3ph To 6ph
3ph To 6ph
3ph To 6ph
Presented before the 60th Annual Georgia Tech Protective Relay Conference May 2-5, 2006
yellow to reference the phases. White is sometimes used rather than blue, but white is also commonly used for neutral in low voltage applications too. Green or bare copper is generally used for a ground conductor.
Phase or Bushing Names
Examples from Industry IEC 60076-1
Transformer Phasors
II
(i)
I
(i)
III
(i)
H2 or X
H H1
X Y
Primary
Reference Angle 1U
H3
y
Secondary
(ii)
(ii)
(ii)
Primary
ii
(i)
(i)
(i)
1W
1V
Transformer Symbols
(ii) (ii) (ii)
Primary
Secondary
Secondary
X0
X1
X2
X3
Figure 1 - Example Transformer Symbology and Terminations Many times the figures that are used to model a transformer and show its connections do not clearly indicate which windings share a common core leg, and do not clearly indicate the polarity of the coupled windings, at least to the first time reviewer. To make the winding polarity more evident in this paper, a variation of the drawings above will be presented that makes it clearer where the polarity of the windings is and which windings share a common transformer leg. See Figure 2. We need to define the term Winding to avoid confusion. In various sources the term winding can refer to either a single continuous coil of wire on a single core leg, or collectively to a 3 phase set of windings connected to the 1U, 1V, and 1W bushings, or even the group of windings associated with a particular phase. Herein, a winding is a single continuous coil of wire on a single core leg, a winding set is the set of three windings that constitute the three phases, each on different core legs, with a common terminal voltage level (e.g., 1U, 1V, and 1W), and a phase set will refer to the two or more windings that are found on a common core leg. See Figure 2.
The windings in the transformer figures are given the terms W1-9. The winding sets associated with the various voltage levels, each on a different core leg, are: Winding Set 1: W1, W2, and W3 Winding Set 2: W4, W5, and W6 Winding Set 3: W7, W8, and W9 (only seen herein in zigzag transformers). The windings sharing a common core leg are: Core Leg 1: W1 and W4 Core Leg 2: W2 and W5 Core Leg 3: W3 and W6 (Windings W7, W8 and W9, used herein for zigzag windings, are hard to classify into a particular leg since zigzag windings cross-connect core phase legs.) (In the figures, core leg 1 is abbreviated as A, core leg 2 as B, and core leg as C.) The windings by themselves are passive devices and which winding is given the number W1, W2, or W3 (or W4, W5, W6, W7, W8, or W9) will not matter initially, but it will matter when we connect the second set of windings to the various bushings since this will affect phase shift of positive (and negative) sequence voltages across the transformer.
Figure 2 - Basic Transformer Representation The paper will show the balanced transformer output current in terms of the flux in the core that is due to load current, which invites discussion on how load flux distributes in a core. There are two issues with core design that affect differential relaying. First, we normally think in terms of power flow in a transformer as staying within a phase set (i.e., current in a single phase on the secondary of a three phase transformer will generate current in the primary only of that same transformer leg), but this is not always the case. 3
Normally when current flows in the secondary winding, it generates a flux in that leg and an equal but opposing flux is generated by load current flowing in the primary on that same phase leg so that the level of excitation flux remains constant. However, in a three phase transformer where all phases are magnetically linked, there is some coupling and power transfer between the phases, especially in the 3 legged core design. The inter-phase coupling provides a mechanism where an external fault on one phase can cause current on unfaulted phases and is part of the limitation on sensitivity of a transformer differential relay. The highest inter-phase coupling occurs in a three legged core transformer. Note that in a 3 legged core all flux that leaves a leg must pass through another leg or air. Examine Figure 2. Assume some current flows in the W4 winding. This current will tend to create flux in a direction that demagnetizes the W4 core, resulting in lower back e.m.f. on the W1 primary. Since in this core the flux in the A leg divides between the B and C legs, the W2 and W3 windings could supply the current/flux to counter the W4 load. However, W4 is generally wired directly under or interleaved within W1, so the W1/W4 coupling is stronger than W2/W4 or W3/W4 coupling. Also, it can be shown that the source that will supply the load current with the least reactive current flow is W1. Hence virtually all the current required to counter the W4 load flux will come from W1. If current did come from W2 or W3 the transformer differential relay would tend toward tripping. In the 4 legged and core form designs, there are flux paths that allow flux to flow without entering other phases, so each phase is more independent of what is occurring in the other phases and is indicated in Figure 2 as the zero sequence flux path. In the 5 legged / 4 core designs, where each phase winding encircles two cores, used mostly on low cost distribution transformers, the two outside phases are fairly independent of each other, but the inside phase can be affected by events in either of the two outside phases. Directly related, a significant difference between core designs that can affect differential protection is whether the core can support zero sequence voltage. If there is no independent zero sequence flux path, as in the three legged core design, and zero sequence voltage is applied to the windings, the excitation flux is forced to travel through air to complete the flux circuit. Excitation current will be very high and can make a transformer differential operate. This high excitation current is sometimes masked in differential relays by schemes that filter zero sequence current from the differential relay. This can be done by connecting CTs in delta, or in numeric relays, by algorithms that measure zero sequence current entering the windings and subtract it from the differential analysis. The ability to remove the zero sequence current mathematically in modern numeric differential relays has reduced the motivation to connect differential relay CTs in delta in most applications. While the connection diagrams to follow will generally show a three legged core, this is only for convenience. The connection diagrams are applicable to either 3x1 phase designs or any three phase core. In all designs, the windings for any given phase are still on a common leg of the core. Positive Sequence Phasing and Even More Possible Winding Configurations The entire paper assumes positive sequence phase rotation and that all the configuration diagrams were built on positive sequence phase rotation. There are actually more connections than listed if one wishes to do phase rotation changes within the transformer by swapping two phases on only one side of the transformer and leaving the third in place in a way that would convert positive sequence voltage on one side of the transformer to negative sequence voltage on the other side. This seems a fairly remote possibility.
