GST Headquarters

GST Production Base

Company Profile
GST , a high tech company, is specialising in R&D, manufacturing, marketing and technical service of Fire Alarm Systems. GST manufactures over 6 million detectors and modules, over 30,000 control panels per year, being one of the largest independent fire detection manufacturing companies in the world. All our main devices are manufactured using robotic controlled pick and place machines and surface mount technology, in strict conformity with ISO9001 and ISO10012.1. Over the years we have successfully gained international recognition and approval, such as LPCB, UL and CE. GST products have been sold in more than 50 countries and regions covering Europe, Asia, Africa and America.

Certification and Approval

Index

Digital Intelligent Devices Intelligent Fire Alarm System Innovative Conventional Devices Conventional Fire Alarm System Gas Extinguishing System Fire Telephone System System Schematics

1- 4 5-21 22-24 25-33 34-36 37-39 40-45

Digital Intelligent Devices

Digital Intelligent Optical Smoke Detector


Advanced digital communication Built in 8 bit microprocessor Algorithm maps for faster response and false alarm rejection Secure and speedy communication Intelligent drift compensation Self diagnosis and history log Electronic addressing Duplicated address report Sensing chamber for exceptional dust proof ability and LED for 360 vision Built in remote indicator output Unique low profile design EN54 compliance

DI-9102

Technical Specifications
Standard: EN54-part7 Operating Voltage: 24VDC Loop Operating Current: Standby Current 0.6mA Alarm Current 1.2mA Operating Environment: Temperature: -10 ~+50C Relative Humidity: 95% Field Programmable Sensitivity: 0.10dB/m ~ 0.25dB/m-3 levels Dimensions: Diameter 100mm, Height 44.5mm

Digital Intelligent Dual Heat Detector


Built in 8 bit microprocessor Advanced digital communication Secure and speedy communication Self diagnosis and history log Electronic addressing Duplicated address report LED for 360 vision Built in remote indicator output Unique low profile design Fixed temperature response is adjustable via hand held programming tool EN54 compliance

DI-9103

Technical Specifications
Standard: EN54-part5 Operating Voltage: 24VDC Loop Operating Current: Standby Current 0.6mA Alarm Current 1.2mA Operating Environment: Temperature: -10 ~+50C Relative Humidity: 95% Detector Class: A1S, A1R, A2S, A2R, BS, BR Dimensions: Diameter 100mm, Height 41mm

Digital Intelligent Multi Sensor


Combined all the features of DI-9102 Optical and the DI-9103 Heat detector Advanced digital communication Electronic addressing LED for 360 vision Sensing chamber for exceptional dust proof ability Ideal alternative to Ionization detector Low profile design

DI-9101

Technical Specifications
Standard: EN54-part 5, part 6 and Part 7 Operating Voltage: 24VDC Loop Operating Current: Standby Current 0.6mA Alarm Current 1.5mA Operating Environment: Temperature: -10 ~+50C Relative Humidity: 95% Field Programmable Sensitivity: 0.10dB/m~0.56dB/m-3 levels Dimensions: Diameter 100mm, Height 44.5mm

Base Mount Isolator


In the event of a short circuit isolates faulty parts of the loop Automatically resetting once the fault has cleared Compatible with digital range of detector Can be used standalone with cover or in stead of standard base LED status indicator

DC-9504

Technical Specifications
Operating Voltage: 24VDC Active Current: 1A Operating Environment: Temperature: -10 ~+50C Relative Humidity: 95% Application: Indoor use Visual Indicator: Yellow LED (lit steady when alarm, off normal state) Dimensions: Diameter 100mm, Height 37.5mm (with cover)

Standard Base
Standard base for digital DI/DC range of detectors No electronics, safe on the time of installation

DB-01

Digital Manual Call Point


Re-settable (non-breaking glass) via special key Advanced digital communication Electronically addressing Friendly installation and test Wiring before termination Semi-flush mount installation Optional back-box for surface mount Stylish pleasing design

DI-9204

Technical Specifications
Protection Rating: IP 30 Operating Voltage: 24VDC Loop Operating Current: Standby Current 0.6mA Alarm Current 1.2mA Operating Environment: Temperature: -10 ~+50C Relative Humidity: 95% Application: Indoor use Dimensions: 87 x 87.5 x 58 mm, Surface Mount 87 x 87 x 23.5 mm, Flush Mount

Digital Sounder Base


Loop powered sounder Low power consumption Compatible with digital range of detectors Wall mounted (stand alone with cover) or ceiling mounting Electronically addressing Multi mode can be configured as single address for evacuation, dual address for alert/evacuation of virtual address to operate with one detector plus programable evacuation Cable-free application

DI-9405

Technical Specifications
Operating Voltage: 24VDC Loop Operating Current: Standby Current 1mA Action Current 4mA Loop capacity: 50 pieces per loop Sound Output: 85dB @ 1metre Dimension: Diameter 148mm, Height 34.4mm(without cover), 49mm(with cover)

Intelligent Fire Alarm System

Intelligent Optical Smoke Detector


Aesthetically pleasing low profile design 8 Bit intelligent processor with A/D converter Built in algorithm maps for false alarm rejection Electronically addressed Twin LEDs for 360 degree vision With Remote Indicator output Sensitivity adjustable via hand held programming tool Removable optical chamber for easy cleaning and maintenance

I-9102

Technical Specifications
Operating voltage: 24VDC Loop Operating current: Standby current: 0.8mA Alarm current 2mA (5mA for RI) Operating Environment: Temperature: -10 ~+50C Relative Humidity: 95% Dimensions: Diameter 100mm, Height 50mm

