Olex Nexan Handbook
Olex Nexan Handbook
Olex Nexan Handbook
2012 EDITION
Pyrolex
Alsecure
The cables that have been keeping Australians safe and secure for 30 years have a new name.
Alsecure is now the name to specify for the cables youve always relied on where safety and security are critical to maintain circuit integrity for mains power, lighting, alarms, pumps and other essential services when under fire. Now, backed by the global resources of Nexans, Olex is, more than ever, your one-stop-shop for the most complete range of performance cables.
SAFETY WARNING
Cables are insulated and sheathed with stable materials which may contain certain toxic sub stances including lead. Insulation and sheathing materials should not be chewed or ingested. Should you require more detailed data regarding materials, please contact our Group Safety Manager on 03 9281 4444 or refer to our web site, www.olex.com.au Installation Cables must be installed in accordance with the requirements of Section 3 Selection and Installation of Wiring Systems in the latest issue of AS/NZS 3000 or the appropriate ruling standard in the country of installation. Cables must also be connected by a licensed electrician, as ruled in the state or country of installation. In particular your attention is drawn to Section 1.5 of the Wiring Rules (AS/NZS 3000) Fundamental Principles. Designers and installers can be assured the products provided by Olex meet the requirements of the relevant cable standard, but must ensure appropriate selection of cables for the electrical installation conditions. Hazardous Areas Installation of wiring and fittings for hazardous areas, e.g. flammable or explosive gas, liquid, dust or solids must comply with Section 7.7 Hazardous Areas, of AS/NZS 3000, and other relevant Australian Standards for specific hazards and occupancies. Technical Note PVC 90C Thermal Rating The current carrying capacities for thermoplastic cables, including flexible cords used as fixed wiring, insulated with V-90 and V-90HT PVC compounds have been based on a conductor operating temperature of 75C (refer AS/NZS 3008.1 Table 1 Note 2).
CONTENTS
Alsecure Envirolex Cables Low Voltage 1 Core 1 Core 1 Core 2 & 3 Core 2 & 3 Core+Earth 2 & 3 Core+Earth 2 & 3 Core+Earth 4 Core+Earth 4 Core+Earth 2 & 3 Core+Earth 2 & 3 Core+Earth 4 Core+Earth 4 Core+Earth Multicore+Earth Multicore+Earth 4 Core 2, 3 & 4 Core Industrial 2 Core, 2, 3 & 4 Core+Earth 2 Core, 2, 3 & 4 Core+Earth 1, 2 & 3 Core 1 Core 2, 3 & 4 Core 5 Core 4 & 5 Core 1 Core 2 Core, Multicore+Earth 2, 3 & 4 Core+Earth 3 & 4 Core+Earth 3 Core+3 Earths Multicore+Earth Multicore+Earth 1 Core Multicore Pairs Pairs
PVC Insulated PVC SDI XLPE/PVC Single Core PVC Flat PVC Flat PVC Circular XLPE/PVC Multicore PVC Circular XLPE/PVC Multicore PVC SWA Circular XLPE/PVC SWA Multicore PVC SWA Circular XLPE/PVC SWA Multicore PVC Control PVC SWA Control XLPE URD Power XLPE Aerial Bundled
9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25
Powerlex PVC OD Cords 28 Powerlex PVC HD Cords 29 Powerlex PVC Cords 30 Versolex HD Single Core 31 Versolex HD Unscreened 32 Versolex HD Unscreened 33 Versolex HD Braid Screened 34 Titanex Single Core 35 Titanex Multi Core 36 Flexolex HD Unscreened 37 Flexolex HD Screened 38 Varolex VSD/EMC 39 PVC Flexible Control 40-41 PVC/EMC Flexible Control 42 Silicone Single Core 43 Silicone Multicore 44 Instrolex Instrumentation 45 Instrolex Instrumentation SWA 46
CONTENTS
Fire Performance 1 Core Multicore Single & Multipair
48 Alsecure Premium Ceramifiable Single Core Flex 49 Alsecure Premium Ceramifiable Multicore Alsecure Premium Ceramifiable Instrumentation & Data 51
Data/Comms Security Security/Audio LAN Coaxial Optical Fibre Telephone Internal Telephone External PVC Garden Lighting Fire Alarm Data Accessories Alco Metal Cable Glands EMC, UW, HUW, AW, HAW Alco Earth Tags Nickel Plated Alco Gland Shrouds
53 54 55 56-57 58 59 60 61 62 63
65-69 70 71
Current Ratings Flexible Cable Cord Colours PVC Flexible Cords Flexible Installation Versolex & Flexolex Welding Aluminium Aerial Copper Aerial Single Phase 2 x 1 Core PVC, XLPE, 110C Single Phase 2 Core PVC, XLPE Three Phase 3 x 1 Core PVC, XLPE, 110C Three Phase 3 & 4 Core PVC, XLPE, 110C General Data Cable Selection Cable Installation Minimum Size of Copper Earthing Conductors Maximum Operating Temperatures DC Resistance 3 Phase Formulae M.C.M. & A.W.G. Conductor Size Conversion Bending Radii & Motor Current Number of Cables in Conduit Cables in Conduit Space Factors Pulling Tension Abbreviations Locations Locations The Olex Cable Range Handbook Subscription The Olex Cable Range
102
107 108
Flame retardant/self-extinguishing Reduced acid, gas and smoke generation Non-corrosive in fire situations Reduced toxicity of fumes during fire Halogen free (i.e. no chlorine, bromine etc.) Lead free No special termination or installation requirements Made in accordance with Australian Standards Alsecure Envirolex cables have been tested according to and comply with the requirements of the single flame tests specified in AS 1660. Alsecure Envirolex products include readily strippable cables for general construction purposes as well as the tougher products commonly found in cables with higher fire performance capability. Alsecure Envirolex materials can also be used as alternatives to all other low voltage power and control cables (refer tables on pages 8 to 25). Cables are available on request, subject to minimum production run. Information on the Alsecure Fire Performance range of cables can be found on pages 47 to 51 of this handbook.
Nom. Main cond. conductor area type mm 2 1.0 1.5 2.5 2.5 4.0 6.0 10.0 16.0 1.5 2.5 Solid Cu Strand Cu Solid Cu Strand Cu Strand Cu Strand Cu Strand Cu Strand Cu Strand Cu Strand Cu
Nom. insul. thick. mm 0.6 0.6 0.6 0.6 0.7 0.7 0.7 0.7 0.6 0.6
Nom. sheath thick. mm 0.9 0.9 1.0 1.0 1.1 1.1 1.2 1.3 0.9 1.0
Approx. mass kg/100m 5.7 7.2 11.0 11.1 15.2 19.2 29.8 43.7 9.4 14.6
Product code
2C+E 1.0 9.0 4.2 1.5 10.0 4.6 2.5 11.2 5.0 2.5 11.7 5.3 2.5 13.4 6.2 2.5 14.5 6.8 4.0 17.0 7.8 6.0 19.7 8.9 3C+E 1.5 12.7 4.6 2.5 14.9 5.3
CTCP02JA002 CTCP05JA002 CTCP06JA002 CTCP07JA002 CTCP09JA002 CTCP11JA002 CTCP13JA002 CTCP15JA002 ETCP05JA003 ETCP07JA003
Note: Alsecure Envirolex cables are lead and halogen free and are suitable for green building installations.
TAGE
RIAL
TAGE
ATED
FIRE RATED
Powering where we live.
Olex has a proud history of cable manufacturing expertise, with more than half a century of experience in the industry. Offering a comprehensive range of low voltage power and control cables, Olex has the cable you need.
MMS
DATA/COMMS
NING
8
MINING
PVC INSULATED
LOW VOLTAGE INDUSTRIAL HIGH VOLTAGE FIRE RATED DATA/COMMS MINING
Single core, 0.6/1kV V-90 insulated, to AS/NZS 5000.1 (unsheathed), copper conductors, 90C.
Nominal Main conductor conductor area type mm 2 0.5 1.0 1.0 1.5 2.5 4 6 10 16 25 35 50 70 95 120 150 185 240 300 400 500 630 1.5 2.5 Solid Cu Solid Cu Strand Cu Strand Cu Strand Cu Strand Cu Strand Cu Strand Cu Strand Cu Compact Cu Compact Cu Compact Cu Compact Cu Compact Cu Strand Cu Strand Cu Strand Cu Compact Cu Strand Cu Strand Cu Strand Cu Strand Cu Single Core Strand Cu Strand Cu
Product code
0.8 2.4 1.0 0.8 2.8 1.6 0.8 2.8 1.5 0.8 3.1 2.0 0.8 3.6 3.2 1.0 4.5 5.1 1.0 5.1 7.1 1.0 6.0 11.1 1.0 6.9 17 1.2 8.4 26 1.2 9.4 35 1.4 10.9 48 1.4 12.4 67 1.6 15.2 96 1.6 17.3 118 1.8 18.8 144 2.0 21.1 180 2.2 24.1 236 2.4 26.9 296 2.6 30.6 376 2.8 34.1 477 2.8 37.8 613 PVC Insulated Copper Earth Conductor 0.6 2.7 1.8 0.7 3.4 3.0
BAAP01AA001 BAAP02AA001 BAAP03AA001 BAAP05AA001 BAAP07AA001 BAAP09AA001 BAAP11AA001 BAAP13AA001 BAAP15AA001 BAAC17AA001 BAAC18AA001 BAAC19AA001 BAAC20AA001 BAAC22AA001 BAAP23AA001 BAAP24AA001 BAAP25AA001 BAAP26AA001 BAAP27AA001 BAAP28AA001 BAAP30AA001 BAAP32AA001 AATP05AA001 AATP07AA001
PVC SDI
LOW VOLTAGE INDUSTRIAL HIGH VOLTAGE FIRE RATED DATA/COMMS MINING
Single core, V-90 insulated, PVC sheathed to AS/NZS 5000, copper conductors, 90C. 1.0 to 16mm2 450/750V to AS/NZS 5000.2 25 to 630mm2 0.6/1kV to AS/NZS 5000.1
Nominal Main conductor conductor area type mm 2 1.0 1.5 2.5 4 6 10 16 25 35 50 70 95 120 150 185 240 300 400 500 630 Strand Cu Strand Cu Strand Cu Strand Cu Strand Cu Strand Cu Strand Cu Compact Cu Compact Cu Compact Cu Compact Cu Compact Cu Strand Cu Strand Cu Strand Cu Compact Cu Strand Cu Strand Cu Strand Cu Strand Cu Nominal insulation thickness mm 0.6 0.6 0.7 0.8 0.8 1.0 1.0 1.2 1.2 1.4 1.4 1.6 1.6 1.8 2.0 2.2 2.4 2.6 2.8 2.8 Nominal sheath thickness mm 0.8 0.8 0.8 0.9 0.9 0.9 1.0 1.4 1.4 1.4 1.4 1.5 1.5 1.6 1.7 1.8 1.9 2.0 2.1 2.2 Nominal overall diameter mm 4.0 4.4 5.1 6.0 6.6 7.8 8.9 11.1 12.1 13.7 15.3 18.2 20.4 22.1 24.5 27.8 30.8 34.7 38.4 42.2 Approx. Product mass code kg/100m 2.7 3.2 4.8 7.1 9.4 14.3 20.8 32.3 43 56 77 107 130 158 197 257 320 406 510 653 AABP02AA001 AABP05AA001 AABP07AA001 AABP09AA001 AABP11AA001 AABP13AA001 AABP15AA001 BABC17AA001 BABC18AA001 BABC19AA001 BABC20AA001 BABC22AA001 BABP23AA001 BABP24AA001 BABP25AA001 BABP26AA001 BABP27AA001 BABP28AA001 BABP30AA001 BABP32AA001
10
Nom. Main cond. conductor area type mm 2 16 25 35 50 70 95 120 150 185 240 300 400 500 630 25 35 50 70 95 120 150 185 240 300 400 500 630 Strand Cu Compact Cu Compact Cu Compact Cu Compact Cu Compressed Cu Compressed Cu Compressed Cu Compressed Cu Compressed Cu Compressed Cu Strand Cu Strand Cu Strand Cu Compact Compact Compact Compact Compact Compact Compact Compact Compact Compact Compact Compact Compact Al Al Al Al Al Al Al Al Al Al Al Al Al
Nominal insulation thickness mm 0.8 0.9 0.9 1.0 1.1 1.1 1.2 1.4 1.6 1.7 1.8 2.0 2.2 2.4 0.9 0.9 1.0 1.1 1.1 1.2 1.4 1.6 1.7 1.8 2.0 2.2 2.4
Approximate Product mass code kg/100m 21 30 40 52 73 101 123 152 189 246 306 386 491 635 15 18 23 31 40 49 60 72 91 112 142 185 233 BDBP15AA001 BDBC17AA001 BDBC18AA001 BDBC19AA001 BDBC20AA001 BDBC22AA001 BDBP23AA001 BDBP24AA001 BDBP25AA001 BDBP26AA001 BDBP27AA001 BDBP28AA001 BDBP30AA001 BDBP32AA001 BDBA17AA001 BDBA18AA001 BDBA19AA001 BDBA20AA001 BDBA22AA001 BDBA23AA001 BDBA24AA001 BDBA25AA001 BDBA26AA001 BDBA27AA001 BDBA28AA001 BDBA30AA001 BDBA32AA001
Copper Conductor 1.4 9.3 1.4 10.5 1.4 11.5 1.4 12.9 1.4 14.7 1.5 17.2 1.5 19.6 1.6 21.3 1.6 23.5 1.7 26.6 1.8 29.4 1.9 33.3 2.0 37.0 2.2 41.4 Aluminium Conductor 1.4 10.7 1.4 11.8 1.4 13.1 1.4 14.9 1.5 16.8 1.5 18.4 1.6 20.5 1.6 22.4 1.7 25.1 1.8 27.6 1.9 31.1 2.0 35.3 2.2 39.5
11
PVC FLAT
LOW VOLTAGE INDUSTRIAL HIGH VOLTAGE FIRE RATED DATA/COMMS MINING
2 & 3 core flat, 450/750V V-90 insulated, PVC sheathed to AS/NZS 5000.2, copper conductors, 90C.
Nom. Main cond. conductor area type mm 2 1.0 1.5 2.5 4 6 10 16 1.5 2.5 Solid Cu Strand Cu Strand Cu Strand Cu Strand Cu Strand Cu Strand Cu Strand Cu Strand Cu
Nominal insulation thickness mm 0.6 0.6 0.7 0.8 0.8 1.0 1.0 0.6 0.7
Nominal sheath thickness mm 2C 0.9 0.9 1.0 1.1 1.1 1.2 1.3 0.9 1.0
Approximate Product mass code kg/100m 5.04 6.17 9.68 14.19 18.59 29.42 42.48 8.84 14.03 CACP02AA002 CACP05AA002* CACP07AA002 CACP09AA002 CACP11AA002 CACP13AA002 CACP15AA002 EACP05AA003 EACP07AA003
6.5 4.2 7.2 4.5 8.9 5.4 10.5 6.3 11.6 6.9 14.2 8.3 16.3 9.5 3C 9.9 4.5 12.3 5.4
12
Note: * Red sheath 450/750V version available for fire alarm wiring systems. A 0.6/1kV red sheath version is also available: DACP05AA002.
