Detailed Specifications & Technical Data

METRIC MEASUREMENT VERSION

9575 Multi-Conductor - Power-Limited Fire Protective Signal Circ Cabl, 2 Cdrs Cabld For more Information please call 1-800-Belden1

General Description: 16 AWG solid bare copper conductors, conductors cabled, PVC insulation, overall Beldfoil shield (100% coverage), 22 AWG stranded TCV drain wire, PVC jacket. Physical Characteristics (Overall)
Conductor
AWG:
# Conductors AWG Stranding Conductor Material 2 16 Solid BC - Bare Copper

Total Number of Conductors:

Insulation
Insulation Material:
Insulation Material Wall Thickness (mm) PVC - Polyvinyl Chloride 0.406

Outer Shield
Outer Shield Material:
Outer Shield Trade Name Type Outer Shield Material Beldfoil (Z-Fold) Coverage (%) Tape Aluminum Foil-Polyester Tape 100

Outer Shield Drain Wire AWG:


AWG Stranding Drain Wire Conductor Material 22 7x30 TC - Tinned Copper

Outer Jacket
Outer Jacket Material:
Outer Jacket Material Nom. Wall Thickness (mm) PVC - Polyvinyl Chloride 0.914

Overall Cable
Overall Cabling Color Code Chart:
Number Color 1 2 Black Red

Overall Nominal Diameter:

6.121 mm

Mechanical Characteristics (Overall)


Operating Temperature Range: UL Temperature Rating: Bulk Cable Weight: Min. Bend Radius/Minor Axis: -40C To +105C 105C 50.599 Kg/Km 63.500 mm

Applicable Specifications and Agency Compliance (Overall)


Applicable Standards & Environmental Programs
NEC/(UL) Specification: NEC Articles: CEC/C(UL) Specification: CMR, FPLR 760 FAS105 Page 1 of 3 08-21-2013

Detailed Specifications & Technical Data


METRIC MEASUREMENT VERSION

9575 Multi-Conductor - Power-Limited Fire Protective Signal Circ Cabl, 2 Cdrs Cabld
CEC/C(UL) Specification: AWM Specification: EU Directive 2011/65/EU (ROHS II): EU CE Mark: EU Directive 2000/53/EC (ELV): EU Directive 2002/95/EC (RoHS): EU RoHS Compliance Date (mm/dd/yyyy): EU Directive 2002/96/EC (WEEE): EU Directive 2003/11/EC (BFR): CA Prop 65 (CJ for Wire & Cable): MII Order #39 (China RoHS): Other Specification: FAS105 UL Style 2464 (300 V 80C) Yes Yes Yes Yes 04/01/2005 Yes Yes Yes Yes California State Fire Marshall

Flame Test
UL Flame Test: CSA Flame Test: UL1666 Vertical Shaft FT4

Electrical Characteristics (Overall)


Nom. Inductance:
Inductance (H/m) 0.492

Nom. Capacitance Conductor to Conductor:


Capacitance (pF/m) 188.658

Nom. Capacitance Cond. to Other Conductor & Shield:


Capacitance (pF/m) 339.584

Nom. Conductor DC Resistance:


DCR @ 20C (Ohm/km) 13.4521

Nominal Outer Shield DC Resistance:


DCR @ 20C (Ohm/km) 34.7786

Max. Operating Voltage - UL:


Voltage 300 V RMS

Max. Recommended Current:


Current 11 Amps per conductor @ 25C

Put Ups and Colors:


Item # 9575 002U1000 9575 002U500 9575 0025000 Putup 305 MT 152 MT 1,524 MT Ship Weight 16.329 KG 8.391 KG 86.183 KG Color RED RED RED CZ Notes Item Desc 2 #16 PVC FS PVC 2 #16 PVC FS PVC 2 #16 PVC FS PVC

Notes: C = CRATE REEL PUT-UP. Z = FINAL PUT-UP LENGTH MAY VARY (+ OR -) 10% FOR SPOOLS OR REELS AND(+ OR -) 5% FOR UNREEL CARTONS FROM LENGTH SHOWN.

Page 2 of 3

08-21-2013

Detailed Specifications & Technical Data


METRIC MEASUREMENT VERSION

9575 Multi-Conductor - Power-Limited Fire Protective Signal Circ Cabl, 2 Cdrs Cabld

Revision Number: 5 2013 Belden, Inc All Rights Reserved.

Revision Date: 10-03-2012

Although Belden makes every reasonable effort to ensure their accuracy at the time of this publication, information and specifications described herein are subject to error or omission and to change without notice, and the listing of such information and specifications does not ensure product availability. Belden provides the information and specifications herein on an "AS IS" basis, with no representations or warranties, whether express, statutory or implied. In no event will Belden be liable for any damages (including consequential, indirect, incidental, special, punitive, or exemplary damages) whatsoever, even if Belden has been advised of the possibility of such damages, whether in an action under contract, negligence or any other theory, arising out of or in connection with the use, or inability to use, the information or specifications described herein. All sales of Belden products are subject to Belden's standard terms and conditions of sale. Belden believes this product to be in compliance with EU RoHS (Directive 2002/95/EC, 27-Jan-2003). Material manufactured prior to the compliance date may be in stock at Belden facilities and in our Distributors inventory. The information provided in this Product Disclosure, and the identification of materials listed as reportable or restricted within the Product Disclosure, is correct to the best of Beldens knowledge, information, and belief at the date of its publication. The information provided in this Product Disclosure is designed only as a general guide for the safe handling, storage, and any other operation of the product itself or the one that it becomes a part of. This Product Disclosure is not to be considered a warranty or quality specification. Regulatory information is for guidance purposes only. Product users are responsible for determining the applicability of legislation and regulations based on their individual usage of the product. Belden declares this product to be in compliance with EU LVD (Low Voltage Directive 73/23/EEC), as amended by directive 93/68/EEC.

Page 3 of 3

08-21-2013