Intelligent Dual Heat Detector


Fixed Temperature and Rate of Rise Heat Detection Aesthetically pleasing low profile design 8 Bit intelligent processor with A/D converter Electronically addressed With Remote Indicator output Dotector class: A1R Twin LEDs for 360 degree vision

I-9103

Technical Specifications
Operating voltage: 24VDC Loop Operating current: Standby current 0.8mA Alarm current 2mA (5mA for RI) Operating Environment: Temperature: -10 ~+50C Relative Humidity: 95% Dotector class: A1R Dimensions: Diameter 100mm, Height 50mm

Intelligent Multi Sensor


Combining all the features of the I-9102 Optical and the I-9103 Dual Heat Detector to provide the ultimate cover for life safety systems Ideal alternative to Ionisation detectors Adjustable smoke detection sensitivity by handhold programmer

I-9101

Technical Specifications
Operating voltage: 24VDC Loop Operating current: Standby current 0.8mA Alarm current 2mA Operating Environment: Temperature: -10 ~+50C Relative Humidity: 95% Field Programmable Sensitivity: 0.1dB/m~0.56dB/m-3 levels Dimensions: Diameter 100mm, Height 50mm

Intelligent Ultraviolet Flame Detector


Sensitive Ultraviolet sensor that detects the UV rays produced by a flame Not effected by sunlight. Aesthetically pleasing Low profile design Dust / corrosion / humidity resistant Electronically addressed Standard calibration set to detect a 3cm flame at 6 metres Effective range 12 metres

I-9104

Technical Specifications
Operating voltage: 24VDC Loop Operating current: Standby current: 1.5mA Alarm current 10mA Operating Environment: Temperature: -10 ~+50C Relative Humidity: 95% Detection Angle: 80 Degree Dimensions: Diameter: 100mm Height: 50mm

Standard Detector Base


Base for termination and fixing of detectors Non-electronic component Common base for GST I-9101 / 2 / 3 / 4

DZ-03

Intelligent Reflective Beam Detector


Range 8 -100 Metres 2 selectable levels of sensitivity adjustment Ideal for Atriums, Warehouses, Shopping Centres, Airport Terminals, etc. Simple and cost effective to install of transmitter and reflective honey comb mirror Quick and easy to set up and align with visual Green LED indication that flashes faster or slower subject to signal strength. Replace the cover and the detector will self calibrate to the required level.

I-9105R

Technical Specifications
Operating voltage: 24VDC Loop, 24VDC Power Supply Operating current (power supply): Power curaent: Commission current 20mA Standby current 8mA Alarm current 12mA Loop current 20mA Detection Range: Length from 8 to 100 metres, width 7 metres in both sides Wiring: Non-polarized two-core 24VDC Non-polarized two-core detection loop Operating Environment: Temperature: -10 ~+50C Relative Humidity: 95% Dimensions: 206mm x 95mm x 95mm

Addressable Combustible Gas Detector


Available for LPG, Natural Gas and Coal Gas (please specify at time of order) Built-in relay contacts for control of Gas Valves / Extract etc Built-in sounder with 2 stage alarm Manual reset and control (on/off) of relay contacts Electronically addressed Wall-mount (LPG) or ceiling mount (Natural Gas and Coal Gas)

I-9602LW

Technical Specifications
Operating voltage: 24V Loop, 24VDC Power Supply Operating Consumption (power supply): 1.5Watt Alarm Level: Pre-alarm 12%LEL Urgent Alarm: 23%LEL Output: K1/K2, N/O contact, 3A/220VAC, active when pre-alarm V1/V2, active output 3A/5VDC, start when urgent alarm Operating Environment: Temperature: -10 ~+50C Relative Humidity: 95% Wiring: Non-polarized 2-core for loop Non-polarized 2-core for 24VDC power supply Dimensions: 121mm x 87mm x 57mm

Addressable Manual Call Point


Addressable Manual Call Point (MCP) with re-settable (non breaking) glass Additional volt free contacts for local interfacing (i.e. PTZ camera preset) Two parts plug-in construction with base mounted termination allows for easy installation and connection MCP can be addressed and plugged in to base at time of commissioning Electronically addressed Suitable for semi-flush and surface mount installation

I-9201

Technical Specifications
Operating Voltage: 24VDC Loop Operating Current: Standby Current 0.8mA Alarm Current 2mA N/O Output Contact: Rating 60VDC, 0.1A Contact Resistance 100m Electronically addressed Operating Environment: Temperature: -10~+ 50C Relative Humidity: 95% Dimensions: 90mm x 122mm x 48.5mm

Addressable Manual Call Point


Compatible with latest EN standards Non-breaking re-settable glass (via special key) Two part plug-in construction with base mounted termination allows easy installation and connection

I-9202

Technical Specifications
Operating Voltage: 24VDC Loop Operating Current: Standby Current 0.8mA Alarm Current 2mA N/O output contact: Rating 60VDC, 0.1A Contact Resistance Operating environment: Temperature: -10~+ 50C Relative Humidity: 95% Dimensions: 95mm x 98mm x 40mm

Intelligent Remote Indicator


Can be program linked to any single or group of devices High intensity flashing LED in alarm condition Electronically addressed

I-9314

Technical Specifications
Operating Voltage: 24VDC Loop Operating Current: Monitoring Current 0.8mA Action Current 16mA Operating Environment: Temperature: -10~+ 50C Relative Humidity: 95% Dimensions: 120mm x 80mm x 49mm

Remote indicator
Remote indicator for direct connection to detector remote indicator terminals Compatible with Digital, Intelligent, Innovation and Conventional series Optical Smoke detectors and Dual Heat Detectors.