Transformer Winding Configurations There are 4 basic winding configurations for the typical large 3 phase power transformers: delta, wye, auto, and zigzag. Within the delta, wye, and zigzag groups, there are multiple means of creating the winding configuration. There is some help available in that only a few versions of each show up in regular practice, but this does not rule out any version showing up in ones work (or from a relay manufacturers point of view, showing up in the relay application) so the possibility should not be excluded from ones plans. Scott T and mid-winding tapped delta transformers are not considered herein.
Figure 3 - Six Ways to Wire a Wye Winding Delta Windings Configurations Given a set of 3 windings W1, W2, and W3, and three transformer phase bushings U, V, W, and again assuming that positive sequence rotation is to be maintained, there are 6 ways the windings and bushings can be interconnected, as shown in Figure 4. Again, some of the methods would not be seen in normal practice. The most common ones would be D1 (= DAB in 6
common US market terminology) and D11 (= DAC in common US market terminology). The D5 and D7 configurations are seen in some documentation of transformer connections in the international market.
Auto-Transformer Winding Configurations There is no flexibility in how an auto-transformer is wired. The only way to obtain a phase shift is to rename the phases from one side to another, but this is quite uncommon; i.e., given a phase set of W 1 and W 4, then if 1U is connected to W1 then 2U would almost invariable be connected to the W4.
Figure 5 - An Auto Transformer Winding. The auto-transformer will not be dealt with any further in this paper. The auto-transformer can be treated as a simple wye-wye transformer for current differential calculations. Phase shift in any delta tertiary connection would be treated as a separate delta/wye connection. Zigzag (Interconnected Star) Winding Configurations In much literature on transformers, the term interconnected star is used in lieu of zigzag. However, most engineers in the power engineering business know with at least a little familiarity what is meant by zigzag and this term will be used herein. Zigzag transformers do not see much application in the US. Most engineers are familiar with a zigzag transformer from its application as a ground reference on an ungrounded system. The wye/zigzag transformer is apparently used in some distribution applications due to the lower cost of a high voltage primary wye winding versus a similar voltage delta winding. When the primary is ungrounded wye, the secondary needs to be zigzag in order to remain an effectively grounded secondary. The zigzag winding also is used for obtaining non-standard phase shifts. It is capable of delivering 0 0 0 secondary power with 0 , +/-30 or +/-60 phase shifts relative to the primary, depending on primary winding configuration. A zigzag winding is a series connection of two windings whose voltages are 60 out of phase. The two windings are typically the same voltage magnitude, but custom phase shifts can be created if the voltage magnitude of the two windings differs. There are two basic ways to create a zigzag winding: Connect the U leg in series with V leg (called a ZUV or a ZAB) or Connect the U leg in series with W leg (called a ZUW or a ZAC) The polarity marks of the two windings either face toward one another or face away from one another. In order to get other phase shifts, some configurations may invert polarity connections,
0
change which side of the winding the bushings are connected to, or introduce a 120 phase shift by swapping the U, V, and W bushings connections. The inter-phase coupling that a zigzag winding creates results in primary current patterns that may be quite unlike what one expects with delta and wye primary windings. Unless a delta tertiary is provided, the primary of a three legged core zigzag transformer cannot supply current that will create zero sequence flux in the core. Even if the primary is connected in delta, the winding cannot support circulating I0 since this creates zero sequence flux. For example: Assume a zigzag secondary and a 1 per unit line to ground fault on the zigzag side. If the primary were wye (see Figure 18), then the current is 1pu on one phase lead, and -1pu on another, similar to a delta/wye bank response. However, if the primary were delta (see Figure 19), the current in the lines feeding the primary will see 2 pu current on one phase and -1 pu on the other two phases, similar to what would be seen for a double delta transformation. If power is to flow from the zigzag side to the wye or delta side, a zero sequence flux path or a buried tertiary may be necessary for the transformer to carry any unbalanced loading, even for phase to phase unbalance on a delta primary. A zigzag winding used as a grounding bank is shown in Figure 6. When a phase U line to ground load is applied, the current in the load will want to return via windings W4 and W3. Current in W4 and W3 will demagnetize the two respective core legs, which will in turn allow phase to ground voltage on the W and V to cause current flow in W1 and W6 to restore a flux balance condition. The net effect is that equal current flows in every phase of the zigzag bank, which constitutes zero sequence current into the system.