PVC FLAT
LOW VOLTAGE INDUSTRIAL HIGH VOLTAGE FIRE RATED DATA/COMMS MINING
2 & 3 core+earth flat, 450/750V V-90 insulated, PVC sheathed to AS/NZS 5000.2, copper conductors, 90C.
Nom. Main cond. conductor area type mm 2 1.0 1.5 2.5 2.5 4.0 6.0 10.0 16.0 1.5 2.5 Solid Cu Strand Cu Solid Cu Strand Cu Strand Cu Strand Cu Strand Cu Strand Cu Strand Cu Strand Cu
Nom. insul. thick. mm 0.6 0.6 0.7 0.7 0.8 0.8 1.0 1.0 0.6 0.7
Nom. sheath thick. mm 0.9 0.9 1.0 1.0 1.1 1.1 1.2 1.3 0.9 1.0
Approx. mass kg/100m 7.74 8.86 13.68 14.03 18.65 23.04 36.05 51.46 11.54 18.31
Product code
2C+E 1.0 8.9 4.2 1.5 9.9 4.5 2.5 11.8 5.4 2.5 12.2 5.4 2.5 13.9 6.3 2.5 15.0 6.9 4.0 18.3 8.3 6.0 21.0 9.5 3C+E 1.5 12.6 4.5 2.5 15.7 5.4
CNCP02AA002 CNCP05AA002 CNCP06AA002 CNCP07AA002 CNCP09AA002 CNCP11AA002 CNCP13AA002 CNCP15AA002 ENCP05AA003 ENCP07AA003
13
PVC CIRCULAR
LOW VOLTAGE INDUSTRIAL HIGH VOLTAGE FIRE RATED DATA/COMMS MINING
2 & 3 core+earth, circular, V-90 insulated, PVC sheathed to AS/NZS 5000, copper conductors, 90C. 1.5 to 6mm2 450/750V to AS/NZS 5000.2 10 to 300mm2 0.6/1kV to AS/NZS 5000.1
Nom. Main cond. conductor area type mm 2 1.5 2.5 4 6 10 16 25 35 50 Strand Cu Strand Cu Strand Cu Strand Cu Strand Cu Strand Cu Compact Cu Compact Cu Compact Cu Strand Cu Strand Cu Strand Cu Strand Cu Strand Cu Strand Cu Compact Cu Compact Cu Compact Cu Compact Cu Compact Cu Strand Cu Strand Cu Strand Cu Compact Cu Strand Cu Nom. insul. thick. mm 0.6 0.7 0.8 0.8 1.0 1.0 1.2 1.2 1.4 0.6 0.7 0.8 0.8 1.0 1.0 1.2 1.2 1.4 1.4 1.6 1.6 1.8 2.0 2.2 2.4 Nom. Earth sheath cond. thick. area mm mm 2 2C+E 1.2 * 1.5 1.2 * 2.5 1.3 * 2.5 1.3 * 2.5 1.8 4 1.8 6 1.8 6 1.8 10 1.8 16 3C+E 1.2 * 1.5 1.3 * 2.5 1.3 * 2.5 1.3 * 2.5 1.8 4 1.8 6 1.8 6 1.8 10 1.8 16 1.9 25 2.1 25 2.2 35 2.3 50 2.5 70 2.7 95 2.9 120 Nom. Approx. overall mass dia. mm kg/100m 8.4 * 10.6 * 9.8 * 15.9 * 11.4 * 20.8 * 12.4 * 25.7 * 16.1 43.5 18.0 59.7 20.5 80.3 22.5 103 25.6 138 9.2 * 11.1 * 12.5 * 13.5 * 17.5 19.6 22.2 24.6 28.0 32.0 37.6 42.4 46.3 51.7 59.4 66.2 12.7 * 19.7 * 26.3 * 33.2 * 56.1 78.2 107 141 188 264 360 442 542 686 902 1124 Product code
CNHP05AA002 CNHP07AA002 CNHP09AA002 CNHP11AA002 DNHP13AA002 DNHP15AA002 DNHC17AA002 DNHC18AA002 DNHC19AA002 ENHP05AA003 ENHP07AA003 ENHP09AA003 ENHP11AA003 FNHP13AA003 FNHP15AA003 FNHC17AA003 FNHC18AA003 FNHC19AA003 FNHC20AA003 FNHC22AA003 FNHP23AA003 FNHP24AA003 FNHP25AA003 FNHP26AA003 FNHP27AA003
14
Note: Earth cores smaller than 25mm 2 are not compacted. 2C+E, 35mm 2 and above, subject to minimum production run. * D ue to a change in standard AS/NZS 5000.2, the minimum calculated value of the sheath thickness for circular multicore cables has reduced, therefore also reducing the OD and mass for 1.5mm 2 6mm 2 cables.
XLPE/PVC MULTICORE
LOW VOLTAGE INDUSTRIAL HIGH VOLTAGE FIRE RATED DATA/COMMS MINING
2 & 3 core+earth, circular, 0.6/1kV X-90 insulated, PVC sheathed to AS/NZS 5000.1, copper conductors, 90C.
Nominal Main conductor conductor area type mm 2 16 25 35 50 70 95 120 16 25 35 50 70 95 120 150 185 240 300 Strand Cu Compact Cu Compact Cu Compact Cu Compact Cu Compact Cu Strand Cu Strand Cu Compact Cu Compact Cu Compact Cu Compact Cu Compact Cu Strand Cu Strand Cu Strand Cu Strand Cu Strand Cu
Nom. insul. thick. mm 0.8 0.9 0.9 1.0 1.1 1.1 1.2 0.8 0.9 0.9 1.0 1.1 1.1 1.2 1.4 1.6 1.7 1.8
Nom. sheath thick. mm 1.8 1.8 1.8 1.8 1.8 1.9 2.0 1.8 1.8 1.8 1.8 1.9 2.0 2.1 2.3 2.4 2.6 2.8
Nom. Approx. Product overall mass code dia. mm kg/100m 17.1 19.3 21.3 24.0 27.6 32.5 37.3 18.6 20.8 23.2 26.3 30.5 35.2 40.3 44.3 49.7 56.8 63.3 54 74 96 128 180 240 298 71 98 132 175 249 337 417 516 655 856 1066 DTHP15AA002 DTHC17AA002 DTHC18AA002 DTHC19AA002 DTHC20AA002 DTHC22AA002 DTHP23AA002 FTHP15AA003 FTHC17AA003 FTHC18AA003 FTHC19AA003 FTHC20AA003 FTHC22AA003 FTHP23AA003 FTHP24AA003 FTHP25AA003 FTHP26AA003 FTHP27AA003
Note: Earth cores smaller than 25mm 2 are not compacted. For insulation thickness refer to page 9. 3 core (3 core+reduced neutral with or without earth) available on request subject to minimum production runs.
15
PVC CIRCULAR
LOW VOLTAGE INDUSTRIAL HIGH VOLTAGE FIRE RATED DATA/COMMS MINING
4 core+earth, circular, V-90 insulated, PVC sheathed to AS/NZS 5000, copper conductors, 90C. 1.5 to 6mm2 450/750V to AS/NZS 5000.2 10 to 300mm2 0.6/1kV to AS/NZS 5000.1
Nominal Main conductor conductor area type mm 2 1.5 2.5 4 6 10 16 25 35 50 70 95 120 150 185 240 300 Strand Cu Strand Cu Strand Cu Strand Cu Strand Cu Strand Cu Compact Cu Compact Cu Compact Cu Compact Cu Compact Cu Strand Cu Strand Cu Strand Cu Strand Cu Strand Cu Nom. insul. thick. mm 0.6 0.7 0.8 0.8 1.0 1.0 1.2 1.2 1.4 1.4 1.6 1.6 1.8 2.0 2.2 2.4 Nom. sheath thick. mm 1.2 * 1.3 * 1.4 * 1.4 * 1.8 1.8 1.8 1.8 1.9 2.1 2.2 2.4 2.5 2.7 2.9 3.1 Earth cond. area mm 2 1.5 2.5 2.5 2.5 4 6 6 10 16 25 25 35 50 70 95 120 Nom. Approx. Product overall mass code dia. mm kg/100m 10.0 * 15.1 * 12.0 * 23.6 * 13.8 * 33.0 * 15.0 * 42.1 * 19.2 70 21.5 98 24.5 136 27.2 180 31.2 242 35.8 339 42.0 465 47.5 573 51.8 700 57.9 885 66.9 1166 74.5 1446 GNHP05AA004 GNHP07AA004 GNHP09AA004 GNHP11AA004 HNHP13AA004 HNHP15AA004 HNHC17AA004 HNHC18AA004 HNHC19AA004 HNHC20AA004 HNHC22AA004 HNHP23AA004 HNHP24AA004 HNHP25AA004 HNHP26AA004 HNHP27AA004
4C+E
16
Note: Earth cores smaller than 25mm 2 are not compacted. * D ue to a change in standard AS/NZS 5000.2, the minimum calculated value of the sheath thickness for circular multicore cables has reduced, therefore also reducing the OD and mass for 1.5mm 2 6mm 2 cables.
XLPE/PVC MULTICORE
LOW VOLTAGE INDUSTRIAL HIGH VOLTAGE FIRE RATED DATA/COMMS MINING
4 core+earth, circular, 0.6/1kV X-90 insulated, PVC sheathed to AS/NZS 5000.1, copper conductors, 90C.
Nominal Main conductor conductor area type mm 2 16 25 35 50 70 95 120 150 185 240 300 Strand Cu Compact Cu Compact Cu Compact Cu Compact Cu Compact Cu Strand Cu Strand Cu Strand Cu Compact Cu Strand Cu
Nom. insul. thick. mm 0.8 0.9 0.9 1.0 1.1 1.1 1.2 1.4 1.6 1.7 1.8
Nom. sheath thick. mm 1.8 1.8 1.8 1.9 2.0 2.1 2.3 2.4 2.6 2.8 3.0
Nom. Approx. Product overall mass code dia. mm kg/100m 20.4 22.9 25.5 29.3 34.0 39.3 45.2 49.5 55.7 63.5 71.2 89 124 167 224 320 436 543 665 842 1100 1385 HTHP15AA004 HTHC17AA004 HTHC18AA004 HTHC19AA004 HTHC20AA004 HTHC22AA004 HTHP23AA004 HTHP24AA004 HTHP25AA004 HTHP26AA004 HTHP27AA004
4C+E
17
0.8 1.5 0.8 2.5 0.8 2.5 1.0 2.5 1.0 4 1.0 6 1.2 6 1.2 10 1.4 16 1.4 25 1.6 25 1.6 35 1.8 50 2.0 70 2.2 95 2.4 120
2C+E 10.5 11.6 13.3 14.5 17.0 18.9 22.1 24.1 27.2 3C+E 9.5 11.3 10.9 12.7 12.6 15.1 13.8 16.3 15.9 18.4 18.0 21.2 20.6 23.8 23.0 26.2 26.4 29.6 30.6 34.6 35.8 39.8 40.4 44.4 44.5 49.5 49.7 54.7 57.2 62.2 63.5 68.5
18
Note: 3 core (3 core+reduced neutral with or without earth) available on request subject to minimum production runs.
2C+E 18.0 20.2 22.9 25.6 29.2 34.7 39.7 3C+E 17.0 19.5 19.2 22.4 21.6 24.8 24.7 27.9 29.1 33.1 33.6 37.6 38.5 42.5 42.5 47.5 47.7 52.7 54.8 59.8 60.9 65.9
Note: 3 core (3 core+reduced neutral with or without earth) available on request subject to minimum production runs.
19
Nom. Main cond. cond. area type mm 2 1.5 2.5 4 6 10 16 25 35 50 70 95 120 150 185 240 300 Strand Cu Strand Cu Strand Cu Strand Cu Strand Cu Strand Cu Compact Cu Compact Cu Compact Cu Compact Cu Compact Cu Strand Cu Strand Cu Strand Cu Compact Cu Strand Cu
Nom. insul. thick. mm 0.8 0.8 1.0 1.0 1.0 1.0 1.2 1.2 1.4 1.4 1.6 1.6 1.8 2.0 2.2 2.4
Nom. dia. over bedding mm 10.4 11.9 13.8 15.2 17.6 19.9 22.9 25.6 29.8 34.0 40.0 45.5 49.6 55.7 64.3 71.8
Nom. Approx. Product overall mass code dia. mm kg/100m 15.9 17.3 20.0 21.4 24.4 26.8 29.8 32.6 38.1 42.5 48.8 55.8 60.1 67.4 76.3 85.8 46 58 83 97 139 166 220 275 380 494 646 824 970 1192 1516 1936 HNMP05AA004 HNMP07AA004 HNMP09AA004 HNMP11AA004 HNMP13AA004 HNMP15AA004 HNMC17AA004 HNMC18AA004 HNMC19AA004 HNMC20AA004 HNMC22AA004 HNMP23AA004 HNMP24AA004 HNMP25AA004 HNMP26AA004 HNMP27AA004
4C+E 12.2 13.7 16.3 17.7 20.8 23.1 26.1 28.8 33.8 38.0 44.0 50.5 54.6 60.7 69.3 78.1
20
Note: 3 core (3 core+reduced neutral with or without earth) available on request subject to minimum production runs.
4C+E 22.0 24.5 27.1 31.5 36.4 41.5 48.4 52.5 58.7 66.1 73.4
Note: 3 core (3 core+reduced neutral with or without earth) available on request subject to minimum production runs.
21
PVC CONTROL
LOW VOLTAGE INDUSTRIAL HIGH VOLTAGE FIRE RATED DATA/COMMS MINING
Multicore circular+earth, 0.6/1kV V-90 insulated, PVC sheathed to AS/NZS 5000.1, copper conductors, 90C.
Number of cores 5+E 6+E 8+E 10+E 12+E 15+E 16+E 20+E 25+E 30+E 36+E 40+E 50+E 5+E 6+E 8+E 10+E 12+E 15+E 16+E 20+E 25+E 30+E 36+E 40+E 50+E
Nominal overall diameter mm 13.1 13.1 15.4 16.1 17.0 18.2 19.1 20.1 22.2 24.3 25.2 27.5 29.4 14.6 14.6 17.3 18.1 19.0 20.6 21.6 22.8 25.2 27.6 28.7 31.5 33.7
Product code
1.5mm2 (7/0.50mm) 22 24 30 35 40 46 51 59 71 83 95 107 129 2.5mm2 (7/0.67mm) 31 34 43 50 57 68 73 85 104 122 141 160 194
BFAP05AA005 BFAP05AA006 BFAP05AA008 BFAP05AA010 BFAP05AA012 BFAP05AA015 BFAP05AA016 BFAP05AA020 BFAP05AA025 BFAP05AA030 BFAP05AA036 BFAP05AA040 BFAP05AA050 BFAP07AA005 BFAP07AA006 BFAP07AA008 BFAP07AA010 BFAP07AA012 BFAP07AA015 BFAP07AA016 BFAP07AA020 BFAP07AA025 BFAP07AA030 BFAP07AA036 BFAP07AA040 BFAP07AA050
22
1.5mm2 (7/0.50mm) 13.3 16.9 13.3 16.9 16.3 20.0 17.0 20.7 17.7 21.4 19.1 22.8 20.7 24.4 21.7 25.4 23.8 27.4 25.9 29.6 26.8 30.7 29.1 32.9 32.0 36.2 2 2.5mm (7/0.67mm) 15.5 19.1 15.5 19.1 18.2 21.9 19.0 22.7 20.6 24.2 22.2 25.8 23.2 26.9 24.4 28.1 26.8 30.6 29.2 33.1 30.3 34.4 34.1 38.3 36.1 40.6
23
LV Distribution 43.0 49.8 47.5 53.4 LV Service 22.1 25.5 27.9 31.2
24
Nominal insulation thickness mm 1.3 1.3 1.5 1.7 1.3 1.3 1.5 1.5 1.3 1.3 1.5 1.5 1.7 1.7 1.7
Diameter over insulation mm 8.6 9.6 11.2 14.9 8.6 9.6 11.2 12.8 8.6 9.6 11.2 12.8 14.9 16.3 17.7
Diameter over laid-up cores mm 2C 17.2 19.3 22.3 29.8 3C 18.5 20.8 24.1 27.5 4C 20.8 23.2 27.0 30.8 36.0 39.3 42.8
Product code
XDAB17AA002 XDAB18AA002 XDAB19AA002 XDAB22AA002 XDAB17AA003 XDAB18AA003 XDAB19AA003 XDAB20AA003 XDAB17AA004 XDAB18AA004 XDAB19AA004 XDAB20AA004 XDAB22AA004 XDAB23AA004 XDAB24AA004
25 35 50 70 95 120 150
Note: A range of PVC insulated neutral screened cables and PVC insulated Hard Drawn Copper Aerials are also available on request.