C-9314P

Technical Specifications
Operating Voltage: 2.5 - 3VDC Operating Current: <5mA Operating environment: Temperature: -10 ~+50C Relative Humidity: 95%

10

Addressable Sounder Beacon


Addressable combined flashing high intensity LED beacon and sounder Two part plug-in construction with base mounted termination allowing easy installation and connection Electronically addressed

I-9401

Technical Specifications
Operating Voltage: 24VDC Loop, 24VDC Power Supply Operating Current: Loop: Standby Current 0.8mA; Alarm Current 6.0mA Power Supply: Standby Current 10mA, Alarm Current 160mA Alarm volume (SPL): 95dB @1 Metre Wiring: Non-polarized 2-core for loop Non-polarized 2-core for power supply Operating Environment: Temperature: -10~+ 50C Relative Humidity: 95% Dimension: 144mm x 90mm x 57mm

Addressable Base Mount Sounder


Loop powered sounder Low power consumption Compatible with intelligent range of detectors Wall mount (stand alone with cover) or ceiling mounting Electronically addressing Multi mode can be configured as single address for evacuation, dual address for alert/evacuation or virtual address to operate with one detector plus programmable evacuation Cable-free application

I-9405

Technical Specifications
Operating Voltage: 24VDC Loop Operating Current: Standby Current 1mA Action Current 7mA Loop capacity: 30 pieces per loop Sound Output (SPL): 86dB @1 Metre Operating Environment: Temperature -10 ~ +50C Relative Humidity 95% Dimension: Diameter 148mm, Height 34.4mm (without cover), 49mm (with cover)

11

Addressable Sounder and Strobe


Two parts construction with base mounted termination allows easy installation Evacuate only or Alert/Evacuate mode can be set through handheld programmer Remote start input can be used to co-operation with other systems Strobe provided by high intensity LED cluster Electronically addressed

I-9403

Technical Specifications
Operation Voltage: 24VDC Loop, 24VDC Power Supply Operating Current: Loop: Standby Current 1mA; Alarm Current 5mA Power Supply: Standby Current 3mA, Alarm Current 65mA Sounder Output: 94dB @ 1 Metre Wiring: Non-polarized 2-core for loop Non-polarized 2-core for power supply Operating Environment: Temperature: -10~+ 50C Relative Humidity: 95% Dimension: Diameter 110mm, Height 97.5mm

Addressable Sounder
Identical in appearance and features to the I-9403 but without the strobe element

I-9404

Technical Specifications
Operation Voltage: 24VDC Loop, 24VDC Power Supply Operating Current: Loop: Standby Current 1mA; Alarm Current 5mA Power Supply: Standby Current 3mA, Alarm Current 35mA Sounder Output: 94dB @ 1 Metre Wiring: Non-polarized 2-core for loop Non-polarized 2-core for power supply Operating Environment: Temperature: -10~+ 50C Relative Humidity: 95% Dimension: Diameter 110mm, Height 97.5mm

Deep Base
Optional deep base for Sounder and Strobe (I-9403 / I-9404)

C-94DB

12

Addressable Sounder Circuit Module


Cost effective (cable saving) distributed addressable control of conventional sounder circuits Connects to conventional polarised 24VDC sounders/strobes Utilizes two addresses (one for Alert and one for Evacuate Control) Two part plug-in construction with base mounted termination allows easy installation and connection Electronically Addressed Cable monitoring for fault of short circuit and open circuit

I-9308

Technical Specifications
Operating Voltage: 24VDC Loop, 24VDC Power Supply Operating Current (loop): Standby Current 1mA Output: Maximum 0.5A, polarized End of line: 10k Operating Environment: Temperature: -10~+ 50C Relative Humidity: 95% Dimensions: 120mm x 80mm x 40mm

Addressable VA Zone Control Module


Voice Alarm system switch module Switch between normal broadcast and emergency voice amplifier line Dual-relay switch to avoid cross-link Two part plug-in construction with base mounted termination allows easy installation and connection Intelligent interface can be addressed and plugged in to base at time of commissioning Electronically addressed

I-9305

Technical Specifications
Operating Voltage: 24VDC Loop, 24VDC Power Supply Operating Current (loop): Standby Current 1mA Action Current 5mA Operating Current (power): Standby Current 0.3mA Action Current 5mA Operating Environment: Temperature -10 ~ +50C Relative Humidity 95% Dimension: 120mm x 80mm x 40mm

13

Addressable Input Module


Monitors switch contacts of remote equipment Loop powered Inputs programmable for NO or NC contacts (Programmable via P9910B hand held programmer) Two part plug-in construction with base mounted termination allows easy installation and connection Intelligent interface can be addressed and plugged in to base at time of commissioning Electronically addressed

I-9300

Technical Specifications
Operating Voltage: 24VDC Loop Operating Current: Standby Current 1mA Action Current 5mA Operating Environment: Temperature: -10~+ 50C Relative Humidity: 95% Dimension: 120mm x 80mm x 40mm

Intelligent Single Input /Output Module


Addressable I/O with 24V / 3Amp relay output contacts Input can be configured as NO / NC or self confirmation of output (programmable via handheld programmer (P9910B)) Two part plug-in construction with base mounted termination allows easy installation and connection Intelligent interface can be addressed and plugged in to base at time of commissioning Electronically addressed