Figure 6 - Zigzag Grounding Bank Given the 6 windings and three bushings associated with a zigzag winding configuration, there are actually 24 different winding configurations connections that could be made. Again, there are two general types, ZUV (=ZAB) and ZUW (=ZAC), defined by how the two sets of windings are interconnected and can be seen by inspection of Figure 7. Figure 7 shows what appears to be 0 the more common variations of ZUV and ZUW but note that a 180 inversion of each is possible by
simply inverting the neutral and bushing connection ends, giving 4 more possible variations of ZUV , ZUW or inverted ZUV- or ZUW-. See figures for examples. For each R1 and R2 swap of the U, V, and W bushing connections one should be able to see 8 more similar variations of the zigzag winding. To fully define a zigzag connection one needs to specify both the phase shift and whether it is a based on ZUV or ZUW . For example, an inspection of Figure 7 will show it is possible to get a Z1 0 (30 ) phase shift by either the Z1UV connection shown in Figure 7 or by starting with a Z5UW 0 connection and then introducing a 120 phase shift by appropriate U/V/W swapping.
10
11
12
13
14
15
16
17
II III
Y0
D11
11
ii
iii
Y0
D11
Z11uw
Yd1
Dy1
Yz1
Y0
1
Y0 D11
D1
Y0
Z 11uw
Yd5
Dy5
Yz5
Y0
D11
Y0
Y6 D7 Z7uv
Yd6
Dd6
Dz6
Y0
6
Y6
D11
D11
D5
Z5 uw
Yd11
Dy11
Yz11
Y0
Y0 D11
11
D1
Y0
Z1uv
Wye Primary
D1
D1
D11
Z11UW
Dd4
Dz4
D 11
D 11
D7
Z7uv
Yd7
Dy7
Yz7
Y0
D1
Y0
D5
Y6
Z5uw
Dd8
Dz8
D1
D1
D5
Z5uw
Dd10
Dz10
10
D 11
D 11
D1
Z1uv
= (1)
NPr ik CI2 3 =N k I
Pr i C 3
NSec k CI4 5 = N k I =
Sec
NSec
k I
C 5
C 6
where N1 and N2 are the number of turns in winding set 1 and 2, and kC is a proportionality constant that would be specific to the core, most notably the cross sectional dimensions and permeability. This kC factor will cancel out of the current differential equations so we do not need to know its specific value. We can invert the concepts of (1) to state the current in terms of the core flux in each leg of the transformer, and we can start to introduce matrix representations of the equations. For winding set W123: I W1 k 1 0 0 1 0 k 1
2
= I2 0 k 1 W IW 3 0 0
(2)
where: 20
k 1 =
1 NPr ik C
(3)
The equations for W456 are similar. In a condensed matrix math form, (2) becomes more compact: I123 = k ,Pri 123 This format will be used extensively in the coming material. It might be noted that when an equation is bold it indicates that the elements in the equation represent matrices, not simply constants. Also, a bold multiplication symbol, x, indicates the multiplication of matrices using appropriate matrix math. Recall the above equations are referring to load flux, not excitation flux. For load induced flux, we can assume that in each leg of the transformer the flux that is caused by load current sums to 0 in normal operation. The equations are: Phase Leg 1: W1 + W 4 = 0 Phase Leg 2: W 2 + W 5 = 0 Phase Leg 3: W 3 + W 6 = 0 (4)
(5)
The equation assumes the summation (not the difference) of the flux is zero. There is a parallel with how currents will be handled. In the equations to come, we will assume a positive current generates positive flux, so in the current differential function, the error current is the summation of currents coming into the relay. Using the abbreviated matrix form of (3) this equality can be stated as: 123 + 456 = 0 (6)
or alternatively, we can say that on each leg that the ratio of flux from the two core flux sources (e.g., W1 and W4) is -1. The current that is delivered by the transformer is the flux times the appropriate k factor (2). This current on the two sides of the transformer will differ in the inverse of the transformer turns ratio (3) so we need to multiply across by the turns ratio in the manner seen below. Using the abbreviated form of (4) and (6) the equation that represents normal operation is: NPri k 1 123 + NSec k 2 456 = 0 (7)
Putting this equation into a more recognizable form, if we expand (7) and cancel the common kC factor from (3) we obtain the current balance equation: NPr iIW 1 + NSecIW 4 = 0 NPr iIW 2 + NSecIW 5 = 0
(8)
21