25
RIAL
AGE
ATED
NING
MINING
New to the Olex Cable Range: Titanex Single & Multi Core Flexible Cable HO7VVH6-F PVC Flat Cable VCVH6-F Screened PVC Flat Cable Buflex XPrem Reeling Cable Rheyhalon Cable Rheyflat -N Screened & Unscreened Rubber Flat Festoon Cable Boitalyon R PVC Pendant Overhead Crane Cable For more information on the range of new products check out the new Olex Industrial Catalogue or visit www.olex.com.au
Nominal conductor area mm 2 0.75 1.0 1.5 2.5 4 0.75 1.0 1.5 2.5 4 0.75 1.0 1.5 2.5 4 0.75 1.0 1.5 2.5 4
Maximum diameter of wires mm 0.21 0.21 0.21 0.21 0.31 0.21 0.21 0.21 0.21 0.31 0.21 0.21 0.21 0.21 0.31 0.21 0.21 0.21 0.21 0.31
Nominal overall diameter mm 2C 6.2 6.6 7.5 9.2 10.4 2C+E 6.6 6.9 8.1 9.9 11.2 3C+E 7.2 7.8 9.1 10.9 12.3 4C+E 8.0 8.5 10.1 12.1 13.9
Product code
CAHR02AA002 CAHR03AA002 CAHR04AA002 CAHR05AA002 CAHR06AA002 EAHR02AA003 EAHR03AA003 EAHR04AA003 EAHR05AA003 EAHR06AA003 GAHR02AA004 GAHR03AA004 GAHR04AA004 GAHR05AA004 GAHR06AA004 APAR02AA005 APAR03AA005 APAR04AA005 APAR05AA005 APAR06AA005
28
Note: For core colour, flexible cords refer to page 72. V-90HT is available on request subject to minimum production runs.
Nominal conductor area mm 2 0.75 1.0 1.5 2.5 4 0.75 1.0 1.5 2.5 4 0.75 1.0 1.5 2.5 4 1.0 1.5 2.5 4
Maximum diameter of wires mm 0.21 0.21 0.21 0.21 0.31 0.21 0.21 0.21 0.21 0.31 0.21 0.21 0.21 0.21 0.31 0.21 0.21 0.21 0.31
Nominal overall diameter mm 2C 8.0 8.3 9.3 11.0 12.7 2C+E 8.6 9.0 9.9 11.7 13.6 3C+E 9.5 9.9 10.9 12.9 15.0 4C+E 10.9 12.0 14.2 16.7
Product code
CBGR02AA002 CBGR03AA002 CBGR04AA002 CBGR05AA002 CBGR06AA002 EBGR02AA003 EBGR03AA003 EBGR04AA003 EBGR05AA003 EBGR06AA003 GBGR02AA004 GBGR03AA004 GBGR04AA004 GBGR05AA004 GBGR06AA004 BSBR03AA005 BSBR04AA005 BSBR05AA005 BSBR06AA005
Note: For core colour, flexible cords refer to page 72. Conductor stranding may vary according to production method and relevant Standard. V-90HT is available on request subject to minimum production runs.
29
Product code
Single Core 0.6/1kV V-90 Insulated, Flexible Cord 0.21 2.7 1.3 0.21 2.9 1.6 0.21 3.2 2.1 0.21 3.8 3.3 0.31 4.6 5.2 2 and 3 Core 250/250V V-90 Insulated, PVC Sheathed LIGHT Duty Flexible Cord 0.21 5.4 4.3 0.21 5.8 5.4 2 Core 250/250V V-90 Insulated, PVC Sheathed LIGHT Duty Flat Flexible Cord 0.31 3.4 5.4 3.2
CBER02AA002 EBER02AA003
CBLR02AA002*
30
Note: For core colour, flexible cords refer page 72. *2 core light duty flat cords supplied in red and white insulation, red sheath for fire alarm wiring systems.
90C
110C
BZHX01AA001 BZHX02AA001 BZHX03AA001 BZHX04AA001 BZHX05AA001 BZHX06AA001 BZHX07AA001 BZHE87AA001 BZHE88AA001 BZHE89AA001 BZHE90AA001 BZHE91AA001 BZHE92AA001 BZHE93AA001 BZHE94AA001
31
VERSOLEX HD UNSCREENED
GE INDUSTRIAL HIGH VOLTAGE FIRE RATED DATA/COMMS MINING
0.6/1kV multicore cords & cables, flexible X-90 (XLPE) insulated and TPE sheathed to AS/NZS 3191 (cords) and where applicable AS/NZS 5000.1 (cables), copper conductors, 90C.
Nom. cond. area mm 2 0.75 1 1.5 2.5 4 0.75 1 1.5 2.5 4 6 Max. dia. of wires mm 0.21 0.21 0.21 0.21 0.31 0.21 0.21 0.21 0.21 0.31 0.31 0.21 0.21 0.21 0.21 0.31 0.31 0.21 0.21 0.21 0.21 0.31 0.31 0.31 0.51 Nom. ins. thick. mm 0.7 0.7 0.7 0.7 0.7 0.7 0.7 0.7 0.7 0.7 0.7 0.7 0.7 0.7 0.7 0.7 0.7 0.7 0.8 0.9 0.9 1.0 1.1 1.1 1.2 Nom. sheath thick. mm 2C 1.3 7.6 1.3 7.9 1.5 8.9 1.7 10.2 1.8 11.6 3C (2C+E) 1.4 8.2 1.4 8.5 1.6 9.5 1.8 10.9 1.9 12.4 1.8 13.4 4C (3C+E or 3C+3E) 1.5 9.0 1.5 9.4 1.7 10.5 1.9 12.0 2.0 13.6 1.8 15.3 1.8 16.6 1.8 18.9 1.8 22.0 1.8 24.7 1.8 28.4 2.0 33.0 2.0 36.7 2.2 42.2 6.4 7.3 9.4 13 19 7.7 8.8 12 16 23 30 9.4 11 14 20 29 38 50 72 108 147 205 279 371 464 CFGR02AA002 CFGR03AA002 CFGR04AA002 CFGR05AA002 CFGR06AA002 EFGR02AA003 EFGR03AA003 EFGR04AA003 EFGR05AA003 EFGR06AA003 FEHR07AA003 GFGR02AA004 GFGR03AA004 GFGR04AA004 GFGR05AA004 GFGR06AA004 FTAR07AA003 FTAX01AA003 FTAX02AA003 FTAX03AA003 FTAX04AA003 FTAX05AA003 FTAX06AA003 FTAX07AA003 FTAE87AA003 Nom. overall dia. mm Approx. mass kg/100m Product code
32
VERSOLEX HD UNSCREENED
GE INDUSTRIAL HIGH VOLTAGE FIRE RATED DATA/COMMS MINING
0.6/1kV multicore cords & cables, flexible X-90 (XLPE) insulated and TPE sheathed to AS/NZS 3191 (cords) and where applicable AS/NZS 5000.1 (cables), copper conductors, 90C.
Nom. cond. area mm 2 0.75 1 1.5 2.5 4 6 10 16 25 35 50 70 Max. dia. of wires mm 0.21 0.21 0.21 0.21 0.31 0.31 0.21 0.21 0.21 0.21 0.31 0.31 Nom. ins. thick. mm 0.7 0.7 0.7 0.7 0.7 0.7 0.7 0.8 0.9 0.9 1.0 1.1 Nom. sheath thick. mm Nom. overall dia. mm Approx. mass kg/100m 12 13 17 24 36 45 70 101 152 207 285 399 BWBR02AA005 BWBR03AA005 BWBR04AA005 BWBR05AA005 BWBR06AA005 BWBR07AA005 BWBX01AA005 BWBX02AA005 BWBX03AA005 BWBX04AA005 BWBX05AA005 BWBX06AA005 Product code
5C (4C+E) 1.6 9.9 1.6 10.4 1.8 11.5 2.0 13.2 2.2 15.2 1.8 16.4 1.8 19.1 1.8 22.1 1.8 26.3 1.9 31.1 2.1 34.7 2.3 40.6
33
4C (3C+E or 3C+3E) 9.1 1.7 13.9 10.2 1.9 15.2 11.6 2.0 17.0 13.8 1.8 18.7 15.0 1.8 20.0 17.4 1.8 22.8 20.5 1.8 26.0 23.2 1.8 28.9 27.1 1.8 32.9 31.1 1.9 37.6 35.2 2.1 41.9 40.2 2.2 47.7 44.7 2.3 52.5 49.7 2.5 57.9 55.8 2.6 64.5 62.0 2.9 69.7 5C (4C+E) 10.1 1.8 15.1 11.4 2.0 16.6 12.8 2.2 18.4 15.6 1.8 21.1 17.2 1.8 22.5 21.7 1.8 26.4 24.9 1.8 30.1 28.5 1.9 33.7 33.7 2.1 39.9 38.4 2.3 43.9
34
Perm. current rating open air A 32 43 56 77 102 136 168 203 254 315 363 416 475 559 637
Minimum outer diameter mm 6.3 7.2 7.2 9.5 10.8 12.7 14.3 16.5 18.6 20.8 22.8 25.2 27.6 30.6 33.5
Maximum outer diameter mm 7.9 9 9.8 11.9 13.4 15.8 17.9 20.6 23.3 26.0 28.6 31.4 34.4 38.3 41.9
Approx. mass kg/km 66 94 109 182 256 369 482 662 895 1164 1430 1740 2160 2730 3480
Product code
HAR1X2.5 HAR1X4 HAR1X6 HAR1X10 HAR1X16 HAR1X25 HAR1X35 HAR1X50 HAR1X70 HAR1X95 HAR1X120 HAR1X150 HAR1X185 HAR1X240 HAR1X300
35
5 G 2.5 5 G 4 5 G 6 12 G 1.5
36
18 G 1.5
FLEXOLEX HD UNSCREENED
GE INDUSTRIAL HIGH VOLTAGE FIRE RATED DATA/COMMS MINING
0.6/1kV cords and cables R-EP-90 (EPR)insulated and CPEsheathed to AS/NZS 3191 (cords) and AS/NZS 5000.1 (cables), bunched tinned copper conductors, 90C, for flexible applications.
Nominal conductor area mm 2 0.75 1.0 1.5 2.5 4 Maximum diameter of wires mm 0.21 0.21 0.26 0.26 0.31 0.26 0.26 0.31 0.31 0.41 0.41 0.41 0.26 0.26 0.31 0.31 0.41 0.41 0.41 0.41 Nominal insulation thickness mm 0.8 0.8 0.8 0.9 1.0 0.8 0.9 1.0 1.0 1.2 1.2 1.4 0.8 0.9 1.0 1.0 1.2 1.2 1.4 1.4 Nominal sheath thickness mm 2C+E 1.4 1.4 1.6 1.8 1.9 3C+E 1.7 1.9 2.0 2.2 3.4 3.6 4.0 4C+E 1.8 2.0 2.2 2.4 3.6 3.8 4.3 4.6 Nominal overall diameter mm 8.8 9.1 10.5 12.5 13.5 11.5 13.5 15.5 18.0 24.4 27.4 32.9 12.3 14.5 17.5 20.0 26.8 30.2 36.4 40.6 Approx. mass kg/100m 11 12 15 22 31 19 27 39 53 94 130 198 23 33 48 65 115 159 244 309 RDER52AA003 RDER53AA003 RDER54AA003 RDER55AA003 RDER56AA003 RDER54AA004 RDER55AA004 RDER56AA004 RDHR57AA004 RDHR58AA004 RDHR59AA004 RDHR60AA004 RDER54AA005 RDER55AA005 RDER56AA005 RDHR57AA005 RDHR58AA005 RDHR59AA005 RDHR60AA005 RDHR61AA005 Product code
Note: Other sizes and conductor configurations are available upon request.
37
FLEXOLEX HD SCREENED
GE INDUSTRIAL HIGH VOLTAGE FIRE RATED DATA/COMMS MINING
0.6/1kV cords and cables R-EP-90 (EPR) insulated, EPR bedded, tinned copper wire braid screened, CPE sheathed to AS/NZS 3191 (cords) and AS/NZS 5000.1 (cables), tinned copper conductors, 90C, for flexible applications.
Nominal conductor area mm 2 1.5 2.5 4 6 10 16 1.5 2.5 4 6 10 16 Maximum Nominal diameter insul. of wires thick. mm mm 0.26 0.26 0.31 0.31 0.41 0.41 0.26 0.26 0.31 0.31 0.41 0.41 0.8 0.9 1.0 1.0 1.2 1.2 0.8 0.9 1.0 1.0 1.2 1.2 Nominal sheath thick. mm 1.8 1.9 2.2 2.4 3.5 3.8 1.9 2.1 2.3 2.5 3.7 4.0 Nominal Nominal Approx. dia. under overall mass braid diameter mm mm kg/100m 3C+E 9.6 11.2 13.1 15.3 19.2 21.8 4C+E 10.5 12.3 14.4 16.9 21.2 24.2 14.6 16.4 18.9 21.8 28.4 31.6 15.7 17.9 20.4 23.9 30.8 34.4 30 39 54 74 123 164 35 47 64 89 147 195 Product code
RDLR54AA004 RDLR55AA004 RDLR56AA004 RDXR57AA004 RDXR58AA004 RDXR59AA004 RDLR54AA005 RDLR55AA005 RDLR56AA005 RDXR57AA005 RDXR58AA005 RDXR59AA005
38
VAROLEX VSD/EMC
GE INDUSTRIAL HIGH VOLTAGE FIRE RATED DATA/COMMS MINING
Fixed conductor variable speed drive cables. 0.6/1kV X-90 (XLPE) insulated, 3 core +3 earths, PVC bedded, copper tape screened, PVC sheathed to AS/NZS 5000.1, copper conductors, 90C.
