Technical Data 33kV GIS GV3
Technical Data 33kV GIS GV3
Technical Data 33kV GIS GV3
1 Description Ratings & Electrical Requirements General Details Manufacturers Name Typical Layout and sectional Drg of Switchgear supplied to Australian environment Switchgear Model No Type 2 Applicable Standards Enclosure Circuit Breaker Curren Transformers Voltage Transformers 3 General Performance Details Rated Frequency Rated Voltage Highest Voltage Rated Insulation Level: One minute power frequency withstand voltage Impulse withstand Rated Short Time Current Rated Duration of Short Circuit Peak withstand current Rated Fifteen-Minute DC Withstand Voltage of Parts Directly Connected to Power Cables: Between Phases Between All Phases and Earth Operating Cycle Configurations & Model Nos
o
Unit
Performance Data*
TAMCO REFER DRG NOS CC/33GIS/08/2008 SHTS 1&2 CC/33GIS/08/2008 SHT 3 GV3 GAS INSULATED
Hz kV (RMS) kV
50 33 36
kV DC kV DC
GV3 GV3D
SF6 Gas Density Pressure at 20 C Bus chamber Breaker chamber Minimum SF6 Gas Density Pressure at 20 oC 4 Enclosure Material ( Main Tank and LV compartment) Thickness of material ( main Tank) Thickness of material ( main Tank)
Tamco 33kV Gas Insulated Switchgear Model No GV3 *Note: Some parameters may be subject to change without notice
Kg/cm2 Kg/cm
2
1.35 1.35
Kg/cm2
1.2
STEEL 6 mm 2
1 OF 5
TAMCO 33kV GAS INSULATED SWITCHGEAR SCHEDULE OF TECHNICAL DATA Separate compartments for each of mm
VCB, DISCONNECTOR SWITCH, BUSBAR AND CABLE COMPARTMENTS
Normal SF6 Gas Operating Pressure Type of Pressure Relief Device Location 5 Circuit Breakers Rated Short Circuit Making Current Rated AC component Short Circuit Breaking Current DC Component of Short Circuit Breaking Current TRV Peak Value for Terminal Faults at Rated Short Circuit Breaking Current (uc) Time Co-ordinate (t3) Time Delay (td) Voltage Co-ordinate (u ) Time Co-ordinate (t )Rate of Rise (uc/t3) Rate of Rise First-Pole-to-Clear Factor Rated Power Frequency Recovery Voltage
1 1
Kg/cm2
1.35
BURSTING DISC FITTED TO EACH COMPARTMENT BACK & TOP OF ENCLOSURE
kAp kA(rms)
63 25 43%
kV s s kV s Kv/ s
kV (RMS)
36
Small Inductive Breaking Current: Rated Small Induction Breaking Current Maximum Instantaneous Value of Current chopped by Circuit Breakers when breaking Small Inductive Currents Cable-Charging Breaking Current: Rated Cable-Charging Breaking Current Maximum Instantaneous Value of Current chopped by Circuit Breakers when breaking Cable Charging Currents Rated Out of Phase Breaking Current A (RMS) A (RMS) 50 3 A (RMS) A (RMS) 20 3
A (RMS)
6.25
Maximum TRV when Breaking Cable-Charging Current up to rated Value: On Supply Side of Circuit Breaker On Load Side of Circuit Breaker Opening Time Maximum Arching Time Rated Maximum Total Break Time Closing Time Rated Normal Current kV (Peak) kV (Peak) ms ms ms ms A 36 64 27 14.7 < 54 < 50 630/1250/ 2000/2500
Tamco 33kV Gas Insulated Switchgear Model No GV3 *Note: Some parameters may be subject to change without notice
2 OF 5
