Transformer Testing - Type Test and Routine Test of Transformer
Transformer Testing - Type Test and Routine Test of Transformer
Transformer Testing - Type Test and Routine Test of Transformer
For confirming the specifications and performances of an electrical transformer it has to go through numbers of testing procedures. Some tests are done at manufacturer premises before delivering the transformer. Mainly two types of transformer testing are done at manufacturer premises type test of transformer and routine test of transformer. In addition to that some transformer tests are also carried out at the consumer site before commissioning and also periodically in regular & emergency basis through out its service life.
of transformer. These tests are done to assess the condition of transformer after installation and compare the test results of all the low voltage tests with the factory test reports. Type tests of transformer includes Transformer winding resistance measurement Transformer ratio test Transformer vector group test Measurement of impedance voltage/short circuit impedance (principal tap) and load loss (Short circuit test) Measurement of no load loss and current (Open circuit test) Measurement of insulation resistance Dielectric tests of transformer Temperature rise test of Transformer Tests on on-load tap-changer Vacuum tests on tank and radiators Routine tests of transformer include Transformer winding resistance measurement Transformer ratio test Transformer vector group test Measurement of impedance voltage/short circuit impedance (principal tap) and load loss (Short circuit test) Measurement of no load loss and current (Open circuit test) Measurement of insulation resistance Dielectric tests of transformer Tests on on-load tap-changer Oil pressure test on transformer to check against leakages past joints and gaskets. That means Routine tests of transformer include all the type tests except temperature rise and vacuum tests. The oil pressure test on transformer to check against leakages past joints and gaskets is included. Special Tests of transformer include Dielectric Tests Measurement of zero-sequence impedance of three-phase transformers Short-Circuit Test Measurement of acoustic noise level Measurement of the harmonics of the no-load current Measurement of the power taken by the fans and oil pumps Tests on bought out components / accessories such as buchhloz relay, temperature indicators, pressure relief devices, oil preservation system etc.
There are different methods for measuring of transformer winding, likewise Current voltage method of measurement of winding resistance. Bridge method of measurement of winding resistance. Kelvin bridge method of Measuring Winding Resistance. Measuring winding resistance by Automatic Winding Resistance Measurement Kit. NB: Transformer winding resistance measurement shall be carried out at each tap.
side phase Voltage applied at central phase Voltage applied at right side phase
115 V 50 V
230 V 180 V
115 V 230 V
performed to ensure the required quality of transformer insulation, dielectric test is one of them. Dielectric tests of transformer is performed in two different steps, first one called Separate source voltage withstand test of transformer, where a single phase power frequency voltage of prescribed level, is applied on transformer winding under test for 60 seconds while the other windings and tank are connected to the earth and it is observed that whether any failure of insulation occurs or not during the test. Second one is induced voltage test of Transformer where, three phase voltage, twice of rated secondary voltage is applied to the secondary winding for 60 second by keeping the primary of the transformer open circuited. The frequency of the applied voltage should be double of power frequency too. Here also if no failure of insulation, the test is successful. In addition to Dielectric tests of transformer there are other type test for checking insulation of transformer, such as lightning impulse test, switching impulse test and partial discharge test.
Transformer winding resistance measurement is carried out as a type test, routine test and also as a field test. In the factory, it helps in determining the following : (a) Calculation of the I2R losses in transformer (b) Calculation of winding temperature at the end of temperature rise test of transformer. (c) As a benchmark for assessing possible damages in the field. It is done at site in order to check for abnormalities due to loose connections, broken strands of conductor, high contact resistance in tap changers, high voltage leads and bushings.
Rt = Winding resistance at temperature t. t = Winding temperature Generally transformer windings are immersed in insulation liquid and covered with paper insulation, hence it is impossible to measure the actual winding temperature in a deenergizing transformer at time of transformer winding resistance measurement. An approximation is developed to calculate temperature of winding at that condition, as follows Temperature of winding = Average temperature of insulating oil. (Average temperature of insulating oil should be taken 3 to 8 hours after de-energizing transformer and when the difference between top & bottom oil temperatures becomes less than 5oC) The resistance can be measured by simple voltmeter ammeter method, Kelvin Bridge meter or automatic winding resistance measurement kit (ohm meter, preferably 25
Amps kit) Caution for voltmeter ammeter method: Current shall not exceed 15% of the rated current of the winding. Large values may cause inaccuracy by heating the winding and thereby changing its temperature and resistance. NB: Measurement of winding resistance of transformer shall be carried out at each tap.