Nominal conductor area mm 2 2.5 4 6 10 16 25 35 50 70 95 120 150 185 240 300 Nomimal insulation thickness mm 0.7 0.7 0.7 0.7 0.8 0.9 0.9 1.0 1.1 1.1 1.2 1.4 1.6 1.7 1.8 Combined earth size area mm 2 2.5* 4.5 4.5 4.5 7.5 12 18 30 30 48 48 75 75 105 150 Nominal dia. over screen mm 10.9 13.0 13.8 14.8 17.0 19.2 21.9 25.1 28.1 33.9 38.9 42.6 47.5 53.6 59.6 Nominal Approx. overall mass diameter mm kg/100m 14.6 16.6 17.5 18.5 20.6 22.8 25.6 28.8 32.0 38.0 43.2 47.3 52.0 58.9 65.2 32 44 51 62 86 121 160 211 277 390 467 585 711 918 1154 Product code
FTDP07AA003 FTDP09AA003 FTDP11AA003 FTDP13AA003 FTDP15AA003 FTDC17AA003 FTDC18AA003 FTDC19AA003 FTDC20AA003 FTDC22AA003 FTDP23AA003 FTDP24AA003 FTDP25AA003 FTDP26AA003 FTDP27AA003
39
40
Note: Black cores with continuous white numbering according to DIN VDE 0293. Not suitable for open air applications. G = green-yellow earth core.
Note: Black cores with continuous white numbering according to DIN VDE 0293. Not suitable for open air applications. G = green-yellow earth core.
41
42
Note: Black cores with continuous white numbering according to DIN VDE 0293. G = green-yellow earth core.
43
Silicone Multicore
GE INDUSTRIAL HIGH VOLTAGE FIRE RATED DATA/COMMS MINING
300/500V cables, silicone insulated, silicone sheathed, halogen free to IEC 60754-2, tinned copper conductors, fixed 60C to 180C (peak 220C). Min. bending radius 7.5xcable o.d.
Number cores x cross section mm 2 2 x1 3 G 1 4 G 1 5 G 1 7 G 1 12 G 1 3 G 1.5 4 G 1.5 5 G 1.5 3 G 2.5 4 G 2.5 5 G 2.5 Nomimal diameter mm 6.6 7.4 8 8.8 9.5 11.5 8 8.8 9.6 9.7 10.6 11.6 Approximate mass kg/km 59 77 94 115 144 231 98 122 147 152 188 228 SF2X1 SF3G1 SF4G1 SF5G1 SF7G1 SF12G1 SF3G1.5 SF4G1.5 SF5G1.5 SF3G2.5 SF4G2.5 SF5G2.5 Product code
44
Note: G = Green-yellow earth core 2 Core = Brown/Blue 3 Core = Brown/Blue/Green-Yellow 4 Core = Brown/Blue/Black/Green-Yellow 5 Core = Brown/Blue/Black/Grey/Green-Yellow 6 Core & above = Black cores with white numbering
INSTROLEX INSTRUMENTATION
GE INDUSTRIAL HIGH VOLTAGE FIRE RATED DATA/COMMS MINING
Plain annealed copper conductor, V-90 RP PVC insulated, twisted pairs, overall screened with aluminium polyester tape plus tinned annealed copper drain wire, rip cord, 5V-90 RP PVC sheathed.
Number and Number nominal diameter of pairs of wires No./mm 7/0.30 7/0.50 7/0.30 7/0.30 7/0.30 7/0.30 7/0.30 7/0.30 7/0.30 7/0.30 7/0.30 7/0.30 7/0.30 7/0.30 7/0.30 7/0.30 7/0.30 7/0.30 7/0.30 7/0.30 7/0.30 7/0.30 7/0.30 7/0.30 Nominal outside diameter mm Approximate mass kg/100m IEB183AA001 IEB184AA001 IEC183AA002 IEC183AA004 IEC183AA006 IEC183AA008 IEC183AA010 IEC183AA012 IEC183AA016 IEC183AA020 IEC183AA024 IEC183AA036 IEC183AA050 IED183AA002 IED183AA004 IED183AA006 IED183AA008 IED183AA010 IED183AA012 IED183AA016 IED183AA020 IED183AA024 IED183AA036 IED183AA050 Product code
Single Pair Screened 1 5.2 3.5 1 6.6 6.0 Overall Screened Pairs 2 7.8 6.3 4 8.4 9.4 6 10.0 13 8 11.2 17 10 12.5 21 12 13.4 24 16 15.1 31 20 16.8 38 24 18.1 45 36 22.0 66 50 25.6 90 Individually and Overall Screened Pairs 2 8.1 7.3 4 10.4 12 6 12.2 17 8 13.9 22 10 14.6 26 12 16.0 31 16 18.0 39 20 20.1 48 24 21.9 57 36 26.3 83 50 30.6 112
Note: 1 . A complete range of 7/0.50 pairs is available. 2. 7/0.30 is equivalent to 20 AWG. 3. 7/0.50 is equivalent to 16 AWG.
45
GE
INDUSTRIAL
FIRE RATED
DATA/COMMS
MINING
Plain annealed copper conductor, V-90 RP PVC insulated, twisted pairs, overall or individually and overall screened with aluminium polyester tape plus tinned annealed copper drain wire, rip cord, PVC bedding, steel wire armour, 5V-90 RP PVC sheathed.
Number & nom. dia. of wires No./mm 7/0.50 7/0.30 7/0.30 7/0.30 7/0.30 7/0.30 7/0.30 7/0.30 7/0.30 7/0.30 7/0.30 7/0.30 7/0.30 7/0.50 7/0.50 7/0.30 7/0.30 7/0.30 No. of pairs (or triples where applicable) Nominal dia. over bedding mm Nominal dia. over armour mm Nominal outside diameter mm Approx. Product mass code kg/100m 22 25 28 36 42 48 54 65 SWA 26 35 45 52 58 7.8 24 13 19 35 IEF184AA001 IEG183AA002 IEG183AA004 IEG183AA006 IEG183AA008 IEG183AA010 IEG183AA012 IEG183AA016 IEH183AA002 IEH183AA004 IEH183AA006 IEH183AA008 IEH183AA010 IGB184AA001 IGF184AA001 IGC183AA004 IGC183AA006 IGC183AA012
Single Pair Screened SWA 1 6.2 8.0 10.2 Overall Screened Pairs SWA 2 7.4 9.2 11.4 4 8.0 9.8 12.0 6 9.4 11.2 13.6 8 10.6 12.4 14.8 10 11.7 13.5 16.1 12 12.6 14.4 17.0 16 14.3 16.1 18.9 Individually & Overall Screened Pairs 2 7.7 9.5 11.7 4 9.8 11.6 14.0 6 11.6 13.4 16.0 8 13.1 14.9 17.5 10 13.8 15.6 18.2 Single Triple Screened 1 6.9 Single Triple Screened SWA 1 6.6 8.4 10.6 Overall Screened Triples 4 10.0 6 11.7 12 16.1
46
Note: Other pair and triple counts available. 7/0.50 SWA pairs and triples available.
RATED
OMMS
INING
The cables Australians trust to stay safe and secure have a new name Alsecure.
Alsecure is now the name to specify for the cables youve always relied on for safety and security to maintain circuit integrity for lighting, alarms, pumps, process applications and other essential services, even under fire.
47
AGE
FIRE RATED
0.6/1kV, single conductor, Stranded Flexible (Class 6) AS/NZS 1125 Plain Annealed Copper conductor, INFIT(Ceramifiable) R-HF-110 to AS/NZS 3808) Insulated, (HFFR) Halogen Free Flame Retardant HFS-110-TP to AS/NZS 3808) Sheathed and to AS/NZS 5000.1, 110C, WS52W Fire Rated to AS/NZS 3013:2005.
Nom. Nom. Nom. cond. insul. sheath cross thick. thick. section area mm mm 2 mm 10 16 25 35 50 70 95 120 150 185 240 300 400 500 630 1.0 1.0 1.2 1.2 1.4 1.4 1.6 1.6 1.8 2.0 2.2 2.4 2.6 2.8 2.8 1.4 1.4 1.4 1.4 1.4 1.4 1.5 1.5 1.6 1.7 1.8 1.9 2.0 2.1 2.2 Nom. Approx. overall mass cable diameter mm 9.4 10.4 12.0 13.6 15.6 17.3 19.6 21.7 23.8 26.4 29.6 32.7 36.6 41.9 45.6 Min. bending Max. radius during pulling installation tension kN 0.2 0.3 0.5 0.8 1.1 1.5 2.1 2.6 3.3 4.0 5.2 6.5 8.7 10.9 13.7 PEKX01AA001 PEKX02AA001 PEKX03AA001 PEKX04AA001 PEKX05AA001 PEKX06AA001 PEKX07AA001 PEKX08AA001 PEKX09AA001 PEKX10AA001 PEKX11AA001 PEKX68AA001 PEKX69AA001 PEKX70AA001 PEKX71AA001 Product code
kg/100m mm 18 24 35 45 61 82 109 131 160 194 255 310 398 517 657 55 60 70 80 95 105 120 130 145 160 180 195 220 250 275
48
AGE
FIRE RATED
Multicore ES90. Copper conductor 0.6/1kV INFIT(Ceramifiable) HFI-90-TP to AS/ANZ 3808 Insulated, (HFFR) Halogen Free Flame Retardant HFS-90-TP to AS/NZS 3808 sheathed, and to AS/NZS 5000.1, 90C. WS52W fire rated to AS/NZ 3013:2005.
Number of cores 2 3 4 2 3 4 2 2+E 3 3+E 4 4+E 2 2+E 3 3+E 4+E 2 2+E 3 3+E 4+E
Nominal conductor cross section area mm 2 0.75 0.75 0.75 1.0 1.0 1.0 1.5 1.5 1.5 1.5 1.5 1.5 2.5 2.5 2.5 2.5 2.5 4.0 4.0 4.0 4.0 4.0
Nominal insulation thickness mm 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0
Nominal sheath thickness mm 90C 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8
Nominal overall diameter mm 10.6 11.1 12.0 10.7 11.2 12.1 11.3 11.8 11.8 12.8 12.7 14.0 12.3 13.0 13.0 14.0 13.8 13.4 13.8 14.1 15.0 16.4
Approx. mass
Product code
kg/100m 14.1 16.0 18.6 14.2 16.1 18.7 17.0 19.0 19.0 22.0 20.7 30.0 21.0 25.0 25.0 30.0 26.0 26.0 29.0 31.2 36.0 43.0 PEKE99AA002 PEKE99AA003 PEKE99AA004 PEKP03AA002 PEKP03AA003 PEKP03AA004 PEKP05AA002 PDKP05AA002 PEKP05AA003 PDKP05AA003 PEKP05AA004 PDKP05AA004 PEKP07AA002 PDKP07AA002 PEKP07AA003 PDKP07AA003 PDKP07AA004 PEKP09AA002 PDKP09AA002 PEKP09AA003 PDKP09AA003 PDKP09AA004
49
AGE
FIRE RATED
Multicore ES110. Copper conductor 0.6/1kV INFIT(Ceramifiable) R-HF-110 to AS/ANZ 3808 Insulated, (HFFR) Halogen Free Flame Retardant HFS-110-TP to AS/NZS 3808 sheathed, and to AS/NZS 5000.1, 90C. WS52W fire rated to AS/NZ 3013:2005.
Number of cores 2+E 3+E 4+E 2+E 3+E 4+E 3+E 4+E 3+E 4+E 3+E 4+E 4+E
Nominal insulation thickness mm 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.2 1.2 1.2 1.2 2.0
Nominal sheath thickness mm 110C 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 2.0
Nominal overall diameter mm 14.7 16.0 17.6 16.3 17.9 19.7 20.1 22.2 22.6 25.0 25.3 28.0 32.3
Approx. mass
Product code
kg/100m 35 44 53 48 60 74 84 103 117 145 156 195 265 PDKP11AA002 PDKP11AA003 PDKP11AA004 PDKP13AA002 PDKP13AA003 PDKP13AA004 PDKP15AA003 PDKP15AA004 PDKP17AA003 PDKP17AA004 PDKP18AA003 PDKP18AA004 PDKP19AA004
50
AGE
FIRE RATED
Alsecure Premium with INFIT Cermifiable Instrumentation and Data are a range of (HFFR) Halogen Free Flame Retardant multipair cable rated to WS51W under fire test standard AS/NZ 3013:2005. These new cables are the only fire rated mltipair product available that do not require glass-mica tapes, thus reducing installation time and eliminating the need for respirators and special gloves.
Number Nominal Approx. of diameter mass pairs kg/100m mm 2 1 2 4 6 8 10 12 16 20 24 1 2 4 6 8 10 12 16 20 24 7.8 12.2 13.5 16.3 18.6 20.4 22.3 25.5 28.3 30.9 8.4 13.2 14.7 17.6 20.2 22.4 24.5 28.0 31.1 33.9 6.6 13.0 20.5 29.3 38.2 46.2 55.0 71.7 88.5 105.2 8.0 15.8 25.6 36.9 48.2 59.6 71.0 92.7 114.5 136.2 Minimum bending radius during installation mm Maximum pulling tension kN 0.06 0.12 0.24 0.36 0.48 0.60 0.72 0.96 1.20 1.40 0.12 0.24 0.48 0.72 0.96 1.20 1.40 1.90 2.40 2.90 Product code
Conductor 0.75mm 2 115 185 200 240 280 310 340 380 430 460 Conductor 1.5 mm2 125 200 220 270 300 340 370 420 470 500
PBKP03AA001 PBKP03AA002 PBKP03AA004 PBKP03AA006 PBKP03AA008 PBKP03AA010 PBKP03AA012 PBKP03AA016 PBKP03AA020 PBKP03AA024 PBK184AA001 PBK184AA002 PBK184AA004 PBK184AA006 PBK184AA008 PBK184AA010 PBK184AA012 PBK184AA016 PBK184AA020 PBK184AA024
51
MMS
DATA/COMMS MINING
NING
SECURITY
DATA/COMMS MINING
Unscreened Security
Number of conductors 4 6 4 6 8 Nominal conductor area mm 2 0.22 0.22 0.50 0.50 0.50 Nominal Approx. overall mass diameter mm kg/100m 7/0.20mm Conductor 3.6 1.4 4.9 3.1 14/0.20mm Conductor 4.7 3.2 5.6 4.7 6.5 5.8 Max. DC resistance @20C Ohms/km 86.5 86.5 44.5 44.5 44.5 Product code
xx Sheath colour: GY Grey; WT White. *Pack size: 1 100m spool; B 300m box; C 250m spool (JSC.5xx6C only); 5 500m spool; B2 200m box (JSC.5xx6C only). Insulation colours: 4C Red, Black, White, Blue; 6C Red, Black, White, Blue, Green, Yellow. 8C Red, Blue, White, Black, Yellow, Green, Violet, Brown.
Screened Security
Number of conductors 2 pair 2 pair Nominal conductor area mm 2 0.35 0.35 Nominal Approx. overall mass diameter mm kg/100m 7/0.25mm Conductor 4.2 2.8 4.3 2.9 Max. DC resistance @20C Ohms/km 55.0 55.0 Product code
JD2PIS JD2PISFPA3
*Pack size: 1 100m spool; B 300m box (JD2PIS only); A3 300m spool (JD2PISFPA3 only); 5 500m spool. Note: Grey PVC Sheath, 7/0.20mm T/C drain wire. Individually screened pairs. Also available in jelly filled version JD2PISFP3). Insulation colours: 4C Red, Blue, White, Black; 7C Red, Blue, White, Black, Orange, Yellow, Green; 2 Pair Black and Red, Green and White. Polypropylene insulated.