In a wye/wye transformer with no phase shift of positive sequence voltages and currents, Yy0, the bushing currents are equal to the winding currents (I1U = IW1, I1V = IW2, I1W = IW3, I2U = IW4, I2V = IW5, and I2W = IW6), equation (8) tells us how to sense flux balance. The balanced condition can be directly measured by a differential relay that only monitors by a simple ratio difference. (A real world transformer differential relay would also need to have a block for inrush detection algorithm as well.) For any other winding or CT configuration than Yy0 we need a systematic method of creating phase compensation equations so that various combined or inverted winding currents on the relay inputs will be recognized as a balanced condition. To proceed, we need to determine the current seen at the transformer bushings and the relay for any given winding and CT configuration. Negative Sequence Transformation Before proceeding, some acknowledgement should be given to the fact that there are even more possible wye and delta connections than listed, if one opens up the thought process of swapping two phases at a time rather than three, on only one side of the transformer, in which case one transforms positive sequence phase rotation to negative sequence phase rotation across the transformer. Since this transformation would not be done in normal practice, it was not considered in development of this paper. Wye Winding Transformations There are 6 ways to connect a wye winding, as described earlier. Each modifies the W1, W2, and W3 (or W4,5,6,etc.) current by some transformation factor. For instance, if we connect the U, V, and W bushings to the non-polarity side of windings W1, W2, and W3, respectively, as is done in the Y6 connection, we have effectively multiplied all currents by -1. Each connection method has its own transformation effect. The equations below state the effective transformation in a mathematical format. This format will be useful when there are several transformations in series and we need to multiply them together to find the total effect. The equations give the current that will be seen on bushings U, V, and W for a given current in W1, W2, and W3, but where current is stated in terms of IW =k. and k is as given in (3). All equations relate IUVW to 123 because the flux generated by the load current on each leg is the common element for all winding sets. There are six 3x3 matrices that represent how the winding currents could be transformed by the various wye connection. In the condensed matrix equations on the right side, it can be seen that only four matrix transformations, 1, -1, R1, and R2, are needed to represent the 6 wye transformation matrices. The value of this reduction in possible transformations will become clearer when delta and zigzag windings are analyzed further below. The R1 and R2 transformations rotate the bushing and winding connections. Given currents I1, I2, and I3, the effect of each rotation is to say: R (1200 CCW shift):
1
Inew = Iold
1 3
Inew = Iold
2 1
Inew = Iold
3 2
(9)
old
R (120 old I
2
CW shift) :
new
=
2
I I
new old
=
3
new
=I
1
The matrix form of (9), R1 and R2, will be seen in the equations to follow. In the equations to follow, note a positive flux generates a positive current.
22
0 0
1 0 0
I = 1 0 0 V 0 k 0
1 0 0
I = 0 0 1 V 0 k 1 0
0 0 0
1 IU 0 k Y6 (Negated Y0): I = V 0 IW
0 1 (13)
1 0 k 0
0 0
0 IUVW = -1 k 123 2 1 0 0 k 3
I U 0
1 0 0 k 1 0 k
Y2 (Negated Y8):
I = V 0 0
IW
0 IU
0 0
3 0
0 0
1 k
0 1 (15)
I = 1 V 0 k 0
IW
0 IUVW = -1 R 2 k 123 2 1 0 0 0 k 3
0 0
where k is as defined by (3) for the particular winding. Note that every matrix can be written of as the negative of one of the other matrices in the list, as noted in the left column. If one says a negated transformation matrix is not unique, there are really only 3 unique matrices above. Delta Winding Transformations If we connect a winding in delta, the current seen by the relay is a summation of two phase currents. There are two basic forms of a delta, D1 connection (i.e., a DAB connection), and a D11 connection (i.e., a DAC connection). Given currents I1, I2, and I3: D old I
1( AB )
new
=I
1
old
Iold = I I
2 2
new
old
new
=I
3
old
I
1
old
(16)
old
D old I
11( AC )
new
=I
1
old
I I
new old
=I
2
old
new
=I
3
old
I
2
Phase swaps (R1 and R2, above) combine with the above connections to create 6 different ways to connect a delta. A mathematical way to say the effect of the 6 possible delta connections on net phase current is given below. As with the wye connections, there are six 3x3 matrices that 23
represent how the winding currents could be transformed by the various delta connections. To perform all transformations listed below, two additional matrix transformation operations, D1 and D2, are needed over what was introduced for the wye transformations. Actually, only one of these is required. Any D1 (or D11) transformation can be restated in terms of a D11 (or D1) operation. For instance, D1 = -1 x R1 x D11 (compare (17) and (22), below). Delta Transformations IU 1 1 0 0 k 1 0 k 0 0 1
D1 (DAB):
I = V 0 1 IW 1
IU 1 1 k D5 (D1 x R2 swap): IW I = V 1
0 1 (18)
1 0 0 k
0 1
0 IUVW = R 2 D1 k 123 2 1 0 0 k 3
IU 0 1 D9 (D1 x R1 swap): IW I = 1 V 0 k 1
1 k
0 1 (19)
0 IUVW = R 1 D1 k 123 2 1 0 0 0 k 3
0 1
IU 1 0 D11 (DAC): I = 1 V 0 k IW 0
1 k
1 0
1 1 0 0
0 0 1
IU
1 1 k
D3 (D11 x R2 swap): IW
I = V 1 0 1