8) For star connected three phase winding, the resistance per phase would be half of measured resistance between two line terminals of the transformer. 9) For delta connected three phase winding, the resistance per phase would be 0.67 times of measured resistance between two line terminals of the transformer. 10) This current voltage method of measurement of winding resistance of transformer should be repeated for each pair of line terminals of winding at every tap position.
The main principle of bridge method is based on comparing an unknown resistance with a known resistance. When electric currents flowing through the arms of bridge circuit become balanced, the reading of galvanometer shows zero deflection that means at balanced condition no electric current will flow through the galvanometer. Very small value of resistance ( in milli ohms range) can be accurately measured by Kelvin Bridge method whereas for higher value Wheatstone bridge method of resistance measurement is applied. In bridge method of measurement of winding resistance, the errors is minimized.
All other steps to be taken during transformer winding resistance measurement in these methods are similar to that of current voltage method of measurement of winding resistance of transformer, except the measuring technique of resistance.
------------------------------ x
------------------------------------
x----------------------------
each phase (Phase-Phase) on HV and induced voltages at LV terminals simultaneously. 3) After measuring the voltages at HV and LV terminals, the tap changer of transformer should be raised by one position and repeat test. 4) Repeat the same for each of the tap position separately. The above transformer ratio test can also be performed by portable Transformer Turns Ratio (TTR) Meter. They have an in built power supply, with the voltages commonly used being very low, such as 8-10 V and 50 Hz. The HV and LV windings of one phase of a transformer are connected to the instrument, and the internal bridge elements are varied to produce a null indication on the detector. Lets have a discussion on Transformer Turns Ratio (TTR) Meter method of turn ratio test of transformer A phase voltage is applied to the one of the windings by means of a bridge circuit and the ratio of induced voltage is measured at the bridge. The accuracy of the measuring instrument is < 0.1 %
This theoretical turn ratio is adjusted on the transformer turn ratio tested or TTR by the adjustable transformer as shown in the figure above and it should be changed until a balance occurs in the percentage error indicator. The reading on this indicator implies the deviaton of measured turn ratio from expected turn ratio in percentage.
Out-of-tolerance, ratio test of transformer can be due to shorted turns, especially if there is an associated high excitation current. Open turns in HV winding will indicate very low exciting current and no output voltage since open turns in HV winding causes no excitation current in the winding means no flux hence no induced voltage. But open turn in LV winding causes, low fluctuating LV voltage but normal excitation current in HV winding. Hence open turns in LV winding will be indicated by normal levels of exciting current, but very low levels of unstable output voltage. The turn ratio test of transformer also detects high resistance connections in the lead circuitry or high contact resistance in tap changers by higher excitation current and a difficulty in balancing the bridge. ------------------------------ x -----------------------------------x----------------------------
Procedure
1) All three line terminals of the winding to be tested are connected together. 2) Other winding terminals which are not under test and also tank of the transformer should be connected to earth. 3) Then a single-phase power frequency voltage of shape approximately sinusoidal is applied for 60 seconds to the terminals of the winding under test. 4) The test shall be performed on all the windings one by one. 6) The test is successful if no break down in the dielectric of the insulation occurs during test.
In this transformer testing, the peak value of voltage is measured, that is why the capacitor voltage divider with digital peak voltmeter is employed as shown in the diagram above. The peal value multiplied by 0.707 (1/2) is the test voltage. The values of test voltage for different fully insulated winding are furnished below in the table. Highest Rated short duration Nominal system system power frequency voltage rating voltage rating withstand for equipment for equipment voltage 415V 1.1 KV 3 KV 11 KV 12 KV 28 KV 33 KV 36 KV 70 KV 132 KV 145 KV 230 / 275 KV 220 KV 245 KV 360 / 395 KV 400 KV 420 KV 570 / 630 KV Winding with graded insulation, which has neutral intended for direct earthing, is tested at 38KV
The induced voltage test of transformer is intended to check the inter turn and line end insulation as well as main insulation to earth and between windings 1) Keep the primary winding of transformer open circuited. 2) Apply three phase voltage to the secondary winding. The applied voltage should be twice of rated voltage of secondary winding in magnitude and frequency. 3) The duration of the test shall be 60 second. 4) The test shall start with a voltage lower than 1/3 the full test voltage, and it shall be quickly increased up to desired value. The test is successful if no break down occurs at full test voltage during test.
----------------------------------------------------------------------------------------------------------
x---------------------------x---------------------------x----------------------------