. If a normally closed pilot valve is used, the four-way function in the de-energized position is reversed, namely; P to B and A to T. For clarity, the de-energized and energized positions are represented in schematic form. Please note that the schematics are shown with a normally open pilot valve.
- 215 -
equal pressure working against this area . . . 0-Ring Seal De-Energized 4-Way Two Position
:J
This vents pressure on this pilot piston . . . 0-Ring Seal Energized 4-Way Two Position
In this circuit, when both solenoids are de-energized, both ends of the cylinder are vented to tank through the A ports of the two normally closed three-way valves. This allows the cylinder to "float." Of course, pump pressure is blocked by the spring load poppet in the deactivated position. When solenoid one is energized, pump flow is connected to the rod end of the cylinder, which causes it to retract . Likewise, the cylinder will extend when solenoid one is de energized and solenoid two is actuated. It is interesting to note that if the two solenoids are simultaneously energized, pump pressure is directed to both sides of the cylinder. Assuming proper valve and cylinder size, the cylinder will ad vance rapidly in regeneration.
l!J
From Pump
In this circuit arrangement of two normally open 3-way poppet valves, the cylinder is positively held in position by the cartridge P port check valves. With both valves deac-
- 216 -
Il- ! I
l arT
I
1
I
- -- -
.1 :
r __
_J
iI ;; Choke
1
.
. I
I
- 217 -
:- I ' I I
rr' I
I I
I '
- 218 -
oulder
- 219 -
The main valve is piloted by a normally closed three way poppet valve. In the de-energized position of the pilot valve, the area behind the pilot piston (on the right-hand side) is vented to tank. Pressure at port P works over the effective area of the poppet nose, and causes it to shift to the right, as shown. Pressure in the P-A passage presses the opposite poppet into the right-hand seat, which positively seals the tank passage. When the solenoid is energized, pressure from port P pressurizes th right-hand side of the pilot piston. Since this piston has an area advantage, the double end-pop pet is pressed into the left-hand seat. The shifting speed of the double end poppet can be adjusted by incorporating the optional pilot choke flow controls. The closed center crossover is achieved by the extended nose on each end of the double end poppet. This nose is closely fitted to the inside diameter of the seat. When the poppet moves from right to left, the first thing that happens is that the right-hand poppet is unseated. However, because the nose Gf the poppet is still extended into the seat, the main flow passage remains closed, except for a minimal
ar:nount of leakage through the clearance fit. At ap proximately midstroke, the left-hand nose extension protrudes into the inside diameter of the left-hand seat, which blocks P from A. This occurs just before the nose of the right-hand poppet opens the A to T flow path. The net result is that the three ports are never interconnected during movement of the double end poppet. Of course, the function is identical when the spool moves to the right, which first blocks A from T, then opens P to A.
- 220 -
(j)
this element . . .
internal or sufficient external pilot pressure . . . All elements are seated, which blocks all possible main flow passages.
- 221 -
I
which holds this poppet . . .
'
I
b
I
I
.. .. -- -- it ._ .. .. .. .. -- -- it-r
__ _ __
L_
B X
0
------ u t t
P To B And A To T
and A with T.
- 222 -
(D
'
I I
'
L _ -TT
L_
.....------1 0
Y A B
I I
X\
CONCLUSION
In this chapter, we have attempted to explain the two most common methods of controlling direction of fluid flow in hydraulic systems: spool type and poppet style direction con trol. Most of the emphasis has been directed toward the sliding spool method of directional control, since this is by far the most popular. On the other hand, research in modem poppet valve design has developed a product with economic and technological feasibility. Among the poppet valve's strongest advantages is its leak free sealing capability and its ability to handle low viscosity fluids (even pure water) at high pressures. Your review of the material presented should give you an understanding of the following points.
capability of the valve. The spool positioning method was also covered in detail for both direct and pilot operated valves. With respect to direct operated valves, we have also covered the various methods of spool positioning. These included a two position valve with double actuators, and double ac tuators with detents or spring offsetting. Springs can also be used to provide a three position spring centered spool positioning. In addition, various types of valve actuators for providing shifting forces have been covered in detail. Ac tuator types include manual, mechanical, pilot operated, and electrical solenoids for use with either an AC or DC current. In addition, the description of solenoid actuators covered the advantages offered by either the air gap or wet pin design. We have also described pilot operated directional valves for use in systems using higher flow rates. In describing the method of operation, we have shown how the slave spool is shifted by a command from a direct operated spool type pilot valve. The description included four methods of positioning the slave spool: two position hydraulic offset, two position spring offset, and three position valves which are either spring or pressure centered. The methods of converting from internal to external pilots and drains have also been pre sented. The special requirements of an internal pilot valve when you use spool types which unload pressure have been discussed, with various methods of maintaining minimum
- 223 -
pilot pressure. In addition, the various accessories for pilot operated valves were explained. These included pilot chokes, stroke limiters and spool position indicators. This chapter also included a discussion of symbolism for both direct and pilot operated directional valves. These sym bols were used to outline the requirements of a number of various circuit applications. The application examples in cluded series circuits, parallel circuits, three methods of ob taining regeneration, and the application precautions with open center spools.
"wire drawing" is eliminated. The direct operated poppet valve has a three-way flow pat tern, and can be supplied in a normally open or a normally closed configuration. A sandwich plate is also available for converting the valve, so that it can be used to perform a two position 4-way function. In addition to solenoid operators, various manual and mechanical actuators are also available for direct operated poppet valves. To accomplish leak free directional control for higher flow rates, the direct operated poppet valve can be used to pilot a main valve housing which incorporates one or more logic elements. Descriptions of two, three and four-way pilot operated poppet type directional valves have been covered. For those of you who have been reading chapter by chapter, you have now been exposed to the major ualue type com ponents used in an industrial hydraulic system. In Chapter 6, we will turn our attention to the hydraulic pump. Selection of this single component can make or break a system design .
- 224 -
In the design of any hydraulic system, proper pump selection will have a significant influence on overall system per formance, operational efficiency, and cost. In regard to cost, it is important to understand that the initial acquisition is only one factor. Long range operating costs can make a bur densome expense of what seemed to be an inexpensive pur chase_ The expenditures which must be considered in evaluating the total cost of any system include: initial com ponent and piping expense, continual cost for generating and dissipating unneeded power, and the money spent to obtain an acceptable noise level. This chapter is intended to familiarize you with the pump types available, so that you can make the proper selection for your particular system.
PRIME MOVERS
In the United States, industrial grade electric motors are available in syncronous speeds of approximately 860, 1140, 1750 and 3420 RPM (the nominal ratings of these motor's speeds are 900, 1 200, 1800 and 3600 RPM). In general, the higher the electric motor speed, the lower is the cost of the electric motor for a given horsepower rating. However, the noise level and the maximum speed ratings of the pump sho uld also be taken into consideration in selecting an elec tric motor. For this reason, most industrial hydraulic systems use either an 1 140 RPM or a 1750 RPM electric motor. Mobile hydraulic systems, on the other hand, usually use in ternal combustion .engines as their prime movers. Since both diesel and gasoline engines have a variable speed output
- 225 -
Work Output
DISPLACEM ENT
The size of a positive displacement pump is usually ex pressed in terms of the number of cubic inches displaced during one revolution of the drive shaft. As will be shown, most pumps have more than one pumping chamber. Con sequently, the total displacement of the pump is the volume created by one pumping chamber multiplied by the number of chambers that pass the outlet porting during one revolution. Generally, displacement is represented in cubic inches per revolution. Another common method of representing the size of a pump is to list its nominal flow at a specific drive speed. For in stance, the variable volume vane pump (which will be discussed later in this chapter) is normally driven by a 1750 RPM electric motor. It is commonplace in the industry simply to refer to these pump sizes as 6 GPM, 8 GPM, 15 GPM, etc. The nominal pump rating does not represent an actual figure. A particular pump with a 8 GPM nominal rating at 1750 RPM may pump slightly more or less than 8 GPM depending on the load conditions. This brings us to another term: volumetric efficiency.
II
Outlet ICheck Suction Check Valve Valve .._FlowSimple Pump During Pressure Stroke
Once upward motion of the pumping piston ceases, the pump cylinder is filled with oil at nearly atmospheric pressure. When pressure in the pumping cylinder is close to the atmospheric pressure in the reservoir, the light spring force closes the suction check valve. Now, when the piston area is exposed to a downward force, a pressure is created in the captive fluid. Initially, as the downward force develops on the input piston, there is no flow, since the pressure in the pump cylinder is less than load induced pressure. However, the moment sufficient pressure is developed, the outlet check valve opens, transmitting flow and pressure (energy) to the output actuator. Needless to say, the output flow of the hand pump is deter mined by the volume displaced during one stroke of the pumping piston, and the number of strokes per unit time. On the the other hand, the pressure capability is determined by the mechanical integrity of the pumping cylinder, and the maximum force potential.
VOLUMETRIC EFFICIENCY
Theoretically, a pump which displaces 20 cubic inches per revolution will deliver 20 cubic inches of oil for each revolution of its input shaft. In reality, however, the actual pump output is reduced by two forms of leakage as pressure increases across the clearance fits of the pump. This leakage can be either crossport leakage, which means pressurized fluid flows back to the suction side of the pump, or in some pump designs, it can be leakage to the case or housing of the pump. Pumps which have case drain leakage ports simply allow pressurized fluid which passes through the clearance fits to collect in the housing and then free flow back to the reservoir through the case drain line. Of course, for a given clearance, the higher the outlet pressure (the higher the pressure drop across the clearance fit - Chapter 1), the greater is the leakage. Volumetric efficiency is a percentage figure determined by dividing the actual flow by the theoretical flow value:
If, for example, a pump size is stated as 10 in'/rev. at 1750 RPM, this pump should deliver:
------
- 226 -
If the actual pump output at 1750 RPM is 69.5 GPM, the pump is said to have a volumetric efficiency of:
OVERALL EFFICIENCY
In the process of selecting a hydraulic pump, it is important that you compare the efficiencies properly. It is quite com mon for technical literature to list one type of efficiency but not the other. However, it is best to compare the pumps on an overall efficiency basis, which would include both volumetric and mechanical inefficiencies. Mathematically, the overall efficiency figure is simply the product of the two values. In our example, the overall efficiency of the pump would be:
Because volumetric inefficiency does not cause mechanical work, the leakage flow produces heat. If the pump is operating at 2000 PSI outlet pressure, the rate of heat generation because of leakage is:
MECHANICAL EFFICIENCY
BTU = 1.5 GPM PSI = HR 1.5 (75. 75 - 69.5) 2000 =18,750 BTU HR
X
-
Another way of determining the overall efficiency of a pump is to compare the theoretical power output with the actual power required to drive the pump. If the pump is actually pumping 69.5 GPM at 2000 PSI, the HP that would be available to produce useful work is:
A nother type of inefficiency is that produced by mechanical friction during operation of the pump. If the pump were to be delivering flow at zero pressure, then no force (torque) should be required. In Chapter 1 we have shown how the pressure relates to the torque of a rotational device, namely:
However, if we use the actual torque required at the drive speed which we assumed to be 1750 RPM, we can calculate the actual horsepower input:
T=
--
PxD
2n
Where:
If w again consider our 10in1/rev. pump operating at 2000 e PSI, the theoretical torque would be:
-------
This is the same efficiency we obtained by multiplying the volumetric and mechanical values of efficiency.
In order to explain the difference between volumetric, mechanical and overall efficiency, we have, more or less, shown the steps by which a pump manufacturer determines the efficiency of his pump. However, from the designer's standpoint, the problem is not how to determine (or calculate) pump efficiency. He must understand what these values mean, and how they will relate to his system. If, for instance, you want to know the exact flow which can be expected from the pump, you must obtain from the manufacturer, the volumetric efficiency for the pressure at
- 227 -
which the pump will operate. The actual output flow can then
be calculated:
Where D =theoretical displacement (in3/rev.) On the other hand, if you want to determine the drive power required by the pump, the overall efficiency figure must be used. This is true because both leakage and friction tum in put energy into heat. Since leakage inefficiency is already in cluded in the E, figure, the actual output flow is used for the GPM value. This eliminates including the volumetric ef ficiency twice in our calculations;
For our example pump, the actual drive horsepower would be:
If we are interested in determining the rate at which the pump generates heat, we simply subtract the theoretical HP output from the actual HP input. This difference in HP can then be converted into heat generated in BTU/HR: 69.5 GPM
93.3 HP
a) HP (theoretical out) =
1714
x2000 PSI
81.1 HP
Angular Misalignment
= 12.2 HP
c) 12.2 HP
It is interesting to note that if we subtract from the total heat generation (31,049 BTU/HR) the heat generated by leakage as previously calculated (18,750 BTU/HR), we can find the amount of heat generated because of mechanical inef ficiency; this value is 12,299 BTU/HR. You will find that the ratio between volumetric and mechanical efficiency changes with pressure and operating speed. At low pressure, volumetric efficiency is high, but mechanical efficiency is low. At high pressure, better lubrication increases the mechanical efficiency, but higher leakage decreases the volumetric efficiency. With respect to speed, mechanical ef ficiency is higher at low speeds. However, volumetric ef ficiency is highest at maximum speed. This is true because pump leakage is pressure dependent. Consequently, the
By nature of its application, the pump must be considered as a precision instrument. For this reason we must pay par ticular attention to the mounting and general installation of this component. Proper support and proper shaft alignment are two of the most important considerations.
- 228 -
deliver flow in an amount equivalent to its fixed displacement. On the other hand, a variable displacement pump is also a positive displacement design. However, with this type of pumping mechanism, the size of the pump's displacement can be changed easily. Variable displacement pumps will be covered in detail later in this chapter. The amount of flow that is delivered by a fixed displacement pump can be changed only by changing the drive speed of the pump. Because there is no means of physically changing the pump's displacement, these pumps are generally less ex pensive and less complicated in design. However, since in dustrial systems usually use constant speed electric motor drives, the application possibilities of fixed displacement pumps are somewhat limited. In Chapter 3 we have shown how flow control valves can be use to adjust speed in a hydraulic system. However, we have also shown how the flow control can be responsible for a consideraple heat generation rate. In fixed displacement pump circuits, if the actuator(s) requires different flow rates during its operation, then the fixed displacement pump must be sized to deliver the highest flow. Unfortunately, when less flow is required at the lower operating speeds, the excess flow must be "dumped" over the relief valve at full system pressure. This unconditionally converts the unneeded energy into heat. For this reason fixed displacement pumps should only be used in constant speed applications, or in circuits in which speed control is very short in duration. Likewise, a fixed displacement pump should never be used to hold pressure on an actuator under static conditions. Nevertheless, there are a multitide of applications where the fixed displacement pumps do the job and do it well. It is, however, imperative that the pump be sized precisely for the speed required. Normally, a fixed displacement pump will be adequate unless you answer "yes" to any one of the following statements.
Precautions must be taken if fixed displacement pumps are used under any one of the following conditions: -System pressure must be maintained on a stalled actuator. -The circuit operates over a broad speed range. -The pump cannot be unloaded by the circuit design during idle periods. -During a portion of the cycle, the actuator must be operated at a relatively low speed.
In summarizing the above, a fixed displacement pump has great potential for generating heat, if, for some reason, it is misapplied. For any system, it is the responsibility of the designer to calculate the heat generation (Chapter 1) during each portion of the cycle. If heating the system is not a problem, then the fixed displacement pump is adequate for the application. On the other hand, if it appears that a good deal of energy will be converted into heat, the designer may have to consider a variable displacement pump.
the gear teeth. As the gear teeth on the left-hand side of the drawing separate, an expanding volume is created. This void causes a partial vacuum, so that atmospheric pressure can push oil into the pump's inlet. Once oil fills the space be tween adjacent pairs of gear teeth, the oil is carried around the outside of the two gears. During this transmittal of oil, the gear tips come in close proximity to the pump housing, effectively sealing and isolating the pressure and the suction sides of the pump. Now, as the gear tips on the right-hand side of the drawing remesh, the oil is mechanically forced from the spaces be tween the gear teeth. This causes a flow of fluid from the outlet of the pump. The pump displacement is related di rectly to the number of teeth on each gear, and to the size of the spaces between adjacent pairs of teeth.
Shaft Seal
Pressure Field
If we now look at the pump from a side view, we can see the major leakage path. Physically, the suction and pressure sides of the pump are closest in the center of the pump housing. We must remember, however, that a clearance fit must exist if the gears are to rotate in the pump housing. This clearance will allow pressurized fluid to flow by the gear faces to the suction side of the pump.
- 230 -
High pressure gear pumps, on the other hand, are designed with floating wear plates (sometimes referred to as thrust plates). These two wear plates are located in the pump housing on either side of the gear faces. To facilitate pump start-up, the wear plates generally have bronze surfaces, and they are lightly mechanically loaded against the faces of the gears. As pressure is developed by the pump, it creates a hydraulic force, which tends to push the wear plates away from the gear faces. However, this hydraulic force is bal anced by a pressure field created on the opposite side of one (or sometimes both, depending on the pump design) of the wear plates. The effective area of this pressure field is precisely designed so that a light hydraulic force always exists to load the wear plates against the faces of the gears. During operation, the plates self-adjust the pump clearance, according to the pressure level. Of course, the higher the system pressure, the higher is the hydraulic loading on the wear plates. The pressure loaded wear plates reduce leakage to a minimum without creating excessive mechanical friction. They also allow the pump to self compensate for wear.
gear pumps which operate with very satisfactory noise levels. Therefore, the stigma which plagued the gear pump in the past is now being removed.
DIRECTION OF ROTATION
When specifying a gear pump for your system, you must be careful to order a pump with the proper direction of rotation. This precaution is necessary since most gear pumps cannot easily be converted from one direction of rotation to another. In fact, it may even require a separate "mirror image" housing to convert the direction of rotation for an external gear pump. Some of the reasons for this will now be considered. Again, it is necessary to refer back to the cross-sectional illustration of the typical pump design. At first it may seem that the direction of rotation can be changed simply by changing the rotational input to the pump. In theory, this would reverse the mechanics of the pumping action, and simply require connecting suction and pressure lines to the opposite sides of the housing. However, this is not the case. Most pumps which are capable of self priming have a larger inlet port than outlet. This facilitates use of the proper pipe diameter at the pump's inlet. Consequently, if only the direc tion of rotation is changed, the pump would try to pull its full displacement through the smaller port, while pumping the fluid out the larger port. This would not be desirable. Another problem in changing the direction of rotation of an external gear pump is that most pumps do not have external drains. Since the pump case is not vented to tank, the low pressure sealing ability of the shaft seal must be internally connected to the suction side of the pump. If this is not done when the direction of rotation is changed, high pressure fluid would inevitably cause a failure of this seal. Finally, pumps with pressure load wear plates may require totally different plates for the opposite direction of rotation. This is true because the pressure field created behind the plate is not symmetrical. In fact, it must be loaded more heavily on the pressure side than on the suction side of the pump. Rotating these pumps in the wrong direction would not provide adequate pressure loading of the wear plates.
- 231 -
constant unmeshing of the gear teeth. The oil is then carried by the spaces between the teeth through the crescent sealing area to the high pressure outlet of the pump. Here the gear teeth remesh for the fluid to flow from the outlet of the pump. Sealing of the high pressure chamber from the pump's inlet is achieved by the close proximity of the crescent to the two gears on the top and the meshed gear teeth on the bottom (according to this drawing).
The cross-sectional illustration shows a typical Gerotor element, which consists of a pair of gear shaped elements. The internal gear (or rotor) drives the outer gear in the same direction of rotation. ]his is identical t o the internal gear pump with a crescent seal (clockwise rotation shown). The inner Gerotor always has one less tooth than the outer element. The pumping chambers are formed by the adjacent pairs of teeth which are constantly in contact (except for clearance) with the outer element. You will notice that, as the rotor is turned, its gear tips are accurately machined so that they precisely follow the con tour of the outer element. The expanding chambers are created (on the left side of this drawing) as the gear teeth withdraw. The chamber reaches its maximum size when the female tooth of the outer Gerotor reaches top dead-center. Likewise, during the second half of the revolution, the spaces collapse, forcing fluid flow from the pump's outlet.
As shown in the operational cross section, the internal crescent seal gear pump consists of a small diameter internal gear, and an external ring gear. The inner gear is driven by the prime mover, in this example, in a clockwise direction. The internal gear meshes with and turns the ring gear in the same direction of rotation. In reference to the lefthand side of the illustration, oil is forced to enter the pump's inlet by the
Inlet
Outlet
- 232 -
through more degrees of rotation. This means that the gears unmesh and remesh with a lower relative speed. This creates a smoother flow of fluid to and from the pump. On the sue lion side of the pump, this lower relative speed of the un meshing of the gears means better pump filling. The lower fluid velocity allows the pump to start with more viscous fluids during cold start-up conditions. Likewise, the less radical meshing of the teeth at the pump's outlet means a smoother output flow, and, consequently, a lower operating noise level.
which produced considerable mechanical noise as the gear teeth meshed at high drive speeds. Second, the limited knowledge of manufacturing materials led to mechanical failure of the bearings and gear teeth. This failure was due to the high pressure unbalance of the basic gear pump design. For these reasons the fixed displacement "bal"nced" vane pump became quite popular. We will now take a closer look at how this pump functions.
As shown in the cross-sectional illustration, the basic vane pump consists of a rotor, an eccentric cam ring, and vanes. The rotor is either keyed or splined to the drive shaft, and is rotated by the prime mover. You will notice that the rotor has a number of radially machined slots which hold the vanes. Other than the rotor, drive shaft,and vanes, all parts, including port plates, are held stationary in the pump housing. Initially, as the rotor is turned, centrifugal force causes the vanes to follow the contour of the eccentric cam ring. In this design an individual vane is fully extended and fully collapsed in its slot twice during each revolution. The expanding and decreasing volumes required for the 'Pumping action are caused by the expanding and contracting volumes formed by the adjacent pairs of vanes. The term balanced comes from the fact that the elliptical shape of the cam ring permits the use of two pressure outlets and two suction inlets. With a single pair of adjacent vanes, two pumping actions occur during one revolution of the drive shaft. Geometrically, the two pressure ports (and the two suction ports) are located directly opposite each other. In reference to the cross section, the hydraulic loading of the rotor and pump bearing to the right is offset by an equal hydraulic force to the left.
In the earlier years of hydraulics, the fixed displacement vane pumps gained wide acceptance over gear pump designs for two major reasons. First, because of manufacturing methods available at the time, gears were not able to be machined with a high degree of precision. This resulted in a gear pump
- 233 -
CARTRIDGE DESIGN
Today, many balanced vane pumps are of cartridge design. This simply means that the pumping elements (ring, rotor and vanes) are supplied as a self contained unit sandwiched between the two port plates. The housing of the pump holds the cartridge, and contains the drive shaft bearings and pipe
DIRECTION OF ROTATION
Inlet
Vane Rotor
Cartridge
Clockwise Rotation
Rear
connections. The cartridge design allows a worn out pump to be rejuvenated to new pump conditions in a matter of minutes, simply by replacing the cartridge. For a given pump housing, cartridges of several different displacements are available. This allows flexibility in matching the pump to the system.
The fixed displacement balanced vane pump is normally field convertible !rom one direction o! rotation to the other. The two assemblies shown should be viewed as if the pump shaft were protruding from the page. You can see that in both drawings, the port plates are oriented so that the suction inlets are on the vertical axis while the pressure outlets are on the horizontal axis. The difference is that the "throw" of the cam ring is to the top right and bottom left for a clock wise rotation pump. For a counterclockwise rotation, the throw is reversed with respect to the port plates, namely, up per left and lower right. In reference to this drawing, direction of rotation is changed simply by "flopping" the cam ring around the vertical axis. With some vane pump designs, the vanes must also be repositioned in their slots so that their "leading edges" follow the direction of rotation.
Counterclockwise Rotation
- 234 -
creasing, forcing oil to flow from the outlet of the pump. Needless to say, the higher the operating pressure, the higher is the force required to collapse the vane. A point is reached at which the operating pressure becomes so high that ex cessive mechanical force is required. If the mechanical force becomes too high, the vane tip cuts through the oil film and comes in contact with the metal surface of the cam ring. This accelerates wear of both the cam ring and the vane tips.
OPERATING PRESSU RE
DU AL VANE DESIGN
The major design difference between vane pumps of dif ferent manufacture is the method incorporated to load the vane tip against the inside surface of the cam ring. This is particular! true of vane pumps which are capable of operating at pressures higher than 1500 PSI.
To alleviate the problems associated with the single vane design, high performance vane pumps incorporate dual vanes in each rotor slot. The purpose of the dual vanes is twofold. First, the two vane tips provide a double seal be tween pumping chambers. Second, the dual vane con struction allows for a hydrostatic balancing of the vanes, thus reducing vane tip loading. Let us now look at how this hydrostatic balance is achieved.
Nevertheless, with any vane pump, the vane must be forced to follow the inside surface of the cam ring. If this were not the case, pressurized fluid could get between the vane tip and the cam ring and push the vane (against centrifugal force) into its slot in the rotor. This would mean that the pumping action would cease. For operating pressures of up to 1500 PSI, the single vane principle is generally used.
Hydrostatic Balancing ---tt-l Pressure Two vane tips provide a double Sealing between high& low pressure chambers.
System pressure
- 235 -
-1 r- -1 r- Clearance
r-----.--
Inlet
1----
This causes errosion of the cam ring at these points. (."\ Too high a vacuum here . . .
r----
---. Outlet
leakage to a minimum. We now will tum away from this basic pump concept and discuss the higher pressure capabilities of the piston pump design.
If an excessive vacuum exists at the pump's inlet, it also exists at the base of the vane. Damage occurs when the vane first loses contact with the ring during suction, and then is "fired" at the cam ring as it is rotated into the pressurized area. In general, this problem is non-existent with properly in stalled pumps.
until pressure loading here . . . "shoots" the 0 the ring with vane at high velocity. 0 does not allow the vane to extend . . .
SIDE CLEARANCE
Vane pumps and gear pumps share equal side clearance characteristics. With any of these designs, the rotating element is sandwiched between a combination of wear plates or port plates. Actually a port plate is nothing more than a wear plate with oil passages. In lower pressure equip ment, these three elements operate with fixed clearances established during manufacture. As already discussed for the gear pump, higher performance pumps incorporate pressure balanced wear plates which compensate for wear and reduce
7 Piston Model
- 236 -
from the housing by flowing through the inlet check valve. To assure more complete filling of the piston element, oil is directed into the pump housing through axial and radial bores in the drive shaft. The radial bores, rotating at high speed, "sling" oil into the pump housing in the same way that a centrifugal pump would. This centrifugal pumping action increases the pressure in the case of the pump to a value slightly higher than atmospheric pressure. This super charging assures better piston priming, which not only im proves the suction characteristics, but also assists in lowering the operating noise level. Piston number 2 is starting-up the ramp of the cam. The inlet check valve has closed, sealing the chamber, but pressure within the element is not yet equal to system pressure. At this point, pressure is developing in the fluid, but there is not sufficient mechanical force to cause flow. Needless to say, as the cam pushes harder on the piston, pressure will develop rapidly in the captive fluid. Piston number 3 is approaching the end of its upward stroke. As the piston moves upward, fluid is forced to flow through the internal passages to the outlet of the pump. The outlet check valve (shown in the open position) will close as soon as the piston begins to retract into its bore. This positively seals the outlet from the inlet of the pump.
Housing
The cross-sectional illustration represents a typical radial piston pump. You can see that three piston elements are located ir. a symmetrical radial arrangement around the drive shaft. The supply of oil to the individual pistons comes from the center of the pump housing (green), while the pressure outlet is connected to a common pressure channel (shown in red). The pistons are actuated by the eccentric ball bearing on the drive shaft. The individual piston elements can ac tually be considered as three separate pumps, operated by a common eccentric drive. The pump can be driven clockwise or counterclockwise without modification, since either direc tion of rotation will cause the pistons to reciprocate in their bores. If we assume that the pump in this illustration is being driven in a counterclockwise direction, pistons 1, 2, and 3 will show us three separate pumping modes. Piston number 1 is approaching the lower portion of the cam and is being retracted from the bore by its spring. A vacuum condition exists in the pumping chamber, and oil is drawn
Barrel Support Bearing Outlet Check Pumping Chamber Piston Barrel :,..,.....J - Spring '<- ---...---- Piston With Integral Inlet Check
REAR VIEW
- 237 -
However, a second, even more unique feature of the radial piston pump, is that it can be supplied with several isolated pressure ports. The /SO - flow pump is nothing more than a modified housing which connects some of the pistons to one pressure port, while the other pistons are connected to a separate pump outlet. In fact, a three piston pump can be supplied with as many as three pressure ports, one for each piston. The cross-sectional illustration (bottom of page 6-13) shows a modem radial piston pump design. Although similar in fun ction to the design previously discussed, this particular pump offers somewhat higher performance characteristics, and is capable of lower operating noise levels. The major design variation is that hydrodynamic bushings are used in place of ball bearings. In this bearing design, pressurized fluid from the pump's outlet is ported between the bearing surfaces. During operation, the shaft and bearing surfaces are actually separated by a film of oil, virtually eliminating metal to metal contact. In hydraulic pump ap plication, these bearings have proven to exceed the life ex pectancy of either needle or ball bearings. They are also capable of supporting higher loads. To provide adequate protection during start-up conditions, the bearings are com posed of a Teflon inpregnated bronze.
pumping chamber. The vacuum created opens the inlet check valve, allowing oil to enter this chamber. The base of the piston is exposed to the oil through a semi-annular groove machined into the eccentric cam. Further rotation of the drive shaft causes the eccentric cam to push the piston back into the cylinder barrel . The inlet check valve closes, and pressure builds rapidly in the captive volume of the fluid. When the pressure in the captive fluid equals system pressure, the outlet check valve opens, allowing flow from the pressure port of the pump. As with any positive displacement pump, the higher the system pressure, the higher is the rotational torque requirement at the mechanical input to the pump.
Oil Entry
Pressure
OPERATING PRINCIPLES
The two previous cross-sectional illustrations show the general arangement of piston elements, eccentric drive shaft, housing, and bearing. As shown, the pistons are arranged radially to the eccentric drive shaft. Each piston element con sists of a hollow piston with integral inlet check valve, a piston barrel support bearing with outlet check valve, and a spring. As the drive shaft is rotated in a clockwise direction, the base of the piston is held in contact with the eccentric cam by the spring. The radius of this hydrodynamic bearing surface is equivalent to the radius of the eccentric cam. Downward motion of the piston causes an increasing volume in the
- 238 -
overall efficiencies on the order of 86%. For this reason, radial piston pumps are also used on lower flow circuits when precise speed control is important (see Chapter 1 ) .
the pumping chamber was increased to a higher value. However, since air is compressible, the pressure could not reach a high enough level to open the outlet check against system pressure. Once this condition is created, it is quite possible that the element will never prime. The air cannot escape over the outlet check, while at the same time air pressure is too high to allow oil entry over the inlet check. If precautions are not taken, the piston element will eventually fail, due to lack of lubrication. Fortunately, this problem is easily detectable and just as easily solved. A pump which is operating with one or more of its pistons not primed is mechanically unbalanced. Since more torque is required to tum the drive shaft past the primed pistons, the unbalanced torque input creates excessive mechanical vibration and noise. The conditions are similar to those in an automobile engine which i s not running on all its cylinders. When you are starting a new installation with a radial piston pump, it is advisable for you to unload the outlet of the pump. In this manner, system pressure cannot build behind the outlet check valves, allowing the air to escape from the pumping chamber. If, after running the pump for several minutes in the unloaded condition, the problem is not solved (noise and vibration when operating under pressure), it may be necessary to bleed the unprimed piston elements in dividually. In isolated instances, it sometimes happens that the outlet check valve cannot be opened by air pressure in the pumping element, even when the outlet of the pump is unloaded. This problem can be overcome by loosening the check valve ac cess nut which will relax the spring force and allow the element to prime. The nut should be retightened as soon as all the air has escaped.
resistance in the system. preve 0 However, an air 0 fillingnted oil from this chamber. pocket here . . . Pressure
IJ'
In this example, during start-up, only two of the three pistons were primed, thus the pump was only producing 2/3 of its rated flow. The third piston received only air at its inlet, and during several reciprocations of the piston, the air pressure in
(;;\ \.!:.)
- 239 -
The cross-sectional illustration represents a typical high pressure in-line piston pump. In this particular pump, nine pistons are contained in the cylinder barrel. The cylinder barrel is keyed to the drive shaft and is rotated by the prime mover. The pistons reciprocate in their bores, causing a pumping action, by following the inclined surface of the
swash plate.
The swash plate in a fixed displacement pump is nothing more than a steel ring held at a fixed angle (typically 15) in the pump housing. The dynamic bearing surface between the piston and the swash plate is created by a bronze slipper pad. The slipper pad has a ball and socket connection to the piston and is held against the swash plate by a retaining ring, which also rotates.
As the cylinder barrel rotates, it carries along each of the nine pistons. During exactly one half of a revolution, the pistons are pulled from their bores as the retaining ring causes the slipper pads to travel down the incline. Upon reaching its maximum extended position, the piston starts travelling up the incline, exerting force on the fluid in the cylinder barrel, forcing it to flow from the outlet of the pump. The displacement of a given pump is determined by the number of pistons, the piston diameter, and the length of the strokes. Of course, the steeper the angle of the swash plate, the longer is the piston stroke.
Slipper Pad
Outlet Kidney
Referring again to the cross-sectional illustration, you will notice that oil is ported to and from the cylinder barrel by the valve plate. The valve plate is nothing more than a flat sur face (usually bronze coated steel) with two semi-circular kid ney shaped openings. The two kidney shaped openings are connected through passages in the pump housing to the inlet and outlet ports o f the pump. Depending on the angle of the swash plate and the direction of rotation, one kidney becomes the inlet port while the other becomes the outlet. The cylinder barrel rotates relative to the valve plate, pulling oil through the suction kidney as the pistons are retracting, and pushing oil from the cylinder barrel through the outlet kidney as the pistons are pushed back into their bores.
total number of piston bores slightly larger than the effective area of the pressure kidney. For clarity, if we think of the flow area between the piston bore and the valve plate as being plugged, it is easy to see that pressure in the cylinder works against the area created by V the total number of piston z bores. This pressure force pushes the cylinder barrel against the valve plate on the pressure side of the pump. The second force working on the cylinder barrel is related to the area of the kidney in the valve plate. This pressure field works against the face of the cylinder barrel, and creates a force to the left which tends to separate it from the port plate. The optimum balancing of these pressure forces is achieved by designing the kidney area of the valve plate so that it has a less effective area than the pressurized area which loads the barrel against the plate. Needless to say, the higher the system pressure, the higher are the forces holding the cylin der barrel to the valve plate. This, however, does not necessarily mean that these two components will always maintain proper contact.