1 0 k 1
IU 1 0 k D7 (D11 x R1 swap): IW I = V 0
0 1 (22)
1 1 0 k
1 0
where k is as defined by (3) for the particular winding. Similar to what was seen for the wye connections, one might say that there are only 3 unique matrices above. Every one can be written of as the negative of one of the other matrices in the list. For eventual calculation of the overall transformation equations we will need to know the transformer turns ratio. Referring to figures 10 and 16 for winding numbers, in a delta/wye and delta/delta transformer, the turns ratios are:
24
Dy Turns Ratio:
RDy =
(23)
Dd Turns Ratio:
RDd =
Double Delta Transformations A double delta refers to the case where there are two delta transformations in series. We can simplify the equations somewhat by pre-multiplying the two matrices together. Some examples of double delta transformation matrices include: 1 1 DD
1x1
1 0 1
=D D =
1 1
0 1 1 1 1 0
11 1 = 1 2 1
2 1
(24)
1 0
1 1 0 DD
1x11
0 1 1 1 = 1 2 1 0 1
1 2 1 1
1 1 1 = -1 R DD
2 1x1
= D D =
1 11
0 1
(25)
1 0
1 1
1 0
1 1 0
1 1 1
DD
11x11
= D D = 1 1 0 1 1 R = DD 11 11 0 1 1 0 1
1 (26) 1 1
2
1 1x1
Note the double deltas found in normal practice can be redefined as a combination of DD1x1, R1, R2, and -1 transformation factors. The double delta transformation does not arise too often, but it is physically possible, does occur, and is easy enough for relay compensation. Targeting and relay testing will be especially problematic whenever a double delta is utilized because current on any phase is seen in all the differential comparators. Zigzag Winding Transformations
To analyze current across a zigzag winding, let us continue to assume that, in balanced conditions, all load flux in each leg sums to zero. Use the Z1UV transformer of Figure 7 for our discussion (one can also refer to Figure 18) and assume the flux on the primary winding set will be named U,V,W . Taking into account that W4,5,6 can be restated in terms of their equivalent W1,2,3 the flux balance says that: U,Pri + W1 W 3 = 0 V,Pri + W 2 W1 = 0 W,Pri + W 3 W 2 = 0 Let us convert the flux to the equivalent current equations, using (1). We have: (27)
25
NPr ik CIU,Pr i + NZk C ( IU,Z IW ,Z ) =0 NPr ik CIV,Pr i + NZk C ( IV,Z IU,Z ) =0 NPr ik CIW ,Pr i + NZk C ( IW ,Z IV,Z =0 Solving (25) for IUVW, primary: IU,Pr i = I NZ (I I ) NPr i U,Z W ,Z
(28)
Z = N V,Pr i
(I
V,Z
I
U,Z
) )
(29)
NPr i
Z = N W,Pr i
(I
W ,Z
I
V,Z
NPr i
1 IU,Z I
V ,Z
1 1 0
(30)
V.Pri I
1 1 I
W ,Z
The analysis will start by viewing the Z winding set side as an effective wye connection; terminal current is equal to winding current. We wish to see how the current will appear to the lines on the other side of the transformer. An examination of (29) and (30) will show that the primary will see the secondary in a fashion that is similar to a delta transformation. Using equations (1) and (2), let us convert (30) to an equation closer to the format used for the wye and delta transformations earlier in the paper. Also note that when solving (28) for IPri we introduced a negative correlation between primary current and secondary current. We do not want the negative correlation. We want to have the concept of a positive flux creates a positive current on both windings, so we will introduce an x -1 factor. IU,Pri I 1 0 1 k ,z 0 0 k 0 0 1(U,Z )
NZ = 1 1
(31)
V,Pri
N
Pr i
1 1 0
,z
2( V,Z )
I W ,Pri
3( W ,Z )
,z
where k,Z=1/(NZkC). Note that the matrix is the same as for a D11 connection, typical of all the wye-zigzag connection transformations. We can reorganize this to the form of the delta and wye winding equations. We need two different equations: one for the transformer as seen from the zigzag side bushings and one as seen from the primary side bushings. First, from the zigzag side, the current in the zigzag windings has the same transformation as a Y0 connection (though other Y# transformations are possible via phase swaps and winding connection reversals). From the high side we will have a variety of transformation equations that vary with how equations (27) through (30) work out for the particular configuration. If the primary is connected in delta, the equations have additional transformation factors, described below. 26
Zigzag Transformations, Seen From Zigzag Side IU,Z 1 0 0 k ,z 0 0 1 0 2 k ,z 3 IUVW = 1 k ,Z 123 (32)
ZZ Side
I 0 1 = 0 0 V.Z IW ,Z 0 0 1 0
k ,z
where k Z =
1 . NZ k C
Phase swaps and winding connection reversal will affect the transformation equations by adding -1, R1, and R2 transformation factors. Zigzag Transformations, Seen From Wye Primary IU,Pr i 1 0 1 k ,Pr i 1 0 0 0 0 1 0 2 IUVW = D11 k ,Pri 123 (33)
Z1 (ZAB/UV):
I 1 = V,Pr i IW ,Pr i
k ,Pr i
0 IU,Pr i
1 1
k ,Pr i 3
1 0 k ,Pr i
Z7 (=-Z1):
I = V,Pr i 1 IW ,Pr i
1 0 0 1 0