I-9301

Technical Specifications
Operating Voltage: 24VDC Loop, 24VDC Power Supply Operating Current (loop): Standby Current 1mA Action Current 5mA Wiring: Non-polarized two-core for loop Non-polarized two-core for 24VDC power supply Operating Environment: Temperature: -10~+ 50C Relative Humidity: 95% Dimension: 120 x mm 80mm x 40mm

14

Intelligent Single Input /Output Module Loop Powered


Addressable I/O with 24V /3Amp relay output contacts Input can be configured as NO / NC or self confirmation of output (programmable via handheld programmer (P9910B) Two part plug-in construction with base mounted termination allows easy installation and connection Intelligent interface can be addressed and plugged in to base at time of commissioning Electronically addressed

DI-9301

Technical Specification
Operating Voltage: 24V Loop Operating Current: Standby Current 1mA Action Current 5mA Wiring: Non-polarized 2-core for loop Operating Environment: Temperature: -10~+ 50C Relative Humidity: 95% Dimension: 120 x mm 80mm x 40mm

Addressable Double I/O Module


Addressable I/O with 24V / 3Amp relay output contacts with 2 independent circuits Input can be configured as NO / NC or self confirmation of output (programmable via handheld programmer (P9910B)) Two part plug-in construction with base mounted termination allows easy installation and connection Intelligent interface can be addressed and plugged in to base at time of commissioning Electronically addressed

I-9303

Technical Specifications
Operating Voltage: 24VDC Loop, 24VDC Power Supply Operating Current (loop): Standby Current 1mA Action Current 8mA Wiring: Non-polarized two-core for loop Non-polarized two-core for 24VDC power supply Operating Environment: Temperature: -10~+ 50C Relative Humidity: 95% Dimension: 120 x mm 80mm x 40mm

15

Addressable Multi-channel Interface


Interface board for plant monitor and control Multi channel integrated for saving installation cost Input cable fault monitored for short circuit and open circuit Ideal for plant room Electronically addressed

DI-9309

Technical Specifications
Operating Voltage: 24VDC Loop, 24VDC Power Supply Operating Current (loop): Monitoring Current 1.5mA Action Current 50mA Operating Current (power): Monitoring Current 3mA Action Current 100mA Capability: 1 C 16 input channels 2 dry contact output channels Rate of relay: 2A/220VAC End of line: 4.7k? resistor Action Resistance: 470~680? Operating Environment: Temperature -10 ~ +50C Relative Humidity 95% Dimension: 200mm x 100mm x 20mm (without case)

Addressable Zone Monitor Unit


Interfaces with conventional fire detection equipment/panels etc Can connect up to 15 detectors with Active EOL or up to 25 detectors with Resistor EOL Ideal for integrating Sprinkler Zone Valve and Flow Switches Electronically addressed

I-9319

Technical Specifications
Operating Voltage: 24VDC Loop, 24VDC Power Supply Operating Current (loop): Monitoring Current 1.5mA Action Current 5mA Capability: 15 conventional detectors End of line: 4.7k resistor or AEOL Action Resistance: 470~680 Operating Environment: Temperature: -10~+ 50C Relative Humidity: 95% Dimension: 120mm x 80mm x 40mm

16

Short Circuit Isolator


Isolates faulty part of the loop in the event of a short circuit Automatically resetting once the fault has cleared LED status indicator

C-9503

Technical Specifications
Operating Voltage: 24VDC Action Current: 2A Operating Environment: Temperature: -10~+ 50C Relative Humidity: 95% Dimensions: 120mm x 80mm x 40mm

Base Mount Short Circuit Isolator


Replaces standard detector base (DZ-03) Cost effective installation without the need for additional cabling Features as per C-9503 Base Type: Diameter 105mm, Height 20mm

C-9504

Handheld Programmer
Portable programming tool for addressing and testing of intelligent devices Programs all loop devices (1-242) 2 Program I C protocol devices like Reflective Beam Detector and GST8903 Mimic Panel Interrogates device for Condition - Manufacturing Batch Number - Date of manufacture - alarm sensitivity Reprogram facility enables adjustment to alarm threshold of detectors Able to switch on or off the rate of rise function of dual heat detector. (I-9103) Adjusts input modules to accept N/C or N/O contacts.

P-9910B

17

Addressable Mini Fire Panel


Single loop addressable panel Can connect up to 128 addressable devises 8 zone fire and fault indication with costumer definable label Self configurable via panel keyboard Easy commissioning making the GST100 an ideal product for electrical installers.

GST100

Technical Specifications
Power supply: 230VAC 50/60Hz Operating Environment: Temperature:0~+ 40C Relative Humidity: 95% Dimension: 210mm x 297mm x 90mm

Intelligent Single Loop Fire Alarm Panel


Single loop addressable fire detection panel packed with features not usually associated with smaller systems, providing a high quality solution at exceptionally good value. Loop capacity 235 intelligent devices 30 logical configurable zones Graphical LCD Display Zone indication and manual intervention panel Net-workable with all GST intelligent fire panels Programmable from PC Built-in RS485 repeater output (Maximum 10 repeaters) Optional GMC system Optional Fireman's Control Panel Optional Panel Printer Advanced user friendly programming software including 'Fuzzy Logic'

GST200

Technical Specifications
Power supply: 230VAC 50/60Hz Operating Environment: Temperature:0~+ 40C Relative Humidity: 95% Dimension: 400mm x 560mm x 178mm