Remember: most in-line piston pumps should not operate with a case drain pressure higher than 5 to 15 PSIG.
- ---. B
Suction Side
- ct_--11---
__.
'
Pressure -. B Side
the cylinder barrel against the valve plate. The forces developed by the differential areas in the cylinder barrel work to the right, and hold the cylinder barrel to the valve plate. If the forces working simultaneously to the right are added together, the resultant (single) force to the right will act at point X at a dimension X, from the circumference of the barrel. Likewise, the resultant force of the kidney area can be thought of as a single force working at point Y to the left at dimension Y, from the circumference. Unfortunately, it is difficult, if not impossible, to design a pump so that dimension X, exactly equals dimension Y,. Since the two forces are out of alignment, a torque (Chapter 1 ) is created on the cylinder barrel. This mechanical im balance must be supported by the drive shaft and bearing in the pump. Of course, too high an operating pressure or a pressure spike can cause mechanical flexing of the drive shaft, allowing separation of the surfaces.
0 The pressure
Contaminated fluids not only accelerate wear of the valve plate and cylinder barrel, but more importantly, they cause blockage in cr itical lubrication passages. The principle of the slipper pad bearing is that the hydraulic force which pushes the piston towards the swash plate is offset by an equal pressure working in the opposite direction. In reference to the cross section, you will notice that a small hole through the piston's ball tip ports pressurized fluid between the slip per pad and the swash plate. The slipper pad is designed to have an effective area which precisely balances the pressure forces on the piston to the right.
with contaminant . . .
0 which must be
mechanically supported.
0 This creates a
Once separation occurs, the cylinder barrel cocks, bearing hard against the valve plate at the bottom and separating at the top (in reference to the drawing). The lubricating film is lost, and rotation causes scoring of the cylinder barrel and valve plate. Damage can also occur at the kidney area. Once the two surfaces separate, high pressure oil is blown into the case of the pump. This oil, travelling at a high velocity, can cause erosion of the metal surfaces. To avoid this type of damage, it is imperative that the pump not be operated above its pressure rating.
- 242 -
pump. The baTI and socket joint which attaches the slipper pad to the piston, although excellent under compression, cannot w ithstand high tension forces. During suction, the retaining ring extracts the piston by pulling on the slipper pad. If the vacuum at the pump's inlet (see Chapter 1) is too high, the bronze slipper pad is simply pulled off the ball tip of the piston. Unfortunately, this cannot be detected by listening to the operation of the pump. The pump continues operating until it totally destroys the swash plate area.
and returned below the minimum oil level in the reservoir,' . . . . . . with the shortest run possible. It is important that the case drain be connected individually, and not teed to any other return line. If a case drain heat exchange is to be used, it is of utmost importance that the heat exchanger be liberally over sized in order to minimize back pressuring of the case. When plumbing the case drain, it is advisable that you use a male run tee, or another suitable fitting, at the case drain port. This will faciitate filling the case of the pump prior to start l up.
Excessive case pressure has the same effect on the ball joint
in the cross-sectional illustration that these two conditions
actually work together in damaging the pump. In other words, both case pressure and high vacuum resist extraction of the piston from its bore. Consequently, both forces must be overcome by the retaining ring pulling on the slipper pad, and, in tum, on the ball joint. T avoid pump damage from either of the two previously o mentioned reasons, it is advisable that both inlet and case drain conditions be optimized. In general, in-line slipper pad pumps should, at the very least, be mounted on an L-shaped reservoir so that the head pressure of the oil is available to force oil into the inlet of the pump. With pumps of large displacement, it may even be necessary to "supercharge" the inlet. This is typically achieved by mounting an internal gear pump of slightly higher displacement ( 1 15%) in series with the inlet of the in-line piston pump. A supercharge relief valve, normally set at an operating pressure of 150 to 300 PSI, is also necessary. The supercharge pump is normally started before start-up of the main pump. On the other hand, it is also necessary to provide adequate case drain plumbing. The case drain line must be full sized,
- 243 -
A more rugged axial piston pump is available in the bent-axis design. In general, this design is capable of higher flows, higher pressures, and higher operating speeds. This pump is also more suitable for self priming applications. Let us now take a look at how it works.
Valve Plate
Rotation
Swash Plate
The cross-sectional illustration shows the general assembly of a fixed displacement bent-axis pump. In a bent-axis pump, the cylinder barrel turns with the drive shaft, but at a bent axis angle. Piston rods connect the pistons to the drive shaft. You can see that the pistons reciprocate in their bores as the distance between the drive shaft flange and cylinder barrel changes. In reference to this view, as the shaft is turned in the direction of the arrow, the pistons on the left are being extracted from the bores, thus creating the inlet condition. As the pistons pass top dead center, they are pushed back into their bore, forcing an oil flow from the outlet of the pump.
Unlike the in-line piston pump, the bent-axis pump trans forms torque directly into the linear force creating pressure. The torque from the prime mover works first on the ball joint connecting the piston rod to the drive shaft. The only resistance to the rotational force is that developed by system pressure over the area of the piston. This is true since the piston must be pushed into the bore if rotation is to occur. The force diagram is shown in the illustration. It is important
F, and F, = Torque transmittal to piston F3 = Reaction force of swash plates on piston F. = Horizontal component of reaction force F3 (develops pressure) F5 = Vertical component of reaction force (drag) Force Diagram Of An In-Line Pump
- 244 -
is a ball joint, which is bolted to the drive shaft flange with a retaining ring. Working together, these two ball joints are quite strong, and can withstand considerable tension forces. Consequently, the bent-axis pump can develop high vacuum conditions in the cylinder barrel without fear of mechanical damage. In fact, a typical bent-axis pump can create a vacuum equivalent to nearly nine inches of mercury, and is capable of pumping a fluid viscosity of up to 4600 SUS during cold start-up.
F, =Force created by torque F. =Resultant force (develops pressure) F3 =Reaction force absorbed by bearings Force Diagram Of A Bent-Axis Pump
to remember that the lateral side loading of the piston is not directly involved in creating a linear force on the piston. The piston rods do not transmit anymore torque than is necessary to cause acceleration of the mass of the cylinder barrel and to overcome the resistance of the barrel, spinning in an oil filled housing.
In considering self-priming applications, you will find that a second advantage is that the inlet porting can be made much larger than it can with an in-line piston design. In the cross sectional illustration, the valve plate is located at the end of Unlike those in in-line piston the rotary group. pumps, the valve plate (and cylinder barrel) in this design can be much smaller in diameter, since a large drive shaft does
Flange
Valve Plate
- 245 -
not pass through its center. As shown, this allows ooth the inlet and outlet kidneys to be located closer to the center of revolution. In tum, this offers several major benefits. First, by locating the kidneys close to the center of revolution, the relative centripetal speed between the rotating cylinder barrel and the stationary port plate is considerably reduced. This has the result of minimizing the turbulence (resistance to flow) in the oil flow as it passes from the stationary valve plate into the rotating cylinder barrel, which improves filling of the pumping chambers. The second advantage of locating the kidneys close to the center of revolution is apparent in the picture of the valve plate. You can see that each kidney has a wider cross sectional flow area. Needless to say, this lessens the resistance to flow as oil enters the cylinder barrel, and also improves filling. The third advantage is that the angle drilling of the passage to the cylinder barrel, creates a centrifugal force on the oil. In principle this centrifugal pump effect actually increases the pressure in the fluid. The increase in pressure is directly proportional to drive speed, and aids in filling the pumping chamber, particularly at higher RPM levels.
Let us go back for a moment to our previous discussion of hydraulic loading of the cylinder barrel to the valve plate for in-line piston pumps in order to consider a few important points. It is important to remember that the area of the kid ney is precisely limited. We emphasize the word precisely because the area of the kidney produces a separation force which must be smaller in magnitude than the hydraulic loading force within the cylinder barrel. Consequently, a bent-axis piston design for a given size can have a wider flow area, but must have an equivalent kidney area. The drawing may be helpful in comparing the kidney shaped openings of the bentaxis and in-line piston pumps.
You can easily understand that moving the kidney area closer to the center of rotation increases the separation of the resultant forces which act on the cylinder barrel. Unless something can be done to compensate for the increased torque created on the cylinder barrel, valve plate separation will become more of a problem.
Bent-Axis Design Valve Plate And Cylinder Barrel Net Areas Are Equal
The spherical surface of the valve plate used in many bent axis pumps prevents the possibility of port plate separation. However, instead of trying to hold the cylinder barrel in
-----
"
Elliptical Flow Area Circular Flow Area Available Available For One Piston For One Piston Bent Axis Design In-Line Design
- 246 -
Force Due To Kidney Off Center Moment Loading Force Due To Pistons
position by sturdy shafts and bearings, the spherical port plate attacks this problem in a different manner. The theory behind the spherical port plate is that separation forces do exist. At some pressure peak, these forces can and will cock the cylinder barrel, no matter how sturdily it is supported. The spherical port plate simply self-compensates for the deflection caused by the unbalanced pressure forces. The illustration shows the force diagram for a bent-axis design pump incorporating the spherical port plate design. First, you will notice that the connection between the cylin der bore and the port plate is drilled at an angle in order to locate the passage close to the center of revolution. As shown, the force due to the kidney area is further off center because of the drilling, but it works in a direction which is perpendicular to the tangent of the spherical surface. Second, the loading force due to the pistons works parallel to the axis of rotation in the direction shown, and is slightly larger in magnitude than the horizontal component of the force due to the kidney area. The off center moment is the vertical comp0nent of the kidney area force, and it is this force which must be supported by the center pin. As operating pressures increase, this off center moment necessarily becomes larger in magnitude. However, if the moment becomes large enough to cause an elastic defor mation of the center pin, the cylinder barrel will relocate on the spherical surface of the port plate.
justment, or it can be totally automated and interfaced with computerized programming. We could not stay within the scope of this text if we were to discuss the exact operation of each control for all the different pump designs available. For this reason, we will discuss the mechanics involved in varying the displacement of vane and piston equipment. The actual control and its intended application will then be discussed as related to the variable displacement pump in general. Before we discuss the different types of pumps and controls, however, we must gain a basic understanding of the types of circuits in which the variable volume pumps can be used. Let us now compare the characteristics of the three different types of pump circuits, open, closed, and half closed circuits.
The open circuit is by far the most popular. Its advantage is that, in this design, several different actuator functions can be performed simultaneously, if necessary, by a single pump. The reservoir's top plate can also be used as the foundation
Open Circuit
Holding Reservoir
- 247 -
for building the entire hydraulic unit. In this type of self contained system, oil conditioning can be optimized by proper reservoir design and use of the proper conditioning equipment. In fact, the only disadvantage to open circuit design is its relatively large size and weight, due to the large volume of oil required.
The closed circuit is always used in conjunction with a smaller supercharge circuit. The supercharge circuit consists of a small fixed displacement pump (usually 1 5 % of the displacement of the main pump), a small oil reservoir , and the necessary liters and heat exchangers. During operation, the main pump control can cause the pump's displacement to go ouer center, which means that the main pump can pump high pressure oil from either of its two main ports. In other words, it can cause a clockwise or counterclockwise flow of fluid through the closed loop plumbing. This, in turn, will allow the motor actuator to operate in either direction of rotation. The port which serves as the high pressure inlet to the actuator will determine the high pressure leg, while the low pressure leg will be deter mined by the actuator's outlet port. The supercharge circuit always works on the low pressure leg of the main loop pumping freshly filtered oil into the loop through the make-up check valve network, while bleeding-off a percentage of oil through the hot oil bleed valve. This hot oil is then cooled by a heat exchanger and stored in the small reservoir before returning to the main system. The pressure in the low pressure leg is maintained at a value of between 100 and 300 PSI by the supercharge relief valve. The pressure setting of the supercharge relief is determined by the requirements of the pump and/or motor actuator, and the operating conditions of the system. In closed loop circuits, pressure, flow, and directional control are all achieved by the controlling element of the pump. The crossport reliefs are incorporated only to protect the actuator from load induced pressure peaks. They cannot function as a main system relief valve, since this would, in short order, cause severe over heating of the circuit. The advantages of a closed circuit pump system are that high horsepower systems are compact, and they operate with minimum amount of excess storage oil. The systems are highly efficient since the pump control must be designed to supply only the oil flow required by the actuator at the load induced pressure. The pump controls direction, acceleration, deceleration, and maximum speed and maximum torque of the motor actuator, thus eliminating the need for pressure and flow control components. The major disadvantage of closed circuit systems is that a single pump can only operate a single output function. In ad dition, this type of hydraulic driue is generally usable only
L{
------
_ _
I I I I
_ _
_,
Heat Filter
% \o o.c.\uo.\o'S.. \.\\
In this closed circuit design, a single hydraulic pump is used to dr ive a single hydraulic motor. The closed circuit has little or no significance for cylinder actuators which displace dif ferent volumes during extension and retraction. The reason for this is that the oil which passes through the motor ac tuator is returned directly to the low pressure side of the pump. For proper operation, the pump must receive the same quantity of oil at its inlet as it is pumping from its outlet.
- 248 -
As shown in the simple circuit schematic during extension of the cylinder, the pump must create a larger flow from its left hand port than is being returned to its right-hand port from the cylinder actuator.
The open circuit pressure compensated vane pump is probably the most popular variable displacement pump used in industrial hydraulic systems. Because the direct operated variable volume vane pump is only available with a pressure compensated control, we must discuss the operation of the pump and it control as a single unit. The cross-sectional illustration (page 6-26) shows the basic direct operated variable volume pressure compensated vane pump design. Unlike its fixed displacement counte.rpart, the variable volume model is not hydraulically balanced. Jn this pump design, the cam ring is round rather than elliptical in shape. As shown, the pump displaces fluid because the spring holds the cam ring in an eccentric position with respect to the rotor. Assuming that the pump shaft is being rotated in a clockwise direction (viewed from the shaft end), you can see that the vanes reciprocate in their slots as the rotor is turned. Because of the eccentricity of the cam ring, the vanes are collapsed in their slots on the right-hand side of. this drawing, and extend as they are rotated past the suction kidney (shown in green) to the left. As the vanes rotate through the upper portion of the pump housing, they are again collapsed in their slots, forcing an oil flow from the outlet of the pump. The reason the variable volume pump cannot be hydraulically balanced is that the pressure forces between the cam ring and the rotor are an integral part of the pump control. As the pump encounters a resistance to flow into the system, pressure builds at the pump outlet and between the rotor and the circular cam ring. Because of the geometry of the pump and the location of the pressure kidney, the resultant force due to this pressure pushes the cam ring up and to the right. When the horizontal component of the pressure force exceeds the force due to the spring, the cam ri g moves to the right, toward a concentr position with n ic
Heat Exchanger L------.J1 Oil Suction Check Valves (Incorporatedin Pump) Reservoir Half-Closed Circuit
The extra oil is drawn by the pump from the reservoir through the suction check valve, which is an integral part of the pump. When the pump control causes the pumping assembly to go over center, flow is reversed and the cylinder begins retrac ting. During retraction, the differential area causes a larger flow than needed at the inlet of the pump. The excess flow is unloaded to the reservoir by means of the unloading valve. This unloaded flow to the reservoir provides for an oil ex change in the closed portion of the circuit, which allows for filtering and cooling of the fluid.
- 249 -
Thrust
Kidney
here . . .
- 250 -
be far better, from an efficiency standpoint, to select a smaller 4 GPM pump for this application.
The graph represents a typical pressure versus flow relation ship for a direct operated vane pump. It must be noted that the shape of this curve depends greatly on the spring selec ted for a given operating pressure. The initial, more gradual decrease in flow from minimum pressure to the point just prior to pump compensation is solely a function of internal pump leakage. Up to the cutoff point, the spring constant is stiff enough so that there is no spring displacement, hence no decrease in flow because of a change in the cam ring's ec centricity. Spring displacement begins at the point where flow begins to drop off drastically with respect to rising pressure. The steep ness of this drop off (or the pressure difference between maximum and minimum flow) depends on the stiffness of the spring. To cover different pressure requirements in the 0 -1 500 range, four different springs are normally available. Since a single spring can only give optimum performance within a specific pressure ran9e , it is impor:tant that you select the proper spring. The comparison indicates the proper spring selection for a typical 900 PSI operating pressure. In this comparison , you will notice that the spring, which gives optimum performance at the 1500 PSI pressure, is inadequate for operating at 900 PSI. As this high pressure
Range
Deadhead Pressure
spring is adjusted for lower and lower operating pressures, the pressure span between cutoff and deadhead becomes broader. We must, of course, limit this pressure differential, since the output speed of the actuator(s) is drastically af fected between cutoff pressure and deadhead pressure. If the pressure span is too great, pressure requirements of the system could allow the actuator to operate at a reduced speed between maximum flow and deadhead. Ideally, this should not occur in a pressure compen sated system. Generally speaking, the direct operated pressure com pensated vane pump displays the best pressure versus flow curve when it is operated at the maximum pressure rating of the spring. When set at a lower pressure, the cutoff toward the deadhead portion of the curve becomes more gradual. The spring should never be adjusted below 50% of its maximum pressure rating. If, for some reason, your system operates at a different pressure from that originally calculated, it is sometimes possible to simply exchange the spring. However, you must consult with the pump manufac turer, since pump clearances and timing of the port plate may also influence the operating pressure capabilities of the pump.
1 500 PSI 900 PSI Comparison Of 1000 PSI And 1 500 PSI Springs When Set At 900 PSI
- 251 -
pilot valve. When system pressure overcomes the setting of the pilot spring, the larger control piston area is vented to tank. The small piston, which is still pressurized, is then able to push the cam ring into a concentric no flow position. This position is then maintained until the system pressure is again reduced below the setting of the pilot spring. At this point, hydraulic loading of both control pistons is re-established, and the cam ring moves back to a flow position. The pilot operated variable volume vane pump is suitable for higher pressure and higher flows than its direct operated counterpart. Generally speaking, direct operated pressure compensated vane pumps are limited to 1500 PSI operating pressure; and maximum flows of up to 20 GPM. Pilot operated versions, on the other hand, are capable of operating pressures of up to 2400 PSI, with flow capabilities as high as 60 GPM. You will notice that the pilot operated pump incorporates dual vane construction. In addition, the pump's volumetric efficiency is increased due to pressure loading of the wear plates. Since these features were discussed for fixed displacement pumps earlier in this chap ter, they will not be covered again.
select from any number of pump controls. However, we will postpone discussion of the various controls until later in this chapter, and study this pump in conjunction with the basic pressure compensated control.
Suction Kidney
Pressure Adjustment
As shown in the cross-sectional illustration, the cam ring is sandwiched between two control pistons. The larger piston, on the right, has twice the effective area as the piston on the left, and is assisted by a light spring force (250-375 PSI). During start-up, this spring force holds the cam ring in an ec centric position, and the pump begins displacing fluid. As the pump meets a resistance to flow; the two control pistons and the end of the spool in the direct operated sequence/ unloading valve are equally exposed to system pressure. As long as the spring setting of the pilot valve is not exceeded, pressure on the two pistons (with a 2 : 1 area ratio) keeps the cam ring eccentric to the rotor, and the pump displaces fluid. System pressure is set by adjusting the spring force of the
- 252 -
The graph consists of superimposed pressure versus flow characteristics of direct and pilot operated pressure com pensated vane pumps. You will notice that both pumps are approximately the same displacement, since they both deliver nearly equal flows at low pressure. The comparison shows two major differences between these two pump designs. First, the effects of pressure loaded port plates and dual vane construction are readily apparent. The pilot operated pump has better volumetric efficiency charac teristics than does the direct operated design. For this reason, there is less decrease in flow with increasing pressure, and the initial slope of the pressure versus flow graph for the pilot operated vane pump falls off more gradually. The second advantage of the pilot operated pressure com pensated vane pump is that its pressure versus flow curve is not affected by the pressure setting. The graph shows that it does not matter whether the pilot operated pump is set at 500 PSI or 1500 PSI. The pressure differential between the cutoff point and deadhead is always the same. For the same reasons that a pilot operated relief is not affected by pressure override (Chapter 2), the pilot operated pressure com pensated vane pump has less pressure differential between cutoff and deadhead.
15
the pump manufacturer prior to making any noise ad justments on your pump. Let us now look at the theory of
noise adjustment. As the pump transfers oil from the suction to the pressure kidney, there is a point at which the volume of oil between adjacent pairs of vanes becomes captive. Also, during this crossover period, the captive volume can be made to decrease in size. By adjusting the amount of volume change, the pressure in the captive fluid can be made to equal the pressure in the system. Matching this precompression pressure with system pressure results in a smooth crossover, which results in extremely low operating noise levels. Ob v iously, this smooth crossover due to pressure match can be optimized only for one specific system pressure. Since most pumps are factory set at the maximum pressure rating of the pump, the noise adjustment must be field tuned for optimum noise level. This tuning is accomplished by sight adjustment of the cam ring thrust screw. The cross-sectional illustration of a typical variable volume
0 500 1 000 1 500 Pressure (PSI) Comparison of Direct and Pilot Operated Pressure Compensated Vane Pumps
- 253 -
Remembering that the ideal noise level is achieved when there is no explosion or implosion of the precompressed fluid, we can understand why the pump can be noisier in a flow condition than in deadhead, or vice-versa. Since noise adjustments are, out of necessity, a compromise, the thrust screw can be set with the pump in its normal operating mode. That is, if the pump operates a high percentage of the time in deadhead, the thrust screw can be adjusted in the no flow condition of the pump. On the other hand, if the pump is more often pumping fluid at a lower pressure, the thrust screw can be set in a flow condition of the pump. This, however, will sacrifice the pump's optimum noise level when in the deadhead no-flow mode. Finally, if we consider the fact that fluid is not compressible, we can understand the fact that very minute changes in the pre-compression volume drastically affect the precom pression pressure. In discussing thrust screw adjustments, we are talking about only a 6(]' rotation of the thrust screw from the factory marked center position. Minimum to maximum adjustment should not exceed a 120" rotation. Radical over-adjustment will cause poor pressure versus flow characteristics and possible catastrophic failure of the pump.
Where: GPM = Actual Flow Output PSI Maximum System Pressure E , = Overall Pump Efficiency
=
For any fixed displacement pump, you must calculate the horsepower for the full flow at maximum pressure, and then size the electric motor accordingly. This, however, is not necessarily mandatory with pressure compensated pumps. The major advantage in selecting a pressure compensated pump is that the control produces only the amount of flow needed by the operating conditions of the system. In systems using flow controls to control actuator speed, the excess flow over the relief valve in a fixed displacement pump circuit is replaced with a pump control which simply does not generate an excess flow. Consequently, by eliminating this flow across the relief valve, the energy consumption and sub sequent heat generation can be drastically reduced (estimating heat generation is discussed in Chapter 1). The ability of the pump to produce full system pressure at noflow unloads the electric motor in the same manner as
- 254 -
does a fixed displacement pump when pumping full flow at no pressure. However, holding pressure at no flow offers definite advantages. If we consider cylinder actuators, we find that the duty cycle often does not require full flow and full pressure simultaneously. In many applications, the cylinder first travels through "free air," then does its work on the load. After completion of the work, the cylinder may be required to maintain a holding force on the load, or it might be possible to retract the cylinder to its fully collapsed position. In either situation, maximum pressure and flow are required simultaneously only when the work is being done. During "free air" extension and retraction, there is virtually no load, and consequently, no pressure. If a holding force on the load is required, or if the cylinder is fully retracted, there is full pressure but no flow. In contrast to the fixed displacement pump, the pressure compensated pump draws very little horsepower. If the work portion of the cycle is short in du ration, and sufficient time is available between con secutive work functions, we can "cheat" on the horsepower rating of the electric motor. The most common electric motor for industrial hydraulic systems is the NEMA (National Electrical Manufacturers Association) design B. A three phase design B electric motor will produce a starting torque which is at least 200% of its maximum continuous running torque specifications. For short periods of time, it can produce up to 200% of its con tinuous torque rating before stalling, or dropping in speed. We must emphasize the word short because the higher than normal current in a motor which continuously operates above its rating will cause overheating and the eventual bum out of the electric motor. Let us now consider the capability of the electric motor in conjunction with the needs of the pressure compensated pump. The graph shows a typical horsepower curve for a pressure compensated pump. The upper curve represents the flow
conditions of the pump, and shows that, for the flow rating of the pump, as the pressure increases, so do the horsepower requirements. Up to the cutoff point of the pressure compensator, this curve is identical to that of a fixed displacement pump. The difference is that when the pressure compensator, reduces pump displacement, the horsepower requirements drop off quickly to the lower limit. This lower limit is call deadhead horsepower (in red on the graph). It represents the mechanical and volumetric in efficiencies of the pump, and indicates the total amount of heat generated during no-flow conditions. If it were possible to make a pump with 100% efficiency, the deadhead horsepower would be zero. More importantly, the graph indicates that the full 10 horsepower draw occurs only at a system pressure of 1400 PSI. In relation to our previously described cylinder actuator, the 10 horsepower demand on the electric motor would be required only during the work portion of the duty cycle. During the other portions of the cycle, a 10 horsepower elec tric motor would be operating considerably below its 10 horsepower rating. In consideration of the overload charac teristics of the electric motor, it is acceptable design practice to use a smaller electric motor.
2 In this application, a 7Y horsepower electric motor would create the required torque to attain the 10 horsepower level with a 33% overload. Assuming a short enough work cycle, this overload would not seriously overheat the electric motor. Besides, if there is sufficient time between overload periods, the motor will be able to rid itself of the heat generated during the overload portion of the cycle. In fact, if the overload oc curs only to get the pressure compensated pump over the "hump" of the pump's horsepower curve, the overload would normally be in the range of only 50 to 100 ms. This type of overloading occurs when the cylinder bottoms out after travelling through "free air" or after doing work at a rate below the horsepower rating of the electric motor.
:c
Cutoff Point Of Pressure Compensator t 10 Horsepower Draw During Flow 8. 5 Deadhead Horsepower
... Q) Q) Ill ... 0
At this point, however, we must refer you to your motor sup plier for recommendations on satisfactory limits of electric motor overloading. There is no good rule of thumb which we can offer since there are too many variables which must be considered. The variables include ambient temperature, altitude of operation, motor design, and the service factor of the motor selected . From an electric efficiency standpoint, electric motors are generally more efficient when operated at their full horse power rating. An unnecessarily large electric motor may be less efficient in conserving electrical power than a motor which has been intentionally undersized. In summary, undersizing the electric motor requ ires a com plete understanding of the system duty cycle. Generally speaking, we can only consider this undersizing if the cylin der actuator overloads the system for brief time periods. Generally, we cannot consider undersized electric motors for use with hydraulic motor circuits which use pressure com pensated pumps. The reason for this is that the hydraulic motor could conceivably operate at pressures and flows near
500
1400 1500
- 255 -
the cutoff point of the pressure compensator for extended time periods. At this point on the curve, the pressure com pensated pump would draw its maximum power from the electric motor.
major difference is that the angle of the swashplate can be changed rather than being at a fixed angle. The housing of a variable displacement in-line piston pump has a yoke which is supported by pintle bearings. As shown, the yoke's position is controlled by a double acting single rod cylinder. The cross-sectional illustration shows the posi tioning cylinder in the fully extended position. In this position of the swashplate the pistons on the top are fully retracted, while the lower pistons are fully collapsed in their bores. Assuming clockwise rotation (when looking at the shaft end), the inlet would be port A, while the outlet would be port B. The photograph of the cut-away pump shows the positioning cylinder at mid stroke. This positions the swashplate in the vertical position (perpendicular to the rotational axis). In this position of tne swashplate there is no incline, and the pistons cease to reciprocate in their bores. This results in no flow, since the piston creates no displacement volume during rotation.
In using this pump in a closed loop circuit, you achieve flow reversal when the positioning cylinder is fully retracted. In this position, the piston on top of the pump would be fully collapsed, while the pistons on the bottom would be fully retracted in their bores. With the same direction of rotation, the flow direction is reversed.
which alters the stroke length of the pistons. 0 This changes the displacement of the pump.
3
The in-line piston pump can be used in either open or closed circuit applications. It is not generally recommended for half closed circuitry, since the suction characteristics of in-line piston pumps are, at best, marginal. For open circuit ap plications, the stroking cylinder incorporates a mechanical stop so that the displacement can be varied only on one side of center. Closed circuit controls, on the other hand, make use of the full stroke length of the positioning cylinder. This allows the pump's displacement to be infinitely varied for either direction of flow in the closed-loop circuit. Various controlling means will be discussed in general later in this chapter.
- 256 -
Positioning Cylinder
in-line piston design is that the pistons are at a slight angle to the axis of rotation rather than parallel to it. This slight angle (5) uses the centrifugal force on the piston to its best ad vantage. We have already explained how too high a drive speed related to the mass of the piston can cause separation of the piston from its slipper pad. This also explains why the pistons on most in-line piston pumps are hollow. This design hydrostatic transmission pump is influenced differently because of its different geometry. Because it is not hollow, the piston mass of the hydrostatic transmission is increased. Rotation of the drive shaft causes a centrifugal force on the piston which tends to retract the piston in its bore. The axial component of this force is ap plied on the slipper pad and ball joint, and tends to keep the slipper pad in contact with the swash plate. This allows the pump to operate at the high drive speeds of internal com bustion engines without fear of damage to the slipper pad bearing.
This Force Component Keeps The Slipper Pad In Contact With The Centrifugal Force On Piston Swash Plate At High Drive Speeds
The hydrostatic transmission pump is designed specifically for closed circuit applications, because it includes all the necessary components within the main pump housing. As shown, the heart of this pump consists of a special variation of the basic variable displacement in-line piston rotary group. Apart from the main rotary group and its positioning cylin der, the hydrostatic transmission also includes an internal gear pump for supercharging the closed loop circuit. In ad dition, the supercharge relief, cross port reliefs, and make up check valves are incorporated in the closed circuit valve housing attached to the rear portion of the pump. The hydrostatic transmission pump is designed primarily
for hydrostatic drive on mobile equipment. For this reason, it
must be sturdy enough to withstand the constant speed variations and relatively high drive speeds of internal com bustion engines. Likewise, the drive shaft must be able to withstand the radial loading forces generated by gear or v belt drives. With respect to the rotary group, the major difference be tween this hydrostatic transmission pump and the standard
- 257 -
Adjustment for the Beginning of Regulation (Control Oil Drain Must Be Connected Separately)
The cross-sectional illustration represents a bent-axis piston pump designed specifically for open circuit applications. It is quite similar to its fixed displacement counterpart, except for the fact that the cylinder barrel can swivel, which varies the displacement of the pump. You will notice that the piston stroke is related to the angle between the drive shaft and the cylinder barreL Needless to say, when the cylinder barrel becomes parallel with the drive shaft, the pistons stop reciprocating in their bores. Depending on the pump control, the housing of this design pump can be supplied for two dif ferent stroke ranges, namely, 0" to 18" and 7 - 25 _ The ()" 18 housing allows the rotary group t o be positioned in a no flow position, but has its maximum flow limited by the 1SO swivel angle. The 7 - 25 housing allows slightly higher flow (large displacement because of longer piston stroke), but does not allow the pumping mechanism to achieve the no flow (zero angle) position.
-
The pump's displacement can be varied by using a lens shaped port plate which is connected to the positioning piston. You will notice that the positioning piston has two ef fective areas for pressure to act upon. The smaller area has approximately one half the effective area of the larger piston, and is constantly pressurized by system pressure. Assuming that the larger piston area is vented, the pressure working on this smaller piston has the ability to hold the pump in its maximum displacement position. When the control function being performed pressurizes the larger area, the pump is then swiveled back towards its no flow (or minimum flow) position. Because of its design, this pump is capable of both high pressure (4600 PSI continuous, 5800 PSI intermittant) and
- 258 -
Pressure Kidney
Suction Slot
If mounting the internally drained pump below the oil level is not feasible, the pump should be mounted with its suction port vertically upward. This allows the housing of the pump to be filled with oil prior to start-up, which aids in achieving proper sealing of the shaft. Needless to say, the suction line must be adequately sized so that the extra pipe fittings required for this type of mounting do not cause too much restriction to the inlet flow.
I /
View Of The Rear Cover And Valve Plate From The Cylinder
The lens shaped valve plate communicates flow from the suction port located in the rear cover to the cylinder barrel. As shown, the suction slot in the rear cover provides a full flow passage at any swivel angle. Pressurized flow passes from the cylinder barrel, through the pressure kidney and pressure slot, to the outlet port of the pump. This arrangement allows the pump to create a vacuum equivalent to 6 inches high without fear of pump damage. Finally, it is important to mention the fact that this pump design does not require a separate case drain line. You will notice that leakage oil, which lubricates the bearings, is collected in the housing of the pump. Since the housing and suction inlet are inter connected, the leakage oil simply passes to the low pressure inlet of the pump. However, due to the fact that the housing and inlet port are inter connected, some mounting precautions are advisable. In general, gear, fixed displacement vanes and any other pump type which internally drains its case to the inlet side of the pumping mechanism possess a potential problem when mounted on top of the oil reservoir. This problem stems from the fact that it may be easier for the pump to pull air through its shaft seal, than to lift oil from the reservoir. Even if the pump operates satisfactorily when new, slight wearing of the shaft seal can cause future service problems. For this reason, it is always advisable to mount internally drained pumps below the oU level in the reservoir. This, of course, maintains a positive head pressure within the housing of the pump (Chapter 1).
Suction Kidney
The cut-away illustration shows the front half of an over center bent-axis pump. Unlike the lens shaped port plate of the open circuit bent-axis pump, this unit uses the stationary valve plate, as already described for the fixed displacement unit. The difference is that the cylinder barrel , pistons and fixed valve plate are contained in a swiuel housing. The swivel housing contains A and B port passages which com municate flow to the A and B port connections of the pump. As shown, the A and B ports are an integral part of the two trunnion bearings which support the swivel housing.
