ComPacAVPAPDS 020509
ComPacAVPAPDS 020509
ComPacAVPAPDS 020509
The Marvair
ComPac
I and ComPac
II air conditioners
are used primarily to cool electronic and communication
equipment shelters. Due to the high internal heat load, these
shelters require cooling even when outside temperatures
drop below 60F (15C). The ComPac I and ComPac II air
conditioners have the necessary controls and components for
operation during these (less than 60F [15C]) temperatures.
The primary difference between the two models is that the
ComPac
I and ComPac
I & ComPac
II 2 to 6 Ton
Vertical Wall Mount Air Conditioners
Models AVPA24-30-36-42-48-60-72
1 ComPac AvPA PD, 2f09
supersedes 1f06
Standard Features
Designed for Operation in
Low Ambient Conditions
Low ambient control cycles
condenser fan to maintain
proper refrigerant pressures.
Three minute by-pass of
the low pressure switch for
start-up of compressor when
outdoor temperatures are
below 55F (13C).
Factory built-in economizer.*
High Efficiency
High efficiency compressor.
Lanced fins and rifled tubing
on many condenser &
evaporator coils.
Built-in Reliability
High pressure switch and low
pressure switch with lockout
protects refrigerant circuit.
Three minute delay on make
for short cycle protection.
Remote Alarm Capability
Dry contacts can be used for
remote alarm or notification
upon air conditioner lockout.
Ease of Installation
Sloped top with flashing
eliminates need of rainhood.
Built-in mounting flanges
facilitate installation and
minimize chance of water
leaks.
Supply and return openings
exactly match previous
models.
Factory installed disconnect
on all 208/230v units,
optional 460V units.
Rugged Construction
Copper tube, aluminum fin
evaporator & condenser coils.
Factory installed heaters on
discharge side of evaporator
coil (optional)
Baked on neutral beige finish
over galvanneal steel for
maximum cabinet life. (Other
finishes are available.)
Ease of Service
Service access valves are
standard.
Standard 2 (50 mm) pleated
filter changeable from
outside.
All major components are
readily accessible.
Front Control Panel allows
easy access and complies
with NEC clearance codes
on redundant side-by-side
systems.
LEDs indicate operational
status and fault conditions.
AVPA36ACA-100C
*ComPac
First Factory
Installed Economizer
Marvairs ComPac
.
The WebStat allows remote users to view or change
set points. See the WebStat Product Data Sheet.
3 ComPac AvPA PD, 2f09
The ComPac
I and ComPac
II air conditioners
were designed and are built to stringent requirements
of the communications/electronic shelter. Applications
occur that have special requirements. Numerous
options are available for the ComPac I and ComPac II
air conditioners that meet these special needs.
Hard Start Kit - Used on single phase equipment to
give the compressor higher starting torque under low
voltage conditions. (Field installed only) (Note: Not
recommended for use on scroll compressors.)
Extreme Duty Package - ComPac
I and ComPac
II A/C - The Extreme Duty Package allows selected
Marvair
II air conditioners (economizer units) will operate
from -20F to 130F (-29 to 54C).
The Extreme Duty Package includes a suction
line accumulator, thermal expansion valve (TXV),
crankcase heater, hard start kit, and an outdoor
thermostat and fan cycle switch. The fan cycle
control is standard on all ComPac air conditioners
and operates based upon the liquid line pressure.
The outside thermostat opens whenever the outside
temperature is below 50F (10C) and closes when
the outside temperature is 50F (10C) or higher.
Whenever the temperature is below 50F (10C), the
fan cycle switch is in the circuit; when temperatures
are 50F (10C) or higher, the fan cycle switch is not
in the circuit. The outdoor thermostat is used with a
TXV to prevent excessive cycling or hunting of the
TXV.
Dehumidification ComPac
I and ComPac
II A/C
Humidity controller overrides thermostat and allows
electric heat to operate simultaneously with cooling.
See Dehumidification Application Bulletin for details.
Note: The electrical characteristics and requirements
of air conditioners with the dehumidification option are
different from standard air conditioners. Refer to the
appropriate Summary Rating Charts for the electrical
characteristics of units with Electric Reheat.
Coastal Environment Package ComPac
I A/C
only Recommended for units to be installed near
an ocean or on seacoast. Includes corrosion resistant
fasteners, sealed condenser fan motor, sealed control
box, protective coating applied to all exposed internal
copper in the condenser section and an impregnated
polyurethane coating on the condenser coil. See
Coastal Environmental Technical Bulletin for more
details.
External Low Noise Blower (ELNB) ComPac
I
and ComPac
II air conditioner.
Note: Filter used in Return Filter Grille is 1 (25 mm)
thick.