18

Intelligent Two / Four Loop Fire Alarm Control Panel


Addressable fire detection with integrated controls providing the perfect solution for all medium sized projects Loop capacity 242 intelligent devices 40 X 12 characters Large Graphical LCD Display 60 zone indication and manual intervention panel Zone indication and manual intervention panel Net-workable with all GST fire panels Programmable from PC Built-in RS485 repeater output (Maximum 64 repeaters) Built-in Gas Extinguishing Control Integrated Security Alarm Facilities Optional Firemans Control Panel Panel Printer included Optional GMC system Advanced user friendly programming software including Fuzzy Logic GST5000/2 Two loop panel can connect up to 480 devices GST5000/4 Four loop panel can connect up to 750 devices

GST5000W

Technical Specifications
Power supply: 230VAC 50/60Hz Operating Environment: Temperature: 0~+ 40C Relative Humidity: 95% Dimension: 500mm x 700mm x 170mm

Intelligent Modular 5-8 Loop Fire Alarm Control Panel


Intelligent panel with modular loop cards expandable to 8 loops, perfect solution for all medium to large sized projects 8 Loops capacity 1920 addressable devices Flush mount 40 X 12 characters Large Graphical LCD Display 60 logical configurable zones Zone indication and manual intervention panel Net-workable with all GST fire panels Programmable from PC Built-in RS485 repeater output (Maximum 64 repeaters) Built-in Gas Extinguishing Control Integrated Security Alarm Facilities Panel Printer included Optional GMC system Advanced user friendly programming software including Fuzzy Logic Separate wall mounted monitored PSU with built-in battery charger Expand loop capacity by additional loop cards LC5000

GST5000F

Technical Specifications
Power supply: 230VAC 50/60Hz Operating Environment: Temperature: -0~+ 40C Relative Humidity: 95% Dimension: 500mm x 706mm x 170mm (front panel) 500mm x 500mm x 189mm (PSU)

19

Intelligent Modular 1-20 Loop Fire Alarm Control Panel


Fully modular and expandable fire command system, with multi loop and full integration with GST Voice Alarm System and Fire Telephone System, housed in either rack or console type housing provides the perfect solution for all medium to large systems. Loop capacity 240 intelligent devices (up to 4800 addressable points) 40 X 12 characters Large Graphical LCD Display 64 zone indication and manual intervention control expandable to 254 zones and plant overrides Net-workable with all GST fire panels Programmable from PC Built-in Gas Extinguishing Control Integrated Security Alarm Facilities Optional Firemans Control Panel Panel Printer included Optional Colour Graphics Advanced user friendly programming software including Fuzzy Logic Total integration with GST addressable Voice Alarm systems Order additional loop cards separately GST5000LC

GST5000/20/C GST5000/20/R

Technical Specifications
Power supply: 230VAC 50/60Hz Operating Environment: Temperature: -0~+ 40C Relative Humidity: 95% Dimension: 580mm x 520mm x 1873mm (Rack type enclocure) 1080mm x 1113mm x 1350mm (2 bay console)

Firemans Control Panel


CPU controlled switches with addressable and direct outputs Ideal for controls of smoke vents, AHUs, exhaust fans, smoke curtains, etc.

GST-FCP14

Components for FCP-014


to build fireman's switch on wall mount panels

FCP-M01& FCP-Z02

20

LCD Passive Repeater Panel


Aesthetically pleasing design with large LCD display Compatible with all GST intelligent fire alarm panels Back Lit LCD displays all fire information Local sounder mute and scroll alarms buttons Two part plug-in construction with base mounted termination allows easy installation and connection Repeater can be plugged in to base at time of commissioning

GST852RP

Technical Specifications
Operation Voltage: 24VDC Standby Power: 2W Maximum Power: 5W Operation Environment: Temperature: -0~+ 40C Relative Humidity: 95% Dimension: 234mm x 104mm x 35mm

Network Repeater Panel


Display network message by LCD screen Achieve remote control of system Password protect access levels Flush-mount or Surface-mount structure

GST-NRP01

Technical Specifications
Operation Voltage: 24VDC Standby Power: 2W Maximum Power: 5W Operation Environment: Temperature 0 ~ +40C Relative Humidity 95% Dimension: 390mm x 270mm x 100mm

Graphical Monitor Centre


Colour graphic control and display system, providing a complete window onto the fire detection systems and ancillary equipment Compatible with all GST intelligent fire panels Multi-level password control for convenient system management PC not included

GSTGMC

21

CONVENTIONAL
DEVICES
The Innovation range of detectors are setting a new standard in conventional detection by utilizing our expertise in intelligent fire detection. We now offer unrivaled features such as: Adjustable Sensitivity Linear Drift Compensation Algorithm maps for faster response and false alarm rejection Blinking LED Magnetic Test Facility

INNOVATIVE

Innovative Multi Sensor


Combined all the features of DC-9102 Optical and the DC-9103 Heat detector LED for 360 vision Sensing chamber for exceptional dust proof ability Ideal alternative to Ionization detector Low profile design

DC-9101

Technical Specifications
Standard: EN54-part 5, part 6 and Part 7 Operating Voltage: 24VDC Operating Current: Standby Current 0.06mA Alarm Current 30mA Operating Environment: Temperature: -10~+ 50C Relative Humidity: 95% Field Programmable Sensitivity: 0.10dB/m ~ 0.56dB/m-3 levels Dimensions: Diameter 100mm, Height 44.5mm

Innovative Optical Smoke Detector


Algorithm maps for faster response and false alarm rejection Intelligent drift compensation Sensing chamber for exceptional dust proof ability and LED for 360 vision Built in remote indicator output Unique Low profile design EN54 compliance