Swivel
Outlet Port B Clockwise Swivel (Right) Top View Of An Overcenter Bent-Axis Pump
- 259 -
The cross-sectional illustration, from a top view, can be used to explain the method whereby the overcenter pump varies its displacement. As shown, the housing is swiveled in the clockwise direction to its maximum angle. In this direction, a right-hand rotation of the input shaft causes pump flow from port A to port B. Assuming constant drive speed, the pump will be producing its maximum flow. Now, if we started swiveling the housing counterclockwise towards the zero swivel angle, a reduction of flow would occur because the relative piston stroke would become less. At the (J' swivel angle, the swivel housing and the drive shaft become parallel. In this position, there is no relative piston motion, and the pump stops delivering flow. If the swivel housing were to continue to move ouercenter in the coun terclockwise direction, a reversal of flow would occur. Of course, the larger the angle in the counterclockwise direction, the greater would be the flow. The following drawing and chart can be helpful in determining the direction of flow as related to swivel direction and direction of rotation.
The overcenter pump, as shown up to this point, is in complete in that the swivel housing is actually contained within the housing of the pump. The control housing is bolted to the rear of the pump. This encloses the swivel housing and provides the means of controlling its position. The drawing shows a pump with the simple hand wheel con trol. Independent of the type of control, the control housing contains a fork which mates with the pintle on the swivel housing. The control causes the fork to move in a horizontal sense, which in tum, adjusts the swivel angle of the pump. The control housing provides an additional function in that it seals the entire pump. In this manner, leakage and lubrication oil collect in the pump housing and is returned to the hydraulic reservoir by a separate case drain line. Likewise, with this closed circuit type pump, it is imperative to fill the pump housing with oil prior to start-up.
.. ..r;
B to A
A to B
Pintle
Swivel Housing
Control Housing
- 260 -
Earlier in this chapter, we have explained the difference be tween open, closed and half closed circuits. In a half closed circuit, the pump is not only required to create a flow of fluid from one service port to the other, but it must also make-up oil when the return flow is less than the output flow. This is easily accomplished by using bent-axis design overcenter pumps. As shown in the cut-away illustration, a half closed circuit pump is nothing more than a closed circuit pump with make up (suction) check valves installed on the rear cover of the swivel housing. The pump modification also includes a con trol housing with a large diameter suction port. Con sequently, a pump for half closed circuit operation has three full size port connections, namely, two service ports for con trolling the direction of flow in the closed portion of the cir cuit, and a full sized suction port for pulling the necessary make-up oil. Since the suction line is common to both the r eservoir and the pump's case, a separate case drain line is not required. Depending on the requirements of the par ticular half dosed circuit pump, full displacement can be drawn over the make-up check valve. You will notice that two check valves are necessary, one for each direction. The check which is not required for a particular direction of flow is simply held closed by system pressure.
flow at a pressure level dictated by the load conditions. You can achieve this optimum transfer of energy simply by se lecting a variable displacement pump with the proper control option. Now that we have discussed the methods through which piston and vane pumps vary their displacements, we can discuss the control means available to alter the flow capability of the pump. We have previously covered the pressure compensator control in detail in conjunction with the variable displacement vane pump. Considering the fact that the same type of control is available for piston equip ment, discussion of its merits would be repititious. At this point, it is more important for you to realize what the control does, rather than how the control operates with all the dif ferent pump designs. Likewise, you must remember to select the control to meet the circuit requirements of your system. Some controls are designed specifically for open circuit pumps, while others can be modified for use in either open, closed or half-closed circuits. We will begin our discussion of the various control options with the simple handwheel con trol.
Handwheel Control
Positioning Piston
positioning piston to move up or down. This, in tum, will change the displacement angle between the cylinder barrel and the drive shaft. The handwheel control is simple in design, which makes this control not only inexpensive to purchase, but also very reliable. Nevertheless, many design eng ineers overlook the benefits this type of control offers to the basic circuit design. Whenever there is a requirement to adjust the speed of the actuator, it is commonplace to select a flow control valve (Chapter 3) for the system. However, we have shown in Chapter 1 that we must also concern ourselves with the heat generation caused by flow control components. In many cases, a handwheel controlled variable displacement pump could be used economically in place of a fixed displacement pump, used in conjunction with a flow control. It is usually better, from an energy conservation standpoint, to cause a change in the pump flow manually, rather than to alter the resistance to that flow, also manually . The handwheel controlled pump, when used to vary system speed, proves the adjusted flow only at the pressure dictated by the load conditions. Although the pump must be used with a full flow relief valve, the relief valve will open only if the system is overloaded or stalled. It never has to bypass flow to tank during reduced speed operation. Consequently, heating of the system can be considerably reduced.
The handwheel control can be incorporated into either open, closed, or halfclosed circuit pumps. In closed or halfclosed circuits, the direction of the actuator is manually changed when the control causes the pump to go ouercenter.
Electric Motor
Fork
1st Stage Mechanical Zero Gear Reduction Stop for Open Circuit Application
- 262 -
The bi-directional electric motor allows the position of the pump's swivel housing to be varied infinitely from zero displacement to maximum, in either flow direction. The stroking time is related to the RPM rating of the electric motor and to the gear ratio. Electric motor and gear ratio combinations are available for a multitude of swivel times. They range from 13 seconds to over 6 minutes. The motor is protected from overload by the slip clutch, which is built into the reduction gear box. In this way, there is no damage if the motor is left running after the pump has reached its maximum displacement. In designing the electrical circuit, you can equip the electric motor control with a number of cam operated limit switches (double pole single throw), a potenti meter, or both, o mounted on the same pump. The limit switches and/or the potentiometer serve as a feedback of the pump's swivel position to the electrical circuit. Rotation of the cam mechanism is accomplished by a rack and pinion drive which senses the pos,ition of the fork assembly.
The constant horsepower control senses the load induced pressure in the system and regulates pump displacement ac cordingly. The pump control holds the pump at its maximum displacement until the pressure level reaches the point at which regulation begins. During regulation, the pump sup plies as much flow as possible for the input power available .
Beginning of Regulation
u:
0
Minimum Flow
_ .!_
I I I I I I I I I I
I .l I I
_ _ _
x RPM HP = T5252
The graph shows the pressure and flow relationships for a constant horsepower control. The black (curved) line represents the theoretical constant horsepower relationship between flow and pressure, while the red line depicts the ac tual characteristics of the pump control. In reference to the graph, the pump is at full displacement until pressure A is reached. The slight slope of the curve between zero pressure and point A represents only a loss in flow because of pump leakage. Once regulation begins, the pump flow decreases quickly as pressure increases from point A to point B. Fur ther increase in pressure (between point B and C) decreases pump flow more gradually until the control reaches the minimum flow valve. The pump control must be used with a main system relief valve capable of relieving this minimum pump flow. Once the end of regulation is achieved, the slightest increase in system pressure will open the relief valve and bypass the minimum pump flow to tank. Needless to say, if load induced pressure drops, the control will follow the curve in the reverse direc tion (toward maximum flow). You can see that the two straight lines, which represent the actual pressure versus flow curve of the pump, closely approximates the actual horsepower curve .
T draw constant horsepower from the prime mover, the o pump must maintain the mathematic product of flow and pressure at a constant value. This means that if the flow out put is high, the operating pressure must be low. Likewise, when pressure increases, flow must decrease. Since the operating pressure level of a system is dictated by the load conditions, the flow must vary with changes in load induced pressure if we want to maintain the product of flow and pressure at a constant value.
- 263 -
Control Rod
Positioning Piston
The cross-sectional view of a bent-axis design open circuit pump can be used to explain the operation of any constant horsepower control. During start-up, control spring number 1 holds the pump on full displacement and the pump begins delivering a flow of fluid to the system. As the flow en counters resistance, system pressure builds on the small area of the positioning piston which holds the pump on full displacement, and on the small piston sensing the pressure in the system. As long as system pressure working over the area of the sensing piston is not high enough to move the pilot spool against the small spring (which establishes the beginning of regulation), the large area of the positioning piston (orange) will be vented to the pump housing (green) through the pilot spool. When system pressure exceeds the pressure setting for the beginning of regulation, the sensing piston w push on the ill control rod and shift the pilot spool. The pilot spool will then direct system pressure (red) to the large area of the positioning piston (orange). Under this condition, the area differential of the positioning piston will cause the pump to begin destroking. Destroking of the pump will cause control spring number 1 to be compressed, which, in tum, will increase the mechanical force on the control rod and the sensing piston. When spring force balances the force due to pressure working over the area of the sensing piston, the pilot spool will modulate the pressure on the large diameter of the positioning pistons. In this way, the pump will destroke only to the point at which the spring force of control spring number 1 will balance the hydraulic force on the sensing piston. Consequently, control spring number 1 establishes the slope of the initial pressure versus flow curve of the pump.
When the pump destrokes to approximately 50% of its maximum displacement control, spring number 2 begins being compressed. This further increases the pressure needed on the sensing piston to cause displacement of the pilot spoo l. The second, more gradual, slope of the pump's pressure versus flow characteristics is shaped by the com bined force of the two control springs .
The load sensing control is becoming quite popular in modem hydraulic systems. Its advantage is that it conserves energy and virtually eliminates heat problems in the hydraulic system. The control operation is based on the principle that
- 264 -
.023" 0 Orifice
Metering Notch
Internal Drain
Control Spool
if there is a constant pressure drop maintained across an orifice, there will also be a constant flow. For this reason, the explanation of the load sensing control will more or less parallel our explanation of the pressure compensated flow control as discussed in Chapter 3. The illustration shows a typical load sensing control.
In this illustration, we are highlighting the pilot control spool of a variable volume vane pump with a load sensing control. The pilot control spool functions much like the hydrostat in a
pressure compensated flow control valve. You will notice that the left-hand area of the spool has the same effective area as that on the right. The spool is held to the left by a light spring force (equivalent to approximately 150 PSI). The left-hand area of the spool senses the inlet pressure of the main flow or ifice, while the opposite end of the spool (spring end) senses the pressure at the outlet of this orifice. Con sequently, the forces which act on the pilot spool are bal anced when the pressure at the orifice's outlet is ap proximately 150 PSI (spring force) lower than the inlet pressure.
- 265 -
0 This allows the small control piston to destroke the pump . ...
Destroking
The first illustration shows the pump in equilibrium, delivering just enough flow so that the pressure loss across the main flow orifice is at the 150 PSI value. If we assumed that a reduction in load were occurring at the actuator, we would immediately see a loss in the load induced pressure which was being fed back to the righthand spool area. With this loss in equilibrium of forces, the pilot spool would move to the right. As shown in the illustration, the pump destrokes (reducing its displacement) when the spool vents the larger control spool area to the housing of the pump.
Now, considering the fact that the pump control reestablishes equilibrium conditions at the lower load in duced pressure, let us look at what will happen when the load increases.
- 266 -
\---,..:....
As load induced pressure increases downstream of the orifice, the system will slow down if the pump is not able to ncrease the pressure at the inlet of the orifice. However, the i increase in load induced pressure increases the pressure forces acting on the pilot control spool to the left. As the spool moves to the left, it upsets the previous established equilibrium condition, and loads the larger control piston with system pressure. This causes the pump to increase its displacement. The pump increases its output flow until the resistance to this flow creates a pressure at the inlet of the main flow orifice which is 150 PSI higher than the pressure at its outlet.
The small pilot relief, which is incorporated in the load sensing control circuit, provides a very important function. Its purpose is to limit the maximum feedback pressure to the pump control. When load induced pressure exceeds the set ting of this relief valve, the valve opens and limits the maximum force available for pushing the pilot spool to the left. The moment the pressure at the outlet of the pump ex ceeds the limited load induced pressure plus spring force, the pilot spool moves to the right. This causes the pump to go into deadhead. The pump pressure compensates and provides only the flow. required to maintain system pressure. The .023 orifice stabilizes the pump control by limiting the
- 267 -
amount of flow in the pilot circuit. If too much flow potential were to be exposed to the piloting relief valve, the pressure override characteristic would adversely affect the proper operation of the pump.
A less obvious feature of the load sensing control is that it will provide a constant flow regardless of the input drive speed. In a fixed displacement pump, an increase in its drive speed will also cause an increase in its flow output. If a restr iction were to be placed downstream of the pump, the higher flow with higher drive speed, would necessarily require a higher pressure drop across the orifice.
In a variable volume pump (with load sensing control), an in crease in RPM will also tend to cause increased flow. However, the moment the increase in flow occurs there will be a higher pressure at the inlet of the main flow ;rifice. The control will sense this increase in pressure on the left-hand area of the control spool (discussed previously), and cause the pump to destroke. If the drive speed decreases, the loss of flow at th main orifice inlet will cause a loss in control pressure. This will allow the load induced pressure plus spring force to move the pilot spool to the left. This, in tum, will cause the pump to increase its displacement to the point at which pressure equilibrium is reestablished at the main flow orifice. When you are selecting a pump with load sensing control for use in applications with variable drive speeds, be sure that the pump is sized so that the maximum flow will be supplied at the minimum dr speed. The pump will then decrease its ive displacement automatically as drive speed increases.
Positioning Piston
Proportional Solenoid
- 268 -
which uses a proportional solenoid to vary pump displacement. The pump responds from minimum to maximum displacement proportional to the current of a 24V D.C. command signal. The displacement of the pump is shown in the minimum position with no electrical signal sup plied to the solenoid. The pump is held in this position by the force of the feedback spring and system pressure working over the smaller area of the positioning piston. As a D.C. curTent is supplied to the proportional solenoid, the solenoid pushes on the pilot spool with a specific force. When the current, and, therefore, the force, is high enough to move the pilot spool against the small spring (which adjusts the beginning of regulation), pilot pressure is exposed to the large diameter of the positioni g piston. Because of the area n difference of the positioning cylinder, the pump begins stroking towards maximum displacement. However, stroking of the pump also causes the feedback spring to be compressed, which increases its force. When feedback spring force exceeds the limited force of the proportional solenoid, tbe spool will be moved back to its original position. This will cause the large diameter of the positioning piston to be disconnected from the pressure source and vented to tank. The net r esult is that the pilot spool modulates the pressure on the large area of the positioning piston, so that the precise balance of feedback spring force and proportional solenoid force is maintained. The pump stays at this displacement position until the current supply is changed, which changes the force output of the proportional solenoid. The control, as described, can be used to change the velocity o the output actuator, while the maximum force (or torque) f output would be controlled by a separate pressure control piped into the hydraulic circuit. There are, however, many other var iations of pump controls which use a proportional solenoid to adjust both displacement and the maximum pressure capability of the pump. For instance, the load sensing control, as previously discussed, is available with the adjustment of both the main flow orifice and the pilot relief established by two proportional solenoids. This allows both velocity and force output of the hydraulic system to be in terfaced with electronic controls.
as a two position control, using a two position four-way directional control, or it can be as sophisticated as a control cylinder which is positioned by a four-way directional servo valve.
Centering Springs
The circuit schematics show two variations of the cylinder controlled variable displacement pump. The top schematic is for use in open circuit applications, while the bottom schematic represents a pump for closed loop overcenter operation. The controls are quite similar, except for the fact that the overcenter pump incorporates centering springs, while the open circuit pump has a fixed stroke limiter which prevents the pump from going overcenter. Although the operation of this type of control is quite simple and needs no further explanation, there are some precautions concerning it which should be observed. First, the pressure and flow requirement must be calculated using the same method described for any double acting hydraulic cylinder (Chapter 1). Normally, the control cylinder size is determined by the size of the pump with which it is used. This, of course, influences the piston area, which is the determining factor for both the flow and the pressure requirements. Second, you will notice that the schematics represent a pump control which uses a double rod cylinder. In this pump design, the cylinder rod is permanently attached to the pump housing. The pump's displacement is changed when the cylinder housing swivels the displacement mechanism. With other pump designs, the stroking cylinder may only have a single rod. With these designs, you must consider the area differential and its influence on both flow and/or pressure intensification. Finally, you will find that there are several optional features offered for use with cylinder controlled pumps. The options include adjustable stroke limiters, centering or single acting return springs, and limit switches or potentiometers for feed back of the pump's displacement position to the electrical control circuit.
- 269 -
rected to the cylinder so that it moves back to the null position. Because the pilot spool is machined with zero overlap (Chapter 5), precise displacement positioning is ob tained. The mechanic servo control is normally supplied with separate pressure and tank connections for the control. To prevent damage to the pilot spool or servo stem, the proper pilot pressure and flow must be supplied to the control. In ad clition, the pilot oil supply circuit must be operating before an attempt is made to reposition the servo system.
0 flow is directed
to this end of the c91inder. which causes a change in pump displacement.
The valve body can catch up with the spool when pump reaches the desired the displacement.
I
0
mechanical link pulls on the housing of the directional control.
<?
The spool lands block flow to and from the positioning cylinder in the null position.
The diagram shows the basic operating principle of any mechanical servo system. The control positions the pump's displacement as determined by the position of the servo stem. You can easily see that if the stem is repositioned to the right, pressure and flow would cause the positioning cylinder to follow the motion of the piloting spool. It is im portant to note that, during operation, the pump is held precisely in the null position determined by the servo stem. Even if leakage by the pilot spool causes the positioning cylinder to drift, the control will self-compensate for this un wanted motion. The slightest drifting of the positioning cylin der causes the directional valve to open. Flow is then di-
- 270 -
PSI.
PSI,
The pressure related control for use with overcenter pumps is somewhat more sophisticated, but it performs the same basic function: it varies pump displacement in accordance with a pilot pressure signal. Because the pump strokes over center, two pilot pressure ports are provided, one for each direction of flow. A typical remote control pilot circuit for a closed circuit pump is shown in the illustration. The illustration shows the typical arrangement of the com ponent parts which make up a proportional hydraulic remote control. Although at first glance, this control looks somewhat complicated, it is actually quite simple in operation.
- 271 -
Overcenter Pump (Shown at Zero Displacement) Positioning Cylinder (Stationing Rod, Movable Cylinder Barrel)
Pilot
; i _j TI! - Remote Operation for Proportional Meter-Out Flow Control for Control Adjusting Stroke Time of the Pump Pump for Pilot Circuit
The remote control unit is a "joystick," (remote pilot control) which allows the operator to control pilot pressure in propor tion to the position of the hand lever. A close look at the valve shows that it is nothing more than two direct operated
three-way pressure reducing valves contained in a single housing. When the joystick is in the neutral position, the spring force on both spools is relaxed. As shown, this unloads the pilot circuit to tank.
- 272 -
When spring force balances hydraulic force, the control spool centers . . .
maintaining the required pump displacement. and directs flow to this side of the position cylinder.
The hydraulic force causes the spool to shift . . . is repositioned . . . the reducing valve increases pilot pressure here.
When the pilot circuit is unloaded, there is no pilot pressure on either end of the directional valve spool. Consequently, there is no hydraulic force causing the spool to shift. As shown, under these conditions, the pump is held in its zero
displacement position. If leakage across the control spool allows the position cylinder to drift, the position error is transmitted to the control spool. This "feedback" is ac complished by the mechanical link between the feedback
- 273 -
spring and the control spool. The error feedback causes the control spool to shift, thus allowing flow to and from the positioning cylinder. Let us now take a look at how propor tional variable displacement is achieved.
less than 100 PSI. This prevents the resistance to flow in the pilot circuit, when unloaded, from inadvertantly shifting the pump.
The illustration indicates the stroking of the pump to one side of center. You will notice that the operation is identical for the reverse direction of stroke. When the pump is operating in the opposite direction, downward motion of the joystick will cause pressure to build on the left end of the control spool. Flow will then be directed to the left side of the stroking cylinder, with the pump displacement varied propor tionally to the pilot pressure. Compression of the feedback spring will push the spool to its center position when the equilibrium between spring force and hydraulic force is achieved. , The control is designed so that the relationship between pilot pressure and pump displacement is perfectly linear. A typical control varies the pump displacement from zero to full as the pilot pressure varies between 100 to 580 PSI. As shown in the graph, the pump does not respond to pilot pressures of
THE CONSTANT HORSEPOWER OVERRIDE FOR THE OVERCENTER PILOT PRESSURE RELATED CONTROL
The pressure related control, as discussed up to this point, can be provided with an optional constant horsepower override. This horsepower override protects the prime mover from being overloaded by either fluctuations in the work load, or by a heavy-handed operator. The horsepower override works on the principle of modifying the control signal at either of the pilot pressure supply ports, in relation to the pressure at the outlet of the main pump. (For a com plete description of the constant horsepower control prin ciple, please refer to the discussion of this control earlier in this chapter.) The hardware which accomplishes this horsepower override is essentially made up of a variable pressure direct operated relief valve and two pressure equalizing sleeves assembled on either end of the pilot control spool.
0.8
0.6
0.4
0.2
Joo
...,..
58 0 PSI
0.4
0.6
0.8
- 274 -
This shuttle valve directs system pressure to the horsepower limiting valve.
the maximum pressure setting of this spool type relief valve is reduced.
G) As long as override
this sleeve equalizes the effect of this pilot supply pressure is higher than pressure. pilot supply pressure . . . When pilot pressure exceeds override pressure . . .
The pilot pressure related control as shown, varies pump displacement proportional to manual remote control valves. These remote control valves are available in a variety of hand lever and foot pedal operators to fit the application at hand.
Detail X (Operating) OTHER USES FOR THE PILOT PRESSURE mind, the designer can design a pilot circuit for controlling RELATED CONTROL the pump to meet virtually any system requirement.'
this pressure equalizing 0 sleeve is held tight against the valve housing . . .
(,"";\
The feed spring in the pump balances the override pressure . . . @ working on this effective area.
'The application of this control is more completely discussed in the Rexroth publication, "Pilot Pressure Related Control On Variable Displacement Hydraulic Pumps and Motors," by Graham Scott, Senior Applications Engineer.
The control, as discussed, is but one of many possible ap plications. The possible uses of a pump control which varies pump displacement directly proportional to a pilot pressure signal are actually limited only by the imagination of the design engineer. The method of generating the command pressure signal is irrelevant as long as it is not effected by pressure fluctuations in other parts of the circuit. With this in
- 276 -
SYMBOL
Variable Displacement Pump for Open Circuit With Separate Case Drain Connection (No Con trol Indication)
Variable Displacement Overcenter Pump for Closed Circuit With Case Drain (No Control Indicated)
Variable Displacement Overcenter Pump for Half Closed Circuit (No Control Indicated)
Variable Displacement Pump, Open Circuit, With Pressure Compensator Control, and Separate Case Drain
- 277 -
Closed Circuit Hydrostatic Transmission With Boost Pump, Make-Up Checks, Crossport Relief
_ _
Variable Displacement Pump With Hydraulic Cylinder Control With Fixed Stroke Limiter for Open Circuit Application
- 278 -
- -- , I , I I L _ LLU _j
- - - - -- .,
I r- - I
_
-'
_ _
I -J -+ - -- -
---- --/ I
_ _
Li.J
_j
- 279 -
_J
L _
..
L -
_ _ _ _
I I I I I I _j
CONCLUSION
This chapter has been devoted to an explanation of the major pump designs used in industrial hydraulic systems, beginning with a very basic explanation of how a pump con verts the energy of the prime mover into hydraulic energy. For a very basic understanding of any hydraulic pump, the reader should know the meanings of the following terms. Without a basic knowledge in this area, it would be difficult to compare pumps in order to make a proper selection for the system requirements at hand. The terms are:
Any variety of hydraulic pump available today can be put into one of three general categories: gear, vane, or piston. If the pump is a variable displacement design, it must either be a vane or piston pump, since gear pumps are available only in the fixed displacement version.
- 280 -
pump has been instrumental in overcoming the stigma that hydraulic systems are inherently inefficient. This old line of thinking is quickly being replaced by an awareness and utilization of components providing higher efficiency, better performance and superior control. The single most important advantage of the variable displacement pump is that heat is not generated by moving oil around the circuit when no work is being done. Even when a fixed displacement pump is unloaded, energy is con verted into heat, simply because the oil is in motion. Likewise, during operation, oil must be diverted, restricted, or removed from the system at a high pressure level. Many times, this pressure level is considerably higher than the ac tual pressure required to do the work during most of the cycle. On the other hand, the variable displacement pump can be made to produce only the hydraulic energy required to do the work. It can also be made to produce this energy only when it is needed to cause the required motion of the load. Our discussion of variable displacement pumps began with a description of the three types of pump circuits: open, closed, and half-closed circuits. We then discussed the mechanics involved in varying the displacement of vane, in-line piston, and bent-axis piston pumps.
VARIABLE DISPLACEMENT P U M P S
Efficient use o f our energy resources has become an im portant topic for discussion in all facets of our life, both at home and on the job. Today, engineers are evaluating the power consumption of new machines and appliances, looking for ways to reduce their energy demands to the lowest possible levels. The use of variable displacement pumps is playing a greater part in modern hydraulic systems. The variable displacement
A great deal more could be said of variable displacement pump controls than has been outlined in this chapter. We have, however, described the more common controls which are more or less standard to industrial pumps. With an understanding of the information presented in this chapter, the design engineer should be well on his way to determining the operation and application of any variable displacement pump control.
- 281 -
while proportional valves, on the other hand, are far more tolerant of contamination .
Servo Values: are usually used in closed loop systems. A ser vo valve has feedback built into the system. Feedback is part of the closed loop system which monitors the machine or processes and feeds a signal back to the valve which con trols it. Proportional Values: are usually used in open loop systems. This means there is no feedback, it is controlled by the operator or a process controller, or there is a fixed setting for the valve. Servo Values: are extremely accurate, generally better than a 1 % error factor. Proportional Values: are not as accurate as servo valves, generally not better than a factor of 3% error. Servo Values: are faster in response when compared to pro portional valves, generally between 60 to sometimes as high as 400 Hz. Proportional Values: are generally low in response, usually below 10 Hz. Although the use of servo valves can be justified for ex tremely accurate control and high dynamic capabilities , pro portional valves may be used anywhere directional and flow control valves are normally used.
It was only through the development of the proportional solenoid and the perfection of simple dirt resistant valves, that proportional valves made a significant breakthrough in the hydraulic system design. The performance of a propor tional valve not only depends on its electronic requirements and unique hydraulic features , but also on the proportional solenoid as well. There are two types of proportional solenoids, one being a stroke controlled solenoid (which will be discussed later) and the other being a force controlled solenoid. Force controlled solenoids are modified DC solenoids providing linear ad justable forces, by simply altering the current signal to the solenoid (see Figure 1 ) . Proportional force solenoids are o f the wet pin D C type which appear similar to a conventional DC solenoid, with a modified internal construction optimizing the linearity of the solenoid. When a conventional DC solenoid is energized, the plunger travels its full distance creating a constant output force. A force controlled solenoid operates on the principle that solenoid force output is linear to the current supplied. This linearity of force output to current, works effectively over a stroke of approximately 0.060" (1 .5mm). The easiest way to comprehend a force controlled solenoid is from the force travel curve (Figure 2). Considering that a given amount of current creates a given force, the force travel curve demonstrates this linear relation ship at various current levels. When current is supplied to the solenoid and held constant, solenoid force also remains con stant over a stroke output of approximately 0.060" ( 1 . 5mm). For example, when a 200 rnA signal is elevated to 400 rnA the force increases, but remains constant over the same stroke output of approximately 0.060" ( l . Smm) . Maximum force output for force controlled solenoids lies between 12 to 14 lbs . . Since adjustable forces can be achieved over a small
High cost: by comparison to proportional valves. The complexity of a servo valve demands far more auxiliary equipment, most of it being electronics. Proportional valves, by comparison , require a minimal amount of electronics. 3. Contamination: servo valves are more dirt sensitive,
Figure 1
Amplifier
stroke, installation dimensions for the solenoid do not be come too eat; therefore, the solenoid is compatible to pilot operated proportional pressure controls , directional control valves, and some variable displacement pump controls (Chapter 6). Also, since the solenoid is a wet pin there is a removable screw to bleed any air that may become trapped.
lbs . This force is sufficient to enable an adjustable force t o hold a small direct operated relief valve poppet in a seated position.
Figure 2
800 mA
-
Q 1.1..
Ql ...
ril
--
Proportional pressure relief valves perform essentially the same function as those of manually adjusted pilot operated types. The major difference between the two, is that the spring adjustment assembly in the pilot head is replaced by a force solenoid. As mentioned previously in our discussion of force sole noids, the solenoids maximum force lies between 12 to 14
Figure
3
Orifice
Proportional solenoid
1 .2
Orifice
1.1
Orifice
1 .2
TB
from port A {pressure port) to port B (tank port). The main poppet is a small low mass poppet which allows for minimal stroke during opening, meaning the valve reacts quickly. The sleeve is manufactured with three radial holes drilled symmetrically around it to allow for a divergent flow characteristic when the valve opens. The result is a much quieter valve. Unlike a conventional pilot operated relief valve, (where the maximum pressure rating of the valve is effectively estab lished by the force of the spring in the pilot head), the maxi mum pressure rating for a proportional pressure relief valve is established by the seat area of the pilot poppet . Con sidering the solenoid provides an adjustable force of up to 14 lbs ., a larger seat results in a lower maximum adjustable pressure rating of the valve. The resultant pressure force therefore has to work over a larger area on the nose of the pilot poppet, thus requiring less pressure to push it open. Likewise, a smaller seat results in a higher pressure rating of the valve since the resultant pressure force must now work over a smaller area on the nose of the pilot poppet. It takes a greater amount of pressure to push the pilot poppet open. The sensitivity of the proportional solenoid requires that the pilot head be externally drained directly back to tank from port Y. If the pilot head is internally drained, back-pressure can develop causing erratic operation of the valve. With the help of the electronic amplifier the pressure setting
of the valve can be either gradually increased or decreased accordingly. Also, solenoid force can be quickly or frequently adjusted during machine operation. Adjusting time; or the time it takes to go from one valve setting to the next, with respect to the signal received from the amplifier, is in a range from 50 ms to 1 50 ms depending on valve size. If power is lost to the valve, solenoid force immediately falls off, allowing oil to pass from port A or port B. To protect the system from high unexpected solenoid forces, {such as those caused by electronic failure or high current peaks), a maxi mum pressure relief valve can be built into the pilot head of the valve. This can be accomplished by using a standard spring and poppet assembly which can be mechanically adjusted just slightly above the maximum desired system pressure. It should also be mentioned, that many times a relief valve is needed for very small flow rates. By removing the pilot head and using it as an electronically adjustable direct operated relief valve, the pilot head alone can handle flows up to about one half a gallon per minute.
Proportional pilot operated pressure reducing valves are similar to proportional pilot operated pressure relief valves, in
Pressure is transmitted through passage 9, and works above and below the main spool. Since the main spool is of equal area, a force balance is created because of the equal pres sures. With a hydraulic balance on the main spool, a light spring force keeps the main spool in an open position. Oil is thus able to flow unrestricted from the primary port B, to the secondary port A. When pressure in the s econdary port exceeds the force of the proportional solenoid, the pilot poppet opens allowing oil to drain from the top of the main spool via port Y to tank. This establishes a pressure drop on orifice 6 and 7 which unbalances the forces on the main spool. The main spool then moves upward reducing the flow area from B to A (due to the radial drillings in the main spool and sleeve) and creating a secondary reduced pressure in port A . The main spool then modulates to maintain pressure in port A at the setting of the proportional solenoid. With the help of the amplifier, solenoid force can be quickly and/or frequently adjusted during machine operation. Adjust mcnt time (or the time it takes to go from one valve setting to the next with respect to the signal received from the amplifier) is in the range of 100 ms to 300 ms depending on the size of the valve. Solenoid force can also be gradually increased or decreased. This results in either a gradual increase or decrease in pres sure as required. For maximum protection, a manually adjusted relief valve can be fitted in the pilot head. As with the proportional pres sure relief valve, the pilot head should be externally drained directly back to tank.
that they eve electronically adjustable and incorporate a force solenoid. The main valve assembly is the same as a manually adjusted pilot operated pressure reducing valve, with the pilot head being the same as the proportional relief valve. The maximum pressure rating of the valve is therefore determined by the seat diameter of the pilot poppet as is the relief valve. When the valve (Figure 4) is supplied with an input signal the force of the proportional solenoid directly operates on the pilot poppet. As long as the force of the solenoid holds the pilot poppet closed the pilot oil remains in a static condition.
(j) Orifice
Main Body --:-J
sure above the main poppet. When pressure in the secondary port A exceeds spring force plus pilot pressure, the main spool moves upward creating a secondary reduced pressure, and modulates as required. If pressure in the secondary port builds too high during a static condition, the overload protection will open allowing oil to return to the pilot head, thus preventing pressure build up due to leakage. Both types of proportional pressure reducing valves can be built with reverse free flow checks.
Pilot Poppet
Orifice
achieved with just one proportional directional valve, when interfaced with the required electronics. With conventional valving, such controllability is sometimes not possible even with as many as seven valves. It is not only the required elec tronics that give the proportional directional valve this capability, but its spool as well, which plays a big part in its overall operation.
cylinder ratios close to 1 : 1). Since it is an equal area spool, the pressure drops from ports P to B, A to T or from ports P to A, and B to T stay fairly equal giving good controllability. Figure 5 shows a restricted center spool which gives a restricted flow path from P to A and B, with T blocked. The restricted center position is achieved by machining square metering notches on both P port spool lands . This allows about 3% metered oil of the full flow rating of the spool. The spool is norrnally used in motor applications providing the necessary make-up oil in the center position, which may be needed due to motor leakage or any suction that is created if the motor is brought to a sudden stop. Other than the modified center position, the spool construction and operation is the same as the closed center spool. Figure 6 shows a 1 : 1 restricted center spool. This spool gives a restricted flow path from ports A and B to T with P blocked. Once f!gain the square metering notches provide 3% metered oil while in the center position. The spool is nor mally used with single rod cylinders with an area ratio close to 1 : 1 . Since all spool valves have some leakage, oil that leaks from port P when the valve is centered, can drain from ports A and B to tank. This eliminates the risks of cylinder extension and pressure intensification. When this spool is used for overhung loads, some type of counterbalance or pilot operated check valve must be used. A regenerative closed center spool is shown in Figure 7. The right outside land contains no control grooves, therefore blocking B to T when the spool is moved left. A regenerative spool (see Figure 8) with a restricted center allows oil to bleed from ports A and B to T with P blocked. The right spool land being extended with a square metering notch cut into it, provides the metered oil from B to T when centered. When the spool is moved to the left, B to T is blocked.