For AVPA24
20 x 12 (508 mm x 305 mm) P/N 80671
For AVPA30,36
28 x 14 (711 mm x 356 mm) P/N 80672
For AVPA42,48,60,72
30 x 16 (762 mm x 406 mm) P/N 80673
Security Cages. Deters theft of the air conditioner
and components. Constructed of 1 by 11 gauge
square tube and 3/4, # 9 expanded metal. Hinges
and latch are made from steel plate. The complete
cage is powder coated for longevity and to match the
color of Marvair air conditioners. Field installed.
ComPac AvPA PD, 2f09 +
ComPac
II A/C
only A minimum position potentiometer that can
be adjusted to prevent the economizer damper
from closing completely. This control ensures that
whenever the evaporator fan is operating, fresh air
is being introduced into the building. Field or factory
installed.
Hot Gas By-pass ComPac
I and ComPac
II A/C
- Units are built with up to 65% efficient filters.
Filters are rated according to ASHRAE Dust Spot Test.
ComPac II units have a prefilter on outside air. Not
to be used with HEPA or absolute filters.
Color - ComPac
I and ComPac
II air conditioners
are available in five different cabinet colors -the
standard Marvair
I A/C
C = ComPac
II A/C
Electric Heat kW
000 = No Heat 090 = 9 kW
040 = 4 kW 100 = 10 kW
050 = 5 kW 150 = 15 kW
080 - 8 kW
Special Option Code
R = Electric Reheat
U = Scroll Comp.
ELECT. HEAT 000 = None 040 = 4 kw 050 = 5 kw 060 = 6 kw 080 = 8 kw 090 = 9 kw 100 = 10 kw 120 = 12 kw 150 = 15 kw
BASIC
MODEL
VOLTAGE
PHASE
CKT #1 CKT #1 CKT #1 CKT #1 CKT #1 CKT #1 CKT #1 CKT #1 CKT #2 CKT #1 CKT #2
MCA MFS MCA MFS MCA MFS MCA MFS MCA MFS MCA MFS MCA MFS MCA MFS MCA MFS MCA MFS MCA MFS
AVPA24ACA 208-230/1 18.9 30 22.3 30 27.4 30 32.7 35 43.0 45 53.5 60
AVPA30ACA 208-230/1 21.9 35 23.4 35 28.5 35 33.8 35 44.1 45 54.6 60 23.4 35 41.6 45 28.5 35 52.1 60
AVPA36ACA 208-230/1 26.7 40 26.7 40 28.5 40 33.8 40 44.1 45 54.6 60 26.7 40 41.6 45 28.5 40 52.1 60
AVPA42ACA 208-230/1 30.7 50 30.7 50 55.2 60 30.7 50 41.6 45 30.7 50 52.1 60
AVPA48ACA 208-230/1 33.2 50 33.2 50 55.2 60 33.2 50 41.6 45 33.2 50 52.1 60
AVPA60ACA 208-230/1 40.8 60 40.8 60 57.3 60 40.8 60 41.6 45 40.8 60 52.1 60
AVPA72ACA 208-230/1 45.6 60 45.6 60 57.3 60 45.6 60 41.6 45 45.6 60 52.1 60
AVPA24ACC 208-230/3 13.3 20 19.4 20 28.5 30 37.5 40
AVPA30ACC 208-230/3 15.6 20 20.5 25 29.6 30 38.6 40 47.6 50
AVPA36ACC 208-230/3 20.8 30 20.8 30 29.6 30 38.6 40 47.6 50
AVPA42ACC 208-230/3 22.9 35 22.9 35 30.2 35 39.2 40 48.2 50
AVPA48ACC 208-230/3 23.0 35 23.0 35 30.2 35 39.2 40 48.2 50
AVPA60ACC 208-230/3 27.5 40 27.5 40 32.3 40 41.3 45 50.3 60
AVPA72ACC 208-230/3 36.1 50 36.1 50 36.1 50 41.3 50 50.3 60
AVPA24ACD 460/3 7.8 15 9.7 15 14.2 15 18.7 20 23.2 25
AVPA30ACD 460/3 9.2 15 10.3 15 14.8 15 19.3 20 23.8 25
AVPA36ACD 460/3 9.7 15 10.3 15 14.8 15 19.3 20 23.8 25
AVPA42ACD 460/3 10.6 15 10.6 15 15.1 20 19.6 20 24.1 25
AVPA48ACD 460/3 10.7 15 10.6 15 15.1 20 19.6 20 24.1 25
AVPA60ACD 460/3 13.6 20 13.6 20 16.1 20 20.6 25 25.1 30
AVPA72ACD 460/3 17.3 25 17.3 25 17.3 25 20.6 25 25.1 30
MCA = Minimum Circuit Ampacity (Wire Size Amps). MFS = Maximum Fuse Size or HACR circuit breaker. MCA and MFS calculated at 240V.