DC-9102

Technical Specifications
Standard: EN54-part7 Operating voltage: 24VDC Operating Current: Standby current 0.06mA Alarm Current 30mA Operating Environment: Temperature: -10~+ 50C Relative Humidity: 95% Field Programmable Sensitivity: 0.10dB/m ~ 0.25dB/m-3 levels Dimensions: diameter 100mm; height 44.5mm

Innovative Conventional Dual Heat Detector


Combined fixed temperature and rate of rise heat detection LED for 360 vision Built in remote indicator output Unique low profile design EN54 compliance

DC-9103

Technical Specifications
Standard: EN54-part5 Operating Voltage: 24VDC Operating Current: Standby Current 0.06mA Alarm Current 30mA Operating Environment: Temperature: -10~+ 50C Relative Humidity: 95% Dimensions: Diameter 100mm, Height 41mm Detector Class: A1S, A1R, A2S, A2R, BS, BR

23

Diode Base
Diode base for DC range of conventional detectors For use with DP-9907 Active End of Line

DB-01D

Active End of Line


Active End of Line for conventional fire detection zones It can be used as conventional detector base or work independent with a cover Provides detector removal indication while still enabling alarms down stream of the missing device to be detected Compatible with all GST conventional panels Compatible with addressable zone interface I-9319

DP-9907

Innovative Manual Call Point


Re-settable (non-breaking glass) via special key Friendly installation and test Wiring before termination Semi-flush or surface mount installation Optional back-box for surface mount Stylish pleasing design

DC-9204

Technical Specifications
Protection Rating: IP 30 Operating Voltage: 24VDC Operating current: Standby Current 0 Alarm Current 30mA Operating Environment: Temperature: -10~+ 50C Relative Humidity: 95% Contact Resistance: 100m Application: Indoor use Dimensions: 87 x 87 x 58 mm, Surface Mount 87 x 87 x 23.5 mm, Recess Mount

24

Conventional Fire Alarm System

Conventional Optical Smoke Detector


Aesthetically pleasing low profile design Twin LED for 360o vision Removable optical chamber foe easy cleaning and maintenance With remote indicator output EN54 compliance

C-9102

Technical Specifications
Standard: EN54-part7 Operating Voltage: 24VDC Operating Current: Standby Current 0.06mA Alarm Current 30mA Operating environment: Temperature: -10~+50 Relative Humidity: 95% Dimensions: Diameter 100mm, Height: 50mm

Conventional Dual Heat Detector


Fixed Temperature and Rate of Rise Heat Detection Aesthetically pleasing low profile design 8 bit intelligent processor Twin LED for 360o vision With remote indicator output

C-9103

Technical Specifications
Standard: EN54-part5 Operating Voltage: 24VDC Operating Current: Standby Current 0.06mA Alarm Current 30mA Operating environment: Temperature: -10~+50 Relative Humidity: 95% Dimensions: Diameter 100mm, Height: 50mm

26

Conventional Multi Sensor


Combined all the features of C-9102 Optical and the C-9103 Heat detector to provide the ultimate cover for life safety systems Twin LED for 360o vision Ideal alternative to Ionization detector

C-9101

Technical Specifications
Standard: EN54-part 5, part 6 and Part 7 Operating Voltage: 24VDC Operating Current: Standby Current 0.06mA Alarm Current 30mA Operating Environment: Temperature: -1 Relative Humidity: 95% Dimensions: Diameter 100mm, Height: 50mm

Conventional Ultraviolet Flame Detector


Sensitive Ultraviolet sensor that detects the UV rays produced by a flame Aesthetically pleasing low profile design Dust / corrosion / humidity resistant Standard calibration set to detect a 3cm flame at 6 metres Effective range 12 metres

C-9104

Technical Specifications

Standard Detector Base


Fixing and terminating of conventional detectors with directional gaps Compatible with GST conventional detectors using 4k7 , resistor end of line (EOLR) Common base for C-9101 / 2/ 3/ 4

DZ-03

Diode Base
Diode base version for conventional detectors utilising P-9907 active end of line (AEOL) Common base for C-9101 / 2/ 3/ 4

DZ-03D

27

Conventional Reflective Beam Detector


Range 8-100 Metres 2 selectable levels of sensitivity adjustment Ideal for Atriums, Warehouses, Shopping Centres, Airport Terminals etc. Simple and cost effective to install of transmitter and reflective honey comb mirror Quick and easy to set up and align with visual Green LED indication that flashes faster or slower subject to signal strength. Replace the cover and the detector will self calibrate to the required level

C-9105R

Technical Specifications
Operating voltage: 24VDC Operating current: Commission Current 20mA Standby current 12mA Alarm current 22mA Detection Range: Length from 10 to 100 meters, width 7 metres on both sides Wiring: Non-polarized 2-core 24VDC Operating environment: Temperature: -10~+50 Relative Humidity: 95%

Conventional Combustible Gas Detector


Available for LPG, Natural Gas and Coal Gas (please specify at time of order) Built-in relay contacts for control of Gas Valves / Extract etc Built-in sounder with 2 stage alarm Manual reset and control (on/off) of relay contacts

C-9602LW

Technical Specifications
Operating voltage: 220VDC Operating Consumption: 5Watt Alarm Level: Pre-alarm 12%LEL Urgent Alarm: 23%LEL Output: K1/K2, N/O contact, 3A/220VAC, active when pre-alarm V1/V2, active output 3A/5VDC, start when urgent alarm Operating Environment: Temperature: -10~+50 Relative Humidity: 95% Wiring: 2-core AC power supply