k ,Pr i
0 1
k ,Pr i 3 0 1
IU,Pr i 1
1 0 k ,Pr i 1 0
k ,Pr i
0 2
(35)
1 0 1
k ,Pr i 3
IU,Pr i Z5 (=-Z11):
1 1 k ,Pr i
I = V,Pr i 0 IW ,Pr i 0
1 1 0 1 1 0
k ,Pr i
k ,Pr i 3
where k ,Pr i =
1 . NPr ik C
Phase swaps and winding connection reversal will affect the transformation equations by adding -1, R1, and R2 transformations. Zigzag Transformations, Seen From D1 Primary The zigzag with a delta winding introduces the issue of back to back delta transformations. Since a zigzag is effectively a delta as seen from the primary, we will have a double delta transformation. The approach is to simply multiply the two delta effects together as was seen in the double delta discussions above. i.e., if a primary is connected in delta, we simply add the
27
appropriate delta transformation to the overall transformation equation. The equation can be simplified a bit using the D1xD11 transformation previously mentioned (25). I U,Pr i 2 1 1 k ,Pr i 0 0 1
D1xZ1 (ZUV):
k ,Pr i
0 2 k ,Pr i 3
0 1
k ,Pr i
0 2 k ,Pr i 3
IUVW = D1 D1 k 123
(38)
The reader can use this example to determine how a D11 connection changes the equations. For eventual calculation of overall transformation equations we will need to know the transformer turns ratio. Referring to Figure 18 and 19 for winding numbers and looking at the windings on one core leg, in a classical zigzag transformer, the turns ratios are: NW 4 = NW 7 Yz Ratio: R Yz = NW1 VY,LL 3 or NW7 = VZ,LL NW 4 NW1 VD,LL =3 NW 4 or NW7 VZ,LL (39)
Dz Ratio:
RDz =
As a side note, setting N4 and N7 different from one another allows a continuous variety of phase shifts across the transformer. Such transformers are used in harmonic cancellation techniques in VFD applications and in large phase shifting transformers used for power flow control in important transmission lines. CT Connections Transformations A wye CT is fairly straightforward and simply changes the transformer current by a specific ratio. A complication can occur if a CT connection is made backwards such that it adds a -1 factor to the current balance equation. This -1 factor might arise if one of the CT sets is connected backwards relative to the relay manufacturers instruction manual. IU,Re lay NCT
NCT 0
0 IV NCT IW
(40)
IU,Re lay
NCT 0
0 NCT 0 0
YCT6 :
IW
28
A delta CT complicates the transformer differential relay compensation by adding a second delta transformation effect. A delta CT connection will virtually always be a D1 or a D11 form transformation, but other connections are not impossible. IU,Re lay DCT1 (DAB): NCT 0 0 1 1 0 IU 1 IV 1 IW = NCT D1 I UVW,Relay IUVW (43)
NCT
0 NCT
0 1 0 0 1 0 NCT 0 1
DCT11 (DAC):
IV,Re lay 0 = 0
IW,Re lay
It might be possible also to have reverse connected CTs that are then connected in delta, resulting in negated versions of DCT1 and DCT11, creating DCT7 and DCT5, respectively.
29
Through Current: U Comparator: Error Current: Through Current: V Comparator: Error Current: Through Current: W Comparator: Error Current:
Compensated
and I + I
Compensated
1 Compensated
4 Compensated
(45)
I I
Compensated 2 Compensated 2
and I + I
Compensated
5 Compensated
(46)
I I
Compensated 3 Compensated 3
and I + I
Compensated
6 Compensated
(47)
The comparators were named U, V, and W above, but be aware that this can lead to some confusion on faulted phase identification when delta connections are involved due to the associated inter-connection of phases.
(48)
(49)
Note that in balanced conditions 123 + 456 = 0, and as seen by comparing (48) and (49), what started out as a balanced condition in the transformer has become two different current values at the relay. The balanced flux has been modified by: Transformer Turns (part of k) Transformer winding connections CT ratios CT connections
30
The approach used in numeric relays is to compensate by adding multiplying factors CF115 and CF13.8 to (48) to create a target multiplication factor that puts the equivalency back into the sensed current, so that the error current is 0 in the differential comparator equations (43), (44), and (45). The initial unmodified compensation equation is: CF115 ( NCT,115 D1 k ,115 123
) + CF (
13.8
) = 0
(50)
The part in the parenthesis in (50) represents the two sets of current inputs to the relay IRelay. and CF# represents the math the relay needs to apply to the current to see the currents as equivalent. Let us simplify (50) by first collecting the magnitude compensation adjustments to the left. The resultant equation is: NCT,13.8 CF115
( ( [
-1
-1
) (
D1 123
456
+ CF13.8 = 0
(51)
This allows us to state CF115 in terms of only phase compensation adjustments and CF13.8 in terms of magnitude and phase adjustments. In this case, CF115 has no phase compensation adjustments, but CF13.8 has both magnitude and phase adjustments. To make (51) true, we need: CF115 = 1