Lockout Mode: If either the high or low pressure switch opens twice on the same call for cooling, the control
board enters into the lockout mode. In the lockout mode, the compressor is turned off, the alarm output is
energized and the status LEDs will blink to indicate which fault has occurred. If there is a call for air flow, the
indoor blower will remain energized. When the lockout condition has cleared, the unit will reset if the demand
of the thermostat is removed or when power is reset. The ComPac
I & ComPac
II Air Conditioners
DISCONNECT
ACCESS
C
FRONT VIEW
OUTSIDE AIR HOOD
A
AIR OUTLET
J
K
B
R.H. SIDE VIEW
HEATER
ACCESS
L
F
E
D
G
2.0"/
51 mm
2.0"/
51 mm
I
AIR INLET
SLOTS IN
CII ONLY
K.O.'s**
2.0"/51 mm
2.0"/
51 mm
3/4" (19 mm)
I.D. DRAIN
(9 PLC'S)
BOTTOM MTG. BRKT.
W/MTG. HOLE LOCATIONS
4-9/16
AA AA
BB
3-9/16 (90 mm)
(116 mm)
1-1/16 (27 mm)
3/8 (10 mm)
TM
M
BACK VIEW
P
O
2.0"
51 mm
34-1/2"
876 mm
18-1/2"
470 mm
50-3/4"
1289 mm
67.0"
1702 mm
N
SUPPLY AIR
OPENING
H
RETURN AIR
OPENING
MOUNTING HOLES
CTR TO CTR
K.O.'s**
H
E
MODEL A B C D E F G H I J K L M N O P AA BB
24 (in.) 39 1/2 17 1/4 71 1/2 8 20 1/2 12 27 11/16 20 3 3/4 36 5/16 1 11/16 7/8 38 27 11/16 26 3 5/8 17 5/8 35 1/4
24 (mm) 1003 438 1816 203 521 305 703 508 95 922 43 22 965 703 660 92 448 895
30/36 (in.) 44 9/16 17 1/4 71 1/2 8 18 14 28 7/16 28 3 3/4 36 5/16 1 11/16 7/8 43 1/8 27 11/16 26 3 5/8 20 1/4 40 1/2
30/36 (mm) 1132 438 1816 203 457 356 722 711 95 922 43 22 1095 703 660 92 514 1029
NOTE: Dimensional tolerance 1/16
* CI does not have side louvers
** KO=knockouts-sized to accept 3/4 (19 mm) x 1 (25 mm) electrical conduit
H dimension centered between A dimension
ComPac AvPA PD, 2f09 10
Dimensional Data - AVPA42-60 ComPac
I Air Conditioners
11 ComPac AvPA PD, 2f09
Dimensional Data - AVPA42-60 ComPac
II Air Conditioners
ComPac AvPA PD, 2f09 12
P.O. Box 400 Cordele, GA 31010
156 Seedling Drive Cordele, GA 31015
Ph: 229-273-3636 Fax: 229-273-5154
Email: marvair@airxcel.com Internet: www.marvair.com
Please consult the Marvair
website at www.marvair.com for the latest product literature. Complete installation instructions are in the
ComPac
Air Conditioners I&O Manual. Detailed dimensional data is available upon request. A complete warranty statement can be found in
each products Installation/Operation Manual, on our website or by contacting Marvair at 229-273-3636. As part of the Marvair continuous
improvement program, specifications are subject to change without notice.
Dimensional Data - AVPA72 ComPac
I & ComPac
II Air Conditioners
7-9/16"
192 mm
29-3/4"
756 mm 1-5/16"
33 mm
Supply Air
30" x 10" (Nominal)
762 mm x 254 mm
3/8" (10 mm)
Diameter Mounting
Holes
2-11/16"
68 mm
Return Air
30" x 16" (Nominal)
762 mm x 406 mm
Electrical KO's
2-11/16"
68 mm
2" (51 mm)
44-7/8"
1140 mm
43-1/8"
1095 mm
40-3/8"
1026 mm
93-1/16"
2364 mm
Pull Disconnect
Access Door
41-3/4"
1061 mm
3-1/4" (83 mm)
18"
457 mm
17-1/2"
445 mm
17-1/2"
445 mm
17-1/2"
445 mm
17-1/2"
445 mm
1-3/4"
45 mm
Fan
Guard
BACK VIEW FRONT VIEW
30-1/4"
768 mm
3/4" (19 mm)
I.D. DRAIN
94-5/16"
2395 mm
2" (51mm)
1/2"
13 mm
15-3/4"
400 mm
30-1/4"
768 mm
9-3/4"
248 mm
Slots in
C2 only
2-7/8" 73 (mm)
1-7/8 (48 mm)
2 (51 mm)
Damper
Hood
(CI only)
Electrical
Knockout
46-5/16"
1176 mm
27-5/8"
694 mm
35-5/16"
897 mm
Coil Guard
Air Inlet
Both Sides
LEFT SIDE VIEW
7-9/16"
192 mm
2" (51 mm)