28

Conventional Manual Call Point


Manual Call Point (MCP) with re-settable (non breaking) glass Additional volt free contacts for local interfacing (i.e. PTZ camera preset) Two parts plug-in construction with base mounted termination allows for easy installation and connection Suitable for semi-flush and surface mount installation

C-9201

Technical Specifications
Operating Voltage: 24VDC Operating Current: Standby Current 0 Alarm Current 30mA N/O Output Contact: Rating Value 60VDC, 0.1A Contact Resistance 100m , Operating Environment: Temperature: -10~+50 Relative Humidity: 95% Dimensions: 90mm x 122mm x 48.5mm

Conventional Manual Call Point


Compatible with latest EN standards Non-breaking re-settable glass (via special key) Two part plug-in construction with base mounted termination allows easy installation and connection

C-9202

Technical Specifications
Operating Voltage: 24VDC Operating Current: Standby Current 0 Alarm Current 30mA N/O output contact: Rating 60VDC, 0.1A Contact Resistance 100m , Operating environment: Temperature: -10~+50 Relative Humidity: 95% Dimensions: 95mm x 98mm x 40mm

29

Conventional Sounder Beacon


Conventional combined flashing high intensity LED beacon and sounder Two part plug-in construction with base mounted termination allowing easy installation and connection

C-9401

Technical Specifications
Operating Voltage: 24VDC Operating Current: Standby Current 0 Alarm Current 160mA Alarm volume (SPL): 95dB @1 Metre Wiring: 2-core polarized Operating Environment: Temperature: -10~+ 50 Relative Humidity: 95% Dimension: 144mm x 90mm x 57mm

Conventional Sounder Base


Conventional Base Mounted Sounder Can be used as a common base of detector or stand alone with a cover Compatible sound with I-9403 / C-9403 Sounder Flasher

C-9402

Technical Specifications
Operating Voltage: 24VDC Operating Current: Standby Current 0 Action Current 15mA Loop capacity: 30 pieces per loop Sound Output (SPL): 89dB @1 Metre Wiring: 2-core polarized Operating Environment: Temperature: -10~+ 50 Relative Humidity: 95% Dimension: Diameter 120mm, Height 38.8mm (without cover) 48.8mm (with cover)

30

Conventional Sounder and Strobe


Two parts construction with base mounted termination allows easy installation Strobe provided by high intensity LED cluster

C-9403

Technical Specifications
Operation Voltage: 24VDC Operating Current: Standby Current 0 Alarm Current 65mA Sounder Output: 94dB @ 1 Metre Wiring: 2-core polarized Operating Environment: Temperature: -10~+50 Relative Humidity: 95% Dimension: Diameter 110mm, Height 97.5mm

Conventional Sounder
Identical in appearance and features to the C-9403 but without the strobe element

C-9404

Technical Specifications
Operation Voltage: 24VDC Operating Current: Standby Current 0 Alarm Current 35mA Sounder Output: 94dB @ 1 Metre Wiring: 2-core polarized Operating Environment: Temperature: -10~+50 Relative Humidity: 95% Dimension: Diameter 110mm, Height 97.5mm

Deep Base
Optional deep base for Sounder and Strobe (C-9403 / C-9404)

C-94DB

31

GST101

Conventional Fire Alarm Panels


1/2/4/8/16 zone conventional fire alarm panels Both End of Line Resister and Active End of Line can be used Day/night mode selected (not valid for GST101&GST102) Zone isolate control One man test Key-control evacuate over-ride Repeater output available Fire alarm output for remote alarm Class change terminal for remote control Active EOL enables multiple alarm reporting from same zone Active EOL max 15 fire detectors and infinite manual buttons each zone Resistor EOL up to 25 detectors and infinite manual buttons each zone Optional relay output board

GST102

Technical Specifications
Power supply: 230VAC 50/60Hz Operating Environment: Temperature: 0~+40 Relative Humidity: 95% Dimension 380mm x 320mm x 95mm

GST104

GST108

GST116

32

16 Zone Conventional Repeater Panel


Compatible with GST102/4/8/16 Powered from FACP directly Zonal Fire and general Fault indication Dimension: 280mm X 110mm X 46mm

GST-RP16

Active End of Line


Active End of Line for conventional fire detection zones It can be used as conventional detector base or work independent with a cover Provides detector removal indication while still enabling alarms 360odown stream of the missing device to be detected Compatible with all GST conventional panels Compatible with addressable zone interface I-9319 Compatible with C-9101/2/3/4

P-9907

33

Gas Extinguishing System

Conventional Gas Extinguishing Control Panel


Two plus one control panel Standalone gas extinguishing control panel 2 conventional detection zones achieve double knock control Additional standard fire detection zone for other areas (no effect on gas release) Automatic and Manual extinguishing control Numerical onboard timer control Adjustable gas release delay timer Duty and Standby Cylinder control Two phase evacuation sounders Adjustable Solenoid Pulsed output Compatible with all GST conventional detectors Fully compliant to BS/EN/CE standards Built-in PSU and Charger

GST-301

Addressable Gas Extinguishing Control Panel


Compatible with all GST Intelligent Fire Alarm Control Panels Sits directly on addressable loop Direct intelligent control via addressable Loop Capable of controlling up to 6 zones of extinguishing Auto and manual control facilities Utilises GST intelligent detectors and programming (inc Fuzzy Logic) for control Fully monitored status control Duty and Standby Cylinder control Requires 24VDC Power supply