-1 CF13.8 = ( -1 k ,115 k ,13.8 NCT,115 NCT,13.8 -1
(52)
) D
(53)
CF13.8 Magnitude Compensation Factor The magnitude effect has to account for the transformer and CT turns ratio. Recall from (1) and (2) that k,# = 1/(N#kC) where N# is the # of transformer coil turns, and kC is a constant for the core design. Recall also the turns ratio calculations of (23). The overall ratio of k,# is: k
,115
-1
NTurns,13.8 NTurns,115
13.8 3 115
= 0.069282
(54)
,13.8
N-1
CT,13.8
5 = 5
200 = 6
(55)
1200
Hence, the relay multiplies the current coming into the 13.8kV side by the factor:
-1 -1
= -1 0.069282 6 (56)
-0.415692 0 0 -0.415692
31
Some may note a missing sqrt (3) factor in this equation that is used to reduce the magnitude of current that is seen after a delta summation. This matter will be discussed later, under Application to Protective Relay Settings. Net Compensation Equations A phase compensation factor is required when different phase transformation factors (e.g., R# or D#) show up in the two phase compensation factors, such as was found in (52) and (53). The compensation is on the currents making it to the relay, so let us give some names to the relay currents: I1,Re lay I115,U,Re lay I2,Re lay = I115,V,Re lay I3,Re lay I115,W ,Re lay I4,Re lay I13.8,U,Re lay I5,Re lay = I13.8,V,Re lay I6,Re lay I13.8,W ,Re lay
(57)
The 115kV phase compensation is the most basic equation possible: I123,Relay I
Compensated
Compensated 123,Relay
I lay 1,Re
Compensated
I 1 0 0 1,Re lay 1 0 I
2,Re lay
Compensated I = 0 2,Re
lay
Compensated I
3,Re lay
0 0 1 I
3,Re lay
The overall (magnitude and phase) 13.8kV compensation equation is: ICompensated = CF13.8,Mag CF 456,Relay 13.8,Phase I 456,Relay I
Compensated
= ( 1 k
,115
-1
N
CT,115
-1
)
I 0 0
D
1 456,Relay
(59)
456,Relay
,13.8
CT,13.8
I lay 4,Re
Compensated
0.415692 0
0 0.415692 0
ICompensated 5,Re =
lay
Compensated I
0.415692
6,Re lay
6,Re lay
(I
4,Re lay
I
5,Re lay
) ) )
(60)
(I
5,Re lay
I
6,Re lay
(I
6,Re lay
I
4,Re lay
6,Re lay
The results of (58) and (60) are then fed into the comparator equations (45), (46), and (47).
32
Example 2 - Dz2 with Delta CT Configuration Let us look at a more complicated application that gives a more involved application of the phase transformation factors. We will use a fairly uncommon transformer and assume someone selects fairly strange CT connections. Lets see if and how the relay could compensate. Dz2 Transformer 115kV (D1) / 13.8kV (Z11(AC/UW)) 20MVA (for IFull Load =100A @ 115kV and 837A @ 13.8kV) Primary CTs 200:5, Y0. Secondary CTs 1200:5, D11 The net 115kV equation is (Note Zigzag with Delta primary created Double Delta): IUVW,Relay,115 = 1 NCT,115 D1 D1 k ,115 123 The net 13.8kV equation is (Note CT is DCT,11): IUVW,Relay,13.8 = D11 NCT,13.8 k ,13.8 456 The overall compensation equation is: D D k ) + CF ( 1 N 115 CT,115 1 1 ,115 123 k ) CF ( D N 13.8 11 CT,13.8 ,13.8 456 =0 (62) (61)
(63)
Again, we can rearrange (63) to bring the magnitude compensation factors to one side of the equation to allow us to state CF115 in terms of only phase compensation adjustments, and CF13.8 in terms of magnitude and phase adjustments. CF
115
( (k
,115
k -1
,13.8
N
CT,115
-1
) ( D
D
1 123
+ (64)
CT,13.8
=0
) (
)
(66)
D1 D1
The magnitude adjustment factor is nearly the same as the previous example, but the Y6 CT
connection added a negative in the previous example, and since this is a delta/zigzag winding, the k is slightly different. Applying (3) and (39) we will find: k ,115 k-1 = ,13.8 NTurns,13.8 NTurns,115 = 3 13.8 = 0.040 115 (67)
and the CT ratio is 6, as it was in the previous example. The net magnitude adjustment factor is:
33
-1
= [ 0.040 6]
(68)
0.240 0 0 0.240
Compensated 123,Relay
(69)
Compensated
1,Re lay
Compensated I = 1 2,Re
lay
0 I
2,Re lay
Compensated
3,Re lay
1 1 I 3,Re lay
This in clearer terms is: I 3,Re = ( 1,Re lay I lay ) Compensated I I I ) =( I1,Re lay
Compensated 2,Re lay 2,Re lay 1,Re lay
(70)
Compensated
=(
I
3,Re lay
I
2,Re lay
3,Re lay
The 13.8kV compensation equation includes a double delta D1xD1 factor, introduced previously (24). The net13.8kV magnitude and phase compensation equation is: ICompensated = CF13.8,Mag CF 456,Relay 13.8,Phase I 456,Relay I456,Relay I lay 4,Re
Compensated ,115 ,13.8 CT,115 CT,13.8 = (k k N N 456,Relay ) ( D1 D1 I -1 -1
(71)
Compensated
0.240
1 1 2
2 1
I 1 4,Re lay 2 I 1 I
5,Re lay
ICompensated 0 5,Re =
lay
0.240
Compensated I
0.240
6,Re lay
6,Re lay
I = 0.240 ( I = 0.240 (
+I
6,Re lay
4,Re lay
2 I 2 I
5,Re lay
) )
(72)
+I
5,Re lay
4,Re lay
6,Re lay
= 0.240
(I
5,Re lay
+I
6,Re lay
2I
4,Re lay
6,Re lay
The results of (70) and (73) are then fed into the comparator equations (43), (44), and (45).