Due to modem precision machining methods, the radial clearance between the proportional spool and the inside bore diameter of the valve housing is approximately 3 to 4 mi crons (.00012" to .00016"). Although all spool valves have internal leakage, at this close tolerance between the spool and inside bore diameter, leakage is kept to a minimum. This also allows for spool overlap to be kept to a minimum. Spool c<JI'lfigurations for 4-way proportional valves are basic ally simple in construction and easy to apply. As previously discussed, the spools are designed specifically to provide metering in both directions.
2 : 1 SPOOLS
When selecting the proper proportional spool for cylinders with area ratios close to 2 : 1 , one must always make a careful decision. Figure 4 shows a closed center spool. The metering notches are provided by machining triangular grooves on the spool lands, often referred to as "control grooves". Each land has eight control grooves cut symmetrically around it, providing equal flow areas in both directions . When the spool i s moved in either direction, the specially designed control grooves never move fully free from the an nuli, thereby always retaining a metering function . As in the condition of conventional directional valves, the spool first moves through a deadband and then completely opens, to virtually eliminate metering. Although all proportional spools are positively overlapped precisely 1 1 % , compensation has been made in the amplifier to reduce this to a minimum. The spool is norrnally used to control motors or cylinders (with A 2:1 cylinder's rod end delivers only half the amount of flow of that received at the blind end: the blind end delivers twice the amount of flow received at the rod end. If an equal area closed center or restricted center spool is used to control a 2 : 1 cylinder, the pressure drop across the valve in both direc tions can become fairly unequal. This can lead to cylinder control problems. To avoid this, a closed center or restricted center spool can be chosen with a reduced flow area giving one half the flow area on one side of the spool, as that of the other side (see Spool Chart on Page 7-9). The photograph shows how this reduced flow area is achieved. By eliminating half of the control grooves on one land, the flow area is one half of that of the other land. This keeps the total pressure drop across the valve fairly equal
maintaining good controllability of 2 : 1 cylinders. Pressure drop calculations for 2:1 cylinders will be shown later in this text, as well as cavitation effects and braking pressure when a 1 : 1 spool is used with a 2 : 1 cylinder.
Figure 4
Triangular grooves cut on both sides of the spool provide metering on both sides of the valve.
P to B _______. A to T
Figure
Square metering notches provide a restricted center position from P to A & B with T blocked.
P to B A to T
_____..
1_. _ _ P to A B to T
Figure 6 Square metering notches, provide a restricted center position from A & B to T with P blocked.
P to B ___._ A to T
..____
P to A B to T
Figure 7 No metering notch here allows for ::::::;:::;:::>>::::: ;:v us ing the va lve in a regenerative circuit.
P to B ____.. A to T
,._____
P to A B to T Blocked
...,. T
"V
A
... p
"V
B
Figure 8
P to B ____.. A to T
P to A ..__ B to T Blocked
... T
"V
A
... p
"V
B
CLOSED CENTER
P - A = Q, B - T = Q P - B = Q , A - T =- Q
PT
a
(
CLOSED CENTER
,,
'
D
t
CLOSED CENTER
P - A = Q/2, B - T = Q P - B = Q, A - T = Q/2
D
(
CLOSED CENTER
'X I)u I
)(
)
Motor Spool
( )( ) I
I
)(
l( ) I
T I
)(
X
r
>l2 l
T
H
)t
X
'(
T
I
) t
1 HT
Regenerative Spool
tially two 3-way proportional pressure reducing valves_ A simplified diagram of a 3-way pmportional pressure reducing valve is show in Figure 9.
Figure 9
When the solenoid is supplied with an input signal, a cor responding force is created, shifting the spool to the right. This action opens port P to outlet port A allowing oil to pass to its required function. At the same time pressure building in port A is fed back to the opposite end of the spool applying a counterforce to that of the solenoid force. When pressure in port A builds up high enough to equal the force from the solenoid, the spool centers and goes to a no-flow condition. If pressure in port A overcomes solenoid force, the spool shifts left allowing oil to pass to tank until equalibrium is achieved between the two forces, once again allowing the valve to return to a no-flow condition. This is basically repre sentative of the actual pilot head. The only difference is the valve incorporate s two proportional force solenoids, and consists of a special 3-piece spool arrangement.
Solenoid force operates directly on this 3-piece arrangement (see Figure 10), which consists of a control spool (4) with a sensing piston (5 and 6) in each end of the spool. Both sens ing pistons are free to move in each end of the control spool. If solenoid B receives an input signal, the force of the sole noid pushes directly against sensing piston 6 which pushes the control spool to the left. This allows oil to flow from port P to A and causes a pressure build-up in port A. At the same time, two radial drilled holes in the control spool allow pressure in port A to feed through the drilled hole furthest to the left, thus acting on sensing piston 5 . Since the piston is free to move in the end of the control spool, the pressure pushes the piston out against solenoid A. The pressure force between piston 5 and the control spool work against the force of solenoid B . When pressure in port A increases (to a point where it corresponds to the force of solenoid B), the control spool is moved to the right, closing off the connection from P to A, while holding pressure in port A constant. If the force of solenoid B is reduced, the pressure in port A pushes
. iii ,
Proportional solenoids
the spool even further to the right. Oil can then drain from A to T until pressure is reduced to where it once again cor responds to the force of the solenoid. If a signal is provided to solenoid A, the process reverses with port P opening up to Port B.
serves to protect the pilot section since its maximum operat ing pressure at port P is limited to 1450 PSI.
Now that the 3-way proportional pressure control valve has been discussed in its entirety, emphasis will now be placed on the total pilot operated proportional directional control valve assembly. Electronically adjustable pilot operated proportional/direc tional valves can be either internally or externally piloted from port X. Pilot pressure requirements must be carefully considered. To ensure full opening of the main spool under all operating condition s, a minimum pilot pressure of 435 PSI is required at the pilot valve's inlet. Also, if the valve is in ternally piloted and the system operates above 1450 PSI, a sandwich mounted pressure reducing valve must be mounted between the main valve and the pilot section . This
In Figure 11 when both solenoids are deenergized, the main spool (closed center 1 : 1 ) is held in its center position by a pretensioned push-pull spring assembly. The push-pull
Figure 1 1 =A=
spring assembly is fixed to one end of the spool by means of a rod, with the spring held between two retaining plates, allowing the rod to move freely through the retaining plates. A pressure signal in pilot chamber 10 moves the spool to the left, compressing the spring against the outer cavity of the end cap; or it can be said that a pressure signal in chamber 10 moves the spool to the left pushing on the spring assem bly. A pressure signal in pilot chamber 1 1 moves the spool to the right compressing the spring against the valve housing or pulling on the spring assembly. The spool is "spring cen tered" until pilot pressure in one of the end caps is sufficient to move the spool to a metering position. The maximum pilot pressure needed in either chamber to cause full movement of the spool is 365 PSI. When solenoid B receives its maximum signal, the solenoid develops 14 lbs. of force and moves the control spool to the right allowing a 365 PSI pressure signal to develop in chamber 10. At the same time, the main spool is moving left a proportional distance to the pressure signal developed by the force solenoid. Not until the force of the solenoid corresponds to that of the pressure in chamber 10, does the pilot valve hold constant pressure in the pilot chamber. The main spool then mainj . t -s -se" p H rf wn os! '!ch- in this case, woulCi cause tl1e spool tai n a to travel its full distance. Since the spool moves in proportion to the input signal to solenoid B, the control grooves open progressively to give an increasing flow from P to A and B to T. If a signal is received at solenoid A, the process reverses
and the main spool moves to the right allowing oil to pass
the spool is also responding to the increasing or decreasing time controlled signal. So, the rate for which the signal is set determines the rate at which the spool reaches its set point. The amount of signal determines the final set point of the valve or the final spool position; which allows us to conclude that:
1. 2.
3.
The amount of signal determines the final spool position. With the help of the amplifier, a time controlled signal determines how fast or how slow the spool is going to reach its set point, directly corresponding to ac celeration and deceleration. The spool provides metering in both directions.
from P to B and A to T. Adjustable forces are achievable by the amount of signal supplied, making it possible for various spool positions to be set. Since the control grooves are triangular in shape to pro vide metering, each time a particular spool position is set a particular orifice is created. Various speeds for motors and cylinders can therefore be set, by the desired amount of signal directed to the valve. With the help of the electronic amplifier, a time controlled movement of the spool can pro vide smooth starting and stopping of loads. If, for example, the pilot operated proportional directional valve just de scribed were used to accelerate a load to a constant velocity and then decelerate the load to a stop, with a time controlled movement of the spool and the precise metering of the spool, this would be accomplished very smoothly. Let us consider solenoid B as requiring a 1 00% signal to determine the set point. When solenoid B receives a 100% signal the signal can be increased with the help of the elec tronics, from 0 to 100% in a given time rate. This means the force of the solenoid is gradually increasing and a pressure signal is gradually developing in the pilot chamber. At the same time the main spool is proportionally moving from its center position to its set point providing a progressive open ing of ports P to A and B to T and accelerating the load to a constant velocity. When decelerating the load to a stop, solenoid B is deenergized decreasing the signal from 100% to zero in a given time rate and proportionally moving the spool back from its set point to its center position bringing the load smoothly to a stop. It should be clear as the signal increases from 0 to 100% or decreases from 100% to 0 that
Many applications require the control of a proportional direc tional valve, but for various reasons designers do not want the electronics involved. A direct pilot operated proportional directional valve without electronics can be used if simple direct control is all that is needed. Its main valve assembly is exactly the same as the electronically controlled pilot operated directional valve. The only difference is, the pilot head is replaced with a connecting plate (see Figure 12). Instead of having an electronically controlled proportional valve, it becomes a hydraulically controlled proportional di rectional valve, requiring external pilot pressure. The connecting plate connects pilot ports A to Y and B to X. Providing pilot pressure at port X causes movement of the spool to the right to give a flow path from P to B and A to T. Pilot pressure at port Y causes the spool to move left giving a
Figure 12
Figure 1 3 GPM 90 80 70
Q., 60 C!) 50
40 ...I 30 ""' 20 10
25
30
/,/ /
/4
1 00
flow path from P to A and B to T. Movement of the spool is proportional to a pilot pressure between 21 and 365 PSI. Common pressure controls used to provide pilot pressure are joysticks, footpedals, and pressure reducing valves. (see description & photograph on pages 6-4 7 and 6-52). Any of these can be mounted away from the main valve, providing easy installation in control consoles and test areas.
= = = = =
control current does not effectively utilize the full spool stroke. The valve would virtually pass 10 GPM unmetered providing little or no controllability at that end of the curve. A smaller spool would be needed to give full control. The curve clearly demonstrates that the purpose of using proportional directional valves is to provide control. In order to provide full control, there must be metering, meaning there must be pressure drop across the valve. The example just given does not consider load conditions . A more detailed ex planation of these curves is covered later in Chapter 9.
1 00 90
( i/ I I '
0 20 40 60 80 1 0 0 0 20 40 60 80 1 0 0
Ql .:ill 0
80 70 60 50 40 30 20 10
' \
... ... en
Figures 14 A, B and C show the fastest possible movement of the spool from one position to another, assuming a stepped (immediate change) input from the electronic am plifier. Figure A shows a change in command from 0 to 100% on the left of the graph and a change in signal from 100% to 0 on the right. Figures B and C are similar, however Figure B shows a 50% stepped signal change (25% to 75%) and Figure C shows an 80% change in command (10% to 90%). It is important to note that the above Figure 14 graphically represent the valve's reaction to a single change in input signal. They show the time required in milliseconds for the valve to reach a desired position, assuming an im mediate command to go to that position. This time requirement introduces phase lag in the system which is im portant when considering a cyclic change in command. In Figure A the graph shows that the signal for the valve to go from 0 to 100% must endure for approximately 80 milliseconds in order to have the valve achieve 100% open ing. Likewise, when the signal is taken away, no new com mand can be introduced for at least 70 milliseconds if the valve is to fully close. In other words, approximately 150 milliseconds are required to achieve a complete cycle. This means:
100 90
SIGNAL STEP 2 5 - 7 5 %
Ql .:ill 0
80 70 60 50 40 30 20 10
0 20 40 60 80 100 0 20 40 60 80 100
1 cycle
1 50 milliseconds
1 000 ms sec
6.6 cycle/sec.
Consequently, the fastest the valve can be cycled and achieve 100% response is 6.6 cycles per second. If the signal changes cyclically at a faster rate, the valve can no longer keep up with the command. For instance if the signal is changing at ten cycles per second, the 0 to 100% com mand to the valve tells the valve to open. The valve, however, may only achieve 50% opening before it gets a new command to close.
TIME t (ms)
Ql .:ill 0
l
1/
1\ \ 1\
... ... en
I I
20
TIME t (ms)
Decibels: Is the log10 of the ratio of output change to input change. Logarithms are used in order to condense numbers. Example
50%
to
Figure 1 6
The negative sign indicates that the output is becoming less since the log,0 of a fractional number is negative. Example 2: Input change: 100% Output change: 100%
r""'""'
I'-." I
I
./
100
100
....
05 I 3
....
1 / ./""-:>' / \ / v
I/>
4 5 6 7 fl 9 10
70
JO 40 50 60 70
Phase lag: The time required for the output to recreate the command of the input. In cyclic occurrences this is normally measured in degrees (refer to Figure 15). Figure 16 shows a typical frequency response curve for a proportional (or servo) valve. In this graph the top curve (descending curve) shows the relationship between ampli tude response and frequency. Curve 1 shows a 25% change assuming a 50% input (50% opening P-+A and B-+ T). Curve 2 shows a 50% signal which varies to a high of 100% and a low of 0% cyclically. For this particular valve at an amplitude -3db (50% output) the frequency response is 10 Hz. It is important to note that the industrial standard for representing valves has been placed at the -3db level. The curves clearly indicate, that as the signal comes faster and faster, the amplitude of spool motion in the valve becomes less and less. The bottom curves in Figure 16 show the relationship be tween phase lag and frequency. Phase lag as measured in degrees is shown on the right vertical axis of the graph. As the signal increases in frequency the ability of the valve to keep up becomes less and less; in other words the phase lag becomes greater. In comparing curve 1 and 2 (variations in the amount of signal change as previously discussed), it takes considerably longer (more degrees of phase lag) for the spool to catch up as the amount of required spool motion is increased.
Figure 1 5
A
Cyclic Output
+--------Input
TIME
Cyclic
90 Phase La g
TIME
1 80 Phase Lag
TIME
NOTE: At 1 80 of phase lag the system goes into instability. This is due to the fact that the output does exactly the op posite of the command. In other words, as the command grows larger the output grows smaller and vice versa.
Up to this point two types of proportional directional valves have been discussed; electronically controlled pilot operated directional valves and hydraulically controlled proportional directional control valves. A third type used for lower flow ranges than those just mentioned is an electronically con trolled direct operated proportional directional valve (see Figure 1 7).
Figure
18
AMPLIFIER
Basic construction of the valve is similar to the 3-way pro portional pressure control valve. Both possess force sole noids, but with this third type of valve, the 3-piece spool assembly is replaced with a proportional spool. In this case, when either one of the solenoids receives an input signal, the force from the solenoid operates directly on the spool. When both solenoids are deenergized the spool is held in its center position by two return springs. If solenoid A receives an input signal, the spoo l is moved to the right a proportional distance to the signal, allowing oil to progressively flow from P to B and A to T. The same holds true for solenoid B, ex cept the spool moves left against the spring force allowing oil to progressively flow from P to A and B to T. A proportional solenoid with a built-in positional transducer, sometimes referred to as a LVDT {linear variable differential transformer) , is called a stroke controlled solenoid. (See Fig ure 18) . The primary reason these solenoids were developed was to improve valve performance. This was made possible through the LVDT which provides electrical feedback allowing the stroke of the solenoid to be measured more ac curately.
Figure
17
Air bleed
Air bleed
-- -- -+---
V .A. V \TJ
A P B (T)
Metering spool
When a proportional solenoid first receives ah input signal causing it to respond, a certain percentage of error is gener ated if direct operation of a process is required. Such would be the case with a directly controlled spool stroke of a direc tional valve. Since the LVDT is built into the end of the proportional solenoid, it measures what the actual spool position is, and then feeds back a signal to the amplifier. The input signal and feedback signal (or actual value) are then compared electronically in the amplifier. From these two values a corrected signal is generated back to the solenoid to compensate for any error generated. This results in the flow forces on the spool (being counteracted), maintaining a very accurate spool position (orifice flow area) .
So far discussion about proportional directional valves has been solely based on directional valves with force controlled solenoids. Proportional directional valves that incorporate positional feedback can be directly operated with a high degree of accuracy.
Figure 19 shows a direct operated proportional valve, stroke controlled, with its spool held in center between two cen tering springs . When solenoid A receives an input signal the spool is moved to the right opening ports P to B and A to T. When solenoid B receives an input signal, the spool moves to the left opening up ports P to A and B to T. The LVDT being mechanically linked to solenoid A is capable of move ment . 1 1 7 in . for either direction of the spool. Thus when either solenoid receives a particular input signal the spool moves a corresponding distance. This causes the core of the LVDT (since it is mechanically linked to solenoid A) to move out of equalibrium, which induces a signal and feeds it back to the amplifier relaying to it the actual spool position . The input signal and feedback signal (or actual value) is then compared electronically in the amplifier. From these two values a corrected signal is generated and fed to the solenoid giving a definite position of the spool. If feedback is lost the spool will return to its center position . This safety feature is built into the amplifier. The main spool , similar to that in the pilot operated propor tional directional valve, has control grooves cut into it giving a progressive flow action. Unlike the pilot operated direc tional there is no need for pilot pressure since the valve is directly operated. It also should be mentioned that stroke controlled direc tionals are the most accurate of all proportional directional valves but have one small drawback, their size. A 002 valve size is the largest available at a nominal flow rating of 16 GPM at 1 50 PSI drop across the valve, whereas pilot oper ated proportional directionals are available in a 010 valve size with a nominal flow rating of 137 GPM at 150 PSI drop. Stroke controlled proportional directionals could be made larger to handle more flow; however, there is the problem of higher flow forces being generated at higher flow rates. With
Figure
19
the solenoid acting directly on the spool, the solenoid would have to become very large to counteract the generated flow forces. Although the electrical feedback would try to main tain spool position, the solenoid would eventually run out of force.
which are electronically adjustable with an LVDT for posi tiona! feedback. (See Figure 20 .) The pressure setting of the valve is directly proportional to the input signal. When the proportional solenoid receives an input signal, the stroke of the solenoid pushes directly on a pressure pad. This in tum pushes on a compression spring with the spring pushing on the poppet . The actual position of the pressure pad is then determined by the LVDT feeding a signal back to the amplifier. The feedback signal and input signal are then compared electronically sending a corrected signal back to the solenoid. A definite position of the pres sure pad is then maintained. A very accurate spring tension is also maintained which accounts for very accurate pressure settings . When pressure exceeds the setting of the spring, the poppet opens allowing oil to flow from the pressure port through the spring chamber to the tank. As with the pilot operated pro portional pressure relief valve, the pressure setting can be gradually increased or decreased with the help of the am plifier. Since the pressure can be set very accurately, the valve is used extensively in injection molding applications where in jection pressure accuracy is critical . It also can be used as a pilot control for logic elements and pressure relief valves. Maximum flow capabilities are limited by the various pres sure ranges, since seat diameter decreases with increased pressure capability. If power is lost, solenoid force is reduced to zero and the valve's pressure setting is dependent only on the unloading characteristics of the valve.
Figure 20
The 2-way proportional pressure compensated flow control valve consists of an electrically adjustable control orifice which is in series with a pressure reducing valve spool called a hydrostat (see Figure 2 1 . ) The hydrostat is placed before the main control orifice and is held in its open position by a light spring. If the input signal to the solenoid is zero, the main control orifice remains in a closed position by means of a light spring force. When the solenoid receives an input signal, the stroke of the solenoid operates directly on the control orifice moving it downward against the spring to an open position, thus allowing oil to pass from A to B (Figure 22.) At the same time the LVDT, as discussed in previous sections, provides the necessary feedback to maintain posi tion . In this case the LVDT is providing feedback to maintain a very accurate orifice setting. Pressure compensation is achieved by feeding a pilot pas sage from the front of the con trol orifice to one end of the hydrostat and feeding a pilot passage beyond the control orifice to the opposite end of the hydrostat, assisted by the spring. Load induced pressure at the outlet port or pressure deviations at the inlet port are therefore compensated for by the hydrostat, resulting in a constant output flow.
Figure 2 2
L.V. D . T.
Proportional flow control valves are pressure compensated 2-way valves with the main control orifice being electron ically adjustable. Similar to conventional pressure compensated flow control valves, a proportional pressure compensated flow control valve maintains a constant flow output by keeping the pres sure drop across the main control orifice constant. The pro portional valve, however, is different in that the control orifice has been modified to work in conjunction with a stroke controlled solenoid.
Solenoid --- -- _
Figure
21
- - - - - - - - -,- - - ,
,I
- - -
I
A
Hydrostat
8
I I I I I _j
_ _j
I I
I
Inlet Pressure Orifice
Outlet Pressure
Time controlled opening and closing of the orifice is made possible with the help of the amplifier. For reverse free flow, a check assembly is built into the valve to give a free flow path from B to A. Proportional flow control valves can also be provided with either linear or progressive flow characteristics. The input signal range is the same for both, except the progressive flow characteristic gives a finer control at the beginning of orifice adjustment . If power or feedback is lost, solenoid force reduces to zero and the spring pushes the orifice closed. Also, when power is supplied and the feedback polarity is reversed, by mistake , the orifice remains in its most open position .
tiometer can make the orifice remotely adjustable while the maximum spool acceleration is still limited by this internal ramp, or a limit switch can be used to tum the ramp on and off. In the event of a power failure, the element will return to its normally closed position.
Figure 2 3
Amplifier
Spring Chamber
Proportional flow control logic valves are electrically ad j ustable flow controls that fit into the standardized logic valve cavity. The cover and cartridge are assembled as a single unit, with the cover consisting of a proportional force solenoid and pilot controller (see Figure 23). When an elec trical signal is put into an electronic amplifier, the solenoid and controller adjust the pilot pressure supplied from the "A" port side, to change the spool position . The position is then fed back to the amplifier by a linear variable differential trans former (LVDT). This maintains the desired orifice condition for flow from the "A" side to the "B" side of the element. The proportional logic valve is available with either linear or progressive flow characteristics which are adjusted by a 0 to 6 volt or a 0 to 9 volt command signal. The valve is relatively unaffected by changes in the system pressare; so it can open and close the orifiCe in the same amount of time. This maximum time can be changed on the amplifier card by adj usting a built-in ramp generator. The amplifier can be used in a variety of ways . An external paten-
Main Piston
f\
- j
-
is assisted by a light spring force which has twice the effec tive area of the smaller piston, therefore, during start-up the spring force holds the cam ring in an eccentric position allow ing the pump to displace fluid. System pressure works on both pistons and as long as the larger piston is not vented to tank, the pump will maintain an output flow. As soon as the larger piston is vented to tank, the smaller piston which is still pressurized, pushes the cam ring in a concentric position providing a no flow condition until system pressure is re established over both piston s. ( For a more detailed explan ation on variable volume pumps refer to Chapter 6.)
CONTROL OP ERATION
The output flow of the pump is diretted through the elec tronically settable orifice which for any particular setting of the orifice, the pressure drop is maintained constant by the load sensing pump control. The control spool in the pump control works much like a hydrostat in a pressure compen sated flow control valve. The control spool (bottom spool in Figure 25) senses pressure at both the inlet and outlet of the proportional orifice. The outlet sensing side of the spool is assisted by an adjustable spring force which is normally set at approximately 1 50 PSI. The setting of this spring force
BASIC PUMP OP ERATION The cam ring of the variable volume vane pump (see Figure 24) is held between two control pistons . The larger piston
Figure
24
L.V. D.T.
Cam ring
compensator spool Small piston Large piston sensing spool Electronic piloting relief
Figure 2 5
pressure at the orifice is no longer sufficient. This, however, unbalances the spool so that it moves left loading the pump control piston. The pump flow increases until the resistance to flow at the main orifice reestablishes the modulating pressure balance on the control spool. Due to the fact that the electronically selected flow is influenced by only the orifice area, and the constantly maintained pressure drop, (GPM CA ), the pump's volumetric efficiency does not influence the desired flow selection .
=
PROPORTIONALLY ADJ USTED PRESSURE COMPENSATION The electronically settable pressure control, and pump's pressure control spool (top spool is Figure 25) works in a manner identical to the electronic proportional relief valve discussed previously. As long as load induced pressure working over the effective area of the pilot poppet does not exceed the adjusted solenoid force, there is no pilot flow, hence there is no b. P on the orifice located adjacent to spring chamber (in reference to Figure 25). A pressure bal ance then exists on this spool and the spring force keeps the spool to the left in a "pump loaded" position. When load in duced pressure exceeds the setting of the proportional relief valve, the pilot flow across the fixed orifice creates a pres sure imbalance on the top control spool . The spool snaps to the right thus pressure compensating the pump.
determines the pressure drop across the main orifice. B y adjusting this differential pressure, a n exact flow can be achieved for a given electronic input signal. Since the control spool is of equal areas at both ends , it modulates to maintain a balance between inlet pressure ex posed on the left side and outlet pressure plus spring force on the right. When the orifice is moved in a closing direction , or where there is a loss in load induced pressure, a tendency exists where inlet pressure tries to exceed outlet pres sure plus spring force. This cannot happen since the higher inlet pressure pushes the control spool to the right partially un loading the pump's larger control piston. In this way pump flow decreases until inlet pressure again balances outlet pressure plus spring force . Conversely, if the proportional orifice is opened, or if load induced pressure increases, inlet
PROPORTIONAL PRESSURE R ELIEF VALVE The proportional pressure relief valve is direct operated, and is controlled by a force solenoid. The desired amount of signal to the solenoid determines the maximum pressure at which the pump compensates . Ukew\se , the minimum pres sure at which the pump compensates is determined by the setting of the spring adjustment on the pressure control
Figure 26
spool. This generally is set at a low pressure for proper oper ation of the pump control. The pilot valve can handle flows up to 3.2 GPM which is more than sufficient for draining oil from the control section of the pump. Sandwiched directly beneath the electronic proportional valve, is a mechanically adjustable pressure relief valve. Similar to the proportional pilot operated relief valve with maximum pressure protec tion, this valve can be adjusted slightly above the setting of the proportional force solenoid. In the case of power failure or high current peaks, there is always maximum protection provided for the pump. The sensitivity of the solenoid requires that the tank port be run separately back to tank, avoiding any back-pressure that otherwise might develop in the valve .
ELECTRONICALLY ADJU STABLE MAIN ORIFICE The main orifice (Figure 26) is a spool type variable orifice controlled by a proportional solenoid with an LVDT for positional feedback. The orifice is shown in a closed con dition. As the desired amount of signal is increased, the solenoid pushes directly on the spool which is counteracted by a light spring at the opposite end. If power or feedback is lost, the force of the spring pushes the spool back to a closed condition . At each position of the spool the orifice propor tionally opens allowing the output flow of the pump to pass from port A to B. For maximum protection of the pump, a quick acting me chanically adjustable relief valve can be obtained in the hous ing of the orifice. This is fitted just before the inlet side of the orifice (A side) so that high pressure peaks can be avoided.
PROPORTIONAL PRESSURE CONTROL SYMBOLS (WITH FORCE SOLENOI DS) SYMBOL Without Maximum Pressure Protection With Maximum Pressure Protection DESCRIPTION Electronically Adjustable
I ly &..L
Pilot Operated, Pressure Reducing Valve, External Drain, Reverse Free Flow Check
IT:.- I I 8
b P B1
_ -
3-Way Pressure Reducing Valve (Pilot head for pilot operated directional valves)
'A
PROPORTIONAL DIRECTIONAL VALVE SYMBOLS (WITH FORCE SOLE NOIDS) SYMBOL DESCRIPTION
I L --i L -- ,.- AI
X p
l f .c), w : Il l i )ic )k
I I l _j
L
- _j
I , - - -=--=-- - - l
i L
b
r----------,
L_ l
I
Detailed Symbol of Pilot Operated Proportional Directional Control Valve
*J-f * T - - - - rv T
_._ J
y
I _j
B
I J
r71 \
1: :r
o
p
r;x5
,y
Electronically Adjustable, Pilot Operated, Spring Centered, Internal Pilot, Internal Drain
XI
l: :r
o A
p A pi
Electronically Adjustable, Pilot Operated, Spring Centered, Internal Pilot, External Drain
--
Cz ! :
a o
\I
.ex \
X
:: :i ::0
B b
x5
I
Electronically Adjustable, Pilot Operated, Spring Centered, External Pilot, Internal Drain
1 B
I T
I 'Y
Electronically Adjustable, Pilot Operated, Spring Centered, External Pilot, External Drain
a, x-
...
A1 I
I
, B I
0 I
'
'
- b, y
i : :j
A B a o b
pi 1
SYMBOL
r - - - - - :1
'>
r&1:
::::::
I I
I I
Electronically Adjustable, Pressure Compensated Flow Control Valve, with Feedback of Main Flow Orifice Setting
t... - ...J
pi
j j
o ' T
Electronically Adjustable, Direct Operated Directional Valve, with Feedback of Spool Setting
X ---
_y f--'--
f-+ A A - f-t t- 1- B
r--
Electronically Adjustable Flow Logic Valve, with Feedback of Flow Orifice Setting
SYMBOL
DESCRIPTION
Q
1--
Load Sensing Pump Control with electronically set flow and electronically set pressure compensator.
ELECTRONICS
order to operate any proportional solenoid, two major electronic devices are needed: an amplifier and a power supply. The electronic amplifier, often referred to as an am plifier card, provides the driving current to the proportional solenoid and interfaces the control signal. The power supply converts 120 volts AC power to 24 volts DC power which is needed for the card, (see Figure 1).
In
To clarify the different types of amplifiers, the first one to be discussed will be referred to as a Type VT-2000. It is pri marily used for controlling pilot operated proportional pressure relief and pressure reducing valves. Other uses are to control single solenoid two position pilot operated propor tional directional valves as well as proportional pumps and motors , all possessing force solenoids. Amplifier Type VT-2000 being the simplest in internal elec tronic circuitry, also requires the least amount of wiring. Figure 2 is a functional block diagram of the VT-2000. The user should mainly concern himself with how to wire the card and how to use the card adjustments in conjunction with the valve, rather than be overly concerned with the in ternal electronic circuitry of each block. The diagram shows an input and output side where all external wiring takes place. Anything in between these two lines, designated by the dashed lines, is already on the amplifier card. Beginning with the input side; this is where power is supplied and where a command signal must be provided. When supplying power to the card a specific polarity must be observed, meaning the positive lead from the power supply must be connected to the proper terminal on the card as must be the negative lead. If these leads are accidently switched, internal damage to the
For each particular proportional valve there is a specific am plifier card that is needed to operate the valve. The following discussion will be based solely on these amplifier cards.
Figure 1
1
Outputs
6ac
1 22ac
P5
I I
- 309 -
card generally does not occur due to the input being diode protected; however, the card will obviously not be able to operate properly. In order to operate the valve, a low level command signal must be provided on the input side. This is achieved by providing reference voltage terminals +9V, OV, -9V, at the points where either a switch or potentiometer can be added. The potentiometer is preferred more often than the switch because it is an electrical device that can provide an ad justable command signal by simply turning a knob. Looking at the output side, terminals are provided for wiring to the force solenoid. Also, only one force solenoid can be con trolled by the amplifier at one time.
block, which is the matching amplifier (3). This is basically an amplification stage. The fourth block is a summing amplifier (4). This block adds together three signals; one signal from the dither oscillator, a signal from adjustment P1 , and the input signal. The dither oscillator generates a modulating signal in order to minimize solenoid hysteresis. The other signal from P1 is a pilot or bias current setting. The last block is a power or output amplifier (5) which has two basic functions. First, it is responsible for amplifying the signal up to the power level needed to drive the solenoid. Secondly, it provides current feedback to continue stable operation over changes in coil temperature and wiring losses.
INTERNAL CIRCUITRY
As was stated previously, anything between the dashed lines is already on the card. Each block in the diagram represents a specific function. As power is supplied to the card (terminal 24 ac (+), terminal 1 8 ac (-)), the first block it encounters is voltage filtering and regulation (1). Since the supply of the 24V DC is not neces sarily consistently smooth or steady, voltage regulation is used to provide a fixed known level of voltage (designated by terminals 1 0 ac (+9V), 14 ac (OV), and 1 6 ac (-9V)) which is used for the rest of the circuitry. Voltage regulation also provides stability with respect to temperature to keep the card accurate over a wide temperature range: as ambient temperature varies, the set point on the card will not vary. From the?e known levels of voltage referred to earlier as reference voltage terminals, a potentiometer or switch can be wired, providing the required command signal. Looking back at Figure 2 a potentiometer is shown wired to the card. One leg of the potentiometer is connected to terminal 10 ac (+9V), the other leg of the potentiometer is connected to ter minal 14 ac (OV) with the wiper or output of the poten tiometer connected to terminal 12 ac. This provides a com mand signal range from 0 to +9V which can be adjusted by turning the potentiometer. As the signal proceeds from 12 ac, the second block it en counters is called a ramp generator (2). The input command signal goes into the ramp generator and comes out as a linear change with respect to time. This is the generator's sole func tion. The most important thing to remember about the ramp generator is the signal from the generator does not change in magnitude, it reproduces the magnitude of the input at a given time rate. In other words, if the input goes from 0 to 100%, the output goes from 0 to 100% but at a given time rate. Likewise, when the input goes from 100% to 0 the out put goes from 100% to 0 at a given time rate. The ramp generator will not allow the output to move any faster than the ramp adjustment setting. Ramp adjustments will be dis cussed later. The output of the ramp generator then proceeds to the next
AMPLIFIER ADJUSTMENTS
Every amplifier card has a number of adjustments on it that need to be set for proper operation of the valve. These are most often referred to as presets which are actually multi tum potentiometers.