53
54
MINING
Max. cond. res. @ 20C ohm/km 55 93.8 26.4 62 13.6 45.2 95.3 89 Grey 300m box JD2PISLSOHB30 Black 300m reel JCAT5ELSZHA3 White/blk stripe 100m reel JSF.75WTBKLSOH1 Black 100m reel JBCRG59CCTVLSOH Red 300m reel JRS1502A3LSOH White 300m box JSC.5WT4LSOHB30 Grey 300m box JD6CSLSOH Grey 300m box JCAT6LSOH Nom. cond. res. @ 20C ohm/km 17.2 7.80 17.2 Pack size B A, B B Insul. Pack thick. size mm 97.8 57.1 23.9 16.3 0.5 0.8 0.8 1.0 A, C A, B, C A, C A Product code JTS1.2VT2CA3 JTS2.5VT2C* JTS1.2VT4CA3 Product code Max. volt. drop @ mV/A.m JSF.5xx* JSF.75xx*1 JSF2.OCL* JSF2.6CL1 Pack sizes A-100m; B-300m spool. Approx. mass area kg/100m 2.0 3.0 5.2 8.1 Maximum DC resistance Ohms/km Standard 44.5 26.0 Oxygen Free Copper 10.9 7.4
No. of cores/ pairs 2 pairs 4 pairs N/A N/A 2 cores 4 cores 6 cores 4 pairs
Nom. cond. area mm 2 0.35 0.22 0.75 6.2 1.5 0.5 0.22 0.54
Nom. Stranding Approx. mass overall dia. for cable mm No./mm kg/100m 4.3 7/0.25 3 5.3 1/0.50 3.2 3.0 x 6.0 24/0.20 3.1 1/0.60 5.5 5.3 7/0.50 5 4.7 14/0.20 3.4 5.5 7/0.20 4.7 6.0 1/0.54
SECURITY/AUDIO
No. of Nom. cond. Stranding Approx. Nom. insul. Nom. overall cores area mass thickness diameter mm 2 No./mm kg/100m mm mm 1.2 70/0.15 5.8 2.2 6.5 2 2 2.5 140/0.15 10 3.3 8.5 4 1.2 70/0.15 8.6 2.2 6.9 Figure 8
0.5 0.75
14/0.20 24/0.20
2.0 2.6
64/0.20 84/0.20
Rated voltage ELV. 2 One plain copper & one tinned copper conductor. Pack sizes A 100m spool; B 250m spool; C 300m spool.
DATA/COMMS
Bare copper conductor, polyolefin insulated, twisted pairs, PVC sheathed, compatible with RJ type connector.
Maximum Nom. Mutual Sheath Pack Product conductor impedence capacitance colour sizes code resistance @ 20C 300m 300m 305m ohm/km ohms pF/m box spool spool
No. of Nominal Nominal Stranding Approximate Shielding pairs conductor overall mass area diameter mm No./mm kg/100m mm2
LAN
MINING
JCAT5Exx
Category 5E Solid 4 0.22 5.3 1/0.50 3.2 N/A 93.8 100 51 Blue, Green, Grey, Red, Yellow Category 5E Underground 4 0.22 5.7 1/0.50 3.2 N/A 93.8 100 51 Black Category 5E Low Smoke Zero Halogen (LSOH) 4 0.22 5.3 1/0.50 3.2 N/A 93.8 100 51 Black Category 5E Screened 4 0.22 5.3 1/0.50 5 Aluminium 93.8 100 50 Grey Foil + DW Category 6 4 0.22 6.3 1/0.50 4.5 N/A 93.8 100 51 Blue, Grey Category 6 Underground 4 0.22 6.3 1/0.54 4.15 N/A 93.8 100 51 Black Category LSOH 4 0.54 6.0 1/0.54 N/A 89 100 Grey
*Only in blue.
55
DATA/COMMS
Coaxial 50 Ohm
Max. cond. Nom. Nom. Pack resistance cap. velocity size @ 20C prop. Ohm/km pF/m % 101 66 A, B JBCRG58CUMIL1 Product code
RG58
Coaxial 75 Ohm
Max. cond. Nom. resistance cap. @ 20C Ohm/km pF/m 66 66 Nom. velocity prop. % Pack size Product code
Nom. Stranding Approx. Shielding Dielectric overall mass diameter mm No./mm kg/100m
6.1 6.2
Pack sizes: A 100m spool; B 250m spool; C 300m box; D 500m spool. Composite cables: RG59 Coaxial and Figure 8 cables available on request.
56
MINING
A, B, D A, C, D JBCRG59BUCCTV JBCRG59PREM
COAXIAL
Nom. Stranding Approx. Shielding Dielectric overall mass diameter mm No./mm kg/100m
5.0
19/0.18 T/C
4.2
95% T/C
1/0.60 1/0.60
5.2 6.0
RG59 Closed Circuit Television (CCTV) 86% B/C Braid Solid PE 62.2 67 95% B/C Braid Solid PE 62.2 67
D DATA/COMMS
Coaxial 75 Ohm
Max. cond. Nom. resistance cap. @ 20C Ohm/km pF/m 53 53 55 82 A 83 D 84 A, B, C JBCRG6QUAD JBCRG11QUAD JBCTVCOAX1 Nom. Pack velocity size prop. % Product code
MINING
COAXIAL
Nom. Stranding Approx. Shielding Dielectric overall mass dia. mm No./mm kg/100m
7.5
1/1.0
5.1
10.3
1/1.63
8.7
6.6
1/1.0
4.5
RG6 TV Downlead Premium/Antenna Al Foil, 60% Braid. Al Foil, 40% Braid Foamed PE 100 RG11 Internal use Al Foil, 60% Braid. Al Foil, 40% Braid Foamed PE 36.1 Air Space Al Foil, 35% B/C Braid Air Space PE 22.4
Pack sizes: A 100m spool; B 300m spool; C 300m box; D 305m spool.
57
OPTICAL FIBRE
DATA/COMMS MINING
Nylon Underground
Description Nom. Approx. O.D. mass mm kg/100m 10/125m SM 6 Fibre 10/125m SM 12 Fibre 10/125m SM 24 Fibre Max. Min. bending Product pulling radius mm code tension During kN installation installed 85 85 110 85 85 85 110 85 FIB06SMJN FIB12SMJN FIB24SMJN FIB06MMJN FIB08MMJN FIB12MMJN FIB24MMJN FIB120M3JN
Single Mode (0S1) 8.5 6.0 1.5 170 8.5 6.0 1.5 170 11.0 9.5 2.3 220 Multi Mode (0M1) 62.5/125m MM 6 Fibre 8.5 6.0 1.5 170 62.5/125m MM 8 Fibre 8.5 6.0 1.5 170 62.5/125m MM 12 Fibre 8.5 6.0 1.5 170 62.5/125m MM 24 Fibre 11.0 9.5 2.3 220 Multi Mode (0M3) 50/125m MM 12 Fibre 8.5 6.0 1.5 170
58
Options Fibre counts up to 324 fibre are available upon request for loose tube cables Corrugated Steel Tape (CST) Armouring Composite (combination of single and multi mode) ADSS (All Dielectric Self Supporting) Sacrificial Sheath Low Smoke Zero Halogen (LSZH) outer sheath Rodent Resistance Note: Minimum order quantity applies to these options. The OS1 fibre is specified to ITU-T G652.D (low water peak).
TELEPHONE INTERNAL
DATA/COMMS MINING
Note: 2 pair and 3 pair available in 100 metre and 300 metre spools. 10 pair available in 200 and 500 metre spools (no cuts). 20 pair and above available in bulk drum (will cut to length).
Wire size mm
0.5
Sheath colour
Product code
JUMPRW*
*Pack Size.
59
TELEPHONE EXTERNAL
DATA/COMMS MINING
Aerial
Pairs 1 10 Nominal overall size mm 7.9 4.9 16.0 12.0 Max. conductor Approx. resistance mass @ 20C Ohm/km kg/100m 0.64mm Diameter Conductor 58.6 4.0 58.6 19 Product code
TEXT64IB001A5 TEXT64IB010*
*Includes aluminium foil screen over the twisted pair. These cables are not power cables or for direct connection of equipment to mains power supplies.
External
No. of pairs 10 20 50 2 2 Nominal Wire Approx. overall size mass diameter kg/100m mm mm 7.0 8.5 9.5 12.8 5.7 Max. cond. Pack Product resistance size code @ 20C Ohm/km TEXT40FP010 TEXT40FP020 TEXT40FP050 TEXT64FP002A5 TEXT90FN002AA Sheath TEXT90FMBN010AA(i) TEXT90FMBN030AA(i) TEXT90FMBN050AA(i) TEXT90FMBN100AA
10 30 50 100
Jelly Filled, Polyethylene Sheath 0.40 5.6 150 B 0.40 10.0 150 B 0.40 25.0 150 B 0.64 3.1 58.6 A Jelly Filled, Polyethylene/Nylon Sheath 9 0.90 9 27.9 B Jelly Filled, Moisture Barrier Polyethylene/Nylon 14.1 0.90 25 27.9 B 21.25 0.90 63 27.9 B 27.29 0.90 104 27.9 B 36.8 0.90 204.0 27.9 B
60
D DATA/COMMS
MINING
No. of cores 7 9 10 12 16 25
2 2 2 2 2 2
4.0 8.6 4.0 6.7 4.0 9.35 5.0 10.4 6.0 12.5 6.7 13.9
61
DATA/COMMS
Unscreened
MINING
Max. cond. Voltage Product resistance rating code @ 20C ohm/km 13.6 ELV JRS1502A5* 26.0 250/250 CBLR02* 21.2 450/750 CACP03* 13.6 450/750 CACP05*
Nominal Stranding conductor area No./mm mm2 1.5 7/0.50 0.75 24/0.20 1.0 7/0.40 1.5 7/0.50
1.5
*Pack sizes.
62
Fire Alarm
Nominal Approx. Core Sheath overall mass colours colour diameter/size mm kg/100m 7.0 7 Red, White Red 3.4 5.5 4 Red, White Red 4.3 6.7 6 Red, White Red 4.6 7.3 10 Red, White Red
7/0.50
7.0
Red, Black
DATA
DATA/COMMS MINING
63
64
ACCESSORIES GLANDS
UT
Mounting Cable details ARMOUR WIRE thread Varolex BODY 'O' RING dia. len. product FIBRE WASHER mm code
DIM E
VersolexSEAL Versolex SLEEVE 4C product 5C product GLAND NUT code code
CLAMPING RING
PVC shroud (orange) ALCSG0 ALCSG2 ALCSG3 ALCSG3 ALCSG3 ALCSG4 ALCSG5 ALCSG6
THREAD DIA
FIBRE WASHER
M12 12 M1612 M2012 FTDP07,P09 GETR04,R05,R06 BWTR04,R05 M2512 FTDP11, * P13,P15 FTTR07,X01 BWTR07 M3212 FTDC17,C18 FTTX02,X03 BWTX01,X02 M4015 FTDC19,C20 FTTX04,X05 BWTX03,X04 M5015 THREAD FTDC22 FTTX06,X07 BWTX05 LENGTH M6319 FTDP23,P24 FTTE87 BWTX06 M7519 FTDP25 GLAND LENGTH FTTE88 M7519 FTDP26 FTTE90AA003 M7519 FTDP27 M7519 FTTE89AA003
DIM OA
THRE
FIBRE WASHER
THREAD DIA
DIM OA
DIM OA
DIM Q
THREAD DIA
THRE
GLAND LENGTH
*FTDP11 Dimensions are within the gland working range but outside the dimension used in certification testing.
65
ACCESSORIES GLANDS
Cable details Seal B (thick) Seal A (thin) OA OA OA OA min max min max 3.5 3.5 7.5 7.5 11.0 17.0 23.0 30.0 36.0 46.0 56.0 68.0 82.0 92.0 98.0 6.0 5.0 10.0 10.0 15.0 20.0 26.5 33.5 42.0 52.0 65.0 75.0 89.0 98.0 105.0
DIM OA
BODY
GLAND NUT
PVC shroud orange* ALCSG0 ALCSG0 ALCSG0 ALCSG1 ALCSG1 ALCSG3 ALCSG3 ALCSG4 ALCSG5 ALCSG6 ALCSG7 ALCSG9 ALCSG10 ALCSG11 ALCSG11
THREAD DIA
FIBRE
M12 10 1.5 3.5 M16 10 1.5 3.5 M16 10 5.0 7.5 M20 10 5.0 7.5 M20 10 10.0 11.0 M25 12 THREAD14.5 17.0 M32 12 LENGTH 20.0 23.0 M40 15 26.0 GLAND LENGTH 30.0 M50 15 33.0 36.0 M63 19 41.5 46.0 M75 19 51.0 56.0 M90 30 64.0 68.0 M105 30 75.0 80.0 M120 30 89.0 92.0 M120 30
SEAL BODY FIBRE WASHER
GLAND NUT
THREAD DIA
66
*For Black Shroud add B to part number: ALCSG2B. Note: To comply with IP68 approval, the washer supplied must be installed on mounting thread.
DIM OA
THREAD DIA
ACCESSORIES GLANDS
Alco Metal Cable Glands Hazardous Area Type HUW (Grpl/IIC, Ex d, Ex e, IP68)(AUS Ex 03 3903)
Item number ALCHUW20SB ALCHUW20A ALCHUW20B ALCHUW25 ALCHUW32 ALCHUW40 ALCHUW50 ALCHUW63 ALCHUW75 ALCHUW 90 ALCHUW105 ALCHUW120A ALCHUW120B Mounting thread dia. length mm Cable details PVC Seal C (thickest) Seal B (thick) Seal A (thin) shroud OA OA OA OA OA OA min max min max min max (orange) 8.0 10.0 8.0 10.0 12.0 14.0 16.0 19.0 22.0 25.0 28.5 31.0 39.0 42.0 50.0 53.0 61.0 64.0 70.0 75.0 82.0 89.0 92.0 98.0 98.0 105.0 ALCSG1 ALCSG3 ALCSG3 ALCSG3 ALCSG3 ALCSG4 ALCSG6 ALCSG7 ALCSG7 ALCSG9
M20 12 4.0 8.0 M20 12 6.5 8.0 M20 12 10.0 12.0 M25 12 14.0 16.0 M32 15 19.0 22.0 M40 15 25.0 28.5 M50 20 31.0 36.0 36.0 39.0 M63 25 42.0 46.5 46.5 50.0 M75 25 53.0 57.0 57.0 61.0 M90 30 64.0 68.0 M105 30 75.0 80.0 M120 30 89.0 92.0 M120 30
FIBRE WASHER SEAL BODY
GLAND NUT
A B FIBRE WASHER
THREAD DIA
DIM OA
THREAD DIA
THRE
*For black shroud add B to part number: ALCSG2B. Note: To comply with IP68 approval, the washer supplied must be installed on mounting thread.