GST-303/306

35

Emergency Start/Abort Switch


Emergency Start/Abort switch for gas extinguishing control Compatible with GST301/303/306 gas extinguishing control panels

C-9317

Gas Extinguishing Warning Indicator


Normally installed above the entrance to a gas extinguishing control area Will eliminate and activate sounder prior to gas release

C-9318

Interposing Relay Module


Compatible with GST303/306 Monitoring cable from gas panel to module Apply power to solenoid valve for gas release initiation Confirmation signal of pressure switch when activated

C-9329

36

Fire Telephone System

Conventional Fire Telephone Panel


8 zone Conventional Fire Telephone Centre, a dedicated audio communication system, providing 2-way speech between the Fire Team and the Central Command Controller Normally installed in high-risk buildings where radio communication would be limited due to the extensive concrete structure 240VDC operated Wall mount type Operator can select single or multi zones for simultaneous communication Operator can ring outstations and fixed handsets

GST-FT8W

Conventional Fire Telephone Panel


24 zone Conventional Fire Telephone Centre, a dedicated audio communication system, providing 2-way speech between the Fire Team and the Central Command Controller Normally installed in high-risk buildings where radio communication would be limited due to the extensive concrete structure Auto-record conversation 24VDC operated 19/3U standard rack mount Operator can select single or multi zones for simultaneous communication Operator can ring outstations and fixed handsets

GST-FT24

38

Speaker Fire Telephone outstation


Hand-free extension of Fire Telephone System Compatible with all GST conventional fire telephone handsets in same zone

P-9911(S)

Fixed Fire Telephone Handset


Fixed extension of Fire Telephone System Open box and lift receiver to communicate with central control Compatible with all GST conventional fire telephone handsets in same zone

P-9911(F)

Fire Telephone Jack Socket


Simply insert mobile handset into jack to establish communications with the control centre Compatible with all GST conventional fire telephone handsets in same zone

P-9911(J)

Fire Telephone Mobile Handset


Mobile handset compatible with GST fire telephone jacks

P-9911(M)

39

Intelligent Fire Alarm System

I-9101 Intelligent Combined Optical/Heat Detector

I-9102 Intelligent Optical Detector

I-9103 Intelligent Dual Heat Detector

C-9503 Short Circuit Isolator

I-9202 Addressable Manual Call Point

I-9300 Addressable Input Module

I-9401 Addressable Sounder Beacon

I-9301 Addressable Single lnput/output Module

GST5000W Two Loops Intelligent Fire Alarm Control Panel

PSU24-6 Power Supply

40

Intelligent Fire Alarm System Connection

41

Conventional Fire Alarm System

C-9403 Conventional Sounder & Strobe

C-9403 Conventional Sounder & Strobe

C-9101 Conventional Optical/Heat Detector

C-9102 Conventional Optical Detector

C-9202 Conventional Manual Call Point

Active End of Line

C-9101 Conventional Optical/Heat Detector

C-9103 Conventional Heat Detector

C-9202 Conventional Manual Call Point

Active End of Line

GST108 8 Zone Conventional Fire Panel

42

Conventional Fire Alarm System Connection

1. Using End of Line Resister NOTE: In compliance with EN/BS standard, when using EOL Resister, call points should be wired before detectors, so that the removal of any detector will not inhibit call points from operating.

Resistor 4.7K

Control Panel

2. Using Active End of Line AEOL enables call points to be installed in any location on zone (circuit), as will not be affected by removal of detector (Diode base DZ-03D is required for detectors) Please pay attention to the polarisation.

Control Panel

With Detector

Control Panel

Without Detector

43

Standalone Gas Extinguishing Control System

C-9102 Conventional Photoelectric Smoke Detector

C-9102 Conventional Photoelectric Smoke Detector

C-9103 Conventional Rate of Rise and Fixed Temperature Heat Detector

C-9103 Conventional Rate of Rise and Fixed Temperature Heat Detector

Alarm Bell

C-9403 Conventional Sounder Strobe

C-9317 Emergency Gas Override Control

GST301 Conventional Gas Extinguishing Control Pane

Cylinder

44

Conventional Fire Telephone System

FT Socket Speaker Handset Fixed Handst

Fixed Handst

Speaker Handset

FT Socket

FT Socket

Mobile Handset

24 Zone Conventional Fire Telephone Control Panel

45

Projects

GST China
GST Holdings Limited
Add.:Suite 6308, Central Plaza, 18 Harbour Road, Hongkong Tel: +852 2877 8566 Fax: +852 2511 8699 Add.:18F, Block B, the Gate Tower, No.19, Zhongguancun Ave., Haidian, Beijing, P.R.China Tel: +86 (0)10 8248 7797 Fax: +86 (0)10 8248 7779 www.gst.com.cn sales@gst.com.cn

Gulf Security Technology Co., Ltd.


Add.:NO.80 Changjiang East Road, QETDZ, Qinhuangdao, Hebei, China Tel: +86 (0)335 850 2383 Fax: +86 (0)335 850 8942

GST UK
Global System Technology PLC
Add.:Lion Court, Staunton Harold Hall, Melbourne Road, Ashby de la Zouch, Leicestershire, England LE65 1RT Tel: +44 (0)1283 225 478 Fax: +44 (0)1283 220 690 www.gst.uk.com info@gst.uk.com

GST Dubai
Add.:ZA04, Jebel Ali Free Zone, P.O. Box 17998, Dubai, UAE Tel: +971 (0)4 8833 050 Fax: +971 (0)4 8833 053

GST Holdings Limited

You might also like