TAMCO 33kV GAS INSULATED SWITCHGEAR SCHEDULE OF TECHNICAL DATA Length of Each Break 6 Earthing Devices Rated Circuit Withstand Current Duration of Short Circuit 7 Busbars & Connectors Main Busbar Rating Primary Busbar Insulation Busbar Material Busbar Insulation medium Temperature Rise of Busbars at Rated Current Resistance of Main contacts of VCB 8 Combined Disconnector/Earthing Switch Insulating Medium Disconnector Switch Rated Voltage Rated Power Frequency Withstand Voltage: Common Value Across The isolating Contact Rated Power Impulse Withstand Voltage: Common Value Across The isolating Contact Rated peak withstand current 9 Cubicle Degree of Protection: HV compartment LV compartment Whether Space Heater is provided in the Switchgear 10 Circuit Breakers Type of Circuit Breaker (i.e. whether Vacuum of SF6) Make of Vacuum Interrupter Number of breaks per Pole Length of Each Break Material of Current Carrying Conductors Type of Main Current Contact/Material Material of Contact Surfaces Type of Arc Control Devices Type of Isolating Contacts: mm VACUUM (SURROUNDED BY SF6 GAS) EATON OR EQUIVALENT SINGLE BREAK PER POLE 23 COPPER BUTT CHROMIUM COPPER VACUUM IP65 IP42 YES kVp kVp kAp 200 210 UP TO 31.5 kV kV 70 80 kV SF6 OFF LOAD TYPE 36
o
mm
23
kA (RMS) sec
UP TO 31.5 3
kA (RMS) kV
56.1 22-35
ohm
Tamco 33kV Gas Insulated Switchgear Model No GV3 *Note: Some parameters may be subject to change without notice
3 OF 5
TAMCO 33kV GAS INSULATED SWITCHGEAR SCHEDULE OF TECHNICAL DATA On Circuit Breaker On Fixed Portion Material of Contacts 11 12 Interlocks Earthing Earthing of Circuits Earthing of Busbar Method of Circuit Earthing 13 Durability Operating Design Life (Rated Current) Contact Life at Rated Interrupting Capacity Type of Power Closing Devices Method of Opening Devices 14 Recommended Maintenance Intervals Recommended Life Expectancy Operating Mechanism Contacts & Interrupting Mechanisms Control & Ancillary Gear 15 Operational Facts Whether Closing Spring can be Charged with the Circuit Breaker in the Closed Position Whether Circuit Breaker can be Closed whilst the Closing Spring is being charged Whether Locking Facilities are provided for the Manual Tripping of the Circuit Breaker Whether the following Position Indicators are provided for Circuit Breaker: Spring Charged Spring Free ON OFF Earth ON Earth OFF 16 Dimensions and Weights Width mm YES YES YES YES
FOR SINGLE BUS & DOUBLE BUS
Times Times
YES NO YES
600 800
NOTE: FOR 600MM WIDE PANEL VOLTAGE TEST PLUGS AT REAR NOT FITTED
Depth Height
mm mm
1925 TO 2580 DEPENDING ON RATING & CONFIGURATION 1900 TO 2500 DEPENDING ON RATING & CONFIGURATION
Tamco 33kV Gas Insulated Switchgear Model No GV3 *Note: Some parameters may be subject to change without notice
4 OF 5
TAMCO 33kV GAS INSULATED SWITCHGEAR SCHEDULE OF TECHNICAL DATA Weights Kg APPROX 1700 TO 2,000 DEPENDING ON SIZE AND QUANTUM OF CTS AND PANEL WIDTH
17
Cable Terminations Type of Cable Termination Size Make PLUG IN TYPE - CONNEX UP TO SIZE 4 PFISTERER OR EQUIVALENT
18
Voltage Transformers Whether 3 Phase or Single Phase VTS are employed Type of VT Whether VTs Withdrawable Type Position in Panel Provision of VT Primary Isolation switch 3 X 1 SINGLE PHASE EPOXY RESIN YES PLUG IN TYPE AT TOP OF PANEL YES
19
Tamco 33kV Gas Insulated Switchgear Model No GV3 *Note: Some parameters may be subject to change without notice
5 OF 5