34
Example 3 - Dy1 but Phase Transformations Cancel Out Assume the same system as Example 1 but let us hook the secondary CT in D1. The compensation equation (50) becomes:
) ( + CF
13.8
D N k 1 CT,13.8 ,13.8
456
=0
(73)
The relay sees the same D1 phase compensation on both inputs and hence the relay adds no additional phase compensation transformation to the incoming currents. It will only need to do magnitude compensation. The rest of the compensation factor analysis is approximately the same as the previous examples so will not be developed.
35
It can be seen that just as there are a very large number of possible ways to configure a transformer and its CTs, there is a similarly very large number of possible phase compensation equations that might be needed. However, the relay does not need to have a library in its memory bank of every possible transformer and CT configuration and the resultant phase compensation that it must apply. This paper has made some effort to show that many transformation equations can be seen as the multiplication of 2 or 3 other transformations. Hence, the relay can have a subset of possible transformation equations that can be applied as needed to create the overall compensation equation for a given application. Once these transformation equations are in the relay memory, the next issue is when and how to apply them. The response from the relay manufacturers on how the various transformations are selected and used and presented to the end user varies quite a bit. Some manufacturers supply a set of transformation equations and ask the user to decide how to apply them, given instructions in the manual that hopefully are sufficient. Extremely detailed analysis, such as found in this paper, is not too common though. Documentation and instruction manuals are always subject to misunderstanding, especially by engineers who have limited time to study the matter. This approach puts the user in the think hard because there is lots of room for messing up mode. Some relays, especially the basic lower budget versions each manufacturer supplies, have a reduced degree of support of all the possible transformers and CT connections. This reduces the confusion factor and makes correct setup easier for the mainstream applications, but it is done at the expense of flexibility. Some manufacturers make the setting a bit more user friendly by listing the phase compensation equations that should be used for a given transformer configuration and phase shift. They appear to say that if you know phase shift and a few other items on the transformer, these are the equations you want to use. Without a detailed analysis of where the equations come from a user might be confused and still make a selection error. Some relay manufacturers attempt to remove the chance of user error by having the user state the specific transformer and CT configurations. It becomes the task of the relay internal coding to decide which phase compensation equations are proper for the configuration that was entered. This approach takes the previous bullet one step farther from a good understanding of what is being calculated by the relay, so has its drawbacks too. Hopefully this paper supplies the needed information so that a user can reason through what is going on inside the relay.
Conclusion/Summary
Hopefully the reader has learned from the above material, 1) how the myriad of round the clock power transformers are internally configured, as well as some understanding of the nomenclature and figures that are used, 2) the various ways delta and zigzag transformers can be configured, 3) the ways that the myriad of possible transformer and CTs connections affect the current seen by a transformer differential relay, and 4) how a transformer differential relay can numerically compensate for the differences in any transformer configuration to still determine balanced current conditions.
Author Biographies
Larry Lawhead received a BS degree in Engineering from Duke University in 1982. He worked at Potomac Electric Power Company in the Substation Test and System Protection groups until joining Basler Electric in 1989. Mr. Lawhead has held a variety of Sales and Marketing positions
36
with Basler and is currently Principal Application Engineer, based at Basler's Highland, Illinois, headquarters. Mr. Lawhead is a member of the IEEE-PES and is active on several working groups of the Power Systems Relay Committee. Randy Hamilton is a Principal Electrical Design Engineer for Basler Electric Company. He has worked for Basler for more than 25 years, with experience in test and design in the areas of magnetic transformers, power supplies, voltage regulators, and, for the last ten years, protective relays. Randy graduated Magna Cum Laude from Southern Illinois University. John Horak received his BSEE degree from the University of Houston in 1988 and his MSEE degree, specializing in power system analysis, from the University of Colorado, Denver, in 1995. John joined Basler Electric in 1997 and is a Senior Application Engineer. Previous work included ten years with Stone and Webster Engineering where he was on assignment for six years in the System Protection Engineering offices of Public Service Company of Colorado. His work has included fault calculations, relay coordination settings, control design, and equipment troubleshooting. Other previous employers include Houston Lighting and Power and Chevron. He has authored, coauthored, and presented technical papers at a variety of industry events and conferences. John is a member of IEEE-IAS and -PES and has P.E. license in Colorado.
References
1) ANSI/IEEE C57.12.00 IEEE Standard General Requirements for Liquid Immersed Distribution, Power, and Regulating Transformers 2) IEEE C57.12.70 IEEE Standard Terminal Markings and Connections for Distribution and Power Transformers 3) IEC 60076-1 Power Transformers Part 1: General 4) J&P Transformer Book, A.C. Franklin, D.P. Franklin (12 Edition, 1998, changes author to Martin Heathcote); Butterworth-Heinemann Division, Reed Educational and Professional Publishing Ltd.
th
37
P.A.E. Les P ins 67319 Wasselonn C ede , e x FRA N C ETel +33 3.88.87.101 Fax +33 0 3.88.87.0808 e-mail franceinfo@ basle : r.com No. 59 Heshu Road Loufen Distric (N), n g t Suzho IndustriaPark, 215122 Suzhou u l , , P.R.C hina Tel +86(0)512 8227 2888 Fax +86(0)512 8227 2887 e-mail chinainfo@ basle : r.com 55 Ubi Avenu 1 #03-05 S ingapor e e 408935 Tel +65 68.44.644 Fax +65 5 65.68.44.8902 e-mail : singaporeinfo@ basle r.com