SEAL
67
META
ACCESSORIES GLANDS
Mounting thread dia. length mm M16 12 M20 12 M20 12 M20 12 M20 12 M25 14 M32 14 M40 15 M50 15 M50 15 M63 19 M63 19 M75 19 M90 19
Cable details overall over bedding SWA min. max. max. dia. mm mm mm mm 10.5 10.5 14.5 14.5 19.5 20.0 26.0 33.0 41.5 49.0 51.0 62.0 63.0 75.0 15.5 15.5 17.5 20.0 22.5 26.0 33.5 42.0 51.0 56.0 64.0 69.0 75.0 90.0
DIM E
PVC shroud (orange) ALCSG2 ALCSG1 ALCSG1 ALCSG3 ALCSG3 ALCSG3 ALCSG4 ALCSG5 ALCSG6 ALCSG6 ALCSG7 ALCSG7 ALCSG8 ALCSG9
BODY FIBRE WASHER
10.0 10.0 11.5 14.0 16.0 19.0 26.0 33.0 42.0 44.5 55.0 56.5 63.0 75.0
CLAMPING RING SEAL SLEEVE GLAND NUT
0.81.25 0.81.25 0.81.25 0.81.25 0.81.25 1.251.6 1.251.6 1.62.0 2.02.5 2.50 2.53.15 2.53.15 2.53.15 2.53.15
IN
THREAD DIA
DIM OA
THREAD DIA
DIM OA
GLAND LENGTH
68
*For Black Shroud add B to part number: ALCSG2B. Note: To comply with IP68 approval, the washer supplied must be installed on mounting thread. Two weatherproof seals are provided with each gland. Fitting instructions will define the seal suitable for your application.
BEAD CHAIN METAL SCREEN BODY INNER SEAL (C) OUTER SEAL (A or B) SLEEVE FIBRE WASHER
LAND NUT
BO
ACCESSORIES GLANDS
Alco Metal Cable Glands Hazardous Area Type HAW (Grpl/IIC, Ex d, Ex e, IP68)(AUS Ex 03.3904)
Item number ALCHAW20LR ALCHAW20 ALCHAW20SB ALCHAW25A ALCHAW25B ALCHAW32A ALCHAW32B ALCHAW40A ALCHAW40B ALCHAW50A ALCHAW50B ALCHAW63A ALCHAW63B ALCHAW75A ALCHAW75B ALCHAW90A ALCHAW90B
THREAD DIA
Cable details Barrier Over bedding Cable SWA gland diameter diameter diameter requirements DIM E min. ARMOUR max. WIRE min. max. mm mm mm mm mm CONE CLAMPING RING
INNER SEAL
ND NUT
M20 15 5.2 8.0 7.8 'O' RING BODY 6.5 10.0 11.5 M20 20 FIBRE WASHER M20 16 9.1 12.3 14.0 M25 20 10.0 14.0 16.0 M25 20 14.0 18.0 20.0 M32 20 18.0 21.5 24.0 M32 20 21.5 25.0 28.0 M40 20 25.0 29.0 32.0 20 28.5 37.0 M40 THREAD LENGTH 33.5 41.0 M50 20 33.0 37.5 GLAND LENGTH M50 20 36.5 42.0 45.0 M63 25 42.0 47.0 51.0 M63 25 47.0 53.0 57.0 M75 25 52.5 58.5 62.0 M75 25 58.0 64.0 66.0 M90 25 63.0 69.0 73.0 M90 25 68.0 75.0 81.0
BODY FIBRE WASHER DIM G
12.7 16.0 18.0 20.0 24.0 28.0 32.0 37.0 42.0 46.0 51.0 57.0 63.0 69.0 75.0 82.0 90.0
0.700.90 SLEEVE 0.801.25 0.801.25 0.801.25 1.251.60 1.251.60 1.602.00 1.602.00 1.602.00 2.002.50 2.002.50 2.503.15 2.503.15 2.503.15 2.503.15 2.503.15 2.503.15
ARMOUR WIRE CLAMPING RING
OUTER SEAL
ALCHAW20LR-B ALCSG1 ALCHAW20-B ALCSG2 GLAND NUT ALCHAW20SB-B ALCSG2 ALCHAW25A-B ALCSG3 ALCHAW25B-B ALCSG3 ALCHAW32A-B ALCSG4 ALCHAW32B-B ALCSG4 ALCHAW40A-B ALCSG4 ALCHAW40B-B ALCSG5 ALCHAW50A-B ALCSG6 ALCHAW50B-B ALCSG6 ALCHAW63A-B ALCSG7 ALCHAW63B-B ALCSG7 ALCHAW70A-B ALCSG8 ALCHAW70B-B ALCSG8 ALCHAW90A-B ALCSG9 ALCHAW90B-B ALCSG9
DIM OA
DIM OA
(A or B) VE GLAND NUT
DIM E
CLAMP SEAL
THREAD DIA
DIM OA
69
Note (page 59): Alco HAW glands are suitable for use with elastomer seals or as a barrier gland. Two seals are provided for bedding to body sealing (see fitting instructions). Alternatively, discard the seals and use the epoxy resin and insert to provide a barrier. When ordering add B to the standard code as indicated in the second last column above.
Dim. F
Dim. B
Dim. C
Dim. A
70
ACCESSORIES SHROUDS
Standard colour for all shrouds is orange. Sizes 1, 2 and 2L are stocked in black. For black shroud part numbers add B to the orange item number in the LH column.
B A
(A+10) (A+5)
C D
71
72
Where a flexible cord is wound on a drum, multiply current carrying capacities by the following factor: Number of layers: 1 2 3 4 Derating factor: 0.76 0.58 0.47 0.40
73
74
A Maximum duty cycle (AS 1995) 10 minute cycle 5 minute cycle 100% 60% 30% 25% 60% 30% 25% 90 125 165 205 260 325 390 455 535 600 715 91 129 175 223 289 370 454 536 636 723 870 99 102 96 114 121 145 151 137 169 181 206 218 188 239 257 270 288 238 309 334 361 386 308 407 440 471 507 391 523 567 590 637 476 644 700 705 763 559 762 829 843 914 661 904 985 968 1051 747 1027 1120 1174 1276 895 1236 1348
Max. DC resist. at 20C m /m 1.91 1.21 0.780 0.554 0.386 0.272 0.206 0.161 0.129 0.106 0.0801
Voltage drop mV/A.m 1 phase 3 phase 5.06 3.10 1.88 1.39 1.05 0.707 0.566 0.453 0.373 0.326 0.276 4.38 2.68 1.63 1.20 0.906 0.612 0.490 0.392 0.323 0.282 0.239
75
76
Note: The current carrying capacities are based on an air ambient temperature of 40C, a maximum conductor temperature of 80C and exposure to direct sunlight having an intensity of 1000W/m 2. The values are based on the use of black XLPE. (a) Also for 2 conductor neutral screened aerial cable. (b) Also for 3 and 4 conductor neutral screened aerial cable. Under normal circumstances there will always be some air movement and the rating for 1.0m/s wind is recommended. General Note applies to all following current rating tables. Reference should be made to AS/NZS 3008.1 for the following derating factors for (a) Grounded circuits (b) Cables fixed to underside of ceilings (c) Cables on perforated or unperforated trays (d) Ambient temperature.
Note: The current carrying capacities are based on an air ambient temperature of 40C, a maximum conductor temperature of 75C and exposure to direct sunlight having an intensity of 1000W/m 2. The values are based on the use of black PVC. (a) Also for 2 conductor neutral screened aerial cable. (b) Also for 3 and 4 conductor neutral screened aerial cable. Under normal circumstances there will always be some air movement and the rating for 1.0m/s wind is recommended.
77
78
Cu Al 6 8 12 16 20 27 36 28 48 38 59 46 Cu Al Cu Al Cu Al Cu Al 18 18 21 51.6 23 23 26 33.0 32 32 36 18.0 41 41 47 11.2 52 52 58 7.50 69 69 77 4.46 122 95 89 69 99 77 2.81 4.68 158 123 116 90 129 100 1.78 2.95 190 147 139 108 155 120 1.29 2.14 225 174 168 130 186 145 0.96 1.58 277 215 206 160 228 177 0.680 1.10 332 257 252 195 278 215 0.507 0.804 378 294 287 223 316 245 0.415 0.644 424 329 329 255 354 274 0.352 0.535 480 374 373 291 408 317 0.301 0.439 556 434 438 342 472 368 0.255 0.352 628 491 496 388 546 425 0.229 0.300 713 564 575 454 621 487 0.209 0.256 805 644 649 520 721 570 0.194 0.226 904 737 750 611 816 652 0.181 0.202
Single Phase Current Ratings Two single core V-90 PVC or PVC/PVC 0.6/1kV cables.
Unenclosed Enclosed Buried Underground ducts Single Cond. Spaced Spaced Touching Conduit Partially Completely direct phase size from in air surrounded surrounded voltage by thermal drop surface by mV/A.m thermal insulation insulation mm2
Cu Al Cu Al Cu Al Cu Al Cu Al 1 16 16 13 13 11 1.5 21 21 16 18 14 2.5 30 29 23 24 20 4 40 39 31 32 25 6 51 49 40 41 33 10 69 67 54 54 44 16 92 72 89 69 72 56 70 54 56 43 25 124 96 119 92 97 75 94 73 75 58 35 153 119 145 113 119 92 112 87 90 70 50 187 145 177 137 146 113 138 107 110 86 70 238 184 223 173 184 143 170 132 136 105 95 295 229 276 214 230 178 212 164 169 131 120 344 267 321 249 267 208 242 188 193 150 150 395 307 367 285 308 239 282 219 225 175 185 459 357 424 331 358 279 320 249 256 199 240 549 427 505 394 428 334 381 298 305 238 300 636 495 582 456 495 388 400 744 583 676 535 577 456 500 867 685 780 624 668 535 630 1014 808 897 730 770 627
Single Phase Current Ratings Two single core XLPE/PVC 90 0.6/1kV cables.
Unenclosed Enclosed Buried Underground Cond. Spaced Spaced Touching Conduit Partially Completely direct ducts size from in air surrounded surrounded by thermal by thermal surface insulation insulation mm2 Cu Al 13 16 24 30 38 52 67 52 90 70 108 84 133 103 164 127 204 158 233 181 263 204 309 241 369 288 Cu Al Cu Al 8 20 10 26 14 36 19 46 24 58 32 78 43 33 139 107 58 45 179 139 72 56 215 167 255 198 313 243 375 291 427 332 480 372 543 423 630 492 711 556 808 638 913 729 1026 833 Cu Al 20 26 36 46 58 78 100 78 131 102 157 122 189 147 233 181 285 221 325 252 365 283 423 329 497 388 562 440 653 516 739 590 856 695 Cu Al Cu Al 24 54.1 30 34.7 41 18.9 53 11.8 66 7.87 87 4.68 112 87 2.95 4.91 146 114 1.87 3.08 175 136 1.35 2.24 211 164 1.01 1.65 258 200 0.710 1.15 309 239 0.528 0.840 358 278 0.431 0.672 401 311 0.365 0.557 463 359 0.311 0.455 536 417 0.262 0.363 620 482 0.233 0.307 706 553 0.211 0.261 800 632 0.196 0.228 930 740 0.184 0.204
Cu Al Cu Al 1 20 20 1.5 26 25 2.5 36 36 4 48 47 6 61 60 10 84 82 16 112 87 108 84 25 151 117 145 112 35 186 144 177 137 50 228 177 216 167 70 291 226 273 212 95 361 280 338 262 120 422 328 393 305 150 486 377 451 350 185 565 439 522 406 240 678 527 622 485 300 787 612 718 562 400 923 723 836 660 500 1078 850 966 772 630 1261 1003 1113 904
Cu Al 16 20 28 37 47 65 86 67 117 91 144 111 176 136 224 174 278 216 325 253 375 291 436 340 522 408 605 473 708 559 821 656 950 772
Cu Al 16 21 30 38 47 65 84 65 113 87 135 105 166 129 204 159 255 198 292 226 329 255 387 301 461 360
79
80
Enclosed Buried Underground Partially Completely direct ducts surrounded surrounded by thermal by thermal insulation insulation Cu 16 20 28 37 46 62 83 109 132 164 204 257 296 344 394 476 Cu 10 13 18 23 30 40 53 72 88 Cu 31 39 55 71 89 119 154 198 238 282 346 416 473 531 601 698 789 898 1018 1148 Cu 23 29 40 53 66 88 115 148 177 214 262 321 366 420 477 561 648 738 837 973 Cu 26 33 46 59 74 97 127 163 195 236 288 352 400 448 517 600 694 790 921 1045 Cu 57.4 36.8 20.1 12.5 8.35 4.97 3.12 1.99 1.43 1.07 0.751 0.556 0.453 0.382 0.323 0.271 0.240 0.216 0.199 0.185 Single phase voltage drop mV/A.m
Single Phase Current Ratings Two single core R-HF-110, R-E-110 or X-HF-110 cables.
Unenclosed Cond. Spaced Spaced Touching Conduit size from in air surface mm2
1 1.5 2.5 4 6 10 16 25 35 50 70 95 120 150 185 240 300 400 500 630
Cu 25 32 45 59 75 103 137 183 225 276 349 434 505 581 673 806 934 1094 1278 1498
Cu 24 31 44 58 73 99 131 175 214 261 328 406 471 540 624 743 857 998 1155 1334
Cu 20 25 36 47 59 81 107 143 176 215 272 339 394 454 527 630 730 853 990 1146
Cu 20 25 35 46 58 78 104 137 165 205 255 321 369 430 493 594
Unenclosed Enclosed Buried U/ground Single ducts phase Cond. Spaced Touching Conduit Unenclosed Unenclosed direct & completely voltage size in air & partially round or surrounded surrounded drop flat cable by thermal by thermal mV/A.m insulation insulation mm 2
Single Phase Current Ratings Two core V-90 PVC/PVC 0.6/1kV cables. Table of ratings are also applicable to armoured cables.
1 1.5 2.5 4 6 10 16 25 35 50 70 95 120 150 185 240 300 400 500 4.67 2.93 2.13 1.57 1.09 0.798 0.638 0.528 0.431 0.343 0.290 0.245 0.215
Cu Al 15 19 27 37 46 64 85 66 113 88 139 108 170 132 215 167 265 205 307 239 351 272 403 314 477 373 547 429 631 500 716 575
Cu Al 14 18 26 34 44 60 80 62 107 83 131 101 159 124 201 156 248 192 288 224 328 255 377 294 446 349 511 401 589 467 668 536
Cu Al 13 16 23 30 39 52 68 52 90 70 112 87 133 103 170 132 204 158 241 187 271 210 313 244 364 285 424 333 482 383 561 451
Cu Al 11 14 20 27 35 48 64 49 85 66 105 81 127 99 161 125 198 154 230 179 263 204 302 235 357 279 409 321 471 373 534 429
Cu Al 7 9 13 17 22 30 40 31 53 41 65 51
Cu Al 17 21 30 39 50 66 114 88 147 114 178 138 211 163 259 201 311 241 355 276 398 309 449 350 520 406 586 460 663 526 741 595
Cu Al 17 21 30 39 50 66 86 66 112 87 136 106 162 126 202 157 243 189 282 220 317 246 363 283 421 329 483 379 548 434 628 504
Cu 51.6 33.0 18.0 11.2 7.50 4.46 2.81 1.78 1.28 0.957 0.673 0.498 0.405 0.342 0.290 0.243 0.215 0.194 0.180
Al
81
82
Single phase voltage drop mV/A.m Cu Al Cu Al Cu Al Cu Al 14 9 19 19 18 11 24 24 25 16 34 34 33 21 45 45 42 27 56 56 58 36 75 75 78 60 49 38 132 102 98 75 105 81 66 51 170 132 128 99 129 100 81 63 205 159 154 119 158 122 244 189 185 144 200 155 300 233 228 177 247 192 360 279 279 216 287 223 410 319 318 247 328 255 460 357 365 283 379 295 520 405 413 322 449 351 603 471 485 379 516 404 680 533 558 437 596 472 771 610 663 501 678 544 862 691 728 583 Cu Al 54.1 34.7 18.9 11.8 7.85 4.68 2.95 4.90 1.86 3.08 1.35 2.23 1.00 1.65 0.703 1.15 0.520 0.835 0.423 0.666 0.355 0.550 0.299 0.448 0.249 0.355 0.219 0.298 0.198 0.249 0.182 0.218
Single Phase Current Ratings Two core XLPE/PVC 90 0.6/1kV cables. Table of ratings are also applicable to armoured cables.