5 sec.
- 310 -
Acceleration, deceleration; and decompression can be achieved through the use of the ramp generator. The given ramp time range for the amplifier card is from 0.1 second minimum to 5 seconds maximum. The maximum 5 second time limit, however, is achievable only by providing a full +9 volt signal to the input of the ramp generator. If a signal is provided lower than +9V, the ramp time will not be achieved in the full 5 seconds as intended. Figure 3 demonstrates this relationship more fully. At 100% signal a maximum ramp time of 5 seconds is achieved. By changing the input signal to 50% and keeping the ramp time set at its maximum value, the ramp time reduces to the change in signal. It also should be mentioned if no ramp time is required, terminals 4 ac and 2 ac can be bridged by either a jumper wire or a switch. By jumping 4 ac and 2 ac the signal bypasses the ramp generator completely. This means the output follows the input, or the valve will re spond directly to the potentiometer setting.
2900 2610
<!:
:::l .5
Q.,
...
f'
.v
200
300
400
500
600
700
800
PRESETS Pl A N D P2
Current (mA)
Figure 4
0 (.1.,
.... .... IJ ...
= Q, = 0
mand signal, as the potentiometer is turned the valve will not build pressure until the point is reached where the signal provides approximately 180 rnA. The signal must first travel through the dead range before the valve responds. In order to boost the input signal to its proper starting point, P1 has to be adjusted to provide approximately 180 rnA signal. In this way, when one first begins to tum a potentiometer, the valve immediately starts to build pressure. (P1 would be set at ap proximately 180 rnA only assuming the lowest set pressure related to flow is about 100 PSI.) To set the maximum pressure of the valve, preset P2 must be used. P2 is a maximum current limitation adjustment, which is accessible on the front face of the card. P2 can be adjusted to limit the command signal, so if the full pressure range for the proportional pressure relief valve in Figure 5 is desired and assuming P1 is set for 180 rnA, P2 would have to be set for its maximum value of 800 rnA. If a lower pres sure setting of the valve is required, P2 can be adjusted ac cordingly (Figure 6). Also, since current is directly related to the pressure setting of the valve, pressure in the system can be adjusted by presets P1 and P2 while reading the pressure gauge at the same time. 180 rnA signal directly corresponds to approximately 100 PSI on the curve just as 800 rnA direc tly corresponds to 2900 PSI. The same holds true for any other limits that are desired. For example, if a particular ap plication calls for a maximum pressure of 2500 PSI and the minimum pressure setting of the valve related to flow is 150 PSI, the lower and upper limits can once again be established by setting P1 and P2. P1 would be adjusted to set the lower 150 PSI limit with P2 being adjusted to set the upper 2500 PSI limit. Also with the use of a potentiometer, the valve would be capable of variable adjustment between 150 to 2500 PSI without exceeding the upper limit. Another thing that must be considered when adjusting P1
Input Signal
The force out of a proportional valve is linear only over a par ticular range (Figure 4). Proportional valves are designed to work over this linear range and anything below the nonlinear point on the curve becomes unpredictable. To overcome this, preset P1 (which is a bias current setting) adds a signal to boost the input signal to that useable linear portion of the curve. This allows the force output of the valve to work only over this useable linear range. Because this amplifier is not exclusively used for proportional pressure relief valves, and because this nonlinear point differs for other components that require the use of this amplifier card, P1 is capable of ad justing a bias current from 0 to 300 rnA. To further demon strate this point, a performance curve for a proportional pressure relief valve is given in Figure 5. From the figure it can be seen that a portion of the curve is called dead range or deadband. Dead range is where the set ting of P1 is of the utmost importance. For example, if P1 is set at zero and a potentiometer is used to provide the com-
- 311 -
and P2 is the fact that P1 adds a signal to boost the input signal; therefore, the setting of P1 adds to the setting of P2. If P1 is set at zero, and P2 is adjusted for some maximum pressure, then P1 is adjusted to its minimum pressure set ting. The maximum pressure setting of the valve will increase by the setting of P1 (see Figure 7); therefore, it is necessary to first establish P1 and then set P2 for its maximum value. This is accomplished by keeping the command signal at zero and setting Pl for the required bias current. P2 can then be set by setting the command signal at 100% and setting the maximum current as desired. The following curves will illus trate these conditions more fully.
Changing the setting of P1 when P2 is already set for its maximum pressure, changes the entire setting of the valve. When P 1 (the bias current) is increased, it can be seen from Figure 7 that the range or span stays the same, but the range is at increased lower and upper limits. The pressure, for example, would increase from a minimum pressure of 100 PSI to a minimum pressure of 200 PSI. If the maximum pressure of the valve was originally set for 2500 PSI, it would also increase 100 PSI so that the final setting would be 2600 PSI.
PRESET P 5
Figure 6 100%
P, P, P,
P,
Preset P S i s the adjustment for the dither oscillator men tioned earlier. PS is preset at the factory and does not need to be adjusted.
HYSTERESIS
For any man-made device there is a certain percentage of error. The amount of error for proportional valves is ex pressed as the hysteresis (%) of the valve and for most good proportional valves does not exceed 6% (3%). Knowing what the hysteresis of the valve is, a direct relationship can be made as to the accuracy of the valve. If the hysteresis of a particular proportional valve is less than 3%, it can be said that the accuracy of the valve is better than 3% error. There are various reasons for hyteresis in proportional valves, but the primary cause is friction, such as solenoid, spool, and poppet friction. For example, hysteresis for a pro portional valve can be defined as the difference in output signal when the input is increased to a set point and then decreased from a higher value to that same set point. Relating this to the spool position of a proportional direc tional valve, hysteresis can be defined as the difference in the spool position when approaching the set point from two dif ferent directions (see Figure 8). The "repeatability" of a proportional valve is another term often referred to when describing the valve's dynamic charac teristics. Repeatability is a measure of exactness with which motion or position can be duplicated. It can also be defined as the error in the output when approaching the set point in the same direction. In other words, if one shifts a propor tional directional valve twice in the same direction, the valve will not return to the exact same position both times. Repeat ability is very often one half of hysteresis and will never be worse than hysteresis . To help reduce hysteresis it was mentioned earlier in the in ternal circuitry section that the dither oscillator provides a modulating signal in order to minimize valve hysteresis. The following curves (Figure 9) of a proportional pressure relief valve demonstrate the difference between a valve with hys teresis and one without.
Command Signal
100%
When P l i s set for its minimum bias current, P 2 can be in creased or decreased to the maximum current desired with out changing the bias current setting. Relating this to the pro portional pressure relief valve, and knowing P2 sets the maximum current level or maximum pressure, the maximum pressure can be increased or decreased without changing the minimum pressure setting of the valve.
Figure 7 100%
Cl)
iO
P, P,
P,
Command Signal
100%
- 312 -
Figure 8 Output
Hysteresis
Ql .. = "' "' Ql ..
(bar PSI
(2001 2900 ( 1 f!O) 26 1 0 ( 1 601 ( 1 401 ( 1 20) ( 1 001 (80) (601 (401 (201 2320 2030 1 740 1450 1 1 60 870 580 290
Input
Q.,
1:?
200
3 00
400
500
600
700
800
-;
(i; .... 0
c Ol
Current (rnA)
quite a substantial difference in pressure settings when a dither signal is excluded. With a dither signal the difference between an increasing pressure setting and decreasing set ting is about 2.5%. Without the dither signal the difference is about 4.5%.
= Q, .... =
Input Signal
Although all electronic amplifiers have this dither feature builtin, the curves clearly demonstrate that there can be
Q.
Dead rang w
A:/'
200 100 300
// /L 1/ /1
500 600
For simple onoff control a single pole double throw switch can be used to provide the required command signal (Figure 10). The switch is shown in the off condition; therefore, the minimum pressure setting of the valve is dependent on Pl. When the switch is thrown to provide the command signal, the valve builds pressure to its maximum limit dependent on the setting of P2, and the time it takes depends on the setting of P3 for ramp up time. When the switch is thrown back to provide zero signal, the valve decreases in pressure depend ent on the setting of P4 which is the ramp down time. This is one of the simplest wiring schemes for achieving a single maximum pressure setting when a controlled time of the set ting is required . The most common wiring scheme to provide a variable com mand signal quickly and conveniently, is through the use of a potentiometer (see Figure 1 1 ) . It was mentioned earlier that a potentiometer provides a variable command signal by simply turning a knob. A potentiometer, when excited by DC or AC voltage, provides a proportional voltage versus displacement relationship. The output signal of the potentiometer is linear
400
700
800
Current (rnA)
- 313 -
Figure 10
- -- -- -- -. --- -- -- -T
14 ac
2ac
:: PS
I _j_ 1 22ac
_j
to the rotation of the potentiometer. As shown in the dia gram, the external potentiometer allows the operator to have full control of the pressure range of the valve as long as P2 is set for its maximum current. Since P2 is in series with the potentiometer, P2 can determine the maximum pressure limit, whereas the potentiometer can be adjusted to whatever pressure is required but not in excess of P2's setting. Also, if the ramp generator is turned off, the operator can control how fast pressure increases or decreases by how fast
he turns the potentiometer. When the ramp generator is on, it does not matter how fast the potentiometer is turned because the ramp generator will allow the signal to reproduce only at the time set. Obviously, one can tum the poten tiometer slower than the ramp setting. This arrangement is very useful in test areas since the potentiometer can be mounted in a remote location away from the test with the op tion of controlling pressure with or without the ramp time. It also should be mentioned that the external potentiometer should have a resistance of no lower than 500 Q or no higher than SOOO Q.
Figure 1 1
c I 6ac
P2
0 :: PS
- 314 -
If, for example, the four potentiometers in the diagram each have a resistance of the total resistance can be calculated from Kirchoffs Law.
5000 Q
------
4 1 RT 5000 Q
R y= 5000 Q 1250 Q 4
The four potentiometers in parallel have a total resistance of which is well above the requi ed r minimum. It 1250 can easily be seen that if more than ten potentiometers are wired in parallel, the minimum of is exceeded.
Q,
500 Q.
500 Q
500 Q
. . . + ------
1 5000 Q lt
1 1 1 1 =- + - +- + . . . RT R, R, RJ
Figure 12
- 315 -
Ten potentiometers wired in parallel each having a resistance of 5000 Q would equal 500 Q, the exact minimum require ment. These three wiring schemes are just a few of the possible schemes that can be applied.
The second type of amplifier which will be discussed is a VT 3000 amplifier card. It is exclusively used to control pilot operated proportional directional control valves and elec tronically controlled hydrostatic transmissions. Amplifier Type VT-3000 basically operates the same as the VT-200 except that it is built to provide a signal to two pro portional force solenoids and has some added internal cir cui try providing additional application uses. Referring to the figure 13, anything between the dashed lines is already on the card. External wiring of switches, poten tiometers, and solenoids is done at the numbered terminals.
Figure 13
P l . P 2 . P3, P4 ""
in ut levels
vsuJ
ramp time
-9v
9v MO
- 316 -
only has one ramp time for setting the speed with which the spool opens and closes. This relates directly to accelerating and decelerating times for the load. Since the signal can be controlled, the valve is controlled as to how fast or slow and how far to open or close. In this way smooth stopping and starting of the load is achieved. These conditions will be discussed later as will typical acceleration and deceleration curves. The output of the ramp generator then proceeds to the next block which is called the function generator (3). The function generator is an added function which compensates for dead band in proportional directional valves. The primary causes for deadband in proportional directional valves can be linked to three sources: 1 . Solenoid friction. 2. Spring bias; springs to hold proportional spools in their center position are under compression and these forces have to be overcome. 3. Spool overlap, which as stated previously, is precisely 1 1 % for all proporticnal spools. To show more fully what the function generator does, the following condition will be considered. If the function gener ator was not included in the amplifier circuitry and a propor tional directional was shifted in both directions, it would take a significant amount of input signal before the valve would produce an output flow in either direction (see Figure 14).
vide the command signal and one turns it, nothing will hap pen until the point is reached where the potentiometer provides enough signal to overcome this amount of dead band. This is obviously not a good condition and the func tion generator compensates for this deadband by abruptly jumping the input signal up to the linear portion of the curve (see Figure 15).
Figure 1 5
... ...
= 0
= Q,
Input
The rest of the card basically operates similar to the VT2000 with block number (4) being the summing unit for add ing the signal from the ramp generator and function gener ator. Block numbers (5) and (6) are the power amplif iers for solenoids A and B. It is important to note that unlike the VT2000, negative and positive voltage (0 to 9V) must be provided in order to shift a 3 position 4-way proportional valve in both directions. In other words, to operate solenoid A, a negative voltage command signal must be provided, and to operate solenoid B a positive voltage command signal must be provided. The inverter stage (7) and diodes (8 and 9) allow for the positive and negative voltage's direction control. 1 . Diode 8 allows positive voltage through. 2. Diode 9 allows positive voltage through. 3. Inverter stage changes negative voltage to positive volt age. When a negative command signal is provided, diode 9 rejects it since it only allows a positive signal through in the direction of the arrow. The inverter changes negative voltage to posi tive voltage allowing it to pass through diode 8 to operate solenoid A. Likewise, when a positive command signal is provided, the inverter changes positive voltage to negative voltage so that diode 8 rejects it and the signal proceeds through diode 9 to operate solenoid B.
Figure 1 4
Output Flow
Input Signal
Dead band
The reasons for this considerable amount of signal being needed are those just mentioned: solenoid friction, spring bias, and spool overlap ( 1 1 %), which together create a significant amount of deadband around zero.
In a more practical sense, if a potentiometer is used to pro-
- 317 -
DC terminal) to a switch (or switches) and connecting the output of the switch to the particular relay terminal (see Figure 16). In series with each relay d1 through d4 is a light emitting diode (LED) indicating when the relay is energized. These are numbered dl through d4 on the front face of the card. Moving to the upper part of the diagram, four adjustable presets (which are accessible on the front of the card) are numbered P1 through P4 and are used to limit the 9V signal. Also accessible on the front of the card is P8 which is used to set the ramp time.
its required solenoid. When relay d4 is de-energized, the LED goes off and the signal decreases to zero. Likewise, when relay d3 is energized, LED d3 comes on and contact d3 con nects to the output of P3 allowing the signal to proceed through the card to its required solenoid. The priority chain continues on respectively with preset P2 corresponding to relay d2 and LED d2. Preset P1 is lowest in priority and corresponds to relay dl and LED dl. The simple wiring scheme in Figure 16 below shows how these presets and relays work in relationship with a 3 posi tion 4-way proportional directional control valve. First, one should notice that a wire is connected from 20 c to 10 c to provide a +9 volts and a wire is connected from 26 ac to 10 a to provide -9 volts. (Remember positive voltage is required to operate solenoid B and negative voltage is required to operate solenoid A). By energizing relay d1, contact dl pulls in sending a signal through the card to solenoid B moving the proportional spool from its center position to a d istance set by P l . In this case P1 can be said to be set to provide +9 volts, thereby allowing the spool to travel its full distance in one direction. By de-energizing relay dl the spool travels back to its center position. When relay d2 is energized con tact d2 pulls in sending a signal to solenoid A moving the spool in the opposite direction, a distance set by P2. Like wise, the spool returns to its center position when relay d2 is de-energized. One must also remember that presets Pl and P2 can be adjusted to limit the 9V value thus limiting the spool stroke. If other settings of the value are required, presets P3 and P4 can be used. Typical wiring schemes showing all the presets in use will be discussed later.
In order to provide the command signal; any one of the relays dl through d4 must be energized. In reference to Figure 1 6 it should be noted that the contacts of relays d1 through d4 are in series just below each preset Pl though P4. As was dis cussed earlier for the VT-2000, when switches or contacts are wired in series, the one having the highest priority (when activated) will always allow the signal to pass through regard less of the other contacts being activated. In this case preset P4 has the highest priority. When relay d4 is energized, LED d4 comes on, and contact d4 breaks from the series wiring sequence and connects with the output of preset P4, thus allowing the signal to proceed to the input of the ramp generator and then through the rest of the card to
PRESETS Pl - P4
Figure 16
P l . P 2 , P 3 , P4 PS PG P7 P8
- 318 -
RAMP
The VT-3000 amplifier card only has one ramp setting (P8) which is usually settable within a range of .03 to 5 seconds. The spool opening and closing time is therefore controlled by the setting of P8 if required. In the example just given, if the ramp time is set for its maximum value of 5 seconds and relay d1 is energized, the signal will increase from 0 to 100% in 5 seconds moving the spool from its center position to its set point in 5 seconds. Likewise, when d 1 is de-energized the signal w decrease from 100% to 0 in 5 seconds and the ill spool will move from its set point back to its center position. If no ramp time is required, relay d5 can be energized which closes contacts d5 by bypassing the ramp generator com pletely, or terminals 14 c and 1 4 a can be bridged with either a switch or jumper wire. If an external time potentiometer is needed, it can be connected to 1 4 a and 1 4 c, but the poten tiometer of the card must be adjusted to its maximum ramp time, so as not to allow the possibility of the external poten tiometer exceeding a time longer than that of the poten tiometer on the card. If, for example, the ramp setting on the card is set for 50% and the external time potentiometer is at its maximum time setting, the signal will take the path of least resistance and the desired time value will not be achieved. It is therefore necessary to keep the ramp setting at its maximum time value when using an external time potentiometer. Also, if a preset is changed in value from 100% signal to a lower value, and the ramp time is held constant, the ramp time
ADJUSTMENT - PS
automatically reduces. When selecting an external time potentiometer the rating of the potentiometer should be 500K Q.
PRESETS 5 , 6 AND 7
Presets 5 and 6 are bias current settings and as with the VT2000, they add a signal to boost the input signal to that use able linear portion of the curve. Unlike the VT-2000, these are already set at the factory for Series 30 cards and do not need to be adjusted. Preset P7 is a zero point, and is also set at the factory needing no adjustment. These three presets are not accessible on the front face of the card.
By energizing relay d6 the changeover contact can be used to provide negative or positive voltage at any of the presets P1 through P4. A typical wiring diagram of this contact in use will be shown later.
CHANGEOVER CONTACT D6
For control systems having analog outputs, terminals 16a and 16 c should be used. Terminal 1 2 c can be used for an input for electrical joysticks. One of the simplest ways to achieve hi-direction for a pro-
ADDITIONAL INPUTS
Figure 17
14c
! J !
!it
I
I I
J:
ll t I
- ----,
---.
Y y1 l
ITl 11
t
P6
P l , P2, P3 , P4 P5
L c""'"
" u l a t or ' _ _ __ __
.._ 't-' ::!:::: !:::: "' ....J ...... :! :!::::!: l::r- P;l
VT-3000-S-30
_j
28
JJ
Typical Wiring Schemes for VT-3000 Amplifier Cards
- 319 -
I I L _ __
portional directional valve and to establish various spoo l positions quickly and conveniently, is through the use of an external potentiometer (Figure 17). By connecting the potentiometer to 20 c for +9 volts, 26 ac for -9 volts, and the wiper to any one of the preset tenninals (in this case it is 10 c for P1) the operator has control of the valve in both directions. P1 would detennine the maximum spool travel in both directions.
mally open, relay 1-CR will latch in, closing contact 1-CR and energizing internal relay d3. This then closes contact d3 allowing the cylinder to accelerate forward to a speed set by preset P3. The cylinder proceeds forward until it closes limit switch LS-3 which in tum energizes relay 3-CR and opens nonnally closed contact 3-CR. Relay 1-CR is de-energized allowing the cylinder to decelerate to a slow speed forward, since the only relay on the card now energized is dl , with its preset P1 set for some minimal value. Once the cylinder reaches limit switch LS-4, relay 4-CR energizes closing con tact 4-CR, energizing relay d4 and allowing the cylinder to accelerate in the reverse direction to a speed set at preset P4. The cylinder proceeds in the reverse direction until it closes limit switch LS-2, which energizes relay 2-CR and drops out relay 4-CR. At the same time relay d2 energizes decelerating the load to a creep speed at a minimal setting of P2. When the cylinder reaches limit switch LS- 1 , the cycle repeats it self. Another important characteristic of the cycle is the ramp set ting. Since there is only one ramp setting, all acceleration and deceleration values are the same. (See the Velocity Vs. Time graph Figure 19). When setting the ramp time for an automatic cycle it generally takes some fine tuning in order to achieve smooth acceleration and deceleration rates.
Figure 1 9
v
LS-1
t One Cycle
- 320 -
LS-1
Figure 1 8
24V
lB
lli
12 12c
- CO
18a
J I
!! 16c
-c_r
VT- 30005-JO
- 321 2LR ov 4- R
Figure 20
14c
VT-3000-S-30
',, 26c.
Power supply
OV
24V
Figure 2 1
t ------
- 322 -
Rapid Retract
From Figure 22, it can be seen that contact d6 is tied directly to the +9 and -9 voltage lines and incorporates a separate terminal enabling it to be wired to any one of the preset ter minals. By energizing relay d6, the contact switches from negative voltage to positive voltage and back again when de energized. The example shown demonstrates a 4-way pro portional directional valve controlling a hydraulic motor and the card is wired to all four presets from the changeover con tacts. It should be fairly obvious that if each preset is ad justed for a different value, four different speeds can be ob tained in either direction, since there would be a different spool position at each preset value. The direction can be changed by use of the changeover contacts. These are just a small fraction of possible wiring schemes which can be ap plied to 4-way proportional directional valves. The wiring scheme to be used is dependent upon the application and the type of cycle to be accomplished.
Figure 22
14c
VT-3000530
='---2
Power supply
ditional board of ramp adjustments. The added relays are in parallel with the relays needed for Pl through P4. Anytime relays dl are energized, contacts d1 pull in, meaning the set point depends on Pl and the ramp time depends on the ramp setting Pl l . If relays d2 are energized contacts d2 pull in, and the set point depends on P2 with the ramp time dependent on the ramp setting Pl2. In other words, the priority chain remains the same for the ramp adjustments as it does for P 1 through P4. Whenever relays d4 are energized, preset P4 and ramp setting P14 will have the highest priority. Since each preset P1 through P4 can be set for a different ramp time, acceleration and deceleration rates can be established separately for each preset. When all presets are de-energized the valve returns to its center position bases on the ramp time setting of (P1 0).
The VT-3006 (Figure 23) is the same type of amplifier card as the VT-3000 amplifier card except it has five ramp set lings (instead of one) which are all accessible on the front face of the card. Looking at the figure it can be seen that an additional board of relays has been added as well as the ad
- 323 -
figure
23
input levels pilot current, sol. pilot current, sol. zero point ramp time
B A
"B"
on
Pl P2 P3 P4
INTERNAL CIRCUITRY
Although block diagram for the VT-5001 through 5004 is the same for all, there are some minor differences (not shown) between each card type. It is, therefore, important to use the correct card for a particular valve . There are basically two major differences between the Series 3000 and the Series 5000 card now being presented. The Series 5000 has cable break detection and it has some ad ditional circuitry to compensate for the feedback on the valves (see Figure 24).
. ...
. ......
1:::
, I;
- 324 -
Figure 24
Inputs I
(i
1
I I 30c
------1----..._,..,,.,---r.!.
M y
I I
Zero point Cable break LED
I
I I I I I
I nductive positional transducer
)------+---i
Power supply
'it"' 1\op.ll!lilor .
...... .,, . .. ., . ., .,, . .,
.,
plifier, oscillator, and demodulator are all needed to ensure the proper positioning of the orifice or spool. The output of the ramp generator serves as the input to the proportional, integral, differential regulator in which a com parison is made to the actual position. This is made possible by the oscillator which is a separate circuit within the ampli fier, generating a signal at a definite frequency within desired limits to the LVDT on the particular valve. The LVDT then sends a signal back to the amplifier, corresponding to the position of the orifice or spool The signal is then received by the demodulator which recovers the intelligence from the signal and delivers a voltage signal proportional to the posi tion of the orifice or spool through the matching amplifier to the P.I.D. regulator. At this point, a comparison is made in the P. I.D. as was previously mentioned resulting in a cor rected signal back to the solenoid maintaining a very accur ate orifice or spool setting. The matching amplifier (which is preset at the factory) limits the stroke of the spool, and in fluences both the accuracy and stability of the valve. The cable break detector monitors the lines to the LVDT and is connected internally to the current regulator. If feedback is lost because of a break in a wire or due to an unconnected wire, the cable break detector switches the current regulator off, which in tum cuts off power to the solenoid. A light emit ting diode (LED) on the front plate of the amplifier will tum on at the same time indicating a cable break. In the case of the direct operated directional valve and flow control valve
The presets and relays can be used the same as they are with the VT-3000. The only significant difference is that unlike the VT-3000 the command signal must be negative in order to energize solenoid B and positive to energize solenoid A. If these solenoid leads are wired incorrectly the spool moves hard over and the valve fully opens. Starting with the added circuitry for the feedback, there are four new blocks presented. A P. I.D. regulator, matching am-
- 325 -
Figure 25
= j -. =-- , ;>- Uo
. .
1 eo
5001<.0 ':
solenoid B
: ;, \ . Q\
solenoid A
14 0
")
"J ' .
The card contains: 1 . Voltage regulation and filtering 2. Ramp generator 3. Function generator 4. Summing unit 5. P.I.D. regulator 6. Current regulator
with feedback, a broken cable results in both valves falling in a closed position. When feedback is lost to the direct operated relief valve, it fails in an open condition preventing any pressure to build. The Series 5000, as with the 2000 and 3000 Series, has:
1. 2. 3. 4.
7. Power amplifier 8. Oscillator 9. Demodulator 1 0 . Matching amplifier 1 1 . Relays with LEOs 12. Presets
ADJ U STMENTS
The only adjustments on the front face of the amplifier are for setting the ramp up and down times and one switch for turning the ramp off.
Voltage regulation and filtering. Current regulator for stabilizing the output. Power amplifier. Ramp generator with separate ramp up and down times, for use in setting spool or orifice opening and closing times, or for setting the pressure controls' in crease or decrease pressure times.
- 326 -
wired properly. The wiring sequence is as follows: pin number 1 on the plug connects to terminal 20 c, pin number 2 on the plug con nects to terminal 1 4 c on the card, and pin ( ) on the plug connects to terminal 22 c, not to a chasis ground (reference Figure 24).
Electronic amplifier Type VT-5000 Figure 26 is used for controlling proportional variable volume vane pumps. The amplifier is unique in the respect that it incorporates a circuit to control a stroke controlled solenoid and a circuit to control a force solenoid. Relating this to the proportional vane pump, the top half of the amplifier provides a signal to the main orifice which has the stroke controlled solenoid and the bot tom half provides a signal to the relief valve which has the force solenoid.
INTERNAL CIRCUITRY
The top half of the circuit contains: 1. 2. 3. 4. 5. 6. 7. Proportional, integral, differential regulator Current regulator Pulse width generator Power amplifier Oscillator, for feeding the LVDT Demodulator, for generating the feedback signal Matching amplifier, for limiting the stroke of the main orifice
Figure 26
/4V
ov
- 327 -
The amplifier also contains voltage regulation and filtering, and a ramp generator. Reference voltage terminals provided from the voltage regulation and filtering block allow for potentiometers to provide the required command signal to operate solenoid A and B. The ramp generator is separated from both circuits, and is provided with an input and output terminal where it can be wired for either setting the ramp times for the main orifice or the ramp times of the relief valve.
have its wiper connected directly to the 9 volt input terminal 10 a. Variable adjustment of the pump compensator would then be achievable. If it is desirable to use the ramp generator for both solenoid A and B, a relay may be used to switch back and forth to operate the ramp generator as desired for a particular solenoid, or a second card with multiple ramps can be incorporated.
PRESETS
P3 is an adjustable preset which is used to set the maximum current to the main orifice, and is accessible on the front face of the card. Although the orifice still can be remotely ad justed by a potentiometer, it will never exceed this value P3. Presets P4 and P5 function in the same manner as do P1 and P2 for the VT-2000 amplifier. P4 is a minimum current setting and is used to establish the minimum pressure setting of the valve or the minimum pressure at which the pump compensates. P5 is a maximum current setting and is used to establish the maximum pressure setting of the valve or the pressure at which the pump compensates. Like the VT2000, the minimum pressure setting of the valve is additive to the maximum pressure setting, therefore, P4 should always be set first.
On the front face of the VT-3000 Series cards there are three sets of test points (Figure 27). One set is for reading the command signal and the other two are for reading coil cur rent, solenoid B and A respectively. Placing a voltmeter across the two command test points enables one to read the command signal just after the sum ming amplifier. (Command test points are marked BU-1 in the diagram.) If it appears an internal relay may not be working properly, the command test points can be used. For example, by energizing each particular internal relay on the card and measuring the voltage across the command test points, one can find out which relay on the card is not work ing. Coil current test points are marked BU-2 in the diagram for solenoid B and BU-3 for solenoid A. Since 1 rnA = 1 mV (1 rna x 1 Q 1 mV) the signal actually being measured is voltage, therefore, when using the coil current test points, a voltmeter should also be used. If for example the voltmeter reads .5 volts this is directly proportional to 500 rnA. A high impedance voltmeter is needed to measure the range of less than 1 volt and it is generally best to use a digital voltmeter.
=
There are two ramp adjustments which can be used to separately set how fast the orifice opens and closes, or they can be used to separately set how fast the proportional pressure relief valve increases and decreases pressure. The ramp generator can be used for either solenoid A or B, but cannot be used for both solenoid A and B at the same time.
RAMP ADJUSTMENTS
ramp generator is separated from both circuits, ex ternal wiring must be done to include the generator for whatever solenoid it is intended to be used with. If the ramp generator is intended to be used with solenoid A (main flow orifice) and remote control is desired for both solenoid A and B by the use of two potentiometers, the potentiometer that operates the main flow orifice (solenoid A) must be con nected from the wiper of the potentiometer to the 9 volt input terminal of the ramp generator. The output of the ramp generator is 6 volts and this is designated by a 6 volt output terminal which must be connected to the 6 volt input ter minal 2 a. The main flow orifice (solenoid A) would then be capable of variable adjustment plus the ramp generator could be set to control orifice opening and closing times. The other potentiometer used to control solenoid B, would
For VT-5000 Series cards two sets of test points are ac cessible on the front face of the card for measuring the com mand signal and the feedback signal.
SHIELDING
Since the input signals for all VT amplifiers ar.e low current signals they are subject to radio frequency interference. The most common way to alleviate this problem is to use shielded wire. Shielded wire is a combination of wire(s) that has a protective guard around it which helps to eliminate the
- 328 -
intrusion of other outside signals. It is usually used when the potentiometer is mounted a few feet from the card, or if the card is mounted in a console and the potentiometer is mounted on top of the console with other electrical devices in the console (such as relays or anything that can produce magnetic or electrostatic fields). Shielded wire should also be used for wiring the LVDT on stroke controlled solenoids. It is important to remember when wiring with shielded wire, that it should only be grounded on one end. If both ends of the shielded wire are grounded, the shield has no effect. In fact, it may even pick up interference making the problem worse.
supply used to provide power to the amplifier is a 24 volt DC 10% regulated power supply. Although unregulated power supplies may also be used, one must be aware of the problems that can occur. The more an unregulated power supply is loaded, the greater the voltage drop is. Likewise, the output voltage is proportional to the input voltage, which can also affect the variable being controlled. Another problem with unregulated power supplies is if 24 volts are required for a load condition, once the load is removed a variation in voltage occurs which can cause the 24 volts to go beyond the maximum 27 volt limit, may times leading to the destruction of the card. With the regulated power supply, the output stays at about 24 volts DC even with changes in load. It is, therefore, more desirable to use the regulated power supply. It also should be mentioned that if more than one amplif is to be used with one power supply, one must ier carefully check the rating of the power supply to ensure that it is large enough to handle the power capacity of the am plifiers.
CARD HOLDER
POWER SUPPLIES
When selecting a power supply for an amplifier card the ab solute limits should not drop below a minimum of 22 volts or a maximum of 27 volts. The most common type of power
Every amplifier card (with the exception of one type) has a 32 pin connector permanently attached to the end of it. With the connector being permanently attached, the card can be plugged directly into a card holder which possesses two rows of terminals for wiring. Each row contains 16 terminal con nections with one row marked "a" and the other row marked "c", each row being evenly numbered from 2 to 32. This allows the user to do all the wiring directly to the card holder so that anytime a card has to be replaced it can be done without rewiring. Consequently, if a terminal is marked with ac, either a or c both can be used for a wiring connection. If, however, two terminals are labeled for one connection, both terminals must be used. This is important because each ter minal has a limited current carrying ability. If a different card is intended to be used with a previously
- 329 -
wired card holder, one must make sure the necessary wiring changes are made, as terminal connections for different am plifier cards may not directly correspond to each other. Not only does the card plug directly into the card holder but there are guide rails as well as two fastening screws to hold the card firmly in place.
fashion when mounting in a console. The rack is made with divisions, allowing for the cards to be equally spaced when required.
If a number of amplifier cards are required, rather than mounting each amplifier card to an individual card holder, a card rack can be used which is capable of holding a number of amplifier cards in one frame. All wiring can then take place at the back of the card rack to wire wrapped terminal con nections as needed, this eliminating an excess of terminal connections as well as keeping the cards in a neat orderly
For conveniently testing solenoid current, an ammeter box which has a scale from 0 to 1 .5 amps can be used. It has a special adapter plug enabling it to be quickly sandwiched be tween the solenoid and solenoid plug. Since the plug can only be hooked up one way it also incorporates a polarity button so that current can be measured for both solenoids for 4-way proportional directional valves. The ammeter test box is also effective during startup and trouble shooting to ensure that power is being supplied to the solenoid or solenoids.
- 330 -
w o = } w
=
The spring constant for a hydraulic system can be directly related to the oil volume trapped between the 4-way propor tional valve and the actuator. The moving mass is the weight of the total load, plus the weight of the oil, divided by gravity. Gravity = 32.2 ft./s2
The natural frequency of a hydraulic system is expressed in ' ' rlz: It Is aependent oh me mass ana me' Otl 'volurrie trapped between the valve and the actuator. With this information one can determine how fast a load can be accelerated and decelerated without causing instability and subsequent dam age to the system. To clearly demonstrate this point we wil l first look at a simple system, which has a weight attached to a spring. The natural frequency of the system is dependent on the spring constant and the mass.
