Function The thermo-electric actuator, in conjunction with convertible thermostatic radiator valves, with radiator and underfloor heating systems distribution manifolds and with zone valves, allows automatic shut-off of the system fluid under the control of a room thermostat or of another electrical switching device.
European Directives conformity CE mark as per Directives 89/336 EC and 73/23 EC.
Reference documentation Leaflet 01051 Convertible thermostatic radiator valves for single and two pipe systems, series 455. Leaflet 01072 Zone valves, series 676. Leaflet 01044 Distribution manifolds for underfloor heating systems, series 668. Leaflet 01065 Distribution manifolds for radiator systems, series 663.
Product range Code 656102 Code 656104 Code 656112 Code 656114 Code 656002 Code 656004 Standard thermo-electric actuator Standard thermo-electric actuator Standard thermo-electric actuator with auxiliary microswitch Standard thermo-electric actuator with auxiliary microswitch Thermo-electric actuator with special connection Thermo-electric actuator with special connection Supply 220 V Supply 24 V (ac) or 24 V (dc) Supply 220 V Supply 24 V (ac) or 24 V (dc) Supply 220 V Supply 24 V (ac) or 24 V (dc)
Technical specification - Materials: - protective cover - colour Normally closed Power supply: Starting current: Working current: self-extinguishing polycarbonate white RAL 9010
220 V (ac) - 24 V (ac) - 24 V (dc) 1A 220 V (ac) = 13 mA 24 V (ac) - 24 V (dc) = 140 mA - Power consumption: 3W - Rating of auxiliary microswitch contacts (code 656112/114): 0,8 A (220 V) - Level of protection: IP44 (in vertical position) - Product with double insulation: CE - Max ambient temperature: 50C - Operating time: opening and closing from 120 s to 180 s - Supply cable length: 80 cm
Operating principle With power off, the device (actuator + valve) is normally closed. With power on, the valve opens thanks to the action of a wax expansion thermostatic element, directly controlled by a PTC resistor.
Connection table The following table highlights the connections between the various types of valve body and the thermo-electric actuator types.
CALEFFI
65611
65610
2-
220 V -
2-
220 V 3W
CALEFFI
65611
65610
4-
24 V -
4-
24 V -
CALEFFI
CALEFFI
3W 3W
Constructional details
338
Electrical connections for code 656002, 656004, 656102 and 656104.
339
401
CALEFFI
65611
65610
1 0
2-
220 V -
2-
220 V 3W
CALEFFI
RT
220
65611
65610
4-
24 V -
4-
24 V -
CALEFFI
CALEFFI
3W 3W
225
221
222
227
BROWN BLUE
*480
*481
*482
*483
*484
663
Electrical connections for code 656112 and 656114
1 0
666 - 668
676
677
678
N L
The auxiliary microswitch can be used to switch off the pump when heat is not required and the valves are closed. If the power consumption of the pump is greater than the rating of the contacts at 0,8 A, an intermediate relay switch should be used.
BLACK BLACK BROWN BLUE
RT
RT
*
Discontinued
65600
2-
220 V -
CALEFFI
65600
4-
24 V 3
W
CALEFFI
3W
656002 656004
*670 *671
*6750
652
6620
6621
Special connection The different configuration of some of these series of valves makes necessary the modification of the connection geometry of the thermo-electric actuator. Compared to the standard actuators , actuators code 656002 and 656004 are supplied with a longer control spindle . Attention: actuators 656002 and 656004 cannot be connected to a valve body designed for use with actuators 656102, 656104, 656112 and 656114, and vice-versa.
*672
*673
*674
Discontinued
Fluid-dynamic characteristics Hydraulic characteristics table for 656 actuator + valve body.
