For More Information Please Call 1-800-Belden1: 1493A Multi-Conductor - 300V Power-Limited Tray Cable
For More Information Please Call 1-800-Belden1: 1493A Multi-Conductor - 300V Power-Limited Tray Cable
For More Information Please Call 1-800-Belden1: 1493A Multi-Conductor - 300V Power-Limited Tray Cable
1-800-Belden1
General Description:
16 AWG pairs stranded (7x24) bare copper conductors, twisted pairs, individually shielded plus an overall
Beldfoil shield (100% coverage), PVC insulation, PVC jacket.
Physical Characteristics (Overall)
Conductor
AWG:
# Conductors # Pairs AWG Stranding Conductor Material
4 16 7x24 BC - Bare Copper
1 22 7x30 BC - Bare Copper
Insulation
Insulation Material:
Insulation Material
PVC - Polyvinyl Chloride
Inner Shield
Inner Shield Material:
Inner Shield Trade Name Type Inner Shield Material Coverage (%)
Beldfoil® Tape Aluminum Foil-Polyester Tape 100
Outer Shield
Outer Shield Material:
Outer Shield Trade Name Type Outer Shield Material Coverage (%)
Beldfoil® Tape Aluminum Foil-Polyester Tape 100
Outer Jacket
Outer Jacket Material:
Outer Jacket Material Nom. Wall Thickness (mm)
PVC - Polyvinyl Chloride 1.397
Overall Cable
Overall Nominal Diameter: 13.360 mm
Pair
Pair Color Code Chart:
Number Color
1 Black & White and Numbered 1
2 Black & White and Numbered 2
3 Black & White and Numbered 3
4 Black & White and Numbered 4
Communication Wire Orange
Page 1 of 3 08-26-2016
Detailed Specifications & Technical Data
METRIC MEASUREMENT VERSION
EU CE Mark: Yes
Flame Test
UL Flame Test: UL1685 FT4 Loading
Suitability
Suitability - Burial: Yes
Plenum/Non-Plenum
Plenum (Y/N): No
Notes:
C = CRATE REEL PUT-UP.
Z = FINAL PUT-UP LENGTH MAY VARY (+ OR -) 10% FOR SPOOLS OR REELS AND(+ OR -) 5% FOR UNREEL CARTONS FROM LENGTH SHOWN.
Page 2 of 3 08-26-2016
Detailed Specifications & Technical Data
METRIC MEASUREMENT VERSION
Belden believes this product to be in compliance with EU RoHS (Directive 2002/95/EC, 27-Jan-2003). Material manufactured prior to the compliance date may be in stock at Belden facilities
and in our Distributor’s inventory. The information provided in this Product Disclosure, and the identification of materials listed as reportable or restricted within the Product Disclosure, is
correct to the best of Belden’s knowledge, information, and belief at the date of its publication. The information provided in this Product Disclosure is designed only as a general guide for the
safe handling, storage, and any other operation of the product itself or the one that it becomes a part of. This Product Disclosure is not to be considered a warranty or quality specification.
Regulatory information is for guidance purposes only. Product users are responsible for determining the applicability of legislation and regulations based on their individual usage of the
product.
Belden declares this product to be in compliance with EU LVD (Low Voltage Directive 2014/35/EU).
Page 3 of 3 08-26-2016