This frequency can be mathematically calculated and in ef fect tells us how fast this weight can be moved back and forth without hav the weight directly opposing the input to ing the spring. For example, the input to the spring-mass system could be someone's hand moving the spring-mass system up and down a certain distance (Figure 1). As long as the spring is moved much more slowly than the natural frequency of the total spring-mass system, the weight will follow the move ment of the spring. There will be very little difference be tween the movement of the spring and weight. The faster the input or hand movement to the spring, the more the weight lags behind. If the input to the spring is at the same frequency of the total spring-mass system, as one moves his hand (the spring-mass system) down, the weight moves up. Likewise, as his hand moves up, the weight moves down. The weight would be in direct opposition to the movement of the spring. This results in the system performing a function opposite of what is required. This is called instability or resonance. To put this in perspective with regard to a hydraulic system, the natural frequency can be calculated (as previously men tioned) and the factor which determines instability is the ac celeration and deceleration time. Trying to accelerate and decelerate high inertial loads too quickly, can cause the cylin der or motor to be unstable. This also creates shock waves in the plumbing, which leads to external system leakage. It iS.OO$sible.to increas.e the.SOQfM'O.}-"UISn{ Oll.111:I uy :'S57Sli::IT keeping the valve as dose to the actuator as possible, thus reducing the oil volume trapped between them. This wiU allow higher acceleration and deceleration rates due to a stiffer spring. If. however too high of an accelerati n is o chosen, the actuator will have an irregular movement, re gardless of the higher natural frequency. If the natural fre quency Is too low, the system will oscillate.
,
Figure 1
Figure 2
- 331 -
Now let us consider how we calculate the natural frequency of a differential cylinder and how we then determine the ac celeration time. The first thing that must be established is the spring con slant. The designer must be cautious when the spring con slant is at its minimum value, which means the natural frequency is at its lowest value. This is the worst case of the spring constant and one must design around it.
By substitution:
(3
Vo
_L
Vo
t::.S x A.2
From F = -Kx: 1::. L
Cm,. must be established. Cm,. however, is related to some distance of the cylinder travel. A formula to calculate this distance has been developed for differential cylinders. The origin of this formula is given below:
In order to determine the distance at which the spring con slant is at its minimum value, the maximum value was first established by determining the spring constant when the cylinder was first fully retracted and then fully extended. When the cylinder is fully retracted the bulk modulus formula be applied, (5 = 0).
A.' x{J
---
= -- =
t::.S
Vo
A.2
fJ
Vo
can
(3
Vo x 1::. P t::. V
The bulk modulus formula dictates the amount of pressure change for a given compression (or decompression). This pressure change is created by the acceleration forces (F rnA).
=
Vo t::. P t::.V Vo Change in pressure (lb/in 2) Change in volume (in') Original volume (in3) Bulk modulus (in/lb2)
c Bulk Modulus Formula: The bulk modulus of a fluid is a measure of the change in volume which occurs when the pressure on the fluid is changed. The magnitude depends on the bulk modulus of the fluid, the original volume and the amount of pressure change.
(3
Pipe volume blind end of cylinder (io3) Area of pipe or tube (in2) Length of pipe or tube between valve & actuator on blind end (in) A.2
X
{J
vl
The volume in the cylinder, the bulk modulus, and the volume between the valve and actuator on the rod end side must also be considered since the proportional valve meters both in and out.
t::.P -
1::. L
--
A.
v.
t::.S xA. Change in load force Change in stroke Area of blind end
V(cyl) Cl
A. x S A;
X
{J
maz
vl v. A. s L2 cl
mcu
_ _
Pipe volume rod end of cylinder (in3) Effective area of rod end (in2) Stroke (in) Length of pipe between valve and actuator on rod end (in) Constant when fully retracted
- 332 -
Likewise, when the cylinder is fully extended, the constant is defined as:
VJ + (A.
d)=V,
V. +A,(S -d) = V1
cl
,....
v, V1
Oil volume on blind end side (in') Oll volume on rod end side (ln3)
The d istance at which the spring constant is at a minimum was then derived from:
The natural frequency for the d ifferential cylinder would then be:
de _ 0 ds -
C' = 0
w.
(A. x S) +V.
d=
VA!
1
- .YL VA:J
1
VA.
VA:
w.
As calculated above "w." is the natural frequency in radians per second (rad./sec). From a theoretical view "w." can now be used to determine the time needed for acceleration. From experience (Figure 4), however, we must consider other capacitances of the system. (e.g. hoses. mechanical com ponents, etc.) As proven by application examples, we find that the useable acceleration is better estimated by dividing the calculated natural frequency by 3. Naturally, Ihis is a sim plified estimate which has been proven to give ample ac curacy for most systems. This simplification avoids a com plex mathematical analysis, which would require variables which are difficult, If not impossible to determine. Therefore; to calculate the useable acceleration:
.9 e u
; (rad./sec.)
c.....
To obtain the natural frequency of the system in hertz (hz) we must divide by 2n.
==
2n
(bz)
- 333 -
figure 4
and other dampening factors. ror vertical load.:; we must also overcome the weight of the load For extremely low levels of force and therefore low levels o l acceleration, the incoming force has a magnitude much lower than the compressive spring force of the system's natural frequency. For these conditions the final velocity is predictable based solely on the low acceleration rate and the desired change In veloc ity. If, however, we attempt to pro v more and more i put force, i order to accelerate the ide n n mass faster and faster, we reach a point where the spring (system's natural frequency) cannot transmit this force. In other words, as the input force i increased, more of this s force is used in compression of the spring while a limited maximum force is transmitted through the spring to cause acceleration. For maximum cycle rate from the system at hand, we try to supply sufficient force to accelerate the mass without supplying add itional forces which only excite the natural frequency of the system (compress the spring). The ideal maximum accelerati n is achieved when the extra force o absorbed by the spring can be quickly dampened by the !ric tiona! forces (dampening factors of the system). If the spring n forces are excessive when compared to dampeni g forces, an unstable oscillation is created.
Likewise; from ''w" (rad/sec) we can also find the time constant "T' This is the time period required for one oscillation.
1 = - (sec.)
w
As described in the following text, the time required for ac celeralion is based on this time constant. Generally, for stable acceleration, the time allowed must be a minimum of 4 to 6 times the time period for one oscillation. The mechanics involved are better described n Figure 5. i
Figure 6
T. T
Time allowed for acceleration (Figure 6) Time period for one oscillation
/ tan a = a
\ :
I / /
=
I
1 I
tan = a. = T
v Tb
Figure 5
6-T -- Time In reference to the graphic analysis of the maximum ac celeration (Figure 6), the lim iting acceleration is based on a time constant as derived from the following formula:
I II l l
During the acceleration of any mechanical system (Figure 5) the available force input is split into three parts. First a per centage of the force is used to cause the actual accelerati n o mA). Second. a percentage of the force goes toward (F compressing the natural frequency of the system (F = Kx). Finally, some force is used In overcoming frictional forces
=
V, Vd e T/T
Actual velocity Desired velocity Irrational number = 2. 72 "" Time constant based on number of time periods
=
- 334 -
a) T b) T
L, L1
Length of pipe on blind end = 46.5" = Length of pipe on rod end = 38.75 "
This formula shows that during the first ume period the maximum velocity achievable is 63% of the desired final velocity. During the second time period the velocity reaches 86% of the desired, the third, fourth, fifth and sixth time period are 95, 97, 99 and 99+% respectively. By allowing six time periods for acceleration a smooth ex ponential increase to final velocity is achieved. If only four time periods are provided for acceleration, there Is a critically dampened oscillation which occurs prior to achieving the final velocity. With less than four time periods an unstable oscillation Is created which typically cannot be tolerated. It is interesting to note that it does not matter what the ac celeration rate is, the mechanical system always reaches 63% of the desired velocity in the first time period. Likewise, It achieves a stable constant velocity in the sixth time period.
Since the following information is known, and as was stated earlier, by designing arounded Cm "d" can be determined (Figure 7):
Figure 7
On the practical side, this nformation is important when i selecting the system pressure, and it is necessary when establishing the maximum pump flow. These considerations will be dealt with in the following examf>le. In the actual system, however, the maximum acceleration is adjusted by starting with maximum ramp time. During machine operation the ramp time is gradually de creased until the instability point is reached. By adjusting the
ramp time to the point just before instability (approximately six time constants) maximum acceleration and therefore maximum production can be achieved without shock.
A, d
=
A,J 1
v.
;;:;
+
IAi
YL
n At this poi t, therefore, It is best to look at a conventional application, where a proportional d irectional valve is used to accelerate a load to a constant velocity and decelerate to a stop, then retract n the same manner to start the cycle over i again. Also, assuming the amplifier used has one ramp set ling, the acceleration and deceleration times will be the same.
Parameters known: The application requires that a 1000 lb. horizontal load be i moved n 1 second a distance of 30 inches and the cylinder size is 11/2" bore, by 1" rod.
rt X
VA.
{A.
(. 62)1
11
46.5 ln.
= 14.04 inJ V.
=
The natural frequency must be calculated first so that the time to accelerate can be determined, and from this the maximum velocity can be determined.
.30 in'
38. 75 in.
= 1 1 . 7 inl
A.
A. S {J
1000lbs. 1.76 in1 .98 in1 30 in. 2.0 x 10$ Jb/in1 3/4" 0.0. x .065"
(.98in' d
/(.98 in1)'
1 +
30ln) + l l . 7 1n'
14.04in '
) 6 ln1P (1.7
Tube size
)t.76 in1
- 335 -
20 in
wo =
---
A.' X
V, x M
A/ X
V, x M
This, however, only determines the time in which the am plitude (velocity) reaches about 63% of its desired final value as was mentioned previously. The acceleration time is proportional to the final desired speed; therefore, a factor or 6 x is used to allow for an acceleration stabilizing time. Using this factor of 6 for a proportional valve system has proven that this time for acceleration and deceleration lies outside the unstable region. Therefore, the acceleration stabilizing time would be:
V, = V. + A. (S - d) = 1 1 .7 ln3 + . 98 In' (30 in - 20 in) = 1 1 . 7 ln 3 + 9.8 ln3 = 2 1 .50 ln3 in ft lbs ( 1 . 7 6 in2)1 x 2.0 x 1 0' - x 32.2 -x 12sec' ft in1
-------
T. =6 x T
From this acceleration time, the maximum velocity can be determined in terms of stroke. From V acceleration rate, acceleration force, acceleration pressure and the required flow rate can then be determined (Figure 8).
m.,
---- -- -- -- - +
Figure 8
in ft lbs (.98 in1)1 x 2.0 x l05-x 3 2 . 2 - x 1 2 -ft in1 sec1 2 1 .05 ln3 x 1000 lbs + 3512
wo =
(sec)'
4840
(sec)'
radians wo = 9 1 . 4 -- second
T
V
I
_ _ _ _
....
.....
The useable acceleration lies at about one third of the natural frequency
S = -- + -- + Vrn x (T - 2I.) 2 2
mo
v ...
, =
---
(I - I,)
V
The acceleration time can then be calculated,
in sec in = 3 7 . 5- x 60-= 2250min min sec l .O - .20 3 7 . 5 in/sec .20 sec 1 8 7 in sec' 1 5.6 ft or ---- sec2
30 in
T = 1/w
Therefore:
= rnu
- 336 -
F = ma = - a = g
485 lbs
Frictional Force:
580 lb + 485 1b
1065 1bs
Ab
605 PSI
F, A,
1085 PSI
wo = wo
Jf
Q.
....
x A.
C I
= The natural frequency Spring constant of the oil Moment of Inertia of the mass
231
NOTE: Since the mass moment of inertia for rotary move 2250 ( . 982) _ ....;. _ __ _ _ = lO.O GPM 231
ment depends on the object being rotated, an example for one particular application will be shown. The effect of the proportional valve being mounted a substantial distance from the motor will also be shown In this example.
Q,
__ ,;,__ ____;_
x A.
231
Since the cylinder has an area rati close to 2:1, the valve o selected should also have a spool area ratio of 2:1. From the calculations that will be shown later n the text, the pressure i drops can be determined and the valve can be selected. If the valve were moved closer to the cylinder, and the natural frequency would be recalculated, It could be seen that the natural frequency would increase. This would then allow for higher acceleration and deceleration rates, thus allowing for a faster cycle rate. This is shown in the following example. It also should be mentioned that if pump flow was determined without considering the accelerating time, the required one second cycle time would not be achieved.
Figure 10
- 337 -
In a molding machine, the movement of prepared molding boxes to the molding line Is carried out by a proportional directional valve operating a hydraulic motor which operates a carriage having a specific gear rat o It is desired to move a . load weighing 8100 lbs to a linear velocity of; V 3.28 ft/s and then stop within 1.5 ft . Therefore the required ac
i = .
I, W = 81001bs r = 2.3 in or .2 ft xr I,
= ---
V1
.-!!.._
8100 Jbs.
a
I, = 2.1
=
lb-ft sec2
Ge r R tio
38 z2 - = Z, 17
=
Displacement of motor 6. 7 in3/rev Desired speed of motor 272 RPM Tube inside diameter = 1/2" 32 ft. Tube length
= =
wo=
wo=
ff
C, +C, WO =
2x 6.7l n 2xn wo = 14.9 sec wo 14.9 w =-= 3 3
x 2.0 x to lb/ln2
--
C,
lb-ft
in 12ft sec2
V, D = p I, =
Trapped oil volume per side (In 3) Volume of the motor (in3) 2.0 X 105 lb/in1 Mass moment of inertia
__,..
4.96 sec-'
Tb
.202
1.21 sec
V, =
--
x393 in +
Acceleration Rate
a=
v.... Tb
2.7 1 ft sec1
80.4 in3
It was stated previously that the requi ed acceleration was to r be 3.56 ftls2 The calculations show that a maxtmum ac
- 338 -
celeration of 2.71 ft/s1 is all that is available if smooth run ning is to be achieved. In order to achieve a higher ac celeration, the natural frequency of the system must be n i
creased.
can
With the reduced oil volume between the motor and the valve, a recalculated acceleration rate of 7.47 ftis1 now allows the load to be accelerated at 3.56 ft/s1 without the system going into i stability. n Calculation of Natural Frequency in Hydraulic Cylinders Double Rod Cylinders
Figure 1 1
(.5 ln)1 4
x 421n
6. 7 ln3 2 2.0x 10 ib S - .... = Bulk modulus of the oU - - ...:.. ln1 = Effective area of the cylinder (ln)1 Stroke of the cylinder (In) = Trapped total oil volume (lnP = Mass = w/g = lb/32.2 ft/s1 = Trapped oil volume in pipeline per cylinder side (in3)
=
wo=
wo =
(sec) '
Achievable Acceleration
=3
wo
40.9
= --
= 13.65 sec
1 T=-=
w
1 13.65 sec
= .073 sec
A double rod cylinder is at its mimmum frequency when it is in midstroke, S/2 (Figure 1 1 ).
Acceleration nme
T. = T x 6 = .439sec
Acceleration Rate
a=
T.
=7.47 ft/sec1
- 339 -
seconds, the acceleration rate was 15.6 ft/s1 and the velocity was 3.2 ft/s. The accelerating/time curve (Figure 12) shows ill that a suitable acceleration w be realized In a time of .20 seconds to obtain a velocity of 3.2 ft/s, proving that the calculations completed e<rliPr are correct. If, however, we ar bttrarily pick a velocity and assume we can accelerate in a particular time period, it can also be seen from the curves that uniform acceleration will not be achieved. For example if it Is desired to accelerate at 9.8 ft/s2 In under .25 seconds to a velocity of 3.3 ft/s, the desired velocity will not be achieved. The curve also shows that if a very low acceler ation rate is desired. a very long acceleration time Is required. This can be established by the ramp setting on the amplifier. Ramp settings range from .03 seconds to 5 seconds, which is more than sufficient for setting acceleration and de celeration rates.
,
v1
2 x 187 ln/s2
4.0 in or .33 ft
When these values are graphically analyzed, linear acceler ation is assumed (see Figure 13). This distance can also be used as a starting point as to where limit switches or proximity switches should be set. These switches are the electrical devices that are physically activated by the cylinder when the acceleration or deceleration point Is reached; therefore it is desirable to set them as close to the actual deceleration point as possible.
Figure 1 2 Deceleration and Acceleration Time for Constant Acceleration 1.15 1.10 1.05 1.00 0.95 0.90 0.85 0.80 0.75 0.70 0.65 o.6o 0.55 o.5o 0.45 o.4o o.35 0.30 o.25 o.2o Figure 1 3 Deceleration and Acceleration Distance for Constant Acceleration (Deceleration) t[sec.]
I I
1.44 1.38 1.31 1.25 1.18 1.11 1.05 .98 .92 .85 .79 .72 .65 .60 .52 .46 .39 .33 .26 .2o .13
t s[] I
I I
I 1 .07
. -
3.3 9.8 45.9 32.8 1 8.7 52.5 39.3 6.5 13.1 26.2 To
istanu the linear acceler determine the accelen:tion d ation distance curve (Figure 13) may be used. Referring back to the previous example, the accelerati n distance is: o
- 340 -
VALVE ANALYSIS
The calculations for the natural frequency of the system is only part of the design procedure that must be considered. In actuality, the natural frequency calculations may only need to be considered if a fast cycle time must be predicted in the design stage. When accuracy is the prime consideration, such as slow and smooth movement of a load, the natural frequency calculations may be considered only on an estimated basis. The following information will be in regard to the two main types of proportional spools ( 1 : 1 and 2 : 1 spools) and the ef fects they have on overrunning loads and resistive loads. From this information a precise analogy may be made as to the proper selection of the valve. This is the final design procedure when considering a proportional valve, whether the natural frequency is calculated or estimated. The calculations that follow have been worked through step by step to show the designer their origin . The resulting for mulas have been charted at the end of this section to provide an easy reference guide for the user.
Figure 1 P,
Figure 2
OVERRUNNING LOADS
Systems requiring a 2:1 cylinder should use a spool with a 2:1 area ratio. It was mentioned in Chapter 7 that a 2:1 spool is machined to give half the flow area on one land as compared to the other land. To further clarify this point, let us mathematically approach the reasoning behind why a 2:1 spool should be used with a 2:1 cylinder. All proportional spools have the ability to meter-in and meter-out . Because of this orifice function, the equation for flow through an orifice applies (Figure 1 ) .
Q,
Q,
> <
,, r
b.P,
,,
Al 2 A2
X
For a 2:1 cylinder with a 2 : 1 spool Q, double of Q,'s value (Figure 2).
will always be
Where Q c A b.P
Flow across the orifice (GPM) Discharge coefficient Area of the orifice (in') Pressure drop across the orifice (lb/in')
CA fi;P
A, 2 x A2t or A, = 2
Since there are two orifices
At first glance, it may seem that extensive calculations would have to be done to determine the pressure drop across the valve; however, considering the load conditions of the system the calculations become rather easy. The first con dition that can be satisfied is the orifice equation . This will be satisfied for a 2:1 spool and then for a 1 : 1 spool to show the adverse effects they cause when they are used with 2:1 cylinders.
Q, CA , Jf;P: Q, = CA,;-;;p;=
A, A, =- or 2A, = A, 2
- 341 -
Therefore:
4). This relates di ectly to the method used to determne the r i pressure drops across the valve as was previously men tioned.
Figure 4
The pressure drop will be fairly equal on both sides of the valve, giving good controllability for 2:1 cylinders.
figure 3
' Q,
>< ><
1500 psi
Based on Newton's Law a force balance must exist at con stant velocity. If we let "F" represent the total net load (Assumi g no friction F = W in this example) we can write: n
P,A. + F = P3A, PJ =
---
P1A1 + F A,
I9J % Q, :Lj
with a
tJ>,
=
l1P,
P3; assuming P. = 0
i When usng a 2:1 cylinder with a 1:1 spool area ratio (Figure 3), .!lP, is four times greater than 6P1. This can cause con siderable problems if the required backpressure on the rod end of the cylinder must be greater than 1/4 of system pressure. A vacuum can be created since the blind end of the cylinder will not completely fill with oil. To see this i more n detail we will consider a condition where there is a 1000 lb. overrunning load and a 1:1 spool with a 2:1 cylinder (Figure
,
Likewise the Pressure drops; (Based on P, and PJ pressures), must also satisfy the orifice equation; which for a 1:1 spool is :
l1P, l1P,
- 342 -
From the orifice calculation completed previ usly for 2:1 o spools
tlP, . T
For the example Problem (Figure 4):
L2QJ = tlP,
By substitution; and solving for P1 the formula becomes:
1500 PSI [15 GPM] 1000 in2 ] 30 GPM 1.66 P, 3.14in' r!5GPMJ 1.66 in1 [30 GPMJ
+
lbs
For the example problem (Figure 4): Note: The minus sign indicate a vacuum would have to be created on the blind side of the cylinder. Since P. 1500 PSI the maximum tlP,an be is:
The above calculation show that to satisfy the flow balance AP, would have to be: tl
15 GPM12 1500 [2 x30 GPM] 1000 in1 [ 1.6 -- --1 -- -- --61 Pl = -- 3.14in-- -- --+ [2x15GP 1.66 in1 L 30 GPMJ P, =309PSI
lbs The cylinder does not pull a vacuum.
Since tlP,
p _ ....:__ tl 2 ___:_ _
lbs
tlP, =PP-P>
- 343 -
overrunning and from keeping the system from creating a vacuum. With a total pressure drop across the valve of 2373 PSI, however, the spool stroke would still have to be con siderably limi ed. t Refering to the performance curve for the valve, at 70% con trol current and 30 GPM the total pressure drop across the valve is 1450 PSI (Figure 5). The calculated pressure drop was 2373 PSI. This means, to obtain the 30 GPM flow re quirement at a 2373 PSI total pressure drop, control current would have to be limited to much less than 70%. Since a small orifice is required at this considerably high t.P, very lit tie of the spool stroke would be used. Also the resolution of the valve at this high t.P will not be as good as if it were n i the range of 1450 PSI and below, at the required flow rate. The load should be counterbalanced. This will be discussed later in this text.
Flgure6
Figure 5
G4'M Ilfmml eo 11o:n ao mn 00 llll lO 1161 0 50 /0 12641
Higher 6P's
I / 7 7/ I/ v / / V' / 7 /v v v v P __ 1 // v- _ /
o /0 60 ,;o CONfROl. CURRENT f11ol 00 00 100
For a 1: 1 valve . . .
11191
lO Ul)t 10 401
/b v L/'.
22.5 GPM nominal at 150 psi across valve lt.p 150psidrop 26p 300 psi drop 36p 450psidrop 46p 1450 psi drop 5t.p 725 psi drop
=
flow
Likewise, for 2:1 valves with resistive load the formula is:
RESISTIVE LOADS
Now that the conditions for 1:1 and 2:1 valves have been satisfied for overrunning loads, we will look at how and 2:1 valves are affected by a resistive load (Figure 6).
1:1
A ' 1 Q ] .1 A, j [2 x Q + A.
lbs
F pp - -
Using the same parameters as before for a 2: l valve wilh a resistive load:
000 1500 PSI - 13.141n1 Jr 30 GPM ] 1.66 tn1 U2){15) GP 3.14 in1
+
P,
P,=729 PSI
.t.P,
1500 - 729
The total pressure drop across the valve is 1548 PSI. To ob tain this 1548 PSI pressure drop, and to use the maximum be selected from the operating curves. It is important to remember, that each direction and load condition will in
possible spool stroke, the optimum valve size would have to
mula for a 1:1 valve is used. The parameters remain the same except for the cylinder area ratio.
For example: A.= 3.14 ln1 and A.= 2.35 in2 1500 PSI---
dicate an optimum valve size. The final selection of the valve will be the best compromise of all possible operating con ditions. In comparing all the operating curves for each valve size for a 2:1 spool, the best choice for this operating con clition Is a 22.5 GPM 2:1 spool for a 30 GPM required flow rate and a total pressure drop of 1548 PSI across the valve.
lOOOibs
1 [22 GPM
3.14in2
Figure 7
GPM ftltt'ul\)
So
70 11641 60 1 111 50
H89J
XI ll6i
JO llll 'o o
40 (ISH
40
P3 = 454 PSI 454 PSI (2.35 in1) + 1000 lbs Pl = ------3.14 in2 P1 =658 PSI
L:.P,
!><)
ll<>
70
8o
90
1 00
22.5 GPM nominal flow at 150 psi across valve lAp 2L:.p 3L:.p 4L:.p 5t:.p = = = = = 150 psi drop 300 psi drop 450 psi drop 725 psi drop 1450 psi drop
A total pressure drop of 1296 PSI was calculated. Referring to figure 8, which is an operating curve for a 13.2 GPM spool (nominal flow rating) with a 150 PSI drop across the valve.
- 345 -
At 30 GPM and a calculated pressure drop of 1296 PSI; ap proximately 90% of the spool stroke can be utilized. For 30 GPM the calculated pressure drop of 12% PSI will fall bet ween curve 4 and 5.
p2 -
1200 PSI
-
Figure 8
Q' llfmnl M 50 12001 40 (1501 JO (1001 20 17) 15 150) 0
l33 GPM 5000 lbs [4 o GPM 6.8 in2 8.29 in.2 @3 GPMj 2 + 6.80 in1 0 GPr.!j
l:>P,
t,P, = 1200 - 43
=
1 1 57 PSI
1Llp 1 50 psi drop 2Llp = 300 psi drop 3Llp 450 psi drop 4Llp = 725 psi drop 5Llp 1450 psi drop
= = =
Figure 9
__ __ __ _
- 346 -
Figure 1 1
counterbalance valve. If we look at the particular pressure curve for the proportional valve used, the loop drop is fairly high for the valve.
P,
Figure 10
P. =0
20 t151
lb501 1
..a so ao 10 CONfROL CURRNT Nl 80 1 00
13.21 GPM nominal flow at 150 psi across valve 150 psi drop 1 .:::.p 2.:::.p = 300 psi drop 450 psi drop 3.:::.p 4.:::.p = 725 psi drop 5D.p = 1450 psi drop
= =
drop across the valve from P to A and B to T will be shared equally Also, since the counterbalance valve's setting in f\uences this condition as if there were no load, by summing forces the pressure drop on both sides of the valve will be 2500 PSI. TI1e forces will balance such that the pressure on the load side of the cylinder will be 2500 PSI and 4500 PSI, which equals 7000 PSI. Likewise the pressure at the op posite end w be 2500 PSI. 7000 PSI pressure at the load ill end is obviously quite high and cannot be tolerated In actual applications if counterbalancing were used this way, depend ing on the load conditions, and the setting of the counterbal ance valve the pressure at the rod end would not be as high. The problem still exists, however, andone must be aware of what can happen. A more acceptable way of counterbal ancing can be seen in Figure 12.
. , .
resolution of the valve can be obtained. It may seem that the counterbalance valve should be used directly between the rod end of the cylinder and the proportional valve (Figure 11), however, there are disadvantages to this. The setting of the counterbalance valve would be the pressure force over the cylinder's piston area needed to keep the load sus pended. Also, we must remember that the proportional valve adds resistance downstream of the counterbalance valve. The spring chamber of the valve is therefore increased to whatever the pressure drop is over the proportional valve from A to T. If set at load induced pressure, the proportional valve controls the cylinder as if there were no load since the counterbalance valve holds the load at its pressure setting The counterbalance valve is difficult to adjust properly, and introduces the possibility of rod end pressure intensification. This possibility can be elimin ted if the counterbalance valve a were to be externally drained. To clearly demonstrate this point we will consider a condition that has the following parameters. A double rod cylinder has an area of 10 in2, and an overhung load of 45,000 lbs (P = 5000 PSQ. P
.
By using
a check valve and connecting the tank port of the counterbalance valve directly back to the tank, the propor
Figure 12
The actual setting of the counterbalance valve nom1ally would be slightly more than 4500 PSI. (Chapter 2). Because this is an equal area cylinder and valve. the pressure
- 347 -
Figure 13
Figure 14
tiona! valve no longer influences the setti g of the valve. n Speed control can still be set electronically controlled since the proportional valve still will be metering-in when lowering the load. This also prevents damage to the cylinder if the proportional valve quickly closes due to a power loss, since the counterbalance also functions as a port relief valve. When holding a load with a remote pilot operated coun terbalance valve, it is more desirable to run the tank port of the valve directly back to the tank (Figure 14), as in the case of placing the valve directly between the valve and actuator (Figure 13) where there are two restrictions in series. Once again, as with the direct operated counterbalance valve, the pressure at the load side of the cylinder can become higher than expected due to the pressure felt at the spring chamber of the counterbalance valve unless the valve is externally drained. One should also remember that the setting of the counterbalance valve must also be higher than the pressure at the no load side of the cylinder P1 (Figure 14). In this case as the load is being pulled up it acts as a resistive load. Since the proportional valve adds resistance to flow at the no load side of the cylinder, pressure at the no load side may be higher than the setting of the counterbalance valve when the load is being moved up. This could cause erratic movement of the load; therefore, the counterbalance valve must be set
0=30 GPM
higher than the pressure at the no load side of the cylinder. To calculate the pressure at P3 for this condition, the equation for a 1 : 1 valve can be used. (See chart of equations on Pages 9-20.) The pressure at the no load side would be 250 PSI; therefore, the counterbalance valve would have to be set slightly higher than 250 PSI.
F A, P= l J tQ + A. Ql A ,
p -p -
5000 PSI -45,000 lbs j 10-- in2 -- -- -- PJ = -- -- -- -- -30 [ GP 2 + 10 in2 l_3o GPPt!) 10 in2
- 348 -
APPLICATION
DIRECTION
PRESSURE AT P,
F Q, P, (2 X Q,)' A.
--
A,
Q,'
--
(2 X Q,)l
PRESSURE AT P3
P,, - P,
.t.P, = P, 6P,
=
P,
t.P, + t.P,
t.P,t.P, +t.P,
- 349 -
APPLICATION
DIRECTION
PRESSURE AT P2
2 pp Q2 2 _ ._ Q A, Ab + Q2 2 A, Q , 2
I
-
PRESSURE AT P3
- 350 -
APPLICATION
...
DIRECTION
Q,
'
Q,
PRESSURE AT PJ
P,=
(2 x Q2)2
---Q, , A, -- +
A.
F p, - A.
pJ ""
PRESSUREATP,
Pz =
F + P,A,
-- A.
AP, = P, - P1 PRESSURE DROP ACROSS VALVE AP, =P3 AP,=AP, + AP, AP1 =P, AP,=AP, +AP,
- 351 -
APPLICATION
DIRECTION
PRESSURE AT P3
F Ab PJ = --pp - -
F A, PJ = Q, 2 A. +Q2 A, 2
pp - -
--
PRESSURE AT P
Pl = F +P3A, Ab
---
.t.P, = Pp -Pl
CHAPTER tO ACCESSORIES
Today, hydraulic systems play a vital role in keeping industry in production. Unfortunately, there are many hydraulic systems now in operation which do not have the accessory equipment necessary to provide for easy maintenance and trouble-shooting. These "no frills" systems are a product of cost cutting system design, which excludes extra cost items that have no apparent influence on the operation of the system. However, the hydraulic system must be dependable and this can only be achieved by designing into the system components which will provide for better serviceability, easier troubleshooting, and longer system life. After much experience with hydraulic applications, we have concluded that only two types of hydraulic systems exist: those which have been designed with the '}:>roper accessories, and those to which the necessary accessory components have been added in the field. Once we accept the fact that accessory items are mandatory for proper operation, we must also accept the fact that it is less expensive to include these items in the design stage than to add them on later. In addition, we will be able to enhance both the appearance and serviceability of the system if we integrate these components in the overall design stage. This chapter is intended to familiarize you with some of the more popular accessories. We will discuss pressure switches, pressure gauges, gauge protectors, modular manifolds, accumulators, and filters.
In modem day hydraulics, safety and automation have made the pressure switch a very important system component. Classical applications include: pressure dependent se quential interlocks, high/low pressure unloading, audio or visual warning systems, and all types of safety interlocks. Pressure switches not only protect expensive components and machinery, but they also provide for operator safety. By nature of their application , extreme operating conditions must be considered in their design and use so that depen dable operation is guaranteed. Typical operating conditions include: - Long periods of pressurization - High cycle frequency - High pressure peaks - Thermal shock - Mechanical vibration Hydraulic pulsations - Silting by contaminated fluids
Basically, there are two different pressure switch designs to meet the needs of various operati g requirements. They are n the piston and the Bourdon tube pressure switches.
PRESSURE SWITCHES
' "" 0
-
..
----,.,_- Pressure Adjustment Spring - -. ..;.a; riffl - Push Rod - f-lt:. OU. +-* Mechanical ---miiii Stop Piston---t-'-'-'-' Actuator
- 353 -
Micro Switch
cycles/minute), high repeatability ( 1 .5% of set pressure), small pressure differential between on and off positions (a deadband within 5% of set pressure), and extremely long life expectancy (107 cycles). The cross-sectional illustration shows the basic design of this piston actuator. The bottom area of the spool is exposed to system pressure, while leakage past the spool is drained through the "L" port. The housing of the switch is sealed from leakage oil by the low pressure, low friction seal located above the "L" port. The seal in this design seals only leakage oil. Since it is not designed for exposure to high system pressures, the maximum allowable pressure on port "L" is 30 PSIG.
The piston design pressure switch should be selected for use in systems with high switching frequencies or in those which have strong mechanical vibration and/or hydraulic pulsation. The basic design incorporates a die cast aluminum housing which includes the spring chamber, pressure adjustment, micro switch, and wiring box. Attached to the bottom of this alumi um housing is a piston actuator assembly. Depending n on the intended use, the piston actuator can be ordered with or without a leakage port connection. In either design the operating principle is identical. The valve actuates when a system pressure, working on the area of the piston actuator, overcomes the spring force. This causes a slight upward motion of the push rod, which, in tum, causes the micro switch to become activated. The mechanical stop prevents overloading of the spring, and limits the travel of the push rod so that the micro switch is not damaged. Before discussing the merits of the various pressure switch designs it is important that we define two terms used to describe the performance capability of these pressure switches. The fi st term, deadband, describes the pressure r differential between the rising pressure which activates the switch and the falling pressure which deactivates the switch. In general, if a switch is set to actuate at some particular set pressure, then each time pressure increases to this point the micro sw itch is activated. Deactivation, on the other hand, does not normally occur at this same set pressure. Because of static friction, we f ind that a typical pressure switch generally deactivates at a pressure which is slightly lower than the pressure which originally actuated the switch. Repeatability is the second term used to define the per formance capability of any pressure switch. Simply stated, repeatability is the accuracy with which the switch actuates on consecutive pressure cycles. Let us now look at the various designs and their intended applications.