Unenclosed Enclosed Buried Underground Cond. Spaced Touching Conduit in Unenclosed Unenclosed direct ducts size air round & partially & completely or flat surrounded surrounded cable by thermal by thermal insulation insulation mm 2
Cu Al 1 18 1.5 24 2.5 34 4 45 6 57 10 78 16 104 81 25 140 109 35 173 134 50 211 163 70 268 208 95 331 257 120 385 299 150 441 342 185 509 396 240 604 472 300 694 544 400 804 636 500 915 734
Cu Al 17 22 31 42 53 73 97 75 131 102 162 125 197 153 250 194 309 239 359 279 411 319 473 369 562 439 645 505 745 590 848 680
Cu Al 16 20 28 37 46 63 82 63 110 85 132 102 162 126 200 155 250 194 285 222 332 257 377 293 448 350 523 410 596 472 695 557
Unenclosed Enclosed Buried Underground Cond. Spaced Spaced Touching Conduit Partially Completely direct ducts size from in air surrounded surrounded surface by thermal by thermal mm2 insulation insulation
Three Phase Current Ratings Three single core V-90 PVC or PVC/PVC 0.6/1kV cables.
Cu Al Cu Al Cu Al Cu Al Cu Al 1 16 14 13 12 10 1.5 20 17 16 15 12 2.5 29 25 23 21 17 4 38 33 31 28 23 6 49 42 40 35 28 10 67 58 54 47 37 16 89 69 77 59 72 56 62 48 50 39 25 120 93 1 03 80 97 75 81 63 64 50 35 148 115 1 27 98 119 92 100 78 80 62 50 181 141 1 56 121 146 113 119 92 95 74 70 230 179 1 97 153 184 143 152 118 122 94 95 287 222 2 46 191 230 178 183 142 147 114 120 335 260 2 87 223 267 208 217 169 173 135 150 385 298 3 30 256 308 239 244 190 195 152 185 447 347 3 83 299 357 278 284 222 227 177 240 535 417 4 57 358 426 334 331 259 265 207 300 620 483 5 29 415 492 387 388 305 311 244 400 726 570 6 15 488 573 455 442 351 353 281 500 846 669 7 10 571 661 532 523 421 418 337 630 990 789 8 17 668 760 622 588 481 471 385 4.05 2.55 1.85 1.37 0.956 0.702 0.565 0.472 0.391 0.319 0.276 0.240 0.216 0.197
Cu Al Cu Al Cu Al Cu Al Cu Al Cu 6 16 16 19 44.7 51.6 8 20 20 24 28.6 33.0 12 27 27 33 15.6 18.0 16 36 36 43 9.71 11.2 20 45 45 53 6.49 7.50 27 59 59 70 3.86 4.46 36 28 104 81 78 60 90 70 2.43 4.05 2.81 48 38 134 104 100 78 117 91 1.54 2.55 1.79 59 46 160 124 122 94 140 108 1.12 1.85 1.29 190 147 144 112 168 131 0.834 1.37 0.970 233 181 180 140 205 159 0.589 0.952 0.690 279 216 217 168 250 194 0.439 0.696 0.519 317 247 252 196 283 220 0.359 0.558 0.429 356 276 283 220 317 246 0.305 0.463 0.368 402 313 325 253 365 284 0.261 0.380 0.320 465 364 377 295 422 329 0.221 0.305 0.277 524 412 434 341 488 380 0.198 0.260 0.253 593 471 492 391 553 434 0.181 0.222 0.233 668 537 571 459 641 507 0.168 0.196 0.221 748 612 639 523 723 578 0.157 0.175 0.209
Al
83
84
Three phase voltage drop mV/A.m Cu Al Cu Al Cu Al Cu Al Cu Al 18 18 22 46.8 46.8 22 22 27 30.0 30.0 31 31 38 16.4 16.4 40 40 49 10.2 10.2 50 50 60 6.81 6.81 67 67 79 4.05 4.05 117 91 86 66 101 79 2.55 4.25 2.55 4.25 151 117 113 87 132 103 1.62 2.67 1.62 2.67 180 140 137 1 06 158 122 1.17 1.94 1.18 1.94 214 166 163 1 26 190 147 0.872 1.43 0.878 1.44 262 203 203 1 58 232 180 0.615 0.997 0.623 1.00 313 243 244 1 90 276 214 0.457 0.727 0.467 0.733 356 277 284 2 21 320 248 0.373 0.582 0.385 0.589 400 310 320 2 49 358 277 0.316 0.482 0.330 0.491 452 352 363 2 83 413 321 0.269 0.394 0.285 0.404 523 409 426 3 33 477 371 0.227 0.314 0.245 0.327 589 463 491 3 85 552 430 0.202 0.266 0.222 0.281 668 530 557 4 42 626 491 0.183 0.226 0.205 0.243 752 604 648 5 20 707 559 0.170 0.197 0.193 0.216 843 688 727 5 93 820 654 0.159 0.177 0.182 0.198
Three Phase Current Ratings Three single core XLPE/PVC 90 0.6/1kV cables.
Unenclosed Enclosed Buried Underground Cond. Spaced Spaced Touching Conduit Partially Completely direct ducts size from in air surrounded surrounded surface by thermal by thermal mm2 insulation insulation
Cu Al Cu Al Cu Al Cu Al Cu Al Cu Al 1 19 16 16 15 12 8 1.5 25 21 20 18 15 10 2.5 35 30 28 25 20 14 4 46 40 37 33 26 19 6 59 50 47 42 34 24 10 81 69 65 56 45 32 16 108 84 92 71 86 67 72 56 58 45 43 33 25 146 113 125 97 117 91 97 75 77 60 58 45 35 180 140 154 119 144 111 1 20 93 96 75 72 56 50 221 171 188 146 176 136 1 43 111 114 89 70 282 219 240 186 224 174 1 83 142 146 114 95 350 271 298 232 278 216 2 20 171 176 137 120 410 318 349 271 325 253 2 61 203 209 162 150 472 366 403 313 375 291 2 95 229 236 183 185 550 427 468 365 435 339 3 35 261 268 209 240 660 513 560 438 521 407 3 99 312 320 250 300 766 596 648 508 602 472 4 69 368 375 294 400 899 705 756 599 702 557 5 34 424 427 339 500 1 051 829 874 703 812 652 6 33 509 506 407 630 1 230 978 1 010 8 24 938 765 7 14 583 571 466
Three Phase Current Ratings Three single core R-E-110/HFS-110-TP 110 0.6/1kV cables.
Unenclosed Enclosed Buried Underground Cond. Spaced Spaced Touching Conduit Partially Completely direct ducts size from in air surrounded surrounded surface by thermal by thermal insulation insulation mm2
1 1.5 2.5 4 6 10 16 25 35 50 70 95 120 150 185 240 300 400 500 630
Cu 24 31 43 57 73 99 132 177 218 267 339 422 492 565 656 786 912 1069 1248 1462
Cu 21 27 38 50 63 86 114 153 188 230 291 363 422 486 564 674 780 910 1053 1217
Cu 20 25 36 47 59 81 107 143 176 215 272 339 394 453 526 629 727 847 981 1132
Cu 17 22 32 41 51 71 93 125 151 182 234 285 337 382 449 548 626 718 865 983
Cu 14 18 25 33 41 57 74 100 121 146 187 228 269 306 359 439 501 575 692 787
Cu 10 13 18 23 30 40 53 72 88
Cu 20 25 36 46 57 77 130 168 201 237 291 348 396 445 503 583 657 746 843 947
Cu 20 25 36 46 57 77 99 130 155 184 230 277 322 362 415 492 556 631 736 827
Cu 24 30 42 54 67 88 115 148 176 212 259 315 357 400 461 533 617 700 815 920
Cu 49.7 31.9 17.4 10.8 7.23 4.3 2.7 1.72 1.24 0.924 0.65 0.481 0.392 0.331 0.28 0.235 0.208 0.187 0.172 0.160
Cu 49.7 31.9 17.4 10.8 7.23 4.3 2.71 1.72 1.25 0.929 0.657 0.491 0.403 0.344 0.296 0.252 0.227 0.208 0.195 0.184
85
86
Cu 9 12 17 23 30 41 54 73 90 109 138 170 198 226 259 307 4.04 2.54 1.84 1.36 0.948 0.691 0.552 0.457 0.373 0.297 0.251 0.212 0.186 Al 42 57 69 85 107 132 154 175 203 240 Cu 6 8 11 15 19 25 34 46 56 Al 26 35 43 Cu 14 18 25 33 42 55 96 125 150 178 219 263 300 336 379 438 493 557 620 Al 75 97 117 138 170 204 233 261 296 344 388 444 501 Cu 14 18 25 33 42 55 73 94 114 136 170 208 237 266 304 359 404 468 522 Al 56 73 89 105 132 161 184 207 237 281 318 374 422 Cu 44.7 28.6 15.6 9.71 6.49 3.86 2.43 1.54 1.11 0.829 0.583 0.431 0.351 0.296 0.251 0.21 0.186 0.168 0.156 Al
Three Phase Current Ratings Three and four core V-90 PVC/PVC 0.6/1kV cables. Table of ratings are also applicable to armoured cables.
Unenclosed Enclosed Buried U/ground Three ducts phase Cond. Spaced Touching Conduit Unenclosed Unenclosed direct & completely voltage size in air & partially round or surrounded surrounded drop flat cable by thermal by thermal mV/A.m insulation insulation mm 2
Cu 13 16 23 31 40 54 72 97 120 146 185 228 265 303 348 412 472 544 616
Al 56 75 93 113 143 177 206 235 272 323 372 434 498
Cu 12 15 22 29 37 51 68 91 112 137 172 213 247 282 324 383 438 504 571
Al 53 71 87 106 134 165 192 219 253 301 345 402 461
Three Phase Current Ratings Three and four core XLPE/PVC 90 0.6/1kV cables. Table of ratings are also applicable to armoured cables.
Unenclosed Enclosed Buried U/ground Three ducts phase Cond. Spaced Touching Conduit Unenclosed Unenclosed direct & completely voltage size in air & partially round or surrounded surrounded drop flat cable by thermal by thermal mV/A.m insulation insulation mm 2
Cu 16 20 28 38 48 66 88 119 147 180 229 283 330 377 436 517 594 685 779
Al 68 93 114 140 178 220 256 293 340 405 467 546 629
Cu 14 19 26 35 45 62 83 111 137 168 213 263 306 350 404 479 549 632 718
Al 64 86 106 130 165 204 238 272 315 375 432 504 579
Cu 7 9 13 18 22 31 41 56 69
Al 32 43 53
Cu 16 20 29 37 46 63 110 143 172 204 251 302 344 385 435 504 567 640 714
Al 85 111 133 159 195 234 267 299 340 395 446 510 577
Cu 16 20 29 37 46 63 81 107 130 155 193 233 270 304 348 411 463 524 601
Al 63 83 101 120 150 181 210 236 272 322 365 417 485
Cu Al 46.8 30 16.4 10.2 6.8 4.05 2.55 4.24 1.61 2.67 1.17 1.93 0.868 1.43 0.609 0.993 0.45 0.723 0.366 0.577 0.307 0.476 0.259 0.388 0.216 0.307 0.19 0.258 0.171 0.216 0.158 0.189
87
88
Three Phase Voltage Drop mV/A.m Cu 9 12 17 22 28 38 50 67 83 Cu 25 31 44 56 71 94 122 158 190 226 277 333 379 426 481 558 629 713 797 Cu 19 24 33 43 53 71 93 122 146 177 217 267 304 346 391 463 522 608 680 Cu-Flex Cu 20 49.7 24 31.9 31 17.4 41 10.8 51 7.22 71 4.29 91 2.70 118 1.71 143 1.24 178 0.920 217 0.645 259 0.475 298 0.385 341 0.322 381 0.271 453 0.224 509 0.196 606 0.175 680 0.160
Three Phase Current Ratings Three and four core R-HF-110, R-E-110 or X-HF-110 cables.
Unenclosed Enclosed Buried Underground Cond. Spaced Touching Exposed Conduit Partially Completely direct ducts size to sun in air surrounded surrounded by thermal by thermal insulation insulation mm2
Cu Cu-Flex Cu Cu-Flex Cu Cu-Flex Cu Cu-Flex Cu 1 20 21 18 19 17 18 16 17 13 1.5 25 26 24 24 22 22 20 21 16 2.5 35 34 33 32 30 29 29 27 23 4 47 45 44 42 40 39 38 36 30 6 59 57 56 54 50 49 47 46 38 10 81 80 76 75 69 68 64 65 51 16 107 106 101 99 91 89 86 84 68 25 144 140 135 131 121 118 116 112 93 35 177 173 166 162 148 145 140 137 112 50 216 218 202 204 180 182 174 175 139 70 272 273 255 255 227 227 217 217 173 95 337 327 314 306 278 271 270 263 216 120 391 387 364 360 322 318 311 306 249 150 447 444 416 413 367 364 360 356 288 185 515 505 479 470 421 412 411 402 329 240 611 602 567 559 496 488 498 489 398 300 701 688 650 638 567 555 400 810 817 751 756 651 655 500 921 936 852 865 737 746
CABLE SELECTION
The size and type of cable required for a given application should be selected according to the following criteria:
2. Installation conditions
Olex cables are available for aerial, underground and submarine installations as well as in conduit, on racks or trays in air. Special constructions available include: Brass or copper taped or nylon sheathed cables for resistance to termite and marine borer. Steel wire armoured for areas where there is a high risk of mechanical damage. Alsecure fire performance low smoke halogen free cables for emer gency power and lighting and other purposes in areas of high fire risk. Alsecure Ceramifiable is a world first in fire performance cable with a polymer layer that hardens into a protective shield when exposed to fire. the new high performance multipurpose cable for fixed & flexible Versolex, applications. Lead alloy sheathing as a barrier to moisture or hydrocarbons. Alsecure Envirolex cables with low smoke emission and no halogen or lead for environmentally sensitive areas. Flexolex cables for flexible applications and where flexibility provides advantages during installation.
89
CABLE SELECTION
dielectric properties and high voltage grades are available for cables up to 33kV. In addition, EPR is halogen free and therefore does not emit toxic or corrosive by-products when burnt.