Installation - The thermo-electric actuator should be tightened by hand without the use of tools. - The thermo-electric actuator should not be dismantled for possible repair. Such interference could lead to permanent damage. - The actuator should always be fitted in a horizontal or vertical position, never upside-down. In chilled water circuits, positions which allow condensation to get into the actuator are not advisable. - For the correct functioning of the actuator, the electrical circuit shoul be sized on the basis of the starting current. - If it is necessary to control multiple zones with actuators in parallel using the same thermostat, the possibility of including an intermediate relay to prevent electrical overload should be considered. - In assemblies with zone valves or manifolds in manifold boxes, a space of at least 20 mm between the thermo-electric actuator and the frame should be left for possible servicing or replacement. Min. 20 mm
Series
DN 3/8 1/2 3/4 1 3/8 1/2 3/4 1 1/2 3/4 1 3/8 1/2 3/4 3/8 1/2 3/4 3/8 1/2 3/8 1/2 3/8 1/2 3/4 3/8 1/2 3/4 1/2 3/4 1 1/4 1 1/4 1 1/4 1/21 1/21 1/21
kv0,01 (l/h) 185 210 270 440 110 145 225 420 200/110 200/110 200/110 180 200 255 100 135 200 80 125 85 125 178 267 446 119 178 356 277 138 287 287 287 370 370/100 370/100
pmax * (m w.g.) 25 25 18 12 25 25 18 12 10 10 10 25 25 18 25 25 18 25 25 25 25 25 25 12 25 25 12 12 12 25 25 25 12 12 12
338 - 401
339 - 402
455
Elbow thermostatic
220 - 222
40 20 0 60 80
CALEFFI
Straight thermostatic
221 - 223
40 20 0 60 80
CALEFFI
CALEFFI
CALEFFI
CALEFFI
CALEFFI
Reverse valve Double elbow thermostatic Elbow valve thermostatic (old) Straight valve thermostatic (old) Reverse valve (old)
Recommendations for use - When thermo-electric actuators are to be installed on devices which shut-off heat emitters automatically, it is always advisable to use a differential by-pass to control the over-pressure of the system during the partial or total closure of the circuits. For pre-assembled manifolds series 663-668, a differential by-pass with a fixed calibration setting of 2000 mm w.g. is available (code 663000).
480-482
481-482
CALEFFI
CALEFFI
10 8 6 4 2 0
10 8 6 4 2 0
10 8 6 4 2 0
10 8 6 4 2 0
10 8 6 4 2 0
10 8 6 4 2 0
10 8 6 4 2 0
10 8 6 4 2 0
10 8 6 4 2 0
10 8 6 4 2 0
10 8 6 4 2 0
10 8 6 4 2 0
10 8 6 4 2 0
CALEFFI
CALEFFI
10 8 6 4 2 0
CALEFFI
Code 663000
656002, 656004 + 3-way zone valves Valves for underfloor heating systems Elbow valve thermostatic (old) Straight valve thermostatic (old) Single pipe (old)
DN 3/4 1/2 1/2 1/2 3/8 1/2 3/4 3/8 1/2 3/4 1/2
kv0,01 (l/h) 445 140 140 140 178 267 446 119 178 356 247 total
pmax * (m w.g.) 12 25 25 25 25 25 12 25 25 12 12
For installations with series 356-357 dual manifolds, a differential by-pass having a fixed differential pressure setting of 2000 mm w.g. is also available (code 356050).
CALEFFI
Code 356050
Mod. Dep.
356
671-673 674
For centralised installations or installations with rising pipes, a differential by-pass valve is available with an adjustable setting of 1 to 6 m w.g. (series 519).
PN 10
Applications Thermo-electric actuators can be installed: On individual radiators as an alternative to thermostatic controls to allow the radiator valves to be converted from manual to automatic operation, in combination with a room thermostat for each room or zone. In domestic water heating systems, for controlling the temperature of the water heater.
65610
2220 V 3W
CALEFFI
CALEFFI
CALEFFI
In radiator systems, with automatic shut-off of the heat emitter directly at the manifold, with reduced work and cost associated with the electrical connections.
40 20 0 60 80
CALEFFI
RT
CALEFFI
In fan coil systems, if they are to be fitted with valves for automatic shut-off of the fluid. In zoned systems, where reduced dimensions and limited flow rate coefficient at the automatic regulating valve are required.
40 20 0 60 80
CALEFFI
CALEFFI
CALEFFI
RT
CALEFFI Mod. Dep.
357
SPECIFICATION SUMMARIES Series 656002/004/102/104 Thermo-electric actuator. Normally closed. Supply voltage 220 V (ac); 24 V (ac); 24 V (dc). Starting current 1 A. Working current 13 mA (220 V (ac)), 140 mA (24 V (ac) - 24 V (dc)). Rated power consumption 3 W. Level of protection IP44 (in vertical position). Maximum ambient temperature 50C. Operating time of 120 to 180 seconds. Length of supply cable 80 cm. Series 656112/114 Thermo-electric actuator. Normally closed, with auxiliary microswitch. Supply voltage 220 V (ac); 24 V (ac); 24 V (dc). Starting current 1 A. Working current 13 mA (220 V (ac)), 140 mA (24 V (ac) - 24 V (dc)). Rated power consumption 3 W. Level of protection IP44 (in vertical position). Rating of auxiliary microswitch contacts 0,8 A. Maximum ambient temperature 50C. Operating time of 120 to 180 seconds. Length of supply cable 80 cm.
We reserve the right to change our products and their relevant technical data, contained in this publication, at any time and without prior notice.
CALEFFI
CALEFFI S.P.A. I 28010 FONTANETO DAGOGNA (NO) S.R. 229, N.25 TEL.INT. +39 0322 8491 R.A. FAX +39 0322 863723 Http://www.caleffi.com E-mail: info@caleffi.it