L port
Spool
The actuator housing is made of gray cast iron with a hard ened steel spool. The clearance between the spool and housing is between 8 to 12 microns (see Chapter 5), which allows a maximum leakage of .18 in3/min at maximum operating pressure. Although this limits the use of the switch in small accumulator circuits, spool clearance and low pressure sealing provide the highest possible accuracy at all operating pressures because friction does not increase with system pressure. This feature is not possible in models with pressure load seals. As with any direct spring operated component, the spring constant (Chapter 2) can influence the operating charac teristics of the pressure switch. However, since the switch does not have to handle varying flow rates, it is not in fluenced by pressure override (Chapter 2). For this reason, only three different springs are necessary to provide adequate adjustment sensitivity in the pressure range from 70 to 7250 PSI. The built-in mechanical stop (shown in the first cross section) protects the micro switch from damage and allows peak pressures of up to 8700 PSI.
- 354 -
nection is particularly suited for operating conditions which include high levels of mechanical and/or hydraulic oscillation, contaminated oil, and long periods of pressurization. In this design, the piston actuator uses a Ucup seal on the pressurized side of the spool. At 5000 PSI the seal has a life expectancy of 5 x 1()6 cycles, with a proporti nal increase in o life expectancy as operating pressure decreases. Since the seal is a normal wear item, the piston actuator is designed ing for easy seal replacement.
As shoo,.vn i the cross-sectional illustration, the low pressure n version of this design incorporates a larger piston than do the higher pressure models. On this model. the seal's friction characteristics become a lower percentage of the shifting force (larger area means higher force), and, consequently, they provide more favorahle characteristics In this model the average deadband drops from 15 to 9% of set pressure, with an average repeatability of 1.5% of set pressure.
.
To obtain suitable life exp ectancy for the high pressure seal, the maximum cycle frequency should be kept below 50 cycles per minute The high pressure seal limits the maximum pressure, so excessive pressure spikes should be avoided.
.
PISTON ACTUATED PRESSURE SWITCHES WITH DIFFERENT MOUNTING STYLES Up to this point, we have shoo,.vn only line mounted pressure switches which must be "teed into the plumbing of the hydraulic system. The cross sectional illustrati n shows a o more compact design piston actuated pressure switch, which can be easily adapted for line mounting, subplate mounting, or sandwich mounting between the directional control valve and its subplate. The sandwich mounted version can be sup plied with one or two sw itch assemblies attached to the adaptor plate. Adaptor plates are available w passages ith which allow the switch(es) to sense pressure in either the P,A, orB ports of the directional control.
n As shoo,.vn i the crosssectional illustration, the location of the seal not only protects against leakage, but it also pre vents contamination from entering the close tolerance fit be tween the piston and its housing. Consequently, jamming of the spool because of silting during long periods of pressurization is not a problem with this design.
Pressure loading of the seal forces it against the spool, thus n i creasing friction. This high friction serves as a dampener for mechanical and hydraulic pulsations, but it also has an in fluence on the operating characteristic of the switch The deadband with this design is pressure dependent with the average deadband being approximately 15% of set pressure. The average repeatability is within 2% of the pressure set
.
ling.
Pressure Seal
Striking Plate Modular Piston Actuator Assembly Pressure Switch For Subplate (Manifold) Mounting
The cross-sectional illustration shows a piston actuated pressure switch which operates in a slightly different manner
- 355 -
from the one discussed up to this point. In this design, the spring holds the striking plate in a position which actuates the single pole double throw micro switch. As pressure in creases in the piston actuator assembly, the spring collapses and allows the striking plate to move away from the micro switch. When the switch deactivates, the electrical path through the switch is changed. As you can see in the cross section, the movement of the striking plate is limited to prevent overstressing of the spring when system pressure goes higher than the switch setting. Because of the compact design , this switch is only available with a high pressure seal on the piston actuator. Consequently, a model with a leakage port is not available.
setting which is read directly from the pressure scale. The second design offers two independently adjustable micro switches which allow for an infinitely adjustable deadband. Let us now take a closer look at the operating principle of the Bourdon tube design pressure switch.
Striking Plate
Snubbing Orifices
- 356 -
are spring loaded so that they are not damaged by further tube expansion when system pressure goes beyond the pressure setting of the switch. The special advantages of the Bourdon tube design are: - Extreme accuracy - Small pressure differential - No seal or leakage problems - Insensitive to contamination - Assured of functioning even after long periods (years) of pressurization - Can be used with gases as well as liquids The sensitivity of the Bourdon tube is a desireable feature of this type of switch. However, in designing a system with a Bourdon tube pressure switch, you must be aware that the pressure setting will be quite inaccurate if the pressure switch is subjected to mechanical vibration or hydraulic pulsations. With respect to mechanical vibration we must remember that the helical coil of tube is suspended in free air, and is supported only at one end. If the housing of the switch is rigidly mounted to a vibrating member of the machine's frame, the vibration will be transmitted to the tube. The spring action of the tube will amplify this mechanical vibration, which, in turn, will cause erratic and unwanted ac tivation of the micro switch. To avoid transmitting this mechanical vibration to the Bourdon tube, the switch housing frequently must be mounted on resilient rubber shock mounts with the pressure connection being made of a short piece of hose. With very little mass and virtually no sliding friction the Bour don tube responds quickly to changes in system pressure. In fact, it is quite possible that the Bourdon tube will sense the pulsation in system pressure as created by the pump. To help alleviate this potential problem, the standard switch is supplied with an orificed inlet to the tube. Nevertheless, ad ditional orificing or the use of a sintered metal gauge snubber may be required. By using a coil of hose for the pressure con nection, the capacitance of the hose will help dampen the hydraulic pulsations.
The photograph shows a typical Bourdon tube pressure switch with a fixed pressure deadband. This design in corporates one sin gle pole double throw micro switch, which is activated by the positioning of the Bourdon tube under pressure. The lockable hand knob positions the micro switch by means of a mechanical cam, and has a pressure scale for setting the actuating pressure. The accuracy of the pressure scale is 2% of the maximum pressure rating. Since the pressure rating of the switch is based on the strength of the Bourdon tube, five different tubes are available to cover the 20 to 6000 PSI pressure range. Repeatability of the Bourdon tube design is better than 1 % of set pressure.
THE BOURDON TUBE PRESSURE SWITCH WITH FIXED PRESSURE DEAD BAND
This model is identical in operation to the model previously discussed except for the fact that this switch contains two micro-switches with a different means of independantly ad justing their position. When used in conjunction with an elec trical relay, the pressure differential is infinitely var iable be tween maximum and minimum values. Let us now take a look at a typical application of this switch. The accumulator unloading circuit is a classical application for a pressure switch with an adjustable pressure differential
- 357 -
(deadband). When used with a normally open solenoid vented relief, the switch offers precision control of the maximum and minimum pressure li its of the accumulator. m The pressure switch with solenoid vented relief is sometimes preferred over the accumulator unloading valve (Chapter 2) simply because the pressure differential can be set at the value necessary to meet the requirements of the system. Remember that with the accumulator unloading valve the pressure differential is established only by the area dif ferential in the pilot valve. Of course, this area differential is not adjustable. The following electrical diagram shows the typical wiring of a switch for this application. The electrical schematic shows the pressure switch with ad justable pressure differential, a double pole double throw coil relay (use of only the normally open contacts is indicated), the solenoid on the solenoid vented relief, and two indicator lights. Initially, upon start-up of the system, the coil relay is energized through the normally closed contact of the low pressure micro switch. This causes CR-A and CR-B to close. The solenoid is energized (which loads the relief valve) through CR-B. As system pressure increases to the low pressure setting, the low pressure micro switch is activated, which causes the "Low Pressure Exceeded" indicator light to function. At this point, the coil relay is still "latched'' in by the electrical con nection through the normally closed contacts of the high pressure micro switch and the now closed CR-A contacts. The third part of the cycle functions when system pressure
reaches the high pressure setting of the second micro switch. Activation of this switch causes illumination of the "High Pressure" indicator light, and, at the same time, "drops out" the coil relay. This, in turn, causes CR-A and CR-B to open. Opening of CR-B causes de-energization of the solenoid and vents the pump to tank. Opening of CR-A "resets" the system. Once CR-A opens, the coil relay can only be reac tivated if system pressure drops below the setting of the low pressure switch.
PRESSURE GAUGES
Obviously, pressure gauges indicate the operating pressure in the part of the system to which they are connected. Once the pressure is known, the output force or torque fo the ac tuator can be calculated precisely. Pressure gauge in dications are also necessary when you are adjusting a pressure control or setting the pressure adjustment on a variable displacement pump control. However, in addition to these more obvious uses, pressure gauges play an even more important role in the operation of the hydraulic system. The pressure gauge is probably the most important tool available to the person who must trouble shoot a hydraulic system. By studying a circuit schematic we can determine the pressure level that is supposed to exist in a given part of the circuit, but, without the aid of a pressure gauge, we have
Solenoid
- 358 -
no means of seeing if this pressure really ex ists. For instance, pressure gauges are instrumental in determining if a d!rec tiona! valve has shifted, in ascertaining whether or not the sequence valve has opened, in tracing hydrauli lines, etc. c For these reasons, an adequate number of pressure gauges must be provided n the design stage so that the pressure in i each portion of the circuit can easily be determined once the system is actually functioning. H a system requires so many gauges that its construction would not be feasible or economical, plugged gauge port connections should be provided in the plumbing. In this way, the troubleshooter can more easily install the required gauges n order to determine i the pressure levels in different portions of the circuit.
i When you are nstalling the gauge, we recommend that you use a gauge shut off or a gauge isolator value. This will isolate the gauge from the system until a pressure reading is required. The simplest form of shutoff valve is a \14' needle valve, while the more sophisticated gauge isolator valve is designed specifically for this purpose.
ugePort
3000
Bourdon Tube
-4000
The crosssectional illustration shows a typical pushto-read gauge isolator valve. This valve is similar in function to a manually operated 3way spool type directional control. In the spring offset position. pressure is blocked and the gauge is vented to tank. Pushing the button blocks the tank con nection and exposes the gauge to system pressure. The major advantage of the gauge isolator valve is that it prevents an improper interpretation of the actual pressure in the system. A needle valve, if shut off under pressure. can ac tually capture pressurized fluid in the gauge. H this occurs. the gauge can read full system pressure even If there is no pressure in the system. Consequently, the gauge isolator valve offers the convenience of isolating the gauge even during operation of the system. The gauge isolator valve, as shown in the illustration, con nects pressure to the gauge port through small diameter passages m the valve body. This restricted flow area provides an orifice effect which dampens out the hydraulic pulsations, helping to avoid inaccurate pressure reading (needle flutter). Although this orificing is sufficient for most applications, it is sometimes necessary to use a gauge snubber to dampen out all the hydraulic pulsati ns. o Gauge snubbers come in a variety of designs and models. but their sole purpose is to prevent hydraulic pulsation from reaching the pressure gauge. The crosssectional illustration shows a sintered metal snubber, which is commonly used in hydraulic systems. The sinlered metal snubber is nothing more than a " NPT fitting which incorporates a sintered metal insert. The sin
GAUGE INSTALLATION
The Bourdon tube design allows extreme gauge accuracy at a nominal cost Production gauges typically display an ac curacy of better than 2% of the full scale pressure. Never theless. these gauges are no more accurate than the Bourdon pressure switch if they are subj ect to mechanical or hydraulic pulsation. When you are selecting a gauge for permanent mounting in the hydraulic system, remember that the full scale pressure should be 1 Y to 2 times the maximum 2 operating pressure of the system. This prolongs the life of the gauge by preven ling an overstress of the Bourdon tube.
- 359 -
- 360 -
MODULAR MANIFOLDS
combinations available from the items now on the market are unlimited. In a general sense, a modular manifold is made up of modules, pieces of standard size, which are fitted together in a variety of ways to comprise the desired manifold. That is, the modular subplate is manufactured in such a way that the subplate of one control valve can be combined in the manifold with the subplate of any other control valve. For complete versatility, such subplates are manufactured for any one of the multitude of valves needed in today's sophisticated circuits. A modular subplate for a 4-way directional control valve is a good example to use to further explain the modular method for reduction of interconnecting piping. Basically, a modular subplate consists of a valve mounting face, external con nections for A & B Ports, and a series of standardized through ports which allow any combination of connections with other control valves. A typical modular subplate for a directional control valve may be described as one with a standard ANSIJNFPA mounti g face for the valve, three n pipe tap plugs on the opposite side to allow for pressure con nection for the entire system, connections for the A & B Ports as required, with five through ports to interconnect the 4-way valve with other valves in the manifold. In a usual modular manifold system, external piping is reduced by reserving the center passage for system pressure and the two inner passages to connect the A & B Ports with other parts of the system, thus reserving the two outer most passages for tank connections , external pilots, or diverted oil flows from other passages in the manifold.
Because of the complexity of today's hydraulic systems, many hydraulic equipment suppliers have sought new ways of piping the many valves needed for such sophisticated cir cuitry. Within the past several years, the modular manifold has become the logical answer for piping the multitude of valves needed in today's complicated circuits. Consequently, modular manifolds are growing in popularity, not only to OEM's, but also to the end user market. There are many reasons for this increased interest in modular manifold units. One advantage for OEM's is that the units can be received from the factory ready to install on their equipment, thus greatly reducing costly labor involved in piping. Furthermore, their final piece of machinery is neat in appearance and easy to service, since hundreds of feet of pipe have been eliminated. It no longer looks like a plumber's nightmare. Likewise, the end user can cut costs and give his equipment a finished look, while retaining the flexibility for future re-design or disassemblement and re-use of the modular manifolds in other designs. The information which follows is intended to show the general processes to be followed in building a modular unit in the most economical way. If your interest is aroused by modular manifolds, you need only let this information kindle your imagination, for the
- 361 -
which is bolted between the subplates of two different valves. Interconnecting plates are designed so that any num ber of ports can be connected or diverted into another passage. Ukewise, interconnecting plates are usually sup plied with plugged piped ports on the back side so that hydraulic oil can be diverted into or out of any one or more of the passages within the modular system. Consequently, in terconnecting plates combined with diuider plates, greatly add to the versatility of the modular manifold.
plate,
End plates, the finishing touch to a modular system, mount against the two end subplates of the module, needing only 0-rings for an oil tight seal. Like inter-connecting plates, end plates add to the versatility of the modular manifold since they are available with pipe connections for oU passages within the manifold. Being the last component of a modular system, end plates not only terminate internal oil passage, but they are also drilled to allow mounting of the complete system to the machinery.
Interconnecting Plate
Divider plates serve two purposes within a modular manifold system. Available in many different patterns, a divider plate is basically a flat piece of steel which is either drilled to allow the flow to continue from one subplate to another, or not drilled to block the flow of oil. Apart from controlling flow within the modular manifold, divider plates have a second function. That is, divider plates are used as 0-ring seats, allowing a leak proof connection between the modular sub plates. Therefore, divider plates are nonnally a necessity in making connection within the modular manifold. However, they are not required when mounting the "end plates."
End Plate
In review, we now have modular subplates for use with almost any hydraulic control valve, each having standardized oU passages which allow the valves to be connected in an un detennined number of ways. Moreover, we have further methods of controlling the direction of oil flow with in terconnecting and dividing plates, and with end plates to f inish the unit and allow us to mount the entire system.
.. . .. ,. _ .
.
..
. . . . :. . : . -:: ::::: . . . ::
Divider Plates
- 362 -
---
Main oil passages Pilot oil passages Drain oil passages Connection porting to the valve mounting face of a subplate Connection porting in an inter-connecting plate
-----
- - - - -
II ____,
,,
S7
Plugged threaded port on line connection side Open threaded port on line connection side
II --4+-II
Connection porting to the valve mounting face, and plugged threaded port on the line connection side Connection porting to the valve mounting face, and open threaded port on the line connection side Passage between two adjoining sub-plates or inter-connecting plates blocked , using "blank" dividing plate Passage between two adjoining sub-plates or inter-connecting plates continued, using drilled dividing plate Passage between sub plate and valve blocked
Valve port letters are given on the dividing line between the valve and the module subplate. Consequently, the special module symbols, along with standard NFPA valve symbols, must be kept in mind as we design a module circuit . In order to design a module unit economically, and to avoid confusion, you should first draw a working conventional cir cuit. For purposes of this discussion, we have chosen a two legged circuit. The circuit, which operates from one pump, operates two cylinders which are controlled by two direc tional control valves . One leg of the circuit conta ins a pressure compensated flow control for meter out speed con trol of the cylinder, while the other leg of the circuit has a fine throttle valve and a pressure reducing valve for speed and pressure control of the cylinder. The entire system is pro tected by a pressure relief valve. The installation of a modular manifold can eliminate virtually all interconnecting piping in this circuit, reducing construction costs and giving a neater appearance. Because modular manifold systems offer complete ver satility, the designer should first draw a conventional circuit, then consider the many possibilities, and, finally, conceive the module from the best of his ideas. Indeed, planning ahead at this early stage will prove to be of economic value in the actual assembly of the modular manifold.
Connection to valve and open threaded port Mounting face for further Line connection face module plates
--
Group Symbol
- 363 -
other leg of the circuit will be connected to the remaining side of the pressure relief subplate at a later time. Having made this decision, we must consider the use of a dividing plate before connecting the directional control valve module subplate to the unit The divider plate is necessary not only to make a positive O'ring seal between the two sub plates, but also to allow only the needed passages to be open.
Si ce the module unit we are to design has two separate cir n cuits with a relief valve common to both legs, it is probably most advantageous to start our module with the subplate of the relief. Therefore, the first decision is to make a pump connection to the center (pressure) passage of the relief valved module subplate. Having chosen this common start ing point, you must remember that there are now two ports in use, pressure (center) and tank (outside).
Since the left leg of the circuit will receive pressure from the center passage and utilize an outside passage for a tank con nection, the remaining ports should be blocked, thus isolating them for future use if necessary. Consequently, the subplate for the directional control valve may now be bolted with O'rings and the div ider plate to the subplate of the relief valve. No intzrconnecting plates are required since the center passage of the directional control is connected to the pressure port of the valve. It should be noted, at this point, that the subplate of the directional valve is turned end for end (another versatile feature of the module system), so that the tank port of the directional control valve is isolated from that of the relief valve, since this line must be directed through a pressure compensated flow control (the next valve to be mounted). Having connected this valve as described, an ac count of our oil passages shows that there are external con nections for A & B ports on the back side of the subplate, and two tank line passages. That is: the tank line from the relief passes undisturbed through the subplate, and the tank line from the directional control which is to be connected to the flow control. Once again taking account of all oil passages we must choose a suitable dividing plate. In this situation, we would choose a dividing plate which would allow the two outside (tank) lines to flow into the next module component, blocking off the three center passages, since the pressure passage (center) must only be connected to the directional control, while the A & B connections (inner passages) must be externally connected to the cylinder. A close look at the subplate for the pressure compensated flow control w show that the A & B ports of this valve are ill connected to passages other than those which have been established so far. Since the A port of the flow control is con nected to the center passage, while the B port is connected to one of the inner passages, we must choose the correct in terconnecting plate. This plate would be one which diverts one of the outermost passages to the center passage, and
. .. . . .
At this time, a decision should be made to work one leg of the circuit, saving the second leg for later on. To avoid con fusion, we have chosen the left leg of the conventional cir cuit, electing to finish the leg with the 4-way directional con trol and the pressure compensated flow control first The
- 364 -
system pressure enters a 4-way directional control which has its A port connected directly to the cylinder, while the pressure from the B port is controlled by a pressure reducing valve. The speed of the cylinder is controlled by metering the oil from the directional valve's tank port through a fine throttle (needle) valve. Knowing the particular control valves needed, we can now build the final leg of the circuit. Since system pressure first enters the directional control valve through the center passage, we must choose a suitable dividing plate. Because the tank line is already externally connected, we should connect this passage with the left leg of the module. Accordingly, the correct choice of an in terconnecting plate would be one with center (pressure) and one of the outermost passages (tank) open . After adding the four way directional control valve to the module manifold, we must now consider the following passages. First of all, the A port of the valve enters one of the inner passages, which must be blocked on both ends because this port is externally connected to the cylinder. Secondly, the pressure passage must be blocked from any additional valving, since system pressure will be distributed by the directional control, thus terminating the pressure passage in this subplate. Furthermore, as with the module subplate of the left leg, this one is also rotated 180, thus isolating the tank line passage of the 4-way valve so that the control of flow through the existing system tank line passage will be directed, undisturbed, through the subplate for future use with additional valves. Consequently, we must choose a divider plate which will block only the A (inner) and pressure (center) passages, allowing the others to flow into the ad ditional valves in the system.
Having finished the left leg of the module circuit on one side of the pressure relief valve, we can now complete the modular manifold by isolating the right leg on the opposite side. A review of the conventional circuit will show that
- 365 -
need for an interconnecting plate to connect the existing passages with the correct ones in the subplate of the fine throttle valve. Since the A port of the fine throttle valve is connected with an inner passage, while the B port is con nected to the center passage, the isolated tank line of the 4-way valve must be diverted to an inner passage. Likewise, the existing system tank line must be directed into the center passage to be connected to the fine throttle valve. The B port of the directional control valve is connected with a passage that will flow through the interconnecting plate and the sub plate of the fine throttle valve undisturbed. The addition of the fine throttle valve along with the correct interconnecting and dividing plate is shown as follows.
ders, pump, and reservoir. The modular conversion requires some careful planning, but in the long run, the time the engineer spends at this will be far less than the assembly time required to pipe the components individually. The actual hardware of the module as described is shown in the two photographs. The compactness of this design is readily apparent considering the fact that 6 valves are mounted on a manifold which is just slightly over two feet in length. The back side of the modular unit shows the pipe connects to the remote parts of this hydraulic system.
--1-U:::-1--o;-;.,.,
-f'-T'Ff'lJr'i--
..TEICONNKTING l'lAlf
-
.. Volvo 1 '"'! I
To complete the system only the B port passage from the 4-way directional control must be controlled by the pressure reducing valve. Since the inner passage from the 4-way valve allows oil to flow into the correct passage (P connection) of the pressure reducing valve subplate, a divider plate must be chosen to block all passages allowing only an inner passage open for the straight line flow of oil from the B Port of the directional valve. The valve with the correct dividing plate is connected as shown, with an external pipe connection to the B port of the cylinder made on the back side of the modular assembly.
The modular manifold is now complete, using only the num ber of pipe runs necessary to make connections to the cylin-
Modular manifolds not only reduce piping and provide an swers to design problems, but they also serve as a form of preventive maintenance. That is, any complex hydraulic unit that is to be piped by the conventional method not only requires an undesirable amount of assembly time, but it also creates hidden problems as the number of pipes and fittings increases. All too often it is found that a valve entangled in a cage of pipes is virtually inaccessible when the time comes for service or replacement. This is not true with a modular manifold, since all piping is done from the back of the unit, placing all the valves within easy access of the repairmen. Another advantage which results from the reduction of
- 366 -
Merely adding, rearranging, or eliminating module com ponents allows flexibility for modification virtually impossible with a drilled type manifold. Although the module system, as described, deals with mounting single components on a particular module sub plate, sandwich mounted valves, as discussed in other chap ters can be used to add to the versatility of the system.
Modular unit mounting a total of 1 8 different valves. Sandwich mounted double pilot operated check valves and sandwich mounted dual flow controls are used with each of the six 50 GPM directional controls.
- 367 -
Directional valve with sandwich mounted dual pilot operated check, dual flow control, and pressure reducing valve all mounted on a modular subplate.
ACCUMULATORS
Today there are three types of accumulators which can be used in a hydraulic system: the weight loaded, the spr ing loaded, and the gas charged. The first two consist basically of a hydraulic cylinder which has a force exerted on one side of its piston by either a vertically acting weight or a heavy spring. Hydraulic fluid then enters the opposite side of the cylinder, and, as pressure rises, lifts the weight or com presses the spring. The fluid is then stored in the housing of the cylinder, until system pressure drops to the point at which the weight or the spring can push oil back into the hydraulic system. With the weight loaded accumulator, system pressure will remain constant as fluid discharges from the accumulator because the weight exerts a constant force. The spring loaded accumulator, on the other hand, causes a decay in system pressure as the accumulator discharges. This happens because the spring force relaxes as the spring becomes longer, during discharge. Although the weight loaded and spring loaded accumulators can be used successfully, they are usually home made devices, incorporating standard hydraulic cylinders. The gas charged accumulator, on the other hand, is a very popular accessory which can be used to perform many different func tions. Since gas charged accumulators are by far the most popular, this section will be devoted to the design, ap plication, and installation of these components.
The cross-sectional illustration shows the operating principle of a typical piston type accumulator. In this design, a sealed but movable piston isolates the gas chamber from the oil chamber. The accumulator is precharged with nitrogen gas to a level dictated by the system requirement. During operation, when system pressure exceeds the gas precharge pressure, oil enters the accumulator and forces the piston up-
ward. This compresses the gas, which increases the pressure in the accumulator. A major advantage offered by the piston type ac cumulator is that it can operate with an infinite gas com pression ratio. In addition, the piston accumulator can be fully discharged during the operating cycle without fear of
- 368 -
damage. Conversely, the disadvantage of this design is that the friction caused by the piston seals, and the inertial mass of the piston tend to slow the accumulator's respon se characteristics. Also, the piston seals are subject to wear, and eventually to leakage of the precharge. For this reason, the piston type accumulator generally requires a more frequent check on the precharge pressure.
BLADDER ACCUMULATORS
between the gas chamber and the oil chamber. Initially, the oil port is vented to atmospheric pressure, and the rubber bladder is precharged with nitrogen gas through the gas valve. Precharging the bladder causes it to stretch until it comes completely in contact with the retai ing n walls of the vessel. During precharging, the mushroom shaped bladder protection valve closes, which prevents the bladder from extruding through the oil connection port. During operation of the hydraulic system, once system pressure exceeds the precharge pressure, oil enters the accumulator and compresses the rubber bladder and the gas it contains. Needless to say, the more the gas is com pressed, the higher the system pressure must be. Likewise, as system pressure decays from maximum to minimum, the gas expands and forces an oil flow from the accumulator. Because the bladder of the accumulator has very little mass and virtually no friction, this design responds to changes in pressure almost instantaneously. In fact, the bladder type accumulator reacts to changes in system pressure faster than any other type of hydraulic system component. There are two precautions concerning the selection of a bladder type accumulator which are worthy of mention at this point. First, to avoid damage to either the bladder or the bladder protection valve, the accumulator must be sized large enough so that it will not close the anti extrusion valve during normal system operation. As will be shown, this protection can also be accomplished through the selection of the proper precharge pressure. Second, it is detrimental to the life expectancy of the rub ber bladder to compress it too much. To avoid excessive bladder deformation when the accumulator is fully charged, there is a defined gas compression ratio which must not be exceeded.
Accumulators with the bladder design are probably used more frequently than the others. As shown in the cross sectional illustration, the bladder accumulator has a steel outer wall which contains the operating pressure of the system. A rubber bladder serves as the separating barrier
- 369 -
Simply stated:
Oil Entry
P, V, =P2 V2=Constant (w constant gas temperature) ith Where: P, =initial gas pressure (PSIA) V, =initial gas volume (in3) V2=Final gas volume (in3)
Discharging
This formula implies that if we have a volume of gas (V,) stored at a pressure (P, ), an increase or decrease of the volume will also change the pressure. You will notice that if V2 is larger than V, , then P2 must be smaller than P,. Likewise, if V2 is smaller than V,, then P2 is greater than P, . It is important to remember that a gas completely fills its containing vessel. Therefore, the volume of the gas is determined by the volume of its container. A ten gallon accumulator, when precharged, holds a gas volume of ten gallons. It does not mean that this same accumulator will store 10 gallons ofpressurizedfluid. Before examining the following example, it is important for you to note that the pressure must always be represented as absolute pressure (Chapter 1 ) when using Boyle's Law. Example: A 5 gallon accumulator is precharged with nitrogen to 1 500 PSI. What would the volume of oil be if the gas pressure increased to 3000 PSI?
P, =Absolute pre-charge pressure = V, =Initial gas volume = 5 gallon x 1500 PSIG + 14.7 PSI=1514.7 PSIA
pl
P,
VI
Since V2=final gas volume the oil volume would be the initial gas volume minus the final gas volume or Voil = V,-V2= 1 155-580=574 in3
- 370 -
There is sometimes a problem when using Boyle's Law to calculate the expected volume and pressure conditions. The problem is that the formula is accurate only when the temperature of the gas remains constant, while the pressure and volume conditions change . Unfortunately a gas increases in temperature when it is compressed, and it cools as it expands. This means that the formula would be accurate only if sufficient time were available for the accumulator to stabilize at room temperature after a change in volume of the gas occurred. This isothermal change of pressure and volume would only be applicable when the duty cycle of the accumulator was quite slow.
It is beyond the scope of this text to fully explain what is meant by the term molar specific heat of a gas. Fortunately, if we accept the fact that the molar specific heat ratio for nitrogen is 1 .4, the understanding of this term is not essential to our calculating pressure and volume conditions of an ac cumulator which undergoes an adiabatic change of con dition. The following example explains the mathematics in volved in working with this formula: You will notice that it is necessary to work with logarithms. This will require the use of log tables, a slide rule or a pocket calculator with a log function. Example: A 5 gallon accumulator is pre-charged with nitrogen to a pressure of 1500 PSI. 1 . What volume of oil will the accumulator store when rapid oil entry increases the gas pressure to 3000 PSI. 2. How much oil will be discharged if the system pressure then drops quickly to 2250 PSI? 1 . Solution: P, V=P2 v;'
P, =absolute pre-charge pressure = 1500 PSI G + 14.7 PSI = 1514.7 PSIA t ta V ,= lnt 1 gas vo1ume
P2=maximum pressure (absolut e)= 3000 PSI + 14.7 PSI=3014.7 PSIA n=1.4 V2=final gas volume (in3)
Pressure
- . :
-
-- I
1 155
Although the formula which expresses the adiabatic change of pressure and volume condition is similar in appearance to Boyle's formula, mathematically it is somewhat more difficult to use. Let us now state this formula, and then we will at tempt to explain its use in simple terms: n n P, V, =P2 V2 =Constant
V2= antilog l9J x 1 155 V2=.61lx1 155 V2=706 in3 (gas volume)
In this formula "n" is the molar specific heat ratio of the gas.
- 371 -
Since V1=final gas volume the oil volume would be the initial gas volume minus the final gas volume:
Consequently, the oil discharged would be found by sub tracting the final oil volume from the initial oil volume:
t:,. V=449-289= 160 in3
(oil discharged)
Von=1 155-706 Von=449 in3 (oil volume in storage) 2. Solution: n n P,V, =P2 V2
P, =Initial gas pressure (absolute) = 3000 PSIG + 14.7 PSI= 3014.7 PSIA
If we compare the oil volumes as calculated in the isothermal and adiabatic examples, we find that the isothermal change stores 125 in3 (574449=125 in3) more oil than the adiabatic change, given an equivalent pressure change. Since this extra 1/2 gallon of fluid can influence the proper operation of the hydraulic system, we must consider the conditions under which the oil enters and leaves the accumulator. Our ex ample has shown that moments after the adiabatic charging of the accumulator with oil, the gas volume would be 706 in3 However, if the same accumulator were given enough time, the temperature of the gas would equalize at room tem perature. As the gas cools, its internal pressure decreases. This allows more oil to enter the accumulator as the gas volume drops to the isothermal level (580 in3).
n=1.4
V1 =
1 .4
3014.7 2264.7
706
V1= antilog
V1= antilog
Ql133J ti
x
706
706
The oil volume stored at this pressure (2250 PSI) would be the total gas volume of the accumulator minus the final gas volume or: Vail =1155 in3- 866 in3=289 in3
- 372 -
1000
.c !J .s !J ;Q = e =
Pressure-Volume Curves Isothermal Relationship 900 5 Gallon Accumulator 11 y 800 T T 700 600 500
I
200
y /I / X
I I
500
I 7
I I
<
:0 -;
;>
400
II
I/
II
:/ /, T
I
I II
:;
TT lA"
I
_....
1000 G'
[i5
7n I
1500
Q.
Q. - ... = (/j
II
v 1 / 1/ 1/
lA
2000
(/j Ia <:)
Ia .c !J
...
1000
-(/j .c !J .5 !J ;Q = e = 0 > :0 Ia <
0 200
r r r r IT
500
2500
3000
200
I
I
17
I
T
"""' -
500 1000 -
..
r J
II
G'
= (/j (/j
Ill ;>
200
300 100
II II
I i
I I
I
I I I I
7 T 7 ,/, r I I I I I
I I
i I
1]'
Ii
_...
y
I
T
_)/
1 500 0: 2000
(/j Ia <:) Ia .c v
..