Olex CPE (Chlorinated Polyethylene) is an excellent flexible insulation and heavy
duty sheathing material. Although having lower insulation resistance than EPRit is suitable for low voltage cable insulation and is used as such in welding cables because of its oil resistance. For special purposes a sheath of Olex EA (Ethylene Acrylic) material can be provided subject to special order. This material is halogen free, extremely flame retardant and has better oil resistance than CPE. EPR/EA cables can safely be used inplenum air ducts and other applications where high flame retardance and freedom from acid gas emission is required. EPR, CPE and EA are all suitable for continuous operation up to 90C.
90
CABLE SELECTION
insulation materials, and is used in a wide range of cables from low voltage up to 275kV. It is halogen-free and also free of heavy metals such as lead and antimony. It has low smoke and toxicity when burned. It is a suitable alternative to PVC and is becoming more widely specified where there are environmental concerns. Ceramifiable An insulation material that is polymeric in its normal state, but converts to an insulating ceramic that provides circuit integrity when burned. Normal state properties are suitable for continuous operation at 110C. It is halogen-free, lead and antimony-free, and does not emit toxic or corrosive products when burned.
HFS-110-TP. Olex offers this thermoplastic, halogen and heavy metal-free sheathing
as an alternative to PVCwhen these characteristics are required. The material has reasonable oil resistance and flexibility, with a high resistance to spread of fire.
91
CABLE INSTALLATION
In all cases, cables must be installed in compliance with the safety requirements of AS/NZS3000.
ground in which they are installed and the degree to which heat can escape. Except for a group of single core cables carrying the phase currents of a circuit, cables should be spaced to allow heat to escape. Wherever cables are installed in close proximity, especially in the ground, or enclosed in such a way as to restrict heat loss, their current carrying capacities must be reduced using a derating factor appropriate to the situation.
For minimum voltage drop single core cables carrying the phase currents of
a single circuit should be installed as closely as possible together, to minimise inductive reactance. The preferred formation for three phase conductors is a trefoil or cloverleaf pattern although flat formation may also be used. Sheaths should be in contact with one another in either case. A single core cable generates an alternating magnetic field around itself which can cause large increases in voltage drop and power loss due to transformer effect when ferrous metal (iron and steel) is allowed to encircle the cable. Steel racking or ladder will not cause trouble, but the following must be observed: Steel wire or tape armour is never used on a single core cable for AC use. Where three single phase cables pass through a steel bulkhead all must pass through the same hole. Where glanding is required it is usual to cut out a panel and replace this with a non-ferrous (metal or plastic) plate in which the three or four glands are mounted. Should plastic or non-ferrous gland plate material not be available, an alternative is to cut a slot (hacksaw blade width is adequate) between adjacent gland holes. This will provide physical and electrical isolation for the eddy current paths and stop the cable from overheating.
92
GENERAL DATA
Minimum size of copper earthing conductors.
Nominal area active conductors mm 2 1 1.5 2.5 4 6 10 16 25 35 50 70 95 120 150 185 240 300 400 500 630 For copper active conductors mm 2 1.0* 1.5* 2.5 2.5 2.5 4 6 6 10 16 25 25 35 50 70 95 120 120 120 120 For aluminium active conductors mm 2
*As defined in AS/NZS 3008.1.1. **V-90HT PVC may be operated up to 105C for restricted periods only.
93
GENERAL DATA
DC Conductor resistances for insulated cables for fixed installations. Solid, stranded conductors; also refer to AS/NZS 1125.
Nominal Conductor conductor type area mm 2 0.5 1.0* 1.0 1.5* 1.5 2.5* 2.5 4 6 10 16 25 35 50 70 95 120 150 185 240 300 400 500 630 Solid Solid Stranded Solid Stranded Solid Stranded Stranded Stranded Stranded Stranded Stranded Stranded Stranded Stranded Stranded Stranded Stranded Stranded Stranded Stranded Stranded Stranded Stranded
Single Core or Multicore Maximum DC resistance at 20C/ /km Copper Plain 36.0 18.1 21.2 12.1 13.6 7.41 7.41 4.61 3.08 1.83 1.15 0.727 0.524 0.387 0.268 0.193 0.153 0.124 0.0991 0.0754 0.0601 0.0470 0.0366** 0.0283** Copper Tinned 36.7 18.2 21.6 12.2 13.8 7.56 7.56 4.70 3.11 1.84 1.16 0.734 0.529 0.391 0.270 0.195 0.154 0.126 0.100 0.0762 0.0607 0.0475 0.0369** 0.0286** Aluminium
1.91 1.20 0.868 0.641 0.443 0.320 0.253 0.206 0.164 0.125 0.100 0.0778 0.0605** 0.0469**
94
GENERAL DATA
Useful 3 phase formulae.
kW = kVA pf
hp 746 kW = 1000 Eff Line Amps Line Volts 1.732 pf kW = 1000 kW kVA = pf hp 746 kVA = 1000 Eff pf Line Amps Line Volts 1.732 kVA = 1000 kW 1000 Line Amps = Line Volts 1.732 pf kVA 1000 Line Amps = Line Volts 1.732 hp 746 Line Amps = Line Volts 1.732 Eff pf Horsepower kW 1000 Eff = (hp) = 746
kVA 1000 Eff pf hp = 746 Line Amps Line Volts 1.732 Eff pf hp = 746 5 1 Line Current = Supply Voltage 100 Route LengthVoltage Drop Factor
95
GENERAL DATA
American conductor sizes M.C.M. & A.W.G. conversion to mm2
M.C.M. 1300 1200 1100 1000 950 900 850 800 750 700 mm 2 659 608 557 507 481 456 431 405 380 355 M.C.M. 650 600 550 500 450 400 350 300 250 200 mm 2 329 304 279 253 228 203 177 152 127 101
Note: The American term mil refers to a milli-inch (1/1000 ) NOTa millimetre. A Circular Mil. (C.M.) is the area of a circle 1 mil in diameter. The term M.C.M. refers to an area of 1000 Circular Mils and is the same as kcmil. 1.0mm 2 is approximately 1974 Circular Mils. A.W.G.
Diameter mm 2 A.W.G. mm 11.68 10.40 9.27 8.25 6.54 5.19 4.12 3.25 107.3 85.0 67.4 53.5 33.6 21.2 13.3 8.4 10 12 14 16 18 20 22 24
0000 000 00 0 2 4 6 8
ote: The American Wire Gauge (AWG) was originally known as the Brown & Sharp (B&S) N Gauge and both terms are synonymous. The gauge number can apply to a single wire or to a stranded or bunched conductor. The cross-sectional areas given apply to single wire only. The larger gauges are sometimes written using a number to denote the number of zeroes, e.g. 0 gauge can be written 1/0 and 000 as 3/0.
96
GENERAL DATA
Factor Cable minimum installed bending radii. During Type Voltage Instal. instal. Fixed wiring PVC or Elastomer or XLPE (1) Single and Multicore (a) Overall diameter to & including 25mm 0.6/1kV (b) Overall diameter over 25mm 0.6/1kV (2) Multicore SWA or metal tape 0.6/1kV (3) Solid aluminium, compacted or sector 0.6/1kV Flexible Cords PVC or Elastomer 250/440V 0.6/1kV 0.6/1kV Flexible Cables PVC or Elastomer (incl. Versolex ) Lead Sheath PVC or Elastomer 0.6/1kV Paper Insulated Single Up to 11kV Multicore Up to 11kV Single Core 22kV Multicore 22kV Single Core 33kV Multicore 33kV Trailing Elastomer (1) Single and Multicore 1.1kV (2) Single and Multicore 3.3kV & above Welding PVC or Elastomer 0.6/1kV Nylon Covered All Cables HDPE Sheathed All Cables Factor cable overall diameter = minimum internal bending radius.
4 6 12 8 4 4 4 12 15 12 18 15 20 18 6 12 6 20 15
6 9 18 12
18 22 18 27 22 30 27
30 25
97
GENERAL DATA
Number of Cables in Conduit. Recommended maximum number of thermo plastic insulated unsheathed single core 0.6/1kV copper or aluminium cables permitted in metallic and non-metallic conduit or pipe.
Nominal area mm 2 1 1.5 2.5 4 6 10 16 25 35 50 70 95 120 150 185 240 300 400 500 630
98
Notes: 1. For PVC flexible conduits, the recommendations are based on conduits used without fittings or with fittings only at the ends of the conduit run. Where intermediate fittings are used in a run of PVC flexible conduit, an appropriate reduction should be made in the number of cables drawn into the conduit. 2. One earth wire of appropriate size, as determined by the requirements of AS/NZS 3000, may be inserted in all conduits, provided that its insertion does not prevent easy drawing in of cables. 3. Table suitable for use with Olex manufactured product only.
GENERAL DATA
Number of Cables in Conduit. Calculated maximum number of thermoplastic insulated and sheathed single core copper or aluminium cables permitted in metallic and non-metallic conduit or pipe. 1.0 to 25mm2 450/750V to AS/NZS 5000.2 35 to 630mm2 0.6/1kV to AS/NZS 5000.1
Nominal area mm 2 1.0 1.5 2.5 4 6 10 16 25 35 50 70 95 120 150 185 240 300 400 500 630 Nominal size of conduit (mm) 20 25 32 40 50 HD HD HD HD HD 5 4 3 2 1 1 1 9 7 5 4 3 2 1 1 1 16 13 10 7 6 4 3 2 1 1 1 27 22 16 12 9 7 5 3 2 2 1 1 1 1 43 36 27 19 16 11 8 5 4 3 3 2 1 1 1 1 63 HD 72 59 44 32 26 18 14 9 7 6 4 3 3 2 1 1 1 1 80 HD 152 126 93 67 56 40 30 19 16 13 10 7 5 4 4 3 2 2 1 1 100 HD 155 112 93 66 51 32 27 21 17 12 9 8 6 5 4 3 2 2 150 HD 131 100 64 54 42 34 24 19 16 13 10 8 6 5 4
Notes: 1. For PVC flexible conduits, the recommendations are based on conduits used without fittings or with fittings only at the ends of the conduit run. Where intermediate fittings are used in a run of PVC flexible conduit, an appropriate reduction should be made in the number of cables drawn into the conduit. 2. One earth wire of appropriate size, as determined by the requirements of AS/NZS 3000, may be inserted in all conduits, provided that its insertion does not prevent easy drawing in of cables. 3. Table suitable for use with Olex manufactured product only.
99
GENERAL DATA
Cables in conduit and pipe space factors.
One cable in conduit or pipe Two cables in conduit or pipe Three or more in conduit or pipe Note: The above values should not be exceeded. 50% 33% 40%
100
ABBREVIATIONS
A.m Ampere metre ABC aerial bundled cable AC alternating current Al aluminium AS Australian Standard C core C degree Celsius CPE Chlorinated Polyethylene CSA cross-sectional area CSP Chlorosulphonated Polyethylene Cu copper dB decibel DC direct current E earth EA Ethylene Acrylic Eff efficiency ELV Extra Low Voltage EPR Ethylene Propylene Rubber HD hard drawn H.D. heavy duty HFS-90-TP halogen free sheath 90C thermoplastic HF-110-R halogen free 110C rubber (sheath) hp horsepower HR heat resistant HRC high rupture capacity ISDN Integrated Services Digital Network kg kilogram kN kilonewton kV kilovolt kVA kilovoltamp kW kilowatt LAN local area network L.D. light duty mm millimetre MM Multi Mode (Fibre) nF/km nanofarad/kilometre OD outside diameter O.D. ordinary duty PACW plain annealed copper wire PE Polyethylene pf power factor pF/m picofarad/metre PILC paper insulated lead covered PVC Polyvinyl Chloride R-CPE-90 rubber Chlorinated Polyethylene 90C R-EP-90 rubber Ethylene Propylene 90C R-HF-110 rubber halogen free 110C (insulation) SM Single Mode (Fibre) SWA steel wire armoured TACW tinned annealed copper wire TPE thermoplastic elastomer UTP unshielded twisted pairs V volt V-75 75C rated PVC V-90 90C rated PVC V-90HT 90C rated PVC 105Cfor restricted periods X-HF-90 XLPE halogen free 90C X-90 Cross-linked Polyethylene
101
OLEX LOCATIONS
Victoria
Head Office 207 Sunshine Road, Tottenham Vic 3012 Phone 03 9281 4444 Fax 03 9281 4476 Vic Sales 1300 CABLES (1300 222 537)
Queensland
State Office 541 Bilsen Road, Geebung Qld 4034 Phone 1300 CABLES (1300 222 537) Fax 07 3259 2606 Townsville Phone 1300 CABLES (1300 222 537) Fax 07 4779 7201
Western Australia
State Office 857 Abernethy Road, Forrestfield WA 6058 Phone 1300 CABLES (1300 222 537) Fax 08 9353 2688
Tasmania
State Office c/ Dynamite Distribution and Storage 241 Main Road, Moonah Tas 7009 Phone 1300 CABLES (1300 222 537) Fax 03 6273 6611
102
OLEX LOCATIONS
Manufacturing Locations
Tottenham 207 Sunshine Road, Tottenham Vic 3012 Lilydale 55 Main Street, Lilydale Vic 3140
103
NOTES
104
NOTES
105
NOTES
106
Subscription
Would you like the next edition of The Handbook delivered to your door?
If you would like to be kept up-to-date with the latest cabling information from Olex and receive the next edition of The Handbook please return this subscription page to Olex Australia, 207 Sunshine Road Tottenham Victoria 3012 Australia. Name* Company name* Postal address* Number of copies required* Contact phone number Email *mandatory information Optional Information: 1. How many people work in your company? 2. What kind of work are you involved in? 9 Residential 9 Commercial 9 Other 3. What electrical distributor do you generally purchase cable from?
Would you like to be kept up-to-date with industry news and information relating to the Olex range of products and services? 9 Yes, please post 9 Yes, please email 9 No thanks
Would you like to receive any further information on any Olex range of cables? (Data Comms / Industrial / Mining / High Voltage / Aerial) 9 No thanks 9 Yes, please specify
All information received on this form will be kept strictly confidential and will be used only for the purposes of sending you the next edition of The Handbook and for sending information of interest (only if you have requested above).
107
108
HV submarine cables
11kV to 33kV (EHV also) XLPE, EPR or PILC insulation Radial water barrier: Al/HDPE, LAS, stainless steel sheath Mechanical protection: Single, double wire armour, HDPE, hessianserved
HV transmission cables
Extra High Voltage U/G XLPE to 330kV (joints, terminations, engineering services, condition monitoring)
Olex has taken every precaution to ensure that the information contained in this booklet is in line with requirements of the appropriate Australian Standards and correct electrical practice. However, we accept no liability of any kind with respect to the information presented here. All information is subject to change without notice. Note: Current carrying capacity tables stated in this handbook are based on AS/NZS 3008.1, Electrical Instal lations Selection of Cables. Part 1: Cables for alternating voltages up to and including 0.6/1kV. The latest edition of this handbook and other Olex product catalogues is always available at www.olex.com.au
DISEGNO OLC11644
Head Office 207 Sunshine Road Tottenham Victoria 3012 Australia Phone 613 9281 4444 Fax 613 9281 4476
Cable Sales
Tel 1300 CABLES Fax 1300 556 For more information see www.olex.com.au
551
LOW VOLTAGE
INDUSTRIAL
HIGH VOLTAGE
FIRE RATED
DATA/COMMS
MINING