0 200
!/
500
/ I A v
1/
1/
2500
3000
Generally speaking, the maximum system pressure is deter mined either by the pressure rating of the pump or the ac cumulator. You will find that most accumulators are rated for a maximum operating pressure of 3000 PSI. Higher pressure versions (up to 6000 PSI) are available. However, they cost considerably more than the 3000 PSI units. It is im portant to fix the maximum pressure limit as high as feasibly possible. In this way the maximum storage capability of the accumulator can be utilized. Let us assume that our maximum operating pressure will be 3000 PSI. NOTE: As previously mentioned, when selecting a bladder type accumulator, we must limit the maximum gas com pression ratio to prevent overflexing of the bladder. To prevent overflexing of the bladder, the maximum system pressure should not exceed three times the minimum operating pressure. If, for example, the minimum operating pressure were 500 PSI, then the maximum operating pressure should not exceed 1500 PSI. STEP 3: Determine the precharge pressure. With a gas charged accumulator, the lower the precharge pressure, the more oil the accumulator will store at maximum operating pressure. Likewise, the lower the precharge pressure, the lower the minimum operating pressure can be before the accumulator completely empties its oil charge. Actually, the precharge pressure is best deter mined by studying the accumulator pressure volume curves, and comparing the performance with the result you expect to obtain for your system. Nevertheless, there are some guidelines to follow for determining the proper precharge pressure range. Although these guidelines specifically set the
limits of precharge pressure for bladder type accumulators, they can also be applied to piston designs. With bladder type accumulators, we must prevent over stressing the bladder when it is fully compressed at maximum operating pressure. To prevent excessive defor mation at high pressure, the precharge pressure should never drop below 25% of the maximum operating pressure. This means that with a maximum pressure of 3000 PSI, the minimum precharge pressure should not be less than 750 PSI. On the other hand, we usually do not want to precharge the accumulator to a level higher than the minimum operating pressure. If this were the case, the precharge would have enough force to empty the accumulator completely. This would cause the bladder protection valve to close during nor mal operation of the system. For mechanical reasons, this is not recommended. One way to assure that the bladder protection valve will always remain open is to limit the maximum precharge to 90% of the minimum operating pressure. In this way, the ac tuator will stall, from lack of pressure force, before the ac cumulator fully discharges. With this method the maximum precharge for a system which must operate wtth at least 1500 PSI would be determined as follows:
This means that the acceptable precharge for the example we are developing would be somewhere between 1350 PSI and 750 PSI.
With a precharge pressure of only 1350 PSI . . . if this cylinder stalls because of lack of force . . . at a system pressure of 1500 PSI.
LOAD
- 374 -
Although the above guideline provides satisfactory operation r for many hydraulic circuits, it may not be desi able to have the load stall at some minimum operating pressure. For instance, in applications with varying loads, we would have to precharge the accumulator based on the minimum pressure required to move the heaviest load. You can see that there would be no safeguard against emptying the ac cumulator if the cylinder were to be extended with no load. For this reason, it is sometimes better to assure that the ac cumulator will not fully discharge simply by oversizing the ac cumulator. In this way the precharge is not limited to some maximum level for a mechanical reason. With this design per spective, the only limiting factor on maximum precharge is how much oil you expect the accumulator to store. As shown in the example, a flow control is usually required to control the speed of the actuator because the pressure of the accumulator, being higher than the pressure required to do the work, can cause an undesirably high flow rate. STEP 4: Determine the size of the accumulator. In general, it will be necessary to determine how much fluid must be displaced to do the required work. Once we deter mine the amount of oil required, we simply choose an ac cumulator from the graphs that will supply the working volume as pressure drops from maximum to minimum values. If, for instance, we require 300 in3 of working volume, and the maximum pressure is 3000 PSI, the minimum pressure 1500 PSI, and the accumulator is precharged to 1000 PSI, the graphic solution would indicate that a 5 gallon accumulator is required. We have assumed that the adiabatic relationship applies to this circuit requirement.
It is important to note that we size the accumulator by the oil it displaces rather than by a flow rate. The flow rate of an ac cumulator is determined solely by the prevailing pressure conditions. High pressure at the accumulator means high potential energy. If the accumulator were discharged into a system with little resistance to flow, the flow rate through the oil port of the accumulator could be quite high. Although this high flow rate is short lived, it is not impossible to achieve in stantaneous flow rates of over 500 GPM from a one gallon accumulator. Consequently, the flow rate from an accumulator is deter mined solely by the time allotted for it to discharge. Nor mally, flow controls (Chapter 3) are required to control the rate of discharge from the accumulator.
ACCUMULATOR APPLICATIONS
In many hydraulic systems, it would be convenient if we could somehow store hydraulic energy during one portion of the cycle, and then use this energy later in the cycle, to per form the required work function. However, hydraulic fluid is only slightly compressible, which eliminates the possibility of storing high levels of energy directly. To store this energy in the system, it then becomes necessary to make use of an oil accumulator. Nevertheless, because of lack of application experience, and because of the misconception that the ac cumulator is both expensive and a service problem, this device is often omitted from the hydraulic system design. Rather than engineer the hydraulic circuit to include an ac-
will supply 125 in3 when pressure drops from 3000 PSI to 2450 PSI. This cylinder has a 4" bore and 10" stroke.
LOAD
- 375 -
I
800
Ui' Ql ..c CJ .5 CJ :0
:I
700
I
600
000
Ql
:I
.-::1
500
0 > 400
tN = 3 5 0 in3
I
T
'
"
Ql ... (I) (I) Ql ... Q.. Ql 0') ... Ill ..c CJ Ql ... Q.. (I) Ill T
"
3000
:I
Ql :0
Ill Ill ;;.
!/!'
300
<C
200
100
200
500
1 000
1 500
2000
2500
cumulator, the designer simply provides a circuit in which the pump can produce instantaneously the hydraulic energy which is required to do the work. Nevertheless there are many circuit designs which could be enhanced by the use of an accumulator. Let us now mention a few examples.
ENERGY STORAGE
In any circuit which has an intermittent duty cycle, there is a potential use for the accumulator. Likewise, circuits which are continuously operating can make good use of an ac cumulator, if during a portion of their cycles, a high flow rate is required for a short period of time. The design theory is that large hydraulic pumps (which also require large prime movers) which operate intermittently, are replaced by smaller pumps which operate a greater percentage of the time. If we look at the overall duty cycle, we are putting the same level of energy into our system by either method. The difference is that the accumulator circuit more continuously supplies this energy at a lower power level . For those of you who are familiar with electric motors and the industrial power factor the efficiency of the accumulator circuit is readily apparent.
system function at some midpoint in the duty cycle, the ac cumulator can be used to store an emergency supply of energy. If there is a pump or power failure, this stored energy can be used to complete the cycle and return the machinery to safe condition. In this type of application, the accumulator must be large enough to supply enough oil to run the machinery through at least one complete cycle.
LEAKAGE COMPENSATION
In many hydraulic circuits it is often necessary for the ac tuator to provide a holding force without any motion. Hydraulically, this requires pressure with no flow. We have shown in Chapter 6 how this problem can be solved by using a pressure compensated pump. However, the accumulator offers the designer a viable alternative. In machine tool cir cuits, for instance, the accumulator will exert pressure on the clamping cylinders for extended periods of time. The oil stored in the accumulator will supply the relatively small oil flow which is requi ed to replace the oil lost by internal r leakage of spool type directional controls (for example) and possible leakage by the piston seals. When leakage losses allow the accumulator to drop below the minimum clamping pressure, the pump will be turned on momentarily to recharge the accumulator. This can be an automatic function if the circuit incorporates an accumulator charg ing valve
ENERG Y RESERVE
In critical application when it would be dangerous to stop the
- 376 -
release of the energy stored in several sticks of dynamite. Whenever an accumulator is to be precharged, it is im perative that the oil side of the accumulator be vented to at mosphere. Also, before attempting to remove an ac cumulator from the system (for repair or replacement), it is mandatory that the oil port be at zero pressure. A charged accumulator which is not mechanically restrained will propel! itself through the air like a rocket once it is unthreaded from the plumbing. For these reasons, proper valving {gate valves, ball valve and/or needle valves) must be incorporated on the oil side of the accumulator. One valve (usually a ball valve) is required for the initial isolation of the accumulator form the rest of the hydraulic system. The second valve (usually a small needle valve) is teed into the line between the isolating valve and the accumulator so that the oil charge can be bled to the reservoir.
THERMAL COMPENSATOR
We have shown in Chapter 2 how a port relief can be used to protect the system from overpressure due to thermal ex pansion of the fluid. However, this method provides no means of maintaining pressure if the oil cools. In static closed systems that are subject to varying temperatures, the accumulator will compensate for the expansion and con traction of the fluid, and mainta system pressure within in safe limits.
ENERGY RECOVERY
In systems in which large masses must be decelerated, it is possible to use the accumulator to recover most of the energy that was originally required to put the load in motion. When the load ouerruns the actuator, load induced pressure will force oil out of the actuator. If this flow of fluid is directed into an adequately sized accumulator, the precharge pressure will offer resistance to this flow. Then, as the ac cumulator becomes more fully charge, the back pressure on the actuator will cause the load to decelerate. When ac cumulator pressure rises to meet the load induced pressure, the motion of the load will stop. By altering the precharge of the accumulator, the deceleration rate can be adjusted. The recovered potential energy now stored by the accumulator can then be used to assist in restarting the system.
Ball or Gate Valve From -------- To System Pump Minimum Valving Needed to Isolate the Accumulator
- 377 -
NOTES ON PRECHARGING
The most important point to remember is that an ac cumulator should be precharged only with "oil pumped" or "dry" nitrogen. Never consider using compressed air or oxygen for precharging accumulator, since oxygen has a ten dency to explode if mixed with oil under compression. Nitrogen is a commercially available bottled gas. A fully charged nitrogen bottle is normally supplied with an internal pressure of approximately 2500 PSI, which is usually adequate for precharging most accumulators. As with any pressure vessel designed for transporting high pressure gases, the shutoff valve on top of the bottle is protected with a metal cover which is threaded to the bottle. This cover protects the valve from being broken if the nitrogen bottle were to be inadvertantly dropped. It is important to remem ber that this protective cover should never be removed unless the bottle is firmly supported. In addition, the cover should be immediately replaced upon completion of the precharging, and before attempting to move the bottle. In order to precharge the accumulator, it will be necessary to purchase an accumulator charging assembly from the ac cumulator manufacturer. This assembly consists of a length of hose, a pressure gauge, a bleeder valve, a check valve, and the necessary fittings for connecting to both the accumulator gas valve and the nitrogen bottle. (The standard thread con nection for an American nitrogen bottle is a 29/32-14 left hand thread gland nut). Although the procedure is different for different charging assemblies, a general procedure would be as follows: Connect the charging assembly first to the nitrogen bot tle and then to the accumulator, carefully making sure that all fittings are tightened. Operate the mechanism of the charging assembly which opens the gas valve on the accumulator. Begin inflating the accumulator by slowly opening and then closing the valve on the nitrogen bottle. Remember, the adiabatic expansion of the nitrogen as it is trans ferred from the bottle to the accumulator will cause the gas to cool. When the required precharge pressure has been reached, allow time for the temperature of the gas to equalize. Then check the pressure on the gauge. Bleed off any excess pressure and/or add nitrogen as required. When satisfied with the isothermal precharge pressure, operate the mechanism to close the gas valve on the ac cumulator. Open bleeder valve to vent residual pressure from the hose and charging assembly. Remove charging assembly from the gas valve on the ac cumulator. Check gas valve with soapy water for gas leak. Remove charging assembly from nitrogen bottle, and replace protective covers on both the nitrogen bottle and the accumulator. Once the accumulator is put into operation, check the precharge when the system is at operating temperature. If
the accumulator was precharged at room temperature, and is then heated by the hydraulic system, the precharge pressure could become higher than desired. After putting the ac cumulator into service, it is good practice to check its precharge pressure period ically. We recommend checking the precharge after one week of service. If no loss of precharge is indicated, the precharge should be checked on increasing time intervals of one month, six months, and then yearly. In order to prevent excessive wear of the gas valve and unnecessary loss of precharge pressure, do not con tinuously (daily) check the precharge pressure by using the gas valve.
FILTRATION
There is nothing more frustrating than to see a well designed system, which uses the best hydraulic components, fail, simply because of dirt. Nevertheless, studies have shown that over 60% of all hydraulic systems down time can be at tributed to untidy maintenance, and lack of proper filtration. In Chapter 5, we have discussed the micron and its relation ship to the close tolerance manufacturing of the directional control valve. If we consider any of the other hydraulic syste.n components covered in other chapters, we can see that close tolerance oil sealing also plays a very important role in obtaining the proper valve function. Consequently, anyone who is responsible for the design and/or main tenance of a hydraulic system must consider the precision with which hydraulic system components are manufactured. Let us now take a practical look at how dirt affects the per formance of the hydraulic system, and what you can do to preserve the life of the system's components.
THE CONTAMINANT
The American National Standard Glossary of Terms for
- 378 -
Fluid Power (ANSI 893.2-1971) as published by The NFPA, (The National Fluid Power Association, 3333 North Mayfair Road, Milwaukee, Wisconsin 53222) defines contaminant as, " . . . any material, or substance which is unwanted or ad versely affects the fluid power system or components, or both." The material or substance they define can have many origins. First, there are the huge amounts of dirt present in the hydraulic system when newly fabricated. When it is first started, a properly filtered system is probably the dirtiest it ever will be. The fact is that during the fabrication stage the reservoir is open for abuse. A newly fabricated reservoir, if not used immediately, often becomes the shops garbage can. During this time it collects cigarette butts, lunch bags, apple cores, soda cans, packing materials, and other large objects. These large objects, though, are usually not harmful to the system, since they will be removed prior to assembly and cleaning of the reservoir. The harmful dirt which is built into the system has much smaller dimensions. The new system, which looks clean, is actually contaminated by millions of in visible contaminants. It is difficult, if not impossible, to remove the invisible con taminants in a new system by washing with solvents and then wiping with rags. Likewise, after the assembly, much of the contamination becomes inaccessable to standard cleaning processes. Harmful, built-in contaminants include rust, paint chips, paint over-spray, shop dust, teflon tape and other sealing compounds, metal chips from bolt threads and pipe fittings, coring sand from cast housings , lint from "cleaning rags", welding slag, etc. The second source of contamination is the dirty environment in which the system must operate. During normal operation , the oil level in the reservoir is constantly changing. For in stance, during extension of a cylinder the oil level drops, and the reservoir inhales polluted dust and water vapor laden air from its surroundings. The dust mixes with the oil and enters the hydraulic system. After shutdown of the system, the moisture which has entered condenses on the walls of the reservoir as the system cools. This not only dilutes the oil but also causes formation of rust particles. Although most air is filtered by the breather element, some air is drawn into the reservoir through other openings. These openings include improperly fitted suction and return line flanges, shaft seals of pumps and motors, and rod seals of cylinder actuators. A third source for contamination is that generated by the system during normal operation. As the system operates fric tion in pumps, valves, cylinders and motors causes normal wearing of the sliding surfaces. Likewise, high oil velocities can cause errosion of these metal surfaces. In either case, microscopic particles enter the system with an abrasive ef fect. These particles in tum accelerate wear which further in creases the contamination level in the system. Another source for contamination which is also generated during normal operation of the system is oil oxidation. This formation of solid carbon particles has been discussed in Chapter 7.
- 379 -
Particle Size
Particle Count For 100 mL of Fluid Class 0 2700 670 93 16 1 Class 1 4600 1 340 210 28 3 Class 2 9700 2680 380 56 5 Class 3 24,000 5360 780 1 10 11 Class 4 32,000 10,700 1510 225 21 Class 5 87,000 2 1 ,400 3 1 30 430 41 Class 6 1 2 8,000 42,000 6500 1000 92
(JA)
5-10 10-25 25-50 50-100 100+
In consideration of the number of contaminants there is an SAE standard which specifies seven levels of cleanliness. The classifications range from Class 0, the cleanest, to Class 6, the dirtiest. The levels of cleanliness, according to the SAE standard, are defined in the chart. A new drum of hydraulic oil, as received from the refinery, typically falls into Class 6. This means that new oil is not satisfactorily clean, for use in most hydraulic systems. To determine the level of cleanliness in your hydraulic system, oil companies and some hydraulic equipment suppliers provide an oil analysis service. As a guideline, we recom mend that servo systems be provided with filtration sufficient to achieve Class 0 or Class 1 specifications. For hydraulic systems which must function dependably, or where ex tended service life of the components is required, the level of cleanliness should fall in the Class 2 to Class 4 category. Finally, hydraulic systems which are used on an infrequent basis, or those which do not require an extreme level of
dependability, can operate with fluid in the Class 4 to Class 6 range. To achieve a specific level of cleanliness, we must of course select the proper filtration for the system. Unfortunately, the degree of filtration required can only be estimated. The level of cleanliness must be then checked by taking test samples of fluid from the system. From experience we have found that the nominal filter rating as listed in the chart below nor mally achieves the specified levels of cleanliness
Let us now look at the types of filtering medias available and some of the considerations which affect the performance of the filter.
Application
Servo System Hydraulic system with piston pumps, piston motors, flow controls, reducing valves. (Extended service life for any type component) Hydraulic system with gear or vane pumps Hydraulic system with infrequent duty cycle, and non critical com ponents
20-251-1
Class 4 to Class 5
401-1
Class 6
- 380 -
. ' : : . . -,
.
'-
J . - .. .. . . . ). , . ., . . . ' . .
. .
0 ,. . ' 1 . . . . . . . ..-.... . .... . . . . . . .. .... , - . . . . . . , . " . . . .. . " . . . . . , . . . . . - . . . . . .. . ' . . . ' . I ,. 't ,,. . . ' . . . . . . . . . .. . . . "' . . . , . . .. . . :' . . . . ' . . ... , . . :... .. . . . . . t' J . . t. I . . . . . - . .
.. .
. :
.
,
., .
. .
'
'
-.
'
. f . . . .
'
:.
. .
'.
,. .
..
..
..
. .
'
.,
..
. . , .. . I ' . .. .
. . . .
Mesh No.
200 325
100
60
238
149
74
44
1 9
i J.I
_t _
1 49JJ
The advantage of the relatively expensive weaving process used in the construction of a surface type filtering media, is the precision control over the pore size in the final product. For this reason surface type filters are normally given an ab solute rating. An absolute rating of 149 microns, for in stance, means none of the holes in the filtering media will be larger than 149 microns. An absolute rating does not mean that the filter absolutely will not pass particles larger than its largest pore.
- 381 -
There are several reasons why particles larger than the ab solute rating can migrate through the filtering media. First, the openings formed by the weaving process are not per fectly rigid. If, for example, a 160 micron particle were to be lodged in the center of a 149 micron opening, the pressure differential from inlet to outlet of the filter could create enough force on the particle to deform the previously square opening, allowing this particle to pass through the media. Second, the contaminant itself may not be perfectly rigid. The force due to the pressure differential can easily extrude 0-ring fragments, and other similar substances, through the smaller openings. Finally, we must consider the fact that all particles are not perfectly dimensioned. A steel splinter, for example may be many times larger in length than the ab solute rating of the filtering media. However, this same splin ter can also be so narrow that it can penetrate the filtering media without even touching the wire mesh. It is then free to pass through the system, causing damage because of its larger dimension.
as accurately controlled as they are in the weaving process for surface filtering medias, depth filters are normally given a nomina/ rating. A nominal rating of 10 microns simply means that the largest percentage of the pores in the element has a dimension of 10 microns or less. Such an element will remove most of the particles 10 microns or larger, while at the same time allowing a few of these larger particles to pass through. On the other hand, it will also remove many par tides smaller than 10 microns. Today depth type elements are readily available with nominal ratings in the range of 1 to 25 microns, with the most common being the 10 micron element. The depth filter offers two major advantages. First, the element has a higher dirt retention capability because it cap tures particles in a volume of filtering media, rather than on a surface area. Generally, this results in depth elements having a longer service life. The second major advantage offered by depth filtration is that these elements, when bonded cor rectly, are mechanically stronger. They can withstand a higher pressure differential before they collapse or rupture. This also increases the service life since full flow can be for ced through a partially clogged element, as long as the pressure differential is high enough. For the most part , the construction material determines the maximum pressure dif ferential the element can withstand. The chart indicates the maximum practical pressure differential for various filtering medias.
.. .
. : -<. :':
; I
. .. .
.. , .
' . . .
; . .-. . . 1 .
-
..
'
,'
.:
I.
..
I .
...
.. ..
..
. .
. .
'
..
I. .
.
.
. . . .. .
O
, II
'
'
.>
.
:.:---. . - "" -
. ;--
.::.:_< : ;_ .
. I.
. IL I
There are two ways to approach the problem as to where the filter should be located in the hydraulic system. The first avenue of thi king is based on the assumption that dirt is n constantly being generated and ingested by the hydraulic system. By placing a filter downstream of the source we can keep the entire system clean, or at least within acceptable limits of cleanliness. The second way to approach the problem is based on the assumption that contamination is always present in the hydraulic system. If we make this assumption, then the logical place for the filter's location is before the oil enters the critical component or components. In this way the filter acts as a barrier between the damaging contamination and the precision component (s).
- 382 -
Locating the filter in your hydraulic system requires a clear understanding of all factors. Let us now consider the ad vantages and disadvantages of suction, pressure and return line filtration.
ADVANTAGES
The suction strainer, from a filtration standpoint, places the filtering media in an ideal location. Both fluid velocity and pressure differential across the element are, out of necessity, extremely low at this point. This increases the filter's efficiency since high fluid velocities are not present to disturb the collected particles, and there is very little pressure force to cause particle migration through the media. Also, the filter is in an ideal location for preventing contamination within the reservoir from entering the system where it can cause damage to critical clearances in pumps, valves and actuators.
SUCTION FILTRATION
Suction filtration is achieved by locating a filtering media between the reservoir and the hydraulic pump. The most common practice involves immersing a "suction strainer" in the hydraulic reservoir which is threaded onto the end of the suction line. Generally, the strainer is oriented horizontally, well below the minimum oil level in the reser voir. It is also good practice to orient the suction strainer a minimum of three inches from the bottom of the reservoir to avoid the possibility of picking up contamination which has settled out of the hydraulic fluid. A typical suction strainer is shown in the illustration.
DISADVANTAGES
The advantages of suction filtration are strongly out weighed by the disadvantage of the pressure drop created by the element. We have shown in Chapter 1 the extreme precautions which must be observed when determining the suction conditions for the hydraulic pump. Any benefit the suction filter offers by keeping contamination out of the pump, is offset by the possibility of damaging the pump because of cavitation. The low pressure dif ferential, which may be sufficient to push oil through a clean element, is not always adequate to supply the required flow when the element becomes partially clogged. To provide an adequate service life, the suction filter must be grossly oversized and maintained on a more frequent basis. Another major disadvantage of the suction strainer is that it is located inside the oil reservoir which makes it in convenient to service. It is for this reason many suction strainers in industrial hydraulic systems go unserviced un til they starve the pump and cause cavitation damage. Due to these disadvantages, a fine degree of filtration at the inlet of the pump is specifically not recommended. lt is possible to install a course filtering media at this location simply to prevent large objects, (nuts, bolts, etc.) from causing catastrophic pump failure . However, even this type of filtration requires definite precautions. When electi g to use a suction strainer it is advisable to n select the most coarse mesh avmlable. We recommend nothing finer than 100 mesh or preferably 60 mesh screen. This strainer should be adequately oversized so that the pressure versus flow characteristics are negligable. Second, the suction strainer should be provided with a safety by-pass check valve. It is important to check the pressure override characteristics of this bypass check valve. This valve must be able to pass the full flow without causing a pressure differential that ex ceeds the vacuum capabilities of the pump. Also, a vacuum gauge should be located at the pump's inlet port so that the vacuum conditions can be continuously monitored during operation. This, of course, indicates the
Threaded Connectio n (
-Hi
!' ,.
rt (
Filtering Media
- 383 -
condition of the suction strainer. One final recom mendation is that the suction strainer should be made as easy to serv ice as possible. This can be accomplished by locating a gasketed access cover on the top plate of the reservoir, directly above the suction strainer. This allows removal of the strainer without draining oil from the reser voir. The cover should be clearly labeled as to its purpose. One last precaution is that the element should be con tained in a plastic bag before it is removed from the suc tion line. This prevents the collected contamination from falling into the reservoir when the element is removed.
Filter Head
PRESSURE FILTERS
Filter
Filter Bowl
DISADVANTAGES
The major disadvantage of pressure filtration is that both the housing and the element itself must be designed to withstand not only high system pressure but also the pressure spikes which occur during operation. To meet such pressure requirements the filter is somewhat more expensive both in initial cost and future element replacement. This is why pressure filtration is normally reserved for servo systems and other components which have a low dirt tolerance. A pressure filter can, however, be used in any system which requires a high degree of reliability, or where extended life expectancy of standard components is desired. A technical disadvantage of pressure filtration is that pressure transients and high flow velocities tend to con tinually disturb the contaminants which are collected by the filtering media. The high pressure forces and the con tinuous motion of particles allow more contaminants to pass through the filtering media than would be common with other types of filtration. This, of course, has a ten clancy to reduce the efficiency of the filtering media.
A pressure filter is nothi g more than a filter element con n tained in a housing which can withstand full system pressure. Generally speaking, a pressure filter can be located in any of the pressure lines downstream of the pump. It provides maximum protection for the component located directly downstream of the filter's outlet. Pressure filters are commonly used to protect high precision equip ment such as electronic servo valves and piston type hydraulic motors. A typical filter is shown in the cross sectional illustration.
ADVANTAGES
Probably the most favorable aspect of a pressure filter is that it can operate with very find filtration rates (1 micron nominal) and still have an acceptable life expectancy for the element. This is due to the fact that there is ample pressure available to force an oil flow through the minute passages in the filtering media.
The most important criteria when selecting a pressure filter for your application is the operating system pressure and the
- 384 -
collapse pressure rating of the element. The fact is, that pressure at the filter's inlet is governed by the pressure set ting of the main relief valve while pressure at the filter's outlet is determined solely by the load conditions. With little or no load induced pressure, it is possible to develop a con siderable pressure drop across the element. This is par ticularly true during cold start-ups or for elements which have been in service for some time and have many pores plugged with contamination. Unless the element can withstand this high pressure differential, it is susceptible to rupture. Of course, if this is allowed to happen the filter immediately dumps a high concentration of contamination directly into the component it was supposed to protect. A common practice used to prevent an element from rup turing is the use of a by-pass check valve in the head of the filter. As the filter becomes more and more clogged with con tamination the pressure drop across the element increases until the cracking pressure of the by-pass check valve (Chap ter 4) is reached. Once the by-pass opens, oil passes directly through the filter head, without being filtered. Unfortunately, if the filter is allowed to continue operating in the by-pass condition, it no longer provides the intended protection for the system or system components. Today, fail-safe filtration is possible because filter elements are now available that can withstand full system pressure without collapsing. This type of element allows the media to become so clogged with contamination that the fi!ter will cause a flow control function before the element will rupture. This means contamination will not be able to pass into the critical parts of the system. The system has fail-safe filtration because without a by-pass, the end actuator w stall due to ill the lack of oil rather !han damage the filter element.
Filter Media
This basket prevents the collected contaminants from entering the reservoir when the element is removed.
(Courtesy of The Hycon Corp.)
Return line filtration is based on the assumption that a clean hydraulic system will remain clean if the contamination is filtered out of the fluid soon after it is ingested or created by the system. If the reservoir is properly designed and gasketed, return line filtration is the ideal choice for the majority of standard hydraulic systems.
ADVANTAGES
By locating a filter in the return line connection to the reser voir we can take advantage of three ideal conditions. First, there is sufficient pressllre available to force an oil flow through a fine filtering media. This not only allows micronic filtration {typically 10 microns) but provides favorable life ex pectancy for the filtering elements. Although pressure is available, it is not high enough to complicate the design of the filter housing or element. The second advantage then, is that a high degree of filtering efficiency can be achieved with a less expensive element design. Since return line elements do not require high collapse pressure ratings, return line filtration is far more economical than is pressure filtration. The third advantage is related to the fact that a properly designed system has relatively low return line flow velocities. Such a flow allows efficient filtering since collected con taminants are not disturbed.
- 385 -
DISADVANTAGES
A disadvantage of return line filtration is that if con tamination exists in the reservoir, then it must pass through every system component before being removed by the filter. Second, some components cannot withstand the varying, flow related, back pressure created by the return line filter. Case drain lines on pumps and motors, for instance, must be connected directly to the reservoir without passing through the filter. This allows a percentage of the flow to return to the reservoir without being filtered. Also, return line fUtration has limited application possibilities in systems which must be decompressed (Chapter 4) rapidly.
f.!
. ;'
Return line filtration is a log ical solution to contaminati n o related problems, only if we make the assumption that the reservoir, and the oil it contains, is clean. Of course, this is possible only if proper maintenance procedures are adhered to. Such procedures should include: - Filling the reservoir only with properly filtered oil (newly refined oil is not clean by hydraulic standards). Whenever a component is temporarily removed from the system, the opening(s) should be covered or capped with plastic plugs. Remember, most harmful contamina tion cannot be seen. - Before removing a component, thoroughly clean the im mediate area with a degreasing solvent. - Do not run the system without the return line filter element in place. - Be sure all gaskets on suction and return line flanges , and access covers are properly fitted. Never weld on the reservoir or plumbing if the system is in service. Another consideration when electing to use return line filtration is the important role the filler/breather cap plays in keeping ambient dirt out of the fluid. Unfortunately, many of the filler/breather caps available do not provide adequate filtration of the air drawn into the reservoir. Ideally, the filtration rate of the filler/breather should be identical to that of the return line filter. This can only be accomplished by specifying a high quality filler/breather for the reservoir. Likewise, the filler cap should be maintained on a regular basis. Finally, when considering a return line filter, remember the return line flow rate can be higher than the flow produced by the pump. If, for example, a cylinder with a 2:1 area ratio is being used, we must consider the flow intensification this type of actuator creates. When sizing the filter, the maximum return flow valve must be used even if this flow rate exists only for a small portion of the total cycle.
- 386 -
Second, it is of the utmost importance that the designer size the filter so that it will operate correctly during cold start-up when the fluid is at its highest viscosity (Chapter 1)_ Since the oil must pass through microscopic pores in the filtering media, it is easy to understand why the filter is more suscep table to high pressure drops during cold start-up than is any other system component. A filter element which collapses and ruptures, or a by-pass valve which opens during cold start-up, provides little protection for the system. This pressure drop information for viscous fluids is not generally published and must be requested from the filter manufac turer.
It is important to note that the aforementioned inspection ap plies to all filter types . The clogging indicator for a pressure filter operates slightly differently since it must sense the pressure drop across the element. As shown in the cross sec tion it does this by subtracting the effects of the outlet pressure from that at the inlet. However, if the element rup tures, the indicator will sense a low pressure differential and give the indication that the element is clean.
0 @ is sensed on
The pressure differential works against this area . . .
FILTER MAINTENANCE
The best filter in the best possible location, will not be able to perform its required function if it is not maintained properly. Unfortunately, there is no rule of thumb, for recommending a time interval for filter inspection and/or element replacement. Therefore, it is the responsibility of maintenance personnel to develop a maintenance schedule, and then follow the schedule faithfully. Guidelines in establishing this schedule are given in the chart.
----ffii
area equal to . . .
Hourly during initial start-up Weekly when daily inspection is found to be unnecessary Daily during first week of operation
CLOGGING INDICATORS
When checking the condition of a filter, do not rely solely on the clogging indicator if the filter is so equipped. A clogging indicator gives a visual or electrical indication of the pressure differential required to force a fluid flow through the filtering media. For example, with return line filters we can assume the pressure at the filter's outlet is zero (atmospheric). Therefore, with this type of filter, the indicator is simply a pressure gauge or pressure switch which senses the pressure at the filter's inlet. Visual indicators may be calibrated in PSI, however, they are more often color coded to indicate the filter's condition. For example, green indicates the filter is clean, yellow indicates the filter is clogging but satisfactory for continued use, and red indicates servicing is needed im mediately. The problem encountered when relying solely on the indicator is that the devise has no way of determining if the element is clean, or whether the element has ruptured. For this reason we suggest that the element be removed and visually inspected on a regular basis.
Filter Element
SYMBOLS
As shown in the following chart, accessory items can be represented in symbol form to aid in circuit design. You will notice that the chart does not list the symbols for modular manifolds since this topic was described adequately in the text. We have also included symbols for some other ac cessory items which were not covered in this chapter.
- 387 -
1 - -- 1
-
Symbol
Description Pressure switch with fixed pressure differential Pressure switch with fixed pressure differential and leakage port Pressure switch with adjustable pressure differential Pressure gauge Pressure gauge with snubber
L.!.J
- - -
C?
L!..J p
*
r\
l
<g
t
I 4
(!)
I 5
I 6
..... T
- __j
I
Filter with electrical indicator and by-pass valve
"------1
_j
Filter with pressure gauge indicator and by-pass valve
- 389 -
Pressure filter with pressure differential mechanical indicator and by-pass valve
CONCLUSION
This chapter has been devoted to a study of the more popular accessory items which are available for use with in dustrial hydraulic systems. These items included pressure switches, pressure gauges, gauge protectors, modular manifolds, accumulators and filters. Although these different product groups have very little in common on a functional basis, they all play an important role in proper operation,
easier maintenance and trouble free life of the hydraulic system. In consideration of pressure switches we have attempted to relate the operational characteristics of the different designs (piston and Bourdon tube) to the intended application . We have also compared operation of the Bourdon tube pressure switch with that of the pressure gauge and have indicated some of the installation precautions common to these two devices.
- 390 -
The modular manifold has been presented as a viable means to provide better serviceability, and reduce the amount of leakage in the hydraulic system. Although the discussion was limited to the design concept of one particular type of manifolding system, the designer should be aware that the modular concept has a much broader significance. Today's more specialized modules are reducing leakage, providing easier serviceability, and allowing a more compact design, The machine tool and press industries are but two examples where specialized modular componentry is rapidly gaining popularity. We hav asked, however, that the interested reader look into these specialized modules individually. The gas charged accumulator has been introduced as a com ponent with many application possibilities. This single item can reduce pump size and installed horsepower, compensate for leakage, provide an emergency energy reserve, recover energy which would otherwise be wasted, compensate for thermal changes, reduce noise, and dampen pressure surges
in the hydraulic system. The application information for ac cumulators included a discussion of Boyle's Law, adiabatic and isothermal pressure volume relationships, calculation of the available volume of oil which is stored in the ac cumulator, and determination of the precharge pressure limits. The final component discussed was the hydraulic oil filter. By selecting this item as the last component covered in this chapter, we hope to leave you with the impression that this single item is a manditory accessory for all hydraulic systems. It is impossible to achieve a satisfactory life ex pectancy for any high performance system or component unless the control of contamination is dealt with properly. To aid the designer in selecting a proper filtration system, we have discussed the different types of filtering media. We have also listed the advantages and disadvantages offered by each possible filter location. These included suction, pressure and return line filters.
- 391 -